Kontaktorji serija M

advertisement
Series M
Three and four pole contactors
9 and 12A (AC3)
20A (AC1)
Contactors
• Control circuit: Alternating current up to 600V
Direct current up to 440V
• Terminal numbering in accordance with EN 50012
• Fixing by clipping onto 35 mm DIN rail (EN 50022-35) or by screws
• Screws and fast-on terminals protected against accidental contact in
accordance with VDE 0106 T.100 and VBG4
• Versions: Ring terminal and printed circuit terminals
• Facility to mount instant and timed auxiliary contact blocks and
voltage suppressor block
• Degree of protection IP20 (EN 60529).
• Maximum number of auxiliary contacts to be added: 6
Standards
Intro
A
B
C
IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
EN 50003
EN 50005
EN 50012
UL 508
NEMA ICS-1
General data
BS 4794
NFC 63-110
CSA C22.2/14
VDE 0660
SEV 10254
JIS C8325
JEM 1038
CENELEC HD 419
750
690
(V)
(V)
750
690
Standard voltages
Approvals
To complete the catalogue number, replace the symbol © by the code
corresponding to the voltage and frequency of the control circuit
(other voltages on request)
D
Alternating current (V). Bifrequency coil
cULus
RINA
IMQ
©
E
F
MC1... MC2...
4
4
20
(A) 20
9
12
(A)
Maximum number of poles
Rated thermal current (Ith) e H 60º (1)
Rated operational current Ie (2)
(3x440V, 50/60Hz, AC3)
Rated insulation current Ui
Rated operational current Ue
10
1
2
9
3
4
5
6
7
8
12 13
AC
12 24 42 48 110 120 220 230 240 440 380 400
50/60Hz
115
Lloyd’s
Register
Bureau
Veritas
CE
Operating voltages limits with bifrequency coils:
With 60Hz =0.85 to 1.1 x Us
With 50Hz =0.8 to 1.1 x Us in continuous service (ED=100%) with a maximum ambient temperature of 40ºC
Alternating current (V).
G
©
AC
50Hz
AC
60Hz
(Contact GE for details)
H
A
E
6
32
G K M
48 115
127
60
208
220
N
S
U W Y
220 260 380 415 500
240
400 440
240
440 480 600
277
C
F
Direct current (V)
I
J/X
A.44
Order codes
Auxiliary contact blocks
Accessories
Technical data
Terminal numbering
Dimensions
!
!
!
!
!
!
pg. A.45
pg. A.48
pg. A.50
pg. A.83
pg. A.89
pg. A.110
©
A
B
DC
6
12 32 24 36 42 48 60 72 110 120 125 220 230 240 250 440
D
E
G
H
Direct current (V) - Wide voltage range
©
DC
WD WE WG WI WJ WN
24
33 48
72 110 220
I
J
K
L
N
17
R
S
16
Series M
Three pole contactors
Max.operat.current
Admissible power AC3
Non1-phase
3-phase
Motors
inductive <440V, 115V 220V 220V 380V 500V
loads
3~
230V 400V
50/60Hz
AC1 (2)
AC3 (3)
kW kW kW kW kW
HP HP HP HP HP
A
A
Terminal: screw
20
9
20
12
0.56 1.12 2.2
0.75 1.5
3
0.75 2
1
2.6
3
4
20
12
0.75 2
1
2.6
3
4
Terminal: faston 2x2.8 insulated (5)
16 (4)
9
0.56 1.12 2.2
0.75 1.5
3
•3
•1
•4
•2
Control circuit:
Alternating
current
Control circuit:
Direct current
Cat. no. (1)
Cat. no. (1)
Pack
Ref. no. see bottom
Pack
Ref. no. see bottom
4
5.5
4
5.5
1
0
0
1
MC1A310AT ©
MC1A301AT ©
20
20
MC1C310AT ©
MC1C301AT ©
10
10
5.5
7.3
5.5
7.3
1
0
0
1
MC2A310AT ©
MC2A301AT ©
20
20
MC2C310AT ©
MC2C301AT ©
10
10
4
5.5
4
5.5
1
0
0
1
MC1A310AR ©
MC1A301AR ©
20
20
MC1C310AR ©
MC1C301AR ©
10
10
5.5
7.3
5.5
7.3
1
0
0
1
MC2A310AR ©
MC2A301AR ©
20
20
MC2C310AR ©
MC2C301AR ©
10
10
Order codes
Terminal: ring terminal
20
9
0.56 1.12 2.2
0.75 1.5
3
Aux.
contacts
Intro
4
5.5
4
5.5
1
0
0
1
MC1A310AF ©
MC1A301AF ©
20
20
MC1C310AF ©
MC1C301AF ©
10
10
A
Terminal: printed circuit
20
9
0.56 1.12 2.2
0.75 1.5
3
4
5.5
4
5.5
1
0
0
1
MC1A310AI ©
MC1A301AI ©
20
20
MC1C310AI ©
MC1C301AI ©
10
10
20
12
0.75 2
1
2.6
5.5
7.3
5.5
7.3
1
0
0
1
MC2A310AI ©
MC2A301AI ©
20
20
MC2C310AI ©
MC2C301AI ©
10
10
3
4
B
C
D
Spare coil
MB0A ©
10
MB0C ©
10
E
F
(1) To complete the catalogue number, replace the symbol © by the code corresponding to the voltage and
frequency of the control circuit (other voltages on request) (see A.44)
(2) Electrical endurance AC-1: MC1... 0.3 x 106 operations
MC2... 0.35 x 106 operations
(3) Electrical endurance AC-3: MC1... (9A) = 0.85 x 106 operations
MC2... (12A)= 0.6 x 106 operations
(4) Terminal with wire 1.5 mm2: Ie = 16A
with wire 1 mm2: Ie = 10A
Insulated terminal type B 2.8 x 0.8 and wire 1 mm2 Ie = 8A in accordance with DIN 46247.
(5) Fast-on 1 x 6.3 terminals on request (replace letter F by H in the catalogue number)
G
H
I
J/X
For reference numbers,
see chapter X, pg. X.2
A.45
Series M
Three pole interface contactors
Admissible power AC3
Max. oper. current
Non- Motors
1-phase
3-phase
inductive <440V, 115V 220V 220V 380V 500V
load
3~
230V 400V
50/60Hz
(3)
AC3
AC1
kW kW kW kW kW
A
A
Terminal: screw
20
9
Contactors
20
Intro
A
12
0.56 1.12 2.2
0.75
2
3
Aux.
contacts
•3
•1
•4
•2
Voltage 24V D.C, coil 1.2W (1)
Cat. no.
(1)
Ref. no. Pack
Voltage 24V D.C, coil 2W (2)
Cat. no. (1)
Ref. no. Pack
4
4
1
0
0
1
MC1I310ATD
MC1I301ATD
100572
100573
10
10
MC1K310ATD
MC1K301ATD
100576
100577
10
10
5.5
5.5
1
0
0
1
MC2I310ATD
MC2I301ATD
100559
100538
10
10
MC2K310ATD
MC2K301ATD
103590
103591
10
10
MB0ID
100470
10
MB0KD
100471
10
Spare coil
(1) No possibility of adding instantaneous auxiliary contact blocks.
(2) Facility to mount an instantaneous auxiliary contact block of two contacts or two instantaneous auxiliary contact
blocks of one contact.
(3) Electrical endurance AC-3:
MC0... (6A) = 1.2 x 106 operations.
MC1... (9A) = 0.85 x 106 operations.
MC2... (12A) = 0.6 x 106 operations.
B
C
Multipack. Series M
To reduce the amount of waste packaging material and to save time during installation,
we offer the opportunity to order contactors in a multipack without the individual packaging.
D
Product
Type
Standard pack
Contactors
MC1...MC2a
20
(1) The quantity ordered must be a multiple of the quantity in each multipack
( with the same frame/size and coil voltage)
E
How to order
Multipack (1)
40
To order a multipack, add the suffix MP to the standard catalogue number
F
G
H
I
J/X
A.46
Example
Standard pack
MC0A310ATN
Multipack
MC0A310ATN MP
(40 pieces)
Series M
Four poles contactors
Poles
Admissible power AC3
Max.oper.current
1-phase
3-phase
NonMotors
inductive <440V, 115V 220V 220V 380V 500V
load
3~
230V 400V
50/60Hz
(3)
(2)
AC1
AC3
kW kW kW kW kW
HP HP HP HP HP
A
A
Screw terminal
20
9
20
12
4.4
-
7.5
-
13
-
17
-
1.12 2.2
1.5
3
4
5.5
4
5.5
4.4
-
7.5
-
13
-
17
-
2
2.6
3
4
5.5
7.3
5.5
7.3
13
-
17
-
4
5.5
4
5.5
Terminal: faston 2x2.8 insulated (5)
16 (4)
9
AC1
2.3 4.4 7.5
AC3
0.56 1.12 2.2
0.75 1.5
3
Cat. no. (1)
Pack
Ref. no. see bottom
Control circuit:
Direct current
Cat. no. (1)
Pack
Ref. no. see bottom
4
2
0
0
2
4
MC1A400AT ©
MC1AB00AT ©
MC1AA00AT ©
20
20
20
MC1C400AT ©
MC1CB00AT ©
10
10
4
2
0
2
MC2A400AT ©
MC2AB00AT ©
20
20
MC2C400AT ©
MC2CB00AT ©
10
10
4
2
0
0
2
4
MC1A400AF ©
MC1AB00AF ©
MC1AA00AF ©
20
20
20
MC1C400AF ©
MC1CB00AF ©
10
10
Order codes
AC1
2.3
AC3
0.56
0.75
AC1
2.3
AC3
0.75
1
Control circuit:
Alternating
current
Intro
A
B
C
Terminal: printed circuit
20
9
AC1
2.3 4.4 7.5
AC3
0.56 1.12 2.2
0.75 1.5
3
13
-
17
-
4
5.5
4
5.5
4
2
0
0
2
4
MC1A400AI ©
MC1AB00AI ©
MC1AA00AI ©
20
20
20
MC1C400AI ©
MC1CB00AI ©
10
10
D
E
F
Spare coil
MB0A ©
10
MB0C ©
10
G
H
(1) To complete the catalogue number, replace the symbol © by the code corresponding
to the voltage and frequency of the control circuit (see A.44)
(2) Electrical endurance AC-1: MC1... 0.3 x 106 operations
MC2... 0.35 x 106 operations
(3) Electrical endurance AC-3: MC1... (9A) = 0.85 x 106 operations
MC2... (12A)= 0.6 x 106 operations
(4) Terminal with wire 1.5 mm2: Ie = 16A
with wire 1 mm2: Ie = 10A
Insulated terminal type B 2.8 x 0.8 and wire of 1 mm2 Ie = 8A in accordance
with DIN 46247.
(5) Faston 1 x 6.3 terminals on request, (replace letter F by H in the catalogue number).
I
J/X
For reference numbers,
see chapter X, pg. X.2
A.47
Series M
Instantaneous auxiliary contact blocks
Number
contacts
Combinations
with basic
contactor
Contacts
in acc. with
EN 50012
Contacts
in acc.with
EN 50005
10E
Front mounting
Aux.contacts
•3
•1
•4
•2
Cat. no.
Ref. no. Pack
• Two or four additional contacts, to cover combinations of 3 or 5 contacts without increasing the surface are
of the basic contactor
Contactors
Screw terminal
Intro
A
B
C
D
E
F
G
H
I
J/X
A.48
2
2
2
2
2
21E
12E
4
4
4
4
4
4
4
4
41E
32E
23E
Ring terminal
2
2
2
2
2
4
4
4
4
4
4
4
4
21E
12E
41E
32E
23E
11
02
20
11
02
1
0
2
1
0
1
2
0
1
2
MACN211AT
MACN202AT
MARN220AT
MARN211AT
MARN202AT
100999
100998
100994
100993
100992
10
10
10
10
10
40
31
22
13
04
3
2
1
4
3
2
1
0
1
2
3
0
1
2
3
4
MACN431AT
MACN422AT
MACN413AT
MARN440AT
MARN431AT
MARN422AT
MARN413AT
MARN404AT
100997
100996
100995
100991
100990
100989
100988
100987
10
10
10
10
10
10
10
10
20
11
02
1
0
2
1
0
1
2
0
1
2
MACN211AR
MACN202AR
MARN220AR
MARN211AR
MARN202AR
103557
103558
103349
103350
103351
10
10
10
10
10
40
31
22
13
04
3
2
1
4
3
2
1
0
1
2
3
0
1
2
3
4
MACN431AR
MACN422AR
MACN413AR
MARN440AR
MARN431AR
MARN422AR
MARN413AR
MARN404AR
103559
103560
103561
103352
103353
103354
103355
103300
10
10
10
10
10
10
10
10
31
22
13
11
02
31
22
13
Series M
Instantaneous auxiliary contact blocks (continued)
Number
contacts
Lateral mounting
Combinations
with basic
contactor
Contacts
in acc. with
EN 50012
Contacts
in acc.with
EN 50005
Aux.contacts
•3
Cat. no.
Ref. no. Pack
•1
10E
•4
•2
• One or two additional blocks, to cover combinations of 1 or 2 contacts without increasing the height of
the basic unit contactor
Screw terminal
1
1
Ring terminal
1
1
10
01
1
0
0
1
MACL110AT
MACL101AT
100560
100561
10
10
20
11E
10
01
1
0
0
1
MACL110AR
MACL101AR
103555
103556
10
10
10
01
1
0
0
1
MACL110AF
MACL101AF
100562
100563
10
10
10
01
1
0
0
1
MACL110AI
MACL101AI
100564
100565
10
10
Terminal: faston 2x2.8 insulated (1)
1
20
1
11E
Terminal: printed circuit
1
1
20
11E
Order codes
20
11E
Intro
• One or two additional blocks, when up to 6 or 7 contacts are needed (combination possible
with frontal blocks)
• One or two additional blocks on both sides, to cover up to five contacts (combination possible only
with lateral blocks)
A
Screw terminal
1
1
10
01
1
0
0
1
MARL110ATS
MARL101ATS
100519
100520
10
10
Ring terminal
1
1
10
01
1
0
0
1
MARL110ARS
MARL101ARS
103299
103298
10
10
B
C
Terminal: faston 2x2.8 insulated (1)
1
1
10
01
1
0
0
1
MARL110AFS
MARL101AFS
100521
100522
10
10
Terminal: printed circuit
1
1
10
01
1
0
0
1
MARL110AIS
MARL101AIS
100523
100524
10
10
(1) Terminal with wire 1 mm2: Ie = 10A
Insulated terminal type B 2.8 x 0.8 with wire 1 mm2: Ie = 8A, in accordance with DIN 46247
D
E
F
G
H
I
J/X
A.49
Series M
Accessories
Contactors
For use
with:
Time
Electronic timer
block
Lateral or front fixing to the contactor
DIN rail adaptor
for electronic
timer block
For fixing onto EN 50022-35
MREBC...
MCR..MC_ ...
MCR..MC_ ...
For use
with:
Voltage suppressor
block
0.5 - 60 seg.
0.2 - 24 seg.
Type
Connection and (plug-in) fixing
on to the connector
MCRA,MC_ ...
R/C
MCRA,MC_ ...
R/C
MCRC,MC_ ...
Diode
MCRC,MC_ ...
Varistor
Function
Ue
Cat. no.
Ref. no.
Pack
delay ON
delay ON
24... 250V AC/DC
24...250V AC/DC
MREBC10AC2
MREBC20AC2
100541
100542
10
10
MVB0R
100543
10
Control
Ue
Cat. no.
Ref. no.
Pack
AC
AC
DC
AC/DC
12...60V 50/60Hz
72...250V 50/60Hz
6...250V DC
24-48V
MP0AAE1
MP0AAE2
MP0CAE3
MP0DAE4
100544
100545
100546
100536
10
10
10
10
Terminal
capacity
Ue
Cat. no.
Ref. no.
Pack
MVP0C
100600
10
Cat. no.
Ref. no.
Pack
Intro
A
B
For use
with:
Pole paralleling
links
Phases
To connect two, three or four phases in parallel
MC_ ...
2, 3, 4 (parallel) Ø4.5mm - 16mm2
C
D
E
For use
with:
Mechanical
interlock
Mechanical interlock and pole jumpers
MCR, MC_ ...
MMH0
100547
10
Cat. no.
Ref. no.
Pack
EAT 260
SPR
100548
100549
1
1
F
For use
with:
G
Identification
H
I
J/X
A.50
MCR, MC_ ...
MCR, MC_ ...
Labels (10 sheets of 260 labels)
Labelling plate base. Plug-in labelling plate bases
(50 pieces in one pack)
Series M
Direct-on-line starters
6 to 12A (AC-3)
Series M - Direct-on-line starters
Empty boxes
Push-buttons
Protection
degree
Cat. no.
Start/Stop + Reset
IP40
IP65
IP40
IP65
IP40
IP65
MG0004PAT0
MG0006PAT0
MG0004RAT0
MG0006RAT0
MG0004QAT0
MG0006QAT0
209780
209781
137567
116402
137566
116074
1
1
1
1
1
1
MAGL110AT
100608
1
Reset only
Start/Emergency stop
Start contact block
Laterally mounted to the contactor, allowing the electrical operation
the box push-button which incises on it.
Ref. no Pack
Intro
A
Reversing starters
B
6 to 12A (AC-3)
C
• Power circuit: up to 690V AC
• Control circuit: up to 600V AC
up to 250V DC
• Assembled versions on request.
• Screw and push-on terminals protected against accidental contact.
• Protection degree IP20 in accordance with EN 60529.
• Facility to mount instant and timed auxiliary contact blocks and voltage
suppressor blocks.
D
E
F
Series M - Reversing starters
Description
Wiring kits
for reversing
starters
Order codes
• Power circuit: up to 690V AC
• Control circuit: up to 600V AC
• Polycarbonate enclosure (IP40 - IP65)
- Shock resistance
- Total insulation §
- 4 knock-out input holes PG13.5
- Cable entry in the base
• Terminals protected against accidental contact
• 16 setting ranges from 0.11 up to 14A
• Start contact block
Suitable to be usd with link
modules
Upper and lower connections
without overload relays
For use with
contactor
MC1.., MC2..
ac/dc
Cat. no.
Ref. no.
Pack.
ac/dc
WKMIU
101421
1
G
H
I
J/X
Wiring diagrams ! page A.134
Dimensions ! page A.137
A.51