ZONAL OFFICE

advertisement
PRICE BID
ZONAL OFFICE
STATE BANK OF PATIALA, PATIALA
ELECTRICAL WORK (SUB-STATION)
BILL OF QUANTITIES & PRICE SCHEDULE
SUMMARY OF PRICES
SECTION DESCRIPTION
A
H T SECTION
B
LT PANELS
C
LT CABLES
D
EARTHING AND MISC. ITEMS
E
LUMINAIRES
F
GENERATORS
SUB TOTAL
SERVICE TAX
GRAND TOTAL RS.
RATE IN WORDS
AMOUNT IN RS.
SECTION - A : H.T. SESCTION
S.NO. DESCRIPTION
QTY UNIT
1.01
GO SWITCH
1
supply, erection, testing & commissioning of 9 pin, 400A, G.O.
Switch with 11Mtr pre stressed PCC pole (2Nos), 6 pin insulators,
3disc insulators, a set (3Nos) of LA`s, B-Class G.I. pipe 25mm dia
6mtr, G.O. Switch operating handle with locking arrangements, 3
Mtr cable protection G.I. pipe 80mm(OD) dia, 30A aerial fuse set,
stay rod 19/20mm dia. 1.8 mtr long G. I. stay rod (4Nos), stay
anchor M.S. plate 300mm x 300mm x 6mm thick with 20mm hole
in the centre (4Nos), stay wire size 7/10SWG with G. I. thimble
(4Nos), stay wire insulator(4Nos) etc complete with G.I. bolts, nuts,
washers 2100mm long c-channel of size 75 x 40 x 6 mm (7Nos)
including 50 x 6 mm flat D-clamps and all related hardware,
earthing of LA`s with 25 x 5 mm G.I. earth strip and structure
complete in all respect as required.
RATE IN WORDS :2.0
XLPE INSULATED HT ARMOURED CABLE (LOOSE)
Supply and layinf of circular aluminium conductor,conductor
screened with extruded semicnfucting compound, XLPE insulated,
insulation screened with extruded semiconducting combination in
combinatyion
with copper tape (0.3KA for 1 Sec.) cores laid up, FRLS PVC inner
sheathed, galvanised steel strip armoured and overall FRLS PVC
sheathed confirming to IS:7098/II/85 worrking voltage 11KV(UE)
grade to laid loose in the existing trench/pipe
a) Circular Aluminium conductor, conductor screened with extruded
120
semiconducting compound, XLPE insulated, insulation screened
with combination in combination with copper tape (0.3KA for 1 sec.)
cores laid up, FRLS PVC inner sheathed, galvanised steel strip
armoured and overall FRLS PVC sheathed cable confirming to
IS:7098/II/85 wirking voltage 11KV(YE) grade 150sqmm (Three
Core)
RATE IN WORDS :3.0
S/E OF HEAT SHRINKABLE CABLE END TERMINATION FOR
11 KV/6.6KV
i
Heat Shrinkable for cable size 120-185 sq mm (Indoor Type)
5
RATE IN WORDS :ii
Heat Shrinkable for cable size 120-185 sq mm (Outdoor Type)
1
RATE IN WORDS :4.0
TRANSFORMER
1
Supply/Test/Commissioning of Dry Type 1000KVA, 11/0.433KV, 3
Phase, 50Hz, Dyn 11 vector group, copper wound, class - F
insulation associated with winding temprature indicator /controller
actuated by means of resistance temprature detector embedded in
LV windings, Indoor type Transformer with Approximately 5%
impedance, tapping for off load operation on HV side in steps of +/2.5%, +/- 5% - 7.5%, having cable boxes on HV and LV side with
neutral brough out separately including supplying & laying of copper
conductor multicore YWY cable from transformer to VCB for safety
tripping and Transformer suitably mounted on M.S. Channel i/c
supplying and suitable M.S. Channel with all accessories and
confirming to IS 11171:1985 & as per specifications complete in all
respect as required at site.
RATE IN WORDS :-
Page 2 of 25
Each
MTR
Each
Each
Each
RATE
AMOUNT
S.NO. DESCRIPTION
5.0
QTY UNIT
VCB
Supply/Test/Commissioning of indoor type floor mounted metal
clad, 11KV VCB panel with one No. VCB, totally enclosed & fully
interlocked, Horizontal drawout, Vertical Isolation type breaker as
per IS 13118, as amended up to date and additional specifications,
having capacities as mentioned below, single break, trip free
mechanism, manually chatfed and auto/manually closing breaker
suitable for use on 11 KV, 3 Phase, 50 Hz, A.C. supply with short
circuit fault level of 350MVa, complete with self contained, fuylly
interlocked, rack in and rack out mechanism, air insulated but
encapsulated copper bus bars of 800A capacity, breaker featured
wit mechanical ON/OFF indicator with hand trip device, spring
release coil, shunt trip coil and auxillary switchgears and
accessories i/c connections suitable for 3 x 150 sq mm XLPE 11 KV
cable (cable entry from bottom/top).
Closing Coil Voltage 24 Volt DC
Auxiliary contact 4NO+4NC
CTR 100/5+5A ---------- 3Nos
Core - 1
Metering : 15VA, CL-1.0
Core - 2 Protection : 15VA, 5P10
STR - 26 kA for 3sec.
PTR : 11KV/Rt.3, 110V AC/Rt.3, ratio-------------3Nos
Resin cast, 1 phase draw out PT with fuses
Class of accuracy : 1.0, Burden - 100VA
1.2 cont. 1.8 for 8 Hrs.
Digital Ammeter, Cl-1.0, 96sqmm with ASS --- 1Nos
Digital Voltmeter, Cl-1.0,96sqmm with VSS ---1Nos
Phase Indicating Lamps LED type------1Set
Breaker - ON Red--1Nos
Breaker - OFF Green----- 1Nos
Spring Charged - Blue----1Nos
Trip Circuit Healthy - Clear---------1Nos
Auto Trip Indicating - Amber
-----1Nos
Hooter -------1Nos
8Window annunciator -------- 1Nos
TNC Switch - Spring Return Type --------- 1Nos
Push button for trip circuit healthy -------- 1Nos
Local/Remote Selector ----------1Nos
Emergency trip push button ---------1Nos
Control fuses/MCB for AC or DC supply--9Nos
Space Heater 100W -------------1Nos
2NosThermostat - 1C/O --------1Nos
Panel Lamps with toggle switch---- 1Nos
Single phase three pin plug & socket--- 1Nos
Power Pack (240V AC to 24 V DC) ------- 1Nos
Protection Relay 3 O/C + 1E/F IDMTL with high set------ 1Nos
Master trip Relay -------1Nos
Auxiliary relay for Tr. fault---------- 1Nos
RATE IN WORDS :-
Page 3 of 25
1
Each
RATE
AMOUNT
S.NO. DESCRIPTION
5.0
6.0
i
a)
b)
ii
iii
iv
v
vi
vii
viii
QTY UNIT
CT/PT AND TRI-VECTOR METER
Supply/Fixing of 11KV CT - PT Metering Cubical Indoor, Dry Type,
Three Phase Four Wire, mounted with CT & PT as detail given
below :a)
3 Nos CTs of Ratio 100/5A of Rated Burden 15VA, Accuracy
Class 0.2S, With insulation level (12KV/28KV/75KV)as per
IS2705/1992 consisting of two metering core suitable forABT/Check
Meter.
b)
1 NosPT 11KV/110Volts of Rated Burden 50VA, Accuracy
Class0.2 with insulation level (12KV/28KV/75KV) as per IS
3156/1992.
c) tri-Vector Meter, Accuracy Class 0.2 as per PSPCl norms
RATE IN WORDS :SAFETY EQUIPMENT
Providing & fixing danger plates made of mild steeel at least 2mm
thick and vitreous enameled white on both sides & with inscriptions
in sinnal red colour on front side as read.
a) High Voltage
Size 250 mm x 200 mm
b) Medium Voltage Size 200 mm x 150 mm
High Voltage
Size 250 mm x 200 m
RATE IN WORDS :Medium Voltage Size 200 mm x 150 mm
RATE IN WORDS :Providing & fixing carbon dioxide (CO2) type fire extinguishers
confirming to IS 2878: 1976 and cylinders fully charged of following
capacity.
A) 4.5 Kg (Panel Room - 1, TR. - 1, VCB - 1 & Metering Room - 1)
RATE IN WORDS :Supply and fixing of Foam Fire Extinguishers, Portable type 9 Ltr
capacity hanged on wall with bracket complete as required. (Near
DG Set - 2 Set)
RATE IN WORDS :Supply and fixing of safety instriction chart in word duly framed
with 5 mm thick glass as required. (Approx. front area 1.20 sq
mtrs.), Panel Room -1 & VCB Room -1
RATE IN WORDS :Providing of set of 4 Nos. 9.5 Ltrs. Capacity GI bucket painted in
post office red colour withy prior coat of red oxide paint and written
with white paint "FIRE" and mounted on MS angle iron frame with
bracket of appropriate size and capacity i/c filling sand etc. (Near
DG Set -1Set)
RATE IN WORDS :Providing First Aid Box as approved bt St. John Ambulance
Brigade/Indian Red Cross conforming to IS 2217 :1963 (Panel
Room-1 & VCB Room -1)
RATE IN WORDS :Supply & fixing shock treatmernt chart duly mounted on a wooden
frame with 5 mm thick glass as required. (Approx. front area 1.20
sq mtr) Panel Room -1 & VCB Room -1
RATE IN WORDS :Prodiding of rubber mat 1 Mtr wide X 2 Mtr long and 3 mm thick to
withstand 15 KV dielectric strength as per IS 5424 :1969
RATE IN WORDS :GRAND TOTAL SEC-A
RATE IN WORDS :-
Page 4 of 25
1
SET
10
Each
10
Each
4
Each
1
Set
2
Each
1
Set
2
Each
2
Each
8
Mtr
RATE
AMOUNT
SECTION - B : L.T. PANELS
S.NO.
DESCRIPTION OF WORK
1.0
LT PANELS
Supply/Receiving/handling/erection/testing/commissioning
of
cubicle type panels fabericated out of 1.6/2 mm rust inhibited
CRCA sheet steel bolted and modular construction complete
with incoming and out-going feeders, bus bars of electrolytic
grade aluminium duly insulated with heat shrinkable PVC
colour coded sleeves and supported on DMC/SMC supporters,
outgoing feeders upto 63A brought out to cable alley in the
form of terminals and above ratings with bus-bar links. All
terminals are marked permanently. Meters, indicating lamps
shall be as per specified and shown in SLD. PCC shall be
totally enclosed dust and vermin proof construction with heavy
duty neoprene gaskets. The floor mounting panels shall be
provided with mounting channels. Panels shall incorporate
double aluminium earthing bus, cable alleys, bus bar chambers,
bus interconnections.
The panel shall be enamel (powder coated) painted. The panel
shall be provided with name pate for all incoming outgoing
feeders, danger plate, panel shall be provided with steel lock
with two key for each panel and the key shall be common for all
compartment/doors. The mechanical /electrical interlocking
shall be provided where ever it is required . Provide de-interlock
facility in off position. If any material not specifcally mentioned
in the BOQ/SLD but required for satisfactorily functionig of the
panel shall be in the scope of contrctor without any price
implication. Panel should be suitable for 50KA short circuit
rating and complete in all respect as required by the Engineerin charge.
NOTE :- Before manufacturing the panel G.A. drawing to be
provided for approval and also control wiring diagrame to be
submitted to the owner on completion of work.
MAIN L.T. PANEL <MLTP>
RATE IN WORDS :INCOMER (MAINS)
1600A 4P,55KA,ACB EDO Type,Micro Processor Based SR18
01 Nos
R-Y-B Phase Indicator with 2A SP MCB
01Set
2 Element O/C and 1 Element Earth fault relay 01Set
Standby Earth Fault Relay 51NS
01 Nos
ON, OFF Trip SC TCH Indication etc
01Set
6 Window Annunciator
01Set
6A TPN MCB, 10kA, Curve-C
02 Nos
Digital Multifuction Meter with 3Nos 2A SPMCB
(V,A F,Pf,KW,KWH)
01Nos
CT 1600/5A , CL-SP10, Burden 15VA
03Nos
CT 1600/5A , CL-SP0.5, Burden 15VA
03Nos
CT 1600/5A, CL-SP0.5, Burden 15VA
01Nos
INCOMER 365KVA DG SET
1600A 4P,55KA,ACB EDO Type,Micro Processor Based SR18
01 Nos
R-Y-B Phase Indicator with 2A SP MCB
01Set
2 Element O/C and 1 Element Earth fault relay 01Set
ON, OFF Trip SC TCH Indication etc. 01Set
A
i
ii
iii
iv
v
vi
vii
viii
ix
x
xi
xii
B
i
ii
iii
iv
Page 5 of 25
QTY. UNIT
1
Nos.
RATE
AMOUNT
S.NO.
DESCRIPTION OF WORK
v
Digital Multifuction Meter with 3Nos 2A SP MCB
(V,A,F,Pf,KW,KWH)
01Nos
CT 800/5A CL-SP10, Burden 15VA
03Nos
CT 800/5A CL-SP 0.5, Burden 15VA
03Nos
INCOMER 640KVA DG SET
1000A, FP, ACB, EDO Type 50kA, with Microprocessr based
SR18
01Nos
R-Y-B Phase Indicator with 2A SP MCB
01Set
2 Element O/C and 1 Element Earth fault relay 01Set
ON, OFF Trip SC TCH Indication etc.
01Set
Digital Multifuction Meter with 3Nos 2A SP MCB
(V,A,F,Pf,KW,KWH)
01Nos
CT 1000/5A , CL-SP10,
Burden 15VA
03Nos
CT 1000/5A , CL-SP 0.5,
Burden 15VA
03Nos
BUS COUPLER
1000A, 4P, ACB, EDO Type
01Nos
ON, OFF Indication
ON OFF Push Button
01Set
BUS-BAR
TPN aluminium bus-bar of minimum of 1600Amp. Capacity with
heat shrinkable coloured sleeves and i/c DMC.SMC bus-bar
cross section , size supporters & their spacing etc. for
withstanding fault level of 31MVA for 1 Sec.
1Set
vi
vii
C
i
ii
iii
iv
v
vi
vii
D
i
ii
E
i
F
i
ii
iii
iv
v
vi
vii
1.01
i
ii
iii
iv
v
vi
OUT GOINGS
800A TP MCCB 50kA with Rotory Handle & Thermal Magnetic
Release
01Nos
630A TP MCCB 50kA with Rotory Handle & Thermal Magnetic
Release
03Nos
200A TP MCCB 25kA,with Rotory Handle & Thermal Magneic
Release
08Nos
100A TP MCCB 25kA,with Rotory Handle & Thermal Magneic
Release
01Nos
80A TP MCCB 25kA,with Rotory Handle & Thermal Magneic
Release
01Nos
40A TPN MCB 10kA, Type Curve - C,
07Nos
63A TPN MCB 10kA, Type Curve - C,
02Nos
CAPACITOR CONTROL PANEL
<CCP> 285kVAR
RATE IN WORDS :INCOMER
630A TP MCCB 50kA with Rotory Handle & Thermal Magnetic
Release
01Nos
R-Y-B Phase Indicator with 2A SP MCB
01Set
CT 600/5A , CL-SP10, Burden 15VA
03Nos
Digital Multifuction Meter with 3Nos 2A SP MCB
(V,A,F,Pf,KW,KWH)
01Nos
15 kVAr with 7% Detuned Copper Reactor 480V, 50Hz +
20kVAr Ultra Heavy Duty Capacitor (Effective 15kVAR)
+ 63A,TP 16kA MCB capacitor bank
01 Nos
50 kVAr with 7% Detuned Copper Reactor 480V, 50Hz
+ 60kVAr Ultra Heavy Duty Capacitor (Effective 50kVAR)
+ 125A, TP 25kA MCCB
+ capacitor duty contactor MOC-50
capacitor bank
03 Nos
Page 6 of 25
QTY. UNIT
1
Nos.
RATE
AMOUNT
S.NO.
DESCRIPTION OF WORK
vii
25 kVAr with 7% Detuned Copper Reactor 480V, 50Hz
+ 30kVAr Ultra Heavy Duty Capacitor (Effective 25kVAR)
+ 63A, TP 16kA MCB
+
capacitor duty contactor MOC-25
capacitor bank
04 Nos
10 kvar 7% Detuned Copper Reactor 480V, 50Hz
+ 12.5kVAR Ultra Heavy Duty Capacitor (Effective 10kVAR)
+ 40A, TP 16kA MCB
+ capacitor duty contactor MOC- 12.5 capacitor bank
01 Nos
5 kvar 7% Detuned Copper Reactor 480V, 50Hz
+7.5KVAR Ultra Heavy Duty Capacitor (Effective 5kVAR)
+ 32A, TP 16kA MCB
+ capacitor duty contactor MOC -8.5
capacitor bank
02 Nos
Auto/Manual switch, , ON ,OFF indicator & Push Button
10Sets
12 Step APFC Relay 5A, 415Volts, Digital
01Nos
FLOOR PANEL GROUND & FIRST FLOOR
Incomer -200A TPN MCCB 25kA with Thermal Magnetic
Release
01Nos
CT - 200/5A, 15VA, CL -0.5
03Nos
Phase indicator R-Y-B with 2A SP MCB
03Nos
Digital V I F Meter
01Nos
Busbar Al. TPN 200A with coloured PVC sleeve 01Set
OUT GOINGS
63A TPN MCB 10kA Type-C
10Nos
40A TPN MCB 10kA Type-C
04Nos
RATE IN WORDS :FLOOR PANEL SECOND & THIRD FLOOR
Incomer -200A TPN MCCB 25kA with Thermal Magnetic
Release
01Nos
CT - 200/5A, 15VA, CL -0.5
03Nos
Phase indicator R-Y-B with 2A SP MCB
03Nos
Digital V I F Meter
01Nos
Busbar Al. TPN 200A with coloured PVC sleeve 01Set
OUT GOINGS
63A TPN MCB 10kA Type-C
12Nos
40A TPN MCB 10kA Type-C
04Nos
RATE IN WORDS :STREET LIGHT PANEL
viii
ix
x
xi
1.02
i
1.02
i
1.03
Page 7 of 25
QTY. UNIT
2
Nos.
2
Nos.
RATE
AMOUNT
S.NO.
DESCRIPTION OF WORK
STREET LIGHT PANEL WITH TIMER
S/E/T & Commissioning of Microprocessor Based Street Light
Controller with digital time switch daily programmed with stand
by lithium battery with back up of 6 years with minimum time
between 2 switching operations is 1 minute, 3 nos, three pole,
power contactors 40A, with coil voltage 220-230V AC with 1 no.
aux. contactor 6A (2NO + 2NC) with coil voltage 220V AC, 3
nos MCB 2Pole 40A (Curve-C, 10kA) and power wiring with
single core PVC insulated FRLS cable 10 Sq mm and control
wiring with PVC insulated FRLS cable 1 sq mm, 1 no. two
position selector switch to bypass timer and other accessories
and petty material (din rail, 2 nos 4pole bakalite terminal strip
63A , 440V AC, required nuts & bolts) should be fixed on
balalite sheet 6 mm thick to mounted in a IP 54 flush mounting
powder coated sheet metal (1.6 mm thick) cabinet having size
450 mm x 600 mm x 150 mm to switch "ON" all the three
phase andswitch "OFF" 3 phases prefixed timings complete in
all tespect as per satisfaction of Engineer-in-charge.
I
II
RATE IN WORDS :S/I/T/C of Incomer to above said panel (Street light Panel) 63A
TPN MCB Curve - C
1nos
RATE IN WORDS :S/I/T/C/ of Spare out goings appart from street light panel
provide 32A DP MCB Curve - C
2nos
RATE IN WORDS :TOTAL SECTION – B :
RATE IN WORDS :-
Page 8 of 25
QTY. UNIT
1
Each
1
Each
2
Each
RATE
AMOUNT
SECTION - C : L.T. CABLES
SUPPLY/LAYING OF CABLES
S.NO.
DESCRIPTION
QTY. UNIT RATE
1.0 Supply & laying of aluminium conductor XLPE PVC
i
ii
iii
iv
v
vi
vii
viii
ix
x
xi
sheathed armoured and served cable to be laid loose
in the existing trench or pipe as per PWD General
Specifications.
RATE IN WORDS :Aluminium conductor XLPE PVC sheathed armoured
and served cable working voltage 1100volts grade 16
sq mm (4 Core) for lift & street light panel
RATE IN WORDS :Aluminium conductor XLPE PVC sheathed armoured
and served cable working voltage 1100volts grade 50
sq mm (3.5 Core) for Main Panel to Public Health
Panel & Common Panel
RATE IN WORDS :Aluminium conductor XLPE PVC sheathed armoured
and served cable working voltage 1100volts grade 95
sq mm (3.5 Core) for Main Panel to Floor Panel
RATE IN WORDS :Aluminium conductor XLPE PVC sheathed armoured
and served cable working voltage 1100volts grade
240 sq mm (3.5 Core) for Main Panel to Mechanical
Ventilation Panel
RATE IN WORDS :Aluminium conductor XLPE PVC sheathed armoured
and served cable working voltage 1100volts grade
400 sq mm (3.5 Core) from TR MAIN LT Panel
RATE IN WORDS :Copper conductor XLPE PVC sheathed armoured
and served cable working voltage 1100volts grade 2.5
sq mm (4 Core) from TR to Main LT Panel Neutral
CT and Main LT Panel to AMF Panel
RATE IN WORDS :Copper conductor XLPE PVC sheathed armoured
and served cable working voltage 1100volts grade 2.5
sq mm (3 Core) for Bush lights etc.
RATE IN WORDS :Copper conductor XLPE PVC sheathed armoured
and served cable working voltage 1100volts grade 2.5
sq mm (7 Core) for DG Set Panel to Main Panel & Tr.
To VCB
RATE IN WORDS :Copper conductor XLPE PVC sheathed Un-armoured
and served cable working voltage 1100volts grade 6.0
sq mm (4 Core) for LDB`s etc.
RATE IN WORDS :Copper conductor XLPE PVC sheathed Un-armoured
and served cable working voltage 1100volts grade
10.0 sq mm (4 Core) for Flor AC DB`s & PDB`s
650
MTR
100
MTR
220
MTR
350
MTR
650
MTR
225
MTR
200
MTR
250
MTR
500
MTR
450
MTR
RATE IN WORDS :PVC insulated copper conductor single core FRLS 2000
cable (ISI) marked overall 2.5 sq mm, 1100Volts
grade. (Green Colour as Earth wire & other colour for
Circuit wireor sub mains)
Page 9 of 25
MTR
AMOUNT
S.NO.
xii
xiii
xiv
2.0
i
ii
ii
iv
v
vi
vii
viii
ix
x
3.0
i
DESCRIPTION
QTY. UNIT RATE
RATE IN WORDS :PVC insulated copper conductor single core FRLS 2000
cable (ISI) marked overall 4.0 sq mm, 1100Volts
grade. (Green Colour as Earth wire & other colour for
Circuit wire or sub mains)
RATE IN WORDS :PVC insulated copper conductor single core FRLS 1000
cable (ISI) marked overall 6.0 sq mm, 1100Volts
grade. (Green Colour as Earth wire & other colour for
Circuit wire or sub mains)
RATE IN WORDS :PVC insulated copper conductor single core FRLS 500
cable (ISI) marked overall 10.0 sq mm, 1100Volts
grade. (Green Colour as Earth wire & other colour for
Circuit wire or sub mains)
RATE IN WORDS :-
PVC, HDPE
PIPES :
PIPES
MTR
MTR
MTR
& PVC FLEXIBLE
Supply and erection of PVC pipes & HDPE pipes (fire
retardent) for wiring puposes incliding bends,
inspection boxes erc., where necessary including
other petty material as per PWD General
Specifications 2010 :
Heavy guage PVC conduit pipe 20mm dia (ISI marked
2mm thick) On Surface
RATE IN WORDS :Heavy guage PVC conduit pipe 25m dia (ISI marked
2mm thick) On Surface
RATE IN WORDS :Heavy guage PVC conduit pipe 32mm dia (ISI marked
2mm thick) On Surface
RATE IN WORDS :Heavy guage PVC conduit pipe 40mm dia (ISI marked
2mm thick) On Surface
RATE IN WORDS :Heavy guage PVC conduit pipe 50mm dia (ISI marked
2mm thick) On Surface
RATE IN WORDS :Heavy guage PVC conduit pipe 20mm dia (ISI marked
2mm thick) Flushed
RATE IN WORDS :Heavy guage PVC conduit pipe 25m dia (ISI marked
2mm thick) Flushed
RATE IN WORDS :Heavy guage PVC conduit pipe 32mm dia (ISI marked
2mm thick) Flushed
RATE IN WORDS :Heavy guage PVC conduit pipe 40mm dia (ISI marked
2mm thick) Flushed
RATE IN WORDS :Heavy guage PVC conduit pipe 50mm dia (ISI marked
2mm thick) Flushed
RATE IN WORDS :-
50
Mtr
100
Mtr
100
Mtr
100
Mtr
100
Mtr
50
Mtr
100
Mtr
100
Mtr
100
Mtr
100
Mtr
300
Mtr
PVC FLEXIBLE PIPES :
Supply and erection of PVC flexible pipe complete
with compression glands, having locking arrangement,
chec-nuts as required :
PVC Flexible pipe 20 mm dia
RATE IN WORDS :Page 10 of 25
AMOUNT
S.NO.
ii
iii
iv
4.0
i
ii
iii
iv
v
vi
vii
viii
ix
5.0
i
DESCRIPTION
QTY. UNIT RATE
PVC Flexible pipe 25 mm dia
RATE IN WORDS :PVC Flexible pipe 32 mm dia
RATE IN WORDS :PVC Flexible pipe 40 mm dia
RATE IN WORDS :-
200
Mtr
50
Mtr
50
Mtr
15
Nos
15
Nos
20
Nos
30
Nos
20
Nos
10
Nos
12
Nos
8
Nos
20
Nos
40
MTR
1
Each
END TERMINATION
supply & making indoor type end termination with
brass single compression cable glands and aluminium
lugs for following sizes of XLPE aluminium conductor
cable of 1.1KV grade.
4 x 2.5 sq mm Cu. Ar. Cable
RATE IN WORDS :7 x 2.5 sq mm Cu. Ar. Cable
RATE IN WORDS :4 x 6.0 sq mm Cu. Ar. Cable
RATE IN WORDS :4 x 10.0 sq mm Cu. Ar. Cable
RATE IN WORDS :4 x 16 sq mm A2XFY power cable
RATE IN WORDS :3.5 x 50 sq. mm A2XFY cable
RATE IN WORDS :3.5 x 95 sq. mm A2XFY cable
RATE IN WORDS :3.5 x 240 sq. mm A2XFY cable
RATE IN WORDS :3.5 x 400 sq. mm A2XFY cable
RATE IN WORDS :-
CABLE TRAY
Supplying and installing following size of perforated
M.S. cable tray with perforation not more than 17.5%,
in convenient sections, joined with connectors,
suspended from the ceiling with M.S. suspenders
including nuts & bolts, painting suspenders etc. as
required.
450mm width x 50mm depth x 2.0 mm thickness
RATE IN WORDS :-
CABLE TRAY BEND
ii
Supplying and installing following size of perforated
M.S. cable tray bends (horizontal type 90 ° ) with
perforation not more than 17.5%, in convenient
sections, joined with connectors, suspended from the
ceiling with M.S. suspenders including nuts & bolts,
painting suspenders etc. as required.
450mm width x 50mm depth x 2.0 mm thickness
RATE IN WORDS :-
Page 11 of 25
AMOUNT
S.NO.
iii
6.0
DESCRIPTION
CABLE TRAY VERTICAL BEND
QTY. UNIT RATE
Supplying and installing following size of perforated
M.S. cable tray bends (vertical type 90 ° ) with
perforation not more than 17.5%, in convenient
sections, joined with connectors, suspended from the
ceiling with M.S. suspenders including nuts & bolts,
painting suspenders etc. as required.
450mm width x 50mm depth x 2.0 mm thickness
RATE IN WORDS :-
1
Each
85
MTR
85
MTR
10
MTR
4
Each
1
Each
1
Each
3
Each
1
Each
CABLE TRAY LADDER TYPE
Ladder type cable tray shall consist of two longitudinal
members (side rails) with transverse members (rungs)
welded to the side rails. Rungs shall be spaced at
250mm on center. Width of the rung shall be 25mm,
side rails and rungs shall be fabricated out of 2mm
CRCA sheet steel and duly hot dipped zinc coated. No
portion of the rungs shall protrude below the bottom
plane of the side rails. Each rung must be capable of
supporting cable load. The cable tray must be
complete in all respect including coupling plates, G.I.
bolts, nuts & washers etc. The cable tray shall be
supported on angle of size of 40 x 40 x 5 mm (at
every 1 meter distance) duly painted with 2 coats of
red oxide and 2coats of enamel paint of required
shade as per sight engineer. The cable tray fixing
includes cable tray, cable tray bends, cable tray Tees,
etc. complete in all respect.
i
ii
iii
iv
v
vi
vii
viii
Cable Tray Size 600 mm width x 75 mm depth x 2mm
thickness
RATE IN WORDS :Cable Tray Size 300 mm width x 50 mm depth x 2mm
thickness
RATE IN WORDS :Cable Tray Size 150 mm width x 50 mm depth x
1.8mm thickness
RATE IN WORDS :Cable Tray Bend Horizontal Size 600 mm width x 75
mm depth x 2mm thickness
RATE IN WORDS :Cable Tray Bend Vertical Size 600 mm width x 75
mm depth x 2mm thickness
RATE IN WORDS :Cable Tray Tees Size 600 mm width x 75 mm depth
x 2mm thickness
RATE IN WORDS :Cable Tray Bend Size 300 mm width x 50 mm depth x
2mm thickness
RATE IN WORDS :Cable Tray Bend Size 150 mm width x 50 mm depth
x 2mm thickness
RATE IN WORDS :-
Page 12 of 25
AMOUNT
S.NO.
7.0 M.S STEEL
DESCRIPTION
QTY. UNIT RATE
1000
Kg
100
MTR
M.S. Equal angle 40 x 5 mm for providing support to
the cable tray including welding, cutting fixing in
position, painting 2 coats of anti corrison and 2 coats
of enamel paint duly approved, The rate includes all
types hardware required for the job like welding rod,
bolts, nuts, spring washer etc completein all respect
as required.
RATE IN WORDS :-
8.0
i
PVC PIPE
Providing, stringing out P.V.C. Pipes as per ISI-4985
casting along the Trenches and laying the same in
trenches to correct alignment and gradients, cutting,
jointing and testing including cost specials complete
as per specifications.
75mm o/d pipe 6Kgf./sqcm
RATE IN WORDS :TOTAL – C :
RATE IN WORDS :-
Page 13 of 25
AMOUNT
SECTION - D : EARTHING AND MISC. ITEMS
S.NO.
DESCRIPTION
1.0
EARTH STATION COOPER
Earthing with copper earth plate 600 x 600 x 3 mm
thick including accessories and providing masonary
enclosure with cover plate having locking
arrangement and watering pipe of 2.7 meter long G.I
(Class - A), with charcoal/ coke and salt as required
including 3 meter copper earth collecting strip of size
25 x 5 mm. The contractor also required to submit
the earth pit value, complete in all respect. (Tr.
Neutral - 2, Gen Neutral -4, UPS -3 & Lift-2)
2.0
3.0
4.0
5.0
6.0
QTY UNIT
RATE IN WORDS :EARTH STATION G.I
Earthing with G.I. (Hot Dip) earth plate 600 x 600 x 6
mm thick including accessories and providing
masonary enclosure with cover plate having locking
arrangement and watering pipe of 2.7 meter long G.I
(Class - A), with charcoal/ coke and salt as required
including 3 meter copper earth collecting strip of size
50 x 6 mm. The contractor also required to submit
the earth pit value, complete in all respect. (Tr.Body 2, Gen Body -2, LT Panel Body - 2, G.O. Switch -2,
HT Metering-2)
RATE IN WORDS :BUILDING LIGHTNING PROTECTION EARTH PIT
Earthing with G.I. earth pipe 4.5 metre long 40mm
dia including accessories and prodiding masonary
enclosure with cover plate having locking
arrangements with charcoal/coke and salt etc. as
required complete in all respect including submission
of earth value. (for LA`s)
RATE IN WORDS :LIGHTNING SPIKE
Providing & fixing of lightning conductor finial, made
of 25 mm dia 300 mm long G.I. tube, having single
prong at top, with 85 mm dia 6mm thick base plate
including holesetc. Complete as required.
RATE IN WORDS :LIGHTNING EARTH TAPE
Providing & fixing of G.I. tape 20 x 3 mm (hot dip) on
parapet or on surface of wall for lightning conductor
complete as required including fixing hardware. The
strip clamp /screw shall be fixed at a distance of
450mm. (for horizontal run)
RATE IN WORDS :LIGHTNING EARTH TAPE
Providing & fixing of G.I. tape 20 x 3 mm (hot dip) on
parapet or on surface of wall for lightning conductor
complete as required including fixing hardware. The
strip clamp /screw shall be fixed at a distance of
450mm. (for vertical run)
RATE IN WORDS :-
Page 14 of 25
11 NOS
10 NOS
6 NOS
6 NOS
400 MTR
100 MTR
RATE AMT. (Rs.)
S.NO.
DESCRIPTION
7.0
TEST LINK
Providing and fixing testing joint made of 20 x 3 mm
G.I. strip , 125 mm long, with 4Nos of G.I. bolts, nuts,
chuck nuts and spring washeretc. Complete as
required. The testing joint shall be made on vertical
run at a height of 1200mm from zero level.
RATE IN WORDS :EARTH TAPES/WIRES
Supplying/fixing/straighteningof following sizes of
earth strips duly clamped at distance of 450mm and
joint must overlap by 100mm on each side of strip &
tightened with 4 Nos of bolts &nuts with plane, spring
washer.Further a test link to be provided on every
earth pit by the contractor for the purpose of testing
at appropriate place.
Providing & fixing copper tape 20 x 3 mm thick ( on
cleats @ 1 meter on wall of electrical shaft) complete
as required (for UPS & Lift)
RATE IN WORDS :Providing & fixing 25 x 5 mm copper strip on surface
or in recess for connections as required including
fixing material complete in all respect for neutral of
transformer , DGsets (2 runs each)
RATE IN WORDS :Providing & fixing 25 x 5 mm G.I. strip (hot dip) on
surface or in recess for connections as required
including fixing material complete in all respect.(2
runs along with cable tray in basement, for G.O.
switch, floor panel and AC Panel )
RATE IN WORDS :50 x 6 mm GI earth strip for body of TR, Gen body,
Main Electrical Panel & AC panel (2run alongwith
cable tray in shaft). Floor panel earth to be tapped
from cable trat earth strip.
RATE IN WORDS :Providing and fixing 6 SWG dia G.I. wire on surface
or in recess for loop earthing along with existing
surface/recessed conduit/submain wiring/cable as
required.
RATE IN WORDS :METAL BOXES
Supplying and fixing metal box of following sizes
(nominal size) on surface or in recess with
suitablesize of phenolic laminated sheet cover in front
including painting etc as required.
150mm x 75mm x 100mm deep
RATE IN WORDS :200mm x 125mm x 100mm deep
RATE IN WORDS :250mm x 150mm x 100mm deep
RATE IN WORDS :300mm x 150mm x 100mm deep
RATE IN WORDS :450mm x 150mm x 100mm deep
RATE IN WORDS :600mm x 150mm x 100mm deep
RATE IN WORDS :-
8.0
i
ii
iii
iv
v
9
i
ii
iii
iv
v
vi
QTY UNIT
Page 15 of 25
4 NOS
50 MTR
100 MTR
300 MTR
120 MTR
50 MTR
20 Each
20 Each
15 Each
15 Each
10 Each
10 Each
RATE AMT. (Rs.)
S.NO.
DESCRIPTION
10
SUB MAINS POWER WIRING
Supply of Sub-Mains power wiring for DB,
Sub-Mains to start from main Panel to
LDB/PDB/UPSDB using 1100 Volts grade,
multystrand, pvc insulated, copper conductor
wiring /PVC insulated PVC sheathed cables
shall be pulled/laid through pipe with wiring
accessories such as bends, identification
ferrules, etc. (NOTE- UPS earthing system
must be isolated from power/lights system),
Phase, Nuetral and Earth wire must run
separate for all circuits from the DB.
a)
b)
c)
d)
11
QTY UNIT
4x6sq. mm copper cable PVC insulated PVC
sheathed in 32mm PVC conduit (from MLTP to
LDB's in Basement All wires need to be
ferruled as per drawing in 32mm PVC conduit.
Rate in Words :
4x6sq. mm copper armoured cable PVC
insulated PVC sheathed in 32mm conduit along
with 2x2.5sqmm copper PVC insulated earth
wire (from FLOOR Panel to LDB's All wires
need to be ferruled as per drawing.
Rate in Words :
2x16sq. mm copper cable PVC insulated PVC
sheathedin
40mm
conduit
along
with
2x2.5sqmm copper PVC insulated earth wire
(from UPS Panel to UPSDB & UPS to UPS
Panel All wires need to be ferruled as per
drawing.
Rate in Words :
4x10sq. mm copper cable PVC insulated PVC
sheathed in 40mm conduit along with
2x4sqmm copper PVC insulated earth wire
from FLOOR panel to PDB's All wires need to
be ferruled as per drawing.
Rate in Words :
LIGHT POINT WIRING
Supplying/Laying/Commissioning of wiring and
testing for light, fan, exhaust fan, 5A socket,
etc. starting from the point control box to the
outlet point, using 1.5 sq.mm copper
conductors, multystrand, pvc insulated 1100
volts grade wiring/cables in concealed conduit
wiring system, in ISI marked PVC conduit
heavy duty including all conduit accessories
such as bends, tees, draw
Page 16 of 25
250
mtr
150
mtr
150
mtr
150
mtr
RATE AMT. (Rs.)
S.NO.
DESCRIPTION
QTY UNIT
boxes, MS fan hook, Concealed light, GI
Modular boxes (HOT DIP) for light point, fan
point/regulator control boxes, together with
wiring accessories such as 5A modular type
switches, 3 pin 5A modular type sockets,
batten holders (wherever required), including 2
x1.5 + 1x1.5 sq mm copper pvc insulated for
point wiring and 2x2.5+1x2.5sqmm for circuit
wiring are inclusive as per drawing.
The conduit for point wiring & circuit wiring shall
be separate. Identification ferrules at both ends
of Phase & Nuetral, complete in all respects.
Conduit being concealed either in ceiling
slab/wall chase including making good and
filling of chases with cement mortar etc. as per
standard specifications and relevent drawings.
Note : All wires of point wiring in the false ceiling
area shall be 2 mtr excess from the slab/JB/Fan
Box, so the joint can take within the light fixture.
a)
12
a)
c)
One 3 pin 5A light plug socket outlet controlled
by one no. 5A Modular type switch (Dependent
to be fitted on existing modular plate only).
Rate in Words :
POWER/LIGHT/UPS SOCKETS :
POWER
SOCKETS
S/F/Commissioning of 6 PIN 15A POWER
SOCKETS Modular type sockets with 15A SP
switch in a suitable M.S.Modular GI box,
Including wires 2x4+1x1.0 sq mm (from DB to
outlet points), in 25mm PVC conduit Heavy
Duty, bends etc . Complete in all respect
including ferruling as per drawing.
Rate in Words :
COMPUTER POINT SUPPLY (UPS SUPPLY) :
Supply/Fixing/Commissioning of Computer point
supply outlet point should comprises of 4 nos.
5A. 5pin Modular type sockets controlled by
one 5A Modular switch and a Modular light
indicator fixed on Modular GI box of suitable
size, isolated earth terminal etc. and fixing shall
be as per computer table design. including
ferruling as per drawing
Rate in Words :
Page 17 of 25
10
Nos.
10
Nos.
20
Nos.
RATE AMT. (Rs.)
S.NO.
DESCRIPTION
QTY UNIT
NOTE- The box shall have the provision of two
module space for 2 in number RJ-45 & 2 in
number RJ-11. where ever space becomes
free should be filled with dummy. The rates are
inclusive
of
2x2.5+1x2.5sqmm
copper
conductor pvc insulate wire from UPSDB to
Outlet point of UPS t.e. on computor table.
13
PVC HEAVY DUTY CONDUITS :
Supplying/Laying/Commissioning of following
PVC conduits heavy duty, bearing ISI marked
with all accessories such as junction boxes,
outlet boxes, bends, tees as required, the
conduit being laid in ceiling slab or floor or RCC
column or wall chase as required with hooks,
etc.complete as required. All repair works must
be completed mortar of required ratio.
a)
50 mm Conduit PVC Heavy Duty ISI
Rate in Words :
40 mm Conduit PVC Heavy Duty ISI
Rate in Words :
32 mm Conduit PVC Heavy Duty ISI
Rate in Words :
25 mm Conduit PVC Heavy Duty ISI
Rate in Words :
20 mm Conduit PVC Heavy Duty ISI
Rate in Words :
LAN
POINT
Supply/laying
of
DIGILINK G600 CAT--6 wire consists of 4 pair
copper solid, twisted pair duly shielded with
tinned copper braiding as well as aluminium foil
to prevent electro-magnetic interface.
Cables must meet and axceed category 6/class
E standards requirements in ISO/IEC11801,
CENELEC EN50173 & TIA 568-B2-1 LAN wire
should be ferruled on both ends and to be
crimpped with RJ--45 at out let point
b)
c)
d)
e)
14
a)
b)
c)
The LAN wire should be pulled through
existing/raceway.The limit of the wires to be
pulled from the conduits is as follows The rate
are inclusive of wire, RJ-45 etc from HUB to
OUT LET point on computor table
19 mm conduit one wire
Rate in Words :
25 mm conduit two wire
Rate in Words :
32 mm conduit five wire
Rate in Words :
Page 18 of 25
20
40
Mtr
60
Mtr
50
Mtr
75
Mtr
50
Mtr
NOs.
RATE AMT. (Rs.)
S.NO.
d)
e)
DESCRIPTION
QTY UNIT
40 mm conduit ten wire
Rate in Words :
50 mm conduit fifteen wire
Rate in Words :
TOTAL – D :
Amount in Words :
Page 19 of 25
RATE AMT. (Rs.)
SECTION - E : LUMINAIRES
SUPPLY/ERECTION OF FAN & LIGHT FIXTURES
S.NO.
QTY UNIT
DESCRIPTION
1
Supply/installation/testing/commissioning of the following
type of LED/ Non LED type light fixtures/ceiling fan/wall
fan/exhaust fan etc. complete with all accessories etc.
directly on wall/false ceiling/ceiling including connection
with 1.5sq mm FRLS PVC insulated, copper conductor,
single core cable and earthing with 1.5sq mm FRLS PVC
insulated, copper conductor cable, PVC flexible conduit,
end socket, 2" M.S.pipe etc. including repairing of walls
with cement mortar. The light fixtures need to be
connected with existing point wires and further number of
light fixtures to be looped as per drawing. All LED fixtures
material like suspension kit, LED`s Driver etc. shall be
treated as inclusive. Complete in all respect as required.
NOTE :- CONTRCTOR TO COUNT THE QUANTITY
AND GET THE MAKE APPROVAL FROM SITE-INCHARGE AND THE PAYMENT FOR EXCESS
MATERIAL WILL NOT BE MADE.
i
ii
iii
iv
v
viii
ix
x
xi
xii
xiii
Wipro LINEOS LED LM 31-211-XXX-57-XX, 21W
Suspension Type including suspension material(Corridor
Reception Area)
RATE IN WORDS :Wipro LINEOS LED LM 30-211-XXX-57-XX, 21W,
Recess Type (GM RNW)
RATE IN WORDS :Philips Full Glow RC308B LED-30-6500 PSE OD WH OR
Wipro Immaculate CRCO 10R 038HP57 (Office Area)
System Lumen O/P -3000 & Total Power Consumption
40W or less (Work Stn. & Office Area)
RATE IN WORDS :Wipro Stunner CRCO 17R013HP57 13W
Recess
mounted (for Waiting Area)
RATE IN WORDS :Wipro Stunner CRCO 17S013HP57 13W surface
mounted (for Stairwell & porch Area)
RATE IN WORDS :Philips down lighter DN193B LED 12S-6500PSU WH OR
Wipro CRDL 10R015HP60 (for Corridor Area) System
Lumen O/P -1200 & Total Power Consumption 18W or
less (All Corridor)
RATE IN WORDS :Philips down lighter DN194B LED 15S-6500PSU WH OR
Wipro CRDL 11R023HP57
(for Reception) System
Lumen O/P -1200 & Total Power Consumption 18W or
less (Reception Area)
RATE IN WORDS :LEGERO LSR 1002-WW 34260400001 (Staff Entrance)
RATE IN WORDS :Philips Green Spot Rangr BBS 313 1 X DLED - 5000 WH
Lumen O/P -850 & Total Power Consumption 8W or less
(Work stn., Mirror light & Conf. Room Area etc.)
RATE IN WORDS :Philips Stratus LED SO7909 LED44S-5000PSE-ODSI
fixture includes suspending mounting having system
lumen 4400, Power Consumption 54W, CRI>80, PF>.9,
THD < 20%, IEC complient for safety, performance & EMI
including Electronic Driver, Extruded Aluminium Housing &
high efficiency opal diffuser. Complete in all respect.
(Conf. room)
RATE IN WORDS :Wipro Aura Plus CRCO 13R038HP57 Recess mounting
LED Luminair with PMMA diffuser, System lm o/p 3200
or more, system wattage 42w or less Philips Model
Sereno RC869B LED 30S-6500PSE Recess Mounting
RATE IN WORDS :DURLUM LUM-R0600-003 (LUMEO-R PENDENT Light)
for Cafeteria
RATE IN WORDS :xv Philips TMC 501 P 2 X LED with LED Tube Rod 20W
6500K OR Wipro WCO 12 -2208 with LED Tube Rod 20W
(for Kitchen , Basement, Ele. Area, Pump Room, Record
Room)
RATE IN WORDS :xvi Philips TMC 501 P 1 X LED with LED Tube Rod 20W
6500K OR Wipro WCO 12 -1208 with LED Tube Rod 20W
(for Kitchen , Basement, Ele. Area, Pump Room, Record
Room)
RATE IN WORDS :xvii Wipro Orbit LED LM 71 -531-XXX-60-XX 58W including
suspension system, Driver etc (AGM Waiting Area, Entry
to Work Stn.)
RATE IN WORDS :xviii Kapoor Hanging Light LEDISK-53 (Custamised) Reception
xiv
xix
xx
xxi
xxii
xxiii
xxiv
xxv
xxvi
xxvii
xxviii
xxix
xxx
xxxi
xxxii
31
NOS
8
NOS
AMT. (Rs.)
339 NOS
13
NOS
48
NOS
449 NOS
33
NOS
20
NOS
100 NOS
4
NOS
22
NOS
15
NOS
97
NOS
98
NOS
12
NOS
15
NOS
RATE IN WORDS :Philips Lux Space Square BBS 482 DLED-4000 PSD-E 20
WH Lumen O/P -1457 with minimum system Lumen
Efficacyof 77 Lumen/Watt. & Total Power Consumption
19W or less (for Reception Lobby)
RATE IN WORDS :Philips Smart LED Wall Mount BWS 150 LED 200/NW 90
PSU 220-240V 7043 or CGL Model CROCUS #
LWOM10WW/HO 10W (For Lift, Ramp, Well & on
Parapit Wall on Roof Top)
RATE IN WORDS :Legero Model Pictor-7, LED 7W (for Bush lighting)
10
RATE IN WORDS :Legero Praca-3, 4270, 70W, 6000K, LED (for Facad light) 5
RATE IN WORDS :Philips Auro LED 7W 6000K, Size L130 X W47 X D130
mm OR Wipro Spotify CRDL12 R007HP57 (for concealed
lights and before purchase check suitability)
RATE IN WORDS :Legrand Code 573564, Skirting Light With LED 230V-3
Module with cover plate
RATE IN WORDS :Legero Model Kube, LED 10W with 2 lamps (for Main
Entry Coloumn lighting)
RATE IN WORDS :200 mm sweep exhaust fan (for Senior Officers wash
Room)
RATE IN WORDS :300 mm sweep exhaust fan 940rpm EXHD300-6-1 CG or
equalent (for Toilets)
RATE IN WORDS :380 mm sweep exhaust fan including fixing etc complete
in all respect (for Electrical Rooms)
RATE IN WORDS :Aluminium Louvers for 300/380 mm sweep exhaust fan
including fixing etc complete in all respect
RATE IN WORDS :400mm sweep wall fan Model CG HIGH FLO 16" CG OR
Bajaj Midea BW-04
RATE IN WORDS :1200mm sweep ceiling fan Model Entrust CGL OR Bajaj
Excel Star
RATE IN WORDS :Electonic fan regulator steo type Legrand 120w 2 module
RATE
NOS
NOS
NOS
NOS
42
NOS
6
NOS
2
NOS
1
NOS
17
NOS
6
NOS
23
NOS
NOS
98
NOS
49
NOS
49
RATE IN WORDS :TOTAL SECTION - E
RATE IN WORDS :-
Page 20 of 25
SECTION - F : DG SETS
SUPPLY/ERECTION OF D G SETS WITH AMF
S.NO.
1
DESCRIPTION
365KVA DG SET
(SUITABLE TO CPCB NORMS-2)
Supply, installation,testing, loading, unloading, shifting and
commissioning of sound proof (silent type) Diesel Generating set
having 365 KVA 415 V at 1500 RPM , 0.8 power factor at 415 V
suitable for 50 Hz, 3 phase system and for 0.85 load factor , Sound
Attenuated DG set comprising of 448 BHP engine coupled to 415
Volts 400 KVA/320KW Stamford make alternator (voltage
regulation should be ±1.0% from no load to full load & power
factor between 0.8 to 0.9 self regulated) mounted on a common
base frame along with AMF and 800A, 4P ACB, EDO type having
sufficient NO/NC contacts for interlock with other transformer &
DG Set Incomers, fuel tank, batteries with leads etc.. water cooled
type DG. Three phase with Neutral supply shall be provided to
AMF for sensing puposes to start.stop the DG Set.
The set should be for continious operation with permissible
overload of 10 % for 1 hr in 12 hrs of operation. The fuel tank
capacity should not be less than 520 Ltrs. The silencer shall be
domestic/ heavy duty residential type. The noise level shall be
less then 75db at one meter distance from the common base and
the viberation sould not be more then 8mm at common base.
Return fuel pipe, battery charger , AVM pads , engine alternator
safeties , electronic governor including all accessories , all housed
in sound proof acoustic enclosure as per entire satisfaction of the
engineer-in-charge .
NOTE :- AMF to provide sufficient NO+NC contacts for interlocing
with other source of supply.
AMF 365KVA
800A,FP,ACB EDO Type,50kA with SR-18
Breaker Control Switch, Spring Return
kWh Meter, 3Ph, 4W, 415V AC
Digital Ammeter& Voltmeter with SS
Digital Hz Meter
6A, 3 Pole, 3 Way SS
Auto/Manual SS, 3 Pole 4 Way
CT Tape Insulated 1000/5A, CL-1, 15VA
CT Tape Insulated 500/5A, CL-10, 15VA
Indicating Lights LED R-Y-G
Indicating Lights LED B
PB with Elements NO/NC
-01 Nos
-01Nos
-01 Nos
-01 Each
-01 Nos
- 01 Nos
-01 Nos
-03 Nos
- 01 Nos
- 13 Nos
-02 Nos
-08 Nos
Page 21 of 25
QTY
UNIT
1
Each
RATE
AMT.
S.NO.
DESCRIPTION
QTY
UNIT
1
Each
Mushroom Head PB with Element 2NO -1 Nos
DC Ammetert & Voltmeter
- 1 Each
MVMR 415V, AC, 2 C/O Trip/OFF Time 1-10Sec. -1
24V DC Automatic Battery Charger with inbuilt Trickle/Boost
Facility 20A
-01 Nos
4 Point Alarm Annunciator with inbuilt Hooter, Test, Accept &
Reset PB
-01 Nos
Electronic Based Hooter
-01 Nos
Aux. Contactor, Coil Voltage- 24V DC
-02Nos
Aux. Contactor, Coil Voltage -240V AC
-01 Nos
Aux. Relay, 24V DC
-01Nos
O/L Relay with inbuilt 1 Phasing Feature -01 Nos
MCB, 10kA TP 10A
-02 Nos
MCB 10kA DP 6-20A
-04 Nos
MCB 10kA SP 6-10A
-09 Nos
MCB 10kA SP 4A
-01 Nos
Earth fault Relay
-01 Nos
Power Contactor 3 Pole, 25A AC-1 Duty -01 Nos
ON Delay Timer, 240V, AC, 0.6-60Sec.
-01 Nos
ON Delay Timer, 240V AC, 0.6-30 Sec
-01 Nos
ON Delay Timer 240V AC, 18-180 Sec
-01Nos
Priming Timer, 240V AC
-01 Nos
800A, 415V, 50kA, TPN Ele. Grade Al. Bus0Bar
RATE IN WORDS :2
640KVA DG SET
(SUITABLE TO CPCB NORMS-2)
Supply, installation,testing, loading, unloading, shifting and
commissioning of sound proof (silent type) Diesel Generating set
having 640 KVA 415 V at 1500 RPM , 0.8 power factor at 415 V
suitable for 50 Hz, 3 phase system and for 0.85 load factor , Sound
Attenuated DG set comprising of 785 BHP engine coupled to 415
Volts 500 KVA/500KW Stamford make alternator (voltage
regulation should be ±1.0% from no load to full load & power
factor between 0.8 to 0.9 self regulated) mounted on a common
base frame along with AMF and 1000A, 4p ACB EDO typewith
sufficient NO/NC contacts for interlock with other transformer &
DG Set Incomers, fuel tank, batteries with leads etc.. water cooled
type DG. Three phase with Neutral supply shall be provided to
AMF for sensing puposes to start/stop the DG Set.
Page 22 of 25
RATE
AMT.
S.NO.
DESCRIPTION
QTY
The set should be for continious operation with permissible
overload of 10 % for 1 hr in 12 hrs of operation. The fuel tank
capacity should not be less than 520 Ltrs. The silencer shall be
domestic/ heavy duty residential type. The noise level shall be
less then 75db at one meter distance from the common base and
the viberation sould not be more then 8mm at common base.
Return fuel pipe, battery charger , AVM pads , engine alternator
safeties , electronic governor including all accessories , all housed
in sound proof acoustic enclosure as per entire satisfaction of the
engineer-in-charge .
AMF 640KVA
1000A,FP,ACB EDO Type,50kA with SR-18 -01 Nos
Breaker Control Switch, Spring Return
-01Nos
kWh Meter, 3Ph, 4W, 415V AC
-01 Nos
Digital Ammeter& Voltmeter with SS
-01 Each
Digital Hz Meter
-01 Nos
6A, 3 Pole, 3 Way SS
- 01 Nos
Auto/Manual SS, 3 Pole 4 Way
-01 Nos
CT Tape Insulated 1000/5A, CL-1, 15VA -03 Nos
CT Tape Insulated 500/5A, CL-10, 15VA - 01 Nos
Indicating Lights LED R-Y-G
- 13 Nos
Indicating Lights LED B
-02 Nos
PB with Elements NO/NC
-08 Nos
Mushroom Head PB with Element 2NO -1 Nos
DC Ammetert & Voltmeter
- 1 Each
MVMR 415V, AC, 2 C/O Trip/OFF Time 1-10Sec. -1
24V DC Automatic Battery Charger with inbuilt Trickle/Boost
Facility 20A
-01 Nos
4 Point Alarm Annunciator with inbuilt Hooter, Test, Accept &
Reset PB
-01 Nos
Electronic Based Hooter
-01 Nos
Aux. Contactor, Coil Voltage- 24V DC
-02Nos
Aux. Contactor, Coil Voltage -240V AC
-01 Nos
Aux. Relay, 24V DC
-01Nos
O/L Relay with inbuilt 1 Phasing Feature -01 Nos
MCB, 10kA TP 10A
-02 Nos
MCB 10kA DP 6-20A
-04 Nos
MCB 10kA SP 6-10A
-09 Nos
MCB 10kA SP 4A
-01 Nos
Earth fault Relay
-01 Nos
Power Contactor 3 Pole, 25A AC-1 Duty
-01 Nos
ON Delay Timer, 240V, AC, 0.6-60Sec.
-01 Nos
ON Delay Timer, 240V AC, 0.6-30 Sec
-01 Nos
ON Delay Timer 240V AC, 18-180 Sec
-01Nos
Priming Timer, 240V AC
-01 Nos
1000A, 415V, 50kA, TPN Ele. Grade Al. Bus0Bar
RATE IN WORDS :-
Page 23 of 25
UNIT
RATE
AMT.
S.NO.
3
4
a)
b)
DESCRIPTION
QTY
STRUCTURE STEEL
2500
Supply/fabrication/installation of steel work in angles, tees, flats,
channels &
plate etc., duly riveted or welded including cutting fixing gusset
plates, bolts,
nuts, rivets, welding rods,etc., with hoisting and erecting in position
as per
given design with two coats of red oxide and two coats of enamel
paint of
approved shed. The rates includes scaffolding etc (for providing
supoort to DG Exhaust Pipe and supoort to Cable Tray).
RATE IN WORDS :150mm DIA MS PIPE
Supplying, assembling and fixing in vertical/horizontal position ERW
(Electric
Resistance Welded) FE 410 mild steel plain ended casding pipes of
required
dia, conforming to IS : 4270, of reputed & approved make, including
required
hire and laboure charge, fittings and accessories, all complete as
per directions
of Engineer-in-charge of following size:150mm nominal size dia having minimum wall thickness 5.00mm
80
RATE IN WORDS :EXHAUST PIPE INSULATION
80
Supply and fixing of 50mm thick layer of LRB Rockwool insulation
having 100Kg density per cubic metre around the exhaust pipe
150mm dia including clading with aluminium sheet 24 SWG and
covering the pipe from out side complete as required suitable for
DG exhaust pipe temperature upto 450° C as requirements of the
Engineers-in-charge at site..
RATE IN WORDS :TOTAL RUPEES
RATE IN WORDS :-
Page 24 of 25
UNIT
Kg
MTR
MTR
RATE
AMT.
APPROVED LIST OF MAKES
S.NO.
DESCRIPTION
MAKES
1
Phase Indicators LED
Schneider / L&T / Seimens
2
MCB, & RCBO 10kA Curve - C
Siemens (Beta guard), Legrand (DX³), Schneider (Acti-9),
3
MCCBs
Legrand (DPX³), Seimens (3VL), Schneider (NSX), L&T (D-Sine)
4
L.T. CTs
Kappa / AE/ L&T
5
Selector Switch
Siemens / Salzer / L&T
6
Dual Track KWh. Meter
Secure (Liberty) L&T (Gemini)
7
Digital Multifunction Meter
Lgrand (DX ³) L&T (Vega), Secure (Elite 112)
8
Push Buttons
Seimens / L & T/ Scheinder
9
Contactors, 500 V (Confirm IEC Specs.)
L&T/ Seimens/Scheinder
10
Over Load Relay
L&T/ Seimens/ Scheinder
11
Change Over Switch
HPL/ L&T/Schneider
12
Lugs, Thimbles etc
Dowells/ Dollors/ Jainson
13
Compression Glands
HMI /Commet /Sudhir
ON/OFF Delay Timer
L&T/ Teknika/ Scheinder
15
Protection Relays
L&T / Schneider /Alsthom /CGL
16
Capacitor Bank
L&T, Schneider, Legrand
17
Power Factor Relay
L&T, Schneider, Legrand
18
Generator Voltage Relay
L&T/ Teknika/ Scheinder
19
Mains Voltage Monitor Relay
L&T/ Teknika/ Scheinder
20
Selector switch
L&T/Vaishno/ Scheinder
21
Power Cable XLPE, 11 KV grade
Finolex / Polycab/ Havells/ CCI
22
Control Cable (1.1KV grade)
Finolex / Polycab/ Havells
23
FRLS PVC Insulated Cu. Wires
Finolex / Polycab/ Havells
24
PVC Conduits & Accessories
Diplast, AKG, BEC
25
Modular Switches & Sockets etc.
Legrand (Arteor) Schneidert (Neo C Metro) Cabtree (Murano)
26
Dist. Boards Double/SingleDoor
Legrand (Ekinoxe), Seimens (Beta Guard), Schneider (Acti-9)
27
DG Set
Cummins Sudhir/Catter Piller/ Kirloskar Green
Light Fixtures
Philips,Wipro, GE
Transformer (Dry / Oil Cooled)
CGL/Voltamp/Scheinder/Sudhir
30
G.O. Switch
Jaipuria/ Isotech/ Skiper
31
VCB
CGL, Schneider, ABB
32
Ceiling Fan, Exh Fan & Wall Fan
CGL, Bajaj, Usha
33
OLTC
CTR or OLG
14
28
29
Page 25 of 25