UTXvRNT Datasheet

advertisement
UTXvRNT
OLTC Transformer
Voltage Regulator
Datasheet
English
UTXvRNT - OLTC Transformer Voltage Regulator
Disclaimer of liability
We have checked the contents of this document for
agreement with the hardware and software described. Since differences can‘t be precluded entirely,
we cannot guarantee full agreement.
However, the data in this manual are reviewed regularly and any necessary corrections are included
in subsequent editions.
Suggestions for improvement are welcome.
Copyright
Copyright © 2010 Computers & Control
The reproduction, transmission or use of this
document or its contents is not permitted without
express written authority. Offenders will be liable
for damages. All rights, including rights created by
patent grant or registration of a utility model or
design, are reserved.
Warranty
The contents of this instruction manual shall not
become part nor modify any prior or existing agreement, commitment or relationship.
The sales contract contains the entire obligations
of Computers & Control. The warranty contained
in the contract between the parties is the sole
warranty of Computers & Control. Any statements
contained herein do not create new warranties nor
modify the existing warranty.
Technical data subject to change.
Version 1.00, 27-09-2010
Contact
CCD Computers & Control Distribution GmbH
Hofaue 35, 42103 Wuppertal, Germany
Tel. +49-202-850 69 49 0
Fax +49-202-850 69 49 9
www.computers-and-control.de
info@computers-and-control.de
2
UTXvRNT - OLTC Transformer Voltage Regulator
Contents
1. General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3. Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1 Analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.2 Binary outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.3 Binary inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.4 Casing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.5 Allowable ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.6 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.7 Disturbance recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.8 Event recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4. Assembly Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5. Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6. Casing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7. Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3
UTXvRNT - OLTC Transformer Voltage Regulator
1. General Information
UTXvRNT is a device with very expanded regulation, recording and remote control functions, destinated for the use in on-load tap changer regulation systems on any high and medium voltage power line.
It can be operated with solidly earthed, compensated or isolated neutral point configurations and
provides fast and reliable regulation.
The extended functions include voltage drop compensation, 24-hours / scheduled / weekend and
holiday settings, disturbance and event recording, voltage quality recording. It enables realization of
the most sophisticated applications.
UTXvRNT is available in two versions:
• UTXvRNT2 is designed to control two-windings transformers
• UTXvRNT3 is designed to control three-windings transformers
2. Characteristics
UTXvRNT can be characterized by the following features:
•
•
•
•
•
•
•
•
•
•
•
•
•
•
multi-processor measuring and regulating system
fully digital information processing
operation with two or three-windings transformers
operation in automatic or manual mode
automatic summer/winter time zone adjust
advanced logic function module with selectable functor
four main regulation rules:
• based on voltage U1 of circuit 1
• based on voltage U2 of circuit 2
• based on mean value of voltages U1 and U2
• based on max value (U1, U2)
up to three /one wekeend/ ten holidays settings for controlled voltage level
all-year programmable calendar with freely adjusted activity zones
three separate configurations sets with on-line switching possibility
galvanic separation of inputs and outputs (analogue and binary)
compensation type XR and Z, set independently for each measuring circuit
tap changer overcurrent protection
energy quality control system
4
UTXvRNT - OLTC Transformer Voltage Regulator
•
•
•
•
•
•
•
•
•
functions of tap changer remote control
operation reporting, event and disturbance recording
local graphic display, 16 synoptic led indicator and 8 separate keys keyboard
presentation of measured values on local display and transmit to remote control system
simultaneously operated IEC 60870-5-103 and CC-Bus protocols
tap changer and operational time counter
permanent self- diagnostic function
three password–protected access levels
possibility of full device control /setting adjust /reading and data presentation via SAZ-2000
program
3. Technical Data
3.1 Analog inputs
•
•
•
•
•
•
Current input nominal value (In)
Voltage input nominal value (Un)
Max. rated burden of current inputs
Max. rated burden of voltage inputs
Input’s insulation withstand Analog input amount
1 or 5[A]
100 [V]
0.2 [VA] (for I=1In)
0.04 [VA] (for U=1Un)
3[kV] AC/DC, 5[kV] 5[us] pulse
up to 4
Measuring range:
• for IL1, IL2 • for UL1, UL2
up to 2 In
up to 2 Un
Overload withstand:
• Voltage inputs
• Current inputs for In=1[A]
• Current inputs for In=5[A]
3Un continuously
100In/1[s], 5In continuously
100In/1[s], 2In continuously
Dynamic withstand:
• for In=1[A] • for In=5[A] up to 250 In / 20[ms]
up to 200 In / 20[ms]
3.2 Binary outputs
• Switching capacity, per relay
250[V]AC/8.0[A], 250[V]DC/0.3[A]
• 8 freely programmable + 2 dedicated (UP and Al function)
3.3 Binary inputs
• Insulation withstand
• Current consumption
3[kV] AC/DC, 5[kV] 5[us] pulse
5[mA]/input
Input levels, high voltage section
• 110[V]DC nominal voltage
• 220[V]DC nominal voltage
(0-60)[V] = FALSE, (70-121)[V] = TRUE
(0-145)[V] = FALSE, (165-242)[V] = TRUE
5
UTXvRNT - OLTC Transformer Voltage Regulator
Input levels, Low voltage section
• 12[V]DC nominal voltage
(0-8)[V] = FALSE, (9-30)[V] = TRUE
• 24[V]DC nominal voltage
(0-16)[V] = FALSE, (18-30)[V] = TRUE
Amount of binary inputs:
14 freely programmable + 1 dedicated (ParSel)
3.4 Casing
Surface mounting case:
CPRO 84 / CPRO63
weight up to 8[kg]
IP class 40 /option-IP65/
Flush mounting case:
EURO 3U (rack 19”)
weight up to 5[kg]
IP class 40 /option-IP65/
3.5 Allowable ratings
•
•
•
•
Supply voltage:
Operation temperature:
Storage temperature:
Storage humidity:
90-340[V]DC / 65-240[V]AC
-5°C to +50°C
-10°C to +60°C
40-80% RH
3.6 Interfaces
CCBUS protocol:
RS232, CL (current loop) and Ethernet (separate channel),(optional fiber optic interface)
IEC 60870-5-103 protocol:
RS485, (optional fiber optic interface)
CANBUS protocol (option):
2 x RS485
3.7 Disturbance recorder
•
•
•
•
•
Maximal capacity: Recorded binary inputs: Recorded analogue inputs: Pre-event time duration
Event time duration: 8 disturbances
14
up to 4
400[ms]
1900[ms]
3.8 Event recorder
Capacity: min. 1000 events (with separate time stamp)
6
UTXvRNT - OLTC Transformer Voltage Regulator
4. Assembly Diagram
5. Connectors
7
UTXvRNT - OLTC Transformer Voltage Regulator
6. Casing
Configuration K4-”A”:
• Analog inputs
• Binary inputs • Binary outputs AA = 2 or 4
IF = (6 + 8) input card
PA = 8 relay’s output card + (AL/UP)
8
UTXvRNT - OLTC Transformer Voltage Regulator
7. Regulations
No.
1
2
Test type
Standard
Tested
elements
Test range
Electrostatic
discharge
immunity
PN-EN 50263:2002
PN-EN 60255-222:1999
Through
- 6/8[kV] contact discharge
the housing - 8/15[kV] discharge through the
access
air
Resistance to
electrical fast
transients
PN-EN 50263:2002
Power port
class III – 2[kV]
PN-IEC 60255-224:1996
I/O ports
class IV – 4[kV]
PN-EN 50263:2002
Power port
class III
PN-EN 60255-225:2003
I/O ports
common voltage – 2[kV]
PN-EN 61000-4-4:2005
3
Shock resistance
differential voltage – 1[kV]
PN-EN 61000-4-5:2006
4
5
6
7
Immunity from
electromagnetic
fields
PN-EN 60255-223:2002
Device
frequency: (900 ± 5)[MHz]
Conducted
immunity
induced by radio
frequency fields
PN-EN 60255-226:2004
Power port
frequency: 0,15< f < 80[MHz]
I/O ports
amplitude : 10[V] r.m.s
unmodulated
Sinusoidal
vibration
PN-EN 60068-2-6:2002
Tolerance to cold
PN-EN 60068-21:2007(U)
electromagnetic field level:
10[V/m]
source impedance: 150[Ω]
Device
frequency: (10-150)[Hz]
acceleration: 5[m/s2] (rms)
Device
test temperature: (-5)˚C
fall time to test temperature 1[h]
test duration 1[h]
fall time to test temperature
0,4[h]
test duration 16[h]
initial temperature (-5)˚C
test duration 1[h]
8
Tolerance to dry
heat
PN-EN 60068-2-2:2002
Device
test temperature: (+50)˚C
rise time to test temperature
0,5[h]
test duration 96[h]
9
10
Resistance to cold
Resistance to dry
heat
PN-EN 60068-21:2007(U)
Device
PN-EN 60068-2-2:2002
Device
temperature: (-10)˚C
test duration 96[h]
temperature: (+60)˚C
test duration 96[h]
9
Download