MTK, UKK Disconnect and component terminal blocks General information In addition to the standard feedthrough modular terminal blocks, modular terminal blocks with different functions are also needed. For some applications, for example, it must be possible to disconnect the signal paths individually in order to switch them off load or to loop in a measuring device . Different knife disconnect terminal blocks are available for such applications. Test socket screws are integrated on the right and left of the disconnect zone, so that the measuring device can be directly looped in with the test plugs . Space-saving solutions such as double-level terminal blocks also exist for the disconnect terminal blocks . Here, two feed-through levels that can each be independently 274 Phoenix Contact disconnected from the other with a knife are integrated . This solution saves 50% more space in comparison with a single-level terminal block. To implement components in signal paths, plugs are available that can be plugged onto the basic terminal blocks without the risk of polarity reversal . Either components such as resistors, diodes or fine fuses can be inserted into these plugs. If the components are to be integrated permanently in the terminal block instead of being pluggable, component and diode terminal blocks are available. Knife disconnect terminal blocks MTK In measurement, regulation and control systems, disconnect terminal blocks are becoming more and more popular in order to rapidly localize faults and to permit inspection work to be carried out under zero voltage conditions. In addition to the easy-to-use disconnect knife, this range is characterized by: Space-saving design High current carrying capacity up to 16 A Type versions with soldering tags Screws with integrated test sockets . Double-level terminal blocks with disconnect knives for both levels, UDMTK Besides the easy-to-use disconnect knives, the UDMTK 5-PIP terminal block features are : A sturdy and closed housing Double connection and Double disconnection . The disconnect knife on the lower level is characterized by a slight vertical offset . The UDMTK 5-TWIN-PIP terminal block has the same advantages as the UDMTKS-PIP. It has a conductor connection on the system side, however, which can be split and disconnected via both disconnect knives . Basic terminal blocks Basic terminal blocks for fuse, component and isolating plugs are used in almost all electrical systems for the most varied switching tasks . As feed-through and basic terminal blocks are often combined on one DIN rail, these are available in the designs of the different terminal block ranges: Mini-strip terminal blocks, MBK 5 Universal terminal blocks, UK 5 N Double terminal blocks, UDK 4 Three-conductor actuator terminal blocks, DOK 1,5 Double-level terminal blocks, UKK 5. Plugs Different plug versions are available for use with the basic terminal blocks described above: ST-K4 isolating plugs are used for simple disconnection The ST-SI-UK 4 fuse plugs are designed for use with 5 x 20 mm cartridge fuse inserts The component plugs, ST-BE offer the possibility of inserting components. All fuse and component plugs are coded to avoid polarity reversal . Component terminal blocks Component terminal blocks can be used as an alternative to using component connectors . These terminal blocks are the same shape as: Mini double-level terminal blocks, MBKKB 2,5 Universal double-level terminal blocks, UKK 5 Double terminal blocks, UDK 4. Components such as diodes, resistors or LEDs are integrated directly in the terminal housing . Diode terminal blocks Various diode circuits are available for different applications . In doublelevel terminal blocks, for example, a diode conducting from bottom right to bottom left is possible as well as a further diode conducting from top to bottom left . In this case, the designation would be as follows: . . .-2 DIO/O-UL/UR-UL, i .e . the direction is always as seen when looking into the open terminal block. Phoenix Contact 275 Knife disconnect terminal blocks, MTK In measurement, regulation and control systems, disconnect terminal blocks are becoming more and more popular in order to rapidly localize faults and to permit inspection work to be carried out under zero voltage conditions. In addition to the easy-to-use disconnect knife, this range is characterized by: The narrow space saving construction, only 5 mm wide The high current carrying capacity of up to 16 A due to low contact resistances The versions with Wire-Wrap ® (WW) or TERMI-POINT® (TP) connection and The versions with soldering tags in zigzag layout, onto which 2 .8 mm slip-on sleeves can be pushed. A test socket hole for 2 .3 mm 0 test plugs is located in the vicinity of the screw shaft. MTK-P/P with test socket screws Color Knife disconnect terminal block, for mounting on v or is, with test socket Gray screws on both sides Knife disconnect terminal block, for mounting on C_) or u, with screw Gray connection on both sides Blue Feed-through terminal block, without disconnect knife . with test socket screws . Gray with screw connection Gray Knife disconnect terminal block, screw / solder connection, soldering tag on right Gray soldering on the left Gray Knife disconnect terminal block with solder connection on both sides, with test Gray holes Knife disconnect terminal block,/ x 1-WW pin on the left, screw Gray connection on the right Knife disconnect t .b ., as above, however, with 2 .4 x 0 .8 TP pin . . .L : for vertical strips . . .Q: for horizontal strips Cover Insertion bridge, fully insul ., 2-pos. fully insulated, 3-pos. divisible, insulated spine 10-pos. Partition plate, for visual and electrical separation of terminal groups, 1 mm thick t rigid solid flexible stranded Connection data 0 .2-4 0 .2-2 .5 % SP P Description Knife disconnect terminal block UK-MTK The UK 5-MTK terminal blocks feature A sturdy and closed housing Low and stable contact resistances A high dielectric strength of 500 V A construction profile similar to the feed-through terminal blocks, UK 3 N through UK 16 N . Terminal width 5.2 (IEC) [mm2] Gray Blue 11 I AWG [A] 24-12 16 U [V 401 NV/PRS/RS Type Order No. Pcs Pkt MTK-P/P 31 04 01 3 50 MTK MTK BU 31 01 01 6 31 01 19 7 50 50 MTKD-P/P MTKD 31 00 02 0 31 00 01 7 50 50 D-MTK D-MTK BU EBL 2-5 EBL3-5 EBL10-5 31 01 02 9 31 01 09 0 12 A 23 03 14 5 12A 2303158 12A 2303132 50 50 10 10 10 ATS-MTK 31 01 22 3 50 SZG 0,6 x 3,5 1205121 10 Screwdriver Zack marker strip, 10-section White MTK. . . / UK 5-MTK-P/P / UDK 4-MTK-P!P ') Meaning of the letters "R" and "L" in type designations: "R" = Soldering tag on the right "L" = Soldering tag on the left _) Current and voltage data for slip-on connections in acc . with EN 61 210 are also dependent on nom . size, material, and insulation of the receptacle and conductor cross section. Wire-Wrap:")= registered trademark of Gardner-Denver TERMI-POINT" = trademark of AMP Incorporated Note: Suitable test plugs are documented starting on page 386 . 276 Phoenix Contact Dimensions Width / length / cover width [mm] Height (NS 35/7 .5 / NS 35/15 / NS 32) [mm] Technical data in accordance with IEC / DIN VDE Max. load current / cross section [A] / [mm2 ] Max. cross section with insertion bridge (solid/stranded) [mm2 ] Rated surge voltage / contamination class [kV] / Surge voltage category / insulating material group - /Connection capacity Stranded with ferrule without / with plastic sleeve [mm2 ] Multi-conductor connection (2 cond . with same cross section) Solid / stranded [mm2] Stranded with ferrules without plastic sleeve [mm-] Stranded with TWIN ferrule with plastic sleeve [mm 2] Stripping length [mm] Internal cylindrical gauge (IEC 60 947-1) Thread Torque [Nm] Insulation material Inflammability class in acc . with UL 94 Approval data (UL/CUL and CSA) Nominal voltage ' current ,' conductor sizes UL/CUL : [V] / [A] / AWG CSA : [V] / [A] i AWG ZB 5 (for order data, see page 397) 5 .2/46/1 40 / 47,5 / 44,5 16/4 4/2 .5 6/3 II/I 0.25 - 2 .5 / 0 .25 - 1 .5 0.2-1 .5/0 .2 - 1 .5 0 .25 - 1 .5 0.5 - 1 .5 7 A3 M3 0.5 - 0 .6 PA VO MTK. .. 300 / 10 / 28 - 12 300 / 15 / 28 - 12 MTKD ... 300 ; 10/28-12 600/20/28-12 Terminal width 6 .2 (IEC) [mm2 ] Connection data UK 5-MTK-P/P MTK-LOE MTK-TP with test socket screws with screw / solder connection with screw. WW or TP connection rigid solid flexible stranded 0 .2-4 0 .2-4 I AWG [Al 24-12 16 U [V] 500 Terminal width 5 .2 (IEC) [mm 2] rigid solid Connection data 0 .2-4 Solder connection 0 .2-1 .5 Slip-on conn . 2 .8 x 0.8 mm flexible stranded AWG [A] U [V] 0 .2-2.5 0 .2-1 .5 24-12 24-16 12 12 400 400 Terminal width 5 .2 (IEC) [mm'] rigid solid Connection data 0 .2-4 WW connection) x 1 TP conn . 1 .6 x 0 .8 TP conn . 2 .4 x 0 .8 flexible stranded 0.2-2 .5 AWG I [A] U [V] 24-12 26-20 28-22 24-20 10 10 10 250 250 125 Aus SP PRS Type Order No . Pcs. Pkt. UK 5-MTK-PIP 30 04 03 2 50 Closed housing, sellout cover ED 2-6 Eli 3 .6 F310-6 Type Order No . Pcs. Pkt. MTK-LOER ') (see illustration) MTK-LOEL ,) 31 05 01 2 31 07 01 0 50 50 MTK-LOEILOE 31 09 01 8 50 D-MTK D-MTK BU L,-, : 12 A 12 A 12 A 31 01 02 9 31 01 09 0 50 50 Type Order No . Pcs. Pkt . MTK-WW (1 x 1) 1 31 1011 7 50 MTK-TP (2,4 x 0,8) 1 L MTK-TP (2,4 x 0,8) 10 31 10 41 8 31 10 51 5 50 50 D-MTK D-MTK BU EBL 2-5 EBL 3-5 EBL 10-5 31 31 23 23 23 01 02 9 01 09 0 03 14 5 03 15 8 03 13 2 50 50 10 10 10 l 31 01 22 3 50 12 05 12 1 10 02 01 15 5 02 01 14 2 02 01 13 9 100 100 10 ATP-UK 5-MTK 2mm thick 30 04 21 0 50 ATS-MTK 31 01 22 3 50 ATS-MTK SZG 0,6 x 3,5 12 05 12 1 10 SZG O,6 x 3 .5 12 05 12 1 10 SZG 0,6 x 3,5 2B6 (tor order data, see page 397) 6.2/51/— 47/54,5/52 1,, ,,, : 11 A 11 A 11 A ZB 5 (for order data, see page 397) ZB 5 (for order data, see page 397) MTK-LOE. . . // MTK-LOEILOE 5 .2/57 .5/1//5 .2!6911 51 .5/59/56 5.2/46/1 67/74 .5/72 16/4 4/4 6/3 III/I 12/4 — 6/3 III/I 10/4 4/4 4/3 III/I 0 .25 - 4 / 0.25 - 2 .5 0 .25-2 .5/ 0 .25 - 2.5 0 .25-2 .5/0 .25- 2 .5 0.2 - 1 .5 / 0 .2 - 1 .5 0 .25 - 1 .5 0 .5 - 2 .5 8 A4 M3 0 .5 - 0 .6 PA VO 600/15/22-12 600/15/18-10 0 .2-1 .5/0 .2 025-1 0.5-1 .5 7 A3 M3 0.5-0 .6 PA VO 1 .5 0.2-1 .5/0 .2-1 .5 0.25-1 0 .5-1 .5 7 A3 M3 0 .5-0 .6 PA VO 300/10/28-12 Phoenix Contact 277 Double and double-level terminal blocks with disconnect knife o - O Circuit diagram . UDMTK 5-P/P UDK 4-MTK-P/P V 0—ja 1 Terminal width 6 .2 (IEC) [mm 2 ] rigid solid flexible stranded Connection data 0 .2-6 0.2-4 I AWG [A] UKK 5-MTK-P/P U [V] 24-10 16 6301 Terminal width 6 .2 (IEC) [mm'] rigid solid flexible stranded I AWG [A] U [V . Connection data upper level lower level 0 .2-4 0 .2-4 0 .2-4 0 .2-4 24-12 12 24-12 26 40i 40! Circuit diagram : UDMTK 5-TWIN-P/P c~us Description Knife disconnect terminal block, for mounting on v or u, with test socket screws Knife disconnect terminal block, as above, however, bridgeable in both levels Double-level terminal block, for mounting on v or Lr, with disconnect knife and light indicator Double-level terminal block, as above, however, with two through contacts, without light indicator Cover LED voltage [V DC] Current [mA] Gray Blue SP Kill B RS/PRS c%us Type Order No. Pcs. Pkt . UDK 4-MTK-P/P UDK 4-MTK-P/P BU 27 75 21 0 27 75 22 3 50 50 e' B r' 8V/FRS/RS Type Order No. Pcs Pkt UKK 5-MTK-P/P 28 00 00 4 50 UKK 5-MTK-P/P-LA 24 RD/O-U UKK 5-MTK-P/P-LA 48 RD/O-U UKK 5-MTK-P/P-LA 60 RD/O-U 28 00 02 0 28 00 03 3 28 00 04 6 Sri 50 50 UKK 5-MTKD-P/P 28 00 01 7 50 1,,, : 22 A 02 03 25 0 10 18 A 03 01 50 5 10 IS-K 4 13 02 33 8 too SZG0,6x3,5 1205121 10 Gray 24 48 60 6,0 5,7 5,5 Gray Gray Blue Fixed bridge, for cross connections in the terminal center, screw heads with insulating collar, 10-position, divisible, with 10 screws Insertion bridge, fully insul .. 2-pos. fully insulated, 3-pos. divisible, insulated spine 10-pos. Isolator bridge bar, 10-position, divisible, with 10 screws, for switchable branches with Bridge bar IS-K 4 as distance piece Partition plate. for visual and electrical separation of terminal groups.. 2 mm thick 27 75 11 3 27 75 19 7 D-UDK 4 D-UDK 4 BU 50 50 Closed housing, without cover FBI 10-6 EB 2-6 EB 3-6 EB 10-6 . 12 A 02 01 15 5 12 A 02 01 14 2 12 A 02 01 13 9 100 100 10 ISSBI 10-6 J " ` ~___—rr,-nycra Screwdriver 1205053 SZS 0,6 x 3,5 10 Zack marker strip, 10-section White ZB 6 (for order data, see page 397) Dimensions Width / length / cover width [mm] Height (NS 35%7.5 / NS 35/15 / NS 32) [mm] Technical data in accordance with IEC / DIN VDE [A]/[mm'] May . load current ; cross section Max . cross section with insertion bridge (solid/stranded) [mm2] Rated surge voltage / contamination class [kV] / Surge voltage category i insulating material group -/Connection capacity Stranded with ferrule without / with plastic sleeve [mm-] Multi-conductor connection (2 cond . with same cross section) Solidi stranded [mm•] [mm'] Stranded with ferrules without plastic sleeve Stranded with TWIN ferrule with plastic sleeve [mm2 ] Stripping length [mm) Internal cylindrical gauge (IEC 60 947-1) Thread Torque [Nm] Insulation material Inflammability class in a= with UL 94 Approval data (UUCUL and CSA) Nominal voltage ! current / conductor sizes UUCUL . [V] / [Al / AWG UUCUL : [V] / [A] / AWG CSA : [V] / [A] / AWG Suitable test plugs are documented starting on page 386. 278 Phoenix Contact 6 .2 / 63 .5/ 1 .5 47/54 .5152 16/6 2 .5/2 .5 8/3 III / ') upper level -) lower level ZB 6 (for order data, see page 397) 6 .2/80/68/76/73 UKK 5-MTK .. . // UKK 5-MTKD ... 26(12')) / 4// 26 / 4) 6/3 III/I 0 .25 - 4 / 0 .25 - 1 .5 0 .25 - 4 / 0 .25 - 2.5 0 .2-1/0 .2-1 .5 025-1 .5 0 .5-1 8 A4 M3 0.6 - 0 .8 PA V2 0 .2 - 1 .5 / 0.2 - 1 .5 0 .25 - 1 .5 0.5 - 2.5 8 A3 (A 4 1 )) // A4 M3 0.6 - 0 .8 PA V2 600/15/30-10 600/10/22-10 300/15/22-10 300/15')250/26-12 300/15/22-12 UDMTK 5-TWIN-P/P UDMTK 5-P/P Disconnect knife for each level Disconnect knife for each level Terminal width (IEC) [mm2] 2 UDMTKB 5-P/P Disconnect knife for each level Terminal width 6 .2 (IEC) [mm 2] rigid solid flexible stranded AWG I [A] Connection data 24-12 8-) 400 upper level 0 .2-4 0 .2-4 24-12 81 400 lower level 0 .2-4 0 .2-4 s) The current supply from the system can take max . 16 A. The current carrying capacity of the branches is max . 8 A each . Connection data upper level lower level 0 .2-4 0 .2-4 0 .2-4 0 .2-4 24-12 24-12 10 10 Mus SP c~us SB P rigid solid flexible stranded AWG I [A] U [V] Type Order No. Pct. Pkt. UDMTK 5-TWIN-PIP UDMTK 5-TWIN-PIP BU 31 01 12 6 31 01 13 9 50 50 ed housing, out cover U [V] Terminal width 6 .2 (IEC) [mm 2 ] rigid solid flexible stranded AWG I [Al U [V] 400 400 Connection data upper level lower level 0 .2-4 0 .2-4 0 .2-4 0 .2-4 24-12 24-12 10 10 400 400 c%us Type Order No. Pcs. Pkt. UDMTK 5-PIP UDMTK 5-PIP BU 31 01 08 7 31 01 11 3 50 50 Type Order No . Pcs. Pkt. UDMTKB 5-P/P 30 24 47 8 50 10 A 02 03 25 0 10 1,,,e, .: 10 A Closed housing. without cover Closed housing, without cover FBI 10-6 03 01 50 5 10 IS-K 4 13 02 33 8 100 SZG 0,6 x 3,5 12 05 12 1 10 ISSBI 10-6 TP-UDMTK 5-TWIN 31 00 24 0 10 TP-UDMTK 5 31 00 26 6 10 MG 0,6 x 3,5 12 05 12 1 10 SZG 0,6 x 3,5 12 05 12 1 10 ZB 6 (for order data . see page 397) E L IId ZB 6 (for order data, see page 397) ZB 6 (for order data . see page 397) 6.2/76.5/68 .5/76/73 6 .2/93/68 .5176/73 6 .2/106/68 .5/76/73 8/4 10/4 10/4 4/ 3 III/I 4/ 3 III/ I 4/ 3 III/I 0 .25-4/0 .25-2 .5 0 .25-4!0.25 - 2 .5 0 .25 - 4 / 0.25 - 2.5 0 .2-1 .5/0 .2- 1 .5 0 .25-1 .5 0 .5 - 2 .5 8 A4 M3 06-0.8 PA V2 0 .2 - 1 .5 / 0 .2 - 1 .5 0 .25-1 .5 0 .5 - 2 .5 8 A4 M3 0 .6-0 .8 PA V2 0 .2-1 .510 .2-1 .5 0 .25-1 .5 0 .5 - 2 .5 8 A4 M3 0 .6 - 0 .8 PA V2 300/8/26-12 300/8/28-12 300/15/26-12 300/15/28-12 300/15/26-12 Phoenix Contact 279 Basic terminal blocks for cartridge fuse, component and isolating plugs MBK 5/E-TG Terminal width 6.2 (IEC) [mm2 ] rigid solid flexible stranded I AWG [A] U [V] Connection data 0 .20-4 0 .2-4 24-12 16' 500' The current and voltage are determined by the component and fuse plug. The 6 mm wide fuse or component terminal blocks consist of basic terminal blocks which hold fuse, component and isolating plugs. The basic terminal blocks are available in the following forms: The mini-strip terminal blocks MBK 5 The universal terminal blocks UK 5 N The double terminal blocks UDK 4 And the double-level terminal blocks UKK 5. The three and four-conductor actuator basic terminal blocks DOK 1,5-TG, DOKD 1,5-TG and VIOK 1,5-D/TG/D/PE are documented in the chapter " Doublelevel, three-level and four-level terminal blocks" (see pages 244 and 246). Basic terminal blocks with spring-cage connection can be found on page 84. For fuse, component and isolating plugs, see page 282. c%us SB PRS Description Type Order No. Pict. Basic terminal block, for component and fuse plugs MBK 5/E-TG 14 15 08 9 50 D-MBK 5/E-T 14 13 70 6 50 02 01 15 5 02 01 14 2 0201139 100 10 10 12 05 05 3 10 Basic terminal block, with test socket screws on both sides Cover Fixed bridge, for cross connections in the 1 ~1 V II If fI 0i J terminal center, screw heads with insulating collar, 10-position, divisible, with 10 screws= 2-pos. Insertion bridge, fully insul ., 3-pos . fully insulated . divisible, insulated spine 10-pos. 't~~ Isolator bridge bar, 10-position, divisible, with 10 screws, for switchable branches with Bridge bar IS-K 4 as distance piece Partition plate, for visual and electrical separation of terminal groups, 1 .5 mm thick 280 Phoenix Contact 1,,,,,,, .: 16 A 16 A 16A Screwdriver SZS O,6 x 3,5 Zack marker strip, 10-section White Dimensions') [mm] Width / length / cover width Height (NS 35/7 .5 / NS 35/15 / NS 32 / NS 15) [mm] Technical data in accordance with IEC / DIN VDE [A]/[mm] Max . load current / cross section [mm2] Max . cross section with insertion bridge (solid/stranded) Rated surge voltage / contamination class [kV)/ Surge voltage category / insulating material group -/Connection capacity [mmi'] Stranded with ferrule without l with plastic sleeve Multi-conductor connection (2 cond . with same cross section) Solid / stranded [mm'] Stranded with ferrules without plastic sleeve [mm/ ] Stranded with TWIN ferrule with plastic sleeve [mm'[ [mm] Stripping length Internal cylindrical gauge (IEC 60 947-1) Thread Torque [Nm[ Insulation material Inflammability class in acc_ with UL 94 Approval data (UUCUL and CSA) Nominal voltage current / conductor sizes UUCUL : [V] / [A] / AWG UUCUL: [V] / [A] / AWG UUCUL: [V] / [A] / AWG CSA: [V] / [A] / AWG UK 4-TG with isolating plug ST-K 4. EB 2-6 EB 3-6 EB10-6 Note: Suitable test plugs are documented starting on page 386 . 6 .2 / 28 / 1 -/-/-/36 16/4 1 .5/1 .5 6/3 III/I 0 .25 - 2 .5 / 0 .25 - 2.5 0 .2 - 1 .5 / 0 .2 - 1 .5 0 .25 - 1 .5 0 .5 - 1 .5 9 A3 M3 0 .6 - 0 .8 PA V2 150/20/28-12 300/10/28-12 300/15/28-12 ') Dimensions without plug . I, illik_ "4 11W. 7:7 UK 4-TG Terminal width 6 .2 (IEC) (nwn2] rigid solid flexible stranded UDK 4-TG I AWG [A] U [V] Terminal width 6 .2 (IEC) [mm 2 ] rigid solid flexible stranded UKK 5-TG I AWG [A] U [V] Connection data 0 .20-4 0.2-4 24-12 16' 5 C onnection 00 data ' 0.20-6 0 .2-4 24-10 16" 400" 'The current and voltage are determined by the component and ' The current and voltage are determined by the component and fuse plug . fuse plug. raw 6P ABS cStlus PRS Type Order No. Pcs. Pkt. UK 4-TG 28 12 01 8 50 UK 4-TG-P/P 28 12 03 4 50 DUK 4/10 30 03 02 0 50 16A 16A 16A 0-6 0201155 0201142 0201139 100 100 10 ATP-UK 3003224 50 SZS 0,6 x 3,5 1205053 10 Zg 6 (for order data, see page 397) with ST-T plug 'with ST-BE plug 'with ST-SI-UK 4 plug Terminal width 6.2 (IEC) [mm2] Type Order No . UDK 4-TG 27 77 01 4 50 D-UDK RELG 27 77 02 7 I,,,,, .: 16 A 0203250 50 EB 2-6 EB3-6 EB 10-6 I,,,,, : 16 A 16A 16 A 02 01 15 5 0201142 02 01 13 9 100 100 10 1205053 ZB 6 (for order data, see page 397) I AWG [A] U [V) e' PRS Type Order No . Pcs. Pkt. UKK 5-TG 30 07 04 2 50 Closed housing, without cover FBI 10-6 SZS 0,6 x 3,5 flexible stranded Connection data upper level 0 .2-4 0.2-4 24-12 16' 400 ' lower level 0 .2-4 0.2-4 24-12 26 400 ' The current and voltage are determined by the component and fuse plug. c%us Pcs. Pkt . rigid solid 10 FBI 10-6 I,, 26 A 02 03 25 0 50 EB2-6 EB 3-6 EB 10-6 ISSBI 10-6 22A 0201155 22 A 02 01 14 2 22 A , 0201139 I,,,a, : 26 A 03 01 50 5 100 100 10 10 IS-K 4 1302338 100 SZG 0,6 x 3,5 1205121 10 Phoenix Contact 281 ZB 6 (for order data, see page 397) 6 .2 / 42 .5 / 1 .8 47/54 .5/52/- 6 .2 / 63 .5 / 1 .5 47/54 .5/52/- 6 .2/80/– 68 .5/76/73/- 16/4 1 .5/1 .5 6/3 III / I 16/6 2.5/2 .5 6/3 III / I 26/4//16/4') 4/4 6/3 III /I 0.25-2 .5/0 .25-2 .5 0 .25-4/0 .25-1 .5 0 .25-4/0 .25-2 .5 0.2 - 1 .5 / 0 .2 - 1 .5 0 .25 - 1 .5 0.5 - 1 .5 9 A3 M3 0 .6 - 0 .8 PA V2 0.2-1/0 .2-1 .5 025-1 .5 0.5-1 8 A4 M3 0 .6 - 0 .8 PA V2 0 .2-1 .5/0.2-1 .5 0 .25 - 1 .5 0 .5 - 2 .5 B A3 2) I A4') M3 0 .6 - 0.8 PA V2 600/20/28-12 2 ) 600/5/28-12 1) 300/6,3/28-12 2) 600/15/28-12 300/15/30-12 300/15/26-122) 300/15/30-12 300/25/26-121 300/15/28-12 =) upper level lower level Fuse, component and isolating plugs ST BE ST-SI-UK 4 c91~us Description LED voltage [V AC/DC] Current [mA] Fuse plug, for cartridge fuse inserts 5 x 20 mm, 26.5 mm high, color : Black Type ii ST-SI-UK 4 Fuse plug n ), as above, however with light indicator: 5 - 15 15-30 30-60 110-250 Component plug, for connecting components with two positions to the basic terminal block. 19 mm high, color : Gray Component plug, for connecting components with two positions to the basic Lb., 19 mm high, with light indicator Component plug=), as above . however, with universal diode 1N 4007 callus SB ABS 2 .0 - 7 .5 3 .5-7 .5 2 .5-5 .5 0 .5-1 ST-SILED 12-UK 4 ST-SILED 24-UK 4 ST-SILED 60-UK 4 ST-SILA 250-UK 4 6 .3 A')') l,, : 6.3 A')') 6.3 A l )') 6.3 A')') 6 .3 A')2) Order No. Pcs. PkI . 09 21 01 1 50 09 21 02 4 i 0921037 09 21 04 0 09 21 05 3 50 50 50 50 for 24 V DC for 230 V AC/DC PA V2 The ST-SI-UK 4 fuse plugs for 5 x 20 mm cartridge fuse inserts are available with or without light indicator. The version with light indicator includes light diodes connected back-to-back as well as preresistors for the three voltage levels up to 60 V and glow lamp with preresistors for the voltage level above 110 V. The plug housing is flapped open at the side to change the fuse. The component plugs, ST-BE are available as single plugs for 2-position components and as double plugs (fourposition plugs) with or without inserted components. The component itself is inserted from above and reliably clamped. Phoenix Contact ST-1N4007 .1 ) 28 02 32 9 ST-BE-VP') 28 02 33 2 ST-B 250C1500 28 02 34 5 I mo , ,: 16 A 300/6 .3/ 300 / 10 / – I ) With single arrangements . -) Max . power dissipation, see table on page 271 . ^) I f the fuse is defective, the downstream circuit is not off load . ST-K 4 : ST-K 4 : R P 28 02 31 6 28 02 37 4 28 02 38 7 50 25 46 2 0306704 TZ _ UUCUL : [V] / [A] / AWG CSA : [V] / [A] / AWG 16 A l) ST-BE-LA 24 ST-BE-LA 230 ST-K 4 Isolating plug, 13.5 mm high 282 I ca, : ST-BE Component plug,`), for components with four positions, two basic terminal blocks are necessary per plug . 19 mm high, color : Gray Component plug, as above, however, with bridge rectifier B 250 C 1500 Plug pliers, simplify removing the isolating plug from a closed row of terminal blocks Insulation material Inflammability class in acc . with UL 94 Approval data (UL/CUL and CSA) Nominal voltage current conductor sizes Order No . Type PA V2 ST-BE : ST-BE: 300/10/ 30-14 300 / 10 / 30-14 Technical data of the component plugs: ST-1N 4007 ST-B 250 C 1500 Diode 1 N 4007 Rectifier : B 250 C 1500 Reverse voltage : 1300 V Reverse voltage : 600 V Max . continuous current : 0 .5 A Nominal voltage : 250 V Nominal current : 1 .5 A PA VC Component plug, BES 6 BES 6 The special advantage of this component plug is that any components with two positions, such as diodes, varistors, etc . can be inserted at a later time between two neighboring standard feed-through terminal blocks. The BES 6 is supplied as a set with two sockets . The sockets are screwed into the center thread of the feed-through terminal blocks . They are different lengths, and this determines the correct functional direction corresponding to the vertically offset multiple-spring wire plugs and prevents later confusion . If several BES 6 plugs are ed next to each other, separating plates uld be provided between the pairs of terminal blocks in order to prevent incorrect plugging. To insert the components, the upper half of the housing is lifted, thus exposing the plug pins for soldering. The BES 6 is also available with a IN 4007 diode fitted for the protection circuit of DC consumers with nominal operating data up to 1300 V and 0 .5 A . In addition, the BES 6 is available with a light indicator for voltages of 15-30 V DC and 110-250 VAC. Diode 1 N 4007 Reverse voltage : 1300 V Maximum continuous current: 0 .5 A Dimensions, see below LED voltage Current [VI [mild Component plug, complete, for connection of components between two neighboring feed-through terminal blocks Description Type Order No. Pcs. Pkt. BES 6 28 02 54 9 10 BES 6-1 N4007 2802552 10 Component plug, as above, however with diode 1 N 4007 Component plug . with light indicator 15- 30 DC 2 .5 - 7 .5 BES 6-LA 24 28 02 56 5 10 Component plug, with light indicator 110 - 250 AC/DC 0 .5 - 1 BES 6-LA 230 28 02 57 8 10 Insulation material Inflammability class in acc . with UL 94 PA V2 2 II Data of the components to be soldered in + Length including connection wires Width or diameter Diameter of the connection wires Max . power dissipation at 25'C 10 mm 6 mm 1 .3 mm 1W Height dimensions a with BES 6 inserted: Type Page Dim . a [mm] 7 0 N o Damping diode with feed-through terminal blocks and BES 6 MBK 5 MBK 5/E-Z UK 5 N UKB 4 UKK 5 UKK 5 UVKB 4 315 309 211 340 239 239 340 64 68 75 75 92 92 76 DIN rail NS 15 NS 15 NS 35/7 .5 NS 35/7 .5 NS 35/7,5 NS 35/7 .5 NS 35/7,5 Construction : BES 6 Phoenix Contact 283 Component terminal blocks MBKKB 2,5-DIO with integrated diodes .) Data is based on the dielectric strength of adjacent terminal Terminal width 5 .2 (IEC) [mm u ] rigid solid flexible stranded AWG I [A] U [V) Connection data 0 .2-4 0.2-2.5 24-12 24 500 1) Integrated : Diode 1 N 4007 Reverse voltage : 1300 V Maximum cont . current : 0.5 A blocks or the DIN rail. 0 ••O 0 ••0 0 0 . .. 0 DIO/0-U • 0 . . . DIO/U-0 If 1J ~O Type Order No. Po. Pkt Terminal block, with integrated 1 N 4007 diode. conducting from top to bottom MBKKB 2,5-DIO/O-U 2800567 50 Terminal block, with integrated 1N 4007 diode, conducting from bottom to top MBKKB 2,5-DIO/U-O 28 00 57 0 50 MBKKB 2,5.2DIO/O-UUO-UR 3003871 50 D-MBKKB 2,5 14 13 05 2 DP-MBKKB 2,5 14 13 06 5 Terminal block, with integrated 1 N 4007 diode, conducting from bottom left to bottom right Terminal block, with two integrated 1N 4007 diodes, conducting from top to bottom left and from top to bottom right or from bottom right to bottom left Terminal block, for soldering in a component from top to bottom Terminal block, for soldering in a component from top to bottom left and from bottom right to bottom left 0•-0 \ j" v Cover Spacer cover, compensates for level offset if standard terminal blocks are aligned tJ O .. . DIO/UL-UR 0 - ~-• p .. . 2 D1010-UUUR-UL 0 -0 0— .. . 2 D101O-UUO-UR 0 .110 . /-- 0 UKK 5-BE or MBKKB 2,5-BE 284 Description Phoenix Contact 110 —6 •- UKK 5-2 BE Spacer plate, compensates for level offset if standard terminal blocks are to be fitted adjacently, 2 .5 mm thick Fixed bridge, for cross connections in the terminal center, with permanently crimped rolls, screw heads with insulating collar as shock protection 2-pos. 3-pos. 4-pos. 10-pos. FBRNI 2-5 N FBRNI 3-5 N FBRNI 4-5 N FBRNI 10-5 N I m „ : 22 A 22 A 22 A 22 A Screwdriver SZS O,6 x 3,5 Zack marker strip, 10-section, white Dimensions [mm] Width r length / cover width )mm] Height (NS 35,7 .5/NS 35/15 / NS 32) Technical data in accordance with !EC/DIN VDE Max . load current / cross section [A]/[mm') [kV] I Rated surge voltage / contamination class -/Surge voltage category / insulating material group Connection capacity Stranded with ferrule without I with plastic sleeve [mm , ] Multi-conductor connection (2 cond . with same cross section) [mm-] Solid / stranded [mm'] Stranded with ferrules without plastic sleeve Stranded with TWIN ferrule with plastic sleeve [mm ,] [mm] Stripping length Internal cylindrical gauge (IEC 60 947-1) Thread [Nm] Torque Insulation material Inflammability class in acc . with UL 94 Approval data (UUCUL and CSA) UUCUL : [V] / [A] / AWG Nominal voltage current / conductor sizes CSA : [V) I [A] / AWG ZB 5 (for order data . see page 397) 5.2 / 62 / 2 .5 48/55 .5/-147 .5 26 / 2 .5 6/3 11111 0 .25 - 2 .5 / 0 .25 - 2 .5 0 .2-1/0 .2-1 .5 025-1S 0 .5- 1 .5 7 A3 M3 OS-OS PA V2 30 00 17 5 30 00 16 2 30 00 15 9 27 70 63 9 10 10 10 10 12 05 05 3 10 MBKKB 2,5-BE UKK 5-DIO UKK 5-BE with integrated diodes Terminal width 5.2 (IEC) [mm=] rigid solid flexible stranded I AWG [A] U [V] Connection data 0 .2-4 0 .2-2 .5 24-12 24 500') Maximum width of components to be soldered i n : 4 mm Terminal width 6 .2 (IEC) [mm'] rigid solid flexible stranded Connection data 0 .2-4 0 .2-4 I‘IKKB 2,5-BE 1414103 D-MBKKB 2,5 14 13 05 2 DP-MBKKB 2,5 FBRNI 2-5 N FBRNI 3-5 N FBRNI 4-5 N FBRNI 10-5 N 22 A 22 A 22 A 22 A SZS 0,6 x 3,5 Z85 (for order data, see page 397) 1 24-12 32 U [V] 500') Integrated : Diode 1 N 4007 Reverse voltage : 1300 V Maximum cont . current : 0.5 A c~us B Order No . I AWG [A] Pcs. Pkt. rigid solid flexible stranded I AWG [A] U [V] Connection data 0 .2-4 0.2-4 24-12 32 500 ' ) Maximum installation width of components to be soldered in . 5 mm NV Type Order No. Pcs. PkI. UKK 5-DIO/O-U 27 91 01 6 50 UKK 5-DIO/U-O 27 91 03 2 50 UKK 5-DIO/UL-UR 27 91 02 9 50 UKK 5-2 DIO/O-UUUR-UL 27 91 11 3 50 50 50 Terminal width 6 .2 (IEC) [mm', ] Type Order No . Pcs. Pkt. UKK 5-BE 30 48 02 7 50 UKK 5-2 BE 30 48 03 0 50 D-UKK 3/5 27 70 02 4 50 D-UKK 3/5 27 70 02 4 50 DG-UKK 3/5 27 70 81 7 50 DG-UKK 3/5 27 70 81 7 50 27 70 79 4 50 DP-UKK 3/5 27 70 79 4 50 0203250 10 FBI 10-6 0203250 10 1205053 10 SZS 0,6 x 3,5 1205053 10 14 13 06 5 50 DP-UKK 3/5 3000175 3000162 3000159 27 70 63 9 10 10 10 10 FBI 10-6 12 05 05 3 10 SZS 0 .6 x 3,5 I m„ : 32 A ZB 6 for order data . see page 397) 32 A ZB 6 (for order data, see page 397) 5 .2/62/2 .5 48/55 .51-/47 .5 6.2 / 56 / 2 .5 62/69 .5/67/- 6 .2/56/2 .5 62/69-5/67/ 26 / 2 .5 6/3 1II/1 32/4 6/3 III / I 32/4 6/3 111 11 0 .25 - 2.5 / 0.25 - 2 .5 0 .25 - 4 / 0 .25 - 2 .5 0 .25-4!0 .25-2 .5 0.2-1/0 .2-1 .5 025-1 .5 0 .5-1 .5 7 A3 M3 0 .6-0.8 PA V2 0 .2-1 .5/0 .2- 1 .5 0 .25 - 1 .5 0 .5 - 1 .5 8 A4 M3 0 .6 - 0 .8 PA VO 0 .2-1 .5/0 .2-1 .5 0.25 - 1 .5 0 .5 - 1 .5 8 A4 M3 0 .6 - 0 .8 PA VO 600/30/26-10 Phoenix Contact 285 Component terminal blocks The constant current circuits common in process automation transmit the measured values as a load-independent current of 0(4) - 20 mA . A voltage signal pick-off can be implemented in the measuring conductor using the UDK 4-DUR terminal block, thus allowing the signal to be used as an analog signal for process computers . The four-conductor connection makes for convenient wiring . The lower level is assigned to the measuring line and the upper level is used for the voltage pickoff via the 249 S2 resistor. The integrated light indicator in UKK 5-LA indicates the voltage condition of the lower feed-through level . UDK 4-DUR UKK 5-LA with differential voltage resistor with light indicator Terminal width 6 .2 (IEC) rigid flexible solid stranded AWG [A] [mm 2 ] ) Connection data 0 .2-6 0.2-4 24-10 ') The current is determined by the component used . U [V] 630 Terminal width 6 .2 (IEC) [mm z] rigid solid flexible stranded I AWG [A] U [V] Connection data 0 .2-4 0 .2-4 24-12 32 5001 2) Data is based on the dielectric strength of adjacent terminal blocks or of the DIN rail. Maximum installation width of components to be soldered in : 5 mm Description LED voltage [V AC/DC] Current [mA] Differential voltage terminal block, a) for self-soldering a resistor b) with fitted resistor 249 Sal_ 1%/1 W Double-level terminal block, 15 - 30 DC 30 - 60 DC with light indicator 110 - 230 AC/DC Type Order No . Pcs. Pkt . a) UDK 4-DUR b) UDK 4-DUR 249 27 75 20 7 27 75 24 9 50 50 2.5-7.5 1 .9-4.0 0.5-1 .0 27 75 11 3 D-UDK 4 Cover Spacer cover, compensates for level offset if standard terminal blocks are aligned in rows, 2.5 mm thick Spacer plate, compensates for level offset if standard terminal blocks are to be fitted adjacently, 2 .5 mm thick Fixed bridge, for cross connections in the terminal center, screw heads with insulating DO'COMoam collar, 10-position, divisible, with 10 screws 2-pos . , Insertion bridge, fully insul ., fully insulated, 3-pos. 10-pos. divisible, insulated spine Isolator bridge bar, 10-position, divisible, with 10 screws, for switchable branches with Bridge bar IS-K 4 as distance piece Separating plate, for electrical separation of neighboring bridges, can be fitted later, no loss of pitch mlvnlm El FBI 10-6 50 Zack marker strip, 10-section White Dimensions Width / length / cover width [mm] [mm] Height (NS 3525 / NS 35/15 / NS 32) Technical data in accordance with IEC / DIN VDE [A]/[mm2] Max . load current / cross section [mm%] Max . cross section with insertion bridge (solid/stranded) [kV] / Rated surge voltage / contamination class Surge voltage category / insulating material group -/Connection capacity Stranded with ferrule without / with plastic sleeve [mm2] Multi-conductor connection (2 cond . with same cross section) [mm-'] Solid / stranded [mm2'] Stranded with ferrules without plastic sleeve Stranded with TWIN ferrule with plastic sleeve [mm2] [mm] Stripping length Internal cylindrical gauge (IEC 60 947-1) Thread [Nm[ Torque Insulation material Inflammability class in acc . with UL 94 Approval data (UUCUL and CSA) UUCUL [V] / [A] / AWG Nominal voltage / current ! conductor sizes CSA : [V] / [Al / AWG 286 Phoenix Contact ZB 6 (for order data, see page 397) 27 70 02 4 50 DG-UKK 3/5 27 70 81 7 50 DP-UKK 3/5 2770794 50141 l,,,,27 A 27 A 27 A Imp , : 24 A 0201155 02 01 14 2 0201139 03 01 50 5 100 100 10 10 100 IS-K 4 13 02 33 8 100 TS-KK 3 27 70 21 5 50 ATP-UKK 3/5 27 78 52 1 50 SZS0,6x3,5 1205053 to 50 Partition plate, for visual and electrical separation of terminal groups, 2 .5 mm thick 12 05 05 3 D-UKK 3/5 EB 2-6 EB 3-6 EB 10-6 ISSBI 10-6 13 02 33 8 SZS 0,6 x 3,5 50 50 50 100 100 10 10 02 01 15 5 02 01 14 2 0201139 03 01 50 5 Screwdriver 27 91 32 0 27 91 33 3 27 91 35 9 10 26 A 26 A 26A 32 A 27 70 21 5 UKK 5-LA 24 RD/U-0 UKK 5-LA 60 RD/U-0 UKK 5-LA 230 02 03 25 0 10 TS-KK 3 Pte' Pkt. I,,,,,, : 32 A 02 03 25 0 IS-K 4 Order No. FBI 10-6 Imo, ; 32 A EB 2-6 EB 3-6 EB 10-6 ISSBI 10-6 Type 10 ZB 6 (for order data, see page 397) 6 .2 / 63.5 / 1 .5 47 / 54.5 / 52 6 .2 / 56 / 2 .5 62 / 69 .5 / 67 1)/6 2 .5/2.5 6/3 III / I 32/4 4/2.5 6/3 II/I 0 .25-4/0 .25 - 1 .5 0 .25 - 4 / 0 .25 - 2 .5 0.2-1/0 .2-1 .5 0.25-1 .5 0 .5-1 8 A4 M3 0.6-0 .8 PA V2 0.2-1/0 .2-1 .5 0 .25 - 1 .5 0 .5 - 1 .5 8 A4 M3 0 .6 - 0 .8 PA VO 600/10/22-10 600/20/26-10 600/20/26-10 Thermoelectric voltage terminal block pair, MTKD- . .. MTKD- . .. Terminal width 10 .4 (IEC) [mm ,] AU=O In thermocouple measurement circuits, the thermocouple is extended by using equalizers . This is the area of application of these special terminal blocks. The equalizers are made of materials which, up to temperatures of approximately 200°C, have the same thermal characteristics as the corresponding thermocouples. The through contacts in these MTKD thermoelectric voltage terminal blocks are made of the same material as the equalizers in acc . with DIN 43 713 and DIN 43 714. This ensures that no false thermoelectric tages result at the connection points of thermocouple/terminal block/equalizer and that the basic values according to EN 60 584/DIN EN 60 584 are observed. The thermoelectric voltage terminal block pair is clearly marked with the compensating material used. rigid flexible solid stranded AWG Connection data 0 .2-4 0 .2-2 .5 24-12 * Voltage to the neighboring feed-through terminal MTK. U [V] 400' C% US Type Order No . Pcs. Pkt. MTKD-CU/CUNI 31 00 05 9 50 MTKD-FE/CUNI 31 00 04 6 50 MTKD-NICR/CUNI 31 00 07 5 50 MTKD-NICRSIINISI 50 43 32 1 50 MTKD-NICR/NI 31 00 06 2 50 MTKD-E-CU/A-CU 31 00 09 1 50 MTKD-S-CUIE-CU 31 00101 50 Cover D-MTK 31 01 02 9 50 Partition plate, for visual and electrical separation of terminal groups, 1 mm thick ATS-MTK 31 01 22 3 SO SZS 1,0 x 4,0 1205066 10 Phoenix Contact 287 Description USA-type Thermoelectric voltage terminal block pair for CU/CUNI44 copper/ constantan Thermoelectric voltage terminal block pair for FE/CUNI44 iron/constantan Thermoelectric voltage terminal block pair for NICR/CUNI44 nickel-chrome/constantan Thermoelectric voltage terminal block pair for NICRSI/NISI nickel-chrome silicone/nickel-silicone Thermoelectric voltage terminal block pair for NICR/NI nickel-chrome/nickel Thermoelectric voltage terminal block pair for E-CU/A-CU copper/copper nickel Thermoelectric voltage terminal block pair for S-C WE-CU S-copper/copper Screwdriver Zack marker strip, 10-section White Dimensions Width / length / end cover width [mm] Height (NS 35/7 .5 / NS 35/15 / NS 32) [mm] Stripping length [mm] Internal cylindrical gauge (IEC 60 947-1) Thread Torque [Nm] Insulation material Inflammability class in acc . with UL 94 Approval data (UL/CUL and CSA) Nom . voltage / nom . current / conduc . UL/CUL . [V] [A] / AWG ZB 10 (for order data, see page 399) 5 .2 / 46 / 1 40/47 .5/45 7 A3 M3 0 .6 - 0 .8 PA VO 300/10/28-12 Table for selecting thermoelectric voltage terminal blocks rmocouple material er+'constantan (Cu/CuNi44) constantan (Fe/CuNi44) Nckel-chrome/constantan (NiCr/CuNi44) Ildtel-chrome/nickel (NiCr/Ni) Platinum-rhodium/platinum(PIPh/Pt) Iblinum, 13% rhodium/platinum Platinum, 30% rhodium/platinum, 6% rhodium Equalizer material Copper/constantan (Cu/CuNi44) Iron/constantan (Fe/CuNi44) Nickel-chrome/constantan (NiCr/CuNi44) Nickel-chrome/nickel (NiCr/Ni) Copper/copper-nickel (E-Cu/A-Cu) Copper/copper-nickel (E-Cu/A-Cu) S-copper/copper (S-Cu!E-Cu) Thermoelectric terminal block pair MTKD-CU/CUNI MTKD-FE/CUNI MTKD-NICR/CUNI MTKD-NICR/NI MTKD-E-CU/A-CU MTKD-E-CU/A-CU MTKD-S-CU/E-CU Light indicator terminal blocks for voltage and current Load current diagram of the current indicator terminal block, UDK 4-ILA Terminal current is dependent on the ambient temperature Duty cycle : 100 UDK 4-ULA UDK 4-ILA with voltage indicator Terminal width 6 .2 (IEC) [mm 2 ] 0,25 IIUUUU1iI011U11 UDK 4-ILA 500 ::. 30 40 50 60 70 flexible stranded I AWG [A] U [V] Connection data 0 .2-6 0.2-4 24-10 32') 500-) ') The rated current must not be exceeded by the total current of all connected conductors. -') To neighboring terminal blocks. 0 20 rigid solid with current indicator 80 Terminal width 6 .2 (IEC) [mm 2 ] rigid solid flexible stranded Connection data UDK 4-ILA 500 0 .2-6 UDK 4-ILA 1000 0 .2-6 'I To neighboring terminal blocks. -) Observe load current diagram. 0 .2-4 0 .2-4 I AWG [A] U [V] 24-10 0 .5'1 500', 24-10 1 .0'1 5001 Ambient temperature ['C] mu, LED Description voltage [V AC/DC] Voltage indicator terminal 15 - 30 DC block, gray with universal foot 30 - 60 DC for mounting on V or u 110 - 230 AC/DC Power terminal block, blue, to connect the reference potential to return busbar RS, I,,,a, = 2 A Current [mA] 2 .5 - 7 .5 1 .9 - 4.0 0 .5 - 1 .0 IKL- 01us SP KE "u Type Order No . Pcs. Pkt. UDK 4-ULA 24 RDIO-U UDK 4-ULA 48 RD/O-U UDK 4-ULA 230 27 75 04 5 27 75 03 2 27 75 05 8 50 50 50 27 75 02 9 50 2775126 1 UDK 4-ULA1EK Return busbar, 3 mm 0, engaged in terminal block and led parallel to terminal strip, length: 1 m Current indicator terminal block, black, shows current flow of an auxiliary circuit via an LED, for a load current of : SP ' RS 4 - 500 300 - 1000 Cover, gray D-UDK 4 Fixed bridge, for cross connections in the terminal center, screw heads with insulating collar. 10-position, divisible, with t0 screws Insertion bridge, fully insul . 2-pos fully insulated, 3-pos divisible, insulated spine 10-pos Isolator bridge bar,for switchable branches, 10 positions, divisible, with 10 screws with Bridge bar isolator IS-Kb4 as distance piece Switch bar for 2 terminal blocks, complete, to increase insulation an end cover must be interposed Separating plate, for electrical separation of neighboring bridges, can be fitted later, no loss of pitch rrnr Order No . Pkt. UDK 4-ILA 500 UDK 4-ILA 1000 2775061 27 75 08 7 50 50 27 75 11 3 27 75 11 3 50 D-UDK 4 02 03 25 0 10 FBI 10-6 I,,,, : 26 A 02 01 15 5 26 A 02 01 14 2 26 A 02 01 13 9 32 A 03 01 50 5 100 100 10 10 EB 2-6 EB 3-6 EB 10-6 ISSBI 10-6 13 02 33 8 100 IS-K 4 32 A FBI 10-6 EB 2-6 EB 3-6 EB 10-6 ISSBI 10-6 Type IS-K 4 USBR 2-7 24 A 23 03 23 9 I 32A I 0203250 10 : 26 A 02 01 15 5 26 A 02 01 14 2 26 A 02 01 13 9 32 A 03 01 50 5 100 100 10 10 13 02 33 8 100 USBR 2-7 24 A 23 03 23 9 TS-KK 3 27 70 21 5 50 TS-KK 3 27 70 21 5 50 SZS 0,6 x 3,5 1205053 10 SZS O,6 x 3,5 1 2 05 05 3 1 Screwdriver Zack marker strip, 10-section White Dimensions Width / length / cover width [mm] [mm] Height INS 35/7.5 '. NS 35 115 / NS 32) Technical data in accordance with IEC / DIN VDE Max . load current / cross section [A]/[ mm, ] Max . cross section with insertion bridge (solid/stranded) [mm, ] Rated surge voltage / contamination class [kV] / – Surge voltage category ! insulating material group Connection capacity Stranded with ferrule without ! with plastic sleeve [mm[] Multi-conductor connection (2 cond . with same cross section) Solid / stranded [mm-] Stranded with ferrules without plastic sleeve [mm[] Stranded with TWIN ferrule with plastic sleeve [mm[] Stripping length [mm] Internal cylindrical gauge (IEC 60 947-1) Thread Torque [Nm] Insulation material Inflammability class in acc . with UL 94 Approval data (UUCUL and CSA) Nominal voltage current ' conductor sizes UL/CUL : [V] / [A] / AWG CSA: [V] / [A] / AWG CSA: [V] .' [A] /AWG 288 Phoenix Contact ZB 6 (for order data, see page 397) ZB 6 (for order data, see page 397) 6 .2 / 63 .5 / 1 .5 47/54.5/52 .5 6 .2 / 63 .5 / 1 .5 47/54 .5/52.5 32/6 2 .5 / 2 .5 6/3 III / I 0 .5'')/6 2.5/2.5 6/3 III/I 0 .25-4/0 .25-1 .5 0.25 - 4 / 0 .25 - 1 .5 0 .2-1/0 .2-1 .5 0 .25-1 .5 0 .5-1 8 A4 M3 0.6-0 .8 PA V2 0 .2-1/0 .2- 1 .5 0 .25 - 1 .5 0 .5 - 1 8 A4 M3 0 .6 - 0.8 PA V2 600/30/30-10 300/25/22-12 600/10/22-12 600/0 .5/30-10 600/0 .5/22-10 C Ground disconnect terminal block, GTF 76 GTF 76 Terminal width 22 .5 (IEC) [mm2 ] In EN 60 204-1/VDE 0113 part 1 " Electrical equipment of industrial machines " , section 9 .4 .3 .1 specifies that: "ground faults in control circuits must not lead to an unintentional startup or dangerous movement of a machine or prevent it shutting down . . .". This requirement is fulfilled by the ground disconnect terminal block, GTF 76. With the disconnect slide closed in " ON " position, the yellow lamp indicates grounded normal operation . If the disconnect slide is moved to the " OFF " osition, the red lamp indicates whether re is a ground fault in the control circuit . s Connection data GTF 76/230 GTF 76/48 rigid solid flexible stranded AWG I [A] U [V[ 0 .5-10 0 .5-10 0.5-6 0.5-6 20-8 20-8 57 57 110-250 24-48 clus GTF 76/230 only Description Type Order No . Pcs. Pkl. 0 .5-1 GTF 76/230 31 21 01 2 10 3 .5-8 GTF 76/48 31 21 02 5 10 SZS 1,0 x 4,0 1205066 10 Current [mA] Ground disconnect terminal block, with universal foot for mounting on U . nr or C_), for 110-250 VAC%DC Ground disconnect terminal block, with universal foot for mounting on U, n__r orC t, for 24-48 V AC/DC Screwdriver Zack marker strip, 10-section, white Dimensions [mm] Width / length Height (NS 15 . NS 35/7 .5 / NS 35/15 / NS 32) [mm] Technical data in accordance with IEC / DIN VDE Rated surge voltage . contamination class [kV)/ Surge voltage category / insulating material group Connection capacity [mm] Stranded with ferrule without / with plastic sleeve Multi-conductor connection (2 cond . with same cross section) [mm/] Solid ! stranded Stranded with ferrules without plastic sleeve [mm] Stranded with TWIN ferrule with plastic sleeve [mm-] Stripping length [mm] Internal cylindrical gauge (IEC 60 947-1) Thread [Nm] Torque Insulation material Inflammability class in acc . with UL 94 Approval data (UUCUL and CSA) Nominal voltage !current .," conductor sizes ZB 10 for order data, see page 399) 22 .5 / 64 .5 53 .5/54/61 .5/59 4/3 III/I 0 .5-10/0.5-4 0.5-6/0 .5-6 0 .5 - 6 0 .5 - 4 12 AS M4 1 .2 - 1 .5 PA VO UUCUL [V[ / [A] / AWG CSA : [V[ / [A] / AWG 250/50/26-8 250/50/26-8 Note: Due to imbalances in the cable insulation, the red indicator may light up slightly when the disconnect slide is in the open position, even though there is no ground fault. This has no effect on the functional efficiency and does not influence the protective functions required by the VDE regulations. external operating indicator 0 01 yellow operating I indicator Warning During insulation testing in accordance with EN 60 204-1 /VDE 0113 part 1, the 'TF 76 should be either disconnected or ridged, as otherwise the light indicator will be damaged or a short circuit will result . 3 . Grounded operating mode Ground fault Phoenix Contact 289