PROCEEDINGS OF WORLD ACADEMY OF SCIENCE, ENGINEERING AND TECHNOLOGY VOLUME 32 AUGUST 2008 ISSN 2070-3740 Improvement of Power Factor for Industrial Plant with Automatic Capacitor Bank Marlar Thein Oo, Ei Ei Cho to sustain the electromagnetic field associated with many commercial/ industrial loads. It is measured in kilovoltamperes-reactive, or kVAR. The total required capacity, including working and reactive power, is known as apparent power. It is expressed in kilovolt-amperes or KVA. Abstract-This paper is intended to uplift the technological standard of industrial plants. The overall power factor of modern industries is very poor because of inductive loads absorbing reactive power. Especially, industrial plant with variable load conditions has large inductive loads and its power factor is very poor. These industries benefit most from automatic capacitor banks. This bank provides improved power factor, increased voltage level on the load and reduced electric utility bills. Besides, automatic capacitor banks may be able to eliminate kVAR energized at light-load periods and undesirable over-voltages. In most cases, the main reason why a customer installs a capacitor bank is to avoid penalization in the electricity bill. This inappropriate installation without enough study gives rise to a great variety of technical problems. Therefore, the fact that capacitor banks are designed for long-term use should be considered. Fig.1 kW power Keywords- industrial plants, poor power factor, automatic capacitor bank, long term I. INTRODUCTION I N most industrial and commercial facilities, a majority of the electrical equipment is inductive loads such as AC induction motors, induction finances, transformers and ballast-type lighting. Problems of power quality in industrial plants are growing due to the increasing number of rectifier controlled motors and the overall increase of harmonics and interharmonics. These loads cause poor power factor in industrial plants. A poor power factor indicates ineffective utilization of electricity and affects total energy costs. These problems are aggravated by the proper selection, sizing and installation of capacitors. G M Motor Field Fig. 2 kVAR power F. A. Miss Marlar Thein Oo is with the Electrical Power Engineering Department, Mandalay Technological University, Mandalay, Myanmar, ( email: marlartheinoo@gmail.com). S. B. Miss Ei Ei Cho with the electrical Power Engineering Department, Mandalay Technological University, Mandalay, Myanmar, (e-mail: eieicho2006@gmail.com) Fig. 3 kVA power FUNDAMENTAL OF POWER FACTOR Power factor is a measure of how effectively electrical power is being used by a system. To understand power factor, we first have to know that power has three components: working, reactive and apparent power. Working power is the current and voltage actually consumed. It performs the actual work, such as creating heat, light and motion. Working power is expressed in kilowatts (kW), which register as kilowatt-hour on electric meter. Reactive is not useful work, but it is needed PWASET VOLUME 32 AUGUST 2008 ISSN 2070-3740 695 © 2008 WASET.ORG PROCEEDINGS OF WORLD ACADEMY OF SCIENCE, ENGINEERING AND TECHNOLOGY VOLUME 32 AUGUST 2008 ISSN 2070-3740 generally are the most economical means to improve power factors. Power factor correction is the term given to a technology that has been used since the turn of the 20th century to restore the power factor to as close to unity as is economically stable. This is normally achieved by the addition of capacitors to the electrical network which compensate for the reactive power demand of the inductive load and thus reduce the burden on the supply. There should be no effect on the operation of the equipment. kVA kW cos ș = kVA kvar =PF ș kW Fig. 4 Power triangle A sample analogy for power factor is to relate it to a garden hose. Circumstances, if you need 10 liters of water per minute to come out at the end of the hose, the tap should be turned on to deliver that amount of water. But if your hose leaks, is squashed between rocks, or is kinked because it is cheap, you will experience a drop in pressure. To achieve your target of 10 liters per minute, therefore, you need to turn up the tap and force more water through the hose. That is Power Factor Correction. Power factor is the ratio of working power to apparent power or kW/kVAR. Power factor values can carry from 0 to 1.00. Typically, values range from 0.80 to 0.98. A power factor below 0.80 is considered low. INDUCTIVE LOADS CONTRIBUTING TO POOR POWER FACTOR II. If the plant inductive loads, which require the use of a magnetizing current to create a magnetic field, Power factor corrections are required. Inductive characteristics are more pronounced in motors and transformers and are found more often in commercial and industrial facilities. One of the worst offenders is a lightly loaded induction motor, often found in “cycle processes” –for example, in the operation of saws, conveyors, and grinders- where the motor must be sized for the heaviest load. Other sources include: induction furnaces, standard stamping machines, weaving machines, single stroke presses, automated machine tools, welders and certain fluorescent lamp ballasts. Table 1 shows incorrect power factor of some industrial plants. Fig. 5 Standard power factor correction TABLE 1 IV. BENEFITS OF POWER FACTOR CORRECTION TYPICAL LOW POWER FACTOR INDUSTRIES Industry 1. Environmental benefit-reduction of power consumption due to improved energy efficiency. Reduced power consumption means less greenhouse gas emissions and fossil fuel depletion by power stations. 65% - 75% 2. Reduction of electricity bills. 70% - 80% 3. Extra kVA available from the existing supply. 4. Reduction of I2R losses in transformers and distribution equipment 5. Reduction of voltage drop in long cables 6. Extended equipment life- reduced electrical burden on cables and electrical components. Saw Milk 45% - 60% Plastic 55% - 70% Machine Tools, Stamping 60% - 70% Planting, Textile, Chemicals Hospitals, Foundries The advantages that can be achieved by applying the correct power factor correction are: Uncorrected power factor III. POWER FACTOR CORRECTION If the power factor of the plant is low, it uses more power than it needs to do the work. Poor power factor should be corrected as it substantially increases costs. Capacitors V. METHODS OF CAPACITOR INSTALLATIONS PWASET VOLUME 32 AUGUST 2008 ISSN 2070-3740 696 © 2008 WASET.ORG PROCEEDINGS OF WORLD ACADEMY OF SCIENCE, ENGINEERING AND TECHNOLOGY VOLUME 32 AUGUST 2008 ISSN 2070-3740 TABLE II We need to choose the optimum type, size and number of capacitors for the plant. There are four methods of capacitor installations: Method 1: SUMMERY OF ADVANTAGES AND DISADVANTAGES Method Capacitor at load Installed a single capacitor at each sizeable motor and energize it whenever the motor is in operation. This method usually offer the greatest advantage of all, and the capacitors could be connected either in location (A) as (B) in Figure below. Advantages Disadvantages Most technically efficient, most flexible Higher installation and maintenance cost Fixed Bank Most economical, fewer installations Less flexible, requires switches and/ or circuit breakers Automatic Bank Best for variable loads, prevents over voltages, low installation cost Higher equipment cost Combination Most practical for larger numbers of motors Least flexible Individual Capacitors Fig. 6 Location of the capacitor connections Location A- Normally used for most motor applications. Location B- Used when motors are jogged, plugged, revered: for multi-speed motors, as reduced voltage start motors. Method 2: Fixed capacitor bank Installed a fixed quality of kVar electrically connected at one or more locations in the plant’s electrical distribution systems, and energized at all times. This method is often used when the facility has few motors of any sizeable horsepower to which capacitors can economically be added. When the system is lightly loaded, and the amount of kVar energized is too large, the voltage can be so great that motors, lamps, and controls can burn out. VI. PARTICULAR NEDS OF THE PLANT When deciding which type of capacitor installation best meets weight the advantages and disadvantages of each and consider several plant variables, including load type, load constancy, load capacity, motor starting method. A. Load type It is a important fact to remember that kVar equal to 20% of the transformer kVA is the maximum size of a fixed kVar bank. Valued greater than this can result in a large resonant current, which is potentially harmful to the system. Method 3: If the plant consist of many large motors, 50 Hp and above, it is usually economical to install one capacitor per motor and switch the capacitor and motor together. If the plant has many small motors, ½ to 25 hp, group motors and install one capacitor at a control point in the distribution system. The best solution per plants with large and small motor is to used both types of capacitor installation. Automatic capacitor bank It is installed at the motor control centre at the service entrance. This bank will closely maintain a preselected value of power factor. This is accomplished by taming a controller switch steps of kVar on, as off, as needed. Automatic switching ensures exact amount of power factor correction, eliminates over capacitance and resulting over voltages. Method 4: B. Load Size Facilities with large loads benefit from a combination of individual load, group load and banks of fixed and automatically-switched capacitor units. A small facility may need only one capacitor as the control board. Combination of methods Sometimes, only an isolated trouble spot requires power factor correction. This may be the case if the plant has welding machines, induction heaters or dc drives. If a particular feeder serving s low power factor load is connected, it may raise Since no two electrical distribution systems are identical, each must be carefully analyzed to arrive at the most cost- effective solution, using are or more of the method. PWASET VOLUME 32 AUGUST 2008 ISSN 2070-3740 697 © 2008 WASET.ORG PROCEEDINGS OF WORLD ACADEMY OF SCIENCE, ENGINEERING AND TECHNOLOGY VOLUME 32 AUGUST 2008 ISSN 2070-3740 overall plant power factor enough that additional capacitors are unnecessary. = 360, 000 kyats Net gain (Annual saving) C. Load Constancy = 1, 080, 000 + 360, 00 If the plant operates around the clock and has a constant load demand, fixed capacitors offer the greatest economy. If lead is determined by eight-hour shift five day a week, switched units are wanted more to decrease capacitance during times of reduced load. = 1, 440, 000 kyats Therefore, annual saving is 1.2 percent of annual charge. This is to illustrate a hypothetical annual estimate. Single line diagram and control circuit diagram of 200 kVAR automatic capacitor bank are designed in appendix. D. Load capacity If the feeder or transformers are overloaded, or if additional load is added to already load lines, correction needs at the load if the facility has surplus amperage, the capacitor banks are installed at main feeders. If load varied a great deal, automatic switching is probably the solution. The linear payback period of this installation is described below. Total cost of installation (survey cost, advice, capacitance and labour) is 3, 2000, 000 kyats. VII. METHODOLOGY FOR POWER FACTOR BILLING ADJUSTMENT Annual saving is 1, 440, 000 kyats. Therefore, the payback period is 2 years and 3 months. Assume a 400 kW load with a power factor of 70 percent. To improve power factor to 90 percent, the total kVar added to your plant (rating of capacity bank) is 200kVar. VIII. The most frequent case at industrial plants is to compensate the reactive power at low voltage. To do this, there are on the market a large no. of manufacturers that offer standardized products with power ratings up to and even exceeding 1000 kVar. This is a very well known and widespread product and, as a result, on many occasions it is installed without enough study. 572 kVA 408 kVar 445 kVA 194 kVar P.f 70% P.f 90% 400 kW 400 kW Therefore, the effects of disturbances are suffered mostly by the owner of the capacitor bank. Please ensure that installation meet your requirements, manufacturers, installations and all applicable codes, standards and regulations. Total annual kWh = 2, 400, 000 Average kWh charge = 50 kyats Annual charge = 120, 000, 000 kyats DISCUSSIONS AND CONCLUSION IX. RECOMMENDATIONS ¾ Power factor adjustment is 0.06 percent or each percentage point below or above 85 percent. ¾ Power factor adjustment for 70 percent (penalty value) ¾ = 85 – 70 Size electric motors to match mechanical loads to increase the overall p.f. Use capacitor banks at motor control centre or service entrances to facilitate switching for varying load. Install conditions as harmonic filters to avoid harmonic resonance problems and excessive voltage distortion levels. = 15 x 0.06 % ACKNOWLEDGEMENT = 0.9 % x 120, 000, 000 = 1, 080, 000 kyats I would like to appreciate and thank His Excellency U Thaung, Minister, Ministry of Science and Technology. I’m also dedicated to acknowledge to Dr. Myo Myint Aung, Head of Electrical Power Engineering Department, M.T.U, U Myint Oo, Management Engineer, S n Q Electrical Engineering Service and all my teachers. Power factor adjustment for 90 percent (credit value) = 90 – 85 = 5 x 0.06% = 0.3 % x 120, 000, 000 PWASET VOLUME 32 AUGUST 2008 ISSN 2070-3740 698 © 2008 WASET.ORG PROCEEDINGS OF WORLD ACADEMY OF SCIENCE, ENGINEERING AND TECHNOLOGY VOLUME 32 AUGUST 2008 ISSN 2070-3740 REFERENCES [1] Electrical Transmission and Distribution Reference Book, 4th edition, 1950, Westinghouse Electric Corporation. [2] IEEE Standard 141-1993, Recommended practice for Electrical Power Distribution for Industrial Plants. [3] R.C. Dugan, M.F. McGranaghan, S. Santoso, and H.W. Beaty, Electrical Power Systems Quality, Second Edition, McGraw-Hill, Professional Engineering Series, New York, 2003. Marlar Thein Oo studied in Electrical Power Engineering Major and held B.E degree in 2004 from Mandalay Technological University, Mandalay, Myanmar. Then I was awarded M.E degree of Electrical Power Engineering in 2006 from Yangon Technological University, Yangon, Myanmar. Now I am a Ph.D candidate. PWASET VOLUME 32 AUGUST 2008 ISSN 2070-3740 699 © 2008 WASET.ORG 700 C1 20Kvar FR 1 14-22A KM C1 40A 2 C2 20Kvar FR 2 14-22A KM C2 40A, 3P MCB2 6mm2 3 40A, 3P MCB1 1 6mm2 3 40A 6mm2 3 C3 20Kvar FR 3 14-22A KM C3 40A, 3P MCB3 3 40A 6mm2 3 40A C5 20Kvar FR 5 14-22A KM C5 40A, 3P MCB5 5 40A 6 600A, 3P DS C6 20Kvar FR 6 14-22A KM C6 40A, 3P MCB6 40A 7 A C7 20Kvar FR 7 14-22A KM C7 40A, 3P MCB7 6mm2 3 40A 8 C8 20Kvar FR 8 14-22A C9 20Kvar FR 9 14-22A KM C9 40A, 3P MCB9 9 Controller FU 1,2,3 40A cosĭ FU 7,8 KM C8 40A, 3P MCB8 FU 4,5,6 V Fig. 7 Single Line Diagram of 200 kVAR Automatic Capacitor Bank C4 20Kvar FR 4 14-22A KM C4 40A, 3P MCB4 4 G 10 6mm2 3 Feeder Bus 6mm2 3 From Sensor CT 4 6mm2 3 Distribution Bus 6mm2 3 PWASET VOLUME 32 AUGUST 2008 ISSN 2070-3740 40A 10 C10 20Kvar FR 10 14-22A KM C10 40A, 3P MCB10 40A Control Source 10A, 3P MCB 11 T.C.L = 200 Kvar Control Source Selector SW Auto-Man 6mm2 3 APPENDIX PROCEEDINGS OF WORLD ACADEMY OF SCIENCE, ENGINEERING AND TECHNOLOGY VOLUME 32 AUGUST 2008 ISSN 2070-3740 © 2008 WASET.ORG Bus 1 S1 Distribution Bus CT1 S2 N Bus L11,L12,L13 630A,3P,DS L1,L2,L3 CT4 CT2 CT3 L11 L12 L13 0 A3 A2 A1 To AS Power capacitor Selector SW 10A,3P M C B 13 16 15 18 17 20 22 19 21 24 23 26 25 28 27 11 AU1 1X11 N11 AU2 3X6 3X5 3X4 K Fig. 8 Control Circuit Diagram of 200 kVAR Automatic Capacitor Bank 21 14 31 11 41 9 12 51 10 M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 7 61 2.5Sq mm 2L111 2L211 2L311 5 8 71 K 2L11 2.5Sq mm 2L12 2L21 2L31 C B 3 6 81 3X3 3X2 3X1 4X2 4X1 4 91 2L1 2L2 2L3 3L3 3L2 1 101 FU 3, 10A FU 2, 2A FU 1, 2A FU 8, 2A FU 7, 2A CT 41 CT 40 2 To VS FU 4,2A 1L1 Bus 2 N 11 Distribution Bus FU 5,2A 1L2 701 FU 6,2A PWASET VOLUME 32 AUGUST 2008 ISSN 2070-3740 1L3 Bus 3 US US US1 US2 IS1 IS2 IS2 4X5 C B 4X4 1 2 3 4 5 6 i A 7 8 9 10 K10 Internal connection of the Controller CT412 Cos ĭ CT411 I A K1 K2 K3 K4 K5 K6 K7 K8 K9 US1 US2 IS1 4X3 PROCEEDINGS OF WORLD ACADEMY OF SCIENCE, ENGINEERING AND TECHNOLOGY VOLUME 32 AUGUST 2008 ISSN 2070-3740 © 2008 WASET.ORG N 12