Revised Feb 2007 Section 24 - Patient Care Areas CHECK LIST Scope This Section applies to the installation of electrical wiring and equipment within Patient care areas of Health care facilities ____________________________________________________________________________________ Health care facility means a set of physical infrastructure elements that are intended to support the delivery of specific health-related services This includes: Hospitals, Clinics for Physiotherapy, Dialysis, Laser Surgery, Hair transplants, Cosmetic Surgery, etc and, Doctors Offices including Dental, Acupuncture, Naturopathic, Chiropractic Ophthalmologist etc. Does not include: Places providing services such as electrolysis, spas, massage, beauty treatments, Vision testing etc. Patient care area means an area intended primarily for the provision of diagnosis, therapy, or care. ____________________________________________________________________________________ Basic care area means a patient care area where body contact between a patient and medical electrical equipment is neither frequent nor usual. Intermediate care area means a patient care area in which body contact between a patient and medical electrical equipment is frequent or normal. Critical care area means a patient care area that is an anaesthetizing location, or in which cardiac contact between a patient and medical electrical equipment is frequent or normal. ____________________________________________________________________________________ Body contact means an intentional contact at the skin surface or internally, but not directly to the heart. Patient care environment means a zone in a patient care area which has been pre-selected for the accommodation of a patient bed, table, or other supporting mechanism, and for the accommodation of equipment involved in patient treatment, and which includes the space within the room 1.5 m beyond the perimeter of the bed, table, or other supporting mechanism in its normal location and to within 2.3 m of the floor. ___________________________________________________________________________________ Circuits in Basic Care Areas (1) Branch circuit conductors shall be copper and shall be sized not smaller than No. 12 AWG and shall be supplied from a grounded distribution system. Intent for Rule [Handbook] The Rule intends that panelboard circuit breakers be inaccessible to patients and other persons not authorized; consequently, this requirement frequently dictates that panelboards be located some distance from their loads. It is also intended that receptacles in patient care environments be capable of supplying 1000 to 1500 W loads with a reasonably stable voltage. To satisfy these conditions and the voltage drop requirements of Section 8, branch circuit conductors should be not smaller than No. 12 AWG and will frequently have to be larger. (2) A branch circuit shall only supply loads within patient care environments. [more than one patient care environment may be supplied by one circuit] (4) All branch circuits for a patient care environment shall be supplied from: (a) A single panelboard; or (b) Two panelboards, providing one of the panelboards is a part of an essential electrical system. Revised Feb 2007 Bonding to Ground in Basic Care Areas (1) Bonding conductors shall be insulated unless they are: (a) Installed in nonmetallic conduit; or (b) Incorporated into a cable assembly in such a manner that contact between any metal shield or armour, if it is present, and a bare bonding conductor is not possible. Field Considerations [Handbook] When using armoured cable, care should be taken in selecting the type of armoured cable to ensure that the bare bonding conductor does not make contact with the metal armour or sheath of the cable. Most types of TECK armoured cable have a PVC inner jacket that satisfies this requirement. Armoured cables [BX] with no inner insulating jacket or only a paper wrap should not be used. (2) All receptacles and other permanently connected equipment shall be bonded to ground by copper equipment bonding conductors, sized not smaller than the minimum size required for circuit conductors, and run in accordance with Rule 10-808, or run with the circuit conductors. (3) Each Panelboard supplying a patient care environment shall be bonded to ground with a copper Table 16 bonding conductor installed in the same raceway or cable as the circuit conductors. Receptacles in Basic Care Areas (1) Receptacles intended for a given patient care environment shall be located so as to minimize the likelihood of their inadvertent use for a patient care environment for which they are not intended. (2) Receptacles located in bathrooms or washrooms within a patient care area shall be: (a) Located 1.5 m to the washbasin; and (b) Located outside of any bathtub enclosure or shower stall; [no distance specified] (3) Receptacles which are located adjacent to a washbasin in a patient care area shall be protected by a ground fault circuit interrupter of the Class A type. [including a washbasin at a dental chair] (4) Receptacles intended for housekeeping equipment and other non-medical loads shall be so identified. (5) All 15 A and 20 A non-locking receptacles shall be hospital grade. (6) All receptacles that are part of an essential electrical system shall be red 24-112 Bonding to Ground in Intermediate and Critical Care Areas Bonding to ground in intermediate and critical care areas shall conform to Basic Care Areas whether the supply is derived from a grounded or an isolated system. If a patient care environment bonding point is provided [per CAN/CSA Z32], it shall be bonded to the panelboard serving the patient care environment with which it is associated by either: (a) A bonding jumper connecting it to the bonding terminal in an enclosure which accommodates the bonding point along with receptacles for a patient care environment; or (b) A copper conductor which is installed for that specific purpose, and is run in the same raceway as the equipment bonding conductors serving that patient care environment. 24-114 Receptacles in Intermediate and Critical Care Areas Receptacles in intermediate and critical care areas shall meet the requirements of Basic Care Areas.