TH104
• Easy Installation. Two way wireless powerline control, no additional control wiring necessary. Retrofits to hotel room light switch
• Insertion of room key card in the TH104 enables the room HVAC.
• Removal of key card when guest leaves disables room HVAC and puts it under control of the TH104 which automatically enables
HVAC to maintain 60 O F minimum (in heating mode) or 80 O F maximum temperature levels (in cooling mode) with card removed.
• Handles two sizes of room key cards.
• Automatically switches Hotel Room HVAC units to unoccupied energy saving cycle when room occupants are not present. Can also control other loads such as T.V., lights, etc.
The TH104 is an A10 enhanced X-10 based product that retrofits to the light switch inside the hotel room door. The slot in the top accepts the room key card. Insertion of the card enables the room HVAC unit by transmitting an ON command over existing power wiring to a powerline carrier receiver controlling the power or thermostat of the HVAC unit.
When guests leave the room, they retrieve the room key card from the TH104 and 60 seconds
later the TH104 transmits an OFF command.
During unoccupied times (no room key card inserted) the TH104 automatically enables the HVAC system if the room temperature falls below 60 O F or exceeds 80 O F (+/- 3 degrees), utilizing an internal thermistor sensor.
Additional connections are provided for two external thermistor sensors to allow monitoring of multi-room suites. A standard Decora TM style wall switch and dual face plate are provided to replace the existing wall switch function.
Specify: TH104 (also requires a powerline receiver in the appropriate voltage installed on the HVAC unit) - see RI and RB series receivers.
Supply Voltage
Signal Output
Load Rating
Card Key Sizes (Field Selectable)
120 VAC, +/-10%
6V p-p (peak to peak) minimum. Carrier frequency is 120 kHz +/-1kHz.
15A, 120 VAC maximum
Power Connections
Remote Sensor Wire
Dimensions
Weight
Housing
Large: Standard Credit Card Size: 3.365" x 2.12" (Factory Set)
Small: 3.365" x 1.71"
4 Flying leads: Hot (BLACK), 12 AWG, stranded
Neutral (WHITE), 16 AWG, stranded
Ground (GREEN), 12 AWG, stranded
Load (BLUE), 12 AWG, stranded
22 AWG recommended
4.75" High x 4.9" Wide x 2.0" Deep
37 ounces
Wire Mold #2948-2 enclosure, mounts to existing 2" x 4" electrical box
ADVANCED CONTROL TECHNOLOGIES, INC.
Indianapolis, Indiana 46278
0463-01
1
TH104 Specification
P/D 061208
Operating Temperature
Storage Temperature
Operating Humidity
32 to 120 degrees F
-40 to 185 degrees F
25 to 95% non-condensing
For Indoor Use Only
Specifications may change without notice to improve product performance.
TH104 Specification
P/D 061208
0463-01
2
ADVANCED CONTROL TECHNOLOGIES, INC.