Digitize, Inc. ■ 158 Edison Road ■ Lake Hopatcong, New Jersey 07849
Tel: (973)663-1011 Fax: (973)663-4333 ■ Website: http://www.digitize-inc.com
Complete Supervised Power Supply and Charger for Outdoor Mesh Radio
Transceivers.
Mesh radio Includes enabled Dual
Transcievers and MIMO
8 EOL Zone Inputs for Local
Connection (3 zones reserved for AC,
DC and Tamper)
72 Hours of Battery Backup. Recharge in 48 hours
Operates from 120/240 Volts AC
(jumper selectable), 50-60 Hz
Fully Supervised Operation
Enclosure houses two series 75 Amp
Hour 12 VDC Batteries
Expandable to 3,168 remote inputs and or relay outputs
Ethernet Connections expandable with
Internal Switch/Router
Internal Visual and Audible indicators
(user selectable)
Wall Mount Lockable Steel enclosure with Door Tamper signal
Fused Outputs
Surge Protected Power and Ethernet
Connections
Class 2 Power Limited
Short Circuit, Over Current, & Over
Temperature Protection
Form C Relay Output
UL 864 Compliant
MeshSentry™ Radio Network - Power Supply /
Charger MeshSentry™ and Battery Enclosure
MeshSentry™ Network
Antennas (Sold
Separately)
The Digitize MeshSentry™ Mesh Radio Network -
Supervised Power Supply / Battery Charger and Mesh
Radio is a complete power solution for Mesh Radio
Transceivers. The Fire Listed Power Supply will power the Mesh Radio Transceiver and provide 72 hours of battery backup during a power failure. All aspects of the
Power Supply are remotely supervisable including: AC
Power Fail, Low or missing battery, and enclosure tamper.
The Power Supply is housed in a lockable steel enclosure that can hold two 75 Amp Hour 12 volt batteries.
The Digitze VersAlarm™ Controller monitors the power supply, 8 zone inputs, and optional Q-Mux Node controller(s) via Ethernet through the Mesh Radio
Transceiver. Expandable to 32 Optional Q-Mux Nodes allows for up to 3,168 additional remote input and or relay outputs.
Lockable Indoor Enclosure measures approximately 22”
Wide x 12” Deep x 20” High.
Order Unit: P/N 425211-0002 CUTSHEET P/N 750652-0001 Rev. C 09/13
Specifications Subject to Change Without Notice
I np ut V o l t ag e: Operat es f rom 120 or 240 V olts AC, 50-60 Hz at 2 A mps M ax
Out p ut V o l t ag e: 12 V DC at 4 A mp M ax f or operation of M esh radio and V ersA larm B d.
24 VDC at 2 Amp M ax f or bat t ery charging.
C o mmuni cat i o n: Et hernet connect ion t o t he M esh Radio.
A ud ib le I nd i cat o rs: Indicates loss of communicat ion t o Head End Equipment.
O ut p ut s: Optional Q-M ux Node – 1 Form C Relay Output on Board Rat ed 30 Volts
DC at 2 A mps M ax. Will accommodat e t wo wit hing enclosure, 30 ext ernal.
I np ut s: 8 Supervised EOL Zones (3 used f or A C Fail, Low B att ery, And Tamper. Q-
Optional Q-M ux Node - addit ional 99 remot e input s and or out put s.
Encl o sur e: St eel Wall M ount ed Red Indoor Enclosure, Hinged Door, Key Lockable
Dimensions: 22” Wide x 12” Deep x 20” High.
M ount indoors in a Dry Environment .
F aul t co nd i t i o ns: Low or missing AC, High or low out put / bat tery, B lown f use, M issing bat t ery, Reversed B att ery, Int ernal Power Supply f ailure, Door Tamper,
Loss of Dat a Comm. sent t o Head End via Digit ize A LAN Prot ocol.
T emp er at ur e R at i ng s: Operat ing Temperat ure: 0 degrees C to 49 degrees C
Ambient Humidity: 93% @ 32 degrees C
Environment : Indoor, dry
B at t er y C har g er
Sp eci f i cat i o ns:
Bat t ery Type: Sealed lead acid rechargeable
Charging V oltage: 24 VDC
M aximum bat tery charge capacity: 80 A h in 48 hours
M aximum bat tery charge current : 2 A
Requires Two, 12 VDC 75 AH B att eries which are not included and must be ordered separat ely.
Digitize MeshSentry Radio Network - Power Supply /
Charger
Shown with Door Open and Batteries Installed
Power Supply / Charger Door Label
Optional MMX Addressable
FACP interface
Optional SNP-3 accommodates Up to three SNP
EOL or RLY IDMs
Digitize VersAlarm Controller
Optional TCU-8 Controller
Can expand to 99 Remote
Inputs and or Outputs IDM’s
Order Unit: P/N 425211-0002 CUTSHEET P/N 750652-0001 Rev. C 09/13
Specifications Subject to Change Without Notice