Installation and Operation Manual Application

Installation and Operation Manual
Model WZ1
Application
SYSTEM
FAN
The WZ1-T is a battery powered, auto-changeover thermostat
that communicates via an RF wireless data link to a damper
control module located on the Zone One™ damper. The
system is designed to prevent overheating and overcooling of
individual zones. Up to 8 WZ1 thermostat controlled dampers
can be used in the same location.
Sequence of operation
An automatic changeover duct sensor located on the damper
senses whether there is warm air or cool air in the branch
supply duct. If the Zone One™ thermostat is calling for cooling
and the duct sensor determines there is cool air in the duct, the
damper will power open; otherwise, the damper will remain
closed. If the Zone One™ thermostat is calling for heating and
the duct sensor determines there is warm air in the duct, the
damper will power open; otherwise, the damper will remain
closed. The relay control module has LED indication to confirm
mode of operation and damper position.
Specifications
Damper Actuator Type
24 Volt, 10 VA, 2-wire, powered open / spring return close
Communications Indicator
Multi-color LED indicates mode of operation
Damper Position Indicator
Green LED indicates when damper is open
Communications
Wireless, 915MHz, proprietary protocol
Range
Up to 100 feet
Control Module Power
24VAC, 40VA
Control Module Housing
Molded plastic
Control Module Dimensions
3.25 x 5.50 x 1.125 inches (WHD)
Thermostat Dimensions
5.00 x 4.50 x 1.00 inches (WHD)
Wireless Zone One™ Module
1
Installation
The Wireless Zone One™ damper control module comes installed on the zone damper and is completely factory wired.
The damper control module is powered by a separate 24 Volt, 40 VA transformer.
DAMPER
ACTUATOR
PO / SC
ON WHEN DAMPER
IS POWERED OPEN
24 VAC
GREEN
LED
LED
PROGRAM
ENABLE
BUTTON
1
2 3 4
5 6
7
G Y W R C
DUCT SENSOR
Solid Red LED = Heat Call
Solid Yellow LED = Cool Call
Flashing Green LED = No Calls
Wireless Zone One™ Thermostat
2
Location
The thermostat should be located in the area being controlled by the zone damper and away from the HVAC unit
thermostat. Do not install the thermostat in an area where drafts are present, near the floor, behind doors or on an
external wall. Avoid placing the thermsotat in areas where the air movement is limited, affected by direct sunlight or other
areas not typical of the temperature in the space.
2
3
4
Removing the Subbase
Hold the subbase with one hand, press the case as shown below and pull the bottom of the thermostat from the subbase.
Press here to release
case from subbase.
4
Installing the Subbase
The thermostat should be installed approximately 5 feet above the floor. Level the subbase for appearance and use the
wall anchors and screws provided.
5
Installing the Batteries
Slide the battery cover off and install two AA batteries included with the thermostat. Install the batteries with the positive
terminals to the right as shown. Replace the battery cover.
3
6
Thermostat Installer Options
The installer options can be accessed by pressing and holding the ENTER key for seven seconds. The LCD displays
Option 01 for setting the Zone number.
(See Installer Options Chart)
Press or hold the NEXT key to advance to the next option. The LCD will advance through to Option 09 and then return to
Option 01.
Press the ENTER key to save all options in non-volatile memory.
If only one wireless thermostat and damper control module are used in an application, the thermostat can be left with the
factory default setting of Zone = 01
If multiple wireless thermostats and damper control modules are used that are less than 500 feet away from one another,
each thermostat must be set to a different Zone number. For convenience, set the Installer Options with the thermostat
off the subbase and in easy access of its damper control module.
7
Setting the Zone Number
If more than one WZ1 is used in the same application, each thermostat and module must be assigned a different
communications address. Use the UP and DOWN keys to set the zone number for each thermostat in the system. The
maximum number that can be used in the same building is eight.
Installer Options Chart
Option
Zone
01
Zone number
Range
01 to 08
Default
01
03
Program damper module to Zone address
Default 01
08
Maximum allowable heating setpoint
Range
60 to 85F
Default
76F
Minimum allowable cooling setpoint
Range
55 to 80F
Default
68F
Option
CANCEL
NEXT
09
ENTER
Description
Press the NEXT key to advance to the next option. Press the ENTER key if no more options are to be changed.
8
Heat
Heating Setpoint Limit
Set To
Press the NEXT key to select Option 08 and press the Up or Down key to
set maximum allowable heating setpoint.
The maximum heating setpoint range is 60 to 85F.
Option
CANCEL
4
NEXT
ENTER
9
Cool
Cooling Setpoint Limit
Set To
Press the NEXT key to select Option 09 and press the Up or Down key to
set the minimum allowable cooling setpoint.
The minimum cooling setpoint range is 55 to 80F.
Option
CANCEL
10
NEXT
ENTER
Programming the Module
If there is only one WZ-1 installed, it is not necessary to program the address as the thermostat and damper
control module default address is Zone 01.
After selecting the Zone number for the thermostat, the same address must be programmed into the damper control
module. Remove the cover on the module and apply 24 Volts power. Press the PROGRAM ENABLE button. The
module will accept a new address for thirty seconds. The LED on the module will alternately blink red and green while it is
waiting for a new address. When the module accepts the address, the LED will begin to flash green confirming
communications with the thermostat.
ACTUATOR
PO / SC
ON WHEN DAMPER
IS POWERED OPEN
24 VAC
PROGRAM
ENABLE
BUTTON
FLASHING LED
GREEN
LED
1
LED
2 3 4
5 6
7
G Y W R C
The multi-colored LED indicator normally flashes green when no calls are active. The LED is continuously
yellow during cooling calls and red during heating calls.
While the module LED is alternately blinking red and green, press and hold
the ENTER key for seven second until the zone number is displayed. Press
NEXT until Option 03 (Pr) and the zone number are displayed. Send the
zone address to the damper control module by pressing the ENTER key.
When the module LED begins to flash green, communications with the
thermostat has be enabled.
Zone
Option
CANCEL
5
NEXT
ENTER
Thermostat Operation
Up and Down keys used when
adjusting temperature, time of day,
day of the week, and other options
Temperature Setting
Space temperature
Heat
Set To
Inside
AUTO
Mo
FAN
AM
MENU
CANCEL
NEXT
Menu key used to set time of
day and day of week
SYSTEM
SYSTEM key selects
Auto and Off
ENTER
Fan key (Not used)
Cancel key used to
cancel changes
Battery compartment, 2 AA batteries.
Enter key used to access
Installer Setup and save
settings
Next key used when setting
time of day and changing
from heating and cooling
setpoint
6
11
Setting the Time
and Weekday
To set the time of day and the day of the week, press the MENU key
and the LCD will display the hour. Use the Up and Down keys to set
the hour. Make sure that the AM or PM is correct.
Press the NEXT key to set the minute. Use the Up and Down keys to
set the minute.
Press the NEXT key to set the current day of the week. Use the Up and
Down keys to select the day of the week and press the ENTER key.
Th
AM
MENU
11
CANCEL
NEXT
Setting the Heating and
Cooling Temperature
ENTER
Heat
Set To
Inside
Press the hold the Up or Down key to change the heating or cooling
temperature. Press the Next key to switch between the heating and
cooling temperature.
HEAT
Th
AUTO
AM
MENU
12
NEXT
Low Battery
Indication
ENTER
Heat
Set To
Inside
If the battery voltage drops to where it could interfere with reliable
operation, the LCD will alternately display Lo in place of the Inside
temperature. Replace batteries immediately.
AUTO
Day
Th
AM
MENU
7
NEXT
ENTER
9
Resetting Factory Defaults
To reset the factory defaults, remove the batteries and re-install them while holding down the SYSTEM key. All prior
changes will default to the factory settings. This will require resetting the time and day. Refer to the Installer Options
Chart default settings to make any additional changes.
Hold down SYSTEM key
while replacing batteries
Although great care has been taken in preparation of this manual, Jackson Systems takes no responsibility
for errors or omissions contained herein. It is the responsibility of the installer to ensure that the Wireless
Zone One™ thermostat, control module and damper are installed and wired properly to provide safe and
efficient operation.
Due to ongoing product improvements, Jackson Systems reserves the right to change the specifications of the
Wireless Zone One™ system and its components without notice.
All rights reserved.
© Jackson Systems, LLC 2010
Intellectual rights apply.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device
may not cause harmful interference and (2) this device must accept any interference received, including interference
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
SYSTEMS
8
06-1059-012611