160901-Electrical Machines-III Electrical Engineering PRACTICAL MANUAL On Electrical Machine-III(160901) AT Shankersinh Vaghela Bapu Inst. Of Tech. VASAN,GANDHINAGAR B.E. Semester 6th (ELECTRICAL ENGINEERING) Year 2014 BY Prof. Lokin Joshi , Electrical Department Prof. Rachana Patel , Electrical Department Page | 1 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering INDEX SR. NO. NAME OF EXPERIMENT 01 TO FIND THE REGULATION OF ALTERNATOR BY DIRECT LOADING. 02 TO FIND THE REGULATION OF ALTERNATOR BY PERFORMING EMF METHOD AND MMF METHOD. 03 TO DETERMINE THE POTIER REACTANCE AND VOLTAGE REGULATION OF 3 PHASE ALTERNATOR BY ZERO POWER FACTOR METHOD . 04 TO PLOT V & INVERTED V CURVES OF A SYNCHRONOUS MOTOR. 05 06 07 08 DATE PAGE NO. SIGN DETERMINE SHORT CIRCUIT RATIO OF ALTERNATOR TO STUDY THE SYNCHRONIZATION AND PARALLEL OPERATION OF ALTERNATOR USING SYNCROSCOPE. TUTORIAL -1 TUTORIAL -2 Page | 2 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering Date: …../…../………. EXPERIMENT NO:-01 AIM:- TO DETERMINE VOLTAGE REGULATION OF 3 PHASE ALTERNATOR BY DIRECT LOADING APPARATUS Sr.no 1 Name of apparatus Ammeter 2 3 Voltmeter Rheostat 4 Load Range 0-5amp.AC 0-1amp.DC 0.300V AC 400 ohms.1.7 Amp 1000 Ohms.1.2 Amp Qty 01 No. 01 No. 01No 01No 01No THEORY: The voltage regulation of an Alternator is defined as the change in terminal voltage from no-load to load condition expressed as a fraction or percentage of terminal voltage at load condition ; the speed and excitation conditions remaining same. For Alternator with small power rating, voltage regulation can be easily determined by direct loading test. In this test alternator is actually loaded by 3 phase load and for that load, percentage regulation can be determine.this method gives real value of regulation.But most of the Alternators are manufactured with large power rating , hundreds of kW or MW, and also with large voltage rating upto 33kV. For Alternators of such power and voltage ratings conducting load test is not possible. Hence other indirect methods of testing are used and the performance like voltage regulation then can be predetermined at any desired load currents and power factors. NAME PLATE DETAIL D.C MOTOR ALTERNATOR Page | 3 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering CIRCUIT DIAGRAM: PROCEDURE: 1) Connect the circuit as shown in the diagram. 2)Keep load zero, set field potential divider to zero output voltage position. 3) Keep field resistance of motor to its minimum value. 4) Start the motor with the help of starter. 5) With the field rheostat of motor adjust the speed to synchronous value. 6) Switch on DC supply of field (Alternator) and adjust the potential divider so that the voltmeter reads rated voltage of the alternator. Note this voltage as no load (E). 7) Increase the load in steps till rated current of alternator and note the different sets of readings. 8) Keep speed constant during all the readings with the help of motor field rheostat.. PRECAUTIONS 1) All connections should be perfectly tight and no loose wire should lie on the work table. 2) Before switching ON the dc supply , ensure that the starter’s moving arm is at it’s maximum resistance position. 3) Do not switch on the supply, until and unless the connection are checked by the teacher 4) Avoid error due to parallax while reading the meters. 5) Hold the tachometer with both hands steady and in line with the motor shaft so that it reads correctly. Page | 4 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering OBSERVATION: E = Terminal voltage at no load = Sr. No. Load current Terminal voltage Vt volts. % Regulation CALCULATIONS: % Regulation = ( ) × 100 RESULT: MODEL GRAPH Page | 5 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering CONCLUSION: DISCUSSION: 1) Give the classification of alternator on the basis of rotor and their application? 2) Mention disadvantages of determining the regulation of alternator by direct loading? 3) What is hunting in Alternator? Page | 6 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering Date: …../…../………. EXPERIMENT NO:-02 AIM: TO FIND REGULATION OF A THREE-PHASE ALTERNATOR BY EMF AND MMF METHOD APPARATUS REQUIRED:Sr.no 1 2 3 Name of apparatus Ammeter Voltmeter rheostat Range 0-5amp.AC 0-1amp.DC 0.300V AC 400 ohms.1.7 Amp 1000 Ohms.1.2 Amp Qty 01 No. 01 No. 01No 01No 01No THEORY: A synchronous machine is an ac machine whose speed under steady-state conditions is proportional to the frequency of the current in its armature. Nearly, all the generators in power stations are synchronous machines. Some of the important performance characteristics of the alternator are; The open circuit characteristic (the open-circuit voltage vs. the field current). The short circuit characteristic (the armature short circuit current vs. the field current). To determine the performance characteristics of the synchronous generator some tests are performed such as the open circuit and the short circuit tests. Then, the equivalent circuit of the alternator is determined. The compounding curves are important curves as they give clear idea about the required field control range to regulate the alternator voltage. NAME PLATE DETAIL D.C MOTOR ALTERNATOR Page | 7 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering CIRCUIT DIAGRAM: Page | 8 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering PROCEDURE: [A] OPEN CIRCUIT TEST 1) Connect the circuit as shown. 2) Set potential divider to zero output position and motor field rheostat to minimum value. 3) keep TPST switch 3) Switch on dc supply and start the motor. 4) Adjust motor speed to synchronous value by motor field rheostat and note the meter readings. 5) Increase the field excitation of alternator and note the corresponding readings. 6) Repeat step 5 till 10% above rated terminal voltage of alternator. 7) Maintain constant rotor speed for all readings. [B] SHORT CIRCUIT TEST 1) Connect the circuit as shown. 2) Star the motor with its field rheostat at minimum resistance position and the potential divider set to zero output. 3) Adjust the motor speed to synchronous value. 4) Increase the alternator field excitation and note ammeter readings. 5) Repeat step 4 for different values of excitations (field current). Take readings up to rated armature current. Maintain constant speed for all readings 6) Measure the value of armature resistance per phase Ra by multimeter or by ammeter-voltmeter method. 7) Plot the characteristics and find the synchronous impedance. PRECAUTIONS: 1) All connections should be perfectly tight and no loose wire should lie on the work table. 2) Before switching ON the dc supply , ensure that the starter’s moving arm is at it’s maximum resistance position. 3) Do not switch on the supply, until and unless the connections are checked by the faculty 4) Avoid error due to parallax while reading the meters. 5) Hold the tachometer with both hands steady and in line with the motor shaft so that it reads correctly. 6) Ensure that the winding currents do not exceed their rated values. Page | 9 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering OBSERVATIONS: Rotor speed = -------------------- RPM (constant) Alternator armature resistance per phase Ra=------------Ohm Sr. No O.C TEST Field urrent Terminal voltage I (Amp) Per phase (Vo) Sr. No. S.C TEST Field f current (IF) Short circuit current(Isc) DETERMINATION OF STATOR ARMATURE RESISTANCE(Ra) SR.NO V(Volt) I(amp) Rdc(Ω) Page | 10 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering CALCULATIONS: (i) EMF Method: OA Vo1 Synchronous impedance Zs = ---------= ----------for field current Isc1. OB Isc1 Isc1 is selected over the linear part of OCC, generally it corresponds to rated armature current. Synchronous reactance, Xs = √ (Zs2 - Ra2) Calculate the excitation emf Eo and voltage regulation for full-load and 1. 0.8 lagging p.f. 2. Unity power factor 3. 0.8 leading p.f. Eo = √[(V cosØ+ Ia Ra)2 + (V sin Ø+ Ia Xs)2] + sign is for lagging pf load. - sign is for leading pf load. V = rated terminal voltage per phase of alternator % Voltage Regulation= (Eo-V) / V x 100 (ii) MMF Method: From the OC and SC characteristics determined from OC and SC tests the field currents If1 and If2 are determined to give rated voltage V on no-load (neglecting armature resistance drop) and cause short-circuit current, equal to full load current, on short-circuit. If1 gives full load rated voltage and If2 gives demagnetizing ampere-turns at full load. Total field current If is: = ( ) +( ) ± ( Where, + sign is for lagging pf load. - sign is for leading pf load. − ) Read E0 (No load phase voltage from OCC curvecorresponding to total field current If % = ( − ) × Page | 11 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering RESULT: EMF Method: Regulation of alternator at full load is found to be, At unity pf = -------------At 0.8 lagging = ---------------At 0.8 leading = -------------Synchronous Impedance varies for different values of excitation. MMF Method: Regulation of alternator at full load is found to be, At unity pf = -------------At 0.8 lagging = ---------------At 0.8 leading = -------------MODEL GRAPH: CONCLUSION: Page | 12 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering DISCUSSION: 1. What is armature reaction effect? 2. What are the advantage and disadvantage of estimating the voltage regulation of an alternator by EMF method? 3. When is the regulation negative and why? 4. Why is EMF method called Pessimistic method? 5. Why is MMF method called Optimistic method? Page | 13 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering Date: …../…../………. EXPERIMENT NO:-03 AIM: TO DETERMINE THE POTIER REACTANCE AND VOLTAGE REGULATION OF 3 PHASE ALTERNATOR BY ZERO POWER FACTOR METHOD . APPARATUS Sr.no 1 Name of apparatus Ammeter 2 3 Voltmeter rheostat Range 0-5amp.AC 0-1amp.DC 0.300V AC 400 ohms.1.7 Amp 1000 Ohms.1.2 Amp Qty 01 No. 01 No. 01No 01No 01No THEORY: This method is based on the separation of armature leakage drop and the armature reaction effects Hence it gives more accurate results. It makes use of (i) Open circuit characteristics and (ii) zero power factor were also called wattless load characteristic. It is the curve of terminal volts against excitation which the armature is delivering full load at zero power factors. By using the two characteristics the potier triangle can be found out. From the potier triangle the armature reaction mmf and armature leakage reactance or the Potier reactance can be determined by combining these two values the total Voltage induced E0 can be calculated. The synchronous machine is run at rated synchronous speed by a primemover. A purely inductive load is connected across the armature terminals and the field current is increased till full load armature current is flowing. The load is then carried in steps and field current is adjusted to maintain full load armature current.The armature terminal voltage and field current are recorded at each step to get point “A” short circuit the output terminal of alternator. Vary the excitation to get rated current flowing through armature. NAME PLATE DETAIL D.C MOTOR ALTERNATOR Page | 14 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering CIRCUIT DIAGRAM:- PROCEDURE: TO PLOT OCC Plot the characteristics between open circuit voltage and field current . TO PLOT ZPF Connect the circuit diagram as shown in figure. Start the motor and run it at synchronous speed. Vary the inductive load in steps and adjust the field current to a value till full load armature current is flowing. Every time note down the field current and the terminal voltage of alternator. SHORT CIRCUIT TEST Connect the circuit as shown. Star the motor with its field rheostat at minimum resistance position and the potential divider set to zero output. Adjust the motor speed to synchronous value. Increase the alternator field excitation and note ammeter readings. Repeat step 4 for different values of excitations (field current). Take readings up to rated armature current. Maintain constant speed for all readings Measure the value of armature resistance per phase Ra by multimeter or by ammetervoltmeter method. Plot the characteristics and find the synchronous impedance. Page | 15 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering TO GET STARTING POINT OF ZPF (i) Connect the circuit diagram as shown in figure. (ii) Start the motor and run it at synchronous speed. (iii) Vary the field excitation to get rated current flowing through armature. Note down this value of field current. A) OCC: Sr.No Voltage Field Current IF Armature current(IA) Field Current IF B) SCC: Sr.No C) ZPF: Sr.No Voltage Field Current RESULTS: Sr.no CosØ sinØ Field Current (If) Voltage (E0) % Reg Page | 16 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering MODEL GRAPH CONCLUSION: DISCUSSION QUESTIONS:1. What is additional effect taken in to account using potier reactance? 2. What are advantages of ZPF method? 3. What is necessity for predetermination of Voltage regulation? Page | 17 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering Date: …../…../………. EXPERIMENT NO:-04 AIM: TO PLOT V & INVERTED V CURVES OF A SYNCHRONOUS MOTOR. APPARATUS:Sr.no 1 Name of apparatus Ammeter 2 3 Voltmeter rheostat 4 Power factor meter Range 0-10amp.AC 0-2amp.DC 0.600V AC, 0-300V DC 400 ohms.1.7 Amp 1000 Ohms.1.2 Amp 600V, 10A Qty 01 No. 01 No. 01No 01No 01No 01No THEORY:If the armature current is plotted versus field current for several power levels, the regulating plots are the motor V-curves shown in Figure. The points marked a, b, and c on the upper curve correspond to the operating conditions (underexitation, normal exaitation, and overexaitation) the lagging power factor operation is electrically equivalent to an inductor and the leading power factor operation is electrically equivalent to a capacitor. Leading power factor operation referred to as synchronous condenser or synchronous capacitor operation. Typically, the synchronous machine Vcurves are provided by the manufacturer so that the user can determine the resulting operation under a given set of conditions. Page | 18 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering NAME PLATE DETAIL SYNCHRONOUS MOTOR CIRCUIT DIAGRAM: PROCEDURE:1) Make the connections as shown in circuit diagram. 2) Adjust the field rheostat of DC generator at maximum position, the potential divider at zero output position and the load at off condition. 3) Switch on the 3-ph. supply, start the synchronous motor and let it run at its rated speed. 4) Switch on the DC supply and adjust the generator field current to a suitable value so that it generates rated voltage. Page | 19 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering 5) Increase the alternator field current and note down corresponding power factor and armature current covering a range from low lagging to low leading power factor through a unity power factor. Note that armature current is minimum when the p.f. in unity. 6) Repeat step No.5 for some constant load on the Generator. OBSERVATIONS:[A] AT NO LOAD Sr.No If Power factor Ia Sr.No If Power factor Ia [B] AT LOAD GRAPH: Plot the curves between (i) Armature current (Ia) vs field current (If) (ii) Power factor (cosØ) vs field current (If) MODEL GRAPH: Page | 20 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering CONCLUSION: DISCUSSION: Page | 21 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering Date: …../…../………. EXPERIMENT NO:-05 AIM: TO FIND SHORT CIRCUIT RATION (SCR) OF ALTERNATOR APPARATUS REQUIRED Sr.no 1 Name of apparatus Ammeter 2 3 Voltmeter rheostat Range 0-5amp.AC 0-1amp.DC 0.300V AC 400 ohms.1.7 Amp 1000 Ohms.1.2 Amp Qty 01 No. 01 No. 01No 01No 01No THEORY: The ratio of the field current required to generate rated voltage on open circuit required to circulate rated armature current during short circuit is termed as short-circuit ratio (SCR). The short-circuit ratio is also the reciprocal of the per unit value of the saturated synchronous reactance. The short-circuit ratio of a generator is a measure of the transient stability of the unit, with higher ratio providing greater stability. For lower value of SCR, the value of Xs is more hence the drop IaXs is more. Hence the machine requires large change in field current for small change in load, to keep terminal voltage costant. NAME PLATE DETAIL D.C MOTOR ALTERNATOR Page | 22 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering CIRCUIT DIAGRAM:- PROCEDURE: [A] OPEN CIRCUIT TEST 1) Connect the circuit as shown. 2) Set potential divider to zero output position and motor field rheostat to minimum value. 3) keep TPST switch 3) Switch on dc supply and start the motor. 4) Adjust motor speed to synchronous value by motor field rheostat and note the meter readings. 5) Increase the field excitation of alternator and note the corresponding readings. 6) Repeat step 5 till 10% above rated terminal voltage of alternator. 7) Maintain constant rotor speed for all readings. [B] SHORT CIRCUIT TEST 1) Connect the circuit as shown. 2) Star the motor with its field rheostat at minimum resistance position and the potential divider set to zero output. 3) Adjust the motor speed to synchronous value. 4) Increase the alternator field excitation and note ammeter readings. Page | 23 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering 5) Repeat step 4 for different values of excitations (field current). Take readings up to rated armature current. Maintain constant speed for all readings 6) Measure the value of armature resistance per phase Ra by multimeter or by ammeter-voltmeter method. 7) Plot the characteristics and find the synchronous impedance. PRECAUTIONS: 1) All connections should be perfectly tight and no loose wire should lie on the work table. 2) Before switching ON the dc supply , ensure that the starter’s moving arm is at it’s maximum resistance position. 3) Do not switch on the supply, until and unless the connections are checked by the faculty 4) Avoid error due to parallax while reading the meters. 5) Hold the tachometer with both hands steady and in line with the motor shaft so that it reads correctly. 6) Ensure that the winding currents do not exceed their rated values. OBSERVATIONS: Rotor speed = -------------------- RPM (constant) Alternator armature resistance per phase Ra=------------Ohm O.C TEST S.C TEST Sr. Field Sr. f current Field urrent Terminal voltage No. (IF) No I (Amp) Per phase (Vo) Short circuit current(Isc) GRAPH: Plot the readings to draw following graphs. Use same graph paper for both curves. 1. I f versus Vo (from OC test) f 2. I versus Isc (from SC test) CALCULATIONS: SCR= XS = Page | 24 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering RESULT: SCR =---------------XS =------------------MODEL GRAPH: CONCLUSION: DISCUSSION: Page | 25 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering Date: …../…../………. EXPERIMENT NO:-06 AIM:- TO STUDY THE SYNCHRONIZATION AND PARALLEL OPERATION OF TWO ALTERNATOR USING SYNCHROSCOPE. APPARATUS:Sr.no 1 2 3 4 2 3 Name of apparatus AC Ammeter AC Voltmeter DC Voltmeter DC Ammeter rheostat Synchroscope Range 0-10 Amp 0-500V 0-200V 0-1 Amp 400 ohms.1.7 Amp Qty 6 No 6 No 2 No. 2 No 2 No 1 Nos. THEORY:To connect two alternators in parallel, the two alternators must be synchronized. The synchronization process must be performed also when connecting an alternator to the grid. The purpose of synchronization is to ensure that at the moment of closing the circuit breaker (closing the 3-pole single throw switch to connect the alternator to the grid in this experiment), the voltages across the three phases of the breaker are as close to zero as possible and remain so after the switch is closed. To ensure that, the following conditions must be metch: 1- The generated voltage of two alternator must be approximately equal. 2- The frequency of the two generated voltages must be equal. 3- The phase sequence of the two generated voltages must be the same. 4- The phase of the generated voltages relative to some reference must be very close to the phase of other alternator. These conditions can be understood by considering the voltage of one line of the alternator-1, va1, to be connected to one line of the alternator-2, va2. Suppose Va1 = va1(t) = Vma1 sin (ωa1t + φa1) _____(1) Va2 = va2(t) = Vma2 sin (ωa2t + φa2) _____(2) The voltage across the switch is Va1-Va2. It is obvious that for this voltage to be close to zero and remains close to zero, the above four conditions must be met. In short, the above two voltage waveforms must be on top of each other if seen on the oscilloscope. The voltage Va1Page | 26 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering Va2 can be seen by applying this voltage to a light bulb. The brightness of the bulb is an indication of the voltage across it. When the light bulb is totally dark, the voltage across it is zero. NAME PLATE DETAIL:D.C MOTOR ALTERNATOR CIRCUIT DIAGRAM:- Page | 27 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering PROCEDURE:1) 2) 3) 4) 5) 6) 7) 8) 9) 10) Connect the circuit as shown in the diagram. Keep all the switches in open position and put on the DC supply. Start the DC motor-1 and bring the speed very near to synchronous speed of the alternator. Gradually increase the DC excitation field supply and adjust alternator output voltage to rated voltage. Now repeat step-3 & 4 for Motor-Alternator set-2. Check whether all the conditions for synchronization are satisfied. Now set the switch for synchroscope and observe the rotation of needle. When the needle comes to zero, the phase difference is minimum. Only at an instant when needle is at zero position, close switch to synchronize both alternator to bus. Connect balanced load. Note all the line voltage and current reading for both alternator. OBSERVATIONS: Alternator-1 Field Current IF (Amp) Line voltage (VA) Volt Alternator-2 Line Current IA (Amp) Field Current IF (Amp) Line voltage (VA) Volt Line Current IA (Amp) Without load With Load RESULTS:- Page | 28 Shankersinh Vaghela Bapu Institute of Technology.Vasan 160901-Electrical Machines-III Electrical Engineering CONCLUSION:- DISCUSSION QUESTIONS:1) What are the conditions of synchronization of two alternators? 2) What are the possible effects of wrong synchronization? 3) What are the different methods for synchronization? 5) 6) 7) After synchronizing what is the effect of changing the excitation of the alternators. Why the incoming m/c in parallel operation is operated at slightly higher speed then the synchronous speed during synchronization. In parallel operation of generator, for which condition circulating current develop even no load on the machine. Page | 29 Shankersinh Vaghela Bapu Institute of Technology.Vasan