VIP 300 protection relay for Ringmaster VIP 300 protection relay Protection relay Providing a wide range of selectivity and quality of supply The VIP 300 is a three phase overcurrent and earth fault protection relay, providing protection for the network and equipment. It is an integral part of the highly successful Ringmaster range of secondary distribution switchgear. The main function of the relay is to detect overcurrent and earth faults within the network and to trip the circuit breaker. Self powered reliability The VIP 300 protection relay is a self powered microprocessor based unit which requires no external DC power source or batteries, making it the ideal solution for location in remote areas or where auxiliary supplies are not available. 2 VIP 300 protection relay Benefits Flexibility There are a wide range of settings available. The IDMT (inverse definite minimum time) characteristics can be adjusted to grade the relay with other devices. Fast power up ensures that when switched on to a fault the power up time is less than )30ms. Testing The VAP6 hand held test unit, is available to provide a simple check of the integrity of the relay and can also perform trip tests. Circuit breaker “trip inhibit” facility allows the relay to be tested without tripping the circuit breaker using the VAP6. Secondary injection can be carried out using conventional test equipment. Ease of use VIP 300 has improved operation and control, with the relay settings being clearly displayed on the front panel. Manual reset flags show separate ‘tripped on fault’ for either overcurrent or earth fault conditions. Reliability The relay has a self monitoring device and diagnostic routine which constantly checks the operation of the relay automatically. 3 VIP 300 protection relay Features ■ Pick-up current ranges: RN2c, RE2c, CN2, CE2 overcurrent : 20A -200A earth fault : 2A-160A. CE6 and RN6c overcurrent : 40A - 400A earth fault : 4A to 320A. overcurrent : 80A - 800A earth fault : 8A to 640A. ■ Hardened electronics Certified EMC performance to IEC 255 and EN 50061, EN50082. ■ Separate overcurrent and earth fault trip indication. ■ Flashing LED’s indicate when the relay pick-up setting has been exceeded (creep test). Protection application guide Product CE2, RN2c, RE2c CE6, RN6c Application transformer ring feeders 200 - 1600kVA 400 - 3800kVA incomers 1900 - 12000kVA Time Fuse Link IDMT VIP 300 *Note: a protection coordination study may be necessary to verify the type of protection. Consult your local Merlin Gerin sales engineer if in doubt. Protection selection guide Primary current (A) Equivalent transformer rating at 11kV Units Application protection CE2 Transformer protection Time Fuse Link CN2 IDMT - VIP 300 RN2c, RE2c CE6 RN6c 4 Feeder protection IDMT - VIP 300 10 200kVA 20 400kVA 80 1600kVA 100 1900kVA 125 2400kVA 200 3800kVA 630 12000kVA VIP 300 protection relay Protection relay Ringmaster - the total solution The Ringmaster range of switchgear comprises non-extensible and extensible ring main units, extensible switches and circuit breakers up to 630A for medium voltage systems up to 13.8kV. RN2c - 200A non-extensible ring main unit incorporating 2 fault make/load break switches and a tee-off circuit breaker (transformer mounted or free standing). RE2c - 200A extensible ring main unit incorporating 2 fault make/load break switches and tee-off circuit breaker (transformer mounted or free standing). Available early 2000. RN6c - 630A non-extensible ring main unit for freestanding network sectionalising. CN2 - 200A non-extensible circuit breaker (transformer mounted or free standing). SN6 - 630A non-extensible switch (transformer mounted or free standing). CE2 - 200A extensible circuit breaker (switchboard mounted). CE6 - 630A extensible circuit breaker (switchboard mounted). SE6 - 630A extensible switch (switchboard mounted). MU2 - 200A feeder metering unit (circuit connected, transformer mounted or free standing). Easergy - Telecontrol cabinets (up to four switch control, freestanding, wall or switchgear mounted). For further details please refer to the Ringmaster range selection guide. ■ Time Fuse Link In addition to the VIP 300 relay, Ringmaster is also available with Time Fuse Link protection as a low cost option for transformers. Further details are given in the Ringmaster range selection guide. 5 6 VIP 300 protection relay Technical specification Content Page Use and settings Relay front panel 8 Curve selection 9 Operating ranges Selection principle 10 Applications Required setting information 11 Setting examples 12 Ex. 1 - Ring main unit protecting an 11kV, 1MVA transformer 13 - 14 Ex. 2 - 200A circuit breaker protecting an 11kV, 2MVA transformer 15 Ex. 3 - 630A circuit breaker protecting a radial feeder of 4MVA at 11kV 16 - 17 Ex. 4 - 630A circuit breaker protecting a radial feeder of 8MVA at 11kV 18 Technical characteristics 19 IDMT & DT tripping curves Standard inverse 20 Very inverse 21 Extremely inverse 22 Definite time 23 7 VIP 300 protection relay Relay front panel 1 2 3 4 5 C B phase overcurrent 7 8 6 10 A I> sensors: 200/1 4509996A0 VIP300LH range: x2 EI 1.2 DT (s) curve selection 15 6 4 2.7 1 12 9 2.4 1.5 off VIP 300 2.1 1.8 SI RI 42 48 56 36 64 30 72 24 80 20 100 90 (A) I>> DT only VI I> trip 9 20 3 (x Is) 3 (x Is) off 0.2 0.15 0.2 0.3 0.1 0.07 x10 0.4 0.05 not time multiplier x1 Is 0.6 0.05 0.9 0.03 0.6 t> 0.4 0.1 warning (s) t>> see table 1.5 VIP 300 Settings Equivalent Time Multiplier t> to> SI VI EI 0.05 0.07 0.1 0.15 0.2 0.3 0.4 0.05 0.6 0.07 0.1 0.15 0.2 0.3 0.4 0.6 x1 x1 x1 x1 x1 x1 x1 x10 x1 x10 x10 x10 x10 x10 x10 x10 0.02 0.02 0.03 0.05 0.07 0.10 0.13 0.17 0.20 0.24 0.34 0.50 0.67 1.01 1.35 2.02 0.03 0.05 0.07 0.10 0.13 0.20 0.27 0.33 0.40 0.47 0.67 1.00 1.33 2.00 2.67 4.00 0.06 0.09 0.12 0.19 0.25 0.37 0.50 0.62 0.74 0.87 1.24 1.86 2.48 3.71 4.95 7.43 reset Io> minimum operating phase current: 20A 2.1 1.8 SI off DT 1.2 (s) 15 6 4 2.7 1 12 9 2.4 1.5 RI trip Io>> DT only EI VI 20 3 3 (x Ios) off curve selection 16 24 32 12 40 8 50 4 60 2 80 70 (A) Io> earth fault 0.15 0.2 0.2 0.3 0.1 0.07 0.4 0.05 (s) x1 0.6 to> Ios not time multiplier 0.4 0.6 0.1 warning x10 0.05 0.03 to>> see table 0.9 (s) 1.5 VAP6 test plug D 11 12 13 14 E 15 17 18 16 19 20 Phase overcurrent setting Earth fault setting Other functions 1. Phase setting area (upper half of relay front panel). 11. Earth fault setting area (lower half of relay front panel). A. Current setting scale label. 2. Red LED phase overcurrent pick-up indicator. 12. Red LED earth fault pick-up indicator. 3. Phase overcurrent trip indicator. 13. Earth fault trip indicator. D. Minimum operating current. 4. Phase overcurrent setting Is. 14. Earth fault setting current Ios. E. VAP6 test plug socket. 5. Choice of low set curve type I>. 15. Choice of low set curve type Io>. 6. Low set pick-up (DT only) I>. 16. Low set pick-up (DT only) Io>. 7. Low set time delay t>. (@10Is) 17. Low set time delay to>. (@10Ios) 8. Multiplying factor (low set). 18. Multiplying factor (low set). 9. High set pick-up I>>. 19. High set pick-up Io>>. 10. High set time delay t>>. 8 20. High set time delay to>>. B. Current transformer and range information. C. Indicator reset button. VIP 300 protection relay Curve selection Phase overcurrent setting: IDMT curve selection t The numbers indicated below are those of the setting switches (refer to the diagram of the front panel on page 8) The letters indicate the curve characteristic as shown opposite. G SI, VI, EI RI Phase overcurrent setting: F ■ Setting current Is (4) G ■ Type of low set I> curve (5) IDMT: SI, VI, EI, RI. Definite time: DT t> H ■ DT low set pick-up I> (6) This setting is only active for the low set DT curve selection (as shown). If IDMT curves are selected this switch is disabled, as SI,VI, EI, low set pick-up is fixed at 1.2 Is. J K t>> J ■ Low set time delay t> (7) and multiplier (8) L Is F 1.2 Is 10 Is K ■ High set I>>(9) L ■ High set time delay t>>(10) Earth fault setting: I>> The principle is the same as for phase protection. Set: F ■ Setting current Ios (14) DT curve selection G ■ Type of low setting Io> curve (15) t IDMT: SI, VI, EI, RI Definite time: DT H I> t> DT H ■ DT low set pick-up Io> (16) This setting is only active for the low set DT curve selection (as shown). If IDMT curves are selected this switch is disabled, as SI, VI, EI low set pick-up is fixed at 1.2 Is. G J J ■ Low set time delay to> (17) and multiplier (18) K ■ High set Io>>(19) L ■ High set time delay to>>(20) K Operation: t>> Is L 1.2 Is I> The high and low set elements operate separately. The tripping order results from the “logical OR” between the two settings. I>> F 9 VIP 300 protection relay Choice of operating ranges Selection principle The operating range for the VIP 300 is dependent on the current transformer (also referred to as sensor) used, which is determined by the Ringmaster panel type chosen from the selection guide. The relay itself can then be set to either the x2 or x4 range as detailed in the table below. Sensor CTs available: Ringmaster 800/1, 400/1 or 200/1 (see Ringmaster selection guide) Range specified: VIP 300LH x2 or x4 range Ringmaster range Application Range RN2c, RE2c, CE2, CN2, 200/1A CT Transformer protection x2 min operating current 20A x4 40A Transformer/ Feeder Protection x2 40A x4 80A Feeder protection x2 80A x4 160A RN6c 400/1A CT CE6, RN6c 800/1A CT Protection Overcurrent earth fault Overcurrent earth fault Overcurrent earth fault Overcurrent earth fault Overcurrent earth fault Overcurrent earth fault Current Setting range Minimum Maximum 20A 100A 2A* 80A 40A 200A 4A* 160A 40A 200A 4A* 160A 80A 400A 8A* 320A 80A 400A 8A* 320A 160A 800A 16A* 640A Example 1 2 3 4 *The earth fault pick-up can be set below minimum operating current but a load current > minimum operating current needs to flow previous to a fault in order to ensure the relay is powered up. SETTING RANGES x2 x4 52 7 x4 range 40A,80A or 160A 5 minimum operating current 3 1 CT1 S1 P1 S2 P2 R P1 S2 P2 Y S2 P2 S1 S1 B 4 C11 C31 5 C31 C51 6 C51 C10 7 C70 C30 8 C50 9 C90 10 x2 range 8 20A, 40A or 80A minimum 6 operating current 4 2 S2 C71 P1 C11 C70 VIP 300 IDMT RELAY 9 50/51 50N/51N 10 11 12 13 14 MITOP - ITC Note: Connection must be made to terminals 2, 4, 6 and 8 or terminals 1, 3, 5 and 7 for the x2 or x4 setting ranges respectively. Note: MITOP - trip coil. 10 K8 K7 (-Ve) (+Ve) 15 16 0v VIP 300 protection relay Application Selection principles Required setting information. Prior to making any settings, you need to know: Ir - rated current of installation to be protected. Current transformer: The current transformer is specified by the panel type chosen from the Ringmaster catalogue. i) Choice of range: To select the minimum operating current and therefore required primary amp operating range two factors can be considered. - The load current and any possible allowable overload (typical allowable overload for transformers is 30%) - The earth fault level (typically set at 0.4 times rated current Ir) It is appropriate to choose the range which will operate above the minimum operating current. Effectively the relay can be operated below this level, see minimum operating note. ii) Choice of curve*: There are 5 types of curve available. SI - Standard inverse, mainly used for feeder applications. VI - Very inverse, mainly used for transformer applications. EI - Extremely inverse, mainly used for transformer applications. DT - Definite time, used for timed applications. RI - Special applications (consult Merlin Gerin). iii) Choice of current setting Is and Ios*: Consider assumptions made in i) and choose the nearest appropriate current setting. iv) Choice of low set time delay t> and to>*: Desired operating time depends on the interval to achieve grading with upstream and downstream devices at the maximum and minimum fault levels. Between IDMT characteristics a grading margin of 0.4s is desired. Between an IDMT characteristic and a LV protective device a grading margin of 0.25s is considered acceptable. v) Choice of high set current setting I>> and Io>>: I>> and Io>> are multiples of Is and Ios respectively. The high set element has the advantage of allowing the protection upstream to reduce its operating time at high fault levels. Grading is carried out at the instantaneous current setting and not at the maximum fault level, therefore it can be achieved at lower currents enabling the upstream device to operate quicker at the maximum fault level. vi) Choice of high set time delay t>> and to>>: Depending on grading required upstream and downstream. *Depends on characteristics of devices upstream and downstream. The selection principles only act as a guide to set up the VIP 300, a proper protection selectivity study should be carried out to set up device settings. 11 VIP 300 protection relay Application Setting examples Typical examples will be given. Consider 4 examples: 1: RN2c unit protecting a typical MV/LV 1MVA transformer. 2: CE2 unit protecting a typical MV/LV 2MVA transformer. 3: CE6 unit protecting a radial feeder with 4 RN2c units fed from it each feeding 4: CE6 unit protecting the same radial feed for which a planned extension is to 1HVA transformers. make a ring feeding 8 RN2c units, each feeding 1HVA transformers. Example schematic 12 VIP 300 protection relay Application - transformers Example 1 An RN2c circuit breaker equipped with a VIP 300 feeds a 1000kVA transformer. The transformer details are as follows: Power rating = 1MVA Primary voltage = 11kV % Impedance Zt = 5% From this the rated current of the transformer can be calculated: Ir = Power voltage x 33 = 1000 x 103 = 52.5A 11000 x 33 The HV fault level (MVAs) will be assumed to be 250MVA. The three phase LV fault level can be calculated: 1 IFLV = 11kV x 33 112 + 112 x Zt MVAs MVAT 100 [ 1 IFLV = 11kV x 33 112 + 112 x 5 250 1 100 [ ] ] A @ 11kV A = 972A @ 11kV The circuit breaker is fitted with 200/1A CTs. From the above the following will now be determined. Choice of range: The setting ranges available for the minimum operating currents are: x2 range, minimum operating current = 20A setting overcurrent 20A-100A earth fault 2A-80A x4 range, minimum operating current = 40A setting overcurrent 40A-200A earth fault 4A-160A By considering the minimum operating current of 20A (x2 range) then the transformer rated current is mid-point within the primary amp range. Hence there is room to consider possible overloads and earth fault levels. Range chosen x2 minimum operating current = 20A Choice of curve: In this case we are dealing with a MV/LV transformer. For this application the type of curve selected for overcurrent protection is usually either a VI or EI characteristic. These curves provide quicker operating times at higher fault currents to allow better protection of the transformer primary. The selection of these curves also helps in co-ordinating with the LV protective device on the secondary side of the transformer. For earth fault protection the curve selected is usually a definite time characteristic and is normally set quite low (typical 40% or 0.4 times the rated current). I> setting VI Io> setting DT Choice of current setting: Overcurrent Is If a typical overload of 30% is considered for the transformer. Is = overload x Ir = 1.3 x 52.5 = 68A Choose the nearest available setting above this in primary amps Is setting 72A. Earth fault Ios Consider a typical earth fault setting of 40% of transformer rated current, 20.8A Ios setting 24A DT only setting 1 13 VIP 300 protection relay Application - transformers Earth fault Choice of low set time delay: Overcurrent t> The time setting corresponds to the actual relay operating time at 10 x Is, in this case 720A. The desired operating time for the relay is determined by the upstream and downstream protective devices. In this example the downstream device is on the LV network, we therefore have to ensure adequate time is given between the two devices upto maximum LV 3ph fault level. It is assumed the LV device is set at 0.1s at the maximum fault level and therefore the desired operating time for the VIP 300 is given as follows: 1000 100 10 Desired operating = time operating time + grading margin between of LV device devices = 0.1 + 0.25 1 (see selection principles) If this value is used as t in the formula for the VI curve selected (see page 21) t= 13.5 [( IfIs ) -1 ] x t> 1.5 desired time t If (fault level) Is (current level) t> = 0.35 = 972A = 72A =? to> 0.1 Io> 0.01 To find t> rearrange formula 1 0.1 10 100 Current (multiples of Ios) [( ) ] t> = If -1 x t x 1.5 Is 13.5 Overcurrent [( ) ] t> = 972 -1 x 0.35 x 1.5 72 1.2 x Is 1000 13.5 By inserting the values into the formula t> = 0.486 Select 0.5 as nearest low set time delay (0.05 and x10 multiplier). The actual operating time can now be found by placing back into the original formula. Actual t = 0.36 t> 0.05s x10 Earth fault to> The earth fault element can be set as low as possible as there is no need to grade with the device on the LV of the transformer. It is set at 0.1 to avoid spurious operation under transient conditions such as magnetizing inrush. to> 0.1s x1 100 10 1 t> 10 x Is 0.1 Choice of high set current setting: t>> Overcurrent I>> The high set instantaneous element is a multiple of the setting current Is> and in this case is graded with the LV protective device. The maximum fault current the LV protective device will see is the 3ph LV fault level, 972A. Hence above 972A the high set can be implemented. Instantaneous = 15 x 72 = 1080 which is above 972A I>> = 15 Earth fault Io>> The high set earth fault element is a multiple of the setting current Ios>. The high set element for the earth fault is not used in this case and should be set in the off position. 0.01 1 10 100 Current (multiples of Is) Io>> off Choice of high set time delay: Dependent on upstream and downstream protection. In this case the phase overcurrent high set time delay t>> is set to the minimum 0.03 as downstream grading has been accounted for. Earth fault high set time delay to>> is disabled as high set is in off position. t>> 0.03 to>> 0.03 (disabled as high set is in off position). phase overcurrent sensors: 200/1 4509996A0 VIP300LH range: x2 I> I> EI 42 48 56 36 64 30 72 24 80 20 100 90 (A) Is 9 2.4 1.2 (s) curve selection 2.7 1 VIP 300 2.1 1.8 1.5 off DT trip I>> DT only VI SI RI (x Is) 3 15 20 3 (x Is) off 0.2 0.15 0.2 0.3 0.1 0.07 warning x10 0.4 0.05 not time multiplier x1 0.6 t> see table 12 6 4 0.4 0.6 0.1 0.05 0.9 0.03 1.5 (s) t>> VIP 300 Settings Equivalent Time Multiplier t> to> SI VI EI 0.05 0.07 0.1 0.15 0.2 0.3 0.4 0.05 0.6 0.07 0.1 0.15 0.2 0.3 0.4 0.6 x1 x1 x1 x1 x1 x1 x1 x10 x1 x10 x10 x10 x10 x10 x10 x10 0.02 0.02 0.03 0.05 0.07 0.10 0.13 0.17 0.20 0.24 0.34 0.50 0.67 1.01 1.35 2.02 0.03 0.05 0.07 0.10 0.13 0.20 0.27 0.33 0.40 0.47 0.67 1.00 1.33 2.00 2.67 4.00 0.06 0.09 0.12 0.19 0.25 0.37 0.50 0.62 0.74 0.87 1.24 1.86 2.48 3.71 4.95 7.43 reset minimum operating phase current: 20A Io> EI 2.1 1.8 SI DT 9 2.4 1.5 off RI trip Io>> DT only VI 1.2 2.7 1 (s) 3 12 15 6 4 20 3 (x Ios) off curve selection Io> earth fault 14 16 24 32 12 40 8 50 4 60 2 80 70 (A) Ios 0.15 0.2 0.1 0.07 0.05 (s) to> 0.2 0.3 0.4 0.6 warning x10 x1 not time multiplier 0.03 see table to>> 0.4 0.6 0.1 0.05 0.9 (s) 1.5 VAP6 test plug VIP 300 protection relay Application - transformers Example 2 Principles as example 1 A CE2 circuit breaker feeds a typical MV/LV 11kV 2MVA transformer. Transformer impedance and fault level as in example 1. The rated current for a 2MVA transformer. = 2000 x 103 = 105A Ir = power voltage x 33 11000 x 33 Choice of range: The load current exceeds the current range for the x2 setting thus the x4 setting is appropriate. Range chosen x4 minimum operating current = 40A Choice of curve: For this example we are dealing with a similar MV/LV application, the curve types are as selected as follows. I> setting Io> setting EI DT Choice of current setting: A typical overload of 30% and earth fault level of 40% are considered as in example 1. Is Ios 144A 48A Choice of Iow set time delay: Overcurrent t>, The LV 3 phase fault level = 1809A @ 11kV (using formula in example 1). t= 80 x [( IfIs ) -1 ] t> = 1809 -1 [( 144 ) ] 2 2 t> 0.808 x 0.35 x 0.808 = 0.55 phase overcurrent sensors: 200/1 4509996A0 VIP300LH range: x4 I> 80 I> EI 1.8 off t> to> 0.6 0.1 x1 x1 Choice of high set current: As before 1 (x Is) 84 96 112 72 128 60 144 48 160 40 200 180 (A) Is 3 15 4 20 3 (x Is) off 0.2 0.15 0.2 warning 0.3 0.1 0.07 x10 0.4 0.05 not time multiplier x1 0.6 t> see table 12 6 0.4 0.6 0.1 0.05 0.9 0.03 1.5 (s) t>> VIP 300 Settings Equivalent Time Multiplier t> to> SI VI EI 0.05 0.07 0.1 0.15 0.2 0.3 0.4 0.05 0.6 0.07 0.1 0.15 0.2 0.3 0.4 0.6 x1 x1 x1 x1 x1 x1 x1 x10 x1 x10 x10 x10 x10 x10 x10 x10 0.02 0.02 0.03 0.05 0.07 0.10 0.13 0.17 0.20 0.24 0.34 0.50 0.67 1.01 1.35 2.02 0.03 0.05 0.07 0.10 0.13 0.20 0.27 0.33 0.40 0.47 0.67 1.00 1.33 2.00 2.67 4.00 0.06 0.09 0.12 0.19 0.25 0.37 0.50 0.62 0.74 0.87 1.24 1.86 2.48 3.71 4.95 7.43 reset minimum operating phase current: 20A I>> 15 Io>> off (disabled) Choice of high set time delay: 2.7 curve selection trip 9 2.4 1.2 DT VIP 300 2.1 1.5 RI The earth fault element is set as before I>> DT only VI SI Io> EI 2.1 1.8 off DT 9 2.4 1.5 RI trip Io>> DT only VI SI 1.2 2.7 1 (s) 3 12 15 6 4 20 3 (x Ios) off curve selection As before t>> 0.03 to>> 0.03 (not used as high set current in off position). Io> earth fault 32 48 64 24 40 16 100 8 120 4 160 140 (A) Ios 0.15 0.2 0.1 0.07 0.05 (s) to> 0.2 0.3 0.4 0.6 warning x10 x1 not time multiplier 0.03 see table to>> 0.4 0.6 0.1 0.05 0.9 (s) 1.5 VAP6 test plug 15 VIP 300 protection relay Application - feeders Example 3 A CE6 unit protects an 11kV radial feed feeding 4 RN2c units each subsequently feeding 1000kVA transformers. The CE6 is an extensible 630A circuit breaker complete with 800/1A CTs. Effective load current. Ir = power = 4000 x 103 voltage x 33 11000 x 33 = 210A The HV three phase fault level is assumed as 250MVA. The earth fault level is assumed as 100 MVA. The corresponding fault current can be calculated from: I3ph = I1ph = MVAs voltage x 33 6 = 250 x 10 = 13121A 11000 x 33 6 MVAEF = 100 x 10 = 5248A voltage x 33 11000 x 33 Choice of range: min. operating current = 80A x2 range min. operating current = 160A x4 range overcurrent 80A - 400A overcurrent 160A - 800A earth fault earth fault 8A - 320A 8A - 640A By selecting the minimum operating current of 80A (x2 range) then the feeder rated current is in the midpoint of the range. Range chosen x2 minimum operating current = 80A Choice of curve: This example deals with feeder protection, SI or VI curves are suitable as they have slower operating times for high fault levels. It depends on the device upstream and downstream and the discrimination to be achieved at the HV fault level. I> Io> SI SI Choice of current setting: Overcurrent protection should take into account the max load current, 210A, and possible overload of one or more of the transformers. Earth fault protection assumes a 40% earth fault. Is Ios 256A 96A Choice of low set time delay setting: Overcurrent: Consider example 1 as downstream device with t> setting equal to 0.5, a t> setting of 1.5 for the upstream device gives adequate margin over the entire characteristic t> 0.15 x 10. 16 VIP 300 protection relay Application - feeders For the earth fault element the downstream device operates at 0.1s, therefore the required operating time for the upstream relay is 0.5s at the maximum phase - earth fault level. t = 0.14 If 0.02 -1 Is [( ) ] x to> 2.97 desired time t If (fault level) Is (current setting) to> = 0.5 = 5248A = 96A =? To find to> rearrange formula to> = [( IfIs ) 0.02 -1 ] x t x 2.97 0.14 to> = -1] x 0.5 x 2.97 [(5248 96 ) 0.02 0.14 By inserting the values into the formula to> = 0.88 select 1.0 as nearest setting. The actual operating time can now be found by placing back into the formula above. Desired operating time t = 0.57 to> 0.1s x10 Choice of high set: Disabled for this application. Earth fault I>> off Io>> off 1.2 x Is 1000 Choice of high set time delay: 100 Disabled as high set is in off position set at minimum t>> & to>> = 0.03 10 t> 1 phase overcurrent sensors: 800/1 4509996A0 VIP300LH range: x2 I> I> I>> DT only EI VI 1.8 SI 2.1 DT 9 2.4 1.5 off RI 1.2 (s) 2.7 1 VIP 300 (x Is) 3 12 15 6 4 20 3 (x Is) off curve selection trip 168 192 224 144 256 120 288 96 320 80 400 360 (A) Is 0.2 0.15 0.2 0.3 0.1 0.07 x10 0.4 0.05 warning not time multiplier x1 0.6 t> see table 0.4 0.6 0.1 0.05 0.9 0.03 1.5 (s) t>> VIP 300 Settings t> 0.05 0.07 0.1 0.15 0.2 0.3 0.4 0.05 0.6 0.07 0.1 0.15 0.2 0.3 0.4 0.6 to> x1 x1 x1 x1 x1 x1 x1 x10 x1 x10 x10 x10 x10 x10 x10 x10 SI VI EI 0.02 0.02 0.03 0.05 0.07 0.10 0.13 0.17 0.20 0.24 0.34 0.50 0.67 1.01 1.35 2.02 0.03 0.05 0.07 0.10 0.13 0.20 0.27 0.33 0.40 0.47 0.67 1.00 1.33 2.00 2.67 4.00 0.06 0.09 0.12 0.19 0.25 0.37 0.50 0.62 0.74 0.87 1.24 1.86 2.48 3.71 4.95 7.43 reset minimum operating phase current: 20A Io> off 1.2 2.7 1 DT 9 2.4 1.5 RI trip 2.1 1.8 EI (s) 3 0.1 0.01 1 100 12 15 6 4 1000 20 3 10 Current (multiples of Ios) Overcurrent Io>> DT only VI SI 10 x Is Equivalent Time Multiplier 1.2 x Is (x Ios) off curve selection 100 Io> earth fault 64 96 128 48 160 32 200 16 240 8 320 280 (A) Ios 0.15 0.2 0.1 0.07 0.05 (s) to> 0.2 0.3 0.4 0.6 warning x10 x1 not time multiplier 0.05 0.03 see table to>> 0.4 0.6 0.1 0.9 (s) 10 1.5 VAP6 test plug t> 1 10 x Is 0.1 0.01 1 10 100 Current (multiples of Is) 17 VIP 300 protection relay Application - feeders Example 4 An extension is planned for the system to feed another 4 RN2c units in a ring as shown in the diagram, the CE6 ring feeders would have to be capable of feeding the load on the ring. Example carried out as example 3. Choice of range Load rating exceeds range x2 maximum, 420A. Rating chosen x4 minimum operating current = 160A Choice of curve As example 3. Choice of current setting Is 512A Iso 192A Choice of low set time delay calculated similarly to example 3 t> to> 0.15 0.07 x10 x10 Choice of high set As example 3. Choice of high set time delay As example 3. phase overcurrent sensors: 800/1 4509996A0 VIP300LH range: x4 I> I> I>> DT only EI VI DT 1.2 (s) 2.7 1 (x Is) 3 curve selection trip 336 384 448 288 512 240 576 192 640 160 800 720 (A) Is 9 2.4 1.5 off RI VIP 300 2.1 1.8 SI 15 6 4 20 3 (x Is) off 0.2 0.15 0.2 warning 0.3 0.1 0.07 x10 0.4 0.05 not time multiplier x1 0.6 t> see table 12 0.4 0.6 0.1 0.05 0.9 0.03 1.5 (s) t>> VIP 300 Settings Equivalent Time Multiplier t> to> SI VI EI 0.05 0.07 0.1 0.15 0.2 0.3 0.4 0.05 0.6 0.07 0.1 0.15 0.2 0.3 0.4 0.6 x1 x1 x1 x1 x1 x1 x1 x10 x1 x10 x10 x10 x10 x10 x10 x10 0.02 0.02 0.03 0.05 0.07 0.10 0.13 0.17 0.20 0.24 0.34 0.50 0.67 1.01 1.35 2.02 0.03 0.05 0.07 0.10 0.13 0.20 0.27 0.33 0.40 0.47 0.67 1.00 1.33 2.00 2.67 4.00 0.06 0.09 0.12 0.19 0.25 0.37 0.50 0.62 0.74 0.87 1.24 1.86 2.48 3.71 4.95 7.43 reset minimum operating phase current: 20A Io> EI 2.1 1.8 off DT 9 2.4 1.5 RI trip Io>> DT only VI SI 1.2 2.7 1 (s) 3 12 15 6 4 20 3 (x Ios) off curve selection Io> earth fault 18 128192 256 96 320 64 400 32 480 16 640 560 (A) Ios 0.15 0.2 0.1 0.07 0.05 (s) to> 0.2 0.3 0.4 0.6 warning x10 x1 not time multiplier 0.03 see table to>> 0.4 0.6 0.1 0.05 0.9 (s) 1.5 VAP6 test plug VIP 300 protection relay Technical characteristics Phase overcurrent I> t> I>> t>> Accuracy - three phase (5% or 0/+2A - single phase (10% or 0/+4A Low set time delay - definite time ( 2% or ( 20ms *(see note) - IDMT class 5 according to IEC 255-3 *(see note) High set (5% High set time delay (2% or (20ms *(see note) % of pick-up 95% storage time 20ms *Operating times refer to when the relay is powered up, the tripping times indicated do not include the Mitop response time. When the relay is switched onto a fault the operating time will be extended by: +30ms at 1.5ls +20ms from 2ls to 10ls +10ms above 10ls Low set Earth fault Accuracy Low set - three phase (5% or 0/+2A - single phase (10% or 0/+4A to> Low set time delay - Definite time (2% or (20ms *(see note) - IDMT class 5 according to IEC 255-3 *(see note) Io>> High set (5% to>> High set time delay (2% or (20ms *(see note) % of pick up 95% storage time 20ms *Operating times refer to when the relay is powered up, the tripping times indicated do not include the Mitop response time. When the relay is switched onto a fault the operating time will be extended by: +30ms at 1.5ls +20ms from 2ls to 10ls +10ms above 10ls Io> General characteristics Value Operating frequency Operating temperature Storage temperature Continuous rating Continuous rating 50Hz +10%, 60Hz +10% -25$C to +70$C -40$C to +85$C 240A 960A With Ringmaster 200/1A CT With Ringmaster 800/1A CT Environment & electromagnetic capability Standard Severity Vibration Enclosure protection index Sensor input isolation 1.2/50 +s impuse voltage 1MHz dampened oscillating wave IEC 255-21-1 EN 60529 IEC 255-5 IEC 255-5 IEC 255-22-1 Rapid transient bursts 1.2/50 (8-20+s) hybrid wave Electrostatic discharge Radio frequency on I/Os HF electromagnetic field IEC 255-22-4 IEC 1000-4-5 IEC 255-22-2 EN 50082-2 IEC 255-22-3 EN 50082-2 EN 50082-3 EN 50082-2 IEC 1000-4-8 EN 50081 Class 2 IP54(cover closed) IP20(cover open) 2kV rms, 50 Hz, 1mn 5kV 2.5kV cm 1kV dm 4kV cm and dm, 5kHz burst 2kV 42 ohms 8kV in air 6kV on contact 10V,0.15 to 80 MHz 30V/m not modulated, 27 to 1000 MHz 10V/m mod. ampl., 80 to 1000MHz 11V/m mod. impuls., 900MHz 30A/m steady 300A/m, 1s 30 dB+V/m at 10m, 30 to 230MHz 37 dB+V/m at 10m, 230 to 1000MHz 50/60 Hz magnetic field Radiant field emitted 19 VIP 300 protection relay IDMT tripping curves IDMT tripping curves ■ The graphs in this section represent the 8 time delay settings for t> and to> available on the x1 and x10 ranges. ■ The low set pick-up settings I> and Io> are fixed at 1.2xIs and 1.2xIso respectively for the IDMT characteristics.> ■ The numbers given on the right of the curves represent the position of the time delay selector switch t> or to>. They correspond to the actual operating time at a current of 10 times the pick-up. ■ If the multiplying factor x1/x10 is in the x10 position, multiply the time delay selector settings by 10 (see x10 graph). ■ The phase overcurrent and earth fault protection curves are the same. SI current/time curves with selector switch on the x1 setting Current in amperes 1000 1.0 A 100 10 Time in seconds t> 0.6 t> 0.4 t> 0.3 t> 0.2 t> 0.15 t> 0.1 t> 0.07 t> 0.05 1 0.10 0.01 1 10 100 Standard inverse Standard Inverse (x1).tcc Ref. Voltage: 11000 Current Scale x10^0 t= SI current/time curves with selector switch on the x10 setting 1000 ( ) Current in amperes 1.0 A 100 t> 6 t> 4 t> 3 t> 2 t> 1.5 t> 1 t> 0.7 t> 0.5 10 Time in seconds 1 0.10 0.01 1 10 100 Standard Inverse (x10).tcc Ref. Voltage: 11000 Current Scale x10^0 20 0.14 x t> 2.97 I 0.02 -1 Is VIP 300 protection relay IDMT tripping curves VI current/time curves with selector switch on the x1 setting 1000 Current in amperes 1.0 A 100 t> 0.6 t> 0.4 t> 0.3 t> 0.2 t> 0.15 t> 0.1 t> 0.07 t> 0.05 10 Time in seconds 1 0.10 Very inverse 0.01 1 t= 10 100 Very Inverse (x1).tcc Ref. Voltage: 11000 Current Scale x10^0 13.5 x t> I 1.5 -1 Is ( ) VI current/time curves with selector switch on the x10 setting 1000 Current in amperes 1.0 A t> 6 t> 4 t> 3 t> 2 t> 1.5 t> 1 t> 0.7 t> 0.5 100 10 Time in seconds 1 0.10 0.01 1 10 100 Very Inverse (x10).tcc Ref. Voltage: 11000 Current Scale x10^0 RI curve (Specific application - please consult Merlin Gerin) 21 VIP 300 protection relay IDMT tripping curves EI current/time curves with selector switch on the x1 setting 1000 1.0 A Current in amperes 100 t> 0.6 t> 0.4 t> 0.3 t> 0.2 t. 0.15 t> 0.1 t> 0.07 t> 0.05 10 Time in seconds 1 0.10 Extremely inverse t= 0.01 1 10 100 Extremely Inverse (x1).tcc Ref. Voltage: 11000 Current Scale x10^0 EI current/time curves with selector switch on the x10 setting 1000 Current in amperes 1.0 A t> 6 t> 4 t> 3 t> 2 t> 1.5 t> 1 t> 0.7 t> 0.5 100 10 Time in seconds 1 0.10 0.01 1 10 100 Extremely Inverse (x10).tcc Ref. Voltage: 11000 Current Scale x10^0 22 80 I Is 2 ( ) -1 x t> 0.808 VIP 300 protection relay DT tripping curves DT tripping curves ■ The graphs below represent the 8 low set pick-up settings for I> and Io> and the 8 time delay settings for t> and to> available on the x1 and x10 ranges. ■ The low set pick up settings I> and Io> are variable between 1 and 3 times Is and Ios respectively. ■ The numbers given at the top of the curves represent the variable setting of the low set selector switch I> and Io>. The numbers given on the right of the curves represent the position of the time delay sector switch t> or to>. ■ If the multiplying factor x1/x10 is in the x10 position, multiply the time delay selector settings by 10 (see x10 graph). ■ The phase overcurrent and earth fault protection curves are the same. DT current/time curves with selector switch on the x1 setting DT current/time curves with selector switch on the x10 setting Current in amperes 1000 Current in amperes 1000 100 100 10 10 Time in seconds t> 6 t> 4 t> 3 t> 2 t> 1.5 t> 1 t> 0.7 t> 0.5 Time in seconds 1 1 t> 0.6 t> 0.4 t> 0.3 t> 0.2 t> 0.15 t> 0.1 t> 0.07 t> 0.05 0.10 0.01 1 10 0.10 100 Definite Time (x1).tcc Ref. Voltage: 11000 Current Scale x10^0 0.01 1 10 100 Definite Time (x10).tcc Ref. Voltage: 11000 Current Scale x10^0 23 MGMV 5477 Merlin Gerin Medium Voltage 123 Jack Lane, Hunslet, Leeds LS10 1BS UK Tel: +44 (0)113 290 3500 Fax: +44 (0)113 290 3710 www.schneider.co.uk JAN 2004