8. TemBreak - directresponseonline.co.uk

advertisement
DIRECT OPENING
Under the heading “Measures to minimise the
risk in the event of failure”, IEC 60204-1 Safety
of Machinery-Electrical Equipment Machinery
includes the following recommendation:
“-the use of switching devices having positive
(or direct) opening operation.”
7
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
TEMBREAK 2
MOULDED CASE CIRCUIT BREAKERS
16A TO 630A
1.
Welcome to TemBreak 2
2.
Ratings and Speciļ¬cations
3.
Operating Characteristics
4.
Application Data
5.
Accessories
6.
Installation
7.
Dimensions
TEMBREAK
MOULDED CASE CIRCUIT BREAKERS
630A TO 1600A
8.
•
Easy Selection Guide
131
•
Ratings and Specifications
133
•
Operating Characteristics
137
•
Electrical Control Using Internally Mounted Accessories
139
•
Electrical Control Using Motor Operation
143
•
Operating Handles
145
•
Insulation Accessories
147
•
Toggle Accessories
148
•
Mechanical Interlocks
149
•
Installation
150
•
Dimensions
157
SECTION 8
9.
TemBreak Moulded Case Circuit Breakers
Order Codes
page 130
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
EASY SELECTION GUIDE
The TemBreak range of products includes:
-Moulded Case Circuit Breakers
-Switch-Disconnectors
-A comprehensive range of accessories.
EXCEPTIONAL CURRENT LIMITING
Terasaki's ingenuity in current breaking is
exemplified by the Fast Break Mechanism (FBM)
of the TemBreak range.
The quick breaking performance of TemBreak
provides exceptional current limiting
characteristics.
F.B.M - Fast Break Mechanism
Exceptional Current Limitation
Provides
kA
84.1
Conventional
800A MCCB
SECTION 8
43.4
TemBreak
XS800NJ
Total break time
Quick-break arc chutes
Dual repulsive contacts
U-shaped conductors
Reduced Peak let through minimises
electrodynamic stress on conductors
Provides
Reduced i 2 t energy let through
minimises thermal stress on conductors
Reduced tripping time minimises damage
after fault to both system and MCCB
page 131
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
EASY SELECTION GUIDE
Frame Ratings (A)
SECTION 8
Terasaki produce MCCBs up to 2500A. Contact us for details.
page 132
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
RATINGS AND SPECIFICATIONS
TemBreak MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 Ann. 1,
AS/NZS 3947-3, NEMA-AB1
Frame
Quantity
Unit
Condition
800
800
XS800NJ
3, 4
XS800SE
3, 4
630, 800
800
AC 50/60 Hz
DC
690
250
690
8
690
690
8
Model
Number of Poles
Nominal current ratings
In
(A)
Rated operational voltage
Ue
(V)
Rated insulation voltage
Rated impulse withstand voltage
Ui
Uimp
(V)
(kV)
Ultimate breaking capacity
(IEC, JIS, AS/NZS)
Icu
(kA)
690V AC*
525V AC
440V AC
415V AC
380/400V AC
220/240V AC
250V DC
20
35
50
50
65
85
50
20
35
50
50
50
85
-
Service breaking capacity
(IEC, JIS, AS/NZS)
Ics
(kA)
690V AC*
525V AC
440V AC
415V AC
380/400V AC
220/240V AC
250V DC
10
18
25
25
33
43
25
10
18
25
25
25
43
-
Rated short-time withstand current
Rated breaking capacity (NEMA)
Icw
(kA rms)
(kA)
0.3 Seconds
480V AC
240V AC
50
85
10
50
85
A
B
•
•
•
•
•
•
•
•
•
•
50°C
Electrical characteristics
Protection
SECTION 8
Adjustable thermal, adjustable magnetic
Fixed hydraulic, fixed magnetic
Microprocessor
Utilisation category
Installation
Front connection (FC)
Attached terminal bar (FB)
Solderless terminal (cable clamp)
Rear connection (RC)
Plug-in (PM)
Draw-out (DR)
DIN rail mounting (DA)
Dimensions
Weight
h
w
(mm)
(mm)
d
w
(mm)
(kg)
3 pole
4 pole
3 pole
4 pole
273
210
280
103
9.4
12.2
273
210
280
103
9.7
12.5
•
•
•
•
Operation
Toggle operation
Door mounted (HP) /breaker mounted handle (HB)
Motor operation (MC)
Standard
page 133
•
Optional
- Not Available
*MCCBs cannot be used in IT earthed systems
at this voltage.
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
800
1600
1250
1250
1600
1600
1600
XH800SE
3, 4
XH800PJ
3, 4
XH800PE
3, 4
TL800NE
3, 4
XS1250CE
3, 4
XS1250SE
3, 4
TL1250NE
3, 4
XS1600CE
3, 4
XS1600SE
3, 4
800
630, 800
630, 800
630, 800
1000, 1250
1000, 1250
1000, 1250 1600
1600
690
690
8
690
250
690
8
690
690
8
690
690
8
690
690
8
690
690
8
690
690
8
690
690
8
690
690
8
20
42
65
65
65
100
-
45
65
85
85
100
125
50
20
42
65
65
65
100
-
45
75
125
125
125
150
-
20
35
50
50
50
85
-
25
45
65
65
85
100
-
45
75
125
125
125
150
-
20
35
50
50
50
85
-
45
65
85
85
100
125
-
10
21
33
33
33
50
-
23
33
43
50
50
63
25
10
21
50
50
50
50
-
34
57
70
70
70
113
-
10
18
25
25
25
43
-
19
34
50
50
65
75
-
34
57
65
65
70/65
113
-
10
18
25
25
25
43
-
34
50
65
65
75
94
-
10
65
85
50
85
10
65
85
15
75
150
15
50
85
15
65
85
15
75
150
20
50
85
20
85
125
B
A
B
B
B
B
B
B
B
-
-
-
-
-
-
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
-
-
-
-
-
-
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
-
>1600
Visit www.terasaki.com for details of MCCBs up to 2500A
800
SECTION 8
800
-
273
210
280
103
9.7
12.5
273
210
280
103
9.4
12.2
273
210
280
103
9.7
12.5
370
210
280
140
25.8
33.5
370
210
280
120
22.0
28.0
370
210
280
120
22.0
28.0
370
210
280
140
26.0
33.7
370
210
280
140
27.0
35.0
370
210
280
140
27.0
35.0
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
page 134
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
RATINGS AND SPECIFICATIONS
TemBreak Switch-Disconnectors Electrical Characteristics to IEC 60947-3, EN 60947-3, AS/NZS 3947-3
Frame
Quantity
Unit
Condition
Model
Number of Poles
800
1250
XS800NN
3, 4
XS1250NN
3, 4
800
1250
690
250
690
8
690
250
690
8
15
9.6
AC-23A
DC-22A
32
15
AC-23A
DC-22A
Nominal current ratings
Ie
(A)
Rated operational voltage
Ue
(V)
Rated insulation voltage
Rated impulse withstand voltage
Ui
Uimp
(V)
(kV)
Rated short-circuit making capacity
Rated short-time withstand current
Utilisation category
Icm
Icw
(kA peak)
(kA rms)
Electrical characteristics
AC 50/60 Hz
DC
0.3 Seconds
AC
DC
Installation
Front connection (FC)
Attached terminal bar (FB)
Solderless terminal (cable clamp)
Rear connection (RC)
Plug-in (PM)
Draw-out (DR)
DIN rail mounting (DA)
Dimensions
Weight
-
•
•
•
•
•
h
w
(mm)
(mm)
d
w
(mm)
(kg)
3 pole
4 pole
3 pole
4 pole
-
•
•
•
273
210
280
103
9.4
12.2
370
210
280
120
20.4
26.4
•
•
•
•
Operation
SECTION 8
Toggle operation
Door mounted (HP) / breaker mounted handle (HB)
Motor operation (MC)
page 135
Standard
•
Optional
- Not Available
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
1600
XS1600NN
3, 4
1600
690
250
690
8
45
20
AC-23A
DC-22A
-
•
-
•
370
210
280
140
24.9
32.9
•
•
SECTION 8
page 136
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
OPERATING CHARACTERISTICS
SECTION 8
800A Frame MCCBs
page 137
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
OPERATING CHARACTERISTICS
1250A and 1600A Frame MCCBs
SECTION 8
page 138
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
ELECTRICAL CONTROL USING INTERNALLY MOUNTED
ACCESSORIES
Shunt Trip
(SHT)
Auxiliary Switch
(AX)
Remote tripping of the breaker
Electrically indicates On/Off status of the
breaker.
Undervoltage Trip (UVT)
Alarm Switch
Automatically trips the breaker when the
circuit voltage falls below pre-set value.
Remote tripping of the breaker is also
possible.
Note: The UVT controller is installed
externally, when provided with AC UVT.
(Refer to Dimensions)
Note: The SHT and UVT cannot be
mounted in the same breaker.
SECTION 8
Overview of Internally Mounted Accessories
page 139
(AL)
Electrically indicates when the breaker is
in the "Tripped" state.
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
ELECTRICAL CONTROL USING INTERNALLY MOUNTED
ACCESSORIES
Valid Combinations of Internally Mounted Accessories
Accessory Combinations
Accessory Combinations for Plug-in MCCBs
SECTION 8
The arrangements shown above represent the view
on the arrow, that is, looking at the MCCB body
from the rear.
page 140
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
ELECTRICAL CONTROL USING INTERNALLY MOUNTED
ACCESSORIES
SECTION 8
Connection Diagrams and Terminal Numbers
Ratings of Auxiliary Switches (AX) and Alarm Switches (AL)
page 141
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
ELECTRICAL CONTROL USING INTERNALLY MOUNTED
ACCESSORIES
Operation of Auxiliary and Alarm Switches
Ratings of Shunt Trips
Ratings of Under Voltage Trips
If the UVT is for AC use, an external controller will be installed. The controller is fitted to the left
side of the breaker as standard. The controller may be installed separately if required (please specify
location). Separate installation is necessary when mechanical interlocks are fitted. UVT controllers
incorporating time delay units are also available (contact us for details). Refer to dimensions of
terminal blocks for the mounting positions of UVT controllers.
SECTION 8
Connection of UVT Controller
Termination of Control Wiring
Leads for internally mounted accessories can be connected
to the terminal block. Each terminal block has six terminals.
Terminal arrangements are standardised. Refer to
dimensions for standard terminal arrangements.
page 142
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
SECTION 8
ELECTRICAL CONTROL USING MOTORISED OPERATION
page 143
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
ELECTRICAL CONTROL USING MOTORISED OPERATION
SECTION 8
page 144
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
OPERATING HANDLES
Door Mounted Handle
ER
Handle unit
C
RO
Optional
key lock
Door Mounted Handle with Optional Keylock
The door mounted handle is
used to operate a circuit breaker
mounted inside a cubicle from
outside the door. It consists of
an operating mechanism that
Operating
is mounted on the breaker,
unit
an operating handle that is
mounted on the door, and a shaft
Anti-tamper
that transmits the turning force
sleeved
from the handle to the operating
extensions
unit. The shaft can be cut to the
required length.
The appearance and operation
of this handle match those of
the door mounted handle
for Tembreak 2 MCCBs
(details in Section 5).
SECTION 8
This means that a switchboard
containing a combination of
TemBreak and TemBreak 2
MCCBs from this catalogue can
be operated with external operating
handles which all look the same,
and work the same way.
page 145
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
OPERATING HANDLES
Breaker Mounted Handle
SECTION 8
page 146
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
INSULATION ACCESSORIES
Terminal Covers
Terminal covers prevent exposure of terminals and other live parts.
Terminal Covers for Front Connection.
Terminal Covers for Rear Connection and Plug-in.
Interpole Barriers
SECTION 8
Interpole barriers provide maximum insulation between phases at the terminals of the MCCB.
They can not be fitted at the same time as any of the terminal covers. Interpole barriers can
easily be fitted to either end of an MCCB.
Interpole Barriers
page 147
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
TOGGLE ACCESSORIES
Toggle Extension
The toggle extension provides extra leverage for the operator when performing manual ON,
OFF and RESET operations.
Toggle Extension
Toggle Lock
The toggle lock enables padlocking of the MCCB in either the ON or OFF position. Padlocks
are not supplied.
SECTION 8
Note: Fits up to three padlocks
Toggle Lock
Key Lock
MCCBs , including those fitted with door mounted handles and some motor operators can
be supplied with Castell locking systems. Contact us for details.
Door Flange
A door flange provides a neat finish for the toggle cutout on the outside of the panel door.
page 148
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
MECHANICAL INTERLOCKS
Rear Interlocks
Rear interlocks consist of a mechanism mounted at the back of each MCCB of an adjacently
mounted pair. The interlock inhibits the closure of one MCCB if the other is already in the
ON position. MCCBs cannot be mounted directly to a flat plate, but are installed on a frame
to ensure space for the interlock mechanism.
Two MCCBs or switch-disconnectors of the same frame size may be rear interlocked.
An operating handle or motor operator can be fitted to an MCCB with rear interlock.
Wire Interlock
Wire interlocks consist of two mechanisms connected by a cable. The mechanisms are mounted
on the back of two MCCBs located at a distance from each other which is limited by the length
and bend radius of the cable. The mechanisms inhibit the closure of one MCCB if the other is
already in the ON position. MCCBs cannot be mounted directly to a flat plate, but are installed
on a frame to ensure space for the interlock mechanism.
Any two of the TemBreak MCCBs or switch disconnectors featured in this catalogue may
be wire interlocked.
An operating handle or motor operator can be fitted to an MCCB with rear interlock.
TemTransfer Automatic Changeover Controller
SECTION 8
TemBreak MCCBs can be configured to provide automatic supply changeover. They are
compatible with the TemTransfer changeover controller. Refer to section 5 for details.
Front Mechanical Interlock
Front interlocks are manually operated toggle locking devices which can be installed between
two adjacent MCCBs. Depending on the position of the interlock, one or other of the MCCBs
is inhibited from being in the ON position.
Two MCCBs or switch-disconnectors of the same frame size may be front interlocked.
Operating handles and motor operators cannot be fitted to MCCBs with front mechanical
interlocks.
page 149
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
INSTALLATION
Connection of Busbars and Terminated Cables
This method is standard for 800A frame models. Solid conductors or cables terminated
with compression terminals can be used.
Connection of Large Conductors and Multiple Conductors
Terminal bars are terminal extensions which can be fitted to line or load side terminals
and are used to connect large conductors and multiple conductors. Optional for 800A
frame, standard for 1250A and 1600A frame models.
SECTION 8
page 150
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
INSTALLATION
Termination in a Separate Compartment
Rear connections allow termination of conductors in a different switchboard compartment
to the MCCB body. Optional.
SECTION 8
Rear Connections for 800A Frame MCCBs
Rear Connections for 1250A and 1600A frame MCCBs
page 151
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
Plug-in Mounting
The plug-in mounting system allows fast replacement of the MCCB body without the need
to disturb the terminations. Solid conductors or cables terminated with compression
terminals can be used. Plug-in mounting is available for 800A and 1250A frame MCCBs.
SECTION 8
page 152
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
Drawout Mounting
SECTION 8
Two types of drawout mounting system are used, depending on the frame size of the MCCB.
page 153
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
Insulation Distances
Attention
80
SECTION 8
page 154
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
Standard Installation Environments and Special Treatments
SECTION 8
Fungus Moisture
Proof Breaker
page 155
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
Power Consumption
SECTION 8
page 156
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
DIMENSIONS
SECTION 8
XS800NN, XS800NJ, XS800SE, XH800SE, XH800PJ, XH800PE
page 157
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
DIMENSIONS
XS1250NN, XS1250CE, XS1250SE
SECTION 8
page 158
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
DIMENSIONS
SECTION 8
XS1600NN, XS1600CE, XS1600SE
page 159
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
DIMENSIONS
TL-800NE, TL-1250NE
ASL: Arrangement Standard Line
HL : Handle Frame Centre Line
Front connected
Drilling plan
184
ASL
ASL
28 18
154
170
140
370
ASL
88
8
140
210
ø9
70
A
70 70 70
105
175
280
45
4P
3P
HL
68
Extension handle
(removable)
170
13
200
13
A 31
Conductor
overlap, max.
33 32 15
8
4P
HL
88
Mounting
3P hole
HL
ø13
17
80
46
140
M8 Mounting screw
191
Breaker type
A
B
TL-800NE
10
10
TL-1250NE
14
12
Rear connected with motor operator
Drilling plan
4P
Panel cutout
4P
3P
3P
Insulator
40
70
230
115
296
70
70
ASL
98
113
45
ø13
70
Conductor
Soft plastic tubing,
overlap, max.
ø50, to be provided on
center pole and neutral pole of
vertical terminal type for insulation.
262.5
226
75
11(max.) 4.5
Mounting plate
19
ASL
111
15 32 8
B
140
73 71 27 86
154
184
13
114 70
ASL
ø9
262.5
HL
M8 Mounting
screw
3P
HL
6
18
4P
HL
R
HL
ø9
70
81
• Panel cutout dimensions
shown give an allowance of
1.5 mm around the handle
escutcheon.
300
ø15 for accessory wiring when necessary
Note: In the standard shipment mode, both terminals on the line side and
the load side are in horizontal direction.
For the vertical arrangement, specify it when ordering.
SECTION 8
Plug-in
Mounting block
(XDM8)
3P
HL
Mtg. Angle
3P
HL
4P
HL
90
90
Drilling plan
4P
Mtg. Angle
3P
26
4P
M10 Mounting screw
Accessory
connection block
HL
70
Conductor overlap, max.
ø13
140
210
70 70 70
175
105
280
94
94
21
199
70
64
64
25
58
147
8
32
85
15
45
70
62 85
ASL
21
169
ASL
26
18
144
13
114
ASL
21
25
58
15
158
18
ø11
90
page 160
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
DIMENSIONS
UVT Controller/
OCR Controller
A
SECTION 8
Door Mounted Handle
page 161
B C
OCR controller
57.5 45 59
UVT controller
81.5 69 83
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
DIMENSIONS
Breaker Mounted Handle
Toggle Extension
SECTION 8
page 162
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
DIMENSIONS
Terminal Covers for Front-Connections
Terminal Covers for Rear Connections and Plug-in Connections
SECTION 8
Interpole Barriers
page 163
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
DIMENSIONS
Front Interlock
Rear Interlock
SECTION 8
page 164
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
DIMENSIONS
Wire Interlock
SECTION 8
Terminal Blocks
page 165
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
DIMENSIONS
Door Flange
Panel Cutout for Adjustment Dials
SECTION 8
page 166
TEMBREAK MOULDED CASE CIRCUIT
BREAKERS
DIMENSIONS
Toggle Operation and Dimensions
SECTION 8
Position of Trip Button and Externally Mounted Accessories
page 167