SINGLE DUCT Airflow CAV (Constant Air Volume) Cooling The airflow remains constant regardless of changes in duct pressure or room temperature. A room thermostat is not used. 80 60 40 20 Min.. DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 RA 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Models: PESV, PECV, PQCV Thermostat Branch Pressure, (psi) Airflow 100 80 60 20 Min. low 40 Max. CAV rF CAV Cooling, Hot Water Reheat The cold airflow remains constant regardless of changes in duct pressure or room temperature. As room temperature increases, the room thermostat modulates the hot water coil valve toward the closed position. ate tW Control Option Code: OO VAV Cooling, Hot Water Reheat As the room temperature increases, the room thermostat modulates the hot water coil valve toward the closed position. On a further increase in room temperature, the room thermostat modulates the cold airflow from the minimum to maximum setting. Max. CAV 100 V Control Option Code: OO VAV (Variable Air Volume) Cooling As the room temperature increases, the room thermostat modulates the cold airflow from the minimum to the maximum setting. Ho O terminal unit accessories VA Redefine your comfort zone™ | www.titus-hvac.com CONTROL SEQUENCES DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 RA Thermostat Branch Pressure, (psi) Model: PESV Control Option Code: OO VAV Cooling, Electric Reheat As the room temperature increases, the room thermostat de-energizes the electric heating one step at a time. On a further increase in room temperature, the room thermostat modulates the cold airflow from the minimum to the maximum setting. CAV Cooling, Electric Reheat The cold airflow remains constant regardless of changes in duct pressure or room temperature. As room temperature increases, the room thermostat de-energizes the electric heating coil one step at a time. Airflow 100 80 20 Max. Step 2 60 40 CAV Step 3 Step 1 Min. DA 0 1 2 3 4 5 6 7 8 910 11 12 13 14 15 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 RA Thermostat Branch Pressure, (psi) CONTROL SEQUENCES Model: PESV Control Option Code: WU VAV Cooling with Morning Warm-Up (MWU) A separate 15 to 25 psi pneumatic signal line to each terminal unit resets the controller setpoint through a signal selector relay for pressure independent hot airflow at the maximum setting. Additional heat may be provided by a heating coil on the discharge of the unit. Airflow 100 Max. MWU 80 60 40 20 Min. DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 RA Models: PESV, PECV, PQCV O18 O18 When the warm-up signal is turned off, the unit resumes normal cooling operation. As the room temperature increases, the room thermostat modulates the cold airflow from the minimum to the maximum setting. Thermostat Branch Pressure, (psi) Control Sequences (continued) terminal unit accessories Total Airflow Control Option Code: DM VAV Cooling, Dual Minimum Flows, with Reheat (Signal Line) When the signal line is zero psi, a decrease in room temperature modulates the cold airflow from the maximum to the minimum setting. Model: PESV Control Option Code: DP VAV Cooling, Dual Minimum Flows, with Reheat (Dual Pressure Main) At the summer main pressure (usually 18 psi) a decrease in room temperature modulates the airflow from maximum down to the minimum setting. Max. 100 When the signal line equals the alternate psi, a decrease in room temperature modulates the airflow from maximum to alternate minimum setting. A further decrease in room temperature modulates the hot water valve or steps the electric coil for reheat. 80 60 40 20 Alt. Min. Min. DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Thermostat Branch Pressure, (psi) Airflow At the winter main pressure (usually 23 psi), a decrease in room temperature modulates the airflow from maximum down to alternate minimum setting. A further decrease in room temperature modulates the hot water valve to open or steps the electric coil on for reheat. Max. 100 80 60 40 20 Alt. Min. Min. DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Thermostat Branch Pressure, (psi) Model: PESV O Airflow Control Option Code: FF 100 Max. Max. 80 Ho 60 tW 40 r ate VAV Cooling and VAV Heating, Equal Maximum Flows (Flip-Flop) A decrease in room temperature modulates the A further decrease in room temperature airflow from maximum to minimum setting (at modulates the airflow from minimum to room thermostat setpoint). maximum setting and modulates the hot water control valve to the open position. Redefine your comfort zone™ | www.titus-hvac.com SINGLE DUCT 20 Min. DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Thermostat Branch Pressure, (psi) Model: PESV Max. 100 80 Min. er 60 40 20 Min. DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Model: PESV Thermostat Branch Pressure, (psi) CONTROL SEQUENCES Airflow at tW Ho Control Option Code: DO VAV Cooling and VAV Heating, Dual Maximum Flows A decrease in room temperature modulates the A further decrease in room temperature airflow from maximum to minimum setting (at modulates the airflow from minimum to room thermostat setpoint). alternate maximum setting and modulates the hot water control valve to the open position. O19 terminal unit accessories DUAL DUCT Airflow Control Option Code: OO VAV, No Mixing The hot and cold duct controllers are set independently for maximum airflow setting. Both controls are set for zero minimum airflow. 100 demanding or unequal inlets are required, the hot duct maximum can be adjusted for a lower setting. 80 20 Hot and cold controls can be set for equal maximum airflow. If heating loads are less Equal Max. Flow Rates Unequal Max. Flow Rates Max. 60 40 Max. Max. t Ho C DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 RA Thermostat Branch Pressure, (psi) Model: PEDV Control Option Code: OO VAV with Mixing (Attenuator required) Diagram shows unit with hot inlet and cold total flow sensors. The hot control is still set for zero minimum airflow. The unit minimum is set on the cold inlet control. Unequal inlets are available for the hot inlet. Airflow Maximum airflow can be independently adjusted for equal or unequal settings. Mixing begins when the cold airflow reaches minimum airflow. When the hot airflow is greater than the unit minimum, the cold damper is fully closed. Optional cold inlet and hot total flow sensors are available. 100 Max. 80 60 40 Max. ld O d ol Max. Co Redefine your comfort zone™ | www.titus-hvac.com Control Sequences (continued) Ho 20 t DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 RA Thermostat Branch Pressure, (psi) Models: PEDV, PMDV Control Option Code: OO O20 O20 100 Maximum airflow for the hot inlet is set equal to unit minimum. Mixing begins when the cold airflow reaches minimum airflow. When the hot airflow is equal to the unit minimum, the cold damper is fully closed. Optional cold inlet and hot total flow sensors are available. Max. 80 60 40 ld Max. Co Ho t 20 DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 RA Thermostat Branch Pressure, (psi) Models: PEDV, PMDV Models: PEDV, PMDC Airflow The cold control minimum and maximum are set equal to total flow. The room thermostat is connected to the hot control only. If the optional cold inlet and hot total sensors are selected, the mixing occurs between 8 and 13 psi thermostat pressure. 100 80 60 40 Max. Max. Co ld Control Option Code: OO Constant Air Volume (Attenuator required) Diagram shows unit with hot inlet and cold total flow sensors. The hot control is set for zero minimum airflow and maximum airflow is equal to total airflow. t Ho CONTROL SEQUENCES VAV with Hot Maximum Equal to Unit Minimum Airflow (Attenuator required) Diagram shows unit with hot inlet and cold total flow sensors. The hot control is still set for zero minimum airflow. The unit minimum is set on the cold inlet control. Unequal inlets are available for the hot inlet. Airflow 20 DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 RA Thermostat Branch Pressure, (psi) Control Sequences (continued) terminal unit accessories Control Option Code: OO Total Airflow 80 60 40 Plenum Air Max. Pr im Ai ary r 100 ate tW Ho y ar im Pr Air r Constant Volume Fan VAV Terminal with Hot Water Heat The unit fan delivers a constant airflow to the With a further decrease in room temperature, space at all times. As the room temperature the room thermostat modulates the water coil decreases, the primary air valve modulates valve to the open position. the airflow from the maximum to the minimum setting. 20 DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 RA Thermostat Branch Pressure, (psi) Models: PTFS, PTQS, PFLS Redefine your comfort zone™ | www.titus-hvac.com FAN POWERED Control Option Code: OO Total Airflow 80 Plenum Air Step 2 60 Step 1 40 y ar im Pr Air 20 DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 RA O Thermostat Branch Pressure, (psi) Models: PTFS, PTQS, PFLS Control Option Code: OO Airflow Max. 100 60 y ar im Pr Air r 20 Plenum Air Pr 40 im Ai ary r 80 ate tW With a further decrease in room temperature, the room thermostat energizes the unit fan and the water coil valve modulates to the full open position. Ho Variable Volume Fan VAV Terminal with Hot Water Heat As the room temperature decreases, the primary airflow modulates from maximum to minimum setting (at room thermostat setpoint). Max. im Ai ary r Step 3 100 Pr Constant Volume Fan VAV Terminal with Electric Heat The unit fan delivers a constant airflow to the With a further decrease in room temperature, space at all times. As the room temperature the electric heating coil is energized one step decreases, the primary air valve modulates at a time. the airflow from the maximum to the minimum setting. DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 RA Thermostat Branch Pressure, (psi) Control Option Code: OO Models: PTQP, PFLP 100 80 With a further decrease in room temperature, the room thermostat energizes the unit fan and the electric heating coil is energized one step at a time. Step 2 60 40 20 Max. Plenum Air Step 1 Pr im Ai ary r Variable Volume Fan VAV Terminal with Electric Heat As the room temperature decreases, the primary airflow modulates from the maximum to the minimum setting (at room thermostat setpoint). Airflow Step 3 y ar im Pr Air DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 RA Thermostat Branch Pressure, (psi) CONTROL SEQUENCES Models: PTQP, PFLP O21 Redefine your comfort zone™ | www.titus-hvac.com Control Sequences (continued) terminal unit accessories FAN POWERED Control Option Code: AC Constant Fan VAV Terminal with Night Shutdown (NSD) PE Day operation, main air ON. See the control Night operation, main air OFF, primary air fan sequence outlined on page O21. must be shut off. The unit fan remains off until the main air is restored. Units with electric heat must use reverse acting thermostats to prevent heat operation when fan is off. Airflow Night Operation Central System Off 100 80 60 No Primary Air 40 Fan Terminal Unit Fan Off 20 RA 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Thermostat Branch Pressure, (psi) Models: PTFS, PTQS, PFLS Control Option Code: AE Airflow Central System Off 100 Plenum Air 80 NSB Setpoint l l na oi tio g C Op atin He 60 40 20 RA Thermostat Branch Pressure, (psi) Control Option Code: AD Constant Fan VAV Terminal with Night Shutdown (NSD) Airflow Switch Day operation, primary air handler ON. See control sequence on page O21. Airflow 100 Night operation, primary air to the unit is shut off. The unit fan remains off until the primary air is restored. 80 Night Operation Central System Off No Primary Air 60 40 20 Fan Shut Down DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 RA Thermostat Branch Pressure, (psi) Control Option Code: AF Constant Fan VAV Terminal with Night Setback (NSB) Airflow Switch Day operation, primary air handler ON. See the Night operation, primary air OFF. The unit fan control sequence on page O21. remains off until the night setback thermostat calls for heat. The unit fan energizes followed by the water or electric heat. Airflow 100 80 60 40 20 Central System Off Plenum Air l l na oi tio g C Op atin He CONTROL SEQUENCES Models: PTFS, PTQP, PFLP O22 O22 No Primary Air 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 NSB Setpoint O Constant Fan VAV Terminal with Night Setback (NSB) PEs Day operation, main air ON. See the control Night operation, main air OFF, Primary air fan sequence outlined on page O21. must be shut off. The unit fan remains off until the night setback thermostat calls for heat. The unit fan energizes followed by the water or electric heat. Units with electric heat must use reverse acting thermostats to prevent heat operation when fan is off. Models: PTFS, PTQS, PFLS No Primary Air DA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 1415 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 RA Models: PTFS, PTQP, PFLP Thermostat Branch Pressure, (psi)