Energy management systems control panel

advertisement
Energy management
systems control panel
construction
Standard control specification
Users guide to Allen Martin heating
controls
Resources directorate
Issue/
Revision No
0
A
B
Date
Originator
05/0//05
07/08/07
14/06/10
R C Smith
T N Thomas
T N THOMAS
Purpose for Issue/
Nature of Change
First issue
Regular Updates
Regular Updates
Energy management systems control panel construction
Standard control specification
2
GENERAL DETAILS
Preamble
It is intended that this specification shall be read in conjunction with the
Standard Technical Specification (ELECTRICAL INSTALLATION SERVICES)
and the Standard Technical Specification (MECHANICAL INSTALLATION
SERVICES).
Certain sections of this specification may not relate to the drawings
supplied and accordingly should be disregarded.
Regulations
The installation shall be designed, installed, tested and commissioned in
accordance with:
The Health and Safety at Work Act together with all relevant
approved Codes of Practice and Memorandum of Guidance
The most recent issue of BS 7671 together with all relevant
approved Codes of Practice and Guidance Notes
The latest requirements of the Building Regulations
The Electricity at Work Regulations together with all relevant
approved Codes of Practice and Memorandum of Guidance
The Electricity Safety, Quality and Continuity Regulations
Construction (Design and Management) Regulations
Control of Substances Hazardous to Health – COSHH
The Control of Asbestos Regulations 2006 including future
amendments and editions
The above shall not be seen as definite list of relevant standards and
regulations and, unless stated otherwise, the whole of the works shall
comply with the requirements of all relevant British Standards and
European Harmonised standards and documents pertinent to the works.
Relevant standards and regulations shall be those that are in force three
months prior to the return of tender or commencement of work unless
stated otherwise in the particular specification documents.
Definitions
For the purpose of this document, terms and definitions shall be as those
of the most recent edition of BS 7671 Part 2.
Energy management systems control panel construction
Standard control specification
3
British Standards
Where a British Standard or Code of Practice issued by the British
Standards Institute is current at the date of tender and appropriate to the
case, the contract shall require that goods, materials and works shall be in
conformity.
General Operating Conditions
This specification is written as general guidance to the methods of panel
manufacture.
It is not intended as a definitive method, as all systems are slightly
different and will have different control methods.
The requirements and standards for equipment and wiring within the
control panel will however apply for all projects.
The electrical equipment shall be such that its installation, operation and
maintenance shall comply with the above legislation and any subsequent
relevant legislation.
CONTROL PANEL
Construction
As far as practicable, all controls, indicator lamps and instruments shall be
grouped and mounted together in a floor or wall-mounted panel.
The control panel shall be constructed within a suitably sized powder
coated steel enclosure, with a cream/grey finish (Bowthorpe Hellerman –
Himel type or equivalent). The enclosure shall incorporate removable
gland plates at both top and bottom.
The control panel shall be constructed to give a protection rating of not
less than IP55 and shall be so constructed as to prevent the ready ingress
of dust. The joints of plates and doors shall be suitably packed, using
neoprene or equal (not rubber).
Mechanical ventilation shall be provided where it is likely that the
operating temperature within the panel will be greater than those limits
set by the equipment manufacturer. That ventilation system shall
maintain the panel temperature to within the manufacturers limits
regardless of the panel environment.
Panels shall be supplied with hinged and lockable access doors at the front
of the panel. Two keys shall be provided which shall be common to all
locks on all panels.
Energy management systems control panel construction
Standard control specification
4
All equipment within the enclosure shall be mounted on a removable back
plate such that if required, the complete system can be removed from the
enclosure to aid installation.
Access doors or covers shall be so arranged that access cannot be made
until an isolating device, interlocking with each door or cover, is opened
and all equipment accessible through that door or cover is isolated. A
purpose made device or suitable isolator shall be provided to enable a
competent engineer to override the interlock when the door has been
opened.
Panels secured to the floor shall be provided with metal plinths of a
suitable size and strength i.e. ‘Unistrut’ or equivalent. This plinth must be
earthed in accordance with BS7671 and BS 7430. Where mounting is on
raised builders work bases, metal plinths are not required, but in all cases
fixing holes and detachable lifting eyes shall be provided.
Control panels shall, as far as is practicable, be manufactured, equipped,
wired and tested before delivery to site.
Indicating lamps, instruments and controls shall be, as far, as is
practicable, from the same manufacturer and of the same style to provide
uniformity of appearance and to facilitate maintenance. Externally visible
equipment shall be flush mounted, with minimum projection and fixed
securely to the front panel.
Internal equipment shall be secured to the back plate using a suitable DIN
type rail. Fixings shall incorporate shake-proof washers or other vibration
resistant fastenings.
The control panel shall be designed and built by an approved control
specialist and shall comply in general with the details given by the Energy
Management Unit and the project documentation supplied.
The control specialist shall supply working drawings and fully numbered
interconnection diagrams to enable an electrical contractor to make all
connections between the control panel, plant and sensors.
This shall be deemed to include all valves, pumps, sensors, remote relays
and all other forms of ancillary equipment associated with the controls
package.
The electrical contractor shall be responsible for all connections external
to the control panel and for this reason, the panel shall be constructed
such that all connections for both low voltage mains wiring and extra low
voltage control, monitoring and data and monitoring wiring are made to a
single DIN rail terminal strip located at the top or alternatively the bottom
of the enclosure.
The DIN rail terminal strip shall be arranged such that low voltage mains
wiring and extra low voltage control, monitoring and data connections are
Energy management systems control panel construction
Standard control specification
5
segregated and suitably labelled. Mains voltage and low voltage cables
must be segregated by a fixed barrier in accordance with IEE Regulations.
All terminals shall be numbered using appropriate slip on numbers, in
accordance with the panel wiring diagram.
Note - the Users Guide to Wiring Allen-Martin Heating Controls
contains drawings for connections to all common equipment.
A label shall be fitted inside each control panel, adjacent to the main
isolator indicating:
Supply voltage
Control voltage
Current rating
Date of manufacture
After installation the electrical contractor shall ensure that all swarf, dust
and cable debris is removed from the panel.
Particular care shall be exercised when working around the energy control
system.
The electrical contractor shall be responsible for and damage resulting
from this cleaning.
Control equipment
The building management control equipment shall be from the AllenMartin range of controllers unless specified otherwise by Cornwall Council.
The BMS controller shall be contained within the control panel. It shall be
fed from a 5A rated un-switched spur taken from the live side of the
incoming isolator such that the supply to the controller is not isolated
when the panel supply is switched off.
A durable yellow notice with black text to this affect shall be located
adjacent to the isolator. This label shall be engraved traffolyte type and
affixed with mechanical fixings, not adhesive.
A single data socket shall be located within the panel for connection to the
building intranet system.
A single socket outlet shall be fitted within the panel for the connection of
a power supply for dialup modem communications when used.
A space shall be set aside for the subsequent mounting of a suitable
power supply and modem unit. Both shall be fixed via proprietary
mechanical fixings.
Energy management systems control panel construction
Standard control specification
6
No interface whatsoever shall be made with the BMS module. All
connections shall be via the incoming terminal strip.
All wiring within the control panel shall be identified at each end with a
number unique to that cable. Numbers shall only change due to a control
device.
All wiring within the control panel shall be terminated using ferrule type
crimp lugs constructed in accordance with the manufacturer’s instructions.
All panel wiring shall be single core, flexible plain annealed copper
conductor, heat resistant PVC insulation. Panel wire to BS6231 type CK
and UL/CSA approved. 600/1000 volts grade.
Wiring within the control panel shall be contained within slotted trunking
with close fitting lids. Trunking shall be Critchley betaduct or approved
equivalent.
Internal wiring shall be colour coded to BS7671 for LV cables
ELV cables shall be coloured as follows:
24V a.c.
24v (0V)
15V + ve
15V –ve
Analogue input
Analogue output
Digital output
Digital input
White
Black
Orange
Grey
Purple
Brown with marker
Brown
Pink
MCB’s shall be used in preference to BS88 fuses and these shall be type C
M9 to BS 60898 for all motor circuits. They shall be selected from the
Merlin Gerin Multi 9 range.
All protective devices shall be so sized and co-ordinated that they provide
shock and overload protection to BS7671.
Contactors shall be DIN rail mounted and from the Telemechanique range.
Overload protection is required for all circuits. The full load current of all
circuits shall be recorded on the as fitted drawings and established to
provide the correct setting of the overcurrent element.
Relays shall be DIN rail mounted and from the Omron/Shrack plug in
range.
Panel indicator lights shall be from the Telemechanique high output LED
range. All indicator lamps shall be coloured for their mode according to
BS EN 60073:1993, IEC 60073:1991.
Energy management systems control panel construction
Standard control specification
7
Running
Tripped
Healthy
Fault
Warning
Abnormal
Green
Red
White
Red
Orange/Amber
Blue
Switches shall be from the Telemechanique range such that they match
the selected indicators.
Volt Free Contacts (v.f.c.) shall be provided for all items of plant to enable
alarm/status signal to be sent to the BMS.
The control panel shall be fitted with a key operated (tumbler type)
maintenance override switch. The switch shall be fitted on the front of the
panel. Operating the switch shall run all plant and open all 240V operated
valves and solenoids.
It shall not be possible to open to open any other valves by using the
plant maintenance override switch.
A red indicator lamp shall be fitted adjacent to the override switch and
shall be illuminated when the switch is operated.
The switch shall be labelled “Plant maintenance override ON/OFF”
The indicator shall be labelled “Override ON”.
Pressure switches
Two pressure switches shall be fitted on the cold feed to the system, these
shall be the high and low limit switches. The set points shall be agreed
with a representative of Cornwall Council/Principal Mechanical Services
Engineer at the commissioning stage.
Activation of either of these pressure switches shall cause the plant to be
shut down immediately and display a “Pressure Fault” on the main control
panel. The control specialist shall also allow for the provision of “Closed
when Healthy” signal to open under these fault conditions and initiate a
fault alarm on the BMS. The fault condition will latch and will require local
or remote manual resetting.
Commissioning
The contractor is to allow for the programming of all testing and
commissioning works to suit the programme of works.
This is to include inspecting, testing and commissioning of all works by
any sub contractors and specialist contractors works arranged by the
contractor.
Energy management systems control panel construction
Standard control specification
8
Commissioning shall mean the advancement of the systems from static
completion to working order, to the specification, and relevant works to
achieve compliance with Part L of the building regulations and
functionality to the complete satisfaction of Cornwall Council’s approved
representative/s.
All shall be conducted without prejudice to the need to comply with all
Health and Safety requirements.
Commissioning works shall include, but not be limited to, the following:
•
•
•
•
Demonstrate the correct operation of all items of equipment
necessary to provide a working building energy control system
Demonstrate the correct operation of all alarm systems and provide
instruction to appointed site personnel involved in daily use and
maintenance of the system
Demonstrate the correct operation of all specialist plant and
equipment supplied and installed as part of the contract/works
Demonstrate the correct procedures for fault finding and reporting
in the event of mechanical or electrical faults within the installed
works
The specialist contractor shall appoint an engineer to commission the
complete system. The whole or part of the process shall be witnessed by
a representative of Cornwall Council/Principal Mechanical Services
Engineer. The data link shall not be accessed until that representative is
present.
Failure to comply could result in damage to either the new or existing
equipment.
The processor shall not be energised.
As fitted control drawings shall be supplied immediately upon completion
of the project.
Energy management systems control panel construction
Standard control specification
9
HEATING/HWS CONTROLS
GENERAL TECHNICAL
SPECIFICATION
Energy management systems control panel construction
Standard control specification
10
General Technical Specification
Heating/HWS Controls
Preface
This technical specification is written as general guidance to the methods
of control and the required standards for new and retrofit heating/hws
control systems. It shall be read in conjunction with the STANDARD
CONTROL SPECIFICATION.
It is not intended as a definitive method statement, as all systems are
slightly different and will have different control requirements. It should
therefore be read in conjunction with the relevant project documentation.
The requirements and standards for equipment and wiring within the
control panels will however apply for all projects.
Heating System Operation (General)
The Allen Martin Series of Controllers are fully microprocessor controlled
Building Management Systems which can be used to control heating and
ventilation plant. The controllers have a self learn facility which will
determine the optimum warm up time of the building from the inside and
outside sensors fitted in various locations within the building.
The controller will start the pump(s), fire the boiler(s), open the valve to
each zone (where applicable) and energise the supply to heat emitters
(e.g. fan convectors - where applicable) to heat each zone as required.
When each heating zone is up to temperature, the controller may close or
modulate the valve to that particular zone.
In the case of mixed flow (variable temperature) circuits with modulating
valves, the pumps shall continue to run to provide circulation.
For constant temperature circuits fitted with 2 port isolating valves, the
pumps shall be stopped as soon as the valve closes by the use of an
auxiliary switch within the valve actuator.
When all heating zones are up to temperature and switched off by the
controller, the boiler shall be shut down.
Primary loop pumps (where applicable) or selected zone heating pumps
(dependant upon the type of installation) shall continue to run on for a
predetermined time to dissipate excess heat within the boiler.
In general, the boiler and loop pumps (where applicable) shall be
interlocked such that if the loop pump trips, the boiler will be shut down.
Energy management systems control panel construction
Standard control specification
11
If a pressurisation unit is fitted to the system, high and low pressure
switches shall be fitted to the cold feed line. Operation of either switch
will indicate an abnormal system pressure condition and shall cause all
plant to be shut down. This may be achieved by wiring the main control
circuit through the pressure switch system.
Pressure fault indication shall be made available to the BMS in the form of
a volt free normally closed contact.
Compensation/optimisation of the system shall be achieved by the use of
immersion type flow and return sensors within the system pipe work.
The type and number of such sensors will be dependant upon the
requirements and degree of control required for each project.
Control of air handling plant shall be achieved in the same way except
that the sensors shall be of a type suitable for installation within ducts.
The control panel shall be fitted with a plant over ride timer. This will
operate the plant so that the engineer can test pumps etc. This timer
should be of a run back type so that the plant can not be left on.
Control Panel/Outstation
The control panel/outstation shall be designed and built by a control
specialist and shall comply in general with the details given on the one
line schematic drawing provided with the project documentation and
within this specification.
The control specialist shall issue working drawings and fully numbered
interconnection diagrams to enable an electrical contractor to make all
interconnections between the control panel, plant and sensors.
This shall be deemed to include all valves, pumps, sensors, remote relays
and all other items of ancillary equipment associated with the controls
package.
All terminals shall be numbered in accordance with the panel wiring
diagram.
No plant or sensors shall be directly connected to the mother board or
modules thus bypassing the main terminal strip.
All wiring within the control panel/outstation shall be easily identifiable by
the use of wire and terminal numbers. All cables shall be marked at both
ends within the panel. All cables to be tri rated to BS 6231.
Outgoing wiring from the terminal strip shall be fitted with terminal
numbers at the panel and remote ends such that they can be easily
identified during testing and commissioning.
Energy management systems control panel construction
Standard control specification
12
Wiring within the control panel to be contained within suitable trunking
with access slots (e.g. Critchley Betaduct).
Volt free contacts shall be provided for all items of plant to enable
alarm/status signals to be sent to the BMS.
E.g. each zone pump will have volt free contacts for both running and
tripped states.
Alarms and trips shall be closed contacts that open on trip, running
contacts will open when running.
Panel Installation
The electrical contractor shall be responsible for the fixing and connection
of the control panel and shall ensure that the control system is protected
during installation.
The electrical contractor shall remove all gland plates and panel entries for
drilling and slotting for cable entries. He shall not drill gland plates with
the control equipment in place unless suitable precautions have been
taken to prevent the ingress of swarf and filings into the contactors/relays
etc.
The contractor shall ensure that the trunking/conduit connection to the
panel is of sufficient width such that only the removable gland plate needs
to be perforated.
Any stray swarf or filings found within the panel after installation shall be
cleaned out with a vacuum cleaner.
Any damage to equipment within the panel which can be
attributed to the ingress or swarf and filings shall be rectified at
the expense of the installer.
Pump Control
Zone heating and HWS pumps within the boiler house area shall be
controlled by the BMS via the control panel.
Remote pumps shall be controlled from the BMS by the use of extra low
voltage relays in the remote location, which will switch the
pump/associated equipment. Supplies to remote equipment shall be
derived from a local distribution board and suitably labelled.
If 2 port valves are used (where applicable), pumps shall be prevented
from running until the two port valves are full open by the use of valve
end switches. Under no circumstances should a pump be made to operate
against a closed valve.
Energy management systems control panel construction
Standard control specification
13
Under normal operating conditions, the BMS will control the valve and the
pump will only start when the end of travel switch within the valve
actuator operates as the valve approaches the full open position.
The controls specialist shall be made aware if there are valve end switches
and their required function.
The end switches are usually supplied as a separate item and will require
fitting into the valve actuator at installation and adjusting to the required
end of travel tolerance.
End switches shall not be used for direct control of signals or supply. End
switches shall operate slave relays in the control panel only.
Switches shall be provided on the control panel for each pump. These
switches shall be Off/Auto only. No hand override shall be provided.
Twin head pumps shall be controlled on an either/or basis and no
automatic changeover shall be allowed.
All pumps shall be fitted with appropriately sized overload relays wired
into the contactor control circuit or a suitable alternative.
Remote Relays
Remote relays used to drive equipment not located within the boiler house
shall in general be an extra low voltage type capable of being driven
directly by the digital output from the BMS or through a relay located
within the control panel.
If the output from the BMS is of insufficient capacity to drive the number
of relays required, a suitable transformer shall be fitted within the control
panel to provide an extra low voltage supply for these relays.
The remote relays must be wired such that they are energised to switch
off the plant they control. For this reason, if they are controlled by a LV
transformer and relay within the panel, the control specialist shall ensure
that the system is capable of providing the required output.
This is required so that in the event of a control system failure, all plant
will run.
For connection of remote relay, see enclosed drawing.
Boiler house wiring
Wiring within boiler houses and/or plant rooms shall be in PVC single core
tri rated cable contained within galvanised steel conduit and trunking.
Final connection to sensors shall be made in flexible conduit with the cable
drawn through.
Energy management systems control panel construction
Standard control specification
14
Two compartment trunking shall be installed within the boiler house where
required to carry extra low voltage and data and low voltage mains wiring.
It is not acceptable to run data cables and mains cables in the same
conduit or trunking unless a metallic barrier is fitted (ref section 528 of
British Standard BS 7671). In all instances of cable routing the
manufacturers recommendations shall be adhered to.
Data cable will be terminated in a suitable galvanised box. The box will
have a numbered din rail mounted terminal strip. The cable will be
numbered at both ends and the box lid will have a label stating DATA.
Sensor and Control Wiring
The zone sensors shall be wired in the type of cable as specified by the
appropriate control drawing but generally to BS5308.
This cable shall physically isolated in the data isolation box for remote
sensors and in by the compartment trunking in the boiler room.
Immersion sensors and outside sensors shall be wired in data cable to CT
units (where applicable) and then to BMS via the terminal strip in the
control panel.
Connection from the CT unit (where applicable) to immersion and duct
sensors shall be in “Kopex” or equal and approved with the data cable
drawn through.
Connections to pressure switches etc shall be made as detailed for
sensors.
Where room sensors are fitted to back boxes or other outlets, the end of
the conduit or back plate of the sensor shall be sealed with a suitable non
setting compound to prevent the ingress of air and draughts from areas
external to the controlled space.
Sensors and thermostats shall be mounted at 1650mm above finished
floor level. Spur for the thermostat shall be mounted at 150mm below
finished ceiling level.
In rooms containing both thermostats and room sensors, the units
shall be mounted adjacent to each other in the same location
within the space.
Isolation
All boilers shall be fed via a multipole isolator mounted adjacent to the
equipment for mechanical maintenance purposes. This shall be capable of
interrupting all live conductors of the supply to each boiler/boiler module.
(Note as BS7671 the neutral is viewed as a live conductor).
Energy management systems control panel construction
Standard control specification
15
Pumps shall be fed from the control panel via 16A European standard IEC
plug and sockets (e.g. Mk Commando range or similar) and using heat
resisting flexible cable to the pump heads.
The socket shall be installed socket facing downwards.
Pressurisation units shall be fed on a permanently live supply from the
control panel via a 16A IEC plug and socket.
Pressurisation unit (where applicable)
Two pressure switches shall be fitted on the cold feed to the system, these
shall be high and low limits. The high limit shall be a break on rise unit
and the low limit shall be a break on fall. These limit switches shall
control slave relays in the control panel.
The set points shall be agreed with the mechanical engineer at
commissioning stage.
Operation of either switch shall cause all plant to be shut down
immediately and display a pressure fault indication on the main control
panel. The control specialist shall also allow for the provision of volt free
normally closed contacts that open under fault conditions to enable the
fault alarm to be detected by the BMS.
The pressurisation unit shall be wired on an exclusive circuit from the
control panel via a 16A European standard fused spur.
Control valves/AHU Dampers
Control valves (where applicable) shall be 2 port for isolation and three
port for mixing or diverting.
The valves/actuators selected shall be dependant upon the particular
project and may be either mains or low voltage operation.
All extra low voltage (e.g. 0-10V) operated valves shall be wired with a
suitable multicore cable with a cross sectional area of not less than
1.5mm2 to allow for the possibility of voltage drop.
Refer to the appropriate control drawing.
Telephony/Belden type cable shall not be used for this purpose.
The mechanical contractor shall in general supply the valves and actuators
and the type/operating voltage shall be indicated on the one line
schematic provided as part of the project documentation.
Mains operated valves shall be terminated with in the valve head. Labels
shall be installed to warn about voltage.
Energy management systems control panel construction
Standard control specification
16
The control specialist shall ensure that the panel is fitted with a suitable
transformer, which is capable of supplying the total connected extra low
voltage load.
HWS Controls
In general, the HWS system shall be controlled by the BMS by the use of a
three port diverting valve on the primary circuit controlled via an
immersion type sensor within the cylinder.
High limit control shall be achieved by a 230v 50Hz spring return 2 port
isolating valve that cuts off all primary flow to the cylinder. This shall be
controlled by a high limit thermostat located within the cylinder.
Immersion heaters for standby use shall be fitted within the cylinder and
controlled by the BMS on a timetable basis if there are sufficient outputs
on the control system.
If the heaters are to be manually controlled, they shall be switched from
the plant control panel. A visual indicator shall be provided on the panel
to show that the standby immersions are in use.
Energy management systems control panel construction
Standard control specification
17
Responsibilities (heating/hws plant)
The electrical contractor shall be responsible for:
E1.
Mounting and positioning of all equipment
E2.
Running of all cables
E3.
All wiring and final connections to sensors plant and control
systems to clear and concise wiring/installation diagrams
provided by the control specialist
E4.
All wiring and final connections to heating equipment as detailed
on the project drawings
E5.
Supply and installation of all controls, sensors and ancillary
equipment
E6.
Full inspection and test of the whole electrical installation
including mechanical control. Certificate to be produced.
E7.
The purchase of all control equipment and associated items
from one of the nominated controls specialists for the particular
project
Controls Specialist
The control specialist shall be responsible for:
a)
Designing and building of the control panel/outstation
b)
Final testing and commissioning of plant and control system
c)
Liaison with Cornwall Council Energy Management Unit and/or Clerk
of Works
d)
Provision of all wiring and interconnection diagrams as detailed
within this specification. This shall include a fully annotated
termination diagram giving terminal number/letters for all items of
plant and the respective connections within the control panel
terminal strip. It shall also give details of cable type, cross
sectional area and colour coding where applicable.
These diagrams will provide the electrical contractor with
sufficiently detailed information to enable him to make all necessary
interconnections between plant items and controls.
e)
As fitted controls drawings on completion of the project.
Energy management systems control panel construction
Standard control specification
18
Data Link (where applicable)
The electrical contractor shall allow for the supply and installation of a
data link from any existing compatible BMS controls to the new control
panel/BMS. This link shall be a multi-core data cable to BS5308 and shall
be run to the nearest energy management outstation within an existing
building/area.
The data link between new and existing equipment shall be left
disconnected until the new control system is ready to be commissioned.
Failure to do this can result in damage to either the existing or new
control equipment.
If the installation is a completely new project or there are no existing
compatible controls, the above shall not apply.
Energy management systems control panel construction
Standard control specification
19
LPHW Heating Systems
Control
Philosophy
If
Heating zone calls for heat
Then
Valve opens (2 or 3 port)
Loop pump starts (where fitted)
Zone heating pump starts
Fan convector circuit energised (Where fitted)
Boiler(s) fire
Run indication for each item to BMS and on
panel
Zone up to temperature
(variable temp circuit)
3 port valve modulates under BMS control
Pump continues to run to circulate pipework
Zone up to temperature
(constant temp circuit)
2 port isolating valve (where fitted) closes
Circulating pump stops
Fan convector zone controls (where fitted)
switched off
All zones up to temperature
Boiler stops
Loop pump (where fitted) runs on to dissipate
heat in boiler
This may be a zone pump if no loop pumps
fitted
Pressurisation unit failure
(where applicable) or system
pressure fault
All plant stops
Alarm signal sent to BMS
Pressure fault indication on control panel
Boiler lockout occurs
Alarm signal to BMS
Lockout indication on control panel
Zone pump trips
Alarm signal to BMS
Trip indication on control panel
Loop pump trips (where
fitted)
Alarm signal to BMS
Trip indication on control panel
Boiler shuts down
Plant override switch
operated
All valves open (except 0-10V analogue
control)
All pumps run
Boilers fire (controlled by integral stats)
Fan convector circuits energised
Control system fails
All plant runs
Boilers control on integral stats
Fan convectors control on local room stats
Energy management systems control panel construction
Standard control specification
20
Fire alarm operates
(interlocked via f/a auxiliary
contact in control circuit)
All plant shuts down
Gas solenoid valve closes (if fitted)
Gas drop valve solenoid releases (if fitted)
Energy management systems control panel construction
Standard control specification
21
Ventilation and Air Handling
Control Philosophy
If
Space requires ventilation (over
temp/poor air quality)
Then
Control system checks outside and
inside air temperature
Outside air temperature low
Heater battery (if fitted) brought on
line (operates in a similar way to a
mixed flow heating zone except that 3
port valve is used for diverting rather
than mixing)
Outside air temp below 5c
(measured by stat on heater
battery
If above conditions satisfied
Fans held off to prevent
chilling/freezing of heater battery
Space at required temperature
Supply/extract air dampers modulate
to provide partial fresh/recirculated air
via heat exchanger
Summer cooling required
Supply and extract fans start, dampers
open allowing fresh air into space thus
providing free cooling. Temperature
within space monitored by duct sensor
in return duct
Low space temperature
Heater battery brought on line, supply
(external) air damper closes, system
recirculates until space temperature
comes up to required level
Dampers then modulate to maintain
temperature/air quality
Space temperature monitored by return
air duct sensor
Space up to temperature
Heater battery 3 port valve modulates
to divert flow away from battery
Valve controlled by system based on
return air temperature as monitored by
return air duct sensor
Dampers modulate to maintain
temperature and air quality based on
return air temperature as measured by
return duct sensor
Supply and extract fans start
Dampers open to allow fresh air into
space (incoming air tempered by
heater battery if required)
Energy management systems control panel construction
Standard control specification
22
Air handling fans trip
Fire alarm operates
Trip indication shows on control panel
Alarm signal to BMS
All fire dampers close (where fitted)
Fans stop
System requires manual reset after fire
alarm cleared
Energy management systems control panel construction
Standard control specification
23
Energy management systems control panel construction
Standard control specification
24
Energy management systems control panel construction
Standard control specification
25
Energy management systems control panel construction
Standard control specification
26
Energy management systems control panel construction
Standard control specification
27
Energy management systems control panel construction
Standard control specification
28
Energy management systems control panel construction
Standard control specification
29
Energy management systems control panel construction
Standard control specification
30
Energy management systems control panel construction
Standard control specification
31
Energy management systems control panel construction
Standard control specification
32
Energy management systems control panel construction
Standard control specification
33
Energy management systems control panel construction
Standard control specification
34
Energy management systems control panel construction
Standard control specification
35
Prepared by:
Terry Thomas
Principal Electrical Engineer
Property Services
26 August 2010
Energy management systems control panel construction
Standard control specification
36
If you would like this information
in another format please contact:
Cornwall Council
County Hall
Treyew Road
Truro TR1 3AY
Telephone: 0300 1234 100
Email: enquiries@cornwall.gov.uk
www.cornwall.gov.uk
Energy management systems control panel construction
Standard control specification
37
Download