1 June 2004 Base Building — Issued for Construction SECTION 15000 — HEATING, VENTILATING AND AIR CONDITIONING for MUSEUM OF ISLAMIC ARTS Doha, Qatar Architect I.M. Pei, Architects 88 Pine Street New York, New York 10005 USA Structural Consulting Engineers Leslie E. Robertson Associates 30 Broad Street New York, New York 10004 USA Mechanical/Electrical/Vertical Transportation Consulting Engineers Jaros, Baum & Bolles 80 Pine Street New York, New York 10005 USA SECTION 15000 HVAC TABLE OF CONTENTS Article Title Page PART 1 - GENERAL 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 1.19 1.20 1.21 1.22 1.23 1.24 1.25 General Requirements Related Work Specified in Other Sections Design Criteria Description of Systems Notice to Bidders Subcontractor/Engineer General Coordination Composite Drawings General Construction Drawings Shop Drawings and HVAC Consulting Engineer's Review Record Drawings Codes and Permits Protective Painting Identification of Systems Tools Sleeves Operating and Maintenance Instructions Repair and Maintenance Parts Subcontracts Engineering Reference Points Guarantee Cutting and Patching Rubbish Removal Protection 1 1 2 3 12 12 13 13 14 16 17 23 24 24 25 26 26 28 28 29 29 30 30 30 31 PART 2 - PRODUCTS 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 Approved Manufacturers Materials for Piping Pipe Fittings Valves Strainers Relief Valves Identification of Systems Hangers, Anchors, Supports, Guides, etc. Flow Measuring Systems Automatic Air Eliminators Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-TC-1 31 45 46 51 56 57 57 58 61 62 HVAC Issued for Construction 1 June 2004 TABLE OF CONTENTS (Continued) Article 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 2.19 2.20 2.21 2.22 2.23 2.24 2.25 2.26 2.27 2.28 2.29 2.30 2.31 2.32 2.33 2.34 2.35 2.36 2.37 2.38 2.39 2.40 2.41 2.42 2.43 2.44 2.45 2.46 2.47 Title Page Pneumatic Diaphragm Expansion Tanks Open Expansion Tanks Water Makeup Pump Sets Centrifugal Pumps In-Line Circulating Pumps Condensate Pumps Centrifugal Refrigeration Machines Induced Draft Cooling Towers Condenser Water Filtration System Cooling Coils and Heat Recovery Coils Electric Heating Coils Factory Assembled Supply and Return Fan Units Centrifugal Fans Axial Flow Fans Packaged Air Conditioning Units (Chilled Water) Air Filters Sheet Metal Ductwork Access Doors Access Doors in Finished Construction Dampers Flexible Connections Grilles, Registers and Diffusers Variable and Constant Volume Boxes (DDC) Volume Control Regulators (DDC) Acoustic Treatment Insulation Foundations, Vibration Isolation Incorporating Seismic Restraints Seismic Restraints Work in Connection with Emergency Generator and Fuel Oil System Duplex Fuel Oil Pumps Motors Variable Speed Motor Controllers Electric Motor Controls Electric Wiring Automatic Temperature Controls Instruments Water Treatment 63 64 64 65 66 67 68 82 86 88 89 90 92 94 96 101 103 111 112 113 114 115 118 121 124 127 135 148 150 166 167 170 181 185 186 320 321 PART 3 - EXECUTION 3.01 3.02 3.03 Cleaning, Testing and Adjusting Testing, Adjusting and Balancing Installation of Piping 337 340 351 APPENDIX Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-TC-2 HVAC Issued for Construction 1 June 2004 SECTION 15000 HEATING, VENTILATING AND AIR CONDITIONING PART 1 - GENERAL 1.01 1.02 GENERAL REQUIREMENTS A. Work of this Section, as shown or specified, shall be in accordance with the requirements of the Contract Documents. B. Drawings, general provisions of Contract, and General Conditions all form a part of this Section of the Contract Documents. C. Where General Conditions clauses are repeated in these Specifications, it is to call special attention to them, or as a further qualification. No General Conditions clause referring to work of this Section shall be considered waived unless specifically stated herein. RELATED WORK SPECIFIED IN OTHER SECTIONS A. Finished painting of exposed pipes and apparatus. B. Outside air intake and discharge louvers, including insulated back-up panels, bulkheads, gratings, etc., with screens in walls. C. Concrete foundations, pads and blocks for equipment mounting (except as otherwise noted hereinafter), except that anchor bolts and templates shall be furnished as the work of this Section. Drawings of equipment foundation, curbs, pads and blocks (with required reinforcing rods, etc., indicated) shall be furnished for approval. D. Installation of access doors in finished building construction. E. Base flashing for all roof equipment, ductwork and piping penetrations. F. Ornamental grilles. G. Excavation and backfill. H. All cutting and patching, except as specifically modified in these Specifications. I. Electric power wiring, except that furnished as an integral part of factory assembled equipment and except as otherwise specified herein. J. Installation of plaster frames for diffusers, grilles and/or registers in finished construction furnished as the work of this Section. K. Framed openings and curbs for roof fans, etc. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-1 HVAC Issued for Construction 1 June 2004 1.03 L. Floor and funnel drains adjacent to equipment requiring the same. M. Undercutting of doors or louvers in doors. N. Domestic hot water heaters. O. Motor disconnect switches and circuit breakers, except in combination starters and where otherwise noted. P. Installation of all variable speed drives, starters and motor control devices, except factory mounted and wired as part of equipment. Q. Smoke detector elements and related wiring. R. Cold water makeup to cooling towers and compression tanks. S. Emergency diesel generator, diesel fire pump and associated monoxide exhaust muffler/silencer(s) and flexible connections. The muffler/silencer(s) and flexible connections shall be finished under another section of the Contract Documents and installed under this Section of the Contract Documents. DESIGN CRITERIA A. Temperature and Humidity Design Conditions 1. Outside Air: Summer: Winter: 2. Inside Air: Dry Bulb: 46°C. Wet Bulb: 30°C. Dry Bulb: Relative Humidity: 10°C. 90% Gallery Exhibit Spaces: Dry Bulb: 21°C. ± 1°C. *Relative Humidity: 50% ± 5% Public Space/ Atrium: Dry Bulb: 21°C. ± 1°C. Relative Humidity: 50% ± 5% Auditorium/ Conference Rooms/ Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Library: Dry Bulb: 24°C. ± 1°C. Relative Humidity: 50% ± 5% Office: Dry Bulb: 24°C. ± 1°C. Relative Humidity: 50% ± 5% 15000-2 HVAC Issued for Construction 1 June 2004 * 1.04 Restaurant/Cafe: Dry Bulb: 24°C. ± 1°C. Relative Humidity: 55% ± 5% Exhibit Storage: Dry Bulb: 21°C. ± 1°C. *Relative Humidity: 50% ± 5% General Storage: Dry Bulb: 26°C. ± 1°C. Relative Humidity: 55% ± 5% Kitchens: Dry Bulb: 30°C. ± 2°C. Exhibit storage and exhibit spaces shall be provided with systems of humidification where required, to maintain constant levels of temperature and humidity during the Winter months. 3. The design conditions for Mechanical Equipment Rooms, Electric Control Rooms, and workshops not used for artwork storage shall be cooled to 10°C. below the outdoor air-dry bulb or 30°C. as per the requirements of the equipment installed in the specific spaces. 4. Electrical Rooms, Elevator Machine Rooms, and Mechanical Equipment Rooms shall be cooled to 30°C. 5. Cooling towers shall be selected to operate at a wet bulb temperature of 32°C. B. Minimum Outside Air Quantity: 34 cubic meters per hour per person with a diversity factor in the population being applied to this quantity. (25 cubic meters per hour per person for Auditorium, Library, and Galleries.) C. Acoustical Performance: Refer to Articles entitled “Variable and Constant Volume Boxes (DDC)” and “Grilles, Registers and Diffusers”. D. Air Filtration: Refer to Article entitled “Air Filters”. E. Chilled Water Operating Conditions 1. Chilled water inlet temperature to coils 5.5ºC. 2. Chilled water leaving temperature from coils 12.2ºC. DESCRIPTION OF SYSTEMS A. Provide all materials, labor, equipment, tools, appliances, services, hoisting, scaffolding, permits, inspections, support and supervision for the furnishing and installing of all the Heating, Ventilating and Air Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-3 HVAC Issued for Construction 1 June 2004 Conditioning Work and all related work complete, in accordance with the Contract Documents. B. C. Central Refrigeration Plant 1. The central refrigeration plant shall consist of three (3) machines located in the B1 Level Mechanical Equipment Room. Each machine shall be sized at 50% of the total load. Machines shall be of the electric motor driven centrifugal type suitable for operation with environmentally acceptable refrigerants. A chilled water and condenser water pump shall be provided for each machine plus a standby (spare) pump for each type and size. Machines shall be piped in a parallel arrangement for operational flexibility and chilled water pumps shall be equipped with variable speed drives (the variable speed drives shall be programmed to maintain minimum required flow rates through the chillers). 2. The central refrigeration plant for water chilling shall include necessary electric motor driven refrigeration units, starters, water pumps, high efficiency motors and motor controllers, automatic controls, piping, insulation, manual and motorized valves, vibration isolation, acoustic treatment, control wiring, water treatment, and all required auxiliaries, etc., to make for a complete and operable system. 3. A complete refrigeration monitoring system shall be provided. Two (2) UL approved refrigerant sensors shall be provided for each chiller, complete with local alarm panel and alarm klaxon(s). Cooling Tower Condenser Water Systems 1. Central cooling tower shall be provided at the Roof Level of the Education Wing and shall consist of one 3-cell cooling tower sized for refrigeration tonnage required for the entire building (Gallery Octagon and Education Wing). Each cell shall be sized for 50% of the total load. 2. Cooling tower cells shall be of the cross-flow design, stainless steel and fiber glass reinforced polyester (FRP) construction and each shall be equipped with variable speed motors. 3. Each cooling tower cell shall have its own independent basin. An equalizing line shall connect the basins of the three (3) cooling cells in order to maintain a constant basin condenser water level. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-4 HVAC Issued for Construction 1 June 2004 D. 4. The condenser water system shall be provided with sand filtration systems at the cooling towers, complete with sand filters, pumps, piping, controls, valves, insulation, vibration isolation, wire tracing, and all required accessories, etc. 5. The condenser water system shall consist of cooling towers, complete with pumps, piping, insulation, water treatment, manual and motorized valves, motors and motor controllers, automatic controls, vibration isolation, acoustic treatment and all required auxiliaries, etc., to make for a complete and operable system. Heating: The building shall be provided with all-electric heating via duct-mounted electric heating coils and VAV boxes with electric heating coils. Systems of water-to-water heat recovery coils and circulating pumps shall provide the first stage of temperature control. E. Gallery, Exhibit Areas, Restaurant and Atrium 1. The air conditioning systems for the Gallery Octagon Exhibit Areas, Restaurant and Atrium shall include multiple all-air constant volume air conditioning (A/C) systems. Each A/C system shall consist of supply and return fans that shall be dedicated to a specific floor and zone. The supply air units shall be factory-assembled type arranged in a draw-through configuration. All units for these systems shall be medium pressure, double wall construction. Each air conditioning unit shall include a mixing chamber and shall be provided with pleated prefilters and rigid type final filters, constant volume centrifugal supply and return fans, chilled water cooling coil, heat recovery coil, high-efficiency motors, variable frequency drives, ductwork, piping valves, insulation, acoustic treatment, vibration isolation, dampers, automatic controls, smoke detectors, finned tubular type electric heating coils, electricdriven canister type steam humidifiers (where indicated on the drawings), and all required auxiliaries. a. Main supply air headers and ductwork within Mechanical Equipment Room shall be double-wall, constructed of two layers of galvanized steel sheets in panel construction with minimum 50 mm. thick thermal insulation. b. Supply air and return air from each fan shall be distributed to each floor/zone via dedicated supply and return air ductwork to duct risers within shaft enclosures. Combination fire/smoke dampers shall be provided at each supply air and return floor/takeoff. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-5 HVAC Issued for Construction 1 June 2004 F. c. Where indicated on the drawings, each zone supply duct shall be provided with a heat recovery coil, and electric heating coil . Coils shall be located in the horizontal duct distribution systems located at the Basement Level. A minimum of 5 meters of 304 stainless steel duct, allwelded pan type construction shall be provided at each duct-mounted steam humidifier. All supply air ductwork shall be insulated unless acoustically lined. d. Return air shall be ducted from all areas. Return air shall be through linear extruded aluminum diffusers, and/or architectural return air slots into the hung ceiling plenum or directly into return air ducts when directly connected to risers and/or shafts. All return air ductwork shall be insulated unless acoustically lined. e. All of the air conditioning units shall be provided with air flow monitoring and regulating stations to maintain a fixed quantity of outside air. Outside air intake dampers shall be closed during periods when the Museum is not occupied (i.e., night setback) and supply and return fans shall operate at reduced air flow rates. Education Wing, Auditorium, 5th Floor Administration and Basement Level 1. The air conditioning systems for the Education Wing, Auditorium, 5th Floor Administration, and Basement Level shall each include variable air volume systems consisting of supply and return fans. The supply air systems shall be factoryassembled type arranged in a draw-through configuration. All units for these systems shall be medium pressure, double wall construction. Each air conditioning unit shall include a mixing chamber and shall be provided with pleated prefilters and rigid final filters, variable speed centrifugal supply and return fans, chilled water cooling coil, heat recovery coils, high-efficiency motors, variable frequency drives, ductwork, piping valves, insulation, acoustic treatment, vibration isolation, dampers, automatic controls, smoke detectors, variable air volume boxes with or without electric heating coils, diffusers and all required auxiliaries. a. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC The A/C systems for the Educational Wing and Basement Level shall be headered for operating flexibility. Supply air header in Mechanical Equipment Room and where indicated on the drawings shall be double-wall, constructed of two (2) layers of galvanized steel sheets in panel construction with minimum 50 mm. thick thermal insulation. 15000-6 HVAC Issued for Construction 1 June 2004 b. Supply air and return air to each floor shall be via common supply air and return air ductwork to duct risers within fire-rated shaft enclosures. Combination fire/smoke dampers shall be provided at each floor/takeoff. All supply air ductwork shall be insulated unless acoustically lined. Supply air distribution devices shall be through conventional louver face or perforated ceiling diffusers for office areas and other general occupancy areas and linear extruded aluminum diffusers for all public areas. c. Return air shall be ducted from each area. Return air shall be through air handling light fixtures, ceiling grilles, and/or architectural return air slots into the hung ceiling plenum for the office and similar areas, and ducted for Conference Rooms, Library, and related areas where indicated on the drawings. d. Variable air volume (VAV) boxes with unitary DDC controllers shall be installed to serve every individual space in accordance with the following density: e. G. For each of the above variable air volume boxes, a separate space mounted temperature sensor shall be provided. 2) All variable air volume boxes shall be installed in locations that shall permit full access for service and maintenance. All of the air conditioning units shall be provided with a fixed quantity of outside air. Miscellaneous Spaces (i.e., Mechanical and Electrical Rooms, etc.) 1. H. 1) Mechanical spaces, Electrical Rooms, Elevator Machine Rooms and similar spaces shall be cooled by packaged chilled water, recirculation type, constant volume, low pressure air conditioning units directly installed in the space or adjacent to the space served with minimal ductwork. Smoke Control System for the Building (Typical for Each of the Two (2) Building Zones) 1. A smoke control and extract system shall be provided to control (limit) the migration of smoke from the area of smoke generation to other non-involved areas and to extract the smoke from the area where it is being generated to atmosphere. The smoke control and extract system shall operate in the following manner: Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-7 HVAC Issued for Construction 1 June 2004 a. b. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Upon activation of a manual fire alarm station, area smoke detector, return air duct smoke detector or sprinkler water flow switch within a building zone, the following automatic actions shall occur: 1) The air conditioning supply units and associated return fans serving the affected building zone shall stop and all associated smoke dampers shall close. Kitchen exhaust fan shall continue to operate if running. 2) All remaining systems serving spaces outside the building zone of alarm would continue to operate under normal mode. Although the initial automatic mode of operation of the Smoke Control System shall be as outlined above, the following additional provisions shall be made: 1) The Fire Command Station, located at the entrance level, as approved by the local Fire Brigade, shall be provided with controls such that, at the Fire Department's discretion, a supply fan that had been shut down and dedicated smoke exhaust fans could be started and air supplied and/or extracted to any and all floors served by the affected systems as desired and the associated dampers that had been automatically closed or opened could have their positions reversed. 2) Atrium smoke exhaust fans shall be provided at the highest level of the Gallery Octagon which, when activated, shall extract air from the Atrium at a rate of not less than nine (9) air changes per hour. The extract air shall be drawn from all areas of the Atrium. Makeup air shall be provided at the lowest levels of the Atrium by the activation of openings at the exterior façade, such as doors, windows and in the glass elements in locations that are indicated on the Architectural Drawings. 3) Gallery smoke exhaust fans shall be provided at the highest level of the Gallery Octagon, which when activated shall provide smoke exhaust at a rate of not less than six (6) air changes per hour based on the area of the largest Gallery floor. Floor shutoff fire/smoke dampers shall be 15000-8 HVAC Issued for Construction 1 June 2004 provided at each smoke exhaust floor takeoff from riser. 4) Smoke exhaust shall be provided via the building return air fans serving the Education Wing to provide smoke exhaust at the rate of not less than six (6) air changes per hour based on the area of the largest floor for that building zone. Floor shutoff fire/smoke dampers shall be provided at each smoke exhaust floor takeoff from riser. I. Systems of air transfer, toilet exhaust, Kitchen exhaust, General exhaust, Emergency Generator Room exhaust, Fuel Oil Storage Tank Room exhaust, Garage exhaust, Mechanical Equipment Room exhaust, truck/loading dock exhaust, including all necessary fans, motors and motor controllers, ductwork, heat detectors (installation only), smoke detector elements (furnished and wired under the Electrical Section of the Contract Documents), insulation, vibration isolation, acoustic treatment, and all required auxiliaries. J. Systems of sound traps, cone attenuators, acoustic insulation and all required auxiliaries. K. A system of water treatment for closed chilled water and heat recovery water and open condenser water systems. This Subcontractor shall provide and install all equipment as required by the water treatment vendor. L. Furnish and install all sensors, etc., in piping and ductwork systems, including piping thermowells, nipples, valves, etc. as required. M. Furnish and install all automatically controlled valves and air flow monitors, or any other devices, such as sensor wells and taps specified, which require installation into systems included as work of this Section of the Contract Documents. N. Furnish and install all dampers (including automatic dampers, combination fire/smoke dampers and smoke dampers) with all associated actuator linkages, damper sleeves, etc., to provide complete damper installation. O. Provide a complete system of condensate and pumped condensate to all equipment as indicated on Contract Drawings, including all necessary piping, valves, insulation, condensate receivers with pumps, and all required auxiliaries, etc. P. System of No. 2 fuel oil distribution, including the fuel oil tanks, tank specialties, transfer pumps, piping, valves, hangers, anchors, guides, Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-9 HVAC Issued for Construction 1 June 2004 piping specialties, and all required auxiliaries, etc., serving the emergency generator located at the 3rd Floor of the Education Wing, and the diesel-driven fire pump located at the Basement Level. Q. A system of monoxide exhaust piping, including piping, hangers, guides, supports, insulation (including insulation of exhaust silencers) and installing flexible connections at engine exhaust outlets and exhaust silencer. (Flexible exhaust connections and silencer furnished under the Electrical Section of the Contract Documents.) R. Thermal insulation. S. Provide a dedicated, stand-alone field programmable direct digital automatic temperature and energy management control system to perform the specified control and monitoring functions. The direct digital control system shall receive signals from the smoke detection system, sprinkler system and fire alarm system for fan shutdown. The system shall be interconnected with the Life Safety System provided under another Section. The direct digital and instrumentation subsystems shall be configured as a distributed processing network with a network computer performing the functions of opeator interface. The computer and software required to communicate with the direct digital control subsystems and perform the specified functions shall be provided under this Section. Field-mounted sensors and transmitters for temperature, relative humidity and static pressure inputs to direct digital controllers shall be electronic with a 4-20 mA current output signal. T. Supports and vibration isolation. U. Sand louvers/ filters. V. Furnish and set all sleeves complete with seals and firestops as specified herein and as required by the Authority having jurisdiction for the passage of pipes and ducts through structural steel, decking, masonry and concrete walls and floors and elsewhere as shall be required for the proper protection of each pipe and duct passing through a wall, floor, etc. Coordinate the work with the work of other Trades in order to properly expedite and perform the work. Furnish shop drawings showing the size and location of all required holes through the concrete floors and walls. W. Submit, as soon as practically possible, a list of all required water makeup and drain locations for equipment. X. Floor drains and funnel drains adjacent to the equipment in the various Machine Rooms shall be provided under the Plumbing Section of these Contract Documents. Pipe valved drain lines from all drains, air conditioning units, pumps, etc., to the nearest funnel or floor drain. Valves shall be located at hand-height where possible. Valved water outlets shall be provided in the various Machine Rooms under the Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-10 HVAC Issued for Construction 1 June 2004 Plumbing Section of these Contract Documents and as indicated on the plumbing drawings. Make all final water connections to this equipment from these valved water outlets. Y. Patch or replace all fireproofing if it is damaged or removed during the installation of the heating, ventilating and air conditioning work. Z. Participate in and assist in the operation of the life safety ventilation equipment as required during the performance testing and startup of the fire detection, alarm and communication systems. Refer to Electrical Section of these Contract Documents for additional requirements. AA. Furnish and deliver to the job site all variable speed drives, starters, motor control devices, etc., required in connection with apparatus specified as work under this Section. BB. Furnish and deliver to the job site all access doors in finished construction. CC. Instruments as required for operating and testing the various systems shall be furnished and installed complete as specified herein. DD. Engineer’s personnel shall be fully instructed regarding operation and maintenance of the entire installation and complete printed or typed instruction booklets shall be provided covering maintenance, operation, and adjustment of each piece of equipment. Spare parts lists for each piece of equipment shall be furnished. EE. Provide cutouts in ductwork for installation of smoke detector elements. Smoke detector elements shall be furnished, installed and wired under another Section of the Specifications. The Electrical Section shall obtain the necessary approvals therefor. Closely coordinate the installation of all smoke detector elements with the work of the Electrical Section of the Contract Documents. FF. Testing and balancing of all systems. GG. Complete flushing and chemical treatment and initial water treatment for all water systems. HH. Piping and equipment identification system. II. Complete all tests required by all rules, regulations, etc., of all authorities having jurisdiction and prepare, complete and file all forms, tabulations, plans, etc., pertinent thereto with the referenced authorities, and accomplish such work with personnel of proper caliber, in particular, Professional Engineers, where so required. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-11 HVAC Issued for Construction 1 June 2004 1.05 1.06 JJ. Participate in and provide all labor as required for “off-hour” testing of equipment and systems if required by job conditions or by Authorities having jurisdiction and as required to obtain the “Temporary Certificates of Occupancy (TCO).” KK. Participate in and provide all labor as required for “pull-the-plug” testing of the emergency power and emergency equipment and systems as scheduled and required by the Contractor to ensure proper system operation of fans and other miscellaneous equipment connected to the emergency power system. The required testing shall be at a time scheduled by the Contractor and may be “off hours”. LL. Participate in and provide all labor as required for system commissioning including any time required for a detailed review of the commissioning process as requested by the Engineer. NOTICE TO BIDDERS A. Before submittal of bid, examine all drawings, specifications, addenda, alternates, special conditions, equipment furnished by others and installed by this Subcontractor, and all other bidding documents of all Sections of this project, verify all governing conditions at the site, and become fully informed as to the extent and character of the work required, as well as its relation to other work in the building. Submittal of a bid is an agreement to all requirements of the Contract Documents, and no consideration shall be granted for any claimed misunderstanding thereof. B. Submittal of a bid is deemed a representation by the bidder that it is qualified in all respects properly to perform the work for which it is bidding and has experience with similar work. Bidders are deemed to be aware, on the basis of their background and experience, of materials which may be required in the discharge of their responsibilities, even though unspecified. For example, claims for extras for unspecified shoring or supporting materials shall not be considered if the need for such materials would have been reasonably obvious to bidders skilled and experienced in the work to be done, and the submittal of a bid shall be deemed a waiver of any such claims. SUBCONTRACTOR/ENGINEER A. Throughout these Specifications, the term "this Subcontractor" shall be understood to mean the individual, partnership or corporation to whom has been awarded the Contract for providing the Heating, Ventilating and Air Conditioning Work. B. Throughout these Specifications, the term “Engineer” shall be understood to mean the Assistant Director Building Engineering Department, in the Ministry of Municipal Affairs and Agriculture, or any other person approved by the government. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-12 HVAC Issued for Construction 1 June 2004 1.07 1.08 GENERAL A. Execute the work in the best and most thorough manner and to the satisfaction of the Engineer, who shall jointly interpret the meaning of the drawings and specifications and shall have the power to reject any work and materials which, in their judgment, are not in full accordance therewith. B. Make every effort to furnish all equipment of any equipment type (such as motors, motor controls, pumps, valves, etc.) from one manufacturer. C. Any equipment or material substitution that is constructed to a different national standard than that specified or implied shall be accompanied by full supporting technical data confirming that the alternative standards meet or exceed the specified standard. It is the intent of this Specification to encourage bidding of acceptable equipment; however, the burden of proof concerning acceptability is on the alternative product or manufacturer. D. The drawings show the various piping and ductwork systems schematically. No added compensation shall be permitted for variations due to field conditions, and final coordination by the various Contractors. E. All information contained within this Specification is intended to set forth the minimum requirements for this project. In the event local and governmental Codes, technical references, ordinances, guidelines and regulations (as hereinafter discussed) exceed the equipment and/or products that are specified herein, this Subcontractor shall provide, at no additional cost to the Engineer, the better quality equipment and products (and any associated labor) accordingly. COORDINATION A. Certain materials shall be furnished, installed, or furnished and installed, under other Sections of the Contract Documents. Examine the Contract Documents (i.e., all work to be performed by other Trades) to ascertain these requirements. B. Carefully check space requirements with other Sections of the Contract Documents to insure that all material can be installed in the spaces allotted thereto. Finished suspended ceiling elevations are indicated on the architectural drawings. C. Transmit information required for work to be provided under other Sections (such as fresh water connections, foundations, electric wiring, access doors, and the like) in ample time for installation. D. Wherever work interconnects with work of other Sections, coordinate this work to insure that other Sections are advised of the information Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-13 HVAC Issued for Construction 1 June 2004 necessary so that they may properly install all the necessary connections and equipment. Identify all work items (valves, dampers, coils, motor control centers, etc.) in an approved manner in order that the work of other Sections may know where to install access doors and panels. 1.09 E. Caution workers both verbally and in writing as to the dangers involved in doing work within or adjacent to electrical closets on various floors, the Mechanical Rooms, Switchboard Rooms, and Transformer Rooms due to dangers caused by presence of high voltages and currents in these spaces. F. Consult with other Sections so that, wherever possible, motors, motor controls, fuses, pumps and valves are of the same manufacture. G. Furnish and set all sleeves for passage of pipes and conduits through structural masonry and concrete walls and floors and elsewhere as shall be required for the proper protection of each pipe and conduit passing through building surfaces. Coordinate this work with the other Trades in order to properly expedite and perform this work. H. Provide required supports and hangers for piping, conduit and equipment, so that loading shall not exceed allowable loadings of structure. Submittal of a bid shall be deemed a representation that such bid has included allowable loadings and has included in estimates the costs associated in furnishing required supports. I. Due to the type of the installation, a fixed sequence of operation is required to properly install the complete systems. It shall be the responsibility of this Section to coordinate, protect and schedule its work with other Sections in accordance with the construction sequence. J. In advance of shop drawing submission for Consulting Engineer's review, sheet metal shop drawings, in addition to those hereinafter specified, shall be prepared as a basis for coordination with all other Trades. Composite Drawings shall be prepared as detailed in Article 1.09 hereinbelow. COMPOSITE DRAWINGS A. The coordination of the Mechanical and Electrical Trades (i.e., heating, ventilating and air conditioning, plumbing, electrical, vertical transportation and fire protection work) with each other and with the interfaced Structural and Architectural Trades shall be accomplished by an "overlay" process by which the final location of the various trades work shall be overlaid onto reproducible Composite Drawings that originate with the Heating, Ventilating and Air Conditioning Subcontractor. This overlay process shall take place to meet the time schedule of the project as set forth by the Engineer or his designated representatives. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-14 HVAC Issued for Construction 1 June 2004 B. Coordination of work shall include, without additional cost to the Owner, the preparations of the composite drawing by each Subcontractor, as well as the necessary re-routing and minor relocation of work to accommodate the detailed job requirement and to clear architectural features and building structural elements. The Composite Drawings shall be on mylar at a scale sufficient to clearly describe all conditions, but not less than a scale of 1:50. The background mylar shall be prepared by the Heating, Ventilating and Air Conditioning Subcontractor at no additional cost to the Owner. It shall be based on the erection drawings as prepared by the Structural Steel and Concrete Contractors. The base drawings, after being prepared by the Heating, Ventilating and Air Conditioning Subcontractor, shall then sequentially have the work of the Plumbing Subcontractor, Electrical Subcontractor and Fire Protection Subcontractor added by the distribution of the drawings to these Subcontractors, who shall add their respective work. C. In preparing the Composite Drawings, minor changes in duct, pipe or conduit routings that do not affect the intended function may be made as required to avoid space conflicts, when mutually agreed, but items may not be resized or exposed items relocated without the Consulting Engineer's approval. No changes shall be made in any wall or chase locations, ceiling heights, door swings or locations, window or other openings, or other features affecting the function or aesthetic effect of the building. The drawing shall indicate all ductwork, grilles, registers, diffusers, dampers, terminal units, coils, smoke detectors, piping, valves, sprinkler heads, smoke detectors, light fixtures, access requirements, access doors, etc. The drawing shall permit the installation of lights and diffusers at any location on any office storey without relocating of horizontal duct runs or sprinkler piping. If conflicts or interference require interpretations of the Contract Documents, the Consulting Engineer's clarifications shall be obtained. Each Trade shall use a different color pencil for work on the coordination drawing. D. After any conflicts or interferences are resolved, the composite mylar drawings shall then be signed and dated by each of the Subcontractors, indicating their awareness of the agreement with the indicated routings and layouts and their interrelationship with the adjoining or contiguous work of all Contracts. The drawings shall be maintained in a current state by the Subcontractors. Thereafter, no unauthorized deviations shall be permitted. E. The original composite mylar drawings signed by all Subcontractors shall be retained by the Subcontractor and be available for examination and reference by the Owner, Engineer and Consulting Engineer at any time. Furthermore, copies of these originals shall be provided at any time if requested by the Engineer. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-15 HVAC Issued for Construction 1 June 2004 F. 1.10 The Composite Drawings shall not substitute for a Subcontractor's shop drawings for the respective Trades which shall be submitted to the Engineer. The shop drawings, required by Article 1.11, shall accurately record the agreed Composite Drawings as detailed for the respective Trade and shall only be submitted for approval after the completion of these Composite Drawings. GENERAL CONSTRUCTION DRAWINGS A. This Subcontractor shall produce General Construction Drawings showing all bases, holes, openings, chases and other general construction work requirements associated with the work of his Trade. The execution of the general construction work shall be by others. B. Any preliminary general construction work and structural information already provided by the Consulting Engineer shall be confirmed by this Subcontractor and incorporated into his own General Construction Drawings. C. General Construction Work Drawings shall be fully detailed and dimensioned and this Subcontractor shall be solely responsible for their accuracy. D. The drawings shall be fully coordinated with all other services and the structure. This Subcontractor shall work in conjunction with other Subcontractors to ensure that the drawings are fully coordinated and that other Subcontractors’ works have been taken fully into account. E. The submission of General Construction Drawings shall be carried out strictly in accordance with a detailed project schedule prepared by the Engineer or the Engineer’s Representative to eliminate any supplemental work by the Contractor. F. If in the event of any general construction work being omitted, carried out incorrectly, or out of sequence, due to inaccuracies in the General Construction Drawings or because they have not been provided in accordance with the agreed project schedule, this Subcontractor shall be held responsible for the cost of all necessary remedial works. G. General Construction Work Drawings shall be subject to the same submission, commenting and issue procedures as detailed in this Specification for the Shop Drawings. H. All General Construction Work Drawings used by site personnel shall bear a Consultant's review stamp. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-16 HVAC Issued for Construction 1 June 2004 1.11 SHOP DRAWINGS AND HVAC CONSULTING ENGINEER'S REVIEW A. Before the installation of any equipment or material by this Subcontractor, full Shop Drawings, as detailed hereinbelow, shall be submitted for approval by the Consulting Engineer. All Shop Drawings shall be submitted by the process approved by the Engineer. The Shop Drawings shall be submitted in sets: one in English, and one in Arabic. B. The Consulting Engineer shall review shop drawings and samples for conformance with the design concept of the project and the information contained in the Contract Documents. The Consulting Engineer's review of shop drawings and samples is only for the convenience of the Engineer in following the work and does not relieve the Subcontractor of responsibility for deviations from the requirements of the Contract Documents. The Consulting Engineer's review shall not be construed as a complete or detailed check of the work submitted, nor shall it relieve the Subcontractor of responsibility for errors of any sort in the shop drawings and samples, or from the necessity of furnishing any work required by the Contract Documents which may have been omitted from the shop drawing submittals. The review of a separate item shall not indicate review of the complete assembly in which it functions. Nothing in the Consulting Engineer's review of shop drawings and samples shall be considered as authorizing 1) a departure from Contract Documents or Specifications, or 2) additional cost to the Engineer, or 3) increased time for completion of the work. C. The Consulting Engineer shall review shop drawings and samples with reasonable promptness and shall return them to the Subcontractor stamped to indicate the appropriate action as follows: 1. "NO EXCEPTIONS TAKEN" means that fabrication, manufacture or construction may proceed providing the submittal complies with the Contract Documents. 2. "MAKE CORRECTIONS NOTED" means that fabrication, manufacture or construction may proceed providing the submittal complies with the Consulting Engineer's notations and the Contract Documents. A copy of the corrected submittal shall be returned to the Consulting Engineer for record. If, for any reason, the Subcontractor cannot comply with the notations, the Subcontractor shall resubmit as described for submittals stamped "REVISE AND RESUBMIT". 3. "REVISE AND RESUBMIT" means that the Subcontractor must comply with the Consulting Engineer's notations and resubmit before fabrication, manufacture or construction may proceed. Submittals stamped in this manner are not permitted on the job site. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-17 HVAC Issued for Construction 1 June 2004 4. D. "REJECTED" means that the submittal does not comply with the Contract Documents and that fabrication, manufacture or construction shall not proceed. Submittals stamped in this manner are not permitted on the job site. All shop drawings and samples shall be identified as follows: 1. Date of submittal. 2. Title of project. 3. Name of Subcontractor and date of his approval. 4. Name of Subcontractor or supplier and date of submittal to Subcontractor. 5. Number of submission. 6. Any qualification, departure or deviation from the requirements of the Contract. 7. Reference Local and Governmental Departments and references to specific standards, where required. 8. Such additional information as may be required by the Specifications for the particular material being furnished. E. Consulting Engineer's review is for general compliance with the design concept and Contract Documents. Markings or comments or the lack thereof shall not be construed as relieving the Subcontractor from compliance with the project plans and Specifications. The Subcontractor remains solely responsible for details and accuracy, for confirming and correlating all quantities and dimensions, for selecting fabrication processes, for techniques of construction, for performing his work in a safe manner, and for coordinating his work with that of other Trades. F. The term "shop drawings" shall include layout, detail, and assembly drawings, diagrams, schedules, catalogue sheets, printed descriptive matter, and tabular and graphical presentations of operating and performance data that describe work required by the Contract Documents. G. No part of the work shall be started in the shop or in the field until the Consulting Engineer has reviewed the shop drawings and samples for that portion of the work. Thereafter, the work shall be executed in accordance with the Contract Documents and the indicated status of the reviewed shop drawing. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-18 HVAC Issued for Construction 1 June 2004 H. Shop drawings and samples shall be submitted for review sufficiently in advance of the scheduled start of the work in the shop or in the field to allow ample time, in consideration of the number and complexity of the drawings in the submittal, for the Consulting Engineer to make an orderly review. No extension of the time to complete the work shall be granted to the Subcontractor by reason of his failure in this respect. I. The Subcontractor shall carefully check shop drawings and samples, including those received by him from Subcontractors and material men, for accuracy, completeness of required information and conformance with the Contract Documents. Shop drawings found to be inaccurate, incomplete or not in conformance with the Contract Documents shall be corrected before being submitted to the Consulting Engineer for review. J. Each submitted shop drawing shall bear the Subcontractor's stamped and signed certification that the work has been checked for all related job conditions, for maintenance of architectural conditions, and coordinated with the shop drawings of other affected trades for interrelated work, as required for the proper and complete performance of the work. No shop drawing submittal shall be reviewed without this certification. K. Each shop drawing and sample submitted for review shall be accompanied by a letter of transmittal, and shall be identified by the project title, Subcontractor's name, and a reference to the related part of the Contract Documents. L. Shop drawings for manufactured material and equipment shall include model numbers, dimension drawings, operating weights, material specifications, operating features and controls, wiring diagrams, performance characteristics, service procedures, including clearance requirements for maintenance work, and conformance to specified codes and code ratings. Note that in addition to these requirements, other specific submittal data, and forms of data submission, are required by the Contract Documents for particular items of equipment and material. M. Shop drawings for Equipment Rooms, and for piping and similar distribution services shall show by dimension the exact size and location of each element of the system in both the horizontal and vertical plane, as well as relationship to the building structure, architectural construction, equipment, and the work of other Trades. Shop drawings shall clearly show where doors providing access to valves, cleanouts and other devices shall be shall be required in finished construction. Pads, foundations, anchorages, supports and attachments to the building structure where required for the installation of the work shall be shown in layout and detail with sizes, dimensions, materials and methods of construction noted. The work described in any shop drawing submission shall he carefully checked by this Subcontractor for all clearances (including those required for maintenance and servicing), field conditions, maintenance of architectural conditions and proper coordination with all Trades on the job. Each submitted shop drawing Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-19 HVAC Issued for Construction 1 June 2004 shall include a certification by the Contractor that all related job conditions have been checked and that no conflict exists. No shop drawing submission shall be reviewed without such certification. N. Samples shall be identical in all respects to the material which is to be installed or applied in the execution of the work, and shall be of sufficient size or quantity to permit proper evaluation and review. Manufacturer's descriptive labels and printed application instructions which are normally attached to the material or its packaging shall be furnished with the sample. Samples shall be submitted for review when requested by the Consulting Engineer. O. Within a period of time as specified by the Engineer after award of the Contract, the Subcontractor shall submit for the Consulting Engineer’s review, a list of the manufacturers and Subcontractors whose products and services he proposes to use for the work. Proposed substitutions for material and equipment required by the Contract Documents shall be submitted to the Consulting Engineer for review during this period. Submittals proposing or requesting substitutions shall be expressly identified as such in a letter of transmittal, with the reasons for requesting the substitution stated. Submittals for this purpose shall be complete in every respect, shall conform to all the information requirements for shop drawing and sample submittals, and shall include, at no cost to the Owner, the necessary revisions to other related work required by the Contract Documents. The judgment of the Consulting Engineer with respect to the adequacy and acceptability of a proposed substitution shall be final and binding on the Subcontractor, and shall not be subject to question in any other place. After the expiration of this period, substitutions for material or equipment shall not be proposed or requested in shop drawing and sample submittals, and the Subcontractor shall be required to execute the work in accordance with the provisions of the Contract Documents. P. After award of the Contract and before submittal of any shop drawings, the Subcontractor shall submit a schedule listing all shop drawings and samples with the projected date that each item shall be submitted to the Consulting Engineer for review. Q. Submit detailed shop layout drawings for each floor of the project, including all the Mechanical Equipment Rooms, showing equipment and piping work. All drawings shall be submitted at a scale of not less than 1:50, with Mechanical Equipment Rooms, core details and sections at 1:20 scale. Piping shop drawings shall also indicate the point loading and spacing of each hanger and the method of support. Drawings shall include full coordinated floor plans and risers. In addition, required detail drawings, such as anchor and guide details, coil and equipment connections, radiation piping within enclosures, fan coil units within Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-20 HVAC Issued for Construction 1 June 2004 enclosures, built-up casing details, plenum details, etc., shall be submitted. R. Submit manufacturer's data or shop drawings of the following: Pumps Packaged Air Conditioning Units Equipment Foundations Refrigeration Machines Cooling Towers Motors Motor Starters and Control Centers Variable Frequency Drives Fans Air Filters Water Treatment Equipment Variable Air Volume Boxes Constant Air Volume Boxes Heat Recovery Coils Automatic Temperature Controls Sound Traps Panelboards Instruments S. Names, sizes, catalogue numbers and/or samples of the following specialties shall also be submitted for review, unless otherwise directed: Strainers Valves Check Valves Hangers and Inserts Sleeves and Escutcheons Valve Tags Air Vent Valves Insulation T. Cabinet Air Supply Units Electric Heating Coils Cooling Coils (Chilled Water) Fuel Oil Tank and Specialties Fuel Oil Pumps and Specialties Schedule of Piping Materials, Fittings, Valves, Hangers, Insulation Expansion Joints Roof Fans Sheet Metal Construction and Fabrication Details (Standards) Expansion (Diaphragm) Tanks Grilles, Registers and Diffusers Combination Fire/Smoke dampers Smoke Dampers Automatic Louver Dampers Fire Dampers Vibration Isolation Devices Seismic Restraints Safety Valves Air Diffusers Relief Valves Registers/Grilles Thermostats Sheet Metal Flexible Connections Acoustic Materials and Sound Traps Steam Traps Automatic temperature control submittals shall include the following: 1. Specification sheets for electronic sensors, transmitters, controllers, actuators, relays, switches, and miscellaneous control devices. 2. Schedule and specification sheets for control dampers, including material and construction details, duct size, damper size, maximum design air velocity, damper rated velocity, leakage and pressure drop test data, as well as damper free area. The schedule shall indicate the closing torque required for each damper to attain the required maximum leakage rate at the Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-21 HVAC Issued for Construction 1 June 2004 specified static pressure differential across the damper. Actuator sizing calculations and configuration shall be submitted. Dampers shall be sized based on approved sheet metal shop drawings. 3. Schedule of automatic control valves and motorized block valves with specification sheets for each valve. The schedule shall list body pressure rating, close-off pressure rating, Kv factor, pressure drop at specified capacity, rangeability, and valve flow characteristics. Valves shall be sized based on approved equipment shop drawings, not mechanical schedules. 4. Dimension and specification sheets for field mounted direct digital control panels. 5. Control diagrams for each system with written sequence of operation, and with control devices and wiring identified with tag numbers. 6. Scaled drawings of local control panel front face panel arrangement showing location of instruments and control devices. 7. Panel nameplate details with lettering size, plate size and legend schedule. 8. Ladder type electrical diagrams for each control system with terminal connections identified by number and location. 9. Symbol and abbreviation list for electrical control diagrams. 10. Specification sheets and dimension cuts for the network computer and peripherals. 11. Layout drawing and space requirements for network computer and peripheral I/O equipment. 12. Complete listing and description of program routines resident in direct digital control units. 13. Complete description of operating system software for the network computer and application program software provided for the system. 14. Control algorithms in flow chart format which define control modes for each system. 15. Panelboard from which power shall be taken, along with total power to be taken from each panelboard. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-22 HVAC Issued for Construction 1 June 2004 16. Complete software (DDC unit) point identification code. 17. Sample of network computer advisory messages, printouts, logging and alarm formats. 18. Drawings of system graphics showing monitored points. 19. Application Programs: Include specific programming for each system, calculation of parameters, method of field tuning, and integration into DDC control sequences. Specifically include: 20. a. Detailed description of how Subcontractor’s program meets application program specified. b. Detailed flow chart of program complete with line-byline section comments. c. List of remote points utilized for each program. d. History of development and past use, if any, of program. e. Explanation of how each parameter value in program is determined; i.e., measurement, “look-up table,” mathematical approximations to empirical curves, internal computation in program. Description of system operation under failure conditions. a. 1.12 Include procedures to be taken during failure mode to minimize impact. 21. Architectural floor plans indicating proposed locations of all wall-mounted devices (i.e., DDC units, control panels, sensors, thermostats, etc.). 22. Mechanical piping shop drawings indicating proposed locations of all temperature, flow and pressure transmitters. RECORD DRAWINGS A. During the progress of the work, make a careful record of all changes by which the actual installation differs from that indicated on the Contract Drawings. B. Upon completion of the installation, furnish two (2) copies of the drawing files in AutoCAD 2002 format on “zip drive” diskettes, and two complete sets of as-built drawings, one of which shall be furnished on mylar transparencies and one of which shall be furnished on paper. These drawings shall be submitted to the Consulting Engineers for approval. After approval they shall become the property of the Engineer. Final payment shall be withheld until receipt of the approved record drawings. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-23 HVAC Issued for Construction 1 June 2004 C. 1.13 1.14 Include the cost of furnishing above prints and preparing these record drawings. CODES AND PERMITS A. Install all work in full accordance with the requirements of all local and governmental departments having jurisdiction over these matters, as well as with any applicable technical references and requirements, ordinances, guidelines and regulations; and all applicable British Standards and Codes. Secure and pay for necessary approvals, permits, inspections, carting, legal dumping, etc., and deliver the official records of the granting of permits to the Engineer without additional costs. B. Pay royalties or fees required in connection with the use of patented devices, or systems, and save the Owner, Engineer and the Consulting Engineers harmless from any claims or lawsuits arising from such use and indemnify each thereof against attorneys' fees in connection therewith. C. Provide signs required by the municipal authorities. PROTECTIVE PAINTING A. Provide protective painting as herein specified. B. Provide a heavy field coat of black asphaltum paint on all steel pipe, cradles, vibration isolating mounts, and the like, that shall be encased or partially encased in building construction, set in cement or fill, before items are built into the general construction. C. Coat interior of each outdoor air chamber with two coats of odorless, rust resisting, nonscaling paint. D. Coat interior of ducts at diffusers and register boxes with two coats of matt black paint, to a dull finish. E. All pumps, motors, fans and all other factory manufactured and assembled apparatus shall be factory coated with one coat of primer and one coat of machinery enamel, and after installation shall be cleaned and touched up to repair any damage incurred during construction. F. All finished painting, except as noted above, including the painting of the various piping systems, shall be done under other Sections of the Specifications, except as otherwise described herein. In addition, the above protection shall be done as a minimum amount of work. G. Tag electrical wiring with clip-sleeve type, nonmetallic wire markers, or as approved. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-24 HVAC Issued for Construction 1 June 2004 1.15 H. Furnish and install a screw-fastened type engraved phenolic nameplate with 6 mm high white lettering on black background, clearly indicating the function, on cabinets, panels, and electrical junction boxes. I. Furnish lists of circuits utilized in each panelboard. Lists shall include panel name, circuit number, C.B. rating, load served, and wattage. IDENTIFICATION OF SYSTEMS A. Provide three sets of charts or diagrams, on mylar, showing outline plans of structures and essential features of the several systems, including all piping, ducts, equipment, valves, dampers and controls. B. All valves, dampers, and controls shall be designated by distinguishing numbers on the charts or diagrams. Provide stamped brass or approved embossed plastic tags for all designated items with numbers corresponding to those on the charts. The nomenclature to be used on these tags shall be submitted to the Consulting Engineer for approval. C. The tags shall be not less than 50 mm. in diameter with depressed black numbers of 13 mm. height, prefixed by the letters "HVAC". They shall be fastened to valves and controls with approved brass chains and hooks. D. Furnish to the Engineer's representative complete valve tag schedules, printed on mylar, properly mounted in three binders. AutoCAD 2002 format (.dwg) drawings of valve schedules shall also be turned over to the Engineer for his use. Furnish schematic flow charts with corresponding valve numbers noted on charts in AutoCAD 2000 format (.dwg). E. Valve tag schedules shall show valve location by floor and nearest column number and shall also show the valve size and service. F. Piping identification shall be in conformance with the following: 1. Provide and affix approved adhesive bands identifying the service, by system and zone, and direction of flow to the various piping systems. Piping shall be painted under another Section of the Specifications. Such bands shall be provided in all occupied and unoccupied rooms as well as in all the other spaces (such as shafts) in which piping may be viewed. A set of such bands shall be affixed to each pipe not less frequently than every 12 m. and there shall be at least one set of identifying bands per pipe in each space requiring identifying bands. Identifying bands shall also be provided adjacent to each valve. Valves at equipment and pumps do not require separate identification. 2. Each set shall consist of one band on which the name of the service is printed in black letters not less than 50 mm. for 75 mm. pipe and larger, 25 mm. high for pipe 65 mm. and smaller Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-25 HVAC Issued for Construction 1 June 2004 and one band on which is printed a black directional arrow. Bands shall be applied where they can be easily read and with their long dimension parallel to the axis of the pipe. Bands shall have backgrounds of different colors for the various service groups. Colors shall conform to BS 1710. 1.16 G. A schedule of symbols shall be stenciled on ducts and fans for identification; the stenciling shall be done by this Subcontractor. H. Tag electrical wiring with clip-sleeve type, nonmetallic wire markers, or as approved. I. Furnish and install a screw-fastened type engraved phenolic nameplate with 6 mm high white lettering on black background, clearly indicating the function, on cabinets, panels, and electrical junction boxes. J. Furnish lists of circuits utilized in each panelboard. Lists shall include panel name, circuit number, C.B. rating, load served, and wattage. TOOLS A. 1.17 All special tools needed for proper operation, adjustment and maintenance of equipment shall be delivered to the Engineer. SLEEVES A. This Subcontractor shall be responsible for the timely placing of sleeves for all piping passing through walls, partitions, beams, floors, and roofs, while the same are under construction. B. If holes and/or sleeves are not properly installed and cutting and patching becomes necessary, it shall be done at no additional expense to the Owner. The Subcontractor shall undertake no cutting or patching without first securing the Engineer's written approval. C. All unused sleeves shall be sealed with firestop devices and systems to maintain the fire rating of the construction penetrated. D. Provide sleeves for all pipes and ducts passing through floors, walls, partitions and roofs. 1. Sleeves through concrete walls and exposed pipes and conduits penetrating floors: 10 mm. track steel pipe. 2. Sleeves within furred out enclosures in floors, partitions, through block walls: 1.3 mm. galvanized sheet metal. 3. Provide waterproof sleeves in foundation walls and in concrete pits with anchor flanges. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-26 HVAC Issued for Construction 1 June 2004 E. F. Provide sleeves with an i.d. at least 12 mm. greater than outside of pipe served, including pipe insulation which must be continuous through sleeve. 1. Finish sleeves flush with underside of slab and 25 mm. above finished floor (100 mm. at Mechanical Rooms). 2. Space between pipes and sleeves in exterior walls, foundation walls and pits shall be equipped with "Link Seal" waterproof assemblies. Where piping penetrates walls (other than foundation walls), partitions, floor slabs, etc., which are of nonrated construction, the space between piping and sleeve shall be packed with mineral wool. 3. Where pipes penetrate fire or smoke rated walls, partitions, floor slabs, etc., the space between sleeves and pipe insulation or the pipe of uninsulated service shall be caulked with a UL listed, intumescent type, firestop system. Space between sleeve and pipe/pipe insulation shall be sized in accordance with the manufacturer's requirements for pipe size and damming material thickness for the type of rated construction for which the system is to be used. The firestop systems shall be as manufactured by 3M Fire Protection Products, or as approved. Set sleeves as construction progresses and secure in place during pouring of concrete. 1. Where cellular steel flooring is installed, furnish and locate sleeves, cut holes through deck, reinforce deck, and set sleeves. Coordinate sleeve locations with the work of other Trades, including flooring and electrical distribution. Submit drawings showing location of holes and proposed reinforcing and obtain Engineer's approval before proceeding with installation. G. Do not support pipes by resting clamps on sleeves. Clamps must extend beyond sleeve and be supported outboard of sleeve in an approved manner. H. Provide waterproof type pipe sleeves, Zurn Z-197, with galvanized 10 mm. thick pipe extensions where penetrating membrane waterproofed floors. I. For pipes passing through roofs, provide roof couplings (Zurn Z-196-3) at suitable level above roof to terminate flashings. J. Wherever pipes are exposed and pass through walls, floors, partitions or ceilings, fit them with chromium plated cast brass escutcheons held in place with set screws. Fit escutcheons snug over insulation, secure in Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-27 HVAC Issued for Construction 1 June 2004 place. Take special care to protect the escutcheons during the course of construction. K. 1.18 1.19 Where space for future pipes is required, provide sleeves and fill with lightweight concrete. OPERATING AND MAINTENANCE INSTRUCTIONS A. Three sets of operating and maintenance instruction manuals, covering completely equipment starting sequences, operation, maintenance, automatic controls, pumps, and air compressors, and listing of all spare parts, shall be furnished to Engineer in Arabic only. Three sets of lubricating charts and manuals for each item of equipment shall be furnished to Engineer. Two additional sets of the above shall be furnished: one in English, and one in Arabic. B. Furnish a list of manufacturers (with names of local representatives) in order to expedite ordering of replacement parts. C. This Subcontractor shall provide operating and maintenance instruction for not more than eight building operators with personal on-the-job instruction by an engineer representing the Subcontractor for 8 hours. This instruction shall be scheduled at time(s) convenient to the Engineer's personnel. Instruction shall cover all equipment and systems provided by this Subcontractor. The number of hours is a minimum requirement. Where additional hours are specified in other paragraphs of this Specification, those hours shall be additive to the minimum above. Instruction shall be comprised of both classroom type and actual handson operating experience. Number of hours in each category to be arranged with the Engineer directly. All travel expenses and accommodations shall be included for the manufacturer’s representatives. REPAIR AND MAINTENANCE PARTS A. Furnish each item listed below. List of parts included in manufacturer's standard export kit shall be submitted for approval. Where no standard export kit exists, the Subcontractor shall submit a suggested list of parts for approval. List of parts shall include any manufacturer's model numbers, serial numbers, parts numbers, or any other identification required for the ordering of spare parts. Equipment Parts Required Air Conditioning (Central Refrigeration Plant) Manufacturer's export kit; 1 complete charge of refrigerant and oil. Pumps Manufacturer's export kit. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-28 HVAC Issued for Construction 1 June 2004 B. 1.20 1 set of belts for each unit, 1 adjustable sheave for each unit; 20% filter replacement. Air Conditioning Control Manufacturer's export kit; 10% thermostat replacement. All Motors Manufacturer's export kit. All Variable Speed Drives Manufacturers export kit. All Starters, Contactors and Relays 2 sets contacts, each type; 2 magnetic coils, each type; 2% heater replacement; 10% pilot light replacement. All Hand-Operated Shutoff Valves 10% complete valves, each size and type; 20% complete repacking, reseating kits, each type. Insulation (Pipe and Duct) 5% replacement, each type and size. Approved kits and listed parts shall be turned over to the Engineer in new condition and a receipt obtained for same. A copy of the receipt shall be submitted for record. SUBCONTRACTS A. 1.21 Air Conditioning Units Where Contract Documents require manufacturers' services, and wherever the staff of the Trade performing the work of this Section cannot adequately perform such services, this Trade shall stipulate such performance in its contracts with its Sub-Subcontractors, vendors, manufacturers, and the like, or else subsequently pay them any additional fees required therefor. ENGINEERING REFERENCE POINTS A. The Contractor shall provide bench marks, monuments, and other reference points on the job which shall be available for this Subcontractor’s use. B. Maintain all existing bench marks, monuments and other reference points and perform all field engineering required to insure that work under this Section shall conform with grades, elevations and lines required. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-29 HVAC Issued for Construction 1 June 2004 1.22 1.23 1.24 GUARANTEE A. Submit a single guarantee stating that all portions of the work are in accordance with Contract requirements. Guarantee all work against faulty and improper material and workmanship for a period of one year from date of final acceptance by the Engineer, except that where guarantees or warranties for longer terms are specified herein, such longer term shall apply. At no additional cost to Engineer, within 24 hours after notification, correct any deficiencies which occur during the guarantee period, all to the satisfaction of the Engineer and Consulting Engineer. This Subcontractor shall require similar guarantees from his Sub-subcontractors. B. Be responsible for all leaks in all pipes for a period of one year from date of acceptance of work under this Contract. Repair at no cost to Engineer all such leaks which occur within 24 hours notice thereof by the Engineer. Leaks which occur prior to the completion of this Contract shall be repaired at once. Be responsible for any damage caused by such leaks and repair thereof and reimburse Owner for all expense incurred thereby. This Subcontractor indemnifies the Owner, the Consulting Engineer and the Contractor against loss, liability, damage or expense, including reasonable attorneys' fees, in connection with any claim resulting from such leaks which may be asserted by tenants or any other third person. CUTTING AND PATCHING A. Do any cutting required for the passage or installation of pipes, supports, and the like, provided under this Section. B. Furnish to the Contractor necessary information so that openings for this work can be built into the floors and walls in time. Such cooperation is required to keep cutting of walls and floors to a minimum. C. Set drains and sleeves for pipes accurately before concrete floors are poured, or set boxes on the forms to leave openings in the floors and subsequently set required sleeves in the openings. D. Should Subcontractor neglect to perform preliminary work, and should cutting be required in order to install equipment, the expense of this cutting and restoring of surfaces to their original condition shall be borne by this Subcontractor. E. All finished patching shall be done by this Subcontractor, with finishes to matching existing, to the Engineer's satisfaction. RUBBISH REMOVAL A. At conclusion of each day's work clean up and stockpile on site, at location designated by the Contractor, all rubbish, debris and trash, Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-30 HVAC Issued for Construction 1 June 2004 which may have accumulated during the day as a result of work of this Subcontractor and of his presence on the job. This Subcontractor shall then remove stockpiled rubbish. B. 1.25 Sidewalks and streets adjoining the property shall be kept broom clean and free of debris, rubbish, trash and obstructions of any kind caused by work of this Subcontractor, which shall affect the condition and safety of streets, walks, utilities and property. PROTECTION A. Be responsible for work and equipment until finally inspected, tested and accepted. Materials and equipment shall be carefully stored which are not immediately installed after delivery to site. Close exposed parts of the work with temporary covers or plugs during construction to prevent entry of moisture or obstructing materials. B. Protect the work and material of others from damage that might be caused by work and make good any damage thus caused. PART 2 - PRODUCTS 2.01 APPROVED MANUFACTURERS A. Furnish all major items of equipment and materials as made by the manufacturers listed herein. B. Being listed herein as an approved manufacturer does not permit the manufacturer to provide standard manufactured equipment which does not comply with the performance and/or physical characteristic requirements of the contract documents. C. All substitutions must be included in the contractors base bid, and must be accompanied by a letter of equivalency certifying the products equivalency in all performance and physical characteristics to the products listed herein. The proposed substitutions shall be all inclusive of all cost and physical implications throughout the project. Under no circumstances should the substitution result in added cost to the project. Project specifications/documents shall not be revised to reflect the substitution should the substitution be approved. Access Doors Finished Construction Karp Mil-Cor Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-31 HVAC Issued for Construction 1 June 2004 Sheet Metal Duct Mate Flexmaster TDC/TDF Access Door Hardware (Sheet Metal) Duro Dyne Ventlok Air Filters American Air Filter Continental Farr Flanders Air Handling Units Factory-Assembled Chilled Water Air Conditioning Units Buffalo Forge - U.S.A. Carrier - U.S.A. McQuay - U.S.A. Trane - U.S.A. York - U.S.A. Packaged Chilled Water Air Conditioning Units (Electric Service Rooms, Telephone Equipment Rooms, Elevator Machine Rooms, Mechanical Rooms) Air Flow - U.S.A. Air Technologies Systems - U.S.A. Data Aire - U.S.A. HiRoss - U.S.A. Liebert - U.S.A. Stultz - U.S.A. Packaged Chilled Water Air Conditioning Units (Ceiling-Mounted) (Electric Service Rooms, Telephone Equipment Rooms, Elevator Machine Rooms, Mechanical Rooms) Air Flow - U.S.A. Air Technology Systems - U.S.A. Enviro-Tec - U.S.A. HiRoss - U.S.A. Liebert - U.S.A. Skil-aire - U.S.A. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-32 HVAC Issued for Construction 1 June 2004 Air Outlets Air Concepts Air Devices Anemostat Enviro-Air Krueger Nailor Industries Titus Air Volume Regulators Anemostat - Doha Environmental Technology, Inc. - USA Krueger Nailor Industries Titus Trok - UK Automatic Temperature Controls Honeywell Excel 5000 - USA Johnson Controls Metasys - USA Siemens (Landis and Staefa) System 600 (Switzerland/UK) Invensys Climate Control (Satchwell) Sigma - UK Breechings and Flues Ambco Industries Metal-Fab The Schebler Co. Centrifugal Chillers Carrier - U.S.A. McQuay - U.S.A. Trane - U.S.A. York - U.S.A. Condensate Pumps Cold Condensate Federal Hartell Little Giant Shipco Watsco Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-33 HVAC Issued for Construction 1 June 2004 Hot Condensate (Low Pressure Steam Return) Bell & Gossett Domestic Shipco Skidmore Weinman Cooling/Heating/Heat Recovery Coils Chilled Water/Heat Recovery Aerofin - U.S.A. Carrier - U.S.A. Heat Craft - U.S.A. Marlo - U.S.A. McQuay - U.S.A. Temtrol - U.S.A. Trane - U.S.A. York - U.S.A. Electric Heating Brasch - U.S.A. Chromalux - U.S.A. Electric Heaters Inc - U.S.A.. Electromode - U.S.A. Indeeco - U.S.A. Markel - U.S.A. Trane - U.S.A. Cooling Towers Baltimore Aircoil Company - U.S.A. Evapco - U.S.A. Marley - U.S.A. Controllers (Water Level) B&W Magnatrol International, Inc. McDonnell Miller Warrick Dampers (Dynamic Fire/Smoke) Imperial Pottorff Ruskin Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-34 HVAC Issued for Construction 1 June 2004 Draft Gauges Dwyer Hays Expansion Joints Ball Type Advanced Thermal Systems Hyspan-Barco Corrugated Type Adsco Badger Industries Hyspan-Barco Keflex Metraflex Microflex Slip Type Advanced Thermal Systems Adsco Hyspan-Barco Yarway Expansion Tanks Adamson Amtrol Bell & Gossett John Woods RECO TACO Fans Axial Type Aerovent Buffalo- Howden Greenheck New Philadelphia Fan Co. (Joy) Strobic Air TFF Aerovent Woods Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-35 HVAC Issued for Construction 1 June 2004 Barrel Type (Tubular Centrifugal) Aerovent Barry Buffalo - Howden Greenheck Woods Centrifugal Aerovent Barry Bayley Buffalo - Howden Peerless Trane Twin City Flexible Duct Clevaflex, Inc. Flexmaster Genflex Wiremold Flow Measuring Devices Air Systems Air Monitor Corporation Ebtron, Inc. Tek-Air Systems, Inc. Water Systems Badger Balance Master Barco (Venturi meters) Dietric Standard Ellison Inst. Michigan New Buffalo Onicon Presso Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-36 HVAC Issued for Construction 1 June 2004 Fuel Oil Pumping Systems Preferred Utilities Mfg. Corp. BFS Industries I. S. P. Automation L. A. Liquid Handling Systems Simplex U. S. Mechanical Specialties Co., Inc. Fuel Oil Specialities EBW Catlow OCP Preferred Utilities Mfg. Corp. Fuel Oil Tanks Steel Cardinal Tank Corporation Fuel Oil Containment Highland Tank & Mfg. Co. Lannon Tank Corporation W/W Engineering Fuel Oil Tank Gauging and Leak Detection Systems Amprodux, Inc. Autostik Pneumaracator Preferred Instrument Veeder Root Hangers, Anchors and Guides Bee-Line Carpenter Patterson Erico, Michigan Hanger Fee & Mason F & S Central Grinnell Piping Technologies, Inc. Humidifiers Steam Armstrong Dri Steam Nortec Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-37 HVAC Issued for Construction 1 June 2004 Inserts Bee-Line Carpenter Patterson Erico, Michigan Hanger Fee & Mason F & S Central Grinnell Piping Technologies, Inc. Inserts (Expansion Bolts) NOTE: Powder or power actuated devices, grip nails, expansion nails and adhesive anchors are NOT permitted. Grinnell Hilti Philips Instruments Pressure Gauges 1.00% Accuracy Ashcroft Barksdale Marshall Town Miljoco Trerice Weiss Weksler Pressure Switches Barksdale Dwyer Mercoid Thermometers 1.00% Accuracy Marshall Town Miljoco Moeller Trerice Weiss Weksler Instrument Test Ports Peterson Equipment Sisco Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-38 HVAC Issued for Construction 1 June 2004 Insulation AFICO Armstrong Certain-Teed KIMMCO Knauf Johns-Manville Owens-Corning Fiberglas (O-C-F) P.P.G. (Pittsburgh Plate Glass) Insulation Adhesives Benjamin Foster Company Elgen Insul-Coustic Insulation Pipe Shields Insul-Coustic Div., Insul-Shield Pipe Shields Inc. Motors Standard Efficiency (Less Than .75 kw) A.O. Smith General Electric Gould Lincoln Marathon Reliance Toshiba Westinghouse High Efficiency (.75 kw and Above) A. O. Smith General Electric MagneTek Reliance Toshiba Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-39 HVAC Issued for Construction 1 June 2004 Motor Starters Allen Bradley Cutler Hammer General Electric Gould Siemens Square "D" Westinghouse Motor Control Centers Allen Bradley Cutler Hammer General Electric Gould Siemens Square "D" Westinghouse Motor Controllers Variable Speed Allen-Bradley Asea Brown Boveri Danfoss Eaton Hitachi Yaskawa Electric America Mitsubishi Reliance Robicon Siemens Allis Toshiba Pipe Fittings Steel Pipe Laclede LTV Newport North Star Steel Quanax Sawhill Sharon U. S. Steel Wheatland Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-40 HVAC Issued for Construction 1 June 2004 Steel Pipe Fittings Hackney Tube Forgings Tube Line Weldbend Corporation Copper Pipe American Brass Co. Bridgeport Brass Chase Brass Lewin Matheis Nibco Phelps Dodge Reading Tube Corp. Revere Wolverine Tube Co. Pressure Regulating Valves (Water) Cash ACME Cla-Val Fisher Leslie Spence Watts Pressure Relief Valves Consolidated Farris Kunkle Lunkenheimer Watts Pumps Horizontal Split, End Suction and In-Line Allis Chalmers Armstrong Aurora Bell & Gossett Buffalo Forge Gould Paco Peerless Weinman Worthington Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-41 HVAC Issued for Construction 1 June 2004 Fuel Oil IMO Viking Simplex Sheet Metal Duct Connections Ductmate TDC TDF Sound Traps I.A.C. (Industrial Acoustics Co.) Rink United McGill Vibro-Acoustics Steam Traps Armstrong Hoffman Mepco Sarco TLV Yarway Strainers Fabrotech Hoffman Lunkenheimer McAlear Mfg. Co. Metraflex Mueller Sarco Yarway System Identification Seton Nameplate Corp. W. H. Brady Co. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-42 HVAC Issued for Construction 1 June 2004 Valves Balancing Valves (Water) Armstrong Autoflow Bell & Gossett Flow Design Griswold Milliken Valve Company, Inc. T&A Ball Type Apollo Crane FlowTek Hammond Jamesbury Rockwell Stockham Watts Balanced Check Hager Mueller Smolenski Butterfly High-Performance High performance type butterfly valves shall be ANSI Class 150, 250 or 300 with double lug body suitable for double dead-end service, with either flange removed in accordance with MSS, SP67 for Type I Valves and/or MSS, SP68. DeZurik Flow Seal Grinnell Bray McCanna Jamesbury Keystone Posi-Seal/Fisher W.K.M. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-43 HVAC Issued for Construction 1 June 2004 Swing Check Crane Grinnell Hammond (I.B. Series only) Milwaukee Powell Rockwell-Nordstrom Walworth Gate Valves Crane Grinnell Hammond (I.B. Series only) Milwaukee Nordstrom Powell Walworth Globe Valves Crane Grinnell Hammond (I.B. Series only) Milwaukee Nordstrom Powell Walworth Plug Valves (Lubricated Type) DeZurik Milliken Valve Company, Inc. Nordstrom Walworth Plug Valves (Non-Lubricated Type) DeZurik Milliken Valve Company, Inc. Walworth Solenoid Valves Asco Magnatrol Skinner Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-44 HVAC Issued for Construction 1 June 2004 Vibration Isolators Amber Booth Mason Industries Water Filtration Aqua-Star Diamond Water Systems, inc. P. E. P. Tower Flo Waterproof Sleeves Link Seal Zurn 2.02 MATERIALS FOR PIPING A. All materials shall be the products of one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. B. Schedule Service Material Type Weight Fuel Oil (Within Building) Steel Black Schedule 40 Seamless ASTM A-53 Grade B NOTE: Piping inside of the building, but outside of the Generator Equipment Room and vertical shaft shall be pipe-within-a-pipe (outer pipe shall be oiltight and watertight, of not lighter than 10 gauge, all welded black steel). The entire assembly shall be enclosed within a UL listed two (2) hour fire rated enclosure. Diesel Engine Exhaust Steel ERW or Seamless ASTM A-53 Grade B Black 9.5 mm. Wall Thickness Steel Black Schedule 40 Black Schedule 80 Steam 75 mm. and Under Seamless ASTM A-53 Grade B Condensate Return and Drips Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Steel Seamless ASTM A-53 Grade B 15000-45 HVAC Issued for Construction 1 June 2004 Service Material Pumped Condensate (Above Ground) Steel Seamless ASTM A-53 Grade B Type Weight Black Schedule 80 Black Schedule 40 Chilled Water, Condenser Water and Heat Recovery 75 mm. and Under Seamless ASTM A-53 Grade B 100 mm. to 250 mm. Steel ERW or Seamless ASTM A-53 Grade B Black Schedule 40 300 mm. and Over Steel ERW or Seamless ASTM A-53 Grade B Black 9.5 mm. Wall Thickness Refrigerant Copper Hard Type L (ACR) Fresh Water Copper Hard Type L Vent Copper Hard Type L Compressed Air Copper ASTM B-88 Hard Type L Drains Copper ASTM B-88 Hard Type L 2.03 C. Note that all pipe shall be suitably reinforced at all anchor points. D. Copper tubing for refrigerant service shall be furnished cleaned, dehydrated, and sealed. E. Dimensions and weights of steel pipe shall conform to ANSI Standard B16.10. PIPE FITTINGS A. All products shall be manufactured by one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-46 HVAC Issued for Construction 1 June 2004 B. Schedule Service Material Type Weight Fuel Oil (Within Project Building) Seamless Steel Butt Welding Schedule 40 Diesel Engine Exhaust Seamless Butt Welding 9.5 mm. Wall Thickness C.I. Screwed 8.5 Bar (Steam Rating) C.I. Screwed 17 Bar (Steam Rating) C.I. Screwed 8.5 Bar (Steam Rating) To 50 mm. (Except Risers) C.I. Screwed 8.5 Bar (Steam Rating) (17 Bar w.o.g.) 65 mm. to 250 mm. Seamless Steel Butt Welding Schedule 40 300 mm. and Above Seamless Steel Butt Welding 9.5 mm. Wall Thickness Steam: Below 3.5 bar 50 mm. and Under Pumped Condensate 50 mm. and Under Condensate Return and Drips Below 3.5 Bar 50 mm. and Under Chilled Water, Condenser Water and Heat Recovery All Chilled Water, Condenser Water and Heat Recovery Risers, Including Offsets in Overhangs Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-47 HVAC Issued for Construction 1 June 2004 Service Material Type Weight All Seamless Steel Butt Welding Standard NOTES: 1. 2. See drawings for locations of all welded construction required in overhangs. Drain mains and expansion lines for all systems shall correspond in weight, class, etc., to above schedule. Refrigerant All Wrought Copper Silver Solder Standard All Wrought Copper Solder Standard All C.I. Screwed 8.5 Bar All Wrought Copper Solder Standard Wrought Copper Solder Standard Fresh Water Vents Drains Compressed Air All C. All steel elbows shall be of long radius pattern except where space conditions do not permit. D. Material for drains shall be as specified above except where otherwise noted on the drawings. E. Welding Piping 1. Where so shown on drawings, specified or directed, welded joints, outlets and flanges shall be used. Welded joints may also be provided elsewhere, at option, except on piping smaller than 65 mm. (which may be screwed except as noted hereinbefore), or at points where it may be explicitly specified or directed to leave flanged joints in order to facilitate future changes. 2. All welded joints (except pipe welded end-to-end) shall be made by the use of forged one-piece weld neck flanges (slip-on flanges shall not be accepted), caps, nozzles, elbows, branch outlets and tees, of Tube-Turn, Taylor-Forge, Ladish, Grinnell or other approved make, except as specified to the contrary herein. Cut Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-48 HVAC Issued for Construction 1 June 2004 samples shall be submitted for approval if directed. All such fittings, etc., shall be of a type which maintains full wall thickness at all points, ample radius and fillets, and proper bevels or shoulders at ends. "Weld-o-lets" may be used where standard fittings of required sizes are not available and elsewhere as approved. All job welding shall be done by the electric arc welding process in accordance with the following: 3. a. Joints shall be 45 degree mill beveled or machine beveled. b. All scale and oxide shall be removed with hammer, chisel, file and/or grinding wheel. Bevel shall be left smooth and clean. c. Pipe lengths must be lined up straight with abutting pipe ends concentric. d. Both conductors from the welding machine shall be extended to locations at which welding work is being done. The leads from welding machine to location of welding work shall be held together in an approved manner and then taped so as to prevent induced current in structural steel, in piping or in other metals within the building. The ground lead shall be connected to length of pipe with suitable clamp in such manner that welding current shall not flow through joints in pipe, structural steel of building or steel pipe supports. e. Weld metal must be thoroughly fused with base metal at all sections and must exhibit complete penetration to weld root. Welds shall be of sound metal, free from laps, slag inclusion or other defects. f. Welders or welding operators shall be certified by the National Certified Pipe Welding Bureau of the Mechanical Contractors Association of America and/or ASME Section 9. Welders shall possess and maintain current Procedure Qualification Records for the service for which they are employed and on which they work. g. All welds shall bear the identifying number, letter or symbol of the welder or welding operator. The Subcontractor must provide current copies of each welder or welding operators Procedure Qualification Record prior to proceeding with any welding. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-49 HVAC Issued for Construction 1 June 2004 4. An independent testing agency shall observe the fitting up and making of all welds as prescribed in ASME/ANSI B31.9. The inspection and testing protocol requirement is as follows. a. Every weld shall be inspected, including any shop welds. b. The first twenty (20) field welds shall be ultrasonically tested. c. Ten percent (10%) of the remaining welds, on a random basis determined by the independent testing agency, shall be ultrasonically tested. d. Based on the results of the ultrasonic testing of the first twenty (20) welds, a determination of the extent of the subsequent testing beyond the minimum 10% noted in Paragraph c. above shall be established by the Engineer. All costs of testing, repair, replacement, schedule impacts, etc., shall be borne by the Subcontractor. 5. Welding tees and saddles may be omitted and shaped cut end connections provided directly to pipe as follows: a. All chilled water and condensing water piping up to two pipe sizes smaller than the size of main. b. "Weld-o-lets" must be used on hot water perimeter risers where horizontal branches tap into risers at each floor. NOTE: Socket "Weld-o-lets" and/or socket tees shall not be permitted. F. Wherever welded piping connections to equipment, valves, or other units need maintenance, servicing, or require possible removal, the connecting joint shall be flanged. Pressure-temperature rating of the pipe flanges shall match the pressure-temperature rating of the flanges on the equipment to which the piping connects. G. Mechanical Couplings for Grooved Copper Piping 1. Mechanical couplings for grooved copper pipe shall be of the rigid type, with plated nuts and bolts to secure housing sections together and a synthetic rubber flush seal gasket of the cavity pressure responsive design. Piping systems are to be installed in accordance with the requirements of the manufacturers latest published literature. 2. Coupling housings shall be cast ductile iron conforming to ASTM A-536 (Grade 65-45-12), or malleable iron conforming to ASTM A-47, finished painted with alkyd enamel. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-50 HVAC Issued for Construction 1 June 2004 3. Flange adapters shall be cast ductile iron conforming to ASTM A-536 (Grade 65-45-12), or malleable iron conforming to ASTM A-47, finished painted with alkyd enamel. Flange adapters shall engage directly into roll grooved copper pipe and fittings and bolt directly to ANSI Class 125 cast iron and Class 150 steel flange components. 4. Gaskets for mechanical couplings and flange adapters shall be molded flush seal type conforming to the outside diameter of the copper pipe and coupling housing or flange adapters. Synthetic rubber of elastomers having properties as indicated in ASTM D2000 shall be used. Gasket selection shall comply with the coupling manufacturers standards, installation and design requirements and shall be suitable for the intended service and temperature range. a. 2.04 Gaskets for water service from -34°C. to +110°C. shall be Grade “E” EPDM. 5. Fittings for 50 mm. to 100 mm. pipe shall be full flow type copper in accordance with ASTM B-75 alloy C12200. Fittings for 125 mm. and 150 mm. pipe shall be cast bronze in accordance with ASTM B-584-7 requirements. Grooves shall be designed to accept mechanical coupling manufacturers castings. Elbows are to be long radius type. 6. Connections between dissimilar metals in liquid systems shall be made with dielectric fittings. H. All soldered joints, except for refrigerant piping, shall be made with 95% tin and 5% antimony solder, having a melting point of not less than 240°C. Refrigerant piping joints shall be made with silver solder. All soldered joints shall be thoroughly cleaned before the application of the solder. All soldered joints for tubing larger than 50 mm. in size shall be made with the simultaneous application of two or three blow torches. I. Where dissimilar metals come in contact, a dielectric coupling shall be installed. Dielectric flange kits shall be permitted where screwed piping is not employed. VALVES A. All valves shall be manufactured by one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. B. Shut-off valves, isolation valves, balancing valves and check valves shall be provided as shown on the drawings, required or directed. The standard features required of valves are listed hereinbelow. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-51 HVAC Issued for Construction 1 June 2004 C. Unless otherwise noted, all valves for shutoff and bypass service shall be ball valves, 65 mm. and below, and butterfly valves 75 mm. and above. D. All end connections shall be the same as are used for fittings for 50 mm. and below. 65 mm. and above, valves shall be flanged. E. Unless otherwise directed, steam pressure/temperature ranges are defined below: 1. Low Pressure: 120°C. @ 1 Bar maximum. 2. High Pressure: 230°C. @ 14 Bar maximum. F. All valves except valves at equipment, shall be labeled with 40 mm. brass tags, with stamped lettering or numbers filled in with black paint bearing a letter to indicate the service and a number to indicate the valve. A permanent valve chart and system schematic diagram shall show the location of all valves. G. A manufacturer's valve tag shall be on all valves identifying the valve type and major component materials. H. Ball Valves 1. For all water services, low pressure steam, low pressure condensate and all other normal noncorrosive services, ball valves shall be: Body Body Style Trim Seat Seat Working P/T Rating Body Working P/T Rating WOG Rating Saturated Steam Rating I. Bronze One piece, standard port 316 Stainless Steel ball and stem Reinforced teflon (RTFE), 15% glass filled, double seal 20 Bar @ 120°C. minimum 20 Bar @ 38°C. minimum 20 Bar minimum 10 Bar minimum Plug Valves Body Body Style Plug Seat Seat Working P/T Rating Body Working P/T Rating WOG Rating Actuator Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Cast Iron One piece, standard port Nickel Plated or EPDM coated Cast Iron Welded Nickel 20 Bar @ 120°C. minimum 20 Bar @ 38°C. minimum 20 Bar minimum 100 mm. and under - locking lever handle; over 100 mm. - gear operator 15000-52 HVAC Issued for Construction 1 June 2004 J. All ball or plug valves specified herein or as shown on drawings, as balancing valves, or used for such purpose, shall, in addition to the options listed, be reduced port type, furnished with a pair of differential ports over a fixed orifice (for the purpose of measuring the flow through the valve) and a locking type memory stop. Furnish flow characteristic curves (differential pressure vs. flow) for each valve type. 1. K. Minimum Flow Coefficients (Cv) Size Cv 15 mm. 20 mm. 25 mm. 30 mm. 40 mm. 50 mm. 65 mm. 8 14 35 50 75 110 300 Butterfly Valves 1. The use of butterfly valves shall be limited to shutoff services only and only where specifically permitted by the Consulting Engineers. Butterfly valves shall not be permitted in those services which require balancing or throttling valves. The manual operator shall be provided with an external position indicator. Butterfly shall permit draining or removal of equipment and piping protected by the valve. Valves shall be full-bodied, full lug type only (wafer type or semilugged valves shall not be permitted) high performance type suitable for double dead-end service with either flange removed. Valves shall be bolted from both ends of the flanges. All butterfly valves for water services shall be ANSI Class 150, 250 or 300 as specified hereinbefore. 2. Butterfly valves shall be leak tested in accordance with MSS, SP-67 for Type I Valves and/or MSS, SP-68. 3. For all water services and all other normal noncorrosive services, butterfly valves shall be: Body Body Style Trim Disc Seat Cast iron Tapped lug 316 Stainless Steel stem Bronze Field replaceable resilient seat, fully bi-directional, totally encapsulated 12 Bar @ 120°C. minimum ANSI 150 Seat Working P/T Rating Body Working P/T Rating Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-53 HVAC Issued for Construction 1 June 2004 Actuator 4. 100 mm. and under - locking lever handle; over 100 mm. gear operator For low pressure steam service, butterfly valves shall be: Body Body Style Trim Cast iron Tapped lug 316 Stainless Steel double offset stem 316 Stainless Steel TFE 7 Bar @ 175°C. minimum ANSI 150 100 mm. and under - locking lever handle; over 100 mm. - gear operator, with locking hardware and position indicator Disc Seat Seat Working P/T Rating Body Working P/T Rating Actuator L. Valve Schedule Service Size Type Balancing Valves for Water Services and Condensate. To 65 mm. Ball 75 mm. and larger Plug Shut-off Valves for Water To 65 mm. Services and Condensate. 75 mm. and larger Ball Check Valves for Water Services, Steam and Condensate in the horizontal position. 15 degree swing checks. All sizes Butterfly Check Valves for Water All Sizes Services and Condensate in the vertical position. Balanced Checks Steam Service To 65 mm. Ball 75 mm. and larger Butterfly Compressed Air All Sizes Ball Valves Refrigerant All Sizes Kerotest, Packless Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-54 HVAC Issued for Construction 1 June 2004 M. All steam service valves 150 mm. and larger shall be furnished with a 25 mm. bypass valve installed around the valve. Bypass valves shall have the same pressure-temperature ratings as the main valve. N. Provide all necessary manual or automatic vent valves. All drain valves in Equipment Rooms shall be located at an elevation not greater than 2 meters above the floor and shall be piped to the nearest floor drain. All automatic and manual vents shall have same pressure rating as primary valves in the system to which they are connected. O. Provide all other hand valves, check valves, cocks, etc., as required for the complete and proper valving of the entire installation as defined herein. P. All water piping connections to equipment shall include all necessary isolation valves, air vent valves, drain connections, balancing valves and the automatic valves arranged as detailed on the drawings. Q. Water pipes shall be vented at the high points and wherever else required or directed. R. Drain cocks with threaded ends for hose connection shall be provided at any low points in the water supply and return mains and risers where directed. S. Compression type, key-operated air cocks shall be provided where shown and where required for venting. Cocks shall be 6.5 mm. in size and shall be all bronze construction; at least two dozen keys shall be delivered to the Engineer's representative for operating these cocks. T. Valves in Pump Rooms, Equipment Rooms or Fan Rooms which are more than 6 feet 0 inches above the floor shall be provided with chain operated sheaves and chains. U. All valves shall have self-packing stems so that they can be packed while open and under pressure. V. Valves on the discharge side of all pumps shall be lubricated plug type. W. All lubricated tapered plug cocks shall be lubricated with the manufacturer's recommended lubricant for water service before shipment to the job site. Lubricated tapered plug cocks installed more than 2 meters above floors shall be furnished with chain wheels if gear operated and double end chain wrenches if wrench operated. All plug valves shall be furnished with an external position indicator on the valve assembly. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-55 HVAC Issued for Construction 1 June 2004 2.05 STRAINERS A. There shall be approved "self-cleaning" strainers in the inlet connections to each feeder and make-up connection and each automatic control valve, and all traps and each pump. The intention is to protect by strainers all apparatus of an automatic character, whose proper functioning would be interfered with by dirt on the seat or by scoring of the seat. B. All strainers in water lines shall be Y-pattern set in a horizontal (or vertical downward) run of the pipe. Where this is not feasible, strainers may be of enlarged cross-section flat type. In all cases, strainers shall be so arranged as not to "trap" pipes, and to facilitate disconnection and opening-up for cleaning. C. All strainers shall have cast iron, or bronze, bodies of ample strength for the pressure to which they shall be subjected and suitable flanges or tappings to connect with the piping they serve. They shall be of such a design as to allow blowing out of accumulated dirt, and to facilitate removal and replacement of a strainer screen, without disconnections of the main piping. Strainer basket screens shall be nickel, copper or brass and shall be of ample strength to prevent collapsing the basket under shock loading. Perforations shall be in accordance with the following table: System or Service Perforation Size No. of Perforations per 645 mm.2 Steam and Air Water - To 125 mm. 150 mm. & over 0.50 mm. 1.6 mm. 3.2 mm. 625 - D. Provide approved valved dirt blowout connections for each strainer. Each such valve shall be located at hand height with hose adapters. In the case of strainers under water pressure, the blowout connections shall terminate in an approved manner at a point where there is no risk of flooding or damage. E. Extra heavy basket or Y-strainer with flanged ends and copper basket, shall be installed in water lines where shown on the drawings. F. Clean the strainers as necessary until accepted by the Engineer. G. All strainers installed upstream of automatic control valves shall be installed line size, which shall mean the size of the inlet pipe shown on the drawings, not the reduced size serving the control valve. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-56 HVAC Issued for Construction 1 June 2004 2.06 2.07 RELIEF VALVES A. Provide, where shown on the drawings, or as required by Code, safety relief valves to carry 100% of scheduled capacity of the larger valves in each step of each pressure reducing station. Relief piping shall be sized according to outlet size of relief valve. B. Where two relief valves are joined, the larger pipe size shall be continued to the point of relief. Relief valve shall comply with ASME requirements and as manufactured by one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. IDENTIFICATION OF SYSTEMS A. Identifications shall be manufactured by one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. B. All valves, dampers, and controls shall be designated by distinguishing numbers on the charts or diagrams. Provide stamped brass or engraved phenolic tags for all designated items with numbers corresponding to those on the charts. The nomenclature to be used on these tags shall be submitted to the Consulting Engineer for approval. C. The tags shall be not less than 50 mm. in diameter with depressed black numbers of 10 mm. height, prefixed by the letters "HVAC". They shall be fastened to valves and controls with brass chains and hooks. D. Provide three sets of charts or diagrams showing outline plans of structures and essential features of the several systems, including all piping, ducts, equipment, valves, dampers and controls. In addition, furnish three complete sets of valve, damper and/or control schedules and schematic flow charts with corresponding numbers noted on chart indicating location of device by floor and nearest column number. Schedule shall also show the valve or damper size and service. Schedules shall be mounted in heavy duty polypropylene sheet protectors and 215 x 280 mm. three ring binders. A reproducible drawing of the schedules and flow charts shall also be provided to the Engineer for his use. E. Provide and affix piping identification labels in conformance with the following: 1. Markers shall be pressure sensitive adhesive type, meeting ANSI/OSHA requirements identifying the service, by system and zone, and direction of flow in the various piping systems. Markers shall be provided on all concealed and exposed piping as well as in shafts and shall be affixed to each pipe not less frequently than every 12 meters. There shall be at least one identifying marker per pipe in each enclosed space and at each Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-57 HVAC Issued for Construction 1 June 2004 floor level within shafts. Identifying markers shall also be provided adjacent to each valve. Valves at equipment and pumps do not require separate identification. 2. F. 2.08 Each set of markers shall consist of one label on which the name of the service is printed in black letters not less than 25 mm. high for pipe 60 mm. and smaller, 50 mm. high for 75 mm. pipe and larger, and one band on which is printed a black directional arrows. Markers shall be applied where they can be easily read and with their long dimension parallel to the axis of the pipe. Markers and bands shall have backgrounds of different colors for the various service groups. Colors shall conform to ANSI Standard A13.1. All equipment (air handling systems, fans, ducts, pumps, chillers, etc.) shall be labeled utilizing painted on stenciled lettering for identification. Identification labels shall match the nomenclature in the equipment schedule sheets or on the drawings. HANGERS, ANCHORS, SUPPORTS, GUIDES, ETC. A. Provide suitable and substantial hangers and supports for all horizontal pipes and ductwork. Hangers and supports shall be of the type, size and spacing specified, or as approved. All piping shall be carried by pipe hangers supported from building structure. Provide drawings indicating pipe loads, including method of suspension and hanger location, and submit them for approval prior to proceeding with installation. Provide all the supplementary steel required to support, guide and anchor piping within shafts, Mechanical Equipment Rooms and all the other floors. Method of attachment to and load imposed on building structures by hangers, anchors, supports, guides and supplemental steel shall be submitted for review. The building is of all-concrete construction. B. Pipe hangers, anchors, supports and guides shall be manufactured, selected, fabricated and installed in accordance with MSS SP-58, MSS SP-69 and MSS SP-89. C. All methods of support shall be as manufactured by one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”, and must be submitted and approved by the structural engineer. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-58 HVAC Issued for Construction 1 June 2004 D. Horizontal piping shall be supported in accordance with the following schedules: SINGLE ROD SUPPORT Pipe Size Maximum Hanger Spacing Rod Size 25 mm. and smaller 30 mm. to 50 mm. 60 mm. to 125 mm. 150 to 350 mm. 400 to 600 mm. 2 meters 2.75 meters 3 meters 3.65 meters 4.75 meters 10 mm. 10 mm. 12 mm. 16 mm. 25 mm. DOUBLE ROD SUPPORT Pipe Size Maximum Hanger Spacing Rod Size 15 to 350 mm. 400 to 600 mm. 3.65 meters 4.75 meters 12 mm. 19 mm. E. Maximum hanger spacing may not be exceeded; however, actual installed spacing shall depend on location of structural supports and floor slab construction. Where building construction does not permit above spacing, provide additional steel supports. F. Where hangers cannot be supported from building structure, they may be supported from concrete inserts, subject to the approval of the Structural Engineer. Furnish, locate and set such inserts and make sure that such inserts are in place when the concrete is poured. Inserts shall be constructed of malleable iron or pressed steel and shall have space for rods of all sizes. All inserts for pipes 75 mm. and larger in size shall be installed with a reinforcing rod 16 mm. in diameter, run through a slot in the insert specifically provided for this purpose. G. Particular care shall be taken to support all pipe mains, ductwork and all large and heavy pipes in a manner approved by the Engineer, including the providing of supplementary steel, if required. Shop drawings indicating support methods, point loadings to the building structure and hanger locations shall be submitted for review sufficiently in advance of concrete pouring schedules to permit evaluation, critique and any necessary changes to hanging and support methods. H. Set all inserts for all pipes in ample time to allow the work of the other Trades to be performed on scheduled time. I. If any pipe or duct has to be hung in space where no inserts have been provided, install two double expansion shields connected by a 50 mm. x 50 mm. angle, from which suspend the hanger rod. For pipe sizes 50 mm. and under, use a single double expansion shields, but the hanger Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-59 HVAC Issued for Construction 1 June 2004 spacing defined above shall be reduced to 1.5 meters. The minimum size shield acceptable is 10 mm. The carrying capacity and size of each shield shall be calculated on the basis of the spacing indicated above but the minimum size shall be 10 mm. Additional shields of the same size shall be installed so that the number of hangers are double that allowed for inserts. The rods on all hangers shall be of adequate size to support the loads which they carry. Shields may be used in stone concrete slabs only. No power or powder actuated inserts shall be permitted. J. Smaller pipes may be suspended from cross-pieces of pipe or steel angles, which, in turn, shall be hung from building concrete construction by means of rods and inserts. The intention is to provide supports which, in each case, shall be amply strong and rigid for the load, but which shall not weaken or unduly stress the building construction. K. Provide approved roller supports, floor stands, wall brackets, etc., for all lines running near the floor or near walls, which can be properly supported or suspended by the floors or walls. Pipelines near walls may also be hung by hangers carried from approved wall brackets at a higher level than the pipe. L. No piping shall be hung from other piping. In no case shall hangers be supported by means of vertical expansion bolts. M. Hangers shall be of heavy construction suitable for the size of pipe to be supported. All materials, except rollers, shall be wrought or malleable iron or steel. Hangers shall be swivel ring, split ring, roller, wrought pipe clamp, or adjustable wrought clevis type. N. All hangers, anchors, supports and guides (swivel ring, split ring, roller, wrought pipe clamp, or adjustable wrought clevis type hangers, roller supports, floor stands, wall brackets, etc.) installed within the building shall be factory finished with red oxide primer. Hangers, anchors, supports and guides installed outside of the building shall be hot dipped galvanized in accordance with ANSI/ASTM A 123. O. Wherever roller type hangers are used, approved steel pipe covering protection saddles shall be spot welded to the piping at each hanger location, except as otherwise specified hereinbelow. P. Piping shall be anchored where required to localize expansion or to prevent undue strain on piping and branches. Anchors shall be entirely separate from hangers and shall be of heavy forged or welded construction of approved design. All anchors shall be submitted and shall include piping reactions which respective anchors are capable of supporting. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-60 HVAC Issued for Construction 1 June 2004 Q. All lines of copper tubing shall be individually supported by approved type hangers not more than 1.75 meters apart or as shown on the drawings. Hangers for uncovered lines shall be especially designed for copper tubing and shall be exact o.d. of tubing. Hangers for covered tubing shall have broad straps fitting outside of covering. R. Hangers for cold piping shall support the pipe without piercing the insulation. Insulation shields shall be used to protect the insulation on cold pipes. Insulation protection saddles shall be welded to insulated hot pipes at roller supports. Wherever fiber glass pipe insulation is installed, Kaylo of equal thickness shall be installed in lieu thereof wherever hangers and insulation shields are installed. It is the intent that the insulation shields shall bear only on an insulation material which is of such density that it shall not compress, crush or deform. S. Anything specified in this Article notwithstanding, all hangers and supports shall comply with the requirements prescribed under "Foundations and Vibration Isolation Incorporating Seismic Restraints". T. Coordinate with other Trades to use common means of support. Submit for approval all pertinent design data relating to the support as well as verification of the responsibility for the support. U. Install pipe guides, ADSCO Model G, or as approved, for all risers located in shafts, at each of the first two floors immediately above and below each anchor, and, where applicable, per the requirements of this Specification, and where indicated on the drawings. V. 2.09 Pipe Size Guide Spacing Up to 75 mm. 100 through 150 mm. 200 mm. and above Every other floor Every third floor Every fourth floor Protect the insulation for a length of the sleeve with a galvanized 1.0 mm. shield (360 deg.). FLOW MEASURING SYSTEMS A. Annular Primary Flow Elements 1. Provide an annular primary flow element to measure the flow through the piping system, one for each metering location, as manufactured by one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. 2. The annular primary flow element shall be made of Type 316 stainless steel and rated to 2,750 kPa. Annular element shall be complete with permanent rustproof metal identification tag on Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-61 HVAC Issued for Construction 1 June 2004 chain showing designed flow rates, meter readings or differential pressure outputs of designed flow rates, metered fluid, line size and tag, station or location number. Station sizes 12 mm. to 30 mm. shall be nipple section type, sizes 50 mm. and 65 mm. shall be either nipple section or weld insert type and sizes 75 mm. and larger shall be weld insert type. Permanent pressure loss to the system shall not exceed 8.2% of the output differential on sizes over 35 mm. and 2.9% on sizes over 125 mm. Accuracy of the flow measuring elements shall be plus or minus .55 to plus or minus 1.5% as verified by independent laboratory reports. 3. 2.10 Metering stations shall be as follows: a. Condenser water return from each refrigeration machine. b. Chilled water supply from each refrigeration machine. c. Chilled water return branch from each side of chilled water coil banks or single coil banks. d. Common discharge of each heat recovery coil system. e. Heat recovery water return branch from each side of duct-mounted recovery coil banks or single coil banks. 4. This system shall, in addition, include a portable meter set supplied by one manufacturer. Each annular measuring station shall be complete with safety shutoff valves and quick coupling connections. Annular measuring stations shall be made of stainless steel and brass. Stations shall be either nipple section or weld insert type. Annular measuring stations shall be rotatable sensing elements so that all pressure sensing ports can be pointed fully downstream when station is not in use. 5. Portable meter set shall consist of a primary standard mercuryless manometer with a scale reading 0-1,200 mm. water. Meter shall be supplied complete with a master chart for direct conversion of meter readings to gpm, carrying case, two 3.65 meters checking hoses rated to 2,750 kPa/107°C., equalizer manifold, check seal, installation and operation instructions. Meter shall become property of the Owner. 6. This system shall be utilized to balance the water system hereinabove described. Be responsible for all necessary readings and required flow adjustments. AUTOMATIC AIR ELIMINATORS A. All free air originally contained in the system and all entrained air bubbles carried by system water shall be eliminated at each cooling coil section and at the highest point in the return piping (connected to pump Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-62 HVAC Issued for Construction 1 June 2004 suction) and at all system points as indicated on the drawings by a combined air separator/eliminator -- a completely integrated unit. Tangential inlet and outlet piping connections shall create a vortex in the body of the unit allowing air separation from flowing system water. Air shall be eliminated to the atmosphere as fast as it is separated through a float activated, remote pressure operated air elimination valve located in the top of the unit. The valve shall have a high removal rate at low pressure differentials (not to exceed 14 kPa at full flow) and shall be fully open for the removal of air at all pressures in the operating range from 14 kPa to 1,035 kPa. It shall be tightly sealed against loss of system water and prevent entrance of air in negative pressure situations. 2.11 B. The automatic air separator/eliminator shall be constructed of cast iron or welded steel, constructed tested and stamped in accordance with Section VIII of the ASME Code for a working pressure of 1,035 kPa, and all working parts shall be noncorrosive. C. Each automatic eliminator shall be piped to the nearest floor drain. PNEUMATIC DIAPHRAGM EXPANSION TANKS A. Provide pneumatic tanks with dimensions and storage capacities as scheduled for the closed chilled water system with all specified appurtenances, as manufactured by one of the approved manufacturers listed in Article 2.01 “ Approved Manufacturers”. Tanks are to be built in accordance with NSF and ASME Code standards, all seams double butt welded by certified code welders, Underwriters' Certificates and stamping to be furnished. Tank sizes and factory set air pressures for tanks to be as indicated on drawings. B. Tanks shall be of the vertical type. C. Tanks to be provided with suitable tappings for cold water inlet, air connection, charging valve, and drain connection. All wetted metal parts must be brass or stainless steel. D. Provide pressure relief valve between shutoff valve and tank on inlet pipe. E. Provide in the expansion line piping near each tank, pressure switches, Honeywell L604A, to alarm at 55 kPa (adjustable) below system operating pressure and at 55 kPa (adjustable) above the system operating pressure. Switch shall include a time delay, adjustable from 1 to 10 minutes, and auxiliary contacts so that the alarm remains off for 2 minutes after alarm condition is reached. Auxiliary contacts shall be wired to the building automation system under another Section of the Specifications. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-63 HVAC Issued for Construction 1 June 2004 2.12 2.13 OPEN EXPANSION TANKS A. All products shall be manufactured by one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. B. Open Expansion Tanks (Heat Recovery Water Systems) 1. Provide where shown on the drawings and connect complete with all necessary appurtenances, an expansion tank for storing the expanding water from each water system shown on the drawings. 2. Tanks shall be of sizes as shown on the drawings, shall be set on or, where applicable, hung from suitable supports and shall be provided with all necessary tappings of sizes as shown on the drawings. Tanks shall be fabricated of not less than 3/16 inch galvanized steel plate, galvanized after fabrication. 3. The necessary tappings with bronze mountings and shutoff valves shall be provided on the tanks for water gauges with proper guard for indicating water level in the tanks at all times. 4. Tanks shall be provided with expansion inlet connection, makeup water, drain, and vent connection. Drain shall be piped to building drainage system and indirectly connected to same. 5. Open type expansion tank shall have a float controlled water feeder installed at each tank for water make-up and shall introduce the water through an open funnel. Provide high and low level alarm devices. WATER MAKEUP PUMP SETS A. There shall be furnished and installed where indicated on the drawings, simplex makeup water pumping units having capacities as listed in the schedule on the drawings. The units shall be complete with steel receiver, pumps, motors and base, float switches, supports and other incidental items necessary to complete the units. The units shall consist of the following elements: 1. A steel base with drip connection and all necessary tappings, holes for foundation bolts, etc. -- arranged to support the receiver and the motor and to keep the entire equipment aligned. 2. A receiver of steel of approved design, with all necessary tappings and glass water gauge. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-64 HVAC Issued for Construction 1 June 2004 2.14 3. Close-coupled pump of approved pattern and construction with the pump inlet piped to the receiver, and with the motor securely supported on the baseplate. 4. An approved oversized funnel at the inlet connection to the receiver. Note that the receiver inlet size shall be not less than 50 mm. Check and ball valves shall be provided at the pump discharge. 5. Automatic controls shall be provided for the pump motor on-off switch and combination starter as hereinafter specified. The lead pump shall be activated by a pressure switch, Honeywell L604A, to fill the system which it serves. The pump shall start at 35 kPa (adjustable) below the system operating pressure and stop at 20 kPa (adjustable) above the system operating pressure. Failure of the lead pump to start shall cause the lag pump to start. Each sequential start shall automatically change to lead/lag arrangement (duplex pump sets only). Control equipment shall be factory mounted and wired on the units. 6. Extreme Low Level Alarm: Pump basin shall be furnished with a factory-installed extreme low level switch which shall be monitored at the DDC system for remote alarm annunciation. CENTRIFUGAL PUMPS A. Provide pumps of sizes, types and performance ratings scheduled, designed and guaranteed for continuous or intermittent service when operating at design speed or at any point over the full range of the pump curve without overheating the motor or bearings, without exceeding the nominal horsepower of its motor, and without producing noise audible in any area of the building outside of space in which it is installed. Pumps shall be designed and tested at 1-1/2 times the scheduled working pressure. Guaranteed performance curves shall be submitted for approval for each pump. B. All pumps and motors shall be the products of one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. C. Pumps shall be driven by constant or variable speed motors as scheduled and as specified under "Motors". Motor windings are to be compatible with starters and variable speed controllers as specified. D. Horizontally split pumps shall be of the single-stage or double-stage volute type as scheduled, with cast iron body, fully bronze fitted, doublesuction inlet, bronze impeller, flanged suction and discharge outlets. E. End suction pumps shall be of vertical split type, cradle-mounted, with iron body, fully bronze fitted. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-65 HVAC Issued for Construction 1 June 2004 2.15 F. Suction and discharge shall be provided with tapped openings suitable for mounting pressure gauges. G. Impellers shall be no greater than 85% of the largest impeller designed to fit pump casing. H. All pumps shall be furnished with grease-lubricated outboard bearings provided with drain plugs and fittings suitable for in-service lubrication. Bearings shall have a minimum of 100,000 hour B10 life. I. Pumps with their motors shall be mounted on integral frame-and-baseplate, suitably reinforced to maintain pump and motor alignment, baseplate shall be furnished with drain outlets. J. Each pump and motor shaft shall be connected by a flexible spacer coupling (Woods, or equal as approved) to permit removal of pump shaft without removing motor. Couplings shall be selected for the torque required. Special care must be taken when selecting couplings for pumps equipped with variable frequency drives. Exposed sections of pump shafts, motor shafts and shaft couplings shall be protected by 1.6 mm. sheet metal guards. K. Seals shall be unbalanced as approved, with tungsten carbide stationary seats. Bronze or stainless steel shaft sleeves shall be provided where required. L. Pumps and/or pump sets shall be leveled with tapered steel wedges to allow a minimum of 20 mm. of non-shrink grout between pump base and inertia base or concrete pad. Grouting must be performed in accordance with pump manufacturer’s recommendations. IN-LINE CIRCULATING PUMPS A. Provide, where shown or specified, circulating pumps of the in-line single stage, vertical split case design, of capacity as listed in the schedule. B. All pumps and motors shall be the products of one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. C. Each pump shall be all bronze construction. The pump internals shall be capable of being serviced without disturbing piping connections. D. The impeller shall be of the enclosed type, hydraulically and dynamically balanced and keyed to the shaft and secured with a locknut. E. Each pump shall have a mechanical seal, with a carbon seal ring and Remite (or as approved) seat. A shaft sleeve shall be furnished under the complete wetted area of the mechanical seal. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-66 HVAC Issued for Construction 1 June 2004 2.16 F. The bearing frame assembly shall be fitted with oil lubricated bronze journal bearings and a hardened alloy steel shaft. G. The pump and motor shall be connected by a flexible coupling, capable of absorbing torsional vibration. The motor shall be resiliently mounted and shall be equipped with oil lubricated journal bearings. H. Pump brake horsepower at design speed shall, under no condition, exceed the nominal motor horsepower. I. Each pump shall be factory tested, thoroughly cleaned, and painted with one coat of machinery enamel prior to shipment. J. Each pump shall be guaranteed to circulate not less than the specified quantity of water against the specified circulating head when operating continuously without overheating the motor or bearings at an approved point on its head capacity curve. K. Certified performance curves shall be submitted for each pump unit before shipping from the factory. L. Each pump shall be mounted from the piping in which it is installed. CONDENSATE PUMPS A. Provide, where indicated on the drawings, duplex condensate return pumping units having capacities as listed in schedule on drawings. The units shall be complete with cast iron condensate receiver, pumps, motors and base, float switches, supports and other incidental items necessary to complete the units. The units shall consist of the following elements: 1. A cast iron base with drip connection and all necessary tappings, holes for foundation bolts, etc. -- arranged to support the receiver and the motors and to keep the entire equipment aligned. 2. A receiver of cast iron of approved design, with all necessary tappings and glass water gauge. 3. Two close-coupled pumps of approved pattern and construction with the pump inlets piped to the receiver, and with the motors securely supported on the baseplate. 4. An approved cleanable strainer at the inlet connection to the receiver. Note that the receiver inlet size shall be not less than one pipe size smaller than the connecting piping shown on the drawings. Check and ball valves shall be provided at each pump discharge. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-67 HVAC Issued for Construction 1 June 2004 5. 2.17 Fully automatic controls shall be provided for each pump motor consisting of a float in the receiving tank, a float switch, on-offautomatic switch, combination starter as hereinafter specified. Control equipment shall be factory mounted and wired on the units. Control equipment shall be arranged so that if one pump fails to carry the load, then the second pump shall be automatically started, and both pumps shall operate simultaneously. A switch shall be provided for manually selecting the leading pump. CENTRIFUGAL REFRIGERATION MACHINES A. General 1. Furnish, as described in this Specification, centrifugal refrigeration machines of the hermetic or open type, complete with all accessories to satisfy the capacity and performance requirements as scheduled, in accordance with the latest version of ARI Standard 550. 2. Each centrifugal refrigeration machine shall consist of an assembly which shall include as its main elements a water chiller, a refrigeration condenser, a rotating drive line and a centrifugal compressor. 3. Furnish, for installation by others, differential pressure switches with field adjustable time delay (0-30 seconds) piped across the water inlet and outlet of each machine to protect against chilled water "no flow" and condenser water “no flow”. Set point range of differential pressure switches shall not exceed 150% of the pressure drop through the condenser or evaporator. Paddle-type flow switches shall not be acceptable. 4. Refrigerant 5. B. a. Non-CFC refrigerant for the vapor refrigeration cycle shall be R-134a. compression b. A complete charge of approved non-CFC refrigerant and of an approved compatible lubricating oil shall be provided for each machine. Refrigeration machine working pressure shall be as scheduled. Compressor 1. Compressor rotor shall be statically and dynamically balanced after fabrication and tested to a minimum of 10 percent overspeed. Each rotor shall be constructed of materials not Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-68 HVAC Issued for Construction 1 June 2004 subject to corrosion when in contact with the refrigerant and water. C. 2. The compressor casing shall be of fine grain cast iron or other appropriate rigid material and shall be suitably divided to permit the easy removal of the rotor shaft. The casing joint shall be provided with gaskets of proper material to prevent inward or outward leakage. 3. The compressor shall be completely assembled at the factory and shall be hydrostatically tested in accordance with ASME standards, either before or after assembly of shaft and rotor. After assembly, the compressor shall be re-tested with a mixture of refrigerant and air, the casing, joints and connections being tested with a Halide torch. 4. Capacity Control: Shall be obtained by means of variable inlet vanes, automatically controlled, at the impeller inlet and shall provide continuously varying capacity from 15 to 100 percent without hot gas bypass, per ARI Standard 550. Guide vanes shall be air foil shaped, stainless steel or nonferrous alloy, supported by high quality, heat-treated stainless steel or nonferrous alloy shafts. Positive seal shall be used at points where vane operating mechanism passes through the compressor casing to automatically protect against leakage of air or refrigerant during operating and nonoperating periods. Provide external electric valve operator and linkage. 5. Refrigerant Flow Control: Refrigerant flow to the evaporator shall be controlled by means of a fixed orifice, float valve or turbine to improve part load efficiency. Float valve and turbine shall be field serviceable. Lubrication System 1. Lubrication system shall be forced circulation type, completely piped and wired with all components necessary to assure positive oil supply on start-up, normal operation, shutdown, and power failure, including oil pump, gravity fed oil reservoir, cooler, filter, pressure and temperature sensors, sight ports, heater, motor controller and controls. 2. An externally mounted, 15 micron, replaceable cartridge oil filter equipped with service valves shall be provided. 3. Oil cooler shall be refrigerant or chilled water cooled, completely factory piped. 4. An automatic oil return system shall recover any oil that has migrated to the evaporator. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-69 HVAC Issued for Construction 1 June 2004 D. E. 5. All oil piping shall be completely factory installed and tested. 6. Oil pump shall be factory wired to a separate starter, configured to be served by a separate electrical circuit at 415 volts, 3 phase, 50 hertz. Refrigeration Evaporator 1. Evaporator shall be shell-and-tube flooded type with marine boxes, constructed of welded steel and shall be designed for the circulation of the quantity of water scheduled. The total water side pressure drop from inlet to outlets (including bolt-on type marine water boxes) shall not exceed that scheduled. 2. Evaporator tubes shall be made of copper. They shall have integral fins and shall not be less than No. 20 BWG nor less than 14 mm. inside diameter and have a minimum wall thickness of .8 mm. at the root of the fin. They shall be rolled into grooved holes in the tube sheet, and shall be removable without affecting the strength or durability of the tube sheet or causing any leakage at adjacent tubes. Water velocity in the tubes shall not exceed 3 meters per second. 3. Tube sheets shall be of carbon steel and welded to the shell of the evaporator. 4. Sufficient intermediate tube sheets shall be provided to prevent tube vibration and in no case should these tube supports be spaced at greater intervals than 1,500 mm. 5. An approved primary relief valve or rupture disc as required by Code with a secondary pressure regulating valve (to prevent complete loss of refrigerant charge upon rupture of the primary device) suitable for the attachment of vent piping shall be provided. Refrigeration Condenser 1. Condenser shall be shell-and-tube type with bolt on marine water boxes. Condenser shall be constructed of welded steel for the circulation of the quantity of water scheduled. The total water side pressure drop from the inlet to the outlet (including bolt-on type marine water boxes) shall not exceed that scheduled. 2. Condenser shall be constructed in a similar manner as specified for evaporator with regard to the shell, tubes, tube sheets, intermediate tube sheet supports and nozzles. Water velocity in the tubes shall not exceed 3 meters per second. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-70 HVAC Issued for Construction 1 June 2004 F. G. 3. Suitable baffles shall be provided to prevent direct impingement of the refrigerant gases upon the tubes and to distribute the gas uniformly over the length of the condenser. For chillers utilizing low pressure refrigerant, a suitable carbon steel baffle sheet shall be provided for the segregation and collection of the noncondensable gases for purging and at this location approved thickness materials shall be provided to prevent corrosion of the condenser shell. A connection shall be provided at the proper location for the removing of noncondensable gases and water vapor through purge and recovery units. 4. Provide suitable means to prevent entrained liquid from entering the compressor, and suitable means for uniformly distributing the liquid refrigerant. Provide float valve housing and float box or fixed orifice, approved type rupture disc or relief valve suitable for attachment of vent piping (in accordance with applicable codes). Marine Water Boxes 1. Provide marine type water boxes with removable end caps for both the condenser/subcooler and the evaporator. 2. Boxes shall have a separable removable (bolt-on) cover so that the entire tube sheet can be exposed for cleaning without disturbing the piping connections. (Removable end caps shall be provided so that the entire tube sheet shall be exposed for cleaning.) Removable cover shall be fitted with approved means for easily securing removal rigging. 3. Main piping (nozzle) connections shall be grooved (mechanical connector type). 4. A valved drain and vent connection (minimum 25 meters, with hose connections) shall be furnished on each marine water box (removable end cap). 5. Nozzle arrangements shall be as indicated on the drawings. Rotating Compressor Drive 1. Electric Motor Drive a. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Compressor shall be driven by a constant speed motor. Manufacturer shall submit details of horsepower rating and starting characteristics and shall coordinate motor selection with driven apparatus and starter manufacturer. 15000-71 HVAC Issued for Construction 1 June 2004 b. Motor shall be synchronous or induction type, wired for solid state, starting, 415 volts 3 phase, 3 wire or 4 wire (as indicated on the drawings), 50 hertz. Induction type motors shall be provided with power factor correction to maintain a minimum power factor of 0.87. c. Motor for "open" compressor drive configuration (i.e., not hermetic) shall be open drip-proof type. d. Motor for "hermetic" compressor drive configuration shall be refrigerant cooled, squirrel cage type. e. Motor Starter Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) Starter shall be solid state starter with closed transition, fusible overcurrent motor protection and circuit interrupter (circuit breaker less overload tripping coils). Each starter shall be provided with an ammeter to measure each phase leg. Overload protection shall be provided in each phase leg. A control transformer with 240 volt secondary tap shall be provided with sufficient capacity for all machine controls and interlocks. Starter shall be enclosed in neatly finished ventilated cabinet of heavy steel plate (NEMA Type I), in accordance with NEMA requirements. All chillers, including starters, shall be capable of automatic restart after an electrical power failure or momentary electrical power loss. Chillers shall automatically initiate starting sequence within 60 seconds after emergency electrical power or normal electrical power has been energized. 2) Each motor starter assembly shall be rated 65,000 A.I.C. 3) Each main bus in each chiller starter shall have current transformers, potential transformer, current and voltage test blocks, kilowatt-hour meter with demand register, elapsed time meter, and pulse transmitter and transducer for energy consumption monitoring by a building management system (BMS). 4) Individual digital meter readouts shall be provided on the chiller starter (or chiller control panel) using true rms measurements accurate to 15000-72 HVAC Issued for Construction 1 June 2004 1% for functions as described hereinabove and as follows: 2. H. a) A.C. input voltage, each phase (line-toline). b) Input current to each phase. c) Input kw/kva. d) Elapsed time using a meter which records 0 to 100,000 hours. 5) Lugs shall be suitable for copper conductors. 6) Unit Mounted Starter: If unit-mounted starters are provided, they shall be factory wired between the starter and compressor drive motor, and between the starter and all other unitmounted electrically driven components. Drive Train Accessories a. Provide drive train accessories (e.g., speed increaser gears and couplings) as required. Accessories shall have sufficient capacity to transmit maximum compressor load under all operating conditions with vibration not to exceed 1 mil. b. Gears: Designed and manufactured in accordance with the latest American Gear Manufacturers Association (AGMA) Standards, helical type continuously lubricated with filter oil and pressure-lubricated bearings. Temperature rise shall not exceed 21°C. above ambient at full load. c. All of the compressor and motor bearings (including high speed, low speed, and thrust bearings) shall have factory installed temperature sensors installed in the oil return lines to monitor bearing temperatures. Controls 1. The chillers shall be controlled by a dedicated microprocessorbased controller, supplied with each chiller by the chiller manufacturer. The controller shall be factory packaged and all required control components shall be tested for reliable equipment operation. The controller shall be battery-backed to provide protection of configured settings during power failures. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-73 HVAC Issued for Construction 1 June 2004 2. The control system shall be a complete system for stand-alone chiller control and shall include controls to safely and efficiently operate the chiller, and shall provide control of chiller operation and monitoring of chiller modules, sensors, actuators, relays and switches. 3. The control system shall monitor all components in order to verify the proper operation of each. a. As a minimum, the control system shall monitor the following safeties: 1) Motor starting and running time between compressor/motor starts. 2) Low chilled water temperature. 3) Low evaporator refrigerant temperature. 4) High condenser refrigerant pressure. 5) Evaporator water flow status. 6) Condenser water flow status. 7) Low oil pressure. 8) Low oil temperature. 9) High oil temperature. 10) High motor winding temperatures. 11) Sensor fault and proper operation of unit controls. b. If any oil temperature (as indicated by oil temperature sensors) reaches or exceeds a set value, the chiller controller shall shut down the chiller, display the diagnostic and the alarm on the front of the panel. c. The control system shall incorporate advanced motor protection to safeguard the motor throughout the starting and running cycles from the adverse effects of: Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) Phase loss (each phase). 2) Phase imbalance and severe phase imbalance. 15000-74 HVAC Issued for Construction 1 June 2004 d. 4. 3) Phase reversal and loss of phase reversal protection. 4) Over/under voltage. 5) Motor overload. 6) Motor overload protection incorrectly set. 7) Momentary power loss protection with auto restart consisting of three-phase current sensing devices that monitor the status of the current. 8) Starter contactor fault protection. 9) Starter transition failure. Alternately, the advanced motor protection system may be furnished integral to the motor starter. The front of the control panel shall be capable of displaying the following in clear language, without the use of codes, look-up tables, or gauges: a. Entering and leaving evaporator water temperature. b. Entering and leaving condenser water temperature. c. Compressor motor winding temperature. d. Saturated evaporator temperature. e. Evaporator and condenser refrigerant pressure. f. Oil temperature. g. Oil tank pressure. h. Oil pump discharge pressure. i. Differential oil pressure. j. Compressor motor starts and running hours. k. Compressor motor current, by phase. l. Compressor motor percent RLA. m. Chilled water set point and set point source. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-75 and condenser refrigerant HVAC Issued for Construction 1 June 2004 5. n. Electrical current limit set point and set point source. o. Current chiller operating mode. p. Chiller diagnostics including a time and date of occurrence (minimum 5 historical diagnostics stored in nonvolatile chiller panel memory). q. Bearing oil temperatures. r. Discharge temperature (compressor). s. Compressor motor kw and voltage, by phase. t. For machines which utilize low pressure refrigerant: 1) Purge compressor suction temperature. 2) Purge pumpout rate. 3) Purge pumpout time last or current cycle. 4) Total purge pumpout time. The chiller control system shall: a. Provide evaporator freeze protection and low limit control. This control shall be used to avoid low evaporator refrigerant temperature tripouts during critical periods of chiller operation. The control shall take progressively more aggressive load limiting action in response to the severity of the rate of change and the actual value of the evaporator refrigerant temperature. A clear language diagnostic message, reflecting the operating status, shall be automatically displayed at the front panel whenever this control is in effect, and if the condition persists, a limit warning alarm relay shall energize to indicate this condition accordingly. b. Chiller controls shall be integrated into the BMS system to provide, as a minimum, the control and monitoring functions listed below. The chiller manufacturer shall be responsible for technical coordination with the BMS manufacturer to ensure proper integration between the chiller and the BMS system. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) Remote start/stop. (Dry contact input signal.) 2) Reset of chilled water temperature (4-20 mA or 0-10V d.c. input signal). 15000-76 HVAC Issued for Construction 1 June 2004 I. 3) Provide an alarm relay output that shall energize whenever a fault requiring manual reset is detected by the panel. 4) Provide an analog output signal that shall indicate the Compressor Motor Percent RLA. 5) Status messages as follows: a) Chiller ready to start. output signal.) (Dry contact b) Chiller operating. (Dry contact output signal.) c) Chiller shutdown on safety (manual reset required). (Dry contact output signal.) c. Break-glass Station Interface: The chiller controller shall be capable of accepting a digital input signal (dry contact) from emergency stop break-glass stations, furnished, installed and wired by the Automatic Temperature Controls Subcontractor. Upon activation of the break-glass station (contact opening), the chiller shall stop. d. Be capable of independently invoking password protection of the entire display and keypad, operator settings (e.g., chilled water set point), machine configuration settings, and service startup settings. e. Provide an RS 232 or RS 485 port to output all system operating data to the BMS system. Miscellaneous Water and Refrigerant Piping: Each machine shall be provided with a water and/or refrigerant supply manifold as required, together with a system of piping between the manifold and the various oil coolers, water jackets, etc. Water for these coolers shall be provided from the chilled water circuit. All coolers shall be suitable for operating at the same pressure as the evaporators. The supply manifold shall be complete, with the required needle type valves to regulate the flow of water or refrigerant to the various services. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-77 HVAC Issued for Construction 1 June 2004 J. Acoustical Requirements 1. K. Primary Mover Acoustical Performance a. Motor for refrigeration machines, when installed per plans and specifications, shall operate with noise levels not exceeding 90 dBA, with all refrigeration machines operating. b. Noise levels shall be determined in accordance with IEEE Standard No. 85 Test Procedure for Airborne Noise Measurements on Rotating Electric Equipment. 2. Refrigeration Machine Gear Train Acoustical Performance: The gear train assembly (between motor drive and compressor) when operating at the refrigeration machine rated capacity per plans and specifications and tested in accordance with AGMA 295-02 shall have noise levels not exceeding 90 dBA, with all refrigeration machines operating. 3. Refrigeration Machine Acoustical Performance: The maximum permissible noise levels under design operating conditions, when measured in accordance with ARI Standard 575-73 specified methods and qualifications shall not exceed 90 dBA, with all refrigeration machines operating. Accessories 1. Refrigerant Pumpout/Storage System a. Provide self-contained, packaged refrigerant pumpout/storage system(s) to handle 120% of the entire installed charge of one chiller, consisting of a refrigerant compressor with oil separator, storage receiver, water cooled condenser, filter drier and all necessary valves and hoses to remove and replace the refrigerant. All necessary controls and safety devices shall be a permanent part of the system. A minimum of two systems shall be provided in cases where more than one chiller is installed (50% capacity each). b. System(s) shall be suitable in all respect for the refrigerant being provided. Storage vessel(s) shall be provided with an ASME Code cleanout port, approved pressure cutoff and relief valve, designed and stamped in accordance with ASME Boiler and Pressure Vessel Code. c. Vessel(s) shall be horizontal or vertical, as indicated on the drawings. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-78 HVAC Issued for Construction 1 June 2004 2. Refrigerant Monitor: Furnish for installation by others two (2) UL approved refrigerant sensors for each machine, complete with local alarm panel and alarm klaxon(s), all as specified hereinafter in accordance with the requirements of the latest version of ASHRAE Standard 15. a. b. Acceptable Models 1) Mine Safety Appliances, Model "Chillgard IR." 2) Or UL approved manufacturer's standard. Alternate Monitors 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Alternate sensors shall be approved prior to bid and meet the following criteria: a) Monitor shall be compound specific with a measurement and display range 0-1000 ppm. b) The monitor must be calibrated for the specified refrigerant. c) The display accuracy shall be ±1 ppm. d) Three factory-set alarm levels shall be provided, each with a front panel light and a latching binary contact closure for the control of remote devices. e) An analog output corresponding to the unit display is required for connection to the building automation or other recording equipment. f) A means to automatically rezero the instrument must be included. g) Regular maintenance of the unit shall be limited to recalibration once per year and monthly confirmation of clean air source for recalibration. h) Ambient temperature operating range shall be 4°C. to 40°C. i) UL approved device. 15000-79 HVAC Issued for Construction 1 June 2004 L. M. N. Codes and Standards: Materials and workmanship as well as all work in connection with the furnishing and installing of this equipment shall comply with all requirements of the latest issues of all applicable British standards as well as the following Codes and Standards: 1. ASME Boiler and Pressure Vessel Code - Section VIII, Division 1. 2. ANSI - American National Standards Institute. 3. ARI Standard 550: Air Conditioning and Refrigeration Institute for Centrifugal and Rotary Screw Water Chillers. 4. UL: Underwriters Laboratories. 5. ASHRAE 15: Safety Code for Mechanical Refrigeration. 6. NEC: National Electric Code. Inspection and Startup Service 1. Provide a competent, factory service representative (including all travel expenses and accommodations) for final inspection and startup of each centrifugal refrigeration unit. 2. After the installation of the refrigeration machines is complete, perform a thorough inspection of each refrigeration machine, including all controls and electrical and piping connections. Report deficiencies in writing to the Engineer's Representative and the Consulting Engineer. 3. Start up each refrigeration machine in the presence of the Engineer's operating personnel and verify the correct operation of all safety devices, operating controls, and auxiliary equipment. 4. The manufacturer shall add the appropriate labor hours to assist the Engineer’s Commissioning Agent in demonstrating integrated startup procedures. A test plan shall be submitted to the manufacturer’s chiller startup agency four (4) weeks prior to scheduled startup for comments and suggestions. Field Performance Test 1. After each refrigeration unit has been started and run satisfactorily, perform tests to verify efficiency, and the ability to provide rated output. Submit certified report of test data to the Engineer's Representative and the Consulting Engineer. The guarantee period shall begin upon completion of the above to the satisfaction of the Engineer. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-80 HVAC Issued for Construction 1 June 2004 2. Provide all instrumentation required for the performance of the tests. O. Factory Performance Test: After each centrifugal chiller has been assembled at the factory, the chiller manufacturer shall operate each machine for as long as necessary to perform all tests necessary under ARI Standard 550 specified conditions to verify machine efficiency and the ability to provide the scheduled output. All tests shall be witnessed by the Engineer and/or his representative. Submit certified report of test data to the Engineer and Consulting Engineer for approval. P. Instruction of Operating Personnel Q. 1. Provide a minimum of 40 hours of operating and maintenance instruction for ten building operators, with personal on-the-job instruction by factory trained engineers representing the refrigeration machine manufacturer. All travel expenses and accommodations shall be included. This instruction shall be scheduled at time(s) convenient to the Engineer's personnel. Instruction shall cover all equipment and systems provided under this Section. The number of hours is a minimum requirement; where additional hours are specified in other paragraphs of this Section, those hours shall be additive to the minimum above. Instruction shall be comprised of both classroom type and actual hands-on operating experience. Submit an outline of the instruction program and instruction manual to the Engineer for his approval at least two weeks prior to the proposed start date of the instruction sessions. The Engineer may videotape all instruction sessions for purposes of future training. Provide a review and written critique of Engineer's videotape within one month after completion of the instruction sessions and receipt of the Engineer's videotapes. The critique shall correct all mistakes and clarify all outstanding questions which arise during the sessions. 2. Furnish four (4) bound copies of complete operating and maintenance instructions, including lubricating charts, project specific wiring diagrams, spare parts list. Service 1. For the duration of the guarantee period, provide all required service at no additional cost. Service shall include parts and labor and shall be available through an attended telephone number on a 24 hour a day basis with a guaranteed response time as follows: Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-81 HVAC Issued for Construction 1 June 2004 a. Telephone contact of qualified technician within four (4) hours. b. Qualified technician on site within twelve (12) hours. Include as part of the bid package, a preventative maintenance contract to begin on the date of expiration of the free service period. R. 2.18 Alternates 1. State the amount to be ADDED to the Base Contract to provide evaporator and condenser tubes of nominal wall thickness of .035 inch in lieu of the specified wall thickness and indicate any resultant changes in refrigeration machine performance. 2. State the amount to be ADDED to the Base Contract to provide evaporator and condenser tubes of 90/10 cupronickel in lieu of the specified copper tubes and indicate any resultant changes in refrigeration machine performance. 3. State the amount to be DEDUCTED from the Base Contract to provide an alternative means for a permanent pumpout and refrigeration storage system for chiller servicing in lieu of that specified. The alternative system must consist of a storage vessel(s) designed and stamped in accordance with ASME Boiler and Pressure Vessel Code. INDUCED DRAFT COOLING TOWERS A. Furnish and install stainless steel and fiberglass-reinforced polyester (FRP) cooling towers in location as shown on the drawings. Cooling tower capacity and performance shall be as shown in the schedule on the drawings. This Subcontractor shall examine the plans and note the relation of all building structures to the cooling tower, and the cooling tower shall be guaranteed to perform as per schedule requirements with the understanding that the building structure in relation to the cooling tower shall be as shown on the drawings. Maximum drift loss from the tower shall not exceed 2/10 of 1%. B. The tower shall be of the induced draft type with all stainless steel frame, except as otherwise specified herein, 2.75 mm., No. 316 stainless steel basins, and stainless steel sumps, fiberglass-reinforced polyester (FRP) casing panels and inlet louvers, polyvinyl chloride fill, eliminators, stainless steel distribution basin covers, and stainless steel fan discharge extension rings. Fan discharge rings for each cell shall be extended as shown on the plans to align with the top of the architectural roof grating and shall be supported by cooling tower and shall not require any external supports. The cooling tower manufacturer shall provide a basin Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-82 HVAC Issued for Construction 1 June 2004 cleaning piping system and equipment as specified herein to effectively control sludge buildup for the basin configuration of the towers furnished for this project. The overall dimensions and operating weights (including 150 mm. of water in the pan) shall not exceed that shown on the drawings. Each cell shall include a single hot water bottom connection as shown on the plans. C. The cooling tower shall be louvered on two sides. The frame shall be constructed entirely of structural stainless steel capable of withstanding the wind load of 145 kg/sq.m. in any direction. D. The fill and eliminators shall be polyvinyl chloride. Fill shall rest on structural stainless steel. E. The casing walls of the tower shall be constructed of fiberglassreinforced polyester (FRP). F. The louvers shall be constructed of fiberglass-reinforced polyester (FRP) or polyvinyl chloride integral with fill. The supports for the louvered blades shall be fabricated of stainless steel plate not less than 3.5 mm. G. A substantial stainless steel railing shall be provided all around the periphery of the cooling tower louver face side platform and access platforms. Stainless steel ladders, with cage, extending to roof deck of building structure or to the metal walkway around the towers, shall be provided. Entire installation shall be in accordance with OSHA requirements. Provide stainless steel bar grating internal walkway extending from one end wall access door to the other end wall. The walkway shall be supported by a stainless steel framework, and the top of the grating shall be above the cold water basin overflow level. An internal ladder shall extend upward from the plenum walkway to an electrical bar grating platform convenient to the care and maintenance of the tower's mechanical equipment. The platform shall be surrounded by a sturdy handrail and kneerail system. All required rigging gear for the removal and replacement of the motor and gear reducer shall be provided in the interior of the cooling tower. H. Fans shall be manufacturer's standard of stainless steel or monel metal or cast aluminum. Allowable tip speed shall not exceed 64 m./s. Each fan shall be driven through a right angle, double reduction, spiral bevel and helical gear reducer with an American Gear Manufacturers Association Class II rating, at fan horsepower requirements. Special provisions shall be made to prevent entrance of moisture into gear box, and for its elimination from oil system. Each fan discharge shall be provided with approved stainless steel mesh guard, and there shall be permanent arrows showing the direction of fan rotation. There shall be furnished and installed beneath each gear box, a stainless steel pan to catch oil leaks, and each such pan shall be drained to the roof. Valves for the oil fill and drain lines shall be located at the gear box and a length (at least 300 Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-83 HVAC Issued for Construction 1 June 2004 mm.) of wire-shielded flexible pipe shall be installed between the valve and the remainder of the pipe run. An unvalved vent line and an oil level gauge line with oil level gauge shall be extended from the gear box connection to the fan deck. The gauge line should also have a flexible connection at gear box. All lines shall be properly supported with noncorrosive hangers or stands and the pipe or tubing shall be noncorrosive. I. TEFC motors suitable for inverter duty shall be provided. Motor shall have a nameplate rating in excess of the required input to the gears. Starters shall be furnished by this Subcontractor and installed and wired by the Electrical Subcontractor. Each cooling tower cell shall be furnished with a weatherproof vibration cutoff switch with time delay relay and alarm relays. Alarm shall be wired to the remote alarm panel and as described in Section, "Automatic Temperature Controls". J. The distribution system shall include all necessary piping which shall be of stainless steel. Nozzles in distribution basin shall be polypropylene. K. The basin shall be at least 250 mm. high, built of 2.75 mm. No. 316 stainless steel with all joints and connections welded. The basin shall contain a brass make-up float assembly (one per cell) to which the Plumbing Subcontractor shall connect piping for control of cooling tower water makeup. Basin shall be provided with sump arrangements as indicated on the drawings. Sumps to be fabricated of the same material and construction, properly braced as to the balance of the basin. Provide No. 304 stainless steel anticavitation plate and screen for each sump. L. This Subcontractor shall furnish shop drawings showing the size and location of all holes through the dunnage steel. All such holes shall be fabricated from the information on these drawings by the Structural Steel Subcontractor provided he receives these drawings in sufficient time to permit fabrication. Where the drawings are not forwarded to him in time, this Subcontractor shall cut all the required holes at his expense. M. Cooling Tower Painting and Corrosion Protection: All ferrous material, structural steel, iron work, etc., used for the support or construction of the tower or any part of or accessory of the tower, and installed at any location wherein it is completely or partially within the tower shall be hot dipped galvanized after fabrication. Only the gear reducer and motor need not be so treated. All bolts, nuts, and all other hardware shall be of stainless steel. All galvanizing shall be in accordance with ASTM A123-47 Standard Specification for zinc (hot galvanized) coating on structural steel shapes, plates and bars, and standard specifications for hot dipped zinc coated iron and steel products as prepared by the American Hot Dip Galvanizers Association, Inc. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-84 HVAC Issued for Construction 1 June 2004 N. Steel supports as shown on architectural and structural drawings shall be provided under Specifications of other Trades, and any changes (including any engineering and/or architectural fees required for checking of same) required in this steel work to suit the tower furnished under this Section shall be made by the Subcontractor at his expense. O. Vibration isolation shall be as described in Article entitled "Foundations and Vibration Isolation incorporating Seismic Restraints". P. An acceptance test, in Engineer's presence, shall be made within one after installation. Test shall be conducted in accordance with the Acceptance Test Procedure for Mechanical Draft Towers of the ASME Power Test Code PTC-23 (latest edition) or the Cooling Tower Institute, except that ambient wet bulb temperature shall be measured not less than 15 meters from the air intake louvers and the average wind velocity during the test shall not exceed 16 km/h. Should the tower fail to perform in accordance with the guarantee conditions, the Subcontractor shall elect to do one of the following: 1. Make the necessary alterations to the design of the cooling tower to correct the tower deficiency. Include all travel expenses and accommodations for the manufacturer’s representatives. 2. Furnish the additional tower capacity to correct the tower deficiency. 3. Any costs (due to cutting, patching, the removal and replacement or alteration in any way of any existing building structure or equipment, etc.) which may be incurred by the then requisite alteration, etc., shall be borne completely by this Subcontractor. Q. Submit performance curves for the tower, which shall show leaving water temperatures from the tower for the design temperature range and for temperature ranges corresponding to 80%, 60%, 40% and 20% of the design temperature range for wet bulb temperatures of 24°C., 23°C., 22°C., 21°C., 18°C., 15°C., 13°C., 10°C. and 4°C., for design waterflow and for 65% of design waterflow. R. Submit octave band sound power levels at distances of 1.5 m. and 15 m. from the tower inlet and discharge. S. Alternate Price: State the amount to be ADDED to the Base Contract to guarantee all materials and workmanship for a period of five (5) years from the date of Engineer’s acceptance. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-85 HVAC Issued for Construction 1 June 2004 2.19 CONDENSER WATER FILTRATION SYSTEM A. Provide a complete system of filters, pumps, valves, piping, etc., as required to maintain cleanliness in the condenser water system. Equipment shall be installed on a "side-stream" basis, with the capacity to filter the volume of water in the condenser water system approximately 24 times in a 24-hour period. Provide one package for every 2 cells; a total of 2 packages shall be provided. B. Equipment 1. Units shall be Model HMF-42, as manufactured by Process Efficiency Products, Inc., or as approved. Filter system shall consist of a vessel with a single permanent media (sand), prefilter with removable basket, recirculating pump, two brass three-way directional valves for flow control. The components shall be fully assembled, tested and adjusted at the manufacturer's plant, and mounted on a channel iron base. Backflush controls shall be automatic and arranged for system water. Components shall be as follows: a. Filter Tank: ASTM-A7 carbon steel with epoxy lining applied to all interior surfaces to control interior corrosion of the vessel and protective painting applied to the exterior, 685 kPa maximum operating pressure, access manhole and port, with bolted covers provided on the top and side of the tank. Schedule 80 PVC underdrain and overdrain system. Provide automatic air vent, manual vent valve, pressure gauges and a full structural steel skirt for tank support. b. Valve System: Dual tandem mounted brass with chrome ball internals actuated by an electric actuator with its operation initiated by a pressure differential switch. c. Electrical Controls: NEMA-3R rainproof enclosure, with door interlock, overload and short circuit protection, control circuit transformer and motor switch or contacts. A pushbutton shall be provided for manual backwash initiation, preset backwash timer for backwash duration, adjustable pressure switch installed between pump and filter, set to activate backwash function on a rise in pressure of 55 kPa above pressure developed with a clean filter, motorized valve actuator to position flow valves for backwash and backwash lockout for multiple units. Lockout circuit shall include time delay adjustable to 10 minutes to prevent a second unit from backwashing until the backwash reservoir has drained. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-86 HVAC Issued for Construction 1 June 2004 d. Pump: Closed coupled, cast iron body, centrifugal type, with bronze open faced impeller, mechanical seal and supplied complete with basket type prestrainer with removable ABS core and clear cover for easy inspection. 1) 2. 3. Pump Motor: 3.75 kw, TEFC, 415 volt, 3 phase, 50 hertz motor. e. Filter Media: Silica sand, all round grain, Unigran 85 filter media supported on a base of Unifill 475, as furnished by PEP, or as approved, capable of removing 90% by volume of suspended solids 10 microns and larger. f. Equipment Piping: Filter shall be provided with necessary face piping and valves mounted on unit before shipping. Piping shall be rigid Schedule 80 PVC pipe, conforming to ASTM-D-1784, Grade 1 with threaded fittings conforming to ASTM-F-437. Joints shall be made with teflon tape applied to male threads. Face piping shall be 75 mm. ips with flange connections to equipment and valves. Piping a. Provide supply and return piping to connect the filtration equipment and the cooling tower pan. Perforated supply and return piping shall be installed in the pan to duplicate, as much as possible, the normal flow across the pan or basin. Pipe shall have equally spaced 6 mm. holes along the entire length of piping in the pan to give a jet action designed to flush dirt and debris towards the suction piping. The number of perforations and physical arrangement of the pipes shall be in accordance with the manufacturer's recommendations for the filtration equipment and cooling tower selected. b. Piping shall be rigid, Schedule 80 PVC pipe, conforming to ASTM-D-1784, Grade 1 with threaded fittings conforming to ASTM-F-437. Joints shall be made with teflon tape applied to male threads. Surge Tanks: Provide a cross-linked high density polyethylene tank to store backwash water until it can be slowly discharged to the sanitary drainage system. Tank shall be 1,150 mm. diameter x 2,225 mm. high, with a capacity of 2,080 liters. Nalgene Model 41319, or as approved. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-87 HVAC Issued for Construction 1 June 2004 2.20 a. Tank shall be supplied with 75 mm. backwash connection, 75 mm. overflow and 50 mm. drain connection with ball valve piped to funnel drain. b. Provide a B/W Control Co. E-3 probe holder and PVC coated electrodes in tank to lock out the backwash circuit until tank is drained. It shall work in conjunction with a Model 1500G relay. COOLING COILS AND HEAT RECOVERY COILS A. General 1. Provide, where shown on the drawings, chilled water cooling coils and heat recovery coils. All coils shall be manufactured by one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers.” 2. All coils shall be of the continuous tube type and shall have dimensions, number of rows, and capacities, as indicated in the schedule. 3. Each water coil shall be guaranteed to withstand the working pressures shown in schedule on drawings, but not less than 1,200 kPa. All coils shall be guaranteed capable of the schedule performance under the actual job conditions and all coil performance ratings shall be certified by the American Refrigeration Institute (ARI). Coils shall be provided with positive means for completely draining and venting each coil. Each drain and vent shall be piped and valved as shown on the drawings. Each vent and drain outlet shall be fitted with a hoseend valve of the packless type and a pipe cap. Coils shall be mounted in suitably flanged casings. In addition, provide "Pete's plug" or as approved combination temperature/pressure port at inlet and outlet to each coil and coil bank, complete with brass chain and brass cap. 4. Connections to coils shall be as shown on the detail drawings. Automatic valves shall be provided for coils where shown and as detailed or specified. 5. Suitable supports as required to properly mount these coils shall be furnished and erected under this Section of the Specifications. All coil frames shall be reinforced so as to accommodate to coil stacking arrangements as shown on plans. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-88 HVAC Issued for Construction 1 June 2004 B. C. 2.21 Cooling Coils (Water) 1. All cooling coils shall be continuous tube type, copper tubes, aluminum fins, solder coated, with nonferrous headers and 304 stainless steel casings. Tubes shall be seamless copper, 16 mm. o.d., 0.90 mm. wall thickness after attachment of fins. Fins shall be .25 mm. thick. All cooling coils located in the air conditioning supply system casing and/or supply air zone ductwork shall be coated with a baked phenolic coating, similar to Trane Technicoat 10-1, or as approved. 2. A continuous horizontal stainless steel drip pan shall be provided for each coil section in height and each such drip pan shall be independently drained to a drain header at the bottom, as shown on the drawings. Drip pans shall be stainless steel, Type 304. 3. For all air conditioning supply systems, space only shall be provided for future installation of eliminators. Drain pans shall be sized and constructed now to be able to accommodate the addition of the eliminators in the future. Water Heat Recovery Coils: Coils shall be constructed of heavy gauge seamless copper tubing, 16 mm. o.d., 0.63 mm. wall thickness, with 0.25 mm. thick aluminum fins. Tubes shall be expanded or joined in an approved manner to steel headers and connections. Coils shall be mounted in suitably flanged galvanized steel casings. All heat recovery coils located in the air conditioning supply system casing and/or supply air zone ductwork shall be coated with a baked phenolic coating, similar to Trane Technicoat 10-1, or as approved. ELECTRIC HEATING COILS A. Provide, where indicated on drawings, duct type electric air heating coils of the finned tubular or open coil type. All electric heating coils shall be manufactured by one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. B. Electric duct heaters mounted in ductwork and variable volume boxes shall have 80% nickel, 20% chromium open resistance coils insulated by floating ceramic bushings and supported in an aluminized steel frame. Electric duct heaters, mounted in fan casings, shall be finned tubular type with 80% nickel, 20% chromium resistance wire centered on steel tube, which is filled with granular magnesium oxide and copper plated steel fin wrapped around the tube. Heater casing shall be flanged type for installation in ductwork larger than 1,800 mm. in length or 750 mm. in height and slip-in type for installation in ductwork up to and including 1,800 mm. in length or up to and including 750 mm. in height. Ceramic bushings shall be recessed into embossed openings and staked into supporting brackets spaced 90 mm. maximum center to center. Coils Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-89 HVAC Issued for Construction 1 June 2004 shall be machine crimped into threaded terminals and insulated with phenolic bushings. All terminal hardware shall be made of stainless steel. C. All heaters shall be listed by the Underwriters Laboratories for zero clearance to combustible surfaces and for use with central air conditioning units. D. Each heater shall be provided with disc type automatic thermal cutouts for primary protection and load carrying manual reset thermal cutouts for secondary protection. E. Voltage, phase and number of heating stages shall be as indicated on drawings. Three phase heaters shall have circuits equally balanced. F. Duct heaters shall be rated at 48 amps maximum in accordance with National Electrical Code requirements. One set of line terminals shall be furnished for each circuit unless heater draws less than 48 amps total. G. All heaters shall be tested dielectrically at 2000 volts before shipment. H. Heaters shall have the following items built in and prewired at factory: I. 2.22 1. Built-in magnetic contactors, factory prewired to terminal strips for line and control connections in the field. Contactors shall be UL approved for a minimum of 100,000 cycles of operation and one contactor shall be furnished for each heating circuit. 2. Control transformer, 240 volts, fused. 3. Airflow switch. 4. Unfused disconnect switch. 5. Pressure-electric switches. Built-in fuses shall be factory wired to each circuit to protect all ungrounded conductors. FACTORY ASSEMBLED SUPPLY AND RETURN FAN UNITS A. Furnish and install, where shown on the Contract Drawings, required factory assembled supply and return fan units. Each such unit shall include within an integral casing a fan unit, heat recovery coils, cooling coils (supply fan units only), and filters, all of which shall comply with the Specifications for these particular items in Articles "Centrifugal Fans", “Motors”, "Cooling Coils and Heat Recovery Coils" and “Filters” as herein specified. Filters shall be furnished and installed as herein specified and shall be furnished as part of the fan unit. Each unit shall fulfill the requirements shown in the schedule on the Contract Drawings. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-90 HVAC Issued for Construction 1 June 2004 B. Each fan unit shall consist of DIDW fans, each internally spring mounted in individual fan housings. Each unit shall include a welded heavy structural frame for supporting the unit assembly and to which each section shall be fastened. Cabinet casings shall be double-wall construction with not less than 1.3 mm. galvanized steel outer panels and 1.0 mm. thick aluminum inner panels, and shall be arranged with removable side panels. Each casing shall be lined (for thermal and acoustic reasons) with 50 mm. thick, 96 kg/m3 density, mat-faced fiber glass. The interior panels within the fan section shall be perforated aluminum panels with a tedlar liner between the welded perforated panels and the sound-absorbent material. Casing insulation shall have a flame spread and smoke developed rating of less than or equal to 25 and 50 respectively. Insulation shall meet the "Erosion Test Method" described in Underwriters Laboratories, Inc., Publication No. 181. C. Each unit shall be assembled with a heavy angle iron frame construction. Each unit shall include a heavy drain pan of not less than 2.75 mm. stainless steel construction under the cooling coil section and precooling heat recovery coil section, and galvanized steel/aluminum which shall extend from the mixing box section up to and including the fan section. The cooling coil drain pan shall have a drain connection. The cabinet casing shall be double-wall construction with not less than 1.3 mm. galvanized steel outer panels and 1.0 mm. thick aluminum inner panels (Type 304 stainless steel inner panels at cooling coil section), arranged with insulated access doors in side panels for each section. Three empty coil sections shall be furnished as part of each supply fan unit, one between the filter section and the cooling coil section, one between the cooling coil section and the heat recovery coil section, and the other between the heat recovery coil section and the fan section. Each such empty coil section shall be furnished with an access door on either end to permit ready and easy access to the unit. Provide an additional 1,500 mm. access section between the heat recovery coil section and the fan section for units with electric heating coils. D. The fans are to be driven by V-belt drives equipped with belt guards, as described under "Centrifugal Fans". E. Each fan motor shall be sized to drive its respective fan when fan is operating at a speed (due to pulley adjustment) of 5% in excess of that required to meet the fan performance, and when fan requires the maximum power at this speed. No motor shall operate within the service factor range. F. Fans shall be guaranteed to fulfill the specified requirements. Fans shall not produce excessive noise as compared to units of like size and power when used in conjunction with the specified vibration isolation. Fan manufacturers shall furnish for approval for each fan certified sound power ratings with an octave band analysis and also the volume- Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-91 HVAC Issued for Construction 1 June 2004 pressure-horsepower characteristic curves from shutoff to free delivery. Wheels shall have ample strength. They shall be statically and dynamically balanced to avoid vibration, and shall have blades to secure quiet efficient operation. 2.23 CENTRIFUGAL FANS A. Provide, as shown on the drawings, and connect up complete, all supply, return, transfer and exhaust fans. All fans shall be of the nonoverloading centrifugal fan type. Fan wheels shall have backwardly curved blades. Fans shall be of type(s) indicated on the drawings. B. The capacities of the fans shall be in accordance with fan schedules as shown. Fans shall have direction of rotation, discharge direction, arrangement, to suit space conditions; unless otherwise directed, they shall conform to the layouts shown on the drawings. Static pressures listed in the fan schedules are exclusive of drive losses, inlet screens, and variable or fixed inlet vane losses. All motor horsepowers and fan selections shall be sized to deliver the design cfm as scheduled versus the listed static pressure plus the additional static pressure required by the fan manufacturer to compensate for the difference in static pressures between the heating and cooling coils to be provided versus that scheduled, the drive losses per AMCA, inlet screen losses, belt guards and inlet vane losses per published data. Motor selections shall not be based on operating within the service factor range. If the approved fan manufacturer requires a larger motor horsepower than that scheduled, all costs (mechanical and electrical) associated in making that change shall be at no additional cost to the Owner. Prior to consideration of an approval for substitution of any fan manufacturer for the manufacturer scheduled on the drawings, submit the manufacturer's certified performance curves for the main supply, return and exhaust air fans showing the system plot from the scheduled design point down to a cfm equal to 40% of design cfm at approximately 500 Pa water static pressure. Certified performance curves shall also indicate the input kilowatts to the motor at design point and 75%, 60%, 50% and 40% of design cfm. This data shall be submitted as a prerequisite to consideration of approval of a substitute fan manufacturer. C. Fan housing shall be rigidly built and braced. Where fan scroll is 480 mm. or more in width or where called for in schedule or shown on plans for scrolls less than 480 mm. in width, on access door with frame and gasket shall be provided. All access doors shall be so fabricated that the inner surface is flush with the inside of the scroll. Raised frame doors of the pan type shall be provided on all fans where insulation is required. The doors shall be secured to the frame by hand-grip latches and shall be provided with lift handles. Bolted doors are not acceptable except where specifically noted in schedules. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-92 HVAC Issued for Construction 1 June 2004 D. All fans operating against a total pressure of 925 Pa or greater shall be equipped with heavy duty, self-aligning, double row, spherical roller bearings with split pillow blocks, and shall be grease lubricated with Zerk or Alemite fittings. Bearings for fans operating against a total pressure less than 925 Pa w.g. shall be self-aligning, spherical, roller type with split pillow blocks for grease lubrication with Zerk or Alemite fittings. On all Class 1 fans, Arrangement No. 1 and No. 2 heavy duty ball bearings may be furnished. All bearing casings shall be furnished with drain plugs. E. All fans shall be guaranteed to fulfill the specified requirements. Fans shall not produce excessive noise as compared to units of like size and power when used in conjunction with the specified vibration isolation. Fan manufacturers shall furnish for approval for each fan, certified sound power ratings with an octave band analysis and also the volumepressure-horsepower characteristic curves from shutoff to free delivery. Wheels shall have ample strength. They shall be statically and dynamically balanced to avoid vibration and shall have blades to secure quiet efficient operation. F. Fans, unless otherwise indicated, shall be belted to respective motors by V-belt drives. Sheaves shall be cast iron. Motor sheaves shall be adjustable type for 2-groove or less. Drives requiring 3-groove sheaves shall have vari-pitch motor sheaves and companion type fan sheaves. Belts shall have a rated capacity of not less than 150% of brake horsepower. All V-belt drives for integral horsepower motors shall have not less than two belts and shall have sufficient belt capacity to drive fans with one belt broken. Sheave ratio shall be selected so that top fan speed is not less than 105% and not more than 110% of rated fan speed. Drives for fractional horsepower motors may have one belt rated at 200% motor kw. Drives for fans with motors 55 kw and larger may be constant pitch type. If, to balance air in system, a fan speed other than that provided should be required, necessary changes shall be made in Vbelt drive at no additional expense. Provide belt guards in accordance with OSHA requirements for all sheaves and belts. G. Each fan motor shall be sized to drive its respective fan when fan is operating at a speed (due to pulley adjustment) of 5% in excess of that required to meet the fan performance, and when fan requires the maximum power at this speed. No motor shall operate within the service factor range. H. All fans shall carry the AMCA performance and construction seal. I. All fans shall be factory coated with one coat of primer and one coat of machine enamel. The interior of all fans and all fan wheels shall be painted as per manufacturer's standards. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-93 HVAC Issued for Construction 1 June 2004 2.24 J. All fans discharging directly up through roof shall be equipped with 35 mm. casing drains and piped with a shutoff gate valve to nearest floor drain. Kitchen range hood exhaust shall be similarly equipped. K. All fans scheduled to be arranged as belted vent sets shall have overhung wheels and motors mounted on a common base with the bearings. All such belted vent sets shall be furnished with weatherproof motor housings, where located outdoors. L. All fans shall be provided with galvanized steel inlet guard screens, built in accordance with OSHA requirements. Inlet guard screens shall be of such design that they shall not reduce the inlet area of fan beyond the maximum reduction permitted by the fan manufacturer to guarantee the fan performance. M. Submit shop drawings plotting current versus time curves for the fans indicated. Curves shall cover the time period from fan rpm = 0 to fan rpm = design fan rpm. Curves shall be based on the equipment to be installed in the project. This information is required in order to verify and coordinate the overcurrent protection devices in the combination motor starters. Where reduced voltage starting is indicated to be required, the current versus time curves shall include the recommended transition time for optimum acceleration. N. Furnish to motor and motor starter manufacturers pertinent data, such as moment of inertia of high inertia fans, to assure proper selection of motors and starters. AXIAL FLOW FANS A. Provide the required vaneaxial fans where shown on the drawings and of the capacities and types as indicated in fan schedule. B. Fan rotor hub and blades shall be cast aluminum construction. Hub to be cast of aluminum, heat treated, and blades shall be cast of aluminum alloy. Fan blades shall be air foil shaped for maximum efficiency. A blade angle indicator shall be provided to indicate blade position for various pitch settings. Blade tip clearance to fan housing shall not exceed 1.25 mm. for 900 mm. diameter or smaller fan rotor and 2.5 mm. for all other sizes. C. Fan blades shall be automatically adjustable through a pitch range as required by design and specification to vary volume and pressure characteristics across this range. D. Where indicated on schedule, fan blades shall be controllable through a pitch range of sufficient angularity to vary volume and pressure characteristics across design range. Each blade must be index marked for various pitch settings and shall be capable of stepless control across Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-94 HVAC Issued for Construction 1 June 2004 the complete pitch range while the motor is operating at full speed. The pitch of the blades in the controllable pitch rotor shall be varied by a pneumatic actuator provided by the fan manufacturer. For accessibility, the actuator and its associated positioner shall be mounted external to the fan mounted on the fan casing. The actuator shall be controlled by a signal from a remote controller, furnished and installed by others. Controllable pitch mechanism shall be equipped with safety stop to prevent blade pitch settings being increased beyond maximum design setting and overloading motor. Periodic overhaul or routine maintenance shall not require disassembly of the controllable pitch rotor assembly. E. To avoid the possibility of hysteresis and to assure a precise blade angle setting for any given signal pressure, regardless of the direction of travel, the pneumatic actuator must be of the double-acting air cylinder type operating by air pressure in both directions. A spring return type actuator shall not be permitted. The actuator shall be sized to operate on a maximum supply pressure of 550 kPa and change the blade pitch range by means of a 20-100 kPa control signal from the control panel through a pilot positioner. F. Vaneaxial fans shall be direct motor driven as indicated on the drawings and/or fan schedule as follows: 1. Direct driven vaneaxial fans shall be Arrangement No. 4 with motor inside the fan housing and fan rotor assembly attached directly to motor shaft. 2. The fan rotor shall be statically and dynamically balanced on fan motor shaft. 3. Motor shall be equipped with ball bearings AFBMA "PP", with B10 life and Class "F" insulation. Motors shall be rated for 55°C. rise over 40°C. ambient and shall be capable of operation at 95°C. rise. External copper grease leads for lubrication of motor bearings, and to relieve excess grease pressure shall be provided by the fan manufacturer. Motors shall be capable of operating at the voltages specified in the schedules. 4. Fan motors shall be NEMA standard,totally enclosed air over, "C" face, flange mounted, squirrel cage induction, single speed, single winding, continuous duty variable torque, and suitable for operation in either vertical or horizontal or angular position. 5. A conduit box shall be mounted on the exterior of fan casing and lead wires from the motor conduit box shall be protected from the air stream by being encased in an airtight metal conduit pipe. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-95 HVAC Issued for Construction 1 June 2004 2.25 6. Inlet bells with radius inlet screens shall be provided for all vane axial fans. Bells may be aluminum, fiber glass or galvanized steel. 7. The fan rotor shall be whirl tested to 125% of maximum operating speed and shall be statically and dynamically balanced on the fan motor shaft to a maximum tolerance, guaranteed in writing, of 1 mil double amplitude at design operating speed. In lieu of whirl test, manufacturer may provide documented results of x-ray test. G. All vaneaxial fans shall be provided with supports for horizontal or vertical mounting, as shown on plans and shown in schedules. Horizontal and vertical fan supports shall be provided by the fan manufacturer and shall be securely bolted or welded to the housing of the fan. Supports shall be braced with angle braces to prevent misalignment and add structural rigidity. H. The fan manufacturer shall furnish published performance curves, and such data is to be based on tests in accordance with AMCA Standard 210-74. I. The fan manufacturer shall furnish published sound power level data based on tests conducted in accordance with AMCA standards. Such data is to define sound power levels (PWL), re: 10-12 watts for each of the eight frequency bands. PACKAGED AIR CONDITIONING UNITS (CHILLED WATER) A. Provide factory assembled packaged chilled water air conditioning units, with discharge airflow pattern as indicated on the drawings and of capacity and sizes as indicated on the drawings. Packaged A/C unit shall serve Electrical Rooms, Telephone Rooms, Mechanical Rooms, Elevator Machine Rooms, etc. B. The packaged chilled water air conditioning system shall have the following built-in components: 1. All pipe shall be Type "L" copper. All pipe forming shall be tool bent with proper bend radii to prevent tube flattening in the curve. The chilled water piping shall be insulated with closed cell thermal insulation. The chilled waterflow shall be controlled by a 2-way valve (1,200 kPa working pressure) with 24 volt, low voltage modulation motor, completely factory prewired. All pipe connections shall be made at the bottom of the unit for ease of field connection. 2. Cooling Coil/Casing: Chilled water coil/casing shall be A-frame configuration with aluminum fins, copper tube, galvanized steel Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-96 HVAC Issued for Construction 1 June 2004 end plates, and stainless steel drain pan. The coil shall be raised above the condensate drain pan. Coils shall be hydrostatically tested to 2,065 kPa and shall deliver the scheduled capacities. 3. The centrifugal fan shall be dynamically and statically balanced and supported by self-aligning ball bearings designed for a minimum of 200,000 hours life. They shall be arranged for pullthrough operation and be driven by an open dripproof motor, with an adjustable motor base with locking assembly. The drive package shall be two belt, variable pitch, sized for 200% above the fan motor horsepower. Motor types shall be high efficiency as specified under "Motors". 4. Filter chambers shall be an integral part of the system. Filters shall be 40% efficient as measured by ASHRAE's Standard 5276. The filters shall be 100 mm. deep with full depth pleats and shall be serviceable from either end or top of the unit without the use of ladders or special rigging. 5. 304 stainless steel condensate pan shall be furnished with drain connection and trap both in front and to the rear of cooling coil and piped to a common outlet. The pan shall be stainless steel construction with nonferrous connections. The unit shall have a factory installed bottom secondary watertight emergency drain pan. An integral condensate pump shall be factory installed and wired when noted on schedule. 6. A solid state electronic control system shall be field programmable, self-calibrating microprocessor controller board with display to provide all system functions and alarm data modules and shall contain no moving parts. The system shall be provided in a factory wired electric control center. Both the temperature and humidity controls shall have only one adjusting and sensing point for the room conditions. The sensing elements for dry bulb and humidity shall be located in the return air stream. The electric control center and electronic control system shall be serviceable by raising a hinged door on the front of the unit. This panel shall be isolated from the conditioned air stream. Each component circuit shall be individually fused. Starters, contactors, and relays shall be controlled from a 24 volt a.c. circuit. The control system shall consist of: a. Temperature Anticipation: Controller shall anticipate and adjust to changing room conditions to minimize the rate of change of temperature and energy consumption. b. On Board Operator Instructions: The factory mounted display shall indicate a step-by-step troubleshooting procedure for preselected alarm conditions. It shall also Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-97 HVAC Issued for Construction 1 June 2004 provide built-in prompting instructions configuration of the controller. for field c. Run Times: Controller shall store in memory, and display on demand, the running hours of the motor devices (blower and 2-way valves) and humidifier. d. Self-Diagnostics: Controller shall display both the microprocessor control output signal and the mode of operation that room conditions require. The system shall self-check the microprocessor status. e. Restricted Program Access: The microprocessor shall have restricted program access to prevent unauthorized modification of system set points and the system configuration options. The level of access shall be field selectable. f. Easy Service: The microprocessor shall be mounted in an aluminum enclosure inside the air conditioner and shall be connected to all of the unit's wiring via a single edge connector to allow easy installation and removal. The microprocessor shall have individual microfuses for each controller output to a system contactor. g. Remote Communication: The microprocessor shall have an output for connection to a multicontroller or PC computer for remote control and alarm. h. Primary/Secondary Operation: Each microprocessor shall have a capability of switching to a secondary unit upon any of the alarm signals. i. The control system shall monitor by means of factory installed and calibrated equipment (audible alarm, indicator lights, and silencer switch) the following control conditions: High Temperature Loss of Supply Air Dirty Filters NOTE: For units with humidification, system shall also monitor high humidity and low humidity. j. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC The complete system shall also include one set of contacts which shall indicate if any of the above safeties are in alarm for auxiliary alarm connections. The sensing devices for these alarm conditions shall be field 15000-98 HVAC Issued for Construction 1 June 2004 adjustable to meet the required design conditions of the installation. Provide one set of contacts for remote indication. 7. An interlocking disconnect switch shall be provided for each unit and shall be built-in as an integral part of the unit. The disconnect switch shall be completely operable without opening the cabinet and shall have exterior stainless steel trim for appearance. 8. The system shall have pilot indicator lights to indicate need to change filters. Pilot indicator lights shall also indicate stages of high return air temperature, dehumidification and humidification cycles. Each system shall have lighted start/stop button mounted on the front top access panel. 9. Provide an adjustable 150 mm. floor stand to match each unit specified and scheduled. 10. All four sides of the unit shall have insulated panels with 32 kg./m.3 density fiber insulation and shall be quickly removable for easy access to service the equipment. The unit is to be made of tubular steel construction or of heliarc welded structural steel. Units shall be painted to match the computer or the Computer Room decor. Insulation shall be as listed under Article "Insulation". 11. Where indicated on Contract Drawings, those units to be furnished with humidifiers shall be of a self-contained steam generating type with a disposable cylinder constructed of high temperature plastic and containing lattice electrodes. The unit shall be designed to operate without chemical additives on ordinary tap water, and shall have fully automatic, solid-state, energy-saving control circuit to control the humidifier output and automatically compensate for changing water conditions via controlled flush and fill logic. The control system shall allow the humidifier to operate with any water conditions without changing electrode spacings or cylinders and still provide maximum cylinder life. The humidification system shall require no cleaning or maintenance during the cylinder life. The humidification control system shall give the service personnel a visual alert that the humidifier canister requires changing. The steam shall be discharged into the evaporator coil air bypass through a calibrated discharge tube designed to equally distribute the steam into the air stream without condensation. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-99 HVAC Issued for Construction 1 June 2004 12. Where indicated on Contract Drawings, those units to be furnished with electric reheat coils shall have electric resistance heaters sized to offset the sensible cooling capacity in the dehumidification mode and additional humidity due to outdoor air supply to areas served. The reheat elements shall be of low watt density, tubular finned construction with a noncorrosive metal sheath. Each stage of electric reheat shall be three phase, with the load on each leg of the three phase electrical system identical to prevent the possibility of uneven phase balance. The reheat elements shall be electrically and thermally protected in accordance with UL requirements. 13. The unit shall be designed so that the control system and electrical circuitry can be serviced and/or checked while the system is in operation without disturbing airflow and performance. 14. An excessive drop of voltage or power interruption shall disconnect the system until power is restored. Upon return of power, the unit shall automatically restart through an adjustable time delay relay (0-2 minutes). The humidity and temperature controller shall sense temperature in the return air stream of the unit. The automatic temperature control panel shall consist of sail switch, adjustable high return air thermostat and a filter indicating flag. The control panel shall be prewired and tested. 15. Unit shall be fully warranted for a period of five years. 16. Shop Testing/Startup Supervision: All units shall be shop tested for at least three hours with a record of pressures, temperatures, air capacity and electric current and voltage listed and sent with unit. Manufacturer shall provide the services of a direct factory field engineer (not salesmen or agents), including all travel and accommodations to supervise the starting, testing and checking of all units, for a minimum period of three working days. 17. Firestat: Firestat shall be provided, built in, to shut down complete system in the event of a fire. A high temperature return air alarm and silencing switch shall also be provided. NOTE: Each unit shall be provided with a contactor which shall be wired such that any alarm shall be transmitted to the building automation system as a single alarm point. 18. Unit shall be UL tested and listed and laboratory tested in accordance with ASHRAE Standard 37-60 and ARI Standard 210-62. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-100 HVAC Issued for Construction 1 June 2004 2.26 AIR FILTERS A. B. C. Filter Unit 1. All filters shall have an Underwriters Laboratories Class I listing. 2. Provide packaged or built-up combination frame and filter assemblies to receive prefilters and final filters. 3. Holding frames shall be minimum 1.6 mm. stainless steel suitably designed to rigidly support prefilters and final filters and shall be suitably sealed to prevent any air or dirt leakage between individual frames or around and between any particular frame at its prefilter or final filter. Frames shall be universal in design, so that various types of filters may be utilized with only a change in the type of retaining clip. There shall be a minimum of four (4) retaining clips with a spring tension of at least 11 kg. installed for each for high efficiency filter. 4. Provide side service filter housings of stainless steel construction with access doors on both sides and filter tracks to accommodate both prefilters and final filters. The filter housing shall be fully gasketed and employ an easily replaceable filter seal to ensure a good seal in the direction of air flow. Leakage shall be guaranteed not to exceed 125 Pa w.g. at 750 Pa w.g. pressure differential. 5. Filters and frame assemblies shall be the product of one of the listed approved manufacturers. See Approved Manufacturers Article 2.01 of this Specification. 6. Filter efficiencies and rated capacities on atmospheric dust over the life of the filter shall meet ASHRAE Standard 52-76 requirements. Replaceable Construction Filters 1. During construction provide prefilters of the throwaway type upstream of final filters hereinbelow described. 2. Prefilters shall 50 mm. thick, UL Class 2 long strand fiber glass fiber media in a fiberboard casing with retaining grids front and rear. Arrestance shall be greater than 70 percent. Initial resistance shall not exceed 70 Pa at 2.5 m/s. Permanent - Prefilters 1. Provide 100 mm. thick, factory fabricated UL Class 2 pleated prefilters with high lofted non-woven reinforced cotton and Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-101 HVAC Issued for Construction 1 June 2004 synthetic media bonded to a heavy gauge metal backing. Media shall have a minimum thickness of 4 mm. and a media weight of .08 kg./sq.m. Total effective net media area shall be .74 sq.m. per sq.m. of filter face area. There shall be a minimum of 13 pleats per linear foot. Filter efficiency shall not be less than 25-30% with a 5 micron particle efficiency of 95% 2. D. Prefilters shall have an initial resistance of not more than 52 Pa with a final resistance of 125 Pa w.g. High Efficiency Final Filters (Rigid Type) 1. Provide factory fabricated rigid type filters consisting of high lofted glass microfiber media with a pleated, bonded metal backing and corner stabilizers in a galvanized metal enclosure having either diagonal reinforcement or welded galvanized faceguards. 2. Glass fiber media shall be high density microfiber type having a minimum of 1.3 sq.m. of media per sq.m. of filter face area. 3. Final resistance may be up to 300 Pa w.g., initial resistance of 600 m. x 600 m. final filters shall be in accordance with the following: Efficiency (at 1.0 micron) Length Flow Rate Pressure Drop 90 - 95% 300 mm. 945 l/s 170 Pa E. Draft Gauges: Provide a draft gauge across each group of roughing prefilters and final filters to indicate the pressure drop across the roughing prefilters and final filters. The gauges shall be legible to 25 Pa of water pressure with a range of 0 to 750 pa. F. Sand Trap Louver (Sand Filter) 1. Provide self-cleaning sand trap louvers at all outside air intake plenums of sizes as shown on the drawings. 2. Sand trap louvers shall be of mill finished aluminum construction with galvanized wire bird screens. Louvers shall be arranged with vertical opposing baffles with top and bottom channels. Bottom channels shall be provided with sand drain holes. 3. Sand trap louver shall have a maximum resistance of 42 Pa at 1.3 m./s. 4. Louver shall be Model AWSL-WS, as manufactured by Troxtechnik, or as approved. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-102 HVAC Issued for Construction 1 June 2004 2.27 SHEET METAL DUCTWORK A. All construction standards, figure numbers and details referred to are from the SMACNA "HVAC Duct Construction Standards (Metal & Flexible)", Second Edition, 1995. B. Provide all ductwork, sheet metal flues, register boxes, air chambers, dampers, and all auxiliary work of any kind necessary to make the various air conditioning, ventilating and heating systems of the building complete and ready for satisfactory operation. C. While the drawings shall be adhered to as closely as possible, the right is reserved to vary the runs and sizes of ductwork and to make offsets, where necessary, to accommodate conditions arising at the building. D. All ductwork shall be built with approved joints and seams smooth on the inside and a neat finish on the outside. Duct joints shall be made with laps in the direction of airflow; flanges shall not project into the air stream. Ducts shall be adequately braced to prevent vibration; additional bracing shall be provided where necessary. E. Exact dimensions of register boxes must await approval of grilles, and exact locations shall be in accordance with architecturally reflected ceiling plans and shall be submitted for approval; otherwise, any changes directed after installation shall be made without additional cost. All register boxes and other openings of the ductwork must be tightly closed during construction to keep out rubbish. F. Whenever intermediate reinforcing angles are required on 500 Pa water gauge and up (even if only on two [2] sides), they must be connected at the corners. G. All angle irons required for any ductwork construction or support shall be galvanized. H. Any ductwork passing through waterproof wall or roof construction shall be provided with counterflashing. I. All ducts and/or plenums exposed to the weather (i.e., plenums which discharge up through a roof and/or floors of outdoor intake plenums), or as shown on the drawings, up to and including discharge caps, hoods, elbows, etc., shall be built substantially as shown on the drawings, of Type 304 stainless steel or aluminum properly braced and supported, and secured to the building construction. Stainless steel or aluminum ductwork shall be of type, thickness, and construction in conformance with the requirements for 500 Pa water gauge, Class "A" sealed. The bottom of all plenums which discharge up through a roof and/or floors of outdoor intake plenums shall be of welded pan construction with a minimum 500 Pa high lip. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-103 HVAC Issued for Construction 1 June 2004 J. Exposed and concealed ductwork connecting to Pantry hoods, equipment discharging water vapors or serving areas with high vapor content (i.e., humidifiers, dishwashers, driers, showers etc.), and all other ductwork where indicated, shall be built of Type 304 stainless steel in accordance with the requirements for 500 Pa water gauge hereinbelow, and properly braced and supported and secured to the building construction. Horizontal ductwork shall be of pan construction with longitudinal seams at the top. All transverse joints of such ducts shall be welded. Bracing of ducts shall be as specified for galvanized iron ducts except that angles, screws and hangers shall be of nonferrous steel. Ductwork shall be watertight. Type 304 stainless steel ductwork shall be provided for a minimum distance of 600 m. upstream of humidifier grid and a minimum distance of 2,400 mm. downstream of humidifier grid. K. All gaskets and sealants shall comply with DW 144 Part 7 Section 27 or DW 151 Section 12 as appropriate and must conform with NFPA requirements of flame spread rating not to exceed 25 and smoke developed rating not to exceed 50. L. Rectangular Duct Joinery and Fabrication 1. Pittsburgh Lock seams shall be minimum 10 mm. 2. The following longitudinal seams are not permitted: a. b. c. 3. Button Punch/Snap Lock (L-2) Standing Seam (L-4) Single Corner Seam (L-5) The following transverse joints are not permitted: a. b. c. d. e. f. g. Lap (T-4) Reinforced S Slip (T-7) Standing Seam (T-15) Reinforced Standing Seam (T-16) Pocket Lock (T-17) Reinforced Pocket Lock (T-18 and T-19) Capped Flange (T-20) 4. Where manufactured transverse joints are used (SMACNA T25a, T-25b, i.e., Duct Mate, TDC, TDF, etc.), they shall be submitted with the manufacturer's standards for construction and installation and installed in accordance with those standards. 5. Tie rod attachments shall be installed in accordance with Figures 1-2 and 1-3, except that attachments D, E and F shown in Figure 1-2 shall not be installed in the field. Only tie rod attachments A, B, C and G shown in Figure 1-2 and all details shown in Figure 1-3 are permitted on return air ductwork. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-104 HVAC Issued for Construction 1 June 2004 6. M. N. O. All unlined duct shall be cross broken or beaded in accordance with the requirements in Figure 1-8. Rectangular Duct Fittings 1. Branch connections shall be made with 45 degree flare connections as shown in Figure 2-6, with complete metal-tometal contact, as noted. 2. Full radius elbows shall be used in all ducts with air velocities in excess of 10 m/s and wherever possible in all other ducts. Radius elbows shall be Type RE-1, RE-3 or RE-5 as shown in Figure 2-2. 3. Where full radius elbows cannot be installed in high velocity ducts (above 10 m/s) due to space restrictions, smaller radius elbows utilizing turning vanes may be used, providing that turning vanes are constructed in accordance with Figure 2-3. Square elbows shall not be used. 4. Where square elbows are used in low velocity ducts (below 10 m/s), single-thickness turning vanes shall be installed in accordance with Figure 2-3. Vanes shall be installed through the runner, with blades welded to the runner. Round and Oval Duct Joinery and Fabrication 1. Round oval ducts shall be: Spiral Seam (RL-1) or continuous butt or lap welded (RL-4) as shown in Figure 3-1. Seam Types RL-2 and RL-3 may be used in accordance with Class I sealing requirements. 2. Transverse joints shall be Beaded Sleeve Type Rt-1 or Van Stone Type Rt-2 as shown in Figure 3-2. Round and Oval Duct Fittings 1. Round and oval duct branch connections to round, oval or rectangular ducts shall be made with conical or bellmouth connections as shown in Figure 2-6, 90 degree tee oval to round taps or 45 degree laterals as shown in Figure 3-4 or conical connections as shown in Figure 3-5. 2. Round elbows shall be stamped, segmented or segmented standing seam as shown in Figure 3-3. Segmented elbows shall have a minimum of five segments. 3. All changes from square to round or round to square must be made with formed transition pieces. Transition angle shall be 15 degrees or less. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-105 HVAC Issued for Construction 1 June 2004 P. Q. Supply Duct Construction Classifications Basement, Auditorium, 5th Floor Administration and Education Wing 1. All longitudinal seams shall be made with 10 mm. Pittsburgh. 2. Headers and ductwork in Machine Rooms, distribution supply air ductwork up to inlet of VAV and FP boxes, risers and takeoff up to and including floor shutoff damper in the Education Wing, 1,000 Pa, Class "A" sealed (transverse joints and longitudinal seams caulked) minimum .70 mm. 3. The main supply headers and ductwork in the Machine Rooms shall be constructed of two layers of galvanized steel sheets in a panel construction with a minimum of 50 mm. thick, 48 kg./cu.m. density thermal insulation (similar to Owens Corning "Duct Liner Board") sandwiched between. The outer layer shall be minimum 1.6 mm., the inner layer perforated, minimum 1.0 mm. Panels shall be provided with integral capped and sealed joints, suitable for continuous use out-of-doors. Refer to Article "Acoustic Treatment" for additional requirements. 4. Distribution headers on 1st and 2nd Floors of the Education Wing from floor shutoff dampers to inlet to VAV/FP box shall be 500 Pa Class "A" sealed (transverse joints, longitudinal seams and branch connections caulked) minimum .70 mm. 5. Ductwork downstream of box shall be 250 Pa Class "C" sealed (transverse joints and branch connections only caulked) minimum .55 mm. Supply Duct Construction Classifications (Galleries, Atrium and Restaurant) 1. Headers and ductwork in Machine Room, distribution ductwork, risers and takeoff up to and including floor shutoff damper, and/or slot air distribution dampers, 750 Pa, Class "A" sealed (transverse joints and longitudinal seams caulked) minimum .70 mm. 2. The main supply headers and ductwork in the Machine Rooms shall be constructed of two layers of galvanized steel sheets in a panel construction with a minimum of 50 mm. thick, 48 kg./cu.m. density thermal insulation (similar to Owens Corning "Duct Liner Board") sandwiched between. The outer layer shall be minimum 1.6 mm., the inner layer perforated, minimum 1.0 mm. Panels shall be provided with integral capped and sealed joints, suitable for continuous use out-of-doors. Refer to Article "Acoustic Treatment" for additional requirements. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-106 HVAC Issued for Construction 1 June 2004 3. R. S. T. Distribution headers on 1st, 2nd, 3rd, and 4th Floors of Galleries from floor shutoff dampers to inlet to air distribution devices shall be 500 Pa Class "A" sealed (transverse joints, longitudinal seams and branch connections caulked) minimum .70 mm. Field erected casings and plenums shall be constructed as follows: 1. The suction and discharge of return fans and exhaust fans (except Kitchen exhaust fans) shall be constructed in accordance with 750 Pa water gauge load classification per Table 6-1. 2. Casings for the supply fan systems from the outside air intake ALD up to the system discharge shutoff damper shall be constructed in accordance with 1,500 Pa water gauge load classification per Table 6-1. 3. Casings and/or plenums which have sheet metal floors shall be constructed with additional bracing to support maintenance personnel. 4. Casings between louvers and automatic dampers shall be constructed in accordance with 750 Pa water gauge load classification per Table 6-1. Return and Exhaust Duct Construction 1. For local ducted return or exhaust systems (except kitchen exhaust) 250 Pa Class "C" sealed. 2. Return risers and exhaust risers, and distribution headers from risers to inlet of return and exhaust fans, 500 Pa Class "A" sealed. Kitchen Hood Exhaust Duct Construction 1. Ducts shall be carbon steel with continuously welded longitudinal seams and transverse joints. All branch duct connections shall also be welded. Duct thickness shall conform with the following: Areas up to 1,000 sq.cm. 1.5 mm. Areas 1,005 sq.cm. to 1,290 cm 1.9 mm. Areas 1,295 sq.cm. to 1,645 sq.cm. 2.6 mm. Areas greater than 1,645 sq.cm. 3. 4mm Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-107 HVAC Issued for Construction 1 June 2004 U. V. 2. Kitchen hood exhaust ducts shall pitch upward in the direction of airflow in accordance with the requirements of all governing codes. 3. All kitchen hood exhaust risers shall be provided with a drip collector located at heel of the riser elbow. 4. All branch connections to kitchen hood exhaust ducts shall be located a minimum of 40 mm. above the bottom of the duct. 5. Raised access doors shall be provided 6 meters on centers and at all changes in direction. Access doors shall be 450 mm. by 450 mm. minimum except where limited by duct dimensions; in such cases, the opening shall be large enough to permit cleaning. However, the minimum horizontal dimension shall be 450 mm. Access doors shall be located a minimum of 40 mm. above the bottom of the duct. Acoustically Lined Ducts 1. Dimensions for acoustically lined ducts are clear inside dimensions. Acoustic lining is to be attached with Type 2 or 3 weld pins as shown in Figure 2-20. 2. The leading edge of all acoustical lining shall be protected with metal nosing as shown in Detail "A" of Figure 2-19 and in Figure 2-22. 3. Hat sections as shown in Figure 2-21 shall be provided at all automatic dampers, balancing dampers and turning vanes in high velocity ducts (above 10 m/s). Equipment Connections 1. Inlet duct connections to air volume regulating devices (i.e., VAV boxes, fan powered boxes, constant volume regulators, etc.) shall be made with hard duct with a minimum straight length of 3 duct diameters, but not less than 900 mm. Flexible ducts are not permitted. 2. All branch ducts to diffusers are to be provided with balancing (volume) dampers as shown in Figure 2-14. Dampers are to be located near the branch duct take-offs as far as possible from the drop to the diffuser. 3. Round drops to diffusers shall be insulated and shall be made with spin-in collars as shown in Figure 3-8, Figures D or E. Square drops to diffusers shall be made with clinch connections. All diffuser connections shall be gasketed and have a minimum Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-108 HVAC Issued for Construction 1 June 2004 20 mm. overlap. Round duct shall have grooved seam, pipe lock or flat lock longitudinal seams. The final connections to diffusers may be made with 300 mm. of insulated flexible duct (maximum offset 10 degrees). Insulation of flexible ducts shall not be less than 20 mm. thick, 24 kg./m.3 density, faced on air side of type approved by NFPA. W. Hangers and Supports 1. All methods of attachment to the building structure shall be of the type approved and described in Article "Hangers, Anchors, Supports and Guides." Methods of attachment must be submitted to the Structural Engineer for approval. Expansion nails, power and/or power actuated devices shall not be permitted. 2. Rectangular and flat oval ductwork shall be supported in accordance with Table 4-1, except that wire shall not be used and the maximum hanger spacing shall not exceed 2.4 meters. 3. Round ducts shall be supported in accordance with Table 4-2, except that wire shall not be used and the maximum hanger spacing shall not exceed 3.0 meters. 4. Where the width of the duct exceeds 1,200 mm., the hanger shall be bent under bottom of ducts and fastened to bottom as well as to sides. 5. Additional hangers shall be provided for all acoustically lined double wall ducts. 6. Where ducts are stacked, they shall be independently supported as above. 7. Particular care shall be taken to support large and heavy ductwork in a manner approved by the Engineer, including the providing of supplementary steel, if required. Shop drawings, indicating support methods, point loadings to the building structure, and hanger locations shall be submitted to the Structural Engineer for review sufficiently in advance of concrete pouring schedules to permit evaluation, critique and any necessary changes of hanging and support methods. If additional hangers, inserts and/or supplemental steel are required, such hangers, inserts and/or supplemental steel shall be provided at no additional cost to the Owner. 8. Where horizontal ducts are required to be enclosed in dry wall, etc., such enclosures shall not be supported from the duct hangers. Supports for such enclosures shall be provided by the Trade responsible for the installation of those enclosures. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-109 HVAC Issued for Construction 1 June 2004 X. Y. Fire Dampers/Fire Smoke Dampers 1. Where fire dampers and/or fire smoke dampers are installed in ducts constructed to SMACNA standards for pressures below 500 Pa water gauge and manufactured transverse joints are utilized, the corner clips or corner bolts are to be eliminated and plastic clips are to be installed -- not metal clips. If plastic clips are not available, sleeves shall be minimum 1.6 mm. for ducts having dimensions less than 600 mm. high and less than 900 mm. wide. For ducts having dimensions greater than 600 mm. high or 900 mm. wide, sleeves shall be minimum 2.0 mm. 2. Where fire dampers and/or combination fire/smoke dampers are installed in ducts constructed to SMACNA standards for pressures 500 Pa water gauge and greater, breakaway connections shall not be used. Sleeves shall be minimum 1.6 mm. for ducts having dimensions less than 600 mm. high and less than 900 mm. wide. For ducts having dimensions greater than 600 mm. high or 900 mm. wide, sleeves shall be minimum 2.0 mm. 3. Fire and/or fire smoke dampers shall be installed in accordance with UL Standards 555 and 555S respectively. Required Access Doors 1. Provide access doors as specified in Article "Access Doors" to permit inspection, operation and maintenance of all valves, coils, controls, fire dampers, splitter dampers, backdraft dampers, automatic dampers, filters, bearings or other apparatus concealed behind the sheet metal work. 2. Each sheet metal chamber shall be provided with access doors in locations shown on the drawings. The doors shall be made with inner and outer shells 50 mm. apart so that they may be properly insulated and properly operated and shall not be smaller than 500 mm. wide x 1,500 mm. high. Door hardware shall be: Ventlok No. 310 cast zinc door latches operable from both sides, or as approved, two per door; Ferum Co. No. 245 extra heavy, zinc plated, 150 mm. T hinges, or as approved, minimum two per door. The doors shall be provided with rubber gaskets so as to make them airtight. Provide reinforcing angles above and below access door frames to stiffen casings. Doors at fan plenums must be large enough to facilitate removal of motors but not less than listed above. All access doors must open against the system pressure. 3. Provide access doors and frames where specified and shown on plans. Minimum size 450 mm. x 450 mm. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-110 HVAC Issued for Construction 1 June 2004 2.28 4. Access doors in insulated ducts shall be double panel insulated of not less than 1.0 mm. Access doors in uninsulated ducts may be of single panel construction of not less than 1.3 mm., galvanized steel, and shall have sponge rubber gaskets around their entire perimeter. 5. Each access door shall be provided with retaining wires or chains, a minimum of four window type latches to allow complete removal. ACCESS DOORS A. Provide access doors and frames to permit inspection, operation and maintenance of all valves, controls, fire dampers, automatic control dampers, filters, humidifiers, bearings, traps or other apparatus concealed behind the sheet metal work shall be provided. All such doors in insulated ducts shall be double panel insulated of not less than 1.0 mm. Access doors in uninsulated ducts may be of single panel construction of not less than 1.3 mm., galvanized, and shall have sponge rubber gaskets around their entire perimeter. B. All access doors in ductwork shall be hung on separate frames on heavy flat hinges and shall be secured in the closed position with Ventlok No. 100 cast zinc latch. A minimum of four heavy window-type latches shall be provided, except on doors 450 mm. x 450 mm. and larger on high velocity air systems where two latches per side shall be furnished. All required gasketing shall be provided for all access doors to make them airtight. C. In no case shall access to any items of equipment requiring inspection, adjustment or servicing, require the removal of nuts, bolts, screws, wingnuts, wedges, or any other screwed or loose device. It is the intention of this Contract that all access doors shall be latched and made airtight. Quantity of latches shall be as stated above and as required to make for an airtight fitting and as approved. D. Access doors into ducts shall in general not be smaller than 450 mm. x 450 mm., except where duct sizes prohibit. In such cases, two access doors are to be installed. Access doors shall be provided at all splitter dampers, upstream and downstream of all electric strip heaters, at all fire dampers, smoke dampers, combination fire/smoke dampers, damper actuators, valves, and automatic and backdraft dampers, etc. Quantity of access doors shall be determined by size and construction of fire dampers and requirements for resetting damper linkage. E. Furnish buttons or tabs to job site for setting, as approved by Engineer, to indicate location of valves, dampers or other equipment located above removable type ceilings where access doors are not furnished. F. Access doors shall be constructed of the same material as the duct or system in which they serve. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-111 HVAC Issued for Construction 1 June 2004 2.29 ACCESS DOORS IN FINISHED CONSTRUCTION A. Furnish access doors as required for all concealed valves, dampers, variable and constant air volume boxes, controls, cleanouts and other elements requiring access above ceilings or behind walls or as indicated on the drawings. Coordinate the work and assume responsibility for the accessibility of all valves, etc. B. Use the following type doors as manufactured by Karp Associates, Inc. 1. In plaster ceilings, KARP DSC 210-PL. 2. In 2 hour masonry enclosures (pipe or duct shafts), KARP KRP150FR. 3. In nonrated masonry, KARP DSC-214M. 4. In drywall construction, KARP DSC-214M. 5. In drywall construction, 2 hour fire rating, KARP KRP-150FR. C. Door and frame shall be given a prime coat of corrosion-resistant paint at the factory. D. Size access doors as indicated on the drawings, or as specified, but not smaller than 400 mm. by 400 mm. Install all valves to fit within the limit of the following size access doors; where two or less valves are located with their bonnets within 300 mm. of the face of the door and all portions of the valves are within the area defined by the opening in the door, 400 mm. x 400 mm. doors may be used. Where more than two valves are served by a door and the bonnets are within 300 mm. of the face of the door, the size of the door shall be increased so that all portions of the valves are within the area defined by the opening in the door. Where the bonnets of the valves are more than 300 mm. from the face of the door, the doors shall have a minimum of 500 mm. x 500 mm. clear opening. E. Construction: 1. General: Factory made, completely flush, heavy metal as manufactured by Karp Associates, Inc. 2. Frames: Welded, minimum 1.9 mm. steel, mitered corners ground smooth, anchors. 3. Doors: Minimum 1.9 mm. steel, heavy hinges flush with frame, invisible when closed, wing type airplane catches; no bolts, screws, nuts or other loose device required for opening of door. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-112 HVAC Issued for Construction 1 June 2004 2.30 DAMPERS A. Fire dampers suitable for installation in dynamic systems shall be installed in all ducts piercing fire-rated shafts, walls or floors. Fire dampers shall be dynamically rated for closure against air flow in both vertical and horizontal mounting configurations and shall be rated to close against 2,000 Pa water gauge maximum, across closed damper. Fire dampers shall meet the requirements of, and be manufactured in accordance with, UL 555. All fire dampers shall meet all NFPA requirements. Dampers shall be installed in accordance with manufacturer’s UL listing requirements. Heat responsive links shall meet the requirements of, and be manufactured in accordance with, UL 33. B. Combination smoke/fire dampers suitable for installation in dynamic systems shall be installed in all ducts piercing fire-rated shafts, walls or floors. Combination smoke/fire dampers shall be dynamically rated for closure against air flow in both vertical and horizontal mounting configurations. Dampers shall be rated to close against 2,000 Pa water gauge maximum, across closed damper. Combination smoke/fire dampers shall meet the requirements of, and be manufactured in accordance with, UL 555S for Class II leakage at 175°C. All combination fire smoke dampers shall meet all NFPA requirements. Dampers shall be installed in accordance with manufacturer’s UL listing requirements. Heat responsive links shall meet the requirements of, and be manufactured in accordance with, UL 33. Damper operators shall meet the requirements of, and be manufactured in accordance with, UL 325 and/or UL 1004. Dampers and damper operators shall be furnished by the Automatic Temperature Control Subcontractor and installed by this Subcontractor. Size of damper and location of actuator shall be coordinated with and approved for use with the Building Automation System and/or Building Fire Alarm System. C. Volume dampers, as shown on the drawings and as required, shall be installed in the various branches of the ductwork to be used in balancing the system. Note that these dampers shall be separate and independent from the registers hereinafter specified to be set behind supply and/or return air grilles. Multiblade dampers shall be provided in large ducts. Volume dampers shall be provided in all supply, return and exhaust branch ductwork, and where indicated on the drawings. D. Volume dampers shall be of the quadrant type, of heavy construction, pivoted to turn easily, and provided with approved operating and locking devices, mounted on outside of the duct in an accessible place. Details as directed. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-113 HVAC Issued for Construction 1 June 2004 2.31 E. Backdraft dampers shall be self-operating, counterbalanced (adjustable) type. Frames shall be 19 mm. x 100 mm. x 19 mm. galvanized channel steel on all four sides. The blades shall be at least 2.75 mm. galvanized steel and shall have blade brackets with tie bar of 30 mm. x 30 mm. galvanized steel. The pivot rods shall be 12 mm. diameter cadmium plated steel. All bearings for the pivot rods and for tie bar shall be of the self-lubricating type. The blades shall have bulb type vinyl stripping on edge for tight closing. Maximum blade length shall be 1,120 mm.; multiple sections shall be used with the frame’s full height for stability. Dampers shall have a maximum leakage of 1% of the design airflow across such damper with the damper closed against 1,500 Pa w.g. pressure across the face. Dampers shall be installed with suitable reinforcing at wall to which they serve so as to maintain their integrity at the design. The damper manufacturer shall review the fan systems and static pressures to ensure that the construction of the damper is adequate, that the dampers shall operate properly without fluttering, and shall open and close under all system operating conditions. F. All dampers shall be constructed of the same material as the duct system in which they are installed, and SHALL BE suitable for the same pressure class and duct velocities. G. Dampers furnished by the Automatic Temperature Control Subcontractor, as indicated on the drawings, in air inlet ducts, discharge ducts, supply air ducts and/or plenums, of supply air fans, exhaust fans, return air fans, etc., or as directed, shall be installed by this Subcontractor. Damper banks consisting of multiple damper sections shall have vertical intermediate 3.5 mm. galvanized steel stiffeners every 1,200 mm. as part of the damper assembly. FLEXIBLE CONNECTIONS A. Fan Flexible Connectors 1. Fan connections, both at inlet and discharge, shall be made with flexible material so as to prohibit the transfer of vibration from fans to ductwork connecting thereto. Connections shall be made of heavy glass fabric and double neoprene coated (type "Ventglas") for conventional systems, except as otherwise required by authorities having jurisdiction and except as otherwise noted below. 2. The flexible connections shall be approximately 150 mm. long and held in place with heavy metal bands or double hemlock securely attached to prevent any leakage at the connection points. 3. The flexible connections at the discharge ends of the fans for the medium pressure air conditioning systems shall be type Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-114 HVAC Issued for Construction 1 June 2004 "Ventglas" fiber glass, of lengths noted above and fastened as above. It is the intent that these flexible connections shall withstand the operating air pressure, shall not permit air leakage and shall not transmit vibration. 4. All materials shall be as manufactured by Ventafabrics and listed and labeled by Underwriters Laboratories, Inc., for a Fire Hazard Classification, as tested under ASTM, NFPA, or UL procedures, not to exceed the following: Flame Spread Fuel Contributed Smoke Developed B. Air Distribution Flexible Connectors 1. Upstream Side of Fan-Powered Boxes and VAV Boxes: No flexible duct connections shall be permitted upstream or downstream of fan-powered boxes and VAV boxes. This Subcontractor shall install a minimum of 900 mm. of straight rigid duct or the equivalent of four (4) inlet diameters, whichever is greater, to the inlet of each fan-powered boxes and VAV unit. 2. All materials shall be listed and labeled by Underwriters Laboratories, Inc., for a Fire Hazard Classification, as tested under ASTM, NFPA, or UL procedures, not to exceed the following: Flame Spread Fuel Contributed Smoke Developed 2.32 25 50 50 25 50 50 GRILLES, REGISTERS AND DIFFUSERS A. Provide, where shown on the drawings, all metal diffusers, grilles and registers of sizes indicated or of equivalent areas as approved. B. All supply ceiling diffusers, unless otherwise noted on the drawings, shall be Anemostat Type “Paragon,” PGD-B (square), CM-1P (round), or as approved. Each supply air ceiling diffuser shall be furnished with air directional control and air volume control devices. See drawings for schedule of sizes. The method of attachment of the diffuser (supply and return) to the ceiling system and the type of margin shall be compatible with the type of ceiling system approved for installation on the job. Coordinate with other Trades. All supply registers shall be of the double deflection type with opposed blade dampers, with the damper operated by a removable knob through lever and cam. Supply registers shall be Anemostat Type S2HO, unless otherwise noted on drawings, or as approved. Refer to diffuser schedules for exact types, sizes, etc. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-115 HVAC Issued for Construction 1 June 2004 C. Return and exhaust registers Anemostat “S3HOD” and grilles Anemostat type S3HD, where called for on drawings, shall be of fixed single deflection type with opposed blade dampers, with the damper operated by a removable knob through lever and cam. Registers shall be as scheduled on plans under grilles and registers, or as approved, with clips and/or flange holes and screws (as required by architectural finishes) to secure registers to ceiling construction and/or exposed ducts as required. Face bars shall be inclined 30 degrees having not less than 86% free area. Round return and exhaust registers shall be Anemostat “CM-1P”, or as approved. D. Linear type ceiling/wall diffusers and grilles shall be Anemostat type SLAD-75 (ceiling), type AL-1 (wall), where shown on drawings, shall be of extruded aluminum construction with finish as indicated. They shall be furnished with air volume pattern control devices and frames where required. Volume dampers located in the branch duct serving the supply plenum over the diffuser shall be operable through the face of the linear diffuser which it serves. E. Extruded aluminum linear diffusers and grilles, complete with blank-off sections and dampers, where required, shall be provided where indicated on the drawings. Linear diffusers shall be provided with mounting frames to match ceiling or wall, or as approved. Actual total lengths of units shall be field verified. Active lengths shall be as indicated on the drawings. F. All registers, grilles and diffusers shall be furnished with matte enamel finish. Color shall be as selected and approved by the Consulting Engineer. G. All grilles, registers and linear diffusers in plaster construction shall be furnished with plaster frames. Plaster frames shall be properly identified and turned over to the Contractor for installation. H. Each air supply outlet shall have the capacity as noted on the drawings and shall be guaranteed to give the required throw with draftless diffusion. Where manufacturer's recommendations require duct sizes differing from those shown on the drawings, provide same at no additional cost to the Owner. All registers and diffusers shall be provided with directional and volume controls specified, and shall be of such dimensions (including the accessory equipment) as to conform to the building space conditions. I. All grilles, registers and diffusers located over showers or steamproducing appliances shall be aluminum covered with a coat of Eisenheis epoxy paint. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-116 HVAC Issued for Construction 1 June 2004 J. A schedule and samples shall be prepared and submitted to the Engineer showing the sizes and model numbers of all grilles, registers and diffusers before they are ordered for installation. K. Acoustical Performance 1. It is the intent of the Specification that the manufacturer shall furnish units that shall permit attaining sound pressure levels in spaces conforming to NCR-35 curves (except as noted hereinbelow) as explained in 1984 and later issues of the ASHRAE Guide. Auditorium, Library, Prayer Room, Study Room Lecture Rooms and Conference Rooms NCR-30 Exhibition Galleries and Private Offices NCR-35 Atrium, Toilets, Storage NCR-40 Open Office Space, Corridors 2. Octave Band 1 2 3 4 5 6 7 8 NCR-40 to 45 Restaurant, Cafe NCR-45 Kitchen, Food Preparation NCR-50 The maximum permissible sound power levels for grilles, registers and diffusers are as follows: Mid-Frequency (cps) 63 125 250 500 1000 2000 4000 8000 NCR-30 59 52 45 41 38 37 36 37 Max. PWL re: 10-12 Watts NCR-35 NCR-40 NCR-45 62 66 68 56 60 63 49 54 58 46 51 56 43 48 53 42 47 52 41 46 51 42 47 52 NCR-50 70 66 62 61 58 57 56 57 3. The terminal device manufacturer shall submit to the Consulting Engineer's representative guaranteed sound power levels by octave bands. This data submitted shall substantiate that the equipment types and sizes operating as in an installed condition per plans and specifications shall conform with the above. Neither the manufacturer nor the specific unit selection shall be approved until such data has been submitted. 4. The terminal devices shall be tested in accordance with ADC Standard 1062-R.3. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-117 HVAC Issued for Construction 1 June 2004 5. 2.33 Should the Engineer desire that units as furnished under this Section be checked for conformance to the above guarantee, the cost of such test shall be paid for by the Owner. If the unit furnished and subsequently tested does not conform to the above guarantee, the cost of the test and the cost of any corrective measures shall be at no additional expense to the Owner. The testing, if required, shall be performed at manufacturer's factory and observed by the Consulting Engineer. VARIABLE AND CONSTANT VOLUME BOXES (DDC) A. Provide low terminal pressure units, as shown on the plans. Unit casings shall be galvanized steel complying with ASHRAE and SMACNA construction standards, with sandwiched thermal and sound attenuating rigid insulation. Thermal and acoustic insulation material shall have a flame spread and smoke developed rating of less than or equal to 25 and 50 respectively and shall comply with the requirements of NFPA Bulletin 90A. Units shall be constructed in accordance with dimensional constraints indicated on the drawings. B. Leakage through the unit casing shall be less than 3% of design volume at 6 inch inlet pressure. C. All VAV and constant volume terminal units shall be of the distributed direct digital control technology type. The direct digital controller (DDC) and its associated wall mounted temperature sensor, power supply communications ports, terminal strips, etc., shall be furnished to the successful terminal unit manufacturer for factory installation and testing at the terminal manufacturer's facility. The DDC unit and appurtenances shall be furnished under another Section of the Specifications. D. All final mounting, wiring, testing, etc., to make the terminal units completely operational shall be the responsibility of the terminal unit manufacturer. All work associated with same shall be closely coordinated with the Building Automation and Temperature Control Subcontractor. E. The DDC controller and its associated power supply, transducers, electric damper operator, etc., shall be neatly mounted within a separate 1.0 mm. sealed and gasketed galvanized sheet metal enclosure, mounted directly to and supported from the terminal device to which it serves. All external electrical connections to the DDC controller within the box shall be terminated in two separate junction boxes (with removable covers), i.e., one for power and one for signal communications. All wiring and tubing shall be permanently labeled and color coded for ease of identification. No access to within the enclosure shall be required for installation, startup or operation of the terminal unit. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-118 HVAC Issued for Construction 1 June 2004 F. Terminal units shall be pressure independent and shall be capable of reset of air volume within plus or minus 5% of required airflow (as determined by the space temperature sensor) regardless of changes in system air pressure. A multiple arm (minimum 4) flow traversing unit shall be used and the means of sensing airflow shall be incorporated within the unit and shall provide control signal pressure for the cfm to the DDC controller. Separate differential pressure taps shall also be provided for airflow measurement with a 0-250 Pa. Each terminal unit shall be provided with a flow chart attached. Maximum and minimum cfm setting shall be factory set but shall be capable of easy readjustment in the field. Terminal units shall be capable of operating as described above at inlet static pressures between 12.5 Pa and 1,500 Pa. Units shall be selected to operate at a static pressure loss through the unit between 12.5 Pa and 62 Pa (maximum). G. Electronic actuator and accessories to operate the terminal unit between maximum and minimum limits as determined by the space temperature sensor and controller shall be provided by the DDC unit manufacturer, installed and tested by the terminal unit manufacturer at the factory. Minimum limit unless otherwise noted shall be to shutoff (maximum leakage of 5% of design airflow with an inlet pressure of 1,500 Pa). Actuator and all accessories shall be mounted in easily accessible enclosure, completely wired, requiring only power. Space temperature sensor and controller shall be furnished under the Automatic Temperature Control Section of the Specifications. Terminal units shall be normally open upon loss of control signal unless otherwise noted. H. This Subcontractor shall coordinate with the Automatic Temperature Control Subcontractor regarding the quantity of power required per VAV box and also as to the quality of the power (voltage limits, etc.). A letter stating the above requirements shall be submitted by this Subcontractor in conjunction with the shop drawings of the VAV boxes. I. Acoustical Performance: VAV unit design and selection shall result in space sound pressure levels conforming to an NCR-35 curve (except as noted hereinbelow) as defined in 1984 and later editions of ASHRAE Guide. Low pressure ductwork downstream of VAV units shall be acoustically lined of sufficient length to achieve the required criteria but not less than the lengths scheduled on the drawings. Auditorium, Library, Prayer Room, Study Room Lecture Rooms and Conference Rooms NCR-30 Exhibition Galleries and Private Offices NCR-35 Atrium, Toilets, Storage NCR-40 Open Office Space, Corridors Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-119 NCR-40 to 45 HVAC Issued for Construction 1 June 2004 J. Octave Band Restaurant, Cafe NCR-45 Kitchen, Food Preparation NCR-50 The maximum discharge permissible sound power levels measured at the terminal outlets of VAV units, based on a maximum inlet static pressure of 500 Pa and 100% design flow, in octave bands for the NCR curves, are as follows: MidFrequency (cps) Max. PWL re: 10-12 Watts NCR-30 NCR-35 NCR-40 NCR-45 NCR-50+ 1 63 59 62 66 68 70 2 125 52 56 60 63 66 3 250 45 49 54 58 62 4 500 41 46 51 56 61 5 1000 38 43 48 53 58 6 2000 37 42 47 52 57 7 4000 36 41 46 51 56 8 8000 37 42 47 52 57 K. Radiated Noise from VAV Units 1. Octave Band 1 2 3 4 5 6 7 8 MidFrequency (cps) 63 125 250 500 1000 2000 4000 8000 Where VAV units are located in ceiling plenum over occupied spaces, the maximum permissible radiated sound power levels in octave bands when operated in an installed condition per plans and Specifications, based on a maximum inlet static pressure of 500 Pa and 100% design flow, shall be as follows: NCR-30 Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 69 66 57 55 52 51 61 60 Max. PWL re: 10-12 Watts NCR-35 NCR-40 NCR-45 72 70 61 60 57 56 66 65 76 74 65 64 62 60 70 70 15000-120 79 77 68 68 67 65 75 75 NCR-50+ 82 80 71 72 72 70 80 80 HVAC Issued for Construction 1 June 2004 2. 2.34 The manufacturer shall submit to the Consulting Engineer guaranteed radiated sound power levels in octave bands, and shall substantiate that the equipment operating in an installed condition in accordance with plans and Specifications shall conform with those described above. Radiated sound ratings shall be without allowance for ceiling absorption. L. The VAV unit manufacturer shall submit guaranteed sound power level ratings by octave bands. These ratings shall list the unit sound power generation with the VAV unit installed within the test chamber. The sound power generation shall be listed for an upstream pressure of 750 Pa, 500 Pa, 250 Pa and minimum water gauge with a downstream pressure of 0.0 Pa. Neither the manufacturer nor the specific unit selection shall be approved until such data has been submitted. M. Sound power shall be measured in accordance with ADC (Air Diffusion Council) Standard 1062-R.3. N. Should the Engineer desire that units as furnished under this Section be checked for conformance to the above performance, the cost of such test shall be paid for by the Engineer provided that the test proves that the unit furnished does conform. If the unit as furnished and subsequently tested does not conform, the cost of the test and of any corrective measures shall be at no additional expense to the Engineer. The testing, if required, shall be performed at the manufacturer's factory and observed by the Consulting Engineer. O. Unit ratings shall be tested in accordance with current ADC Test Code Standards. P. Shop Testing/Startup Supervision: All units shall be shop tested for pressures, temperatures and flow capacities as scheduled, with test and calibration results shipped with each unit. The unit manufacturer shall provide the services of direct factory personnel to supervise the installation, testing, checking, balancing and final calibration of each unit, for not less than ten working days. VOLUME CONTROL REGULATORS (DDC) A. Volume regulators shall be provided where shown on the drawings. Regulators shall be provided with multi-point sensor and maintain constant flow within plus or minus 5% of specified or set value for a minimum pressure of 0.10 inch water gauge. A calibration chart shall be furnished for field volume adjustment. Valves, consisting of multiple sections, where possible, shall be factory assembled. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-121 HVAC Issued for Construction 1 June 2004 B. Regulators shall be furnished by the manufacturer with automatic digital electronic controller, actuator, control transformer and unit-mounted thermostat (if required) for installation under this Section. C. Regulators shall be as manufactured by Titus, Type DQCV, or as approved. D. Direct Digital Control (DDC) Type 1. All volume control regulators shall be of the distributed direct digital control technology type. The direct digital controller (DDC) and its associated power supply communications ports, terminal strips, etc., shall be furnished to the successful regulator manufacturer for factory installation and testing at the regulator manufacturer's facility. The DDC unit and appurtenances shall be furnished by the Automatic Temperature Control Subcontractor. 2. All final mounting, wiring, testing, etc., to make the regulator units completely operational shall be the responsibility of the regulator manufacturer. All work associated with same shall be closely coordinated with the Building Automation and Temperature Control Subcontractor. 3. The DDC controller and its associated power supply, transducers, electric damper operator, etc., shall be neatly mounted within a separate 20 gauge sealed and gasketed galvanized sheet metal enclosure, mounted directly to and supported from the regulator it serves. All external electrical connections to the DDC controller within the box shall be terminated in two separate junction boxes (with removable covers), i.e., one for power and one for signal communications. All wiring and tubing shall be permanently labeled and color coded for ease of identification. No access to within the enclosure shall be required for installation, startup or operation of the regulator. 4. Regulator shall be pressure independent. A multiple arm (minimum 4) flow traversing flow sensor shall be used and the means of sensing airflow shall be incorporated within the regulator and shall provide control signal pressure for the cfm to the DDC controller. Flow sensor shall be of the multi-point, averaging, ring or cross type. Bar or single point sensing type is not acceptable. Separate differential pressure taps shall also be provided for airflow measurement with a 0-1 inch gauge. Each regulator shall be provided with a flow chart attached. Cfm setting shall be factory set but shall be capable of easy readjustment in the field. Regulator shall be capable of operating as described above at inlet static pressures between .05 Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-122 HVAC Issued for Construction 1 June 2004 inch and 6 inch water gauge. Regulator shall be selected to operate at a static pressure loss through the unit between .05 and .25 inch water gauge (maximum). E. 5. Electronic actuator and accessories to operate the regulator and controller shall be provided by the DDC unit manufacturer, installed and tested by the regulator manufacturer at the factory. Actuator and all accessories shall be mounted in easily accessible enclosure, completely wired, requiring only power. Regulator shall be normally open upon loss of control signal unless otherwise noted. 6. This Subcontractor shall coordinate with the Automatic Temperature Control Subcontractor regarding the quantity of power required per regulator and also as to the quality of the power (voltage limits, etc.). A letter stating the above requirements shall be submitted by this Subcontractor in conjunction with the shop drawings of the regulator. Regulator Acoustical Performance 1. It is the intent of the Specification that the manufacturer shall furnish units that shall permit attaining sound pressure levels in spaces conforming to NC-40 curve (except as noted hereinbelow) as explained in 1984 and later issues of the ASHRAE Guide: Mechanical Equipment Rooms, Service Areas and Loading Dock 2. NC-55 The maximum permissible sound power level for regulators is as follows: SOUND POWER LEVELS Maximum Sound Power Levels in dB re: 10-12 Watts Octave Band Center Frequency (Hertz) Regulator Size 24 X 24 125 250 500 1K 2K 4K 8K 65 63 64 66 68 67 65 3. The regulator manufacturer shall submit to the Engineer's representative guaranteed sound power levels by octave bands. Sound power level data submitted shall substantiate that the equipment types and sizes operating as in an installed condition as per plans and specifications shall conform with the acoustical performance described above. Neither the manufacturer nor the specific unit selection shall be approved until such data has been submitted. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-123 HVAC Issued for Construction 1 June 2004 2.35 4. The regulators shall be tested in accordance with ADC (Air Diffusion Council) Standard 1062-R.3. Sound power ratings shall be listed for an upstream pressure of 2 inches water gauge upstream pressures and a downstream pressure of 1.0 inch water gauge. 5. Should the Engineer desire that units as furnished under this Section be checked for conformance to the above performance, the cost of such test shall be paid for by the manufacturer. If the unit as furnished and subsequently tested does not conform, the cost of the test and of any corrective measures shall be at no additional expense to the Owner. ACOUSTIC TREATMENT A. Where shown on the drawings and specified hereinbelow, supply ductwork and return and exhaust ductwork shall be installed with 50 mm. thick acoustic lining. Such acoustic lining shall be 40 kg./m3 density mat-face duct liner of a type approved by the NFPA. Acoustic lining shall be the products of one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. Dimensions of lined ducts shown on drawings are the inside dimensions of the duct after the lining has been installed. Stapling method of attachment shall not be permitted. Mat-faced duct liner shall be adhered by a fire retardant adhesive such as Benjamin Foster 81-99, or as approved. All abutting edges of acoustic lining shall be caulked, and all exposed edges of acoustic lining shall be installed with sheet metal nosings. B. All acoustic lining in all supply air systems, including inside the fanpowered boxes and VAV boxes and ducts, shall be faced with a duct liner facing, suitable for use in an air handling system. Material as installed shall have a flame spread and fuel construction rating equal to or less than 25 and 50, respectively, and shall be similar to "Toughskin" as manufactured by Manville, or as approved. C. All round or rectangular ductwork of supply and return ductwork within the Mechanical Equipment Rooms where called for on the drawings, and/or as stated hereinafter, shall be lined with 50 mm. thick, 40 kg./m3 density, sound absorption material. The sound absorption material shall be faced with a galvanized perforated metal facing having the same dimensions as the unlined ductwork connecting to the lined section of the ductwork. A Tedlar liner between the perforated liner and the acoustic absorbent material shall be provided throughout the double-wall ductwork. The perforated metal shall be .70 mm. gauge and have one of the following perforation patterns, or approved equal: Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-124 HVAC Issued for Construction 1 June 2004 Open Area 3 mm. round holes on 5 mm. staggered centers 3 mm. round holes on 6 mm. staggered centers 3 mm. round holes on 6 mm. staggered centers 2 mm. round holes on 4 mm. staggered centers 1.5 mm. round holes on 3 mm. staggered centers 29% 29% 23% 29% 22.5% D. All acoustic lining and sound absorber materials shall have a flame spread and smoke developed rating of less than or equal to 25 and 50 respectively. E. All pipe sleeves and duct openings penetrating floor slabs, partitions, walls, etc., shall be packed with mineral wool and sealed with nonhardening mastic. F. Factory Built Sound Traps 1. Prefabricated duct silencers shall be constructed of all incombustible materials and shall be the standard product of an approved manufacturer. The shell of the silencer shall be at least 1.0 mm. galvanized steel sheet and shall be leakproof when subjected to a differential pressure of 42 kPa. 2. Pressure drop shall be not greater than shown in the sound trap schedule. Total system pressure before and after the sound traps shall be measured after the traps are installed. Should the pressure drop be greater than specified or scheduled, replace the traps and/or modify the entrance or discharge aerodynamic flow to achieve the specified results. Make all corrective measures at no additional cost to the Owner. 3. All sound traps shall, in addition to the other provisions of this Article, be furnished with a Tedlar liner between the welded perforated liner and the acoustic absorbent material within. Liner and assembly shall have a flame spread and smoke developed rating of less than or equal to 25 and 50, respectively. 4. The sound traps shall provide the following net insertion ratings under design airflow velocities as scheduled on the drawings. The ratings shall be determined by the duct to reverberant room test method. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-125 HVAC Issued for Construction 1 June 2004 Dynamic Net Insertion Loss (dB) Band Width Center Freq. (cps) Sound Trap Types A B C Bands 2 3 4 5 6 125 250 500 1000 2000 5. Bands 7 14 20 22 14 7 11 14 14 12 12 21 23 22 16 The maximum self-generated noise by the above sound trap types shall not exceed the following sound power levels at face velocities of 10 m/s. Sound Power Level dB re: 10-12 Watts Band Width Center Freq. (cps) Sound Trap Types AB CD 2 3 4 5 6 6. 5 9 13 13 10 D 125 250 500 1000 2000 45 48 49 50 54 50 54 56 56 59 Vaneaxial fan cone/diffuser silencers shall be factory prefabricated and constructed from 1.3 mm. galvanized steel (minimum) exterior and 1.3 mm. perforated galvanized steel (minimum) interior. The center cone shall be constructed of 1.3 mm. perforated steel (minimum) with 23% open area. All acoustical filler materials shall comply with this Specification Section and the interior center cone shall be the same diameter as the fan hub. a. Minimum dynamic insertion loss shall be as follows: Bands Band Width Center Freq. (cps) Dynamic Insertion Loss (dB) Cone/Diffuser Silencer 2 3 4 5 6 125 250 500 1000 2000 11 17 18 16 12 Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-126 HVAC Issued for Construction 1 June 2004 7. 2.36 Certification: Submit certified test data of pressure drop and insertion loss ratings for a 600x600 cross-section rectangular trap or 600 mm. diameter conical trap. The certification data for both pressure drop and insertion loss shall be based upon tests of the same trap for both measurements. The certifying laboratory shall be open to inspection and/or test of sound traps upon request of the Consulting Engineer. INSULATION A. Provide insulation systems for all piping, ductwork and equipment using an installer approved by the insulation manufacturer. Execute the work in accordance with the best practice and workmanship of the Trade and the requirements of this Section of the Specifications. B. Insulation materials and adhesives shall be products of one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. C. Quality Assurance: Insulation materials shall comply with BS476. D. Fire and Smoke Hazard Rating 1. All thermal and acoustical insulation jackets, facings, membrane, adhesives, mastics, coatings and accessory materials shall be tested in compliance with the latest versions of BS4735-Class Q, BS476, ASTM E-84 and NFPA 255. All materials shall be listed and labeled by Underwriters Laboratories, Inc. for a fire hazard classification, as not to exceed the following: Flame Spread Fuel Contributed Smoke Developed E. 25 50 50 2. The rating for insulation with factory applied jackets or facings shall be on a composite basis of insulation, jacket or facing, and the adhesive used to adhere the jacket or facing to the insulation. 3. Shipping containers for insulation and accessory materials shall be labeled to indicate conformance to the fire hazard classification. 4. Submittals of insulation and accessory materials shall include a written certification that the material being submitted for approval meets the above criteria and shall include the required Materials Safety Data Sheets. Before applying insulation, all surfaces shall be free of dust, grease and foreign matter. Insulation shall not be applied to any piping, ductwork or equipment until required pressure testing has been completed and the system approved for tightness. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-127 HVAC Issued for Construction 1 June 2004 F. Insulation jackets, facings, vapor barriers and finishes on ducts and piping handling cold water shall be continuous and sealed through floor and wall sleeves, hangers, supports and attachments. G. Pipe Insulation 1. Material a. Fiber glass, molded, one-piece insulation with white Kraft, fiber glass reinforced, aluminum foil laminated, All-Service Jacket (ASJ). Pipe insulation shall be capable of continuous service at a pipe temperature of 232°C. without oxidation or burnout of binders or the development of odors or smoke by any constituent of the material. Physical characteristics shall be as follows: Minimum Density Thermal Conductivity Jacket Vapor Permeability Jacket Puncture Resistance b. 2. 65 kg./cu.m. 0.034 w./mk at 24°C. 0.02 perms. 50 units (Beach). Calcium silicate pipe insulation shall be composed of asbestos-free hydrous calcium silicate for use on systems operating up to 649°C. Insulation shall be preformed half-sections (two-piece) secured with 15 mm. wide, .50 mm. aluminum bands or 2 mm. wire 300 mm. on centers. Insulation shall be covered with a .40 mm. aluminum jacket with factory-applied moisture barrier, secured in place with .50 mm. aluminum bands 300 mm. on centers. Physical characteristics shall be as follows: Average (Dry) Density: 240 kg./cu.m. Thermal Conductivity: 0.066 w./mk at 24°C. Insulation Thickness Service Pipe Size Temp Thickness Emergency Generator and Diesel Fire Pump All 540°C 100 mm. Calcium Silicate Exhaust Piping and Muffler Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-128 HVAC Issued for Construction 1 June 2004 Service Pipe Size Temp Low Pressure Steam, All Steam Condensate, Supply and Return Risers, Mains and Branches 150 mm. and under 200 mm. and over Thickness 50 mm. 232°C. 75 mm. Fiber glass Condenser Water Supply and Return (Exposed on Roof and Exposed Within Building, Except in MER) Chilled Water and Heat Recovery - Supply and Return Fresh Water Makeup 50 mm. 150 mm. and under 200 mm. and over 75 mm. fiber glass All 25 mm. Fiber glass Condensation Drains Risers, Mains and Branches 3. All 25 mm. Fiber glass Installation of Insulation a. Pipe insulation sections firmly butted together at all joints with jacket laps and joint butt strips pulled tight and smooth. Longitudinal joints, a minimum of 50 mm. overlap. Butt joint strips a minimum of 75 mm. wide. b. Fittings insulated with premolded polyisocyanuratic rigid closed cell foam, fitting covers for the sizes manufactured. For other types and sizes, fittings insulated with radially mitered segments of pipe covering secured in place with 2 mm. copper plated, annealed steel wire. Molded fitting covers suitable for same service temperature as pipe insulation. c. Valves insulated over the bonnet with cut and built-up sections of pipe insulation. Voids and irregular spaces between pipe insulation section bore and valve body filled with in-situ polyisocyanurate chemical system furnished by the pipe insulation manufacturer and Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-129 HVAC Issued for Construction 1 June 2004 installed in accordance with the manufacturer’s installation instructions (suitable for same service temperature as pipe insulation) wired to valve body. d. Flanges insulated with built-up sleeves of pipe covering overlapping adjacent pipe insulation. e. Insulation for fittings, valves, flanges, and accessories, same thickness as adjacent pipe insulation. f. Valves, strainers, expansion joints and other specialties requiring periodic servicing or inspection shall be provided with insulation covers, removable and replaceable without damaging insulation, vapor barriers or finishes. Insulation on valves shall be extended over the bonnets. g. Hot Service Piping h. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) Insulation jacket laps and joint butt strips stapled on 4 inch centers with flare type staples and secured with aluminum bands on 18 inch centers with one band over each joint butt strip. 2) Voids around fittings, valves and at flanges, filled with insulation and covered with premolded thermoplastic covers. Cold Service Piping 1) Insulation jacket laps and joint butt strip sealed with lap sealing adhesive. At all fittings, valves, etc., and at intervals of every 5 sections of straight run pipe insulation, apply a vapor barrier coating, 1.6 mm. thick, to all butt joints and on the bore of the pipe insulation for a minimum of 50 mm. from the joint. Position insulation and press firmly into place making certain that a complete unbroken seal is obtained. 2) Voids around fittings, valves and at flanges, filled with in-situ polyisocyanurate chemical system furnished by the pipe insulation manufacturer and installed in accordance with the manufacturer’s installation instructions, and covered with premolded thermoplastic covers. 3) Apply a 200 g/m2 woven glass cloth cover over the entire system, painted with two (2) coats of approved sealant. 15000-130 HVAC Issued for Construction 1 June 2004 4. Protection of Insulation a. Insulation on hot pipes 100 mm. and larger shall be protected from hangers, guides and rollers by pipe protection saddles welded to the pipe, and filled with pipe insulation or insulating cement. Saddles shall not be welded to the pipe hanger or support. b. Insulation on hot pipes smaller than 100 mm. shall be supported on factory assembled thermal protection shields. c. Insulation on cold pipes shall be protected from hangers, guides and rollers by a 180 degree galvanized steel shield on the outside of the insulation and vapor barrier. A half-section of waterproof, calcium silicate, high density insulation of the same thickness as the pipe insulation, and full length of the shield, shall be used to support weight of the pipe at the shield. Factory assembled thermal protection shields may also be used. Pipe Size 40 mm. to 65 mm. 75 mm. to 150 mm. 200 mm. to 250 mm. 300 mm. and over Shield Length 250 mm. 300 mm. 400 mm. 550 mm. d. Pipe protection shields may be factory assembled thermal protection shields as manufactured by one of the approved manufacturers. See Approved Manufacturers Article 2.01 of this Specification. e. Piping Exposed to Weather and Exposed Within the Building: Insulated water piping, insulated emergency generator and diesel fire pump combustion exhaust pipes exposed outside of building and where exposed within the building shall be covered with 11 gauge polished aluminum jacket. f. Piping Penetrating Floors and Walls: Insulation on cold service piping shall be continuous through the penetrations of walls, partitions, floor slabs, etc. The space between piping and/or insulation and the sleeve shall be packed with an approved fire resistive material. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-131 HVAC Issued for Construction 1 June 2004 H. Insulation for Sheet Metal Work 1. Materials and Finishes Built-up air supply apparatus chambers, outside air intake and ducts between connections to louvers and/or gratings up to lined casings and built-up spill and exhaust plenums and ducts between louvers and/or gratings and automatic louver dampers (ALD’s). 50 mm. thick, 96 kg./cu.m. density, fiber glass, rigid insulation board with white Kraft, fiber glass reinforced, aluminum foil laminate, All-Service Jacket (ASJ). Adhere to outside of chambers and/or ducts with weld pins and speed washers spaced on 300 mm. centers maximum, but not more than 75 mm. from insulation joints and/or corners. Minimum of two rows of pins per side of duct. Seal all joints with 100 mm. wide ASJ tape. Seal all punctures and pin penetrations with approved vapor barrier coating. Where stiffening angles are larger than 50 mm., insulation thickness shall match size of angle. Apply a 200 g/m2 canvas cover over the entire system adhered between two coats of approved fungicidal protective fire resistant lagging adhesive. Exposed rectangular air conditioning supply ductwork and return ductwork within all Mechanical Equipment Rooms and exposed in all other spaces. Same as above. Rectangular air conditioning supply duct risers and return duct risers within shafts 50 mm. thick, 48 kg./cu.m. density fiber glass rigid insulation board factory applied foil faced, scrim reinforced, Kraft vapor barrier (FSK) and 50 mm. flange. Wrap insulation tightly on duct and firmly butt all joints with 50 mm. flange overlap on circumferential joints. Adhere to duct with 2/3 coverage of approved adhesive applied in 100 mm. wide bands, 200 mm. on centers. Seal all joints and seams with minimum 75 mm. wide FSK tape applied with same adhesive. Additionally, support insulation on the bottom side of rectangular ducts over 900 mm. wide with a single row of weld pins and speed washers. Clip off pins flush with facing and seal all pin punctures and breaks in vapor barrier with FSK tape and adhesive. Apply a 200 g./m2 canvas cover over the entire system adhered between two coats of approved fungicidal protective fire resistant lagging adhesive. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-132 HVAC Issued for Construction 1 June 2004 Concealed rectangular and round air conditioning supply ducts and return ducts on all floors except Mechanical Equipment Rooms and where exposed Same as above. All low pressure supply air ductwork, both upstream and downstream of VAV boxes and fan-powered boxes where concealed Same as above. NOTE: All supply air ductwork and return air ductwork shall be insulated in its entirety, except where internal acoustic lining is provided. All exhaust air ducts Uninsulated except where internal acoustic treatment is required by the drawings or specifications. Kitchen hood exhaust ducts and fans, from hood connection to system discharge at exterior wall or roof opening. 2 layers of 25 mm. thick asbestos-free, calcium silicate block insulation. Apply blocks to ducts with edges tightly butted, joints of adjacent layers are to be staggered and secured with 2 mm. gauge galvanized, annealed steel wire, or 15 mm. x 4.0 mm. galvanized steel bands on 300 mm. centers maximum. Point all joints on each layer with insulating cement. Anchor wires or bands to studs welded to duct. For concealed and exposed ducts, stretch 25 mm. hexagonal galvanized, wire mesh over block insulation, with edges of mesh tied together and secured to weld studs. Reinforce all corners with corner bead secured to attachment wires and wire mesh. Finish with a 25 mm. thick coat of insulating cement troweled to a smooth, hard finish. 2. All vapor barriers shall be completely sealed against moisture penetration. 3. Wherever external duct insulation is specified and internal acoustic treatment of equivalent insulating effect is also required (by drawings or specifications) for the same location, the external insulation may be omitted. 4. All duct sleeves and openings penetrating floor slabs, partitions, walls, etc., shall be packed for full depth of penetration with approved fire resistive material and sealed with nonhardening mastic. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-133 HVAC Issued for Construction 1 June 2004 I. Equipment Insulation 1. Material and Finishes Air Conditioning Axial Flow Return Fans 50 mm. thick, 100 kg./cu.m. density, fiber glass, rigid insulation board with white Kraft, fiber glass reinforced, aluminum foil laminate, All-Service Jacket (ASJ). Adhere to duct with weld pins and speed washers spaced on 300 mm. centers maximum. Pins spaced not more than 75 mm. from insulation joints and from corners of duct. Minimum of two rows of pins per side of duct. Seal all joints with 100 mm. wide ASJ butt strips adhered with approved adhesive. Seal all punctures and pin penetrations with approved vapor barrier coating. Where stiffening angles are larger than 50 mm., insulation thickness shall match size of angle. Chillers, Chilled Water and Heat Recovery Water Expansion Tanks 50 mm. thick, 100 kg./cu.m. density, rigid board fiber glass insulation with ASJ. Cut, score and miter insulation to fit contour of equipment and secure with weld pins and speed washers on 300 mm. centers maximum. Pins shall not be more than 75 mm. from insulation joints or corners. Seal all joints with 100 mm. wide ASJ strips adhered with approved adhesive. Entire insulation jacket shall be sealed to maintain vapor barrier, see “Removable Head Insulation” Chilled Water Pumps 50 mm. thick, 50 k.g/cu.m. density, unfaced Fiberglas rigid board insulation applied to the inside of 1.0 mm. thick aluminum sheet metal housing with approved adhesive and secured with weld pins and speed washers. Details as described herein below under "Removable Head Insulation". 2. Weld pins shall be clipped flush to insulation surface. On cold service equipment, pin penetration shall be sealed with vapor barrier coating. 3. Removable Head Insulation: Removable insulation jackets shall be provided for all equipment such as chillers, chilled water, etc., Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-134 HVAC Issued for Construction 1 June 2004 and all other equipment which requires access to internal parts for servicing and maintenance. The removable insulated covers shall consist of an appropriately shaped, 1.31 mm. thick aluminum sheet metal housing lined with 50 kg/cu.m. density fiber glass insulation board. The insulation shall be carefully cut to fit contour of the inside of the housing and shall be adhered to the sheet metal with adhesive weld pins, speed washers and adhesive. All seams and joints in the sheet metal shall be soldered, or welded to form a vapor-tight enclosure. The enclosure shall be split and flanged so that removal of the insulated housing shall permit convenient access to seals, bearings and casing. A bolted and gasketed flanged joint shall be provided for convenient removal. Lifting eyes or handles shall be furnished to facilitate removal. A soft seal shall be installed at point of shaft entry into the insulated enclosure. Submit details of removable, insulated enclosures prior to proceeding with their assembly. 2.37 FOUNDATIONS, VIBRATION ISOLATION INCORPORATING SEISMIC RESTRAINTS A. All equipment, piping, etc., shall be mounted on or suspended from approved foundations and supports, all as specified herein, as shown on the drawings, or as required. B. All equipment, whether isolated or not, shall be bolted to structure to allow for minimum 0.5 “g” of acceleration. Bolt points and diameter of inserts shall be submitted and verified as part of the Subcontractor's submission for each piece of equipment and certified by a licensed Civil or Structural Engineer. 1. 2. Seismically restrain all piping and ductwork with center bracing or Type II restraining system in accordance with SMACNA guidelines to comply with 1997 Uniform Building Code (UBC) as outlined below: a. Piping to be braced at 12 m. intervals and at turns of more than 4 feet. b. Ductwork to be braced every 9 m. and at every turn and duct run ends. c. Piping to be restrained as per 1997 UBC. d. Ductwork to be restrained as per 1997 UBC. Seismic restraints are not required for the following: a. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Gas piping less than 25 mm. internal diameter. 15000-135 HVAC Issued for Construction 1 June 2004 b. Piping in Mechanical Equipment Rooms that is less than 30 mm. internal diameter. c. All other piping and electrical conduit less than 60 mm. internal diameter. d. All rectangular ducts less than 0.50 sq./m. in crosssectional area. e. All round ducts less than 700 mm. in diameter. f. All piping suspended by individual hangers 250 mm. in length or less from the top of the pipe to the bottom of the structural support for the hanger. g. All ducts suspended by hangers 250 mm. or less in length from the top of the duct to the bottom of the structural support for the hanger. 3. Chimneys and stacks passing through floors are to be bolted at each floor level or secured above and below each floor with riser clamps. 4. Chimneys and stacks running horizontally to be braced every 9 m. with Type II restraining system. 5. Where base anchoring is insufficient to resist seismic forces, supplementary restraining such as Seismic Restraint System Type II shall be used above system's center of gravity to suitably resist "g" force levels. Vertically mounted tanks may require this additional restraint. 6. For overhead supported equipment, overstress of the building structure must not occur. Bracing can occur from: a. Flanges of structural beams. b. Upper or lower truss chords in bar joist construction at the panel points. c. Cast-in-place inserts or drilled and shielded inserts in concrete structures. 7. All structurally suspended overhead equipment isolated or unisolated shall be four-point independently braced with Type II seismic restraining system. 8. Install Seismic Restraining System Type II: Taut for overhead suspended unisolated equipment, piping or ductwork, and slack with 12 mm. cable deflection for isolated systems. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-136 HVAC Issued for Construction 1 June 2004 C. All concrete foundations and supports and required reinforcing therefor shall be furnished and installed under another Contract. However, this Subcontractor shall furnish shop drawings showing adequate concrete reinforcing steel details and templates for all concrete foundations and supports, and all required hanger bolts and other appurtenances necessary for the proper installation of his equipment. Although the Contractor shall complete all concrete work, all such work shall be shown in detail on the shop drawings, prepared by this Subcontractor, which drawings shall be submitted to the Consulting Engineer showing the complete details of all foundations including necessary concrete and steel work, vibration isolation devices, seismic restraints, etc. D. All floor-mounted equipment shall be erected on 100 mm. high concrete pads over the complete floor area of the equipment unless specified to the contrary herein. Wherever hereinafter vibration eliminating devices and/or concrete inertia blocks are specified, these items shall, in all cases, be in turn mounted upon 4 inch high concrete pads unless specified to the contrary herein. E. The vibration isolation systems shall be guaranteed to have the deflection indicated on the schedule on the drawings. Mounting systems and components of the isolation mounting shall not be resonant with any of the forcing frequencies of supported equipment or piping. Mounting sizes shall be determined by the mounting manufacturer, and the sizes shall be installed in accordance with the manufacturer's instructions. F. All mounting systems including seismic restraints exposed to weather and other corrosive environments shall be protected with factory corrosion resistance. All metal parts of mountings (except springs and hardware) to be hot dip galvanized. Springs shall be cadmium plated and neoprene coated. Nuts and bolts shall be cadmium plated. G. Where supplementary steel is required to support piping, the supplementary steel shall be designed to provide a maximum deflection of 2.0 mm. at the midspan under the supported load. The piping shall be rigidly supported from the supplementary steel and the supplementary steel isolated from the building structure by means of isolators as described in paragraphs entitled "Support of Piping.” H. Where steel spring isolation systems are described in the following specifications, the mounting assemblies shall utilize bare springs with the spring diameter not less than 0.8 of the loaded operating height of the spring. Each spring isolator shall be designed and installed so that the ends of the spring remain parallel. The spring specified minimum deflection from loaded operating height shall be 50% of the rated deflection. The maximum motion of any resiliently supported equipment at startup or shutdown shall be 8 mm. Approved lateral restraints shall be provided as required to limit motions in excess of 8 mm. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-137 HVAC Issued for Construction 1 June 2004 I. J. Where neoprene-in-shear isolation systems are described in the following specifications, the mounting assemblies shall utilize bare neoprene elements with unit type design molded in oil resistant neoprene. The neoprene shall be compounded to meet the following: 1. Not greater than 70 durometer. 2. Minimum tensile strength of 13,800 kPa. 3. Minimum elongation of 300%. 4. Maximum compression at 25% of original deflection. Vibration isolation equipment submittal drawings shall include the following information: 1. Isolation mounting deflections. 2. Spring diameters, compressed spring heights at rated load; solid spring heights, where steel spring isolation mountings are used. 3. Equipment operating speed. 4. Maximum motion at fan flexible connections. 5. Drawings, as required, to show the number and location of seismic restraints for each equipment, specific details of restraints, including anchor bolts for mountings and maximum load (static plus dynamic) expected at each restraint or snubbing device and showing that fastening devices for the seismic restraints are capable of maintaining equipment in a captive position when subjected to external forces of 0.5 “g” in any direction. K. During equipment installation, floor supported spring isolation bases shall be set on 50 mm. high spacers between the isolation base and the housekeeping pad. After all connections (pipe, dust, and conduit), have been made to the equipment and the system filled, the normal operating equipment load shall be removed without change of equipment elevation or transfer of stress to the equipment. L. Mountings incorporating vertical limit stops shall be furnished and installed with 8 mm. spacers. The mounting shall serve as blocking during installation. Mountings shall be adjusted and spacers removed after equipment achieves normal operating loads. M. Each seismic restraint, snubbing device or isolation mounting incorporating seismic restraint shall be installed and/or adjusted to provide the minimum operating clearance in all directions to permit the operation of the equipment without objectionable noise or vibration to Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-138 HVAC Issued for Construction 1 June 2004 any part of the building structure. The operating clearance for equipment seismic restraints shall not be greater than 8 mm. N. Equipment seismic restraints or snubbing devices and vibration isolation systems mounting shall be the product of one manufacturer. The following vibration control manufacturers shall be approved provided mounting systems are in strict accordance with the design intent as specified herein: Mason Industries, Inc., Hauppauge, NY Amber Booth, Houston, TX O. Floor Mounting of Centrifugal Fans - Mounting Type I 1. Each such fan and driving motor shall be mounted on an integral one-piece structural base, reinforced as necessary, to prevent flexure of the base at startup and during operation of the fan. The unitized structural mounting base for the fan and motor shall include motor slide rails. The structural frame shall be drilled and tapped to receive the fan and motor so that the frame shall act as a template. 2. The structural steel integral base shall be supported on steel spring mountings. These mountings shall be positioned in accordance with the weight distribution to ensure adequate deflection and vibration isolation. Housing or snubbing devices shall not be used to contain the isolator springs. 3. Isolator types shall be the following or as approved: Type SLF 4. P. - M.I.I. Mounting system shall incorporate seismic restraint Type I. Floor Mounting of Centrifugal Fans - Mounting Type II 1. Each such fan and motor shall be mounted on a reinforced spring supported concrete foundation. The foundation shall be poured within structural perimeter frame set on roofing paper. The structural perimeter frame, complete with motor slide rails, height saving spring mounting brackets, springs and equipment anchor bolt templates shall be provided by the vibration isolation control vendor. Spring supports shall be located under the brackets and shall incorporate a neoprene acoustical pad and leveling adjustment to raise the entire isolation base 50 mm. above the foundation pad. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-139 HVAC Issued for Construction 1 June 2004 2. Motor Size Minimum Inertia Block Thickness Required Up to 37 kw 45 to 55 kw 75 kw and greater 200 mm. 250 mm. 300 mm. 3. Mounting assemblies shall be the following or as approved: Structural Steel Perimeter Form Wood Perimeter Form Type KSL Type KIPWF 4. Q. Reinforced concrete inertia base thickness shall be in accordance with the following schedule: Mounting system shall incorporate Seismic Restraint Type I. Floor Mounting of Fans - Mounting Type III 1. This equipment shall be mounted exactly as described under Mounting Type I, except that mountings shall be neoprene-inshear and the following, or as approved: Type ND 2. R. - M.I.I. Mounting system shall incorporate Seismic Restraint Type I. Mounting of Factory Assembled Fans, Tubular Fans and Belted Vent Sets - Mounting Type IV 1. Each such equipment shall be mounted on neoprene-in-shear isolators. Mountings shall be the following, or as approved: Type ND 2. S. - M.I.I. - M.I.I. Mounting system shall incorporate Seismic Restraint Type I. Mounting of Factory Assembled Fans - Mounting Type V 1. This equipment shall be mounted directly on stable bare steel spring isolators, except that where the units to be mounted are furnished with internal structural frames and external lugs (both of suitable strength and rigidity), or without any severe overhangs, no additional structural frame need be furnished and installed beneath the unit. In any event, the motor shall be integrally mounted to the unit and shall be mounted on slide rails. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-140 HVAC Issued for Construction 1 June 2004 2. Isolator mounting types shall be the following, or as approved: Type SLF 3. T. - M.I.I. Mounting system shall incorporate Seismic Restraint Type I. Mounting of Ceiling Supported Factory Assembled Fans, Axial Flow Fans, Tubular Fans and Belted Vent Sets - Mounting Type VI 1. All such units shall be hung by means of vibration isolation hangers consisting of a steel housing or retainer incorporating a steel spring and neoprene isolators. 2. If the equipment to be mounted is not furnished with integral structural frames and external mounting lugs (both of suitable strength and rigidity), approved structural sub-base shall be installed in the field, which shall support the equipment to be hung and to which shall be attached the hangers. All such equipment shall be supported by a rigid structural frame from the structure above to capture the equipment laterally under seismic forces. 3. Isolators shall be the following, or as approved: Type DNHS U. - M.I.I. 4. Resilient diagonal restraining isolators shall be provided as required to limit horizontal motion to 8 mm. maximum under fan operating conditions. 5. Seismic Restraints Type II shall be provided to hold captive the equipment for lateral movements. Mounting of Ceiling Supported Factory Assembled Fans, Axial Flow Fans, Tubular Fans and Belted Vent Sets - Mounting Type VII 1. This equipment shall be mounted exactly as described under Mounting Type VI except that mountings shall be the following, or as approved: Type HD - M.I.I. 2. Resilient diagonal restraining isolators shall be provided as required to limit horizontal motion to 8 mm. maximum under fan operating conditions. 3. Seismic Restraints Type II shall be provided to hold captive the equipment for lateral movements. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-141 HVAC Issued for Construction 1 June 2004 V. Mounting of Centrifugal Pumps (Greater than 2.2 kw) - Mounting Type VIII 1. Each pump with its driving motor shall be bolted and grouted to a spring supported concrete inertia base reinforced as required. 2. Each concrete base (rectangular or "T" shape for horizontally split pumps) shall include supports and base elbows for the suction and discharge connections. Base elbows shall be bolted and grouted to the concrete foundation. 3. Reinforced concrete inertia base thickness shall be in accordance with the following schedule: Motor Size Minimum Inertia Block Thickness Required 4.0 kw to 11 kw 18.5 kw to 37 kw 45 kw to 75 kw Greater than 75 kw 150 mm. 200 mm. 250 mm. 300 mm. 4. The spring supported reinforced concrete inertia foundation shall be poured within structural perimeter frame of the required thickness indicated in the above schedule. The structural perimeter frame shall be equipped with height saving brackets and stable bare spring isolators having spring diameters no less than 0.8 of the compressed height of the spring at rated load. The mountings shall provide minimum static deflection of 25 mm. The structural perimeter frame, mounting templates, reinforcing bars, height saving brackets and spring system shall be provided as an assembly by vibration control vendor. There shall be a minimum of 50 mm. operating clearance between the pump inertia base and the foundation pad. 5. Vertical piping loads including water, strainers, and valves between the pump base elbow supports and the suction and discharge header piping shall be supported by the pump base spring isolators without stress or strain to the pump casing. 6. Provide suitable and adequate space between suction and discharge valves and the pump to permit the future installation of flexible stainless steel braided metal hose connectors capable of accepting the operating working pressures with a burst pressure of not less than four times the operating pressure. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-142 HVAC Issued for Construction 1 June 2004 7. 8. W. Mounting assemblies shall be the following, or as approved: Structural Steel Perimeter Form Wood Perimeter Form Type KSL Type KIPWF Mounting system shall incorporate Seismic Restraint Type I. Mounting of Centrifugal Pumps (2.2 kw or less) - Mounting Type IX 1. Pumps 2.2 kw or less shall be bolted and grouted to rubber-inshear supported reinforced concrete inertia blocks that are a minimum of 150 mm. thick. Rubber-in-shear isolators shall provide a minimum static deflection of 10 mm. and shall be protected against corrosion. 2. Mountings shall be the following, or as approved: Type ND X. - M.I.I. 3. Provide base elbow supports and structural perimeter frames and reinforcement as described for Mounting Type VIII. 4. Mounting system shall incorporate Seismic Restraint Type I. Mounting of Refrigeration Machines, Mounting Type X 1. Each refrigeration machine (cooler, condenser, compressor and motor) shall be installed on an integral one-piece steel rigid structural frame which shall be installed on spring supported mountings. Each spring mounting shall be bare and stable and shall provide a minimum static deflection of 25 mm. All spring mountings shall provide a leveling device, neoprene acoustical pad and built-in vertical stop to prevent spring extension when equipment is removed from the base or drained. Mountings shall be the following, or as approved: Type SLR 2. Y. - M.I.I. - M.I.I. Mounting system shall incorporate Seismic Restraint Type I. Mounting of Miscellaneous Packaged Chilled Water Units - Mounting Type XI 1. Resiliently floor support units on the following, or as approved, mountings providing a minimum static deflection of 10 mm.: Type ND 2. - M.I.I. Resiliently suspend units with the following, or as approved, mounting types providing a minimum static deflection of 10 mm. Type HD Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC - M.I.I. 15000-143 HVAC Issued for Construction 1 June 2004 Z. Support of Piping and Diesel Exhaust Flue Piping - Mounting Type XII 1. The following water piping, fuel oil piping and diesel exhaust flue piping shall be resiliently supported: a. All piping and diesel exhaust flue piping in Equipment Rooms. b. Piping and diesel exhaust flue piping within 20 m. of connected rotating equipment. c. All piping and diesel exhaust flue piping where exposed on the roof. 2. All other piping shall be rigidly supported and provided with approved seismic restraints to maintain the piping in a captive attitude without excessive motion. 3. All piping seismic restraints shall be installed with a maximum spacing conforming to the hanger rod spacing schedule as hereinbefore specified, or as required to limit transmitted forces to the building structure to acceptable limits. 4. Resilient diagonal mountings or other approved devices shall be provided as required to limit piping motion due to equipment startup or shutdown, to a maximum of 8 mm. 5. Isolators for water piping and fuel oil shall be resiliently spring and neoprene supported with mountings providing a minimum static deflection of 30 mm. 6. Isolators for all other piping and diesel exhaust flue piping shall be supported by means of neoprene-in-shear mountings providing a minimum static deflection of 10 mm. 7. Where supplementary steel is required to support piping, the supplementary steel shall be sized so that maximum deflection between supports does not exceed 2 mm. and shall be resiliently supported from the building structure with mountings as described in the preceding two paragraphs. Supported piping from the supplementary steel shall be rigidly supported. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-144 HVAC Issued for Construction 1 June 2004 8. Positioning type hanger rod isolators shall be provided for diesel exhaust flue piping and for all piping greater than 300 mm. diameter and all supplementary steel supports. Positioning type hanger rod isolators shall be the following, or as approved: Type PDNHS - M.I.I. 9. All other water piping and fuel oil piping hanger rod isolators shall be the following, or as approved: Type DNHS 10. Floor supported water piping and fuel oil piping shall be mounted on the following, or as approved: Type SSLR AA. - M.I.I. - M.I.I. Piping and Diesel Exhaust Flue Anchors, Guides and Supports - Mounting Type XIII 1. Pipe and diesel exhaust flue guides, anchors and supports in all risers, and piping anchors in Mechanical Equipment Rooms or occupied spaces shall be isolated from the building structure such that there shall be no direct metal-to-metal contact of the piping and the diesel exhaust fluewith the building structure. 2. Piping and Diesel Exhaust Flue Guides a. Steel guides shall be welded to the pipe at a maximum spacing of 60 degrees. The outside diameter of the opposing guide bars shall be smaller than the inside diameter of the pipe riser clamp in accordance with standard field construction practice. Each end of the pipe anchor shall be rigidly attached to an all-directional pipe anchor isolation mounting, which in turn shall be rigidly fastened to the steel framing within the shaft, in an approved manner. b. The all-directional pipe anchor isolation mountings shall consist of a telescoping arrangement of two sizes of steel tubing separated by a minimum of 12 mm. thick heavy duty neoprene and canvas duck isolation pad. Vertical restraints shall be provided by similar material arranged to prevent vertical travel in either direction. The allowable load on the isolation material shall not exceed 3,445 kPa. c. Mountings shall be Type ADA - M.I.I., or as approved. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-145 HVAC Issued for Construction 1 June 2004 d. 3. 4. Low temperature and high temperature piping guides shall be constructed with a 360 degrees, 3.4 mm. metal sleeve around the piping. The thermal insulation requirements for the piping shall be provided between the piping and the sleeve. Heavy duty neoprene and canvas duck isolation pad of thickness equal to thermal insulation requirements shall space the metal sleeve away from the piping with urethane or other suitable thermal insulation provided in the voids between the pipe sleeve and isolation pad material. The metal sleeve outside diameter shall be smaller than the pipe riser clamp inside diameter in accordance with field construction practice. The pipe riser clamp shall be rigidly attached to the steel framing within the shaft. Anchors a. The pipe riser clamp at anchor points shall be welded to the pipe and to pairs of vertical acoustical pipe anchor mountings which in turn, shall be rigidly fastened to the steel framing in the pipe shaft. b. The acoustical pipe anchor mountings shall be capable of safely accepting loads developed by the installed piping and shall consist of a bolted assembly of steel plates with laminations of 12 mm. thick heavy duty neoprene and canvas duck isolation material. A heat shield shall be provided as required. The isolation material loading shall not exceed 3,445 kPa. c. Acoustical pipe anchor mountings shall be Type VPA Mason Industries, Inc., or as approved. Supports a. Piping supports within shafts shall be provided with suitable bearing plates and two layers of 8 mm. thick ribbed or waffled neoprene pad loaded for 345 kPa maximum. The isolation pads shall be separated with 8 mm. steel plate. b. The isolation pads shall be the following, or as approved: Type W c. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC - M.I.I. Piping isolation supports at the base of risers shall be two layers of 12 mm. thick heavy duty neoprene and canvas duck isolation pad separated by 8 mm. thick steel 15000-146 HVAC Issued for Construction 1 June 2004 plate. Suitable bearing plates sized to provide a pad loading of 3,445 kPa maximum shall be provided. The stanchion between the pipe and isolation support shall be welded to the pipe and welded or bolted to the isolation support. The isolation support shall be bolted to the floor slab with resilient sleeves and washers. d. 5. BB. CC. All pipe support resilient materials shall be Type HL M.I.I., or as approved. Piping Penetrations of Shafts, Floor Slab and/or Partitions: There shall be no direct contact of piping with shaft walls, floor slabs and/or partition. All uninsulated piping shall be sleeved with one inch fiber glass the full depth of the penetration. Mounting of Control Air Compressor - Mounting Type XIV 1. This equipment shall be mounted as described for Mounting Type VIII. 2. Mounting system shall incorporate Seismic Restraint Type I. Air Compressor Flexible Connectors - Mounting Type XV 1. Flexible stainless steel metal pipe connectors shall be installed in two planes 90 degrees to each other in the discharge piping from the compressor. Flexible connectors shall have a minimum burst pressure of four times the operating pressure. Pipe sizes through 50 mm. i.d. shall be furnished with hex male nipple fittings and pipe sizes 60 mm. i.d. and larger shall be furnished with fixed steel flanges both sides. Connectors shall be the following, or as approved: Type BSS DD. - M.I.I. Mounting of Cooling Tower - Mounting Type XVI 1. Each cooling tower shall be resiliently isolated from the building structure by means of bare, stable spring isolators provided between suitable framed grillage and dunnage steel. Spring mounting design shall incorporate a leveling device, neoprene acoustical pad, vertical limit stops to prevent elongation when water is removed from the basin and lateral restraints to safely accept a shear load of two times the supported load without failure. Spring mountings shall provide a minimum static deflection of 100 mm. and shall be adjusted to operate freely with a minimum operating clearance of 12 mm. in all directions. All mountings shall be hot dip galvanized (or other approved corrosion protection). Mountings shall provide seismic restraint Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-147 HVAC Issued for Construction 1 June 2004 in all directions. Mountings shall be capable of withstanding 45 m/s wind loads without failure. 2. The mountings shall serve as blocking during the erection of the towers. After the tower basins have been filled with water, the Subcontractor shall adjust spring mountings to carry the tower and water load resiliently. 3. Mountings shall be the following, or as approved: Type SSLR EE. 2.38 - M.I.I. Mounting of Emergency Generator - Mounting Type XVII: Each unit shall be installed on spring supported mountings. Each spring mounting shall be bare and stable and shall provide a minimum static deflection of 25 mm. All spring mountings shall incorporate a leveling device, neoprene acoustical pad and built-in vertical stop to prevent spring extension when equipment is removed from the base or cooler and condensers drained. Spring mountings shall be Type SLR as manufactured by Mason Industries, Inc., Type KW as manufactured by Vibration Eliminator, or as approved. SEISMIC RESTRAINTS A. All seismic restraints shall be capable of safely accepting one-half "g" external forces without failure and shall maintain all equipment, piping, ductwork, etc., in a captive position. Seismic restraints shall not short circuit isolation systems or transmit objectionable vibration or noise, and shall be provided on all equipment as scheduled on drawings. Calculations by registered Civil or Structural Engineer shall be submitted to verify snubber capacities for each piece of equipment. B. Equipment mounted on springs does not require additional seismic restraints providing that the spring mountings: 1. Comply with general characteristics of spring isolators. 2. Have vertical limit stops and are capable of supporting equipment at fixed elevation during equipment erection. 3. Incorporate seismic snubbing restraint in all directions at specified acceleration loadings. 4. Acceptable seismic spring mountings are: Type SSLR Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC - 15000-148 M.I.I. HVAC Issued for Construction 1 June 2004 C. Seismic Restraint Types 1. 2. Seismic Restraint Type I a. Each corner or side seismic restraint shall incorporate minimum 16 mm. thick pad limit stops. Restraints shall be made of plate, structural members or square metal tubing in a welded assembly, incorporating resilient pads. Angle bumpers are not acceptable. System to be field bolted to deck with 1 g acceleration capacity. b. Seismic spring mountings as described above are an acceptable alternative providing all seismic loading requirements are met. c. Mason Industries Type Z-1011, Type Z-1225, or as approved. Seismic Restraint Type II: Metal cable type with approved end fastening devices to equipment and structure. System to be field bolted to deck or overhead structural members or deck with aircraft cable and clamps as per SMACNA guidelines. D. Furnish and install as shown, or as approved, all necessary supports for equipment furnished under this Section. To meet the varying conditions in each case, these supports shall consist of pipestands, steel angle or strap hangers, saddles, brackets, etc., as shown, or as approved. All such supports shall have substantial flanges bolted to floor construction; hangers shall be supported from the framing as described hereinabove. Supports shall be properly located with reference to any supporting pads, legs, etc., of the equipment carried and must be of such number and so distributed as not to bring any undue strains to the equipment. All details shall be as approved. E. Provide suitable brackets, pipestands, piers or other supports for all various float traps, receivers, etc. Also provide suitable supports for all tempering stacks, air filters, mixing and control dampers, etc., securely clamped to steel beams, column or bearing walls. All details of this work shall be as shown on the drawings, or as approved. F. Guarantee that the work, as installed under this Section of the Specifications, shall not result in the transmission of objectionable noise or vibration to any occupied parts of the building, and take full responsibility for any necessary modifications of this equipment, or of the foundations and supports for the same, necessary to secure this result. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-149 HVAC Issued for Construction 1 June 2004 2.39 WORK IN CONNECTION WITH EMERGENCY GENERATOR AND FUEL OIL SYSTEM A. Emergency generator and diesel fire pump, flexible connectors and silencers shall be provided under the Electrical Section and Plumbing Section of the Specifications, respectively. The work to be performed under this Section shall include all work associated with the installation monoxide exhaust system, flexible connectors, generator silencers, the fuel oil system, including all piping, valves and pipe specialties, tank, and tank accessories, the ventilation air system, automatic dampers, etc. as shown on drawings and specified. B. All products specified herein shall be manufactured by one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers” C. Exhaust flue piping shall be attached to the building structure in such a manner as to prevent any vibrations from the generator being transmitted to the building and to allow for the thermal growth of the generator silencer and the flue pipe without exerting any forces due to such thermal movement on the building structure. Submit method of supporting the silencer and flue piping which shall be as recommended by the generator manufacturer. Submit weights and reactions of the silencers and flue piping for review by the Structural Engineers. D. The exhaust flexible connection(s), exhaust silencer(s), and exhaust piping arrangement shall be installed in accordance with the successful engine/generator and fire pump manufacturer's installation drawings. The engine-generator manufacturer shall furnish a detailed piping installation drawing. If, as a result of a different arrangement of pipe sizes, equipment, sizes and/or quantities of engine-generator sets or fire pump made by the successful engine-generator or fire pump manufacturer, there are any additional costs incurred, all changes required shall be at no additional cost to the Owner. E. Engine exhaust piping and silencers shall be insulated in its entirety and protected from the weather in accordance with Article entitled "Insulation". F. Subcontractor shall provide sufficient fuel oil for the initial testing and starting up of the emergency generator. G. Fuel Oil Storage Tanks 1. Provide two (2) all welded horizontal fuel oil main storage tanks, each having a capacity of 37,850 liters, and one (1) all-welded horizontal fuel oil storage day tank having a capacity of 1,040 liters, suitable for installation inside the building. Tank shall be constructed of not less than 7 mm. thick Class A steel, in strict accordance with Underwriters Laboratories specification. All Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-150 HVAC Issued for Construction 1 June 2004 heads and shell rings shall be of 8mm. thick one-plate construction. Tanks 1,850 mm. to 3,050 mm. in diameter shall have 8 mm. thick shell rings and 10 mm. thick heads, tanks larger than 3,050 mm. in diameter shall have 10 mm. thick shells and heads and angle ring stiffening. Plates shall be gauged and inspected by a UL representative before fabrication. 2. Each tank shall be lap welded continuously on the outside, and may be tack welded on the inside in accordance with UL specifications for same. Prior to painting, tank shall be pressure tested against leakage of not less than 35 kPa nor more than 50 kPa. 3. Each tank shall be furnished with suitable saddles welded to the tank designed to continuously support the tank along the full length of the saddle base. 4. Both the interior and exterior surfaces of tank(s) shall be sand blasted after fabrication to remove rust and scale to a near white blast in accordance with Specification SSPC-SP10 prior to factory applying paint. Tank(s) shall be internally coated with one coat of epoxy primer to a dry film thickness of 1.5 mils with two top coats of epoxy to a dry film thickness of 2.0 mils per coat, cured under controlled conditions, and be suitable for use with No. 2 fuel oil as intended. Coating shall be Carboline 187 system or as specified. Paint exterior of tank(s) and the supporting frame(s) with two coats of red oxide paint, and suitably prepare for final field finish painting. 5. Provide tank(s) with 600 mm. diameter gasketed combination hinged manhole cover and emergency vent, integral internal ladder (painted in accordance with the above) and exterior ladder extending from the top of the tank down to the floor. Furnish each above ground tank with an exterior ladder with OSHA approved safety cage. The exterior ladder shall terminate at the top of tank to a continuous platform at the top of the tank. The platform shall be constructed of galvanized grating and be completely enclosed with OSHA approved safety railing. Platform shall be such that all tappings into the top of the tank are completely accessible from within the railed area. All piping connection fittings, manways and covers and structural accessories, including ladders, saddles, platforms, railings, support frames, etc., shall be furnished complete by the tank manufacturer. 6. The main fuel oil storage tanks shall be furnished with fuel oil level switches with dry contacts for remote alarm indication of tank high level, low level, or extreme low level at the master fuel Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-151 HVAC Issued for Construction 1 June 2004 oil system control cabinet. The day tank shall be furnished with four level switches to provide the following functions: 7. H. a. Extreme High Level: Alarms at emergency generator control cabinet and via dry contact from the emergency generator control cabinet alarms at the master fuel oil control cabinet, closes fill solenoid valve to day tank. b. Normal Level: Closes solenoid fill valve and stops pumps if the generator is off. c. Low Level: Opens solenoid fill valve and starts pumps if not running. d. Extreme Low Level: Alarms at emergency generator control cabinet and via dry contact from the emergency generator control cabinet alarms at the master fuel oil control cabinet. Provide a competent, factory service representative for final inspection of the fuel oil storage tank after installation is complete to perform a thorough inspection of the fuel oil storage tank(s), including all piping connections. Report deficiencies in writing to the Engineer's Representative and the Consultant. Tank Gauging System: Furnish a master fuel oil system control cabinet to provide continuous indication of fuel oil level in each fuel oil tank, manual fuel oil transfer pump control, fuel oil system alarm monitoring, water level alarm and tank status. The fuel oil control cabinet shall be free standing, constructed of 3 mm. steel continuous seam welded construction. The cabinet shall have two (2) full length, fully gasketed rear doors constructed of 2 mm. steel with 3 point latch and locking handle and three (3) lifting eyebolts. All internal components shall be mounted on removable perforated subplates. Cabinet finish shall be prime coated and painted as follows: exterior: Chemical resistant textured gray enamel; interior: white baked enamel; subplates: white baked enamel. The cabinet shall be factory wired and tested. All cabinet mounted devices shall be prewired to terminal strips for connection to field mounted devices. Cabinet mounted devices and field mounted devices shall include, but not be limited to the following: 1. Cabinet-Mounted Devices a. Digital Tank Gauge/Leak Monitoring Instrument 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Leak monitoring instrument shall be a remote reading microprocessor based tank gauge with integral audible alarm and adjustable alarm set points. Instrument shall be designed for use with single or double wall and vaulted fuel oil storage tanks with all grades of fuel oil. Visual 15000-152 HVAC Issued for Construction 1 June 2004 display shall be 20 mm. digital characters with Arabic messages for leak detection, tank overfill, and low liquid level. Calibration shall be non-volatile. Power interruption shall not necessitate recalibration. Door-mounted devices shall include tank volume content, alarm displays, operational pushbutton and audible alarms. 2. a) Instrument housing shall be 200 mm. wide x 250 mm. high x 100 mm. deep. Instrument shall provide 4-20 mA output, indicating actual volumetric quantity and relay contact (SPDT) indicating alarm. Power requirement shall be 240VAC. b) Digital tank gauge/leak monitoring instrument shall be as manufactured by Preferred Instrument, Model TG-EL-D3. b. One (1) programmable logic controller (PLC) as manufactured by G.E. Fanuc or Engineer approved equal. c. Two (2) pump-hand-off-auto selector switches. d. One (1) lead pump selector switch. e. All necessary alarm lights, alarm horn, lamp test pushbutton, alarm silence pushbutton, 0-30 minute (adjustable timer to reenergize the alarm horn after actuation of the silence pushbutton, including circulation alarm beacon light, indicating status lights, circuit breakers, relays, motor starters, etc. to provide all required control status and alarm functions as indicated in Table "A". Field-Mounted Devices a. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Provide one (1) leak sensor each for the Diesel Fire Pump Room, day tank basin, main fuel oil tank vault, and Fuel Oil Transfer Pump Room. Leak sensor shall be intrinsically safe and shall be capable of detecting the presence of oil or water. Sensor shall indicate either water or oil detection and send a signal to the leak monitoring instrument. Leak sensor shall contain a magnetic test switch for manual testing. Sensor shall be 15000-153 HVAC Issued for Construction 1 June 2004 water- and oil-tight. Leak sensors shall be equal to Preferred Instruments Model HD-A1. b. Provide five (5) leak sensors for outer pipe containment. Switch wiring shall be protected in a heavy duty cast aluminum NEMA-4 watertight enclosure. Electrical rating shall be 8 VA pilot duty. Switch action shall be SPST N.C./N.O. Leak sensors shall be equal to Preferred Instruments Model RBS. c. All leak sensors shall be intrinsically safe, have continuous electronic checking, fail-safe to an alarm condition and have indicating transmitters with test switches to exercise the sensors and check the instrument response. Test systems that bypass the sensors or relay only on electronic simulation are unacceptable. d. Water Detection: Provide and install a single point capacitance level switch in each fuel oil tank to detect presence of water. The assembly shall consist of an integral mounting between a weighted TFE coated flexible probe and a NEMA 4X enclosure. Probe length shall be coordinated with tank size and shall be field adjusted to alarm at a level of water 500 mm. above the bottom of the fuel oil tank. Unit shall operate on a 240 VAC input. TABLE "A" Alarm No. Alarm Description 1 2 3 4 5 Main Fuel Oil Tank No. 1 - High Level Main Fuel Oil Tank No 2 - High Level Main Fuel Oil Tank No 1 - Low Level Main Fuel Oil Tank No 2 - Low Level Main Fuel Oil Tank No 1 - Extreme Low Level Main Fuel Oil Tank No 2 - Extreme Low Level Fuel Oil Day Tank - Extreme High Level Fuel Oil Day Tank - Extreme Low Level Fuel Oil Pump FOP-1 - Malfunction Fuel Oil Pump FOP-2 - Malfunction Main Fuel Oil Tank No. 1 Supply/Return Solenoid Valve Misaligned 6 7 8 9 10 11 Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-154 HVAC Issued for Construction 1 June 2004 Alarm No. Alarm Description 12 Main Fuel Oil Tank No. 2 Supply/Return Solenoid Valve Misaligned Emergency Generator No. 1 - Supply Isolation Valve Closed Emergency Generator No. 1 - Supply Solenoid Valve Closed Emergency Generator No. 2 - Supply Isolation Valve Closed Emergency Generator No. 2 - Supply Solenoid Valve Closed Emergency Generator No. 3 - Supply Isolation Valve Closed Emergency Generator No. 3 - Supply Solenoid Valve Closed Diesel Fire Pump Isolation Valve Closed Diesel Fire Pump Day Tank - Supply Solenoid Valve Closed Firematic Valve Closed (Transfer Pump Room) Firematic Valve Closed (Generator Room) Firematic Valve Closed (Diesel Fire Pump Room) Fuel Oil Pump FOP-1 - Inlet/Discharge Valves Closed Fuel Oil Pump FOP-2 - Inlet/Discharge Valves Closed Fuel Oil System - Isolation Valves Misaligned Fuel Oil Pump FOP-1 - Relief Valve Actuation Fuel Oil Pump FOP-2 - Relief Valve Actuation Duplex Strainer - Fuel Oil Pump FOP-1 - High Differential Duplex Strainer - Fuel Oil Pump FOP-2 - High Differential Fuel Oil Outer Pipe Containment Leak (Base of Riser) Fuel Oil Outer Pipe Containment Leak (Pump Room) (Two Required) Fuel Oil Outer Pipe Containment Leak (Generator Room) 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-155 HVAC Issued for Construction 1 June 2004 Alarm No. Alarm Description 34 Fuel Oil Outer Pipe Containment Leak (Fire Pump Room) Fill Sump - Tank High Level Main Fuel Oil Tank Vault - Leak Fuel Oil Transfer Pump Room - Leak Diesel Fire Pump Room - Leak Fuel Oil Day Tank Basin - Leak Main Fuel Oil Tank No. 1 - High Water Level Main Fuel Oil Tank No. 2 - High Water Level Fuel Oil Day Tank - High Water Level PLC - Education Wing Roof (Emergency Generator Room) - Malfunction PLC - Basement (Fuel Oil Pump Room) - Malfunction 35 36 37 38 39 40 41 42 43 44 3. All alarms listed in Table "A" shall be retransmitted to the DDC system via dry contact outputs originating from the master or remote fuel oil system control cabinet PLC. Instantaneous tank level readings shall also be monitored at the DDC system via interface with the cabinet PLC via a N.O. bus protocol. 4. In addition, each panel shall have pilot lights indicating each alarm listed in Table "A", as well as a five (5) digit display of each tank content level. The indicating lights shall be activated from PLC digital outputs. 5. Provide a remote fill alarm with both audible and visible alarms, alarm silence and test push buttons, mounted in the wallmounted fill spill box enclosure. The audible alarm shall be a 100 mm. 90 dB bell which is automatically silenced after 90 seconds or immediately silenced after activation of the alarm silence push button. There shall be a separate visual alarm for each fuel oil storage tank. The visual alarm shall be a red protruding lens which is visible in direct sunlight for 180º. The visual alarm shall flash continuously until the fuel oil level goes below the alarm set point. 6. Furnish a remote fuel oil annunciator cabinet to provide the identical control, monitoring and alarm function provided by the master fuel oil system control cabinet. The remote fuel oil annunciator cabinet shall be constructed identical to the master fuel oil system control cabinet and contain the same components. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-156 HVAC Issued for Construction 1 June 2004 I. 7. The master fuel oil system control cabinet PLC and the remote fuel oil annunciator cabinet PLC shall be interconnected via a communications cable which shall be run in conduit. 8. The master fuel oil system control cabinet shall be located in the Fuel Oil Transfer Pump Room. The remote fuel oil system control cabinet shall be located in the Emergency Generator Room. Automatic Tank Selection System: Provide a PLC based automatic tank selection system to provide automatic selection of the "in service" tank from the two main tanks. 1. 2. Panel-mounted components shall include: a. Two electronic tank gauges as hereinbefore specified. b. Three-position Tank Selector Switch for selection of Tank 1, Tank 2, or Automatic Tank Selection. c. Lead Tank Selector Switch, to select Tank 1 or Tank 2, to be used first. d. Logic to provide automatic selection of tank based on tank level and to operate the multiport tank selector valve in the supply and return lines to each tank. e. Audible and visual alarm of tank leak, tank high level, tank low level and extreme low level. f. Relay contacts to operate the Tank Overfill Alarm Panel. g. Relay contacts to forward tank alarms to the building automation system. Tank Selection Sequence of Operation a. In the "Automatic Tank Selection" mode, the multiport valve shall be positioned to open the supply and return for the lead tank and close the supply and return to the lag tank tank. b. Should the level of oil in the lead tank fall below the low alarm set point, an alarm shall sound and the multiport valve shall be repositioned for the lag tank. c. At no time shall all of the supply and return ports be closed. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-157 HVAC Issued for Construction 1 June 2004 d. When both tanks are at the low level alarm set point or below, a relay contact shall close and an alarm shall sound. e. If tank selection is performed manually, the logic shall provide overlap between tanks any time the tank selection is changed to prevent operation without a supply and return path for oil at all times. f. Logic shall continuously check that the supply and return valves on the pumps are open. Should any valve fail to maintain the correct position an alarm light shall light and the alarm shall sound. Alarm contacts shall be available for the connection of remote alarms. J. Fuel Oil Tank Accessories: Provide for each of the main fuel oil tanks, a 100 mm. “Preferred Utilities” Model No. 2-4, or as approved, lock-type in-wall spill fill box, 60 mm. vent hood and 50 mm. stick gauge box of approved type, see drawings for locations. Provide a 40 mm. vent hood and 50 mm. stick gauge box of approved type for the fuel oil day tank. Spill box shall be equipped with overfill alarms and level indication for each tank. Fill connections for each tank shall be equipped with an adaptor fitting with spring loaded check valve suitable for use with "Kamvalok" type hose coupler. K. Fuel Oil Transfer Pumps: Fuel oil transfer pumps shall be as scheduled and as shown on plans. The pump set shall be duplex, rotary screw, positive displacement type (refer to Article "Duplex Fuel Oil Pumps"). Pump set shall be resiliently mounted on a substantial steel base, prepiped with separate suction lines (flanged) and common discharge line (flanged), and shall include but not be limited to the following: Pressure gauges on suction (compound type on suction) and discharge, relief valve on each pump discharge piped back to pump suction, ball valves and duplex canister strainers on each pump suction and separate ball valve and check valve on discharge of each pump. The pump set shall be furnished with a completely prewired electrical control system with all components including all required starters, surface mounted Lead/Lag selector switches and Hand/Off/Auto switches for each pump, indicator lights, control transformers, pressure interlocks, lead/lag alternator, auxiliary contacts for remote start/stop, etc., all components shall be installed within an approved NEMA type enclosure mounted on the base. L. All horizontal fuel oil piping between the Fuel Oil Transfer Pump Room and the Generator Room, and the Fuel Oil Transfer Pump Room and Diesel Fire Pump Room, shall be run within welded black steel outer piping and the entire installation covered with a two-hour fire rated enclosure. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-158 HVAC Issued for Construction 1 June 2004 M. Central Fuel Oil Filtration and Dewatering System 1. Furnish and install a factory assembled and tested system to continuously filter and de-water the stored No. 2 diesel fuel, monitor the integrity of the main fuel transfer pump set suction piping, periodically test the flow control and fuel transfer system, and automatic injection of fuel stabilizing additive. The system shall filter and treat the contents of two (2) 37,850 liter main storage tank(s). The entire contents of one main tank shall be circulated every 16 hours of system operating time. The integrity of the suction piping to the main fuel transfer pump and the operation of the main fuel transfer set shall be checked at least once every 24 hours. In addition, the fuel in the generator supply manifold shall be circulated and exchanged regularly with the treated and filtered oil from the main storage tanks. a. 2. Water removed from the fuel shall be stored in a corrosion proof double wall container until disposal can be arranged. Fuel quality monitoring control and annunciation system shall be integrated with the main oil transfer pump control system contained in one NEMA 12 cabinet. The control system cabinet shall contain (as a minimum) the following devices: a. A Programable Logic Controller (PLC) to control and annunciation system functions as described herein to monitor the performance of the fuel maintenance system and to alert operating personnel of excessive fuel contamination, loss of pump prime for the main transfer systems, failure of the main transfer system to prove flow daily, dirty filter cartridge, or filled water storage reservoir. Provide annunciator panel for remote mounting to duplicate all status and alarm information. b. System main disconnect. c. Combination circuit breaker/motor starter for circulating pump motor. d. Contactor for the water transfer pump. e. Selector switches for the following: Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) Hand/Off/Auto switch for the main circulating pump. 2) Auto/Off switch for the water transfer pump. 15000-159 HVAC Issued for Construction 1 June 2004 f. 3) Cycle duration selector switch. 4) Auto/Off switch for the chemical additive pump. Pushbuttons for the following: 1) Fuel Maintenance Cycle Start Pushbutton. 2) Fuel Maintenance Cycle Cancel Pushbutton. 3) Lamp Test. 4) Alarm Acknowledge. 5) Alarm Silence. g. Alarm Horn. h. Indicating lights for: i. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) Circulating pump run. 2) Additive pump run. 3) Water removal pump run. The following alarm points shall sound the alarm horn and illuminate an alarm indicating light which shall remain lit until the alarm is acknowledged and cleared: 1) Failure during Flow Test. 2) Excess Water in Fuel Alarm. 3) Water Storage Tank Full Alarm. 4) Strainer Dirty Alarm. 5) Filter Dirty Alarm. 6) Leakage into System Drip Pan Alarm. 7) Leakage into Water Secondary Containment Alarm. 8) Loss of Flow, Filtration Cycle. 9) Additive Tank Empty. 15000-160 HVAC Issued for Construction 1 June 2004 3. j. An automatic tank selection system as herein described above shall be included to sequence the tank in service based on individual tank level signals. The system shall also rotate tanks for filtration and dewatering. k. The fuel monitoring and tank selection system shall be fabricated as an integral part of the main fuel transfer system and the controls described herein fully integrated with the control system for the fuel transfer and supply manifold flow management system. All of the components shall be factory mounted on a 6 mm. thick structural steel base with integral 150 mm. high steel containment lip, seam welded to the steel base to form a leaktight pan. Base shall extend beyond any fitting, valve, pump or strainer to assure that a fuel leak from any component, fitting, or packing in the system shall be contained within the pan. The same steel base and containment pan shall be used to support the fuel transfer pumping and straining system described elsewhere in this Specification. a. Furnish a liquid detector to provide an audible and visual alarm should any liquid accumulate within the pan. b. The Subcontractor shall grout the base in place at time of installation to minimize the generation of noise by the pumps. c. Suction from the fuel maintenance system shall extend to the lowest point of the storage tank(s) so that any water accumulating from leakage, contaminated fuel delivery, or condensation shall be drawn into the filter and dewatering system. A separate suction pipe terminating approximately 150 mm. above the low point of the tank shall be used as the inlet to the fuel oil transfer pumps to eliminate the possibility of drawing water or sediment into the engine fuel system. d. Fuel entering the maintenance system shall pass through a suction line sized cast iron body duplex strainer with a bronze plug type selector valve and 100 mesh stainless steel wire cloth baskets to remove large particles and foreign matter from the fuel. A single swing handle shall make one basket active and isolate the other so that the inactive basket may be inspected and cleaned without shutting down the system. The unit shall be rated for the system operating oil pressure. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-161 HVAC Issued for Construction 1 June 2004 e. f. Fuel leaving the duplex strainer shall enter a sealed filter and dewatering unit housed in a rugged, epoxy coated steel enclosure with removable gasketed cover, and fitted with an integral water containment sump and electronic water detector. 1) Fuel shall first pass through a turbine type water separation unit to remove large water droplets prior to passing through a resin impregnated cellulose water coalescing element designed to remove suspended water from the fuel. Water removed by the separator and coalescing element shall flow to the temporary water holding sump. 2) The moisture content of the exiting fuel shall br reduced to less than 10 ppm. 3) After the water removal stages, the fuel shall pass through a polishing filter with a 96% removal efficiency for particles larger than 2 microns. 4) The water and solids removal elements shall be field replaceable without special tools. The filter unit enclosure shall be fitted with a removable top cover and nitrile "O" ring seal. The unit shall be supplied with all elements installed and four complete sets of replacement filter cartridges. 5) A differential pressure indicator shall be installed around the filter unit to provide a visual indication of filter element condition. A differential pressure switch shall be installed to provide an alarm when the filter elements require replacement. The fuel maintenance system shall be provided with an oil circulating pump. The pump shall be capable of pumping .65 l/s per hour of diesel fuel through the filtration and dewatering system. 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Oil pump shall be positive displacement type with cast iron body, precision milled and ground ductile iron rotor and idler gear, self-adjusting Buna-N mechanical ring seal, and ball bearing drive shaft support coupled via flexible coupling to a NEMA frame, three-phase, open dripproof motor. 15000-162 HVAC Issued for Construction 1 June 2004 2) Motor and pump shall be precision aligned and mounted to a structural steel channel base, and installed on the common baseplate via synthetic rubber vibration isolators. Electrical and piping connections shall be flexible to minimize noise and vibration transmission into the building system. g. Provide a relief valve for each pump piped to the common return line back to the main tanks. Relief valves shall be constructed with 20 bar bronze body, adjustable spring and stainless steel ball sized to pass the full flow of the pump without overloading the pump drive motor. h. Provide flow sensors in the pump discharge to signal failure of the system. i. All water removed from fuel shall be pumped automatically from the filter housing sump to a holding tank. A bronze body gear pump with carbon bushings, stainless steel shafts, and Teflon mechanical seal shall be furnished to pump water to the holding tank. Pump capacity shall exceed the water removal rating of the coalescing unit. j. 1) The water transfer pump shall be mounted and piped with vibration isolators similar to those utilized for the oil pumps. 2) Provide an electrically operated valve between the sump and the water transfer pump to prevent leakage of water into the fuel, or fuel into the water holding tank, when the system is idle. Holding tank shall be centrifugally cast fiber glass reinforced isophalic polyester resin and shall have a capacity of not less than 75 liters. Tank shall be equipped with a high level switch to sound an alarm, light a light and shut down the fuel maintenance system until the tank is emptied. 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC The holding tank shall be fully enclosed in a secondary containment vessel of equal construction and furnished with a fill pipe for connection to the fuel maintenance system, a vent tapping, high level switch, and dip tube to allow periodic withdrawal of the waste water for disposal. 15000-163 HVAC Issued for Construction 1 June 2004 k. A welded steel chemical additive holding tank be sized to hold a minimum of five years supply of fuel stabilizing additive, as recommended for this installation by the additive manufacturer. 1) l. m. n. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Tank shall be manually filled with fuel stabilizer additives every five years or whenever the main tank(s) are refilled. A positive displacement cast iron metering pump with stainless steel trim, Teflon diaphragm and totally enclosed 1/3 hp motor shall inject additive into the oil while the oil is circulating in order to ensure complete mixing. 1) Output of pump shall be adjustable from 0% to 100% of capacity to trim the amount of additive delivered during each operating cycle. 2) Control system shall automatically operate the metering pump during each filtration cycle to maintain an effective level of fuel stabilizer in the main tank(s). Piping in the fuel oil fuel maintenance system shall be as follows: 1) Fuel piping shall be standard weight malleable iron with screwed fittings. 2) Water piping shall be copper with hard soldered sweat fittings or threaded brass pipe and fittings. 3) All other piping shall be suitable for the fluids handled. Nonmetallic tubing or hose is not permitted. Furnish valves where shown on the drawings, and where required for the operation of the system and to allow any component to be removed without draining the entire system. 1) Shutoff valves shall be class 150 bronze body ball valves with stainless steel balls and Teflon seats. 2) Check valves shall be "Y" construction, swing type bronze body with regrindable metal to metal seal. 15000-164 HVAC Issued for Construction 1 June 2004 o. Furnish liquid filled, 100 mm. diameter gauges, with built-in pulsation dampener and stainless steel case at the inlet and discharge of each filter or pump. 1) Unless otherwise noted, all gauges for the fuel maintenance system shall be compound type with 100 kPa vacuum to 1.0 bar pressure range to accommodate low operating pressures. p. Operation of the fuel maintenance system shall be adjustable to coincide with the schedule of the operating and maintenance staff of the facility, so that any alarm conditions generated by the system may be acknowledged and attended to at once. q. A solid-state water detector in the water sump of the filter enclosure shall cause a solenoid to open and the pump in the discharge of the water sump to operate, transferring the accumulated water to the holding tank. r. If the water transfer pump cannot keep up with the amount of water being removed, an alarm shall sound and a light shall light indicating that this has occurred, the oil circulating pumps shall shut down until the water can be cleared from the sump. Water shall not be returned from the system to the oil storage tank(s). s. The alarm light shall require a manual reset action to extinguish so that the alarm shall remain visible until the system returns to normal operation when the water is cleared. t. To prevent fuel degradation, the additive feed pump shall operate during circulating pump operation when required to maintain an effective level of fuel stabilizer in the fuel storage tank. u. If the integrity of the suction piping to the main transfer pumps is proven, the day tank replenishment and level management test shall begin. At the completion of the test the PLC controller shall simulate a "generator run" signal to call the main transfer pumps into operation resulting in recirculation of fuel between the tank(s) and the generator supply manifold so that the contents of the manifold are replenished with clean fuel. v. A check timer shall start to verify fuel flow to the generator supply manifold, if system has failed its flow Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-165 HVAC Issued for Construction 1 June 2004 test cycle within the check time period an alarm shall annunciate at the control panel. w. 2.40 This test shall be automatically suspended if any alarm conditions are logged during the preceding phases of the fuel maintenance and system test cycle. DUPLEX FUEL OIL PUMPS A. Provide, where shown on the drawings, fuel oil pumps. Pumps to be complete with all equipment hereinafter specified, mounted, piped and wired by Subcontractor in field on a steel stand ready for oil suction, discharge and electrical connections. The unit shall be complete with the following equipment: 1. Pumps shall be positive displacement gear type units, suitable for No. 2 fuel oil piping. Shop drawings must make a statement to this fact. Fuel oil pump motors shall be 415 volt, 3 phase, 50 hertz, and shall operate at a maximum speed of 1800 rpm. 2. One (1) screwed duplex strainer for the suction side of pump. Strainers shall be similar to Preferred Instruments No. 50 standard cast iron body, or as approved. Strainer shall have onepiece cast iron body ASTM A-48-58, Class 30, hydrostatically tested at 20 bar, and suitable for 15 bar service. 3. Provide two (2) fuel oil pump relief valves, piped from the pump discharge piping to the return pipe leading to the storage tanks. Each valve shall be similar to Bailey No. 118, or as approved, with an adjustable range of 5 to 15 bar, set at 7 bar. In addition, provide two (2) 3-wire resistance temperature detectors to monitor transfer pump relief valve temperature. 4. Provide two (2) 40 mm. dial compound gauges to be placed on suction and discharge sides of suction strainer (see drawings). Each gauge shall be similar to Ashcroft, 2 bar and 100 kPa vacuum, or as approved. 5. Provide one (1) dial pressure gauge to be placed on discharge side of pumps (see drawings). Gauge shall be similar to Ashcroft, 0-20 bar, or as approved. 6. Provide solenoid valves to interlock fuel oil flow to emergency generators and/or diesel fire pump day tank. 7. Provide in the common discharge pipe of each duplex pump set, a flow switch to prove flow upon pump activation. If flow is not proven within 20 seconds of pump activation, a “no-flow” alarm shall be transmitted to the master fuel oil system control cabinet. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-166 HVAC Issued for Construction 1 June 2004 B. C. Motor Starters 1. Provide motor starters and control packages for each duplex fuel oil pump set, in NEMA enclosures. The control package shall include control transformer, pressure interlocks, automatic alternator, lead/lag controls, selector switches, auxilliary contacts for remote start stop and all indicator lights. 2. Provide On/Off switches and Hand-Off-Automatic switch for each oil pump. 3. A wiring diagram shall be mounted on the Fuel Oil Transfer Pump Room wall. 4. Perform necessary wiring and provide necessary components to interlock operation of fuel oil pump with emergency generator start contacts and diesel fire pump day tank level contacts. Wiring between the emergency generator/emergency generator control panel shall be furnished and installed under the Electrical Section of the Specifications. Piping and Valves 1. All fuel oil piping shall be of the sizes noted on the drawings and as scheduled elsewhere. All oil side gate valves, as noted, shall be similar to Jenkins, or as approved. Ball valves shall be equipped with stainless steel ball and stem. Globe valves shall be similar to Jenkins, or as approved. Vertical ball check valves for discharge side of each fuel oil pump shall be constructed of bronze with steel ball and shall be similar to Lunkenheimer, or as approved. 2. All piping, valves and fittings shall be in accordance with the drawings and shall be field fabricated. NOTE: 2.41 Fuel oil piping arrangement shall have pressure loop, servicing each emergency generator. Supply line to each generator shall originate from pressurized side of supply loop, and return line from each generator shall be connected to return loop piped back to the main fuel oil storage tank(s). MOTORS A. All motors and accessories shall comply in all respects with NEMA, ANSI, IEEE and NEC Standards, all applicable Codes and the requirements of local authorities. Motors shall be manufactured by one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-167 HVAC Issued for Construction 1 June 2004 B. Furnish and install all electric motors driving heating, ventilating and air conditioning equipment. Motors shall be “high-efficiency” of sizes and types as specified, of the proper power and speed to suit the specified makes of equipment. If other than the specified makes of equipment are accepted, the proper adjustment of motor horsepower, motor speed, wiring, motor disconnect and starter sizing must be included without additional cost. Drawings and data sheets shall be submitted for approval before the equipment is purchased. C. All motors .37 kw and larger shall operate on 415 volt, 3 phase, 50 hertz, alternating current, except as otherwise noted. All motors smaller than .37 kw shall operate on 240 volt, single phase, 50 hertz, alternating current, except as otherwise noted. D. Motors driving vaneaxial fans and pumps shall be direct connected; motors driving centrifugal fans shall be belt connected. All motors shall be suitable for the use intended i.e. with variable speed (variable frequency/voltage) drives cycled start/stop and/or constant speed as scheduled. Motors used in variable speed applications shall be designed to operate under variable torque load (or as specified) from maximum rated speed down to 10% of rated speed. Motors shall be designed to operate continuously at any point in the speed range. Any deviation from this requirement shall be noted and submitted with bid. E. In general, except as otherwise specified, all motors shall be open dripproof squirrel-cage induction type, guaranteed to fulfill the specified requirements without producing any sound audible outside of Machine Rooms. Motors shall be constructed in accordance with the following: 1. NEMA Class "B", with Class "B" or "F" nonhygroscopic insulation. 2. Motors rated for continuous duty shall operate with a 1.15 service factor at 40°C. ambient temperature. Motor temperature ratings shall conform to NEMA Standard MG-1-12.42. 3. The motor conduit box shall be cast iron, diagonally split with threaded hole for conduit. 4. Motors shall be of cast iron construction. Aluminum frames are not acceptable. 5. Each motor shall have a stainless steel nameplate containing the following minimum information: Manufacturer Type Model Horsepower Service Factor Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC rpm Voltage/Phase/Frequency Enclosure Type Frame Size 15000-168 UL Label Connection Diagram Motor Efficiency Full-Load Current HVAC Issued for Construction 1 June 2004 6. All belt-connected motors shall be provided with adjustable bases and set screws to maintain proper belt tension and alignment. Provide proper belt guards meeting all OSHA requirements. F. Motors shall be fitted with extra heavy duty bearings and seals with a minimum B10 life of 100,000 hours (rated at continuous duty). Bearings shall be fitted with Zerk or Alemite lubrication fittings and excess lubrication drains. Where motors are concealed or as specified elsewhere, the grease fittings and lubrication drains shall be extended to the outside of the respective housing of the unit for ease of service. G. Motors shall have the following guaranteed minimum efficiencies when tested in accordance with IEEE Standard 112 Test Mounted Method B: The spread between the specified minimum efficiency and the nominal efficiency shall not exceed the values listed in NEMA Standard MG-112.536. KW HP .75 1.1 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 150 1 1-1/2 2 3 5 7-1/2 10 15 20 25 30 40 50 60 75 100 125 150 200 H. Nominal Minimum Efficiencies (%) @ 1750 rpm Driproof Type TEFC Type 84.0 86.5 86.5 86.5 86.5 88.5 88.5 90.2 91.0 91.7 91.7 92.4 93.0 93.0 93.6 93.6 93.6 94.1 94.1 82.5 82.5 82.5 84.0 85.5 87.5 88.5 88.5 90.2 91.0 91.7 91.7 92.4 93.0 93.0 93.6 93.6 94.10 94.5 Coordinate motor with the torque and inertia load of the equipment served, and the inrush characteristics of the motor with the starter selection, so that all items furnished constitute a properly related package. No motor shall operate in the service factor range. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-169 HVAC Issued for Construction 1 June 2004 2.42 I. All motors shall be sized to have sufficient starting torque to be able to accelerate the driven load from zero rpm to design speed rpm within 6 seconds maximum. Submit substantiating calculations. J. Motor shall be adequately protected against water and dirt damage until operational. K. Extra Stock: Provide one (1) spare motor for each type, size and capacity scheduled for air handling units, fans, pumps, cooling towers, etc. Obtain receipt from Engineer that spare motors have been received. VARIABLE SPEED MOTOR CONTROLLERS A. Variable Speed Motor Controller 1. Variable speed motor controllers and starters shall be designed and constructed in accordance with the National Electrical Code all applicable local code requirements and ANSI, FS, IEEE, NEMA and UL standards. 2. Variable motor controllers shall be manufactured by one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. 3. Controllers shall be designed to withstand the following service conditions: 4. a. Elevation: To 1,000 meters altitude without derating. b. Ambient Temperature: 0°C. to 40°C. c. Relative Humidity: To 95% noncondensing. d. Input Voltage: 415 VAC, ±10%, 3-phase, 50 Hertz, ±2 Hz. e. Output Voltages: 0 to 415 VAC, 3-phase 3 to 50 Hz. The variable speed motor drives shall consist of a fully digital (front end) adjustable frequency, variable torque, a.c. motor controller performance matched to a high efficiency motor. The controller manufacturer shall assume responsibility for matching motor and adjustable frequency controller characteristics to each other and to the requirements of the driven load. The controller must be able to safely vary the speed of the motor while allowing the motor to meet the requirements of the attached fan or pump speed torque curve as dictated by the system static and dynamic requirements at the shaft of the motor. The selection of the controller/motor combination must result in acoustically compatible performance without objectionable motor noise. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-170 HVAC Issued for Construction 1 June 2004 Costs associated with field adjustment and/or modifications of the controller to eliminate objectionable motor noise shall be borne by the controller manufacturer. 5. Enclosures shall be NEMA 1. All controllers and associated auxiliaries shall be mounted within enclosures, suitable for floor, rack, or motor control center mounting without modification of the enclosure. 6. Power terminations shall consist of pressure type copper feeder cable terminals for top or bottom entrance, with wire way space suitable to meet the applicable Codes. All exit/entrance conditions must be coordinated with the Plans and the Installing Subcontractor. Ground lugs shall be provided for incoming and outgoing ground connections. All internal power wiring, control wiring, bus bars and associated components shall be copper. 7. Enclosure doors shall be key-locked with interlock provisions to prevent unauthorized opening of the door with the disconnect circuit breaker in the on position. 8. The enclosure shall provide adequate conduit space and wire ways and/or troughs in accordance with all applicable code requirements. 9. Field wiring of the adjustable frequency motor controllers and motors shall be limited to power supply connections to the controller, power output wiring from controller to the motor, grounding connections, and signal wiring and single phase interlock control wiring that is required for connection to devices for the remote control of motor speed and system operation from the building central control system. Field installed power, signal and control wiring shall be provided under another Section of the Specifications. 10. A built-in digital keypad shall be provided for adjustment of all internal drive functions. 11. The controller shall include, as a minimum, the following features and functions: a. A.C. incoming line circuit breaker with an interlocked, padlockable handle mechanism. b. The controller assembly shall be rated for 65,000 A.I.C. c. Designed to withstand output terminal line-to-line and line-to-ground short circuits without component failure. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-171 HVAC Issued for Construction 1 June 2004 d. Reverse phase and single phase loss protection for each phase on both the line (input) and load (output) sides of the VFD. e. Overfrequency protection. f. D.C. overvoltage protection. g. Surge protection from a.c. line transients. h. Motor slip dependent speed regulation 3% maximum. i. Frequency stability ±0.5% for 24 hours with voltage regulation of ±2% of maximum rated output voltage. j. Adjustable dwell time at start to optimize motor starting torque. k. 115 volt a.c. control power for operator devices. Control power shall be isolated from logic circuits. Control power transformer shall be fused on the primary and the secondary side. l. Instantaneous overcurrent protection at 115% of the control's rated current. m. Adjustable current limit (50-110% of the controller's rated current). n. Selectable volts per hertz (V/Hz.), linear or squared. o. Adjustable acceleration and deceleration times of 0-360 seconds for 0-50 Hz. p. Adjustable maximum speed 100-0%. q. Adjustable minimum speed 0-100%. r. Adjustable motor output voltage boost. s. Adjustable electronic motor overload protection from 60-100% of the control's rated current. t. Selectable inverted speed signal. u. Selectable automatic restart after a fault. v. External fault indicator of fire or smoke. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-172 HVAC Issued for Construction 1 June 2004 w. Up to two motor thermal overload relays with throughthe-door reset button. x. Critical speed avoidance (adjustable). y. Low frequency voltage boost. z. Stability from 0-100%. aa. 97% minimum efficiency at rated load. 12. The controller shall be capable of operation without motor connected. 13. The controller shall have power outage ride-through capability of 5 cycles. 14. The controller shall be capable of starting into a rotating motor, in forward or reverse direction. 15. A built-in digital display shall be provided to indicate: 16. a. Output Frequency b. Output Current c. Output Power d. Input Voltage per Phase e. Output Voltage per Phase f. Torque g. Motor rpm The display shall also indicate the following fault conditions: a. High Motor Current; line-to-line (overcurrent) b. High Motor Current; line-to-ground (ground fault) c. Overvoltage (high d.c. bus voltage) d. Overtemperature e. Undervoltage (low d.c. bus voltage) f. Stalled Motor g. Electronic Motor Overload Trip I2R h. Internal Control Fault (Function Loss) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-173 HVAC Issued for Construction 1 June 2004 17. 18. 19. i. 24 VDC Auxiliary Voltage Fault j. Drive Ready Input (Converter) Section a. The converter shall incorporate full wave diode bridge input. b. The input diode bridge shall offer complete immunity against voltage dips, line noise and harmonics. c. The input displacement power factor shall be 0.98 or better over the entire operating frequency and load range. d. The converter shall incorporate metal oxide varistors (MOV's) in accordance with ANSI C63.41-1980 for input surge protection. PWM Inverter Section .75 kw to 90 kw a. The inverter logic shall be fully digital, microprocessorbased, and the control logic circuits shall be galvanically isolated from the power circuitry. All inverter programming shall be via the digital keypad. b. The inverter shall provide smooth stepless operation of the drives motor from .5 to 50 hertz. The drive shall have the ability to operate up above 50 hertz in a constant horsepower mode up to 87 hertz. c. The inverter shall incorporate a switching power supply operating off of the d.c. link of the control, eliminating line disturbance sensitivity. d. Inverter shall be voltage source type with a pulse width modulated (PWM) output utilizing short circuit limiting bipolar power transistors. e. Pulse width modulation technique shall be flux-vector. Alternatively, insulated gate bipolar transistors (IGBT's) may be utilized. The drive shall include the following features and be capable of providing isolated output signals and accepting the following input signals, to permit interface with a microprocessor-based direct digital control (DDC), building automation and temperature control system: Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-174 HVAC Issued for Construction 1 June 2004 B. a. A hand-off-automatic switch to allow local speed control by a potentiometer in the hand position and remotely controlled with a dry contact signal and a remote speed command. b. Start/stop commands via closure of a dry contact (voltage-free contact). c. Status (via dry contact closure from drive). d. Drive malfunction (via dry contact closure from drive). e. Speed command input signal: 4-20 mA d.c., impedance 250 ohms. f. Drive speed feedback (via 4-20 mA signal). g. Drives serving fan systems shall have the following additional features: 1) Safety stop (via dry contact closure from DDC). 2) Fire system override start (via dry contact). This override shall function with the selector switch in hand, off or auto position. Distortion Factor 1. The drive manufacturer shall ensure that the distortion factor does not exceed 3% THD (voltage) at each drive input and 5% THD (voltage) at the point of common coupling (as defined on the electrical drawings) as defined by IEEE 519-1992. In no case shall the current THD exceed 10%. 2. If line reactors or tuned filters are required, they shall be supplied inside the inverter cabinet. If line transformers are required they shall be supplied in matching cabinets immediately adjacent to the drive which they serve. 3. Input line filters shall be capable of protecting electronics against transient voltage spikes of 10 kv, 50 joule. 4. Provide the necessary isolation transformers and/or filters such that the area of the notch in the line-to-line voltage waveform caused by the shorting of the converter bridge during the commutation cycle shall not exceed 22,800 volt/microseconds. 5. A harmonic analysis of the power system defining distortion factor (DF) through the 16th harmonic shall be provided with the submittal. This analysis shall show voltage and current Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-175 HVAC Issued for Construction 1 June 2004 distortion at 10%, 30%, 50%, 67%, 80% and 100% speed. Full motor power shall be used at 50 Hz. and follow the cubed speed power requirements of a centrifugal fan or pump at the lower speeds. If filtering is required, the analysis must show how the addition of the filters shall reduce the DF to within the specified levels. 6. C. D. A field test of the system harmonics shall be provided to ensure that the THD does not exceed 5% DF at the point of common coupling. If the inverter load causes greater distortion than defined, the drive manufacturer shall be responsible to further filter the line. Cost associated with the supply of the additional filters and their installation shall be borne by the drive manufacturer. Contactor Bypass 1. Each controller shall be provided with a contactor bypass to allow motor to be safely transferred from controller output power to the a.c. line, or from the a.c. line to the controller, while the motor is at zero speed. 2. The contactor bypass shall utilize two motor contactors electrically interlocked. One contactor is to open and close the connection between the controller output and the motor. The other contactor shall open and close the connection between the bypass power line and the motor, providing "across-the-line" starting. 3. Motor protection shall be provided in both the "controller" mode and the "bypass" mode by a motor overload relay. Relay control logic shall be included within the controller enclosure to allow the same "start/stop" command and system safety shutdown commands to operate the motor in both "controller" and "bypass" modes. The relay logic power shall be 115 volts. 4. The bypass circuit shall include a second disconnect installed in the controller. This disconnect shall provide the ability to safely troubleshoot and test the controller, both energized and deenergized, while the motor is operating in the "bypass" mode. 5. The entire contactor bypass assembly, as well as all associated auxiliaries, shall be mounted within the controller enclosure and shall be electrically, structurally and mechanically isolated from the controller itself. Painting: All internal and external surfaces shall be thoroughly cleaned and, except as otherwise noted, all factory manufactured and assembled apparatus that is not galvanized shall be factory coated with one coat of Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-176 HVAC Issued for Construction 1 June 2004 primer and two coats of machinery enamel at the factory. Provide one can of touch-up paint of matching color per unit to repair any damage which may have occurred during installation. E. Permanent Identification: A stainless steel tag shall be attached to all units and stamped in not less than 16 mm. high letters with the Engineer's designated identifying number and nomenclature as directed and as shown on the drawings and schedules. F. Coordination with Fan and Pump Manufacturers 1. G. The variable speed motor controller manufacturer shall be responsible for the following: a. Coordination of variable speed motor controller capabilities with the requirements of each fan or pump to ensure proper matching of components. b. Review of approved shop drawings for each fan and pump to ensure complete compatibility of all system components. c. Factory preprogramming of each controller so as to prevent fan or pump operation at critical speeds. Inspection and Startup Service 1. The drive manufacturer shall provide factory trained, field service personnel for the final checkout and startup of the variable speed drive systems. This service shall include: a. Field checkout of power and control wiring to controllers and motors, including interfacing signal wiring to the building control system. b. Initial power-up of the equipment, including measurement of input voltages and d.c. bus voltage with no output load. c. Initial operation of the equipment, including measurement of output voltage and current under operating load. d. Operational check of control logic, operator devices, safety devices, protective functions, power modules, regulators, motors, and auxiliary control devices. e. Adjustment of drive operating parameters and controls to meet the performance requirements of the variable speed drive systems. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-177 HVAC Issued for Construction 1 June 2004 H. Performance Tests 1. The performance tests of the variable speed drive units shall be in multiple stages. A comprehensive performance testing and commissioning document shall be forwarded to the Engineer for review before testing commences. (Submit a minimum of five copies.) 2. This commissioning document shall comprise: 3. 4. a. Full details of all test equipment and instruments, including test equipment calibration certificates. b. Comprehensive procedures commissioning activities. c. All relevant manufacturers' performance data and a column for entering test results. d. Outline of proposed report format. This to detail performance assessments that shall be made and how they shall be determined. Electrical and mechanical parameters of the drive system, including the combined efficiency of the controller and motor combination for each fan drive. for all tests and The following tests shall be provided for each drive size, and shall be documented and performed in the presence of the Engineer and/or their deemed representatives: a. Preproduction factory harmonics test, at all operating conditions, providing a hard copy printout of complete three phase harmonic voltage and current distortion content to the 25th harmonic, fundamental frequency power, current, voltage and power factor. b. Commissioning and performance test of each variable speed drive (as installed). c. Final acceptance test of each variable speed drive (as installed). Field Performance Test a. Before on-site commissioning commences, the following items shall be completed by others: 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Connection of electrical power wiring. 15000-178 HVAC Issued for Construction 1 June 2004 2) 5. I. Attendance shall be by others as required, to override or operate external control systems to enable the variable speed drives to operate continuously throughout the commissioning cycle. b. A field test of the system harmonics shall be provided to ensure that the THD does not exceed 5% DF at the point of common coupling. If the inverter load causes greater distortion than defined, the drive manufacturer shall be responsible to further filter the line. Cost associated with the supply of the additional filters and their installation shall be borne by the drive manufacturer. c. These tests shall ensure variable speed motor controllers are regulated and capable of proper operation. d. All performance testing shall be performed in the presence of the Engineer . Final Acceptance Test a. This test shall duplicate the test procedure and reporting as outlined in Paragraph 4. above, except it shall be performed utilizing all final controls. b. Parameters measured and recorded shall include: 1) Motor Data: Volts, amps, winding temperature. 2) Power factor. 3) Electrical power consumption. 4) Control from 100% to 10%. c. Calculations substantiating overall system efficiency, power factor conformance and final DF. d. The commissioning document, with test results and report, shall be issued to the Engineer . Guarantees 1. All equipment shall be new, of first class material, and of latest design. Workmanship shall be of the best quality, free from any defects that might render the equipment unsuitable or inefficient. 2. The manufacturer shall guarantee his equipment to meet the performance conditions specified for the period of time which is Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-179 HVAC Issued for Construction 1 June 2004 normal industry practice for this type of equipment, but in no case for less than one year from the date of Engineer's acceptance. If the base price includes a guarantee period of more than one year, but less than three years, state the following: J. K. a. The period included in base price. b. Additional cost for three years. Packaging, Delivery and Storage 1. The drives shall be delivered on the date and to the location designated by the Engineer. 2. Manufacturer shall be responsible for all shipping costs. The manufacturer shall bear the costs of all storage if storage is required between the completion of factory tests and the designated delivery date. 3. After completion of factory tests, the drives shall be broken down for shipping to the location designated. Splits shall be individually wrapped for protection, and mounted on skids. 4. Coordinate size of shipping splits, delivery date and shipping location with the installing Subcontractor. Instruction of Operating Personnel 1. Provide a minimum of 40 hours of operating and maintenance instruction for building operators, with personal on-the-job instruction by factory trained engineers representing the variable speed drive unit manufacturer. This instruction shall be scheduled at time(s) convenient to the Engineer's personnel. Instruction shall cover all equipment and systems provided under this Section. Instruction shall be comprised of both Classroom type and actual hands-on operating experience. Submit an outline of the instruction program and instruction manual to the Engineer for his approval at least two weeks prior to the proposed start date of the instruction sessions. The Engineer may videotape all instruction sessions for purposes of future training. Provide a review and written critique of Engineer's videotape within one month after completion of the instruction sessions and receipt of the Engineer's videotapes. The critique shall correct all mistakes and clarify all outstanding questions which arise during the sessions. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-180 HVAC Issued for Construction 1 June 2004 L. 2. Furnish five bound copies of operating and maintenance instructions, covering the complete operation and recommended maintenance procedures and intervals for the variable speed drive units and controls. 3. Include spare parts data listing; source and current price of replacement parts and supplies for each item of equipment. Service 1. For the duration of the guarantee period, provide all required service at no additional cost. Service shall include parts and labor and shall be available through an attended telephone number on a 24-hour-a-day basis with a guaranteed response time as follows: a. Telephone contact of qualified technician within four (4) hours. b. Qualified technician on site within twelve (12) hours. The manufacturer shall make available to the Engineer a Preventive Maintenance Contract to begin on the date of expiration of the free service period. 2.43 ELECTRIC MOTOR CONTROLS A. Furnish and turn over to the Contractor who shall coordinate the installation of same, suitable starting and controlling equipment, all as specified hereinafter and as shown on drawings. Starting equipment shall be arranged, generally, in control centers or, in certain cases, as isolated combination starters, as specified or indicated. The control equipment shall be turned over to the Contractor at the building site for installation. B. Variable motor controllers shall be manufactured by one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. C. Individual starters shall be fully enclosed in neatly finished ventilated boxes of code gauge steel, machine formed and welded. These boxes shall be arranged for floor, wall or angle iron frame mounting as shown on plans or as directed, and shall each have a door with a spring catch handle. These controllers shall be of the combination starter and lockout fusible switch type. The Electrical Trade shall mount the controllers on suitable concrete curbs and/or pads, furnished by others. Isolated starters shall generally be used for isolated pieces of equipment, such as propeller type unit heaters, special exhaust fans and wherever else indicated. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-181 HVAC Issued for Construction 1 June 2004 D. Control Centers 1. The various motor control centers shown on the drawings shall be furnished under this Section. Centers shall include cubicles for all required starters, controllers, fusible switches, fuses, transformers, relays, etc., for the Heating, Ventilating and Air Conditioning, Plumbing and Electrical Sections. For starter sizes, fusible switch sizes and fuse type and sizes, see electrical drawings. Be responsible for furnishing complete information to the manufacturer of the control centers. It is the intent that the control centers shall be completely integrated units, of neat appearance. 2. Control centers shall be drawout or fixed connection type for front connection as indicated on the drawings. They shall be NEMA Class II, Type "B" with individual terminal boards in each starter. Line bus shall be separated from starter cubicles except at starter or device connection points. Separate wiring compartments shall be furnished for control wiring suitably barriered from line bus sections. Control centers shall be in NEMA Type I general purposes enclosure and be 2,285 mm. high and 510 mm. deep. Width of section shall be either 510 mm. or as required. 3. Control centers main and vertical buses shall be copper rated as indicated on the electrical drawings. All buses shall be carried full size throughout their entire length. The temperature rise of buses, connecting straps and terminals above the ambient temperature shall not exceed 50°C. Shop drawings shall substantiate by calculation or test data the above requirements. All bus work shall be braced to withstand a maximum of 65,000 symmetrical amperes. Control center power bus shall be 415 volts, 3 phase, 3 wire or 4 wire (as indicated on the drawings), 50 hertz, alternating current. Control circuits shall be 240 volt, single phase, 50 hertz, alternating current with individual fuse protection on both primary and secondary side of transformer in each starter. Fuses shall be furnished. Transformers to be of adequate size to supply required control power for all circuit components as hereinafter specified or shown on drawings. Lugs shall be suitable for the type of conductors being used and shall be closely coordinated with the work of other Trades (see Electrical Section of the Specifications). Bolted connections between and to aluminum bus bars shall be made by means of cadmium plated bolts and Belleville washers. 4. All starters in control centers shall be of the combination starter and lockout fusible switch type as hereinafter described. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-182 HVAC Issued for Construction 1 June 2004 E. 5. Provide, as indicated on electrical drawings, additional empty spaces in each control center for future use. These spaces shall be equipped with vertical buses and 2 mm. blank steel plates. 6. All required relays shall be ganged in local control panels where indicated on drawings. These relays shall include those for use with the break-glass station for the refrigeration compressors and the life safety systems as described under other Sections. Provisions shall be made for the inclusion of relays and devices as furnished and described hereinafter and under other Sections of the Specifications. 7. Electric-pneumatic switches shall be provided as specified under the Automatic Temperature Control Section of the Specifications in separate cabinets next to the motor control centers. 8. All starters, whether in control centers or remotely located, shall be the product of one manufacturer, except as otherwise noted herein. 9. All wiring between adjacent sections of control centers, and/or external to the control centers, shall be furnished as hereinafter described. 10. Provide adequate space and bus details for termination and connection of incoming feeders to the main buses in a manner that shall afford access to the connections for maintenance and periodic tightening of the lug bolts. Provide separate compartment or special box on top of the center as required for this purpose. See electrical drawings for sizes of incoming feeders. 11. Provide ground bus full length of motor control center. 12. Provide engraved nameplates for each unit, including future spaces and one for entire center, indicating center designation and power origin; nomenclature of each to be approved prior to fabrication. General 1. All starters for motors less than .37 kw shall be 240 volt, single phase, 50 hertz, a.c. service. Manual starters with overload protection and lockout type disconnect switch or breaker may be used to control such motors, except where interlocks or automatic controls are required. In such cases, magnetic acrossthe-line starters shall be furnished. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-183 HVAC Issued for Construction 1 June 2004 2. All starters for motors .37 kw to 55 kw shall be magnetic acrossthe-line type with combination fusible switches. Such starters shall be 415 volts, 3 phase, 3 wire or 4 wire (as indicated on the drawings), 50 hertz, a.c. service. 3. All starters for pump motors over 75 kw shall be part-winding (1/2-1/2) type. All starters for fan motors 75 kw and over shall be reduced voltage, autotransformer closed-transition type. These starters shall be for 415 volts, 3 phase, 3 wire or 4 wire (as indicated on the drawings), 50 hertz, a.c. service, and they shall be combination lockout fusible switch type. 4. Controllers for condensate pumps, duplex air compressor, sump and ejector pumps, etc., shall be factory mounted and wired as part of the work of this Section and the Plumbing Section. 5. All fusible switches in control centers shall be in accordance with the schedules on the electrical drawings. 6. All magnetic starters subject to manual start and in direct view of the motors they control shall have momentary contact start and stop buttons built into cover. All magnetic starters subject to electrical interlock or automatic control shall have Hand-OffAutomatic switches built into cover. All selector switches in starters shall be of the maintain-contact type. Refer to motor control center schedules on the electrical drawings. 7. All starters shall have a pilot light built into cover. 8. All starters for 415 or 240 volt service shall have 415 or 240 volt transformers built into each starter casing. Each control transformer shall be provided with fuse protection on both the primary and secondary side of the transformer. Transformers shall serve all control circuits, including auxiliary devices. Each starter subject to electrical interlock and/or automatic control shall have the necessary auxiliary contacts. One set of terminals shall be provided for each control circuit. Control centers shall be provided with control terminal blocks. 9. All magnetic starters shall have ambient compensated, manually resettable, thermal overload in each phase leg and low voltage protection. Overload selection shall be based on actual full load nameplate amps of motor installed. 10. All coils, cores, resistance, insulation contacts, trippers, etc., of starters and relays shall be of the approved type. All parts subject to wear, arcing, etc., shall be renewable. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-184 HVAC Issued for Construction 1 June 2004 2.44 11. All wiring, starters, switches, etc., shall be in full accordance with all local and Underwriters Code requirements. 12. Furnish detailed composite wiring diagrams to those assembling control centers and those installing the electrical work, and furnish such other information necessary to assure the proper connection, operation and control of motorized equipment, including interlocks, and automatic and safety control auxiliary circuits. 13. Furnish the pertinent information, such as starting torque requirements of high inertia equipment, so that the proper type starter may be provided by the starter manufacturer. All information is subject to the review of the Consulting Engineer. 14. Starter to be coordinated with fan, pump and motor manufacturers for required starting time. 15. Furnish interposing relays where indicated on the electrical drawings, built into starters, where possible. In all other cases, relays shall be furnished in separate enclosures or local control panels. ELECTRIC WIRING A. The installation of all starting equipment furnished under this Section shall be as specified under the Electrical Section, except starters specified to be factory mounted and wired as part of the equipment, and all wiring necessary to supply power to the electric motors provided under this Section shall be provided under the Electrical Section, including connections from the starters and/or motor control centers to the motors. B. Power wiring to unit heaters shall be provided under the Electrical Section. Wiring of their thermostats and aquastats and wiring of all the electric-pneumatic and pneumatic-electric switches shall be provided under Automatic Temperature Control Section of the Specifications. Under the Electrical Section of the Specifications, the connecting of all electric safety thermostats and smoke detector systems to controlled motors shall be provided. C. Wiring of all packaged equipment shall be in accordance with the requirements of the local and National Electrical Codes. D. Provide all wiring in connection with the automatic and safety control of the refrigerating machines, including all auxiliary equipment. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-185 HVAC Issued for Construction 1 June 2004 2.45 AUTOMATIC TEMPERATURE CONTROLS A. Provide all materials, labor, equipment, tools, appliances, services, hoisting, scaffolding, permits, controlled inspections, support and supervision for the furnishing and installing of all the Automatic Temperature Control Work and all related work complete, in accordance with the Contract Documents. B. General System Capabilities: Provide a dedicated, stand-alone field programmable direct digital automatic temperature and energy management control system to perform the specified control and monitoring functions. The direct digital control system shall receive signals from the smoke detection system, sprinkler system and fire alarm system for fan shutdown. The system shall be interconnected, with the Life Safety System provided under another Section. C. Data Transmission: The transmission system shall serve to transfer data and command functions between the DDC panels and the network computer, Fire Command Stations and firemen's smoke control override panels. D. The direct digital control and instrumentation subsystems shall be configured as a distributed processing network with a network computer performing the functions of operator interface. The computer and software required to communicate with the direct digital control subsystems and perform the specified functions shall be provided under this Section. E. The direct digital control system operator interface shall be a network computer, including a colorgraphic CRT, keyboard, and a printer. The equipment shall be installed in the Facilities Management Office. F. Field mounted sensors and transmitters for temperature, relative humidity and static pressure inputs to direct digital controllers shall be electronic with a 4-20 mA current output signal. G. Provide 220 VAC, low voltage, and signal wiring required for: 1. All direct digital control units, unitary controllers, field equipment panels, miscellaneous field devices, network computers, printers, modems, and all other items furnished and installed by this Section. 2. Direct digital control communication bus network between remote field controllers and the network computer. 3. Interlocking control between motor controllers and system controls. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-186 HVAC Issued for Construction 1 June 2004 4. Floor/area isolation damper controls. 5. Signal wiring from DDC control panels for the interconnection of system smoke controls to the Fire Command Station. 6. Analog and digital signal wiring from signal originating device to direct digital control field panels. 7. Final connections to Engineer furnished equipment, as defined by Engineer furnished equipment shop drawings. 8. Do any cutting required for the passage or installation of pipe, conduit, tubing, supports, and the like, provided under this Section. H. The direct digital control system shall function as a fully integrated system incorporating the requirements of this Section of the Specifications and the Contract Drawings. The Specification and the Contract Drawings define the minimum system. I. Where disagreements occur between the plans and the Specifications, or within either document itself, the item or arrangement of better quality, greater quantity or higher cost shall be included in the Base Bid. J. Abbreviations: The following legend list defines the abbreviations used throughout this Specification: Abbreviation Definitions AI AO ASCII Analog Input Analog Output American Standard Code Information Interchange Central Processing Unit (Network Computer) Cathode Ray Tube Dry Bulb Digital Input Digital Output Electronic Industries Association Electro-Mechanical Interference Hand-Off-Automatic Input/Output Kilobyte Valve Sizing Coefficient Megabyte Motor Control Center Normally Closed Normally Open CPU CRT d.b. DI DO EIA EMI H-O-A I/O KB KV MB MCC NC NO Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-187 HVAC Issued for Construction 1 June 2004 Abbreviation Definitions PI PID Proportional Plus Integral Proportional Plus Integral Plus Derivative Pressure Reducing Valve Radio Frequency Interference Resistance Temperature Detector Recommended Standard Single-Pole Double Throw Uninterruptible Power Supply PRV RFI RTD RS SPDT UPS K. Technical Proposal 1. Each of the Vendors shall submit for consideration a system which is the best and most current system he has to offer. FAILURE TO COMPLY WITH THIS SECTION SHALL RESULT IN A REJECTION OF VENDOR'S BID AND SHALL AUTOMATICALLY ELIMINATE THE VENDOR FROM ANY FURTHER CONSIDERATION. 2. The Mechanical Consulting Engineer and the Engineer shall be the sole judge of quality and equivalence of equipment, materials and methods, and shall specifically select which equipment Vendor shall supply equipment to the project after review of the technical proposals and conclusion of the selection process. 3. To allow for a complete and accurate evaluation of each Vendor's capabilities, each bid shall include a detailed project proposal. The project proposal, which shall accompany the bid form and pricing information, shall include all of the information requested below. The structure and format of the proposal shall follow the outline below, with a subject index included for crossreference. Each bidder shall be responsible for including any additional information requested in the various sections of this Specification but not mentioned below. The existing printed literature used must be edited to indicate exactly what is being offered (i.e., if existing printed literature references options available - all options not included must be crossed out). If a Vendor wishes to furnish additional information that is relevant to the evaluation, this may be supplied in an appendix. Any information submitted by the Vendor that is to be kept confidential shall be clearly marked as such. 4. The use of existing printed literature to respond to various sections of this proposal is acceptable. If an excerpt from a product manual or technical handbook is used, only the specific page(s) that address the specification requirement in question shall be used. If the material is in several places in a product manual, it shall be condensed or packaged by the Vendor in a Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-188 HVAC Issued for Construction 1 June 2004 concise response. When material is used from various sources, it shall be properly referenced. Where necessary, the Vendor shall attach additional information to the printed literature for clarification or if the literature does not fully respond to the Specification requirement. 5. Each Vendor shall provide a separate concordance schedule which shall include the section, paragraph and subparagraph of the Specification and direct statement to indicate compliance or non-compliance with all requirements. For all areas of noncompliance, the manufacturer shall describe what specific and alternative approach has been taken. Where a full description of a deviation is not provided, it shall be assumed that the Vendor cannot comply with the paragraph in question. The Vendors may propose alternates to this Specification. All voluntary alternates must be expressed as line item adds or deducts to the base bid. Alternates shall include all materials and labor necessary to provide a fully operational system as specified. Prices shall be based on quantities necessary to complete entire job as shown on the Contract Documents. All alternates shall be referenced to the appropriate Specification Section. Any deviations in quality and performance from the specified item shall be clearly stated. The Vendor shall supply any technical information necessary to evaluate the proposed alternates. 6. Each Vendor shall furnish a letter of compliance to the Mechanical Consulting Engineer and the Engineer, signed by the corporate officer of the firm, certifying the compliance and noncompliance items as stated above. 7. Note: None of the technical data required with the proposal shall be construed as "shop drawings", nor shall they fulfill the contractual obligations for submission of "shop drawings", as noted in the Contract Documents. 8. The proposal shall describe in general the entire integration system architecture including the central and remote equipment required for specified system operation. Descriptions of the hardware engineering considerations shall be reviewed. 9. Items that are unclear as to the intent in the specification shall be pointed out. 10. System Specifications a. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Hardware Specifications: Provide specification data sheets on the primary hardware components of the system proposed. The following list of device specifications shall be the minimum required for the 15000-189 HVAC Issued for Construction 1 June 2004 Project Proposal. Any additional information the bidder feels is required shall be included in this Section: b. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) Direct digital controllers. 2) Local equipment instruments). 3) Network computers (printed literature should be used). 4) Diagnostic capability at each level of system processing. 5) Local area network(s). 6) Bidder shall describe in detail the steps and necessary field hardware required to add one (1) point of each of the following types: AI, DI, AO, DO and Pulse Counter. 7) Specification sheets for electronic transmitters, controllers, actuators, relays, switches, and miscellaneous control devices. 8) Specification sheets for control dampers, including material and construction details, and leakage and pressure drop test data. 9) Specification sheets for each type of control valve. 10) Power system riser diagram. panels (for interface Software Specifications: Provide the requested information for the following system software features. Include printed literature where applicable. This list is the minimum required. The bidder, at his discretion, shall provide additional information as he deems necessary. 1) System application programming and reporting. 2) Generic listing and description of program routines resident in DDC units. 3) Description of direct digital control features. 4) Description of energy management application programs. 15000-190 HVAC Issued for Construction 1 June 2004 c. d. e. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 5) Description of management and reporting programs (e.g., Trend, Logging, Archiving). 6) Description of custom control programming capabilities. 7) Sample of a standard control algorithm/logic diagram in flow chart format detailing all of the necessary software programming. Network Computer Software: Describe the following and provide specifications and samples where applicable. 1) Colorgraphics: Provide sample graphics. 2) Report capabilities. 3) Trend plots. 4) DOS transfer capability. 5) Mouse operation. 6) Operating system. 7) Third party software interaction. 8) Description of procedure required to create a new graphic screen and add real-time monitoring points. 9) Alarm reporting and acknowledging procedure. Communications Management: Describe the following: 1) Communication protocol(s). 2) Network management procedure. System Architecture: Bidder shall provide, as a minimum, a schematic drawing (AutoCAD preferred) detailing the architecture of the proposed DDC system, including total analog and digital input/output point quantities and communication baud rates. 15000-191 HVAC Issued for Construction 1 June 2004 f. Bidder Qualifications 1) 2) 3) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Project Team a) Principal Sales Engineer: Identify and define what shall be the Sales Engineer's responsibilities (if any) after award of Contract. b) Project Manager: Identify and provide detailed resume, and define responsibilities. c) Project staffing, with resumes. d) Preliminary project schedule (bar chart) with associated manpower scheduling. e) Define where responsibilities shall lie, i.e., local branch office vs. corporate headquarter f) Corporate Officer: Identify, as requested in front end scope of work document. Vendor’s Company Organization: Provide the following information on the Vendor responsible for the project. a) Organization key personnel resumes. b) Listing of major projects completed in the last five (5) years by the Vendor. c) Listing of major projects currently in the process of installation by the Vendor. Vendor’s Service Capabilities a) Service department organization chart detailing reporting structure and number of factory trained technicians. b) Service customer reference list. Provide five (5) references of service customers currently under Contract with Vendor. c) Typical response time. 15000-192 HVAC Issued for Construction 1 June 2004 g. h. Z:\worldox\docs\122690\spc\00015619.DOC Details on typical inventory maintained at local Vendor’s office. e) Typical delivery time of hardware not maintained at Vendor’s office. Corporate Qualifications: topics shall be addressed: Response to the following 1) Number of years in the automatic temperature controls business. 2) Number of years supplying and installing microprocessor based control systems. 3) Number of years the proposed system has been manufactured. (Individually address major components, if necessary.) 4) A written guarantee of how long the system proposed shall be a standard product and backed by ongoing parts availability and factory trained field support. 5) A brief summary of the product line development of microprocessor based controls, starting with the first DDC field panels and network computers and work stations. Identify which products are still being manufactured, and which products currently have full parts availability and factory trained field support. This summary shall also describe how backward compatibility and non-obsolescence have been addressed in the Vendor's product line development. 6) A description of quality assurance procedures and testing of manufacturer's products. Address both hardware and software. 7) Provide case histories on systems similar to the one proposed which detail applications and references. 8) Provide corporate financial information for the last two (2) fiscal years. Training 1) Museum of Islamic Art Doha, Qatar d) Provide description of course content and tools to be used for the following: 15000-193 HVAC Issued for Construction 1 June 2004 2) L. a) Operator training (on-site). b) Programmer training (class). c) Service training (on-site). Audiovisual Training Aids: Describe any audiovisual training tools that shall be provided as part of the training program. i. Future Development: The Vendor shall, at his discretion, provide information on future developments/enhancements to the company's products and services. This may address items that would become available in time to incorporate in this project, as well as long range plans. The Vendor may also provide information on projected company growth and overall objectives over the next several years. j. Requested Alternates: Provide technical information for each alternate requested. Direct Digital Control System 1. The direct digital control system shall consist of a network of microprocessor based direct digital control units (DDC). Each direct digital control unit shall perform all specified control and monitoring functions independently. Failure of one control unit shall have no effect upon any other unit in the network. The direct digital control units shall communicate with each other and a PC based network computer located in the Facility Management Office. a. Communications between the direct digital control units and the network computer shall be by way of a network communications cable. b. System input/output point capacity shall be expandable by the addition of DDC units and unitary controllers to the communication network. c. The operator, through the network computer, shall have the ability to monitor DDC application and sensor data, override set points and schedules, set and reset control points and download programs to the local direct digital control units. The network computer is to be furnished programmed and debugged. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-194 HVAC Issued for Construction 1 June 2004 2. The direct digital control system furnished shall be complete in all respects so that it shall perform its specified functions in accordance with this Section of the Specifications. Implementation of all control functions shall be the responsibility of the Subcontractor. 3. The entire direct digital control system shall be complete with all necessary control devices, thermostats, valves, motors, relays, switches, dampers, panels, and electric wiring to provide the functions as described hereinafter, regardless of whether or not specifically mentioned. 4. The direct digital control system shall be installed complete in all respects by competent personnel, factory trained by the manufacturer of the control system. All automatic control valves and dampers shall be installed in pipelines and ducts by the respective trade under the supervision of the control system provider. 5. System Functions and Performance a. The direct digital control system shall be capable of accepting analog inputs (4-20 mA d.c., 0-5 volt d.c., etc.), digital, pulsed digital, thermistor and RTD's from field devices and producing analog outputs (4-20 mA d.c.) and digital type to enforce specific control and monitoring functions. The control system shall be able to: 1) Adjust control parameters for process controlled variables. 2) Initiate, define and acknowledge audible alarms. 3) Start/stop motors and position valves and dampers. 4) Initiate emergency shutdowns. 5) Communicate with a network computer. b. Equipment normally associated with a conventional analog control panel shall be replaced by a local, standalone direct digital control unit. c. There shall be a discrete analog and/or digital output signal for each field device. Split ranging of a single analog output to sequence valves and dampers is not acceptable. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-195 HVAC Issued for Construction 1 June 2004 6. 7. System Architecture a. The system architecture shall consist of a network of independent, stand-alone direct digital control units and unitary controllers communicating over a two-tier local area network. Each control unit shall perform all specified control functions independently. Failure of one control unit shall have no effect upon any other unit in the network. b. Each direct digital control unit shall communicate with each other and with a network computer. c. Each direct digital control unit shall be capable of sharing point information with other direct digital control units, such that control sequences or closed loop control executed at one control unit may receive input signals from sensors connected to other units on the network. If the network communications link fails or the originating control unit malfunctions, the control loop shall continue to function, using the last value received from the failed direct digital control unit. d. Each direct digital control unit shall control, at a maximum, one (1) air conditioning system. In addition, multiple direct digital control units shall be dedicated to each chilled and condenser water system. Provide multiple control units per system such that each control system serving water system shall be configured so that the loss of a control unit shall not result in loss of an entire system for those systems associated with the chilled water and condenser water systems. Wherever possible, the DDC control units shall be located in Mechanical Equipment Rooms. e. The direct digital control system shall be capable of supporting multiple network computers. f. The direct digital control system shall be capable of interfacing with a higher level local area network, allowing creation of a global network. Any functions associated with the DDC system that are accessible by the network shall also be accessible to the global network. Operating Environment a. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC The entire control system installed within the building shall be capable of operating at ambient temperature between 5°C. and 50°C., except for the network 15000-196 HVAC Issued for Construction 1 June 2004 computer where the operating temperature range shall be between 10°C. and 30°C. with relative humidity maintained between 20% and 85%, noncondensing. All equipment installed outside the building or exposed to outdoor temperature shall be subject to ambient design dry bulb and wet bulb for the area. b. 8. The entire system shall operate normally within fluctuations of plus or minus 10 percent in the rated voltage of primary power sources. Operation shall be at 50 hertz plus or minus 1/2 hertz. Direct Digital Field Control Units and Unitary Controllers a. b. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Field monitoring and control shall be by stand-alone site programmable microprocessor based direct digital control units (DDC's). Each direct digital control unit shall provide the following: 1) All control functions shall be by means of software in the direct digital control units. 2) Specified software functions. 3) Specified energy management functions. Each direct digital control unit and unitary controllers shall provide the following features: 1) The direct digital control unit shall be a completely self-contained, site programmable, real time, microprocessor based controller. 2) It shall include integral power supplies, communications channels, clocks, analog and digital input and output modules and a selfcharging battery capable of supporting all random access memory (RAM), clock functions, and DDC database and operating programs within the control unit for 72 hours (minimum) in the event of power failure or power interruption. 3) In the event of power failure or power interruption, equipment or life safety system trip, all unit outputs shall go to a fail-safe condition, allowing all final control elements (i.e., valves, dampers, fans, pumps, etc.) to go to their respective fail-safe modes. 15000-197 HVAC Issued for Construction 1 June 2004 4) Upon recovery from a power failure (normal power restored), the control unit shall automatically resume full operation based upon a restart software program. In addition, all control loops shall be reset upon system restart to the condition they would have been in had a power failure not occurred. The control unit shall automatically restart equipment that was running prior to power failure subject to local safety devices and time program override. Restart shall be sequential with time delays between equipment starting. 5) Each direct digital control unit and unitary controller shall have the ability on a stand-alone basis to adjust controller variables, start/stop motors and position valves and dampers. 6) Digital control algorithms shall be resident in the controller to permit proportional, integral, derivative and two-position control modes in any combination to meet the needs of the application. Temperature controller shall be three mode (P+I+D) controllers. All other controllers shall be two mode (P+I) controllers. 7) Offer immunity to EMI and RFI radiated noise (e.g., walkie-talkies within a 3 meter radius of the closed DDC (enclosure). 8) The operator shall have the ability to communicate with a control unit through the use of any of the following: 9) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC a) The control unit integral display and control panel or hand-held terminal. (If control unit does not contain an integral display, as a minimum, two hand-held terminals shall be furnished to the Engineer.) b) Laptop computer. c) The network computer. The operator, through any of the devices mentioned, shall, with the exception of the handheld terminal, perform any of the following functions: 15000-198 HVAC Issued for Construction 1 June 2004 a) Display the status of any point. b) Change set points. c) Command points on or off. d) Enable or disable existing points. e) Report status of all points in the system. f) Report all failed points. g) Report all points being trended. h) Report all points being totalized. i) Report command priority of all points. j) Report all points in alarm status. k) Add a new point. l) Modify an existing point. m) Remove an existing point. n) Copy an existing point. o) Adjust control settings (proportional band reset rate, etc.). p) Initiate energy management programs. q) Define control algorithms. r) Acknowledge alarms. The operator, through the hand-held terminal, shall be capable of performing Points a), b), c), j), 1), o) and r). 10) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC All variables shall be continuously monitored for sensor failure. When a calculation uses a variable (sensed or calculated) that is in a trouble condition, the variable shall alarm and the calculation shall use a user-defined default value or use the last reliable input from the sensor. 15000-199 HVAC Issued for Construction 1 June 2004 9. 11) Each direct digital control unit and unitary controller shall be provided with the ability to prevent unauthorized access to its software program. This shall be accomplished by a keyboard or cabinet lock or through software programming. In the locked, unauthorized position or without password authorization, the operating characteristics of the system cannot be changed, although inputs, outputs and set point values can be displayed. In the unlocked, authorized position, or with password, the ability to change the control unit program shall be unhindered. 12) The direct digital control units shall interface directly with the network computer via a token passing pier-to-pier local area network communicating at a minimum rate of 2.5 megabit/sec. The unitary controllers shall communicate with each other via an industrial standard RS-485 network operating at 9600 baud, minimum. 13) Direct digital control units shall contain manual override switches for all digital and analog outputs. Manual override switches for digital outputs shall provide “hand-off-auto” selection. Override switches for analog outputs shall provide “automatic” or “manual” selection. In the “manual” position, the operator can adjust the output proportionally between full open and closed. Override switches shall bypass outputs commanded via software login. Variable Air Volume Terminal Unit Controllers and Constant Air Volume Terminal Unit Controllers a. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC The DDC system Subcontractor shall ship for mounting and wiring to the terminal unit manufacturer the following items: 1) Microprocessor based pressure independent terminal unit controller. 2) Software. 3) Enclosure terminations. 4) Control transformer (if required). 15000-200 HVAC Issued for Construction 1 June 2004 5) Air velocity sensor. 6) Electric damper actuator. 7) Interposing relays. b. The DDC controller and its associated power supply, transducers, electric damper operator, etc., shall be neatly mounted within a separate 20 gauge sealed and gasketed galvanized sheet metal enclosure by the Automatic Temperature Control Subcontractor. The completed assembly shall be shipped by the Automatic Temperature Control Subcontractor to the terminal unit manufacturer for mounting directly to and supported from the terminal device it serves. All external electrical connections to the DDC controller within the box shall be terminated in two separate junction boxes (with removable covers), i.e., one for power and one for signal communications. All wiring and tubing shall be permanently labeled and color coded for ease of identification. No access to within the enclosure shall be required for installation, startup or operation of the terminal unit. c. The terminal unit manufacturer shall provide the terminal unit with fail-in-place electric damper. d. The Automatic Temperature Control Subcontractor shall field calibrate the microprocessor controller and all field devices. e. This Subcontractor shall be responsible for shipping costs associated with the devices discussed above, the repair and/or replacement of all devices damaged during shipment and all instructions pertaining to mounting, wiring and tubing, including wiring diagrams. f. The control unit shall be capable of interfacing with a hand-held terminal unit, DDC panel and the network computer. The control unit shall accept a temperature signal from an electronic space sensor/transmitter. Room temperature, actual and calculated air flows and flow and temperature alarms shall be continuously transmitted to the network for access by the network computer or other DDC units. The accuracy of the air flow measurement shall be ±5%, within the temperature range of 50-90°F. The status of all control unit I/O points shall be available to the entire network or the network computer at any time. All alarms shall be Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-201 HVAC Issued for Construction 1 June 2004 automatically transmitted to the appropriate locations as required by the system programming. g. Control algorithms necessary to accomplish the stated sequence of operation shall be preprogrammed in the control unit and shall be ready for operation after application and unit address information is programmed into the controller. All control sequences shall be selectable from the network computer, DDC panel and/or hand-held terminal unit. The operator at the network computer shall be able to change temperature set points, change minimum and maximum velocity set point, display room temperature and display duct velocity. Control software shall be maintained in nonvolatile memory for reset after a power failure. h. The hand-held terminal unit shall connect into the system via a jack connector at the room temperature sensor and at the terminal unit. It shall be capable of display of system variables, override control, enabling/disabling of resident control programs, and adjustment of control parameters. 1) i. The unit controller shall have, as a minimum, the following I/O: 1) 2) 3) 4) j. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Connection of a hand-held terminal, or multiple hand-held terminals, shall not interrupt nor interfere in any way with normal peer network operation, prevent alarms from being indicated, or preclude central initiated commands and system modification from the network computer. The hand-held terminal shall have its own rechargeable battery-supplied power. Battery supply shall be sufficient for 24 hours nominal usage before recharging. Low battery condition shall be visibly displayed. Space temperature. Differential pressure (velocity pressure). Damper control. Electric reheat coil control (as required per application). The control of each terminal unit shall be capable of complete stand-alone operation and shall not depend on information from any other element in the building, including other terminal units and network computer for 15000-202 HVAC Issued for Construction 1 June 2004 primary control. Failure of any component shall not interrupt control of any other terminal unit controller. k. 10. The terminal unit shall be furnished complete with factory mounted air velocity sensor (unless otherwise noted), direct digital control unit and software, nonindicating, non-adjustable space temperature sensor, damper, damper actuator, and power transformer (if required). This Subcontractor shall mount and wire the space temperature sensor and provide communication wiring between each terminal unit and the network computer. Power wiring of variable volume terminal units shall be furnished and installed by this Subcontractor. This Subcontractor shall also provide all required software interface for the network computer to monitor temperatures and air flows and adjust set points. The operator at the network computer shall be able to change temperature set point, change minimum and maximum velocity set point, display space temperature, actual air flow and duct velocity. Each terminal unit shall be addressable through the network computer. This Subcontractor shall field calibrate the air velocity sensor and DDC controller. Network Computer a. The network computer, located in the Facility Management Office, shall function as the primary means of overall system control and monitoring. The console equipment shall be arranged to present an efficient and organized appearance. The following components shall be located with the network computer: 1) 2) 3) 4) 5) b. PC based network computer. Color graphic monitor. Logging and alarm, receive only printer. External modem. Report generation printer. Provide a network computer to meet Specification requirements. The computer shall include the following: Intel Pentium 4 microprocessor operating at 1.7 GHz. 128 MB SDRAM (expandable to 384 MB) with 512KB integrated L2 cache memory. 30 GB (minimum) internal hard disk drive, 9.5 msec. access time. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-203 HVAC Issued for Construction 1 June 2004 One 1.44 MB 3-1/2 in. floppy disk drive. Local bus 32-bit IDE controller capable of supporting two hard disk drives and two floppy disk drives. One (1) 16X/10X/40X CD-RW drive with 8 MB memory with 50 CD’s. ISA expansion bus with three spare expansion slots. Local bus SVGA video output card (1280 x 1024 pixels, 256 color) with 8 MB VRAM graphics accelerator. Iomega Zip 100 MB internal drive with 10 formatted cartridges. One parallel port (printer). Two serial ports (one dedicated for mouse, one spare). Tower type chassis including high capacity power supply with surge suppressor. 101 key keyboard. Microsoft mouse. c. Audio tone generator to activate on reception of an alarm. Audio tone shall be capable of being enabled or disabled on operator command. d. Network computer keyboard, mouse and monitor shall be the primary means of operator access to the system. They shall provide the operator interface for control of the entire system. Hard copy of the display shall be transferred at the operator's request to the alarm and logging printer. To communicate with the direct digital control system, the operator shall input via the keyboard or mouse a command along with a proper identification of the system. e. Receive-only printer shall be provided for all hard copy output, including alarm reporting, system logging and program development. 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC The printer shall be 24 pin dot matrix heavy duty type with 132 characters per line. The printer shall be capable of print speeds of not less than 400 characters per second at draft quality and 100 characters per second at letter quality. Printer shall include a 80K buffer to hold data waiting to print in order to free the network computer for other tasks. Printer shall be 15000-204 HVAC Issued for Construction 1 June 2004 capable of top and rear paper feeds. Printers shall be provided with alarm tone sound. 2) The print shall have a full alphanumeric capability plus punctuating and miscellaneous characters. 3) The output typed copy shall be paper and shall be suitable for easy insertion into ring binder with calendar date and time of day automatically typed at beginning of each log. 4) The printer supplied with the system shall operate when messages fall due. The printer shall be used for the recording of information associated with system logs requested by the operator, binary alarms, off-normals of analog indication, and operator changes introduced through the keyboard. A descriptive format shall be used, for ready interpretation by the operator without use of an index or other reference. 5) The printer shall utilize two-color printing or an alternative approved means to distinguish between alarm conditions and return to normal. f. Report Generation Printer: Printer shall utilize thermal ink jet print method. Engine speed in letter size, full page graphics presentation print mode shall be 1/2 page per minute. Printable width shall be 80 characters at 10 cpi. Form feed rate shall be 8 seconds per 11 inch page. Printer shall accept furnished with 6 MB of memory expandable to 72 MB. Printer shall accept letter size, legal size and A4 size paper. Color resolution shall be 300 by 300 dpi. Printer shall be capable of producing up to 16.8 million colors. g. The color display monitor shall be 18 inch, high contrast, flat panel type operating with an SVGA high speed 8 MB video output card. The monitor and video card shall be capable of displaying color graphics and text. The display area shall have a resolution of 1028 horizontal by 1024 vertical resolvable pixels. The monitor shall be capable of displaying 256 colors selected from a palette of 16.7 million colors. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-205 HVAC Issued for Construction 1 June 2004 11. h. A digital display clock shall display on the monitor at all times. Provision for manually resetting it shall be provided. It shall be a 24 hour real time clock and seven day calendar to provide data for logging. i. A network control key or software passwords shall allow automatic functions of the system to continue, but prevent unauthorized tampering with any computer pushbuttons or controls while the computer is unattended. This shall not disable the scanning or alarming functions. j. The network computer shall be capable of remote communication through a dedicated auto dial-out/auto answer dial-in modem. 1) The external modem shall be Hayes compatible, and shall be capable of interface with the network computer through a standard EIA RS232-C connection. Speed/data communication rate shall be 56 Kbps minimum. An operator accessing the system via a modem shall be capable of executing all commands permissible by his access level. Modem communication shall at no time interfere with the operation and performance of the network computer or the direct digital field control units. 2) A local switch shall be provided for the modem connection to allow the operator to enable the dial-in port. System Communications a. Each direct digital control unit shall communicate with each other and the network computer through a software "token passing" protocol. If a control unit or the network computer fails, all other devices on the communications network shall be notified of the failure and the communications network shall automatically adjust to reflect the failure. When the failed control unit(s) or network computer reestablishes communications, all other devices on the network shall be notified and normal communications shall resume. b. Communication between unitary controllers shall be through a peer-to-peer protocol or polling protocol at a minimum speed of 9600 baud. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-206 HVAC Issued for Construction 1 June 2004 c. 12. The network computer shall alarm and notify the operator by screen display, printout, and audio tone when a communications breakdown occurs between any direct digital control unit and the network computer or unitary controller, and direct digital control unit. Direct Digital Control Unit and Unitary Controller Software a. The direct digital control unit and unitary controller programming language shall be designed for facility automation and control applications. System controller programming, editing and data base generation, control and reporting functions shall be performed at the network computer. b. The software program shall be made to permit on-line programming modifications to add, delete or modify points to any existing programmed category in the field by the Engineer subsequent to inputting an established authorization Code. c. The direct digital control unit and unitary controller shall contain resident software as follows: 1) Mathematical, logic, and utility functions. 2) Standard energy functions. 3) Routines available in any combination for site programming the unit, including the following: a) calculations and control Math Routines Basic Arithmetic Binary Logic Fixed Formulas for Psychometric Calculations b) Utility Routines Process Entry and Exit Keyboard Functions Variable Adjustments and Output Alarm Indication Restart Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-207 HVAC Issued for Construction 1 June 2004 c) Control Routines Signal Compensation Loop Control Control Tuning Energy Conservation Timed Programming User Defined Programming d. Sensing and Control 1) Monitor and control functions indicated on the point list or as specified. 2) Resident programs shall include: 3) a) Control algorithms to permit proportional, integral and derivative control modes to meet the needs of the application. b) Other control modes, such as incremental, floating or two positions. c) Control routines to bypass or suppress integral and derivative time constants in two-mode and three-mode control algorithms during startup of systems to prevent reset windup. d) Automatic control loop tuning. Point monitoring and control functions shall include the following: a) b) c) d) e) 4) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Digital Inputs (DI). Analog Inputs (AI). Digital Output (DO). Pulsed Outputs (PO) with feedback. Analog Output (AO) with feedback. Analog to digital conversion for analog point monitoring shall be provided at the direct digital control unit before digital transmission to the network computer. The conversion resolution shall be preferably not less than 12 bit. 15000-208 HVAC Issued for Construction 1 June 2004 e. f. Power Fail Restart 1) The operating programs and data base shall be protected against loss of normal power by 72 hour (minimum) volatile memory battery backup. When normal power is restored after failure, a software restart program shall be automatically initiated. 2) Following recovery from a power failure, all control points in the local controllers and network computer shall be updated to current status. Interface: The unitary controllers shall interface with the direct digital control units. The direct digital control units shall interface with the network computer. The software portion of this interface shall provide the ability for monitoring and control from the network computer. The interface shall have implemented, as a minimum, the protocol for the following: 1) 2) 3) 4) 5) 6) 7) 8) g. Initialization and down load of programs and data bases. Data base definition. Process definition. Operation interface definition. Point monitor and control. Enable/disable process and point functions. Direct digital control unit status. Unitary controller status. Stand-Alone Operation 1) In the stand-alone mode, the direct digital control unit and unitary controller shall perform the following operations: a) h. Energy Management 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Processing of local loop control and energy management functions. The direct digital control unit shall contain all necessary firmware to implement any of the following energy management functions with the addition of any required field sensors and software programming: 15000-209 HVAC Issued for Construction 1 June 2004 2) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC a) Supply air reset from specific load demands. b) Optimal start using an adaptive algorithm to prevent the need for manual adjustment or parameters. c) Chiller optimization controlling both chilled water (from specific load demands) and condenser water using outdoor wet bulb and tower approach temperature as the decision criteria. d) Chiller efficiency. e) VAV fan matching and supply fan control. f) Trending of system variables at DDC. g) Short term data storage. h) Totalization of system variables. i) Holiday programming. j) Supply water reset from specific load demands. k) Engineer tailored programs. The Engineer shall be capable of generating additional programs as may be required through the library of routines available in firmware. The unitary controllers shall contain all necessary firmware to implement, as a minimum, the following energy management functions. a) Supply air reset from specific load demands. b) Economizer control. c) Holiday programming. d) Engineer tailored programs. The Engineer shall be capable of generating additional programs as may be required through the library of routines available in firmware. 15000-210 HVAC Issued for Construction 1 June 2004 13. i. Diagnostics and Serviceability: The direct digital control units and unitary controllers shall have built-in, nondestructive procedure for checking the local display(s) and the memory. It shall display advisories for maintenance, performance, and/or software problems. j. Program Availability: The Engineer shall be furnished with all software programs required to modify and create new DDC and unitary controller software programs and upload and download the programs. In addition, all programs shall become property of the Engineer on completion of the project at no additional cost. All application programs and software programming created for this project shall become the property of the Engineer on completion of the project at no additional cost. Network Computer Software a. b. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Real-Time Operating System: The operating system shall be a Microsoft Windows NT based real-time, multi-tasking, operating system. The following shall be executed in the direct digital control unit or the network computer. 1) Task services (create/delete, suspend/resume, priority change, status inquiry, lock/unlock, etc.). 2) Full intertask queuing, including semaphores. 3) Memory allocation/deallocation. 4) Real time clock services. 5) Character I/O services. 6) Interrupt services. Third Party Software Interface: The network computer operating software shall be capable of supporting "wellbehaved" Microsoft Windows third party application programs, such as WordPerfect for Windows, Microsoft Paintbrush, Ami Pro, Lotus 1-2-3 for Windows, Paradox for Windows and Microsoft Excel for Windows, etc. Both the network computer operating software and a third party application program shall be capable of multitasking operation in either the "maximized" or 15000-211 HVAC Issued for Construction 1 June 2004 "minimized" modes. When a third party software program is in use in the "maximized" mode and an automatic alarm condition occurs, an alarm window shall be superimposed on the application program to notify the operator of the alarm condition. The operator shall then place the application software file in the "minimized" mode and place the operating software in the "maximized" mode to further investigate the alarm condition. c. Distributed I/O Processing: The network computer shall monitor the DDC system. d. Point Processing: The network computer shall read the point data transmitted from the DDC systems, receive the data for change-of-state and alarms, stores the current state of the points in its internal data base, and reports changes or alarms. Alarms shall be annunciated and logged on the printer. The operator, via network computer, shall manually initiate control points (start, stop, adjust, etc.). e. Applications: The network computer also provides the following extended features to the basic point processing operation of the system: Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) Priority Operation: This allows the assignment of an execution and a residual priority for each commanded state sent down from the network computer to the DDC system controllers so the command functions are each assigned a certain priority level and shall override lower priority commands. 2) Confirmation: Confirmation is the mechanism for determining if a start/stop or a reset point responded to a given command. A start/stop point shall be confirmed by a change-of-state of a digital input point. A reset point shall be confirmed by an expected value of an analog input point. 3) Time of Day: The time of day includes current time, day of week, month and year, and a holiday schedule for the current year. The time shall be kept in the network computer by means of a clock backed up by a battery. 15000-212 HVAC Issued for Construction 1 June 2004 f. g. 4) DDC Program Development: Development and maintenance of DDC programs shall be done in the network computer. Required data bases shall be developed as part of the software package and shall include analog, digital and alarm points specified herein. 5) DDC Algorithm Download: The executable object programs shall be downloaded to any of the direct digital control units from the network computer. Provide software to allow downloading of DDC programs from the network computer. In addition, any programs resident in a direct digital control unit may be uploaded and archived at the network computer. 6) Historical Data: The network computer shall be capable of storage of historical data and, upon operator command, shall transfer historical data to an external system. Alarms 1) Alarms shall be processed by their alarm classification. 2) Alarms shall be recorded on the alarm/logging printer and shall include the system point identification, time and date of the alarm occurrence. 3) Critical alarm points shall be configured to provide on-screen alerts to the operator immediately upon entering the alarm state. Alarms shall be processed with analog and nuisance alarms inhibited and capable of routing by time schedule, event and operator command. This procedure is required irrespective of which DOS partition the operator is operating under at any given time. This requirement may be fulfilled either by partitioning the monitor display page or by other methods acceptable to the Engineer. Reports 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC The system shall be provided with the following numeric and graphic software programs for online or off-line report generation: 15000-213 HVAC Issued for Construction 1 June 2004 a) b) c) d) e) 2) h. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Energy usage. Alarm status. Trend logging. Network status. Point status. The printed information shall include the system name, the point name and the time and date. Operator Interface 1) The network computer shall contain an operator interface to allow point display, alarming, and control of the points using the monitor and keyboard. Points are specified by point name using a three level identifier (e.g., Building, System, Point). 2) The network and point data bases shall be created in stand-alone mode in the network computer. The site validation of the data bases shall be performed sequentially; first, I/O points shall be proved through to the direct digital control units and, secondly, the I/O points shall be proved through the DDC control units and network computer to the entire system. 3) The interface shall be menu driven and give the operator the following capabilities based upon password access level: a) Place the DDC system on/off line. b) Enable/disable site control. c) Perform verification network computer. d) Initialize configuration of the network computer parameters (baud rate, ID, etc.). e) Upload of new versions of DDC control code. f) Start, stop, adjust DDC system data points. g) Display DDC system data points. 15000-214 tests on the HVAC Issued for Construction 1 June 2004 4) i. LEVEL 1 2 3 4 5 h) Self-test diagnostics. i) Adjust DDC system set points. The monitor screen shall be logically partitioned to allow the simultaneous occurrence of operator interaction and alarm indication with no interference to each other's screen display. Password 1) System software shall provide for a log-on procedure to gain access to the system. A minimum of 8 unique passwords shall be available with five access levels available. 2) Password access shall segment the capabilities of the system programmers and the system operators to access any DDC unit on line and to manually execute from the network computer the following based upon access level. ACCESS Full access, including Password definition and summary. Full access (except Password definition and summary), including ability to define new objects, nodes, and database. Allows additions to an existing network. Access to modify object attributes. Access to override commands. Allows manual control/adjustment of individual objects. Access to activity/error logs, system summaries, and alarm acknowledgment. j. Program Availability: The Engineer shall be furnished with all software programs required to modify and create new network computer software programs. The programs shall become property of the Engineer on completion of the project at no additional cost. All software graphics created for this project and associated software tools shall become property of the Engineer on completion of the project. k. Graphics 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC The graphics package shall minimize the use of typewriter style keyboard through the use of a mouse. 15000-215 HVAC Issued for Construction 1 June 2004 a) Graphics software package shall be fully implemented and operational and shall provide dynamic graphic displays and controls for each system. Color graphics software shall be capable of producing a minimum of sixteen colors. Graphics shall detail the mechanical, electrical and control features of each system; and shall continuously update to provide a dynamic mimic of system operation. b) The Engineer shall have the capability of performing the following functions as a minimum requirement: (1) (2) (3) (4) (5) (6) (7) c) In the development of a graphic display, the software package shall support all operator functions required to: (1) (2) (3) (4) (5) (6) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Create a new graphic display. Modify a portion of a graphic display. Delete a graphic display. Call up and cancel a display. Start and stop equipment. Enable and disable software modes. Change set points. 15000-216 Define the background of the display. Establish colors for the display. Locate, orient and size the symbols. Position and edit alphanumeric descriptors. Establish connecting lines. Establish sources of real-time data and location of their readouts. HVAC Issued for Construction 1 June 2004 d) Software shall permit the creation of display symbols by a single keystroke or control sequence. Graphic symbols shall include the following as a minimum: Pump Two-way Valve Three-way Valve Temperature Element Humidity Element Flow Element Pressure Element Fan Damper and Actuator Limit Switch Temperature Switch e) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Flow Switch Cooling Coil Heating Coil Filter Piping Run Duct Run Flow Arrows Chiller Pressure Reducing Valve Cooling Tower Provide a separate graphic display for each system specified below. Use different colors to indicate the various components and the state of these components. Colors shall conform on all displays and shall allow easy interaction and rapid recognition. Alarms shall not automatically generate a graphic display but shall send a message to the operator indicating on which graphic display the alarm condition may be viewed. (1) Fresh air intake fans. (2) Each air conditioning system. (3) Each ventilation and exhaust system. (4) Each exhaust fan. (5) Each floor plan indicating all fans, floor dampers, etc., per floor. (6) Emergency generator system. (7) Each chilled water system. (8) Each condenser water system. 15000-217 HVAC Issued for Construction 1 June 2004 f) (9) Ten (10) additional graphics to be defined by the Engineer. (10) Each graphic shall display, as a minimum, the following: (a) Set points. (b) Process variable measurements. (c) Damper position (open/ closed, % open). (d) Valve position (open/ closed, % open). (e) Equipment status (green - on, white - off, red alarm). (f) Alarms (green - normal, red - alarm). A graphical penetration scheme shall be furnished to allow an Engineer access to each graphic. The scheme shall consist of the following (in order): (1) Site plan. (2) Building plan. (3) Floor plan. (4) Individual rooms (Mechanical Equipment Rooms, Elevator Machine Rooms, Offices, etc.). In addition, an operator shall be capable of bypassing the graphical penetration scheme and accessing a graphic directly. M. Temperature Control Instruments 1. Instruments and control devices shall be provided for all required points detailed hereinafter. Instruments shall have accuracies as stated herein. Instrument characteristics such as hysteresis, relaxation time, span, and maximum and minimum limits, shall Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-218 HVAC Issued for Construction 1 June 2004 be accounted for in applications of instruments and controls. Not all devices specified may be required for this project. 2. Field wiring for each digital device shall be manufacturer's standard. The details of the wiring shall be included in the submittal. 3. The overall accuracy of values at the remote points which are reported to the network computer are given below. Final testing, using test methods as approved by the Mechanical Consulting Engineers, to determine instrument accuracy, shall be made under the direction of the Mechanical Consulting Engineers. 4. This Subcontractor shall make every effort to provide all automatic control instruments subject to outdoor air conditions or located outdoors constructed of material to withstand the outdoor air conditions. 5. Temperature Transmitters (Electronic Type) a. Duct mounted averaging type transmitters shall consist of a 100 ohm platinum RTD averaging element housed in a flexible sheath and electrical box for wiring connections. Transmitter shall provide 2 wire 4-20 mA d.c. output linear over specified temperature range, with an accuracy of ±0.5°C. over entire operating span. Wiring connections shall accept 1.0 mm. wire. b. Duct mounted nonaveraging type transmitters shall consist of a 100 ohm platinum RTD mounted on a 850 mm. probe and electrical box for wiring connections. Transmitter shall provide a 2 wire 4-20 mA d.c. output linear over specified temperature range with an accuracy of ±0.3°C. over the entire operating span. c. Liquid insertion type transmitters shall consist of a spring loaded 100 ohm platinum RTD and electrical box for wiring connections. Transmitter shall provide a 2 wire 4-20 mA d.c. output linear over specified temperature range with an accuracy of ±0.2°C. over entire operating span. d. Transmitters for duct locations shall not be affected by vibrations encountered in normal duct systems. e. Space transmitter shall be designed for wall mounting in a decorative ventilated enclosure and consist of a 1000 ohm platinum RTD element and electrical box for wiring connections. Transmitter shall provide 2-wire 4-20 mA d.c. output linear over temperature range of 0-38°C., Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-219 HVAC Issued for Construction 1 June 2004 with an accuracy of ±0.5°C. over entire operating span. Wiring connections shall accept 1.0 mm. wire. Finish and final location shall be reviewed by the Engineer and Consulting Engineers. f. 6. Combination temperature and humidity transmitters are not acceptable. Thermistors a. Thermistor temperature sensing elements are an acceptable alternate for RTD's provided they meet the following performance criteria: 1) Thermistors must be measurement grade, semiconductor glass encapsulated bead type with a negative temperature coefficient of resistance. Thermistors shall meet or exceed the following performance criteria: Temperature Range -80°C. to 250°C. Accuracy (0°C.) 0.2°C. to 0.05°C. Accuracy (70°C.) 0.2°C. to 0.05°C. Accuracy (150°C.) 1.0°C. Sensitivity -4%/°C. (100 ohm to 100,000 ohm) 7. Static Pressure Transmitters (Electronic Type): Duct static pressure transmitters shall consist of static pressure probe, transmitter and electrical box for wiring connections. Duct wall pressure taps shall be acceptable. Reference pressure sensing connections to duct static pressure transmitters shall be made through an ambient pressure probe or chamber which shall minimize effects of air disturbances and maintain a steady, uniform reference pressure. Transmitter shall provide 2-wire 420 mA d.c. output linear over specified pressure range, with an accuracy of 125 Pa over a range of 0-1000 Pa. Wiring connections shall accept 1.0 mm. wire. 8. Protective Thermostats and Detectors a. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Electric high temperature thermostats shall be bimetallic element type with snap-acting manual reset switch and with a sensing element with at least 254 mm. insertion length. Thermostats shall be set for duct temperature of 52°C., unless otherwise noted. Install where noted on 15000-220 HVAC Issued for Construction 1 June 2004 drawings, or as directed by the Mechanical Consulting Engineer. 9. b. The Electrical Subcontractor shall furnish and wire all smoke detector elements for installation where noted on drawings, or as directed by the Electrical Consulting Engineer. c. Electric low temperature (freeze protection) thermostats shall have 6 meter capillary (not averaging type) installed to cover the entire cross-sectional area of coil face. Switch actuation shall occur if any 30 cm. length of capillary senses a temperature below set point. As a minimum, one thermostat shall be furnished and installed for each cooling coil. If one thermostat is not sufficient to provide adequate coverage of coil, this Subcontractor shall furnish and install additional thermostats to provide sufficient coverage. Sufficient coil coverage shall be field verified by Mechanical Consulting Engineer. These thermostats shall be twoposition automatic reset type. The elements shall be suspended at least 150 mm. to 200 mm. downstream of the preheat coils. Furnish in the direct digital control system a software time delay relay to delay fan shutdown and alarming at the network computer for 180 seconds (adjustable), unless otherwise stated. Relative Humidity Transmitters a. Duct mounted relative humidity transmitter shall provide 4-20 mA linear d.c. output corresponding to range of 0 to 95% R.H. Calibrated end-to-end accuracy shall be ±1.0% R.H. over the range of ±10% R.H. of set point and ±2.5% R.H. over the range of 0-95% R.H. at 25°C. Repeatability ±0.5% R.H.; linearity ±1% R.H. b. Space relative humidity transmitter shall provide a 4-20 mA linear d.c. output corresponding to the range of 0 to 95% R.H. Calibrated end-to-end accuracy shall be ±1.0% R.H. over the range of ±10% R.H. of set point and ±2.5% R.H. over the range of 0-95% R.H. at 25°C. Repeatability ±0.5% R.H.; linearity ±1% R.H. Finish and final location shall be reviewed by the Engineer and Consulting Engineer. c. Combination temperature and humidity transmitters are not acceptable. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-221 HVAC Issued for Construction 1 June 2004 10. 11. Weather Station a. The weather station shall be used to measure outside air dry bulb temperature and relative humidity. b. The components of the station shall be: 1) Temperature sensor and signal conditioner generating a 4-20 mA signal over a range of 40°C. to 49°C. Accuracy shall be ±0.5°C. 2) Relative humidity sensor and signal conditioner generating a 4-20 mA signal over a range of 0100% R.H. Accuracy shall be ±2% R.H. over the range of 20-90% R.H. 3) Surge arresters at sensor inputs to prevent system damage from high voltage lightning spikes. 4) Chassis assembly used to house the signal conditioners for the sensors and a 120/240 volt, 50/60 Hz. power supply. 5) Sensing elements shall be provided with Teflon filters. 6) All wire terminations shall be provided with a silicon coating. Thermowells a. Provide a Thermowell for every temperature sensing element installed in piping and equipment, including transmitter sensing bulbs, RTD's and temperature switches. b. Thermowells shall be Type 304 stainless steel, tapered pattern, 15 mm. NPT external process connection, 13 mm. NPT internal thread, with lagging extension, equal to insulation thickness, where installed in insulated piping. Thermowells shall have an insertion length of at least 1/3 of pipe diameter but in no case shall wells be less than 114 mm. insertion length. Thermowells shall be rated for maximum system operating pressure, temperature and fluid velocity. c. Internal bore of Thermowells shall be sized to exactly fit the diameter of the sensing element to be installed. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-222 HVAC Issued for Construction 1 June 2004 12. Resistance Temperature Detector (RTD) a. For monitoring of temperature, use of an RTD as a direct signal input into the direct digital system is an acceptable alternate to a temperature transmitter, provided the accuracy is equal to that of the substituted transmitters (± 0.15% of calibrated span). b. The RTD shall be a platinum three-wire RTD with base resistance 100 ohms at 0°C. Compensated for lead wire resistance, and wired directly to direct digital controller analog input terminals. Operating range 0 to 40°C. Maximum temperature indication error in operating range not to exceed plus or minus 0.3°C. c. Platinum sensing wire shall be wound on ceramic or glass mandrel with lead wires encased in ceramic lead support tube and epoxy sealed in 6 mm. OD, Type 304SS, pressuretight sheath. For RTD's installed in air ducts, the sensing element shall be averaging type, wound to provide sensing of the average of temperatures along the full length of the probe sheath. The complete RTD assembly shall include a die-cast aluminum connector head fitted to the lead end of the probe sheath. Connector head shall be weather resistant with threaded aluminum captive cap and chain, terminal block for lead wires, 13 mm. NPT process end and extension wiring connections. d. Pipe Mounting: Install RTD in matched Thermowell with an internal diameter to exactly fit the probe sheath. The RTD probe shall be inserted to the full depth of the Thermowell. Provide a union connection in the 13 mm. NPT pipe nipple extension between the Thermowell and the connector head. e. Duct Mounting: RTD probes installed in air ducts shall be the full width of the duct. Provide a 13 mm. NPT common flange and gasket bolted to the duct side wall at mid-height. Install RTD assembly on flange with union connection in the 13 mm. NPT pipe nipple extension from flange to connector head. Provide continuous support of exposed RTD probe inside of duct by strapping to support angle iron spanning full width of duct. The sensing probe shall be fully exposed to the airstream, and the support sufficiently rigid to prevent any vibration or movement of the sensing probe due to air velocity effects. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-223 HVAC Issued for Construction 1 June 2004 13. Differential Pressure Transmitters (Used in Water Service) a. Differential pressure transmitters shall be variable capacitance type arranged for 2 wire, 4-20 mA control signal output. Transmitter shall be enclosed in a gasketed, dust and watertight housing. All body cavities open to the process fluid shall be provided with drain ports at the cavity bottom and vent ports at the top of the cavity. Both drain and vent ports shall be minimum 6 mm. - 18 NPT. The transmitter shall have continuously adjustable (externally) zero and span. b. The differential pressure range span shall be adjustable to permit maximum zero elevation of 600% of calibrated span and a maximum zero suppression of 500% of calibrated span. These adjustments shall be made within the transmitter housing without a change of parts. The transmitter shall be capable of sustaining differential pressures in either direction, up to the body rating without damage to the instrument or a loss of accuracy or zero shift. c. The transmitter shall be fully compensated for both process and ambient temperature variations and a calibrated accuracy of ±0.25% of calibrated span. d. Transmitter shall be furnished complete with factory mounted 5-valve manifold. 14. Turbine Flow Meters: Insertion type turbine flow meters shall be designed to mount through a fully open 80 mm. ball, plug or gate valve. Meter flow range shall be 0.6-12 m./sec. for liquid. Meter linearity shall be ±1% over a 10:1 range. Repeatability shall be 0.10%. Turbine head and stem shall be constructed of stainless steel, bearings shall be tungsten carbide, housing and flange shall be carbon steel. Housing pressure rating shall be 200 psig. A d.c. powered two-wire flow transmitter shall be flow meter mounted. Flow transmitter output shall be 4-20 mA d.c. linear with flow. Transmitter input shall be magnetic pickup. Transmitter accuracy shall be ±25% of span. Turbine meter shall be as approved by the Mechanical Consulting Engineer. 15. Vortex Flow Meters: Flow meters shall have an accuracy of ±0.1% of flow rate, and a repeatability of 0.2% of flow rate. Flow meter shall be capable of producing an analog 4 to 20 mA d.c. output linear with flow or a pulse output. Body material shall be 316 stainless steel or carbon steel. End connections shall be RF flange. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-224 HVAC Issued for Construction 1 June 2004 16. 17. 18. Airflow Measuring Stations a. Airflow measurement accuracy shall be ±2% of actual flow over a range of 6 to 1 capacity turndown. The probe installation shall not produce any static barrier (resistance to airflow). b. Each airflow measuring station shall be furnished with an electronic differential pressure transmitter capable of transmitting a 4 to 20 mA d.c. output signal. Transmitter accuracy shall be ±0.5% of span, including linearity, hysteresis and repeatability. Repeatability ±0.5% of span. The transmitter shall be capable of being field recalibrated for a different span within its range limits. Span shall be matched for a specific cfm range. Transmitter zero shall be field adjustable. c. Air flow measuring stations located in otdoor air ducts shall be constructed of 316L stainless steel. Differential Pressure Switch - Water a. Differential pressure switch shall contain brass bellows which shall operate snap-acting SPDT contacts. b. High and low sensing ports shall be 6 mm. NPT. c. Adjustable operating range shall be capable of sustaining 517 kPa in either direction. Differential Pressure Switch - Air a. Differential pressure switch shall be diaphragm operated with DPDT contacts activated by photocell controlled relay. Contact rating shall be 15A, 220VAC. Incorporate gauge, set point indicator and tamperproof knobs. b. High and low sensing ports shall be 3 mm. NPT connected to angle type tips designed to sense pressure. 19. Pressure Electric Switch: Pressure electric switch shall be pneumatically operated snap-acting switch with SPDT contacts. Set point adjustable from 20 kPa to 138 kPa, 14 kPa differential (deadband), fixed. 20. High Temperature Room Thermostat: High temperature room thermostat shall contain either bi-metallic or mercury type switches, SPDT rated for 5 amps at 220 VAC. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-225 HVAC Issued for Construction 1 June 2004 N. 21. Current Sensing Relays: Relay shall be field adjustable for detecting a.c. current levels in equipment served. Relay shall be non-latching and shall have no time delay. Nominal input voltage and current sensing range shall be selected based on electrical characteristics of equipment served. Relay shall be installed on one lead of the load side of motor feed. Relay contacts shall be Form C rated for 5A at 220 VAC. 22. Valves shall be single seated type. 23. Chilled water control valves shall have equal percentage flow characteristics. 24. Control valve shall be provided with travel indicator (pointer) attached to steam stem and a travel indicator scale attached to the yoke to indicate valve travel. Automatic Control Valves 1. All automatic control valves shall be globe valves and shall have equal percentage flow characteristics unless specified otherwise. The valves shall be quiet in operation and fail-safe in either normally open or normally closed position in the event of power failure. All valves shall be capable of operating at varying rates of speed to correspond to the exact dictates of the controllers and variable load requirements. The valves shall be capable of operating in sequence with other valves and/or dampers when required by the sequence of operation. All control valves shall be sized by the control manufacturer and shall be guaranteed to meet the cooling loads as scheduled. All control valves shall be suitable for the pressure conditions and shall close against the differential pressures involved. Valve operators shall be electric spring return type. Body pressure rating and connection type construction shall conform to fitting and valve schedules, as per the Heating, Ventilating and Air Conditioning Section of the Specifications. Control valves 50 mm. and smaller shall have bronze bodies and stainless steel trim and stem. End connections shall be threaded. Control valves 80 mm. and larger in a service where pressure does not exceed 8.6 bar at 282°C. or where steam pressure does not exceed 7 bar shall have 8.6 bar cast iron bodies. Trim and stem shall be stainless steel. End connections shall be flanged. Valves 80 mm. and larger in a service where pressure does not exceed 17.2 bar at 200°C. shall have 17.2 bar cast iron bodies. Trim and stem shall be stainless steel. End connections shall be flanged. Valves shall have sufficient stuffing box protection to insure against leakage at hydrostatic head involved. Control valve operators shall be sized to close against a differential pressure equal to the design pump head plus 10 percent. Where pressure and flow combinations exceed Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-226 HVAC Issued for Construction 1 June 2004 ratings for commercial valves and operators, industrial class single-seated valves and operators or double-seated valve with a leakage rate of .1% of rated valve capacity shall be provided. O. 2. Valves shall be single seated type. 3. Chilled water control valves shall have equal percentage flow characteristics. 4. Control valve shall be provided with travel indicator (pointer) attached to stem and a travel indicator scale attached to the yoke to indicate valve travel. Motorized Valves 1. All motorized valves, where shown on the drawings or specified herein, shall be high performance butterfly type with lug ends. Motorized valves used in on/off service shall be furnished with electric piston operators, and open and closed limit switches. Valves shall fail in their last position upon loss of electric power. Motorized valves used in modulating service shall have electric spring return actuators. All such valves shall be provided under this Section. Valve body shall be carbon steel with 316 stainless disc, 17-4 pH stainless shaft. Seat and seal materials shall be Teflon. The valve shall be provided with a speed control device (adjustable) to prevent the valve from too rapid a closure rate. Body pressure rating and connection type construction shall conform to fitting and valve schedules. The electric operator shall be provided with an external position indicator. Valves shall be full-bodied, full lug type only (wafer type or semilugged valves shall not be permitted). Valves shall be bolted from both ends of the flanges. Valves shall be capable of bubble-tight double dead-end closure with either upstream or downstream flange removed through the valve full rated pressure. 2. All motorized valves shall be provided with manually operated de-clutchable handwheels for overriding the operator in both emergency and normal operation. 3. Motorized valves, automatic control valves, actuators, solenoid valves, limit switches, manual override handwheels, position indicators, etc., which are located outdoors shall be constructed for outdoor use. All electrical devices shall be weatherproof and NEMA 4 rated. All exposed valve components (i.e., stem, shaft, gear operators, handwheel, etc.) shall be constructed of nonrusting metal or factory-coated with rust-inhibiting paint. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-227 HVAC Issued for Construction 1 June 2004 P. Automatic Control and Automatic Smoke Dampers 1. Low leakage automatic control dampers, automatic smoke dampers and/or combination smoke/fire dampers shall be furnished under this Section of the Specifications. Smoke dampers shall meet the requirements of UL 555S for Class II leakage at 170°C. Combination smoke/fire dampers shall meet the requirements of UL555 and UL 555S for Class II leakage at 170°C. All electrical wiring (power and control) for the dampers shall be furnished and installed by this Subcontractor. 2. Dampers Which Require Opposed Blade Action: Dampers under modulating control such as outdoor air, return air and spill air dampers in air conditioning systems and air intake, recirculation air, and exhaust air dampers in ventilation systems, minimum outdoor air dampers serving restaurant air conditioning units. 3. Dampers Which Require Parallel Blade Action: Dampers in two-position service such as outdoor air intake and exhaust air dampers in 100 percent outdoor air ventilation systems, fan discharge dampers and floor isolation dampers in supply and return air ducts. 4. Smoke Dampers: All floor isolation dampers, fan discharge dampers and return air shall be smoke dampers. Provide smoke dampers at all in two hour rated walls and wherever a fire damper is installed. In systems over 7.08 L/S, the fan discharge damper and return air damper at the mixed air plenum shall be smoke dampers. 5. Combination Smoke/Fire Damper: Combination smoke/fire damper incorporating a one-time 74°C. fusible link shall be furnished and installed in all two hour fire rated walls. Damper shall be capable of being reopened only up to the link disconnect temperature and be dynamically rated for closure against air flow in both vertical and horizontal mounting configurations. All combination smoke/fire dampers shall meet all NFPA requirements. 6. Dampers installed in outdoor and exhaust air ducts shall be completely constructed of 316 stainless steel, including linkages. Damper frame shall be 203 mm. x 51 mm. flanged and 2 mm. thick 316 stainless steel channel. Damper blades shall be 2 mm. thick 316 stainless steel. Blade, shaft and jamb seals be stainless steel. Axles shall be 13 mm. diameter stainless steel. Bearings shall be outboard type with shaft seal. Linkages shall be external. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-228 HVAC Issued for Construction 1 June 2004 7. All other dampers located in non-outdoor air environment (i.e., within a conditioned environment) shall be constructed with 125 mm. x 25 mm. welded frames of 1.65 mm. (min.) galvanized steel, roll formed into triple "U" configuration, or 50 mm. x 25 mm. x 3 mm. welded galvanized steel channel frame. Blades shall be not less than 1.65 mm. galvanized steel formed with multiple, longitudinal breaks and interlocking "V" groove edges. Maximum blade width, 200 mm.; maximum blade length, 1200 mm. Blades shall pivot on 12 mm. diameter zinc plated steel axles through-bolted to blade, and mounted in low friction bearings. Smoke dampers shall be provided with stainless steel bearings. Damper blade linkages shall be face mounted on the blades. Drive linkage and damper operators shall be located outside of the duct. Damper operator drive brackets and linkage hardware, including brackets, couplings, connecting rods, bolts and set screws shall be zinc or cadmium plated steel of sufficient size and strength to operate dampers against the maximum rated static pressure. Linkage trunnions shall be brass or bronze. All damper hardware shall be bolted in place. Speed screws shall not be permitted. Dampers shall have continuous stainless spring steel jamb seals installed the full height of each vertical frame member to maintain tension on the thrust bearing sealing the blade ends and axle. Non-smoke dampers shall be provided with fabric reinforced, or vinyl neoprene edge seals. Smoke dampers shall be furnished with silicon rubber blade edge seals. Edge seals shall be securely attached to the damper blades and shall increase the tightness of the seal as the differential static pressure across the damper increases. 8. Total blade height shall not be less than duct height minus the damper frame width. Blank-off plates shall not be permitted. Blade stops shall not exceed 19 mm. Where damper sizes are increased above those indicated on mechanical drawings due to standard blade width, this Section of the Specification shall be responsible for coordinating with the Sheet Metal Subcontractor to incorporate transition ducts. All costs for fabrication and installation of transition ducts shall be included as part of this Section of the Specification. Transitions shall be installed by the Sheet Metal Subcontractor. 9. Breaks in the galvanized finish caused during fabrication operations shall be cleaned and completely covered with a sound coat of zinc rich paint. 10. All dampers shall be constructed to withstand the approach velocity developed at maximum design air flow for each damper and ductwork configuration as shown on the mechanical drawings. This Subcontractor shall determine the maximum Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-229 HVAC Issued for Construction 1 June 2004 design air flow through each damper, calculate the air velocity through the damper, and select a damper suitable to withstand the velocity developed without excessive noise or vibration. Maximum design air flow calculations shall be included with damper schedule submissions. 11. For non-smoke control dampers, air leakage through a closed damper shall not exceed the following values: Damper Area Differential Pressure Total Leakage 1.5 m.2 1 kPa 270 m3/hr. 12. Damper banks consisting of multiple damper sections shall be furnished with continuous vertical 3.4 mm. galvanized steel or stainless steel stiffeners every 1200 mm. as part of the damper assembly. Drive blades of multiple section damper assemblies shall be coupled together with jack shafts. The assembly of damper sections shall be constructed to operate against the maximum differential static pressure specified for individual damper sections. 13. Smoke dampers and combination smoke/fire dampers consisting of multiple damper sections shall be provided with mounting frames, mullions and hardware required to conform with their UL listing. This Section of the Specification shall be responsible for coordinating with the Sheet Metal Subcontractor and insuring that the dampers are installed in accordance with the manufacturer’s and UL requirements. 14. Damper Operators: All damper operators shall be electric spring return type so that the damper shall fail-safe on interruption of power. They shall be quiet in operation and have ample power to overcome friction of damper linkage and air pressure acting on louvers to position dampers accurately and smoothly for velocities up to 18 m/s. The damper operator mounting arrangement shall be outside the air stream wherever possible. The control manufacturer shall provide a substantial (strong) linkage between operator and damper. Operators shall be capable of 60 second travel time from full open to full closed and from full closed to full open, and shall be fully proportional unless otherwise noted. 15. A sufficient number of damper operators shall be installed to operate single and multiple damper sections smoothly and in unison at the maximum rated static pressure and air velocity, and to provide the close-off torque required to meet damper leakage criteria. Provide auxiliary drive shafts with pillow block Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-230 HVAC Issued for Construction 1 June 2004 bearings and bearing support brackets rigidly attached to the damper frame assembly on damper banks more than one damper section wide. 16. Dampers and Actuators Serving Emergency Generators a. Q. Damper construction shall be as described above with the following exceptions: 1) Emergency generator discharge dampers shall be furnished with high temperature edge seals capable of withstanding an ambient temperature of 230°C. 2) Actuators used with emergency generator discharge dampers shall be extended temperature actuators capable of withstanding an ambient temperature of 150°C. minimum. Field Equipment Cabinets 1. Provide, adjacent to each air conditioning system, ventilating system, water circulation system and other systems as required, field equipment cabinet. The cabinet shall be made of steel or extruded aluminum, with proper bracing for rigid wall or floor mounting. The cabinet shall not be attached to any piece of building equipment. Mount in this cabinet all associated temperature controls, such as relays, switches, air gauges, etc., except as otherwise specified. All adjustable devices shall be mounted within a cabinet section with doors and a key-operated lock of an approved type. 2. Each control device on the cabinet shall be marked with engraved nameplates describing its function and crossreferencing it to control diagrams shown on the panel. 3. Internal cabinet wiring shall have identification sleeves at each termination at the terminal strip. 4. Field equipment panels shall be complete so that they may be erected at the site and after connection of external wiring and tubing to the designated terminal points. Each panel assembly shall be a unit capable of performing its functions in accordance with the Specifications, and any other attachments which are a part of this Section. 5. Failure of Specifications to state or show materials which are essential to make the instrument panel assemblies a complete and operating unit shall not relieve the responsibility of furnishing such materials without additional cost to the Owner. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-231 HVAC Issued for Construction 1 June 2004 R. 6. Cabinets shall be provided with space for future addition of instruments. Fully loaded cabinets shall not be acceptable. 7. Separate terminal blocks shall be installed for 220 volt a.c. wiring and for low level signal wiring within field equipment cabinets. Terminal blocks for line voltage wiring shall be separated from low level signal wiring terminal blocks by a barrier partition. 8. Terminal blocks shall be 600 volt rated, medium duty, channel mounted, with numbered marking strips. 9. Submit shop drawings of each panel for review before fabrication. 10. Interlock Relays: The control manufacturer shall check the electrical diagrams (starter diagrams) and shall furnish all required interlock relays and manual switches prewired in the field equipment cabinets. 11. Each cabinet shall have a laminated readable drawing of the final working cabinet and sensors, controllers, etc. Drawing to be permanently fixed to cabinet. If there is no room in the cabinet, affix the drawing next to the cabinet. Electrical Wiring and Materials 1. Install, connect and wire the items included under this Section. This work includes providing required cable tray, conduit, wire, fittings, and related wiring accessories. All wiring shall be installed in conduit or cable tray. a. Provide wiring for thermostats, wiring of all control and alarm devices for all Sections of the Specifications, and wiring for all break-glass stations furnished under this Section. b. Power for each direct digital control unit, field equipment panel, network computer, unitary controller as well as all devices furnished under this Section shall be taken from 220 volt a.c. circuits connected to emergency power panels connected to the emergency power distribution system. Wiring and conduit between the emergency power panel circuits and all direct digital control units, field equipment cabinets, network computer and unitary controllers, etc., shall be furnished and installed by this Section of the Specifications. In addition, this Subcontractor shall provide 220 volt, 50 hertz convenience outlet in each controller and panel. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-232 HVAC Issued for Construction 1 June 2004 c. Provide status function conduit or cable tray and wiring for equipment covered under this Section. d. Provide conduit or cable tray and wiring between the DDC control units and field equipment cabinets and the temperature, humidity, or pressure sensing elements, including low voltage (under 100 volt) control wiring and coaxial cable in conduit. e. Provide conduit or cable tray and control wiring for devices specified in this Section. f. Provide conduit or cable tray and signal wiring between motor starters relay contacts and remote relays in DDC panels. g. Provide conduit or cable tray and wiring between the network computer, electrical panels, metering instrumentation, indicating devices, miscellaneous alarm points, remotely operated contactors, and DDC units as shown on the drawings or as specified. h. Provide control and signal wiring between the DDC system and equipment provided by other Sections such as chillers, house pumps, etc. i. Provide control and signal cable tray and wiring between the DDC system and chiller control panels, and all control and signal interwiring between each chiller and its respective control panel. j. Provide communication conduit or cable tray and wiring between direct digital control units (including direct digital control units serving variable and constant volume terminal units), and between direct digital control units and network computers. k. Provide all power and control cable tray and wiring for all damper and valve actuators. l. Provide all control cable tray or conduit and wiring for cooling tower, thermostats, low level cutout, etc. m. Provide power and control wiring for cooling tower vibration switches. n. Provide all control wiring for variable air volume terminal units, and constant volume terminal units. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-233 HVAC Issued for Construction 1 June 2004 Provide power wiring for all variable and constant air volume terminal units. 2. Wires and cables shall be as follows: a. Single Conductor (220 volt a.c.): 1.5 mm. stranded copper with 600 volt insulation color coded red for hot leg, white for neutral, black for all others. Larger gauge cables shall be provided where necessary to limit the voltage drop to 5% or 6 volts from the source to the last device. b. Signal Cables (4-20 mA Analog) NOTE: 1) For Use in Areas Other Than Air Plenums: 2/C 1.0 mm.2 shielded and multi-pair 0.75 mm.2 individually shielded, or as approved by the Mechanical Consulting Engineer. 2) For Use in Air Plenums: Plenum type Teflon insulated, 2/C 1.0 mm.2 shielded and multi-pair 0.75 mm.2 individually shielded, or as approved by the Mechanical Consulting Engineer. The cables listed above have conductors with 220 volt insulation ratings. Similar cables with 600 volt insulation ratings must be provided for any cable terminating within or occupying an enclosure containing conductors operating at a voltage greater than 220 volts (i.e., 380 volt motor starter enclosure). c. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Alarm, Digital Input/Output and Control Cables (24 volt a.c.) 1) For Use in Areas Other Than Air Plenums: 2/C 1.0 mm.2 and multi-pair 0.75 mm.2, or as approved by the Mechanical Consulting Engineer. 2) For Use in Air Plenums: Plenum type Teflon insulated, or as approved by the Mechanical Consulting Engineer, 2/C 1.0 mm.2 and multipair 0.75 mm.2 3) Larger gauge cables shall be provided where necessary to limit the voltage drop to 1.2 volts from the source to the last device. 15000-234 HVAC Issued for Construction 1 June 2004 NOTE: The cables listed above have conductors with 220 volt insulation ratings. Similar cables with 600 volt insulation ratings must be provided for any cable terminating within or occupying an enclosure containing conductors operating at a voltage greater than 220 volts (i.e., 380 volt motor starter enclosure). d. 3. RTD Wiring 1) For Use in Areas Other Than Air Plenums: 3/C 1.0 mm.2, or as approved by the Mechanical Consulting Engineer. 2) For Use in Air Plenums: Plenum type Teflon insulated 3/C 1.0 mm.2, or as approved by the Mechanical Consulting Engineer. e. DDC Communications Cables: DDC communications wiring between the local control units and the network computer shall be 1.0 mm.2 shielded cable, fiber optic cable or coaxial cable and shall be run in separate conduit. The control manufacturer shall be responsible for selection of fiber optic and coaxial cable types. f. Fiber Optic Cable 1) Fiber optic cable shall be constructed of 62.5/125 µm multimode fiber, with aluminum armor protection. Cable shall be rated for both indoor and outdoor use. Cable shall be FT-4 flame rated. Cable bundle shall have 12 fibers minimum, 24 fiber cable bundle recommended. 2) Maximum pulling tensions as specified by the manufacturer shall not be exceeded during installation. Post-installation residual cable tension shall be within cable manufacturer’s specifications. 3) All cabling and associated components shall be installed in accordance with manufacturers’ instructions. Minimum cable and unjacketed fiber bend radii, as specified by cable manufacturer, shall be maintained. Terminal junction boxes shall be fabricated in accordance with applicable Code requirements and standard insofar as materials, gauges, dimensions and methods of fastening are concerned. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-235 HVAC Issued for Construction 1 June 2004 S. 4. Sheet metal boxes of 819 cm.2 internal capacity and smaller shall be sheet steel, galvanized with suitable covers and screws. 5. Sheet metal boxes larger than 819 cm.2 internal capacity shall be constructed of code gauge welded sheet steel, reinforced if required, and finished with standard gray enamel or galvanized. Boxes shall have removable screw mounted covers. Steel boxes shall use brass screws. 6. Boxes installed outdoors shall be weatherproof. Boxes installed indoors shall be general purpose in Control Room and dust-tight, driptight type elsewhere. 7. Tags for wires and cables shall be Brady clip-sleeve type nonmetallic wire markers or equivalent. 8. For conduit fittings, conduit hangers and supports, expansion joints, sleeves and wiring devices, see applicable paragraphs of the Electrical Section of the Specifications. Electrical Wiring Installation 1. Wiring in Mechanical Equipment Rooms, communications or electrical closets shall be in approved raceways (cable tray, conduit, etc.). Wiring within dry wall cavities or enclosures or beneath raised floor construction shall be in conduit. Wiring shall be independently supported from the building structure with bridal rings and clips. The supporting of wiring from mechanical ductwork or piping is not acceptable. 2. Cables for 220/24 volt a.c. wiring, communications wiring and low level signal wiring (i.e., 4-20 mA analog) shall always be run in separate raceways. 3. Use liquidtight flexible metal conduit, 13 mm. minimum size, for making connections at instruments and devices mounted on piping or vessels or on equipment subject to vibration. 4. Low level signal wiring homeruns to local control stations may be by means of multi-pair cables. The number of pairs in such cables shall be uniform throughout the installation, and, in general, there shall be at least 20% spare pairs in each such cable. 5. 220 volt a.c. circuits used for control and instrumentation shall be taken from panelboards connected to the emergency power distribution system, with the exception of circuits powered from motor starters. Panelboard and circuit breakers shall be provided by the Electrical Subcontractor , but the wiring and raceway Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-236 HVAC Issued for Construction 1 June 2004 materials and installation for ATC system power requirements shall be furnished by this Subcontractor. 6. 220 volt a.c. circuits used for control and instrumentation shall be dedicated to the BMS system and shall not be used for any other purposes. 7. Conveniently located terminal junction boxes shall be used for the transition from the single pair local signal cables to the multipair homerun cable. These boxes shall have "terminal schedules" attached to the inside of their covers displaying the terminals and the service tags of the cables terminated there. 8. Conduits shall be run exposed in mechanical spaces, concealed in occupied spaces, and parallel or perpendicular to structural members or architectural features. 9. Bends in conduit shall not have a radius less than six (6) times the diameter of the conduit, nor bend more than 90 degrees. 10. Provide junction boxes or pull boxes as required and necessary to avoid excessively long runs or too many bends between outlets. 11. Fittings in conduit containing multi-conductor cables shall be oversized to accommodate 3 times cable bending radius for 90 degree bends and 4 times bending radius for straight runs. 12. Expansion fittings shall be provided with bonding jumpers. Expansion joint fittings shall be provided at each point where conduits cross expansion joints and conduit is rigidly attached to structure on both sides of joint. Where there is a 45 degree or greater bend and 2 meters of unconfined conduit on one side of the joint, the fittings may be omitted. 13. For conduit supports and installation of wires and cables, see applicable paragraphs of the Electrical Section of the Specifications. 14. Conduit entering a cabinet, box, trough, etc., shall be secured with a locknut on the outside and on the inside, such that the conduit system is electrically continuous throughout. A bushing shall also be provided on the inside. Bushings shall be metal with insulated throats. Locknuts shall be the type designed to bite into the metal, or on the inside of the enclosure shall have a grounding wedge lug under the locknut, as manufactured by Thomas & Betts, or approved equal. Top or side of any enclosure in a nonfinished area, such as Garages, Substations, Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-237 HVAC Issued for Construction 1 June 2004 Rooms, etc., shall be terminated with screwed waterproof hubs such as manufactured by Myers. 15. Conduit box type connectors for conduit entering enclosures shall be the insulated throat type. 16. Conduits shall be offset where they enter surface mounted equipment. Wiring installed in panels and other enclosures shall be neatly looped and laced. 17. Conduit runs which extend from the interior to the exterior of a building shall be sealed to prevent the circulation of air. This shall be accomplished by the installation of sealing fittings. 18. All wires terminating at each field device, terminal box, field equipment cabinet, DDC control unit, or any other terminals, shall be identified using Brady clip sleeve type nonmetallic wire markers or equivalent. The identification shall be consistent with the tagging indicated on the approved shop drawings. The same identification code shall be carried through from the field device to the final termination point. After identification is complete, the wire markers shall be anchored using a single layer of non-yellowing clear mylar tape. 19. Wires shall be terminated with insulated spade type lugs on screw terminals. Soldered connections shall only be made at instruments where no other means of termination is practical. 20. Perform continuity testing for all wiring installed. 21. Control raceways shall not be hung from electrical raceways or attached to ceiling grid hanger wires. 22. Percent fill of conduit, EMT or IMC shall not exceed Code maximum, regardless of service. 23. No 300 volt insulated wiring shall terminate within or occupy any enclosure containing conductors operating at a voltage greater than 300 volts. This particularly applies to any analog or digital I/O wiring entering 460 volt motor starter enclosures or motor control centers. 24. Provide, install and wire receptacles for Control Room devices. 25. Use of tie wraps for supporting conduit, wire, cable, etc., shall not be permitted. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-238 HVAC Issued for Construction 1 June 2004 T. Location of Wiring and Outlets: Coordinate with other Sections involved in this work so that exact locations may be obtained for outlets, apparatus, appliances and wiring. U. Testing, Calibration and Commissioning 1. After completion of the installation of work in this Section, test, regulate, and adjust system equipment, controllers, alarms, thermostats, humidistats, automatic control valves, automatic damper motors, and related system accessories, the entire automation system, and any other equipment or system that the control system interfaces with, including interconnections with the building life safety system, and place these items in complete and satisfactory operating condition. 2. Furnish labor and test apparatus required to calibrate and prepare for service instruments, controls and accessory equipment furnished under this Section. This work includes: Zero, span and range calibration checks of instruments and accessories, both field and panel mounted. In addition, this Subcontractor shall check actuators, control valves and automatic dampers, to insure proper action, stroke each actuator valve and automatic damper, and make necessary adjustments for stem and blade travel. 3. Furnish labor and test apparatus required to check the operation of control loops, set points and interlocks, as well as electronic equipment. This Subcontractor shall test every input/output point for proper performance through the entire system and maintain accurate test records for each point throughout the testing cycle and thereafter. In addition, this Subcontractor shall have the responsibility for integrated system testing with equipment and Subcontractors not covered under this Contract but with whom the control system interfaces. The Engineer reserves the right to inspect those test records at any time and also to witness any of the point tests he deems appropriate. Testing shall be witnessed and accepted by Engineer's representative and this Subcontractor shall be responsible for correcting any work unacceptable to Engineer. 4. Upon completion of the testing and calibration and in the presence of the Engineer and Mechanical Consulting Engineer, conduct an inspection of the control system and perform such tests that shall be required to determine that contract obligations have been fulfilled. Notify Engineer and Mechanical Consulting Engineer two (2) weeks in advance of readiness to make such tests. 5. For site tests, this Subcontractor shall submit a test plan and commissioning forms for each system (i.e., air conditioning Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-239 HVAC Issued for Construction 1 June 2004 system, exhaust fans, pumps, chillers, cooling towers, etc.) for review by the Engineer. After review of the plan, this Subcontractor shall prepare and submit a detailed test procedure for review. The test procedure shall also include reference to the Specification Section and Paragraph with which each test is intended to demonstrate compliance, together with the criteria for acceptance or rejection. 6. The site system test, conducted by this Subcontractor in accordance with the test procedures and project schedules, and witnessed by the Engineer or Mechanical Consulting Engineer, shall be a comprehensive test of the system to demonstrate that all aspects of the hardware and software are in conformance with the Specification requirements. The system test shall include testing of all network computers so as to demonstrate no substantial degradation of performance of their functions as buildings, blocks, and network computers are added to the system. The Engineer shall be notified at least five (5) working days prior to any testing and shall have the option of witnessing any and all tests. 7. Minimum validation and sign-off requirement (on all work stations) shall be as follows: a. b. c. d. e. f. g. h. i. j. k. l. Run samples of specified reports and trends. Execute menu tree. Display all required graphics. Execute digital and analog commands via mouse and keyboard. Demonstrate data entry/point modification/ programming. Demonstrate program downloading. Demonstrate program uploading. Demonstrate control loop execution and stability. Demonstrate specified diagnostics. Demonstrate scan, update and alarm response. Execute all-points summary. Execute communication status checks. 8. The guarantee period shall not start until systems in this Section have been approved and accepted by the Engineer and Mechanical Consulting Engineer, as detailed in the previous paragraph, at which time the Engineer shall accept, in writing, the system of this Section in its entirety. This does not preclude the beneficial use by the Engineer of any portion of the system prior to final acceptance of the whole system. 9. During the guarantee period, this Subcontractor shall test the system under varying seasonal conditions to ensure that all operational sequences, as specified, are performed correctly. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-240 HVAC Issued for Construction 1 June 2004 This shall include at least three additional visits after initial Engineer acceptance. Where necessary, this Subcontractor shall make programming adjustments and instrument calibrations at no cost to the Engineer. V. Instruction of Operating Personnel: Provide a minimum of 40 hours of operating and maintenance instruction for ten building operators, with personal on-the-job instruction by factory trained engineers representing the direct control system manufacturer. This instruction shall be scheduled at time(s) convenient to the Engineer's personnel. Instruction shall cover all equipment and systems provided under this Section. The number of hours is a minimum requirement; where additional hours are specified in other paragraphs of this Section, those hours shall be additive to the minimum above. Instruction shall be comprised of both classroom type and actual hands-on operating experience. Submit an outline of the instruction program and instruction manual to the Engineer for his approval at least two weeks prior to the proposed start date of the instruction sessions. The Engineer shall videotape all instruction sessions for purposes of future training. Provide a review and written critique of Engineer's videotape within one month after completion of the instruction sessions and receipt of the Engineer's videotapes. The critique shall correct all mistakes and clarify all outstanding questions which arise during the sessions. W. Servicing and Maintenance Requirements 1. Ten complete sets, each, of the following shall be provided: Written operating and maintenance instructions, as-built drawings, specification data sheets and maintenance schedules. 2. Three service kits for use by building personnel in testing and making minor service adjustments of the system shall be furnished and delivered to the Engineer and a receipt obtained. This kit shall be adequate for the building personnel trained by this Trade to effect the immediate repair of the remote equipment specified above. The following items shall be included as a minimum service kit requirement: a. 3. Specialized nonstandard tools and adapters and fittings required for operating, maintaining, testing and adjustment of the system. In addition to the above service kits, special tools and spare parts required for operation and maintenance of equipment shall be furnished and delivered to the Engineer and a receipt obtained. A list of the special tools and spare parts to be supplied shall be detailed in the technical proposal. These items shall be given to the Engineer prior to or at the time of the instruction to Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-241 HVAC Issued for Construction 1 June 2004 operating personnel. The special tools and spare parts shall, as a minimum, consist of the following: a. Keys for thermostats and humidistats, six each. b. Lubricant required for automatic valves and automatic dampers, one year supply. 4. Warrant the continuous future availability of service for the central automation system. The servicing shall be provided by a factory trained service representative. 5. Components, parts and assemblies shall be guaranteed against defects in workmanship and materials for a period of one year after final Engineer acceptance. In addition, provide 400 day preventive maintenance, operator instruction (as described hereinbefore) and system maintenance training. During the one (1) year guarantee, the Subcontractor shall assume all costs associated with the repair or replacement of defective components. 6. During system commissioning and prior to the guarantee period, provide the operating instructions to the Engineer's operators. 7. For the purpose of definition, the following shall apply: 8. a. Beneficial Use: This shall mean that the Engineer's operators are able to use the facility and receive reliable information therefrom in their normal work schedules for inputs and outputs in the automation system in which this Subcontractor has completed work. b. Acceptance: The effective date of the start of the 12 month service contract shall constitute formal acceptance of the system or portions thereof. c. Guarantee: The terms of the service contract shall fulfill the guarantee requirements. The expiration of the first 12 month paid-up service contract shall constitute termination of the guarantee period unless excepted by amendments to the service contract. Alternates a. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Alternate No. 15000-1: State the amount to be ADDED to the Base Contract to provide an annual service contract for the automatic temperature control system for the 1st through 5th year. Provide a copy of the service 15000-242 HVAC Issued for Construction 1 June 2004 agreement which is the basis of your pricing, which you would ask the client to sign. 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC The service contract shall include the following minimum provisions: a) To provide regularly scheduled preventive maintenance and service of at least one man-day per month by factory trained service representatives of this Subcontractor. This service shall be provided from a fully staffed direct branch office of this Subcontractor located within 20 km. of the job site. Annual service agreement shall include all travel and accommodation expenses. b) To replace defective components as required. c) To incorporate improved system reliability as it becomes available for the system from the manufacturer. This provision includes direct component replacements and wiring changes, but shall not include major system design changes. d) To make available, upon request, 24hour emergency maintenance service which includes on-site response to emergency service call within 4 hours of initial request and system interrogation within 2 hours of initial request via telephone modem interface. e) The Engineer shall reserve the right to exclude from the service agreement those input points and installation thereof for which construction conditions prohibit installation, calibration, and checkout by the manufacturer. As these input points are subsequently placed in operation, they shall be included in the service agreement by amendment to the agreement. 15000-243 parts and HVAC Issued for Construction 1 June 2004 b. X. Alternate 15000-2: State the amount to be ADDED to the Base Contract to furnish and install an on-line UPS system, power distribution panel(s), circuit breakers, power riser, etc., to serve the entire DDC system. The UPS system shall be of a PWM design with separate rectified chargers and inverter sections (double conversion design). The UPS inverter shall supply conditioned/regulated power to the critical load 100% of the time. The UPS complete with batteries, external bypass and line conditioning shall be provided to totally back up all DDC control units, field panels, and all field devices (i.e., transmitters, relays, etc.) for 15 minutes. One UPS system shall supply the entire BATC system. Sizing of UPS system (i.e., maximum power requirements) shall be provided by this Subcontractor, and submitted to the Mechanical Consulting Engineer for review. Location of power source and UPS system to be determined by the Mechanical Consulting Engineer upon submission of UPS capacity. UPS shall be sized for 50% spare capacity. Wiring and conduit between the emergency power source and the UPS and between the UPS and the distribution panel and between the distribution panel and all direct digital control units, field equipment cabinets, network computer and unitary controllers, etc., shall be furnished and installed by Subcontractor. Description of Control Operation 1. General a. Control of building systems shall be accomplished by a DDC system, including a network computer and peripherals. b. All control algorithms, computation functions and energy management functions shall be software-based and resident in the DDC system. The operator shall have the capability through the network computer operator's keyboard to access all programs, display all data resident in the DDC system memory and perform analog and digital functions at each local direct digital control unit or at the network computer. c. The DDC system network computer shall be the primary location for operator access to the system. d. Unless otherwise noted, all equipment described hereinafter may be started manually from the DDC Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-244 HVAC Issued for Construction 1 June 2004 system network computer, the smoke control panel, or from a time program within the local stand-alone direct digital control units and run subject to smoke detector and protection interlocks. In addition, the network computer can start and stop each system regardless of the time program. e. All motors shall be provided with MCC "Hand-OffAuto" switches located at the starter. Motors can be started locally by placing these switches in the "Hand" position. These switches should be placed in the "Auto" position for DDC operation. f. If a motor which was last commanded "off" is started locally from the "Hand" position of the starter H-O-A switch, an "off-normal" alarm shall be transmitted to the network computer, the system controls for that motor only shall be activated, and a normal starting procedure shall be executed. The system shall remain in the "offnormal" alarm state until the starter H-O-A switch is returned to the "Auto" position. Similarly, if a motor last commanded "on" is running and is stopped locally by placing the starter H-O-A switch in the "Off" position, an "off-normal" alarm shall be transmitted to the network computer, the control system shall be deactivated and the system shall remain in the "offnormal" alarm state until the H-O-A starter switch is returned to the "Auto" position. During normal starting or stopping of the motors from a DDC program or the network computer, a motor which fails to follow its commanded state shall generate an "off-normal" alarm at the network computer. g. Simultaneous starting of motors shall be prevented by a sequential start program in the DDC system. This program shall also provide sequential restart after power failure of motors that were running prior to power failure. h. When a fan is started manually from the life safety smoke control panel, fan shutdown due to high discharge pressure and low suction pressure switches shall remain active. i. Automatic restart of fans after an equipment or life safety system shutdown trip shall be software prohibited through the deenergization of the remote start/stop contact. Fan restart shall be manually initiated by the Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-245 HVAC Issued for Construction 1 June 2004 operator either locally or remotely through the DDC system network computer. 2. j. Alarming devices (i.e., pressure switches, dry alarm contacts) shall be wired so that alarm contacts "open" in the alarm condition. k. All devices required to properly and timely position outdoor, return, fan discharge and fan inlet dampers when a fan is started via the “Hand” position of the starter shall be provided and installed by this Section. A time delay relay shall be hardwired to the starter circuit to allow the dampers to open prior to fan start. l. All software set points shall be operator adjustable via the network computer. m. Each fan which in started via the DDC system shall be monitored at the DDC system for run status via currentsensing relays. Atrium Air Conditioning Systems and Associated Return Fans a. Each air conditioning system is a constant air volume system which operates in conjunction with a constant volume return fan. There shall be two (2) headered systems to serve the 1st Floor and two (2) headered systems to serve the 2nd, 3rd and 4th Floors. b. The systems shall be controlled by a direct digital control system (DDC) with electronic sensing of system parameters, and electronic of control valves and dampers. The Atrium shall be exhausted for smoke via dedicated smoke exhaust fans. c. Each supply and return fan shall be furnished with a variable frequency drive. The drives shall operate at two (2) preset speeds based on a software occupied/unoccupied time program. d. When the fans are not in operation, the minimum outdoor air, maximum outdoor air purge, maximum exhaust air purge, return air, supply and return floor/area isolation (i.e., fire/smoke dampers) and fan discharge dampers shall be closed. The normally closed chilled water coil valve shall be closed. The various electric duct heaters located in the supply air ducts shall be off. The heat recovery coil three-way valve shall be closed to the coil and the pump shall be off. The systems serving Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-246 HVAC Issued for Construction 1 June 2004 the 2nd and 3rd Floors shall contain a spill damper. When the fan system is off, the spill damper shall be closed. When the system starts, the damper shall open. e. When fan start is initiated, the temperature control system shall be in operation, and a software time delay shall inhibit supply fan start until the system return air damper is open. The start of each supply fan shall be time delayed to avoid simultaneous starting of fans on the same system. The supply fan and return discharge dampers shall open after a time delay to enable the fan to reach minimum speed. f. The Engineer shall have the ability to override a starting or stopping or occupied/unoccupied mode of any fan from the network computer or the direct digital field control unit. g. On a command to stop a fan, the fans shall stop and all dampers shall close. h. During normal operation (i.e., non-fire alarm condition), fans shall operate continuously. A DDC software time program shall determine the occupied and unoccupied mode via preprogrammed time settings established by the operating engineer. During the occupied mode, the supply and return fans shall operate at full speed. During unoccupied mode, the supply and return fans speeds shall be automatically reset to a lower speed equal to 50% of the design fan maximum airflow (adjustable). i. Normal Operation Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) The minimum outdoor air damper shall remain open. 2) A three-mode DDC software fan discharge temperature controller shall position the cooling coil valve to maintain the supply air temperature set point. 3) A return air humidity transmitter shall provide an input to the software controller which shall override the control of the chilled water valve on sensing a return air relative humidity above set point (50% RH adjustable). The controller shall modulate open the chilled water valve to maintain return air relative humidity set point. 15000-247 HVAC Issued for Construction 1 June 2004 On sensing a decrease in return air humidity below 45% (adjustable), the program shall allow the chilled water valve to be controlled to maintain supply air temperature set point. j. k. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Electric Duct Heaters 1) Each electric duct heater shall be controlled via an independent DDC three-mode software controller which shall monitor the space temperature via a temperature transmitter and modulate the SCR controlled heating coils to maintain space temperature set point. Space temperature transmitter shall be nonindicating type with no local adjustment. There shall be a temperature transmitter and software controller for each reheat coil. Each heater shall be provided with an airflow switch which shall disable operation of the heater on a loss of airflow. 2) There shall be a temperature transmitter and software controller for each reheat coil. Heat Recovery Coil Control: 1) The heat recovery coil shall be utilized as the first stage of heating. 2) Dehumidification Mode: During this mode, the heat recovery coil three-way valve shall modulate based on a DDC discharge temperature controller. A temperature transmitter located downstream of the coil shall provide an input to the software controller which shall position the three-way valve to maintain supply temperature set point. 3) When the dehumidification mode is not active, a DDC software program shall monitor the space temperature, space temperature set point, and output command to each reheat coil. A DDC reset program shall monitor each reheat coil controller, its temperature set point and each space temperature transmitter. The program shall reset upwards the supply temperature set point one degree every 30 minutes (adjustable) if all electric reheat coils are in operation. The discharge temperature reset program shall first 15000-248 HVAC Issued for Construction 1 June 2004 modulate close the cooling coil (when dehumidification mode is not active) then modulate open the heat recovery coil control valve. The controller shall continue to reset the air conditioning unit’s supply air temperature set point until a reheat coil is deenergized or any space temperature rises above set point with its reheat coil deenergized, at which point the controller shall reset downwards the supply temperature set point at the same rate as described above to satisfy the space temperature which requires the greatest cooling load. 3. l. High Discharge Pressure Switches and Low Suction Pressure Switches: Pressure differential switches installed in the discharge of each supply and return fan, which sense discharge pressure, shall stop the fan and transmit an alarm to the network computer by means of a digital input to the system DDC controller, if the pressure set point of the switch is exceeded. A separate pressure switch installed in the inlet of each supply and return fans shall also stop the fan and transmit the alarm if fan suction pressure is below its set point. The fan shutdown shall be operative whether the starter H-O-A switch is in the "Auto" or "Hand" position. m. Minimum Outdoor Air Flow Quantity Control: Air flow measuring stations installed upstream of the minimum outside air dampers of each air conditioning system shall measure minimum air flow. Should outside air flow be below set point, the return air damper shall be modulated closed until the minimum outside air flow is at set point. On an increase of outside air above set point, the return air damper shall be modulated open to achieve set point. The minimum outside airflow rates shall be transmitted, on a real time basis, to the DDC system for monitoring and trending. The software controller shall contain a software minimum position for the return air damper. Gallery Air Conditioning Systems and Associated Return Fans Serving the 1st Floor a. Each air conditioning system is a constant air volume system which operates in conjunction with a constant volume return fan. There shall be two (2) headered systems. b. The systems shall be controlled by a direct digital control system (DDC) with electronic sensing of system Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-249 HVAC Issued for Construction 1 June 2004 parameters, and electronic of control valves and dampers. The Gallery shall be exhausted for smoke via dedicated smoke exhaust fans. c. Each supply and return fan shall be furnished with a variable frequency drive. The drives shall operate at two (2) preset speeds based on a software occupied/ unoccupied time program. d. When the fans are not in operation, the minimum outdoor air, maximum outdoor air purge, minimum exhaust air purge, return air, supply and return floor/area isolation (i.e., fire/smoke dampers) and fan discharge dampers shall be closed. The normally closed chilled water coil valve shall be closed. The various electric duct heaters located in the supply air ducts shall be off . The heat recovery coil valve shall be closed to the coil and its associated pump shall be off. e. When fan start is initiated, the temperature control system shall be in operation, and a software time delay shall inhibit supply fan start until the system return air damper is open. The start of each supply fan shall be time delayed to avoid simultaneous starting of fans on the same system. The supply fan and return discharge dampers shall open after a time delay to enable the fan to reach minimum speed. f. The Engineer shall have the ability to override a starting or stopping or occupied/unoccupied mode of any fan from the network computer or the direct digital field control unit. g. On a command to stop a fan, the fans shall stop and all dampers shall close. h. During normal operation (i.e., non-fire alarm condition), fans shall operate continuously. A DDC software time program shall determine the occupied and unoccupied mode via preprogrammed time settings established by the operating engineer. During the occupied mode, the supply and return fans shall operate at full speed. During unoccupied mode, the supply and return fans speeds shall be automatically reset to a lower speed equal to 50% of the design fan maximum airflow (adjustable) and the outdoor air dampers shall be closed. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-250 HVAC Issued for Construction 1 June 2004 i. j. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Normal Operation 1) The minimum outdoor air damper shall remain open. 2) A three-mode DDC software fan discharge temperature controller shall position the cooling coil valve to maintain the supply air temperature set point. 3) A return air humidity transmitter shall provide an input to the software controller which shall override the control of the chilled water valve on sensing a return air relative humidity above set point (50% RH adjustable). The controller shall modulate open the chilled water valve to maintain return air relative humidity set point. On sensing a decrease in return air humidity below 45% (adjustable), the program shall allow the chilled water valve to be controlled to maintain supply air temperature set point. Heat Recovery Coil Control: 1) The heat recovery coil shall be utilized as the first stage of heating. 2) Dehumidification Mode: During this mode, the heat recovery coil three-way valve shall modulate based on a DDC discharge temperature controller. A temperature transmitter located downstream of the coil shall provide an input to the software controller which shall position the three-way valve to maintain supply temperature set point. 3) When the dehumidification mode is not active, a DDC software program shall monitor the space temperature, space temperature set point, and output command to each reheat coil. A DDC reset program shall monitor each electric reheat coil controller, its temperature set point and each space temperature transmitter. The program shall reset upwards the supply temperature set point one degree every 30 minutes (adjustable) if all electric reheat coils are in operation. The discharge temperature reset program shall first modulate close the cooling coil (when dehumidification mode is not active) then 15000-251 HVAC Issued for Construction 1 June 2004 modulate open the heat recovery coil valve. The controller shall continue to reset the air conditioning unit’s supply air temperature set point until all the reheat coils are deenergized or any space temperature rises above set point with its reheat coil deenergized, at which point the controller shall reset downwards the supply temperature set point at the same rate as described above to satisfy the space temperature which requires the greatest cooling load. k. Electric Duct Heaters: Each electric duct heater shall controlled via an independent DDC three-mode software controller which shall monitor the space temperature via a temperature transmitter and modulate the SCR controlled heating coils to maintain space temperature set point. Space temperature transmitter shall be indicating type with no local adjustment. There shall be a temperature transmitter and software controller for each reheat coil. Each heater shall be provided with an airflow switch which shall disable operation of the heater on a loss of air flow. l. High Discharge Pressure Switches and Low Suction Pressure Switches: Pressure differential switches installed in the discharge of each supply and return fan, which sense discharge pressure, shall stop the fan and transmit an alarm to the network computer by means of a digital input to the system DDC controller, if the pressure set point of the switch is exceeded. A separate pressure switch installed in the inlet of each supply and return fans shall also stop the fan and transmit the alarm if fan suction pressure is below its set point. The fan shutdown shall be operative whether the starter H-O-A switch is in the "Auto" or "Hand" position. m. Minimum Outdoor Air Flow Quantity Control: Air flow measuring stations installed upstream of the minimum outside air dampers of each air conditioning system shall measure minimum air flow. Should outside air flow be below set point, the return air damper shall be modulated closed until the minimum outside air flow is at set point. On an increase of outside air above set point, the return air damper shall be modulated open to achieve set point. The minimum outside airflow rates shall be transmitted, on a real time basis, to the DDC system for monitoring and trending. The software controller shall contain a software minimum position for the return air damper. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-252 HVAC Issued for Construction 1 June 2004 n. 4. Smoke Control: On activation of a life safety alarm within the Gallery, the air conditioning unit supply and return fans shall stop and remain off. Dedicated smoke exhaust fans serving the Gallery shall be manually started via the smoke control panel. Gallery Air Conditioning Systems and Associated Return Fans Serving 2nd, 3rd, and 4th Floors a. Each air conditioning system is a constant air volume system which operates in conjunction with a constant volume return fan. There shall be two (2) headered systems to serve each floor, 2nd through 4th. b. The systems shall be controlled by a direct digital control system (DDC) with electronic sensing of system parameters, and electronic of control valves and dampers. The Gallery shall be exhausted for smoke via dedicated smoke exhaust fans. c. Each supply and return fan shall be furnished with a variable frequency drive. The drives shall operate at two (2) preset speeds based on a software occupied/ unoccupied time program. d. When the fans are not in operation, the minimum outdoor air, maximum outdoor air purge, minimum exhaust air purge, return air, supply and return floor/area isolation (i.e., fire/smoke dampers) and fan discharge dampers shall be closed. The normally closed chilled water coil valve shall be closed. The various electric duct heaters located in the supply air ducts shall be off and their associated humidifiers shall be off. The heat recovery coil valve shall be closed to the coil and its associated pump shall be off. The system serving the 3rd Floor shall contain a spill damper. When the system is off, the spill damper shall be closed. When the system starts, the damper shall open. e. When fan start is initiated, the temperature control system shall be in operation, and a software time delay shall inhibit supply fan start until the system return air damper is open. The start of each supply fan shall be time delayed to avoid simultaneous starting of fans on the same system. The supply fan and return discharge dampers shall open after a time delay to enable the fan to reach minimum speed. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-253 HVAC Issued for Construction 1 June 2004 f. The Engineer shall have the ability to override a starting or stopping or occupied/unoccupied mode of any fan from the network computer or the direct digital field control unit. g. On a command to stop a fan, the fans shall stop and all dampers shall close. h. During normal operation (i.e., non-fire alarm condition), fans shall operate continuously. A DDC software time program shall determine the occupied and unoccupied mode via preprogrammed time settings established by the operating engineer. During the occupied mode, the supply and return fans shall operate at full speed. During unoccupied mode, the supply and return fans speeds shall be automatically reset to a lower speed equal to 50% of the design fan maximum airflow (adjustable) and the outdoor air dampers shall be closed. i. Normal Operation j. 1) The minimum outdoor air damper shall remain open. 2) A three-mode DDC software fan discharge temperature controller shall position the cooling coil valve to maintain the supply air temperature set point. 3) A return air humidity transmitter shall provide an input to the software controller which shall override the control of the chilled water valve on sensing a return air relative humidity above set point (50% RH adjustable). The controller shall modulate open the chilled water valve to maintain return air relative humidity set point. On sensing a decrease in return air humidity below 45% (adjustable), the program shall allow the chilled water valve to be controlled to maintain supply air temperature set point. Zone Heat Recovery Coils, Electric Duct Heaters 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Each zone heat recovery coil and electric duct heater shall controlled via an independent DDC three-mode software controller which shall monitor the space temperature via a temperature transmitter and modulate the heat recovery coil 15000-254 HVAC Issued for Construction 1 June 2004 three-way control valve and SCR controlled heating coils in sequence to maintain space temperature set point. The heat recovery coils shall operate before the electric heating coils. Space temperature transmitter shall be indicating type with no local adjustment. There shall be a temperature transmitter and software controller for each heat recovery and reheat coil. Each electric heater shall be provided with an airflow switch which shall disable operation of the heater on a loss of air flow. k. Supply Air Temperature Reset: A DDC reset program shall monitor each electric reheat coil controller, its temperature set point and each space temperature transmitter. The program shall reset upwards the supply temperature set point one degree every 30 minutes (adjustable) if any electric reheat coil is in operation. The controller shall continue to reset the air conditioning unit’s supply air temperature set point until all the reheat coils are deenergized or any space temperature rises above set point with its reheat coil deenergized, at which point the controller shall reset downwards the supply temperature set point at the same rate as described above to satisfy the space temperature which requires the greatest cooling load. l. High Discharge Pressure Switches and Low Suction Pressure Switches: Pressure differential switches installed in the discharge of each supply and return fan, which sense discharge pressure, shall stop the fan and transmit an alarm to the network computer by means of a digital input to the system DDC controller, if the pressure set point of the switch is exceeded. A separate pressure switch installed in the inlet of each supply and return fans shall also stop the fan and transmit the alarm if fan suction pressure is below its set point. The fan shutdown shall be operative whether the starter H-O-A switch is in the "Auto" or "Hand" position. m. Minimum Outdoor Air Flow Quantity Control: Air flow measuring stations installed upstream of the minimum outside air dampers of each air conditioning system shall measure minimum air flow. Should outside air flow be below set point, the return air damper shall be modulated closed until the minimum outside air flow is at set point. On an increase of outside air above set point, the return air damper shall be modulated open to achieve set point. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-255 HVAC Issued for Construction 1 June 2004 The minimum outside airflow rates shall be transmitted, on a real time basis, to the DDC system for monitoring and trending. The software controller shall contain a software minimum position for the return air damper. n. Indoor Air Quality Control: A combination CO2/VOC transmitter shall be installed in the each zone of each air conditioning system. In addition, a CO2/VOC transmitter shall be installed downstream of supply air filter on each air conditioning system. The output of the CO2/VOC shall be monitored by the DDC system and compared to their high limit setting. Should either measurement exceed its high limit setting, an alarm shall be generated at the network computer, alerting the operator of the alarmed condition. In addition, a DDC controller shall proportionally control each individual fresh air damper from fully closed to fully open (with user-defined minimum and maximum software limits) to satisfy the CO2/VOC set point. o. Purge Outdoor Air and Exhaust Air Dampers p. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) Dampers shall be operator selectable only. The dampers shall provide two-position (full open or full closed) operation, positioned via the network computer and the smoke control panel. 2) The purge outdoor air and exhaust air dampers shall be utilized to provide a fresh air purge of the space when the outdoor air conditions permit their use. The operator shall manually open the purge dampers via the network computer and start the air conditioning system. During this mode, the main return air damper to the air conditioning system shall be closed to provide 100% outdoor air and exhaust air to the space. 3) During smoke exhaust or normal mode of operation of the space, the dampers shall be closed. Smoke Control: On activation of a life safety alarm within the Gallery, the air conditioning unit supply and return fans shall stop and remain off. Dedicated smoke exhaust fans serving the Gallery shall be manually started via the smoke control panel. 15000-256 HVAC Issued for Construction 1 June 2004 5. Auditorium Air Conditioning System and Associated Return Fan (Typical for 5th Floor Administration Air Conditioning System and Associated Return Fan) a. The air conditioning system is a variable air volume system which operates in conjunction with a variable volume return fan. The supply and return air fans shall be provided with variable frequency drives. The systems shall be controlled by a direct digital control system (DDC) with electronic sensing of system parameters, and electric actuation of control valves and dampers. b. When the fans are not in operation, the minimum outdoor air, purge outdoor air, return air, purge exhaust air damper, supply and return floor/area isolation (fire/smoke dampers) and fan discharge dampers shall be closed. No control signal shall be transmitted to the variable frequency drive process follower speed controller. The normally closed chilled water coil valve shall be closed. The heat recovery coil valves shall be closed and the associated pump shall be off. c. When fan start is initiated, the temperature control system shall be in operation, and a software time delay shall inhibit supply fan start until the system return air damper is open. Fans shall start and run at minimum speed required to maintain rotation, but not less than 6 Hz. The start of each supply fan shall be time delayed to avoid simultaneous starting of fans on the same system. The supply fan and return discharge dampers shall open after a time delay to enable the fan to reach minimum speed. After the fans are running, and the discharge dampers are open, the software static pressure controller shall slowly ramp up the speed of the supply fan to satisfy system static pressure demand. d. The Engineer shall start or stop any fan from the network computer or the direct digital field control unit. Fans shall be started and run continuously. A DDC software time program shall determine the occupied and unoccupied mode via preprogrammed time settings established by the operating engineer. During the occupied mode, the minimum outdoor air damper shall be open. During the unoccupied mode, the minimum outdoor air damper shall be closed. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-257 HVAC Issued for Construction 1 June 2004 e. On a command to stop a fan, the fan shall ramp down to its minimum speed, the fans shall stop and all dampers shall close. f. Normal Operation g. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) The minimum outdoor air damper shall remain open. The purge outdoor and purge exhaust damper shall remain closed. 2) A three-mode fan discharge temperature controller shall position the cooling coil valve to maintain the supply air temperature set point. 3) A return air humidity transmitter shall provide an input to the software controller which shall override the control of the chilled water valve on sensing a return air relative humidity above set point (50% RH adjustable). The controller shall modulate open the chilled water valve to maintain return air relative humidity set point. On sensing a decrease in return air humidity below 45% (adjustable), the program shall allow the chilled water valve to be controlled to maintain supply air temperature set point. 4) During occupied hours, the discharge air temperature set point shall be set for 55ºF. (adjustable). 5) During the night and unoccupied times, a DDC software program shall reset the set point of the supply air temperature from 55ºF. to 64ºF., as return air temperature drops from 75ºF. to 72ºF. Heat Recovery Coil Control: 1) The heat recovery coil shall be utilized as the first stage of heating. 2) Dehumidification Mode: During this mode, the heat recovery coil three-way valve shall modulate based on a DDC discharge temperature controller. A temperature transmitter located downstream of the coil shall provide an input to the software controller which shall position the three-way valve to maintain supply temperature set point. 15000-258 HVAC Issued for Construction 1 June 2004 h. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 3) When the dehumidification mode is not active, a DDC software program shall monitor the space temperature, space temperature set point, and output command to each VAV box reheat coil. 4) A DDC reset program shall monitor each reheat coil controller, its temperature set point and each space temperature transmitter. The program shall reset upwards the supply temperature set point one degree every 30 minutes (adjustable) if all electric reheat coils are in operation. The discharge temperature program shall first modulate close the cooling coil (when dehumidification mode is not active) then modulate open the heat recovery coil control valve. The controller shall continue to reset the air conditioning unit’s supply air temperature set point until a reheat coil is deenergized or any space temperature rises above set point with its reheat coil deenergized, at which point the controller shall reset downwards the supply temperature set point at the same rate as described above to satisfy the space temperature which requires the greatest cooling load. Static Pressure Control 1) A reverse-acting 2-mode (proportional plus integral) DDC software controller shall control the supply fan speed, based upon the input from a static pressure transmitter located upstream from the furthest terminal unit served by the air conditioning unit. 2) The output of the software controller shall be the input to the speed controller on the supply fan. As duct static pressure decreases, the controller output shall increase, to increase fan speed. On an increase in duct static pressure, the output of the controller shall decrease, to decrease fan speed. A software auto/manual switch function shall enable the operator to override the output of the static pressure controller and adjust fan speed from the network computer or the DDC controller. 3) A static pressure transmitter in the common supply fan discharge duct shall provide a signal proportional to fan discharge static pressure to a 15000-259 HVAC Issued for Construction 1 June 2004 software based 2-mode pressure controller with reverse action, acting as a high limit. If fan discharge static pressure exceeds its set point, the high limit controller shall, through a software low selector, override the output of the system static pressure controller to proportionally reduce the speed of the supply fan to maintain fan discharge pressure high limit set point. 4) Static pressure controls shall control system operation during all cycles of operation, including smoke control mode. 5) During system start-up, the static pressure control algorithm, integral control mode shall be suppressed until the control point is within the proportional band of the controller to avoid reset wind-up. i. Flow Control: A software based DDC flow control program shall receive input signals from airflow measuring stations installed in the inlet of each supply and return fan, and totalize, linearize and scale them. The flow control program shall match the return fan with the supply fans and maintain the volumetric balance between return and supply airflow by varying return fan speed to maintain a constant differential between supply and return airflow. A software bias shall be provided to compensate the return flow for a constant outside air minimum at all operating loads. The operator shall be able to manually override the flow control program and manually control each supply and return fan. The software bias shall be suppressed during the smoke control override mode of operation. j. High Discharge Pressure Switches and Low Suction Pressure Switches: Pressure differential switches installed in the discharge of each supply and return fan, which sense discharge pressure, shall stop the fan and transmit an alarm to the network computer by means of a digital input to the system DDC controller, if the pressure set point of the switch is exceeded. A separate pressure switch installed in the inlet of each supply and return fans shall also stop the fan and transmit the alarm if fan suction pressure is below its set point. The fan shutdown shall be operative whether the starter H-O-A switch is in the "Auto" or "Hand" position. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-260 HVAC Issued for Construction 1 June 2004 k. Minimum Outdoor Air Flow Quantity Control: Air flow measuring stations installed upstream of the minimum outside air dampers of each air conditioning system shall measure minimum air flow. Should outside air flow be below set point, the return air damper shall be modulated closed until the minimum outside air flow is at set point. On an increase of outside air above set point, the return air damper shall be modulated open to achieve set point. This program shall be overridden during the economizer mode of operation. The minimum outside airflow rates shall be transmitted, on a real time basis, to the DDC system for monitoring and trending. The software controller shall contain a software minimum position for the return air damper. l. Indoor Air Quality Control: A combination CO2/VOC transmitter shall be installed in the main return air duct of the air conditioning system. In addition, a CO2/VOC transmitter shall be installed downstream of supply air filter on each air conditioning system. The output of the CO2/VOC transmitters shall be monitored by the DDC system and compared to their high limit setting. Should either measurement exceed its high limit setting, an alarm shall be generated at the network computer, alerting the operator of the alarmed condition. In addition, a DDC controller shall proportionally control each individual fresh air damper from fully closed to fully open (with user-defined minimum and maximum software limits). m. Purge Outdoor Air and Exhaust Air Dampers Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) Dampers shall be operator selectable only. The dampers shall provide two-position (full open or full closed) operation, positioned via the network computer and the smoke control panel. 2) The purge outdoor air and exhaust air dampers shall be utilized to provide a fresh air purge of the space when the outdoor air conditions permit their use. The operator shall manually open the purge dampers via the network computer and start the air conditioning system. During this mode, the main return air damper to the air conditioning system shall be closed to provide 100% outdoor air and exhaust air to the space. 3) During smoke exhaust of the space, the space return fan shall be started from the smoke control panel. When the fan starts, the DDC 15000-261 HVAC Issued for Construction 1 June 2004 system shall automatically close the main return air damper and open the purge exhaust damper. During this mode, the outdoor air dampers shall remain closed and the air conditioning unit supply fan shall be off. n. 6. Smoke Control: On activation of a life safety alarm within the space, the air conditioning unit supply and return fans shall stop. The supply fan shall remain off. The return air fan shall be utilized as a smoke exhaust fan and used to exhaust the space. Refer to description of operation titled “Purge Outdoor Air and Exhaust Air Dampers” for description of damper control. Restaurant Air Conditioning Systems and Associated Return Fans a. Each air conditioning system is a constant air volume system which operates in conjunction with a constant volume return fan. There shall be two (2) headered systems to serve the 5th Floor. b. The systems shall be controlled by a direct digital control system (DDC) with electronic sensing of system parameters, and electronic of control valves and dampers. c. Each supply and return fan shall be furnished with a variable frequency drive. The drives shall operate at three (3) preset speeds based on an occupied/unoccupied mode and the operation of the kitchen hood exhaust fan. d. When the fans are not in operation, the minimum outdoor air, maximum outdoor air purge, maximum exhaust air purge, return air, supply and return floor/area isolation (i.e. fire/smoke dampers) and fan discharge dampers shall be closed. The normally closed chilled water coil valve shall be closed. The various electric duct heaters located in the supply air ducts shall be off. The Kitchen transfer fan shall be off. e. When fan start is initiated, the temperature control system shall be in operation, and a software time delay shall inhibit supply fan start until the system return air damper is open. The start of each supply fan shall be time delayed to avoid simultaneous starting of fans on the same system. The supply fan and return discharge dampers shall open after a time delay to enable the fan to reach minimum speed. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-262 HVAC Issued for Construction 1 June 2004 f. The Engineer shall start or stop any fan from the network computer or the direct digital field control unit. g. On a command to stop a fan, the fans shall stop and all dampers shall close. h. During normal operation (i.e., non-fire alarm condition), fans shall operate subject to a software time program which shall determine the occupied and unoccupied mode via preprogrammed time settings established by the engineer. During the occupied mode, the minimum outdoor air damper shall be open and the supply and return fans shall operate at a preset speed sufficient to supply the Restaurant only. When the Kitchen hood exhaust fan is operating, the Kitchen transfer fan shall be on and the air conditioning system shall operate at full speed. During unoccupied mode, the supply and return fans shall operate at low speed and the minimum outdoor air damper shall be closed. Refer to the following matrix for airflow quantities and various operating modes. Occupied Mode Kitchen Exhaust Off Fan On Systems Air Conditioning System Supply Fan (Each) Minimum Outdoor Air Damper Air Conditioning System Return Fan (Each) Kitchen Constant Air Volume Terminal Unit Kitchen Transfer Fan Toilet Exhaust Fans (Each) General Exhaust Fan i. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Unoccupied Mode 5192 l/s 5664 l/s 2832 l/s 2360 l/s 3304 l/s 3304 l/s 2360 l/s Closed 2360 l/s 2596 l/s 3540 l/s Off On On On On On Terminal unit damper fully open Off On Normal Operation 1) The minimum outdoor air damper shall remain open. 2) A three-mode DDC software fan discharge temperature controller shall position the cooling coil valve to maintain the supply air temperature set point. 3) A return air humidity transmitter shall provide an input to the software controller which shall 15000-263 HVAC Issued for Construction 1 June 2004 override the control of the chilled water valve on sensing a return air relative humidity above set point (50% RH adjustable). The controller shall modulate open the chilled water valve to maintain return air relative humidity set point. On sensing a decrease in return air humidity below 45% (adjustable), the program shall allow the chilled water valve to be controlled to maintain supply air temperature set point. j. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Heat Recovery Coil Control 1) The heat recovery coil shall be utilized as the first stage of heating. 2) Dehumidification Mode: During this mode, the heat recovery coil three-way valve shall modulate based on a DDC discharge temperature controller. A temperature transmitter located downstream of the coil shall provide an input to the software controller which shall position the three-way valve to maintain supply temperature set point. 3) When the dehumidification mode is not active, a DDC software program shall monitor the space temperature, space temperature set point, and output command to each VAV box reheat coil. A DDC reset program shall monitor each reheat coil controller, its temperature set point and each space temperature transmitter. The program shall reset upwards the supply temperature set point one degree every 30 minutes (adjustable) if all electric reheat coils are in operation. The discharge temperature program shall first modulate close the cooling coil (when dehumidification mode is not active) then modulate open the heat recovery coil control valve. The controller shall continue to reset the air conditioning unit’s supply air temperature set point until a reheat coil is deenergized or any space temperature rises above set point with its reheat coil deenergized, at which point the controller shall reset downwards the supply temperature set point at the same rate as described above to satisfy the space temperature which requires the greatest cooling load. 15000-264 HVAC Issued for Construction 1 June 2004 k. Normal Operation 1) The minimum outdoor air damper shall remain open. 2) A three-mode DDC software fan discharge temperature controller shall position the cooling coil valve to maintain the supply air temperature set point. 3) A return air humidity transmitter shall provide an input to the software controller which shall override the control of the chilled water valve on sensing a return air relative humidity above set point (50% RH adjustable). The controller shall modulate open the chilled water valve to maintain return air relative humidity set point. On sensing a decrease in return air humidity below 45% (adjustable), the program shall allow the chilled water valve to be controlled to maintain supply air temperature set point. l. Supply and Return Flow Control: A software based DDC flow control program shall receive input signals from airflow measuring stations installed in the inlet of each supply and return fan, and totalize, linearize and scale them. The flow control program shall modulate the respective fan’s variable frequency drive to maintain airflow set point based on the matrix listed above. The operator shall be able to manually override the flow control program and manually control each supply and return fan. The software bias shall be suppressed during the smoke control override mode of operation. m. Electric Duct Heaters 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Each electric duct heater shall controlled via an independent DDC three-mode software controller which shall monitor the space temperature via a temperature transmitter and modulate the SCR controlled heating coils to maintain space temperature set point. Space temperature transmitter shall be nonindicating type with no local adjustment. There shall be a temperature transmitter and software controller for each reheat coil. Each heater shall be provided with an airflow switch which shall disable operation of the heater on a loss of air flow. 15000-265 HVAC Issued for Construction 1 June 2004 2) There shall be a temperature transmitter and software controller for each reheat coil. n. High Discharge Pressure Switches and Low Suction Pressure Switches: Pressure differential switches installed in the discharge of each supply and return fan, which sense discharge pressure, shall stop the fan and transmit an alarm to the network computer by means of a digital input to the system DDC controller, if the pressure set point of the switch is exceeded. A separate pressure switch installed in the inlet of each supply and return fans shall also stop the fan and transmit the alarm if fan suction pressure is below its set point. The fan shutdown shall be operative whether the starter H-O-A switch is in the "Auto" or "Hand" position. o. Minimum Outdoor Air Flow Quantity Control: Air flow measuring stations installed upstream of the minimum outside air dampers of each air conditioning system shall measure minimum air flow. A DDC software program shall position the minimum outdoor air damper as required to maintain airflow set point based on the air conditioning unit’s operating mode. Refer to matrix above. Should outside air flow be below set point, the return air damper shall be modulated closed until the minimum outside air flow is at set point. On an increase of outside air above set point, the return air damper shall be modulated open to achieve set point. The minimum outside airflow rates shall be transmitted, on a real time basis, to the DDC system for monitoring and trending. The software controller shall contain a software minimum position for the return air damper. p. Indoor Air Quality Control: A combination CO2/VOC transmitter shall be installed in the main return air duct of each air conditioning system. In addition, a CO2/VOC transmitter shall be installed downstream of supply air filter on each air conditioning system. The output of the CO2/VOC shall be monitored by the DDC system and compared to their high limit setting. Should either measurement exceed its high limit setting, an alarm shall be generated at the network computer, alerting the operator of the alarmed condition. In addition, a DDC controller shall proportionally control each individual fresh air damper from fully closed to fully open (with user-defined minimum and maximum software limits) to satisfy the CO2/VOC set point. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-266 HVAC Issued for Construction 1 June 2004 q. 7. Purge Outdoor Air and Exhaust Air Dampers 1) Dampers shall be operator selectable only. The dampers shall provide two-position (full open or full closed) operation, positioned via the network computer and the smoke control panel. 2) The purge outdoor air and exhaust air dampers shall be utilized to provide a fresh air purge of the space when the outdoor air conditions permit their use. The operator shall manually open the purge dampers via the network computer and start the air conditioning system. During this mode, the main return air damper to the air conditioning system shall be closed to provide 100% outdoor air and exhaust air to the space. 3) During smoke exhaust or normal mode of operation of the space, the dampers shall close. r. Smoke Control: On activation of a life safety alarm with the Restaurant or Atrium, the air conditioning unit supply and return fans shall stop and remain off. Dedicated smoke exhaust fans serving the Atrium shall automatically start and their associated outdoor air makeup damper shall open. The Restaurant is exhausted via the Atrium smoke exhaust system. s. Kitchen Make-Up Air: The Kitchen shall be provided with make-up air via a supply air duct with an isolation damper. When the Kitchen hood exhaust fan is in operation, the isolation damper shall open and the fan shall operate at full speed. If the air conditioning system is off, when the Kitchen hood fan is started, the DDC system shall automatically start the air conditioning system, operate the fan system at full speed and open the isolation damper. Education Wing Air Conditioning System and Associated Return Fan a. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Each air conditioning system is a variable air volume system which operates in conjunction with a variable volume return fan. There shall be two (2) headered air conditioning systems to serve the Basement, 1st, 2nd and 3rd Floors. The supply and return air fans shall be provided with variable frequency drives. The systems shall be controlled by a direct digital control system (DDC) with electronic sensing of system parameters, and electric actuation of control valves and dampers. 15000-267 HVAC Issued for Construction 1 June 2004 b. When the fans are not in operation, the minimum outdoor air, maximum outdoor air purge, maximum exhaust air purge, return air, supply and return floor/area isolation (fire/smoke dampers) and fan discharge dampers shall be closed. No control signal shall be transmitted to the variable frequency drive process follower speed controller. The normally closed chilled water coil valve shall be closed. The heat recovery coil valve shall be closed and its associated pumps shall be off. c. When fan start is initiated, the temperature control system shall be in operation, and a software time delay shall inhibit supply fan start until the system return air damper is open. Fans shall start and run at minimum speed required to maintain rotation, but not less than 6 Hz. The start of each supply fan shall be time delayed to avoid simultaneous starting of fans on the same system. The supply fan and return discharge dampers shall open after a time delay to enable the fan to reach minimum speed. After the fans are running, and the discharge dampers are open, the software static pressure controller shall slowly ramp up the speed of all fans to satisfy system static pressure demand. d. The Engineer shall start or stop of any fan from the network computer or the direct digital field control unit. Fans shall be started and run continuously. A DDC software time program shall determine the occupied and unoccupied mode via preprogrammed time settings established by the operating engineer. During the occupied mode, the minimum outdoor air damper shall be open. During the unoccupied mode, the minimum outdoor air damper shall be closed. e. On a command to stop a fan, the fan shall ramp down to its minimum speed and the fans shall stop in the reverse order of starting. The fan discharge damper shall close slowly and shall not be fully closed until fan speed has decreased to approximately 10%. The dampers shall close. f. Normal Operation 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC The minimum outdoor air damper shall remain open. 15000-268 HVAC Issued for Construction 1 June 2004 g. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 2) A three-mode DDC software fan discharge temperature controller shall position the cooling coil valve to maintain the supply air temperature set point. 3) A return air humidity transmitter shall provide an input to the software controller which shall override the control of the chilled water valve on sensing a return air relative humidity above set point (50% RH adjustable). The controller shall modulate open the chilled water valve to maintain return air relative humidity set point. On sensing a decrease in return air humidity below 45% (adjustable), the program shall allow the chilled water valve to be controlled to maintain supply air temperature set point. 4) During occupied hours, the discharge air temperature set point shall be set for 55ºF. (adjustable). 5) During the night and unoccupied times, a DDC software program shall reset the set point of the supply air temperature from 55ºF. to 64ºF., as return air temperature drops from 75ºF. to 72ºF. Heat Recovery Coil Control 1) The heat recovery coil shall be utilized as the first stage of heating. 2) Dehumidification Mode: During this mode, the heat recovery coil three-way valve shall modulate based on a DDC discharge temperature controller. A temperature transmitter located downstream of the coil shall provide an input to the software controller which shall position the three-way valve to maintain supply temperature set point. 3) When the dehumidification mode is not active, a DDC software program shall monitor the space temperature, space temperature set point, and output command to each VAV box reheat coil. A DDC reset program shall monitor each reheat coil controller, its temperature set point and each space temperature transmitter. The program shall reset upwards the supply temperature set point one degree every 30 minutes (adjustable) if 15000-269 HVAC Issued for Construction 1 June 2004 all electric reheat coils are in operation. The discharge temperature program shall first modulate close the cooling coil (when dehumidification mode is not active) then modulate open the heat recovery coil control valve. The controller shall continue to reset the air conditioning unit’s supply air temperature set point until a reheat coil is deenergized or any space temperature rises above set point with its reheat coil deenergized, at which point the controller shall reset downwards the supply temperature set point at the same rate as described above to satisfy the space temperature which requires the greatest cooling load. h. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Static Pressure Control 1) A reverse-acting 2-mode (proportional plus integral) DDC software controller shall control the supply fan speed, based upon the input from a static pressure transmitter located at the end of each duct riser served by the air conditioning unit. Each transmitter shall provide a signal to a low signal selector. The output of the signal selector shall be the input to the controller. 2) The output of the software controller shall be the input to the speed controller on the supply fans. As duct static pressure decreases, the controller output shall increase, to increase fan speed. On an increase in duct static pressure, the output of the controller shall decrease, to decrease fan speed. A software auto/manual switch function shall enable the operator to override the output of the static pressure controller and adjust fan speed from the network computer or the DDC controller. When multiple supply fans of a headered system are in operation, the controller shall operate the fan speeds in parallel. 3) A static pressure transmitter in the common supply fan discharge duct shall provide a signal proportional to fan discharge static pressure to a software based 2-mode pressure controller with reverse action, acting as a high limit. If fan discharge static pressure exceeds its set point, the high limit controller shall, through a software low selector, override the output of the 15000-270 HVAC Issued for Construction 1 June 2004 system static pressure controller to proportionally reduce the speed of each supply fan to maintain fan discharge pressure high limit set point. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 4) Static pressure controls shall control system operation during all cycles of operation, including smoke control mode. 5) During system start-up, the static pressure control algorithm, integral control mode shall be suppressed until the control point is within the proportional band of the controller to avoid reset wind-up. 6) Flow Control: A software based DDC flow control program shall receive input signals from airflow measuring stations installed in the inlet of each supply and return fan, and totalize, linearize and scale them. The flow control program shall match the return fan with the supply fans and maintain the volumetric balance between return and supply airflow by varying return fan speed in parallel to maintain a constant differential between supply and return airflow. A software bias shall be provided to compensate the return flow for a constant outside air minimum at all operating loads. The operator shall be able to manually override the flow control program and manually control each supply and return fan. The software bias shall be suppressed during the smoke control override mode of operation. A software program shall notify the operator via the network computer to start an additional fan system when a system is operating at 95% of its design airflow. When multiple headered systems are in operation, the program shall notify the operator to stop a fan system when a system is operating at 40% of its design airflow. 7) High Discharge Pressure Switches and Low Suction Pressure Switches: Pressure differential switches installed in the discharge of each supply and return fan, which sense discharge pressure, shall stop the fan and transmit an alarm to the network computer by means of a digital input to the system DDC controller, if the 15000-271 HVAC Issued for Construction 1 June 2004 pressure set point of the switch is exceeded. A separate pressure switch installed in the inlet of each supply and return fans shall also stop the fan and transmit the alarm if fan suction pressure is below its set point. The fan shutdown shall be operative whether the starter H-O-A switch is in the "Auto" or "Hand" position. 8) Minimum Outdoor Air Flow Quantity Control: Air flow measuring stations installed upstream of the minimum outside air dampers of each air conditioning system shall measure minimum air flow. Should outside air flow be below set point, the return air damper shall be modulated closed until the minimum outside air flow is at set point. On an increase of outside air above set point, the return air damper shall be modulated open to achieve set point. The minimum outside airflow rates shall be transmitted, on a real time basis, to the DDC system for monitoring and trending. The software controller shall contain a software minimum position for the return air damper. 9) Indoor Air Quality Control: A combination CO2/VOC transmitter shall be installed in each return air duct of each floor served by the air conditioning systems (total of two transmitters per floor). In addition, a CO2/VOC transmitter shall be installed downstream of supply air filter on each air conditioning system. The output of the CO2/VOC shall be monitored by the DDC system and compared to their high limit setting. Should either measurement exceed its high limit setting, an alarm shall be generated at the network computer, alerting the operator of the alarmed condition. In addition, a DDC controller shall proportionally control each individual fresh air damper from fully closed to fully open (with user-defined minimum and maximum software limits) to satisfy the CO2/VOC set point. 10) Floor Isolation Dampers a) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Supply floor/area isolation dampers shall open when any supply fan serving the damper is started, and shall close 15000-272 HVAC Issued for Construction 1 June 2004 when the fans serving the damper are stopped. Return floor/area isolation dampers shall open when the return fan serving the damper is started and shall close when the fans are off. b) 11) 12) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Each floor damper shall be capable of being positioned from the network computer. Each floor shall contain two (2) damper groups. One group shall consist of all supply dampers and the other group shall consist of all exhaust dampers. A damper position established through the DDC control system shall be overridden by actuation of the override switches on the smoke control panel. Purge Outdoor Air and Exhaust Air Dampers a) Dampers shall be operator selectable only. The dampers shall provide twoposition (full open or full closed) operation, positioned via the network computer and the smoke control panel. b) The purge outdoor air and exhaust air dampers shall be utilized to provide a fresh air purge of the space when the outdoor air conditions permit their use. The operator shall manually open the purge dampers via the network computer and start the air conditioning system. During this mode, the main return air damper to the air conditioning system shall be closed to provide 100% outdoor air and exhaust air to the space. c) During smoke exhaust or normal mode of operation of the space, the dampers shall close. Smoke Control: On activation of a life safety alarm within the Education Wing, the air conditioning unit supply and return fans shall stop and remain off. Dedicated smoke exhaust fans serving the Education Wing shall be manually started and their associated outdoor air makeup damper shall open. 15000-273 HVAC Issued for Construction 1 June 2004 8. Basement Air Conditioning System and Associated Return Fan a. Each air conditioning system is a variable air volume system which operates in conjunction with a variable volume return fan. There shall be two (2) headered air conditioning systems to serve the Subbasement and Basement areas. The supply and return air fans shall be provided with variable frequency drives. The systems shall be controlled by a direct digital control system (DDC) with electronic sensing of system parameters, and electric actuation of control valves and dampers. b. When the fans are not in operation, the minimum outdoor air, maximum outdoor air purge, maximum exhaust air purge, return air, supply and return floor/area isolation (fire/smoke dampers) and fan discharge dampers shall be closed. No control signal shall be transmitted to the variable frequency drive process follower speed controller. The normally closed chilled water coil valve shall be closed c. When fan start is initiated, the temperature control system shall be in operation, and a software time delay shall inhibit supply fan start until the system return air damper is open. Fans shall start and run at minimum speed required to maintain rotation, but not less than 6 Hz. The start of each supply fan shall be time delayed to avoid simultaneous starting of fans on the same system. The supply fan and return discharge dampers shall open after a time delay to enable the fan to reach minimum speed. After the fans are running, and the discharge dampers are open, the software static pressure controller shall slowly ramp up the speed of all fans to satisfy system static pressure demand. d. The Engineer shall start or stop of any fan from the network computer or the direct digital field control unit. Fans shall be started by an operator at the network computer and run continuously. A DDC software time program shall determine the occupied and unoccupied mode via preprogrammed time settings established by the operating engineer. During the occupied mode, the minimum outdoor air damper shall be open. During the unoccupied mode, the minimum outdoor air damper shall be closed. e. On a command to stop a fan, the fan shall ramp down to its minimum speed and the fans shall stop in the reverse order of starting. The fan discharge damper shall close Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-274 HVAC Issued for Construction 1 June 2004 slowly and shall not be fully closed until fan speed has decreased to approximately 10%. The dampers shall close. f. g. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Normal Operation 1) The minimum outdoor air damper shall remain open. 2) A three-mode DDC software fan discharge temperature controller shall position the cooling coil valve to maintain the supply air temperature set point. 3) A return air humidity transmitter shall provide an input to the software controller which shall override the control of the chilled water valve on sensing a return air relative humidity above set point (50% RH adjustable). The controller shall modulate open the chilled water valve to maintain return air relative humidity set point. On sensing a decrease in return air humidity below 45% (adjustable), the program shall allow the chilled water valve to be controlled to maintain supply air temperature set point. 4) During occupied hours, the discharge air temperature set point shall be set for 55ºF. (adjustable). 5) During the night and unoccupied times, a DDC software program shall reset the set point of the supply air temperature from 55ºF. to 64ºF., as return air temperature drops from 75ºF. to 72ºF. Heat Recovery Coil Control 1) The heat recovery coil shall be utilized as the first stage of heating. 2) Dehumidification Mode: During this mode, the heat recovery coil three-way valve shall modulate based on a DDC discharge temperature controller. A temperature transmitter located downstream of the coil shall provide an input to the software controller which shall position the three-way valve to maintain supply temperature set point. 15000-275 HVAC Issued for Construction 1 June 2004 3) h. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC When the dehumidification mode is not active, a DDC software program shall monitor the space temperature, space temperature set point, and output command to each VAV box reheat coil. A DDC reset program shall monitor each reheat coil controller, its temperature set point and each space temperature transmitter. The program shall reset upwards the supply temperature set point one degree every 30 minutes (adjustable) if all electric reheat coils are in operation. The discharge temperature program shall first modulate close the cooling coil (when dehumidification mode is not active) then modulate open the heat recovery coil control valve. The controller shall continue to reset the air conditioning unit’s supply air temperature set point until a reheat coil is deenergized or any space temperature rises above set point with its reheat coil deenergized, at which point the controller shall reset downwards the supply temperature set point at the same rate as described above to satisfy the space temperature which requires the greatest cooling load. Static Pressure Control 1) A reverse-acting 2-mode (proportional plus integral) DDC software controller shall control the supply fan speed, based upon the input from a static pressure transmitter located at the end of each duct riser served by the air conditioning unit. Each transmitter shall provide a signal to a low signal selector. The output of the signal selector shall be the input to the controller. 2) The output of the software controller shall be the input to the speed controller on the supply fans. As duct static pressure decreases, the controller output shall increase, to increase fan speed. On an increase in duct static pressure, the output of the controller shall decrease, to decrease fan speed. A software auto/manual switch function shall enable the operator to override the output of the static pressure controller and adjust fan speed from the network computer or the DDC controller. When multiple supply fans of a headered system are in operation, the controller shall operate the fan speeds in parallel. 15000-276 HVAC Issued for Construction 1 June 2004 3) A static pressure transmitter in the common supply fan discharge duct shall provide a signal proportional to fan discharge static pressure to a software based 2-mode pressure controller with reverse action, acting as a high limit. If fan discharge static pressure exceeds its set point, the high limit controller shall, through a software low selector, override the output of the system static pressure controller to proportionally reduce the speed of each supply fan to maintain fan discharge pressure high limit set point. 4) Static pressure controls shall control system operation during all cycles of operation, including smoke control mode. 5) During system start-up, the static pressure control algorithm, integral control mode shall be suppressed until the control point is within the proportional band of the controller to avoid reset wind-up. i. Flow Control: A software based DDC flow control program shall receive input signals from airflow measuring stations installed in the inlet of each supply and return fan, and totalize, linearize and scale them. The flow control program shall match the return fan with the supply fans and maintain the volumetric balance between return and supply airflow by varying return fan speed in parallel to maintain a constant differential between supply and return airflow. A software bias shall be provided to compensate the return flow for a constant outside air minimum at all operating loads. The operator shall be able to manually override the flow control program and manually control each supply and return fan. The software bias shall be suppressed during the smoke control override mode of operation. A software program shall notify the operator via the network computer to start an additional fan system when a system is operating at 95% of its design airflow. When multiple headered systems are in operation, the program shall notify the operator to stop a fan system when a system is operating at 40% of its design airflow. j. High Discharge Pressure Switches and Low Suction Pressure Switches: Pressure differential switches installed in the discharge of each supply and return fan, Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-277 HVAC Issued for Construction 1 June 2004 which sense discharge pressure, shall stop the fan and transmit an alarm to the network computer by means of a digital input to the system DDC controller, if the pressure set point of the switch is exceeded. A separate pressure switch installed in the inlet of each supply and return fans shall also stop the fan and transmit the alarm if fan suction pressure is below its set point. The fan shutdown shall be operative whether the starter H-O-A switch is in the "Auto" or "Hand" position. k. Minimum Outdoor Air Flow Quantity Control: Air flow measuring stations installed upstream of the minimum outside air dampers of each air conditioning system shall measure minimum air flow. Should outside air flow be below set point, the return air damper shall be modulated closed until the minimum outside air flow is at set point. On an increase of outside air above set point, the return air damper shall be modulated open to achieve set point. The minimum outside airflow rates shall be transmitted, on a real time basis, to the DDC system for monitoring and trending. The software controller shall contain a software minimum position for the return air damper. l. Indoor Air Quality Control: A combination CO2/VOC transmitter shall be installed in each return air duct of each floor served by the air conditioning systems (total of two transmitters per floor). In addition, a CO2/VOC transmitter shall be installed downstream of supply air filter on each air conditioning system. The output of the CO2/VOC shall be monitored by the DDC system and compared to their high limit setting. Should either measurement exceed its high limit setting, an alarm shall be generated at the network computer, alerting the operator of the alarmed condition. In addition, a DDC controller shall proportionally control each individual fresh air damper from fully closed to fully open (with user-defined minimum and maximum software limits) to satisfy the CO2/VOC set point. m. Floor Isolation Dampers 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Supply floor/area isolation dampers shall open when any supply fan serving the damper is started, and shall close when the fans serving the damper are stopped. Return floor/area isolation dampers shall open when the return fan serving the damper is started and shall close when the fans are off. 15000-278 HVAC Issued for Construction 1 June 2004 n. 9. 2) Each floor damper shall be capable of being positioned from the network computer. Each floor shall contain two (2) damper groups. One group shall consist of all supply dampers and the other group shall consist of all exhaust dampers. A damper position established through the DDC control system shall be overridden by actuation of the override switches on the smoke control panel. 3) Purge Outdoor Air and Exhaust Air Dampers a) Dampers shall be operator selectable only. The dampers shall provide twoposition (full open or full closed) operation, positioned via the network computer and the smoke control panel. b) The purge outdoor air and exhaust air dampers shall be utilized to provide a fresh air purge of the space when the outdoor air conditions permit their use. The operator shall manually open the purge dampers via the network computer and start the air conditioning system. During this mode, the main return air damper to the air conditioning system shall be closed to provide 100% outdoor air and exhaust air to the space. c) During smoke exhaust or normal mode of operation of the space, the dampers shall close. Smoke Control: On activation of a life safety alarm within the Education Wing, the air conditioning unit supply and return fans shall stop and remain off. Dedicated smoke exhaust fans serving the Education Wing shall be manually started and their associated outdoor air makeup damper shall open. Toilet Exhaust Fans a. When an exhaust fan is off, its discharge damper shall be closed. b. When the exhaust fan is started, the discharge damper and all floor/area isolation (fire/smoke) dampers shall be open. Fan shall be started via a software time program. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-279 HVAC Issued for Construction 1 June 2004 c. 10. 11. 12. Fan status shall be displayed at the network computer via current sensing relays. Mechanical Equipment Room Air Conditioning Units (Gallery, Basement, and 3rd Floor Education Wing) a. Air conditioning unit is a chilled water-cooled unit. Each Mechanical Equipment Room shall contain one (1) air conditioning unit. b. The unit shall be started locally or manually from the network computer, and shall run continuously. c. A wall-mounted space temperature transmitter shall provide an input to a DDC two-mode software controller, which shall modulate the chilled water valve to maintain space temperature set point. Chilled water valve shall be furnished and installed by this Subcontractor. d. A current-sensing relay for each unit, furnished and installed by this Section, shall be wired to the DDC system for remote monitoring. Basement and Mechanical Equipment Room Smoke Exhaust Fans a. Fans shall be started via the DDC or smoke control panel. b. When the fan is off, its associated dampers shall be closed. c. When the fan starts, its dampers shall open. d. A differential pressure switch, furnished and installed by this Section, shall annunciate fan run status at the DDC system and the smoke control panel. Refrigeration Room Break-Glass Switches: Two (2) new dual action (i.e., break glass, pull lever) break glass switches shall be located outside each exit of the chiller plant. One switch shall start the exhaust fan and the other shall stop the chillers. The break-glass switches shall be hard wired into the chillers and exhaust fan starter circuits. Break-glass switches to start fans shall be wired in parallel. Switches to stop chillers shall be wired in series. Break-glass switches and associated wiring and conduit shall be furnished and installed under this Section of the Specifications. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-280 HVAC Issued for Construction 1 June 2004 13. Refrigerant Leak Detection a. b. 14. A long-term monitoring refrigerant leak detection system to detect both Groups A1 and B1 refrigerant leaks shall be provided and installed by this Subcontractor. The leak detection system shall be interlocked with a refrigeration plant mechanical equipment room exhaust system to start the system upon detection of a refrigerant leak and shall transmit an alarm to the DDC system. The refrigeration machine shall be monitored by two (2) sensors located on either side of each machine and mounted at a height of 450 mm. above the floor. The system shall utilize a multichannel scanner to monitor each individual location. Each monitor shall have a method for setting the zero reference point. The following alarm relay outputs shall be monitored at the DDC system network computer. 1) TVL (Threshold Limit Value). At this level, the refrigerant purge ventilation system is started. 2) STEL (Short-Term Exposure Limit) of 3 times the TVL. 3) EEL (Emergency Exposure Limit). 4) Failure Relay (Detect monitor system failure). In addition, the system shall have a remote reset switch that shall allow the alarm condition to be reset from a switch located outside the refrigeration plant. The alarm shall only be capable of reset if the alarm condition is cleared. Smoke Exhaust Fans Serving Atrium, Gallery, Basement and Education Wing a. When the fan is not in operation, the fan discharge and/or intake damper shall be closed. b. Fan shall be started manually from the smoke control panel or network computer. c. In addition, fan shall be capable of being started locally (for testing purposes). d. Upon activation of the fan, the dampers shall open. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-281 HVAC Issued for Construction 1 June 2004 15. 16. e. If the fan fails to start, an alarm, actuated by a differential pressure switch, shall be transmitted to the smoke control panel and the network computer. f. Atrium Smoke Exhaust Fans 1) Activation of a fire alarm within the Atrium or the Restaurant shall automatically stop the air conditioning unit supply and return fans serving these areas and start the Atrium smoke exhaust fan and open the respective intake and discharge dampers. 2) Each exhaust fan shall be provided with a variable frequency drive which shall operate at a constant speed determined via coordination with the balancer. Kitchen Exhaust Fans a. Each exhaust fan shall be started locally via a wallmounted switch furnished and installed and wired by this Section. b. Exhaust fan status shall be indicated at the network computer through current sensing relays. c. Hood water wash sequence shall be coordinated with Kitchen hood manufacturer. d. Activation of the hood fire suppression shall automatically start the Kitchen exhaust fan if off, or cause it to continue to run if running. e. Activation of the high temperature detector in the hood collar shall stop the exhaust fan. f. Interwiring between the hood water wash, fire suppression system and high temperature detector and the exhaust fan shall be by this Subcontractor. Truck Dock and Garage Exhaust Fans a. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC The exhaust fans shall be started and stopped via interface to a carbon monoxide detection system. Each truck dock and garage exhaust fan shall be a two-speed fan. Makeup air fans serving the truck dock shall be constant speed fans. Each fan’s speed shall be 15000-282 HVAC Issued for Construction 1 June 2004 monitored at the DDC system and smoke control panel via differential pressure switches. b. Carbon Monoxide System 1) General Requirements a) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC The work covered by this Subcontractor includes the installation of a carbon monoxide (CO) detection system, as specified herein. The major items of work to be included are: (1) Furnishing and installing CO detection system and accessories. (2) Furnishing and installing all necessary sample tubing and terminal filters. (3) Furnishing and installing all necessary electrical service to the CO detection system and required interconnections to alert status devices and control fans. b) The carbon monoxide detection system control housings are to be located by this Subcontractor in the building areas as indicated on the plans, or as directed. Sample tubing is to be run from the control housing to the various terminal points as indicated on the plans. c) Sensors shall be installed based on manufacturer's recommendation. d) Any deviation from these specifications, no matter how minor, shall be submitted for approval in writing, with sufficient data outlining the deviation, at least 15 days prior to time of bidding. If the proposed changes are not acceptable, then this Subcontractor shall be required to furnish the equipment and system as specified with no substitution. 15000-283 HVAC Issued for Construction 1 June 2004 No consideration shall be given to substitution after award of contract. e) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Method of Analysis (1) Measurement of carbon monoxide shall be by means of electrochemical cell or catalytic oxidation principle. Semiconductor solid-state sensors shall not be employed. (2) Detection cell design must be such that no humidifier, with inherent maintenance, is required. (3) Design must be such that calibration may be accomplished solely by one man direct at carbon monoxide detection system console. Individual type sensors shall not be employed. (4) Detection cell design shall be such that it is nonsensitive to nominal variations in sample flow rate. (5) The CO detection system must have a full scale range of 0 to 100 parts per million CO in air. Ranges higher than 100 ppm not acceptable. (6) The CO detection system shall be standard product, and all components shall have proven successful operation in similar installation for a period of at least ten years. (7) Detection cell is to be selective to CO, with average lifespan of 18-24 months before need for replacement. 15000-284 HVAC Issued for Construction 1 June 2004 (8) f) Control Modules: The CO control consoles shall be wall mounted or freestanding type, and each module section shall consist of control unit assembly section, detector assembly section, and sample handling and conditioning assembly section. Full hinged locking doors are to be provided. Front access sections are to be provided. Each control module section shall contain detection cell assembly, sample flow control, equipment to sequentially sample from each of the monitor points, and relay circuits, as required. 30 ampere rated field interconnect block construction is to be supplied in each control module section. g) Sample Flow System (1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Accuracy shall be ±1% of full scale reading. Repeatability shall be ±1% of full scale reading. 15000-285 The following describes operation, and constituent parts of each sample flow system, which must be adhered to without exceptions: (a) Replacement dust filters shall be employed at inlet of each sample tube run. (b) Sample shall be drawn at a rapid rate through tubing lines to minimize log time. During analysis of a given point, flow must be maintained through succeeding line. Sample flow through the analysis cell must be under positive pressure. HVAC Issued for Construction 1 June 2004 h) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC (c) A cell bypass pump is to be supplied. "No Sample Flow" indication and alarm must be supplied to indicate lack of sample flow. (d) Bypass control rotometer and sample rotometer must also be supplied to permit ease of observation and control of sample flow. (e) Trouble lamp circuitry is to be provided on control module, to illuminate in the event of no sample flow. (f) Both a prime pump and a cell bypass pump must be supplied on each sample flow system. Prime pump must be vacuum/ pressure type designed to operate in the 0-310 kPa range and rated for at least 400 day maintenance-free operation. Sample Tubing Lines (1) This Subcontractor shall furnish and install all sample tube lines from sample pick-up points to the identified bulkheads on the CO control modules, using 9.5 mm o.d. Type L hard drawn seamless copper tube with solder fittings. Compression type bulkhead unions shall be provided on the CO detection system control modules. (2) All tubing shall be run along ceiling in such a manner as not 15000-286 HVAC Issued for Construction 1 June 2004 to be exposed to abuse. Attach all tubing securely to building structure using copper plated clips and approved anchors. (3) i) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC All tubing shall be cleaned thoroughly before installation and then blown out after installation to ensure that no foreign matter remains in system. Test tube as required during work progress to ensure against leaks. Operation, Alarms and Fan Controls (1) Each CO analyzer control module shall operate electrically independent of any other, and the electrical shutdown of one particular control module shall not affect the operation of another. (2) The CO analyzer system shall be designed to operate from 220 volt a.c., 50 Hz, single phase power supply. (3) Each sample point on each control module shall have an identifiable illuminated digit readout, said identification being synchronized with the automatic sample programmer. (4) Malfunction indicator shall be provided on each control module, and are to illuminate on "Lack of Sample Flow", "Programmer Stop", or "Low Cell Temperature". 15000-287 HVAC Issued for Construction 1 June 2004 (5) All electrical terminations within CO control module are to be at 30 ampere rated identified blocks to facilitate field interconnects. (6) Range on each control module must be 0-100 ppm CO in air, with threshold sensitivity less than 1 ppm CO in air. Accuracy to be ±1% of full scale reading. (7) Amber “CO Warning Concentration” lamps, associated with each sample point shall be provided on the control modules. (8) Red "CO Alarm Concentration" lamp shall be provided on the control modules. (9) Lamp test circuitry shall be provided to permit illuminated check of all function lamps. (10) Provide a 4-20 mA output indicating CO concentration per floor level which shall be monitored via the DDC system. The DDC system shall utilize this signal to modulate the garage and truck dock supply and exhaust fan speeds. j) The following zone with associated fan systems shall be monitored: Each Parking area and truck dock. k) Calibration Equipment (1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-288 A manually operated calibration valve shall be provided in each detector module, to permit introduction of calibration gas to the CO analyzer detection cell to permit checking and adjusting span. HVAC Issued for Construction 1 June 2004 c. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC (2) A cylinder containing a certified mixture for 100 ppm CO in air range shall be provided complete with a regulator gauge set and mounted integral to the console. If required, a cylinder of pure nitrogen for zero adjustment shall be provided with regulator. (3) Calibration design must be such that calibration may be accomplished solely by one man at the carbon monoxide detection system console. (4) Startup and Instruction Service: Following installation of the CO detection system by this Subcontractor, the manufacturer shall make available services of a factory engineer to check out the system, and instruct the Engineer's personnel on operation and maintenance of the system. (5) Guarantee: The CO detection system control console and accessory equipment (excluding all normally expendable items) shall be guaranteed against defective materials and workmanship for a period of one year operation. Description of Operation - Parking Levels 1) When the fans are off, the fan discharge and intake dampers shall be closed. 2) When the exhaust fan is started through the DDC system, the fan discharge and intake dampers shall open, and their associated intake dampers shall open. The DDC system shall be interfaced to the carbon monoxide system and shall start the fan and sequence fan speeds based on carbon monoxide concentration level. 15000-289 HVAC Issued for Construction 1 June 2004 3) d. 17. A high temperature detector in the exhaust fan discharge shall shut down the fan and alarm at the network computer. The high temperature shutdown shall be implemented through software. Description of Operation - Truck Dock 1) When the truck dock exhaust fan is off, its associated dampers shall be closed. Fans E-B17 and E-B-10 shall be off and their respective dampers shall close. When a fan starts, its dampers shall open. 2) The truck dock exhaust fan shall operate based on a DDC software program, the carbon monoxide level of the truck dock as well as the smoke control system. 3) The smoke control system shall override all operations of the truck dock fan and operate the fan at full speed. 4) When the fan is started via software time program, the fan shall operate at low speed and E-B-17 shall start. 5) On sensing a carbon monoxide concentration level above set point, the DDC system shall operate the truck dock fan at high speed, start EB-17, start E-B-10 and stop the exhaust fan serving MER B1-04. 6) Each fan’s run status (each speed) shall be monitored at the DDC system via currentsensing relays. FM-200 Systems Serving Switchgear Room, High Voltage Room, Low Voltage Room, Rare Books, Transformer Rooms, Main Telephone Equipment Room, Vault: Activation of a FM200 system cross-zone detector shall close the dampers and stop the respective air conditioning units as per the control matrix indicated on the mechanical drawings. Refer to fire protection drawings and specifications for panel quantity and location. The FM-200 panels shall be furnished and installed by the Fire Protection Subcontractor. The wiring between the panel and the dampers, air conditioning units, and exhaust fans shall be by this Subcontractor. Wiring between the panel and electrical Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-290 HVAC Issued for Construction 1 June 2004 equipment required for shutdown shall be furnished and installed by the Electrical Subcontractor. 18. 19. FM-200 Exhaust Fans a. When the exhaust fan is off, its normally closed discharge damper and respective intake dampers shall be closed. b. When the fan is called to start, the dampers shall open. A time delay relay in the FM-200 exhaust fan starter shall prevent fan operation until the dampers are open. The time delay relay shall be furnished and installed by this Subcontractor. c. Fan shall be started and stopped from the respective FM200 exhaust panel. Interlock wiring from the panel to the FM-200 exhaust fan starter and the damper shall be by this Section of the Specifications. Emergency and Normal Power Restart Program a. The DDC system shall contain an automatic restart program for the equipment controlled via the DDC system. The program shall automatically start equipment that was operating prior to a loss of normal power. b. The DDC system shall monitor each automatic transfer switch for the following points: 1) 2) Load On Emergency. Load On Normal. c. On a loss of power, the equipment shall stop and the DDC system shall provide the normal shutdown sequence. d. When power is restored (normal or emergency), the DDC units serving equipment connected to respective transfer switches shall monitor the respective automatic transfer switches to determine if the switch in operating on emergency or normal power. 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC If the switch is operating in the normal power mode (i.e., “Load on Normal”) or emergency power mode (i.e., “Load on Emergency”), the DDC units shall initiate a restart program, which shall restart equipment, which was previously 15000-291 HVAC Issued for Construction 1 June 2004 operating prior to a power loss subject to existing software programs. 2) 20. 21. When equipment is operating under emergency power, it shall continue to be controlled as operating under normal power as described within the description of operations. The equipment shall operate subject to all operating and life safety devices (i.e., pressure switches, low temperature thermostats and smoke detectors, etc.). e. If at any time the DDC system is operating equipment which is currently connected to emergency power and the transfer switch transfers from emergency to normal, the DDC system shall restart equipment which was previously operating as well as equipment which should be operating subject to software time programs. f. All equipment restarting shall be subject to software time delays to prohibit simultaneous starting of equipment. General Kitchen Exhaust Fans a. When an exhaust fan is off, its discharge damper and floor/area isolation (fire/smoke) dampers shall be closed. b. When the exhaust fan is started locally through the network computer, the dampers shall open. Fan shall run continuously. c. Fan status shall be displayed at the network computer via current sending relays. Emergency Generator Exhaust Fan, Fuel Oil Tank and Pump Room Exhaust Fan a. When an exhaust fan is off, its discharge damper and floor/area isolation (fire/smoke) dampers shall be closed. b. When the exhaust fan is started locally through the network computer, the dampers shall open. c. Fan status shall be displayed at the network computer via current sending relays. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-292 HVAC Issued for Construction 1 June 2004 22. Refrigeration Room, Emergency Generator Room, Switchgear Room, Telephone Equipment Room, Mechanical Equipment Room, Engineer’s Office, High Voltage Room, Low Voltage Room, Transformer Room, and Elevator Machine Room Air Conditioning Units a. Packaged air conditioning units shall be chilled water cooled air conditioning units. Units shall be either ceiling hung or floor standing. b. A wall mounted temperature transmitter shall provide an input to a DDC software controller which shall provide a output to modulate the chilled water valve to maintain space temperature set point. Chilled water valve shall be furnished by this section and installed by the mechanical Subcontractor. c. A space temperature transmitter shall annunciate a high temperature alarm at the network computer on sensing a temperature above set point. d. Fan status shall be indicated at the network computer via current sensing relays. An operator at the network computer shall be capable of starting and stopping the unit remotely. e. A leak detector furnished, installed and wired by this Section shall annunciate an alarm at the DDC system network computer. 23. Emergency Generator Ventilation and Exhaust: When an engine is started locally, the respective engine-driven automatic damper, an engine-mounted and driven fan discharge shall open and all automatic intake dampers shall open. The dampers shall close when engine is stopped. Automatic dampers shall be of the normally open type. Wiring from the contact in the engine control panel start circuit to the dampers shall be provided by this Subcontractor. Dampers shall be rated for continuous duty. Dampers shall be normally open type, spring return open. 24. Variable Air Volume Terminal Unit Controllers and Constant Volume Terminal Unit Controllers a. General 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC The DDC system Subcontractor shall ship for mounting and wiring to the terminal unit manufacturer the following items: 15000-293 HVAC Issued for Construction 1 June 2004 a) Microprocessor based pressure independent terminal unit controller. b) Enclosure terminations. c) Control transformer (if required). d) Primary air velocity transducer. e) Electric primary damper actuator. b. The DDC controller and its associated power supply, transducers, electric damper operator, etc., shall be neatly mounted within a separate 20 gauge sealed and gasketed galvanized sheet metal enclosure by this Subcontractor. The completed assembly shall be shipped by this Subcontractor to the terminal unit manufacturer for mounting directly to and supported from the terminal device it serves. All external electrical connections to the DDC controller within the box shall be terminated in two separate junction boxes (with removable covers), i.e., one for power and one for signal communications. All wiring and tubing shall be permanently labeled and color coded for ease of identification. No access to within the enclosure shall be required for installation, startup or operation of the terminal unit. c. The terminal unit manufacturer shall provide the terminal unit with fail-in-place damper. d. This Subcontractor shall field calibrate microprocessor controller and all field devices. e. This Subcontractor shall supply written instructions and drawings containing sufficient information to enable the terminal unit manufacturer to undertake the installation satisfactorily. This Subcontractor shall visit the terminal unit manufacturer’s facility shortly after the commencement of production for this Project to ensure that the terminal unit manufacturer’s installation and wiring procedures are satisfactory. The terminal unit manufacturer shall prepare a drawing of the wiring for the terminal unit controller and all associated instrumentation and final control elements based on the information provided by this Subcontractor. The terminal unit manufacturer and this Subcontractor shall both certify on the drawing that the drawing is correct and the drawing shall be submitted as a shop drawing for Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-294 the HVAC Issued for Construction 1 June 2004 review by the Mechanical Consulting Engineer. This Subcontractor shall visit the terminal unit manufacturer’s facility at the completion of the first production run for this Project and, prior to the shipping of any terminal unit to the project site, shall inspect the installation of the control devices. The terminal unit manufacturer shall not make any factory adjustments to the terminal unit controller or enter any data into the terminal unit controller in any way. All testing, entry of data and adjustments of any kind to the terminal unit controller shall be undertaken by this Subcontractor at the project site. f. This Subcontractor shall be responsible for shipping costs associated with the devices discussed above, the repair and/or replacement of all devices damaged during shipment and all instructions pertaining to mounting, wiring and tubing, including wiring diagrams. g. The control unit shall be capable of interfacing with a hand-held terminal unit, DDC panel and the network computer. The control unit shall accept a temperature signal from an electronic space sensor/transmitter. Room temperature, actual and calculated air flows and flow and temperature alarms shall be continuously transmitted to the network for access by the network computer or other DDC units. The accuracy of the air flow measurement shall be ±5%, within the temperature range of 10-32°F. The status of all control unit I/O points shall be available to the entire network or the network computer at any time. All alarms shall be automatically transmitted to the appropriate locations as required by the system programming. h. Control algorithms necessary to accomplish the stated sequence of operation shall be preprogrammed in the control unit and shall be ready for operation after application and unit address information is programmed into the controller. All control sequences shall be selectable from the network computer, DDC panel and/or hand-held terminal unit. The operator at the network computer shall be able to change temperature set points, change minimum and maximum primary air flow set point, display room temperature and display primary air flow. Control software shall be maintained in nonvolatile memory for reset after a power failure. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-295 HVAC Issued for Construction 1 June 2004 i. The hand-held terminal unit shall connect into the system via a jack connector at the room temperature sensor and at the terminal unit. It shall be capable of display of system variables, override control, enabling/disabling of resident control programs, and adjustment of control parameters. j. Connection of a hand-held terminal, or multiple handheld terminals, shall not interrupt nor interfere in any way with normal peer network operation, prevent alarms from being indicated, or preclude central initiated commands and system modification from the network computer. The hand-held terminal shall have its own rechargeable battery-supplied power. Battery supply shall be sufficient for 24 hours nominal usage before recharging. Low battery condition shall be visibly displayed. k. The unit controller shall have, as a minimum, the following I/O: 1) Space temperature (variable air volume units only). 2) Differential pressure (velocity pressure). 3) Damper control. 4) Heating coil application). control (as required per l. The control of each terminal unit shall be capable of complete stand-alone operation and shall not depend on information from any other element in the building, including other terminal units and network computer for primary control. Failure of any component shall not interrupt control of any other terminal unit controller. m. The DDC terminal unit control package shall be furnished complete with air velocity transducer, direct digital control unit and software, space temperature sensor, damper, damper actuator, and power transformer (if required). This Subcontractor shall mount and wire the space temperature sensor and provide communication wiring between each terminal unit and the network computer. Power wiring of constant and variable volume terminal units shall be furnished and installed by this Subcontractor. This Subcontractor shall also provide all required software interface for the Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-296 HVAC Issued for Construction 1 June 2004 network computer to monitor temperatures and air flows and adjust set points. The operator at the network computer shall be able to change temperature set point, change minimum and maximum velocity set point, display space temperature, actual air flow and duct velocity. Each terminal unit shall be addressable through the network computer. This Subcontractor shall field calibrate the air velocity sensor and DDC controller. n. Description of Operation 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Variable Volume Terminal Units a) Electric controlled terminals with failin-place dampers shall be controlled from a unit mounted direct digital control unit. b) A software interlock shall enable the terminal unit controller when the primary air fan serving the terminal unit starts. c) When the space temperature rises, as sensed by an electronic space temperature transmitter, the software controller shall modulate the terminal unit primary damper open. d) As the space temperature decreases, the terminal unit primary damper shall modulate closed. e) Each terminal unit's direct digital control unit shall be capable of remote reset of all set points and damper position automatically or manually through the network computer. f) Whenever the primary fan system serving the terminal unit is off, the terminal unit damper shall be positioned fully open. 15000-297 HVAC Issued for Construction 1 June 2004 2) 3) Variable Volume Terminal Units with Electric Reheat Coil a) Electric controlled terminals with failin-place dampers shall be controlled from a unit mounted direct digital control unit. b) A software interlock shall enable the terminal unit controller when the primary air fan serving the terminal unit starts. c) When the space temperature rises, as sensed by an electronic space temperature transmitter, the software controller shall modulate the terminal unit primary damper open. d) As the space temperature decreases, the terminal unit primary damper shall modulate closed. e) When space temperature continues to decrease, the output of the controller shall modulate the electric heating coil to maintain space temperature. f) Each terminal unit's direct digital control unit shall be capable of remote reset of all set points and damper position automatically or manually through the network computer. g) Whenever the primary fan system serving the terminal unit is off, the terminal unit damper shall be positioned fully open. Constant Volume Terminal Units a) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Electric controlled terminals with failin-place dampers shall be controlled from a unit mounted direct digital control unit. A pressure independent DDC software controller shall modulate the terminal unit damper to maintain supply air flow set point. 15000-298 HVAC Issued for Construction 1 June 2004 b) 4) o. 25. Each terminal unit's direct digital control unit shall be capable of remote reset of all set points and damper position automatically or manually through the network computer. Constant Volume Terminal Units with Electric Reheat Coils a) Electric controlled terminals with failin-place dampers shall be controlled from a unit mounted direct digital control unit. A pressure independent DDC software controller shall modulate the terminal unit damper to maintain supply air flow set point. b) A space temperature transmitter shall provide an input to a DDC software controller which shall modulate the electric reheat coil to maintain space temperature set point. Each terminal unit's direct digital control unit shall be capable of remote reset of all set points and damper position automatically or manually through the network computer. Emergency Generator Fuel Oil System: The emergency generator fuel oil system shall consist of two (2) 37,850 liter fuel oil tanks and one (1) duplex transfer pump set. a. The fuel oil tanks shall be located in the lowest level of the building. b. The fuel oil system shall be furnished with a "Master Fuel Oil System Control Cabinet" located in the Pump Room and a "Remote Fuel Oil Annunciator Cabinet" located at the Generator Room. c. The "Master Fuel Oil System Control Cabinet" shall contain a PLC to monitor the alarms listed in Table "A", tank status indicating lights, a lead/lag alternator, all necessary alarm lights, an alarm horn, a circulating alarm beacon light mounted atop panel, "lamp test" pushbutton and a 0-30 minute (adjustable) timer to reenergize the alarm horn after the silence pushbutton is actuated, if the alarm condition did not return to normal. This cabinet shall be powered from two separate power Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-299 HVAC Issued for Construction 1 June 2004 sources. The panel shall contain a power sensing relay which shall transfer control power from the failed source to the active source. d. The "Remote Fuel Oil Annunciator Cabinet" shall contain the same components as the master fuel oil system alarm and control panel with the exception of the lead/lag alternator, which is not required. The "Remote Fuel Oil Annunciator Cabinet" shall also monitor the alarms listed in Table "A". e. Both fuel oil annunciator cabinets shall have a full graphic of the fuel oil system. Alarm lights shall be incorporated into the graphic. f. All alarms listed in Table "A" as well as tank status indication shall also be monitored at the DDC system network computer via interface with each cabinet’s PLC via digital outputs from the PLC to digital inputs to the DDC system. This Subcontractor shall furnish and install the wiring. g. The "Master Fuel Oil System Control Cabinet" PLC shall be interconnected to the PLC located in the "Remote Fuel Oil Annunciator Cabinet" via a communications cable which shall be run in conduit. This Subcontractor shall furnish and install the communications cable. h. Cabinets shall be shipped to the site with all panelmounted components completely wired and tested. A terminal strip internally wired to the PLC shall be provided for the termination of field wire from field devices. This Subcontractor shall be responsible for furnishing and installing all wiring between the cabinets and field devices, the cabinets and fuel oil pump motors, and the cabinets and DDC system. i. The fuel oil pump set shall be hardwired interlocked with the emergency generator start circuits or the diesel fire pump so that the lead pump shall start when any of its generators or fire pump start and stop when all of its generators and fire pump are off. Form "C" dry contacts shall be available at the emergency power plant master control cubicle, located near the generators for wiring into the fuel oil pump starter circuits by this Subcontractor. A pump start contact shall be made available at the diesel fire pump day tank for wiring into the fuel oil pump starter circuits by this Subcontractor. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-300 HVAC Issued for Construction 1 June 2004 The diesel fire pump day tank level probes shall be furnished with the day tank by the Plumbing Section of the Specification. When the fuel oil pumps start due to low level of the diesel fire pump day tank, a hardwired interlock shall open a solenoid valve in the fuel oil supply pipe to the day tank. When the fuel oil pumps start due to low level of the diesel fire pump day tank and all generators are off, a solenoid in the generator bypass pipe shall open. If a generator is in operation, the valve shall remain closed. j. A lead/lag alternator provided for the duplex fuel oil transfer pump station shall automatically start the lag pump on failure of the lead pump to start. Pump running status (each pump) and pump malfunction (each pump) shall be annunciated at the DDC system network computer. The PLC shall not be used to provide lead/lag functions. An RTD temperature sensor installed by this Subcontractor in the downstream side of each fuel oil pump relief valve shall alarm at the PLC and DDC system network computer on an increase in temperature indicating relief valve actuation. Temperature sensor shall be furnished with the pump station, installed and wired by this Subcontractor. k. Each fuel oil tank shall be furnished with level sensors to monitor: 1) High level. 2) Low level. 3) Extreme low level. l. Multiple sump tell-tale high level alarms shall monitor the outer pipe within the building at the Fuel Oil Pump Room and Tank Room. The level sensor shall be provided by the fuel oil system Subcontractor. The sensor shall be installed by this Subcontractor. m. Leak alarms furnished by the fuel oil system Subcontractor, and installed by this Subcontractor in the new Fuel Oil Tank Room and the Fuel Oil Transfer Pump Room shall alarm at both panels and the DDC system upon detection of a leak. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-301 HVAC Issued for Construction 1 June 2004 n. A differential pressure switch installed across each pump duplex strainer shall alarm on high differential pressure across the strainers. The differential pressure switches shall be furnished with the pump strainers and installed by this Subcontractor. o. The fuel oil supply and return automatic and manual isolation valve at each fuel oil tank, at each generator, at the inlet to each fuel oil pump, and the isolation and bypass valves located at the Firematic fusible link valve shall come furnished with open and closed limit switches. This Subcontractor shall furnish and install the wiring from every limit switch to the PLC in closest proximity to the isolation valves. p. Flow switches furnished with the PLC system, installed and wired by this Subcontractor in each fuel oil header vent line shall indicate a vent high level. q. A fuel oil system fill line annunciator shall be furnished and installed by the fuel oil system provider, located at the Street Level in the vicinity of the fill box to annunciate when a tank is overfilled. The annunciator shall consist of an audible and visual alarm indicator and an alarm silence button. An alarm contact shall be available to indicate an overfill condition of any fuel oil storage tank at the “Master Fuel Oil System Control Cabinet.” This Subcontractor shall be responsible for providing and installing all alarm wiring between the fill line annunciator panel and the “Master Fuel Oil System Control Cabinet.” r. The “Master Fuel Oil System Control Cabinet” shall contain a lead fuel oil tank selector switch. The switch shall be wired as an input to the PLC system, which shall automatically open the lead tank’s isolation valves and close the standby tank’s valves. The PLC shall monitor the valve end switches and fuel oil level, and activate an alarm at the PLC and DDC system is a valve fails to follow its commanded state or the fuel level drops below low setting. On valve failure, the PLC shall automatically close the valves on the failed tank system and open the standby tank’s valves. s. Interlock wiring between the fuel cleaning system and the fuel oil system motorized isolation valves shall be furnished and installed by this Subcontractor. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-302 HVAC Issued for Construction 1 June 2004 t. All power, control, communications and signal wiring and conduit for the fuel oil monitoring and alarm system and fuel oil filtration and watering system shall be furnished and installed by this Subcontractor. u. The following table summarizes the alarms to be monitored at the “Master Fuel Oil System Control Cabinet,” the "Remote Fuel Oil Annunciator Cabinet," and the DDC network computer. TABLE "A" Alarm No. Alarm Description 1 2 3 4 5 6 7 8 9 10 11 Main Fuel Oil Tank No. 1 - High Level Main Fuel Oil Tank No 2 - High Level Main Fuel Oil Tank No 1 - Low Level Main Fuel Oil Tank No 2 - Low Level Main Fuel Oil Tank No 1 - Extreme Low Level Main Fuel Oil Tank No 2 - Extreme Low Level Fuel Oil Day Tank - Extreme High Level Fuel Oil Day Tank - Extreme Low Level Fuel Oil Pump FOP-1 - Malfunction Fuel Oil Pump FOP-2 - Malfunction Main Fuel Oil Tank No. 1 - Supply/Return Solenoid Valve Misaligned Main Fuel Oil Tank No. 2 - Supply/Return Solenoid Valve Misaligned Emergency Generator No. 1 - Supply Isolation Valve Closed Emergency Generator No. 1 - Supply Solenoid Valve Closed Emergency Generator No. 2 - Supply Isolation Valve Closed Emergency Generator No. 2 - Supply Solenoid Valve Closed Emergency Generator No. 3 - Supply Isolation Valve Closed Emergency Generator No. 3 - Supply Solenoid Valve Closed Diesel Fire Pump Isolation Valve Closed Diesel Fire Pump Day Tank - Supply Solenoid Valve Closed Firematic Valve Closed (Transfer Pump Room) Firematic Valve Closed (Generator Room) Firematic Valve Closed (Diesel Fire Pump Room) 12 13 14 15 16 17 18 19 20 21 22 23 Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-303 HVAC Issued for Construction 1 June 2004 Alarm No. Alarm Description 24 Fuel Oil Pump FOP-1 - Inlet/Discharge Valves Closed Fuel Oil Pump FOP-2 - Inlet/Discharge Valves Closed Fuel Oil System - Isolation Valves Misaligned Fuel Oil Pump FOP-1 - Relief Valve Actuation Fuel Oil Pump FOP-2 - Relief Valve Actuation Duplex Strainer - Fuel Oil Pump FOP-1 - High Differential Duplex Strainer - Fuel Oil Pump FOP-2 - High Differential Fuel Oil Outer Pipe Containment Leak (Base of Riser) Fuel Oil Outer Pipe Containment Leak (Pump Room) (Two Required) Fuel Oil Outer Pipe Containment Leak (Generator Room) Fuel Oil Outer Pipe Containment Leak (Fire Pump Room) Fill Sump Tank - High Level Main Fuel Oil Tank Vault - Leak Fuel Oil Transfer Pump Room - Leak Diesel Fire Pump Room - Leak Fuel Oil Day Tank Basin - Leak Main Fuel Oil Tank No. 1 - High Water Level Main Fuel Oil Tank No. 2 - High Water Level Fuel Oil Day Tank - High Water Level PLC - Education Wing Roof (Emergency Generator Room) - Malfunction PLC - Basement (Fuel Oil Pump Room) Malfunction 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 v. 26. In addition, each panel shall have pilot lights indicating the tank status. The indicating lights shall be activated from PLC digital outputs. This information shall also be displayed at the DDC network computer. Sufficient quantity of input points shall be provided to include the monitoring points associated with the future generators. Life Safety Operation a. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC A complete automatic smoke detection system provided by the life safety system provider shall be provided for all the air conditioning systems in the building interfaced with the automatic sprinkler system and fire alarm system. 15000-304 HVAC Issued for Construction 1 June 2004 b. c. d. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Air conditioning systems that are included in the building are as hereinbefore specified and summarized below. 1) Central air conditioning supply units installed in Mechanical Equipment Rooms, which provide conditioned air for all comfort conditioned spaces such as the Restaurant, Gallery, Atrium, Education Wing, 5th Floor Administration Area, Basement and Auditorium. 2) Return fans that operate in conjunction with the supply fans and remove return air from the air conditioned spaces. 3) Miscellaneous packaged air conditioning units installed in the Elevator Machine Rooms and various Equipment Rooms. 4) Miscellaneous toilet exhaust fans, smoke exhaust fans, Kitchen exhaust fans, transfer fans, Mechanical Equipment Room, Truck Dock and garage exhaust fans located at various points in the building. Smoke detectors shall be incorporated under the Electrical Section of the Contract Documents into the air handling systems and duct system, located as follows: 1) Smoke detectors shall be installed in the discharge duct from each of the air conditioning supply fans and ventilation supply fans (downstream of the filters in case of all supply fans). 2) In each supply and return air duct connection to the supply and return air shafts. Automatic dampers and automatic smoke dampers shall be located at the outside air intakes and in the discharge of each air conditioning unit and at each return air duct connection and spill connection to the Mechanical Equipment Rooms and at each point of supply and return air connection to each shaft at each floor level. The fresh air intake and spill dampers shall be automatic type. The discharge dampers and return air dampers shall be smoke dampers. The return and supply dampers at each return and supply connection at each floor shall be combination fire/smoke dampers. 15000-305 HVAC Issued for Construction 1 June 2004 e. During normal operation, whenever the air fans are shut down, the automatic dampers, smoke dampers and combination fire/smoke dampers associated with their respective air fans shall automatically close. Control of all dampers shall be via the automatic temperature control system. f. Activation of a return air smoke detector, located in a return fan, or any smoke detector, sprinkler waterflow switch or beam detector serving the Atrium or Restaurant, shall automatically cause the following sequence of events to take place: g. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) An audible and visual alarm signal shall be transmitted to the Fire Command Station and the DDC system network computer. 2) All air conditioning systems and exhaust/return air systems serving the Atrium and Restaurant, shall shut down if the systems are running, or remain off if all systems are not running. 3) The Atrium smoke exhaust fans shall start and their respective discharge and fresh air intake dampers and associated architectural intake louvers and associated doors shall open. Interlock wiring between the door controllers and the DDC system shall be furnished and installed by this Section. A hard-wired time delay relay shall allow the dampers to open prior to fan start. 4) The Gallery, Auditorium, 5th Floor Administration and Restaurant air conditioning system supply and return fans shall stop. 5) The respective air conditioning system’s dampers, including combination fire/smoke dampers, in the supply and return air ducts, shall close. 6) Basement and Education Wing air conditioning system supply and return fans shall continue to operate if currently running. Activation of a return air smoke detector, located in a return fan, or any smoke detector or sprinkler waterflow switch serving the Gallery, Auditorium or 5th Floor 15000-306 HVAC Issued for Construction 1 June 2004 Administration, shall automatically cause the following sequence of events to take place: h. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) An audible and visual alarm signal shall be transmitted to the Fire Command Station and the DDC system network computer. 2) All air conditioning systems and exhaust/return air systems serving the Gallery, 5th Floor Administration, Atrium and Restaurant and Auditorium shall shut down if the systems are running, or remain off if all systems are not running. 3) The respective air conditioning system’s dampers, including combination fire/smoke dampers in the supply and return air ducts, shall close. 4) Basement and Education Wing air conditioning system supply and return fans shall continue to operate if currently running. Activation of a return air smoke detector, located in a return fan, or any smoke detector or sprinkler waterflow switch serving the Education Wing, shall automatically cause the following sequence of events to take place: 1) An audible and visual alarm signal shall be transmitted to the Fire Command Station and the DDC system network computer. 2) All air conditioning systems and exhaust/return air systems serving the Education Wing shall shut down if the systems are running, or remain off if all systems are not running. 3) The respective air conditioning system’s dampers including combination fire/smoke dampers in the supply and return air ducts shall close. 4) Basement, Atrium, Restaurant, Auditorium, 5th Floor Administration and Gallery air conditioning system supply and return fans shall continue to operate if currently running. 15000-307 HVAC Issued for Construction 1 June 2004 i. j. Activation of a return air smoke detector, located in a return fan, or any smoke detector or sprinkler waterflow switch serving the Basement, shall automatically cause the following sequence of events to take place: 1) An audible and visual alarm signal shall be transmitted to the Fire Command Station and the DDC system network computer. 2) All air conditioning systems and exhaust/return air systems serving the Basement, Education Wing, Atrium, Restaurant, Auditorium, 5th Floor Administration and Gallery shall shut down if the systems are running, or remain off if all systems are not running. 3) The respective air conditioning system’s dampers including combination fire/smoke dampers in the supply and return air ducts shall close. Activation of a smoke detector in a supply air system located downstream of the filters shall automatically cause the following sequence of events to occur: 1) The affected supply air system supply and return fans shall stop and its respective return air and fresh air intake dampers shall automatically close. 2) An audible and visual alarm signal shall be transmitted to the Fire Command Station and the network computer. 3) The supply air discharge detector shall not be automatically reset. Each detector must be manually cleared in order to restart the respective supply fan system. k. All signals from an activated smoke detector or sprinkler flow valve shall be transmitted to a Fire Command Station located in the building lobby. The Fire Command Station shall be furnished and interwired by the Electrical Subcontractor. l. A keyed overcall switch (labeled "For Fire Department Use Only"), located at the smoke control panel, shall overcall the automatic life safety system operation and permit manual stopping and starting of any smoke Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-308 HVAC Issued for Construction 1 June 2004 exhaust fan and return fan used for smoke exhaust and the control of all smoke dampers in the return air ducts to each floor. Activation of the overcall switch shall permit, from the smoke control panel, manual starting and stopping of any fan listed herein system which was automatically stopped as a result of a fire mode condition, and permit opening and closing of smoke dampers in ductwork which were automatically closed as a result of a fire mode condition. m. Under manual operation in the fire mode, the following shall occur: 1) n. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Any return air fans that are started shall operate as exhaust fans and exhaust 100% of the air they are handling directly to atmosphere. This Subcontractor shall be responsible for the interwiring between the Fire Command Station life safety interface panel and the DDC system, and between the DDC system and a smoke control panel located next to the Fire Command Station. A dry contact for each of the following alarms shall be wired to a terminal strip to implement a shutdown. Dry contacts shall be monitored at the DDC system as “supervised” digital inputs. The inputs shall be “supervised” utilizing a parallel/series resistor arrangement for each input. All required resistors and associated wiring shall be furnished and installed by this Section. This Section shall also be responsible for providing the smoke control panel and all required control functions detailed hereinafter. Any additional wiring, appurtenances or devices required to provide the Code mandated or specified system shall be furnished by this Section. 1) Each supply air duct smoke detector. 2) One common return air smoke detector/area smoke detector/waterflow switch for all Gallery spaces. 3) One common return air smoke detector/area smoke detector/waterflow switch/beam detector for the Atrium and Restaurant areas. 4) One common return air smoke detector/area smoke detector/waterflow switch for the Auditorium. 15000-309 HVAC Issued for Construction 1 June 2004 5) One common return air smoke detector/area smoke detector/waterflow switch for 5th Floor Administration. 6) One common return air smoke detector/area smoke detector/waterflow switch for all Basement spaces. 7) One common return air smoke detector/area smoke detector/waterflow switch for the Education Wing. 8) Elevator Machine Room and/or hoistway second area smoke detector per Machine Room. 9) Each top of stair smoke detector. 10) Each top of shaft smoke detector. o. The smoke control panel shall have lights to monitor the status of fans and dampers and selector switches for manual override of the fan and damper controls. All control in the firemen's override mode shall be from this panel only. The panel shall have a door provided with keylock flush handle and plexiglass window, permitting the lights and switches to be seen, but not tampered with. All control in the firemen override mode shall be from this panel only. Switches and lights shall be mounted on the panel door. In addition, the door shall contain a schematic diagram (profile) of the building indicating the location of all fan systems and damper groups controlled from the panel switches. Panel door shall contain an engraved sequence of operation for switch and status light operation. p. There shall be a three-position “Off-Auto-Run” fan selector switch for each smoke exhaust fan and each return fan used for smoke exhaust (Auditorium and 5th Floor Administration return fans). Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) The “Run” position shall manually activate all equipment into the smoke-control mode. 2) The “Auto” position shall allow for operation in the normal building mode or in the smokecontrol mode upon receipt of an alarm signal from the fire alarm system. 15000-310 HVAC Issued for Construction 1 June 2004 q. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 3) The “Off” position shall shut down all equipment and return all dampers to their normal position (closed). 4) When an Auditorium or 5th Floor Administration return fan is started in the smoke exhaust mode, its respective purge exhaust air damper shall open and main return air damper to supply air system shall close. Smoke Exhaust of the Gallery 1) There shall be four (4) smoke exhaust damper selector switches to serve the Gallery. There shall be an individual switch for the 1st and 2nd Floors and the Gallery Mechanical Equipment Room and one switch to serve the 3rd and 4th Floors. 2) Selector switches shall be two-position switches labeled "Close- Open". 3) Placing a selector switch in the “Open” position shall open all respective floor smoke exhaust dampers on the floor as a group. Placing the switch in the “Closed” position shall close all dampers on the floor as a group. 4) There are four (4) smoke exhaust fans used to exhaust the Gallery. Each fan is furnished with a variable frequency drive. Each fan must be manually started via its respective switch. When Floors 1 or 2 are selected for smoke exhaust, and the fans’ are started, the DDC system shall automatically position the fans variable frequency drive to 50% speed (adjustable). When Floors 3 and 4 are selected for smoke exhaust, and the fans are started, the DDC system shall automatically position the fans’ variable frequency drive to 50% speed (adjustable). 5) The DDC system shall monitor the floor smoke exhaust switch positions. If a switch is selected for the “open” position and after a 1 minute time delay the smoke exhaust fans are not started manually via the panel, the DDC system shall automatically start the fans and position the drives as described above. The operator shall be 15000-311 HVAC Issued for Construction 1 June 2004 capable of stopping a fan via the “off” position of its respective switch. r. s. t. Atrium Smoke Exhaust 1) Exhaust of the Atrium shall be an automatic function of the DDC system as described above. In addition, the smoke control panel shall contain a three-position switch labeled “RunAuto-Off” for each smoke exhaust fan which shall allow an operator to manually start and stop a fan. 2) In addition, the panel shall contain a threeposition “open-auto-close” switch which shall allow an operator to manually open or close the makeup air dampers and doors. Basement Smoke Exhaust 1) The Basement smoke exhaust fans shall simultaneously exhaust the Gallery Basement and Subbasement as well as the Education Wing Basement. 2) All exhaust fans are required to operate simultaneously to exhaust these spaces. Auditorium and 5th Floor Administration Smoke Exhaust 1) u. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Each area shall be exhausted via the air conditioning system’s return fan. The fan shall be utilized as a smoke exhaust fan. There shall be an individual switch per fan at the smoke control panel. Smoke Exhaust of the Education Wing 1) There shall be three (3) smoke exhaust damper selector switches to serve the Education Wing. There shall be an individual switch for the 1st, 2nd and 3rd Floors. 2) Selector switches shall be two-position switches labeled "Close- Open". 3) Placing a selector switch in the “Open” position shall open all respective floor smoke exhaust 15000-312 HVAC Issued for Construction 1 June 2004 dampers on the floor as a group. Placing the switch in the “Closed” position shall close all dampers on the floor as a group. 4) Each floor shall be exhausted by the air conditioning system’s return fans. 5) The DDC system shall monitor the floor smoke exhaust switch positions. If a switch is selected for the “open” position and after a 1 minute time delay the smoke exhaust fans are not started manually via the panel, the DDC system shall automatically start the fans and position the drives as described above. The operator shall be capable of stopping a fan via the “off” position of its respective switch. v. There shall be a three-position “open-auto-close” selector switch for each stair, shaft and Elevator Machine Room hoistway smoke vent damper. When the switch is in the “open” position, the respective damper shall open. When the switch is in the “auto” position, the respective damper shall be controlled via the DDC system. When the switch is in the “closed” position, the respective damper shall be closed. w. There shall be two indicating lights for each smoke exhaust fan, truck dock exhaust fan, garage exhaust fan, Mechanical Equipment Room exhaust fan, and return fan used for smoke exhaust. There shall be two indicating lights for each damper group. x. Indicating lights shall be labeled "On-Off" for fans and "Open-Close" for floor damper groups. y. Indicating light colors shall be: Color Fan Damper Red Amber Green Off Auto On Closed Auto Open z. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Fan "On-Off" indicating lights shall be actuated from digital outputs (DO's) derived from fan status digital inputs (DI's) to the DDC system. Damper "Open-Close" indicating lights shall be actuated from DO's derived from DDC command state of the associated damper, as 15000-313 HVAC Issued for Construction 1 June 2004 commanded by the damper switch input to the DDC system. aa. 27. The total response time for individual components to achieve their desired state of operation mode (i.e., completion of damper travel or fan operation at the desired state) shall be in accordance with NFPA 92A, Paragraph 3-4, 3.3. Primary Chilled and Condenser Water System a. The chilled and condenser water system shall consist of three (3) 800 ton electric drive chillers, one (1) three-cell cooling tower, three (3) condenser water pumps, and three (3) chilled water pumps. The chilled water pumps shall be variable speed pumps. The condenser water pumps are constant speed pumps. The cooling tower fans shall be furnished with variable frequency drives. One (1) chiller, condenser water pump, chilled water pump, and cooling tower cell shall be standby. b. The lead chiller, lead condenser water pump, lead cooling tower cell, and lead chilled water pump shall be selected by the operator via a DDC mode selection program. Under normal conditions, all MCC and VFD H-O-A (Hand-Off-Auto) and local chiller control switches should be in the "Auto" position. Based on the equipment selected, a DDC program shall automatically position the motorized valves as shown on the mechanical drawings for the selected mode of operation and the equipment selected. When the position of the motorized valves have been verified for the correct position, the DDC program shall allow the operator, through the DDC system via the network computer, to start the lead condenser water pump and lead chilled water pump and enable the lead cooling tower fan. Once flow through the condenser and evaporator is established and verified (via low flow differential pressure switch across condenser and evaporator did not trip), the operator of the network computer, through communications with operator stationed at the lead chiller panel, shall direct that the lead chiller be started. Differential pressure switches shall be furnished by the chiller manufacturer and installed by this Subcontractor to provide input to the DDC system for each chiller. In addition, a second set of differential pressure switches shall be furnished and installed by this Subcontractor to provide proof of flow to the chillers. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-314 HVAC Issued for Construction 1 June 2004 c. The alignment of the motorized valves in the selected mode of operation shall manually be accomplished through system software. Should indication be received that a valve did not transfer within 20 seconds of being commanded to do so, the software program shall shut down the lead system, close the motorized valves serving the equipment, and generate an alarm at the network computer. Indication shall be verified via open and closed limit switches, two (2) switches per valve. d. The DDC system shall monitor pump and fan status via current sensing. Should the system receive indication that a pump or fan did not start within 20 seconds after being commanded to do so, or a pump or fan fail to run after starting, an alarm shall be generated at the network computer and alarm printer. An audible signal shall also alert the operator to the alarmed condition. The DDC system shall automatically start the standby pump or fan. e. Subsequent chiller, condenser and chilled water pumps and cooling towers shall be manually added or subtracted to match the cooling load. A DDC software load calculating program shall monitor the common chilled water flow and the common supply and return temperature and calculate the instantaneous cooling load on the plant. The program shall notify the operator to start additional chillers, pumps and cooling towers when the load reaches 90% (adjustable) of the maximum design capacity of the currently operating system. Similarly, on a drop in load to 40%, the program shall notify the operator to stop lag equipment. When a chiller is running, its temperature controller shall maintain the set point of the leaving chilled water. f. Each cooling tower fan shall be equipped with variable speed motors. g. The operator shall select the active cooling tower cell via a manual command at the network computer and shall manually open the respective cooling tower cell isolation valves. The speed of the active cooling tower fans shall be controlled via a DDC PI software controller based on the common condenser water supply temperature. A transmitter located in the common condenser water supply pipe shall provide an input to the controller. On initial startup when the supply condenser water temperature is above set point, the controller shall start the lead cooling tower fan. When only one cell has been Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-315 HVAC Issued for Construction 1 June 2004 selected, the program shall step the fan speed from off to minimum speed (adjustable) and modulate the fan speed from minimum to full speed to maintain temperature set point. When both cells are active, the program shall operate both fans simultaneously. With both cells active, the program shall first start the lead fan and operate it at minimum speed. On an increase in temperature, the program shall start the lag fan and operate it at minimum speed. On a continued increase in temperature, the program shall ramp the fan speeds, in parallel, from minimum to maximum speed to maintain temperature set point. On a drop in temperature, the reverse shall occur. Fans shall be stopped in reverse order of starting. On a continued drop in temperature, the controller shall continue to reduce the fan speed until the fans are off. h. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Chilled Water Pressure Control: A DDC software twomode (P+I) differential pressure controller shall control the on-line variable speed pumps to maintain set point. There shall be one (1) differential pressure transmitter in each main mechanical equipment room (total of five). Each transmitter shall provide an input to a DDC software low signal selector which shall select the lowest signal representing the machine room which requires the greatest water flow to satisfy its set point. The signal selector shall provide an input signal to the DDC differential pressure controller. On decreasing differential pressure below set point, the DDC software controller output to the variable speed drive shall increase to drive the pump to full speed. On an increase in differential pressure above set point, the DDC software controller output to the variable speed drive shall decrease to drive the pump to reduce speed. A DDC software program shall limit the turndown on the variable speed drives to ensure that a chiller does trip off-line due to low chilled water flow through the evaporator. To accomplish this, the DDC software program shall monitor common chilled water flow through the on-line chiller and, via two-mode software flow controller, modulate open a bypass valve installed across the chilled water supply and return piping, resulting in a decrease in system differential pressure, which shall result in increased chilled water flow. The differential pressure transmitter shall be wired to the DDC units serving the chilled water system. The differential pressure signal shall not be transmitted throughout the network for pump speed control. 15000-316 HVAC Issued for Construction 1 June 2004 i. j. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Alarm Devices 1) The DDC system shall be notified of a chiller malfunction through digital inputs originating from the local chiller control panel. 2) Temperature transmitters, located in the chilled water supply piping of each chiller shall cause a DDC software alarm when chilled water supply temperature rises above set point. 3) Cooling tower high level and low level switches furnished and installed by this Section of the Specification shall provide alarms at the DDC system through digital inputs. There shall be one (1) high and low level switch per cell. 4) Cooling tower fan trip, due to excessive vibration, shall be alarmed at the DDC system through digital inputs from vibration switches furnished with the cooling tower. Wiring between the vibration switches and fan starters shall be provided under this Section. 5) Temperature transmitters, located in the main condenser water supply and return headers, shall provide temperature monitoring at the DDC system and cause a DDC software alarm when condenser water supply temperature falls below set point. 6) Expansion tank high and low pressure alarm switches furnished and installed by Section 15600 shall provide alarms at the DDC system through digital inputs. Break-Glass Switches: Two new dual action (i.e., breakglass, pull lever) break-glass switches shall be located outside each exit of the chiller plant. One switch shall start the exhaust fan and the other shall stop the chillers. The break-glass switches shall be hard wired into the chillers and exhaust fan starter circuits. Breakglass switches to start fans shall be wired in parallel. Switches to stop chillers shall be wired in series. Breakglass switches and associated wiring and conduit shall be furnished and installed by this Subcontractor. 15000-317 HVAC Issued for Construction 1 June 2004 k. Inhibitor or Biocide Injection: When the refrigeration machines are operational, the condenser water system normally closed flush valves shall be closed. When the refrigeration machines are off-line, the flush valves shall be manually opened. The injection of inhibitor or biocide shall cause the following sequence of operation to occur: 1) The DDC system shall receive an input from the water treatment system, indicating an inhibitor or biocide pump has started. The DDC system shall start the lead condenser pump. If, after a 030 second adjustable time delay, proof of flow is not established via current sensing relay switch indication, a software alarm shall alert the operator to start the lag pump. When biocide or inhibitor pump has stopped, the circulation condenser pump shall also stop after a minimum time delay has been satisfied (adjustable from 5 to 30 minutes). l. Condenser Water Filtration: This Section shall provide all control interwiring required for the condenser water filtration systems provided under Section 15712AC of the Contract Documents operational. m. Expansion Tank Makeup Pump Controls n. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) This Section shall provide all control wiring associated with the expansion tank makeup pump controls as described in the Mechanical Section of the Contract Documents and the associated Contract Drawings. 2) The DDC system shall monitor pump run status via current-sensing relay. A DDC software program shall totalize and trend pump run times at the network computer. 3) The expansion tank makeup pump basin shall contain a low level switch which shall be wired to the DDC system to activate an alarm on sensing low level. A DDC software program shall calculate the total cooling load of the primary chilled water system via inputs from a primary chilled waterflow meter and common supply and return water temperature transmitters. 15000-318 HVAC Issued for Construction 1 June 2004 o. Condenser Water Makeup System and Makeup Tank System: This Section of the Specification shall provide all control and power wiring for the condenser water makeup system provided by the Plumbing Subcontractor. All required relays, level probes, control panels, interposing relays, etc., shall be furnished by the Plumbing Subcontractor. Power wiring of control panel, and hardwired interlock between relay probes and control panel, and between the panel and pump starter and all miscellaneous wiring of field devices shall be furnished and installed by this Section. Wiring of all makeup tank level probes and associated controls shall be furnished and installed by this Subcontractor. p. House Tank Makeup System: This Subcontractor shall provide all control and power wiring for each house tank makeup system provided by the Plumbing Section of the Specification. All required relays, level probes, control panels, interposing relays, etc., shall be furnished by the Plumbing Subcontractor. Power wiring of control panel, and hardwired interlock between relay probes and control panel, and all miscellaneous wiring of field devices shall be furnished and installed by this Subcontractor. q. Heat Recovery Coil Water Systems Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 1) Each system shall consist of two (2) pumps. Pumps shall be constant speed. One (1) pump shall be a standby pump. 2) The lead pump shall be started via a software interlock when its respective air conditioning system is in operation. 3) The DDC system shall monitor pump status via current-sensing relay. Should a pump fail to start, the DDC system through a 0-30 second (adjustable) time delay relay shall send an alarm to the network computer and alarm printer and the standby pump shall start. An audible signal shall also alert the operator to the alarmed condition. 4) The DDC system shall monitor the common heat recovery system supply and return water temperatures via temperature transmitters furnished and installed by this Subcontractor. 15000-319 HVAC Issued for Construction 1 June 2004 r. 2.46 5) The DDC system shall monitor a high and low level alarm from each heat recovery system expansion tank. Level switches shall be furnished and installed by this Subcontractor. 6) All required power and control wiring for the expansion tank makeup valve shall be furnished and installed by this Subcontractor. 7) A flow meter furnished and installed by this Section in each expansion line shall be monitored by the DDC system for remote indication and totalization. Miscellaneous Input/Output Points: Refer to Appendix A for point summaries. INSTRUMENTS A. B. C. General 1. All thermometers and pressure gauges shall have ranges suitable for the service intended. Pressure gauges shall be as manufactured by one of the approved manufacturers listed in Article 2.01 “Approved Manufacturers”. 2. All instruments called for hereinbelow shall be provided in addition to any other instruments called for elsewhere. Duct Thermometers 1. Duct thermometers shall be of the dial type having liquid-filled thermal elements and necessary length of capillary tubing. Dial shall be 100 mm. diameter with stainless steel casing. Dials of thermometers shall be mounted on casings or ducts in a manner that permits easy reading. 2. Thermometers shall be installed in all air conditioning and ventilating units, one (1) downstream and one (1) upstream of each coil bank to read the dry bulb temperature of the respective coil. In addition, such thermometers shall also be installed in the inlet to all return fans, in all fresh air intakes, and downstream of supply fan discharge. Pipe Thermometers 1. Pipe thermometers shall be stem type, environmentally safe organic spirit filled, red reading, 225 mm. scale, having a separable socket and be field adjustable in all planes to permit a convenient viewing angle. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-320 HVAC Issued for Construction 1 June 2004 D. 2.47 2. Thermometers for outdoor use shall be 75 mm. bi-metal dial type having a 100 mm. rear connection stem and separable 100 mm. brass socket well with waterproof stainless steel casing and components. Lens shall be double-strength glass. 3. Indicating thermometers shall be provided at the inlet and outlet of all water coil banks, water chillers, and refrigerant condensers. They shall also be provided in the common chilled water supply line and the common condenser water outlet line from the refrigerant condensers. Pressure Gauges 1. Pressure gauges shall be phosphor bronze bourdon type, with 6 mm. NPT bottom outlet, 100 mm. dials, adjustable pointers, aluminum cases and acrylic lenses. Gauges on air and water services shall be fitted with pulsation snubbers and brass positive shut-off ball valves rated at 4,137 kPa WOG (ball cocks with plug type mechanisms are not acceptable). Pressure gauges on steam services shall be fitted with brass needle valves rated at 13,800 kPa and a steel siphon (pigtail) to form a water barrier to prevent steam damage to the internals. 2. Pressure gauges for outdoor use shall be stainless steel bourdon type, with 6 mm. NPT bottom outlet, 100 mm. dials, adjustable pointers, high-impact polypropylene cases, seal rings and acrylic lenses. 3. Pressure gauges shall be provided on water and oil lines at the inlet and outlet of all pumps, water coil banks, chillers (evaporating and condensers), refrigerant condensers, and as shown on plans. 4. Range of gauges shall be selected gauge range. WATER TREATMENT A. General 1. Install all connections, pipe, valves, feeding equipment, etc., required to provide water treatment for control of scale, corrosion, fouling and microbiological growth and deposition in the following mechanical piping systems: Main Condenser Water System Closed Chilled Water System Closed Heat Recovery Water Systems Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-321 HVAC Issued for Construction 1 June 2004 B. Equipment and Installation 1. Condenser Water System: Install on the condenser water system an automatic feed system and controller supplied by the water treatment supplier for single source responsibility for treatment, feed equipment and service to insure compatibility of equipment and service. a. The controller and feed pumps shall be a fully enclosed factory assembled, prewired and prepiped in a Pulsa Feeder Inc., MCT 300 Series assembly, or similar assembly provided by Nalco, Union or Aquatrac. b. Controller 1) 2) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Provide in a single enclosure a microprocessor based controller for use in a recirculating condenser water system that shall: a) Allow for the proportional feed of inhibitor chemicals based on the quantity of makeup water as measured by a contact head water meter. b) Accurately control the level of total dissolved solids (TDS) in terms of electrolytic conductivity. c) Provide a programmable dual 28-day biocide timer for accurate addition of biocide chemicals. d) Accurately measure the pH of the circulating water, e) Accurately control the level of bromine as measured in terms of the oxidation reduction potential (ORP) in the cooling system water. Controller shall be housed in a 25.4 cm. (square) NEMA 4X – high impact resistant polystyrene enclosure complete with: a) A continuous hinged door and lexan viewing window. b) Dual padlocking hasps. c) An 2.5 meters, 3 wire power cord with molded plug. 15000-322 HVAC Issued for Construction 1 June 2004 d) 3) Panel shall have an external combination mounted flow switch with transparent sight tube and back check valve. The flow switch shall disable the control outputs if waterflow is less than 3.785 liters per minute. The flow switch shall come complete with 19.05 mm. connections and shall contain the conductivity, ORP, pH and temperature electrodes. 4) All functions shall be fully programmable through the keyboard. a) 5) Z:\worldox\docs\122690\spc\00015619.DOC All readouts can be set to scroll continuously. Controller shall provide temperature corrected measurements by reading water temperature and adjusting pH and conductivity values according to a known temperature curve. a) Museum of Islamic Art Doha, Qatar Duplex receptacles located on the bottom of the enclosure. Range shall be 0-100° Celsius and 32212° Fahrenheit with an adjustable high alarm. 6) Controller shall have a real-time clock. 7) Controller shall have real-time settings in one minute increments. 8) Controller shall have a front panel, 22.83 cm. (square), anchored into the enclosure by four corner screws. a) Removal of the front panel shall be effected by removing the four screws and disconnecting color coded connectors located behind the panel. b) Replacement of this panel shall effect a replacement of all electronic parts. c) The controller shall be backed by a one year warranty plus an extended factory exchange policy. This policy shall provide a replacement panel in case of 15000-323 HVAC Issued for Construction 1 June 2004 malfunction other than physical or electrical abuse. 9) Controller shall have a six-mode, operator selectable, inhibitor chemical feed code which includes: a) Any percentage of a continuously repeating 10 minute cycle. b) Any percentage of the time controller is calling for bleed-off. (1) Z:\worldox\docs\122690\spc\00015619.DOC Post bleed percentage. c) Any percentage of the time controller is calling for pH control. the d) A timer triggered by a contacting head water meter. 10) Controller shall operate over an input voltage range of 240 VAC, ambient temperature rating of between -40 to 60°C. and shall be operational with 0-100% relative humidity. 11) Controller shall have a nickel/cadmium rechargeable battery backup which shall maintain the program during power outage. 12) Controller shall have a low voltage Class II signal to water meter which: 13) Museum of Islamic Art Doha, Qatar the a) Shall have an accumulator (counter). b) Shall have an elapsed time and pulse count readout. c) Shall have elapsed times for solenoid valve, inhibitor. The panel display shall include: a) Bi-lingual menu driven programs for easy operation. b) Liquid crystal display (LCD) which shall be alphanumeric, 6 line, 40 characters per line, to display information in menu form for easy operation and programming. 15000-324 HVAC Issued for Construction 1 June 2004 c) 14) 15) 16) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC A 16 key keypad for settings, calibration and timer adjustments. The biocide feed control shall be as follows: a) Dual but independent, 28 day timers on a 24 hour basis. b) Shall activate a chemical pump or other electrical device for 1 minute to 24 hours in 1 minute increments. c) Shall allow feed on any day(s) of the week. The conductivity control shall be as follows: a) A high scale of 0-20,000 micromhos/cm. and a low scale of 02000 micromhos/cm. b) High and low alarms, factory set 20% above and below the trip point with operator adjustable capabilities. c) An adjustable conductivity differential. d) A bleed limit timer which is settable from 0 to 23 hours and 59 minutes. The pH control shall be equipped as follows: a) With either a rising or falling trip point. b) High and low adjustable alarms. c) A differential settable between 0.1 and 1.0 pH units. d) To monitor pH as it relates to ORP. e) A scale of 0-14 pH units. f) A scale of 0-10 ppm as chlorine and ORP. 15000-325 HVAC Issued for Construction 1 June 2004 17) The electrodes included shall be: a) b) c) c. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC An CN-1A stainless steel combination conductivity and temperature electrode. This electrode: (1) Shall be quick disconnect. (2) Shall be supplied in the flow switch assembly. A PN-1 sealed combination type silver/silver chloride reference pH electrode. This electrode: (1) Shall be quick disconnect. (2) Shall be supplied in the flow switch assembly. An ON-1 ORP electrode to monitor ORP. 18) Relays, contacts, wiring and terminals to activate one or more condenser water pumps when either inhibitor or biocide feed pumps are activated. 19) Relays and contacts to activate the solenoid valve controlling the flow to the brominator. Pumps 1) Inhibitor feed pump, Neptune, Milton Roy or LMI, diaphragm type controlled volume pump polypropylene construction, 3.78 l/hr capacity, 10 bars working pressure, single phase, 50 hertz, 240 volt motor, or as approved, output adjustable from 0 to 100 percent of capacity while pump is in operation. 2) Automatic biocide feed pump(s), Neptune, Milton Roy, or LMI, 100 lph capacity, diaphragm type, controlled volume pump, polypropylene construction, 10 bars working pressure, single phase, 50 hertz, 240 volt motor, or as approved, output adjustable from 0 to 100 percent of capacity while pump is in operation. 15000-326 HVAC Issued for Construction 1 June 2004 2. d. Provide a 50 mm. Badger, Hershey, or Carlson turbine water meter with 1000 liter contact head in makeup water line to condenser water system, with a valved bypass. Meter shall be 10 bars wwp construction sized for operation at maximum makeup rate with electric contact switch in the register. Meter shall be furnished under this Section, for installation under the Plumbing Section. e. Bleed-off assembly shall include a 50 mm. ASCO Model 8210D22, or as approved, solenoid bleed-off valve and ball flow indicator, RCM, or as approved, on bleed-off line from condenser water return line. f. Corporation stop injection nozzle assembly for each pump, 12.5 mm. PVC injection nozzle with 20 mm. NPT male connection to the main line for injecting inhibitor and biocide into condenser water return line downstream from bleed-off line. g. Provide a Great Lakes Chemical Corp automatic brominator for feed of bromo-chloro-dimethylhydantoin to the system. Brominator shall consist of reinforced polyester tank, complete with 100 mm. cover, 20 mm. PVC connections with 80 mm. flow control valve and flow indicator designed for 5.5 bars maximum pressure. Brominator suction line shall be run from the (filter) water pump discharge to the brominator. A 20 mm. PVC discharge line shall be run from the .brominator to the filter discharge pipe return to the pan. Flow indicator and flow control valve and solenoid control valve shall be installed on the inlet. Closed Recirculating Water Systems: Install in the chilled water system and each heat recovery water system a closed loop filter system. Filter system shall include a vertical, epoxy lined carbon steel tank, constructed for 10 bars wwp at 65°C, hand hole with a gasketed removable cap at the top to permit use of the unit as a bypass chemical feeder and for media access. Galvanized steel overdrain and stainless steel underdrain shall be provided. a. Filter Media: Shall be Unigran 55 capable of removing 95% by volume of suspended solids 5 microns and larger. b. Valve System: Four electric solenoid valves for automatic control of backwash, ball valves and discharge check for equipment isolation. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-327 HVAC Issued for Construction 1 June 2004 C. c. Electrical Controls: Shall include disconnect switch, 24 hour timer or backwash control and required contacts mounted in a NEMA-3R rainproof enclosure. Controls and solenoids shall operate on 110 volt, single phase power. d. Backwash Water: Shall be taken from the domestic cold water system. Provide an approved reduced pressure backflow preventer with atmospheric relief and a Dole, or as approved, 1.26 lps flow regulator on the water makeup. Discharge the backwash to a floor or funnel drain. Chemical Treatment Program 1. Engage a qualified and approved water treatment supplier to provide a supervised water treatment program from the date of the initial introduction of water into the systems and/or equipment indicated. Continue the treatment program for a period of one year after acceptance of the system(s) by the Engineer for his operation. 2. The water treatment supplier shall have at least one officer or official holding a college or university degree in chemistry, chemical engineering, or sanitary engineering. He should have at least ten years' experience in treating the water in systems of similar size and capacity, and he shall be in active responsible charge of all treatment work. 3. The supplier's laboratory shall be equipped to analyze samples in accordance with the standard testing methods of the American Water Works Association and the American Society for Testing Materials. 4. The water treatment supplier shall include the following services: a. Supervise all water related operations, including testing, cleaning and passivation. b. Provide the necessary inhibitors required for all pressure testing of piping systems, and maintaining the inhibitor levels in systems until systems are ready for cleaning and passivation. c. Provide the Engineer with complete written instructions for chemical feeding, bleed-off, testing and other procedures required for successful routine operation of the water systems. Instructions shall include Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-328 HVAC Issued for Construction 1 June 2004 recommended lay-up, on-line and off-line cleaning procedures. 5. d. Demonstrate to Engineer's personnel the proper application of written instructions (minimum of one man-days of training). e. Provide all chemicals, chemical feeding equipment and testing equipment, as described herein. f. Provide (monthly field service visits by a qualified representative for the supervision of the chemical treatment program. A written report detailing treatment conditions and including any necessary recommendations shall be submitted to the Engineer following each visit. In addition, laboratory water analysis, corrosion tests and microbiological tests shall be provided. All site visits by the Water Treatment Subcontractor shall be scheduled with the Engineer. g. Provide an analysis of glycol strength and inhibitor level after initial fill and every three months thereafter. If it complies with these Specifications, automatic water treatment control systems manufactured by one of the following manufacturers shall be acceptable: Betz Entec. Nalco Watergy. Diversey Water Services. Drew Ashland Chemical. Kurita Degremont/Houseman 6. Hydrostatic Testing, Initial Cleanout and Flushing a. Hydrostatic Testing: Only water containing an adequate level of corrosion inhibitor shall be used for hydrostatic testing and, if permitted to remain in the system, the chemical level shall be adequate for passivation purposes. A minimum of 1500 ppm of buffered sodium nitrite or equivalent corrosion inhibiting formulation shall be maintained in all condenser water, chilled water and hot water systems. b. Cleaning Procedures 1) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Fill each entire closed recirculating water system with clean fresh water while adding the passivating agent and recirculate for 1 hour. 15000-329 HVAC Issued for Construction 1 June 2004 These chemicals shall not be injurious to persons, piping, pipe joint compounds, packings, coils, valves, pumps and their mechanical seals, tubes or other parts of the system. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 2) Drain the entire system. 3) Remove all screens and strainers, clean and replace cartridge filter elements in the temporary skid mounted portable side stream filter. 4) Fill and flush all recirculating water systems, both open and closed, with a 0.5% solution, by weight, of a nonfoaming chemical detergent, or suitable approved product proposed by water treatment service company, to remove all foreign matter. These chemicals shall not be injurious to persons, piping, pipe joint compounds, packings, coils, valves, pumps and their mechanical seals, tubes or other parts of the system. 5) Recirculate the cleaning solution at a high rate in system for 4 hours. 6) Drain the entire system as rapidly as possible. 7) Remove all screens and strainers, clean and replace cartridge filter elements in the temporary skid mounted portable side stream filter. 8) Fill entire system with clean fresh water with passivating agent and recirculate for 1 hour. 9) Drain the entire system as rapidly as possible. 10) Remove all screens and strainers, clean and replace cartridge filter elements. 11) Fill the entire system again and flush with clean fresh water. 12) Drain system as rapidly as possible. 13) Remove all screens and strainers, clean and replace. 14) The pH of the water shall be within 0.5 of the pH of the fresh incoming water. All traces of detergent dispersant or alternate product used, as 15000-330 HVAC Issued for Construction 1 June 2004 well as products of corrosion and foulants, shall be gone as confirmed by a system water analysis performed by the water treatment supplier and submitted to the Engineer for approval. 7. 15) The disposal of waste water from the piping system cleaning and flushing shall be at the Subcontractor’s expense. 16) Filtration Procedure: Change bypass cartridge filter element as often as required starting with forty (40) micron elements until system is clean with (1) micron cartridge filter elements. c. Immediately after filling the system with clean water, add sufficient quantities of the specified biocides and inhibitor to passivate the system. d. The water treatment supplier shall certify as to the adequacy of the cleanout/flush, passivating and corrosion inhibiting procedures performed under his supervision. Application of Chemicals: Provide an environmentally acceptable nontoxic water treatment program to maintain the hereinafter specified conditions in each of the systems. The treatment program has been based an analysis similar to the following, but it is the water treatment supplier's responsibility to verify the nature of the incoming water. No extra charges shall be allowed for additional chemicals required due to seasonal variations in the water analysis. All chemicals used and disposal methods shall be acceptable to the authorities having jurisdiction, for discharge to the sanitary sewer. Constituent Expressed As *Total Hardness CaCO3 92 *Calcium Ca 27 Magnesium Mg 6 Total Iron Fe .04 *pH - 7.87 *Conductivity umhos/cm 308 *Total Alkalinity CaCO3 86 Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-331 HVAC Issued for Construction 1 June 2004 Bicarbonate CaCO3 -- Carbonate CaCO3 -- *Phosphate PO4 --- *Chlorides Cl 53 *Silica SiO2 -- *Sulfates SO4 5 a. Supply water treatment chemicals concurrently with the operation of each system. Supply an initial dosage(s) of treatment chemical(s) immediately after each system is filled with water in preparation for operation. No system shall be accepted without written certification and demonstration of biological cleanliness and proper inhibitor levels. b. The chemicals which are to be utilized in the treatment program must be completely acceptable to the authorities. All chemicals and combinations proposed for the treatment program must be approved by the authorities having jurisdiction. All treatment chemicals used in the course of the Contract must be similarly approved by the authorities having jurisdiction and follow the following criteria: c. 1) They must be nontoxic to personnel and not hazardous to handle. 2) At use concentrations in the systems, they must be readily disposable to the receiving sewer system or waterway. 3) Procedures for cleaning up spills of neat or diluted chemical must be simple, readily available and not dangerous to personnel. The cleaned material must be readily disposable. The water treatment supplier shall certify the chemicals used in the treatment program shall meet or improve on the following general performance criteria: 1) Open Cooling Water Systems Corrosion rate on mild steel Corrosion rate on brass and copper Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-332 Less than 2.0 mpy Less than 0.2 mpy HVAC Issued for Construction 1 June 2004 Scaling rate Biofouling 2) Closed Cooling System and Heat Recovery Systems Corrosion rate on mild steel Corrosion rate on brass and copper Scaling rate 8. No loss in performance No loss in performance No visible algae/slime No health hazards Planktonic CFU less than 103/ml less than 0.5 mpy less than 0.1 mpy None Chemicals a. Open Condenser Water Systems 1) The following is a specification for an acceptable nontoxic scale and corrosion inhibitor program. Alternate treatment programs, conforming to specification requirements, may be submitted for evaluation and approval. Alternate programs must be documented sufficiently to demonstrate that they shall produce the required results. Documentation should include: Product literature and MSD sheets; composition; laboratory and field performance and case history data; handling, disposal and environmental data; and an explanation of why the alternate program should be selected over other programs. 2) Treatment and Chemical Conditions Control Level Nontoxic all organic corrosion Phosphonate and scale inhibitor, with triazole 10-15 mg/L nonferrous metal organic inhibitors and polyacrylate dispersants similar to the following Ppm in Water % in Product at 100 ppm Product Hydroxy Phosphono Acetic Acid Polymaleic-Acid-Copolymer Zinc oxide Sodium molybdate dihydrate Tolyltrizole 50% Caustic 10 8 3 10 5 To pH 10.4 10 12 6 (as Zn) 6 (as Mo) 3 (as TT) 15000-333 HVAC Issued for Construction 1 June 2004 Component Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Treatment and Chemical Conditions Control Level Organic growths pH Cycles of Concentration None 8-9 Max. 6 3) Apply, on a shock dosing basis, Environmental Protection Agency registered biocides as required to supplement continuously maintained bromine level. Quaternary ammonium compounds, organic sulfur compounds, isothiazolines, glutaraldehyde, azoles, phosphonium quaternary compounds, tributyl tin oxide, and chlorine release agents are acceptable. Biocides should be matched to the system needs and alternated as necessary. a) 9. Provide bromine tablets for the brominator and adjust controls to maintain a level of no more than .2 ppm as halogen. Closed Recirculating Water Systems Treatment and Chemical Conditions System Chilled Water And Heat Recovery Water a. Control Level Buffered sodium nitrite as sodium nitrite with triazole nonferrous metal organic inhibitor and polymeric deposit inhibitor 500-1000 ppm Organic growths None pH 9.0-10.5 Testing: Provide all necessary field test equipment for maintaining control of treatment standards and cycles of concentration as above. Test kits shall be supplied by the water treatment supplier and remain the property of the Engineer. Test kits shall be as follows: 1) Open Condenser Water Systems Field Drop Chloride Test Kit Field Kit for Phosphonate or Molybdate Field Kit for pH in range of 6.0-9.0 Field Kit for Bromine Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-334 HVAC Issued for Construction 1 June 2004 2) Chilled Water System and Heat Recovery Systems Field Kit for Nitrite or Molybdate Field Kit for pH in range 6.0-12.0 10. System Monitoring a. Water treatment supplier shall provide a 25 mm. coupon rack consisting of at least four (4) corrosion test coupon holders. Three (3) holders shall contain preweighed mild steel coupons, and one (1) holder shall contain a preweighed copper coupon, or a coupon of other metals used in the system. The coupon rack is to be installed with a flow indicator and means of regulating the water flow through the rack. Water flow shall be regulated to 122-183 cm/s. The copper coupon shall be removed for analysis every 90 days. The steel coupons shall be rotated so that one (1) 90-day coupon is removed every 30 days. Reports shall be issued by the water treatment supplier’s laboratory for the period of the Contract. A removable 25 mm. x 300 mm. long black steel spool piece shall be provided on the horizontal pipe leading into the coupon rack. This pipe section is to be removed after one year of exposed flow rate and sent to a metallurgical laboratory for destructive testing to evaluate the performance of the chemical treatment program. Stations shall be installed where indicated on the drawings, or as directed by the Engineer’s representative. b. Open cooling water systems and closed recirculating systems shall be monitored on a regular basis for biological activity. Testing shall be done according to the following schedule, or more frequently if results indicate that problems may be present: 1) Monthly samples shall be taken from open systems and monitored for total planktonic count, using "dip sticks" or similar simple field test devices. a) 2) Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC A referee sample shall be taken quarterly for plate counts in a qualified microbiological laboratory. A "Robbins Device" or similar device for collecting sessile bacteriological deposits shall be installed in each system and inspected at least 15000-335 HVAC Issued for Construction 1 June 2004 quarterly. The removable spoolpiece included in the corrosion monitoring station may be used for this purpose. 3) Biocide dosages and operating parameters shall be adjusted as needed, based on the results of these tests, to maintain required microbiological control limits. 4) At least semiannually, a properly prepared sample shall be submitted to a qualified laboratory for identification of pathogenic bacteria that may be present in the system. 5) Test the cooling tower basin on a quarterly basis for the presence of legionella pneumophila, utilizing the DFA method as practiced by Bioindustrial Technologies, Inc. of Grafton, New York. The report shall give the result in bacteria per milliliter and shall reference deviations from the previous month. Any major increase in legionella pneumophila bacterial growth shall require shock treatment of the cooling tower basin with an oxidizing agent such as chlorine at a level of 25-50 ppm for 1/2 hour. 11. The control system shall be fully warranted from defects in parts and workmanship for a period of two (2) years from the date of the issuance of a “Certificate of Completion” by the Engineer. 12. Detailed Shop Drawings of all equipment, materials, flow diagrams, piping diagrams, wiring diagrams, bleed valve, etc., shall be submitted for the review of the Consulting Engineer. 13. This Subcontractor shall furnish the following chemicals as required for the system until the Engineer has issued a “Certificate of Completion”. a. Corrosion Inhibitor: One hundred fifty (150) liter drums of liquid corrosion inhibitor shall be provided until the Engineer issues a “Certificate of Completion”. The corrosion inhibitor shall be non-polluting and comply with local regulations covering waste water discharge and shall be permitted by the local authorities having jurisdiction. b. Dispersant: One hundred fifty (150) liter drums of dispersant shall be provided until the Engineer issues a “Certificate of Completion”. The dispersant shall be Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-336 HVAC Issued for Construction 1 June 2004 non-polluting and comply with local regulations covering waste water discharge and shall be permitted by the local authorities having jurisdiction. 14. c. Biocide: One hundred fifty (150) liter drums of biocide shall be provided until the Engineer issues a “Certificate of Completion”. The biocide shall be non-polluting and comply with local regulations covering waste water discharge and shall be permitted by the local authorities having jurisdiction. d. pH adjustment chemical, corrosion inhibitor, dispersant, and biocide shall be as recommended by chemical company for the local water characteristics. The Mechanical Subcontractor shall install corrosion coupon racks as recommended and supplied by the chemical company. D. Water treatment piping shall be as specified for chilled, condenser, and heating hot water piping. Refer to Articles entitled “Materials for Piping” “Pipe Fittings” and “Valves”. E. All water treatment systems and accessories shall be installed in accordance with the latest industry standards, per the manufacturer’s recommendations, and as indicated on the Drawings. F. The water treatment equipment manufacturer shall install the required shielded control wire in conduit for all remote sensors. G. All water treatment systems shall be tested in accordance with the latest applicable industry standards. PART 3 - EXECUTION 3.01 CLEANING, TESTING AND ADJUSTING A. Cleaning and Testing of Piping 1. During construction, properly cap all lines, so as to prevent the entrance of sand, dirt, etc. Each system of piping shall be blown through after completion (for the purpose of removing grit, dirt, sand, etc., from coils and piping), for as long a time as required to thoroughly clean the apparatus. Bypass arrangements shall be provided at all coils and equipment such that water can be circulated through all mains during the flushing and cleaning of the system. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-337 HVAC Issued for Construction 1 June 2004 2. Only water with corrosion inhibitors added may be used for hydrostatic testing. The inhibitor levels shall be maintained until systems are ready for cleaning and passivation. 3. All piping, etc., shall be tested, prior to application of insulation, by hydrostatic pressure at least 1-1/2 times the maximum operating pressure (but not less than 700 kPa) for a sufficiently long time (minimum four [4] hours) to detect all leaks and defects and after testing shall be made tight in an approved manner. If necessary, piping shall be taken down and reassembled as no makeshift method of temporarily repairing leaks, etc., shall be permitted. 4. Apply a chemical cleaning operation to interior of all piping for all water and steam systems to remove and dissolve foreign substances. This shall be done under the supervision of the Contractor. Provide all necessary tappings, piping and valves required for the installation and injection of water treatment equipment and chemicals. Valving, piping and fittings shall be in accordance with the requirements of the respective system pressures. All chemicals required for cleaning and initial treatment of systems shall be provided under this Section. 5. After the piping system has been properly cleaned as indicated above, the piping systems shall be operated for a minimum of three days with surgical felt bonded to baskets on each pump strainer. These felt filters shall be removed and replaced as required and the systems shall be run as long a time as necessary to thoroughly clean all piping until approved by the Engineer's representative. All systems provided with flushout connections, as indicated on the drawings, shall be operated during this cleaning operation with all coil and equipment valves closed. 6. It is to be specifically noted that the work under this Section shall not be accepted until it is free of foreign matter to the satisfaction of the Engineer. Repair or replace free of additional charge any and all control valves or other system components which do not function properly because of imperfect cleaning of any piping system. Replace any materials rusted, corroded, or otherwise damaged due to improperly operating and maintaining the installation without charge, prior to the acceptance by the Engineer. 7. Piping shall be tested in sections where directed by the Contractor, in order to permit construction to proceed. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-338 HVAC Issued for Construction 1 June 2004 B. Cleaning and Leakage Testing of Ductwork 1. The open ends of all unfinished sections of ductwork, including fan outlets, tappings for air outlets, etc., shall be properly capped at all times during construction, unless the particular section of ductwork is actually being worked on. 2. The requirement for capped duct openings shall continue until white plastering or equivalent finishing operations in the building are completed. 3. If the above requirements have not been strictly enforced during the construction period, cover all air outlets with cheesecloth and blow out the duct system to the satisfaction of the Engineer. 4. The leakage testing of medium and low pressure ductwork shall comply with the following: a. Air testing during erection shall include separate leakage air tests of each complete and/or partial air riser, each completed and/or partial horizontal distribution system, and, after all ductwork is installed and central station apparatus is erected, leakage testing of the pressure side of the whole system up to the inlet of the variable air volume boxes. It is the intent of the Specifications that ductwork shall be tested in sections, if required, or as directed by the Contractor in order to permit work of other Trades to proceed. b. Tests shall be made prior to insulation of system being tested -- using suitable test equipment, including "U" tube, orifice, tubing and cocks, arranged to indicate the amount of air leakage. c. The leakage test of the Class “A” sealed medium rectangular and conduit ductwork upstream of VAV boxes shall be made with pressure in the ductwork maintained at approximately 1,000 Pa., obtained by operation of the air supply fan or, if the fan cannot be operated, by use of the test blower(s). Leakage test of the low pressure, Class “A” sealed ductwork shall be made with pressure maintained at approximately 750 Pa. of water gauge. All joints shall be inspected and checked for leakage, by means as directed, and total leakage shall be limited to a maximum of 1% of the total system design cfm. Even if a duct section passes the leakage test, all audible leaks shall be sealed. Test procedure shall be in accordance with the test procedure Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-339 HVAC Issued for Construction 1 June 2004 outlined in SMACNA "HVAC Air Duct Leakage Test Manual”, First Edition, 1985. d. Leakage Class Ductwork Type Round Round Rectangular Rectangular 3.02 3 3 6 6 The maximum allowable leakage rates for ductwork between the fan discharge and the inlet to the VAV boxes is as follows: Construction Class (in. W.G.) 4 3 4 3 Allowable Leakage Rate Positive Integral Test (cfm/100 Pressure (in. sq.ft. of tested duct surface W.G.) area) 4 7.5 3 6.0 4 14.5 3 12.0 TESTING, ADJUSTING AND BALANCING A. Related Documents: Drawings and general provisions of Contract, including General Conditions and General Requirements, apply to work of this Section. B. Codes: The work shall comply with all federal, state and local Codes, AABC, NAAB, OSHA and ASHRAE standards. C. Documents 1. Sample report forms for all tests performed shall be submitted and approved prior to commencement of tests. Refer to Paragraph E. of this Specification for precise requirements. 2. Before commencing with the balancing of the systems, submit for approval the name of the Professional Engineer under whose direct field supervision the adjustments specified shall be made. The submission shall also include the methods and instruments proposed to be used to adjust and balance the systems. Data for instrumentation shall include the date of last calibration. 3. Submit single-line diagrams of each duct system indicating all terminal outlets and terminal boxes identified by number. Data sheets shall list all such outlets denoted by the same numbers, including the outlet size, "K" factor, location, cfm and jet velocity. Submit this data for all supply, return and exhaust air systems. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-340 HVAC Issued for Construction 1 June 2004 D. 4. Fan Characteristic Charts: Submit four characteristic curve charts for each fan. Characteristic curve charts shall be not less than 215 mm. by 275 mm. and shall show the static pressure, capacity, horsepower and overall efficiency for operating conditions from no load to 130% of specified load. 5. Air Terminal Devices: Submit performance characteristics for VAV (constant/variable) boxes, grilles, registers and diffusers, packaged chilled water air conditioning units. 6. Submit single-line diagrams for water systems indicating all coils, pumps, heat exchangers. Include flow rate, pressure drop and temperature differentials. 7. Pump Characteristic Charts: Submit four (4) characteristic curve charts for each chilled water, condenser water and fuel oil pump. Charts shall be not less than 215 mm. by 275 mm. showing head developed, efficiency and power required for varying capacities at the operating speeds of the equipment. Test Preparation and Procedure 1. The Balancer shall review the design drawings and shop drawings and shall walk-through the project when the HVAC systems are 30% and 90% complete and submit a written report highlighting any perceived problems. 2. Initial startup shall be performed by this Subcontractor. Prior to any tests, check the rotation and running amperage of all pump and fan motors to prevent damage to equipment by overload. 3. After the installation of each system has been completed, make all required adjustments in the Engineer's presence to balancing valves, air vents, pumps, air dampers, registers, variable volume boxes, fans, humidifiers, etc., until all performance requirements are met. During all such periods of adjustment prior to the date of acceptance of the heating, ventilating and air conditioning systems by the Engineer, this Subcontractor shall operate all equipment. During all such periods of adjustment after the date of acceptance of the heating, ventilating and air conditioning systems by the Engineer, the Engineer's maintenance personnel shall operate all equipment. 4. Preliminary balancing may be done prior to completion of systems; however, final balancing must be done with systems completely installed and operational. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-341 HVAC Issued for Construction 1 June 2004 E. 5. All piping systems should have been completely filled and vented, and all strainers cleaned by this Subcontractor prior to balancing. 6. New, clean filters must be installed in all supply systems by this Subcontractor prior to balancing. 7. Record and submit the total outside air and minimum outdoor air quantities after final adjustments. 8. All main air ducts shall be traversed, using a pitot tube and manometer. The manometer shall be calibrated to read two significant figures in all velocity pressure ranges. The intent of this operation is to measure by traverse the total air quantity supplied by the fan and to verify the distribution of air to zones. 9. Submit data in support of all fan deliveries by the following methods: a. Summation of the air quantity readings at all outlets. b. Duct traverses of main supply ducts. c. Verification of airflow quantities at the air volume sensors at the inlet to each VAV box. 10. Inspect all fan scrolls and remove objects or debris. Inspect all coils and remove debris or obstructions. Verify that all dampers and fire dampers are open. 11. Submit daily progress reports of test and balance work indicating any problem areas. Copies of deficiencies shall be transmitted to the Contractor and Engineer. 12. Mark all settings made during system balancing. Report Forms 1. Submit reports on all tests performed. Prior to commencing testing and balancing work, sample copies of all test forms and detailed descriptions of the test procedures (specific for each component and system being tested) shall be submitted for approval. In all cases, indicate the nominal or specified value. Indicate test date and technician name on all tests. Individual tests shall be prefaced with a general report of the system or equipment being tested. As a minimum, forms and tests shall include the following information. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-342 HVAC Issued for Construction 1 June 2004 2. Title Page a. b. c. d. e. f. g. h. i. 3. Instrument List a. b. c. d. e. f. 4. Instrument. Manufacturer. Model. Serial number. Range. Calibration Date. Air Moving Equipment a. b. c. d. e. f. g. h. i. j. k. l. m. n. 5. Company name. Company address. Company telephone number. Project name. Project location. Project Engineer. Project Engineer. Project Subcontractor. Project altitude. Location. Manufacturer. Model, size. Airflow (l/s), specified and actual. Outside airflow, specified and actual. Static pressure (external and total) - Pa, specified and actual. Inlet pressure. Discharge pressure. Fan rpm, specified and actual. Maximum tip speed - m/s. Outlet velocity - m/s. Fan motor data. Static pressure profile indicating pressure drops across all filters, coils, eliminators, dampers, etc. V-belt drive data. Electric Motors a. b. c. d. e. f. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Manufacturer. KW/BKW, specified and actual. Phase, voltage, hertz, amperage (each phase leg), FLA; nameplate, actual, no load. RPM. Service factor. Starter size, rating, heater elements. 15000-343 HVAC Issued for Construction 1 June 2004 6. V-Belt Drive a. b. c. d. 7. Duct Traverse a. b. c. d. e. f. g. h. i. j. 8. System zone/branch. Duct size. Area. Design velocity. Design airflow. Test velocity. Test airflow. Duct static pressure. Air temperature. Air correction factor. Air Distribution Tests a. b. c. d. e. f. g. h. i. j. 9. Driven sheave, diameter and rpm. Belt, size and quantity. Motor sheave, diameter and rpm. Center to center distance, maximum, minimum, and actual. Air terminal number. Room number/location. Terminal type. Terminal size. Area factor. Design velocity. Design airflow. Test (final) velocity. Test (final) airflow. Percent of design airflow. Variable Air Volume Boxes a. b. c. d. e. f. g. h. i. j. k. l. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Manufacturer. Type, constant, variable. Identification/number. Location. Model. Size. Minimum static pressure. Minimum design airflow. Maximum design airflow. Maximum actual airflow. Inlet static pressure. Flow coefficient. 15000-344 HVAC Issued for Construction 1 June 2004 All readings taken shall be separate and independent of the control devices. 10. Pumps a. b. c. d. e. f. g. h. i. j. k. l. m. n. o. p. q. 11. Factory-Assembled and Packaged Air Conditioning Units a. b. c. d. e. f. g. h. i. j. k. l. m. n. o. 12. Identification/number. Manufacturer. Size/model. Impeller size. Service. Design flow rate (l/s), pressure drop, brake kw, motor kw. Actual flow rate, pressure drop, brake kw, motor kw. Discharge pressure. Suction pressure. Total operating head pressure. Shutoff, discharge and suction pressures. Shutoff, total head pressure - kPa. (Plot this value on pump curve as a verification of impeller size.) Head at final, adjusted flow - kPa. NPSH. Motor data, specified and actual. Pressure drop across each balancing valve (constant speed pumps) - feet of fluid being pumped. Speed (rpm). Identification/number. Location. Manufacturer. Model. Design sensible capacity and actual sensible capacity. Design latent capacity and actual latent capacity. Design total capacity and actual total capacity. Entering d.b. air temperature, design and actual. Leaving d.b. air temperature, design and actual. Waterflow, design and actual. Water pressure drop, design and actual. Entering water temperature, design and actual. Leaving water temperature, design and actual. Motor data, specified and actual. V-belt drive data. Chilled Water Cooling Coil Data a. b. c. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Identification/number. Location. Service. 15000-345 HVAC Issued for Construction 1 June 2004 d. e. f. g. h. i. j. k. l. m. n. 13. Heat Recovery Coil Data a. b. c. d. e. f. g. h. i. j. k. l. m. n. 14. Identification/number. Location. Service. Manufacturer. Airflow, design and actual. Entering air d.b. temperature, design and actual. Entering air w.b. temperature, design and actual. Leaving air d.b. temperature, design and actual. Leaving air w.b. temperature, design and actual. Waterflow, design and actual. Water pressure drop, design and actual. Entering water temperature, Design and actual. Leaving water temperature, design and actual. Air pressure drop, design and actual. Electric Heating Coil Data a. b. c. d. e. f. g. h. i. j. k. l. 15. Manufacturer. Airflow, design and actual. Entering air d.b. temperature, design and actual. Entering air w.b. temperature, design and actual. Leaving air d.b. temperature, design and actual. Leaving air w.b. temperature, design and actual. Waterflow, design and actual. Water pressure drop, design and actual. Entering water temperature, Design and actual. Leaving water temperature, design and actual. Air pressure drop, design and actual. Identification/number. Location. Service. Manufacturer. Airflow, design and actual. Number of stages. Kw/stage. Total kw input. Electrical characteristics, volts, phase, hertz. Entering air temperature, design and actual. Leaving air temperature, design and actual. Air pressure drop, design and actual. Flow Measuring Station a. b. c. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC Identification/station. Location. Size. 15000-346 HVAC Issued for Construction 1 June 2004 d. e. f. g. h. i. j. 16. Manufacturer. Model. Design flow rate. Design pressure drop. Actual/final pressure drop. Actual/final flow rate. Station calibrated setting. Duct Leak Test (Witnessing of Test Only) a. b. c. d. e. Description of ductwork under test. Duct design operating pressure. Duct design test static pressure. Maximum allowable leakage duct capacity times leak factor. Test Apparatus: 1) 2) 3) 4) 5) 6) 7) F. Blower. Orifice, tube size. Orifice size. Calibrated. Test static pressure. Test orifice differential pressure. Leakage. Water Balance 1. Record the data required for the report forms (Paragraph E.) for all pumps and pump motors installed at the project. Follow the AABC National Standards for balancing hydronic systems. 2. Pumps and piping systems shall be balanced by the adjustment of plug cocks, globe valves or other control devices to obtain the flow quantities indicated on the design drawings. Balancing shall be done with all controls set for full-flow through coils. A sufficient quantity of automatic throttling valves shall be in the full-open position or full-closed position to simulate design diversity. All automatic three-way valves shall have the bypass port closed. System shall be balanced to insure design flow to the most hydraulically remote equipment. 3. Balance and record the waterflow and pressure drops through all chillers, condensers, cooling towers, coils, balancing valves, packaged air handling units, etc., in accordance with design requirements. 4. For all orifice plates record the pipe size, orifice size, flow factor, required differential pressure, final differential pressure and calculated final flow quantity. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-347 HVAC Issued for Construction 1 June 2004 G. 5. For all Venturi type, flow tube, pitot tube, or other flow measuring devices, record the pipe size, manufacturer and size of device, the direct reading or the differential pressure, and calculated final flow. 6. Flow shall be balanced through all equipment and coils by means of pressure drop and calibrated flow control valves. Obtain curves from the various manufacturers indicating the relationship between flow and pressure drop through the coils and equipment. Readings shall be taken on calibrated test gauges. Submit curves with the final report. 7. Upon completion of the water balance, reconcile the total heat transfer through all coils and heat exchangers by recording the entering and leaving water temperatures and the entering and leaving air dry bulb and wet bulb temperatures along with water and air quantities. 8. Upon completion of balancing, adjust differential bypass valves. 9. Where pump impellers are required to be trimmed to produce no more than 110 percent of their scheduled flow with the discharge valve wide open, this Subcontractor shall establish the new impeller size and submit this data with the balancing reports. 10. Check that all air vents are installed and operating. Air Balance 1. All fan systems shall be operated for as long a time as shall be necessary to test airflow from all openings, make all necessary damper and other adjustments until air quantities required at each outlet or inlet as shown are obtained throughout the various systems. Balance all air systems to obtain design air quantities at the least static pressure. Follow the AABC National Standards for balancing air systems. 2. Fans and duct systems shall be completely balanced to obtain the air quantities indicated on the design drawings by the adjustment of sheaves, controllable or adjustable pitch blades, air valves, dampers, registers and other volume and diverting control devices. All final adjusted air quantities shall be within 10% of the design requirements. Verify static pressure control and fan tracking with controllable pitch and variable frequency drives in VAV systems. Follow the approved manufacturers standards for balancing DDC VAV boxes. 3. If, to balance air in system, a fan speed other than that provided should be required, necessary changes shall be made in V-belt drive. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-348 HVAC Issued for Construction 1 June 2004 H. 4. Submit single line diagrams of all duct systems indicating all terminal outlets and terminal boxes identified by number. Data sheets shall list all such outlets denoted by the same numbers, including the outlet size "K" factor, location, cfm and jet velocity. Submit this data for all supply, return and exhaust air systems. 5. Outside air dampers shall be adjusted to deliver the correct air quantity at all damper positions. Record and submit the outside air temperatures for both cycles after final adjustments. 6. During this testing period, make all necessary settings and adjustments of temperature regulating equipment with the assistance of the various control manufacturer(s) and/or installer(s). Miscellaneous 1. Submission of certified tests shall in no way relieve fulfillment of the guarantee provided by this Subcontractor. 2. The automatic control systems and fire detection systems shall be properly adjusted and left in good working condition. 3. Verify that overload heaters installed in motor starters are properly sized for the motors they serve. 4. Verify that all motors, pumps, fans, compressors, etc., have been properly lubricated and left ready for operation. 5. All gauges, instruments, thermometers and meters shall be checked and tested. Notify both the Engineer and Contractor of deficiencies. 6. All alarms (BMS, equipment, etc.) shall be tested to fulfill satisfactory operating conditions. Verify proper operation of electrical safety interlocks, damper sequencing, smoke control operation, Hi/Lo limit switches and freezestats. Spot check (minimum 5% of all locations) space temperature control using hand-held temperature readings as part of the seven (7) day test described in Paragraph I. 7. Allow sufficient time to perform all tests, adjustments, etc., necessary to place the various systems in final operation condition, verify performance requirements and check all safety devices. Labor, instruments, etc., required for various tests shall be provided. See that all manufacturers' representatives necessary to check and adjust various systems are present with sufficient labor to perform all this work without delay. All test Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-349 HVAC Issued for Construction 1 June 2004 data shall be recorded on suitable forms and submitted to the Engineer for approval. I. 8. Unless otherwise specified, equipment shall be adjusted in accordance with manufacturers' recommendations to function properly with capacities required and/or specified. 9. The Balancing Subcontractor shall be responsible for witnessing the duct leakage tests and submitting a written report. Final Acceptance 1. The Engineer and/or the Engineer's representatives shall make final check of all systems only after the balancing agency has completed and returned to the Engineer or Engineer's representatives all recorded test data, together with letter that his work is to the best of his knowledge 100% complete. Field performance tests shall be required by the Engineer and/or the Engineer's representatives at this time to verify performance and workmanship, and to make final system component adjustments. 2. Points and areas for recheck shall be selected by the Engineer's representative. 3. Measurements and tests shall be same as the original test-andbalance procedures. 4. Specific and random selections for recheck shall not normally exceed 15% of the total number tabulated in the report, except where special air systems require a complete recheck for safety reasons. 5. If random tests demonstrate a measured flow deviation of 10% or more from that recorded in the certified test-and-balance report, the report shall automatically be rejected. In the event the report is rejected, all systems shall be readjusted and tested, new data recorded, a new certified test-and-balance report submitted and a new inspection test made, all at no additional cost to the Engineer. 6. After satisfactory passing of the field tests and after all necessary adjustments have been made, test the complete systems for a minimum of seven (7) days under regular operating conditions or as long as may be required to establish compliance with Contract Documents. Randomly check values recorded during final balancing of air and water systems. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-350 HVAC Issued for Construction 1 June 2004 3.03 INSTALLATION OF PIPING A. All piping shall be properly supported or suspended on stands, clamps, hangers, etc., of approved design and make as directed. Supports shall be designed to permit free expansion and contraction while minimizing vibration. Pipes shall be anchored where shown or directed by means of steel clamps, or other approved means, securely fastened to the pipe and rigidly attached to the building construction. Riser heels shall have capped dirt pockets. B. Screw threads shall be cut clean and true; screw joints shall be made tight without caulking and without red or white lead. No bushings shall be used. All reductions shall be made with eccentric reducers or eccentric fittings. All pipe 50 mm. and less shall be reamed out after cutting to remove all burrs. C. The drawings indicate generally the size and location of piping, and while sizes must not be decreased, the right is reserved to change runs and sizes of pipes in order to accommodate conditions at the job. Any pipes not shown on plans shall be of sizes as directed, and run where directed. Pipework shall conform fully to the following requirements: 1. Piping shall be properly graded to secure easy circulation and prevent noise and water hammer. Steam piping and steam condensate return piping shall pitch 25 mm. in 6 meters; water piping shall pitch 25 mm. in 18 meters. Steam and steam condensate return piping shall pitch downward in direction of flow. Water piping shall pitch upward in direction of flow. Dirt pockets with valved outlet with hose adapter shall be provided at all riser heels, low points, and other places where dirt and scale may accumulate. Proper provision shall be made for expansion and contraction in all portions of pipework, to prevent undue strains on piping or on fixtures or apparatus connected therewith. 2. Approved screw unions, with steel or bronze bodies and ground brass taper or spherical joints, shall be installed at traps, instruments, etc., and wherever else required, to permit easy connection and disconnection. 3. Steam Mains: To meet conditions at the job, steam mains shall set up (with drip connections to return lines), at any points where so directed, to save headroom, clear other pipes, etc. Steam mains shall be kept as high as possible. All piping shall be arranged to secure free venting at ends of mains without permitting ingress of air. 4. Return and Drip Mains: All low pressure and drips shall gravitate to receiver of condensate pump or condensate cooler. Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-351 HVAC Issued for Construction 1 June 2004 D. 5. Riser branches and other offsets shall be made up with 4-elbow swings. This shall also apply to copper risers and branches. 6. To meet job conditions, water supply and return mains shall be set up and down where so directed; in any such case, drain cocks shall be provided at low points and vent traps at high points -with vent connections extended to nearby points of disposal as directed. 7. Vent connections shall be provided at all high points, connected to expansion tanks or to air traps, or to valve blowoffs, as shown or directed. Where valve blowoffs are used, valves are to be installed no higher than 2 meters above finished floor. Automatic air and vent traps of the ball float type shall be installed at all high points of chilled water system and be installed with copper drain lines piped to nearest funnel drain. Provide a manual shutoff valve ahead of all vents. 8. Alterations: If, after plant is in operation, any coils do not circulate quickly and noiselessly (due to trapped or airbound connections), make proper alterations in these defective connections. If connections are concealed in furring, floors or ceilings, bear all expense of tearing up finished construction, and refinish, leaving same in as good condition as before it was disturbed. 9. Pipe Nipples: Any piece of pipe 75 mm. in length or less shall be considered a nipple. All nipples shall be extra heavy. Close nipples shall not be used. 10. All piping connections to coils and equipment shall be made with offsets provided with screwed or flanged unions so arranged that the equipment can be serviced or removed without dismantling the piping. Unions shall not be directly screwed to coil header piping connections. 11. Connections from headers to pump suction and discharge piping shall be made with laterals. Connections from overhead piping to the inlet and discharge of pumps shall be made with reducing elbows, and connections from horizontal headers shall be made with eccentric reducers. Provide protective pans under or over individual pipes passing high voltage electrical bus duct, transformer and switchgear equipment, motor control centers, motor starter racks, telephone equipment, or other electrical equipment. The pans shall be constructed of 3.6 mm. steel with a 150 mm. lip, the corners being welded to make the pans watertight. Each pan shall be given three coats of Rust-Oleum paint and shall be supported by pipe hangers. The pan shall drain clear of the bus Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-352 HVAC Issued for Construction 1 June 2004 duct or electrical or telephone equipment. Where pans are above piping, they shall be designed to serve as a deflector plate. Pans over bus duct and electrical or telephone equipment shall be sized to fully protect equipment. Pans over electrical equipment shall be not less than 2.0 meters from equipment. END OF SECTION Museum of Islamic Art Doha, Qatar Z:\worldox\docs\122690\spc\00015619.DOC 15000-353 HVAC Issued for Construction 1 June 2004 1) Consists of pressure switches, freezestats, and life safety alarms. 2) Refer to Description of Operation for quantity of all systems. System A/C Units (Each) Atrium Gallery (1st Floor) Gallery (2nd, 3rd, and 4th Floors) Auditorium 5th Floor Administration Restaurant Education Wing Basement Refrigeration Plant Mechanical Room and Generator Room Air Conditioning Unit Jaros, Baum & Bolles 1 June 2004 Minimum Outside Air Damper Return Air Damper Supply Fan Variable Frequency Drive - Speed Control Cooling Coil Valve Return Fan Variable Frequency Drive - Speed Control Zone Duct Heaters (Each) Unit Heat Recovery Coil Three Way Valve Duct Heat Recovery Coil Three Way Valve Notes: Supply Fan - High Suction Pressure Supply Fan - High Discharge Pressure Supply Fan Variable Frequency Drive - Malfunction Supply Fan Variable Frequency Drive Status - Inverter Supply Fan Variable Frequency Drive - Bypass Return Fan - High Suction Pressure Return Fan High Discharge Pressure Return Fan Variable Frequency Drive - Malfunction Return Fan Variable Frequency Drive Status - Inverter Return Fan Variable Frequency Drive Status - Bypass Supply Fan Status - Via Current-Sensing Relay Return Fan Status - Via Current-Sensing Relay Heat Recovery Pump Status Kitchen Makeup Damper Open/Close Purge Outside Air Damper Supply Fan - Start/Stop Supply Fan Safety Stop (Note No. 1) Purge Exhaust Dampers Supply Fan Discharge Damper - Open/Close Return Fan - Start/Stop Return Fan Safety Stop (Note No. 1) Return Fan Override Start (Life Safety) Return Fan Discharge Damper - Open/Close Supply Floor Isolation Dampers Return Floor Isolation Dampers Heat Recovery Coil Pump Start/Stop Outside Air Flow (Minimum) Supply Air Flow Supply Van Variable Frequency Drive - Speed Feedback Return Air Humidity Supply Air Discharge Temperature Space Temperature (Each Zone) Supply Air Static Pressure - High Limit Supply Air Static Pressure - Riser or Duct Indoor Air Quality (See Note 2) Return Air Flow Return Fan - Variable Frequency Drive Speed Feedback Return Air Temperature ● Required Points Inputs ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●● ● ● ● ● ● ● ● ● BMS POINT MATRIX MUSEUM OF ISLAMIC ARTS DOHA, QATAR DIGITAL Outputs ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●● ● ●● ● ●● ● ●● ●●●● ● ●● ● ●● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● Inputs ANALOG ● ● ● ● ●●●● ● ●●●● ●●●●●● ●●●●●● ● ●●●● ● ●●●● ● ●●●● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●● ●● ● ●● ●● Outputs ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●● ●● ● ● ● ● ●● ● ● ● Appendix A-1 Worldox: 00015622.XLS BMS POINT MATRIX MUSEUM OF ISLAMIC ARTS DOHA, QATAR DIGITAL ANALOG Jaros, Baum & Bolles 1 June 2004 ● ● ● ● ● ● ● ● Inputs Space Temperature VFD Speed Feedback CO Concentration Start/Stop Floor Exhaust Isolation Damper Group Per Floor System Toilet Exhaust Fans (each) General Kitchen Exhaust Fans (each) Mechanical Room Air Conditioning Units (each) Basement and Mechanical Equipment Room Smoke Exhaust Fans (each) Kitchen Exhaust Fans (each) Smoke Exhaust Fans Constant Speed (each) Smoke Exhaust Fans Variable Speed (each) Truck Dock/Garage Exhaust Fans (each) Carbon Monoxide System Refrigerant Leak Detection System Outputs Status VFD Common Alarm VFD Drive System - Invertor VFD Drive System - Bypass Threshold Limit Value (TVL) Short-Term Exposure Limit (STEL) Emergency Exposure Limit (EEL) Failure Relay Inputs Outputs VFD Speed Control Chilled Water Valve ● Required Points ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● Appendix A-2 Worldox: 00015622.XLS Jaros, Baum & Bolles 1 June 2004 Inputs Outputs Chilled Water Valve Control System Switchgear Room, Telephone Equipment Room, ●● Mechanical Equipment Room, and Elevator Machine Room Chilled Water Cooled A/C Units (each) Weather Station Emergency Generator Room Exhaust Fan ● Fuel Oil Tank and Pump Room Exhaust Fan ● ● Vent Dampers (Stairway, Hoistway and Shafts - each) Outputs Space Temperature Outdoor Air Temperature Outdoor Air Humidity Outdoor Air CO2 1) One detector per 100 sq.ft. 2) Provide 50 digital outputs. ANALOG Start/Stop Damper (Open/Close) Notes: Run Status Leak Alarm (A/C Unit External Drip Pan) Alarm Status ● Required Points BMS POINT MATRIX MUSEUM OF ISLAMIC ARTS DOHA, QATAR DIGITAL Inputs ● ● ● ●●● ● ● Appendix A-3 Worldox: 00015622.XLS BMS POINT MATRIX MUSEUM OF ISLAMIC ARTS DOHA, QATAR ● Required Points DIGITAL Inputs ANALOG Outputs Inputs Outputs Jaros, Baum & Bolles 1 June 2004 Damper Control Electric Reheat Control System Fan-powered VAV Boxes (each) (REMOVE) Fan-powered VAV Boxes with Reheat (each) (REMOVE) VAV Boxes (each) VAV Boxes with Reheat (each) CV Boxes (each) CV Boxes with Reheat (each) Space Temperature Air Flow Fan Status (REMOVE) 1) One transmitter per room. Fan Start/Stop (REMOVE) Notes: ● ● ● ● ● ● ● ● ● ● ● ● ● Appendix A-4 Worldox: 00015622.XLS Fuel Oil Tank No. 1 - High Level Fuel Oil Tank No. 1 - Low Level Fuel Oil Tank No. 1 - Extreme Low Level Fuel Oil Tank No. 2 - High Level Fuel Oil Tank No. 2 - Low Level Fuel Oil Tank No. 2 - Extreme Low Level Fuel Oil Pump Set No. 1 FOP-1 - Malfunction Fuel Oil Pump Set No. 1 FOP-2 - Malfunction Fuel Oil Tank No. 1 - Supply/Return Isolation Valves Closed Fuel Oil Tank No. 2 - Supply/Return Isolation Valves Closed Emergency Generator No. 1 Supply Isolation Valve Closed Emergency Generator No. 2 Supply Isolation Valve Closed Emergency Generator No. 3 Supply Isolation Valve Closed Emergency Generator No. 1 - Supply Solenoid Valve Closed Emergency Generator No. 2 - Supply Solenoid Valve Closed Emergency Generator No. 3 - Supply Solenoid Valve Closed Firematic Isolation Valve Closed (Transfer Pump Room) Firematic Isolation Valve Closed (Generator Room) Firematic Valve Closed (Diesel Fire Pump Room) Fuel Oil System Isolation Valves Misaligned Fuel Oil Pump Set No. 1 FOP-1 Relief Valve Actuation Fuel Oil Pump Set No. 1 FOP-2 Relief Valve Actuation Fuel Oil Pump Set No. 1 FOP-1 Inlet/Discharge Valves Closed Fuel Oil Pump Set No. 1 FOP-2 Inlet/Discharge Valves Closed Duplex Strainer-Fuel Oil Pump Set No. 1 FOP-1 High Differential Duplex Strainer-Fuel Oil Pump Set No. 1 FOP-2 High Differential Fuel Oil Outer Pipe Containment Leak (Base of Riser) Fuel Oil Outer Pipe Containment Leak (Pump Room) Fuel Oil Outer Pipe Containment Leak (Generator Room) Fuel Oil Outer Pipe Containment Leak (Fire Pump Room) Fuel Oil Tank Vault - Leak Fuel Oil Day Tank - High Water Level Fuel Oil Day Tank Basin - Leak Fill Sump Tank - High Level Fuel Oil Transfer Pump Room (Leak Detector in Room) Each PLC Malfunction Fuel Oil Tank No. 1 High Water Level Fuel Oil Tank No. 2 High Water Level Fuel Oil Tank No. 1 Instantaneous Level Fuel Oil Tank No. 2 Instantaneous Level Diesel Fire Pump Isolation Valve Closed Diesel Fire Pump Day Tank - Supply Solenoid Valve Closed Fuel Oil Pump Set No. 1 - Run Status (Each Pump) Diesel Fire Pump Day Tank - Low Level Diesel Fire Pump Day Tank - High Level Diesel Fire Pump Day Tank - Leak Diesel Fire Pump - Contaminant Leak (Pump Room) Diesel Fire Pump Room - Leak ● Required Points Qty System Fuel Oil System BMS POINT MATRIX MUSEUM OF ISLAMIC ARTS DOHA, QATAR DIGITAL Inputs ●●●●●●●●●●● ● ●●●● ● ● ● ● ● ● ●●●●●●●●●●●●●●●●●●●●●●●●●● Jaros, Baum & Bolles 1 June 2004 Appendix A-5 Worldox: 00015622.XLS Notes: 1. Provide control of floor exhaust isolation dampers for fans which serve more than one floor. Refer to Specification for description. System Life Safety Interface/Smoke Control System Jaros, Baum & Bolles 1 June 2004 Elevator EMR/Hoistway Smoke Detector Fire Alarm (each service EMR/Hoistway) Common Fire Alarm (Atrium) Common Fire Alarm (Restaurant) Common Fire Alarm (Gallery) Common Fire Alarm (Auditorium) Common Fire Alarm (5th Floor Administration) Common Fire Alarm (Education Wing) Common Fire Alarm (Basement) Discharge Smoke Detector Activation (Each Supply Fan) Smoke Exhaust Fan On - Via SCP (Each Fan Utilized for Smoke Exhaust) Smoke Exhaust Fan Off - Via SCP (Each Fan Utilized for Smoke Exhaust) Floor Exhaust Isolation Damper - Open - Via SCP (Each Floor) (Note 1) Floor Exhaust Isolation Damper - Close - Via (Each Floor) (Note 1) Fireman's Override Key Enable A/C Unit Shutdown (Each System) Supply Fan Status at Smoke Control Panel (Each Fan) Return Fan Status at Smoke Control Panel (Each Fan) Smoke Exhaust Fan Status at Smoke Control Panel (Each Fan) Floor Return Isolation Damper Open/Close (Per Floor) (Note 1) Floor Return Isolation Damper Status (each floor) (Note 1) BMS POINT MATRIX MUSEUM OF ISLAMIC ARTS DOHA, QATAR ● Required Points Inputs DIGITAL Outputs Inputs ANALOG Outputs ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● Appendix A-6 Worldox: 00015622.XLS Failure During Flow Test Excess Water in Fuel Water Storage Tank Full Strainer Dirty Filter Dirty Leakage Into System Drip Pan Leakage Into Water Secondary Container Loss of Flow, Filtration Cycle Additive Tank Empty ● Required Points System Central Fuel Oil Filt. and Dewatering System Jaros, Baum & Bolles 1 June 2004 BMS POINT MATRIX MUSEUM OF ISLAMIC ARTS DOHA, QATAR DIGITAL Inputs ●●●●●●●●● Appendix A-7 Worldox: 00015622.XLS Jaros, Baum & Bolles 1 June 2004 Inputs ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● Pan Water Temperature (each cell) Common Supply Water Temperature Common Return Water Temperature Condenser Water Supply Temperature Upstream of Chillers Variable Frequency Drive Feedback (each) Condenser Water Return Temperature Chilled Water Supply Temperature Flow (gpm) (common per system) System Differential Pressure (Per Riser) Total Dynamic Head Across Header Chilled Water Return Temperature Secondary CHW Supply Temperature Condenser Water Return Temperature Secondary Condenser Water Supply Temperature Common Heat Recovery Supply Water Temperature Common Heat Recovery Return Water Temperature Heat Recovery System Flow Meter (each) Variable Frequency Drive Speed Control Temperature Bypass Valve Minimum Flow Valve Supply Water Reset Start/Stop (each) Safety Stop (each) Motorized Valve Open Command (each valve) Motorized Valve Closed Command (each valve) System Cooling Tower (3 cells) CW Pumps (each) CHW Pumps (each) Electric Drive Chillers (each) Heat Recovery Coil Water System Status (each) Variable Frequency Drive - Inverter (each) Variable Frequency Drive - Bypass (each) Variable Frequency Drive - Malfunction (each) High Water Level (each cell) Low Water Level (each cell) Vibration Alarm (each fan) Motorized Valve Open Indication (each valve) Motorized Valve Closed Indication (each valve) Common Alarm Expansion Tank High Pressure Expansion Tank Low Pressure Heat Recovery Expansion Tank High Level Alarm Heat Recovery Expansion Tank Low Level Alarm ● Required Points BMS POINT MATRIX MUSEUM OF ISLAMIC ARTS DOHA, QATAR DIGITAL Outputs ANALOG Inputs ● ● ● ● ● ● ● ● ● Outputs ● ● ● ● ● ● ● ● ● Appendix A-8 Worldox: 00015622.XLS BMS POINT MATRIX MUSEUM OF ISLAMIC ARTS DOHA, QATAR DIGITAL Inputs Outputs ANALOG Inputs Outputs Common Alarm Run Status Failure to Run Blown Fuse Indication (Note 4) Ground Fault Interruption (Note 3) Open Indication (Note 4) Closed Indication (Note 4) ATS Connected to Emergency ATS Connected to Normal ● Required Points Electrical Monitoring Diesel Generator (Each) Automatic Transfer Switch (Each) Jaros, Baum & Bolles 1 June 2004 ●●● ●● Appendix A-9 Worldox: 00015622.XLS Domestic Water Pumps Pump Failure (Each) Domestic Water Pumps Low Pressure (Each) Domestic Hot Water Heater High Temperature (Each) Domestic Hot Water Heater Low Temperature Alarm (Each) Expansion Tank Make-Up Pump Run Status Expansion Tank Low Water Level Alarm ● Required Points Qty. System Miscellaneous Plumbing Alarms Jaros, Baum & Bolles 1 June 2004 BMS POINT MATRIX MUSEUM OF ISLAMIC ARTS DOHA, QATAR DIGITAL Inputs Inputs ANALOG Outputs ●●●●●● Appendix A-10 Worldox: 00015622.XLS