TSD047 FireCell Sounder - Visual Indicator Installation Iss 13

Wireless Sounder / Visual Indicator
Installation Guide
Example shown:
Part No
Product Description
FC-171-001
FC-171-002
FC-172-001
FC-172-002
FC-173-002
FC-173-003
FC-173-004
FC-178-002
FC-178-003
FC-178-004
White Wireless Sounder Base Only
Red Wireless Sounder Base Only
White Sounder Only
Red Sounder Only
Red Sounder Visual Indicator Only
Amber Sounder Visual Indicator Only
Clear Sounder Visual Indicator Only
Red Visual Indicator Only
Amber Visual Indicator Only
Clear Visual Indicator Only
CPR
See the Specification section for compliance information.
FC-172-001
TONE
1.
2.
3.
[2]
[2]
TONE
[1]
[1]
[1]
[1]
[1]
4.
5.
6.
7.
8.
FC-171-001
9.
10.
11.
12.
!
13.
2 Components
1 Pre Installation
Installation must conform to applicable local installation
codes and should only be installed by a fully trained
competent person.
14.
3
2
1
4
15.
16.
17.
Ensure that the device is installed as per the site survey.
18.
The use of a non-metallic spacer should be considered if
mounting the device on to a metal surface.
19.
20.
Do NOT Press the Log On button on a pre-programmed device,
as this will cause communication with the Control Panel to be
lost. Should this happen, delete the device from the system
and add it back on.
21.
22.
23.
ATTENTION
24.
1 Sounder/Visual Indicator Variant 2 Wireless Module
OBSERVE PRECAUTIONS
FOR HANDLING
25.
ELECTROSTATIC
SENSITIVE
3 Battery Retaining Plate
4 Mounting Plate26.
27.
28.
4 Power Device
3 Fix Mounting Plate
Remove the mounting plate from the wireless module by turning
it anticlockwise.
31. polarity,
When fitting / replacing batteries; observe correct
using only specified batteries.
32.
When wall mounting, ensure the mounting plate is fitted in the
orientation shown.
Use both mounting holes.
29.
Unclip the battery retaining plate from the wireless module.
30.
Connect the power jumper across the PIN header.
63mm
Use suitable fasteners and fixings.
device
unpowered
(pins unlinked)
SIZE AA
SIZE C
SIZE AA
SIZE C
SIZE C
THIS WAY
UP WHEN
WALL
MOUNTING
device
powered
(both pins linked)
SIZE AA
Once powered, reassemble the device.
5 Optional Device Locking
To lock the Sounder into
the
wireless
module,
remove the cut out section
as shown.
6 Configuration
The device’s loop address is configured within the menu structure
of the Radio Hub.
Refer to the programming manual (Doc Ref: MK98) for full
programming information.
Cut out section
(shaded area)
To unlock the device,
insert a 1.5mm Allen key
to depress the locking clip
and turn anticlockwise to
release.
©2015 EMS Security Group Ltd. All rights reserved
Free to download from
www.emsgroup.co.uk
Page 1 of 2
TSD047 Iss 13 09/02/2016
AJM
Tone Table
Configuration Continued
TONE DESCRIPTION / APPLICATION
SWITCHES PRIMARY
SECOND
DIP SWITCH
TONE 1-5TONE TYPE
TONE
DESCRIPTION
/ APPLICATION
TONE
TYPE
TONE
DESCRIPTION
TONE
TYPE
TONE
DESCRIPTION/ /APPLICATION
APPLICATION
TONE
TONETONE
1-2-3-4-5
970Hz
1. O-O-O-O-O
1.1.
1 2 3 4 5
Sounder Tone (Set on Sounder/Visual Indicator)
ON
SECONDARY
DIP
DIPSWITCH
SWITCH
TONE
11
-2
- 2- 3
- 3- 4
- 4- 5
-5
O-O-O-O-O
18
O-O-O-O-O
O-O-O-O-O
18
970Hz
ON
1
800Hz/970Hz @ 2Hz
800Hz/970Hz
800Hz/970Hz@@2Hz
2Hz
O-O-O-O-|
1
O-O-O-O-|
O-O-O-O-|
3. O-O-O-|-O
3.3.
1 2 3 4 5
ON
1
800Hz - 970Hz @ 1Hz
800Hz
800Hz- 970Hz
- 970Hz@@1Hz
1Hz
ON
O-O-O-|-O
1
O-O-O-|-O
O-O-O-|-O
4. O-O-O-|-|
4.4.
1 2 3 4 5
1
970Hz 1s OFF / 1s ON
970Hz
970Hz1s1sOFF
OFF/ /1s1sON
ON
ON
O-O-O-|-|
1
O-O-O-|-|
O-O-O-|-|
5. O-O-|-O-O
5.5.
1 2 3 4 5
4
970Hz, 0.5s / 630Hz,
0.5s 0.5s
970Hz,
970Hz,
0.5s/ /630Hz,
630Hz,0.5s
0.5s
4
O-O-|-O-O
O-O-|-O-O
554Hz, 0.1s / 440Hz, 0.4s (AFNOR NF S 32 001)
ON
O-O-|-O-O
6. O-O-O-|-|
6.6.
1 2 3 4 5
1
554Hz, 0.1s / 440Hz,
0.4s (AFNOR
NF S 32
001)
O-O-O-|-|
554Hz,
0.1s
0.4s
(AFNOR
S S32
554Hz,
0.1s/ /440Hz,
440Hz,
0.4s
(AFNORNF
NF
32001)
001)
1
O-O-O-|-|
O-O-O-|-|
500 - 1200Hz, 3.5s / 0.5s OFF (NEN 2575:2000)
7. O-O-|-O-|
7.7.
1 2 3 4 5
1
ON
500 - 1200Hz, 3.5s /500
0.5s
(NEN3.5s
2575:2000)
O-O-|-O-|
/ /0.5s
500- 1200Hz,
-OFF
1200Hz,
3.5s
0.5sOFF
OFF(NEN
(NEN2575:2000)
2575:2000)
1
O-O-|-O-|
O-O-|-O-|
The 800Hz/970Hz
5 way switch
is used to configure the
@ 2Hz
sounder tone.
800Hz - 970Hz @ 1Hz
All
32
available
970Hz 1s OFF / 1s ON
configurations are shown
970Hz,
/ 630Hz, 0.5s
in the
tone0.5s
table.
ON
MAX
MIN
2
5
3
1
2
3
6
4
7
5
Sounder /
Visual Indicator
2. O-O-O-O-|
2.2.
1 2 3 4 5
ON
970Hz
970Hz
8. O-O-|-|-|
8.8.
1 2 3 4 5
9
ON
420Hz 0.625s ON / 0.625s
OFF0.625s
(Australia
AS1670
Alert
tone)
O-O-|-|-|
420Hz
/ 0.625s
OFF
Alert
420Hz
0.625sON
ON
/ 0.625s
OFF(Australia
(AustraliaAS1670
AS1670
Alerttone)
tone)
9
O-O-|-|-|
O-O-|-|-|
500 - 1200Hz, 0.5s / 0.5s OFF x 3 / 1.5s OFF (AS1670 Evacuation)
9. O-|-O-O-O
9.9.
1 2 3 4 5
1
1
O-|-O-O-O
O-|-O-O-O
550Hz / 440Hz @ 0.5Hz
ON
500 - 1200Hz, 0.5s / 0.5s500
OFF
3 / 1.5s0.5s
OFF
Evacuation)
O-|-O-O-O
0.5s
x x3 3/ 1.5s
500- 1200Hz,
-x1200Hz,
0.5s/ (AS1670
/ 0.5sOFF
OFF
/ 1.5sOFF
OFF(AS1670
(AS1670Evacuation)
Evacuation)
10.O-|-O-O-|
10.
10.
1 2 3 4 5
19
550Hz / 440Hz @ 0.5Hz
550Hz
550Hz/ /440Hz
440Hz@@0.5Hz
0.5Hz
1
970Hz, 0.5 ON / 0.5s
OFF x0.5
30.5
/ ON
1.5s
O-|-O-|-O
970Hz,
OFF
x x33/ /1.5s
(ISO
970Hz,
ON/OFF
/0.5s
0.5s(ISO
OFF8201)
1.5sOFF
OFF
(ISO8201)
8201)
420Hz
0.625s ON
/ 0.625s OFF
(Australia
AS1670 Alert tone)
Default
Setting:
Primary
Tone
5
Volume (Set on Sounder/Visual Indicator)
The sound output of the unit can also be
ON
11.
11.
970Hz,by
0.5 adjusting
ON / 0.5s OFF
x 3 /potentiometer
1.5s OFF (ISO 8201)
1 2 3 4 5
reduced
the
as 11.O-|-O-|-O
ON
shown.
12.
2850Hz, 0.5s ON / 0.5s OFF x 3 / 1.5s OFF (ISO 8201) 12.O-|-O-|-|5 12.
O-|-O-O-|
19
O-|-O-O-|
O-|-O-O-|
1
O-|-O-|-O
O-|-O-|-O
1
ON
2850Hz, 0.5s ON / 0.5s
OFF x0.5s
3 / ON
1.5s
O-|-O-|-|
1
2850Hz,
OFF
x x33/ /1.5s
OFF
2850Hz,
0.5s
ON/OFF
/0.5s
0.5s(ISO
OFF8201)
1.5s
OFF(ISO
(ISO8201)
8201) O-|-O-|-|
O-|-O-|-|
13.O-|-|-O-O
13.
13.
1 2 3 4 5
1
ON
1200Hz - 500Hz @ 1Hz
(DIN- 33
404)@@1Hz
1200Hz
500Hz
1200Hz
- 500Hz
1Hz(DIN
(DIN33
33404)
404)O-|-|-O-O
1
O-|-|-O-O
O-|-|-O-O
14.O-|-|-O-|
14.
14.
1 2 3 4 5
18
400Hz
O-|-|-O-|
18
O-|-|-O-|
O-|-|-O-|
550Hz, 0.7s / 1000Hz, 0.33s
ON
15.O-|-|-|-O
15.
15.
1 2 3 4 5
1
550Hz, 0.7s / 1000Hz,
0.33s0.7s
550Hz,
550Hz,
0.7s/ /1000Hz,
1000Hz,0.33s
0.33s
ON
O-|-|-|-O
1
O-|-|-|-O
O-|-|-|-O
Visual Indicator
1500Hz
- 2700Hz @ 3Hz
16.O-|-|-|-|
16.
16.
1 2 3 4 5
1
1500Hz - 2700Hz @1500Hz
3Hz
1500Hz- 2700Hz
- 2700Hz@@3Hz
3Hz
O-|-|-|-|
1
O-|-|-|-|
O-|-|-|-|
1 2 3 4
1200Hz - 500Hz @ 1Hz (DIN 33 404)
400Hz
MAX
ON
MAX
MIN
2
5
3
1
MIN
2
3
6
4
7
5
Sounder /
ON
400Hz
400Hz
750Hz
17.|-O-O-O-O 17.
17.
1
750Hz
750Hz
750Hz
|-O-O-O-O
1
|-O-O-O-O
|-O-O-O-O
2400Hz
18.|-O-O-O-|5 18.
18.
1
2400Hz
2400Hz
2400Hz
|-O-O-O-|
1
|-O-O-O-|
|-O-O-O-|
660Hz
Default
setting: High Volume
19.|-O-O-|-O
19.
19.
1 2 3 4 5
18
660Hz
660Hz
660Hz
|-O-O-|-O
18
|-O-O-|-O
|-O-O-|-O
660Hz 1.8s ON / 1.8s OFF
20.|-O-O-|-|
20.
20.
1 2 3 4 5
19
660Hz 1.8s ON / 1.8s
OFF 1.8s
660Hz
660Hz
1.8sON
ON/ /1.8s
1.8sOFF
OFF
|-O-O-|-|
19
|-O-O-|-|
|-O-O-|-|
660Hz 0.15s ON / 0.15s OFF
21.|-O-|-O-O5 21.
21.
19
660Hz 0.15s ON / 0.15s
OFF
660Hz
0.15s
660Hz
0.15sON
ON/ /0.15s
0.15sOFF
OFF
|-O-|-O-O
19
|-O-|-O-O
|-O-|-O-O
22.|-O-|-O-|
22.
22.
1 2 3 4 5
1
510Hz, 0.25s / 610Hz,
0.25s0.25s
510Hz,
510Hz,
0.25s/ /610Hz,
610Hz,0.25s
0.25s
ON
|-O-|-O-|
1
|-O-|-O-|
|-O-|-O-|
23.|-O-|-|-O
23.
23.
1 2 3 4 5
1
800 / 100Hz 0.5s each
(1Hz)
800
/ /100Hz
800
100Hz0.5s
0.5seach
each(1Hz)
(1Hz)
ON
|-O-|-|-O
1
|-O-|-|-O
|-O-|-|-O
24.|-O-|-|-|
24.
24.
1 2 3 4 5
1
250Hz - 1200Hz @ 12Hz
250Hz
250Hz- 1200Hz
- 1200Hz@@12Hz
12Hz
ON
|-O-|-|-|
1
|-O-|-|-|
|-O-|-|-|
25.|-|-O-O-O
25.
25.
1 2 3 4 5
1
500Hz - 1200Hz @ 0.33Hz
500Hz
500Hz- 1200Hz
- 1200Hz@@0.33Hz
0.33Hz
|-|-O-O-O
1
|-|-O-O-O
|-|-O-O-O
ON
18
2400Hz - 2900Hz @2400Hz
9Hz
2400Hz- 2900Hz
- 2900Hz@@9Hz
9Hz
|-|-O-O-|
18
|-|-O-O-|
|-|-O-O-|
27.|-|-O-|-O5 27.
27.
18
2400Hz - 2900Hz @2400Hz
3Hz
2400Hz- 2900Hz
- 2900Hz@@3Hz
3Hz
|-|-O-|-O
18
|-|-O-|-O
|-|-O-|-O
28.ON
28.
|-|-O-|-| 28.
1
800Hz - 970Hz @100Hz
800Hz
800Hz- 970Hz
- 970Hz@100Hz
@100Hz
|-|-O-|-|
1
|-|-O-|-|
|-|-O-|-|
29.|-|-|-O-O 29.
29.
1
800Hz - 970Hz @ 9Hz
800Hz
800Hz- 970Hz
- 970Hz@@9Hz
9Hz
|-|-|-O-O
1
|-|-|-O-O
|-|-|-O-O
30.ON
30.
|-|-|-O-| 30.
1
800Hz - 970Hz @ 3Hz
800Hz
800Hz- 970Hz
- 970Hz@@3Hz
3Hz
|-|-|-O-|
1
|-|-|-O-|
|-|-|-O-|
1
800Hz, 0.25s ON / 1s
OFF 0.25s
800Hz,
800Hz,
0.25sON
ON/ /1s1sOFF
OFF
|-|-|-|-O
1
|-|-|-|-O
|-|-|-|-O
8
500Hz - 1200Hz, 3.75s
/ 0.25s
OFF (AS2220)
|-|-|-|-|
500Hz
- 1200Hz,
3.75s
500Hz
- 1200Hz,
3.75s/ /0.25s
0.25sOFF
OFF(AS2220)
(AS2220)
1 2 3 4 5
8
|-|-|-|-|
|-|-|-|-|
1 1 2 2 3 34 4 5 5
1 2 3 4 5
ON
ON
ON
Audio Monitoring (Set on Wireless Module)
The 510Hz,
primary
secondary
stage sounder
0.25sand
/ 610Hz,
0.25s
tones can be monitored. If enabled and no
800is/ 100Hz
0.5s each
(1Hz) 10 seconds upon
audio
detected
within
sounder
a fault is indicated at the
250Hzactivation,
- 1200Hz @ 12Hz
control panel.
500Hz - 1200Hz @ 0.33Hz
SWITCHES
2400Hz - 2900Hz
@ 9Hz
1&2
2400Hz - 2900Hz @ 3Hz
PRIMARY SECONDARY
TONE
TONE
MONITORED MONITORED
ON
ON
1 2
800Hz - 970Hz @100Hz
www.emsgroup.co.uk
ON
OFF
1 2
800Hz - 970Hz @ 9Hz
Wireless Sounder Base
IDENT
800Hz - 970HzOFF
@ 3Hz
1 2
1 2 3 4
ON
PRESS HERE TO
LOG ON
ON
ON
1 2 3 4
26.|-|-O-O-|5 26.
26.
1 2 3 4
ON
1 2 3 4
1 2 3 4 5
ON
1 2 3 4 5
ON
1 2 3 4 5
800Hz, 0.25s ON
/ 1s OFF
OFF
31.|-|-|-|-O
31.
31.
1 2 3 4 5
500Hz - 1200Hz, 3.75s / 0.25s OFF (AS2220)
32.|-|-|-|-|5 32.
32.
11 22 33 4
4
OFF
Default setting: Audio Monitoring Disabled
ON
5
Specification
1 2 3 4
1 2 3 4
Regulatory Information
Manufacturer
Operating
Temperature
-10°C to 55°C
Storage
Temperature
5°C to 30°C
Humidity
Up to 95% non-condensing
Supply
3x AA Alkaline (Panasonic LR6AD Powerline / Varta
4006 Industrial) 3x C Alkaline (Panasonic LR14AD
Powerline / Varta 4014 Industrial)
Year of
manufacture
Certification
Certification body
CAUTION!
Fitting of an incorrect battery type invalidates the product certification and
may result in poor performance.
Sounder Output
99dBA @ 1m (as dispatched)
IP Rating
IP54
Operating Frequency 868MHz
Output Transmitter
Power
Auto adjusting 0 - 14 dBm (0 - 25 mW)
Dimensions
120mm (Ø) 125mm (D)
EMS Security Group Ltd. Technology House, Herne
Bay, Kent, CT6 8JZ, United Kingdom
See devices serial number label
10
0359
CPR Certificate DOP
See part listing for associated products:
[1]0359-CPR-0022, [2]0359-CPR-0040
Approved to
See part listing for associated products:
EN54-3:2001. Incorporating Amendments Nos. 1 and
2. Fire detection and fire alarm systems. Part 3: Fire
alarm devices - Sounders.[1]
EN54-25:2008. Incorporating corrigenda September
2010 and March 2012. Fire detection and fire alarm
systems. Part 25: Components using radio links. [2]
European union
directives
EMS Security Group Ltd hereby declares that this
device is in compliance with the essential
requirements and other relevant provisions of
Directive 2014/53/EU (R&TTE directive).
2012/19/EU (WEEE directive):
Products marked with this symbol cannot be disposed
of as unsorted municipal waste in the European Union.
For proper recycling, return this product to your local
supplier upon purchase of equivalent new equipment,
or dispose of it at designated collection points. For
more information see www.recyclethis.info
Page 2 of 2