Standard Drawings 2006 Edition

advertisement
CHIEF ENGINEER
4"
STANDARD METHOD OF
INSTALLING SADDLES
A
0
SECTION B-B
0
SHORT
MORTAR
CEMENT
420-C-2000
RADIUS BEND
SEE NOTE
EXISTING SEWER
6"
STANDARD "Y" SADDLE
B
SADDLE
6" STD " T "
6" - 45
BY DISTRICT INSPECTOR
IN FIRM SOIL WHEN APPROVED
THIS PORTION MAY BE OMITTED
SECTION A-A
(SHALLOW LINE)
SADDLE
6" STD " T "
SEE NOTE
EXISTING SEWER
6"
STANDARD "T" SADDLE
420-C-2000
45
12"
END VIEW
5"
5"
C
C
5"
SEE NOTE
SECTION A-A
(DEEP LINE)
SADDLE
6" STD " T "
SEE NOTE
SECTION C-C
EXISTING SEWER
STANDARD "T" SADDLE
4"
ENCASEMENT
5"
" Y " BRANCH
CONNECTED
CONCRETE
6" STD DOUBLE
BRANCHES NOT
PLUG ALL
SURFACE
GROUND
6"
HOLES IN NRCP AND VCP 18" AND SMALLER
MAY BE MADE BY CHIPPING THE PIPE.
PER S-a-86.
LARGER THAN 18" SHALL BE MADE BY CORE DRILLING
HOLES IN RC PIPES AND IN NRCP AND VCP PIPES
NOTE:
THIS DRAWING DOES NOT APPLY TO CONNECTIONS TO LINED PIPE
END VIEW
B
LE
AB
RI
VA
END VIEW
LE
AB
RI
VA
4"
" Y " BRANCH
6" STD DOUBLE
NOT CONNECTED
8"
PLUG ALL BRANCHES
MIN
A
3"
4"
STEPHEN R. MAGUIN
VARIABLE
18"
3"
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
2006 EDITION
S-a-79
SHEET 1 OF 1
BLOCKOUT OR CORED HOLE
SECURELY MORTAR STUB INTO
4" OR 6" DIA
HC ONLY
SECURELY MORTAR
STUB INTO CORED HOLE
"
EL
EV
"A
CORED HOLE
DIA = OD + 1" MAX
(TYP)
CONNECTION TO REINFORCED
CONNECTION TO RCP (ALL SIZES)
CONCRETE STRUCTURE
& NRCP & VCP 21" OR LARGER
NOTES:
1.
ELEVATION "A" FOR LATERAL SEWER CONNECTIONS SHALL BE AS SHOWN ON APPROVED LATERAL SEWER DRAWINGS.
2.
HOUSE CONNECTION TO THE PIPE SHALL BE AS SHOWN ON S-a-79 EXCEPT AS SHOWN HEREON.
THE CORED HOLE SHALL BE MADE WITH EQUIPMENT SPECIALLY DESIGNED TO CUT A SMOOTH HOLE WITHOUT SPALLING OR
3.
DAMAGE TO THE REINFORCING STEEL,
PIPE OR STRUCTURE.
4.
THE CORING OF THE HOLE AND THE PLACING OF THE STUB SHALL BE DONE IN THE PRESENCE OF THE DISTRICT INSPECTOR.
5.
NO CONNECTION SHALL BE MADE TO THE STUB UNTIL DISTRICT INSPECTOR HAS APPROVED THE STUB.
THIS DRAWING DOES NOT APPLY TO CONNECTIONS TO
LINED PIPES OR STRUCTURES
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
STANDARD METHOD FOR CONNECTION
TO PIPES AND STRUCTURES
2006 EDITION
S-a-86
SHEET 1 OF 1
STD MH F&C
(SEE S-a-228)
GROUND SURFACE
4"
8" BRICKWORK TO DEPTH
OF 22’-0". 12" BRICKWORK
BELOW DEPTH OF 22’-0"
FORM CHANNELS WITH
BRICK & MORTAR OR
420-C-2000 CONCRETE
C
VARIABLE
C
4"
MIN
660-B-4000
INLET
3/4 DIA
3’-9" MIN
VARIABLE
1/2"
OUTLET
PLASTER
BRICK ARCH
FOR HEIGHT LESS THAN 6’-6"
5"
24" DIA
USE TYPE "C" MANHOLE (S-a-203)
16" MAX
24" DIA
(TYP)
1/2" P
LAST
ER
9"
KEYS
2 x 4 x 3’-0"
SECTION A-A
SECTION B-B
NOTES:
B
1.
FOR 15" SEWERS AND LARGER, TURN 8" ARCH OVER
PIPE.
OPTIONAL BASE
2.
FOR 12" SEWERS AND SMALLER, TURN 4" ARCH OVER
PIPE.
MH STEP
3.
(SEE NOTE 3 & 4)
THE LOWEST MANHOLE STEP SHALL BE PLACED
NOT LESS THAN 8" NOR MORE THAN 24" ABOVE
SHELF.
E
A
LF
SHELF
SH
A
4.
VARIABLE
48" DIA
SEE NOTE
THE UPPER MANHOLE STEP SHALL BE PLACED
BETWEEN THE TOP OF MANHOLE AND MANHOLE
FLOW
COVER FRAME AND SHALL PROJECT NOT MORE
THAN 4" INSIDE MANHOLE. ALL OTHERS SHALL
PROJECT 5".
5.
6
FOR LAYING BRICK OR PLASTERING, THE MORTAR
SHALL CONFORM WITH SECTION 201-5.1 (CLASS "D")
OF THE STANDARD SPECIFICATIONS.
SHELF
6.
FOR 30" PIPE AND LARGER, THE TOP PORTION OF
THE PIPES WITHIN THE MANHOLE SHALL BE CUT
OUT TO PROVIDE A CIRCULAR OPENING BETWEEN
THE PIPE ENDS OF NOT LESS THAN 42". THE CUT
EDGES SHALL BE PLASTERED SMOOTH WITH
CEMENT MORTAR FOR CONCRETE PIPE AND EPOXY
FOR CLAY PIPE. THE CIRCULAR OPENING SHALL
B
BE CUT PRIOR TO INSTALLATION OF THE RISER
SECTIONS.
PLAN SECTION C-C
FOR 8" TO 30" PIPE
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD MANHOLE, TYPE "A"
S-a-201
SHEET 1 OF 1
GROUND
STD 36" MH FRAME &
3" MAX CLASS
COVER PER S-a-226
"B" MORTAR
GROUND
SURFACE
SURFACE
CONC RING
ADJUSTING RING
( SEE NOTE 5 )
MH
9" MAX
STEPS
6" MIN
36" DIA
36" DIA
36" PRECAST CONC
SHAFT & PLASTIC LINER
w/ LOCKING EXTENSIONS
MH STEPS
#5@12
FOR REINF
PER S-a-209
SEE ROOF PLAN
FOR REINF
#5@12
C
SEE ROOF PLAN
2" CLR
" u " BARS
(TYP)
PULL RING
PULL RING
S-a-220
" w " BARS
S-a-220
(TYP)
#4@12
PLATE
(TYP)
INLET
IAB
VAR
LE
OD OF
LOWER LIMIT
OUTLET
PIPE
PLASTIC LINER
OF PLASTIC
LINER PLATE
3"
" v " BARS
3"
LOWER LIMIT
OF PLASTIC
D
LINER PLATE
" v " BARS
#5@12
" w " BARS
30d
MATCH EXIST
ADJ PIPE, 90
O
MAX
LAP
#5@12
LONGITUDINAL SECTION
CROSS SECTION
MH STEPS
(SEE NOTE 2)
PULL RING
(SEE NOTE 1)
#5 DIAGS
T&B (TYP)
ADD #5 T&B
C
L PIPE
"r"
"r"
A
B
C
L PIPE
BARS
6"
#5@12T
"s"
BARS
IN
N
PE
36
O
"
D
E
IA
G
M
H
6"
BARS
A
EACH SIDE
B
" t " BARS
#5@12T
ROOF PLAN
0
O
TO 15
O
FOR 48" TO 96" PIPE
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD MANHOLE, TYPE "B"
S-a-202
SHEET 1 OF 3
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STEPHEN R. MAGUIN
STANDARD DRAWING
CHIEF ENGINEER
STANDARD MANHOLE, TYPE "B"
2006 EDITION
S-a-202
SHEET 2 OF 3
90" TO 96"
75" TO 84"
63" TO 72"
51" TO 60"
48"
PIPE DIA
DEPTH
12"
8"
8"
12"
UP TO 30’
31’ TO 50’
7"
10"
7"
10"
UP TO 30’
31’ TO 50’
7"
10"
7"
10"
UP TO 30’
31’ TO 50’
6"
6"
6"
B
8"
8"
8"
A
31’ TO 50’
UP TO 30’
31’ TO 50’
UP TO 30’
TO INV
20"
18"
18"
16"
18"
15"
18"
15"
15"
12"
C
8"
8"
7"
7"
7"
7"
6"
6"
6"
D
DIMENSIONS
10”
5’-2"
4’-0"
15”
7”
15”
7”
5’-2"
4’-0"
8”
15”
4’-10"
4’-0"
15”
8”
4’-0"
4’-10"
15”
10”
15”
4’-8"
4’-0"
4’-8"
10”
4’-0"
10”
15”
4’-4"
4’-0"
15”
4’-0"
4’-4"
15”
15”
(MAX)
4’-0"
4’-0"
E
"r"
5 - #9
4 - #9
5 - #8
4 - #8
5 - #9
4 - #9
5 - #7
4 - #7
4 - #8
4 - #7
3 - #8
3 - #7
3 - #7
3 - #6
TABLE OF DIMENSIONS AND REINFORCING BARS
"s"
#9@6
#8@6
#9@6
#7@6
#8@6
#7@6
#8@6
#7@6
#7@6
#6@6
#6@12
#5@12
#6@12
#5@12
#6@12
#5@12
#6@12
#5@12
#6@12
#5@12
"t"
#6@6
#5@6
#6@6
#5@6
#5@6
#4@6
#5@6
#4@6
#4@6
#4@6
"u"
"v"
#8@6
#7@6
#8@6
#6@6
#7@6
#6@6
#5@6
#5@6
#5@6
#4@6
REINFORCING BARS
"w"
#8@6
#7@6
#7@6
#6@6
#7@6
#5@6
#6@6
#5@6
#5@6
#4@6
NOTES:
1. ALL MANHOLES SHALL BE PROVIDED WlTH A STANDARD PULL RlNG IN ACCORDANCE
WlTH S-a-220. THE PULL RlNG SHALL BE LOCATED 6" ABOVE THE SOFFIT ON THE
UPSTREAM SlDE OF THE MANHOLE AND ALONG THE AXIS OF THE DOWNSTREAM
OUTLET. WHERE THE MANHOLE IS TO BE USED AS A DOWNSTREAM SIPHON
MANHOLE, IT SHALL BE PROVIDED WlTH AN ADDITIONAL STANDARD PULL RING, BUT
LOCATED 6" ABOVE THE SOFFIT ON THE DOWNSTREAM SlDE OF THE MANHOLE AND
ON THE CENTERLINE OF THE UPSTREAM SIPHON PIPE.
2. MANHOLE STEPS SHALL BE IN ACCORDANCE WlTH S-a-209 AND SHALL BE
UNIFORMLY SPACED NOT MORE THAN 16" APART. THE TOP STEP SHALL BE PLACED
WITHIN 16" BELOW THE MANHOLE FRAME. THE BOTTOM MANHOLE STEP SHALL BE
PLACED WITHIN 16" ABOVE THE TOP OF THE PIPE. THE MANHOLE STEP SHALL
PROJECT 5". THE MANHOLE STEPS SHALL BE PLACED SUCH THAT THEY ARE
ADJACENT TO BUT NOT INTERFERINGWlTH ACCESS TO THE PULL RING.
3. THE MANHOLE SHALL BE PROVIDED WlTH PLASTIC LlNER WlTH LOCKING
EXTENSIONS. THE PLASTIC LlNER AND THE PLASTIC LlNER INSTALLATION SHALL BE
IN ACCORDANCE WlTH THE STANDARD SPECIFICATIONS. THE LlNER SHALL EXTEND
FROM THE BOTTOM OF THE ADJUSTING RINGS TO A POINT IN THE CHANNEL
MATCHING THE BOTTOM OF THE LlNER IN THE LINED PIPE. LlNER RETURNS SHALL
BE PROVIDED WHERE THE LlNER TERMINATES AT THE ADJUSTING RING. THE JOINT
BETWEEN THE LlNER AND THE STAINLESS STEEL STEPS AND PULL RINGS SHALL BE
THOROUGHLY SEALED WlTH MASTIC SEAM MATERIAL AS MANUFACTURED BY
LINABOND INC., SYLMAR, CALIFORNIA (818) 362-7373, OR EQUAL. APPLICATION OF
SEALANT AND PREPARATION OF SURFACES SHALL BE IN STRICT CONFORMANCE
WlTH THE MANUFACTURER'S DIRECTIONS.
4. UNLESS OTHERWISE SPECIFIED, ALL CONCRETE SHALL BE 660-8-4000 AND ALL
REINFORCING BARS SHALL BE DEFORMED BARS CONFORMING TO ASTM-A706
GRADE 60.
5. A 12" WIDE BY 12" HIGH CONCRETE RlNG SHALL BE PROVIDED AROUND THE
MANHOLE FRAME. IN UNPAVED AREAS, THE CONCRETE RlNG SHALL BE PROVIDED
WlTH #3 REBAR. 30 DIAMETER LAP.
6. EXCEPT AS NOTED HEREON, THE PRECAST UNITS SHALL BE MANUFACTURED AND
TESTED IN ACCORDANCE WlTH ASTM C478. THE CURING OF THE PRECAST UNITS
SHALL CONFORM TO SECTION 207-2.7 OF THE STANDARD SPECIFICATIONS. AS AN
ALTERNATE, THE UNITS MAY BE CURED USING SATURATED STEAM FOR A MINIMUM
OF 12 HOURS FOLLOWED BY 6 DAYS OF WATER CURING OR MEMBRANE CURING. IF
THE UNITS ARE CURED BY THE ALTERNATE METHOD, THEY SHALL NOT BE SHIPPED
PRIOR TO 8 DAYS AFTER CASTING NOR UNTIL THE CONCRETE HAS ATTAINED A
MINIMUM STRENGTH OF 4,000 PSI. THE RISER SECTIONS MAY BE REINFORCED OR
UNREINFORCED. REINFORCED SECTIONS SHALL HAVE A MINIMUM WALL THICKNESS
OF 5" AND UNREINFORCED SECTIONS SHALL HAVE A MINIMUM WALL THICKNESS OF
6". JOINTS SHALL BE TONGUE AND GROOVE AND SHALL BE ASSEMBLED USING
CLASS "B" MORTAR. THE MORTARED JOINTS SHALL BE FLUSH AND TROWELED
SMOOTH.
COUNTY
STEPHEN R. MAGUIN
CHIEF ENGINEER
SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD MANHOLE, TYPE "B"
STANDARD DRAWING
2006 EDITION
S-a-202
SHEET 3 OF 3
PLASTIC LINER WITH
LOCKING EXTENSIONS
(SEE NOTE 3)
CONCRETE RING
3" MAX CLASS
FOR REINF
"B" MORTAR
SEE ROOF PLAN
(SEE NOTE 6)
9" MAX
STD MH FRAME & COVER
6" MIN
(SEE NOTE 5)
GROUND SURFACE
SEE ROOF
ADJUSTING RING(S)
EDGE SEALING
10"
DETAIL ON
PRECAST CONC
SHAFT & PLASTIC
2 1/2"
S-a-206 (TYP)
MH
LINER w/ LOCKING
EXTENSIONS
C
STEP
5"
PULL RING
C
SHELF
3"
(SEE NOTE 1)
VARIABLE
PULL RING
(SEE NOTE 1)
9"
SEE
OUTLET
INLET
VARIABLE
NOTE 8
VA
RIA
B
LE
2" CL
(TYP)
10"
#5@12
#5@12
#5@12
6"
#5@12
48" DIA
6"
SECTION A-A
SECTION B-B
OPTIONAL BASE
D
B
MH STEP
#5
(SEE NOTE 2)
HK
@6
1 - #5 HKD
2"
SHELF
P)
Y
L
48"
(T
A
FLOW
C
A
0"
2’-
A
DI
DIA
1 - #5 HKD
4
-
CL
YP
)
(T
PULL RING
HKD
2"
SHELF
4 - #5@8
8
D
K
@
H
#5
SEE
NOTE 8
(SEE NOTE 1)
#5 CONT
3 - LIFTING EYES @120
B
0
(SEE S-a-230)
PLAN SECTION C-C
ROOF PLAN
FOR 8" TO 30" PIPE
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD MANHOLE, TYPE "C"
S-a-203
SHEET 1 OF 3
NOTES:
1. ALL MANHOLES SHALL BE PROVIDED WlTH A STANDARD PULL RlNG IN ACCORDANCE
WlTH S-a-220. THE PULL RlNG SHALL BE LOCATED 5" ABOVE THE TOP OF THE PlPE
ON THE UPSTREAM SlDE OF THE MANHOLE AND ALONG THE AXIS OF THE
DOWNSTREAM OUTLET. WHERE THE MANHOLE IS TO BE USED AS A DOWNSTREAM
SIPHON MANHOLE, IT SHALL BE PROVIDED WlTH AN ADDITIONAL STANDARD PULL
RING, BUT LOCATED 5" ABOVE THE TOP OF THE PIPE ON THE DOWNSTREAM SlDE OF
THE MANHOLE AND ON THE CENTERLINE OF THE UPSTREAM SIPHON PIPE.
2. MANHOLE STEPS SHALL BE IN ACCORDANCE WlTH S-a-209 AND SHALL BE
UNIFORMLY SPACED NOT MORE THAN 16" APART. THE TOP STEP SHALL BE PLACED
WITHIN 16" BELOW THE MANHOLE FRAME. THE BOTTOM MANHOLE STEP SHALL BE
PLACED WITHIN 16" ABOVE THE SHELF. THE MANHOLE STEP SHALL PROJECT 5".
THE MANHOLE STEPS SHALL BE PLACED SUCH THAT THEY ARE ADJACENT TO BUT
NOT INTERFERING WlTH ACCESS TO THE PULL RING.
3. THE MANHOLE SHALL BE PROVIDED WlTH PLASTIC LINER WlTH LOCKING
EXTENSIONS.
PLASTIC LINER WlTH LOCKING EXTENSIONS SHALL BE IN
ACCORDANCE WlTH THE STANDARD SPECIFICATIONS. THE LINER SHALL EXTEND
FROM THE BOTTOM OF THE ADJUSTING RINGS TO THE TOP OF THE SHELF. LINER
RETURNS SHALL BE PROVIDED WHERE THE LINER TERMINATES AT THE ADJUSTING
RlNG AND THE SHELF. THE JOINT BETWEEN THE LINER AND THE STAINLESS STEEL
STEPS AND PULL RlNG SHALL BE THOROUGHLY SEALED WlTH MASTIC SEAM
MATERIAL AS MANUFACTURED BY LINABOND INC., SYLMAR, CALIFORNIA (818) 3627373, OR EQUAL. APPLICATION OF SEALANT AND PREPARATION OF SURFACES
SHALL BE IN STRICT CONFORMANCE WlTH THE MANUFACTURER'S DIRECTIONS.
4. UNLESS OTHERWISE SPECIFIED, ALL CONCRETE SHALL BE 660-8-4000 ALL
REINFORCING BARS SHALL BE DEFORMED BARS CONFORMING TO ASTM-A706
GRADE 60.
5 . IN PAVED AREAS SUBJECT TO TRAFFIC, A 24" TRAFFIC MANHOLE FRAME AND COVER
IN ACCORDANCE WlTH S-a-228 SHALL BE PROVIDED. IN ALL OTHER AREAS, A 24"
LOCKING MANHOLE FRAME AND COVER IN ACCORDANCE WlTH S-a-207 SHALL BE
PROVIDED.
6. A 12" WIDE BY 12" HIGH CONCRETE RlNG SHALL BE PROVIDED AROUND THE
MANHOLE FRAME. IN UNPAVED AREAS, THE CONCRETE RlNG SHALL BE PROVIDED
WlTH #3 REBAR, 30 DIAMETER LAP.
COUNTY
STEPHEN R. MAGUIN
CHIEF ENGINEER
I
SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD MANHOLE, TYPE "C"
STANDARD DRAWING
2004 EDITION
S-a-203
NOTES:
7. EXCEPT AS NOTED HEREON, THE PRECAST UNITS SHALL BE MANUFACTURED AND
TESTED IN ACCORDANCE WlTH ASTM C478. THE CURING OF THE PRECAST UNITS
SHALL CONFORM TO SECTION 207-2.7 OF THE STANDARD SPECIFICATIONS. AS AN
ALTERNATE, THE UNITS MAY BE CURED USING SATURATED STEAM FOR A MINIMUM
OF 12 HOURS FOLLOWED BY 6 DAYS OF WATER CURING OR MEMBRANE CURING.
IF THE UNITS ARE CURED BY THE ALTERNATE METHOD, THEY SHALL NOT BE
SHIPPED PRIOR TO 8 DAYS AFTER CASTING NOR UNTIL THE CONCRETE HAS
ATTAINED A MINIMUM STRENGTH OF 4,000 PSI. THE RISER SECTIONS MAY BE
REINFORCED OR UNREINFORCED.
REINFORCED SECTIONS, INCLUDING
ECCENTRIC CONES, SHALL HAVE A MINIMUM WALL THICKNESS OF 5" AND
UNREINFORCED SECTIONS, INCLUDING CONES, SHALL HAVE A MINIMUM WALL
THICKNESS OF 6". JOINTS SHALL BE TONGUE AND GROOVE AND SHALL BE
ASSEMBLED USING CLASS "B" MORTAR. THE MORTARED JOINTS SHALL BE FLUSH
AND TROWELED SMOOTH.
8. THE TOP PORTION OF THE PIPES WITHIN THE MANHOLE SHALL BE CUT OUT AS
NECESSARY TO PROVIDE A CIRCULAR OPENING BETWEEN THE PlPE ENDS OF AT
LEAST 42". THE CUT ENDS SHALL BE PLASTERED SMOOTH WlTH CEMENT
MORTAR FOR CONCRETE PlPE AND EPOXY FOR CLAY PIPE. THE CIRCULAR
OPENING SHALL BE CUT PRIOR TO INSTALLATION OF THE RISER SECTIONS.
COUNTY
SANITATION DISTRICTS OF LOS
OFFICE OF CHIEF ENGINEER
ANGELES COUNTY
I
STEPHEN R. MAGUIN
CHIEF ENGINEER
I
I
STANDARD MANHOLE, TYPE "C"
II
STANDARD DRAWING
2006 EDITION
S-a-203
SHEET 3 OF 3
3" MAX CLASS
STD MH FRAME & COVER
ADJUSTING RING
"B" MORTAR
(SEE NOTE 5)
9" MAX
CONCRETE RING
6" MIN
(SEE NOTE 6)
GROUND SURFACE
REDUCER
MAX 21"
24" MAX - 12" MIN
IF DEPTH OF MH
CONE
24" MIN
PLASTIC LINER WITH
MIN
12"
MH STEPS
(SEE NOTE 2)
LOCKING EXTENSIONS
MH STEPS
OR 16"
(SEE NOTE 2)
15"
ECCENTRIC
PERMITS
CONE
30" DIA
24" MIN
RING
ECCENTRIC
24" DIA
24" DIA
48" DIA
48" DIA
ALTERNATE SECTION MAY BE USED IF
SPECIFIED IN BID DOCUMENTS
3"
PULL RING
(SEE NOTE 1)
B
9"
SEE NOTE
OUTLET
3/4 D
INLET
VARIABLE
8
"S" BARS
(SEE NOTE 1)
SH
EL
SHELF
A
#5@12
"R" BARS
PULL RING
F
A
SEE NOTE
10"
8
48"
DIA
#5@12
6"
48" DIA
FLOW
6"
SECTION A-A
SHELF
MH STEP
(SEE NOTE 2)
MH STEP
PRECAST
B
CONC WALL
PULL RING
SHELF
(SEE NOTE 1)
VARIABLE
PLAN
"R" BARS
TABLE OF REINFORCING BARS
VA
RIA
BL
E
PIPE DIA
2"
#5@12
CL
DEPTH
BARS "R"
BARS "S"
UP TO 15’
#5@12
#5@12
16’ TO 30’
#6@12
#6@12
UP TO 15’
#5@12
#5@12
16’ TO 30’
#7@12
#6@12
TO INV
8" TO 21"
24" TO 30"
"S" BARS
#5@12
SECTION B-B
FOR 8" TO 30" PIPE
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD MANHOLE, TYPE "D"
S-a-204
SHEET 1 OF 3
NOTES:
1. ALL MANHOLES SHALL BE PROVIDED WlTH A STANDARD PULL RlNG IN ACCORDANCE
WlTH S-a-220. THE PULL RlNG SHALL BE LOCATED 5" ABOVE THE TOP OF PlPE ON
THE UPSTREAM SlDE OF THE MANHOLE AND ALONG THE AXIS OF THE DOWNSTREAM
OUTLET. WHERE THE MANHOLE IS TO BE USED AS A DOWNSTREAM SIPHON
MANHOLE, IT SHALL BE PROVIDED WlTH AN ADDITIONAL STANDARD PULL RING, BUT
LOCATED 5" ABOVE THE TOP OF PlPE ON THE DOWNSTREAM SlDE OF THE MANHOLE
AND ON THE CENTERLINE OF THE UPSTREAM SIPHON PIPE.
2. MANHOLE STEPS SHALL BE IN ACCORDANCE WlTH S-a-209 AND SHALL BE
UNIFORMLY SPACED NOT MORE THAN 16" APART. THE TOP STEP SHALL BE PLACED
WITHIN 16" BELOW THE MANHOLE FRAME. THE BOTTOM MANHOLE STEP SHALL BE
PLACED WITHIN 16" ABOVE THE SHELF. IN MANHOLE SHAFTS 36" IN DIAMETER AND
LARGER, THE MANHOLE STEP SHALL PROJECT 5". IN MANHOLE SHAFTS SMALLER
THAN 36" IN DIAMETER, THE MANHOLE STEP SHALL PROJECT 4". THE MANHOLE
STEPS SHALL BE PLACED SUCH THAT THEY ARE ADJACENT TO BUT NOT
INTERFERING WlTH ACCESS TO THE PULL RING.
3. THE MANHOLE SHALL BE PROVIDED WlTH PLASTIC LlNER WlTH LOCKING
EXTENSIONS.
PLASTIC LlNER WlTH LOCKING EXTENSIONS SHALL BE IN
ACCORDANCE WlTH THE STANDARD SPECIFICATIONS. THE LlNER SHALL EXTEND
FROM THE BOTTOM OF THE ADJUSTING RINGS TO THE TOP OF THE SHELF. LlNER
RETURNS SHALL BE PROVIDED WHERE THE LlNER TERMINATES AT THE ADJUSTING
RlNG AND THE SHELF. THE JOINT BETWEEN THE LlNER AND THE STAINLESS STEEL
STEPS AND PULL RlNG SHALL BE THOROUGHLY SEALED WlTH MASTIC SEAM
MATERIAL AS MANUFACTURED BY LlNABOND INC., SYLMAR, CALIFORNIA (818) 3627373, OR EQUAL. APPLICATION OF SEALANT AND PREPARATION OF SURFACES
SHALL BE IN STRICT CONFORMANCE WlTH THE MANUFACTURER'S DIRECTIONS.
4. UNLESS OTHERWISE SPECIFIED, ALL CONCRETE SHALL BE 660-8-4000 ALL
REINFORCING BARS SHALL BE DEFORMED BARS CONFORMING TO ASTM-A706
GRADE 60.
5. IN PAVED AREAS SUBJECT TO TRAFFIC, A 24" TRAFFIC MANHOLE FRAME AND COVER
IN ACCORDANCE WlTH S-a-228 SHALL BE PROVIDED. IN ALL OTHER AREAS, A 24"
LOCKING MANHOLE FRAME AND COVER IN ACCORDANCE WlTH S-a-207 SHALL BE
PROVIDED. IF A 30" MANHOLE FRAME AND COVER IS REQUIRED, A FRAME AND
COVER IN ACCORDANCE WlTH S-a-223 SHALL BE PROVIDED AND INSTALLED WHERE
THE REDUCER RlNG IS SHOWN AND THE REDUCER RING, 24" ADJUSTING RINGS, AND
24" FRAME AND COVER SHALL BE OMITTED.
6. A 12" WIDE BY 12" HIGH CONCRETE RlNG SHALL BE PROVIDED AROUND THE
MANHOLE FRAME. IN UNPAVED AREAS, THE CONCRETE RlNG SHALL BE PROVIDED
WlTH #3 REBAR, 30 DIAMETER LAP.
COUNTY
STEPHEN R. MAGUIN
CHIEF ENGINEER
SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD MANHOLE, TYPE "D"
STANDARD DRAWING
20- EDITION
I
S-a-204
SHEET 2 OF 3
NOTES:
7. EXCEPT AS NOTED HEREON, THE PRECAST UNITS SHALL BE MANUFACTURED AND
TESTED IN ACCORDANCE WlTH ASTM C478. THE CURING OF THE PRECAST UNITS
SHALL CONFORM TO SECTION 207-2.7 OF THE STANDARD SPECIFICATIONS. AS AN
ALTERNATE, THE UNITS MAY BE CURED USING SATURATED STEAM FOR A MINIMUM OF
12 HOURS FOLLOWED BY 6 DAYS OF WATER CURING OR MEMBRANE CURING. IF THE
UNITS ARE CURED BY THE ALTERNATE METHOD, THEY SHALL NOT BE SHIPPED PRIOR
TO 8 DAYS AFTER CASTING NOR UNTIL THE CONCRETE HAS ATTAINED A MINIMUM
STRENGTH OF 4,000 PSI.
THE RISER SECTIONS MAY BE REINFORCED OR
UNREINFORCED. REINFORCED SECTIONS, INCLUDING ECCENTRIC CONES, SHALL HAVE
A MINIMUM WALL THICKNESS OF 5" AND UNREINFORCED SECTIONS, INCLUDING CONES,
SHALL HAVE A MINIMUM WALL THICKNESS OF 6". JOINTS SHALL BE TONGUE AND
GROOVE AND SHALL BE ASSEMBLED USING CLASS "B" MORTAR. THE MORTARED
JOINTS SHALL BE FLUSH AND TROWELED SMOOTH.
8. THE TOP PORTION OF THE PIPES WITHIN THE MANHOLE SHALL BE CUT OUT AS
NECESSARY TO PROVIDE A CIRCULAR OPENING BETWEEN THE PlPE ENDS OF AT LEAST
42". THE CUT ENDS SHALL BE PLASTERED SMOOTH WlTH CEMENT MORTAR FOR
CONCRETE PlPE AND EPOXY FOR CLAY PIPE. THE CIRCULAR OPENING SHALL BE CUT
PRIOR TO INSTALLATIONOF THE RISER SECTIONS.
COUNTY
STEPHEN R. MAGUIN
CHIEF ENGINEER
SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD MANHOLE, TYPE "D"
STANDARD DRAWING
ZOO6 EDITION
S-a-204
SHEET 3 OF 3
3" MAX CLASS
STD MH FRAME & COVER
"B" MORTAR
(SEE NOTE 5)
ADJUSTING RING
9" MAX
CONCRETE RING
6" MIN
(SEE NOTE 6)
GROUND SURFACE
REDUCER
RING
24" DIA
24" MAX - 12" MIN
30" DIA
IF DEPTH OF MH
CONE
24" MIN
OR 16"
ECCENTRIC
(TYP)
15"
PERMITS
4"
MH STEPS
(SEE NOTE 2)
PLASTIC LINER WITH
MH STEPS
LOCKING EXTENSIONS
48" DIA
8" MIN
PULL RING
SHELF
(SEE NOTE 1)
3"
PULL RING
(SEE NOTE 1)
SEE NOTE
9
9"
SEE NOTE
2"
VARIABLE
RIA
BL
E
INLET
2/3 D
VA
VARIABLE
8
CL
OUTLET
#5@12
#5@12
(TYP)
6"
48" DIA
6"
3"
#5@12
FOR REINF SEE
CL
10"
#5@12
S-a-204 (TYP)
SECTION B-B
SECTION A-A
PULL RING
B
(SEE NOTE 1)
SEE NOTE 8
MH STEP
(SEE NOTE 2)
A
SHELF
A
DIA
FLOW
SHELF
48"
SEE NOTE 8
MH
OPTIONAL BASE
COVER
LOCATION
B
PLAN
FOR 8" TO 30" PIPE
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD DROP MANHOLE
S-a-205
SHEET 1 OF 4
C
C
ACCESS FRAME
14 1/2"
1/2"
11 3/4"
7/8"
1 1/2"
13 1/2"
1 1/4"
1/2"
2 3/4"
11 1/2"
2 3/4"
5/8"
1/2"
17"
SECTION C-C
12" MIN
12" MIN
THE LETTER "S" SHALL
FINISHED SURFACE
BE RAISED 3/8"
D
11 3/4"
D
12" MIN
18" MAX
3"
s
ACCESS CAP 11" DIA x 1/2"
THICK WITH 3/4" DIA FINGER
HOLE IN CENTER
ACCESS COVER
CONSTRUCTION JOINT
8" VCP RISER
7/8"
13"
3/8"
10"
3 7/8"
1 3/8"
3"
1"
DETAIL
3/8"
10 3/4"
SECTION D-D
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD DROP MANHOLE
S-a-205
SHEET 2 OF 4
NOTES:
1. ALL MANHOLES SHALL BE PROVIDED WlTH A STANDARD PULL RlNG IN ACCORDANCE
WlTH S-a-220. THE PULL RlNG SHALL BE LOCATED 5" ABOVE THE TOP OF PlPE ON THE
UPSTREAM SlDE OF THE MANHOLE AND ALONG THE AXIS OF THE DOWNSTREAM
OUTLET. WHERE THE MANHOLE IS TO BE USED AS A DOWNSTREAM SIPHON MANHOLE,
IT SHALL BE PROVIDED WlTH AN ADDITIONAL STANDARD PULL RING, BUT LOCATED 5"
ABOVE THE TOP OF PlPE ON THE DOWNSTREAM SlDE OF THE MANHOLE AND ON THE
CENTERLINE OF THE UPSTREAM SIPHON PIPE.
2. MANHOLE STEPS SHALL BE IN ACCORDANCE WlTH S-a-209 AND SHALL BE UNIFORMLY
SPACED NOT MORE THAN 16" APART. THE TOP STEP SHALL BE PLACED WITHIN 16"
BELOW THE MANHOLE FRAME. THE BOTTOM MANHOLE STEP SHALL BE PLACED WITHIN
16" ABOVE THE SHELF. IN MANHOLE SHAFTS 36" IN DIAMETER AND LARGER, THE
MANHOLE STEP SHALL PROJECT 5". IN MANHOLE SHAFTS SMALLER THAN 36" IN
DIAMETER, THE MANHOLE STEP SHALL PROJECT 4". THE MANHOLE STEPS SHALL BE
PLACED SUCH THAT THEY ARE ADJACENT TO BUT NOT INTERFERING WlTH ACCESS TO
THE PULL RING.
3. THE MANHOLE SHALL BE PROVIDED WlTH PLASTIC LlNER WlTH LOCKING EXTENSIONS.
PLASTIC LlNER WlTH LOCKING EXTENSIONS SHALL BE IN ACCORDANCE WlTH THE
STANDARD SPECIFICATIONS. THE LlNER SHALL EXTEND FROM THE BOTTOM OF THE
ADJUSTING RINGS TO THE TOP OF THE SHELF. LlNER RETURNS SHALL BE PROVIDED
WHERE THE LlNER TERMINATES AT THE ADJUSTING RlNG AND THE SHELF. THE JOINT
BETWEEN THE LlNER AND THE STAINLESS STEEL STEPS AND PULL RINGS SHALL BE
THOROUGHLY SEALED WlTH MASTIC SEAM MATERIAL AS MANUFACTURED BY LINABOND
INC., SYLMAR, CALIFORNIA (818) 362-7373, OR EQUAL. APPLICATION OF SEALANT AND
PREPARATION OF SURFACES SHALL BE IN STRICT CONFORMANCE WlTH THE
MANUFACTURER'S DIRECTIONS.
4. UNLESS OTHERWISE SPECIFIED, ALL CONCRETE SHALL BE 660-B-4000 AND ALL
REINFORCING BARS SHALL BE DEFORMED BARS CONFORMING TO ASTM-A706
GRADE 60.
5 . IN PAVED AREAS SUBJECT TO TRAFFIC, A 24" TRAFFIC MANHOLE FRAME AND COVER IN
ACCORDANCE WlTH S-a-228 SHALL BE PROVIDED. IN ALL OTHER AREAS, A 24" LOCKING
MANHOLE FRAME AND COVER IN ACCORDANCE WlTH S-a-207 SHALL BE PROVIDED. IF A
30" MANHOLE FRAME AND COVER IS REQUIRED, A FRAME AND COVER IN ACCORDANCE
WlTH S-a-223 SHALL BE PROVIDED AND INSTALLED WHERE THE REDUCER RlNG IS
SHOWN AND THE REDUCER RING, 24" ADJUSTING RINGS, AND 24" FRAME AND COVER
SHALL BE OMITTED.
6. A 12" WIDE BY 12" HIGH CONCRETE RlNG SHALL BE PROVIDED AROUND THE MANHOLE
FRAME. IN UNPAVED AREAS, THE CONCRETE RlNG SHALL BE PROVIDED WlTH #3
REBAR, 30 DIAMETER LAP.
-
COUNTY
STEPHEN R. MAGUIN
CHIEF ENGINEER
I
I
-
- -- -
-
SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWlNG
2000 EDITION
STANDARD DROP MANHOLE
S-a-205
I
SHEET 3 OF 4
NOTES:
7. EXCEPT AS NOTED HEREON, THE PRECAST UNITS SHALL BE MANUFACTURED AND
TESTED IN ACCORDANCE WlTH ASTM C478. THE CURING OF THE PRECAST UNITS
SHALL CONFORM TO SECTION 207-2.7 OF THE STANDARD SPECIFICATIONS. AS AN
ALTERNATE, THE UNITS MAY BE CURED USING SATURATED STEAM FOR A MINIMUM
OF 12 HOURS FOLLOWED BY 6 DAYS OF WATER CURING OR MEMBRANE CURING
IF THE UNITS ARE CURED BY THE ALTERNATE METHOD, THEY SHALL NOT BE
SHIPPED PRIOR TO 8 DAYS AFTER CASTING NOR UNTIL THE CONCRETE HAS
ATTAINED A MINIMUM STRENGTH OF 4,000 PSI. THE RISER SECTIONS MAY BE
REINFORCED OR UNREINFORCED.
REINFORCED SECTIONS, INCLUDING
ECCENTRIC CONES, SHALL HAVE A MINIMUM WALL THICKNESS OF 5" AND
UNREINFORCED SECTIONS, INCLUDING CONES, SHALL HAVE A MINIMUM WALL
THICKNESS OF 6". JOINTS SHALL BE TONGUE AND GROOVE AND SHALL BE
ASSEMBLED USING CLASS "B" MORTAR. THE MORTARED JOINTS SHALL BE FLUSH
AND TROWELED SMOOTH.
8. THE TOP PORTION OF THE PIPES WITHIN THE MANHOLE SHALL BE CUT OUT AS
NECESSARY TO PROVIDE A CIRCULAR OPENING BETWEEN THE PlPE ENDS OF AT
LEAST 42". THE CUT ENDS SHALL BE PLASTERED SMOOTH WlTH CEMENT MORTAR
FOR CONCRETE PlPE AND EPOXY FOR CLAY PIPE. THE CIRCULAR OPENING SHALL
BE CUT PRIOR TO INSTALLATION OF THE RISER SECTIONS.
9. THE DROP CONNECTION INTO THE MANHOLE SHALL BE VCP AND SHALL BE THE
SAME SIZE AS THE LATERAL SEWER OR A MINIMUM OF 8" IN DIAMETER,
WHICHEVER IS LARGER. THE RISER SHALL BE 8" VCP.
COUNTY
STEPHEN R. MAGUIN
CHIEF ENGINEER
I
1
SANITATION DISTRICTS OF LOS
OFFICE OF CHIEF ENGINEER
ANGELES COUNTY
STANDARD DROP MANHOLE
II
STANDARD DRAWING
2006 EDITION
S-a-205
SHEET 4 OF 4
& COVER
SURFACE
(SEE NOTE 5)
6" MIN
(SEE NOTE 5)
GROUND
9" MAX
"B" MORTAR
STD MH FRAME
6" MIN
& COVER
9" MAX
STD MH FRAME
3" MAX CLASS
CONCRETE RING
MH
PLASTIC LINER WITH
STEPS
LOCKING EXTENSIONS
VARIES
MH STEP
(SEE NOTE 2)
A
SEE ROOF EDGE
VARIES
DEPTH TO INVERT
A
SEALING DETAIL
ON SHT 2 (TYP)
36" DIA
PULL RING
A
(SEE NOTE 1)
#5@12
" U " BARS
(TYP)
(TYP)
OUTLET
PRECAST CONC SHAFT w/
MIN
6’-6"
DEPTH TO INVERT
A
ADJ RINGS
REQ’D
CONE AS
24" MIN
ECCENTRIC
(SEE NOTE 6)
3"
PLASTIC LINER PLATE
3"
(SEE NOTE 7)
" V " BARS
A
3"
FLOW
B
t
A
INLET
PULL RING
(SEE NOTE 1)
9"
(TYP)
2" CL
SEE NOTE 10
" U " BARS
(TYP)
(TYP)
t
INLET
3"
t
(TYP)
OUTLET
#5@12
ID OF SHAFT
CL
3"
2 - #5@12
#5@12
" V " BARS
SECTION B-B
3"
LOWER LIMIT
(TYP)
OF LINER PLATE (TYP)
CASE II
FLOW
t
ID + 2 t
B
SEE NOTE 7
" r " BARS HKD
t
A
ID OF SHAFT
3"
t
CL
" s " BARS HKD
#5@12
SECTION B-B
2-#5@12
C
PLASTIC LINER
2"
PLASTIC LINER PLATE
CL
(TYP)
CASE I
" r " BARS HKD
PLATE
#5 CONT
KD
S H
"s"
BAR
SHELF
B
B
MH STEP
(SEE NOTE 2)
36"
OR
24"
H
M
DIA
G
NIN
OPE
FLOW
SHELF
9"
BAR
(SEE NOTE 1)
"s"
PULL RING
(TYP)
96" MH SHAFT
SEE NOTE 10
(SEE NOTE 9)
(TYP)
C
PLAN - SECTION A-A
3 - LIFTING EYES @120
o
60", 72", 84" OR
S H
KD
2 - #4
(SEE S-a-230)
DETAIL OF FLAT SLAB TOP
24" OR 36" x 60", 72", 84" OR 96"
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD MANHOLE, TYPE "E"
S-a-206
SHEET 1 OF 4
PRECAST
PIPE SHAFT
MH STEP
PLASTIC LINER WITH
(SEE NOTE 2)
LOCKING EXTENSIONS
PULL RING
(SEE NOTE 1)
q
PROVIDE PLASTIC LINER PLATE WHEN
ADJ PIPE IS PVC T-LOCK LINED RGRCP,
VARIES
OTHERWISE LINE TO TOP OF SHELF
ID
OF
#5@ TOP
CA
RR
IER
" U " BARS
PIP
_ 8"
#5@12 TYPICAL EA SIDE, WHEN q >
E
2" CL
B+t
" V " BARS
PRECAST CONCRETE
COVER
#5@12
2 - #5@12 @ENDS
MATCH EXIST
3/4" CHAMFER ALL
ADJ PIPE,
AROUND EXTERIOR
90 0 MAX
TOP EDGES
4’
I.D. + 2 t +
SECTION C-C
BEARING PAD SHALL
BE 1" THICK NEOPRENE
PLASTIC LINER PLATE
PAD TYPE 2, GRADE 2C1,
PER ASTM D1056-00 AS
PLASTIC LINER WITH
MANUFACTURED BY
LOCKING EXTENSIONS
RUBATEX OR EQUAL
PRECAST
CONC WALL
ROOF EDGE SEALING DETAIL
TABLE OF REINFORCING BARS
SHAFT DIA
DEPTH
REINFORCING BARS
DIMENSIONS
TO INV
A
B
"r"
"s"
"u"
"v"
UP TO 15’
10"
8"
#6@6
#6@6
#5@12
#5@12
60"
16’ TO 30’
12"
10"
#7@6
#7@6
#6@10
#6@12
UP TO 15’
10"
8"
#6@6
#6@6
#5@12
#5@12
16’ TO 30’
12"
10"
#8@6
#8@6
#7@12
#7@12
UP TO 15’
10"
10"
#7@6
#7@6
#5@12
#5@12
16’ TO 30’
14"
10"
#8@6
#8@6
#7@12
#8@12
UP TO 15’
12"
10"
#7@6
#7@6
#6@12
#6@12
16’ TO 30’
15"
12"
#8@6
#8@6
#7@6
#8@12
72"
84"
96"
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD MANHOLE, TYPE "E"
S-a-206
SHEET 2 OF 4
NOTES:
1. ALL MANHOLES SHALL BE PROVIDED WlTH A STANDARD PULL RlNG IN ACCORDANCE
WlTH S-a-220. THE PULL RlNG SHALL BE LOCATED 5" ABOVE THE TOP OF PlPE ON THE
UPSTREAM SlDE OF THE MANHOLE AND ALONG THE AXIS OF THE DOWNSTREAM
OUTLET. WHERE THE MANHOLE IS TO BE USED AS A DOWNSTREAM SIPHON
MANHOLE, IT SHALL BE PROVIDED WlTH AN ADDITIONAL STANDARD PULL RING, BUT
LOCATED 5" ABOVE THE TOP OF PlPE ON THE DOWNSTREAM SlDE OF THE MANHOLE
AND ON THE CENTERLINE OF THE UPSTREAM SIPHON PIPE.
2. MANHOLE STEPS SHALL BE IN ACCORDANCE WlTH S-a-209 AND SHALL BE UNIFORMLY
SPACED NOT MORE THAN 16" APART. THE TOP STEP SHALL BE PLACED WITHIN 16"
BELOW THE MANHOLE FRAME. THE BOTTOM MANHOLE STEP SHALL BE PLACED
WITHIN 16" ABOVE THE SHELF. IN MANHOLE SHAFTS 36" IN DIAMETER AND LARGER,
THE MANHOLE STEP SHALL PROJECT 5". IN MANHOLE SHAFTS SMALLER THAN 36" IN
DIAMETER, THE MANHOLE STEP SHALL PROJECT 4". THE MANHOLE STEPS SHALL BE
PLACED SUCH THAT THEY ARE ADJACENT TO BUT NOT INTERFERINGWlTH ACCESS TO
THE PULL RING.
3. THE MANHOLE SHALL BE PROVIDED WlTH PLASTIC LlNER WlTH LOCKING EXTENSIONS.
PLASTIC LlNER WlTH LOCKING EXTENSIONS SHALL BE IN ACCORDANCE WlTH THE
STANDARD SPECIFICATIONS. THE LlNER SHALL EXTEND FROM THE BOTTOM OF THE
ADJUSTING RINGS TO THE TOP OF THE SHELF UNLESS THE ADJACENT PlPE IS LINED.
IF THE ADJACENT PlPE IS LINED, THE LlNER SHALL EXTEND TO A POINT IN THE
CHANNEL MATCHING THE BOTTOM OF THE LlNER IN THE LINED PIPE. LlNER RETURNS
SHALL BE PROVIDED WHERE THE LlNER TERMINATES AT THE ADJUSTING RlNG AND
THE SHELF. THE JOINT BETWEEN THE LlNER AND THE STAINLESS STEEL STEPS AND
PULL RINGS SHALL BE THOROUGHLY SEALED WlTH MASTIC SEAM MATERIAL AS
MANUFACTURED BY LINABOND INC., SYLMAR, CALIFORNIA (818) 362-7373, OR EQUAL.
APPLICATION OF SEALANT AND PREPARATION OF SURFACES SHALL BE IN STRICT
CONFORMANCE WlTH THE MANUFACTURER'S DIRECTIONS.
4. UNLESS OTHERWISE SPECIFIED, ALL CONCRETE SHALL BE 660-B-4000 AND ALL
REINFORCING BARS SHALL BE DEFORMED BARS CONFORMING TO ASTM-A706
GRADE 60.
5 . IN PAVED AREAS SUBJECT TO TRAFFIC, A 24" TRAFFIC MANHOLE FRAME AND COVER IN
ACCORDANCE WlTH S-a-228 SHALL BE PROVIDED. IN ALL OTHER AREAS, A 24"
LOCKING MANHOLE FRAME AND COVER IN ACCORDANCE WlTH S-a-207 SHALL BE
PROVIDED. IF A 36" MANHOLE FRAME WlTH 30" COVER IS REQUIRED, A FRAME AND
COVER IN ACCORDANCE WlTH S-a-226 SHALL BE PROVIDED.
6. A 12" WIDE BY 12" HIGH CONCRETE RlNG SHALL BE PROVIDED AROUND THE MANHOLE
FRAME. IN UNPAVED AREAS, THE CONCRETE RlNG SHALL BE PROVIDED WlTH #3
REBAR, 30 DIAMETER LAP.
COUNTY
STEPHEN R. MAGUIN
CHIEF ENGINEER
SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD MANHOLE, TYPE "EM
STANDARD DRAWING
2006 EDITION
S-a-206
SHEET 3 OF 4
NOTES:
EXCEPT AS NOTED HEREON, THE PRECAST UNITS SHALL BE MANUFACTURED
AND TESTED IN ACCORDANCE WlTH ASTM C478. THE CURING OF THE PRECAST
UNITS SHALL CONFORM TO SECTION 207-2.7 OF THE STANDARD SPECIFICATIONS.
AS AN ALTERNATE, THE UNITS MAY BE CURED USING SATURATED STEAM FOR A
MINIMUM OF 12 HOURS FOLLOWED BY 6 DAYS OF WATER CURING OR MEMBRANE
CURING IF THE UNITS ARE CURED BY THE ALTERNATE METHOD, THEY SHALL
NOT BE SHIPPED PRIOR TO 8 DAYS AFTER CASTING NOR UNTIL THE CONCRETE
HAS ATTAINED A MINIMUM STRENGTH OF 4,000 PSI. THE RISER SECTIONS MAY BE
REINFORCED OR UNREINFORCED.
REINFORCED SECTIONS, INCLUDING
ECCENTRIC CONES, SHALL HAVE A MINIMUM WALL THICKNESS OF 5" AND
UNREINFORCED SECTIONS, INCLUDING CONES, SHALL HAVE A MINIMUM WALL
THICKNESS OF 6". JOINTS SHALL BE TONGUE AND GROOVE AND SHALL BE
ASSEMBLED USING CLASS "B" MORTAR. THE MORTARED JOINTS SHALL BE
FLUSH AND TROWELED SMOOTH.
UNLESS OTHERWISE INDICATED ON THE DRAWINGS, CASE I OR II MAY BE USED
BY THE CONTRACTOR AT HIS OPTION CONSISTENT WlTH DIAMETER COVER
LIMITATIONS INDICATED HEREON.
CASE I SHALL NOT BE USED FOR COVER ON PlPE LESS THAN 12'
CASE II SHALL NOT BE USED FOR COVER ON PlPE MORE THAN 12'.
RISER SECTIONS 6 0 THROUGH 96" I.D. SHALL BE REINFORCED IN ACCORDANCE
WlTH ASTM C 478 AND SHALL HAVE THE FOLLOWING MINIMUM WALL
THICKNESS (t).
6 0 I.D. - 5";72" I.D. - 6"; 84" I.D. - 7"; 96" I.D. - 8"
THE TOP PORTION OF THE PIPES WITHIN THE MANHOLE SHALL BE CUT OUT AS
NECESSARY TO PROVIDE A CIRCULAR OPENING BETWEEN THE PlPE ENDS OF AT
LEAST 54" IN THE 60" DIAMETER MANHOLE AND 66" IN THE 72" DIAMETER
MANHOLE, 78" IN THE 84" DIAMETER MANHOLE AND 90" IN THE 96" DIAMETER
MANHOLE. THE CUT ENDS SHALL BE PLASTERED SMOOTH WlTH CEMENT
MORTAR FOR CONCRETE PlPE AND EPOXY FOR CLAY PIPE. THE CIRCULAR
OPENING SHALL BE CUT PRIOR TO INSTALLATION OF THE RISER SECTIONS.
COUNTY
STEPHEN R. MAGUIN
CHIEF ENGINEER
SANITATION
I
I
DISTRICTS OF LOS
OF CHIEF ENGINEER
A N G E L E S COUNTYOFFICE
STANDARD MANHOLE, TYPE "E"
I
1
STANDARD DRAWING
2006 EDITKIN
S-a-206
SHEET 4 OF 4
1/
4"
P)
2"
Y
(T
(TYP)
6 - 1/2" RIBS
1/
SEE DETAIL
OF NOTCHES
3/
4"
2"
1/
P)
Y
(T
1/8"
1
"A"
C
L SLOT
3/4"
1
3/8"
A
31
A
B
9/1
6
B
C
"
3"
6"
3"
7 1/2
28
15
C
71
/2
LOCKING GUIDE
(TYP)
60
3"
25 1/4" DIA
"A"
C
L SLOT
SLOT "A"
1 1/4"
22 1/2" DIA
1 1/2"
PLAN OF COVER
TOP VIEW
R=1/8" (TYP)
PLAN OF FRAME
7/8"
25 1/4" DIA
3/4"
25 1/2" DIA
2 5/8"
3/4" DIA
1 1/2"
9/16"
1/8"
1/8"
1 3/4"
7/32"
29/32"
2 3/16"
3 5/16"
1 1/8"
1 1/2"
3/4"
R=1/8"
4 1/8"
HOLE
4"
3 PLCS
VARIABLE
SECTION A-A
3 7/8"
24"
31 3/4"
SECTION B-B
END VIEW
60
3 7/8"
3/4"
23 3/4"
1 11/32"
1 9/32"
1 5/16"
1 3/16"
(TYP)
1 5/32"
6"
8"
"
4 1/8"
1"
2 1/2"
5/8"
1"
5/8"
SIDE VIEW C-C
1 1/2"
LOCKING GUIDE
3/4"
7/
2"
3/16"
16
1/
30
3/
5"
3/4"
1 3/4"
1/8"
"
/8
63
9"
(TY
P)
1/2"
30
73
/8
"
60
1 1/2"
COVER LUG
DETAIL OF NOTCHES
1" HOLE
20 3/4"
(TYP)
NOTES:
21 1/8"
1.
CAST IRON USED SHALL CONFORM WITH ASTM A-48 CLASS 35B.
22 1/8"
2.
FRAME AND COVER SHALL BE COATED WITH ASPHALTUM OR
BITUMINOUS PAINT AFTER TESTING AND INSPECTION.
22 1/2"
25 1/4" DIA
PLAN OF COVER
3.
FRAME AND COVER SHALL BE TESTED FOR ACCURATE FIT PRIOR
TO DELIVERY AND SHALL BE MARKED IN SETS.
4.
ALL CASTINGS SHALL COMPLY
WITH SECTION 206-3 OF THE
STANDARD SPECIFICATIONS.
BOTTOM VIEW
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
STANDARD 24" LOCKING MANHOLE
CHIEF ENGINEER
FRAME AND COVER
2006 EDITION
S-a-207
SHEET 1 OF 1
28 15/16"
27 3/16"
27 1/16"
1 13/32"
1 3/4"
1 3/4"
3 1/4"
NOTE:
COVER SHALL BE SNUG FIT, NOT TIGHT
5/8" DIA x 10" LG
SS ANCHOR BOLT
"
7"
OR CONC) ON
5 /16" x 24 1/2"
FLAT SLAB
TYPE 316 SS PLATE
2
1/
6"
MH WALL (BRICK
1"
7/8"
w/ HH NUT TYPE 316
SS TYPE 316 (2 REQUIRED)
TOP
22 1/2"
24"
31 3/4"
APPLY ANTI-FREEZE
CASTING TO BE SET
SECTION
AGENT (TYP)
IN WET MORTAR
2 3/32"
MANHOLE FRAME AND COVER
1 7/32"
1 1/2"
3/8"
1/16"
1 3/4"
3 3/8"
1/8"
1/4"
5/32"
1 5/8"
1"
11/16"
3/16"
1 1/2"
15
R
R = 1/4"
DIA
"
R
3/8" x 1" TYPE 316
1 3/4"
=1
24 3/4’’
"
1/2
11/16"
SS CAP SCREW
(12 REQUIRED)
3 1/8"
6"
15
/2
=1
7/8"
USS STD THD
7/8"
1/2’’ DIA
HOLE (TYP)
3/4"
24
1/2"
1"
IA
1/
SECTION B-B
1 1/8"
SS PLATE
"
/2
3
1
2
IA
3 1/2"
5/16’’ TYPE 316
NEOPRENE GASKET
10"
D
1 1/4"
1 1/8’’ WIDE BY 1/8"
1/2"
3/4"
2"
D
4 5/8"
27 1/16"
SECTION A-A
PRESSURE PLATE
1’’ DIA HOLE
2 PLCS
3/4’’ DIA
HOLE (TYP)
7"
A
DI
9
C
S D
E
W E
"
3/4
R
A
23
11
/2"
IA
D
4"
1/
IA
B
B
S
1
/2
71
4"
1/
D
29
R
2"
1/
A
1
2"
1/
DRILL &
TAP 3/8’’
7
1/
2
1
30
5
PRY NOTCH
PLAN OF COVER
PLAN OF COVER
PLAN OF FRAME
BOTTOM VIEW
TOP VIEW
NOTE:
FOR NOTES SEE S-a-207.
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
STANDARD 24" PRESSURE MANHOLE
CHIEF ENGINEER
FRAME AND COVER
2006 EDITION
S-a-208
SHEET 1 OF 1
CONC WALL
CONC WALL
OR MH RISER
OR MH RISER
3/4" DIA SS BAR TYPE
316 CAST-IN-PLACE
PLASTIC LINER
WITH
LOCKING EXTENSIONS
A
1 1/2"
C
L
A
C
L
C
L
2 1/2"
1’-2"
C
L
4" OR 5"
AS REQ’D
C
L
4" OR 5"
AS REQ’D
8" FOR PRECAST SECTIONS
13" FOR CAST-IN-PLACE
C
L
PLAN
SECTION A-A
TYPE I MANHOLE STEP
CONC WALL
CONC WALL
3/4" DIA SS BAR
TYPE 316
PLASTIC LINER
WITH
LOCKING EXTENSIONS
C
L
B
B
C
L
2 1/2"
1’-2"
C
L
THREADED BARS IN
DRILLED HOLES AND
EPOXY GROUT (TYP)
4" OR 5"
AS REQ’D
C
L
4" OR 5"
AS REQ’D
13"
C
L
PLAN
SECTION B-B
TYPE I I MANHOLE STEP
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD MANHOLE STEP
S-a-209
SHEET 1 OF 1
TRAP CASTING
SHELF
C
1/2" MORTAR
B
SEWAGE LEVEL IN TRAP
BASE WHEN NO SEWAGE
INLET
C
/
2
WATER SEAL
TRAP AND
/2
MANHOLE
C
CHANNEL BASE
9"
INCREASER
BASE
B
VARIABLE
A
A
D
SECTION A-A
OUTLET
C
INCREASER
VARIABLE
9"
CAULK WITH CEMENT MORTAR
TRAP
TRAP CASTING
SHELF
LEVEL
1"
CASTING
POINT WITH MORTAR
OUTLET
A
2" MIN
IS FLOWING
VARIABLE
NORMAL CHANNEL
BASE
B
PLAN - SINGLE TRAP BASE
A
660-B-4000
INLET
VARIABLE
9"
CHANNEL BASE
T
1
1:
TRAP AND
OUTLET
1:
1
VARIABLE
THE ENGINEER
1/2"
AS APPROVED BY
C
/
2
OR OFFSET OUTLET
C
/
2
B
420-C-2000
SECTION B-B
TABLE OF DIMENSIONS
DIA OF MANHOLE BASE (D)
INLET
INLET
TRAP
TRAP
DIA
INCREASER
SIZE
PER
VARIABLE
OUTLET DIAMETER
8"
10"
12"
4’
4’
4’
4’
4’
INLET
INCREASER
8" x 10"
10"
S-a-211
10"
10" x 12"
12"
S-a-211
C
/2
MANHOLE
8"
( FOR 12" INLETS AND LARGER SEE CONSTRUCTION DRAWINGS )
INCREASER
TRAP BASE DIMENSIONS
9"
A
A
A
TRAP CASTING
OUTLET
/2
VARIABLE
C
INLET
VARIABLE
D
A
B
C
10"
7 1/2"
14 1/2"
13"
28 1/2"
9"
12"
8 1/2"
16 1/2"
15"
32 1/2"
10"
A+B+
/2
T MIN
NOTES:
1.
WHERE A TRAP IS NECESSARY IN AN EXISTING STRUCTURE,
BREAK OUT CONCRETE AND CONSTRUCT NEW BASE.
2.
PLAN - DOUBLE TRAP BASE
C
TRAP DIA
FOR GENERAL NOTES AND CONSTRUCTION DETAILS OF
BRICKWORK, SEE S-a-201.
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD TRAP MANHOLE BASE
S-a-210
SHEET 1 OF 1
DIMENSIONS OF CASTINGS
1 3/8"
INLET DIA
A
B
R
L
10"
6"
9"
11"
14 3/4"
12"
7"
11"
13"
17 3/4"
7/16" x 3/4"
7/8"
MACHINED SLOT
7/8" R
1" R
1/
60
3/4"
1.
CAST IRON USED SHALL CONFORM WITH ASTM A-48 CLASS 35B.
2.
FLANGES OF CASTING SHALL BE MACHINED FACED.
3.
CASTINGS SHALL BE DIPPED TWICE IN HOT ASPHALT PAINT.
4.
RUBBER GASKET SHALL BE NEOPRENE 35-50 SHORE.
2 3/4"
1 7/8"
7/16" HOLE
NOTES:
3/4"
o
R
1 7/8"
4"
1"
1/2"
1 1/2"
2"
DETAIL "A"
SEE DETAIL "A"
DETAIL "B"
SEE DETAIL "B"
1/4
"
1/8"
1/4"
3/4"
A
2"
2"
"
2"
1
4
1/
R
B
1/8"
2"
1" BRASS FACING
1 1/2" DIA
BRAZED & MACHINE
FINISHED
o
85
o
2"
65
R
1" R
1/4" x 1/2" RUBBER GASKET
1"
SEE DETAIL "C"
1/2"
L
SECTIONAL VIEW
3/8
"
1/4" x 1/4" GROOVE
1/4" x 1/2"
IN FLANGE FACE
RUBBER
OF ELBOW
BRASS COTTER PIN
GASKET
3/4"
4 3/8"
DETAIL "C"
1’ BRASS WASHER
3/4"
3/4"
BRASS ROD
2 5/8"
3/8" x 6 3/4"
3/4"
1’ BRASS WASHER
3/4"
3/8"
BRASS COTTER PIN
PLAN VIEW
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD TRAP CASTING
S-a-211
SHEET 1 OF 1
O
D
IN
O
6"
IN
M
PERMISSIBLE EXCAVATION
LINE
M
PERMISSIBLE EXCAVATION
LINE
CRADLE TYPE 1
6" MIN
D
O
6"
6"
6" MIN
1/4 OD
M
D
1/4 OD
6"
6" MIN
MIN
6" MIN
IN
PERMISSIBLE EXCAVATION
LINE
CRADLE TYPE 2
ENCASEMENT TYPE 1
6" MIN
6" MIN
6" MIN
6" MIN
6" MIN
D
D
6"
OPTIONAL CONST JOINT
6" MIN
6" MIN
2"
6" MIN
1/4 OD
2"
6"
O
3/4 OD
O
1/4 OD
D
1/4 OD
O
OPTIONAL CONST JOINT
CRADLE TYPE 1A
CRADLE TYPE 2A
ENCASEMENT TYPE 1A
NOTES:
1. ALL CONCRETE FOR CRADLES TYPE 1 AND 2 AND ENCASEMENT TYPE 1 SHALL BE 420-C-2000. ALL CONCRETE FOR
CRADLES TYPE 1A AND 2A AND ENCASEMENT TYPE 1A SHALL BE 660-B-4000. USE IS LIMITED TO BEDDING CONCRETE
OVER WHICH BACKFILL WILL BE PLACED NOT LESS THAN 40 HOURS AFTER PLACEMENT. FOR BACKFILL AFTER 24 HOURS,
ADD A NON-CHLORIDE ACCELERATING ADMIXTURE APPROVED BY THE ENGINEER AT DOSEAGES AS REQUIRED BY THE
MANUFACTURER OF THE ADMIXTURE. FOR BACKFILL AFTER 16 HOURS AND REMOVAL OF SHEETING AFTER 18 HOURS,
USE 660-C-4000 WITH A NON-CHLORIDE ACCELERATING ADMIXTURE APPROVED BY THE ENGINEER AT DOSAGES AS
REQUIRED BY THE MANUFACTURER OF THE ADMIXTURE.
2. THE CONCRETE FOR CRADLES TYPE 1 AND 2 AND ENCASEMENT TYPE 1 SHALL NOT BE POURED AGAINST TRENCH
SHEETING, FORMS, OR ON LOOSE MATERIAL IN THE TRENCH BOTTOM, BUT SHALL BE POURED AGAINST AND ON THE
UNDISTURBED TRENCH WALLS AND BOTTOM.
3. THE CONCRETE FOR CRADLES TYPE 1A AND 2A AND ENCASEMENT TYPE 1A MAY BE POURED AGAINST TRENCH SHEETING,
FORMS, OR AGAINST THE TRENCH WALLS, BUT SHALL NOT BE POURED ON LOOSE MATERIAL IN THE TRENCH BOTTOM.
4. UNLESS OTHERWISE PROVIDED IN THE SPECIFICATIONS OR AUTHORIZED BY THE ENGINEER, WHEN THE MAXIMUM
ALLOWABLE TRENCH WIDTH HAS BEEN EXCEEDED.
THE PIPE SHALL BE CRADLED WITH TYPE 1 OR TYPE 2 IF THE
TRENCH IS IN UNDISTURBED SOIL OR TYPE 1A OR TYPE 2A IF THE TRENCH IS IN UNSTABLE SOIL. IF THE TRENCH
WIDTH IS LESS THAN ONE AND ONE HALF TIMES THE MAXIMUM ALLOWED BY THE SPECIFICATIONS WITHOUT SPECIAL
BEDDING, OR IF THE COVER ON THE PIPE IS LESS THAN TEN FEET. CRADLE TYPE 1 OR 1A SHALL BE USED. IF THE
TRENCH WIDTH IS MORE THAN ONE AND ONE HALF TIMES THE MAXIMUM ALLOWED BY THE SPECIFICATIONS WITHOUT
SPECIAL BEDDING AND THE COVER IS TEN FEET OR MORE, CRADLE TYPE 2 OR 2A SHALL BE USED.
5. UNLESS OTHERWISE AUTHORIZED BY THE ENGINEER, ALL CRADLES AND ENCASEMENTS SHALL BE PLACED SUCH THAT
BOTH ENDS TERMINATE WITHIN 18 INCHES OF A FLEXIBLE JOINT.
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
STANDARD CONCRETE CRADLES
AND ENCASEMENTS
2006 EDITION
S-a-212
SHEET 1 OF 1
A
2"
6"
1’-4"
4"
3"
V
A
R
IA
B
LE
4"
4"
420-C-2000
MAIN SEWER PIPE
A
PLAN
SECTION A-A
3"
1’-4"
MAIN SEWER PIPE
ELEVATION
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD "T" FOUNDATION
S-a-213
SHEET 1 OF 1
NOTES:
6"
1.
A
THE UPPER END OF THE CHIMNEY PIPE SHALL
BE 8 FEET BELOW THE GRADE OF THE LOWER
6"
12"
CURB, UNLESS OTHERWISE SPECIFIED.
2.
WHERE ONE OR TWO HOUSE CONNECTIONS ARE
TO BE JOINED TO THE CHIMNEY PIPE, USE A
SINGLE "Y" BRANCH.
WHERE THREE HOUSE
CONNECTIONS ARE TO BE JOINED USE A DOUBLE
CEMENT
"Y" BRANCH.
MORTAR
3.
WHERE THE CHIMNEY PIPE IS TO BE USED FOR
A SINGLE HOUSE CONNECTION, FACE THE "Y"
TOWARDS THE PROPERTY TO BE SERVED; WHERE
USED FOR HOUSE CONNECTIONS ON BOTH SIDES
OF THE SEWER, THE "Y" SHALL FACE TOWARD
THE RIGHT (LOOKING UP GRADE) AND THE HOUSE
ON THAT SIDE SHALL BE CONNECTED TO THE "Y"
BRANCH BY A 6 INCH ONE-EIGHTH BEND AND THE
HOUSE CONNECTION ON THE LEFT SIDE SHALL BE
1’-4"
1’-4"
CONNECTED TO THE UPPER END OF THE CHIMNEY
BY A 6 INCH ONE-QUARTER BEND UNLESS OTHERWISE SPECIFIED.
4.
THE MAIN SEWER PIPE SHALL BE OF THE MATERIAL
SHOWN ON THE PLANS.
6" VCP
B
2"
B
420-C-2000
3"
3"
V
A
R
IA
B
LE
4"
MAIN SEWER PIPE
SECTION A-A
A
ELEVATION
4"
4"
1’-4"
MAIN SEWER PIPE
PLAN-SECTION B-B
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD CHIMNEY PIPE
S-a-214
SHEET 1 OF 1
LIFTING EAR &
RIB 8 PLCS
1 1/4" DIA
SEE DETAIL
HOLE 8
PLCS
A
A
B
45
0
B
IB
R
S
C
8"
L
7/
P
8
30 0
PRY NOTCH
PLAN OF COVER
TOP VIEW
8
40 1/2"
PLAN OF FRAME
5/16"
20
PRY
1"
3 1/8"
(TYP)
DIA
1 1/4"
GROOVE (TYP)
42 1/4"
1"
39"
1"
3/4"
4"
3/4"
3/4"
37"
1 1/2"
6"
20"
1 1/4"
5"
1/2"
8
2 1/2"
3 1/4"
5/8"
3"
1 1/4"
2 1/2"
40 3/4"
NOTCH
36" CLEAR
SECTION A-A
4"
44"
SECTION B-B
1 1/4"
30
1 1/2"
1" DIA HOLE
2 PLCS
1 1/4" HOLE
8 PLCS
"
/2
11
R =
PRY
2 1/2"
1" (TYP)
5/8" (TYP)
NOTCH
DETAIL
13
1/4
"
LIFTING EAR & RIB
R
45
NOTES:
1.
CAST IRON USED SHALL CONFORM WITH ASTM A-48 CLASS 35B.
2.
FRAME AND COVER SHALL BE COATED WITH ASPHALTUM OR
BITUMINOUS PAINT AFTER TESTING AND INSPECTION.
2
22
1/
3.
PRIOR TO DELIVERY AND SHALL BE MARKED IN SETS.
4.
PLAN OF COVER
FRAME AND COVER SHALL BE TESTED FOR ACCURATE FIT
ALL CASTINGS SHALL COMPLY
WITH SECTION 206-3 OF THE
STANDARD SPECIFICATIONS.
BOTTOM VIEW
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
STANDARD 36" MANHOLE FRAME
CHIEF ENGINEER
AND COVER
2006 EDITION
S-a-215
SHEET 1 OF 1
PLUG
SEWER LATERAL
FROM HOUSE
4" MIN
FLOW
1"
5" MIN
MIN
FLOW
STD 4" SPIGOT END
HAND-HOLE TRAP
NOTES:
1. GAS TRAP SHALL BE INSERTED AT THE POINT OR POINTS
OF CONNECTION TO THE HOUSE PLUMBING TWO (2) FEET
OUTSIDE THE BUILDING AT PROPERTY OWNER’S EXPENSE.
2. SPIGOT END HAND-HOLE TRAPS OF CAST IRON SOIL PIPE
MAY BE USED IN LIEU OF VITRIFIED CLAY PIPE FITTINGS.
3. GAS TRAP MADE OF OTHER MATERIALS MAY BE SUBMITTED
FOR APPROVAL.
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD HOUSE CONNECTION GAS TRAP
S-a-216
SHEET 1 OF 1
PIPE
OD
6
OD
MIN
A
APPLY 1 COAT ASPHALT
CONCRETE
CONCRETE
SUPPORT
SUPPORT
PROPOSED
PROPOSED
SEWER
SEWER
EMULSION OR APPROVED
EQUAL TO PREVENT
BONDING.
6" DIA
HOLES
OD MIN
A
ELEVATION
SECTION A-A
NOTES:
1.
CONCRETE SUPPORT SHALL BE POURED AGAINST UNDISTURBED SOIL ON THE BOTTOM AND
SHALL EXTEND THE FULL WIDTH OF EXCAVATION.
2.
CONCRETE SHALL BE 420-C-2000. WHEN APPROVED BY THE ENGINEER, THE CONTRACTOR
MAY SUBSTITUTE CONCRETE WITH 2-SACK CEMENT SAND SLURRY.
3.
CONTRACTOR SHALL OBTAIN APPROVAL FROM THE ENGINEER OF HIS PROPOSED METHOD OF
SUPPORTING THE EXISTING PIPE LINES DURING CONSTRUCTION.
4.
CONTRACTOR SHALL PROVIDE
CONCRETE PIPE SUPPORT UNDER ALL EXISTING CONCRETE,
ASBESTOS CEMENT, CLAY, TELEPHONE AND POWER CONDUITS AND UNDER ALL OTHER
CONDUITS WHERE REQUIRED ON THE PLANS OR REQUESTED BY
5.
OWNER.
CONCRETE PIPE SUPPORT TO BE PAID UNDER THE APPROPRIATE PIPE BID ITEM.
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD CONCRETE PIPE SUPPORT
S-a-217
SHEET 1 OF 1
GROUND SURFACE
GROUND SURFACE
EXIST BRICK OR
24" DIA
CONCRETE WALLS
STEP
(SAND FILL)
(SAND FILL)
BREAK OUT 2
DRAIN HOLES
100-C-100
24" MIN
100-C-100
HALF SEGMENT OF
PIPE TIGHTLY SEATED
ER
ER
W
ET
SE
AM
K
DI
N
U
FLOW
TR
TIGHTLY SEATED
DIAMETER
HALF SEGMENT OF PIPE
6"
TRUNK SEWER
6"
CUT AWAY EXISTING MASONRY
OR CONCRETE TO FORM SEAT
FOR SEGMENT AND MORTAR
LONGITUDINAL SECTION
CROSS SECTION
NOTES:
1.
FORTY-EIGHT HOURS PRIOR TO COMMENCING THE ABANDONMENT OF THE MANHOLE. THE CONTRACTOR
SHALL CONTACT THE DISTRICTS’ SUPERINTENDENT OF MAINTENANCE AT (323) 774-7272.
2.
NO WORK SHALL BE DONE ON MANHOLE EXCEPT IN THE PRESENCE OF COUNTY SANITATION DISTRICT
REPRESENTATIVE.
3.
MANHOLE FRAME AND COVER OF THE MANHOLE TO BE ABANDONED SHALL BE SALVAGED, CLEANED
AND DELIVERED TO THE DISTRICTS’ COMPTON FIELD OFFICE, 920 SOUTH ALAMEDA STREET, COMPTON,
CALIFORNIA.
4.
THE CONTRACTOR SHALL REMOVE A MINIMUM OF THREE FEET OF THE MANHOLE SHAFT BELOW STREET
SUBGRADE.
5.
IF THE LOWER PORTION OF THE EXISTING CHANNEL THROUGH THE MANHOLE IS NOT AS SHOWN. THE
CHANNEL SHALL BE REFORMED AS DIRECTED BY THE COUNTY SANITATION DISTRICT REPRESENTATIVE.
6.
HALF SEGMENT OF PIPE SHALL BE OF THE TYPE USED IN THE SEWER.
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
STANDARD ABANDONMENT OF EXISTING
MANHOLES TYPE "A" OR "D"
2006 EDITION
S-a-218
SHEET 1 OF 1
RESET MANHOLE
FRAME AND COVER
5"
PROPOSED
GROUND SURFACE
48" MAX
EXISTING
GROUND SURFACE
(DIM " A ")
10"
REMOVE EXISTING
24" DIA
30" DIA
FRAME & COVER
EXISTING
EXISTING
GROUND SURFACE
GROUND SURFACE
1/2"
PROPOSED
PLASTER
CONC CURB
& GUTTER
EXISTING PORTION
NEW
PLASTER
TO REMAIN
ALLOWABLE
NEW
BRICK-
PLASTER
NEW
BRICK5
WORK
CASE I
WORK
2
ALLOWABLE
VERTICAL
WALL
TO REMAIN
MAXIMUM
1/2"
24" DIA
MAXIMUM
EXISTING PORTION
2
TO REMAIN
5
5
EXISTING PORTION
30" MIN
24" DIA
TO BE REMOVED
1/2"
WORK
TO BE REMOVED
SURFACE
2
EXISTING PORTION
EXIST. PORTION
GROUND
EXISTING PORTION
BRICKPROPOSED
CASE II
CASE III
NOTES:
1.
PRIOR TO THE REMOVAL OF THE FRAME OF ANY MANHOLE, THE CHANNEL OF THE MANHOLE SHALL
BE COMPLETELY COVERED WITH PLANKING OR OTHER SUITABLE MATERIAL SO AS TO PREVENT DEBRIS
FROM ENTERING THE CHANNEL. AFTER THE MANHOLE RECONSTRUCTION HAS BEEN COMPLETED ALL
DEBRIS SHALL BE REMOVED FROM WITHIN THE MANHOLE AND THE COVER OVER THE CHANNEL SHALL
BE REMOVED.
2.
WHEN THE MANHOLE IS TO BE RECONSTRUCTED TO A STRAIGHT SIDED MANHOLE, THE BRICK WORK
SHALL BE REMOVED TO THE HIGHEST POINT OF THE VERTICAL WALL. THE SLOPE OF THE CORBELED
SIDE SHALL NOT EXCEED 2 INCHES IN 5 INCHES. THE MANHOLE STEPS SHALL BE PLACED ON THE
VERTICAL SIDE. SEE CASE III.
3.
WHEN THE MANHOLE IS TO BE RAISED AN AMOUNT SUCH THAT DIMENSION "A" (CASE II) IS LESS THAN
4’, THE BRICKWORK SHALL BE REMOVED TO A POINT WHERE THE INSIDE DIAMETER IS A MINIMUM OF
30 INCHES. THE MANHOLE WALL SHALL THEN BE CONSTRUCTED VERTICALLY TO A POINT 15 INCHES
BELOW THE TOP OF THE MANHOLE. SEE CASE II.
4.
WHERE THE MANHOLE IS TO BE RAISED SUCH THAT DIMENSION "A" (CASE II) WOULD EXCEED 4’, THE
BRICKWORK SHALL BE REMOVED TO THE HIGHEST POINT OF THE VERTICAL WALL AND THE MANHOLE
RECONSTRUCTED PER S-a-201 OR S-a-204.
5.
WHEN THE DEPTH OF THE MANHOLE TO BE LOWERED IS SUCH THAT THE MAXIMUM ALLOWABLE
SLOPES FOR THE BRICKWORK SHOWN FOR CASE I WOULD BE EXCEEDED. THE MANHOLE SHALL BE
RECONSTRUCTED AS
6.
A TYPE "C" MANHOLE PER S-a-203.
MANHOLE STEPS, PER S-a-209, SHALL BE PLACED UNIFORMLY SO AS NOT TO BE MORE THAN 16 INCHES
APART WITH THE TOP STEP BEING 16 INCHES BELOW THE MANHOLE FRAME.
7.
PRIOR TO COMMENCING WORK OF RECONSTRUCTION, THE CONTRACTOR SHALL CONTACT DISTRICTS’
SUPERINTENDENT OF MAINTENANCE AT (323) 774-7272.
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
STANDARD RECONSTRUCTION
OF BRICK MANHOLES
2006 EDITION
S-a-219
SHEET 1 OF 1
3/4" DIA SS TYPE 316,
R=3"
ASTM A-276
PLASTIC LINER WITH
INSIDE FACE OF
VARIES
6"
CONCRETE
9"
R =1"
BRICK OR
STRUCTURE WALL
3"
LOCKING EXTENSIONS
FOR CONCRETE STRUCTURE OR
TYPE "A" MANHOLE WALL
DRYPACK WITH 5000 psi
3/4" DIA SS TYPE 316,
R=3"
ASTM A-276
NON-SHRINK GROUT
PLASTIC LINER WITH
PRECAST MANHOLE
LOCKING EXTENSIONS
VARIE
S
3"
SECTION
WASHER (TYP)
MIN
2"
2" x 2" x 3/8" SS
1" x 9"
BACKFILL IN 2-SACK
BLOCKOUT
SAND SLURRY
FOR PRECAST MANHOLE SECTION OR
CONCRETE WALL LESS THAN 8"
3/4" DIA SS THREADED
BAR IN EPOXY ADHESIVE
3/4" DIA SS TYPE 316,
R=3"
ASTM A-276
CONCRETE ANCHORS
PLASTIC LINER WITH
3"
WALL
EMBEDMENT
CL
2"
8" MIN
LOCKING EXTENSIONS
3 3/8" 3 3/8"
ALTERNATE PULL RING FOR
CONCRETE STRUCTURE
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD PULL RING
S-a-220
SHEET 1 OF 1
4’-0"
3"
SEWER CONSTRUCTION PROJECT
2 1/2"
3"
CONTRACTOR
2"
6"
CONTRACTOR’S NAME
3"
PHONE
2"
DISTRICT
NUMBER
FOR
6’-0"
4’-0"
5"
INSERT
3 1/2"
2"
2"
SANITATION DISTRICT No.
OF LOS ANGELES COUNTY
STEPHEN R. MAGUIN
2 1/2"
1
1
1
1
1/2"
1/2"
3/4"
3/4"
1"
CHIEF ENGINEER & GENERAL MANAGER
6"
1’-11"
2’-0"
3"
6"
5’-0"
FRONT VIEW
SIDE VIEW
NOTES:
1.
ALL FRAMING LUMBER SHALL BE 2" x 6" S4S D.F.
2.
ENTIRE SIGN, INCLUDING FRAMING, SHALL BE PAINTED WITH TWO
COATS OF EXTERIOR OIL BASE WHITE PAINT.
3.
LETTERING SHALL BE DONE IN BLACK BY QUALIFIED SIGN PAINTER
AND TO THE SATISFACTION OF THE ENGINEER.
4.
SIGNS SHALL BE MAINTAINED IN A CONDITION SATISFACTORY TO
THE ENGINEER.
5.
SIGNS SHALL BE FURNISHED BY CONTRACTOR AND INSTALLED
AND MOVED BY CONTRACTOR AS DIRECTED BY THE ENGINEER.
NO CONSTRUCTION SHALL COMMENCE UNTIL SIGNS ARE IN PLACE.
TWO REQUIRED.
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD PROJECT SIGN
S-a-221
SHEET 1 OF 1
C
L BEARING BLOCKS
C
L BEARING BLOCKS
SPAN
2" THICK
A
TIMBER PADS
STEEL BEAM (SEE TABLE)
DETAIL "1"
STEEL SUPPORT
BEAMS (SEE TABLE)
2x OR 4x
2’
4’
MAX
MAX
2x12 OR
4x12 Gr 2 S4S
BEARING
TIMBER BLOCKS
(TYP)
BLOCKS
(SEE TABLE)
(SEE TABLE)
DETAIL "2"
TURNBUCKLE
(SEE TABLE)
TURNBUCKLE
WIRE CLIPS
VERTICAL
3 WIRE ROPE
SHORING AS
CLIPS EACH SIDE
REQUIRED
@ 3" O.C.
WIRE
WIRE ROPE
ROPE
EXISTING
PIPE
EXISTING
PIPE
4x4 TIMBER
BLOCKS 8"
LONG (TYP)
NOTE:
4x4 TIMBER
BLOCK 8"
A
LONG (TYP)
A MINIMUM OF 2 HANGER
ASSEMBLIES PER JOINT OF PIPE
ELEVATION
SECTION A-A
WIRE ROPE
THIMBLE (TYP)
2" THICK
TIMBER PADS
STEEL
BEAM
STANDARD
TURNBUCKLE
(SEE TABLE)
WIRE
ROPE
3 WIRE ROPE
CLIPS EACH SIDE
@ 3" O.C.
DETAIL "1"
DETAIL "2"
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD TEMPORARY PIPE SUPPORT
S-a-222
SHEET 1 OF 2
TABLE OF MEMBER SIZES (PART I)
STEEL BEAMS
PIPE
WIRE
SPAN
SIZE
0’ - 10’
11’ - 15’
16’ - 20’
TURNBUCKLE
ROPE
21’ - 30’
31’ - 40’
8" - 10"
w6x9
w6x9
w6x9
w 8 x 18
w 10 x 22
3/8"
1/2"
12" - 15"
w6x9
w 6 x 15
w 6 x 20
w 10 x 22
w 12 x 30
3/8"
1/2"
18" - 21"
w6x9
w 8 x 18
w 8 x 24
w 10 x 33
w 12 x 53
3/8"
1/2"
24" - 27"
w 6 x 15
w 8 x 18
w 8 x 28
w 12 x 40
w 12 x 72
3/8"
1/2"
30"
w 6 x 15
w 8 x 18
w 8 x 31
w 12 x 53
2 - w 12 x 53
1/2"
5/8"
33"
w 8 x 18
w 8 x 24
w 10 x 33
w 12 x 65
2 - w 12 x 65
1/2"
5/8"
36"
w 8 x 18
w 10 x 22
w 10 x 33
w 12 x 72
2 - w 12 x 65
1/2"
5/8"
39"
w 8 x 18
w 10 x 22
w 10 x 39
w 12 x 72
2 - w 12 x 72
1/2"
5/8"
42"
w 8 x 18
w 10 x 22
w 10 x 49
w 12 x 79
2 - w 14 x 61
1/2"
5/8"
48"
w 8 x 18
w 12 x 30
w 12 x 53
1/2"
5/8"
54"
w 10 x 22
w 12 x 30
w 12 x 53
5/8"
3/4"
60"
w 10 x 22
w 12 x 40
w 12 x 65
5/8"
3/4"
66"
w 10 x 33
w 12 x 53
2 - w 12 x 53
5/8"
3/4"
72"
w 12 x 30
w 12 x 53
2 - w 12 x 65
5/8"
7/8"
TABLE OF MEMBER SIZES (PART II)
BEARING BLOCKS
PIPE
SPAN
SIZE
0’ - 10’
11’ - 15’
16’ - 20’
21’ - 30’
31’ - 40’
8" - 10"
1 - 2 x 12 x 2’
1 - 2 x 12 x 2’
2 - 2 x 12 x 2’
2 - 2 x 12 x 2’
2 - 2 x 12 x 2’
12" - 15"
1 - 2 x 12 x 2’
1 - 2 x 12 x 2’
2 - 2 x 12 x 2’
2 - 2 x 12 x 2’
2 - 4 x 12 x 3’
18" - 21"
1 - 2 x 12 x 2’
1 - 2 x 12 x 3’
2 - 2 x 12 x 3’
2 - 4 x 12 x 3’
2 - 4 x 12 x 4’
24" - 27"
1 - 2 x 12 x 3’
2 - 2 x 12 x 2’
2 - 2 x 12 x 3’
2 - 4 x 12 x 5’
3 - 4 x 12 x 4’
30"
1 - 2 x 12 x 3’
2 - 2 x 12 x 3’
2 - 4 x 12 x 4’
3 - 4 x 12 x 4’
3 - 4 x 12 x 5’
2 - 4 x 12 x 4’
3 - 4 x 12 x 5’
2 - 2 x 12 x 2’
33"
2 - 2 x 12 x 3’
36"
2 - 2 x 12 x 2’
2 - 2 x 12 x 3’
2 - 4 x 12 x 4’
39"
2 - 2 x 12 x 3’
2 - 4 x 12 x 4’
2 - 4 x 12 x 5’
42"
2 - 2 x 12 x 3’
2 - 4 x 12 x 4’
2 - 4 x 12 x 5’
48"
2 - 4 x 12 x 4’
2 - 4 x 12 x 5’
3 - 4 x 12 x 5’
54"
2 - 4 x 12 x 4’
2 - 4 x 12 x 5’
3 - 4 x 12 x 5’
60"
2 - 4 x 12 x 4’
3 - 4 x 12 x 5’
3 - 4 x 12 x 5’
66"
2 - 4 x 12 x 5’
3 - 4 x 12 x 5’
3 - 4 x 12 x 6’
72"
2 - 4 x 12 x 5’
3 - 4 x 12 x 5’
4 - 4 x 12 x 5’
3 - 4 x 12 x 5’-6"
4 - 4 x 12 x 5’
4 - 4 x 12 x 5’-6"
3 - 4 x 12 x 6’
4 - 4 x 12 x 5’-6"
4 - 4 x 12 x 6’
4 - 4 x 12 x 6’-6"
NOTES:
1.
FORTY-EIGHT HOURS PRIOR TO COMMENCING CONSTRUCTION OF THE TEMPORARY SUPPORT, THE CONTRACTOR
SHALL CONTACT THE DISTRICT SUPERINTENDENT OF MAINTENANCE AT (323) 774-7272.
2.
APPROVAL SHALL BE OBTAINED FROM THE COUNTY SANITATION DISTRICT
REPRESENTATIVE OF THE SPAN TO BE
USED IN DETERMINING THE SIZE OF THE STEEL BEAM.
3.
ALL WORK ON THE TEMPORARY SUPPORT SHALL BE DONE ONLY IN THE PRESENCE OF THE COUNTY SANITATION
DISTRICT REPRESENTATIVE.
4.
THE CONTRACTOR SHALL BE COMPLETELY
RESPONSIBLE FOR THE ADEQUACY OF THE TEMPORARY SUPPORT AND
FOR THE MANNER IN WHICH IT IS INSTALLED.
5.
FOR PIPES AND MEMBER SIZES NOT SHOWN IN THE ABOVE TABLES, THE CONTRACTOR SHALL SUBMIT DETAILS OF
THE PROPOSED SUPPORT AND CALCULATIONS PREPARED BY CIVIL / STRUCTURAL ENGINEER REGISTERED IN THE
STATE OF CALIFORNIA TO THE COUNTY SANITATION DISTRICT REPRESENTATIVE FOR WRITTEN APPROVAL PRIOR
TO COMMENCING CONSTRUCTION.
6.
APPROVAL SHALL BE OBTAINED FROM THE COUNTY SANITATION DISTRICT REPRESENTATIVE PRIOR TO USING
MEMBERS OR PARTS OF THE TEMPORARY SUPPORT DIFFERENT THAN DETAILED.
7.
LARGER STEEL BEAMS WITH CORRESPONDINGLY
LARGER SECTION MODULI MAY BE SUBSTITUTED.
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD TEMPORARY PIPE SUPPORT
S-a-222
SHEET 2 OF 2
3 1/2" HIGH LETTERS
A
A
TYP
7 1/2
4"
R
B
LE
B
A
C
3
0"
PRY NOTCH
4"
PLAN OF COVER
TOP VIEW
32"
3 1/8" DIA
1 1/4"
1 1/8"
5/16"
1"
(TYP)
GROOVE
20
PLAN OF FRAME
(TYP)
5 1/2" DIA
2 3/4"
2"
1 1/4"
1" (TYP)
5/8" (TYP)
33 3/4"
PRY
32 1/4"
NOTCH
26 1/2"
1 1/4"
5
2 MIN (TYP)
29 1/4"
5"
SECTION A-A
5
1" DIA HOLE
30" CLEAR
4"
5/8"
4"
1 1/4"
1 1/2"
7/8"
30
2 PLACES
38"
1" (TYP)
5/8" (TYP)
SECTION B-B
PRY
NOTCH
12
" R
(TY
P)
NOTES:
45
1. CAST IRON USED SHALL CONFORM WITH ASTM A-48 CLASS 35B.
2. FRAME AND COVER SHALL BE COATED WITH ASPHALTUM OR
BITUMINOUS PAINT AFTER TESTING AND INSPECTION.
3. FRAME AND COVER SHALL BE TESTED FOR ACCURATE FIT PRIOR
TO DELIVERY AND SHALL BE MARKED IN SETS.
2
22
1/
4. ALL CASTINGS SHALL COMPLY
WITH SECTION 206-3 OF THE
STANDARD SPECIFICATIONS.
PLAN OF COVER
BOTTOM VIEW
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
STANDARD 30" MANHOLE FRAME
CHIEF ENGINEER
AND COVER
2006 EDITION
S-a-223
SHEET 1 OF 1
B
VARIES
B
3" TO 4’-0"
" t " BARS
" r " BARS
(TYP)
(TYP)
" r " BARS
(TYP)
(TYP)
A
" s " BARS
C
PLASTIC
LINER
PLATE
PLASTIC
LINER
LAP
D
(TYP)
MIN
1’ - 6"
PIPE SIZE
E
BL
A
RI
VA
A
C
3"
(SEE TABLE)
PLATE
" t " BARS
(SEE TABLE)
" s " BARS
MATCH EXIST. ADJACENT
(TYP)
PIPE, 90
LONGITUDINAL SECTION
0
MAX
CROSS SECTION
TABLE OF REINFORCING BARS
PIPE
DEPTH TO
SIZE
INVERT
24" TO
0’ TO 15’
33"
16’ TO 30’
36"
48"
54"
16’ TO 30’
16’ TO 30’
8"
3"
16"
#4 @ 10"
8"
3"
6"
8"
3"
7"
8"
3"
7"
8"
4"
7"
8"
4"
8"
8"
4"
8"
10"
5"
8"
10"
5"
0’ TO 15’
0’ TO 15’
15’ TO 30’
#4 @ 12
2 - #4
16"
#4 @ 12
2 - #4
#4 @ 8
#4 @ 10
9"
12"
5"
9"
12"
6"
0’ TO 15’
96"
"t"
NOTES:
6"
0’ TO 15’
15’ TO 30’
"s"
#4 @ 10
0’ TO 15’
16’ TO 30’
84"
6"
0’ TO 15’
16’ TO 30’
72"
"r"
0’ TO 15’
16’ TO 30’
66"
D
0’ TO 15’
16’ TO 30’
60"
C
0’ TO 15’
16’ TO 30’
42"
REINFORCING BARS
B
0’ TO 15’
16’ TO 30’
39"
DIMENSIONS
A
16"
#4 @ 6
16"
#4 @ 10
20"
#5 @ 10
16"
#4 @ 10
20"
#5 @ 8
16"
#4 @ 8
20"
#5 @ 8
16"
#4 @ 6
24"
#6 @ 8
20"
#5 @ 8
28"
#7 @ 8
20"
#5 @ 8
28"
#7 @ 6
20"
#5 @ 8
28"
#7 @ 6
20"
#5 @ 6
28"
#7 @ 6
#4 @ 12
2 - #4
#5 @ 12
2 - #5
#5 @ 12
2 - #5
#5 @ 12
2 - #5
1. CONCRETE SHALL BE 660-B-4000.
2. ALL REINFORCING BARS SHALL BE
ASTM A-706, CLASS 60.
3. THE CONCRETE SHALL BE CONSOLIDATED
BY MEANS OF HIGH FREQUENCY INTERNAL
VIBRATORS.
4. DETAIL APPLIES FOR PIPES WITH COVER
FROM 3’-0" TO 30’-0"
FOR TRENCH
CONDITION AND FOR PIPES WITH COVER
#5 @ 12
2 - #5
#5 @ 12
3 - #5
#5 @ 12
3 - #5
3’-0" TO 10’-0" FOR EMBANKMENT
CONDITION.
5. PIPE BARRELLING SHALL BE DONE AT
LOCATIONS AND LENGTHS SHOWN ON
THE DRAWINGS OR AUTHORIZED BY
THE ENGINEER.
#5 @ 12
3 - #6
#5 @ 9
3 - #6
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD PIPE BARREL
S-a-224
SHEET 1 OF 1
ANGLE VARIES
0 o TO 10 o
A
(TYP)
B
B
A
(TYP)
A
" r " BARS
(TYP)
(TYP)
" s " BARS
" s " BARS
A/2
(TYP)
2 1/2" CL
2" CL
VARIABLE
V
E
BL
" r " BARS
(TYP)
(TYP)
24d
LAP
(TYP)
IA
AR
INSTALL
" r " BARS
WATERSTOP
MATCH EXIST. ADJACENT
PIPE, 90
0
PER NOTE 6
MAX
CROSS SECTION
LONGITUDINAL SECTION
TABLE OF REINFORCING BARS
DIMENSIONS
REINFORCING BARS
PIPE DIAMETER
A
B
24" TO 36"
8"
8"
#4 @ 8
#4 @ 12
39" TO 57"
8"
10"
#6 @ 8
#5 @ 12
60" TO 78"
10"
12"
#7 @ 6
#5 @ 12
84" TO 96"
12"
16"
#7 @ 6
#5 @ 9"
"r"
"s"
NOTES:
1.
CONSTRUCT CONCRETE COLLAR WHERE REQUIRED ON THE DRAWINGS AND AT ALL PIPE JOINTS WHERE THERE IS A
CHANGE IN THE TYPE OF JOINT OR A CHANGE IN THE THICKNESS OF THE WALLS OF ADJACENT PIPES.
2.
UNLESS OTHERWISE SPECIFIED, CONCRETE SHALL BE 660-B-4000 AND ALL REINFORCING BARS SHALL BE DEFORMED
BARS CONFORMING TO ASTM-A706 GRADE 60.
3.
EXTERIOR SURFACES OF CONCRETE PIPE SHALL BE CLEANED BY SANDBLASTING PRIOR TO PLACING CONCRETE.
4.
THE CONTRACTOR SHALL SUBMIT WORKING DRAWINGS THAT SHOW DETAILS FOR JOINING ANY PLASTIC LINERS IN
ADJACENT PIECES OF PIPE.
5.
FOR VITRIFIED CLAY PIPE HAVING NO ANGULAR DEFLECTION, THE CONTRACTOR MAY USE A REPAIR COUPLING AND
OMIT THE REINFORCING STEEL FROM THE CONCRETE COLLAR.
SHEAR BAND.
6.
THE REPAIR COUPLING SHALL INCLUDE AN INTEGRAL
DETAILS OF THE REPAIR COUPLING SHALL BE SUBMITTED TO THE DISTRICTS FOR APPROVAL.
HYDROTITE CJ - 2010 - 2 / 6 HYDROPHILIC WATERSTOP OR ADEKA MC 2010M OR EQUIVALENT. INSTALL ALL AROUND.
EACH PIPE.
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD CONCRETE COLLAR
S-a-225
SHEET 1 OF 1
1" DIA HOLE
2 PLACES
A
45
7 1/2
(TY
P)
A
B
B
R
C
A
LE
30
3/4"
3 1/2" HIGH
LETTERS
PRY NOTCH
PLAN OF COVER
TOP VIEW
31 3/4"
3 1/8" DIA
3
5/16"
1" (TYP)
1 3/8"
GROOVE
(TYP)
1" (TYP)
PRY
1/8"
3 3/8"
PLAN OF FRAME
NOTCH
2"
1 1/2"
20
8 3/4" DIA
1/2" (TYP)
1 1/4"
1 1/2" DIA HOLE
(4 REQ’D) ON
34 1/4"
27" DIA
43 1/2" DIA
32" DIA RING ID
SECTION A-A
5 +
-
30
3/4"
2 PLACES
2 7/8"
1" DIA HOLE
1 1/4"
1 1/4"
1 1/2"
5 5/8"
30
3"
1 1/2"
3
3"
30" DIA CLEAR
36" DIA MIN
5" MIN
47" DIA MIN
1" (TYP)
5/8" (TYP)
5" MIN
PRY
NOTCH
SECTION B-B
12
" R
(TY
P)
45
NOTES:
1. CAST IRON USED SHALL CONFORM WITH ASTM A-48 CLASS 35B.
2. FRAME AND COVER SHALL BE COATED WITH ASPHALTUM OR
BITUMINOUS PAINT AFTER TESTING AND INSPECTION.
3. FRAME AND COVER SHALL BE TESTED FOR ACCURATE FIT PRIOR
2
22
1/
TO DELIVERY AND SHALL BE MARKED IN SETS.
4. ALL CASTINGS SHALL COMPLY
WITH SECTION 206-3 OF THE
STANDARD SPECIFICATIONS.
PLAN OF COVER
BOTTOM VIEW
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
STANDARD 36" MANHOLE FRAME
CHIEF ENGINEER
WITH 30" COVER
2006 EDITION
S-a-226
SHEET 1 OF 1
4" OR 6" VC
S
OR CI PIPE
MINIMUM BEDDING
1/2 OD OF PIPE
CLASS "C" MORTAR
DEPTH
A
OF COVER
1-#5 BAR IF BEAM
SEWER
IS PRECAST
2" CL (TYP)
t
CONNECTION
2" CL
HOUSE
SEE TABLE
FOR BAR No.
A
"X"
1
"V" BOTTOM
1
BLE
VARIA
10"
ELEVATION
SECTION A-A
DIMENSIONS OF
NOTE:
REINFORCED CONCRETE BEAM
BEAM CONCRETE SHALL BE 660-B-4000.
ALL REINFORCING BARS
SHALL BE DEFORMED BARS CONFORMING TO ASTM-A706 GRADE 60.
DEPTH OF COVER
A "V" BOTTOMED BEAM AS DETAILED ABOVE SHALL BE POURED
S
0 TO 8’-0"
(FEET)
8’-1" TO 16’-0"
IN PLACE OR, IF APPROVED BY THE ENGINEER. A RECTANGULAR
PRECAST BEAM SHALL BE PLACED ON
t
BAR No
t
BAR No.
4
8"
4
10"
5
5
9"
5
12"
5
6
10"
5
13"
6
BACKFILL WHICH HAS BEEN
PREVIOUSLY CONSOLIDATED TO THE INVERT OF THE HOUSE
CONNECTION AND REEXCAVATED TO ACCOMMODATE THE BEAM.
IN EITHER CASE, THE BEAM SHALL BEAR ON UNDISTURBED OR
CONSOLIDATED SOIL.
7
11"
6
15"
6
8
12"
6
16"
6
9
13"
6
17"
7
10
14"
7
19"
7
MINIMUM LENGTH OF BEARING
11
15"
7
20"
7
OF ENDS OF REINFORCED CONCRETE BEAMS
12
16"
7
22"
7
13
17"
7
23"
8
14
18"
8
25"
8
15
19"
8
26"
8
16
20"
8
17
21"
8
18
22"
8
DEPTH OF COVER
0 TO 8’-0"
8’-1" TO 16’-0"
S
MIN BEARING - "X"
0 TO 12’-0"
18"
12’-1" TO 18’-0"
24"
0 TO 7’-0"
18"
7’-1" TO 11’-0"
24"
11’-1" TO 15’-0"
30"
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
STANDARD CONCRETE BEAM FOR
CHIEF ENGINEER
HOUSE CONNECTIONS
2006 EDITION
S-a-227
SHEET 1 OF 1
28 11/16" MIN
27 3/16"
27 1/16"
1 3/4"
1 3/4"
3 1/4"
1 13/32"
DIA
NOTE: COVER SHALL BE SNUG
SEE DETAIL 1
4"
FIT, NOT TIGHT
7" DIA
CASTING TO BE SET
IN WET MORTAR
24"
34"
SECTION
MANHOLE FRAME AND COVER
2 11/32"
1 7/32"
3/4"
1 5/8"
1 5/8"
1/16"
3 3/8"
15
R = 1/4"
1/2" DIA HOLE IN
1/2" THK PLATE4"
11/16"
1/4"
1 3/4"
1 1/2"
11/16"
3/16"
15
3/8"
1 31/32"
1 1/2"
3 REQ’D AT 120
1/8"
3/8"
0
3/4"
1"
SECTION A-A
5/32"
27 1/16"
5"
1’’ DIA HOLE
2 PLCS
DETAIL 1
R
E
W E
1"
15
4"
A
71
/2
2"
1/
S
1
A
R
1/
S D
7 1/2
/4"
93
1
C
30
PRY NOTCH
NOTE:
PLAN OF COVER
PLAN OF COVER
BOTTOM VIEW
TOP VIEW
FOR NOTES SEE S-a-207.
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
STANDARD 24" TRAFFIC MANHOLE
CHIEF ENGINEER
FRAME AND COVER
2006 EDITION
S-a-228
SHEET 1 OF 1
48"
40"
38 1/4"
38"
3 1/4"
1"
1"
(TYP 8 PLCS)
2 1/4"
SS ANCHOR BOLT w/ H H NUT
1 1/4"
5/8’’ DIA x 10’’ LG TYPE 316
1 3/8"
5/16"
3 1/8"
DIA
1"
7 1/4"
7"
1"
6"
1/2"
PAINT WITH
5/8"
ASPHALTUM PAINT
CASTING TO BE SET
33"
IN WET MORTAR
5/8’’ DIA x 1 1/4’’ LG TYPE 316
1 1/8’’ WIDE (MIN) X 1/8’’ THICK
SS CAP SCREWS, (TYP OF 24)
NEOPRENE GASKET
REINFORCED
36"
CONCRETE
SECTION
APPLY ANTI-FREEZE
1/2"
1 1/2"
MANHOLE FRAME AND COVER
AGENT (TYP)
7/8"
1 7/8"
+
32"
1 7/8"
0
10
1 1/4"
LIFTING EYE, (TYP 2 PLCS)
SEE DETAIL
3/4’’ x 1 1/2 ’’ x 32’’ LG
1/4
1/8"
6 1/16"
4 REQ’D AT 90
0
5/8"
(TYP 2 PLCS)
TYP
3/4"
1/2" DIA HOLE
TYPE 316 L SS FLAT BAR
4 13/16"
TYPE 316 L SS FLAT BAR
R
=
17
8"
7/
3/4’’ DIA HOLE
5/
(TYP 24 PLCS)
8"
3/4"
THREAD FOR
3/4"
3/4"
1/2" TYPE 316 L
SS PLATE 35 3/4" DIA
3/4’’ x 1 1/2’’ x 15 5/8’’ LG
3"
0
2"
15
7 1/2
45
-
5/8" CAP SCREW
1 1/2"
R =1"
1/4
TYP
1 1/2 - 6
PRESSURE PLATE
7 1/2"
TYPE 316 L BAR
TYP
3/16
3 1/2"
1/2’’ DIA SS
DETAIL- LIFTING EYE
SECTION A-A
BOTTOM VIEW
45
1’’ DIA HOLE
DRILL 3/4’’
22.5
2 PLACES
C
S D
E
W E
A
NOTCH
34 1
/2"
43
"
D
IA
PRY
A
R
/4"
13 1
P)
(TY
DIA
DRILL & TAP
1
S
4"
1/
R
)
Y
FOR 5/8’’ SCREW
8"
P
(T
)
P
5/
Y
1
1"
(T
PRY NOTCH
"
2
1/
FLANGE RIBS
30
PLAN OF COVER
0
3/4’’ THICK
TOP VIEW
(TYP 8 PLCS)
PLAN OF FRAME
PLAN OF COVER
BOTTOM VIEW
NOTE:
FOR NOTES SEE S-a-207.
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
STANDARD 36" PRESSURE MANHOLE
CHIEF ENGINEER
FRAME AND COVER
2006 EDITION
S-a-229
SHEET 1 OF 1
7/8" DIA SS
3" R
TYPE 316 ROD (TYP)
PRECAST CONCRETE
2"
CL
SEE PLAN
3"
SLAB
6"
PLASTIC LINER w/ LOCKING
EXTENSIONS
TYPE I LIFTING EYE DETAIL
B
A
3"
3"
A
5"
5"
B
PLAN
10"
CONCRETE SLAB
8"
TYPE 316 ROD
6"
PRECAST
7/8" DIA SS
4"
2"
CL
3" R
6"
PLASTIC LINER w/
FILL RECESS w/ "HENRYS" ROOF
FILL RECESS w/ "HENRYS" ROOF
PLASTIC LINER w/ LOCKING
MASTIC OR APPROVED EQUAL
EXTENSIONS
MASTIC OR APPROVED EQUAL
SECTION A-A
LOCKING EXTENSIONS
7/8" DIA SS TYPE 316 ROD
SECTION B-B
TYPE II LIFTING EYE DETAIL
(FOR COVER LESS THAN 12" THICK)
COUNTY SANITATION DISTRICTS OF LOS ANGELES COUNTY
OFFICE OF CHIEF ENGINEER
STANDARD DRAWING
STEPHEN R. MAGUIN
CHIEF ENGINEER
2006 EDITION
STANDARD LIFTING EYE
S-a-230
SHEET 1 OF 1
Download