PRICE BID ZONAL OFFICE STATE BANK OF PATIALA, PATIALA ELECTRICAL WORK (SUB-STATION) BILL OF QUANTITIES & PRICE SCHEDULE SUMMARY OF PRICES SECTION DESCRIPTION A H T SECTION B LT PANELS C LT CABLES D EARTHING AND MISC. ITEMS E LUMINAIRES F GENERATORS SUB TOTAL SERVICE TAX GRAND TOTAL RS. RATE IN WORDS AMOUNT IN RS. SECTION - A : H.T. SESCTION S.NO. DESCRIPTION QTY UNIT 1.01 GO SWITCH 1 supply, erection, testing & commissioning of 9 pin, 400A, G.O. Switch with 11Mtr pre stressed PCC pole (2Nos), 6 pin insulators, 3disc insulators, a set (3Nos) of LA`s, B-Class G.I. pipe 25mm dia 6mtr, G.O. Switch operating handle with locking arrangements, 3 Mtr cable protection G.I. pipe 80mm(OD) dia, 30A aerial fuse set, stay rod 19/20mm dia. 1.8 mtr long G. I. stay rod (4Nos), stay anchor M.S. plate 300mm x 300mm x 6mm thick with 20mm hole in the centre (4Nos), stay wire size 7/10SWG with G. I. thimble (4Nos), stay wire insulator(4Nos) etc complete with G.I. bolts, nuts, washers 2100mm long c-channel of size 75 x 40 x 6 mm (7Nos) including 50 x 6 mm flat D-clamps and all related hardware, earthing of LA`s with 25 x 5 mm G.I. earth strip and structure complete in all respect as required. RATE IN WORDS :2.0 XLPE INSULATED HT ARMOURED CABLE (LOOSE) Supply and layinf of circular aluminium conductor,conductor screened with extruded semicnfucting compound, XLPE insulated, insulation screened with extruded semiconducting combination in combinatyion with copper tape (0.3KA for 1 Sec.) cores laid up, FRLS PVC inner sheathed, galvanised steel strip armoured and overall FRLS PVC sheathed confirming to IS:7098/II/85 worrking voltage 11KV(UE) grade to laid loose in the existing trench/pipe a) Circular Aluminium conductor, conductor screened with extruded 120 semiconducting compound, XLPE insulated, insulation screened with combination in combination with copper tape (0.3KA for 1 sec.) cores laid up, FRLS PVC inner sheathed, galvanised steel strip armoured and overall FRLS PVC sheathed cable confirming to IS:7098/II/85 wirking voltage 11KV(YE) grade 150sqmm (Three Core) RATE IN WORDS :3.0 S/E OF HEAT SHRINKABLE CABLE END TERMINATION FOR 11 KV/6.6KV i Heat Shrinkable for cable size 120-185 sq mm (Indoor Type) 5 RATE IN WORDS :ii Heat Shrinkable for cable size 120-185 sq mm (Outdoor Type) 1 RATE IN WORDS :4.0 TRANSFORMER 1 Supply/Test/Commissioning of Dry Type 1000KVA, 11/0.433KV, 3 Phase, 50Hz, Dyn 11 vector group, copper wound, class - F insulation associated with winding temprature indicator /controller actuated by means of resistance temprature detector embedded in LV windings, Indoor type Transformer with Approximately 5% impedance, tapping for off load operation on HV side in steps of +/2.5%, +/- 5% - 7.5%, having cable boxes on HV and LV side with neutral brough out separately including supplying & laying of copper conductor multicore YWY cable from transformer to VCB for safety tripping and Transformer suitably mounted on M.S. Channel i/c supplying and suitable M.S. Channel with all accessories and confirming to IS 11171:1985 & as per specifications complete in all respect as required at site. RATE IN WORDS :- Page 2 of 25 Each MTR Each Each Each RATE AMOUNT S.NO. DESCRIPTION 5.0 QTY UNIT VCB Supply/Test/Commissioning of indoor type floor mounted metal clad, 11KV VCB panel with one No. VCB, totally enclosed & fully interlocked, Horizontal drawout, Vertical Isolation type breaker as per IS 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, manually chatfed and auto/manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz, A.C. supply with short circuit fault level of 350MVa, complete with self contained, fuylly interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 800A capacity, breaker featured wit mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxillary switchgears and accessories i/c connections suitable for 3 x 150 sq mm XLPE 11 KV cable (cable entry from bottom/top). Closing Coil Voltage 24 Volt DC Auxiliary contact 4NO+4NC CTR 100/5+5A ---------- 3Nos Core - 1 Metering : 15VA, CL-1.0 Core - 2 Protection : 15VA, 5P10 STR - 26 kA for 3sec. PTR : 11KV/Rt.3, 110V AC/Rt.3, ratio-------------3Nos Resin cast, 1 phase draw out PT with fuses Class of accuracy : 1.0, Burden - 100VA 1.2 cont. 1.8 for 8 Hrs. Digital Ammeter, Cl-1.0, 96sqmm with ASS --- 1Nos Digital Voltmeter, Cl-1.0,96sqmm with VSS ---1Nos Phase Indicating Lamps LED type------1Set Breaker - ON Red--1Nos Breaker - OFF Green----- 1Nos Spring Charged - Blue----1Nos Trip Circuit Healthy - Clear---------1Nos Auto Trip Indicating - Amber -----1Nos Hooter -------1Nos 8Window annunciator -------- 1Nos TNC Switch - Spring Return Type --------- 1Nos Push button for trip circuit healthy -------- 1Nos Local/Remote Selector ----------1Nos Emergency trip push button ---------1Nos Control fuses/MCB for AC or DC supply--9Nos Space Heater 100W -------------1Nos 2NosThermostat - 1C/O --------1Nos Panel Lamps with toggle switch---- 1Nos Single phase three pin plug & socket--- 1Nos Power Pack (240V AC to 24 V DC) ------- 1Nos Protection Relay 3 O/C + 1E/F IDMTL with high set------ 1Nos Master trip Relay -------1Nos Auxiliary relay for Tr. fault---------- 1Nos RATE IN WORDS :- Page 3 of 25 1 Each RATE AMOUNT S.NO. DESCRIPTION 5.0 6.0 i a) b) ii iii iv v vi vii viii QTY UNIT CT/PT AND TRI-VECTOR METER Supply/Fixing of 11KV CT - PT Metering Cubical Indoor, Dry Type, Three Phase Four Wire, mounted with CT & PT as detail given below :a) 3 Nos CTs of Ratio 100/5A of Rated Burden 15VA, Accuracy Class 0.2S, With insulation level (12KV/28KV/75KV)as per IS2705/1992 consisting of two metering core suitable forABT/Check Meter. b) 1 NosPT 11KV/110Volts of Rated Burden 50VA, Accuracy Class0.2 with insulation level (12KV/28KV/75KV) as per IS 3156/1992. c) tri-Vector Meter, Accuracy Class 0.2 as per PSPCl norms RATE IN WORDS :SAFETY EQUIPMENT Providing & fixing danger plates made of mild steeel at least 2mm thick and vitreous enameled white on both sides & with inscriptions in sinnal red colour on front side as read. a) High Voltage Size 250 mm x 200 mm b) Medium Voltage Size 200 mm x 150 mm High Voltage Size 250 mm x 200 m RATE IN WORDS :Medium Voltage Size 200 mm x 150 mm RATE IN WORDS :Providing & fixing carbon dioxide (CO2) type fire extinguishers confirming to IS 2878: 1976 and cylinders fully charged of following capacity. A) 4.5 Kg (Panel Room - 1, TR. - 1, VCB - 1 & Metering Room - 1) RATE IN WORDS :Supply and fixing of Foam Fire Extinguishers, Portable type 9 Ltr capacity hanged on wall with bracket complete as required. (Near DG Set - 2 Set) RATE IN WORDS :Supply and fixing of safety instriction chart in word duly framed with 5 mm thick glass as required. (Approx. front area 1.20 sq mtrs.), Panel Room -1 & VCB Room -1 RATE IN WORDS :Providing of set of 4 Nos. 9.5 Ltrs. Capacity GI bucket painted in post office red colour withy prior coat of red oxide paint and written with white paint "FIRE" and mounted on MS angle iron frame with bracket of appropriate size and capacity i/c filling sand etc. (Near DG Set -1Set) RATE IN WORDS :Providing First Aid Box as approved bt St. John Ambulance Brigade/Indian Red Cross conforming to IS 2217 :1963 (Panel Room-1 & VCB Room -1) RATE IN WORDS :Supply & fixing shock treatmernt chart duly mounted on a wooden frame with 5 mm thick glass as required. (Approx. front area 1.20 sq mtr) Panel Room -1 & VCB Room -1 RATE IN WORDS :Prodiding of rubber mat 1 Mtr wide X 2 Mtr long and 3 mm thick to withstand 15 KV dielectric strength as per IS 5424 :1969 RATE IN WORDS :GRAND TOTAL SEC-A RATE IN WORDS :- Page 4 of 25 1 SET 10 Each 10 Each 4 Each 1 Set 2 Each 1 Set 2 Each 2 Each 8 Mtr RATE AMOUNT SECTION - B : L.T. PANELS S.NO. DESCRIPTION OF WORK 1.0 LT PANELS Supply/Receiving/handling/erection/testing/commissioning of cubicle type panels fabericated out of 1.6/2 mm rust inhibited CRCA sheet steel bolted and modular construction complete with incoming and out-going feeders, bus bars of electrolytic grade aluminium duly insulated with heat shrinkable PVC colour coded sleeves and supported on DMC/SMC supporters, outgoing feeders upto 63A brought out to cable alley in the form of terminals and above ratings with bus-bar links. All terminals are marked permanently. Meters, indicating lamps shall be as per specified and shown in SLD. PCC shall be totally enclosed dust and vermin proof construction with heavy duty neoprene gaskets. The floor mounting panels shall be provided with mounting channels. Panels shall incorporate double aluminium earthing bus, cable alleys, bus bar chambers, bus interconnections. The panel shall be enamel (powder coated) painted. The panel shall be provided with name pate for all incoming outgoing feeders, danger plate, panel shall be provided with steel lock with two key for each panel and the key shall be common for all compartment/doors. The mechanical /electrical interlocking shall be provided where ever it is required . Provide de-interlock facility in off position. If any material not specifcally mentioned in the BOQ/SLD but required for satisfactorily functionig of the panel shall be in the scope of contrctor without any price implication. Panel should be suitable for 50KA short circuit rating and complete in all respect as required by the Engineerin charge. NOTE :- Before manufacturing the panel G.A. drawing to be provided for approval and also control wiring diagrame to be submitted to the owner on completion of work. MAIN L.T. PANEL <MLTP> RATE IN WORDS :INCOMER (MAINS) 1600A 4P,55KA,ACB EDO Type,Micro Processor Based SR18 01 Nos R-Y-B Phase Indicator with 2A SP MCB 01Set 2 Element O/C and 1 Element Earth fault relay 01Set Standby Earth Fault Relay 51NS 01 Nos ON, OFF Trip SC TCH Indication etc 01Set 6 Window Annunciator 01Set 6A TPN MCB, 10kA, Curve-C 02 Nos Digital Multifuction Meter with 3Nos 2A SPMCB (V,A F,Pf,KW,KWH) 01Nos CT 1600/5A , CL-SP10, Burden 15VA 03Nos CT 1600/5A , CL-SP0.5, Burden 15VA 03Nos CT 1600/5A, CL-SP0.5, Burden 15VA 01Nos INCOMER 365KVA DG SET 1600A 4P,55KA,ACB EDO Type,Micro Processor Based SR18 01 Nos R-Y-B Phase Indicator with 2A SP MCB 01Set 2 Element O/C and 1 Element Earth fault relay 01Set ON, OFF Trip SC TCH Indication etc. 01Set A i ii iii iv v vi vii viii ix x xi xii B i ii iii iv Page 5 of 25 QTY. UNIT 1 Nos. RATE AMOUNT S.NO. DESCRIPTION OF WORK v Digital Multifuction Meter with 3Nos 2A SP MCB (V,A,F,Pf,KW,KWH) 01Nos CT 800/5A CL-SP10, Burden 15VA 03Nos CT 800/5A CL-SP 0.5, Burden 15VA 03Nos INCOMER 640KVA DG SET 1000A, FP, ACB, EDO Type 50kA, with Microprocessr based SR18 01Nos R-Y-B Phase Indicator with 2A SP MCB 01Set 2 Element O/C and 1 Element Earth fault relay 01Set ON, OFF Trip SC TCH Indication etc. 01Set Digital Multifuction Meter with 3Nos 2A SP MCB (V,A,F,Pf,KW,KWH) 01Nos CT 1000/5A , CL-SP10, Burden 15VA 03Nos CT 1000/5A , CL-SP 0.5, Burden 15VA 03Nos BUS COUPLER 1000A, 4P, ACB, EDO Type 01Nos ON, OFF Indication ON OFF Push Button 01Set BUS-BAR TPN aluminium bus-bar of minimum of 1600Amp. Capacity with heat shrinkable coloured sleeves and i/c DMC.SMC bus-bar cross section , size supporters & their spacing etc. for withstanding fault level of 31MVA for 1 Sec. 1Set vi vii C i ii iii iv v vi vii D i ii E i F i ii iii iv v vi vii 1.01 i ii iii iv v vi OUT GOINGS 800A TP MCCB 50kA with Rotory Handle & Thermal Magnetic Release 01Nos 630A TP MCCB 50kA with Rotory Handle & Thermal Magnetic Release 03Nos 200A TP MCCB 25kA,with Rotory Handle & Thermal Magneic Release 08Nos 100A TP MCCB 25kA,with Rotory Handle & Thermal Magneic Release 01Nos 80A TP MCCB 25kA,with Rotory Handle & Thermal Magneic Release 01Nos 40A TPN MCB 10kA, Type Curve - C, 07Nos 63A TPN MCB 10kA, Type Curve - C, 02Nos CAPACITOR CONTROL PANEL <CCP> 285kVAR RATE IN WORDS :INCOMER 630A TP MCCB 50kA with Rotory Handle & Thermal Magnetic Release 01Nos R-Y-B Phase Indicator with 2A SP MCB 01Set CT 600/5A , CL-SP10, Burden 15VA 03Nos Digital Multifuction Meter with 3Nos 2A SP MCB (V,A,F,Pf,KW,KWH) 01Nos 15 kVAr with 7% Detuned Copper Reactor 480V, 50Hz + 20kVAr Ultra Heavy Duty Capacitor (Effective 15kVAR) + 63A,TP 16kA MCB capacitor bank 01 Nos 50 kVAr with 7% Detuned Copper Reactor 480V, 50Hz + 60kVAr Ultra Heavy Duty Capacitor (Effective 50kVAR) + 125A, TP 25kA MCCB + capacitor duty contactor MOC-50 capacitor bank 03 Nos Page 6 of 25 QTY. UNIT 1 Nos. RATE AMOUNT S.NO. DESCRIPTION OF WORK vii 25 kVAr with 7% Detuned Copper Reactor 480V, 50Hz + 30kVAr Ultra Heavy Duty Capacitor (Effective 25kVAR) + 63A, TP 16kA MCB + capacitor duty contactor MOC-25 capacitor bank 04 Nos 10 kvar 7% Detuned Copper Reactor 480V, 50Hz + 12.5kVAR Ultra Heavy Duty Capacitor (Effective 10kVAR) + 40A, TP 16kA MCB + capacitor duty contactor MOC- 12.5 capacitor bank 01 Nos 5 kvar 7% Detuned Copper Reactor 480V, 50Hz +7.5KVAR Ultra Heavy Duty Capacitor (Effective 5kVAR) + 32A, TP 16kA MCB + capacitor duty contactor MOC -8.5 capacitor bank 02 Nos Auto/Manual switch, , ON ,OFF indicator & Push Button 10Sets 12 Step APFC Relay 5A, 415Volts, Digital 01Nos FLOOR PANEL GROUND & FIRST FLOOR Incomer -200A TPN MCCB 25kA with Thermal Magnetic Release 01Nos CT - 200/5A, 15VA, CL -0.5 03Nos Phase indicator R-Y-B with 2A SP MCB 03Nos Digital V I F Meter 01Nos Busbar Al. TPN 200A with coloured PVC sleeve 01Set OUT GOINGS 63A TPN MCB 10kA Type-C 10Nos 40A TPN MCB 10kA Type-C 04Nos RATE IN WORDS :FLOOR PANEL SECOND & THIRD FLOOR Incomer -200A TPN MCCB 25kA with Thermal Magnetic Release 01Nos CT - 200/5A, 15VA, CL -0.5 03Nos Phase indicator R-Y-B with 2A SP MCB 03Nos Digital V I F Meter 01Nos Busbar Al. TPN 200A with coloured PVC sleeve 01Set OUT GOINGS 63A TPN MCB 10kA Type-C 12Nos 40A TPN MCB 10kA Type-C 04Nos RATE IN WORDS :STREET LIGHT PANEL viii ix x xi 1.02 i 1.02 i 1.03 Page 7 of 25 QTY. UNIT 2 Nos. 2 Nos. RATE AMOUNT S.NO. DESCRIPTION OF WORK STREET LIGHT PANEL WITH TIMER S/E/T & Commissioning of Microprocessor Based Street Light Controller with digital time switch daily programmed with stand by lithium battery with back up of 6 years with minimum time between 2 switching operations is 1 minute, 3 nos, three pole, power contactors 40A, with coil voltage 220-230V AC with 1 no. aux. contactor 6A (2NO + 2NC) with coil voltage 220V AC, 3 nos MCB 2Pole 40A (Curve-C, 10kA) and power wiring with single core PVC insulated FRLS cable 10 Sq mm and control wiring with PVC insulated FRLS cable 1 sq mm, 1 no. two position selector switch to bypass timer and other accessories and petty material (din rail, 2 nos 4pole bakalite terminal strip 63A , 440V AC, required nuts & bolts) should be fixed on balalite sheet 6 mm thick to mounted in a IP 54 flush mounting powder coated sheet metal (1.6 mm thick) cabinet having size 450 mm x 600 mm x 150 mm to switch "ON" all the three phase andswitch "OFF" 3 phases prefixed timings complete in all tespect as per satisfaction of Engineer-in-charge. I II RATE IN WORDS :S/I/T/C of Incomer to above said panel (Street light Panel) 63A TPN MCB Curve - C 1nos RATE IN WORDS :S/I/T/C/ of Spare out goings appart from street light panel provide 32A DP MCB Curve - C 2nos RATE IN WORDS :TOTAL SECTION – B : RATE IN WORDS :- Page 8 of 25 QTY. UNIT 1 Each 1 Each 2 Each RATE AMOUNT SECTION - C : L.T. CABLES SUPPLY/LAYING OF CABLES S.NO. DESCRIPTION QTY. UNIT RATE 1.0 Supply & laying of aluminium conductor XLPE PVC i ii iii iv v vi vii viii ix x xi sheathed armoured and served cable to be laid loose in the existing trench or pipe as per PWD General Specifications. RATE IN WORDS :Aluminium conductor XLPE PVC sheathed armoured and served cable working voltage 1100volts grade 16 sq mm (4 Core) for lift & street light panel RATE IN WORDS :Aluminium conductor XLPE PVC sheathed armoured and served cable working voltage 1100volts grade 50 sq mm (3.5 Core) for Main Panel to Public Health Panel & Common Panel RATE IN WORDS :Aluminium conductor XLPE PVC sheathed armoured and served cable working voltage 1100volts grade 95 sq mm (3.5 Core) for Main Panel to Floor Panel RATE IN WORDS :Aluminium conductor XLPE PVC sheathed armoured and served cable working voltage 1100volts grade 240 sq mm (3.5 Core) for Main Panel to Mechanical Ventilation Panel RATE IN WORDS :Aluminium conductor XLPE PVC sheathed armoured and served cable working voltage 1100volts grade 400 sq mm (3.5 Core) from TR MAIN LT Panel RATE IN WORDS :Copper conductor XLPE PVC sheathed armoured and served cable working voltage 1100volts grade 2.5 sq mm (4 Core) from TR to Main LT Panel Neutral CT and Main LT Panel to AMF Panel RATE IN WORDS :Copper conductor XLPE PVC sheathed armoured and served cable working voltage 1100volts grade 2.5 sq mm (3 Core) for Bush lights etc. RATE IN WORDS :Copper conductor XLPE PVC sheathed armoured and served cable working voltage 1100volts grade 2.5 sq mm (7 Core) for DG Set Panel to Main Panel & Tr. To VCB RATE IN WORDS :Copper conductor XLPE PVC sheathed Un-armoured and served cable working voltage 1100volts grade 6.0 sq mm (4 Core) for LDB`s etc. RATE IN WORDS :Copper conductor XLPE PVC sheathed Un-armoured and served cable working voltage 1100volts grade 10.0 sq mm (4 Core) for Flor AC DB`s & PDB`s 650 MTR 100 MTR 220 MTR 350 MTR 650 MTR 225 MTR 200 MTR 250 MTR 500 MTR 450 MTR RATE IN WORDS :PVC insulated copper conductor single core FRLS 2000 cable (ISI) marked overall 2.5 sq mm, 1100Volts grade. (Green Colour as Earth wire & other colour for Circuit wireor sub mains) Page 9 of 25 MTR AMOUNT S.NO. xii xiii xiv 2.0 i ii ii iv v vi vii viii ix x 3.0 i DESCRIPTION QTY. UNIT RATE RATE IN WORDS :PVC insulated copper conductor single core FRLS 2000 cable (ISI) marked overall 4.0 sq mm, 1100Volts grade. (Green Colour as Earth wire & other colour for Circuit wire or sub mains) RATE IN WORDS :PVC insulated copper conductor single core FRLS 1000 cable (ISI) marked overall 6.0 sq mm, 1100Volts grade. (Green Colour as Earth wire & other colour for Circuit wire or sub mains) RATE IN WORDS :PVC insulated copper conductor single core FRLS 500 cable (ISI) marked overall 10.0 sq mm, 1100Volts grade. (Green Colour as Earth wire & other colour for Circuit wire or sub mains) RATE IN WORDS :- PVC, HDPE PIPES : PIPES MTR MTR MTR & PVC FLEXIBLE Supply and erection of PVC pipes & HDPE pipes (fire retardent) for wiring puposes incliding bends, inspection boxes erc., where necessary including other petty material as per PWD General Specifications 2010 : Heavy guage PVC conduit pipe 20mm dia (ISI marked 2mm thick) On Surface RATE IN WORDS :Heavy guage PVC conduit pipe 25m dia (ISI marked 2mm thick) On Surface RATE IN WORDS :Heavy guage PVC conduit pipe 32mm dia (ISI marked 2mm thick) On Surface RATE IN WORDS :Heavy guage PVC conduit pipe 40mm dia (ISI marked 2mm thick) On Surface RATE IN WORDS :Heavy guage PVC conduit pipe 50mm dia (ISI marked 2mm thick) On Surface RATE IN WORDS :Heavy guage PVC conduit pipe 20mm dia (ISI marked 2mm thick) Flushed RATE IN WORDS :Heavy guage PVC conduit pipe 25m dia (ISI marked 2mm thick) Flushed RATE IN WORDS :Heavy guage PVC conduit pipe 32mm dia (ISI marked 2mm thick) Flushed RATE IN WORDS :Heavy guage PVC conduit pipe 40mm dia (ISI marked 2mm thick) Flushed RATE IN WORDS :Heavy guage PVC conduit pipe 50mm dia (ISI marked 2mm thick) Flushed RATE IN WORDS :- 50 Mtr 100 Mtr 100 Mtr 100 Mtr 100 Mtr 50 Mtr 100 Mtr 100 Mtr 100 Mtr 100 Mtr 300 Mtr PVC FLEXIBLE PIPES : Supply and erection of PVC flexible pipe complete with compression glands, having locking arrangement, chec-nuts as required : PVC Flexible pipe 20 mm dia RATE IN WORDS :Page 10 of 25 AMOUNT S.NO. ii iii iv 4.0 i ii iii iv v vi vii viii ix 5.0 i DESCRIPTION QTY. UNIT RATE PVC Flexible pipe 25 mm dia RATE IN WORDS :PVC Flexible pipe 32 mm dia RATE IN WORDS :PVC Flexible pipe 40 mm dia RATE IN WORDS :- 200 Mtr 50 Mtr 50 Mtr 15 Nos 15 Nos 20 Nos 30 Nos 20 Nos 10 Nos 12 Nos 8 Nos 20 Nos 40 MTR 1 Each END TERMINATION supply & making indoor type end termination with brass single compression cable glands and aluminium lugs for following sizes of XLPE aluminium conductor cable of 1.1KV grade. 4 x 2.5 sq mm Cu. Ar. Cable RATE IN WORDS :7 x 2.5 sq mm Cu. Ar. Cable RATE IN WORDS :4 x 6.0 sq mm Cu. Ar. Cable RATE IN WORDS :4 x 10.0 sq mm Cu. Ar. Cable RATE IN WORDS :4 x 16 sq mm A2XFY power cable RATE IN WORDS :3.5 x 50 sq. mm A2XFY cable RATE IN WORDS :3.5 x 95 sq. mm A2XFY cable RATE IN WORDS :3.5 x 240 sq. mm A2XFY cable RATE IN WORDS :3.5 x 400 sq. mm A2XFY cable RATE IN WORDS :- CABLE TRAY Supplying and installing following size of perforated M.S. cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including nuts & bolts, painting suspenders etc. as required. 450mm width x 50mm depth x 2.0 mm thickness RATE IN WORDS :- CABLE TRAY BEND ii Supplying and installing following size of perforated M.S. cable tray bends (horizontal type 90 ° ) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including nuts & bolts, painting suspenders etc. as required. 450mm width x 50mm depth x 2.0 mm thickness RATE IN WORDS :- Page 11 of 25 AMOUNT S.NO. iii 6.0 DESCRIPTION CABLE TRAY VERTICAL BEND QTY. UNIT RATE Supplying and installing following size of perforated M.S. cable tray bends (vertical type 90 ° ) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including nuts & bolts, painting suspenders etc. as required. 450mm width x 50mm depth x 2.0 mm thickness RATE IN WORDS :- 1 Each 85 MTR 85 MTR 10 MTR 4 Each 1 Each 1 Each 3 Each 1 Each CABLE TRAY LADDER TYPE Ladder type cable tray shall consist of two longitudinal members (side rails) with transverse members (rungs) welded to the side rails. Rungs shall be spaced at 250mm on center. Width of the rung shall be 25mm, side rails and rungs shall be fabricated out of 2mm CRCA sheet steel and duly hot dipped zinc coated. No portion of the rungs shall protrude below the bottom plane of the side rails. Each rung must be capable of supporting cable load. The cable tray must be complete in all respect including coupling plates, G.I. bolts, nuts & washers etc. The cable tray shall be supported on angle of size of 40 x 40 x 5 mm (at every 1 meter distance) duly painted with 2 coats of red oxide and 2coats of enamel paint of required shade as per sight engineer. The cable tray fixing includes cable tray, cable tray bends, cable tray Tees, etc. complete in all respect. i ii iii iv v vi vii viii Cable Tray Size 600 mm width x 75 mm depth x 2mm thickness RATE IN WORDS :Cable Tray Size 300 mm width x 50 mm depth x 2mm thickness RATE IN WORDS :Cable Tray Size 150 mm width x 50 mm depth x 1.8mm thickness RATE IN WORDS :Cable Tray Bend Horizontal Size 600 mm width x 75 mm depth x 2mm thickness RATE IN WORDS :Cable Tray Bend Vertical Size 600 mm width x 75 mm depth x 2mm thickness RATE IN WORDS :Cable Tray Tees Size 600 mm width x 75 mm depth x 2mm thickness RATE IN WORDS :Cable Tray Bend Size 300 mm width x 50 mm depth x 2mm thickness RATE IN WORDS :Cable Tray Bend Size 150 mm width x 50 mm depth x 2mm thickness RATE IN WORDS :- Page 12 of 25 AMOUNT S.NO. 7.0 M.S STEEL DESCRIPTION QTY. UNIT RATE 1000 Kg 100 MTR M.S. Equal angle 40 x 5 mm for providing support to the cable tray including welding, cutting fixing in position, painting 2 coats of anti corrison and 2 coats of enamel paint duly approved, The rate includes all types hardware required for the job like welding rod, bolts, nuts, spring washer etc completein all respect as required. RATE IN WORDS :- 8.0 i PVC PIPE Providing, stringing out P.V.C. Pipes as per ISI-4985 casting along the Trenches and laying the same in trenches to correct alignment and gradients, cutting, jointing and testing including cost specials complete as per specifications. 75mm o/d pipe 6Kgf./sqcm RATE IN WORDS :TOTAL – C : RATE IN WORDS :- Page 13 of 25 AMOUNT SECTION - D : EARTHING AND MISC. ITEMS S.NO. DESCRIPTION 1.0 EARTH STATION COOPER Earthing with copper earth plate 600 x 600 x 3 mm thick including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long G.I (Class - A), with charcoal/ coke and salt as required including 3 meter copper earth collecting strip of size 25 x 5 mm. The contractor also required to submit the earth pit value, complete in all respect. (Tr. Neutral - 2, Gen Neutral -4, UPS -3 & Lift-2) 2.0 3.0 4.0 5.0 6.0 QTY UNIT RATE IN WORDS :EARTH STATION G.I Earthing with G.I. (Hot Dip) earth plate 600 x 600 x 6 mm thick including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long G.I (Class - A), with charcoal/ coke and salt as required including 3 meter copper earth collecting strip of size 50 x 6 mm. The contractor also required to submit the earth pit value, complete in all respect. (Tr.Body 2, Gen Body -2, LT Panel Body - 2, G.O. Switch -2, HT Metering-2) RATE IN WORDS :BUILDING LIGHTNING PROTECTION EARTH PIT Earthing with G.I. earth pipe 4.5 metre long 40mm dia including accessories and prodiding masonary enclosure with cover plate having locking arrangements with charcoal/coke and salt etc. as required complete in all respect including submission of earth value. (for LA`s) RATE IN WORDS :LIGHTNING SPIKE Providing & fixing of lightning conductor finial, made of 25 mm dia 300 mm long G.I. tube, having single prong at top, with 85 mm dia 6mm thick base plate including holesetc. Complete as required. RATE IN WORDS :LIGHTNING EARTH TAPE Providing & fixing of G.I. tape 20 x 3 mm (hot dip) on parapet or on surface of wall for lightning conductor complete as required including fixing hardware. The strip clamp /screw shall be fixed at a distance of 450mm. (for horizontal run) RATE IN WORDS :LIGHTNING EARTH TAPE Providing & fixing of G.I. tape 20 x 3 mm (hot dip) on parapet or on surface of wall for lightning conductor complete as required including fixing hardware. The strip clamp /screw shall be fixed at a distance of 450mm. (for vertical run) RATE IN WORDS :- Page 14 of 25 11 NOS 10 NOS 6 NOS 6 NOS 400 MTR 100 MTR RATE AMT. (Rs.) S.NO. DESCRIPTION 7.0 TEST LINK Providing and fixing testing joint made of 20 x 3 mm G.I. strip , 125 mm long, with 4Nos of G.I. bolts, nuts, chuck nuts and spring washeretc. Complete as required. The testing joint shall be made on vertical run at a height of 1200mm from zero level. RATE IN WORDS :EARTH TAPES/WIRES Supplying/fixing/straighteningof following sizes of earth strips duly clamped at distance of 450mm and joint must overlap by 100mm on each side of strip & tightened with 4 Nos of bolts &nuts with plane, spring washer.Further a test link to be provided on every earth pit by the contractor for the purpose of testing at appropriate place. Providing & fixing copper tape 20 x 3 mm thick ( on cleats @ 1 meter on wall of electrical shaft) complete as required (for UPS & Lift) RATE IN WORDS :Providing & fixing 25 x 5 mm copper strip on surface or in recess for connections as required including fixing material complete in all respect for neutral of transformer , DGsets (2 runs each) RATE IN WORDS :Providing & fixing 25 x 5 mm G.I. strip (hot dip) on surface or in recess for connections as required including fixing material complete in all respect.(2 runs along with cable tray in basement, for G.O. switch, floor panel and AC Panel ) RATE IN WORDS :50 x 6 mm GI earth strip for body of TR, Gen body, Main Electrical Panel & AC panel (2run alongwith cable tray in shaft). Floor panel earth to be tapped from cable trat earth strip. RATE IN WORDS :Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/recessed conduit/submain wiring/cable as required. RATE IN WORDS :METAL BOXES Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitablesize of phenolic laminated sheet cover in front including painting etc as required. 150mm x 75mm x 100mm deep RATE IN WORDS :200mm x 125mm x 100mm deep RATE IN WORDS :250mm x 150mm x 100mm deep RATE IN WORDS :300mm x 150mm x 100mm deep RATE IN WORDS :450mm x 150mm x 100mm deep RATE IN WORDS :600mm x 150mm x 100mm deep RATE IN WORDS :- 8.0 i ii iii iv v 9 i ii iii iv v vi QTY UNIT Page 15 of 25 4 NOS 50 MTR 100 MTR 300 MTR 120 MTR 50 MTR 20 Each 20 Each 15 Each 15 Each 10 Each 10 Each RATE AMT. (Rs.) S.NO. DESCRIPTION 10 SUB MAINS POWER WIRING Supply of Sub-Mains power wiring for DB, Sub-Mains to start from main Panel to LDB/PDB/UPSDB using 1100 Volts grade, multystrand, pvc insulated, copper conductor wiring /PVC insulated PVC sheathed cables shall be pulled/laid through pipe with wiring accessories such as bends, identification ferrules, etc. (NOTE- UPS earthing system must be isolated from power/lights system), Phase, Nuetral and Earth wire must run separate for all circuits from the DB. a) b) c) d) 11 QTY UNIT 4x6sq. mm copper cable PVC insulated PVC sheathed in 32mm PVC conduit (from MLTP to LDB's in Basement All wires need to be ferruled as per drawing in 32mm PVC conduit. Rate in Words : 4x6sq. mm copper armoured cable PVC insulated PVC sheathed in 32mm conduit along with 2x2.5sqmm copper PVC insulated earth wire (from FLOOR Panel to LDB's All wires need to be ferruled as per drawing. Rate in Words : 2x16sq. mm copper cable PVC insulated PVC sheathedin 40mm conduit along with 2x2.5sqmm copper PVC insulated earth wire (from UPS Panel to UPSDB & UPS to UPS Panel All wires need to be ferruled as per drawing. Rate in Words : 4x10sq. mm copper cable PVC insulated PVC sheathed in 40mm conduit along with 2x4sqmm copper PVC insulated earth wire from FLOOR panel to PDB's All wires need to be ferruled as per drawing. Rate in Words : LIGHT POINT WIRING Supplying/Laying/Commissioning of wiring and testing for light, fan, exhaust fan, 5A socket, etc. starting from the point control box to the outlet point, using 1.5 sq.mm copper conductors, multystrand, pvc insulated 1100 volts grade wiring/cables in concealed conduit wiring system, in ISI marked PVC conduit heavy duty including all conduit accessories such as bends, tees, draw Page 16 of 25 250 mtr 150 mtr 150 mtr 150 mtr RATE AMT. (Rs.) S.NO. DESCRIPTION QTY UNIT boxes, MS fan hook, Concealed light, GI Modular boxes (HOT DIP) for light point, fan point/regulator control boxes, together with wiring accessories such as 5A modular type switches, 3 pin 5A modular type sockets, batten holders (wherever required), including 2 x1.5 + 1x1.5 sq mm copper pvc insulated for point wiring and 2x2.5+1x2.5sqmm for circuit wiring are inclusive as per drawing. The conduit for point wiring & circuit wiring shall be separate. Identification ferrules at both ends of Phase & Nuetral, complete in all respects. Conduit being concealed either in ceiling slab/wall chase including making good and filling of chases with cement mortar etc. as per standard specifications and relevent drawings. Note : All wires of point wiring in the false ceiling area shall be 2 mtr excess from the slab/JB/Fan Box, so the joint can take within the light fixture. a) 12 a) c) One 3 pin 5A light plug socket outlet controlled by one no. 5A Modular type switch (Dependent to be fitted on existing modular plate only). Rate in Words : POWER/LIGHT/UPS SOCKETS : POWER SOCKETS S/F/Commissioning of 6 PIN 15A POWER SOCKETS Modular type sockets with 15A SP switch in a suitable M.S.Modular GI box, Including wires 2x4+1x1.0 sq mm (from DB to outlet points), in 25mm PVC conduit Heavy Duty, bends etc . Complete in all respect including ferruling as per drawing. Rate in Words : COMPUTER POINT SUPPLY (UPS SUPPLY) : Supply/Fixing/Commissioning of Computer point supply outlet point should comprises of 4 nos. 5A. 5pin Modular type sockets controlled by one 5A Modular switch and a Modular light indicator fixed on Modular GI box of suitable size, isolated earth terminal etc. and fixing shall be as per computer table design. including ferruling as per drawing Rate in Words : Page 17 of 25 10 Nos. 10 Nos. 20 Nos. RATE AMT. (Rs.) S.NO. DESCRIPTION QTY UNIT NOTE- The box shall have the provision of two module space for 2 in number RJ-45 & 2 in number RJ-11. where ever space becomes free should be filled with dummy. The rates are inclusive of 2x2.5+1x2.5sqmm copper conductor pvc insulate wire from UPSDB to Outlet point of UPS t.e. on computor table. 13 PVC HEAVY DUTY CONDUITS : Supplying/Laying/Commissioning of following PVC conduits heavy duty, bearing ISI marked with all accessories such as junction boxes, outlet boxes, bends, tees as required, the conduit being laid in ceiling slab or floor or RCC column or wall chase as required with hooks, etc.complete as required. All repair works must be completed mortar of required ratio. a) 50 mm Conduit PVC Heavy Duty ISI Rate in Words : 40 mm Conduit PVC Heavy Duty ISI Rate in Words : 32 mm Conduit PVC Heavy Duty ISI Rate in Words : 25 mm Conduit PVC Heavy Duty ISI Rate in Words : 20 mm Conduit PVC Heavy Duty ISI Rate in Words : LAN POINT Supply/laying of DIGILINK G600 CAT--6 wire consists of 4 pair copper solid, twisted pair duly shielded with tinned copper braiding as well as aluminium foil to prevent electro-magnetic interface. Cables must meet and axceed category 6/class E standards requirements in ISO/IEC11801, CENELEC EN50173 & TIA 568-B2-1 LAN wire should be ferruled on both ends and to be crimpped with RJ--45 at out let point b) c) d) e) 14 a) b) c) The LAN wire should be pulled through existing/raceway.The limit of the wires to be pulled from the conduits is as follows The rate are inclusive of wire, RJ-45 etc from HUB to OUT LET point on computor table 19 mm conduit one wire Rate in Words : 25 mm conduit two wire Rate in Words : 32 mm conduit five wire Rate in Words : Page 18 of 25 20 40 Mtr 60 Mtr 50 Mtr 75 Mtr 50 Mtr NOs. RATE AMT. (Rs.) S.NO. d) e) DESCRIPTION QTY UNIT 40 mm conduit ten wire Rate in Words : 50 mm conduit fifteen wire Rate in Words : TOTAL – D : Amount in Words : Page 19 of 25 RATE AMT. (Rs.) SECTION - E : LUMINAIRES SUPPLY/ERECTION OF FAN & LIGHT FIXTURES S.NO. QTY UNIT DESCRIPTION 1 Supply/installation/testing/commissioning of the following type of LED/ Non LED type light fixtures/ceiling fan/wall fan/exhaust fan etc. complete with all accessories etc. directly on wall/false ceiling/ceiling including connection with 1.5sq mm FRLS PVC insulated, copper conductor, single core cable and earthing with 1.5sq mm FRLS PVC insulated, copper conductor cable, PVC flexible conduit, end socket, 2" M.S.pipe etc. including repairing of walls with cement mortar. The light fixtures need to be connected with existing point wires and further number of light fixtures to be looped as per drawing. All LED fixtures material like suspension kit, LED`s Driver etc. shall be treated as inclusive. Complete in all respect as required. NOTE :- CONTRCTOR TO COUNT THE QUANTITY AND GET THE MAKE APPROVAL FROM SITE-INCHARGE AND THE PAYMENT FOR EXCESS MATERIAL WILL NOT BE MADE. i ii iii iv v viii ix x xi xii xiii Wipro LINEOS LED LM 31-211-XXX-57-XX, 21W Suspension Type including suspension material(Corridor Reception Area) RATE IN WORDS :Wipro LINEOS LED LM 30-211-XXX-57-XX, 21W, Recess Type (GM RNW) RATE IN WORDS :Philips Full Glow RC308B LED-30-6500 PSE OD WH OR Wipro Immaculate CRCO 10R 038HP57 (Office Area) System Lumen O/P -3000 & Total Power Consumption 40W or less (Work Stn. & Office Area) RATE IN WORDS :Wipro Stunner CRCO 17R013HP57 13W Recess mounted (for Waiting Area) RATE IN WORDS :Wipro Stunner CRCO 17S013HP57 13W surface mounted (for Stairwell & porch Area) RATE IN WORDS :Philips down lighter DN193B LED 12S-6500PSU WH OR Wipro CRDL 10R015HP60 (for Corridor Area) System Lumen O/P -1200 & Total Power Consumption 18W or less (All Corridor) RATE IN WORDS :Philips down lighter DN194B LED 15S-6500PSU WH OR Wipro CRDL 11R023HP57 (for Reception) System Lumen O/P -1200 & Total Power Consumption 18W or less (Reception Area) RATE IN WORDS :LEGERO LSR 1002-WW 34260400001 (Staff Entrance) RATE IN WORDS :Philips Green Spot Rangr BBS 313 1 X DLED - 5000 WH Lumen O/P -850 & Total Power Consumption 8W or less (Work stn., Mirror light & Conf. Room Area etc.) RATE IN WORDS :Philips Stratus LED SO7909 LED44S-5000PSE-ODSI fixture includes suspending mounting having system lumen 4400, Power Consumption 54W, CRI>80, PF>.9, THD < 20%, IEC complient for safety, performance & EMI including Electronic Driver, Extruded Aluminium Housing & high efficiency opal diffuser. Complete in all respect. (Conf. room) RATE IN WORDS :Wipro Aura Plus CRCO 13R038HP57 Recess mounting LED Luminair with PMMA diffuser, System lm o/p 3200 or more, system wattage 42w or less Philips Model Sereno RC869B LED 30S-6500PSE Recess Mounting RATE IN WORDS :DURLUM LUM-R0600-003 (LUMEO-R PENDENT Light) for Cafeteria RATE IN WORDS :xv Philips TMC 501 P 2 X LED with LED Tube Rod 20W 6500K OR Wipro WCO 12 -2208 with LED Tube Rod 20W (for Kitchen , Basement, Ele. Area, Pump Room, Record Room) RATE IN WORDS :xvi Philips TMC 501 P 1 X LED with LED Tube Rod 20W 6500K OR Wipro WCO 12 -1208 with LED Tube Rod 20W (for Kitchen , Basement, Ele. Area, Pump Room, Record Room) RATE IN WORDS :xvii Wipro Orbit LED LM 71 -531-XXX-60-XX 58W including suspension system, Driver etc (AGM Waiting Area, Entry to Work Stn.) RATE IN WORDS :xviii Kapoor Hanging Light LEDISK-53 (Custamised) Reception xiv xix xx xxi xxii xxiii xxiv xxv xxvi xxvii xxviii xxix xxx xxxi xxxii 31 NOS 8 NOS AMT. (Rs.) 339 NOS 13 NOS 48 NOS 449 NOS 33 NOS 20 NOS 100 NOS 4 NOS 22 NOS 15 NOS 97 NOS 98 NOS 12 NOS 15 NOS RATE IN WORDS :Philips Lux Space Square BBS 482 DLED-4000 PSD-E 20 WH Lumen O/P -1457 with minimum system Lumen Efficacyof 77 Lumen/Watt. & Total Power Consumption 19W or less (for Reception Lobby) RATE IN WORDS :Philips Smart LED Wall Mount BWS 150 LED 200/NW 90 PSU 220-240V 7043 or CGL Model CROCUS # LWOM10WW/HO 10W (For Lift, Ramp, Well & on Parapit Wall on Roof Top) RATE IN WORDS :Legero Model Pictor-7, LED 7W (for Bush lighting) 10 RATE IN WORDS :Legero Praca-3, 4270, 70W, 6000K, LED (for Facad light) 5 RATE IN WORDS :Philips Auro LED 7W 6000K, Size L130 X W47 X D130 mm OR Wipro Spotify CRDL12 R007HP57 (for concealed lights and before purchase check suitability) RATE IN WORDS :Legrand Code 573564, Skirting Light With LED 230V-3 Module with cover plate RATE IN WORDS :Legero Model Kube, LED 10W with 2 lamps (for Main Entry Coloumn lighting) RATE IN WORDS :200 mm sweep exhaust fan (for Senior Officers wash Room) RATE IN WORDS :300 mm sweep exhaust fan 940rpm EXHD300-6-1 CG or equalent (for Toilets) RATE IN WORDS :380 mm sweep exhaust fan including fixing etc complete in all respect (for Electrical Rooms) RATE IN WORDS :Aluminium Louvers for 300/380 mm sweep exhaust fan including fixing etc complete in all respect RATE IN WORDS :400mm sweep wall fan Model CG HIGH FLO 16" CG OR Bajaj Midea BW-04 RATE IN WORDS :1200mm sweep ceiling fan Model Entrust CGL OR Bajaj Excel Star RATE IN WORDS :Electonic fan regulator steo type Legrand 120w 2 module RATE NOS NOS NOS NOS 42 NOS 6 NOS 2 NOS 1 NOS 17 NOS 6 NOS 23 NOS NOS 98 NOS 49 NOS 49 RATE IN WORDS :TOTAL SECTION - E RATE IN WORDS :- Page 20 of 25 SECTION - F : DG SETS SUPPLY/ERECTION OF D G SETS WITH AMF S.NO. 1 DESCRIPTION 365KVA DG SET (SUITABLE TO CPCB NORMS-2) Supply, installation,testing, loading, unloading, shifting and commissioning of sound proof (silent type) Diesel Generating set having 365 KVA 415 V at 1500 RPM , 0.8 power factor at 415 V suitable for 50 Hz, 3 phase system and for 0.85 load factor , Sound Attenuated DG set comprising of 448 BHP engine coupled to 415 Volts 400 KVA/320KW Stamford make alternator (voltage regulation should be ±1.0% from no load to full load & power factor between 0.8 to 0.9 self regulated) mounted on a common base frame along with AMF and 800A, 4P ACB, EDO type having sufficient NO/NC contacts for interlock with other transformer & DG Set Incomers, fuel tank, batteries with leads etc.. water cooled type DG. Three phase with Neutral supply shall be provided to AMF for sensing puposes to start.stop the DG Set. The set should be for continious operation with permissible overload of 10 % for 1 hr in 12 hrs of operation. The fuel tank capacity should not be less than 520 Ltrs. The silencer shall be domestic/ heavy duty residential type. The noise level shall be less then 75db at one meter distance from the common base and the viberation sould not be more then 8mm at common base. Return fuel pipe, battery charger , AVM pads , engine alternator safeties , electronic governor including all accessories , all housed in sound proof acoustic enclosure as per entire satisfaction of the engineer-in-charge . NOTE :- AMF to provide sufficient NO+NC contacts for interlocing with other source of supply. AMF 365KVA 800A,FP,ACB EDO Type,50kA with SR-18 Breaker Control Switch, Spring Return kWh Meter, 3Ph, 4W, 415V AC Digital Ammeter& Voltmeter with SS Digital Hz Meter 6A, 3 Pole, 3 Way SS Auto/Manual SS, 3 Pole 4 Way CT Tape Insulated 1000/5A, CL-1, 15VA CT Tape Insulated 500/5A, CL-10, 15VA Indicating Lights LED R-Y-G Indicating Lights LED B PB with Elements NO/NC -01 Nos -01Nos -01 Nos -01 Each -01 Nos - 01 Nos -01 Nos -03 Nos - 01 Nos - 13 Nos -02 Nos -08 Nos Page 21 of 25 QTY UNIT 1 Each RATE AMT. S.NO. DESCRIPTION QTY UNIT 1 Each Mushroom Head PB with Element 2NO -1 Nos DC Ammetert & Voltmeter - 1 Each MVMR 415V, AC, 2 C/O Trip/OFF Time 1-10Sec. -1 24V DC Automatic Battery Charger with inbuilt Trickle/Boost Facility 20A -01 Nos 4 Point Alarm Annunciator with inbuilt Hooter, Test, Accept & Reset PB -01 Nos Electronic Based Hooter -01 Nos Aux. Contactor, Coil Voltage- 24V DC -02Nos Aux. Contactor, Coil Voltage -240V AC -01 Nos Aux. Relay, 24V DC -01Nos O/L Relay with inbuilt 1 Phasing Feature -01 Nos MCB, 10kA TP 10A -02 Nos MCB 10kA DP 6-20A -04 Nos MCB 10kA SP 6-10A -09 Nos MCB 10kA SP 4A -01 Nos Earth fault Relay -01 Nos Power Contactor 3 Pole, 25A AC-1 Duty -01 Nos ON Delay Timer, 240V, AC, 0.6-60Sec. -01 Nos ON Delay Timer, 240V AC, 0.6-30 Sec -01 Nos ON Delay Timer 240V AC, 18-180 Sec -01Nos Priming Timer, 240V AC -01 Nos 800A, 415V, 50kA, TPN Ele. Grade Al. Bus0Bar RATE IN WORDS :2 640KVA DG SET (SUITABLE TO CPCB NORMS-2) Supply, installation,testing, loading, unloading, shifting and commissioning of sound proof (silent type) Diesel Generating set having 640 KVA 415 V at 1500 RPM , 0.8 power factor at 415 V suitable for 50 Hz, 3 phase system and for 0.85 load factor , Sound Attenuated DG set comprising of 785 BHP engine coupled to 415 Volts 500 KVA/500KW Stamford make alternator (voltage regulation should be ±1.0% from no load to full load & power factor between 0.8 to 0.9 self regulated) mounted on a common base frame along with AMF and 1000A, 4p ACB EDO typewith sufficient NO/NC contacts for interlock with other transformer & DG Set Incomers, fuel tank, batteries with leads etc.. water cooled type DG. Three phase with Neutral supply shall be provided to AMF for sensing puposes to start/stop the DG Set. Page 22 of 25 RATE AMT. S.NO. DESCRIPTION QTY The set should be for continious operation with permissible overload of 10 % for 1 hr in 12 hrs of operation. The fuel tank capacity should not be less than 520 Ltrs. The silencer shall be domestic/ heavy duty residential type. The noise level shall be less then 75db at one meter distance from the common base and the viberation sould not be more then 8mm at common base. Return fuel pipe, battery charger , AVM pads , engine alternator safeties , electronic governor including all accessories , all housed in sound proof acoustic enclosure as per entire satisfaction of the engineer-in-charge . AMF 640KVA 1000A,FP,ACB EDO Type,50kA with SR-18 -01 Nos Breaker Control Switch, Spring Return -01Nos kWh Meter, 3Ph, 4W, 415V AC -01 Nos Digital Ammeter& Voltmeter with SS -01 Each Digital Hz Meter -01 Nos 6A, 3 Pole, 3 Way SS - 01 Nos Auto/Manual SS, 3 Pole 4 Way -01 Nos CT Tape Insulated 1000/5A, CL-1, 15VA -03 Nos CT Tape Insulated 500/5A, CL-10, 15VA - 01 Nos Indicating Lights LED R-Y-G - 13 Nos Indicating Lights LED B -02 Nos PB with Elements NO/NC -08 Nos Mushroom Head PB with Element 2NO -1 Nos DC Ammetert & Voltmeter - 1 Each MVMR 415V, AC, 2 C/O Trip/OFF Time 1-10Sec. -1 24V DC Automatic Battery Charger with inbuilt Trickle/Boost Facility 20A -01 Nos 4 Point Alarm Annunciator with inbuilt Hooter, Test, Accept & Reset PB -01 Nos Electronic Based Hooter -01 Nos Aux. Contactor, Coil Voltage- 24V DC -02Nos Aux. Contactor, Coil Voltage -240V AC -01 Nos Aux. Relay, 24V DC -01Nos O/L Relay with inbuilt 1 Phasing Feature -01 Nos MCB, 10kA TP 10A -02 Nos MCB 10kA DP 6-20A -04 Nos MCB 10kA SP 6-10A -09 Nos MCB 10kA SP 4A -01 Nos Earth fault Relay -01 Nos Power Contactor 3 Pole, 25A AC-1 Duty -01 Nos ON Delay Timer, 240V, AC, 0.6-60Sec. -01 Nos ON Delay Timer, 240V AC, 0.6-30 Sec -01 Nos ON Delay Timer 240V AC, 18-180 Sec -01Nos Priming Timer, 240V AC -01 Nos 1000A, 415V, 50kA, TPN Ele. Grade Al. Bus0Bar RATE IN WORDS :- Page 23 of 25 UNIT RATE AMT. S.NO. 3 4 a) b) DESCRIPTION QTY STRUCTURE STEEL 2500 Supply/fabrication/installation of steel work in angles, tees, flats, channels & plate etc., duly riveted or welded including cutting fixing gusset plates, bolts, nuts, rivets, welding rods,etc., with hoisting and erecting in position as per given design with two coats of red oxide and two coats of enamel paint of approved shed. The rates includes scaffolding etc (for providing supoort to DG Exhaust Pipe and supoort to Cable Tray). RATE IN WORDS :150mm DIA MS PIPE Supplying, assembling and fixing in vertical/horizontal position ERW (Electric Resistance Welded) FE 410 mild steel plain ended casding pipes of required dia, conforming to IS : 4270, of reputed & approved make, including required hire and laboure charge, fittings and accessories, all complete as per directions of Engineer-in-charge of following size:150mm nominal size dia having minimum wall thickness 5.00mm 80 RATE IN WORDS :EXHAUST PIPE INSULATION 80 Supply and fixing of 50mm thick layer of LRB Rockwool insulation having 100Kg density per cubic metre around the exhaust pipe 150mm dia including clading with aluminium sheet 24 SWG and covering the pipe from out side complete as required suitable for DG exhaust pipe temperature upto 450° C as requirements of the Engineers-in-charge at site.. RATE IN WORDS :TOTAL RUPEES RATE IN WORDS :- Page 24 of 25 UNIT Kg MTR MTR RATE AMT. APPROVED LIST OF MAKES S.NO. DESCRIPTION MAKES 1 Phase Indicators LED Schneider / L&T / Seimens 2 MCB, & RCBO 10kA Curve - C Siemens (Beta guard), Legrand (DX³), Schneider (Acti-9), 3 MCCBs Legrand (DPX³), Seimens (3VL), Schneider (NSX), L&T (D-Sine) 4 L.T. CTs Kappa / AE/ L&T 5 Selector Switch Siemens / Salzer / L&T 6 Dual Track KWh. Meter Secure (Liberty) L&T (Gemini) 7 Digital Multifunction Meter Lgrand (DX ³) L&T (Vega), Secure (Elite 112) 8 Push Buttons Seimens / L & T/ Scheinder 9 Contactors, 500 V (Confirm IEC Specs.) L&T/ Seimens/Scheinder 10 Over Load Relay L&T/ Seimens/ Scheinder 11 Change Over Switch HPL/ L&T/Schneider 12 Lugs, Thimbles etc Dowells/ Dollors/ Jainson 13 Compression Glands HMI /Commet /Sudhir ON/OFF Delay Timer L&T/ Teknika/ Scheinder 15 Protection Relays L&T / Schneider /Alsthom /CGL 16 Capacitor Bank L&T, Schneider, Legrand 17 Power Factor Relay L&T, Schneider, Legrand 18 Generator Voltage Relay L&T/ Teknika/ Scheinder 19 Mains Voltage Monitor Relay L&T/ Teknika/ Scheinder 20 Selector switch L&T/Vaishno/ Scheinder 21 Power Cable XLPE, 11 KV grade Finolex / Polycab/ Havells/ CCI 22 Control Cable (1.1KV grade) Finolex / Polycab/ Havells 23 FRLS PVC Insulated Cu. Wires Finolex / Polycab/ Havells 24 PVC Conduits & Accessories Diplast, AKG, BEC 25 Modular Switches & Sockets etc. Legrand (Arteor) Schneidert (Neo C Metro) Cabtree (Murano) 26 Dist. Boards Double/SingleDoor Legrand (Ekinoxe), Seimens (Beta Guard), Schneider (Acti-9) 27 DG Set Cummins Sudhir/Catter Piller/ Kirloskar Green Light Fixtures Philips,Wipro, GE Transformer (Dry / Oil Cooled) CGL/Voltamp/Scheinder/Sudhir 30 G.O. Switch Jaipuria/ Isotech/ Skiper 31 VCB CGL, Schneider, ABB 32 Ceiling Fan, Exh Fan & Wall Fan CGL, Bajaj, Usha 33 OLTC CTR or OLG 14 28 29 Page 25 of 25