Operating instructions, mounting & installation ABWF Outdoor motion sensor ⁄ presence detector DBWF Ceiling built-in motion sensor ⁄ presence detector RBWF Room motion sensor ⁄ presence detector RBWF - UP Room motion sensor ⁄ presence detector S+S REGELTECHNIK GMBH | KLINGENHOFSTR. 11 | 90411 NUREMBERG | GERMANY | PHONE +49(0)911 ⁄ 51947-0 | FAX +49(0)911 ⁄ 51947-70 | www.S p lusS.eu | mail@SplusS.eu Industry-oriented solutions – Complete control technology from one source! KINASGARD ® ABWF Outdoor motion sensor with switching output APPLICATION: The motion sensor detects the motions of persons. It is used to monitor or recognize conditions and for the motion-depending control of room functions, e.g. for lowering temperatures in unused rooms. It is ­applied in corridors, in outdoor areas, in industrial halls, in offices, residential and business facilities. ABWF TECHNICAL DATA: Power supply: ................................... 24 V AC ⁄ DC Sensor: . ............................................ infrared motion sensor Detection range .............................. 360°, angle of beam 90° ⁄ 110°, reach ca. 10 m Motion detection: ............................ of persons and objects, necessary temperature difference between subject and ambience ≥ 5 K Output: .............................................. without ⁄ with motion, potential-free normally-open ⁄ breaker contact 24 V After-running time: . ........................ adjustable from 4 s to 16 min Ambient temperature: .................... - 10 …+ 50 °C Electrical connection: ..................... 0.14 - 1.5 mm², via terminal screws on circuit board Enclosure: ......................................... plastic, material polyamide, 30 % glass-globe-reinforced, with quick-locking screws, colour pure white (similar RAL 9010) Dimensions: . .................................... 72 x 64 x 39.4 mm Detection range ABWF Circuit diagram ABWF Connecting diagram ABWF Installation: ....................................... on-wall Cable union: ...................................... M16, including strain relief Protection class: . ............................ III (according to EN 60 730) Protection type: ............................... IP 65 (according to IEC 529) Standards: ........................................ CE conformity, electromagnetic compatibility according to EN 61 326 + A1 + A2, EMC directive 89 ⁄ 336 ⁄ EWG ABWF Dimensional drawing Type ⁄ WG1 Detection Presence ⁄ motion Output ABWF - Ö ⁄ S Yes ⁄ No Normally-open ⁄ breaker contact KINASGARD ® DBWF Ceiling built-in motion sensor with switching output APPLICATION: The motion sensor detects the motions of persons. It is used to monitor or recognize conditions and for the motion-depending control of room functions, e.g. for lowering temperatures in unused rooms. It is installed in suspended ceilings in corridors, offices, residential and business facilities. The measuring transducer is accommodated in a separate enclosure apart from the sensor. DBWF TECHNICAL DATA: Power supply: ................................... 24 V AC ⁄ DC Sensor: . ............................................ infrared motion sensor Detection range: . ............................ 360°, angle of beam 90° ⁄ 110°, reach ca. 10 m, circular, when installed at a height of ca. 3 m, the sensor covers a radius (r) of ca. 3.4 m Motion detection: ............................ of persons and objects, necessary temperature difference - between subject and ambience ≥ 5 K Output: .............................................. potential-free normally-open contact 24 V After-running time: . ........................ adjustable from 4 s to 16 min Ambient temperature: .................... 0 …+ 50 °C Cable length: .................................... 2 m, other lengths optional (connecting cables between sensor and electronics) Process connection: ....................... in suspended ceiling, ceiling cutout Ø = 26 mm, cover Ø= 30 mm Connecting head: . ........................... aluminium, colour signal white (similar RAL 9003) Protection type (sensor): ............... IP 30 (according to IEC 529) Measuring transducer: Enclosure: ......................................... plastic, material polyamide, 30 % glass-globe-reinforced, with quick-locking screws, colour pure white (similar RAL 9010) Dimensions: ...................................... 72 x 64 x 39.4 mm Cable union: . ...............................................M16, including strain relief Electrical connection: ............................0.14 - 1.5 mm² via terminal screws Protection class: . ............................ III (according to EN 60 730) Protection type (Enclosure): .......... IP 65 (according to IEC 529) Standards: ........................................ CE conformity, electromagnetic compatibility according to EN 61 326 + A1 + A2, EMC directive 89 ⁄ 336 ⁄ EWG DBWF Dimensional drawing Type ⁄ WG1 Detection Presence ⁄ motion Output DBWF - Ö ⁄ S Yes ⁄ No Normally-open⁄ breaker contact Detection range DBWF Circuit diagram DBWF Connecting diagram DBWF KINASGARD ® RBWF Room motion sensor with switching output, series Odin I APPLICATION: The motion sensor detects the motions of persons. It is used to monitor or recognize conditions and for the motion-depending control of room functions, e.g. for lowering tempe-ratures in unused rooms. It is applied in corridors, in industrial halls, in offices, residential and business facilities. RBWF TECHNICAL DATA: Power supply: ................................... 24 V AC ⁄ DC Sensor: . ............................................ infrared motion sensor Detection range: . ............................ 360°, angle of beam 90° ⁄ 110°, reach ca. 10 m Motion detection: ............................ of persons and objects, necessary temperature difference between subject and ambience ≥ 5 K Output: .............................................. without ⁄ with motion, potential-free normally-open ⁄ breaker contact 24 V After-running time: . ........................ adjustable from 4s to 16 min Ambient temperature: .................... 0 …+ 50 °C Electrical connection: ..................... 0.14 - 1.5 mm², via terminal screws on circuit board Enclosure: ......................................... plastic, material ABS, colour pure white (similar RAL 9010), stainless steel optional Dimensions: ...................................... 79 x 81 x 26 mm Detection range RBWF Circuit diagram RBWF Connecting diagram RBWF Installation: ....................................... wall mounting or on in-wall flush box Ø 55 mm, base with 4 holes for mounting on vertically or horizontally installed flush boxes, with Protection class: . ............................ III (according to EN 60 730) Protection type: ............................... IP 30 (according to IEC 529) Standards: ........................................ CE conformity, electromagnetic compatibility according to EN 61 326 + A1 + A2, EMC directive 89 ⁄ 336 ⁄ EWG Enclosure Odin I RBWF Dimensional drawing Type ⁄ WG1 Detection Presence ⁄ motion Output RBWF - Ö ⁄ S Yes ⁄ No Normally-open ⁄ breaker contact KINASGARD ® RBWF - UP Room motion sensor with switching output, in-wall, panel switch programme APPLICATION: The motion sensor detects the motions of persons. It is used to monitor or recognize conditions and for the motion-depending control of room functions, e.g. for lowering temperatures in unused rooms. It is applied in corridors, in offices, residential and business facilities. RBWF - UP TECHNICAL DATA: Power supply: ................................... 24 V AC ⁄ DC Sensor: . ............................................ infrared motion sensor Detection range: . ............................ 360°, angle of beam 90° ⁄ 110°, reach ca. 10 m Motion detection: ............................ of persons and objects, necessary temperature difference between subject and ambience ≥ 5 K Output: .............................................. without ⁄ with motion, potential-free normally-open contact 24 V After-running time: . ........................ adjustable from 4 s to 16 min Ambient temperature: .................... 0 …+ 50 °C Enclosure: ......................................... plastic Installation: ....................................... in in-wall flush box Ø 55 mm Electrical connection: ..................... 0.14 - 2.5 mm², via plug terminals on circuit board Protection class: . ............................ III (according to EN 60 730) Protection type: ............................... IP 20 (according to IEC 529) Standards: ........................................ CE conformity, electromagnetic compatibility according to EN 61 326 + A1 + A2, EMC directive 89 ⁄ 336 ⁄ EWG Detection range RBWF - UP Circuit diagram RBWF - UP Installation scheme RBWF - UP SWITCH PROGRAMME: Manufacturer:................................... Busch-Jaeger Reflex Si (other switch programmes, manufacturers, colours and prices upon request Enclosure:......................................... plastic, standard colour alpine white (similar RAL 9010) (other colours with colour variants depending on the respective light switch programme are possible on request) RBWF - UP Dimensional drawing Type ⁄ WG1 Detection Presence ⁄ motion Output RBWF - UP - S Yes ⁄ No Normally-open contact General notes Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions. In addition, the following points are to be observed: - These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded! - Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device (e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed. - This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind. - No warranties or liabilities will be assumed for defects and damages arising from improper use of this device. - Consequential damages caused by a fault in this device are excluded from warranty or liability. - These devices must be installed by authorised specialists only. - The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products. - In case of any modifications made by the user, all warranty claims are forfeited. - This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided. - Operating this device close to other devices that do not comply with EMC directives may influence functionality. - This device must not be used for monitoring applications, which solely serve the purpose of protecting persons against hazards or injury, or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes. - Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions. - Modifications of these records are not permitted. - In case of a complaint, only complete devices returned in original packing will be accepted. Notes regarding products ABWF, DBWF, RBWF, RBWF-UP - The sensor is mounted inside the enclosure cover. Make sure not to damage the cable ⁄ sensor when opening enclosure. - If necessary for mounting and/or electric wiring, unplug connector carefully and plug it back on again in the same position after mounting and electric wiring. - Protect sensor surface against any kind of dirt and/or damage. - Scratches, dirt, and also partial shading falsify the measuring result. - Applying overvoltage will destroy the device. - If this device is operated beyond the specified range, all warranty claims are forfeited. General description: This device is used for the detection of persons in up to 10 meters distance. The temperature difference between persons to be detected and ambience must be greater than 5 K. When motion is detected, the potential-free relay output closes (-S) respectively opens (-Ö). The hold time for the output (closed relay contact in case of -S, open relay contact in case of -Ö), measured from the time when last motion was detected, can be pre-set at a potentiometer between 4 seconds and ca. 16 minutes. The sensor is characterized by its broad reach while being small in size. The potential-free normally-open / breaker contact is used for switching extra-low voltage only. These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded! Technical data Supply voltage: Connection scheme Individual operation Connection scheme Parallel operation For operating voltage reverse polarity protection, a one-way rectifier or ­r everse polarity protection diode is integrated in this device variant. This­ ­internal one-way rectifier also allows operating 0 - 10 V devices on AC supply voltage. The output signal is to be tapped by a measuring instrument. Output voltage is measured here against zero potential (0 V) of the input voltage! When this device is operated on DC supply voltage, the operating voltage input UB+ is to be used for 15...36 V DC supply and UB– or GND for ground wire! When several devices are supplied by one 24 V AC voltage supply, it is to be ensured that all ”positive“ operating voltage input terminals (+) of the field devices are connected with each other and all ”negative“ operating voltage input terminals (–) (= reference potential) are connected together (in-phase connection of field devices). All outputs of field devices must be referenced to the same potential! In case of reversed polarity at one field device, a supply voltage short-circuit would be caused by that device. The consequential short-circuit current flowing through this field device may cause damage to it. © Copyright by S+S Regeltechnik GmbH · Reprints, in part or in total, are only permitted with the approval of S+S Regeltechnik GmbH. 1252 III ⁄ 08 Therefore, pay attention to correct wiring!