MTK, UKK Disconnect and component terminal blocks

advertisement
MTK, UKK Disconnect and component terminal blocks
General information
In addition to the standard feedthrough modular terminal blocks,
modular terminal blocks with
different functions are also needed.
For some applications, for example,
it must be possible to disconnect the
signal paths individually in order to
switch them off load or to loop in a
measuring device . Different knife
disconnect terminal blocks are
available for such applications.
Test socket screws are integrated
on the right and left of the disconnect
zone, so that the measuring device
can be directly looped in with the
test plugs . Space-saving solutions
such as double-level terminal blocks
also exist for the disconnect terminal
blocks . Here, two feed-through
levels that can each be independently
274
Phoenix Contact
disconnected from the other with a
knife are integrated . This solution
saves 50% more space in comparison
with a single-level terminal block.
To implement components in
signal paths, plugs are available that
can be plugged onto the basic
terminal blocks without the risk of
polarity reversal . Either components
such as resistors, diodes or fine fuses
can be inserted into these plugs.
If the components are to be
integrated permanently in the
terminal block instead of being
pluggable, component and diode
terminal blocks are available.
Knife disconnect terminal blocks
MTK
In measurement, regulation and
control systems, disconnect terminal
blocks are becoming more and more
popular in order to rapidly localize
faults and to permit inspection work
to be carried out under zero voltage
conditions.
In addition to the easy-to-use
disconnect knife, this range is
characterized by:
Space-saving design
High current carrying capacity up
to 16 A
Type versions with soldering tags
Screws with integrated test
sockets .
Double-level terminal blocks
with disconnect knives for both
levels, UDMTK
Besides the easy-to-use disconnect
knives, the UDMTK 5-PIP terminal
block features are :
A sturdy and closed housing
Double connection and
Double disconnection .
The disconnect knife on the lower
level is characterized by a slight
vertical offset .
The UDMTK 5-TWIN-PIP terminal
block has the same advantages as the
UDMTKS-PIP. It has a conductor
connection on the system side, however,
which can be split and disconnected via
both disconnect knives .
Basic terminal blocks
Basic terminal blocks for fuse,
component and isolating plugs are
used in almost all electrical systems
for the most varied switching tasks . As
feed-through and basic terminal
blocks are often combined on one
DIN rail, these are available in the
designs of the different terminal block
ranges:
Mini-strip terminal blocks, MBK 5
Universal terminal blocks, UK 5 N
Double terminal blocks, UDK 4
Three-conductor actuator terminal
blocks, DOK 1,5
Double-level terminal blocks, UKK 5.
Plugs
Different plug versions are
available for use with the basic
terminal blocks described above:
ST-K4 isolating plugs are used for
simple disconnection
The ST-SI-UK 4 fuse plugs are
designed for use with 5 x 20 mm
cartridge fuse inserts
The component plugs, ST-BE offer
the possibility of inserting
components.
All fuse and component plugs are
coded to avoid polarity reversal .
Component terminal blocks
Component terminal blocks can
be used as an alternative to using
component connectors . These
terminal blocks are the same shape as:
Mini double-level terminal blocks,
MBKKB 2,5
Universal double-level terminal
blocks, UKK 5
Double terminal blocks, UDK 4.
Components such as diodes,
resistors or LEDs are integrated
directly in the terminal housing .
Diode terminal blocks
Various diode circuits are available
for different applications . In doublelevel terminal blocks, for example, a
diode conducting from bottom right
to bottom left is possible as well as a
further diode conducting from top to
bottom left . In this case, the
designation would be as follows:
. . .-2 DIO/O-UL/UR-UL, i .e . the
direction is always as seen when
looking into the open terminal block.
Phoenix Contact
275
Knife disconnect terminal
blocks, MTK
In measurement, regulation and control
systems, disconnect terminal blocks are
becoming more and more popular in order
to rapidly localize faults and to permit
inspection work to be carried out under
zero voltage conditions.
In addition to the easy-to-use disconnect
knife, this range is characterized by:
The narrow space saving construction,
only 5 mm wide
The high current carrying capacity of up
to 16 A due to low contact resistances
The versions with Wire-Wrap ® (WW)
or TERMI-POINT® (TP) connection and
The versions with soldering tags in
zigzag layout, onto which 2 .8 mm slip-on
sleeves can be pushed.
A test socket hole for 2 .3 mm 0 test
plugs is located in the vicinity of the screw
shaft.
MTK-P/P
with test socket screws
Color
Knife disconnect terminal block, for
mounting on v or is, with test socket
Gray
screws on both sides
Knife disconnect terminal block, for
mounting on C_) or u, with screw
Gray
connection on both sides
Blue
Feed-through terminal block, without
disconnect knife . with test socket screws .
Gray
with screw connection
Gray
Knife disconnect terminal block, screw
/ solder connection, soldering tag on right
Gray
soldering on the left
Gray
Knife disconnect terminal block with
solder connection on both sides, with test
Gray
holes
Knife disconnect terminal
block,/ x 1-WW pin on the left, screw
Gray
connection on the right
Knife disconnect t .b ., as above, however, with 2 .4 x 0 .8 TP pin
. . .L : for vertical strips
. . .Q: for horizontal strips
Cover
Insertion bridge, fully insul .,
2-pos.
fully insulated,
3-pos.
divisible, insulated spine
10-pos.
Partition plate, for visual and electrical
separation of terminal groups, 1 mm thick
t
rigid
solid
flexible
stranded
Connection data
0 .2-4
0 .2-2 .5
% SP P
Description
Knife disconnect terminal block
UK-MTK
The UK 5-MTK terminal blocks feature
A sturdy and closed housing
Low and stable contact resistances
A high dielectric strength of 500 V
A construction profile similar to the
feed-through terminal blocks, UK 3 N
through UK 16 N .
Terminal width 5.2
(IEC)
[mm2]
Gray
Blue
11
I
AWG [A]
24-12
16
U
[V
401
NV/PRS/RS
Type
Order No.
Pcs
Pkt
MTK-P/P
31 04 01 3
50
MTK
MTK BU
31 01 01 6
31 01 19 7
50
50
MTKD-P/P
MTKD
31 00 02 0
31 00 01 7
50
50
D-MTK
D-MTK BU
EBL 2-5
EBL3-5
EBL10-5
31 01 02 9
31 01 09 0
12 A 23 03 14 5
12A
2303158
12A 2303132
50
50
10
10
10
ATS-MTK
31 01 22 3
50
SZG 0,6 x 3,5
1205121
10
Screwdriver
Zack marker strip, 10-section
White
MTK. . . / UK 5-MTK-P/P / UDK 4-MTK-P!P
') Meaning of the letters "R" and "L" in
type designations:
"R" = Soldering tag on the right
"L" = Soldering tag on the left
_) Current and voltage data for slip-on connections in acc . with
EN 61 210 are also dependent on nom . size, material, and
insulation of the receptacle and conductor cross section.
Wire-Wrap:")= registered trademark of Gardner-Denver
TERMI-POINT" = trademark of AMP Incorporated
Note:
Suitable test plugs are documented
starting on page 386 .
276
Phoenix Contact
Dimensions
Width / length / cover width
[mm]
Height (NS 35/7 .5 / NS 35/15 / NS 32)
[mm]
Technical data in accordance with IEC / DIN VDE
Max. load current / cross section
[A] / [mm2 ]
Max. cross section with insertion bridge (solid/stranded)
[mm2 ]
Rated surge voltage / contamination class
[kV] / Surge voltage category / insulating material group
- /Connection capacity
Stranded with ferrule without / with plastic sleeve
[mm2 ]
Multi-conductor connection (2 cond . with same cross section)
Solid / stranded
[mm2]
Stranded with ferrules without plastic sleeve
[mm-]
Stranded with TWIN ferrule with plastic sleeve
[mm 2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Thread
Torque
[Nm]
Insulation material
Inflammability class in acc . with UL 94
Approval data (UL/CUL and CSA)
Nominal voltage ' current ,' conductor sizes
UL/CUL : [V] / [A] / AWG
CSA : [V] / [A] i AWG
ZB 5 (for order data, see page 397)
5 .2/46/1
40 / 47,5 / 44,5
16/4
4/2 .5
6/3
II/I
0.25 - 2 .5 / 0 .25 - 1 .5
0.2-1 .5/0 .2 - 1 .5
0 .25 - 1 .5
0.5 - 1 .5
7
A3
M3
0.5 - 0 .6
PA
VO
MTK. ..
300 / 10 / 28 - 12
300 / 15 / 28 - 12
MTKD ...
300 ; 10/28-12
600/20/28-12
Terminal width 6 .2
(IEC)
[mm2 ]
Connection data
UK 5-MTK-P/P
MTK-LOE
MTK-TP
with test socket screws
with screw / solder connection
with screw. WW or TP connection
rigid
solid
flexible
stranded
0 .2-4
0 .2-4
I
AWG [Al
24-12
16
U
[V]
500
Terminal width 5 .2
(IEC)
[mm 2]
rigid
solid
Connection data
0 .2-4
Solder connection
0 .2-1 .5
Slip-on conn .
2 .8 x 0.8 mm
flexible
stranded
AWG
[A]
U
[V]
0 .2-2.5
0 .2-1 .5
24-12
24-16
12
12
400
400
Terminal width 5 .2
(IEC)
[mm']
rigid
solid
Connection data
0 .2-4
WW connection) x 1
TP conn .
1 .6 x 0 .8
TP conn .
2 .4 x 0 .8
flexible
stranded
0.2-2 .5
AWG
I
[A]
U
[V]
24-12
26-20
28-22
24-20
10
10
10
250
250
125
Aus SP PRS
Type
Order No .
Pcs.
Pkt.
UK 5-MTK-PIP
30 04 03 2
50
Closed housing,
sellout cover
ED 2-6
Eli 3 .6
F310-6
Type
Order No .
Pcs.
Pkt.
MTK-LOER ') (see illustration)
MTK-LOEL ,)
31 05 01 2
31 07 01 0
50
50
MTK-LOEILOE
31 09 01 8
50
D-MTK
D-MTK BU
L,-, : 12 A
12 A
12 A
31 01 02 9
31 01 09 0
50
50
Type
Order No .
Pcs.
Pkt .
MTK-WW (1 x 1) 1
31 1011 7
50
MTK-TP (2,4 x 0,8) 1 L
MTK-TP (2,4 x 0,8) 10
31 10 41 8
31 10 51 5
50
50
D-MTK
D-MTK BU
EBL 2-5
EBL 3-5
EBL 10-5
31
31
23
23
23
01 02 9
01 09 0
03 14 5
03 15 8
03 13 2
50
50
10
10
10
l 31 01 22 3
50
12 05 12 1
10
02 01 15 5
02 01 14 2
02 01 13 9
100
100
10
ATP-UK 5-MTK
2mm thick
30 04 21 0
50
ATS-MTK
31 01 22 3
50
ATS-MTK
SZG 0,6 x 3,5
12 05 12 1
10
SZG O,6 x 3 .5
12 05 12 1
10
SZG 0,6 x 3,5
2B6 (tor order data, see page 397)
6.2/51/—
47/54,5/52
1,, ,,, : 11 A
11 A
11 A
ZB 5 (for order data, see page 397)
ZB 5 (for order data, see page 397)
MTK-LOE. . . // MTK-LOEILOE
5 .2/57 .5/1//5 .2!6911
51 .5/59/56
5.2/46/1
67/74 .5/72
16/4
4/4
6/3
III/I
12/4
—
6/3
III/I
10/4
4/4
4/3
III/I
0 .25 - 4 / 0.25 - 2 .5
0 .25-2 .5/ 0 .25 - 2.5
0 .25-2 .5/0 .25- 2 .5
0.2 - 1 .5 / 0 .2 - 1 .5
0 .25 - 1 .5
0 .5 - 2 .5
8
A4
M3
0 .5 - 0 .6
PA
VO
600/15/22-12
600/15/18-10
0 .2-1 .5/0 .2
025-1
0.5-1 .5
7
A3
M3
0.5-0 .6
PA
VO
1 .5
0.2-1 .5/0 .2-1 .5
0.25-1
0 .5-1 .5
7
A3
M3
0 .5-0 .6
PA
VO
300/10/28-12
Phoenix Contact
277
Double and double-level
terminal blocks with
disconnect knife
o
-
O
Circuit diagram . UDMTK 5-P/P
UDK 4-MTK-P/P
V
0—ja
1
Terminal width 6 .2
(IEC)
[mm 2 ]
rigid
solid
flexible
stranded
Connection data
0 .2-6
0.2-4
I
AWG [A]
UKK 5-MTK-P/P
U
[V]
24-10 16 6301
Terminal width 6 .2
(IEC)
[mm']
rigid
solid
flexible
stranded
I
AWG [A]
U
[V .
Connection data
upper level
lower level
0 .2-4
0 .2-4
0 .2-4
0 .2-4
24-12
12
24-12 26
40i
40!
Circuit diagram : UDMTK 5-TWIN-P/P
c~us
Description
Knife disconnect terminal block, for
mounting on v or u, with test
socket screws
Knife disconnect terminal block, as
above, however, bridgeable in both
levels
Double-level terminal block, for
mounting on v or Lr, with
disconnect knife and light indicator
Double-level terminal block, as
above, however, with two through
contacts, without light indicator
Cover
LED
voltage
[V DC]
Current
[mA]
Gray
Blue
SP Kill
B
RS/PRS
c%us
Type
Order No.
Pcs.
Pkt .
UDK 4-MTK-P/P
UDK 4-MTK-P/P BU
27 75 21 0
27 75 22 3
50
50
e' B r'
8V/FRS/RS
Type
Order No.
Pcs
Pkt
UKK 5-MTK-P/P
28 00 00 4
50
UKK 5-MTK-P/P-LA 24 RD/O-U
UKK 5-MTK-P/P-LA 48 RD/O-U
UKK 5-MTK-P/P-LA 60 RD/O-U
28 00 02 0
28 00 03 3
28 00 04 6
Sri
50
50
UKK 5-MTKD-P/P
28 00 01 7
50
1,,, : 22 A
02 03 25 0
10
18 A
03 01 50 5
10
IS-K 4
13 02 33 8
too
SZG0,6x3,5
1205121
10
Gray
24
48
60
6,0
5,7
5,5
Gray
Gray
Blue
Fixed bridge, for cross connections in the
terminal center, screw heads with insulating
collar, 10-position, divisible, with 10 screws
Insertion bridge, fully insul ..
2-pos.
fully insulated,
3-pos.
divisible, insulated spine
10-pos.
Isolator bridge bar, 10-position, divisible, with 10
screws, for switchable branches with
Bridge bar IS-K 4 as distance piece
Partition plate. for visual and electrical
separation of terminal groups.. 2 mm thick
27 75 11 3
27 75 19 7
D-UDK 4
D-UDK 4 BU
50
50
Closed housing,
without cover
FBI 10-6
EB 2-6
EB 3-6
EB 10-6
. 12 A 02 01 15 5
12 A 02 01 14 2
12 A 02 01 13 9
100
100
10
ISSBI 10-6
J
"
`
~___—rr,-nycra
Screwdriver
1205053
SZS 0,6 x 3,5
10
Zack marker strip, 10-section
White
ZB 6 (for order data, see page 397)
Dimensions
Width / length / cover width
[mm]
Height (NS 35%7.5 / NS 35/15 / NS 32)
[mm]
Technical data in accordance with IEC / DIN VDE
[A]/[mm']
May . load current ; cross section
Max . cross section with insertion bridge (solid/stranded)
[mm2]
Rated surge voltage / contamination class
[kV] / Surge voltage category i insulating material group
-/Connection capacity
Stranded with ferrule without / with plastic sleeve
[mm-]
Multi-conductor connection (2 cond . with same cross section)
Solidi stranded
[mm•]
[mm']
Stranded with ferrules without plastic sleeve
Stranded with TWIN ferrule with plastic sleeve
[mm2 ]
Stripping length
[mm)
Internal cylindrical gauge (IEC 60 947-1)
Thread
Torque
[Nm]
Insulation material
Inflammability class in a= with UL 94
Approval data (UUCUL and CSA)
Nominal voltage ! current / conductor sizes
UUCUL
. [V] / [Al / AWG
UUCUL : [V] / [A] / AWG
CSA : [V] / [A] / AWG
Suitable test plugs are documented
starting on page 386.
278 Phoenix Contact
6 .2 / 63 .5/ 1 .5
47/54 .5152
16/6
2 .5/2 .5
8/3
III /
') upper level
-) lower level
ZB 6 (for order data, see page 397)
6 .2/80/68/76/73
UKK 5-MTK .. . // UKK 5-MTKD ...
26(12')) / 4// 26 / 4)
6/3
III/I
0 .25 - 4 / 0 .25 - 1 .5
0 .25 - 4 / 0 .25 - 2.5
0 .2-1/0 .2-1 .5
025-1 .5
0 .5-1
8
A4
M3
0.6 - 0 .8
PA
V2
0 .2 - 1 .5 / 0.2 - 1 .5
0 .25 - 1 .5
0.5 - 2.5
8
A3 (A 4 1 )) // A4
M3
0.6 - 0 .8
PA
V2
600/15/30-10
600/10/22-10
300/15/22-10
300/15')250/26-12
300/15/22-12
UDMTK 5-TWIN-P/P
UDMTK 5-P/P
Disconnect knife for each level
Disconnect knife for each level
Terminal width
(IEC)
[mm2]
2
UDMTKB 5-P/P
Disconnect knife for each level
Terminal width 6 .2
(IEC)
[mm 2]
rigid
solid
flexible
stranded
AWG
I
[A]
Connection data
24-12 8-)
400
upper level
0 .2-4
0 .2-4
24-12 81
400
lower level
0 .2-4
0 .2-4
s) The current supply from the system can take max . 16 A.
The current carrying capacity of the branches is max . 8 A each .
Connection data
upper level
lower level
0 .2-4
0 .2-4
0 .2-4
0 .2-4
24-12
24-12
10
10
Mus SP
c~us SB P
rigid
solid
flexible
stranded
AWG
I
[A]
U
[V]
Type
Order No.
Pct.
Pkt.
UDMTK 5-TWIN-PIP
UDMTK 5-TWIN-PIP BU
31 01 12 6
31 01 13 9
50
50
ed housing,
out cover
U
[V]
Terminal width 6 .2
(IEC)
[mm 2 ]
rigid
solid
flexible
stranded
AWG
I
[Al
U
[V]
400
400
Connection data
upper level
lower level
0 .2-4
0 .2-4
0 .2-4
0 .2-4
24-12
24-12
10
10
400
400
c%us
Type
Order No.
Pcs.
Pkt.
UDMTK 5-PIP
UDMTK 5-PIP BU
31 01 08 7
31 01 11 3
50
50
Type
Order No .
Pcs.
Pkt.
UDMTKB 5-P/P
30 24 47 8
50
10 A
02 03 25 0
10
1,,,e, .: 10 A
Closed housing.
without cover
Closed housing,
without cover
FBI 10-6
03 01 50 5
10
IS-K 4
13 02 33 8
100
SZG 0,6 x 3,5
12 05 12 1
10
ISSBI 10-6
TP-UDMTK 5-TWIN
31 00 24 0
10
TP-UDMTK 5
31 00 26 6
10
MG 0,6 x 3,5
12 05 12 1
10
SZG 0,6 x 3,5
12 05 12 1
10
ZB 6 (for order data . see page 397)
E
L
IId
ZB 6 (for order data, see page 397)
ZB 6 (for order data . see page 397)
6.2/76.5/68 .5/76/73
6 .2/93/68 .5176/73
6 .2/106/68 .5/76/73
8/4
10/4
10/4
4/ 3
III/I
4/ 3
III/ I
4/ 3
III/I
0 .25-4/0 .25-2 .5
0 .25-4!0.25 - 2 .5
0 .25 - 4 / 0.25 - 2.5
0 .2-1 .5/0 .2- 1 .5
0 .25-1 .5
0 .5 - 2 .5
8
A4
M3
06-0.8
PA
V2
0 .2 - 1 .5 / 0 .2 - 1 .5
0 .25-1 .5
0 .5 - 2 .5
8
A4
M3
0 .6-0 .8
PA
V2
0 .2-1 .510 .2-1 .5
0 .25-1 .5
0 .5 - 2 .5
8
A4
M3
0 .6 - 0 .8
PA
V2
300/8/26-12
300/8/28-12
300/15/26-12
300/15/28-12
300/15/26-12
Phoenix Contact
279
Basic terminal blocks for
cartridge fuse, component and
isolating plugs
MBK 5/E-TG
Terminal width 6.2
(IEC)
[mm2 ]
rigid
solid
flexible
stranded
I
AWG [A]
U
[V]
Connection data 0 .20-4 0 .2-4 24-12 16' 500'
The current and voltage are determined by the component and
fuse plug.
The 6 mm wide fuse or component
terminal blocks consist of basic terminal
blocks which hold fuse, component and
isolating plugs.
The basic terminal blocks are available in
the following forms:
The mini-strip terminal blocks MBK 5
The universal terminal blocks UK 5 N
The double terminal blocks UDK 4
And the double-level terminal blocks
UKK 5.
The three and four-conductor actuator
basic terminal blocks DOK 1,5-TG,
DOKD 1,5-TG and VIOK 1,5-D/TG/D/PE
are documented in the chapter " Doublelevel, three-level and four-level terminal
blocks" (see pages 244 and 246).
Basic terminal blocks with spring-cage
connection can be found on page 84.
For fuse, component and isolating plugs,
see page 282.
c%us SB PRS
Description
Type
Order No.
Pict.
Basic terminal block,
for component and fuse plugs
MBK 5/E-TG
14 15 08 9
50
D-MBK 5/E-T
14 13 70 6
50
02 01 15 5
02 01 14 2
0201139
100
10
10
12 05 05 3
10
Basic terminal block,
with test socket screws on both sides
Cover
Fixed bridge, for cross connections in the
1 ~1
V II If fI 0i J
terminal center, screw heads with insulating
collar, 10-position, divisible, with 10 screws=
2-pos.
Insertion bridge, fully insul .,
3-pos .
fully insulated .
divisible, insulated spine
10-pos. 't~~
Isolator bridge bar, 10-position, divisible, with 10
screws, for switchable branches with
Bridge bar IS-K 4 as distance piece
Partition plate, for visual and electrical
separation of terminal groups, 1 .5 mm thick
280
Phoenix Contact
1,,,,,,, .: 16 A
16 A
16A
Screwdriver
SZS O,6 x 3,5
Zack marker strip, 10-section
White
Dimensions')
[mm]
Width / length / cover width
Height (NS 35/7 .5 / NS 35/15 / NS 32 / NS 15)
[mm]
Technical data in accordance with IEC / DIN VDE
[A]/[mm]
Max . load current / cross section
[mm2]
Max . cross section with insertion bridge (solid/stranded)
Rated surge voltage / contamination class
[kV)/ Surge voltage category / insulating material group
-/Connection capacity
[mmi']
Stranded with ferrule without l with plastic sleeve
Multi-conductor connection (2 cond . with same cross section)
Solid / stranded
[mm']
Stranded with ferrules without plastic sleeve
[mm/ ]
Stranded with TWIN ferrule with plastic sleeve
[mm'[
[mm]
Stripping length
Internal cylindrical gauge (IEC 60 947-1)
Thread
Torque
[Nm[
Insulation material
Inflammability class in acc_ with UL 94
Approval data (UUCUL and CSA)
Nominal voltage current / conductor sizes UUCUL : [V] / [A] / AWG
UUCUL: [V] / [A] / AWG
UUCUL: [V] / [A] / AWG
CSA: [V] / [A] / AWG
UK 4-TG with isolating plug ST-K 4.
EB 2-6
EB 3-6
EB10-6
Note:
Suitable test plugs are documented
starting on page 386 .
6 .2 / 28 / 1
-/-/-/36
16/4
1 .5/1 .5
6/3
III/I
0 .25 - 2 .5 / 0 .25 - 2.5
0 .2 - 1 .5 / 0 .2 - 1 .5
0 .25 - 1 .5
0 .5 - 1 .5
9
A3
M3
0 .6 - 0 .8
PA
V2
150/20/28-12
300/10/28-12
300/15/28-12
') Dimensions without plug
.
I,
illik_
"4
11W.
7:7
UK 4-TG
Terminal width 6 .2
(IEC)
(nwn2]
rigid
solid
flexible
stranded
UDK 4-TG
I
AWG [A]
U
[V]
Terminal width 6 .2
(IEC)
[mm 2 ]
rigid
solid
flexible
stranded
UKK 5-TG
I
AWG [A]
U
[V]
Connection
data
0 .20-4
0.2-4
24-12 16'
5
C
onnection
00
data
'
0.20-6
0 .2-4
24-10 16" 400"
'The current and voltage are determined by the component and
' The current and voltage are determined by the component and
fuse plug .
fuse plug.
raw 6P ABS
cStlus PRS
Type
Order No.
Pcs.
Pkt.
UK 4-TG
28 12 01 8
50
UK 4-TG-P/P
28 12 03 4
50
DUK 4/10
30 03 02 0
50
16A
16A
16A
0-6
0201155
0201142
0201139
100
100
10
ATP-UK
3003224
50
SZS 0,6 x 3,5
1205053
10
Zg 6 (for order data, see page 397)
with ST-T plug
'with ST-BE plug
'with ST-SI-UK 4 plug
Terminal width 6.2
(IEC)
[mm2]
Type
Order No .
UDK 4-TG
27 77 01 4
50
D-UDK RELG
27 77 02 7
I,,,,, .: 16 A
0203250
50
EB 2-6
EB3-6
EB 10-6
I,,,,, : 16 A
16A
16 A
02 01 15 5
0201142
02 01 13 9
100
100
10
1205053
ZB 6 (for order data, see page 397)
I
AWG [A]
U
[V)
e'
PRS
Type
Order No .
Pcs.
Pkt.
UKK 5-TG
30 07 04 2
50
Closed housing,
without cover
FBI 10-6
SZS 0,6 x 3,5
flexible
stranded
Connection data
upper level
0 .2-4
0.2-4
24-12 16'
400 '
lower level
0 .2-4
0.2-4
24-12 26
400
' The current and voltage are determined by the component and
fuse plug.
c%us
Pcs.
Pkt .
rigid
solid
10
FBI 10-6
I,,
26 A
02 03 25 0
50
EB2-6
EB 3-6
EB 10-6
ISSBI 10-6
22A
0201155
22 A
02 01 14 2
22 A , 0201139
I,,,a, : 26 A
03 01 50 5
100
100
10
10
IS-K 4
1302338
100
SZG 0,6 x 3,5
1205121
10
Phoenix Contact
281
ZB 6 (for order data, see page 397)
6 .2 / 42 .5 / 1 .8
47/54 .5/52/-
6 .2 / 63 .5 / 1 .5
47/54 .5/52/-
6 .2/80/–
68 .5/76/73/-
16/4
1 .5/1 .5
6/3
III / I
16/6
2.5/2 .5
6/3
III / I
26/4//16/4')
4/4
6/3
III /I
0.25-2 .5/0 .25-2 .5
0 .25-4/0 .25-1 .5
0 .25-4/0 .25-2 .5
0.2 - 1 .5 / 0 .2 - 1 .5
0 .25 - 1 .5
0.5 - 1 .5
9
A3
M3
0 .6 - 0 .8
PA
V2
0.2-1/0 .2-1 .5
025-1 .5
0.5-1
8
A4
M3
0 .6 - 0 .8
PA
V2
0 .2-1 .5/0.2-1 .5
0 .25 - 1 .5
0 .5 - 2 .5
B
A3 2) I A4')
M3
0 .6 - 0.8
PA
V2
600/20/28-12 2 )
600/5/28-12 1)
300/6,3/28-12 2)
600/15/28-12
300/15/30-12
300/15/26-122)
300/15/30-12
300/25/26-121
300/15/28-12
=) upper level
lower level
Fuse, component and isolating
plugs
ST BE
ST-SI-UK 4
c91~us
Description
LED
voltage
[V AC/DC]
Current
[mA]
Fuse plug, for cartridge fuse inserts 5 x 20 mm,
26.5 mm high, color : Black
Type
ii
ST-SI-UK 4
Fuse plug n ), as above, however
with light indicator:
5 - 15
15-30
30-60
110-250
Component plug, for connecting components
with two positions to the basic terminal block.
19 mm high, color : Gray
Component plug, for connecting
components with two positions to the basic
Lb., 19 mm high, with light indicator
Component plug=), as above . however, with
universal diode 1N 4007
callus
SB ABS
2 .0 - 7 .5
3 .5-7 .5
2 .5-5 .5
0 .5-1
ST-SILED 12-UK 4
ST-SILED 24-UK 4
ST-SILED 60-UK 4
ST-SILA 250-UK 4
6 .3 A')')
l,, : 6.3 A')')
6.3 A l )')
6.3 A')')
6 .3 A')2)
Order No.
Pcs.
PkI .
09 21 01 1
50
09 21 02 4 i
0921037
09 21 04 0
09 21 05 3
50
50
50
50
for 24 V DC
for 230 V AC/DC
PA
V2
The ST-SI-UK 4 fuse plugs for 5 x 20 mm
cartridge fuse inserts are available with or
without light indicator. The version with
light indicator includes light diodes connected
back-to-back as well as preresistors for the
three voltage levels up to 60 V and glow
lamp with preresistors for the voltage level
above 110 V. The plug housing is flapped
open at the side to change the fuse.
The component plugs, ST-BE are
available as single plugs for 2-position
components and as double plugs (fourposition plugs) with or without inserted
components.
The component itself is inserted from
above and reliably clamped.
Phoenix Contact
ST-1N4007 .1 )
28 02 32 9
ST-BE-VP')
28 02 33 2
ST-B 250C1500
28 02 34 5
I mo , ,: 16 A
300/6 .3/
300 / 10 / –
I ) With single arrangements .
-) Max . power dissipation, see table on page 271 .
^) I f the fuse is defective, the downstream circuit is not off load .
ST-K 4 :
ST-K 4 :
R
P
28 02 31 6
28 02 37 4
28 02 38 7
50 25 46 2
0306704
TZ
_
UUCUL : [V] / [A] / AWG
CSA : [V] / [A] / AWG
16 A l)
ST-BE-LA 24
ST-BE-LA 230
ST-K 4
Isolating plug, 13.5 mm high
282
I ca, :
ST-BE
Component plug,`), for components with four
positions, two basic terminal blocks are
necessary per plug . 19 mm high, color : Gray
Component plug, as above, however, with bridge
rectifier B 250 C 1500
Plug pliers, simplify removing the
isolating plug from a closed row of
terminal blocks
Insulation material
Inflammability class in acc . with UL 94
Approval data (UL/CUL and CSA)
Nominal voltage current conductor sizes
Order No .
Type
PA
V2
ST-BE :
ST-BE:
300/10/ 30-14
300 / 10 / 30-14
Technical data of the component plugs:
ST-1N 4007
ST-B 250 C 1500
Diode 1 N 4007
Rectifier : B 250 C 1500
Reverse voltage : 1300 V
Reverse voltage : 600 V
Max . continuous current : 0 .5 A Nominal voltage : 250 V
Nominal current : 1 .5 A
PA
VC
Component plug, BES 6
BES 6
The special advantage of this component
plug is that any components with two
positions, such as diodes, varistors, etc . can
be inserted at a later time between two
neighboring standard feed-through terminal
blocks.
The BES 6 is supplied as a set with two
sockets . The sockets are screwed into the
center thread of the feed-through terminal
blocks . They are different lengths, and this
determines the correct functional direction
corresponding to the vertically offset
multiple-spring wire plugs and prevents
later confusion . If several BES 6 plugs are
ed next to each other, separating plates
uld be provided between the pairs of
terminal blocks in order to prevent
incorrect plugging.
To insert the components, the upper
half of the housing is lifted, thus exposing
the plug pins for soldering.
The BES 6 is also available with a
IN 4007 diode fitted for the protection
circuit of DC consumers with nominal
operating data up to 1300 V and 0 .5 A . In
addition, the BES 6 is available with a light
indicator for voltages of 15-30 V DC and
110-250 VAC.
Diode 1 N 4007
Reverse voltage : 1300 V
Maximum continuous current: 0 .5 A
Dimensions, see below
LED
voltage
Current
[VI
[mild
Component plug, complete, for connection of components
between two neighboring feed-through terminal blocks
Description
Type
Order No.
Pcs.
Pkt.
BES 6
28 02 54 9
10
BES 6-1 N4007
2802552
10
Component plug, as above, however with diode 1 N 4007
Component plug . with light
indicator
15- 30 DC
2 .5 - 7 .5
BES 6-LA 24
28 02 56 5
10
Component plug, with light
indicator
110 - 250 AC/DC
0 .5 - 1
BES 6-LA 230
28 02 57 8
10
Insulation material
Inflammability class in acc . with UL 94
PA
V2
2 II
Data of the components to be soldered in
+
Length including connection wires
Width or diameter
Diameter of the connection wires
Max . power dissipation at 25'C
10 mm
6 mm
1 .3 mm
1W
Height dimensions a with BES 6 inserted:
Type
Page
Dim . a [mm]
7
0
N
o
Damping diode with feed-through terminal blocks and BES 6
MBK 5
MBK 5/E-Z
UK 5 N
UKB 4
UKK 5
UKK 5
UVKB 4
315
309
211
340
239
239
340
64
68
75
75
92
92
76
DIN rail
NS 15
NS 15
NS 35/7 .5
NS 35/7 .5
NS 35/7,5
NS 35/7 .5
NS 35/7,5
Construction : BES 6
Phoenix Contact
283
Component terminal blocks
MBKKB 2,5-DIO
with integrated diodes
.) Data is based on the dielectric strength of adjacent terminal
Terminal width 5 .2
(IEC)
[mm u ]
rigid
solid
flexible
stranded
AWG
I
[A]
U
[V)
Connection data
0 .2-4
0.2-2.5
24-12
24
500 1)
Integrated : Diode 1 N 4007
Reverse voltage : 1300 V
Maximum cont . current : 0.5 A
blocks or the DIN rail.
0 ••O
0 ••0
0
0
. ..
0
DIO/0-U
• 0
. . . DIO/U-0
If
1J
~O
Type
Order No.
Po.
Pkt
Terminal block, with integrated 1 N 4007 diode.
conducting from top to bottom
MBKKB 2,5-DIO/O-U
2800567
50
Terminal block, with integrated 1N 4007 diode,
conducting from bottom to top
MBKKB 2,5-DIO/U-O
28 00 57 0
50
MBKKB 2,5.2DIO/O-UUO-UR
3003871
50
D-MBKKB 2,5
14 13 05 2
DP-MBKKB 2,5
14 13 06 5
Terminal block, with integrated 1 N 4007 diode,
conducting from bottom left to bottom right
Terminal block, with two integrated 1N 4007 diodes,
conducting from top to bottom left and from top to bottom right
or from bottom right to bottom left
Terminal block, for soldering in a component
from top to bottom
Terminal block, for soldering in a component from top
to bottom left and from bottom right to bottom left
0•-0
\
j"
v
Cover
Spacer cover, compensates for level offset if
standard terminal blocks are aligned
tJ
O
.. . DIO/UL-UR
0
- ~-• p
.. . 2 D1010-UUUR-UL
0
-0
0—
.. . 2 D101O-UUO-UR
0 .110
.
/--
0
UKK 5-BE or
MBKKB 2,5-BE
284
Description
Phoenix Contact
110 —6
•-
UKK 5-2 BE
Spacer plate, compensates for level offset if
standard terminal blocks are to be fitted
adjacently, 2 .5 mm thick
Fixed bridge, for cross connections in
the terminal center, with permanently
crimped rolls, screw heads with
insulating collar as shock protection
2-pos.
3-pos.
4-pos.
10-pos.
FBRNI 2-5 N
FBRNI 3-5 N
FBRNI 4-5 N
FBRNI 10-5 N
I m „ : 22 A
22 A
22 A
22 A
Screwdriver
SZS O,6 x 3,5
Zack marker strip, 10-section, white
Dimensions
[mm]
Width r length / cover width
)mm]
Height (NS 35,7 .5/NS 35/15 / NS 32)
Technical data in accordance with !EC/DIN VDE
Max . load current / cross section
[A]/[mm')
[kV] I Rated surge voltage / contamination class
-/Surge voltage category / insulating material group
Connection capacity
Stranded with ferrule without I with plastic sleeve
[mm , ]
Multi-conductor connection (2 cond . with same cross section)
[mm-]
Solid / stranded
[mm']
Stranded with ferrules without plastic sleeve
Stranded with TWIN ferrule with plastic sleeve
[mm ,]
[mm]
Stripping length
Internal cylindrical gauge (IEC 60 947-1)
Thread
[Nm]
Torque
Insulation material
Inflammability class in acc . with UL 94
Approval data (UUCUL and CSA)
UUCUL : [V] / [A] / AWG
Nominal voltage current / conductor sizes
CSA : [V) I [A] / AWG
ZB 5 (for order data . see page 397)
5.2 / 62 / 2 .5
48/55 .5/-147 .5
26 / 2 .5
6/3
11111
0 .25 - 2 .5 / 0 .25 - 2 .5
0 .2-1/0 .2-1 .5
025-1S
0 .5- 1 .5
7
A3
M3
OS-OS
PA
V2
30 00 17 5
30 00 16 2
30 00 15 9
27 70 63 9
10
10
10
10
12 05 05 3
10
MBKKB 2,5-BE
UKK 5-DIO
UKK 5-BE
with integrated diodes
Terminal width 5.2
(IEC)
[mm=]
rigid
solid
flexible
stranded
I
AWG [A]
U
[V]
Connection data
0 .2-4
0 .2-2 .5
24-12 24
500')
Maximum width of components to be soldered i n : 4 mm
Terminal width 6 .2
(IEC)
[mm']
rigid
solid
flexible
stranded
Connection data
0 .2-4
0 .2-4
I‘IKKB 2,5-BE
1414103
D-MBKKB 2,5
14 13 05 2
DP-MBKKB 2,5
FBRNI 2-5 N
FBRNI 3-5 N
FBRNI 4-5 N
FBRNI 10-5 N
22 A
22 A
22 A
22 A
SZS 0,6 x 3,5
Z85 (for order data, see page 397)
1
24-12
32
U
[V]
500')
Integrated : Diode 1 N 4007
Reverse voltage : 1300 V
Maximum cont . current : 0.5 A
c~us B
Order No .
I
AWG [A]
Pcs.
Pkt.
rigid
solid
flexible
stranded
I
AWG [A]
U
[V]
Connection data
0 .2-4
0.2-4
24-12 32
500 ' )
Maximum installation width of components to be soldered in . 5 mm
NV
Type
Order No.
Pcs.
PkI.
UKK 5-DIO/O-U
27 91 01 6
50
UKK 5-DIO/U-O
27 91 03 2
50
UKK 5-DIO/UL-UR
27 91 02 9
50
UKK 5-2 DIO/O-UUUR-UL
27 91 11 3
50
50
50
Terminal width 6 .2
(IEC)
[mm', ]
Type
Order No .
Pcs.
Pkt.
UKK 5-BE
30 48 02 7
50
UKK 5-2 BE
30 48 03 0
50
D-UKK 3/5
27 70 02 4
50
D-UKK 3/5
27 70 02 4
50
DG-UKK 3/5
27 70 81 7
50
DG-UKK 3/5
27 70 81 7
50
27 70 79 4
50
DP-UKK 3/5
27 70 79 4
50
0203250
10
FBI 10-6
0203250
10
1205053
10
SZS 0,6 x 3,5
1205053
10
14 13 06 5
50
DP-UKK 3/5
3000175
3000162
3000159
27 70 63 9
10
10
10
10
FBI 10-6
12 05 05 3
10
SZS 0 .6 x 3,5
I m„ : 32 A
ZB 6 for order data . see page 397)
32 A
ZB 6 (for order data, see page 397)
5 .2/62/2 .5
48/55 .51-/47 .5
6.2 / 56 / 2 .5
62/69 .5/67/-
6 .2/56/2 .5
62/69-5/67/
26 / 2 .5
6/3
1II/1
32/4
6/3
III / I
32/4
6/3
111 11
0 .25 - 2.5 / 0.25 - 2 .5
0 .25 - 4 / 0 .25 - 2 .5
0 .25-4!0 .25-2 .5
0.2-1/0 .2-1 .5
025-1 .5
0 .5-1 .5
7
A3
M3
0 .6-0.8
PA
V2
0 .2-1 .5/0 .2- 1 .5
0 .25 - 1 .5
0 .5 - 1 .5
8
A4
M3
0 .6 - 0 .8
PA
VO
0 .2-1 .5/0 .2-1 .5
0.25 - 1 .5
0 .5 - 1 .5
8
A4
M3
0 .6 - 0 .8
PA
VO
600/30/26-10
Phoenix Contact
285
Component terminal blocks
The constant current circuits common
in process automation transmit the
measured values as a load-independent
current of 0(4) - 20 mA . A voltage signal
pick-off can be implemented in the
measuring conductor using the UDK 4-DUR
terminal block, thus allowing the signal to be
used as an analog signal for process
computers . The four-conductor connection
makes for convenient wiring . The lower
level is assigned to the measuring line and
the upper level is used for the voltage pickoff via the 249 S2 resistor.
The integrated light indicator in
UKK 5-LA indicates the voltage condition
of the lower feed-through level .
UDK 4-DUR
UKK 5-LA
with differential voltage resistor
with light indicator
Terminal width 6 .2
(IEC)
rigid
flexible
solid
stranded
AWG [A]
[mm 2 ]
)
Connection data
0 .2-6
0.2-4
24-10
') The current is determined by the component used .
U
[V]
630
Terminal width 6 .2
(IEC)
[mm z]
rigid
solid
flexible
stranded
I
AWG [A]
U
[V]
Connection data
0 .2-4
0 .2-4
24-12 32 5001
2) Data is based on the dielectric strength of adjacent terminal
blocks or of the DIN rail.
Maximum installation width of components to be soldered in : 5 mm
Description
LED
voltage
[V AC/DC]
Current
[mA]
Differential voltage terminal block,
a) for self-soldering a resistor
b) with fitted resistor 249 Sal_ 1%/1 W
Double-level terminal block,
15 - 30 DC
30 - 60 DC
with light indicator
110 - 230 AC/DC
Type
Order No .
Pcs.
Pkt .
a) UDK 4-DUR
b) UDK 4-DUR 249
27 75 20 7
27 75 24 9
50
50
2.5-7.5
1 .9-4.0
0.5-1 .0
27 75 11 3
D-UDK 4
Cover
Spacer cover, compensates for level offset if
standard terminal blocks are aligned in rows,
2.5 mm thick
Spacer plate, compensates for level offset if
standard terminal blocks are to be fitted
adjacently, 2 .5 mm thick
Fixed bridge, for cross connections in the
terminal center, screw heads with insulating
DO'COMoam
collar, 10-position, divisible, with 10 screws
2-pos . ,
Insertion bridge, fully insul .,
fully insulated,
3-pos.
10-pos.
divisible, insulated spine
Isolator bridge bar, 10-position, divisible, with 10
screws, for switchable branches with
Bridge bar IS-K 4 as distance piece
Separating plate, for electrical separation of neighboring
bridges, can be fitted later, no loss of pitch
mlvnlm
El
FBI 10-6
50
Zack marker strip, 10-section
White
Dimensions
Width / length / cover width
[mm]
[mm]
Height (NS 3525 / NS 35/15 / NS 32)
Technical data in accordance with IEC / DIN VDE
[A]/[mm2]
Max . load current / cross section
[mm%]
Max . cross section with insertion bridge (solid/stranded)
[kV] / Rated surge voltage / contamination class
Surge voltage category / insulating material group
-/Connection capacity
Stranded with ferrule without / with plastic sleeve
[mm2]
Multi-conductor connection (2 cond . with same cross section)
[mm-']
Solid / stranded
[mm2']
Stranded with ferrules without plastic sleeve
Stranded with TWIN ferrule with plastic sleeve
[mm2]
[mm]
Stripping length
Internal cylindrical gauge (IEC 60 947-1)
Thread
[Nm[
Torque
Insulation material
Inflammability class in acc . with UL 94
Approval data (UUCUL and CSA)
UUCUL [V] / [A] / AWG
Nominal voltage / current ! conductor sizes
CSA : [V] / [Al / AWG
286
Phoenix Contact
ZB 6 (for order data, see page 397)
27 70 02 4
50
DG-UKK 3/5
27 70 81 7
50
DP-UKK 3/5
2770794
50141
l,,,,27 A
27 A
27 A
Imp , : 24 A
0201155
02 01 14 2
0201139
03 01 50 5
100
100
10
10
100
IS-K 4
13 02 33 8
100
TS-KK 3
27 70 21 5
50
ATP-UKK 3/5
27 78 52 1
50
SZS0,6x3,5
1205053
to
50
Partition plate, for visual and electrical
separation of terminal groups, 2 .5 mm thick
12 05 05 3
D-UKK 3/5
EB 2-6
EB 3-6
EB 10-6
ISSBI 10-6
13 02 33 8
SZS 0,6 x 3,5
50
50
50
100
100
10
10
02 01 15 5
02 01 14 2
0201139
03 01 50 5
Screwdriver
27 91 32 0
27 91 33 3
27 91 35 9
10
26 A
26 A
26A
32 A
27 70 21 5
UKK 5-LA 24 RD/U-0
UKK 5-LA 60 RD/U-0
UKK 5-LA 230
02 03 25 0
10
TS-KK 3
Pte'
Pkt.
I,,,,,, : 32 A
02 03 25 0
IS-K 4
Order No.
FBI 10-6
Imo, ; 32 A
EB 2-6
EB 3-6
EB 10-6
ISSBI 10-6
Type
10
ZB 6 (for order data, see page 397)
6 .2 / 63.5 / 1 .5
47 / 54.5 / 52
6 .2 / 56 / 2 .5
62 / 69 .5 / 67
1)/6
2 .5/2.5
6/3
III / I
32/4
4/2.5
6/3
II/I
0 .25-4/0 .25 - 1 .5
0 .25 - 4 / 0 .25 - 2 .5
0.2-1/0 .2-1 .5
0.25-1 .5
0 .5-1
8
A4
M3
0.6-0 .8
PA
V2
0.2-1/0 .2-1 .5
0 .25 - 1 .5
0 .5 - 1 .5
8
A4
M3
0 .6 - 0 .8
PA
VO
600/10/22-10
600/20/26-10
600/20/26-10
Thermoelectric voltage
terminal block pair, MTKD- . ..
MTKD- . ..
Terminal width 10 .4
(IEC)
[mm ,]
AU=O
In thermocouple measurement circuits,
the thermocouple is extended by using
equalizers . This is the area of application of
these special terminal blocks.
The equalizers are made of materials
which, up to temperatures of approximately
200°C, have the same thermal characteristics
as the corresponding thermocouples.
The through contacts in these MTKD
thermoelectric voltage terminal blocks are
made of the same material as the equalizers
in acc . with DIN 43 713 and DIN 43 714.
This ensures that no false thermoelectric
tages result at the connection points of
thermocouple/terminal block/equalizer
and that the basic values according to
EN 60 584/DIN EN 60 584 are observed.
The thermoelectric voltage terminal
block pair is clearly marked with the
compensating material used.
rigid
flexible
solid
stranded
AWG
Connection data
0 .2-4
0 .2-2 .5
24-12
* Voltage to the neighboring feed-through terminal MTK.
U
[V]
400'
C% US
Type
Order No .
Pcs.
Pkt.
MTKD-CU/CUNI
31 00 05 9
50
MTKD-FE/CUNI
31 00 04 6
50
MTKD-NICR/CUNI
31 00 07 5
50
MTKD-NICRSIINISI
50 43 32 1
50
MTKD-NICR/NI
31 00 06 2
50
MTKD-E-CU/A-CU
31 00 09 1
50
MTKD-S-CUIE-CU
31 00101
50
Cover
D-MTK
31 01 02 9
50
Partition plate, for visual and electrical
separation of terminal groups, 1 mm thick
ATS-MTK
31 01 22 3
SO
SZS 1,0 x 4,0
1205066
10
Phoenix Contact
287
Description
USA-type
Thermoelectric voltage terminal block pair for
CU/CUNI44
copper/ constantan
Thermoelectric voltage terminal block pair for
FE/CUNI44
iron/constantan
Thermoelectric voltage terminal block pair for
NICR/CUNI44
nickel-chrome/constantan
Thermoelectric voltage terminal block pair for
NICRSI/NISI
nickel-chrome silicone/nickel-silicone
Thermoelectric voltage terminal block pair for NICR/NI
nickel-chrome/nickel
Thermoelectric voltage terminal block pair for
E-CU/A-CU
copper/copper nickel
Thermoelectric voltage terminal block pair for
S-C WE-CU
S-copper/copper
Screwdriver
Zack marker strip, 10-section
White
Dimensions
Width / length / end cover width
[mm]
Height (NS 35/7 .5 / NS 35/15 / NS 32)
[mm]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Thread
Torque
[Nm]
Insulation material
Inflammability class in acc . with UL 94
Approval data (UL/CUL and CSA)
Nom . voltage / nom . current / conduc .
UL/CUL . [V] [A] / AWG
ZB 10 (for order data, see page 399)
5 .2 / 46 / 1
40/47 .5/45
7
A3
M3
0 .6 - 0 .8
PA
VO
300/10/28-12
Table for selecting thermoelectric
voltage terminal blocks
rmocouple material
er+'constantan (Cu/CuNi44)
constantan (Fe/CuNi44)
Nckel-chrome/constantan (NiCr/CuNi44)
Ildtel-chrome/nickel (NiCr/Ni)
Platinum-rhodium/platinum(PIPh/Pt)
Iblinum, 13% rhodium/platinum
Platinum, 30% rhodium/platinum, 6% rhodium
Equalizer material
Copper/constantan (Cu/CuNi44)
Iron/constantan (Fe/CuNi44)
Nickel-chrome/constantan (NiCr/CuNi44)
Nickel-chrome/nickel (NiCr/Ni)
Copper/copper-nickel (E-Cu/A-Cu)
Copper/copper-nickel (E-Cu/A-Cu)
S-copper/copper (S-Cu!E-Cu)
Thermoelectric terminal block pair
MTKD-CU/CUNI
MTKD-FE/CUNI
MTKD-NICR/CUNI
MTKD-NICR/NI
MTKD-E-CU/A-CU
MTKD-E-CU/A-CU
MTKD-S-CU/E-CU
Light indicator terminal blocks
for voltage and current
Load current diagram of the current
indicator terminal block, UDK 4-ILA
Terminal current is dependent on the ambient temperature
Duty cycle : 100
UDK 4-ULA
UDK 4-ILA
with voltage indicator
Terminal width 6 .2
(IEC)
[mm 2 ]
0,25
IIUUUU1iI011U11
UDK 4-ILA 500
::.
30
40
50
60
70
flexible
stranded
I
AWG [A]
U
[V]
Connection data
0 .2-6
0.2-4
24-10 32') 500-)
') The rated current must not be exceeded by the total current of all
connected conductors.
-') To neighboring terminal blocks.
0
20
rigid
solid
with current indicator
80
Terminal width 6 .2
(IEC)
[mm 2 ]
rigid
solid
flexible
stranded
Connection data
UDK 4-ILA 500
0 .2-6
UDK 4-ILA 1000
0 .2-6
'I To neighboring terminal blocks.
-) Observe load current diagram.
0 .2-4
0 .2-4
I
AWG [A]
U
[V]
24-10 0 .5'1 500',
24-10 1 .0'1 5001
Ambient temperature ['C]
mu,
LED
Description
voltage
[V AC/DC]
Voltage indicator terminal
15 - 30 DC
block, gray with universal foot
30 - 60 DC
for mounting on V or u
110 - 230 AC/DC
Power terminal block, blue, to connect the reference
potential to return busbar RS, I,,,a, = 2 A
Current
[mA]
2 .5 - 7 .5
1 .9 - 4.0
0 .5 - 1 .0
IKL-
01us SP KE "u
Type
Order No .
Pcs.
Pkt.
UDK 4-ULA 24 RDIO-U
UDK 4-ULA 48 RD/O-U
UDK 4-ULA 230
27 75 04 5
27 75 03 2
27 75 05 8
50
50
50
27 75 02 9
50
2775126
1
UDK 4-ULA1EK
Return busbar, 3 mm 0, engaged in terminal block and
led parallel to terminal strip, length: 1 m
Current indicator terminal block, black, shows
current flow of an auxiliary circuit via an LED, for a load
current of :
SP
'
RS
4 - 500
300 - 1000
Cover, gray
D-UDK 4
Fixed bridge, for cross connections in the
terminal center, screw heads with insulating
collar. 10-position, divisible, with t0 screws
Insertion bridge, fully insul .
2-pos
fully insulated,
3-pos
divisible, insulated spine
10-pos
Isolator bridge bar,for switchable branches,
10 positions, divisible, with 10 screws with
Bridge bar isolator IS-Kb4 as distance piece
Switch bar for 2 terminal blocks, complete, to
increase insulation an end cover must be
interposed
Separating plate, for electrical separation of neighboring
bridges, can be fitted later, no loss of pitch
rrnr
Order No .
Pkt.
UDK 4-ILA 500
UDK 4-ILA 1000
2775061
27 75 08 7
50
50
27 75 11 3
27 75 11 3
50
D-UDK 4
02 03 25 0
10
FBI 10-6
I,,,, : 26 A
02 01 15 5
26 A 02 01 14 2
26 A 02 01 13 9
32 A
03 01 50 5
100
100
10
10
EB 2-6
EB 3-6
EB 10-6
ISSBI 10-6
13 02 33 8
100
IS-K 4
32 A
FBI 10-6
EB 2-6
EB 3-6
EB 10-6
ISSBI 10-6
Type
IS-K 4
USBR 2-7
24 A
23 03 23 9
I
32A I 0203250
10
: 26 A 02 01 15 5
26 A
02 01 14 2
26 A 02 01 13 9
32 A 03 01 50 5
100
100
10
10
13 02 33 8
100
USBR 2-7
24 A
23 03 23 9
TS-KK 3
27 70 21 5
50
TS-KK 3
27 70 21 5
50
SZS 0,6 x 3,5
1205053
10
SZS O,6 x 3,5
1 2 05 05 3
1
Screwdriver
Zack marker strip, 10-section
White
Dimensions
Width / length / cover width
[mm]
[mm]
Height INS 35/7.5 '. NS 35 115 / NS 32)
Technical data in accordance with IEC / DIN VDE
Max . load current / cross section
[A]/[ mm, ]
Max . cross section with insertion bridge (solid/stranded)
[mm, ]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category ! insulating material group
Connection capacity
Stranded with ferrule without ! with plastic sleeve
[mm[]
Multi-conductor connection (2 cond . with same cross section)
Solid / stranded
[mm-]
Stranded with ferrules without plastic sleeve
[mm[]
Stranded with TWIN ferrule with plastic sleeve
[mm[]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Thread
Torque
[Nm]
Insulation material
Inflammability class in acc . with UL 94
Approval data (UUCUL and CSA)
Nominal voltage current ' conductor sizes UL/CUL : [V] / [A] / AWG
CSA: [V] / [A] / AWG
CSA: [V] .' [A] /AWG
288
Phoenix Contact
ZB 6 (for order data, see page 397)
ZB 6 (for order data, see page 397)
6 .2 / 63 .5 / 1 .5
47/54.5/52 .5
6 .2 / 63 .5 / 1 .5
47/54 .5/52.5
32/6
2 .5 / 2 .5
6/3
III / I
0 .5'')/6
2.5/2.5
6/3
III/I
0 .25-4/0 .25-1 .5
0.25 - 4 / 0 .25 - 1 .5
0 .2-1/0 .2-1 .5
0 .25-1 .5
0 .5-1
8
A4
M3
0.6-0 .8
PA
V2
0 .2-1/0 .2- 1 .5
0 .25 - 1 .5
0 .5 - 1
8
A4
M3
0 .6 - 0.8
PA
V2
600/30/30-10
300/25/22-12
600/10/22-12
600/0 .5/30-10
600/0 .5/22-10
C
Ground disconnect terminal
block, GTF 76
GTF 76
Terminal width 22 .5
(IEC)
[mm2 ]
In EN 60 204-1/VDE 0113 part 1
" Electrical equipment of industrial
machines " , section 9 .4 .3 .1 specifies that:
"ground faults in control circuits must not
lead to an unintentional startup or
dangerous movement of a machine or
prevent it shutting down . . .".
This requirement is fulfilled by the
ground disconnect terminal block, GTF 76.
With the disconnect slide closed in " ON "
position, the yellow lamp indicates
grounded normal operation . If the
disconnect slide is moved to the " OFF "
osition, the red lamp indicates whether
re is a ground fault in the control circuit .
s
Connection data
GTF 76/230
GTF 76/48
rigid
solid
flexible
stranded
AWG
I
[A]
U
[V[
0 .5-10
0 .5-10
0.5-6
0.5-6
20-8
20-8
57
57
110-250
24-48
clus GTF 76/230 only
Description
Type
Order No .
Pcs.
Pkl.
0 .5-1
GTF 76/230
31 21 01 2
10
3 .5-8
GTF 76/48
31 21 02 5
10
SZS 1,0 x 4,0
1205066
10
Current
[mA]
Ground disconnect terminal block, with
universal foot for mounting on U . nr or C_), for
110-250 VAC%DC
Ground disconnect terminal block, with
universal foot for mounting on U, n__r orC t, for
24-48 V AC/DC
Screwdriver
Zack marker strip, 10-section, white
Dimensions
[mm]
Width / length
Height (NS 15 . NS 35/7 .5 / NS 35/15 / NS 32)
[mm]
Technical data in accordance with IEC / DIN VDE
Rated surge voltage . contamination class
[kV)/
Surge voltage category / insulating material group
Connection capacity
[mm]
Stranded with ferrule without / with plastic sleeve
Multi-conductor connection (2 cond . with same cross section)
[mm/]
Solid ! stranded
Stranded with ferrules without plastic sleeve
[mm]
Stranded with TWIN ferrule with plastic sleeve
[mm-]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Thread
[Nm]
Torque
Insulation material
Inflammability class in acc . with UL 94
Approval data (UUCUL and CSA)
Nominal voltage !current .," conductor sizes
ZB 10 for order data, see page 399)
22 .5 / 64 .5
53 .5/54/61 .5/59
4/3
III/I
0 .5-10/0.5-4
0.5-6/0 .5-6
0 .5 - 6
0 .5 - 4
12
AS
M4
1 .2 - 1 .5
PA
VO
UUCUL [V[ / [A] / AWG
CSA : [V[ / [A] / AWG
250/50/26-8
250/50/26-8
Note:
Due to imbalances in the cable
insulation, the red indicator may light up
slightly when the disconnect slide is in the
open position, even though there is no
ground fault. This has no effect on the
functional efficiency and does not influence
the protective functions required by the
VDE regulations.
external
operating
indicator
0
01
yellow
operating I
indicator
Warning
During insulation testing in accordance
with EN 60 204-1 /VDE 0113 part 1, the
'TF 76 should be either disconnected or
ridged, as otherwise the light indicator will
be damaged or a short circuit will result .
3
.
Grounded operating mode
Ground fault
Phoenix Contact
289