iec separable connectors

advertisement
UTILITIES
IEC SEPARABLE
CONNECTORS
IEC SEPARABLE CONNECTORS / 42 KV / 1250 A
Chardon Front T-Body / Coupling (Rear) T-Body connectors are fully
screened and fully submersible, products are used to terminate polymeric
cable to dead front apparatus such as transformers, switchgear, and other
equipment. They can be use at 36kV and 42 kV. Products can be used for
indoor or outdoor applications, and are able to be used for all polymeric cable
types ( XLPE, ETP, etc.) with copper or aluminum conductors. The design is
especially suited for the harsh off-shore wind farm environment where long
runs and large cable are needed.
ESPECIFICAÇÕES DOS PRODUTOS
KEY FEATURES
• Maximum Voltage Class (Um): 42kV.
•
Provides a fully shielded and submersible connection when mated with the
proper bushing or plug.
• AC 5 Minute Withstand: 117kV.
• DC 15 Minute Voltage Withstand: 125 V.
•
Type “C” 1250A interface.
•
Mounting can be vertical, horizontal, or any angle in between.
•
No minimum phase clearance requirements.
• BIL and Full Wave Crest (Impulse):
200kV.
•
100% electrical tested in production.
• Thermal Short Circuit (Conductor, 3 sec.):
45kA.
• Minimum Corona Voltage Level:
45kV < 10pC.
• Dynamic Short Circuit: 100kA.
PRODUCT RATINGS
• Continuous Current: 1250A.
Tests conducted in accordance with IEC 60502-4:
•
Minimum Corona Voltage Level: 45kV ≦ 10pC.
•
AC 5 Minute Withstand: 117kV.
PRODUCTION TESTS
To determine the part number in the choice of accessories,
follow the steps below:
STEP 3
___
Selection of Conductor Size
_
___
_
STEP 2
STEP 3
STEP 4
42 - _ _ _ 1250
STEP 1
STEP 1
___
Selection of Front / Rear T-body
TYPE
CODE
FDT
Front T-body
RDT
Coupling(Rear)T-body
STEP 2
CODE
mm²
25mm²
185
35mm²
240
240mm²
050
50mm²
300
300mm²
070
70mm²
400
400mm²
095
95mm²
500
500mm²
120
120mm²
630
630mm²
150
150mm²
800
800mm²
CODE
mm
185mm²
025
_
Selection of Compression Connector Material
Selection of Cable Insulation Dimension
CODE
mm²
035
STEP 4
_
CODE
MATERIAL
A
Alumínio
CODE
mm
B
Bimetálico (Al e Cu)
C
Cobre
A
15.3 - 18.9
G
32.1 - 36.9
B
16.9 - 21.5
H
35.9 - 41.1
C
20.5 - 24.1
J
40.1 - 45.7
D
23.1 - 26.7
K
44.7 - 50.7
E
25.7 - 29.7
L
49.7 - 55.7
F
28.7 - 33.1
M
54.9 - 60.7
EXEMPLE:
For a CHARDON 42kV Front T-body with cable insulation outer dimension of
26.4mm and a conductor size of 185mm² with copper compression
connector, the part number would be as follows.
42 - FDT 1250 E 185 C
Front T-body Connector
185mm (7.28")
INSULATING PLUG
Molded epoxy insulating plug
provides excellent electrical,
thermal and mechanical reliability.
Ф101mm (3.98")
STUD
Zinc plated, threaded steel stud.
RUBBER END CAP
Molded EPDM conducting rubber end
cap protects and grounds the insulating
plug test point.
CONDUCTING INSERT
Precision molded peroxide cured
conducting insert provides
corona-free electrostatic shielding
of the compression connector.
COMPRESSION CONNECTOR
Compression connector made of aluminum,
copper, or bi-metal(aluminum/copper).
391mm (15.39")
INSULATION LAYER
High quality peroxide cured EPDM
insulation is mixed and formulated
in-house for complete control of
rubber characteristics.
CONDUCTING SHIELD
Precision molded peroxide cured
conducting shield provides ground
shield continuity.
CABLE ADAPTER
Molded cable adapter, sized to fit the cable
insulation, provides stress relief for the
terminated cable.
Ф116mm (4.57")
Coupling (Rear) T-body Connector
315mm (12.40")
INSULATING PLUG
Molded epoxy insulating plug
provides excellent electrical,
thermal and mechanical reliability.
Ф101mm (3.98")
CONTACT ROD
Copper made contact rod
provides a consistent
current transfer path.
RUBBER END CAP
Molded EPDM conducting rubber end
cap protects and grounds the insulating
plug test point.
STUD
Zinc plated, threaded steel stud.
391mm (15.39")
COMPRESSION CONNECTOR
Compression connector made of aluminum,
copper, or bi-metal(aluminum/copper).
CONDUCTING INSERT
Precision molded peroxide cured
conducting insert provides
corona-free electrostatic shielding
of the compression connector.
INSULATION LAYER
High quality peroxide cured EPDM insulation is
mixed and formulated in-house for complete
control of rubber characteristics.
CONDUCTING SHIELD
Precision molded peroxide cured
conducting shield provides ground
shield continuity.
CABLE ADAPTER
Molded cable adapter, sized to fit the cable
insulation, provides stress relief for the
terminated cable.
Ф116mm (4.57")
129mm (5.08")
The Front T-body Connector and Coupling (Rear) T-body Connector are manufactured by CHARDON GROUP .
Brasil +55 (47) 3337-5382
USA +1 (305) 6004356
info@seielectric.com
www.seielectric.com
Download