Hospital Trunking

advertisement
Hospital Trunking
Construction Kit for Medical Ward Units
P2148
TECHNICAL INFORMATION 2001:12
P3722
FrontLine Installation System
FrontLine is a system for installation of service to
modern office workplaces. The system includes products which enable the services to be supplied from
the ceiling, the wall or the floor.
The system consists of two parts:
1. Service content which includes socket outlets and
connections for power, telecommunication and data
for access to networks and other services.
2. Service carriers are the cable trunking, servicepoles, floor outlet boxes, service posts and service boxes, with 80 mm front openings (F80®), which make the
socket outlets and connections accessible.
The F80® front openings ensure that the service
content is compatible with the various service carriers.
Most FrontLine service carriers can also be delivered pre-wired, with the required service content,
ready for connection to service gates in the main network. This will reduce the on-site installation time
and make rearrangement of the premises easier.
Every pre-wired product is given a serial number
and is tested prior to delivery. An individual test re-
port is always included.
Trademarks
The following is a list of Thorsman's and other companies' trademarks, registered and unregistered, used throughout this catalogue.
Trademark
Company
AGA ................................................AGA GAS AB
AMP-CO, NetConnect........................AMP Inc
Blolite...............................................BICC Brand-Rex
Dräger .............................................Dräger Gmbh
Ethernet ............................................Digital Equipment Corp./Xerox/Intel
Greggersen.......................................Greggersen Gastechnik Gmbh
IBM..................................................International Business Machines Corp
LUXO ...............................................JAC Jacobsen AS
Keystone...........................................Keystone International Holdings
PremisNet .........................................Krone(UK)Technique Ltd
LexCom ............................................LK as
Systimax ...........................................Lucent Technologies Ltd
MEDÆS GEM 10 ..............................Meaæs Ltd
SUNNEX ..........................................Nolato Sunnex Equipment AB
Reichle & De-Massari .........................Reichle & De-Massari
Hirschmann.......................................Richard Hirschmann Radiotechnisches Werk
CYB, F80, FrontLine, INKA .................Thorsman & Co AB
Other brand and product names are the trademark of their respective holders.
Approval and Quality Assurance
The Thorsman policy is to test and
approve products to applicable local
and international standards. We operate
quality assurance and quality control systems certified according to ISO 9000.
Hospital Trunking
Construction Kit for Medical Ward Units
Medical Ward Unit For All Requirements ........ 4
Straightforward Construction .......................... 6
Many Combinations - Freedom of Choice ........ 8
Complete Access & Outlet Program.................. 10
Design and Dimensions .................................. 12
Medical Ward Unit in Common Ward.............. 13
Medical Ward Unit in Intensive Care .............. 14
Cable Trunking Design .................................. 16
Composition of Lighting Profile ........................ 18
Placement of Light Fitting Rail .......................... 19
Lighting Techniques ........................................ 20
Gas Outlet Installation Techniques .................... 22
Layout Planning ............................................ 24
Colour Choice .............................................. 25
Product Range
Service carriers.............................................. 26
Service Content
Power ........................................................ 30
Communication .......................................... 38
Lighting ........................................................ 41
Gas.............................................................. 44
Accessory Rail .............................................. 48
Tools ............................................................ 49
Cable Capacity ............................................ 50
Technical Data .............................................. 59
Mounting Details............................................ 60
Specification Guide........................................ 67
Line drawings/photos
L31700
For testing and approving we use the following test houses:
The number beside line
drawings and photos is intended only for ordering digital
picture material.
NB: When ordering products, use the T-number in the
table.
Products and technical details are subject to change
during the lifetime of the brochure.
© THORSMAN & CO AB, 2001.
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 3
Medical Ward Unit in Kit Form for All Requirements
1
2
3
5
4
P2146
1. Lighting unit, full length, colour code L11.
2. Trunking base, type INKA-217-2/90, colour code
L11 and L65.
3. Service content, CYB.
4 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
4. Gas profile, full length, colour code L11.
5. Dräger gas outlets.
6. Accessory rail equipped with monitor shelf.
Established and Approved Components
With a number of established and approved components you can, on-site, construct and install Medical
Ward Units adapted to unique nursing situations.
The kit allows the construction of a ward unit for
the most straightforward form of common ward up to
the most complex installations for intensive care spaces.
The cable trunking that is one of the main components can also be used to advantage as a carrier of, for
example, service content (power, telecommunications,
data, etc.) in other work spaces of the hospital or
nursing home such as offices or laboratories.
The Basis: Cable Trunking, INKA
The concept for the kit is built around Thorsman’s
cable trunking in aluminium of type INKA. This installation trunking is carrier for all electricity, telecommunications, data and low-voltage current. The
size of the trunking is chosen with regard to cable capacity and equipment required. Cable trunking is
available in several heights. Some are two-compartment systems, where the lower compartment is
screened off by an integral partition. The trunking is
available in two depths, 72 mm or 90 mm. A wide
range of accessories are available for all INKA cable
trunking to ease installation and offer complete solutions.
Outlets for Power, Telecommunications
and Data Connections
6
A complete range of products for outlets and connections for power, telecommunication, data etc., is available, all mounted easily in the front of the installation
trunking.
General and Reading/Examining Lighting
The kit includes a combined lighting unit for general
and reading/examining light. The lighting complies
with the German DIN requirements for light dispersion in nursing spaces. The lighting unit can be fitted
on the wall close to the INKA cable trunking or separately. Length can be either full-length or adapted to
the choice of lighting rail. A bed/examining lamp with
arm for mounting on either wall or table is available as
an accessory.
Gas
The assortment of gas outlets include units of
Scandinavian, German and English standard for connection to air, oxygen, nitrous oxide, etc. The gas duct
can, as with the lighting unit, be mounted on the wall
close to the INKA trunking or separately. Gas-pipe
cover is available in two designs.
Colour Choice
All of the visible profile components can be natural
anodized or powder coated in a number of standard
colours. The colours can be combined in accordance
to the wishes of the customer to harmonize with
room decor.
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 5
P3826
Straightforward Construction and Installation
6 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Basic Data
Description
INKA cable trunking, aluminium, 72 and 90 mm
deep, with one or two compartments, 80 mm front
cover (F80®).
Lighting profile with general (indirect), reading/
examining (direct) and optional night light. Choice
of light fittings, 80 mm front cover (F80®)
Gas outlet profile to suit several gas outlet brands
and standards. Gas-pipe cover is available in two
designs.
• Kit form gives flexibility
• Based on Thorsman standard products
• Wide assortment
• Simple to specify
• Easy to install according to clear instructions
• Separation of power and low current,
lighting and gas
• Rapid installation with snap fittings
• Labelling of outlets
• Easy to clean
• Easy to upgrade and add new functions
Mounting and installation
The hospital trunking components are fixed directly
to the wall. The service content is installed in the
front opening.
The snap-in system makes the installation quick
and easy. Detailed mounting instructions are
enclosed.
Power and Communication
The trunking can be equipped with FrontLine Access
and Outlet Program type CYB.
Delivery lengths
Standard length of INKA trunking and front covers,
2.5 m. INKA, lighting and gas pipe front cover
available cut to length, max. 5.0 m by special
order.
Colours
Natural anodized or powder coated aluminium1).
1)
Can be painted in any shade listed in the NCS and RAL colour
ranges, see page 25.
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 7
Many Combinations Give Freedom Of Choice
1
2
3
5
P2150
4
1. Lighting unit, length adjusted to light fitting, see
Lighting pages 41-43, anodized.
2. Trunking base, INKA-101/72, see Service carriers,
page 26, anodized F80® front with foil M03 red beech
8 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
3. Power and Communication type CYB.
4. Gas profile, with Medaes gas outlets, see page
44, anodized
5. Cover for gas pipe, TRL, see page 46, anodized.
A12480
A12490
A12470
Lighting profile in full length and gas pipe cover of TRL type.
A12500
Lighting profile and gas pipe cover in full length.
Cut-to-length lighting profile and gas pipe cover of TRL type.
A10030
Cut-to-length lighting profile and gas pipe cover in full length.
Medical Ward Unit installation with lighting profile and gas pipe cover in full length. Accessory rail for attachment of gas and other
hospital equipment.
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 9
P4808
Complete Access and Outlet Program
Gas outlets for different standards
General and Reading/Examining Lighting
Our assortment includes outlets corresponding to
Scandinavian (AGA), German (Dräger, Greggersen)
and British (Medaes) standards. The gas outlets are
self-closing and the gas flow cuts off when equipment
is disconnected from the quick coupling.
The outlets are gas-specific according to the different hospital standards, which means that connection
to the wrong outlet is impossible.
The selection includes outlets for breathing oxygen,
nitrous oxide, breathing air, vaccum, etc.
There are lighting rails for different light requirements.
10 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
P4809
FrontLine Hospital Trunking offers a complete
selection of every conceivable outlet and connection
for electricity, telecommunications, data, gas and
lighting.
P2154
The ultimate task of a properly designed Medical
Ward Unit is to offer the exact function that the nursing situation calls for.
The lighting profile can be fitted with various lighting
rails for general light (indirect), reading/examining
and night light.
General light is available in various lengths with
standard fluorescent tubes type T26 or new technology tube type T5. Reading/examining light is of standard compact tube type TC.
As a supplement to the permanent lighting there are
two types of bed/examining lamps by Luxo and
Sunnex for table or wall mounting.
P2152
Power and Communication, type CYB
The power outlet can be delivered colour-coded in
white, green or red in order to differentiate normal
power from disruption-free or priority power.
Call system
Mix-up proof labelling
P2155
Service content of type CYB contains outlets and connections for power, telecommunications and data networks. The CYB outlet cover plate has a completely
smooth surface which facilitates cleaning.
Almost any of the existing call systems can be integrated into the Thorsman Medical Ward units. Different types of patient call units are easily mounted
into the Thorsman Medical Ward Unit, giving the
patient quick access for emergency calls.
P3827
Outlets and connections for power, telecommunications and data have distinct labelling panels. Labelling
is applied to the mounting frame behind the cover
plate. This means that labelling remains even if the
cover plate is removed, thus eliminating risk of a mixup when refitting.
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 11
Design and Dimensions
B11
B7
B9
B10
B1
B6
B2
B5
B3
A3
B4
B8
A1
A2
C11
C5
C9
C6
S13380
C7
C1
C2
C3
C4
C8
Cable trunking
A1
Trunking base, INKA
A2
Stop end, trunking base
A3
Front cover
Lighting
B1
Lighting profile
B2
Stop end, lighting profile
B3
Light fitting rail, TC
B4
Compact flourescent tube, TC
B5
Prismatic shade
B6
Front cover
B7
Light fitting rail, T26, T5 (Light tube section)
B8
Light fitting rail , T26, T5 (Ballast section)
B9
Reflector
B10 Flourescent standard tube, T26, T5
B11 Up-light cover
Fixing profile, gas outlets
Mounting adapter
Gas outlet
Front cover, gas outlet profile
Wall bracket, gas pipe profile
Mounting plate with pipe clamps
Stop end, front cover
Front cover, gas pipe profile
Stop end, front cover (gas pipe cover TRL type)
Base clamp
Gas pipe cover TRL type
D14060
Gas
C1
C2
C3
C4
C5
C6
C7
C8
C9
C10
C11
12 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
C10
A10050
Medical Ward Unit in Common Ward
functions. Suitable for common wards in hospitals, nursing
homes and sanatoriums.
A10370
A10060
Medical Ward unit with lighting profile only. The unit includes
general and reading light and a limited number of electrical
A10040
Easy to upgrade with additional electrical and gas functions
after installation.
A10390
A10380
Medical Ward unit with lighting profile in full length and gas
pipe cover of TRL type. Suitable for common wards in hospitals.
Medical Ward Unit with lighting profile and gas pipe cover in
full length. Accessory rail for attachment of gas and other hospital equipment. INKA cable trunking in two compartments,
where the lower compartment is screened off by an integral partition. Suitable for common wards in hospitals.
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 13
Medical Ward Unit in Intensive Care
A10400
Wall mounted IC unit
Medical Ward Unit with INKA cable trunking in two compartments and gas pipe cover in full length. Possibility for a large
number of electrical and gas functions. Double accessory rail
system with monitor shelf and examining lamp.
A10410
Ceiling mounted IC unit
Ceiling mounted Medical Ward Unit for one or several patient
beds. The electrical, lighting and gas sections can be double-side
equipped.*
14 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
* Ceiling and Floor/Ceiling mounted Intensive Care units are
customer specific solutions and are offered on special request
A10590
Floor/Ceiling mounted IC unit
Floor/ceiling mounted Medical Ward Unit with possibility of
maximizing number of electrical and gas functions. The vertical
* Ceiling and Floor/Ceiling mounted Intensive Care units are
customer specific solutions and are offered on special request
as well as the horizontal sections can be double-side equipped.*
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 15
Cable Trunking Design
Aluminium cable trunking for wall surface and flush
mounting. Cable shelves can be used to divide the
trunking into various compartments, so that power
and low current cables can be routed in the same
trunking as telecommunications and data cables.
Several cable trunking products, e.g. INKA-161-2 and
INKA-217-2 are two-compartment systems, in which
the lower compartment is screened off by an integral
partition. Both compartments have separate flush
front covers. Earthing slots are provided in trunking
base and front cover.
For Cable capacity information, see page 50-58.
INKA-101/72 and -101/90
R33210M
R32430M
L38880
For wall surface mounting.
INKA-123/72 and -123/90
R33230M
R32480M
L38890
For wall surface mounting.
INKA-123-4/72
R33220
L38900
For flush mounting.
INKA-161-2/72 and -161-2/90
16 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
R33250M
R32500M
L38920
For wall surface mounting. Two screened
compartments with separate front covers.
INKA-161-3/72 and -161-3/90
R33260M
R32780M
L47890
For wall surface mounting.
INKA-183-2/90
R33280M
L47920
For wall surface mounting. Two screened
compartments with separate front covers.
INKA-217-2/72 and -217-2/90
R33290M
R33170M
L28370
For wall surface mounting. Two screened
compartments with separate front covers.
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 17
Composition of Lighting Profile
The Medical Ward Unit offers many possible variations for installation of reading/examining light as
well as general light. This makes it possible to obtain
the right lighting environment for varying ward requirements.
Fitting the lighting profile around the entire room
gives maximum space and flexibility for lighting
installation.
Reading/Examining Light
General Light
Lighting Profile Dimensions
A suitable number of lighting rails can be fitted in the
upper compartment of the profile for general (indirect) light. The indirect light can be of standard fluorescent tubes of type T26 (36 or 58W). Alternatively
the new technology fluorescent tubes of type T5
(28W or 54W) can be chosen. The lighting rails can
either be installed with standard or electronic ballasts.
There is also space for a 5W night light in these rails.
The lighting profile can be cut to length for a smaller
unit and fitted with stop ends for mounting over a
bed. Whether the general light is to be provided by
standard fluorescent tubes of type T26 or of type T5,
the minimum length (L) for cutting the lighting profile can be seen in Figure 1.
Lighting rails for reading/examining are installed in
the lower compartment over the respective beds. The
reading/examining light uses standard compact TC
tubes (18 W or 36 W) with either standard or electronic ballasts. The TC 36 W compact tube may also
be installed with a dimmable feature for adjustment as
a reading or examining light.
Figure 1 – Lighting Profile
L
A10600
L1
L = Length of lighting profile excluding stop ends (2x2mm)
General light - Minimum dimensions (mm)
Type
L
Reading/Examining light (mm)
Type
L1
T26 36W
1400
TC 18W
200
T26 58W
1700
TC 36W
400
T5 28W
1250
TC 36W dimmable (1-10V)
400
T5 54W
1250
18 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Placement of Light Fitting Rail
The Light Fitting Rail of type TC (A) is always in one
section and is installed in the lower compartment of
the lighting profile.
The Light Fitting Rail of type T26 or T5 is divided
into two sections. The Light Tube section (B) is
installed in the upper compartment of the Lighting
Profile. The ballast section (C) can be installed in the
lower compartment for a short lighting profile section
or in the upper compartment for a long lighting profile section.
All rails are provided with push-in termination for
easy wiring. For selection of Light Fitting Rail, see
page 41.
A10610
Figure 2 – Placement of Light Fitting Rail into the Lighting Profile
Length of Light Fitting Rail (mm)
Type
A
B
C
TC
18W
550
TC
36W
830
TC
36W dimmable
830
T26
36W
1300
400
T26
58W
1600
400
T5
28W
1230
400
T5
54W
1230
400
T5 Tubes
Electronic Ballasts
The new T5 fluorescent tubes are characterized by a
reduced cross-sectional dimension (16 mm). The
more conventional T26 tubes are 26 mm in diameter.
More important are the economical advantages of the
T5 tubes:
•
Higher luminous efficiency
•
Optimized thermal behavior
•
Longer Lamp service life
All fluorescent tubes can be connected to electronic
ballasts (35000 Hz). Lighting with electronic ballasts
gives an energy saving of about 25% compared to
standard ballasts (50Hz). The lamp service life of the
fluorescent tube increases by up to 50%.
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 19
Lighting Techniques
The values stated below are valid for a 2-bed room. Room dimensions are L=4.5 m, W=4 m, H=2.5 m.
General Light
General lighting is indirect, creating a comfortable
atmosphere by the use of non-dazzling illumination.
Fluorescent lamps in either T26 (36 W or 58 W) or T5
(28 W or 54 W) format may be used.
Medium intensity of illumination
The use of fluorescent lamps conserves energy while
providing the required illumination intensity. The
warm-white colour of the light helps provide a sense
of comfort and well being.
DIN 5035 Part 3
2 x T26 36W
2 x T26 58W
2 x T5 28W
2 x T5 54W
100 lx
103 lx
144 lx
103 lx
174 lx
Light Dispersion
Measuring Levels
1)
2)
A10620
A10630
3)
1) Reading level 2) Examining level 3) Bed level.
Reading Light
The reading light is placed above each bed. The choice
is either a TC 18W or 36W compact tube. The statio-
nary reading light gives a non-dazzling light without
disturbing other patients in the same room.
DIN 5035 Part 3
1 x TC 18W*
1 x TC 36W
200 lx
231 lx
354 lx
Medium intensity of illumination on the reading surface (75º)
* with indirect room light T26 36W
Examining light
When examining and attending the patient in bed, a
certain intensity of illumination is required. These
Medium intensity of illumination at bed length
axis, 0,85m above floor
Minimum intensity of illumination at bed length axis
* with indirect room light T26 36/58W
20 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
lighting values are achieved when both the general
light and the reading light are turned on.
DIN 5035 Part 3
1 x TC 18W *
1 x TC 36W *
alt. dimmable*
300 lx
327/392 lx
537/622 lx
≥ 150 lx
155/198 lx
193/253 lx
Isolux diagram, 2-bed room
Room dimensions: Length 4.5 m x Width 4.0m x Height 2.5 m.
Reflexion values: 0.8 Ceiling, 0.5 Wall, 0.3 Floor
Measuring height 0.85 m.
50
50
100
150
100
200
250
150
300
200
350
250
300
350
General light
Reading/examining light
Medium intensity of illumination
2 x T26
2 x TC
246 lx
36W
36W
General light
Reading/examining light
Medium intensity of illumination
2 x T5
2 x TC
347 lx
54W
36W
Night light
The night light helps the hospital staff to move in the
room without switching on the main lighting. The
night light can be a 5W bulb fastened on the Light
Medium intensity of illumination at bed
Fitting Rail. It can also be a light diode unit producing 5 lx at short distance.
DIN 5035 Part 3
5W bulb
Light diode unit
5 lx
≥ 5 lx
≤ 5 lx
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 21
Gas Outlet Installation Techniques
The Thorsman Medical Ward Unit offers the possibility to include gas outlets to Scandinavian, German
and British standards. The selection includes outlets
for breathing oxygen, nitrous oxide, breathing air, gas
exit, vacuum and instrumental air, see page 44.
Figure 1 – Positioning of gas outlets
The gas outlet is fixed on a wall-mounted fixing profile, the gas outlet cover is snap-fitted on to the fixing
profile.
The gas outlet cover profile is designed to provide
large capacity for gas piping. The cover is prepared for
choice of 1,2,3, or 4 gas outlets, see page 45. For more
gas outlets a combination of these covers is possible.
The positioning of the gas outlets is prepared for
c/c measure of 200 mm. This distance is suitable to
give appropriate space for a smooth installation and
gas pipe connection.
300
150
150
500
150
200
150
700
150
200
200
150
150
200
200
200
150
A10650
A10640
900
The Medical Ward Unit is normally installed as one entire unit. If preferred, the gas outlet profile can be installed separately from the
electrical and lighting section.
22 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Gas Outlet Installation Techniques
A10660
The gas pipe cover comes in two designs, depending upon how many outlets are required.
200
600
A10670
500
A10680
1. For a limited amount of gas outlets the gas pipe cover can be of TRL type.
200
600
A10690
900
2. For a large number of gas outlets , a full length gas pipe cover is recommended for piping capacity.
Gas connection standards
Different standards for gas connection are used in various countries. Common to the different standards is
the unique adaptation technique in combination with
a colour code, preventing connection of the wrong
type of equipment to the wrong gas type.
The program offers gas outlets according to
Scandinavian, German (DIN, two types) and British
(BS) standard. The flexible mounting technique also
makes it possible to mount gas outlets according to
additional standards or local brands.
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 23
Layout Planning
The Thorsman Medical Ward Unit (MWU) can to a
large extent be adapted to the existing room dimensions. In the layout planning phase there has to be
paid attention to certain minimum dimensions when
specifying the Medical Ward Unit.
The graphics below visualizes a layout of a Medical
Ward Unit for up to 3 beds. The length of the Medical
Ward Unit is mainly depending on the lighting alternative chosen. The dimensions marked in the graphics
are of importance when deciding the total installation.
Dimensions:
A
B
Distance from the left end of the MWU until centre of the reading light.
Distance between centre of reading lights for two beds.
Recommended minimum distance is 1600 mm.
Distance from the right end of the MWU until centre of the reading light.
Total length of the MWU.
Mounting height from floor to top end of the MWU.
Recommended distance is 1800 mm.
C
L
H
A10710
H
The minimum dimensions per 1, 2, 3 beds is depending on the general light chosen, see table below:
No of
General Light
beds
*)
Reading
Minimum dimensions* mm
Light
A
B
C
L
1
2
3
1 x T26 36W
2x”
3x”
TC 18 or 36W
”
”
700
700
700
1600
1600
700
700
700
1400
3000
4600
1
2
3
1 x T26 58W
2x”
3x”
”
”
”
850
850
850
1700
1700
850
850
850
1700
3400
5100
1
2
3
1 x T5 28/54W
2x”
3x”
”
”
”
625
625
625
1600
1600
625
625
625
1250
2850
4450
Dimensions excluding stop ends (2 x 2 mm)
24 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Colour Choice
All Thorsman service carriers may
be powder coated in any NCS or
RAL colour with any gloss value.
Below you will find 19 of our
stocked colours, in which our products can be powder coated and
delivered on short notice.
All other RAL or NCS colours
are to be offered on special request.
When ordering products in a
stocked colour, use the three character code which specifies both colour
and gloss, eg L01 (=RAL 9010, Semi
gloss). Place the code immediately
after the article number.
P3601
Stocked RAL colours
RAL 9010
Code: L01 Semi gloss
Code: L02 High gloss, L03 Textured*
RAL 7035
Code: L22 High gloss
Stocked NCS colours
NCS 0402-B91G
(≈NCS S 0500-N)
NCS S 2502-Y
NCS S 6030-R70B
RAL 9007
RAL 1013
NCS S 3060-B
RAL 1018
RAL 6026
NCS S 0580-Y10R
Code: L23 High gloss
Code: L61 High gloss
Code: L06 High gloss
Code: L71 High gloss
A selection of non-stocked RAL colours
RAL 5024
Code: L31 Semi gloss
Code: L11 Semi gloss
RAL 1017
Code: L55 Semi gloss
Code: L56 Semi gloss
Code: L65 Semi gloss
A selection of non-stocked NCS colours
NCS S 1010-G03Y
NCS S 1005-Y80R
Non-stocked RAL or NCS colours may be offered on special request.
Note: For technical reasons due to the printing process, the colour representations may deviate slightly from the reference colours. There may
also be slight differences in shade between batches delivered, even with the same NCS/RAL code. If colour matching with other products is
important, please contact Thorsman customer service.
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 25
Service Carriers
Trunking bases
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
100/72/2500
5504 000
5504 002
123/72/2500
5507 000
5507 002
Trunking base, INKA-101/72
Can be divided into four compartments. With earthing slot.
Available cut to length, max 5.0 m by special order.
L31700
INKA-U101
Anodized
Aluminium
Powder coated1)
Trunking base, INKA-123/72
Can be divided into four compartments. With earthing slot.
Available cut to length, max 5.0 m by special order.
L31400
INKA-U123
Anodized
Aluminium
Powder coated1)
Trunking base, INKA-123-4/72
Can be divided into four compartments. With earthing slot.
Available cut to length, max 5.0 m by special order. Also suitable as feeder trunking.
L32730
INKA-U123-4
Anodized
Aluminium
Powder coated1)
145/72/2500
5506 310
5506 319
L31450
Trunking base, INKA-161-2/72
Can be divided into five compartments. Includes compartment for telephone communications, data
cables, etc. The trunking is pre-punched every 200 mm between the lower and upper compartment.
Earthing slot provided. Available cut to length, max 5.0 m by special order.
INKA-U161-2
Anodized
Aluminium
Powder coated1)
161/72/2500
5510 010
5510 012
161/72/2500
5510 020
5510 022
L31300
Trunking base, INKA-161-3/72
Can be divided into four compartments. With earthing slot.
Available cut to length, max 5.0 m by special order.
INKA-U161-3
Anodized
Aluminium
Powder coated1)
L31250
Trunking base, INKA-217-2/72
Can be divided into eight compartments. Lower compartment for telecommunications, data cables,
etc. The trunking is pre-punched every 200 mm between the lower and upper compartment.
Earthing slots provided. Available cut to length, max 5.0 m by special order.
INKA-U217-2
Anodized
Aluminium
Powder coated1)
217/72/2500
5514 000
5514 002
100/90/2500
5519 010
5519 012
123/90/2500
5506 400
5506 402
L31020
Trunking base, INKA-101/90
Can be divided into four compartments. With earthing slot.
Available cut to length, max 5.0 m by special order.
INKA-U101
Anodized
Aluminium
Powder coated1)
L31090
Trunking base, INKA-123/90
Can be divided into four compartments. Earthing slot provided.
Available cut to length, max 5.0 m by special order.
1)
INKA-U123
Anodized
Aluminium
Powder coated1)
Colour choice, see page 25.
26 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Service carriers
Trunking bases (cont.)
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
L31170
Trunking base, INKA-161-2/90
Can be divided into five compartments. Includes compartment for telecommunications, data cables,
etc. The trunking is pre-punched every 200 mm between the lower and upper compartment.
Earthing slots provided. Available cut to length, max 5.0 m by special order.
INKA-U161-2
Anodized
Aluminium
Powder coated1)
161/90/2500
5519 020
5519 022
161/90/2500
5512 230
5512 232
Trunking base, INKA-161-3/90
Can be divided into four compartments. With earthing slot.
Available cut to length, max 5.0 m by special order.
L32790
INKA-U161-3
Anodized
Aluminium
Powder coated1)
Trunking base, INKA-183-2/90
Can be divided into six compartments. Includes compartment for telecommunications, data cables,
etc. The trunking is pre-punched every 200 mm between the lower and upper compartment.
Earthing slots provided. Available cut to length, max 5.0 m by special order.
L31240
INKA-U183-2
Anodized
Aluminium
Powder coated1)
183/90/2500
5519 060
5519 062
Trunking base, INKA-217-2/90
Can be divided into eight compartments. Includes compartment for telecommunications, data
cables, etc. The trunking is pre-punched every 200 mm between the lower and upper compartment.
Earthing slots provided. Available cut to length, max 5.0 m by special order.
Anodized
Aluminium
Powder coated1)
217/90/2500
5519 040
5519 042
Type/
Description
Colour/
Finish
Dimensions
A/B/C (mm)
Art. No.
L44190
INKA-U217-2
Front covers
Materal
Front cover
FCA-F40, F80. Snap-fit fastening onto trunking.
With earthing slots.
Anodized
Aluminium
Powder coated1)
40/2500
5580 030
5580 039
FCA-F80
Anodized
Aluminium
Powder coated1)
80/2500
5580 080
5580 089
L30840
L30830
FCA-F40
1)
Colour choice, see page 25.
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 27
Service carriers
Stop ends
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
L32410
L32570
L46040
Stop end
Stop ends including screws for fixing and angle brackets (for 72 mm deep trunking only). The angle
brackets are inserted in the jointing piece rails (for INKA-101 also into the earthing rail). Stop ends
are used to terminate cable trunking and to limit electric fields.
INKA-ES101/72
Powder coated1)
Aluminium/Steel2)
100/72/51
5504 172
INKA-ES123/72
Powder coated1)
Aluminium/Steel2)
123/72/36
5507 172
INKA-ES161/72
Powder coated1)
Aluminium/Steel2)
161/72/36
5510 172
INKA-ES217/72
Powder coated1)
Aluminium/Steel2)
217/72/36
5514 172
INKA-ES101/90
Powder coated1)
Aluminium
100/90
5590 217
INKA-ES123/90
Powder coated1)
Aluminium
123/90
5591 152
INKA-ES161-2/90
Powder coated1)
Aluminium
161/90
5590 277
INKA-ES161-3/90
Powder coated1)
Aluminium
161/90
5591 062
INKA-ES183-2/90
Powder coated1)
Aluminium
183/90
5591 032
INKA-ES217-2/90
Powder coated1)
Aluminium
217/90
5590 307
Stop end
INKA-ESV123-4/72
Left
Powder coated1)
Aluminium
5590 203
Powder coated1)
Aluminium
5590 208
Colour/
Finish
Material
INKA-ESH123-4/72
Right
Trunking Accessories
Type/
Description
Dimensions
A/B/C (mm)
Art. No.
Cable shelf
Used to divide the trunking into a maximum of eight compartments. Cable shelves are used for
improved segregation and screening between power, low current, telephone and data cables.
L32020
KH72 for 72 mm deep and KH90 for 90.
TTI-KH72
TTI-KH72
TTI-KH90
TTI-KH90
Anodized
Unspecified
Untreated
White
Aluminium
PVC
Aluminium
PVC
12/72/500
12/72/500
12/90/500
12/90/500
5590
5590
5590
5590
312
314
315
316
L32010
Cable clip
Snap-fitted on cable shelf. Prevents cables falling out of trunking compartment before front cover is
installed.
TTI-KHK
Brown
ABS
-
5590 340
L53540
Mounting washer
Used when mounting the trunking directly on the wall. The carrier is hung on a number of mounting
washers before being secured to the wall with screws.
TTI-MB
Black
PA
16/6/19
1)
Colour choice, see page 25.
2)
If trunking base in anodized finish is being used, powder coated stop end in ’RAL 9007’ is recommended.
28 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
5590 180
Service carriers
Trunking Accessories (cont.)
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
Untreated
Aluminium
8/32/60
5590 112
Jointing piece
For jointing trunking.
L44850
INKA-SSA
Earthing clamp
For bonding the front cover, trunking base and accessories to earth.
Zinc passivated
Steel
–
5590 500
L34520
TTI-JB
Earth wire
For bonding the front cover, trunking base and accessories to earth.
Green/Yellow
Copper
Length = 300 mm
5590 505
L51170
TTI-JK300
L32140
Sound insulation strip
For sound insulation of up to 53 dB where trunking passes through walls. Suitable for up to four
compartments. Supplied in sets of four.
TTI-T3045
TTI-T5070
Black
Foam rubber
30/350/45
50/350/70
5590 410
5590 414
Ø 13
5590 520
Cup washer
For covering screw heads and protecting the cable.
Black
PE
L33370
TTI-KB
L33380
Grommet
To cover edges where cables passes between trunking base and lighting profile. Provides a hole of
Ø 19 mm for cable entry. (Use plunge tool ISV-HS, see page 43).
INKA-GF19
White
PP
Ø 20
5902 100
Edge protection
To protect cables from sharp edges when a small gap is left between two aluminium trunking bases.
Transparent
PE
–
5902 120
–
5586 600
L33390
INKA-KD82
L12600
Locking plate
To fix various equipment directly to the trunking.
TTI-GM
Grey
PA
L33090
Washer
For insertion between cable trunking/lighting profile/gas profile and wall to compensate for uneveness in the wall.
TTA-KM1
TTA-KM3
TTA-KM5
Grey
PA
114/1/38
114/3/38
114/5/38
5583 405
5583 408
5583 410
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 29
Power
1. Angled corners for simple cable entry with two adjoining boxes
2
1
2. Snap-fitting to F80™ front opening. Fits all FrontLine service carriers.
3
3. Strain relief clamps without screws
4
4. Large label window, 66 x 10 mm, for fixed mounting in the box
5
5. Opening for label window
6. Bridging terminal 4 x 2.5 mm2. Push-in.
6
7. Outlet recesses angled at 37°
8. Child protection
7
P2158
8
Colours
White = NCS 0701-G46Y ≈ RAL 9016
Red = RAL 3003 ≈ NCS 3163-Y97R
Green = RAL 6029 ≈ NCS 3658-G03Y
Connection kits, Schuko
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
With child protection
CYB-PS
White
PC/ABS
84/52/84
5975 000
With child protection and LED indication, green
CYB-PS
White
PC/ABS
84/52/84
5975 005
L58920
L57350
Connection kit Single earthed socket outlets, Schuko 90°
Includes box, adapter, 2x strain relief clamps, cover, label and label window.
The socket has push-in terminals.
Connection kit Double earthed socket outlets, Schuko 37°
Includes box, adapter, 2x strain relief clamps and cover. The socket has push-in terminals.
With label and label window.
(The different colours may be used for special outlet designation e.g., priority power)
L46510
With child protection
CYB-PS
White
Red
Green
Orange
PC/ABS
84/46/110
5951
5951
5951
5951
480
482
485
487
Connection kit Three-gang earthed socket outlets, Schuko 37°
Includes box, adapter, 2x strain relief clamps and cover. The socket has push-in terminals.
With label and label window.
(The different colours may be used for special outlet designation e.g., priority power)
L46520
With child protection
CYB-PS
White
Red
Green
Orange
30 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
PC/ABS
84/46/142
5951
5951
5951
5951
430
432
435
437
Power
Connection kits, Double socket, French Standard
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
French Standard, for Poland and France (with Push-in terminals)
CYB-outlet. Two-gang, 16A/250V. Includes double earthed socket, box, strain relief clamps and
spacer.
CYB-PF
CYB-PF
White
Red
PC/ABS
84/45/110
84/45/110
5969 215
5969 217
L57830
French Standard, for Belgium, Poland and France (with screw terminals)
CYB-outlet. Two-gang, 16A/250V. Includes double earthed socket, box, strain relief clamps and
spacer.
CYB-PF
CYB-PF
White
Red
PC/ABS
84/45/110
84/45/110
5969 210
5969 212
French Standard, for Czech Rep., Poland and France (with Push-in terminals)
CYB-outlet. Two-gang, 16A/250V. Includes double earthed socket, box, strain relief clamps and
spacer.
CYB-PF
CYB-PF
White
Red
PC/ABS
84/45/110
84/45/110
5969 115
5969 117
L57820
French Standard, for Czech Rep., Poland and France (with screw terminals)
CYB-outlet. Two-gang, 16A/250V. Includes double earthed socket, box, strain relief clamps and
spacer.
CYB-PF
CYB-PF
White
Red
PC/ABS
84/45/110
84/45/110
5969 110
5969 112
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
Connection kits, British Standard
Connection kit, Power, single, 13 A
Snap-fastened 13 A single standard outlet, consisting of CYB-S40 box, outlet, adapter and front
plate. The outlet can be mounted either horizontally or vertically. Used as single outlet, in conjunction with CYB outlets for power, telecommunication, data and blank covers.
CYB-PU, unswitched
White
PC/ABS
84/47/84
5961 130
CYB-PU, switched
White
PC/ABS
84/50/84
5961 120
CYB-PU, switched
with indicator
White
PC/ABS
84/50/84
5961 140
L44520
L44510
L44500
Type/
Description
L44550
L44540
L44530
Connection kit, power, twin, 13 A
Snap-fastened 13 A double standard outlet, consisting of box CYB-D40, outlet, adapter and front
plate. Used as double outlet, in conjunction with CYB outlets for power, telecoms, data and blank
covers.
CYB-PU, unswitched
White
PC/ABS
84/47/142
5961 135
CYB-PU, switched
White
PC/ABS
84/50/142
5961 125
CYB-PU, switched
with indicator
White
PC/ABS
84/50/142
5961 145
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 31
Power
Basic kit, CEE socket outlets
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
L28200
L28190
CEE socket outlets
Power socket outlets including mounting frame for 80 mm front (F80®) opening. To be used in conjunction with Thorsman MIB-box.
Single-phase CEE216-6, 250 V/16 A for cable 3x1.5 mm2
CYB-C220
Grey/blue
PC
82/49/82
5960 110
Three-phase CEE416-6, 440 V/16 A, for cable 5x2.5 mm2
CYB-C380
Grey/red
PC
82/57/82
5960 100
Connection kit, Surge protection
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
L53510
Connection kit with overvoltage protection 16 A/230 V, TN system
CYB-PP connection kit with overvoltage protection is suitable for 230 VAC and TN system.
The protection is intended for individual workplaces and not for entire buildings or installations. The
protection has a built-in acoustic alarm and external indications for operation and overloading. The
acoustic alarm is controlled with the aid of a switch mounted in the front. The protection can also
be monitored by a circuit-opening contact for connection to a monitoring centre, for example.
CYB-PP
White
PC/ABS
84/53/84
5972 010
Connection kit, Switches
Type
Description
Closed
position
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
Connection kit, Switches, 16A/250V
Includes box, socket, adapter, two strain relief clamps, cover with rocker, label with label window.
L57370
Single-pole
CYB-PB
Up
White
PC/ABS
84/54/84
5980 002
Single-pole, spring-return rocker
CYB-PB
Up
White
PC/ABS
84/54/84
5980 007
Single-pole, red indicator lamp
CYB-PB
Up
White
PC/ABS
84/54/84
5980 012
Single-pole, green indicator lamp
CYB-PB
Up
White
PC/ABS
84/54/84
5980 017
Double-pole
CYB-PB
White
PC/ABS
84/54/84
5980 032
Single-pole/two-way
CYB-PB
Up
White
PC/ABS
84/54/84
5980 052
Intermediate
CYB-PB
White
PC/ABS
84/54/84
5980 062
Up
Up
32 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Power
Connection kits, Switches (cont.)
Type
Description
Closed
position
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
Connection kit, switches, 16 A/250 V
Includes box, socket, adapter, two strain relief clamps, cover with two rockers and label with label
window.
L57360
Two-gang
CYB-PB
Up
White
PC/ABS
84/54/84
5980 072
Venetian blind
CYB-PB
Up
White
PC/ABS
84/54/84
5980 087
Venetian blind, single-pole switch
CYB-PB
Up
White
PC/ABS
84/54/84
5980 082
Double single-pole/two-way
CYB-PB
Up
PC/ABS
84/54/84
5980 057
16/25/39
5972 105
White
L57480
Pilot lamp 0.9 mA 250 V
Intended to be mounted together with switch.
CYB-GL2
L58940
Push-in plint
For single socket outlets, switches and dimmers. 16A/250V, 3x2,5 mm2.
CYB-PT
White
10/10/14
5972 200
Double single-pole/
two-way (6/2)
D13950
Double-pole (2)
D13940
D13970
D13910
Intermediate (7)
Two-gang (5)
Venetian blind single-pole
D13990
D13960
Single-pole/two-way (6)
Single-pole
with indication (1)
D13980
Single-pole with
spring-return (1)
Single-pole (1)
D13900
D13920
D13930
Wiring diagrams for switches
Venetian blind
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 33
Power
Connection kit
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
L59000
Light Diode Kit
The light diode kit consists of 8 pcs. high intensity diode in a CYB mounting frame with protective
casing. For night light in common ward. Available autumn 1999.
CYB-PO angled
White
PC/ABS
84/50/84
Material
Dimensions
A/B/C (mm)
5974 010
Connection kit, Dimmers 230V, F80 Mounting
Type/
Description
Colour/
Finish
Art. No.
L57840
Dimmers
To control fluorescent light fittings with controllable HF units. 1-50 HF units can be controlled. The
positive and negative poles of the controller must be connected to the positive and negative poles
of the HF unit. Poles 1 and 2 of the switches are wired to switch the fittings on and off. The break
function is rated at max 6 A (max 360 W fluorescent tube rating). If the load is higher, the break
function can control a relay coil instead. Note that the fluorescent tubes must not go out at the minimum setting of the controller. Rating 1-10 V for 1-50 HF units made by Philips, Osram, Siemens,
Helvar, etc. To be connected to the plus and minus connections of the controller.
Note that it is very important to observe correct polarity throughout the installation.
Controller 1-10 V (APE 10 T).
CYB-PR
White
PC/ABS
84/53/84
5985 020
For incandescent lamps and electronic transformers, 300W (ATD 300R).
CYB-PR
White
PC/ABS
84/53/84
5985 000
For incandescent lamps and conventional transformers, 400W, VA (AD 400UTT).
CYB-PR
White
PC/ABS
84/53/84
5985 030
For incandescent lamps, fluorescent lamps with dimmable electronic ballast and conventional transformers, 900W, VA (ATTD 1000RL).
CYB-PR
White
PC/ABS
84/53/84
5985 050
Dimensions
A/B/C (mm)
Art. No.
Mounting boxes and blank covers
Type/
Description
Colour/
Finish
Material
L44350
L44360
Mounting box
For the installation of power and low-current equipment in FrontLine service carriers with 80 mm
front (F80™). When fitted with screw pillars CYB-P40, the box is also suitable for standard socket
outlets with centres to BS 4662:1970 and with screw pillars CYB-P3 for 60 mm centres.
Single box with ten 16 mm knockouts
CYB-S40
White
PC
Double box with fourteen 16 mm knockouts
CYB-D40
White
PC
79/44/84
5961 030
79/44/142
5961 035
Blanking cover, single
CYB-PL
White
PC/ABS
84/12/84
5961 550
Blanking cover, double
CYB-PL
White
PC/ABS
84/12/142
5961 555
L44370
L44380
Blanking cover
Blanking cover for snap fitting. Includes adapter and front plate. Fits CYB-S30 and CYB-S40. To
blank off mounting boxes for future expansion of electrical installations.
34 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Power
Accessories for Mounting boxes and Mounting kits
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
L44390
Screw pillars
Screw pillars which snap-fit to CYB-D40 and CYB-S40 boxes, so that standard socket outlets can be
fitted. CYB-P40 to British standard, and CYB-P3 for 60 mm centres.
CYB-P40
CYB-P3
White
PA
14/12/37
10/11/42
5961 505
5961 506
L16310
Adapter, for flexible conduit
For snap-fitting flexible conduit as a protective cable conduit. CYB-D20 is used for 20 mm, CYBD25 for 25 mm flexible conduit.
CYB-D20
CYB-D25
Black
PA,PP
Ø 26/24
Ø 29/26
5956 250
5956 255
L46080
Earthing terminal
Used in CYB-S30/D30 and S40/D40 mounting boxes. The earthing terminal can take 2x4 mm2
cable.
CYB-ET
Natural
Brass
–
5961 500
L45400
Conduit bush
For use between CYB mounting boxes, mounted directly beside each other for protection of cables.
CYB-CT
PC/ABS
5961 510
L34510
Strain relief
Used when connecting power cable to box. Snap-fits in the recess of the CYB box.
FDS
Orange
25/27/17
5956 150
Installation boxes
Single and double installation box intended for mounting of standard devices in front F80® service
carriers, MIB-A1 for devices with a c/c distance of 60 mm and MIB-A2 for a c/c distance of 71
mm. Can be combined with junction box MIB-J.
White
PC/ABS
79/45/71
5586 150
MIB-A2
White
PC/ABS
79/45/152
5586 155
L59810
L59800
MIB-A1
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 35
Power
Mounting kit for accessories (other suppliers)
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
CYB-MB
White
PC/ABS
84/50/84
5971 790
CYB-MB
White
PC/ABS
84/50/84
5971 794
Dimensions
A/B/C (mm)
Art. No.
L46940
L13300
Mounting kit for other types of socket outlets
Includes mounting box and universal adapter for socket outlets according to DIN 49075.
Equipotential connection
Type/
Description
Colour/
Finish
Material
Equipotential connection
Equipotential connection in front cover F80®. For potential balancing, max. 63A or according to
DIN standard. Pole marking yellow/green.
Anodized
Powder coated1)
Aluminium
80/-/110
5971 302
5971 301
CYB-PO, DIN
Anodized
Powder coated1)
Aluminium
80/-/110
5971 307
5971 306
L50820
L50540
CYB-PO, (max 63 A)
Equipotential connection kit
Equipotential connection kit for snap-in mounting in service carriers with front cover F80®.
For potential balancing according to DIN standard 42801.
White
PC/ABS
84/28/84
5971 315
L64230
CYB-PO, DIN
Plug for equipotential connection. DIN type
L64280
CTA-PO
1)
Colour choice, see page 25.
36 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
5914 050
Power
DIN enclosures
Type/
Description
Material
Colour
Dimensions
A/B/C (mm)
Art. No.
L61530
DIN enclosure
4-module DIN enclosure intended for snap-in mounting in service carriers with front F80®. The
enclosure is suitable for 1-4 DIN modules and has a hinged lid to protect the devices.
CYB-PN
PC/ABS
White
84/86/168
5960 251
White
84/86/168
5960 256
Colour
A/B/C (mm)
Dimensions
Art. No.
L61540
Same as above but with keylock and keys to lock the lid.
CYB-PN
PC/ABS
Circuit breakers
Type/
Description
Circuit breakers
Miniature circuit breakers (MCB) 6 kA according to DIN VDE 0641, Part 11/08.92 and
EN 60 898, B- and C- characteristics. Rated current 10 A and 16 A. 1, 2, 3-poles (1-2-3 DIN
modules). To be mounted in CYB-PN DIN-enclosure. Material: ABS.
L46870
CYB-PN,
CYB-PN,
CYB-PN,
CYB-PN,
CYB-PN,
CYB-PN,
CYB-PN,
CYB-PN,
CYB-PN,
CYB-PN,
1-pole,
1-pole,
2-pole,
2-pole,
2-pole,
2-pole,
3-pole,
3-pole,
3-pole,
3-pole,
C10A
C16A
B10A
C10A
B16A
C16A
B10A
C10A
B16A
C16A
Grey
90/74,5/18
Grey
90/74,5/36
Grey
90/74,5/54
5960
5960
5960
5060
5960
5960
5960
5960
5960
5960
480
485
460
490
465
495
470
500
475
505
Earth leakage breaker
Residual-current circuit breakers for pulsating direct and altering earth-leakage current according to
DIN VDE 0644, Part 1/10.85. Resistance to surge current up to 250 A. Rated current 25 A. Rated
residual current 0,03 A.2 and 4 poles (2 and 4 DIN modules). To be mounted in CYB-PN DINenclosure. Material: ABS. Colour: Grey.
CYB-PN, 2-pole
CYB-PN, 4-pole
Grey
Grey
84/74/36
84/74/72
5960 415
5960 410
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 37
Communication
9
1
3
2
4
1.
2
3.
4.
5.
6.
6
7.
5
8.
9.
P2159
7
8
Extra distinct label 66x10 mm
Label window to protect label (snap-fits into mounting frame)
Connectors
Snap-fitting cover
Mounting frame for F80®. Suitable for horizontal or vertical
snap-fitting.
Mounting frame which allows a full visual check of the completed installation
Modular mounting plate for angled or flush snap-fitting. With
facility for extra marking 21x4.7 mm
Silk-matt glare-free easy-clean surface
Protective cover for data connectors. Additional.
Colours
White = NCS 0701-G46Y ≈ RAL 9016
Connection kits, Data
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
L55310
L55300
Connection kit, LexCom 250, 125 UTP and STP
For mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,
mounting plate, label with label window, connector and termination instructions.
1
2
1
2
1
2
1
2
x
x
x
x
x
x
x
x
Cat6 UTP, A/B
Cat6 UTP, A/B
Cat6 STP, A/B
Cat6 STP, A/B
Cat5e UTP, A/B
Cat5e UTP, A/B
Cat5e STP, A/B
Cat5e STP, A/B
White
PC/ABS
84/50/84
White
PC/ABS
84/30/84
5974
5974
5974
5974
5970
5970
5970
5970
090
095
100
105
900
905
910
915
L55220
Connection kit, Avaya (Lucent) MPS300, 100 UTP
For mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,
mounting plate, label with label window, connector and termination instructions. With built-in shutters.
1
2
1
2
1
2
1
2
x
x
x
x
x
x
x
x
Cat6 UTP, A
Cat6 UTP, A
Cat6 UTP, B
Cat6 UTP, B
Cat5e UTP, A
Cat5e UTP, A
Cat5e UTP, B
Cat5e UTP, B
White
PC/ABS
84/33/84
White
PC/ABS
84/33/84
5970
5970
5970
5970
5970
5970
5970
5970
960
965
870
975
800
805
810
815
L55220
Connection kit, AMP110, Netconnect UTP and STP
For mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,
mounting plate, label with label window, connector and termination instructions. With built-in shutters.
1
2
1
2
1
2
1
2
x
x
x
x
x
x
x
x
Cat6 UTP A/B
Cat6 UTP A/B
Cat5e UTP A/B
Cat5e UTP A/B
Cat5e STP A
Cat5e STP A
Cat5e STP B
Cat5e STP B
White
PC/ABS
84/33/84
White
PC/ABS
84/33/84
5970
5970
5970
5970
5970
5970
5970
5970
930
935
840
845
850
860
855
865
L55300
Connection kit, IBM ACS type C, UTP and FTP
For mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,
mounting plate, label with label window, connector and termination instructions.
1x
2x
1x
2x
Cat5,
Cat5,
Cat5,
Cat5,
UTP
UTP
FTP
FTP
White
38 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
PC/ABS
84/50/84
5970
5970
5970
5970
355
360
365
370
Communication
Connection kits, Data (cont.)
Type/
Description
Colour
Material
Dimensions
A/B/C (mm)
Art. No
L55270
Connection kit, IBM type 1, STP for structured cable systems
For mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,
mounting plate, label with label window, connector and termination instructions.
1 x IBM type 1, STP
White
PC/ABS
84/50/84
5970 345
L55360
Connection kit, IBM type 2, STP for structured cable systems
For mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,
mounting plate, label with label window, connector and termination instructions.
1x IBM type 2, STP and
1 x 8-way modular socket
White
PC/ABS
84/50/84
5970 350
L55220
Connection kit, Krone Keystone for PremisNET structured cable systems
For mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,
mounting plate with built-in dust shutter, label with label window, connector and termination instructions. With built-in dust shutters.
1
2
1
2
x
x
x
x
Cat5e
Cat5e
Cat5e
Cat5e
UTP, B
UTP, B
STP, B
STP, B
White
PC/ABS
84/33/84
5970
5970
5970
5970
760
765
770
775
Material
Dimensions
A/B/C (mm)
Art. No
Connection kits, fibre optics
Type/
Description
Colour
L55250
Connection kit, LexCom fibre, multimode for fibre-based cable systems
For mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,
mounting plate, SC/SC adapter, label with label window, and termination instructions.
1 x SC-duplex, multimode
2 x SC-duplex, multimode
White
PC/ABS
84/50/84
5974 000
5974 005
L55260
Connection kit, AMP SC and Avaya (Lucent) ST, multimode for fibre-based cable
systems
For mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,
mounting plate, label with label window, connector and termination instructions.
2x ST, Multimode
1 x SC-duplex, multimode
2 x SC-duplex, multimode
White
PC/ABS
84/50/84
5970 375
5970 380
5970 385
L55260
Protective casing for fibre optics
For mounting in FrontLine service carriers together with two CYB-BK sockets. Suitable for horizontal
or vertical mounting, since outlets can be rotated in the casing.
Copper and fibre cables can be connected to the casing. In the short side there is a breakout notch
for a cable nipple type BICC Brand-Rex Blolite system.
CYB-DF
White
PP
79/39/168
5971 220
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 39
Communication
Connection kits, Telephone
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No
Connection kits, modular socket Cat 5e
For mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,
mounting plate, label with label window, connector and termination instructions.
L55310
1x RJ45
2x RJ45
White
PC/ABS
84/26/84
84/26/84
5970 520
5970 525
Connection kits, modular socket
For mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,
mounting plate, label with label window, connector and termination instructions.
1x RJ11
2x RJ11
White
PC/ABS
84/26/84
84/26/84
5970 510
5970 515
Connection kits, Low current and Coaxial cable networks, Aerial, Radio/TV
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No
L28250
L50890
Connection kit, radio/TV aerial
For mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting box
CYB-S40 and connectors with centre plate.
1 x radio/TV
White
PC/ABS
84/51/84
CAN-A75, termination resistor
5970 595
5954 120
L55290
Connection kit, D-connectors
For mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,
mounting plate, label with label window, connector and termination instructions.
1 x D-sub 9-pole
1 x D-sub 15-pole
1 x D-sub 25-pole
White
PC/ABS
84/50/84
5970 310
5970 315
5970 320
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No
Accessories
Protective Casing
For data connectors and cable connections. To be mounted on the back of the mounting frame.
Red
Red
L55300
CYB-RK, high
CYB-RK, low
40 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
PP
63/38/63
63/26/63
5971 200
5971 205
Lighting
Lighting profile, Light fitting rail, Covers, Stop ends
Type/
Colour/
Dimensions
Description
Finish
A/B/C (mm)
Art. No.
L50700
Lighting profile
Provides general light, reading/examining light and night light. To be equipped with Thorsman light
fitting rails in combinations of your own choice. Two separate compartments. With earthing slot.
F80® front cover and CYB outlets will snap fit into the 80 mm front (F80®) opening of the profile.
Available cut to length, max 5.0 m by special order. For cutting of profile in correct length to suit
chosen light fitting rail, see Figure 1 page 18. Material: Aluminium.
MWU-LP
Anodized
Powder coated1)
Anodized
Powder coated1)
72/180/2500 6200
6200
72/180/1250 6200
6200
002
001
006
005
Light fitting rail
To be fixed into the lighting profile. Provides for general light, reading/examining light and night
light. Complete with standard or electronic ballasts and reflectors, ready to use. All wiring on the
rail is provided for. Push-in termination. Prepared for earthing. Screw fixed, supplied with screws.
The rails type T26 and T5 are two-section rails to be installed in separate compartments in the lighting
profile, see Figure 2 page 19. Fluorescent tubes to be ordered separately. Material: Zinc coated steel.
L57550
MWU-LR,
MWU-LR,
MWU-LR,
MWU-LR,
MWU-LR,
Type
Type
Type
Type
Type
TC
TC
TC
TC
TC
18W,
18W,
36W,
36W,
36W,
fluorescent compact
fluorescent compact
fluorescent compact
fluorescent compact
fluorescent compact
dimmable (1-10V)
tube,
tube,
tube,
tube,
tube,
standard ballasts
electronic ballasts
standard ballasts
electronic ballasts
electronic ballasts
40/77/550
40/77/550
40/77/830
40/77/830
6200
6200
6200
6200
40/77/830
6200 212
MWU-LR, Type T26 36W,fluorescent standard tube, standard ballasts
L50500
L50870
L57570
40/77/1300+
40/77/400
MWU-LR, Type T26 36W,fluorescent standard tube, electronic ballasts
”
MWU-LR, Type T26 58W,fluorescent standard tube, standard ballasts 40/77/1600+
40/77/400
MWU-LR, Type T26 58W,fluorescent standard tube, electronic ballasts
”
150
151
210
211
6200 205
6200 206
6200 200
6200 201
MWU-LR, Type T5 28W, fluorescent standard tube, electronic ballasts 40/77/1230+
40/77/400
MWU-LR, Type T5 54W, fluorescent standard tube, electronic ballasts
”
6200 160
6200 165
T26, fluorescent std. Tube 36W
T26, fluorescent std. Tube 58W
T5, fluorescent std. Tube 28W
T5, fluorescent std. Tube 54W
TC, fluorescent compact Tube 18W
TC, fluorescent compact Tube 36W
6200
6200
6200
6200
6200
6200
L=1200
L=1500
L=1149
L=1149
L=217
L=410
225
230
245
250
240
220
L64330
Pull-cord switch
Pull-cord switch, 1-pole 2A 250V, to be mounted on light fitting rail of type TC, 18W and 36W.
Length of cord = 100 cm. Suitable for: MWU-LR Type TC.
MWU-LS
30/11,5/22
6200 301
L50490
L57540
Night Light
Lamp holder for night light. Suitable for lamp bulbs with E14 socket. To be fixed on the light tube
section of the general rails type T26 or T5 (fixation prepared). Lamp to be ordered separately.
MWU-LA
6200 291
IBP/F 5 W bulb (dim)
6200 605
L59000
Light Diode Kit
The light diode kit consists of 8 pcs. high intensity diodes in a CYB mounting frame with protective
casing. For night light in common ward. Available autumn 1999. Material: PC/ABS
1)
CYB-PO angled
Colour choice, see page 25.
White
84/50/84
5974 010
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 41
Lighting
Lighting profile, Light fitting rail, Covers, Stop ends, cont.
Type/
Colour/
Description
Finish
Material
Dimensions
Art. No.
A/B/C (mm)
L50710
Up-light cover
To cover upper part of lighting profile. To be positioned in track of the profile. Material: PMMA
MWU-LC
Transparent
3/100/2500
6200 805
80/2500
5580 080
5580 089
Front cover
Snap-fit fastening onto lighting profile. With earthing slots.
L30840
FCA-F80
Anodized
Powder coated1)
Aluminium
L50780
Prismatic shade
Transparent front cover with a linear prismatic back-side to direct the light. Snap-fit fastening onto
lighting profile.
MWU-LF
Transparent (TC 36W) PMMA
Transparent (TC 18W)
80/400
80/200
6200 800
6200 801
72/180/2
6200 051
6200 056
L50670
Stop end, lighting profile
The stop end is fixed with screws. Supplied with screws 2).
1)
MWU-LE, left
MWU-LE, right
Colour choice, see page 25.
2)
Powder coated1)
Powder coated1)
Aluminium
If lighting profile in anodized finish is being used, powder coated stop end in ’RAL 9007’ is recommended.
Lighting accessories
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
4/11/50
5440 810
L35960
Jointing piece
Used to joint lighting profile. Supplied with screws.
FED-SSJ
Aluminium
Earthing clamp
For bonding lighting profile, light fitting rail, and accessories to earth.
Zinc passivated
Steel
5590 500
L34520
TTI-JB
Earth wire
For bonding lighting profile, light fitting rail and accessories to earth.
Green/Yellow
L51170
TTI-JK 300
42 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Copper
Length = 300mm
5590 505
Lighting
Bed/Examining lamps
Type/Description
Colour/
Dimensions
Finish
A/B/C (mm)
Art. No.
Bed/Examining lamp, Luxo
Supplement to the lamp unit MWU-LP. To be fixed on wall. Provided in 1100 mm armlength.
White
L=1100
6200 401
18W compact flourescent tube.
With a two level switch for reading and night light.
MWU-L18W
White
L=1100
6200 411
Standard light bulb (max 40W), socket E27
MWU-LE27
White
L=1100
6200 416
Wall fixing
MWU-L
White
130/70/130
6200 501
L66030
L66020
13W compact flourescent tube.
MWU-L13W
Bed/Examining lamp, Sunnex
Supplement to the MWU lighting unit. With flexible arm. Built-in 12 V transformer for 20 W halogen. Separate 12 V transformer (plug-in) for 50 W halogen. To be fixed on wall or on desk (screw
fixed or with clamp). Halogen lamp included.
L=900
6200 420
12V/50W halogen lamp, plug-in transformer White
L=900
6200 425
Wall fixing
White
6200 505
Desk fixing (clamped)
White
6200 535
L50860
L50520
L50510
L50600
L50590
12 V/20W halogen lamp, built-in transformer White
12 V/20 W halogen lamp (spare part)
12 V/50 W halogen lamp (spare part)
6200 610
6200 615
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 43
Gas
Gas outlets
Type/
Dimensions
Description
A/B/C (mm)
Art. No.
Gas outlets, AGA MC 70
Gas outlet with self-closing gas-type coded outlet valve and name plate in the colour code of the
gas type. The outlets are supplied with a protective plug to prevent impurities from penetrating into
the outlets when they are not connected.
To be mounted onto the fixing profile. A mounting adaptor is to be used (ordered separately). Gas
pipe, copper ∆ 8 mm, soldered on the inlet tube of the gas outlet.
L50740
Breathing oxygen
Nitrous oxide
Breathing air, 4 bar
Gas exit
Vacuum
Instrumental air, 7 bar
90/68/90
6100
6100
6100
6100
6100
6100
500
505
510
515
520
525
Gas outlet, Greggersen
Gas outlet with self-closing gas-type coded outlet valve and name plate in the colour code of the
gas type according to DIN. To be mounted onto the fixing profile. A mounting adaptor is to be
used (ordered separately). Gas pipe, copper ∆ 8 mm, soldered on the inlet tube of the gas outlet.
L50730
Breathing oxygen
Nitrous oxide
Breathing air, 4 bar
Vacuum
Instrumental air, 7 bar
CO2
40/57/40
6100
6100
6100
6100
6100
6100
530
535
540
545
550
555
Gas outlet, Dräger
Gas outlet with self-closing gas-type coded outlet valve and name plate in the colour code of the
gas type according to DIN. To be mounted onto the fixing profile. Mounting adaptor is to be used
(ordered separately). Gas pipe, copper ∆ 8 mm, soldered on the inlet tube of the outlet.
L50720
Breathing oxygen
Nitrous oxide
Breathing air, 4 bar
Vacuum
CO2
64/72/74
6100
6100
6100
6100
6100
560
565
570
575
580
L50570
O
Gas outlet, MEDÆS, GEM 10
Gas outlet with self-closing gas-type coded outlet valve and name plate in the colour code of gas
type according to BS 5682. To be mounted directly onto the fixing profile (no mounting adaptor is
required). Gas pipe, copper ∆ 12 mm, soldered on the inlet tube of the gas outlet.
X
YG
EN
Breathing oxygen
Nitrous oxide
Breathing air, 4 bar
Vacuum
Instrumental air, 7 bar
Entonox
56/67/90
6100
6100
6100
6100
6100
6100
590
595
600
605
620
625
MWU-GA
for
for
for
for
AGA MC65
AGA MC70
Dräger
Greggersen
L50640
L57530
Mounting adaptor kit
To be used when fixing AGA, Dräger or Greggersen gas outlets to the fixing profile. Complete with
screws. Mounted between gas outlet and the fixing profile. Material PA
44 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Black
Black
Black
Black
72/6,5/50
77/8,5/71
77/8,5/71
77/8,5/71
6100
6100
6100
6100
801
802
803
804
Gas
Fixing profile and Front covers
Type/
Description
Colour/
Finish
Dimensions
A/B/C (mm)
Art. No.
L50750
Fixing profile, gas outlets
To mount gas outlets on to. Wall mounted. For AGA, Greggersen and Dräger gas outlets a mounting adapter is used between the gas outlets and the fixing profile. Medæs outlets are fixed directly
to the fixing profile. For 1–4 gas outlets. Material: Aluminium.
MWU-GF1,
MWU-GF2,
MWU-GF3,
MWU-GF4,
for1 outlet
for 2 outlets
for 3 outlets
for 4 outlets
Untreated
104,2/11,5/300
104,2/11,5/500
104,2/11,5/700
104,2/11,5/900
Front cover, gas outlet, AGA
Front cover to suit AGA MC70 gas outlets. Snap-fitted on to fixing profile2).
For 1-4 gas outlets with a c/c measure of 200 mm. Material: Aluminium.
MWU-GU1, for 1 outlet
MWU-GU2, for 2 outlets
L50830
MWU-GU3, for 3 outlets
MWU-GU4, for 4 outlets
Anodized
Powder coated1)
Anodized
Powder coated1)
Anodized
Powder coated1)
Anodized
Powder coated1)
110/71,5/300
110/71,5/500
110/71,5/700
110/71,5/900
Front cover, gas outlet, Greggersen
Front cover to suit Greggersen gas outlets. Snap-fitted on to fixing profile2).
For 1–4 gas outlets with a c/c measure of 200 mm. Material: Aluminium.
MWU-GU1, for 1 outlet
MWU-GU2, for 2 outlets
L50840
MWU-GU3, for 3 outlets
MWU-GU4, for 4 outlets
Anodized
Powder coated1)
Anodized
Powder coated1)
Anodized
Powder coated1)
Anodized
Powder coated1)
110/71,5/300
110/71,5/500
110/71,5/700
110/71,5/900
6100
6100
6100
6100
200
201
202
203
Ø = 75 mm
6100
6100
6100
6100
6100
6100
6100
6100
222
221
227
226
232
231
237
236
Ø = 42 mm
6100
6100
6100
6100
6100
6100
6100
6100
252
251
257
256
262
261
267
266
Front cover, gas outlet, Dräger
Ø = 60 mm
Front cover to suit Dräger and AGA MC65 gas outlets. Snap-fitted on to fixing profile2).
For 1-4 gas outlets with a c/c measure of 200 mm. Material: Aluminium.
MWU-GU1, for 1 outlet
MWU-GU2, for 2 outlets
L50770
MWU-GU3, for 3 outlets
MWU-GU4, for 4 outlets
Anodized
Powder coated1)
Anodized
Powder coated1)
Anodized
Powder coated1)
Anodized
Powder coated1)
110/71,5/300
110/71,5/500
110/71,5/700
110/71,5/900
Front cover, gas outlet, MEDÆS, GEM 10
Front cover to suit Medæs gas outlets. Snap-fitted on to fixing profile2).
For 1–4 gas outlets with a c/c measure of 200 mm. Material: Aluminium.
MWU-GU1, for 1 outlet
MWU-GU2, for 2 outlets
L50770
MWU-GU3, for 3 outlets
1)
2)
MWU-GU4, for 4 outlets
Anodized
Powder coated1)
Anodized
Powder coated1)
Anodized
Powder coated1)
Anodized
Powder coated1)
110/71,5/300
110/71,5/500
110/71,5/700
110/71,5/900
6100
6100
6100
6100
6100
6100
6100
6100
282
281
287
286
292
291
297
296
Ø = 52 mm
6100
6100
6100
6100
6100
6100
6100
6100
312
311
317
316
322
321
327
326
Colour choice, see page 25.
For gas outlet installation techniques, see page 22.
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 45
Gas
Front cover, Wall bracket, Stop ends
Type/
Description
Colour/
Finish
Dimensions
A/B/C (mm)
Art. No.
L50790
Front cover, gas pipe
To conceal gas pipe installation. Front cover is snap-fitted to the wall brackets.
Available cut to length, max 5.0 m by special order. Material: Aluminium.
MWU-GP
Anodized
Powder coated1)
110/71,5/2500
6100 002
6100 001
L50760
Wall bracket, gas pipe front cover
Front cover to gas pipe is snap-fitted to the wall bracket. Recommended distance between the wall
brackets 600 mm. Stud partition wall – adjust the bracket distance according to the studding. Gas
pipes to be fixed on the wall brackets. Material: Aluminium.
MWU-GB
Untreated
104,2/11,5/50
6100 090
L50660
Stop ends
To be fixed on to the gas pipe cover or on to the gas outlet front cover2). The stop end is fixed with
screws. Supplied with screws. Material: Aluminium.
MWU-GE, left
MWU-GE, right
Powder coated1)
Powder coated1)
109,6/71,6/2
6100 051
6100 056
L50690
Stop ends
To be fixed on to the gas pipe cover or on to the gas outlet front cover2). With outlet for TRL gas
pipe cover. The stop end is fixed with screws. Supplied with screws. Material: Aluminium.
MWU-GE, left TRL5630
MWU-GE, right TRL5630
Powder coated1)
Powder coated1)
109,6/71,6/2
6100 071
6100 076
MWU-GE, left TRL5656
MWU-GE, right TRL5656
Powder coated1)
Powder coated1)
6100 061
6100 066
MWU-GE, left TRL7640
MWU-GE, right TRL7640
Powder coated1)
Powder coated1)
6100 081
6100 086
L12740
Cover for gas pipe
To conceal gas pipe installation. Cover is snap-fitted on TRL socket clamps. Material: Aluminium.
TRL-D5630
TRL-D5656
TRL-D5656
TRL-D7640
Anodized
Anodized
Powder coated1)
Anodized
56/30/2500
56/56/2500
56/56/2500
76/40/2500
5321
5321
5321
5321
100
120
122
210
Base clamp (with ties)
To fix gas pipes and to mount cover onto. The bracket is screw fixed to the wall surface.
Material: PA.
TRL-H56
TRL-H76
Black
–/–/–
5322 010
5322 020
Black
7/140/-
5322 050
60/57/30
5322 122
L12750
Tie (loose)
TRL-T
L12770
Stop end
For terminating TRL gas pipe covers. Material: ABS.
1)
2)
TRL-ES5656
Grey
Colour choice, see page 25.
If front cover, gas profile in anodized finish is being used, powder coated stop end in ’RAL 9007’ is recommended.
46 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Gas
Gas accessories
L50810
Type/
Description
Colour/
Finish
L50800
Dimensions
A/B/C (mm)
Art. No.
Mounting plate with pipe clamps
Gas pipes are snap-fitted into the clamps. For gas pipes in dimensions of Ø 8, 10 and 12 mm.
Pipe clamps are fixed by screws onto the mounting plate. The complete pipe clamp unit is screw
fixed to wall brackets. Supplied with screws.
MWU-GA 4 x Ø 8 mm
L50630
Material
PE
77/24/53
6100 810
MWU-GA 2 x 2 Ø 10 mm
77/27/53
6100 811
MWU-GA 2 x 2 Ø 12 mm
77/29/53
6100 812
Earthing clamp
For bonding the front cover gas outlet profile, gas outlets and accessories to earth.
Zinc passivated Steel
5590 500
L34520
TTI-JB
Earth wire
For bonding the front cover, gas outlet profile, gas outlets and accessories to earth.
Green/Yellow
Copper
L = 300 mm
5590 505
L51170
TTI-JK300
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 47
Accessory rail
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
Accessory rail, Scandinavian type
For hanging hospital equipment or instruments on. The rail must not be mounted on the hospital
trunking. To be mounted directly on the wall surface, preferably below the hospital trunking, by
using mounting brackets,which are screwed to the wall. The Accessory rail is snap-fitted to the
mounting bracket. Recommended distance between mounting brackets; 400 mm. Stud partition wall
– adjust the bracket distance according to studding.
The Accessory rail is compatible with the AGA Accessory rail system. Dimension 30 x 10 mm.
Anodized
Aluminium
30/9,8/2500
6100 820
MWU-AB, bracket
Anodized
Aluminium
30/38/50
6100 830
MWU-AA, cap
Grey
PP
37/16/20
6100 825
L50850
L50680
L50650
MWU-AP, rail
L59020
Accessory rail, DIN type
For hanging hospital equipment or instruments on. The rail must not be mounted on the hospital
trunking. To be mounted directly on the wall surface, over or below the hospital trunking. The rail
brackets are pre-mounted on the wall. Complete with screws.
The rail is compatible with the DIN-standards. Dimension 25 x 10 mm. Maximum load 100 kg/m
mounted on a solid wall. Available autumn 1999.
MWU-AP, rail
Untreated
SS
25/10/2000
6100 840
L59010
DIN-rail shelf
To be mounted on the accessory rail, DIN type. For hospital equipment such as monitors. Carries up
to 40 kg (400 N). Available autumn 1999.
MWU-AS
Grey
48 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
SS
170/369/540
6100 845
Tools
Type/
Description
Colour/
Finish
Material
Dimensions
A/B/C (mm)
Art. No.
D11130
Electrical cutting saw
Used to cut aluminium profiles. Maximum cutting 90x220mm. Spare blade available.
Jepson Dry Cutter V-Power, type KA-M335.
ISV-KS
Blade
Steel
5900 055
5900 056
L35480
Radial arm cutting saw with work-table
Used to cut aluminium profiles. Maximum cutting height x depth = 90 x 300 mm.
DeWalt DW 8003.
ISV–SG217
Steel
5900 040
L10770
Mitre box
To cut aluminium profiles at any angle. Complete with saw.
Maximum cutting height x depth = 120x170 mm.
ISV-G400
Aluminium
490/260/645
5900 000
Steel
550/45/1
5900 001
Saw blade
Replacement blade for saw ISV-G400.
L10720
ISV-GS550
L50620
Plunge tool
To make a Ø 18.6 mm hole for the edge protection grommet INKA-GF19. The plunge tool is used
to make a hole for cables between trunking base and lighting profile.
ISV-HS
Steel
5900 020
Jig template
For the mounting of cable trunking. Prevents scratching when drilling machine is used.
Steel
80/40/12
5900 130
L12560
INKA-JT
Front cover opener
For removing the front cover without damaging the trunking base or front cover.
Blue
PA
100/160
5900 900
L32330
ISV
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 49
Cable Capacity Guide (CCG)
Approximate calculation for dimensioning cable trunking
The CCG diagram is a quick and simple way of working out the minimum dimensions of the installation trunking for a given number of cables. If the cables are to be laid in different compartments in the same
trunking, the total height of the trunking will be the sum of the compartment heights.
This is how to use the CCG diagram:
1. Read the diagram clockwise
2. Choose the number of cables (N) on the upper vertical scale in the
middle of the diagram
3. Go to the right in the diagram up to the red line that corresponds to
the relevant cable diameter (D). Directly below the intersection point
you can read off the total cable area (A) on the right-hand horizontal scale. If there are cables with different diameters, the total cable
area (A) is the sum of the cable areas for the various cable diameters.
4. Now continue down from the intersection point for total cable area
to the line that corresponds to the desired fill factor.
5. Directly to the left of the intersection point you can read off a suitable trunking area (S) on the lower vertical scale.
6. Then continue to the left from the value for trunking area to the line
that corresponds to the desired trunking depth for trunking with or
without flush boxes (if the trunking is used as feeder trunking).
7. Go straight up from the intersection point and read off on the lefthand horizontal scale the smallest trunking height (H) that is required to run the cables.
H
(mm)
Trunking
height
Trunking
depth (mm)
250
200
A number of cables are to be laid in installation trunking fitted with a
cable shelf so that power cables and low-current cables can be kept
separate.
Known data:
Power cables: 10 cables of 20 mm diameter (the lower green line in
the upper part of the diagram)
Low-current cables: 22 cables of 12 mm diameter (the upper green
line)
The installation trunking must be 90 mm deep, without boxes and be
60 % filled.
Calculated data:
The cable area (A) for the low-current will be about 3350 mm2. For a
60% fill factor this cable area gives a compartment area (S) of about
5600 mm2. This means that the minimum height (H) of the compartment
where the cables will run is about 60 mm (trunking without box).
The cable area (A) for the power cables will be about 4600 mm2. For
a 60% fill factor this cable area (S) gives a compartment area of about
7700 mm2. This means that the minimum height (H) of the compartment
where the cables will run is about 85 mm (trunking without box).
Suitable installation trunking should therefore be higher than 145 mm
(the sum of 60 mm for the low current cable compartment and 85 mm
for the power cable compartment).
The final choice of installation trunking is made with the aid of the list
of our range of trunking (page 16-17) and the associated detailed
cable capacity tables (pages 52-58).
150
52
52
72
72
90
90
Trunking without box
Example
130
130
Trunking with box
50 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
100
50
N
Number of
cables
ø3
ø4
ø5
50
ø6
48
ø7
ø8
ø9
46
ø10
44
D
(mm)
Cable diameter
ø11
42
ø12
40
Ø
ø13
38
36
ø14
34
ø15
32
30
ø16
28
ø17
26
ø18
24
ø19
22
ø20
20
18
16
14
12
10
8
6
A (mm )
2
4
Total cable
area
2
1000
2000
3000
4000
5000
6000
7000
8000
9000
1
2
3
4
5
6
7
8
Trunking
fill factor
9
10
80%
11
12
13
60%
14
15
50%
16
17
40%
18
19
20
21
22
23
24
25
S x 1000 (mm )
2
Trunking/Compartment area
© THORSMAN & CO AB, 1997.
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 51
Cable Capacity
Height*
Cross section
area mm2
Cable capacity mm2
40%
50%
60%
Without mounting boxes
1
2
3
4
5
6
7
8
96
Not applicable
Not applicable
Not applicable
23
25
25
23
20
Not applicable
Not applicable
Not applicable
15
15
15
20
2226
2783
3339
1303
1199
1199
1308
521
480
480
523
652
600
600
654
782
719
719
785
3580
1432
1790
2148
30
Not applicable
Not applicable
Not applicable
20
20
20
20
Cross section
area mm2
Cable capacity mm2
40%
50%
60%
1037
522
522
1025
415
209
209
410
519
261
261
513
622
313
313
615
1
2
3
4
5
6
7
8
96
Not applicable
Not applicable
Not applicable
23
25
25
23
7152
2861
3576
4291
1521
1641
1641
1764
608
656
656
706
761
821
821
882
913
985
985
1058
5010
2004
2505
3006
1218
975
975
1389
487
390
390
556
609
488
488
695
731
585
585
833
With standard mounting boxes
With mounting box CYB 30 mm deep
1
2
3
4
5
6
7
8
Height*
Without mounting boxes
5565
With standard mounting boxes
1
2
3
4
5
6
7
8
Comp
No
1
2
3
4
5
6
7
8
40
Not applicable
Not applicable
Not applicable
20
20
20
20
With mounting box CYB 30 mm deep (Fig C, B, A)
4171
1668
2086
2503
1102
752
752
1092
441
301
301
437
551
376
376
546
661
451
451
655
R32430
* Internal compartment height
52 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
1
2
3
4
5
6
7
8
50
Not applicable
Not applicable
Not applicable
20
20
20
20
5754
2302
2877
3452
1348
1198
1198
1506
539
479
479
602
674
599
599
753
809
719
719
904
* Internal compartment height
R33210
Comp
No
R37580
R37580
INKA-101/90
R37580
R37580
INKA-101/72
Cable Capacity
INKA-123-4/72
R37580
R37580
R37580
R37580
INKA-123/72
Height*
Cross section
area mm2
Cable capacity mm2
40%
50%
60%
Without mounting boxes
1
2
3
4
5
6
7
8
118
Not applicable
Not applicable
Not applicable
34
25
25
34
20
Not applicable
Not applicable
Not applicable
20
15
15
20
2520
3151
3781
1912
1199
1199
1709
765
480
480
684
956
600
600
855
1147
719
719
1025
4786
1914
2393
2872
30
Not applicable
Not applicable
Not applicable
25
20
20
25
1637
522
522
1664
655
209
209
666
819
261
261
832
982
313
313
998
R32480
Cable capacity mm2
40%
50%
60%
1
2
3
4
5
6
7
8
118
Not applicable
Not applicable
Not applicable
33
25
25
33
6857
2743
3429
4114
1865
1199
1199
2089
746
480
480
836
933
600
600
1045
1119
719
719
1253
1
2
3
4
5
6
7
8
25
Not applicable
Not applicable
Not applicable
20
15
15
20
4706
1882
2353
2824
1597
522
522
1669
639
209
209
668
799
261
261
835
958
313
313
1001
With mounting box CYB 30 mm deep
5362
2145
2681
3217
1701
752
752
1718
680
301
301
687
851
376
376
859
1021
451
451
1031
* Internal compartment height
Cross section
area mm2
With standard mounting boxes
With mounting box CYB 30 mm deep
1
2
3
4
5
6
7
8
Height*
Without mounting boxes
6301
With standard mounting boxes
1
2
3
4
5
6
7
8
Comp
No
1
2
3
4
5
6
7
8
35
Not applicable
Not applicable
Not applicable
30
20
20
25
5499
2200
2750
3299
1717
752
752
1794
687
301
301
718
859
376
376
897
1030
451
451
1076
* Internal compartment height
R33220
Comp
No
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 53
Cable Capacity
R37580
R37580
INKA-123/90
Comp
No
Height*
Cross section
area mm2
Cable capacity mm2
40%
50%
60%
Without mounting boxes
1
2
3
4
5
6
7
8
118
Not applicable
Not applicable
Not applicable
34
25
25
34
8823
3529
4412
5294
2388
1199
1199
2602
955
480
480
1041
1194
600
600
1301
1433
719
719
1561
With standard mounting boxes (Fig C, B, A)
1
2
3
4
5
6
7
8
40
Not applicable
Not applicable
Not applicable
20
20
20
20
6680
2672
3340
4008
2087
975
975
2227
835
390
390
891
1044
488
488
1114
1252
585
585
1336
With mounting box CYB 30 mm deep (Fig C, B, A)
1
2
3
4
5
6
7
8
50
Not applicable
Not applicable
Not applicable
20
20
20
20
7424
2970
3712
4454
2215
1198
1198
2344
886
479
479
938
1108
599
599
1172
1329
719
719
1406
R33230
* Internal compartment height
54 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Cable Capacity
R37920
R37920
INKA-161-2/90
R37920
R37920
INKA-161-2/72
Height*
Cross section
area mm2
Cable capacity mm2
40%
50%
60%
Without mounting boxes
1
2
3
4
5
6
7
8
9
108
Not applicable
Not applicable
Not applicable
34
25
25
23
48
20
Not applicable
Not applicable
Not applicable
20
15
15
20
2440
3051
3661
1925
1199
1199
1273
2740
770
480
480
509
1096
963
600
600
637
1370
1155
719
719
764
1644
3914
1566
1957
2348
30
Not applicable
Not applicable
Not applicable
25
20
20
20
1651
522
522
1001
660
209
209
400
826
261
261
501
991
313
313
601
R32500
Cable capacity mm2
40%
50%
60%
1
2
3
4
5
6
7
8
9
108
Not applicable
Not applicable
Not applicable
34
25
25
23
48
7982
3193
3991
4789
2388
1199
1199
1747
3468
955
480
480
699
1387
1194
600
600
874
1734
1433
719
719
1048
2081
1
2
3
4
5
6
7
8
40
Not applicable
Not applicable
Not applicable
20
20
20
20
5839
2336
2920
3503
2087
975
975
1372
835
390
390
549
1044
488
488
686
1252
585
585
823
With mounting box CYB 30 mm deep
4704
1882
2352
2822
1713
752
752
1052
685
301
301
421
857
376
376
526
1028
451
451
631
* Internal compartment height
Cross section
area mm2
With standard mounting boxes
With mounting box CYB 30 mm deep
1
2
3
4
5
6
7
8
Height*
Without mounting boxes
6101
With standardmounting boxes
1
2
3
4
5
6
7
8
Comp
No
1
2
3
4
5
6
7
8
50
Not applicable
Not applicable
Not applicable
20
20
20
20
6584
2634
3292
3950
2215
1198
1198
1489
886
479
479
596
1108
599
599
745
1329
719
719
893
* Internal compartment height
R33250
Comp
No
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 55
Cable Capacity
INKA-161-3/90
Height*
Cross section
area mm2
Cable capacity mm2
40%
50%
60%
Without mounting boxes
1
2
3
4
5
6
7
8
157
Not applicable
Not applicable
Not applicable
34
25
25
72
20
Not applicable
Not applicable
Not applicable
20
15
15
40
3748
4685
5621
1909
1199
1199
4556
764
480
480
1822
955
600
600
2278
1145
719
719
2734
7372
2949
3686
4423
30
25
25
40
25
20
20
40
1620
522
522
4273
648
209
209
1709
810
261
261
2137
972
313
313
2564
3989
773
438
2276
850
376
376
2172
4787
927
526
2731
1019
451
451
2606
7978
1545
876
4552
1699
752
752
4343
Cross section
area mm2
Cable capacity mm2
40%
50%
60%
1
2
3
4
5
6
7
8
157
Not applicable
Not applicable
Not applicable
34
25
25
72
12149
4860
6075
7289
2433
1632
1632
5888
973
653
653
2355
1217
816
816
2944
1460
979
979
3533
10115
4046
5058
6069
1658
958
958
5562
663
383
383
2225
829
479
479
2781
995
575
575
3337
With standard mounting boxes
With mounting box CYB 30 mm deep
1
2
3
4
5
6
7
8
Height*
Without mounting boxes
9369
With standard mounting boxes
1
2
3
4
5
6
7
8
Comp
No
3191
618
350
1821
680
301
301
1737
1
2
3
4
5
6
7
8
67
Not applicable
Not applicable
Not applicable
31
23
23
67
With mounting box CYB 30 mm deep
R32780
* Internal compartment height
56 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
1
2
3
4
5
6
7
8
67
Not applicable
Not applicable
Not applicable
31
23
23
67
10750
4300
5375
6450
1754
1185
1185
5640
702
474
474
2256
877
593
593
2820
1052
711
711
3384
* Internal compartment height
R33260
Comp
No
R37580
R37580
R37580
R37580
INKA-161-3/72
Cable Capacity
Height*
Cross section
area mm2
Cable capacity mm2
40%
50%
60%
Without mounting boxes
1
2-4
5
6
7
8
9
10
11
108
Not applicable
34
25
25
22
70
32
39
40
Not applicable
20
20
20
20
30
25
30
3193
3991
4789
2388
1199
1199
1747
5391
2130
3054
955
480
480
699
2156
852
1222
1194
600
600
874
2696
1065
1527
1433
719
719
1048
3235
1278
1832
5839
2336
2920
3503
2087
975
975
1372
5391
2130
3054
835
390
390
549
2156
852
1222
1044
488
488
686
2696
1065
1527
1252
585
585
823
3235
1278
1832
With mounting box CYB 30 mm deep
1
2-4
5
6
7
8
9
10
11
50
Not applicable
20
20
20
20
30
25
30
6584
2634
3292
3950
2215
1198
1198
1489
5391
2130
3054
886
479
479
596
2156
852
1222
1108
599
599
745
2696
1065
1527
1329
719
719
893
3235
1278
1832
* Internal compartment height
Height*
Cross section
area mm2
Cable capacity mm2
40%
50%
60%
Without mounting boxes
7982
With standard mounting boxes
1
2-4
5
6
7
8
9
10
11
Comp
No
1
2-4
5
6
7
8
9
10 - 11
12
13
14
15
16
105
Not applicable
33
25
25
20
105
Not applicable
30
20
25
25
33
5962
2385
2981
3577
1905
1199
1199
1130
6010
762
480
480
452
2404
953
600
600
565
3005
1143
719
719
678
3606
1766
1082
1199
1199
1985
706
433
480
480
794
883
541
600
600
993
1060
649
719
719
1191
3980
1592
1990
2388
1614
476
476
843
4014
646
190
190
337
1606
807
238
238
422
2007
968
286
286
506
2408
1409
807
476
476
1699
564
323
190
190
680
705
404
238
238
850
845
484
286
286
1019
With standard mounting boxes
1
2-4
5
6
7
8
9
10 - 11
12
13
14
15
16
20
Not applicable
20
15
15
20
20
Not applicable
25
15
15
15
25
With mounting box CYB 30 mm deep
1
2-4
5
6
7
8
9
10 - 11
12
13
14
15
16
30
Not applicable
25
20
20
25
30
Not applicable
25
15
15
15
25
4568
1827
2284
2741
1696
752
752
911
4616
678
301
301
364
1846
848
376
376
456
2308
1018
451
451
547
2770
1580
883
752
752
1766
632
353
301
301
706
790
442
376
376
883
948
530
451
451
1060
R33280
* Internal compartment height
R33170
Comp
No
R37360
R37700
INKA-217-2/72
R37360
R37360
INKA-183-2/90
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 57
Cable Capacity
R37700
R37700
INKA-217-2/90
Comp
No
Height*
Cross section
area mm2
Cable capacity mm2
40%
50%
60%
Without mounting boxes
1
2-4
5
6
7
8
9
10 -12
13
14
15
16
105
Not applicable
33
25
25
20
105
Not applicable
20
25
25
33
7745
3098
3873
4647
2388
1199
1199
1567
7819
955
480
480
627
3128
1194
600
600
784
3910
1433
719
719
940
4691
1358
1199
1199
2619
543
480
480
1048
679
600
600
1310
815
719
719
1571
5602
2241
2801
3361
1087
975
975
1191
5676
435
390
390
476
2270
544
488
488
596
2838
652
585
585
715
3406
1055
975
975
2244
422
390
390
898
528
488
488
1122
633
585
585
1346
With standard mounting boxes
1
2-4
5
6
7
8
9
2-4
13
14
15
16
40
Not applicable
20
20
20
20
40
Not applicable
15
20
20
30
With mounting box CYB 30 mm deep
1
2-4
5
6
7
8
9
2-4
13
14
15
16
50
Not applicable
20
20
20
20
40
Not applicable
15
20
20
30
6346
2538
3173
3808
2215
1198
1198
1309
6472
886
479
479
524
2589
1108
599
599
655
3236
1329
719
719
785
3883
1186
1198
1198
2361
474
479
479
944
593
599
599
1181
712
719
719
1417
R33290
* Internal compartment height
58 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Technical Data
Chemical Resistance
Aluminium
(Al) is resistant to most first acids and organic solvents. Aluminium is not resistant to most strong acids (except nitric acid) and
alkali.
PVC
According to ISO Technical report 7473 1981, PVC (polyvinylchloride, uPVC) is resistant to most acids, lyes, salt solutions
and hydrous organic combinations. PVC is not resistant to aromatic and chlorinated solvents, e.g. acetone, thinner, trichloreethylene, ethyl acetate, tetrahydrofurane, metylene chloride, metyl ethyl ketone.
Material data
Material data
Density
Longitudinal expansion
Water absorption
Volume resistivity
Electrical strength
Fire class
PC
1.17 g/cm3
70x10-6 m/m°C
0.6%
>1013 Ω cm
18 kV/mm
UL 94 V-2, 1.6 mm halogen-free
Material data
Density
Longitudinal expansion
Water absorption
Volume resistivity
Electrical strength
Fire class
PA
1.39 g/cm3
100x10-6 m/m°C
2.8%
>1015 Ω cm
60 kV/mm
UL 94 HB, halogen-free
Material data
Density
Longitudinal expansion
Water absorption
Volume resistivity
Electrical strength
Fire class
PC/ABS
1.14 g/cm3
–
0.6%
>1013 Ω cm
19 kV/mm
UL 94 V-0, 1.6 mm halogen-free
Material data
Density
Longitudinal expansion
Water absorption
Volume resistivity
Electrical strength
Fire class
PMMA
1.19 g/cm3
80x10-6 m/m°C
0.3%
>1015 Ω cm
30 kV/mm (DIN 53481)
UL 94 HB, 1.6 mm halogen-free
Material data
Density
Longitudinal expansion
Water absorption
Volume resistivity
Electrical strength
Fire class
PP
0.905 g/cm3
100x10–6 m/m°C
<0,1%
1012 Ω cm
>30 kV/mm
UL 94 HB halogen-free, withstands glow wire test 750°
Material data
Density
Longitudinal expansion
Water absorption
Volume resistivity
Electrical strength
Fire class
Aluminium
2.7 g/cm3
24x10–6m/m°C (0.024 mm/m°C)
-
Material data
Density
Longitudinal expansion
Water absorption
Volume resistivity
Electrical strength
Temperature resistance:
PVC
ISO 1183 1.5 g/cm3
60x10–6 m/m°C (0.06 mm/m°C)
Maximum 60°C
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 59
Mounting Details
M38540
TTA-KM 1
TTA-KM 3
TTA-KM 5
60 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Mounting details
ISV-FO
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 61
Mounting details
TTI-JB
62 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Mounting details
x2
2
1
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 63
Mounting details
MWU-LS
Optional
225
225
=
=
MI2072
10 mm
64 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Mounting details
MWU-GA
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 65
MI2073
66 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Specification Guide
Due to the great flexibility of the FrontLine Hospital
Trunking system and the many possibilities for combining the various products, we recommend the following procedure when specifying/ordering:
General
1.
2.
3.
4.
5.
6.
Service carrier
Service Content
Lighting
Gas
Accessory rail
Tools
P3826
All items are presented in the same order they appear
in this brochure.
Information given in the order form under
Type/Description is somewhat restricted due to space
considerations.
For colour choice, fill in the corresponding colour
code (for example L11), see page 25.
Numbers in parentheses, for example (p. 26-27), refer
to pages in this brochure.
Begin by copying the Specification/Order form,
then choose:
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 67
Specification/Order form
(Copy this form before filling in)
2. Service content
1. Service carrier
Art. No. T-
Type/Description
(p 26-27)
Trunking bases
5504
5504
5507
5507
5506
5506
5510
5510
5510
5510
5514
5514
000
002
000
002
310
319
010
012
020
022
000
002
5519
5519
5506
5506
5519
5519
5512
5512
5519
5519
5519
5519
010
012
400
402
020
022
230
232
060
062
040
042
INKA-U101, anodized
INKA-U101, colour code:
INKA-U123, anodized
INKA-U123, colour code:
INKA-U161-2, anodized
INKA-U161-2, colour code:
INKA-U161-3, anodized
INKA-U161-3, colour code:
INKA-U183-2, anodized
INKA-U183-2, colour code:
INKA-U217-2, anodized
INKA-U217-2, colour code:
030
039
080
089
Front covers
FCA-F40, anodized
FCA-F40, colour code:
FCA-F80, anodized
FCA-F80, colour code:
172
172
172
172
217
152
277
062
032
307
203
208
Stop ends*
INKA-ES101/72, colour code:
INKA-ES123/72, colour code:
INKA-ES161/72, colour code:
INKA-ES217/72, colour code:
INKA-ES101/90, colour code:
INKA-ES123/90, colour code:
INKA-ES161-2/90, colour code:
INKA-ES161-3/90, colour code:
INKA-ES183-2/90, colour code:
INKA-ES217-2/90, colour code:
INKA-ESV123-4/72, left, colour code:
INKA-ESH123-4/72, right, colour code:
Qty (pcs)
Art. No. T-
Type/Description
(p 30)
Connection kits, Schuko
INKA-U101, anodized
INKA-U101, colour code:
INKA-U123, anodized
INKA-U123, colour code:
INKA-U123-4, anodized
INKA-U123-4, colour code:
INKA-U161-2, anodized
INKA-U161-2, colour code:
INKA-U161-3, anodized
INKA-U161-3, colour code:
INKA-U217-2, anodized
INKA-U217-2, colour code:
5975 000
5975 005
CYB-PS, white
CYB-PS, white
5951
5951
5951
5951
480
482
485
487
CYB-PS,
CYB-PS,
CYB-PS,
CYB-PS,
5951
5951
5951
5951
430
432
435
437
90 mm deep
(p 31)
CYB-PS, white
CYB-PS, red
CYB-PS, green
CYB-PS, ornage
Connection kits, French Standard
5969 215
5969 217
CYB-PF, Two-gang, push-in terminals, white
CYB-PF, Two-gang, push-in terminals, red
5969 210
5969 212
CYB-PF, Two-gang, screw terminals, white
CYB-PF, Two-gang, screw terminals, red
5969
5969
5969
5969
(p 31)
CYB-PF, Two-gang, push-in terminals, white
CYB-PF, Two-gang, push-in terminals, red
CYB-PF, Two-gang, screw terminals, white
CYB-PF, Two-gang, screw terminals, red
Connection kits, British Standard
5961 130
5961 120
5961 140
CYB-PU, switched, white
CYB-PU, switched, white
CYB-PU, switched with indicator, white
5961 135
5961 125
5961 145
CYB-PU, unswitched, white
CYB-PU, switched , white
CYB-PU, switched with indicator, white
Basic kit, CEE socket outlets
CYB-C220, 250 V/16 A, grey/blue
CYB-C380, 440 V/16 A, grey/red
72 mm deep
(p 27)
5580
5580
5580
5580
(p 28)
5504
5507
5510
5514
5590
5591
5590
5591
5591
5590
5590
5590
(p 28-29)
5590
5590
5590
5590
5590
5590
5590
5590
5590
5590
5590
5590
5902
5902
5586
5583
5583
5583
312
314
315
316
340
180
112
500
505
410
414
520
100
120
600
405
408
410
Trunking accessories
TTI-KH72, Cable shelf, aluminium
TTI-KH72, Cable shelf, PVC
TTI-KH90, Cable shelf, aluminium
TTI-KH90, Cable shelf, PVC
TTI-KHK, Cable clip
TTI-MB, Mounting washer
INKA-SSA, Jointing piece
TTI-JB, Earthing clamp
TTI-JK300, Earth wire
TTI-T3045, Sound insulation strip
TTI-T5070, Sound insulation strip
TTI-KB, Cup washer
INKA-GF19, Grommet
INKA-KD82, Edge protection
TTI-GM, Locking plate
TTA-KM1, Washer
TTA-KM3, Washer
TTA-KM5, Washer
68 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Qty (pcs)
Single socket outlets, Schuko 90°
Double socket outlets, Schuko 37°
white
red
green
orange
Three-gang socket outlets, Schuko 37°
For Poland and France
For Belgium, Poland, France
For Czech Rep., Poland, France
115
117
110
112
Single, 13 A
Twin, 13 A
(p 32)
5960 110
5960 100
002
007
012
017
032
052
062
072
082
087
057
Connection kit, Overvoltage protection
CYB-PP, white
Connection kits, Switches
CYB-PB, Single-pole
CYB-PB, Single-pole, spring-return rocker
CYB-PB, Single-pole, red indicator lamp
CYB-PB, Single-pole, green indicator lamp
CYB-PB, Double-pole
CYB-PB, Single-pole/two-way
CYB-PB, Intermediate
CYB-PB, Two-gang
CYB-PB, Venetian blind
CYB-PB, Venetian blind, single-pole
CYB-PB, Double single-pole/two-way
5972 105
CYB-GL2, to be mounted together with switch
5972 200
CYB-PT, For single socket, 3x2,5 mm2
Light diode kit
CYB-PO, angled, white
(p 32)
5972 010
(p 32-33)
5980
5980
5980
5980
5980
5980
5980
5980
5980
5980
5980
Pilot lamp 0.9 mA 250 V
Push-in plint for16A/250V
(p 34)
5974 010
(p 34)
5985
5985
5985
5985
020
000
030
050
Connection kit, Dimmers 230 V,
F80® Mounting
CYB-PR, dimmer, white (APE 10T)
CYB-PR, dimmer, white (ATD 300R)
CYB-PR, dimmer, white (AD 400UTT)
CYB-PR, dimmer, white (ATTD 1000RL)
* If anodized trunking is chosen, stop ends in colour code L23 (RAL 9007) are recommended.
Specification/Order form
2. Service content (cont.)
2. Service content (cont.)
Art. no. T-
Type/Description
(p 34)
Mounting boxes and blank covers
CYB-S40, Single box
CYB-D40, Double box
CYB-PL, Blanking cover, single
CYB-PL, Blanking cover, double
5961
5961
5961
5961
030
035
550
555
Qty (pcs)
(p 35)
Accessories for Mounting boxes
and Mounting kits
5961 505
5961 506
CYB-P40, for British standard
CYB-P3, for 60 mm centres
Screw pillars
Art. No. T-
Type/Description
(p 38-39)
Connection kits, Data (cont.)
5970
5970
5970
5970
5970
5970
5970
5970
960
965
970
975
800
805
810
815
1
2
1
2
1
2
1
2
5970
5970
5970
5970
5970
5970
5970
5970
930
935
840
845
850
860
855
865
1
2
1
2
1
2
1
2
5970
5970
5970
5970
355
360
365
370
1x
2x
1x
2x
Qty (pcs)
Avaya (Lucent) MPS 300, 100 UTP
x
x
x
x
x
x
x
x
Cat6 UTP, A, white
Cat6 UTP, A, white
Cat6 UTP, B, white
Cat6 UTP, B, white
Cat5e UTP, A, white
Cat5e UTP, A, white
Cat5e UTP, B, white
Cat5e UTP, B, white
AMP110, Netconnect UTP and STP
Adapter for flexible conduit
5956 250
5956 255
CYB-D20, Adapter
CYB-D25, Adapter
5961 500
CYB-ET, can take 2x4 mm2 wires
5961 510
CYB-CT
5956 150
FDS
Earthing terminal
Conduit bush
Strain relief
x
x
x
x
x
x
x
x
Cat6 A/B UTP, white
Cat6 A/B UTP, white
Cat5e A/B UTP, white
Cat5e A/B UTP, white
Cat5e A, STP, white
Cat5e A, STP, white
Cat5e B, STP, white
Cat5e B, STP, white
IBM ACS type C, Reichle de Massari UTP and FTP
(p 35)
Installation boxes
5586 150
5586 155
MIB-A1
MIB-A2
Cat5,
Cat5,
Cat5,
Cat5,
UTP, white
UTP, white
FTP, white
FTP, white
IBM type 1, STP for structured cable systems
(p 36)
5971 790
5971 794
Mounting kit for access.
CYB-MB
CYB-MB
(other suppliers)
5970 345
1x IBM type 1, white
5970 350
1x IBM type 2, white
5970
5970
5970
5970
1
2
1
2
IBM type 2, STP for structured cable systems
Krone Keystone for PremisNET struct. cable syst.
(p 36)
5971
5971
5971
5971
302
301
307
306
5971 315
5914 050
(p 37)
5960 251
5960 256
(p 37)
5960
5960
5960
5060
5960
5960
5960
5960
5960
5960
5960
5960
480
485
460
490
465
495
470
500
475
505
415
410
Equipotential connection
CYB-PO, (max 63 A), anodized
CYB-PO, colour code:
CYB-PO DIN, anodized
CYB-PO DIN, colour code:
Equipotential connection Kit
CYB-PO DIN
CTA-PO
DIN enclosures
CYB-PN
CYB-PN
Circuit breakers
CYB-PN, 1-pole, C10A
CYB-PN, 1-pole, C16A
CYB-PN, 2-pole, B10A
CYB-PN, 2-pole, C10A
CYB-PN, 2-pole, B16A
CYB-PN, 2-pole, C16A
CYB-PN, 3-pole, B10A
CYB-PN, 3-pole, C10A
CYB-PN, 3-pole, B16A
CYB-PN, 3-pole, C16A
CYB-PN 2 pole, Earth leakage breaker
CYB-PN 4 pole, Earth leakage breaker
(p 38-39)
Connection kits, Data
5974
5974
5974
5974
5970
5970
5970
5970
1
2
1
2
1
2
1
2
LexCom 250, 125 UTP and STP
090
095
100
105
900
905
910
915
x
x
x
x
x
x
x
x
Cat6 UTP, A/B, white
Cat6 UTP, A/B, white
Cat6 STP, A/B, white
Cat6 STP, A/B, white
Cat5e UTP, A/B, white
Cat5e UTP, A/B, white
Cat5e STP, A/B, white
Cat5e STP, A/B, white
760
765
770
775
x
x
x
x
Cat5
Cat5
Cat5
Cat5
UTP, B, white
UTP, B, white
STP, B, white
STP, B, white
(p 39)
Connection kits, fibre optics
5974 000
5974 005
1 x SC-duplex, multimode, white
2 x SC-duplex, multimode, white
5970 375
5970 380
5970 385
2 x ST, multimode, white
1 x SC-duplex, multimode, white
2 x SC-duplex, multimode, white
5971 220
(p 40)
CYB-DF, white
Connection kits, Telephone
5970 520
5970 525
1x RJ45, white
2x RJ45, white
5970 510
5970 515
1x RJ11, white
2x RJ11, white
(p 40)
Connection kits, low current and coaxial cable networks, aerial, radio/TV
5970 595
5954 120
1 x radio/TV, white
CAN-A75, termination resistor
5970 310
5970 315
5970 320
1 x D-sub 9-pole, white
1 x D-sub 15-pole, white
1 x D-sub 25-pole, white
Accessories
CYB-RK, high, Protective Casing, red
CYB-RK, low, Protective Casing, red
LexCom fibre multimode for fibre-based cable syst.
AMP SC and Lucent Technologies ST
Protective casing for fibre optics
AMP 8-way modular socket Cat 3
AMP 6-way modular socket
Connection kit, radio/TV aerial
Connection kit, D-connectors
(p 40)
5971 200
5971 205
▲
FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 69
Specification/Order form
3. Lighting
4. Gas
Art. No. T-
Type/Description
(p 41-42)
Art. No. T-
Type/Description
Lighting profile, Light fitting rail,
Covers, Stop ends
(p 44)
Gas outlets
Lighting profile
6100
6100
6100
6100
6100
6100
500
505
510
515
520
525
Breathing oxygen
Nitrous oxide
Breathing air, 4 bar
Gas exit
Vacuum
Instrumental air, 7 bar
6100
6100
6100
6100
6100
6100
530
535
540
545
550
555
Breathing oxygen
Nitrous oxide
Breathing air, 4 bar
Vacuum
Instrumental air, 7 bar
CO2
6100
6100
6100
6100
6100
560
565
570
575
580
Breathing oxygen
Nitrous oxide
Breathing air, 4 bar
Vacuum
CO2
6100
6100
6100
6100
6100
6100
590
595
600
605
620
625
Breathing oxygen
Nitrous oxide
Breathing air, 4 bar
Vacuum
Instrumental air, 7 bar
Entonox
801
802
803
804
Mounting adaptor kit
MWU-GA for AGA MC65
MWU-GA for AGA MC70
MWU-GA for Dräger
MWU-GA for Greggersen
6200
6200
6200
6200
002
001
006
005
MWU-LP,
MWU-LP,
MWU-LP,
MWU-LP,
6200
6200
6200
6200
6200
6200
6200
6200
6200
6200
6200
6200
6200
6200
6200
6200
6200
150
151
210
211
212
205
206
200
201
160
165
225
230
245
250
240
220
MWU-LR, Type TC 18W
MWU-LR, Type TC 18W, HF**
MWU-LR, Type TC 36W
MWU-LR, Type TC 36W, HF**
MWU-LR, Type TC 36W, HF dimm.**
MWU-LR, Type T26 36W
MWU-LR, Type T26 36W, HF**
MWU-LR, Type T26 58W
MWU-LR, Type T26 58W, HF**
MWU-LR, Type T5 28W, HF**
MWU-LR, Type T5 54W, HF**
T26, fluorescent std. Tube 36W, L=1200
T26, fluorescent std. Tube 58W, L=1500
T5, fluorescent std. Tube 28W, L=1149
T5, fluorescent std. Tube 54W, L=1149
TC, fluorescent compact Tube 18W, L=217
TC, fluorescent compact Tube 36W, L=410
Qty (pcs)
anodized
colour code:
L=1250 mm, anodized
L=1250 mm, colour code:
Light fitting rail
Pull-cord Switch
6200 301
MWU-LS
6200 291
6200 605
MWU-LA
IBP/F 5 W bulb (dim)
Night Light
AGA MC 70
Greggersen
Dräger
MEDÆS, GEM 10
Light Diode Kit
(p 44)
5974 010
CYB-PO, angled, white
6200 805
MWU-LC, transparent
(p 42)
Front cover
6100
6100
6100
6100
5580 080
5580 089
FCA-F80, anodized
FCA-F80, colour code:
(p 45)
Up-light cover
Fixing profile and Front covers
Prismatic shade
6200 800
6200 801
MWU-LF, transparent (TC 36W)
MWU-LF, transparent (TC 18W)
6200 051
6200 056
MWU-LE, left, colour code:
MWU-LE, right, colour code:
Stop end*, lighting profile
5440 810
5590 500
5590 505
Lighting accessories
FED-SSJ, Jointing piece
TTI-JB, Earthing clamp
TTI-JK 300, Earth wire
(p 43)
Bed-Examining lamps
6200 401
6200 411
6200 416
6200 501
MWU-L13W compact flourescent tube
MWU-L18W compact flourescent tube
MWU-L 40W bulb
Wall fixing
6200 420
6200 425
6200 505
6200 535
6200 610
6200 615
12 V/20W halogen lamp, built-in transformer
12V/50W halogen lamp, plug-in transformer
Wall fixing
Desk fixing (clamped)
12 V/20 W halogen lamp
12 V/50 W halogen lamp
(p 42)
Luxo
Sunnex
*
If anodized lighting profile is chosen, stop ends in colour code L23
(RAL 9007) are recommended.
** HF=Electronic ballasts
70 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112
Qty (pcs)
Fixing profile, gas outlets
6100
6100
6100
6100
200
201
202
203
MWU-GF1,
MWU-GF2,
MWU-GF3,
MWU-GF4,
6100
6100
6100
6100
6100
6100
6100
6100
222
221
227
226
232
231
237
236
MWU-GU1,
MWU-GU1,
MWU-GU2,
MWU-GU2,
MWU-GU3,
MWU-GU3,
MWU-GU4,
MWU-GU4,
6100
6100
6100
6100
6100
6100
6100
6100
252
251
257
256
262
261
267
266
MWU-GU1,
MWU-GU1,
MWU-GU2,
MWU-GU2,
MWU-GU3,
MWU-GU3,
MWU-GU4,
MWU-GU4,
6100
6100
6100
6100
6100
6100
6100
6100
282
281
287
286
292
291
297
296
MWU-GU1,
MWU-GU1,
MWU-GU2,
MWU-GU2,
MWU-GU3,
MWU-GU3,
MWU-GU4,
MWU-GU4,
for
for
for
for
1
2
3
4
outlet
outlets
outlets
outlets
Front cover, gas outlet, AGA, Ø = 75 mm
for
for
for
for
for
for
for
for
1 outlet, anodized
1 outlet, colour code:
2 outllets, anodized
2, colour code:
3, outlets, anodized
3, colour code:
4 outlets, anodized
4 outlets, colour code:
Front cover, gas outlet, Greggersen, Ø = 42 mm
for
for
for
for
for
for
for
for
1
1
2
2
3
3
4
4
outlet, anodized
outlet, colour code:
outlets , anodized
outlets, colour code:
outlets, anodized
outlets, colour code:
outlets, anodized
outlets, colour code:
Front cover, gas outlet, Dräger, Ø = 60 mm
for
for
for
for
for
for
for
for
1
1
2
2
3
3
4
4
outlet, anodized
outlet, colour code:
outlets, anodized
outlets, colour code:
outlets, anodized
outlets, colour code:
outlets, anodized
outlets, colour code:
Specification/Order form
4. Gas (cont.)
Art. No. T(p 45)
6100
6100
6100
6100
6100
6100
6100
6100
4. Gas (cont.)
Type/Description
Qty (pcs)
Front cover ,gas outlet, MEDÆS, GEM 10, Ø = 52 mm
312
311
317
316
322
321
327
326
MWU-GU1,
MWU-GU1,
MWU-GU2,
MWU-GU2,
MWU-GU3,
MWU-GU3,
MWU-GU4,
MWU-GU4,
for
for
for
for
for
for
for
for
1
1
2
2
3
3
4
4
outlet, anodized
outlet, colour code:
outlets, anodized
outlets, colour code:
outlets, anodized
outlets, colour code:
outlets, anodized
outlets, colour code:
Front cover, Wall bracket, Stop ends
(p 46)
Front cover, gas pipe
6100 002
6100 001
MWU-GP, anodized
MWU-GP, colour code:
Art. No. T-
Type/Description
(p 47)
Gas accessories
6100 810
6100 811
6100 812
MWU-GA 4 x Ø 8 mm
MWU-GA 2 x 2 Ø 10 mm
MWU-GA 2 x 2 Ø 12 mm
5590 500
TTI-JB
5590 505
TTI-JK300
Mounting plate with pipe clamps
Earthing clamp
Earth wire
5. Accessory rail
Art. No. T-
Type/Description
(p 48)
Accessory rail
6100 820
6100 830
6100 825
MWU-AP, rail, anodized
MWU-AB, bracket, anodized
MWU-AA, cap, grey
MWU-GB, untreated
6100 051
6100 056
MWU-GE, left, colour code:
MWU-GE, right, colour code:
Stop ends*
Stop ends with outlet for TRL gas pipe cover*
6100 840
MWU-AP, rail, untreated
6100
6100
6100
6100
6100
6100
071
076
061
066
081
086
MWU-GE,
MWU-GE,
MWU-GE,
MWU-GE,
MWU-GE,
MWU-GE,
5321
5321
5321
5321
100
120
122
210
left TRL5630, colour code:
right TRL5630, colour code:
left TRL5656, colour code:
right TRL5656, colour code:
left TRL7640, colour code:
right TRL7640, colour code:
6100 845
MWU-AS, untreated/grey
Accessory rail, DIN type
DIN-rail shelf
6. Tools
Art. No. T-
Type/Description
Cover for gas pipe
(p 49)
TRL-D5630,
TRL-D5656,
TRL-D5656,
TRL-D7640,
5900 055
5900 056
5900 040
Tools
ISV-KS, Electrical cutting saw
Blade, for Electrical cutting saw
ISV-SG217, Radial arm cutting saw
with work-table
5900
5900
5900
5900
5900
ISV-G400, Mitre box
ISV-GS550, replacement blade for ISV-G400
ISV-HS, Plunge tool
INKA-JT, Jig template
ISV, Front cover opener
anodized
anodized
colour code:
anodized
Base clamp (with ties)
5322 010
5322 020
5322 050
TRL-H56
TRL-H76
TRL-T
5322 122
TRL-ES5656, grey
Qty (pcs)
Accessory rail, Scandinavian type
Wall bracket, gas pipe front cover
6100 090
Qty (pcs)
000
001
020
130
900
Qty (pcs)
Stop end (for terminating TRL gas pipe covers)
* If anodized gas profile is chosen, stop ends in colour code L23
(RAL 9007) are recommended.
Project: ....................................................................................................................................................................
Sub-specification: ......................................................................................................................................................
Company: ....................................................................................................................................................................
Reference: ....................................................................................................................................................................
Address: ......................................................................................................................................................................
Phone: ..........................................................................................................................................................................
Telefax: ........................................................................................................................................................................
Fax or mail the Specification/Order form to Thorsman International
or to your local Thorsman representative.
THORSMAN INTERNATIONAL
Thorsman & Co AB, Box 1010, SE-611 29 Nyköping, Sweden
Telephone +46-155 26 50 00. Telefax +46-155 26 63 66
E-mail: mail.int@tcn.thorsman.se Web Site: www.thorsman.com
Lexel in Brief
The Lexel Group is one of Europe’s leading suppliers
of installation solutions for power, telecom, datacom
and control applications with special focus on 'smart
buildings', i.e. buildings equipped with technology
providing increased levels of comfort, economy and
security.
The Lexel product programme includes everything
from switches, outlets, installation materials and
installation systems for cable management to communication networks, security systems, and systems and
software for control of building functions.
Respect for the environment is an integral part of
all Lexel activities. One example is the development
and certification of environmental management systems complying with ISO 14000. In the field of polymers Lexel is working to eliminate the use of heavy
metals and ozone-depleting substances.
The Lexel Group is owned by Schneider Electric of
France and has its operational head office in
Stockholm, Sweden. The Group has a turnover of
over EUR 650 million and employs some 6000 people.
Lexel is a market leader in the Nordic countries,
Poland and the Baltic States, but is also strongly
placed in Russia and a number of Central European
countries. Sales are effected through subsidiaries in 18
countries and distributors in more than 30.
Europe
Austria, Belgium, Bosnia and Herzegovina, Bulgaria, Belarus, Croatia,
Cyprus, France, Greece, Hungary, Iceland, Italy, Macedonia, Portugal,
Romania, Slovenia, Spain, Switzerland, Ukraine, Yugoslavia.
Other markets
Argentina, Australia, Bahrain, Hong Kong, Israel, Japan, Jordan,
Kazakhstan, Kuwait, Lebanon, Malaysia, Mexico, Oman, Qatar, Saudi
Arabia, Singapore, Turkey, U.A.E., U.S.A.
THORSMAN INTERNATIONAL
Electricity the professional way
Thorsman & Co AB • Box 1010 • SE-611 29 Nyköping, Sweden • Telephone +46-155-26 50 00 • Telefax +46-155-26 63 66 • www.thorsman.com
MC1823/INT/GB/0112. © THORSMAN & CO AB.
Österbergs & Sörmlandstryck, 23550
International representation, brand Thorsman
Thorsman International is the marketing organization responsible for marketing in all non-subsidiary markets by
working with a large network of agents and distributors
throughout the world.
Download