Medium Voltage Products NPS modular outdoor switch disconnectors Operating, maintenance and recycling This common document is applicable to all versions of NPS modular outdoor switch disconnectors. Detailed mounting instructions for each type are included in the delivery. Designation: The basic NPS pole element is a disconnector. It can be upgraded to limited purpose switch disconnector (according to IEC standard) by adding optional breaking elements. Breaking chambers (630A breaking capacity) fulfill all requirements of general purpose switch disconnector except short-circuit making capacity, which is less than the rated peak withstand current of the disconnector element, but more than necessary in most rural overhead line applications. In some cases designation switch or load-break switch is adopted from spoken language. WARNING HAZARDUS VOLTAGE CAN SHOCK, BURN, OR CAUSE DEATH. Do not attempt to handle, install, use or service this product before reading instruction this document. Safety Notices Must always follow the directions in the manual and good engineering practice. Dangerous voltage can cause electric shock and burns. – Do not perform any activity described in this document with the switch energized. – ALWAYS follow your company’s or country’s Safety procedures before performing any work on this equipment. – NPS outdoor switch disconnector should be installed only within the design limitation. – All the activities listed on this document it must be performed with the switch completely de-energized, isolated, grounded and out of service. – Must be observed appropriate guidance given in the manuals for all operations performed on the apparatus. – This product is intended to be installed, operated and maintained by qualified personel, thoroughly trained and knowledgeable with the regards of the hazards involved. This publication is written only for such qualified persons and is not intended to be a substitute for adequate training and experience in the safety procedures for this device. Warning Detailed descriptions of standard repair procedures, safety principles, and service operations are not included. It is important to note that this document contains some warnings and cautions against some specific service methods that could cause personal injury to service personnel, or could damage equipment or render it unsafe. These warnings do not cover every conceivable method in which service (whether or not recommended by ABB) may be performed. Secondly, ABB cannot predict or investigate all potential hazards resulting from all conceivable service methods. Anyone using service procedures or tools, whether or not recommended by ABB, must satisfy himself thoroughly that neither personal safety nor equipment safety will be jeopardized by the service method or tools selected. All information contained in this manual ris based on the latest product information available at the time of printing. The right is reserved to make changes at any time without notice. NPS modular outdoor switch disconnectors Operating, maintenance and recycling Operation Application NPS switch disconnectors are intended for medium voltage overhead lines. Typical functions are: – To make a safe isolating distance between live parts and the working object. All criteria of IEC publication 62271‑102 (2001) are fulfilled: increased withstand voltage, visible isolating distance, eventual leakage current is led away to earth, and locking options. All safety procedures shall be followed: ensure the load current does not exceed the breaking capacity, open disconnector, use voltage detector, connect earthing device, lock the disconnector, and use the warning shield. The risk of eventual back feed shall be eliminated. – To isolate faulty network portions and restore other portions. – Fault localizing by closing against fault. The maximum fault current at the location shall be known and specified fault making capacity of the switch shall not be exceeded. See more details in chapter: Application limitations. – Isolating distribution transformers. Transformer voltage Breaking current Max. transformer of the whips power [kV] [A] [kVA] 10 40 690 15 32 830 20 25 866 Other applications are possible, if the specified switch ratings are not exceeded. Application limitations – The rated load breaking current and number of breaking operations, together with the rated short-circuit making current and number of making operations, is given for each type in the NPS brochure. NPS is not suitable for fault breaking and frequent load control. – Ambient conditions – The ice-breaking class is 5 mm for motor operated switches and 10…20 mm for manually operated switches. A heavier ice layer may prevent normal operation. – Ambient temperature –40 … +40 °C versions with porcelain and silicone insulators –50 … +40 °C versions with epoxy resin insulators Contact the manufacturer for higher ambient temperatures. Higher ambient temperatures are possible for lower rated currents. – Pollution – The creepage distance of standard insulators is sufficient to cover the requirements of IEC 60815 for pollution classes II-IV depending on the rated voltage and insulator type. Detailed information about available creepage distance is given in NPS brochure. 2 NPS modular outdoor switch disconnectors – Altitude – The type tested ratings are valid up to 1000m altitude. Correction factors for higher altitudes are given in IEC publication 60694 (1996) Fig.1. Sometimes it is necessary to select a switch for a higher rated voltage, but in many cases it is possible to accept a minor reduction of withstand voltages. In that case the risks can be minimized by using lightning arresters. Operation under different fault conditions – The fault (short-circuit or earth fault) shall be cleared by a circuit breaker before opening the disconnectors or switch disconnectors. – NPS_ switches can be closed against fault if the specified shortcircuit making current is not exceeded. The making capacity depends on the closing speed in case of a disconnector with breaking whips or breaking chambers NPAK4 (250A). Manual closing shall be fast and determined (operating time 1,2 s). The control cabinet should be equipped with fast operating motor drive (operating time 1,2 s). The operator shall be protected against eventual sparking. Breaking chambers NPAK5 have an internal spring device and the making capacity is independent of the operating speed. Manual operation The disconnector shall be operated in one continuous determined movement. Speed is important when closing against a fault. The required operating force is higher under ice conditions. The manual operating device shall be always locked to prevent unauthorized operation. After opening ensure complete opening of breaking elements. After closing ensure fully closed position and that the hook of the breaking whips is caught behind the whips. During manual operation it is easy to detect the eventual need of adjustment and maintenance. See chapter „maintenance”. Control cabinets The motor is operated by push-buttons behind the door or by remote control system. Manual operation is possible by a hand crank, which is stored behind the door. Detailed instructions in 34 UEMC 35_ manual. Also the motor operating device shall be padlocked in open position if safe isolation is required. Remote control and local automation applications The main purpose of remote control and local automation systems is to reduce outage times by fast isolating and restoring operations. Normal safety procedures shall not be forgotten, if a safe isolating distance is needed for maintenance or repair actions. Earthing and application of the operating rod insulator For safety reasons, the mounting crossarm (beam) of the switch disconnector must always be earthed. Concerning earthing practices and application of the eventual operating rod insulator, the local safety regulations and IEC publication 61936‑1 shall be followed. Line connections the line conductor direct also to the moving terminal. The following issues shall be observed: – The cable and connector may be mechanically stressed by the operation movement. A loose connection or broken conductor strand may result from frequent operations in the worst cases. – A thick cable or inflexible cable routing may increase the required operating force. These risks can be reduced by the following application guide: Line Recommended connection < 50 mm2 overhead line Direct connection possible < 100 mm 2 overhead line Hinged terminal recommended on the > 100 mm2 overhead line Third insulator set recommended rocking side Earth cable Flexible dropper recommended Transformer connection Flexible extension bar The mm2 limits above are informative only. The function is strongly affected by the flexibility, length and routing of the jumper cable. The clearances may be changed during operation. This risk can be reduced by sufficient tolerances or by using insulated jumper cables. Minimum clearances basing to IEC publication 61936‑1: – 12 kV 150 mm, – 24 kV 220 mm, – 36 kV 360 mm (200 kV). The minimum clearance across open contacts is based on type tests and is given for each type in the mounting instructions. The line connector shall be selected based on conductor material and size. See Enclosure 1. for details. Maintenance In most cases manual switches are operated so seldom that scheduled maintenance is not economically feasible. Operating staff should observe the function during operation and report to maintenance staff if necessary. Adjustment can also be made when the switch is operated. Reliable operation is a primary requirement for remote controllable switches and regular maintenance should be arranged. Preventive maintenance Manual switches with breaking whips Action Lubrication of main contacts Visual inspections: Frequency Notes 5 years or if special need observed Only if the line is dead for other reasons 3-5 years during normal operation Adjustment of closed position Some overtravel in closed direction needed Breaking whip function The hook is caught behind the whip in closed position Breaking whip condition Replace, if broken or badly deformed Condition of the operating rod insulator (if any) Replace, if damaged Condition of the insulators Clean if excessive pollution layer observed Crossarm fixing Tighten, if moving during operation Earthing cable Measurement of the earthing resistance Repair mechanical damages, loose or corroded connections (6 years) According to local safety codes NPS modular outdoor switch disconnectors 3 NPS modular outdoor switch disconnectors Operating, maintenance and recycling Motor operated switches and switches with breaking chambers Action Lubrication of the main contacts and operating arm/lever of the breaking chamber Inspection of the mechanical operation of the breaking Frequency Notes 3-5 years 3-5 years Operating arm and lever are in line, the switch reaches normal end positions chamber 5 years Eventual signs of oil leakage Inspection of control rod adjustment Visual inspection oil the oil chamber NPAK2 3-5 years Some overtravel in closed position needed, see mounting instructions Breaking whips function and condition 3-5 years The hook is caught behind the whip in closed position. Replace broken or Crossarm fixing 5 years Tighten, if moving during operation Condition of the operating rod insulator (if any) 5 years Replace, if damaged. Composite type NPSZJ 30 recommended for this 5-10 years 3 years Clean if excessive pollution layer observed badly deformed whips. application. Condition of the insulators Earthing cables Measurement of the earthing resistance Lubrication of the mechanism Inspection and replacement of batteries (6 years) According to local safety codes 5 years See control cabinet manual 34 UEMC 35 As needed See control cabinet manual 34 UEMC 35 Electrical and mechanical endurance – The mechanical endurance of NPS disconnectors and load break switches with chambers is at least 2000 no-load operations. There is no need to replace parts due to mechanical wear in normal applications. – Electrical endurance – Breaking whips: – 100 breaking operations specified max. breaking current (25 A/24 kV, 40 A/12 kV) – Breaking chamber NPAK 4: – 100 breaking operations 250 A mainly active load – Breaking chamber NPAK 5: – 100 breaking operations 400 A mainly active load – 10 breaking operations 630 A – 50 making operations 8 kA (peak) or 2 making operations 10 kA (peak) – 10 making operations 12,5 kA (12 kV) Repair All disconnector components can be replaced using standard hand tools. A damaged breaking chamber should be replaced or sent to ABB for repair. 4 NPS modular outdoor switch disconnectors Repair mechanical damages, loose or corroded connections Spare parts Switch type Part Current path, complete with 24 kV 24 kV 36 kV epoxy insulators silicone or porcelain insulators silicone insulators NPSZC 2 NPSZC 1 NPSZC 1 NPSZJ 21 (replaces NPSZJ 20) NPSZJ31 – silicon insulator silicon insulators NPSZJ32 NPSZJ 1 standard – normal creepage and NPSZJ33 contacts Insulator Operating rod insulator NPSZJ 2 long increased creepage NPTOE3 „black” NPTOE 3 „black” NPSZJ 30 NPSZJ30 composite NPSZJ 30 composite Breaking whips (3 pcs) NPAB 1/3 NPAB 1/3 Breaking chambers (complete NPAK 4/3 NPAK 41/3 3 pcs set with brackets)) NPAK 5/3 NPAK 5/3 Oil for NPAK 2 breaking NPAB 4/3 Transformer oil, for example Neste Trafo10X chamber Contact grease Spark gap Hinged terminal MOBILUX EP2 MOBILUX EP2 NPAP 4/3 for epoxy insulators only NPAP 3/3 for porcelain insulators only OJUPZL 9/3 OJUPZL 9/3 Grease for motor operating MOBILUX EP2 Isoflex Topas NCA52 (Klueber) device Instructions for recycling the product Introduction Environmental regulations vary from country to country and develop fast. These instructions are informative only. The appropriate current local regulations shall be followed at the time of recycling. Packaging The switch elements are packed in corrugated cardboard boxes. The cardboard can be recycled. Sometimes the boxes are wrapped in transparent polyethylene foil, which may be recycled, or disposed of together with normal waste. The operating rods and mounting crossarms are normally not packed. To avoid pollution due to unnecessary transportation, the manufacturer will not accept used packaging. Recycling has to be arranged locally according to local instructions. NPS modular outdoor switch disconnectors 5 NPS modular outdoor switch disconnectors Operating, maintenance and recycling Materials of the product Part Material Weight kg/pc Phase element NPS 24kV, epoxy resin insulators and silicon insulators normal creepage Base Insulator Current path Breaking whip Whip support + hook Hot dip galv. steel 2.4 Epoxy resin, silica filler 1.6 Copper, tin and silver plating 0.76 Stainless steel 0.05 Hot dip galv. steel 1.1 /phase Hot dip galv. steel 4; 5 – for silicon insulators Porcelain 3.9; Phase element NPS 24kV, porcelain insulators and silicon Base Insulator Insulator caps Current path Breaking whip Whip support + hook silicon rubber 6 Aluminium alloy 2 x 0.2 Copper, tin and silver plating 1.2 Stainless steel 0.05 Hot dip galv. steel 1.1 Hot dip galv. steel 4; 5 – for silicon insulators Phase element NPS 36kV, porcelain and silicon insulators Base Insulator Porcelain 8 silicon rubber 9 for normal creepage distance version and 8 for increased creepage disnatce version Insulator caps Current path Aluminium alloy 2 x 0.2 Copper, tin and silver plating 1.2 Stainless steel 0.05 Hot dip galv. steel 1 Housing Epoxy resin, silica filler 2.05 Arc extinguishing sheets Polyacetal resin (POM) 0.15 Operating lever Stainless steel 0.05 Shaft + bushing Aluminium alloy 0.26 Moving contact Stainless steel 0.15 Breaking whip Whip support + hook Breaking chamber NPAK 4 (dry) Fixed contact Contact tips Springs Copper, silver plating 0.2 Tungsten copper 0.01 Stainless steel 0.1 Copper 0.23 Hot dip galv. steel 1 Housing Epoxy resin, silica filler 2.05 Arc extinguishing sheets Polyacetal resin (POM) 0.15 External arc control Brackets + operating arm Breaking chamber NPAK 5 (dry) Operating lever Stainless steel 0.3 Shaft+bushing Aluminium alloy 0.26 Moving contact Copper, silver plating 0.18 Fixed contact Copper, silver plating 0.2 Tungsten copper 0.01 Contact tips Springs Operating arm Brackets 6 NPS modular outdoor switch disconnectors Stainless steel 0.1 Copper and Hot dip galv. steel 1.1; 2.2 Hot dip galv. steel 0.5 Part Material Weight kg/pc Mounting accessories and manual operating device Crossarm Hot dip galv. steel 20 Operating shaft+lever Hot dip galv. steel 6.9/11.9 Angular supports Hot dip galv. steel 8.5 Operating rods Hot dip galv. steel 12 Rod supports Hot dip galv. steel 1.0 Polyacetal resin (POM) 0.25 Silicon rubber, glasfiber composite, aluminium 0.65 Hot dip galv. steel 4 Operating rod insulator NPTOE3 NPSZJ30 Handle Recycling The product can be dismantled by hand or crushed mechanically. No special tools are required for dismantling manually. In case of dismantling, the parts can be sorted, for example, in the following way: – steel, – stainless steel, – aluminium, – copper, – insulators and breaking chamber housings, – transformer oil, – others. The aluminium caps of porcelain insulators can be separated by melting the sulphur cement at 110…150 °C or by crushing. In case of mechanical crushing the parts may be sorted by special machines. Parts including hazardous materials (e.g. transformer oil) shall be removed manually before crushing. Enclosure Line connections Copper connectors: – Check that the conductor area fits the connector being used and tighten to the correct torque. Aluminium connectors: – Ensure that the conductor area and material fits the connector type being used. The solid aluminium bar shall be left in the empty slot, if a double slot connector (type KG_) is used for a single conductor. The oxidized surface of the conductor end and the grooved bottom of the connector shall be removed by a steel brush and the surfaces greased immediately with a special grease formulated for aluminium connections to prevent reoxidation. The slots of KG_ connectors are greased by the manufacturer. – Tighten to the correct torque. – Recommended greases: ENSTO type SR1, ABB DSAX-RK, PENETROX-A. Directory of potentially hazardous material and problem waste Note! The aluminium oxide layer increases contact resistance and may cause dangerous overheating. Part Oil breaking chamber Damaging material Note Transformer oil*) Problem waste Eventual residues of Problem waste contact grease**) (grease only)) (NPAK2) Copper parts *) oil chambers never are never more in ABB offer however can still be exploited, **) contact grease MOBILEX EP2. NPS modular outdoor switch disconnectors 7 Conductor material and area Bolt size/torque OJUZLL1/3 Cu 16…63 mm2 M8 20 Nm NPTL 24/3 Al 62…90 mm2 M8 20 Nm 2 x Al 16…70 mm2 M8 20 Nm 2 x Al 50…240 mm2 M10 40 Nm Cu 10…95 mm2 M10 40 Nm max. 20 max. 42 Connector type preceding instructions depending on the conductor type. Leave the solid aluminium bar in the aluminium slot, if only copper conductor is connected. (42) (36) (45) (50) max. 20 (45) max. 42 (42) OJUZLL 3/3 (KG6.1) (36) max. 42 (50) OJUZLL 4/3 (KG43) max. 20 max. 42 Cu (50) (36) (50) (36) KG 36 Al 50…240 mm2 Al Al For more information please contact: ABB Sp. z o.o. Branch in Przasnysz 59 Leszno St 06-300 Przasnysz, Poland Phone: +48 29 75 33 000 Fax: +48 29 75 33 327 www.abb.pl (42) Cu (45) Al (42) (45) max. 20 Al Cu Cu We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB. © Copyright 2012 ABB All rights reserved 3405PL518-W1-en. Edition 02.2012 Combined connector for aluminium and copper (KG36) Note which slot is for copper (a force-fit tin plated copper bar will be found inserted into the slot for copper conductors). Follow the