INSTRUCTION MANUAL IM670-U v0.1 COMPALARM C2C ALARM SYSTEM GENERAL • Compact alarm system, with a basic module of 12 signals • Multiple modules coupling possibility • Easy printing of the alarm points description • Opto-isolated inputs for 5÷250V, NO or NC contacts, which can be set point by point • Signal power free inputs • 7 alarm sequence possibilities according with ISA S 18.1 • Easy and fast programming by dipswitches • ”First out” feature for recognizing the first tripped alarm • ModbusRTU protocol via RS485 serial port • Interconnected systems for Alarm Management, distributed in various units • High safety and reliability The COMPALARM C2C is a very compact and efficient alarm system, suitable for 12 points connection, with NO or NC input contacts and LED signals. This system is supplied in a 96 mm x 96 mm enclosure for flush mounting. An easy alarm’s description printing, easy wiring by plug-in terminals and a good front protection degree, come to complete this attractive alternative. The COMPALARM C2C is being manufactured, in such a way to be capable to ensure an intrinsically safe reading of the inputs. The know how, used in the present instrument, has simplify the circuits up to a maximum, granting a high reliability and safety for avoiding false signals. It has also enabled to have a high immunity degree against external disturbance and signal management with increased voltage capability. The electronic management system allows to program the alarm behavior, according with the ISA S 18.1 standard, so as the inputs and outputs position. INPUTS The COMPALARM C2C has 12 inputs that can be set as NO or NC by dipswitches. All inputs are optoisolated and can be supplied with any voltage between 5 ÷ 250V ac/dc. It has been also foreseen the inputs for acknowledgement, test and reset push buttons. OUTPUTS The outputs are fitted with two voltage free contacts relays. One of them is intended for the acoustic or alarm signaling and the other for a cumulative of alarms (normally excited or diexcited in case of alarm) for process activation approval, in presence of one active alarm (or non resetted yet) at least. The mentioned relay will also react due to a lack of power supply or due to its internal malfunction. INTERCONNECTION WITH OTHER MODULES With the wiring of one cable through other similar devices, it is possible to enlarge the system, which will work as an unique system, in order to grant a correct operation of the various alarm sequences, “first out” function included. In such a case, the outputs can be detected by any of the interconnected modules. PROGRAMMING AND OPERATION Each COMPALARM C2C module accepts up to 12 contacts, with a common pole, either open or closed in a rest position, which can be set for each input by dipswitches, placed behind the alarms description panel. The activation, memory and reset modes can be selected among the 8 most common sequences, according with the ISA 18.1 standard ISA A – ISA M – ISA R8 – ISA M5 – ISA F1A – ISA F1M – ISA F3 A. The mentioned sequences have following basic sequences: ISA A Automatic reset. ISA M Manual reset. ISA R8 Ringback. ISA M5 Signaling like ISA-M, but without flashing, when optical signaling. ISA F1A Automatic reset “first out” with no subsequent alarm state. ISA F1M Manual reset “first out” with no subsequent alarm state. ISA F3A Automatic reset “first out” with first out flashing and reset pushbutton Compalarm C2C instruction manual IM670-U v0.1 pag. 1 / 8 APPLICATION C2c is suitable for connection of 12 inputs from normally open or normally closed contacts. The operating alarm sequences can be easily configured according to ISA specifications. C2c is a compact device, all microprocessor based logic is embedded in the display unit. Alarm status are displayed by means of hi-brightness, maintenance free red led. A printed paper sheet can hold alarm associated text, placed under the front panel polyester foil and retained by an easily removable frame. High reliability, continuous self check, fail safe logic are important features for this device that is more than a simple annunciator and could be used like supervisor. Legend 1 - Alarm Inputs terminal (ac/dc) 6 2 - Ext. Switches Inputs terminal (ac/dc) IN1÷12 R2_NA IN1 3 - Power supply terminal COM B- A+ IN2 R2_C IN1÷12 4 - Extension Line Connection IN3 R2_NC 5 - Output Relays 5 IN4 R1_NA RELAYS 6 - RS485 Serial Communication 1 IN5 R1_C OUTPUTS IN6 R1_NC PUSH BUTTONS IN7 IN8 TEST IN9 RESET IN10 ACK IN11 IN12 C.I. C.I. C.I. 4 EXTN AUX SUPPLY 230V 115V 0V 3 2 OPERATION At power-on or return from power-fail, the alarm system will reach an idle condition i.e. no visual and acoustic signalling. When an input associated contact changes state the alarm system turn from steady to alarm condition, this means that visual devices and horn output follows the pre-set sequence operation. The load output will be disabled until reset. By means of push buttons it’s possible to acknowledge the alarm, silence the horn and reset to normal condition. A specific push button perform the visual device test, without perturbation to normal operation. Operating dip-switched are located under the polyester front foil, retained by removable click-in frame and must be selected before power-on. Before to place the polyester layer is possible to insert a simple paper sheet with alarm text to be visible through the transparent windows. This paper could be written, engraved or printed. Templates are available for easy PC printing. RESET TO FACTORY DEFAULT Press all the three push buttons on the first and, at the same time, switch ON the device. Compalarm C2C instruction manual IM670-U v0.1 pag. 2 / 8 FRONT PANEL Legend 1 - Removable front frame 2 - LED lamp 3 - Transparent window for alarm description 4 - Power ON LED 5 - Push buttons compalarm C2C 1 2 3 4 Power ON Alarm 1 Alarm 7 Alarm 2 Alarm 8 Alarm 3 Alarm 9 Alarm 4 Alarm 10 Alarm 5 Alarm 11 Alarm 6 Alarm 12 ACK RESET TEST 5 Legend 1 - Normally open/close input 1÷8 mode selection 2 - Normally open/close input 9÷12 mode selection 3 - Internal buzzer off/on 4 - Operating sequence selector 5 - LED's light intensity adjust 1 2 3 4 Compalarm C2C 5 instruction manual IM670-U v0.1 pag. 3 / 8 ALARM SEQUENCES The following alarm sequences are available: Sequence A, Automatic Reset Sequence features 1. Acknowledge, Test, and Mute pushbuttons. 2. Audible alarm can be silenced by pressing Mute pushbutton. 3. The audible device is silenced and flashing stops when acknowledged 4. Automatic reset of acknowledged alarm when process conditions return to normal. 5. Operational test. Sequence M, Manual Reset Sequence features 1. Acknowledge, Reset, Test, and Mute pushbuttons. 2. Audible alarm can be silenced by pressing Mute pushbutton. 3. The audible device is silenced and flashing stops when acknowledged 4. Manual reset of acknowledged alarm when process conditions return to normal. 5. Operational test. Sequence M5, Manual Reset with No flashing The visual display flashing feature is deleted. New alarms have the same visual display indication as acknowledged alarms. Compalarm C2C instruction manual IM670-U v0.1 pag. 4 / 8 Sequence R, Ringback Sequence features 1. Acknowledge, Reset, Test, and mute pushbuttons. 2. Alarm and ringback audible devices. 3. Audible alarm or ringback alarm can be silenced by pressing Mute pushbutton. 4. Ringback visual and audible alarm when process conditions return to normal. 5. Manual reset of ringback indications. 6. Operational test. Sequence R, Ringback Sequence features 1. Acknowledge, Reset, Test, and mute pushbuttons. 2. Alarm and ringback audible devices. 3. Audible alarm or ringback alarm can be silenced by pressing Mute pushbutton. 4. Ringback visual and audible alarm when process conditions return to normal. 5. Manual reset of ringback indications. 6. Operational test. Compalarm C2C instruction manual IM670-U v0.1 pag. 5 / 8 Sequence F1A, Automatic Reset First Out with No Subsequent Alarm State Sequence features 1. Acknowledge, Test, and Mute pushbuttons. 2. Alarm audible devices. 3. Audible alarm can be silenced by pressing Mute pushbutton. 4. Flashing and audible indications for first alarm only. New subsequent alarms go to the acknowledge state. 5. First out indication is reset and the audible is silenced when acknowledged. 6. Automatic reset of acknowledged alarm when process conditions return to normal. 7. Operational test. Sequence F1M, Manual Reset First Out with No Subsequent Alarm State Sequence features 1. Acknowledge, Reset, Test, and Mute pushbuttons. 2. Alarm audible devices. 3. Audible alarm can be silenced by pressing Mute pushbutton. 4. Flashing and audible indications for first alarm only. New subsequent alarms go to the acknowledge state. 5. First out indication is reset and the audible is silenced when acknowledged. 6. Manual reset of acknowledged alarm when process conditions return to normal. 7. Operational test Compalarm C2C instruction manual IM670-U v0.1 pag. 6 / 8 Sequence F3A, Automatic Reset First Out with First Out Flashing and Reset Pushbutton Sequence features 1. Acknowledge, First out Reset, Test, and Mute pushbuttons. 2. Alarm audible devices. 3. Audible alarm can be silenced by pressing Mute pushbutton. 4. First out flashing different from subsequent flashing. 5. Fist out Reset pushbutton to change the first out visual indication to be the same as subsequent visual indications. 6. Automatic reset of acknowledged alarm when process conditions return to normal. 7. Operational test. DIMENSIONS Compalarm C2C instruction manual IM670-U v0.1 pag. 7 / 8 TECHNICAL DATA MAIN POWER SUPPLY TYPE Supply voltage 115 or 230 V - 50/60Hz or 85÷265Vac/dc Power consumption 4.5 VA MAX Line fuse (external) 500 mA LOW VOLTAGE SUPPLY TYPE Supply voltage 20÷60Vac/dc Power consumption 4.5 VA MAX Line fuse (external) 1A TERMINALS SCREW AND PLUG TERMINAL BLOCK Operating temperature 0 ÷ 60 °C Storage temperature -20 ÷ 80 °C Relative humidity NON CONDENSING max 95 % Vibration allowed 0.5 G Overall dimensions (DIN43700) 72 x 144 x 65 mm Cut-out dimensions 92 x 92 mm Protection class (DIN VDE0470) IP40 Material Noryl UL V-0 SERIAL INTERFACE (OPTION) Standard RS485 Half-duplex (ModBus protocol) Connector 5.0mm pitch extractible screw terminals Isolation 4KVpeak o 2.5KVRMS – transceiver stage self powered BaudRate 4800 – 9600 – 19200 – 38400 Node-ID 1 ÷ 247 Parity Even – Odd - None Stop bit 1 or 2 Emergency recovery configuration Node 1 – Baud Rate 38400 – no-parity – 1 stop bit Mounting position Any Weight 500 g MAX Text window dimensions 34 x 9 mm Output channels 2 SPDT contacts Max switching voltage 250 Vac Max switching current 5A @ 250V cosj=1 Max switching power 750 VA / 100 W Input channels 12 OPTOCOUPLED Input pushbuttons 4 OPTOCOUPLED Inputs Voltage 24 / 48 / 115 / 230 Vac/dc ± 20% Inputs current 5 mA MAX Extension line 1000 m MAX FOR COMMON SUPPLY SYSTEMS Power-on delay 5s Galvanic separation Inputs | Outputs | Supply Test voltage 2500 V @ 50 Hz, 1 minute Isolation voltage 300 VRMS max EMC Compliance Directive EMC 89/336/EEC Emission EN 50082-1 Immunity EN 50082-2 ETHERNET MODULE (OPTION) Speed 10/100 base T magnetics on-board Connector RJ45 (standard RJ Ethernet connector) Contact the technical assistance or refer at specific document for application don’t described in this manual. NOTE At reason of the evolution of standards and products, the company reserves to modify in every time the features of the product described in this document, that it’s necessary to verify preventively. The liability of the producer for damage caused by defect of the product ”can be reduced or deleted (…) when the damage is caused joint by a defect of product or for blame of the damaged or a person of which the damaged is responsible” (Article 8, 85/374/CEE). Compalarm C2C instruction manual IM670-U v0.1 pag. 8 / 8