Universal and Reconfigurable to UPS Active Power Filter for Line Conditioning Fermín Barrero, Member, IEEE, Salvador Martínez, Senior Member, IEEE, Fernando Yeves, Member, IEEE, Francisco Mur, and Pedro Mª Martínez Abstract—This paper describes an improved universal active power line conditioner designed to attenuate every disturbance in the electric power system and critical loads, except frequency variations. The circuit has a series voltage filter and a parallel current filter interconnected through a shared dc bus. In case of a supply interruption, the current filter reconfigures to UPS and feeds a preselected 20% of load during 500 ms at the expenses of the dc bus. Over previous reconfigurable solutions, the input and output series static switches have been eliminated improving the reliability, efficiency and cost. Optional parallel LC tuned current filters have also been proved to be control compatible. The search has been guided by an iterative analysis+synthesis cost comparative method, initiated in previous works, showing the cost of the components involved in each explored topology. Experimental results on three laboratory models and a 400 kVA industrial prototype validate the topology and suggest improvement of some control loops. Index Terms—Active filter, hybrid current filters (new index term proposed), load flow control, power conditioning, power line filter, power quality, pulse with modulation, uninterruptible power systems. I. INTRODUCTION HE demand for a better quality in the electric grid and the increase of disturbing loads have promoted the appearance of the so called line conditioners based on active power filters as one of the possible solutions. Compared with a traditional on-line uninterruptible power supply (UPS), they normally provide to the load a worse voltage wave but they are cheaper and, in the sophisticated versions, ameliorate the current harmonics injected to the mains by UPS variants with poor input rectifier. Combining one parallel (with regard to the load) current active filter and one series (with regard to the load+current filter ensemble) voltage active filter has demonstrated to be one of the most general and economical solutions to eliminate both the current disturbs injected by the load to the grid (solved by the current filter) and the voltage disturbs that the grid can show to the load (solved by the voltage filter). T Manuscript received November 14, 2001; revised July 18, 2002. This work was supported in part by the Spanish R&D Electrical Plan under under identification P.I.E. 132.206. F. Barrero is with the Department of Electrical Engineering, Universidad de Extremadura, Badajoz E 06006, Spain (e-mail: fbarrero@unex.es). S. Martínez, F. Yeves, and F. Mur are with the Department of Electrical, Electronic and Control Engineering, Universidad Nacional de Educación a Distancia (UNED), Madrid E 28040, Spain (e-mail: smartine@ieec.uned.es; fyeves@ieec.uned.es; francisco.mur@ieec.uned.es). P. M. Martínez is with the R&D Electrical Lines Division, Iberdrola S.A., Bilbao E 48008, Spain (e-mail:pedro.mcid@iberdrola.es). First concepts on active filters, as generators of the nonideal component of a voltage or current wave, appear in the seventies and early eighties [1]–[3], [5], and the hybrid (passive plus active) filter concept is established by the late eighties and early nineties [4], [6]. The search for a universal (or unified) line conditioner can be dated in the nineteen decade, first as an interactive and self-feed combination of current filter and voltage filter intended for power flow control [7], then adding the reconfiguration of the current filter to voltage inverter for feeding part of the load in case of a sustained line interruption [8], [9], [11], [16]. This improved universal line conditioner can reduce every voltage and current disturb, competing with the UPS except in frequency correction. The ACCIONE project, integrated in the Spanish Electric Research Program (PIE 132.206), began in 1990 to investigate the application of the new active filters to the power quality for low voltages distribution lines in the range of 25–1000 kVA. One technical and economical summary of the first solutions explored can be seen in [24]. The search for more complete topologies lead to an universal line conditioner [16] having over other solutions [7], [10], [13], [21], the ability to eliminate voltage interruptions in a selected part of the load, due to the reconfiguration of the power circuit and the control program of the current filter to act as a voltage inverter. The new topology shown here improves the first version in [8] and [16] by means of a new maneuver strategy for the reconfiguration to UPS which eliminates the input and output series static switches rated to nominal current plus overload. It remains an unique maneuver switch rated to less than half of nominal load and located out off the main current stream. Then, the reliability, efficiency and cost are improved. Furthermore, the topology gains generality by adding one or several optional LC filters, tuned to low frequency current harmonics, in parallel with the active current filter [23]. This hybrid configuration for the current filter can be convenient in cases when a substantial part of the nonideal load current is composed by low and constant frequency harmonics. It has been proved by experiment than the resonance likely to appear between the mains impedance and the LC filters can be damped by an appropriate control of the, now reduced in power, active current filter which is dedicated also to compensate the high frequency components in the load current. II. SPECIFICATIONS In general, it is expected from an universal line conditioner to reduce or eliminate every line disturbance (except frequency, reserved for the UPS) as detailed in Table I. Intended for such a TABLE I DISTURBANCES REDUCED OR ELIMINATED AND SPECIFICATIONS Fig. 1. Schematics of the analysis+synthesis cost comparative method. The results are in one table showing the rates of the main components for every power topology solution investigated, transformed in terms of actual ready-to-use standard components price lists. general compliance, the designed line conditioner series has the main specifications, also shown in Table I. can be easily obtained from an up-to-date price list of common use components ( ). III. ITERATIVE ANALYSIS+SYNTHESIS COST COMPARATIVE SEARCH METHOD The choice of power topology is based on a previous solutions research process, taking into account technical and economics aspects. Fig. 1 shows a synthetic vision for the described method. For a more detailed explanation, see [24]. The method is made concrete in the following steps: A. Analysis: Power Circuit Equations This step is the traditional attainment of the equations showing the physical variables ( ) time evolution, as a function of the components rates ( ). It is repeated for several topologies, 1 to . B. Synthesis: Component Synthesis Equations They give the components rates ( tion of equipment specifications (Spec) ) as a func- C. Transformation: Variants Transformations They show the relationship among component rates for those groups of circuits that are variants of an unique topology, and obtain those rates for a new variant ( ) as a function of the rates of an already known variant ( ). D. Standardization and Cost Formulas for transformers, coils, capacitors, electronic devices, etc, that transform the actual component rates ( ) into standard components rates of similar economical cost ( ). So, the cost of the actual components ( ) E. Comparison: Comparative Table Finally, a table shows, for each topology and variant, their basic performances, synthesis equations, standard component rates, the component usage coefficients and their economical cost. (The usage coefficient indicates the relationship among the equipment output rated power and the sum of the power rate of a main group of components standardized in an specific way.) IV. POWER TOPOLOGY The conditioner (see Fig. 2) has, per phase, one series voltage active filter (VAF), which cancels the voltage perturbations coming from the mains to the load, and one parallel current active filter (CAF) which cancels the non ideal component that the load demands from the mains. The current filter also feeds the voltage filter through one common dc bus and, in case of a mains sustained interruption, reconfigures to voltage inverter and feeds a critical part of the load. As the dc bus is common for all the phases, the current filters can compensate load current unbalance transferring energy from one phase to another. The voltage filters can also compensate mains voltage unbalance at the expense of the current filter energy support. In this way, the grid is seen by the load as an stiff voltage source and the load is seen by the grid as an resistive balanced load. Due to functional independence of the filters (except in the overall energetic balance), the current filters are also able (while compensating the nonideal components of load current) to act as reactive power generators dedicated to compensate certain selected upstream mains area. Fig. 2. Universal power conditioner based on active voltage and current filters. Three-phase block diagram. The energetic interconnection among phases through one common dc bus allows the reduction of every nonideal behavior both in the load current and in the line voltage. Fig. 3. One phase circuit. In the dotted line appears optional LC resonant current filters for low-order harmonics (5 ; 7 ; 11 ; . . .). Critical load (CL) and the noncritical (NCL) have been rated 20% and 80%, respectively, in the 3- and 400-kVA prototypes. A more detailed one-phase power circuit is shown in Fig. 3. The three-phase circuit is made up from three similar circuits wye connected. The voltage filter is a full bridge IGBT inverter, S1 to S4, followed by the low-pass filter - feeding the primary of the series compensating transformer T1. The current filter is a half bridge IGBT inverter, S5-S6, with a center-tap dc bus – followed by the filter coil . This active current filter can be optionally complemented with one or several passive LC filters tuned to low frequency harmonics as 3rd (for 4-wire load), 5th, 7th, 11th. Normally, the static switch SO is closed and both the non critical load (NCL) and the critical load (CL) are fed by the mains through the voltage filter. In case of a mains interruption SO opens isolating CL which is now fed by the current filter inverter acting as voltage inverter controlled by a reconfigured program. Capacitor completes the output filter coil of this inverter which feeds CL from the energy remaining in the dc bus capacitors (UPS operation). Rating the dc bus capacitors for the normal internal voltage filter operation, a 20% of the nominal load can be feed during 100 ms. As the electrical companies consider that typically less than 5% of the interruptions last more than 500 ms, the dc capacitor has been overrated five times to ensure this emergency time to a selected 20% of the nominal load (CL). This means an affordable extra cost in the overall conditioner. If bigger emergency and/or selected critical load are needed, the dc bus can be paralleled with fast batteries and the reference signal for the control loop 2 (see Fig. 6) must be programmed to ensure correct charge along normal operation. The prototypes have not been tested in this condition. The high switching frequency of the current filter, when acting as voltage inverter (15,6 kHz), allows a small capacity for (whose reactive 50 Hz power is in the range of 1% of does not disturb the normal operation the nominal power). of the conditioner counting on some prevention in the voltage filter control for its resonance with the line impedance. As shown in Section III, the topology has been optimized through an exhaustive search which guaranties to be one of the most economical possible solutions. The usage coefficients [24] obtained in the case of non passive LC current filters are: Usage Coefficients of the main components: Coils and transformer: ,8 Capacitors: ,03 Semiconductors: ,27 As said before, the main innovation presented here over other reconfigurable to UPS topologies [16], [24] is the elimination of the input and output static switches in the main circuit, due to a new reconfiguration strategy of the power circuit. The input switch has been eliminated and the output switch is relocated as SO and derated from the nominal current (plus overload) to the sum of the active filter current plus non critical load current (typically under 50% of the nominal current). This leads to a better usage coefficient for the whole conditioner rising from 0.12 (calculated in [24] for the circuit described in [16]) to 0.27, as can be easily seen repeating the synthesis calculus for the new circuit. In as much of a cost reduction, the contribution means a substantial amelioration in efficiency and, more important, in reliability (as only the overloads in CL affect to SO). The switch SI is normally off and closes in case of overload to protect the voltage filter. After approximately 100 ms closes the mechanical breaker COR removing the current from SI which can be selected upon a nonrepetitive peak current criteria. Furthermore, the compensating transformer divides by (typically 11) the overload current seen by SI, resulting a relatively very small thyristor pair (also alternistors are usable). It has not been considered in the usage coefficient calculation, nor in [24], nor here. V. CONTROL The control circuit has two independent and interactive processors, one for the voltage filter and another for the current filter. Both operate in their inner loop under a time domain deadbeat technique. In the voltage section control, whose guidelines have been described in [17], the line voltage and the load current asymmetrical model showed in Fig. 5. The duty cycle, calculated by deadbeat technique (similar to the one described for the voltage filter in [18]) is given by (1) Fig. 4. Equivalent electric circuit for the current filter showing the variables operating in the control algorithm. Fig. 5. Pulse pattern for the current filter switches S5-S6. The commuting 64 s. frequency is 15.6 kHz. T = Fig. 6. Current filter control block diagram. The inner loop operates with a very fast beat-dead algorithm. The peripheral loops, which elaborate the i reference signal for inner loop, are hierarchically arranged under a function preference-speed level criteria. are the main input signals and the output signal is the duty cycle for the switches. This signal is applied to a pulse pattern generator which commands the voltage active filter IGBT drivers. In the current filter (see Fig. 4 for the electric equivalent circuit) the main input signal to the processor is the load current . The output signal is, again, the duty cycle of the pulse pattern for the IGBT drivers (see Fig. 5). The input voltage seen by this filter, , is the line voltage corrected by the voltage filter and can be considered as an ideal sinus. The current active filter generates , which (neglecting the dc bus charge, the phase current unbalance reduction, and the possible reactive current compensation over other areas outside the load) is the equal-but-opposite of the nonideal component of the load current , thus eliminating it from the current provided by the mains. Considering a negligible effect of over the system dynamics (ideal coil), the pulse pattern can be simplified to the The target of the inner control loop is to follow as quickly as possible (7 or 8 pattern periods , in practice) the instantaneous reference value decided for by the hierarchical ensemble of outer control loops. In this operating mode, is considered as part of the load. The outer loops pay attention to the dc bus voltage and to every load+line current amelioration function prescribed for the conditioner. Their preference hierarchy is carried out by their response time, the faster (lower response time) being the first in preference. The current filter block diagram is shown in Fig. 6. The first (fastest) loop refreshes the current reference signal after every sample of the data logger. In absence of other constraints non related itself with the own phase current, this reference is elaborated, as announced before, as the difference between the instantaneous value of the load current and the extracted fundamental component. In turn, this ideal value is elaborated by a filter algorithm who continuously averages the actual value of along a time period inversely proportional to the required precision [22]. In this way, the first loop eliminates, from the line current the nonideal component of the load current. The second and third loop controls the dc bus voltage (average value 720 V in practice) and the reactive power generated by the conditioner. Their time constant is about one line period. The fourth loop controls the balance of the top and bottom capacitor voltage and of and in the dc bus. Its time constant is much higher than the one in the previous loops. The fifth controls the mains current unbalance. Another control strategy, for the hybrid current filter option, has been implemented in the same DSP (ADSP-2101 from Analog Devices) using sliding mode techniques [23]. It watches both the cancellation of the high frequency current harmonics reserved to the active filter and the elimination of the resonance of the LC arms with the line impedance, thus alleviating the voltage filter from this task (see Fig. 12). The control algorithm of the current filter, when acting as a voltage inverter, is an adapted version of the one used in the voltage filter. They share the basic control strategy and differ in the measured and the controlled variables. VI. PROTOTYPES The electric and electronic design of six conditioners ranging from 50 kVA to 1 MVA has been completed. The first test of the control algorithms has been carried out over an 1-kVA onephase and a 3-kVA three-phase laboratory model. The last one is a complete copy of the 400-kVA industrial prototype, in which the coils and transformer quality factors have been replicated. The line voltage and load current disturbances have been implemented in the 3-kVA model by means of programmable ac sources. The hybrid current filter option has been tested over a 15-kVA three-phase prototype in which the passive filter (three Fig. 9. Voltage active filter test. Response to an 18% positive step in the line voltage: Upper trace, line voltage. Lower trace, output voltage. The recovery time is in the order of 0.5 ms. Fig. 7. A 400-kVA prototype under test, front view: Control circuit, top left. Compensating transformers, middle left. DC bus, bottom. Static switches, right top. Input-output terminals and protectors, middle right. Fig. 8. The 400-kVA prototype, rear view: IGBT drivers, top. Paralleled power IGBT, middle. DC bus, bottom. LC arms for 5th, 7th, 11th harmonics) ranges 9 kVA and the load is a six diodes rectifier bridge charged with a 15-kW resistor. A 400 kVA industrial prototype (Fig. 7) has been constructed and validated under full load conditions tests, except for some voltage disturbances. In the prototypes construction have collaborated SAFT Ibérica, UNED and CENIDET (Centro de Investigación y Desarrollo Tecnológico, Cuernavaca). The tests have been supervised by ASINEL (Asociación para la Investigación Eléctrica) and IBERDROLA. Power IGBT in parallel, directly connected to the dc bus, have been used for the active filters in the 400-kVA prototype. In order to prevent voltage spikes during commutation, it has been crucial obtaining a low stray inductance in the dc bus through the direct connection of the dc capacitors terminals to three isolated, but close together cooper-plates (see Fig. 8). The extra dc capacitors needed for obtaining 500 ms of UPS operation over 20% of critical load have been located in an nearby cabinet. The connecting cables inductance is not important because the capacitors in the main dc bus provide by themselves a low impedance way for the ripple currents. Also important for the correct operation of the power transistor has been the use of drivers provided by drain-source voltage sensor. One first level protection inhibits the local driver in case of a too high value of the sensed voltage. Another second level protection, commanded by a central watching unit, inhibits every driver (thus stopping the filters operation) and shorts the primary of T1, leaving the load connected to the grid trough its short-circuit impedance. In this way, the minimal disturbance is caused to the load in case of a general failure of the conditioner. The active filters inductances construction elected has been air-core, Litz wire multilayered cylindrical coil. As the commuting frequency is high (15.6 kHz), other solutions based on new core materials are liable to be cheaper than that. Each control circuit has been implemented on an ADSP-2101 from Analog Device. Certain degree of saturation has been observed when all the tasks are required. No special coupling problems have been encountered between power circuit and control circuit using standard isolation techniques. Special care has been taken over the decoupling of the power dc supplies by means of an unique high voltage source feeding several dc-dc converters distributed into the control blocks. VII. RESULTS A. Voltage Active Filter The time response of the active voltage filter for positive and negative steps is in the range of 0.5 ms. See Fig. 9. This means than the proposed power topology, associated to the inner dead-beat control loop described in [17] with 15.6 kHz commutation frequency, is likely to reduce significantly line voltage harmonics up to order 11th (whose period is 1,8 ms and frequency is 550 Hz in 50-Hz systems). The prevention of the resonance between capacitor and the line impedance, which can appear in ’weak’ systems (for values of this impedance typically over 2% of the nominal impedance) can be achieved by means of an input impedance resistant algorithm for the inner loop, or by filtering the voltage input signal Fig. 10. Voltage active filter test. Flicker attenuation. Response to a 15% amplitude modulation at 10 Hz. Up, modulated line voltage. Down, output voltage in the case of a high impedance line; the modulation is reduced from 21:72) to 3.9% (P st = 8:094). With a low impedance line, the 15% (P st P st is reduced to 8.6. = Fig. 11. Voltage active filter test. Reduction of third harmonic. Top, distorted line voltage. Bottom, output voltage. Left, harmonic and fundamental in phase, THD reduction from 15% to 2.66%. Right, harmonic and fundamental opposite, reduction from 19% to 3.3%. TABLE II CURRENT HARMONIC REDUCTION for the resonance frequency. As this frequency is high (in the order of 2.5 kHz for a line impedance of 0.04 p.u. and a reactive power in of 0.01 p.u.) the overall active filter operation is not penalized greatly. In practice, the voltage control has shown acceptable results in low frequency disturbances as flicker (see Fig. 10) and in harmonics up to 7th (see Fig. 11 for harmonic 3 reduction) and needs optimization for 11th and 13th. B. Active Current Filter Although the commutation frequency and the control strategy of the inner control loop used in the current filter are similar to those used in the voltage filter, the results obtained for the current harmonic reduction are poorer. Table II shows the reduction of the current harmonics measured in the mains, with respect to those measured in the load, obtained in the 400-kVA prototype when charged with a power resistor through a six pulse noncontrolled rectifier. Fig. 12. Optional hybrid current filter operation damping the resonance of three LC arms tuned to 5 , 7 and 11 harmonics with the line impedance in a 15 kVA, three phase, 110-V line-neutral prototype [23]. Upper figure: Currents when resonance damping is off. Upper trace, load current; 2nd trace, passive filter current; 3rd trace, mains current. (50 A/div.). Lower figure: Idem when the resonance damping is on. Upper trace, load current; 2nd trace, passive filter current; 3rd trace, active filter current; 4th trace, mains current. (50 A/div.). The low degree of inverse proportionality between the harmonic order and the correspondent obtained reduction indicates than the control algorithm needs supplementary optimization work. The appreciable reduction in harmonics as high as 17th and 19th indicates than this optimization must be done preferably in the outer control loops. C. Hybrid Current Filter As part of the plan for obtaining a complete power topology for line conditioners, the test of the hybrid option for the current filter has been carried out on the mentioned 15-kVA prototype. The active circuit of the filter is significantly reduced in power as it is dedicated to reduce the current harmonics 13th and higher, the fifth, seventh, 11th harmonics being attenuated by the LC arms. This option has not been taken into account for the usage coefficients calculations and may be interesting if an important part of the nonideal load current comes from stable and low frequency harmonics. It has been also proved [23] than the damping of the resonance between the passive LC arms and the line impedance Fig. 13. Operation as uninterruptible power supply (UPS). Upper trace, line voltage showing a 500-ms interruption. Lower trace, voltage in the critical load output. can be trusted on the active current filter. In this way, the universal conditioner showed integrates as well the advantages of this damping solution [17] over other solutions that relay on an additional voltage active filter [6], [12]. In Fig. 12 are shown the results of the hybrid current filter for both tasks: the load current harmonic reduction and the damping of the resonance. Another role not investigated for this current filter control version is to extend the damping effect up to the resonance frequency among the line impedance and capacitor , thus releasing the voltage filter control from this task. D. UPS Operation As shown in Fig. 13, the transfer of the critical load from mains to the current filter, acting as a voltage inverter, happens with no significant dead time. The key is to turn-off the thyristor switch SO in a fast mode. This has been done, without auxiliary forced commuting switches, by means of an adequate sequence in the SO driving pulses, coordinated with the pulses (as voltage inverter) of the active filter during the first 50-Hz period. The procedure has shown to be sensitive to the accuracy in the detection of the line phase. VIII. CONCLUSION A very complete universal line conditioner showing a high effectiveness/cost ratio has been developed guided by an iterative analysis+synthesis cost comparative method which allows to know the effective power and cost of the components needed for every topology investigated. The conditioner is composed by one fast active voltage filter and one fast active current filter (both made with IGBT modulated at 15.6 kHz). The active power filter can be paralleled with classic resonant LC filters for low frequency current harmonics. The active voltage filter reduces slow line deviation (as flicker and voltage unbalance) and fast deviations (up to harmonic 19th). The active current filter reduces current harmonics up to order 19th and can compensate power factor and current unbalance. In case of a line sustained interruption, the current filter reconfigures to uninterruptible power supply, feeding 20% of the nominal load during 500 ms from the energy stored in the dc bus capacitor (overrated five times for this purpose). Main improvements over previous solutions [7], [8], [10], [15] are the elimination of the input and output series static switches which accomplish the reconfiguration to UPS, and the possibility of hybridizing the active current filter with LC resonant arms. In this case, the control circuit of the active current filter can eliminate the resonance of the LC arms with the line impedance with no help from the voltage filter [23]. The last improvement means also a sound simplification for the hybrid (LC arms plus active) current filters applied on its own. The tests confirm the universality of this cost effective power topology, but also indicates that the control circuit needs new investigation in order to improve the results on high frequency voltage and current harmonic reduction and in the resonance damping. This could be facilitated by lowering the sampling time (64 s) by the use of a faster DSP. REFERENCES [1] L. Gyugyi and E. C. Strycula, “Active power filters,” in Proc. IEEE/IAS Annu. Meeting, 1976, p. 529. [2] N. Mohan and H. A. Peterson, “Active filters for AC harmonic suppression,” in Proc. IEEE/Power Eng. Soc. Winter Meeting, 1977. [3] J. Uceda, P. Martínez, and F. Aldana, “Active filters for static power convertors,” Proc. Inst. Elect. Eng. B, vol. 130, pp. 347–354, Sept. 1983. [4] F. Z. Peng, H. Akagi, and A. Nabae, “A new approach to harmonics compensation in power systems,” in Proc. 1998 IEEE-IAS Annu. Meeting, Oct. 1988, pp. 874–880. [5] W. M. Grady, M. J. Samotyj, and A. H. Noyola, “Survey of active power line conditioning methodologies,” IEEE Trans. Power Delivery, vol. 5, pp. 1536–1542, July 1990. [6] T. Tanaka and H. Akagi, “A new combined system of series active and shunt passive filter aiming at harmonic compensation for large capacity thyristor converters,” in Proc. IEEE IECON, 1991. [7] L. Gyugyi, “A unified power flow control concept for flexible AC transmission systems,” Proc. Inst. Elect. Eng. C, vol. 139, pp. 323–331, July 1992. [8] L. Azpiazu, P. M. Martínez, S. Martínez, V. Feliu, and F. Yeves, “Voltage and current conditioner for distribution networks reconfigurable to UPS,” in Proc. CIRED Int. Conf., Birmingham, AL, 1993, pp. 17–21. [9] S. Martínez, V. Feliu, F. Yeves, J. L. Iribarren, and P. M. Martínez, “Acondicionador de Línea Para Reducción o Eliminación de Perturbaciones,” (in Spanish), P-9 300 932/1, 03,05-1993/3, 1993. [10] C. H. Chen and D. M. Divan, “Simple topologies for single phase AC line conditioning,” IEEE Trans. Ind. Applicat., vol. 30, pp. 406–412, Mar. 1994. [11] S. Martínez, V. Feliu, F. Yeves, J. L. Iribarren, and P. M. Martínez, “Dispositif de Condicionnement de Ligne Pour Reduire ou Eliminer les Perturbations,” (in French), European Patent 94 069631, 05, 1994. [12] H. Akagi, “Trends in active power line conditioners,” IEEE Trans. Power Electron., vol. 9, pp. 263–268, May 1994. [13] M. B. Brennen and B. Banerjee, “Low cost, high performance active power line conditioners,” in Proc. PQA, 3rd Int. Conf. Power Qual.: End Use, Applicat. Perspectives, Amsterdam, The Netherlands, Oct. 1994. [14] C. Pumar, F. Mur, F. Yeves, and V. Feliu, “Interactive voltage and current high frequency line conditioner,” in Proc. PQA, 3rd Int. Conf. Power Quality: End Use, Applicat. Perspectives, Amsterdam, The Netherlands, Oct. 1994, pp. 24–27. [15] L. Gyugyi, C. D. Schauder, S. L. Williams, and T. R. L. Rietman, “The unified power controller: A new approach to power transmission control,” IEEE Trans. Power Delivery, vol. 10, pp. 1085–1093, Apr. 1995. [16] F. Yeves, J. Carpio, S. Martínez, V. Feliu, and C. Pumar, “Iteractive voltage and current high frequency line conditioner,” EPE J., vol. 5, pp. 38–43, Jan. 1996. [17] H. Akagi, “New trends in active filters for power conditioning,” IEEE Trans. Ind. Applicat., vol. 32, pp. 1312–1322, May 1996. [18] V. Feliu, F. Mur, I. de la Nuez, and S. Martínez, “Pulse width modulation based control system for voltage conditioning of distribution networks,” in Proc. IFAC World Congress, San Francisco, CA, June-July 30–5, 1996. [19] J. Häfner, M. Aredes, and K. Heumann, “A shunt active power filter applied to high voltage distribution lines,” IEEE Trans. Power Delivery, vol. 12, pp. 266–272, Jan. 1997. [20] S. Bhattacharya, P.-T. Cheng, and D. M. Divan, “Hybrid solutions for improving passive filter performance in high power applications,” IEEE Trans. Ind. Applicat., vol. 33, pp. 732–747, May 1997. 290 [21] M. Aredes, K. Heumann, and E. H. Watanabe, “An universal active power line conditioner,” IEEE Trans. Power Delivery, vol. 13, pp. 545–551, Apr. 1998. [22] F. Mur, V. Cárdenas, J. Vaquero, and S. Martínez, “Phase siynchronization and measurement digital systems of AC mains for power converters,” in Proc. IEEE Int. Power Electron. Conf. (CIEP’98), Oct. 1998, pp. 188–194. [23] V. M. Cárdenas, “Filtros activos híbridos para compensación armónica de corriente y corrección de factor de potencia en sistemas trifásicos,” Ph.D. dissertation, CENIDET, Cuernavaca, México, 1999. [24] F. Barrero, S. Martínez, F. Yeves, and P. M. Martínez, “Active power filters for line conditioning: A critical evaluation,” IEEE Trans. Power Delivery, vol. 15, pp. 319–325, Jan. 2000. [25] H. Fujita, T. Yamasaki, and H. Akagi, “A hybrid active filter for camping of harmonic resonance in industrial power systems,” IEEE Trans. Power Electron., vol. 15, pp. 215–222, Mar. 2000. [26] M. El Shatshat, M. Kazerani, and M. M. A. Salama, “Multi converter approach to active power filtering using current source converters,” IEEE Trans. Power Delivery, vol. 16, pp. 38–45, Jan. 2001. [27] S. M.-R. Rafiei, H. A. Toliyat, R. Ghazi, and T. Gopalarathnam, “An optimal and flexible control strategy for active filtering and power factor correction under nonsinusoidal line voltages,” IEEE Trans. Power Delivery, vol. 16, pp. 297–305, Apr. 2001. Fermín Barrero (M’95) received the M.Sc. degree in electrical engineering from the Universidad Politécnica de Madrid, Madrid, Spain, in 1984 and the Ph. D. degree from the Universidad Nacional de Educación a Distancia, Spain, in 1995. He is a Full Professor in electrical engineering at the Universidad de Extremadura, Spain. His research interests are power electronics in the power system, FACTS, active power filters, and electrical machine drives. Dr. Barrero is a member of the IEEE IAS Industrial Static Converters Committee, European Working Group. Salvador Martínez (SM’90) received the M.Sc. and Ph. D. degrees in electrical engineering from Universidad Politécnica de Madrid, Madrid, Spain, in 1966 and 1969, respectively. He was an Associate Professor at the Universidad Politécnica de Madrid, from 1975 to 1979, and at the Universidad Nacional de Educación a Distancia, Madrid, from 1979 to 1982, where he has been a Full Professor since 1982. He spent eight years as a Design Engineer on power electronics equipment in several companies. His research interests are integrated magnetics, transformer calculation programs, and power line conditioners. Dr. Martínez is a member of the IEEE IAS Industrial Static Converter Committee, European Working Group. Fernando Yeves (M’90) received the M.Sc and Ph.D. degrees in electrical engineering from Universidad Politécnica de Madrid, Madrid, Spain, in 1981 and 1987, respectively. He was an Associate Professor at the Universidad Politécnica de Madrid, from 1985 to 1990, and a Full Professor at the Universidad Nacional de Educación a Distancia, Madrid, since 1990. His research interests are power electronics equipment for solar energy systems and the electrical grid, both in power topology and control circuits supported by DSPs. converters. Francisco Mur received the M.Sc degree in electrical engineering from the Universidad Politécnica de Madrid, Madrid, Spain, in 1992 and the Ph.D. degree in electrical engineering from the Universidad Nacional de Educación a Distancia, Madrid, in 1998. He has been a Full Professor at the Universidad Nacional de Educación a Distancia, Madrid, since 1998. Since 1993, he has participated in several activities on power conditioning. His research interests are power circuits, control circuits supported by DSPs and control programs for power static Pedro Mª Martínez received the M.Sc. degree in electrical engineering from the Universidad Nacional de Educación a Distancia, Madrid, Spain, in 1989. Since 1995, he has been a Tutorial Professor in the Bilbao Center. Universidad Nacional de Educación a Distancia, Madrid. He joined the Electric Power Corporation IBERDROLA S.A., in 1979, where he has been leader of several research projects on FACTS. His current status is Technological Development Manager of the Electrical Lines Division. He participates in several international committees promoting FACTS development.