Grounding Transformer Specially engineered to provide fault detecting and voltage control in deltaconnected systems like wind farm medium-voltage networks: • Provide low impedance ground path by maintaining the neutral at or near ground potential • Limit the magnitude of transient over-voltages when re-striking ground faults occur • Provide a source of ground fault current during line to ground faults • Provide power to a secondary load, if desired No other manufacturer has the experience and knowledge that PCT has for this truly engineered solution. Contact your PCT representative and provide the following information: Available Fault Current _______________________A Fault Duration _______________________________Seconds Continuous Neutral Current ___________________A Ohms Per Phase (or % Z)______________________ Configuration: Padmount or Substation Zig Zag or Wye/Delta StylePadmount or Substation Range Sized by requirement Temperature Rise 55°C, 65°C, 55/65°C, or as specified (75°C, consult factory) Primary 34.5 kV or as specified Secondary As Specified Winding MaterialCopper Winding Types Circular Layer Core Types Mitered Step Lap (Cruciform or Rectangular) Stacked Fluids Mineral Oil (Type II), Silicone, Envirotemp FR3, Luminol, Alpha 1 Standard Features: • Magnetic Liquid Level Gauge (ANSI 71) • Oil Temperature Gauge (ANSI 26) • Pressure/Vacuum Gauge • No-Load Tap Changer (when required) • Pressure Test and Upper Filter Press (1” connection) • Corrosion Resistant Nameplate • Provisions for Jacking and Lifting • Base Suitable for Rolling or Skidding • Drain and Sampler Valve • Pressure Relief Valve Optional Features: • Current Transformers • Contacts on Standard Gauges • Pressure Relief Device • Winding Temperature Gauge (ANSI 49) • Sudden Pressure Rise Relay (ANSI 63) • Seal in Relay (ANSI 63X) • Lightning Arresters • Stainless Steel Construction Design/Application Considerations: • Zig Zag • Wye/Delta