technical details

advertisement
DIN rail mount type
TB559, 556, 564, 563 series
• 24-hour program (TB559, TB556)
• Weekly program (TB564, TB563)
• 300-hour reserve battery (TB556, TB563)
• With robust metal setting pins
• DIN 3P module
Applicable installation
Dimensions (unit: mm)
Indoor use
66.5
61
44
54
Series
TB559 series
TB556 series
TB564 series
Item No.
TB5590185N
TB5560187N
TB5640185N
TB5630187N
Operating voltage / frequency
230V AC 50Hz
220-240V AC 50-60Hz
230V AC 50Hz
220-240V AC 50-60Hz
Drive method
AC motor
Quartz motor
AC motor
Power reserve
Time accuracy
Load
capacity
110
45
90
DIN
railmounting
grove
Terminal cover
(option parts)
TB563 series
Quartz motor
300 hours(at 25˚C)
300 hours(at 25˚C)
Same as AC frequency ±15 sec/month(at 25˚C) Same as AC frequency ±15 sec/month(at 25˚C)
Circuit configuration
No voltage contact output
Type of contact
Single pole, double through
(1c Contact)
250V AC 16A
Resistive load(cosø=1)
Inductive load(cosø=0.6)
>time
Shortest switching=
Number of ON/OFF>
=operations
33
34.5
Weekly
Daily
Program
250V AC 3A
15 minutes
2 hours (*1)
96 operations
84 operations
*1. Operating time accuracy is ±30 minutes.
DIN rail mount type
TB62 series (Digital)
• Weekly type
• 6-year reserve battery
• With a manual ON/OFF button
• Possible to lock the manual button
• Holiday setting function
• Manual ±1 hour changeover function
• DIN 2P module
Dimensions (unit: mm)
Applicable installation
61
55
44
40
35
33
5.5
Weekly
Series
TB62 series
Item No.
1.8
TB621018A7(1circuit)
TB622018A7(2circuits)
Operating voltage / frequency
220-240V AC 50-60Hz
Drive method
Electronic
Front cover
Power reserve
6 years
Time accuracy
±15 sec/month(at 25°C)
Circuit configuration
No voltage contact output
Type of contact
Single pole, double through
(1c Contact)
65.2
45
Mounting plate
(option parts)
Load
capacity
65
45
130
90
Indoor use
Program
Terminal cover
(option parts)
34.5
Resistive load(cosø=1)
250V AC 16A
Inductive load(cosø=0.6)
>time
Shortest switching=
250V AC 8A
Number of ON/OFF>
=operations
78
1 minute
50 operations (ON/OFF 25 sets) / circuit
Surface & DIN rail mount type
TB35N, 36N, 38N, 39N series
• 24-hour program
• Surface and DIN rail mount
• 300-hour reserve battery (TB38N, 39N)
• Battery exchange from the front side.
• 96 operations per day
• Shortest switching time is 15 minutes.
• Easy to read and set, clock display.
Applicable installation
Indoor use
Program
Dimensions (unit: mm)
Daily
Series
TB35N series
TB36N series
TB38N series TB39N series
TB38809NE7
Item No.
TB35809NE5
TB35809NE6
TB36809NE5
Operating voltage / frequency
220-240V AC 50Hz
220-240V AC 60Hz
220-240V AC 50Hz
Drive method
AC Motor
Quartz Motor
Same as AC frequency
±15 sec/month(at 25˚C)
Power reserve
300 hours
Time accuracy
Load capacity
TB39809NE7
220-240V AC 50-60Hz
Circuit configuration
Voltage contact output
No voltage contact output
Voltage contact output No voltage contact output
Type of contact
Single pole, single through
(1a Contact)
Single pole, double through
(1c Contact)
Single pole, single through Single pole, double through
(1a Contact) (1c Contact)
Resistive load(cosø=1)
250V AC 20A
Incandescent lamp load
Inductive load(cosø
Motor load(cosø
250V AC 10A
0.6)
250V AC 12A
0.6)
220V AC 1500W
Shortest switching time
15 minutes
Number of ON/OFF operations
96 operations
Applicable installation
Indoor use
Surface mount type
TB17N, TB11N series
• 24-hour program
• ON/OFF operations are set with separated pins
• With a manual ON/OFF switch
• 300 hours reserve battery (TB11N)
• Battery exchange from the front side.
Program
Dimensions (unit: mm)
�8
16.5
Item No.
TB178NE5
Operating voltage / frequency
�4.5
50
TB118NE7
220-240V AC 50Hz
220-240V AC 60Hz
AC Motor
220-240V AC 50-60Hz
Quartz Motor
Same as AC frequency
±15 sec/month(at 25˚C)
300 hours
Time accuracy
Load capacity
31.5
TB11N series
TB178NE6
Power reserve
120
101 (Fixing Pitch)
123
2.5
TB17N series
Drive method
Front
Cover
72
Daily
Series
Circuit configuration
Voltage contact output
Type of contact
Single pole, single through
(1a Contact)
Resistive load(cosø=1)
250V AC 15A
Incandescent lamp load
250V AC 15A
Inductive load(cosø
Motor load(cosø
0.6)
0.6)
250V AC 12A
220V AC 1500W
Shortest switching time
30 minutes
Number of ON/OFF operations
Standard 6 operations (Max. 48 operations)
79
Surface mount type
TB35N, 38N series (Steel box type)
• Robust steel box
• 24-hour program
• Surface mount
• 300-hour reserve battery (TB38N)
• Battery exchange from the front side.
• 96 operations per day
• Shortest switching time is 15 minutes.
• Easy to read and set, clock display.
Applicable installation
Indoor use
Program
Dimensions (unit: mm)
Daily
Series
TB35N series
Item No.
TB358NE5
Operating voltage / frequency
Drive method
TB38N series
TB358NE6
TB388NE7
220-240V AC 50Hz
220-240V AC 60Hz
AC Motor
220-240V AC 50-60Hz
Quartz Motor
Same as AC frequency
±15 sec/month(at 25˚C)
Power reserve
300 hours
Load capacity
Time accuracy
Circuit configuration
Voltage contact output
Type of contact
Single pole, single through
(1a Contact)
Resistive load(cosø=1)
250V AC 20A
Incandescent lamp load
250V AC 10A
Inductive load(cosø
Motor load(cosø
0.6)
0.6)
250V AC 12A
220V AC 1500W
Shortest switching time
15 minutes
Number of ON/OFF operations
96 operations
Applicable installation
Outdoor and Indoor use
Surface mount type
TB43N series (Weatherproof)
• Weatherproof type (IP53)
• 24-hour program
• Surface mount
• 300-hour reserve battery
• Battery exchange from the front side.
• 96 operations per day
• Shortest switching time is 15 minutes.
• Easy to read and set, clock display.
Program
Daily
Series
TB43N series
Item No.
TB438NE7
Operating voltage / frequency
220-240V AC 50-60Hz
Quartz Motor
Dimensions (unit: mm)
Load capacity
Drive method
80
Power reserve
300 hours
Time accuracy
±15 sec/month(at 25˚C)
Circuit configuration
No voltage contact output
Type of contact
Single pole, single through
(1a Contact)
Resistive load(cosø=1)
250V AC 20A
Incandescent lamp load
250V AC 10A
Inductive load(cosø
Motor load(cosø
0.6)
0.6)
250V AC 12A
220V AC 1500W
Shortest switching time
15 minutes
Number of ON/OFF operations
96 operations
80
Wiring Examples
Single Pole, Single Through (1a Contact)
When a magnetic switch and contactor are used together
When direct controlled
by a time switch
Single phase
Three phase
Time Switch
Time Switch
S2
S1
S2
S1
L2
S2
S1
Time Switch
When the time
switch and load
power supply are
separate
L2
L2
L1
L1
Power
source
L1
Power
source
Power
source
Load
Power
source
3
4
1
2
MC
A1
Power
source
No
voltage
contact
output
Load
96
13
Power
source
1
2
3
4
5
6
MgS
95
Load
A2
A1
Electromagnetic switch
A2
Electromagnetic switch
Note: Before operating, take off all protective wires of
electromagnetic switch shown with dotted lines in diagram.
Time Switch
When the time
switch and load
power supply are
the same
(Connect a
crossover wire
between S2
and L2 .)
Time Switch
S2
S1
S2
S1
Time Switch
S2
S1
L2
L2
L1
96
13
L1
Power
source
L2
L1
Load
Power
source
Power
source
3
4
1
2
MC
A1
Load
1
2
3
4
5
6
95
Load
MgS
A2
A1
Electromagnetic switch
A2
Electromagnetic switch
Note: Before operating, take off all protective wires of
electromagnetic switch shown with dotted lines in diagram.
Time Switch
Time Switch
S1
Time Switch
Voltage
contact
output
When the time
switch and load
power supply are
the same
S1
S2
S1
L2
S2
L2
L1
L2
S2
L1
96
13
L1
Power
source
Load
Power
source
3
4
1
A1
MC
Load
1
Power
source
3
2
Load
4
5
A2
95
2
MgS
6
A2
A1
Electromagnetic switch
Electromagnetic switch
Note: Before operating, take off all protective wires of
electromagnetic switch shown with dotted lines in diagram.
Single Pole, Double Through (1c Contact)
When a magnetic switch and contactor are used together
When direct controlled
by a time switch
Single phase
Three phase
Time Switch
Time Switch
Time Switch
When the time
switch and load
power supply are
separate
S1
S2
S1
COM
NO
S2
COM
S1
NO
S2
NC
Load
Power
source
3
4
1
A1
No
voltage
contact
output
NO
Power
source
Power
source
Power
source
COM
Power
source
NC
NC
MC
Load
13
Power
source
2
2
3
4
5
6
A1
A2
96
1
MgS
95
Load
A2
Electromagnetic switch
Electromagnetic switch
Note: Before operating, take off all protective wires of
electromagnetic switch shown with dotted lines in diagram.
Time Switch
Time Switch
When the time
switch and load
power supply are
the same
(Connect a
crossover wire
between S2
and COM .)
Time Switch
S1
Power
source
S2
COM
NO
S1
S2
COM
S1
NO
S2
COM
NO
NC
NC
NC
13
Load
Power
source
Power
source
3
1
A1
4
MC
2
A2
Electromagnetic switch
Load
96
1
2
3
4
5
A1
MgS
95
Load
6
A2
Electromagnetic switch
Note: Before operating, take off all protective wires of
electromagnetic switch shown with dotted lines in diagram.
81