Series M Three and four pole contactors 9 and 12A (AC3) 20A (AC1) Contactors • Control circuit: Alternating current up to 600V Direct current up to 440V • Terminal numbering in accordance with EN 50012 • Fixing by clipping onto 35 mm DIN rail (EN 50022-35) or by screws • Screws and fast-on terminals protected against accidental contact in accordance with VDE 0106 T.100 and VBG4 • Versions: Ring terminal and printed circuit terminals • Facility to mount instant and timed auxiliary contact blocks and voltage suppressor block • Degree of protection IP20 (EN 60529). • Maximum number of auxiliary contacts to be added: 6 Standards Intro A B C IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 EN 50003 EN 50005 EN 50012 UL 508 NEMA ICS-1 General data BS 4794 NFC 63-110 CSA C22.2/14 VDE 0660 SEV 10254 JIS C8325 JEM 1038 CENELEC HD 419 750 690 (V) (V) 750 690 Standard voltages Approvals To complete the catalogue number, replace the symbol © by the code corresponding to the voltage and frequency of the control circuit (other voltages on request) D Alternating current (V). Bifrequency coil cULus RINA IMQ © E F MC1... MC2... 4 4 20 (A) 20 9 12 (A) Maximum number of poles Rated thermal current (Ith) e H 60º (1) Rated operational current Ie (2) (3x440V, 50/60Hz, AC3) Rated insulation current Ui Rated operational current Ue 10 1 2 9 3 4 5 6 7 8 12 13 AC 12 24 42 48 110 120 220 230 240 440 380 400 50/60Hz 115 Lloyd’s Register Bureau Veritas CE Operating voltages limits with bifrequency coils: With 60Hz =0.85 to 1.1 x Us With 50Hz =0.8 to 1.1 x Us in continuous service (ED=100%) with a maximum ambient temperature of 40ºC Alternating current (V). G © AC 50Hz AC 60Hz (Contact GE for details) H A E 6 32 G K M 48 115 127 60 208 220 N S U W Y 220 260 380 415 500 240 400 440 240 440 480 600 277 C F Direct current (V) I J/X A.44 Order codes Auxiliary contact blocks Accessories Technical data Terminal numbering Dimensions ! ! ! ! ! ! pg. A.45 pg. A.48 pg. A.50 pg. A.83 pg. A.89 pg. A.110 © A B DC 6 12 32 24 36 42 48 60 72 110 120 125 220 230 240 250 440 D E G H Direct current (V) - Wide voltage range © DC WD WE WG WI WJ WN 24 33 48 72 110 220 I J K L N 17 R S 16 Series M Three pole contactors Max.operat.current Admissible power AC3 Non1-phase 3-phase Motors inductive <440V, 115V 220V 220V 380V 500V loads 3~ 230V 400V 50/60Hz AC1 (2) AC3 (3) kW kW kW kW kW HP HP HP HP HP A A Terminal: screw 20 9 20 12 0.56 1.12 2.2 0.75 1.5 3 0.75 2 1 2.6 3 4 20 12 0.75 2 1 2.6 3 4 Terminal: faston 2x2.8 insulated (5) 16 (4) 9 0.56 1.12 2.2 0.75 1.5 3 •3 •1 •4 •2 Control circuit: Alternating current Control circuit: Direct current Cat. no. (1) Cat. no. (1) Pack Ref. no. see bottom Pack Ref. no. see bottom 4 5.5 4 5.5 1 0 0 1 MC1A310AT © MC1A301AT © 20 20 MC1C310AT © MC1C301AT © 10 10 5.5 7.3 5.5 7.3 1 0 0 1 MC2A310AT © MC2A301AT © 20 20 MC2C310AT © MC2C301AT © 10 10 4 5.5 4 5.5 1 0 0 1 MC1A310AR © MC1A301AR © 20 20 MC1C310AR © MC1C301AR © 10 10 5.5 7.3 5.5 7.3 1 0 0 1 MC2A310AR © MC2A301AR © 20 20 MC2C310AR © MC2C301AR © 10 10 Order codes Terminal: ring terminal 20 9 0.56 1.12 2.2 0.75 1.5 3 Aux. contacts Intro 4 5.5 4 5.5 1 0 0 1 MC1A310AF © MC1A301AF © 20 20 MC1C310AF © MC1C301AF © 10 10 A Terminal: printed circuit 20 9 0.56 1.12 2.2 0.75 1.5 3 4 5.5 4 5.5 1 0 0 1 MC1A310AI © MC1A301AI © 20 20 MC1C310AI © MC1C301AI © 10 10 20 12 0.75 2 1 2.6 5.5 7.3 5.5 7.3 1 0 0 1 MC2A310AI © MC2A301AI © 20 20 MC2C310AI © MC2C301AI © 10 10 3 4 B C D Spare coil MB0A © 10 MB0C © 10 E F (1) To complete the catalogue number, replace the symbol © by the code corresponding to the voltage and frequency of the control circuit (other voltages on request) (see A.44) (2) Electrical endurance AC-1: MC1... 0.3 x 106 operations MC2... 0.35 x 106 operations (3) Electrical endurance AC-3: MC1... (9A) = 0.85 x 106 operations MC2... (12A)= 0.6 x 106 operations (4) Terminal with wire 1.5 mm2: Ie = 16A with wire 1 mm2: Ie = 10A Insulated terminal type B 2.8 x 0.8 and wire 1 mm2 Ie = 8A in accordance with DIN 46247. (5) Fast-on 1 x 6.3 terminals on request (replace letter F by H in the catalogue number) G H I J/X For reference numbers, see chapter X, pg. X.2 A.45 Series M Three pole interface contactors Admissible power AC3 Max. oper. current Non- Motors 1-phase 3-phase inductive <440V, 115V 220V 220V 380V 500V load 3~ 230V 400V 50/60Hz (3) AC3 AC1 kW kW kW kW kW A A Terminal: screw 20 9 Contactors 20 Intro A 12 0.56 1.12 2.2 0.75 2 3 Aux. contacts •3 •1 •4 •2 Voltage 24V D.C, coil 1.2W (1) Cat. no. (1) Ref. no. Pack Voltage 24V D.C, coil 2W (2) Cat. no. (1) Ref. no. Pack 4 4 1 0 0 1 MC1I310ATD MC1I301ATD 100572 100573 10 10 MC1K310ATD MC1K301ATD 100576 100577 10 10 5.5 5.5 1 0 0 1 MC2I310ATD MC2I301ATD 100559 100538 10 10 MC2K310ATD MC2K301ATD 103590 103591 10 10 MB0ID 100470 10 MB0KD 100471 10 Spare coil (1) No possibility of adding instantaneous auxiliary contact blocks. (2) Facility to mount an instantaneous auxiliary contact block of two contacts or two instantaneous auxiliary contact blocks of one contact. (3) Electrical endurance AC-3: MC0... (6A) = 1.2 x 106 operations. MC1... (9A) = 0.85 x 106 operations. MC2... (12A) = 0.6 x 106 operations. B C Multipack. Series M To reduce the amount of waste packaging material and to save time during installation, we offer the opportunity to order contactors in a multipack without the individual packaging. D Product Type Standard pack Contactors MC1...MC2a 20 (1) The quantity ordered must be a multiple of the quantity in each multipack ( with the same frame/size and coil voltage) E How to order Multipack (1) 40 To order a multipack, add the suffix MP to the standard catalogue number F G H I J/X A.46 Example Standard pack MC0A310ATN Multipack MC0A310ATN MP (40 pieces) Series M Four poles contactors Poles Admissible power AC3 Max.oper.current 1-phase 3-phase NonMotors inductive <440V, 115V 220V 220V 380V 500V load 3~ 230V 400V 50/60Hz (3) (2) AC1 AC3 kW kW kW kW kW HP HP HP HP HP A A Screw terminal 20 9 20 12 4.4 - 7.5 - 13 - 17 - 1.12 2.2 1.5 3 4 5.5 4 5.5 4.4 - 7.5 - 13 - 17 - 2 2.6 3 4 5.5 7.3 5.5 7.3 13 - 17 - 4 5.5 4 5.5 Terminal: faston 2x2.8 insulated (5) 16 (4) 9 AC1 2.3 4.4 7.5 AC3 0.56 1.12 2.2 0.75 1.5 3 Cat. no. (1) Pack Ref. no. see bottom Control circuit: Direct current Cat. no. (1) Pack Ref. no. see bottom 4 2 0 0 2 4 MC1A400AT © MC1AB00AT © MC1AA00AT © 20 20 20 MC1C400AT © MC1CB00AT © 10 10 4 2 0 2 MC2A400AT © MC2AB00AT © 20 20 MC2C400AT © MC2CB00AT © 10 10 4 2 0 0 2 4 MC1A400AF © MC1AB00AF © MC1AA00AF © 20 20 20 MC1C400AF © MC1CB00AF © 10 10 Order codes AC1 2.3 AC3 0.56 0.75 AC1 2.3 AC3 0.75 1 Control circuit: Alternating current Intro A B C Terminal: printed circuit 20 9 AC1 2.3 4.4 7.5 AC3 0.56 1.12 2.2 0.75 1.5 3 13 - 17 - 4 5.5 4 5.5 4 2 0 0 2 4 MC1A400AI © MC1AB00AI © MC1AA00AI © 20 20 20 MC1C400AI © MC1CB00AI © 10 10 D E F Spare coil MB0A © 10 MB0C © 10 G H (1) To complete the catalogue number, replace the symbol © by the code corresponding to the voltage and frequency of the control circuit (see A.44) (2) Electrical endurance AC-1: MC1... 0.3 x 106 operations MC2... 0.35 x 106 operations (3) Electrical endurance AC-3: MC1... (9A) = 0.85 x 106 operations MC2... (12A)= 0.6 x 106 operations (4) Terminal with wire 1.5 mm2: Ie = 16A with wire 1 mm2: Ie = 10A Insulated terminal type B 2.8 x 0.8 and wire of 1 mm2 Ie = 8A in accordance with DIN 46247. (5) Faston 1 x 6.3 terminals on request, (replace letter F by H in the catalogue number). I J/X For reference numbers, see chapter X, pg. X.2 A.47 Series M Instantaneous auxiliary contact blocks Number contacts Combinations with basic contactor Contacts in acc. with EN 50012 Contacts in acc.with EN 50005 10E Front mounting Aux.contacts •3 •1 •4 •2 Cat. no. Ref. no. Pack • Two or four additional contacts, to cover combinations of 3 or 5 contacts without increasing the surface are of the basic contactor Contactors Screw terminal Intro A B C D E F G H I J/X A.48 2 2 2 2 2 21E 12E 4 4 4 4 4 4 4 4 41E 32E 23E Ring terminal 2 2 2 2 2 4 4 4 4 4 4 4 4 21E 12E 41E 32E 23E 11 02 20 11 02 1 0 2 1 0 1 2 0 1 2 MACN211AT MACN202AT MARN220AT MARN211AT MARN202AT 100999 100998 100994 100993 100992 10 10 10 10 10 40 31 22 13 04 3 2 1 4 3 2 1 0 1 2 3 0 1 2 3 4 MACN431AT MACN422AT MACN413AT MARN440AT MARN431AT MARN422AT MARN413AT MARN404AT 100997 100996 100995 100991 100990 100989 100988 100987 10 10 10 10 10 10 10 10 20 11 02 1 0 2 1 0 1 2 0 1 2 MACN211AR MACN202AR MARN220AR MARN211AR MARN202AR 103557 103558 103349 103350 103351 10 10 10 10 10 40 31 22 13 04 3 2 1 4 3 2 1 0 1 2 3 0 1 2 3 4 MACN431AR MACN422AR MACN413AR MARN440AR MARN431AR MARN422AR MARN413AR MARN404AR 103559 103560 103561 103352 103353 103354 103355 103300 10 10 10 10 10 10 10 10 31 22 13 11 02 31 22 13 Series M Instantaneous auxiliary contact blocks (continued) Number contacts Lateral mounting Combinations with basic contactor Contacts in acc. with EN 50012 Contacts in acc.with EN 50005 Aux.contacts •3 Cat. no. Ref. no. Pack •1 10E •4 •2 • One or two additional blocks, to cover combinations of 1 or 2 contacts without increasing the height of the basic unit contactor Screw terminal 1 1 Ring terminal 1 1 10 01 1 0 0 1 MACL110AT MACL101AT 100560 100561 10 10 20 11E 10 01 1 0 0 1 MACL110AR MACL101AR 103555 103556 10 10 10 01 1 0 0 1 MACL110AF MACL101AF 100562 100563 10 10 10 01 1 0 0 1 MACL110AI MACL101AI 100564 100565 10 10 Terminal: faston 2x2.8 insulated (1) 1 20 1 11E Terminal: printed circuit 1 1 20 11E Order codes 20 11E Intro • One or two additional blocks, when up to 6 or 7 contacts are needed (combination possible with frontal blocks) • One or two additional blocks on both sides, to cover up to five contacts (combination possible only with lateral blocks) A Screw terminal 1 1 10 01 1 0 0 1 MARL110ATS MARL101ATS 100519 100520 10 10 Ring terminal 1 1 10 01 1 0 0 1 MARL110ARS MARL101ARS 103299 103298 10 10 B C Terminal: faston 2x2.8 insulated (1) 1 1 10 01 1 0 0 1 MARL110AFS MARL101AFS 100521 100522 10 10 Terminal: printed circuit 1 1 10 01 1 0 0 1 MARL110AIS MARL101AIS 100523 100524 10 10 (1) Terminal with wire 1 mm2: Ie = 10A Insulated terminal type B 2.8 x 0.8 with wire 1 mm2: Ie = 8A, in accordance with DIN 46247 D E F G H I J/X A.49 Series M Accessories Contactors For use with: Time Electronic timer block Lateral or front fixing to the contactor DIN rail adaptor for electronic timer block For fixing onto EN 50022-35 MREBC... MCR..MC_ ... MCR..MC_ ... For use with: Voltage suppressor block 0.5 - 60 seg. 0.2 - 24 seg. Type Connection and (plug-in) fixing on to the connector MCRA,MC_ ... R/C MCRA,MC_ ... R/C MCRC,MC_ ... Diode MCRC,MC_ ... Varistor Function Ue Cat. no. Ref. no. Pack delay ON delay ON 24... 250V AC/DC 24...250V AC/DC MREBC10AC2 MREBC20AC2 100541 100542 10 10 MVB0R 100543 10 Control Ue Cat. no. Ref. no. Pack AC AC DC AC/DC 12...60V 50/60Hz 72...250V 50/60Hz 6...250V DC 24-48V MP0AAE1 MP0AAE2 MP0CAE3 MP0DAE4 100544 100545 100546 100536 10 10 10 10 Terminal capacity Ue Cat. no. Ref. no. Pack MVP0C 100600 10 Cat. no. Ref. no. Pack Intro A B For use with: Pole paralleling links Phases To connect two, three or four phases in parallel MC_ ... 2, 3, 4 (parallel) Ø4.5mm - 16mm2 C D E For use with: Mechanical interlock Mechanical interlock and pole jumpers MCR, MC_ ... MMH0 100547 10 Cat. no. Ref. no. Pack EAT 260 SPR 100548 100549 1 1 F For use with: G Identification H I J/X A.50 MCR, MC_ ... MCR, MC_ ... Labels (10 sheets of 260 labels) Labelling plate base. Plug-in labelling plate bases (50 pieces in one pack) Series M Direct-on-line starters 6 to 12A (AC-3) Series M - Direct-on-line starters Empty boxes Push-buttons Protection degree Cat. no. Start/Stop + Reset IP40 IP65 IP40 IP65 IP40 IP65 MG0004PAT0 MG0006PAT0 MG0004RAT0 MG0006RAT0 MG0004QAT0 MG0006QAT0 209780 209781 137567 116402 137566 116074 1 1 1 1 1 1 MAGL110AT 100608 1 Reset only Start/Emergency stop Start contact block Laterally mounted to the contactor, allowing the electrical operation the box push-button which incises on it. Ref. no Pack Intro A Reversing starters B 6 to 12A (AC-3) C • Power circuit: up to 690V AC • Control circuit: up to 600V AC up to 250V DC • Assembled versions on request. • Screw and push-on terminals protected against accidental contact. • Protection degree IP20 in accordance with EN 60529. • Facility to mount instant and timed auxiliary contact blocks and voltage suppressor blocks. D E F Series M - Reversing starters Description Wiring kits for reversing starters Order codes • Power circuit: up to 690V AC • Control circuit: up to 600V AC • Polycarbonate enclosure (IP40 - IP65) - Shock resistance - Total insulation § - 4 knock-out input holes PG13.5 - Cable entry in the base • Terminals protected against accidental contact • 16 setting ranges from 0.11 up to 14A • Start contact block Suitable to be usd with link modules Upper and lower connections without overload relays For use with contactor MC1.., MC2.. ac/dc Cat. no. Ref. no. Pack. ac/dc WKMIU 101421 1 G H I J/X Wiring diagrams ! page A.134 Dimensions ! page A.137 A.51