GE - ASTAT - Softstarters for 3ph standard induction motors

advertisement
GE
Industrial Solutions
ASTAT
Soft starters for 3ph standard induction motors
High reliability for multiple applications
GE imagination at work
ASTAT S
Small soft starters with integral bypass
ASTAT S is compact, easy to operate soft starter, designed for use with
standard 3-phase squirrel cage motors. It provides an advanced method of
reducing current during motor starting and stopping.
ASTAT S will start supplying a reduced voltage to the motor, increasing up to
the rated voltage, so avoiding, high currents and generating soft
starting and stopping.
The motor has to be able to start in a reduced voltage.
Approvals/Marking
Solid soft starter for standard 3ph AC motors up to 30kW at 400V AC
Voltage ratings up to 600V
Two phase control with integral bypass
Compact, small case
DIN rail mounting. Optional from 31A
Start and soft stop features
Small soft starters
•
•
•
•
•
•
Technical data
Ratings
Voltage ratings
cULus
The cUL, is achieved for all range of ASTAT S,
except for 58A models, items QA02P058S,
QA12P058S, QA22P058S, QA32P058S.
Frequency range
Load
3ph AC systems
220/230V (+10%, -15%) for units QA02P_ _ _ S
380/415V (+10%, -15%) for units QA12P _ _ _ S
480/500V (+10%, -15%) for units QA22P _ _ _ S
575/600V (+10%, -15%) for units QA32P _ _ _ S
50/60Hz (±5%)
3ph, AC standard motors
Control specifications
Ramp up
Ramp down
Initial voltage
Starting torque
0.5 - 10 s (set by potentiometer)
0.5 - 10 s (set by potentiometer)
0 - 80% Un (set by potentiometer)
0 - 64% Tn
I/O control
Inputs
Outputs
one input for Start/Stop
one output for «End of Ramp» signal
for ratings 31, 44, 58A
Ambient conditions
Operating temperature
Storage temperature
Relative humidity
Max. altitude
Protection degree
0 to 40ºC. Up to 60ºC derating by 1.2% per ºC
-20 to 70ºC
up to 80%, without condensation
up to 1000m.
Above this derate by 5% each 100m
IP20
1
ASTAT S
Small soft starters with integral bypass
Digital soft starters
Input Current
voltage rating (2)
VAC
A
220
8
17
22
31
44
58
Maximum
current
A
28
60
77
110
150
200
220/230V
kW / HP
1.5 / 2
4 / 5.5
5.5 / 7.5
7.5 / 10
11 / 15
15 / 20
Maximum motor power (1)
380/415V 480/500V 575/600V
kW / HP kW / HP kW / HP
-
Cat. No.
Ref. no. Pack
QA02P008S
QA02P017S
QA02P022S
QA02P031S
QA02P044S
QA02P058S
120881
120882
120883
120884
120885
120886
1
1
1
1
1
1
400
8
17
22
31
44
58
28
60
77
110
150
200
-
4 / 5.5
7.5 / 10
11 / 15
15 / 20
22 / 30
30 / 40
-
-
QA12P008S
QA12P017S
QA12P022S
QA12P031S
QA12P044S
QA12P058S
120892
120893
120894
120895
120896
120897
1
1
1
1
1
1
500
8
17
22
31
44
58
28
60
77
110
150
200
-
-
5.5 / 7.5
11 / 15
15 / 20
22 / 30
30 / 40
45 / 60
-
QA22P008S
QA22P017S
QA22P022S
QA22P031S
QA22P044S
QA22P058S
120898
120899
120900
120901
120902
120903
1
1
1
1
1
1
600
8
17
22
31
44
58
28
60
77
110
150
200
-
-
-
7.5 / 10
15 / 20
22 / 30
30 / 40
37 / 50
55 / 75
QA32P008S
QA32P017S
QA32P022S
QA32P031S
QA32P044S
QA32P058S
120904
120905
120906
120907
120908
120909
1
1
1
1
1
1
QAOPTDIN
120910
1
Accessory
DIN rail mounting kit for types 31A, 44A and 58A
(1) Ratings for standard 4-poles AC motors
(2) See Operations/hour in table below
Cycles/hour includes both soft start and soft stop
Time between rampings Start/Stop
Starting
Ramp 1 sec.
current (A)
QA_2P008S
8
7
16
16
24
26
28 (*)
32
QA_2P017S
17
7
34
16
51
26
60 (*)
32
QA_2P022S
22
7
44
16
66
26
77 (*)
32
QA_2P031S
31
4
62
8
93
12
110 (*)
15
QA_2P044S
44
4
88
8
132
12
155(*)
15
QA_2P058S
58
4
116
8
174
12
200 (*)
15
(*) Maximum starting current at all
2
Ramp 2 sec.
Ramp 5 sec.
Ramp 10 sec.
15
33
51
62
15
33
51
62
15
33
51
62
8
15
24
31
8
15
24
31
8
15
24
31
35
77
125
155
35
77
125
155
35
77
125
155
20
38
62
80
20
38
62
80
20
38
62
80
70
155
250
70
155
250
70
155
250
40
76
124
40
76
124
40
76
124
-
ASTAT S
Diagrams
Control by push-buttons,
line contactor and thermal overload
relay (soft start)
Control by permanent command
(soft start and stop)
Small soft starters
start/stop
Control by push-buttons and line
contactor (soft start)
Motor power
380/415V
kW
Hp
4
7.5
11
15
22
30
5.5
10
15
20
30
40
ASTAT S
Q1
QA12P008
QA12P017
QA12P022
QA12P031
QA12P044
QA12P058
GPS1B*AK
GPS1B*AN
GPS1B*AP
GPS1B*AR
GPS2B*AT
GPS2B*AU
Forward/reverse control by
push-buttons(3)
Q2
KM1
F1-F2
S1-S2-S3
Contactor
Q3
Thermal
overload relay
Am fuses
10
25
32
40
63
80
EC25A
EC25A
EC25A
EC32A
CL06A
CL07A
268103
268105
268106
268108
113722
113723
-
P9
P9
P9
P9
P9
P9
Coordination type 2, with thermal overload relays, class 10.
For other thermal class, please consult our Controls & Power Electronics catalogue.
(1)
(2)
(3)
(4)
Use dry contact only.
End of Ramp output relay (only types 31A, 44A and 58A).
Forward/Reverse operation must be done when motor is not rotating.
Ground terminal only for types 31A, 44A and 58A.
3
ASTAT S
Performances
Direct-on-line start
ASTAT S soft start
DOL
Voltage
Current
Voltage
Speed
Speed
Current
Digital soft starters
Uo=0.5Un, To=25Tn, RAMP UP 0.9s
Time
Time
Direct-on-line stop
ASTAT S soft stop
Current
Current
Speed
Speed
Time
4
RAMP DOWN 0.5s
Voltage
Voltage
DOL
Time
ASTAT S
Dimensional drawings
Small soft starter with integral bypass
TYPE
Weight (kg)
QA_2P017S
0.610
QA_2P022S
0.650
QA32P008S
0.650
TYPE
Weight (kg)
QA12P008S
0.470
QA22P008S
0.470
Small soft starters
Dimensions in mm
Dimensions in mm
TYPE
QA_2P031S
QA_2P044S
QA_2P058S
Weight (kg)
1.370
1.400
1.400
2
2
Dimensions in mm
5
ASTAT
Notes
Soft starters
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
6
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
ASTAT XT
ASTAT XT
D
Digital
soft starters for 3ph standard
induction motors
in
Digital soft starters
G new ASTAT XT solid state soft starter features microprocessor control
GE´s
digital technology. Setup and adjustment is performed through a six-button
d
keypad and parameters or messages are displayed out trough a friendly
ke
LCD multilanguage interface with two rows, sixteen alphanumeric characters
LC
each. The design includes isolated I/O and high level of protection in their
ea
circuits to minimize the disturbance effects while working in the hardest
ci
industrial environment.
in
ASTAT XT soft starter offers reliable performance and smooth acceleration
A
for a variety of standard AC motors up to 1400A and up to 690V, reducing
fo
mechanical shock to the driving system, resulting in extended component
m
and motor life.
a
Approvals / Marking
ASTAT XT offers many traditional features such a motor overload function,
A
adjustable ramps, current limit, kick start, but also other high end features
like Inside-Delta operation, Torque control, Pump control and a reliable motor
and unit set of protections.
Key features
For units up to 820A. “U” type
Control panel
• Ratings up to 1400Amps and up to 690VAC
• Friendly multilanguage interface with two rows, sixteen characters each
• Built-in with three extra power terminals for external bypass
• In-Line or Inside-Delta operation modes
• Torque control and pump control advanced features
• Motor protection according IEC 10, 20 and NEMA 10, 20, 30, even if
ASTAT XT is in bypass
• Built-in communications RS485 port, and ModBus protocol as standard
• ProfibusDP and DeviceNet optional interfaces for communications
7
ASTAT XT
Recommended motor and type unit ratings
Light Duty
Normal Duty (IEC Class 10)
Max rating
Rated
current (A) current (A)
Digital soft starters
Mains voltage
230-500Vac
Control voltage
230Vac
Digital inputs
voltage
90-230Vac
Mains voltage
690Vac
Control voltage
230Vac
Digital inputs
voltage
90-230Vac
230V
kW
400V-415V 480V-500V
kW
kW
Heavy Duty
690V
kW
Rated
current (A)
230V
kW
400V-415V 480V-500V
kW
kW
690V
kW
8
17
34
54
65
72
104
130
156
170
248
361
390
480
480
610
610
820
820
1180
1375
1750
8
17
31
44
58
72
85
105
145
170
210
310
390
460
460
580
580
650
820
950
1100
1400
1.5
4
7.5
11
15
22
22
30
45
55
55
90
110
132
132
160
160
200
250
315
355
400
3
7.5
15
22
30
37
45
55
75
90
110
160
200
250
250
315
315
355
400
560
630
800
4
7.5
18.5
30
37
45
55
55
90
110
132
200
250
315
315
400
400
400
560
630
800
1000
-
8
12
31
44
55
66
80
99
130
134
203
310
344
432
432
488
552
552
690
950
1076
1400
1.5
3
7.5
11
15
18.5
22
30
37
37
55
75
110
132
132
160
160
160
200
315
355
400
3
5.5
15
22
30
37
45
55
55
75
110
160
160
250
250
250
315
315
400
560
630
800
4
5.5
18.5
30
37
45
55
55
90
90
132
200
250
315
315
355
400
400
500
630
800
1000
-
8
17
34
54
65
72
104
130
156
170
248
361
390
480
610
820
1180
1375
1750
8
17
31
44
58
72
85
105
145
170
210
310
390
460
580
650
950
1100
1400
-
-
-
5.5
15
22
37
55
55
75
90
132
160
200
250
355
400
560
630
900
1000
-
8
12
31
44
55
66
80
99
130
134
203
310
344
432
488
552
950
1076
1400
-
-
-
5.5
7.5
22
37
45
55
75
90
90
132
200
250
315
400
400
560
900
1000
-
Remarks page 8
- Motor kW ratings given in above table are for IEC, standard AC four poles motors.
- Always check that motor rated current is less than the specified rated current of the starter, for the specific application (Normal Duty or Heavy Duty)
- Other control and digital inputs voltages are available. Please contact GE
- Profibus or DeviceNet options cannot be ordered separately. For those communication networks, please order the ASTAT XT with the required option built-in
remarks page 9
- Motor HP ratings given in NEMA table are for standard AC four poles motors.
- Always check that motor rated current is less than the specified rated current of the starter, for the specific application (Light Duty, Normal Duty or Heavy Duty)
- Remote mounting kit for keypad that includes cable (3m), remote keypad box, dummy cover, frame and brackets:
- Frame A
QTAKPADKIT1
169072
- Frame B and others QTAKPADKIT2
169073
For the international version:
- Frame A
QTAKPADKIT1SG
- Frame B and others QTAKPADKIT2SG
QT10008U21MS
ASTAT XT 8A-72A
8
129052
129053
QT10105U21MS
ASTAT XT 105A-170A
QT10460N21MS
ASTAT XT 460A-650A
ASTAT XT
Built-in communication network
Modbus
Profibus DP
QT___N21PS
QT___U21PS
Cat. No.
Ref. No.
Ref. No.
International version
Modbus
DeviceNet
QT___N21DS
QT___U21DS
Ref. No.
Cat. No.
Ref. No.
Profibus DP
QT___N21PSG
QT___U21PSG
Ref. No.
DeviceNet
QT___N21DSG
QT___U21DSG
Ref. No.
169075
169076
169077
169078
169079
169080
169081
169082
169083
169084
169085
169086
169087
169094
169088
169095
169089
169096
169090
169097
169098
169099
169214
169215
169216
169217
169218
169219
169220
169221
169222
169223
169224
169225
169226
169233
169227
169234
169228
169235
169229
169236
169237
169238
169314
169315
169316
169317
169318
169319
169320
169321
169322
169323
169324
169325
169326
169333
169327
169334
169328
169335
169329
169336
169337
169338
QT10008U21MSG
QT10017U21MSG
QT10031U21MSG
QT10044U21MSG
QT10058U21MSG
QT10072U21MSG
QT10085U21MSG
QT10105U21MSG
QT10145U21MSG
QT10170U21MSG
QT10210U21MSG
QT10310U21MSG
QT10390U21MSG
QT10460N21MSG
QT10460U21MSG
QT10580N21MSG
QT10580U21MSG
QT10650N21MSG
QT10820U21MSG
QT10950N21MSG
QT11100N21MSG
QT11400N21MSG
129213
129214
129215
129216
129217
129218
129219
129220
129221
129222
129223
129224
129225
129229
129226
129230
129227
129231
129228
129232
129233
129234
120954
120957
120958
120959
120960
120961
120962
120963
120964
120965
120966
120967
120968
120972
120969
120973
120970
120974
120971
120975
120976
120977
817850
817851
817852
817853
817854
817855
817856
817857
817858
817859
817860
817861
817862
817863
817864
817865
817866
817867
817868
817869
817870
817871
QT30008N21MS
QT30017N21MS
QT30031N21MS
QT30044N21MS
QT30058N21MS
QT30072N21MS
QT30085N21MS
QT30105N21MS
QT30145N21MS
QT30170N21MS
QT30210N21MS
QT30310N21MS
QT30390N21MS
QT30460N21MS
QT30580N21MS
QT30650N21MS
QT30950N21MS
QT31100N21MS
QT31400N21MS
169119
169120
169121
169122
169123
169124
169125
169126
169127
169128
169129
169130
169131
169132
169133
169134
169135
169136
169137
169490
169491
169492
169493
169494
169495
169496
169497
169498
169499
169500
169501
169502
169503
169504
169505
169506
169507
169508
169573
169574
169575
169576
169577
169578
169579
169580
169581
169582
169583
169584
169585
169586
169587
169588
169589
169590
169591
QT30008N21MSG
QT30017N21MSG
QT30031N21MSG
QT30044N21MSG
QT30058N21MSG
QT30072N21MSG
QT30085N21MSG
QT30105N21MSG
QT30145N21MSG
QT30170N21MSG
QT30210N21MSG
QT30310N21MSG
QT30390N21MSG
QT30460N21MSG
QT30580N21MSG
QT30650N21MSG
QT30950N21MSG
QT31100N21MSG
QT31400N21MSG
129257
129258
129259
129260
129261
129262
129263
129264
129265
129266
129267
129268
129269
129270
129271
129272
129273
129274
129275
129511
129512
129513
129539
129540
129541
129542
129543
129544
129545
129546
129547
129548
129549
129550
129551
129552
129553
129554
817872
817873
817874
817875
817876
817877
817878
817879
817880
817881
817882
817883
817884
817885
817886
817887
817888
817889
817890
Order codes
QT10008U21MS
QT10017U21MS
QT10031U21MS
QT10044U21MS
QT10058U21MS
QT10072U21MS
QT10085U21MS
QT10105U21MS
QT10145U21MS
QT10170U21MS
QT10210U21MS
QT10310U21MS
QT10390U21MS
QT10460N21MS
QT10460U21MS
QT10580N21MS
QT10580U21MS
QT10650N21MS
QT10820U21MS
QT10950N21MS
QT11100N21MS
QT11400N21MS
NEMA ratings. Recommended unit type and motor ratings
Mains voltage
230-500VAC
Mains voltage
460-600VAC
Light Duty - NEMA 10
Normal Duty - NEMA 20
Heavy Duty - NEMA 30
Current 230V 460V 575V Current 230V 460V 575V Current 230V 460V 575V
rating
rating
rating
A
HP
HP
HP
A
HP
HP
HP
A
HP
HP
HP
8
2
5
8
2
5
8
2
5
17
5
10
17
5
10
12
3
7.5
34
10
25
31
10
20
31
10
20
54
20
40
44
15
30
44
15
30
65
20
50
58
20
40
55
20
40
72
25
50
72
25
50
66
20
50
104
40
75
85
30
60
80
30
60
130
50
100
105
40
75
99
40
75
156
60
125
145
50
100
130
50
100
170
60
125
170
60
125
134
50
100
262
100
200
210
75
150
203
75
150
387
150
300
310
100
250
310
100
250
414
150
350
390
150
300
361
150
300
480
200
400
460
150
350
432
150
350
610
250
500
580
200
400
552
200
400
820
820
250
500
690
250
500
8
17
34
54
65
72
104
130
156
170
262
387
414
480
610
820
-
5
10
25
40
50
50
75
100
125
125
200
300
350
400
500
-
5
15
30
50
60
60
100
125
150
150
250
400
400
500
-
8
17
31
44
58
72
85
105
145
170
210
310
390
460
580
820
-
5
10
20
30
40
50
60
75
100
125
150
250
300
350
400
500
5
15
25
40
50
60
75
100
150
150
200
300
400
400
400
500
8
12
31
44
55
66
80
99
130
134
203
310
361
432
552
690
-
5
7.5
20
30
40
50
60
75
100
100
150
250
300
350
400
500
5
10
25
40
50
60
75
100
125
125
200
300
300
400
500
-
Cat. No.
Ref. No.
QT10008U21MS
QT10017U21MS
QT10031U21MS
QT10044U21MS
QT10058U21MS
QT10072U21MS
QT10085U21MS
QT10105U21MS
QT10145U21MS
QT10170U21MS
QT10210U21MS
QT10310U21MS
QT10390U21MS
QT10460U21MS
QT10580U21MS
QT10820U21MS
169075
169076
169077
169078
169079
169080
169081
169082
169083
169084
169085
169086
169087
169088
169089
169090
QT20008U21MS
QT20017U21MS
QT20031U21MS
QT20044U21MS
QT20058U21MS
QT20072U21MS
QT20085U21MS
QT20105U21MS
QT20145U21MS
QT20170U21MS
QT20210U21MS
QT20310U21MS
QT20390U21MS
QT20460U21MS
QT20580U21MS
QT20820U21MS
169100
169101
169102
169103
169104
169105
169106
169107
169108
169109
169110
169111
169112
169113
169114
169115
9
ASTAT XT
Unit configuration
QT
1
0008
U
2
1
M
ASTAT XT range
Digital soft starters
Main voltage
230-500V
460-600V
690V
1
2
3
UL certification(1)
UL
non-UL
U
N
Control voltage(2)
110VAC
230VAC
1
2
Digital inputs, voltage(3)
90-230VAC
24VDC
1
2
Communications
Standard
Profibus
DeviceNet
M
P
D
Versions
Standard
S
International SG
Current ratings
(1) - ASTAT XT up to 600V, and up to 170A (Cat Numbers up to QT10170_ or up to QT20170) are always cUL certified. Option “N” not available
- Units QT2, from QT20008_, up to QT20820_ are always cUL certified. Option “N” not available.
- Units QT1, or QT2 from QTx0950_ up to QTx1400 are not UL certified. Option “U” not available.
- Units QT3__, rated to 690V, are not UL certified. Option “U” not available
(2) ASTAT XT standard control voltage configuration is option 2, voltage 230VAC, +10%, -15%
(3) ASTAT XT standard configuration for inputs is option 1, voltage 90-230VAC, +10%, -15%
OPTIONS:
- Remote mounting kit for keypad that includes cable (3m), remote keypad box, dummy cover, frame and brackets:
- Frame A
QTAKPADKIT1
169072
- Frame B and others QTAKPADKIT2
169073
For the international version:
- Frame A
QTAKPADKIT1SG
- Frame B and others QTAKPADKIT2SG
10
129052
129053
S
ASTAT XT
Technical data
Ratings
3ph AC supply
Main voltage
Starter current rating
Motor current rating
Control voltage
for 3ph AC motors
3ph Induction motors
1ph AC supply
Frequency range
Digital inputs voltage
50/60Hz systems
230 to 500VAC +10%, -15% for QT1xxx units
460 to 600VAC +10%, -15% for QT2xxx units
690VAC +10%, -15% for QT3xxx units
From 8A up to 1400A.
Motor rated current from 50% to 100% of starter current
230VAC, +10, -15%, 50/60Hz or
110VAC, +10, -15%, 50/60Hz (optional)
Wide from 45Hz to 65Hz. Auto-tracking frequency range
90-230Vac, +10 -15%, 50/60Hz
24Vdc, +10%, -15% (optional)
Control specifications
Operation mode
Run operation
Operator interface
Initial voltage
Starting current
Acceleration ramp time
Deceleration ramp time
Current limitation
Bypass
Monitoring
Digital control with microcontroller.
Starting ramp, with progressive increase in voltage and current limitation
In-Line (three wires) or Inside-Delta (six wires) of the motor
Soft Start and Soft stop by multiple choices, including torque control both at start or Stop phases
By LCD display, keypad and Indication LEDs
Display: LCD with two rows, 16 characters each
Type: Multilanguage, dip-switch selectable for English, Italian, Spanish and German
Keys: Six keys, Mode, reset, Set, Select and Up / Down
LEDs: ON, Start, Run, Soft Stop, Stop, Save / Slow Speed, Dual Set / Reverse and Fault
10-50% Un. Up to 80% with expanded settings function
100-400% In. Can be extended up to 500%, by using extended settings
1-30 sec. Can be extended up to 90 sec, by using extended settings
1-30 sec. Can be extended up to 90 sec, by using extended settings
100-400% of motor rated current. Can be extended up to 500% by using extended settings
By external contactor while motor is full protected by ASTAT XT
Motor current, line voltage, motor thermistor resistance, test and maintenance and statistics
Technical data
Control system
Environmental conditions
Operating temperature
Storage temperature
Maximum altitude
Humidity
Protection degree
Pollution degree
-10°C up to 60ºC, with current derating by 2.5% per °C, from 50ºC
-20ºC up to 70ºC
Up to 1000 mts. Ask your dealed for installation at higher altitude
95% at 50ºC or 98% at 45ºC
IP20 for units up to 72A, IP00 for units from 85A up to 1400A
Class 3
Standards
Global standards
EMC emissions
Immunity
Safety
CE for the full trange. UL, cUL for specified units up to 820A
EN 61000-6-4
CISPR 11 Class A
EN 61000-6-2
ESD 8KV air, IEC 801-2;
Electric RF field 10 V/m, 20-1000Mhz, IEC 801-3
Fast transients 2KV, IEC 801-4
EN 600947-1
Related to safety requirements. UL508C
11
ASTAT XT
Functions
Available standard functions
Soft start and soft stop
Pump control
Torque control
Digital soft starters
In line / Inside delta
Bypass
Kick start
End of ramp
Lock-out
Dual settings
Energy saving
Slow speed
Auto reset
Cooling fan control
Generator supply
Keypad lock
Built-in communications
Statistic data
ASTAT XT is provided with a soft start and soft stop features, including five independent acceleration and
decelertaion curve models.
The factory default curve is used for general purpose, other three are used for pump control and the last one for
torque control.
Specific function for pump control, that avoids overpressure in the system at the end of acceleration phase and
suppresses the hammering at stopping phase.
Provides a smoth time controlled torque ramp acelleration and deceleration, with linear deceleration of the torque
resulting in a close to linear speed deceleration, thus eliminating stall conditions.
ASTAT XT allows either traditional Line operation or Inside Delta operation.
When the ASTAT XT is installed to operate Inside Delta, the individual phases of the starter are connected in series
with the individual motor windings (six wiring connections like the Start-Delta starters), thus reducing the current
x1.73, and allowing the use of a much smaller starter (x1.5 less than motor rated current).
ASTAT XT allows bypass operation using an external contactor, controlled ON/OFF by starter function EOR
(End Of Ramp).
The starter is provided with three dedicated power terminals to facilitate wirings to the bypass contactor.
ASTAT XT protections to motor are enabled, even in bypass.
This function allows to start high friction loadsthat require high starting torque for a short period of time. When
this function is enabled, a pulse of 80% Un during an adjustable time from 0 to 1sec is given to the motor. After
this pulse the output voltage is ramping down to starting voltage setting, before ramping up again to full voltage.
Detects end of acceleration and outputs a signal by an dry relay contact. This signal can be delayed by an
adjustable timer from 0-120 sec.
Allows to control the number of startings into a period of time, then protecting both motor and ASTAT.
By this function, ASTAT XT is able to control a secondary motor Dual setting of Starting voltage, Starting current,
Current limit, Ramp up, Ramp down and Motor current parameters can be selected by using one of the
programmable ASTAT XT inputs.
Activated when the motor has a light load for extended periods of time, then reducing the output voltage level
and decreasing the reactive current and motor copper/Iron losses.
This function can be enabled or disabled by dedicated parameters in ASTAT XT.
Function that allows the motor to run at 1/6 constant rated speed, for a short period of time of maximum 30sec.
This function supports forward and reverse operation.
This function allows the ASTAT XT automatic recover after a fault caused by Undervoltage, Undercurrent or
Phase lost. Auto-reset can be programed up to maximum 10 attempts.
Allows thre method of control for the ASTAT´s built-in cooling fans.
- Continuous operation
- Controlled by an external Input
- Automatically OFF controlled, after five minutes ASTAT XT is stopped
This is a specific function useful when the starter is powered from a diesel generator rather than from
commercial power supply. The function is enabled by an internal Dip switch, and helps to minimize the negative
effects caused by the generator´s voltage fluctuations during starting.
This function is enabled by means of starter´s internal dipswitch, then locking the keypad.
This is usefull to prevent undesired parameter modifications.
ASTAT XT includes a ModBus RTU communications protocol. Communications are carried out through a half duplex
RS485 port, with maximum baudrate of 9600, supporting up to 247 stations.
ASTAT XT records useful data for maintenance and start up
- Last 10 trip events
- Statistical data like number of starts, number of trip events and elapsed RUN time.
- Last trip data information of motor current, starting current and acceleration time.
Motor and starter protection
Overload
Motor thermistor
Too many starts
Long start time
O/C JAM fault
Undercurrent
Undervoltage
Overvoltage
Phase loss
Frequency loss
Phase sequence
Slow speed time
Wrong connection
Shorted SCR
Over temperature
External fault
Wrong parameters
OC or wrong CON
12
Trips the ASTAT XT when current exceeds the overload trip level according IEC Class 10, 20 or NEMA 10, 20, 30.
Trips when motor thermistor resinstance decreases below trip level set ASTAT XT allows both PTC or NTC sensors,
with adjustable trip level.
Trips if the number of starts, during duty cycle time exceeds the preset number.
Trips if output voltage does not reach rated voltage at the preset Max. Start time.
Trips under the following conditions:
- Instantaneously when current exceeds 8.5 x ASTAT XT current
- During starting when current exceeds 8.5 x motor current
- During running when current exceeds 200-850% of motor current
O/C JAM has a programmable triping delay of 0-5 seconds
Trips when line current drops below the preset level for the preset time.
Trips when line voltage drops below the preset level for the preset time.
Trips when line voltage increases above a preset level for a preset time.
Trips if 1 or 2 phases are lost.
Trips if frequency is not in the range of 40-66.6Hz.
Trips if line phase sequence is wrong.
Trips when operating at slow speed for extended periods
Trips the ASTAT XT when one or more motor phases is not properly connected to ASTAT XT’s load terminals
or if there is an internal disconnection in the motor winding.
Trips and prevents starting if any SCR is short-circuited or when motor windings are shorted.
Heat-sink over-temperature. Trips the ASTAT XT when the heat-sink temperature rises above 85°C.
Trips the ASTAT XT when a NO contact between terminals 19-21 closes for over two seconds.
Parameters not transferred from RAM to EEPROM or vice versa.
Trips when the ASTAT XT is connected inside Delta and wrong connection or overcurrent is detected.
ASTAT XT
Overload protections - Thermal characteristics
The ASTAT XT allows motor protection according IEC Class 10 or Class 20 and NEMA 10, 20 or 30.
User free selectable by ASTAT internal dedicated parameter.
IEC Class 10
IEC Class 20
Sec.
10000
1000
1000
100
100
Overload protections
Sec.
10000
COLD
COLD
10
10
HOT
HOT
1
1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0
Multiples of motor FLA Rating In
NEMA 10 Light Duty
1
1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0
Multiples of motor FLA Rating In
NEMA 20
Sec.
10000
Sec.
10000
1000
1000
100
100
COLD
COLD
10
10
HOT
1
1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0
Multiples of motor FLA Rating In
HOT
1
1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0
Multiples of motor FLA Rating In
Maximum number starting /hour
NEMA 30
Ramp time
Sec.
10000
Starting
current
I/In (1)
1000
100
COLD
10s
20s
30s
2
24
12
8
3
16
8
5
4
12
6
4
(1) In= rated current of ASTAT XT in the specified class IEC/NEMA
10
HOT
1
1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0
Multiples of motor FLA Rating In
13
ASTAT XT
1L1
A
Main supply
Digital soft starters
I/O Wiring, basic scheme
3L2
CT1
2T1
CT2
M
3ph
4T2
B
5L3
6T3
C
L
10
F
11
N
12
Stop 4
13
Soft Stop 5
14
Start 6
15
Energy save/Slow speed/reset 7
16
D.Adj./Reversing/Reset 8
17
Common 9
18
External fault input 19
SG
Control supply
Inmediate
RUN
Fault relay
EOR (End Of Ramp) relay
RS485 port
DNeutral 21
Ground
T1 28
Thermistor input
T2 29
D+
Grd
31 (-)
32 (+)
Analogue output
Profibus
(option)
V-
Power supply
CL
Signal CAN-H
Dr
Drain
CH
Signal CAN-L
V+
Power supply
Note: Profibus or DeviceNet options cannot be ordered separately.
For those communication networks, please order the ASTAT XT with the required option built-in (see pages 8 and 9).
14
DeviceNet (option)
Ground 30
ASTAT XT
I/O terminal board specifications
Power I/O terminals
Terminals
Function
1L1, 3L2, 5L3
Mains input
2T1, 4T2, 6T3
A, B, C
G
Output to motor
Bypass
Ground
Description
3ph Input voltage according ASTAT XT main voltage option rating
(Option 1, QT1_) 230-500VAC, +10%/-15% 50/60Hz
(Option 2, QT2_) 460-600VAC, +10%/-15% 50/60Hz
(Option 3, QT3_) 690VAC, +10%/-15% 50/60Hz
Power output terminals to 3ph AC motor
Bypass terminals for external bypass contactor
ASTAT XT, ground connection
L, N
F
Control supply
Fan control
110VAC or 220VAC, according ASTAT XT control voltage rating
Cooling fan external control, together with jumper J1
Control voltage and fan consumption VA:
QTx0008 to QTx0031: No fan. Total consumption: 150VA
QTx0044 to QTx0072: Fan 35 VA. Total consumption 185VA
QTx0085 to QTx0170: Fan 60 VA. Total consumption 210VA
QTx0210 to QTx0390: Fans 105VA. Total consumption 255VA
QTx0390 to QTx 1400A : Fans 150VA. Total consumption 300VA
Digital inputs
4
5
6
7
8
9
Stop
Soft Stop
Start
Progammable inputs
Progammable inputs
Common
Dedicated input to Stop
Dedicated input to Soft Stop
Dedicated input to Start
Programmable to functions Energy saving, slow speed and reset
Programmable to functions Dual set, Reverse and Reset
Common terminal for digital inputs from 4, 5, 6, 7 and 8
I/O terminal board
Control power supply
Operating voltage of digital inputs from 4 to 9
Digital Input hardware is operated according either of below ordered voltage ratings
(Option 1, standard) from 90 to 230VAC +10%, 50/60Hz
(Option 2, optional) 24VDC +10%/ -15%
Other inputs
19, 21
21
28, 29
External fault
Neutral
Motor thermistor
Requires a free voltage relay contact, to detect external fault
This terminal may be connected to mains neutral when available
PTC or NTC programable input for motor thermistor protection
The input can be enabled or disabled, and programmed at desired trip level resistance
Digital outputs
10, 11, 12
13, 14, 15
16, 17, 18
RUN
FAULT
EOR
Run relay with NO and NC dry contact. Programmable ON delay
Fault to ON or Fault to OFF programmable function
End of ramp relay. Programmable ON delay
Relay outputs ratings
Max rating: 8A, 250VAC, 2000VA max
Analogue output
31, 32
30
Current output
Ground
Range 0 to 2xIn. Programmable 0-10VDC, 0-20mA or 4-20mA.
Ground terminal for analogue output
Communications
D+, D-, SG
RS485 terminals
D-9 connector
V+, CL, Dr, CH, V-
Profibus port
DeviceNet terminals
RS485 communication port, half duplex for ModBus protocol
Baudrate 1200, 2400, 4800, 9600 BPS
Optional Profibus communications port
Optional Devicenet communications port
15
ASTAT XT
Application wiring diagrams
Basic diagram without line contactor(1)
With Soft Start and coast to Stop
by permanent command control
L1 L2 L3
Q1
1
3
5
2
4
6
1
T1
1
2
Q3
4
Q2
0 STOP
I START
START 6
SOFT STOP 5
STOP 4
L
N
5L3
6T3
COMMON 9
1L1
3L2
A1
4T2
F1
2T1
Digital soft starters
3
2
GND
EOR
R
18 17 16
FAULT
R
15 14 13
RUN
R
12 11 10
U1 V1 W1
M
3~
Basic diagram without line contactor(1)
With Soft Start and Soft Stop
by permanent command control
L1 L2 L3
Q1
1
3
5
2
4
6
1
3
2
4
T1
1
2
Q3
Q2
0 STOP
I START
START 6
SOFT STOP 5
L
STOP 4
N
5L3
6T3
GND
COMMON 9
1L1
3L2
4T2
A1
2T1
F1
EOR
R
18 17 16
FAULT
R
15 14 13
RUN
R
12 11 10
U1 V1 W1
M
3~
(1) Schemes are given for information purposes. Add additional emergency safety stop, if it is required for your application.
Remarks
1. Check coordination tables for proper selection of breaker and line contactor.
2. Control voltage and control input voltage are from same source in above example. Please check manuals if you have different sources for
control voltage and control input voltage.
3. Semiconductor fuses “F” are only required for Type 2 coordination. Please check coordination tables.
4. In spite of ASTAT XT can operate without line contactor, the use of a line contactor will increase the operation safety. Anyway provide a way to
switch off the breaker in case of an emergency.
5. Line and bypass contactors should be dimensioned according AC1 category.
16
ASTAT XT
Application wiring diagrams
Basic diagram without line contactor(1)
With Soft Start and Soft Stop
by push-buttons control
L1 L2 L3
Q1
1
3
5
2
4
6
1
2
3
4
1
T1
2
Q3
Q2
EOR
R
START 6
SOFT STOP 5
L
STOP 4
N
5L3
6T3
COMMON 9
1L1
3L2
4T2
A1
2T1
START
GND
FAULT
R
18 17 16
RUN
R
15 14 13
Wiring diagrams
STOP
F1
12 11 10
U1 V1 W1
M
3~
Basic diagram with line contactor(1)
With Soft Start and coast to Stop
by push-buttons control
L1 L2 L3
Q1
1
3
5
2
4
6
1
3
KM1
.8
1
3
5
2
4
6
2
4
T1
1
2
13
Q1
.2 14
Q3
STOP
Q2
K1
21
START
24
K1
A1
F1
FAULT
RELAY
START 6
SOFT STOP 5
STOP 4
L
6T3
N
5L3
4T2
GND
COMMON 9
1L1
3L2
2T1
K1
A1
KM1
14
15
A1
A2
EOR
R
18 17 16
13
14
K1
31
34
11
14
A1
10
RUN
RELAY 12
KM1
A1
A2
FAULT
R
15 14 13
RUN
R
12 11 10
U1 V1 W1
M
3~
(1) Schemes are given for information purposes. Add additional emergency safety stop, if it is required for your application.
Remarks
1. Check coordination tables for proper selection of breaker and line contactor.
2. Control voltage and control input voltage are from same source in above example. Please check manuals if you have different sources for
control voltage and control input voltage.
3. Semiconductor fuses “F” are only required for Type 2 coordination. Please check coordination tables.
4. In spite of ASTAT XT can operate without line contactor, the use of a line contactor will increase the operation safety. Anyway provide a way to
switch off the breaker in case of an emergency.
5. Line and bypass contactors should be dimensioned according AC1 category.
17
ASTAT XT
Application wiring diagrams
Basic diagram with line contactor(1)
L1 L2 L3
Q1
1
3
5
2
4
6
With Soft Start and Soft Stop
by push-buttons control
1
2
Digital soft starters
3
KM1
.8
1
3
5
2
4
6
1
T1
2
13
Q1
.2 14
Q3
4
STOP
Q2
21
K1
KM1
START
24
K1
A1
FAULT
RELAY
F1
15
A1
GND
K1
34
10
12
A1
A2
FAULT
R
18 17 16
31
14
KM1
A2
EOR
R
START 6
SOFT STOP 5
STOP 4
L
N
5L3
6T3
COMMON 9
1L1
3L2
4T2
A1
2T1
K1
14
11
A1
RUN
RELAY
14
13
RUN
R
15 14 13
12 11 10
U1 V1 W1
M
3~
Basic diagram with line and bypass contactors(1)
With Soft Start and Soft Stop
by push-buttons control
L1 L2 L3
Q1
1
3
5
2
4
6
1
3
1
KM1
=8/1.8 2
3
5
4
6
2
4
T1
1
2
Q1
Q3
K1
21
24
K1
A1
14
FAULT
RELAY 15
GND
START 6
SOFT STOP 5
L
STOP 4
BPC
COMMON 9
N
5L3
C
3L2
B
6T3
A
4T2
A1
1L1
6
2T1
5
4
KM1
START
K1
3
14
STOP
Q2
F1
1
KM2
=8/1.9 2
13
A1
A2
EOR
R
18 17 16
13
14
K1
31
34
11
14
A1
A1
10
RUN
RELAY 12
KM1
16
EOA
RELAY 18
A1
KM2
A2
FAULT
R
15 14 13
A1
A2
RUN
R
12 11 10
U1 V1 W1
M
3~
(1) Above schemes are given for information purposes. Add additional emergency safety stop, if it is required for your application.
Remarks
1. Check coordination tables for proper selection of breaker and line contactor.
2. Control voltage and control input voltage are from same source in above example. Please check manuals if you have different sources for
control voltage and control input voltage.
3. Semiconductor fuses “F” are only required for Type 2 coordination. Please check coordination tables.
4. Line and bypass contactors should be dimensioned according AC1 category.
18
ASTAT XT
Application wiring diagrams
Basic diagram in “Inside Delta” configuration with line and bypass contactors(1)
With Soft Start and Soft Stop
by push-buttons control
L1 L2 L3
Q1
1
3
5
2
4
6
1
3
KM1
1
3
5
2
4
6
2
4
T1
1
2
Q1
Q3
Q2
K1
21
24
A1
14
FAULT
RELAY 15
GND
START 6
SOFT STOP 5
C
L
B
BPC
STOP 4
A
N
A1
COMMON 9
6
5L3
5
4
6T3
3
2
1L1
1
3L2
KM2
4T2
6
2T1
5
4
K1
A1
A2
13
K1
14
31
34
11
14
A1
RUN
RELAY
KM1
EOR
R
18 17 16
A1
EOA
RELAY
10
12
A1
A2
A1
KM3
FAULT
R
15 14 13
A2
KM2
RUN
R
12 11 10
16
18
A1
A2
Wiring diagrams
3
2
KM1
START
K1
1
14
STOP
F1
KM3
13
U1 V1 W1
PE
U2 V2 W2
(1) Above schemes are given for information purposes. Add additional emergency safety stop, if it is required for your application.
Remarks
1. Check coordination tables for proper selection of breaker and line contactor.
2. Control voltage and control input voltage are from same source in above example. Please check manuals if you have different sources for
control voltage and control input voltage.
3. Semiconductor fuses “F” are only required for Type 2 coordination. Please check coordination tables.
4. Wrong connection of the motor, or the ASTAT XT when it is inside-delta connected may seriously damage the motor or the ASTAT XT.
Please check additional details given in the ASTAT XT instruction manual.
5. Line and bypass contactors should be dimensioned according AC1 category.
19
ASTAT XT
Coordination Type 1
Digital soft starters
Type 1 coordination with GE circuit breakers Record Plus
Soft starter
Rated current
A
Overload current
A
8
17
31
44
58
72
85
105
145
170
210
310
390
460
580
650
820
950
1100
1400
16
40
50
63
80
80
125
160
160
250
250
400
400
630
630
800
1250
1250
1250
1600
Record Plus circuit breakers
Frame type
O/L type
FD63
FD63
FD63
FD160
FD160
FE160
FE160
FE160
FE160
FE250
FE250
FG630
FG400
FG630
FG630
FK800
FK1250
FK1250
FK1250
FK1600
Breaking capacity
kA
LTMD 16
LTMD 40
LTMD 50
LTMD 63
LTMD 80
LTMD 80
SMR1-125
SMR1-160
LTMD 160
LTMD 250
LTMD 250
SMR1-400
SMR1-400
SMR1-630
SMR1-630
SMR1s-800
SMR1s-1250
SMR1s-1250
SMR1s-1250
SMR1s-1600
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
50
50
50
50
50
Type 1 coordination with Type aM Siba fuses
20
Soft starter
Rated current
A
Rated current
A
8
17
31
44
58
72
85
105
145
170
210
310
390
460
580
650
820
950
1100
1400
16
20
35
50
80
100
125
160
200
200
250
400
500
630
800
800
1000
2x630
2x800
2x800
Siba aM fuses
Part No.
Size
20 477 08.16
20 477 08.20
20 477 08.35
20 477 08.50
20 209 08.80
20 209 08.100
20 209 08.125
20 210 08.160
20 211 08.200
20 211 08.200
20 211 08.250
20 212 08.400
20 213 08.500
20 213 08.630
20 225 08.800
20 225 08.800
20 225 08.1000
2x20 213 08.630
2x20 225 08.800
2x20 225 08.800
0
0
0
0
0
0
0
0
1
1
1
2
3
3
4
4
4
2x3
2x4
2x4
Un
Type
Breaking capacity
kA
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
ASTAT XT
Coordination Type 2
Type 2 coordination with Bussman fuses
Soft starter
Rated current
A2 sec
A
400
5000
10000
12000
15000
18000
50000
60000
10000
140000
200000
600000
700000
800000
1200000
2000000
2000000
4500000
4500000
6500000
40
63
125
160
160
200
250
315
315
400
500
500
800
900
1000
2x800
2x800
2x1000
2x1100
2x1400
Bussman fuses DIN 43620
Part No.
Size
Un
Type
170M3808D
170M3810D
170M3813D
170M3814D
170M3814D
170M3815D
170M3816D
170M3817D
170M3817D
170M3819D
170M4864D
170M4864D
170M5814D
170M6813D
170M6814D
2x170M5814D
2x170M5814D
2x170M5816D
2x170M6892D
2x170M8555D
1
1
1
1
1
1
1
1
1
1
1
1
2
3
3
2x2
2x2
2x2
2x2
2x3
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
H.S.D.I.
Breaking capacity
kA
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
Coordination tables
8
17
31
44
58
72
85
105
145
170
210
310
390
460
580
650
820
950
1100
1400
Rated current
A
For Type 2 coordination
Use fuses for semiconductor protection to protect the ASTAT XT soft starter from a short
circuit. Fuses for semiconductor protection give excellent results because they have low I²t
values and high interruption ratings.
Recommended fuse selection procedure
Fuse rated voltage
Choose minimum fuse rated voltage which is above the rated voltage of the mains.
Fuse rated current
Select a fuse which is able to carry 8 times the rated ASTAT XT soft starter current for 30 seconds
(this is double the maximum ASTAT XT soft starter current for the maximum acceleration time).
Fuse I²t
Verify that the I²t value of the fuse is less than or equal to the I²t value of the thyristor in the
ASTAT XT soft starter as shown in the table.
21
ASTAT XT
Dimensions and weights
Cat. No.: QTx0008U_ , QTx0017U_ , QTx0031U_ , QTx0044U_ , QTx0058U_ , QTx0072U_
158
Bypass
ABC
1L1, 3L2, 5L3
298
310
Digital soft starters
7
GND M5
2T1, 4T2, 6T3
130
D1
153
D2
Power terminal size (mm²)
Dimensions
Cat. No
QTx0008U__
QTx0017U__
QTx0031U__
QTx0044U__
QTx0058U__
QTx0072U__
IEC and UL certified units
D1
160
160
160
207
207
207
D2
182.5
182.5
182.5
229.5
229.5
229.5
Input
Bypass
Output
Weight (kg)
1L1, 3L2, 5L3
16
16
16
16
16
35
A, B, C
16
16
16
16
16
35
2T1, 4T2, 6T3
16
16
16
35
35
35
4.2
4.2
5.3
6.7
6.7
6.7
Cat. No.: QTx0085U_ , QTx0105U_
278
65.5
20
104.5
9
188
65.5
4
1L1, 3L2, 5L3
355
365
O 8.5
385
137
15
GND M6
2T1, 4T2, 6T3
71.8
32.7
32.8
32.7
200
274
32.8
117
4
243
Bypass
ABC
Cat. No.
IEC and UL certified units
22
QTx0085U__
QTx0105U__
Weight (kg)
15.2
15.2
ASTAT XT
Dimensions and weights
Cat. No.: QTx0145U_ , QTx0170U_
188
278
65.5
20
65.5
137
1L1, 3L2
355
Dimensions
365
O 8.5
385
4
15
99.5
9
GND M6
2T1, 4T2, 6T3
66.8
32.7
32.8
32.7
32.8
32.7
117
200
274
Bypass
ABC
4
244
Cat. No.
Weight (kg)
QTx0145U__
QTx0170U__
IEC and UL certified units
15.2
15.2
Cat. No.: QTx0210U_ , QTx0310U_ , QTx0390U_ , QTx0460N_
15
160
43.5
125
O 10
125
54.2
30
182.2
5
By Pass
ABC
5
1L1, 3L2, 5L3
9.5
125
125
H4
H3
H2
H1
GND M8
299.4
380
Dimensions
Cat. No.
IEC and UL certified units
This 460A frame is only IEC certified.
Please consult dimensions of 460A frame for UL in page 26
2T1, 4T2, 6T3
5
182.2
43.5
QTx0210U__
QTx0310U__
QTx0390U__
QTx0460N__
H1
455
455
455
555
H2
425
425
425
525
H3
414
414
414
528.5
Weight (kg)
H4
427
427
427
527
32.7
32.7
32.7
58.4
23
ASTAT XT
Dimensions and weights
Cat. No.: QTx0580N_
180
20
150
150
221.7
171.7
50.5
5
5
Digital soft starters
1L1, 3L2, 5L3
9.5
Bypass
ABC
40
O 13.5
50.5
150
615
600
542
528
615
655
GND M8
2T1, 4T2, 6T3
216.7
150
5
309.4
470
Cat. No.
Weight (kg)
QTx0580U__
Non-UL certified unit
63.2
Cat. No.: QTx0650N_
180
20
150
150
221.7
171.7
50.5
5
5
1L1, 3L2, 5L3
9.5
Bypass
ABC
40
O 13.5
50.5
150
150
470
615
600
542
528
615
655
GND M8
2T1, 4T2, 6T3
216.7
5
309.4
Cat. No.
Non-UL certified units
24
QTx0650N__
Weight (kg)
64.8
ASTAT XT
Dimensions and weights
Cat. No.: QTx0950N_
625
292.4
195
195
234.5
640
626.5
Dimensions
659
9.5
2T1, 4T2, 6T3
10
1L1, 3L2, 5L3
10
10
114
114
50
17.5
245
114
74.7
45
O10.5
20
45
GND
M8
80
440
Remarks
1. This unit must be operated with a bypass contactor
2. Add space for current transformers (supplied separately from the main unit)
and bus bars for preparation for bypass
Approximate current transformers dimensions: W=240mm, H=130mm, D=90mm
Cat. No.
Non-UL certified unit
QTx0950N__
Weight (kg)
86.7
Cat. No.: QTx1100N_ , QTx1400N
230
230
165
230
230
GND M10
712
1100
230
29
45
10
1L1, 3L2, 5L3
45
O10.5
O9
16.5
94
20
80
786
131.5
9
8
230
230
45
2T1, 4T2, 6T3
20
80
191.5
230
230
723
Remarks
1. Units must be operated with a bypass contactor
2. Add space for current transformers (supplied separately from main unit)
and bus bars for preparation for bypass
Approximate current transformers dimensions:
W=240mm, H=130mm, D=90mm. (for 1100A unit, Cat. No. QTx1100N__
W=270mm, H=155mm, D=90mm. (for 1400A unit, Cat. No. QTx1400N__
Non-UL certified unit
45
O10.5
266
10
376.8
Cat. No.
QTx1100N__
QTx1400N__
Weight (kg)
169.8
175.5
25
ASTAT XT
Dimensions and weights
Cat. No.: QTx0460U_
625
195
292.4
234.5
195
659
818
640
626.5
Digital soft starters
9.5
GND
M8
25
25
50
2T1, 4T2, 6T3
13
1L1, 3L2, 5L3
25
25
O10
13
65
130
74.2
65
130
65
80
Bypass
ABC
6
155.2
6
Cat. No.
Weight (kg)
QTx0460U__
UL certified unit
61.8
Cat. No.: QTx0580U_ , QTx0820U_
625
195
292.4
234.5
195
818
659
626.5
640
9.5
GND
M8
25
25
50
2T1, 4T2, 6T3
13
1L1, 3L2, 5L3
25
Bypass
ABC
13
25
74.2
195
195
77
73.5
6
155.2
Cat. No.
UL certified unit
26
QTx0580U__
QTx0820U__
6
Weight (kg)
69.5
69.5
ASTAT
Notes
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
27
ASTAT
Numerical index
By reference number
Numerical index
Ref. No.
28
120000
120881
120882
120883
120884
120885
120886
120892
120893
120894
120895
120896
120897
120898
120899
120900
120901
120902
120903
120904
120905
120906
120907
120908
120909
120910
129000
129213
129214
129215
129216
129217
129218
129219
129220
129221
129222
129223
129224
129225
129226
129227
129228
129229
129230
129231
129232
129233
129234
129257
129258
129259
129260
129261
129262
129263
129264
129265
129266
129267
129268
129269
129270
129271
129272
129273
129274
129275
169000
169075
169076
169077
169078
169079
169080
169081
169082
169083
169084
169085
169086
169087
Typbez.
Pag.
QA02P008S
QA02P017S
QA02P022S
QA02P031S
QA02P044S
QA02P058S
QA12P008S
QA12P017S
QA12P022S
QA12P031S
QA12P044S
QA12P058S
QA22P008S
QA22P017S
QA22P022S
QA22P031S
QA22P044S
QA22P058S
QA32P008S
QA32P017S
QA32P022S
QA32P031S
QA32P044S
QA32P058S
QAOPTDIN
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
QT10008U21MSG
QT10017U21MSG
QT10031U21MSG
QT10044U21MSG
QT10058U21MSG
QT10072U21MSG
QT10085U21MSG
QT10105U21MSG
QT10145U21MSG
QT10170U21MSG
QT10210U21MSG
QT10310U21MSG
QT10390U21MSG
QT10460U21MSG
QT10580U21MSG
QT10820U21MSG
QT10460N21MSG
QT10580N21MSG
QT10650N21MSG
QT10950N21MSG
QT11100N21MSG
QT11400N21MSG
QT30008N21MSG
QT30017N21MSG
QT30031N21MSG
QT30044N21MSG
QT30058N21MSG
QT30072N21MSG
QT30085N21MSG
QT30105N21MSG
QT30145N21MSG
QT30170N21MSG
QT30210N21MSG
QT30310N21MSG
QT30390N21MSG
QT30460N21MSG
QT30580N21MSG
QT30650N21MSG
QT30950N21MSG
QT31100N21MSG
QT31400N21MSG
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
QT10008U21MS
QT10017U21MS
QT10031U21MS
QT10044U21MS
QT10058U21MS
QT10072U21MS
QT10085U21MS
QT10105U21MS
QT10145U21MS
QT10170U21MS
QT10210U21MS
QT10310U21MS
QT10390U21MS
9
9
9
9
9
9
9
9
9
9
9
9
9
Ref. No.
169088
169089
169090
169094
169095
169096
169097
169098
169099
169100
169101
169102
169103
169104
169105
169106
169107
169108
169109
169110
169111
169112
169113
169114
169115
169119
169120
169121
169122
169123
169124
169125
169126
169127
169128
169129
169130
169131
169132
169133
169134
169135
169136
169137
By catalogue number
Typbez.
Pag.
QT10460U21MS
QT10580U21MS
QT10820U21MS
QT10460N21MS
QT10580N21MS
QT10650N21MS
QT10950N21MS
QT11100N21MS
QT11400N21MS
QT20008U21MS
QT20017U21MS
QT20031U21MS
QT20044U21MS
QT20058U21MS
QT20072U21MS
QT20085U21MS
QT20105U21MS
QT20145U21MS
QT20170U21MS
QT20210U21MS
QT20310U21MS
QT20390U21MS
QT20460U21MS
QT20580U21MS
QT20820U21MS
QT30008N21MS
QT30017N21MS
QT30031N21MS
QT30044N21MS
QT30058N21MS
QT30072N21MS
QT30085N21MS
QT30105N21MS
QT30145N21MS
QT30170N21MS
QT30210N21MS
QT30310N21MS
QT30390N21MS
QT30460N21MS
QT30580N21MS
QT30650N21MS
QT30950N21MS
QT31100N21MS
QT31400N21MS
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
Cat. No.
QA...
QA02P008S
QA02P017S
QA02P022S
QA02P031S
QA02P044S
QA02P058S
QA12P008S
QA12P017S
QA12P022S
QA12P031S
QA12P044S
QA12P058S
QA22P008S
QA22P017S
QA22P022S
QA22P031S
QA22P044S
QA22P058S
QA32P008S
QA32P017S
QA32P022S
QA32P031S
QA32P044S
QA32P058S
QAOPTDIN
QT
QT10008U21MS
QT10008U21MSG
QT10017U21MS
QT10017U21MSG
QT10031U21MS
QT10031U21MSG
QT10044U21MS
QT10044U21MSG
QT10058U21MS
QT10058U21MSG
QT10072U21MS
QT10072U21MSG
QT10085U21MS
QT10085U21MSG
QT10105U21MS
QT10105U21MSG
QT10145U21MS
QT10145U21MSG
QT10170U21MS
QT10170U21MSG
QT10210U21MS
QT10210U21MSG
QT10310U21MS
QT10310U21MSG
QT10390U21MS
QT10390U21MSG
QT10460N21MS
QT10460N21MSG
QT10460U21MS
QT10460U21MSG
QT10580N21MS
QT10580N21MSG
QT10580U21MS
QT10580U21MSG
QT10650N21MS
QT10650N21MSG
QT10820U21MS
QT10820U21MSG
QT10950N21MS
QT10950N21MSG
QT11100N21MS
QT11100N21MSG
QT11400N21MS
QT11400N21MSG
QT20008U21MS
QT20017U21MS
QT20031U21MS
QT20044U21MS
QT20058U21MS
QT20072U21MS
QT20085U21MS
QT20105U21MS
QT20145U21MS
QT20170U21MS
QT20210U21MS
Ref. No. Pag.
120881
120882
120883
120884
120885
120886
120892
120893
120894
120895
120896
120897
120898
120899
120900
120901
120902
120903
120904
120905
120906
120907
120908
120909
120910
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
169075
129213
169076
129214
169077
129215
169078
129216
169079
129217
169080
129218
169081
129219
169082
129220
169083
129221
169084
129222
169085
129223
169086
129224
169087
129225
169094
129229
169088
129226
169095
129230
169089
129227
169096
129231
169090
129228
169097
129232
169098
129233
169099
129234
169100
169101
169102
169103
169104
169105
169106
169107
169108
169109
169110
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
Cat. No.
QT20310U21MS
QT20390U21MS
QT20460U21MS
QT20580U21MS
QT20820U21MS
QT30008N21MS
QT30008N21MSG
QT30017N21MS
QT30017N21MSG
QT30031N21MS
QT30031N21MSG
QT30044N21MS
QT30044N21MSG
QT30058N21MS
QT30058N21MSG
QT30072N21MS
QT30072N21MSG
QT30085N21MS
QT30085N21MSG
QT30105N21MS
QT30105N21MSG
QT30145N21MS
QT30145N21MSG
QT30170N21MS
QT30170N21MSG
QT30210N21MS
QT30210N21MSG
QT30310N21MS
QT30310N21MSG
QT30390N21MS
QT30390N21MSG
QT30460N21MS
QT30460N21MSG
QT30580N21MS
QT30580N21MSG
QT30650N21MS
QT30650N21MSG
QT30950N21MS
QT30950N21MSG
QT31100N21MS
QT31100N21MSG
QT31400N21MS
QT31400N21MSG
Ref. No. Pag.
169111
169112
169113
169114
169115
169119
129257
169120
129258
169121
129259
169122
129260
169123
129261
169124
129262
169125
129263
169126
129264
169127
129265
169128
129266
169129
129267
169130
129268
169131
129269
169132
129270
169133
129271
169134
129272
169135
129273
169136
129274
169137
129275
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
The policy of GE is one of
continuous improvement.
The right is reserved to alter the
design or any structural details of
the products at any time without
giving notice.
May 2013
GE Industrial Solutions
108781
GE
Industrial Solutions
GE Industrial Solutions is a first class global supplier of low and medium
voltage products including wiring devices, residential and industrial
electrical distribution components, automation products, enclosures
and switchboards. Demand for the company’s products comes
from wholesalers, installers, panelboard builders, contractors,
OEMs and utilities worldwide.
www.ge.com/ex/industrialsolutions
www.ge.com/uk/industrialsolutions
Belgium
GE Industrial Belgium
Nieuwevaart 51
B-9000 Gent
Tel. +32 (0)9 265 21 11
Finland
GE Industrial Solutions
Kuortaneenkatu 2
FI-00510 Helsinki
Tel. +358 (0)10 394 3760
France
GE Industrial Solutions
Paris Nord 2
13, rue de la Perdrix
F-95958 Roissy CDG Cédex
Tel. +33 (0)800 912 816
Germany
GE Industrial Solutions
Robert-Bosch Str. 2a
D-50354 Hürth-Efferen
Tel. +49 (0) 2233/ 9719-0
Hungary
GE Hungary Kft .
Vaci ut 81-83.
H-1139 Budapest
Tel. +36 1 447 6050
Italy
GE Industrial Solutions
Centro Direzionale Colleoni
Via Paracelso 16
Palazzo Andromeda B1
I-20864 Agrate Brianza (MB)
Tel. +39 039 637 3701
Netherlands
GE Industrial Solutions
Parallelweg 10
Nl-7482 CA Haaksbergen
Tel. +31 (0)53 573 03 03
Poland
GE Power Controls
Ul. Odrowaza 15
03-310 Warszawa
Tel. +48 22 519 76 00
Ul. Leszczyńska 6
43-300 Bielsko-Biała
Tel. +48 33 828 62 33
Portugal
GE Industrial Solutions
Rua Camilo Castelo Branco, 805
Apartado 2770
P-4401-601 Vila Nova de Gaia
Tel. +351 22 374 60 00
Russia
GE Industrial Solutions
27/8, Electrozavodskaya street
Moscow, 107023
Tel. +7 495 937 11 11
South Africa
GE Industrial Solutions
Unit 4, 130 Gazelle Avenue
Corporate Park Midrand 1685
P.O. Box 76672 Wendywood 2144
Tel. +27 11 238 3000
Spain
GE Industrial Solutions
P.I. Clot del Tufau, s/n
E-08295 Sant Vicenç de Castellet
Tel. +34 900 993 625
United Arab Emirates
GE Industrial Solutions
Injaz Building, 3rd Floor
Dubai Internet City
PO Box 11549, Dubai
Tel. +971 4 4546912
United Kingdom
GE Industrial Solutions
2 The Arena, Downshire Way
Bracknell, Berkshire.
RG12 1PU
Tel. +44 (0)800 587 1239
GE imagination at work
680855
Ref. C/4694/E/EX 4.0 Ed. 05/13
© Copyright GE Industrial Solutions 2013
Download