Protection Fundamentals Kevin Hinkley Technology and Innovation Manager TransGrid What are we doing in this topic? Basics of protection n Policy for Protection n Backup (CBF) Protection n What is a fault? n Abnormal current flow greater than nominal ratings of the equipment – Load current 1 kA, fault current 40kA n n Faults can be due to HV equipment insulation failure, lightning or human mistakes. Types of faults – 3ph, 3ph-e, 1ph-e, 2ph-e, ph-ph What is a Fault? Per unit voltage Circle – Blue QLD – Red NSW – Cyan VIC – Purple SA Simulation By Michael Bradbery Why do we have faults? n To economically deliver power over large distances – X and R must be kept low (Losses) – The voltage is increased to lower losses n n Transformer copper losses are reduced by using a larger conductor Hence low X and R means large current if connected to earth or phase to phase. What does a fault do to the power system? Generators slip poles n Stress generator shafts n Conductors overheating n Over rating of equipment n Split power system n How do we detect and control a fault? CTs n VTs n CB’s and Relays n Fuses n How Quick do we need to remove a fault? 500 kV Near 80 ms, Far 100 ms 330 kV Near 100 ms, Far 120 ms 132 kV Near 120 ms, Far 220 ms Protection Policy Objectives To disconnect the faulty circuit with minimum damage due to the fault n To leave the rest of the power system in a healthy state n To prevent or minimise n – Injury to people – Damage to property – Loss of Supply Design limitation of Protection The protection system is designed to clear a single fault despite the failure of one protection scheme or CB. n This is: ‘N-1’ n Requirements of a Protection System n Reliability – Protection should always operate when required n Security – Protection should refrain from operating when not required Basic Protection Policy n Any Fault must be: – Seen by two protections – Able to be cleared by two CB’s n Allow for a single contingency (N-1) – Failure of one protection system or – Circuit breaker n Only remove the faulted element of the power system Requirements of a Protection System Backup for relay and scheme failure n Backup for circuit breaker failure n No dead zones n No permanent damage due to clearance times n Clearance time should not exceed system stability time (CCT) n Protection Relay Policy All main Protections are duplicated n Relays are of different manufacture n – If same manufacturer, then they should operate on different principles – Exceptions are allowed for some relays with proven field service n Conform to appropriate IEC Standards Industry accepted risks n It is accepted that the following low probability events may result in a loss of system stability under certain operating conditions: – 2-Phase Phase-earth bus fault – Circuit breaker failure – Battery failure at single battery locations – Failure of a CB or disconnector pallet switch – Blindspot fault at critical locations Blind spot fault Fault between the CT and CB n Protection operates but does not clear the fault (Total Operation time 100ms) n Circuit breaker fail logic used to clear the fault (Total Clearance time 250ms) n No.1 A Protection No.1 B Protection A Feeder B Feeder P1 P2 P1 P2 P2 P1 P2 P1 Backup Protection n Backup is provide for: – Protection (relay & scheme) failure – Circuit breaker failure. n Backup can be: – Remote Backup - 66 kV and below – Local Backup - 132 kV and above Remote Backup n Backup for relay & circuit breaker is at a remote location – suited to radial systems – Slower clearance, maximum disruption – Minimum complexity & inexpensive Source Relay A Relay B Ideal Local Backup Relay & CB duplicated - ie, locally backed up. n Faster clearance, minimal disruption n Complex circuitry & expensive n Source P1 P2 Current Checked Circuit Breaker Fail C D E F A Protection Current Check B Timer Trip CB’s B,C,D,E & F Protection of individual systems Feeder Protection n Transformer Protection n Busbar Protection n Reactor Protection n Capacitor Protection n What we have done ? Basics of protection n Policy for Protection n Backup (CBF) Protection n