Tech Sheet

advertisement
BUY AMERICAN ACT OF 2009 COMPLIANT
FINELITE
Series 12WM-P, I, ID Technical Sheet
Date
Project
Type
Comments
Parabolic Louver
Diffuse Center Optic
Signal White is
standard finish
DESCRIPTION
Series 12 Wall Mount comes in three distinct styles; P with perforations, I - 100% indirect,
and Indirect/Direct (ID) with either WCB White Cross Blade, PLV Parabolic Louver baffles or
Diffuse Center Optic. All fixtures are available with 1 or 2 T8, T5 or T5HO lamps in 4' and
8' lengths. Standard flat endcaps or optional curved die-cast endcaps. Mounting includes
SO standoff mount, MB mounting bracket, or SUR surface mount flush to wall without a
mounting bracket.
Standoff Mount
S12WM-ID: 2T8
S12WM-ID: 1T8
2.5"
Mounting Bracket
6.3"
S12WM-P: 1T8
S12WM-I: 1T8
Surface Mount
DIMENSIONS / LAMPING:
ENDCAP SELECTION:
MOUNTING OPTIONS:
Available in 1 or 2 T8, T5, or T5HO lamps.
Available in 4’ and 8’ section lengths.
S12 Wall Mount is available with standard flat
endcap on optional curved diecast endcap.
Mounting includes SM standoff mount, MB
mounting bracket, or SUR surface mount
flush to wall without a mounting bracket.
ORDERING GUIDE
Sample Number: S12WM-I - WCB - 32’ - 2T8 - SC - 91W - 277 - SUR- FE - 0.88
S12WM-I
Due to continuing product improvements, Finelite reserves the right to change specifications without notice. Please visit www.finelite.com for most current data.
Form CTK0028.12/14
Finelite, Inc. • 30500 Whipple Road • Union City, CA 94587-1530 • 510 / 441-1100 • Fax: 510 / 441-1510 • www.finelite.com
© 2014 FINELITE, INC. ALL RIGHTS RESERVED.
Finelite Series 12WM (P-Perforated, I-Indirect, ID-Indirect/Direct)
Shielding (ID ONLY - DCO, WCB, PLV)
Run length (4', 8', multiples standard)
Number of lamps in cross section (1, or 2 T8, T5 or T5HO)
Circuiting (SC-single circuit, DC-dual circuit)
Reflector system (91W, EP)
Voltage (120, 277, 347V)
Mounting (SUR, SO, MB)
Endcap FE (flat), CE (curved)
Ballast factor (Standard 0.88 for T8 lamps, 1.0 for T5 or T5HO)
BUY AMERICAN ACT OF 2009 COMPLIANT
FINELITE
Series 12WM-P, I, ID Technical Sheet
PHOTOMETRY
700
800
350
400
S12WM-ID: 1 T8-WCB-91W
350
700
0
5
15
25
35
45
55
65
75
85
90
95
105
115
125
135
145
155
165
175
180
45.0
457
463
468
394
293
191
122
80
43
9
0
48
291
403
415
437
448
455
450
462
473
67.5
457
469
485
391
279
174
127
92
48
12
0
54
305
488
499
488
486
478
455
461
473
90.0
457
478
486
383
262
169
131
90
45
9
0
37
268
501
538
502
499
484
460
460
473
S12WM-P: 1 T8-91W
Efficiency: 83.4%
Peak Candela Value: 612@ 125˚
LSI Report: 18466
CANDLEPOWER SUMMARY
22.5
457
455
434
397
330
235
150
83
45
13
0
83
223
273
319
363
400
427
452
469
473
400
S12WM-ID: 1 T8-WCB-EP
Efficiency: 83.3%
Peak Candela Value: 538@ 125˚
LSI Report: 18462
0.0
457
451
411
353
286
213
143
82
41
10
0
18
98
180
258
328
386
431
462
474
473
800
Efficiency: 77.3%
Peak Candela Value: 712@ 155˚
LSI Report: 18562
400
800
CANDLEPOWER SUMMARY
Flux
23
64
89
91
77
60
42
24
6
34
131
184
182
164
139
105
64
22
0
5
15
25
35
45
55
65
75
85
90
95
105
115
125
135
145
155
165
175
180
0
447
442
402
345
281
210
140
81
39
9
0
16
92
172
248
315
373
416
445
460
457
22.5
447
444
418
377
317
227
146
82
45
14
0
78
220
285
338
382
413
430
444
454
457
45
447
449
444
378
282
187
120
79
42
8
2
25
310
439
462
486
490
481
461
449
457
67.5
447
453
463
375
272
169
125
91
48
13
1
25
325
539
560
559
544
519
475
450
457
CANDLEPOWER SUMMARY
90
447
461
464
369
256
166
128
89
45
9
2
6
280
550
612
580
568
535
486
451
457
Flux
22
61
85
88
75
59
42
23
6
29
136
198
200
181
150
110
65
22
0
5
15
25
35
45
55
65
75
85
90
95
105
115
125
135
145
155
165
175
180
0
23
23
23
20
17
14
8
5
2
0
0
25
148
272
380
473
554
618
662
685
682
22.5
23
24
24
23
23
19
16
11
7
3
6
139
282
369
454
529
615
658
684
688
682
45
23
25
26
26
27
24
23
18
12
6
13
126
424
490
548
605
647
674
703
695
682
67.5
23
24
27
29
31
29
27
23
18
11
14
162
505
600
633
669
696
702
715
695
682
90
23
25
29
31
33
31
29
25
19
11
16
131
484
635
664
686
707
712
711
695
682
Flux
1
4
6
8
9
9
8
6
4
72
197
236
241
230
202
156
98
34
— Refer to www.finelite.com for additional photometry and product information.
SPECIFICATIONS
CONSTRUCTION: Body is 20-gauge die-formed steel
with 18-gauge die-formed internal joiner system, plugtogether wiring standard. All components are
hard-tooled to tolerances of 0.010".
ACCESSORY: Optional Dust Cover, clear acrylic. T5 and
T8 lamps only. Not suitable for T5HO lamps. NOTE: Will
significantly impact light level performance. Contact
Factory.
S12WM-P ONLY: Precision-punched 0.093" diameter
perforations cover the bottom side of the fixture.
ACCESSORY S12WM-P ONLY: Optional Clearperf™ Lens
factory installed, semi-translucent opal acrylic, UV
stable, covers perforations inside fixture. Standard with
1-T5HO lamp. NOTE: Impacts light level performance.
Contact Factory.
ENDCAPS: (FE) Flat Endcap standard, 20-gauge dieformed steel, adds 0.1" at each end. Optional: (CE)
Curved Endcap, aluminum die-cast endcap with 0.100"
reveal, add 5.0" at each end. No exposed fasteners, holes
or knockouts.
REFLECTORS: Standard (91W) 91 White : Die-formed
pre-painted aluminum, 91% reflective white. Optional
Extended Performance (EP) reflector system.
LAMPING: Available in 1 or 2 T8, T5, or T5HO lamp
cross sections.
BALLAST: Electronic instant-start ballast <10% THD,
0.88 BF standard for T8 lamps. Electronic rapid-start
ballasts <10% THD, 1.0 BF standard for T5/T5HO lamps.
Optional adders: rapid-start ballasts (standard for
T5/T5HO), 347V, emergency battery packs, dimming
ballasts (controls by others). Requires low-profile
ballasts and battery packs.
FEED: 18 gauge wire. 14 gauge wire used when fixture
current exceeds 6 amps. Optional feed uses cord.
FINISHES: Finelite Signal White standard. Optional
Adders: 185 colors available from Tiger Drylac’s RAL
color chart.
LENGTHS: 4' and 8' section lengths can be combined to
make longer runs. Contact factory for additional lengths.
WEIGHT: Fixture weight = 2.0 lb/ft.
LABELS: Fixture and electrical components are ETL
listed conforming to UL 1598 in the U.S.A., and
Canada; ETL listed to certified CAN/CSA C22.2 No.
250.0. Fixtures will bear ETL labels.
Due to continuing product improvements, Finelite reserves the right to change specifications without notice. Please visit www.finelite.com for most current data.
Form CTK0028.12/14
Finelite, Inc. • 30500 Whipple Road • Union City, CA 94587-1530 • 510 / 441-1100 • Fax: 510 / 441-1510 • www.finelite.com
© 2014 FINELITE, INC. ALL RIGHTS RESERVED.
(S12WM-ID ONLY)
SHIELDING OPTIONS:
DCO Diffuse Center Optic, 73% transmissive,
99% diffusion.
WCB White Cross Blade Baffle, white cross
blades with curved bottoms, perforated;
PLV Parabolic Louver, semi-specular louvers
with straight edge, spaced approximately
1.0" apart.
ELECTRICAL: 120 or 277V prewired. Fixture and electrical components are UL/C-UL listed and fixture will bear
UL/C-UL labels. Optional Adders: 347V prewired, dual
circuit, emergency circuits, low-profile emergency
battery packs. Contact factory.
MOUNTING OPTIONS: Standard (SUR) Surface Mount,
fixture is bolted directly into existing wall studs. Optional
(SO) Standoff Mount, fixture hangs from tapered
mounting bracket fastened to wall at fixture ends and
joints. Standoff bracket measures 4.5" wide, 6.0" tall,
and 0.5" deep. Fixture hangs 0.5" from wall. Feed goes
through mount to vertical J-box. Optional (MB)
Mounting Bracket, fixture hangs from bracket fastened
directly to wall. Mounting bracket in 4', 8' lengths.
Fixture hangs 0.5" from wall. Mounting bracket is
concealed behind fixture.
Download