COMPALARM C2C ALARM SYSTEM

advertisement
INSTRUCTION MANUAL
IM670-U v0.1
COMPALARM C2C
ALARM SYSTEM
GENERAL
• Compact alarm system, with a basic module of 12 signals
• Multiple modules coupling possibility
• Easy printing of the alarm points description
• Opto-isolated inputs for 5÷250V, NO or NC contacts, which can be set point by point
• Signal power free inputs
• 7 alarm sequence possibilities according with ISA S 18.1
• Easy and fast programming by dipswitches
• ”First out” feature for recognizing the first tripped alarm
• ModbusRTU protocol via RS485 serial port
• Interconnected systems for Alarm Management, distributed in various units
• High safety and reliability
The COMPALARM C2C is a very compact and efficient alarm system, suitable for 12 points connection, with NO or NC
input contacts and LED signals. This system is supplied in a 96 mm x 96 mm enclosure for flush mounting. An easy
alarm’s description printing, easy wiring by plug-in terminals and a good front protection degree, come to complete this
attractive alternative.
The COMPALARM C2C is being manufactured, in such a way to be capable to ensure an intrinsically safe reading of the
inputs. The know how, used in the present instrument, has simplify the circuits up to a maximum, granting a high reliability
and safety for avoiding false signals. It has also enabled to have a high immunity degree against external disturbance and
signal management with increased voltage capability.
The electronic management system allows to program the alarm behavior, according with the ISA S 18.1 standard, so as
the inputs and outputs position.
INPUTS
The COMPALARM C2C has 12 inputs that can be set as NO or NC by dipswitches. All inputs are optoisolated and can
be supplied with any voltage between 5 ÷ 250V ac/dc. It has been also foreseen the inputs for acknowledgement, test
and reset push buttons.
OUTPUTS
The outputs are fitted with two voltage free contacts relays. One of them is intended for the acoustic or alarm signaling
and the other for a cumulative of alarms (normally excited or diexcited in case of alarm) for process activation approval,
in presence of one active alarm (or non resetted yet) at least.
The mentioned relay will also react due to a lack of power supply or due to its internal malfunction.
INTERCONNECTION WITH OTHER MODULES
With the wiring of one cable through other similar devices, it is possible to enlarge the system, which will work as an
unique system, in order to grant a correct operation of the various alarm sequences, “first out” function included. In such a
case, the outputs can be detected by any of the interconnected modules.
PROGRAMMING AND OPERATION
Each COMPALARM C2C module accepts up to 12 contacts, with a common pole, either open or closed in a rest position,
which can be set for each input by dipswitches, placed behind the alarms description panel. The activation, memory and
reset modes can be selected among the 8 most common sequences, according with the ISA 18.1 standard ISA A – ISA
M – ISA R8 – ISA M5 – ISA F1A – ISA F1M – ISA F3 A.
The mentioned sequences have following basic sequences:
ISA A
Automatic reset.
ISA M
Manual reset.
ISA R8
Ringback.
ISA M5
Signaling like ISA-M, but without flashing, when optical signaling.
ISA F1A Automatic reset “first out” with no subsequent alarm state.
ISA F1M Manual reset “first out” with no subsequent alarm state.
ISA F3A Automatic reset “first out” with first out flashing and reset pushbutton
Compalarm C2C
instruction manual
IM670-U v0.1
pag. 1 / 8
APPLICATION
C2c is suitable for connection of 12 inputs from normally open or normally closed contacts. The operating alarm
sequences can be easily configured according to ISA specifications. C2c is a compact device, all microprocessor based
logic is embedded in the display unit.
Alarm status are displayed by means of hi-brightness, maintenance free red led.
A printed paper sheet can hold alarm associated text, placed under the front panel polyester foil and retained by an easily
removable frame.
High reliability, continuous self check, fail safe logic are important features for this device that is more than a simple
annunciator and could be used like supervisor.
Legend
1 - Alarm Inputs terminal (ac/dc)
6
2 - Ext. Switches Inputs terminal (ac/dc)
IN1÷12
R2_NA
IN1
3 - Power supply terminal
COM B- A+
IN2
R2_C
IN1÷12
4 - Extension Line Connection
IN3
R2_NC
5 - Output Relays
5
IN4
R1_NA
RELAYS
6 - RS485 Serial Communication
1
IN5
R1_C
OUTPUTS
IN6
R1_NC
PUSH
BUTTONS
IN7
IN8
TEST
IN9
RESET
IN10
ACK
IN11
IN12
C.I.
C.I.
C.I.
4
EXTN
AUX
SUPPLY
230V
115V
0V
3
2
OPERATION
At power-on or return from power-fail, the alarm system will reach an idle condition i.e. no visual and acoustic signalling.
When an input associated contact changes state the alarm system turn from steady to alarm condition, this means that
visual devices and horn output follows the pre-set sequence operation. The load output will be disabled until reset.
By means of push buttons it’s possible to acknowledge the alarm, silence the horn and reset to normal condition. A
specific push button perform the visual device test, without perturbation to normal operation.
Operating dip-switched are located under the polyester front foil, retained by removable click-in frame and must be
selected before power-on.
Before to place the polyester layer is possible to insert a simple paper sheet with alarm text to be visible through the
transparent windows. This paper could be written, engraved or printed. Templates are available for easy PC printing.
RESET TO FACTORY DEFAULT
Press all the three push buttons on the first and, at the same time, switch ON the device.
Compalarm C2C
instruction manual
IM670-U v0.1
pag. 2 / 8
FRONT PANEL
Legend
1 - Removable front frame
2 - LED lamp
3 - Transparent window for alarm description
4 - Power ON LED
5 - Push buttons
compalarm C2C
1
2
3
4
Power
ON
Alarm 1
Alarm 7
Alarm 2
Alarm 8
Alarm 3
Alarm 9
Alarm 4
Alarm 10
Alarm 5
Alarm 11
Alarm 6
Alarm 12
ACK
RESET
TEST
5
Legend
1 - Normally open/close input 1÷8 mode selection
2 - Normally open/close input 9÷12 mode selection
3 - Internal buzzer off/on
4 - Operating sequence selector
5 - LED's light intensity adjust
1
2
3
4
Compalarm C2C
5
instruction manual
IM670-U v0.1
pag. 3 / 8
ALARM SEQUENCES
The following alarm sequences are available:
Sequence A, Automatic Reset
Sequence features
1. Acknowledge, Test, and Mute pushbuttons.
2. Audible alarm can be silenced by pressing Mute pushbutton.
3. The audible device is silenced and flashing stops when acknowledged
4. Automatic reset of acknowledged alarm when process conditions return to normal.
5. Operational test.
Sequence M, Manual Reset
Sequence features
1. Acknowledge, Reset, Test, and Mute pushbuttons.
2. Audible alarm can be silenced by pressing Mute pushbutton.
3. The audible device is silenced and flashing stops when acknowledged
4. Manual reset of acknowledged alarm when process conditions return to normal.
5. Operational test.
Sequence M5, Manual Reset with No flashing
The visual display flashing feature is deleted. New alarms have the same visual display indication as acknowledged
alarms.
Compalarm C2C
instruction manual
IM670-U v0.1
pag. 4 / 8
Sequence R, Ringback
Sequence features
1. Acknowledge, Reset, Test, and mute pushbuttons.
2. Alarm and ringback audible devices.
3. Audible alarm or ringback alarm can be silenced by pressing Mute pushbutton.
4. Ringback visual and audible alarm when process conditions return to normal.
5. Manual reset of ringback indications.
6. Operational test.
Sequence R, Ringback
Sequence features
1. Acknowledge, Reset, Test, and mute pushbuttons.
2. Alarm and ringback audible devices.
3. Audible alarm or ringback alarm can be silenced by pressing Mute pushbutton.
4. Ringback visual and audible alarm when process conditions return to normal.
5. Manual reset of ringback indications.
6. Operational test.
Compalarm C2C
instruction manual
IM670-U v0.1
pag. 5 / 8
Sequence F1A, Automatic Reset First Out with No Subsequent Alarm State
Sequence features
1. Acknowledge, Test, and Mute pushbuttons.
2. Alarm audible devices.
3. Audible alarm can be silenced by pressing Mute pushbutton.
4. Flashing and audible indications for first alarm only. New subsequent alarms go to the acknowledge state.
5. First out indication is reset and the audible is silenced when acknowledged.
6. Automatic reset of acknowledged alarm when process conditions return to normal.
7. Operational test.
Sequence F1M, Manual Reset First Out with No Subsequent Alarm State
Sequence features
1. Acknowledge, Reset, Test, and Mute pushbuttons.
2. Alarm audible devices.
3. Audible alarm can be silenced by pressing Mute pushbutton.
4. Flashing and audible indications for first alarm only. New subsequent alarms go to the acknowledge state.
5. First out indication is reset and the audible is silenced when acknowledged.
6. Manual reset of acknowledged alarm when process conditions return to normal.
7. Operational test
Compalarm C2C
instruction manual
IM670-U v0.1
pag. 6 / 8
Sequence F3A, Automatic Reset First Out with First Out Flashing and Reset Pushbutton
Sequence features
1. Acknowledge, First out Reset, Test, and Mute pushbuttons.
2. Alarm audible devices.
3. Audible alarm can be silenced by pressing Mute pushbutton.
4. First out flashing different from subsequent flashing.
5. Fist out Reset pushbutton to change the first out visual indication to be the same as subsequent visual indications.
6. Automatic reset of acknowledged alarm when process conditions return to normal.
7. Operational test.
DIMENSIONS
Compalarm C2C
instruction manual
IM670-U v0.1
pag. 7 / 8
TECHNICAL DATA
MAIN POWER SUPPLY TYPE
Supply voltage
115 or 230 V - 50/60Hz or 85÷265Vac/dc
Power consumption
4.5 VA MAX
Line fuse (external)
500 mA
LOW VOLTAGE SUPPLY TYPE
Supply voltage
20÷60Vac/dc
Power consumption
4.5 VA MAX
Line fuse (external)
1A
TERMINALS SCREW AND PLUG TERMINAL BLOCK
Operating temperature
0 ÷ 60 °C
Storage temperature
-20 ÷ 80 °C
Relative humidity
NON CONDENSING max 95 %
Vibration allowed
0.5 G
Overall dimensions
(DIN43700) 72 x 144 x 65 mm
Cut-out dimensions
92 x 92 mm
Protection class
(DIN VDE0470) IP40
Material
Noryl UL V-0
SERIAL INTERFACE (OPTION)
Standard
RS485 Half-duplex (ModBus protocol)
Connector
5.0mm pitch extractible screw terminals
Isolation
4KVpeak o 2.5KVRMS – transceiver stage self powered
BaudRate
4800 – 9600 – 19200 – 38400
Node-ID
1 ÷ 247
Parity
Even – Odd - None
Stop bit
1 or 2
Emergency recovery configuration
Node 1 – Baud Rate 38400 – no-parity – 1 stop bit
Mounting position
Any
Weight
500 g MAX
Text window dimensions
34 x 9 mm
Output channels
2 SPDT contacts
Max switching voltage
250 Vac
Max switching current
5A @ 250V cosj=1
Max switching power
750 VA / 100 W
Input channels
12 OPTOCOUPLED
Input pushbuttons
4 OPTOCOUPLED
Inputs Voltage
24 / 48 / 115 / 230 Vac/dc ± 20%
Inputs current
5 mA MAX
Extension line
1000 m MAX
FOR COMMON SUPPLY SYSTEMS
Power-on delay
5s
Galvanic separation
Inputs | Outputs | Supply
Test voltage
2500 V @ 50 Hz, 1 minute
Isolation voltage
300 VRMS max
EMC Compliance Directive
EMC 89/336/EEC
Emission
EN 50082-1
Immunity
EN 50082-2
ETHERNET MODULE (OPTION)
Speed
10/100 base T magnetics on-board
Connector
RJ45 (standard RJ Ethernet connector)
Contact the technical assistance or refer at specific document for application don’t described in this manual.
NOTE At reason of the evolution of standards and products, the company reserves to modify in every time the features of the
product described in this document, that it’s necessary to verify preventively. The liability of the producer for damage caused
by defect of the product ”can be reduced or deleted (…) when the damage is caused joint by a defect of product or for blame
of the damaged or a person of which the damaged is responsible” (Article 8, 85/374/CEE).
Compalarm C2C
instruction manual
IM670-U v0.1
pag. 8 / 8