OPERATING INSTRUCTIONS, MOUNTING & INSTALLATION
Outdoor motion sensor ⁄ presence detector ABWF
Room motion sensor ⁄ presence detector RBWF
Room motion sensor ⁄ presence detector RBWF - UP
Ceiling built-in motion sensor ⁄ presence detector DBWF
Dear clients and business partners!
We offer the controls specialist a complete, vast and highly efficient product programme of feelers, sensors, and field devices
based on electrical, electronic or electro-mechanical elements. Our equipment will not only give you significant customer benefits,
but shall also contribute to the preservation of our all common resources, to your feeling comfortable, and to energy conservation.
첸 We produce in Nuremberg, Germany.
첸 Our devices are marketed under our trademark S+S all over Europe.
첸 Our company is certified by TÜV according to DIN EN ISO 9001: 2000.
첸 We have competence in providing advice, know-how, and knowledge of the market.
첸 We employ qualified personnel, specializing in the fields of electrical engineering ⁄ electronics ⁄ precision mechanics.
첸 We sell you concepts and solutions.
By permanent further development of our equipment in cooperation with our customers, we achieve the optimum in meeting
the market‘s requirements for competitive, high-performing, perfected technical products, which we want to provide to our
customers. Also for special and problem solutions are we your competent partners. We are looking forward to a pleasant
partnership-like cooperation.
Sincerely yours, S+S Regeltechnik GmbH
PRESSURE · TEMPERATURE · FLOW · LIGHT INTENSIT Y · HUMIDIT Y · AIR QUALIT Y · MOTION
S+S REGELTECHNIK GMBH
KLINGENHOFSTRASSE 11
90411 NUREMBERG/GERMANY
PHONE +49 (0) 911/5 19 47-0
FAX
+49 (0) 911/5 19 47-70
kontakt@SplusS-regeltechnik.de
www.SplusS-regeltechnik.de
OPERATING INSTRUCTIONS, MOUNTING & INSTALLATION
Outdoor motion sensor⁄presence detector with switching output
ABWF
APPLICATION:
A motion sensor⁄presence detector detects the presence of persons and motions. It is used in
monitoring or recognizing conditions and for motion-depending control of room functions, e.g. for
lowering temperatures in unused rooms. It is applied in corridors, in outdoor areas, in industrial
halls, in offices, residential and business facilities.
ABWF
TECHNICAL DATA:
Power supply: .....................................24 V AC⁄DC
Sensor:..................................................infrared motion sensor
Detection range: ...............................360°, angle of beam 90°/110°, reach ca. 10 m
Output: ..................................................without ⁄ with motion,
potential-free normally-open⁄breaker contact 230 V⁄2 A
Follow-up time: ...................................adjustable from 1s to 16 min
Ambient temperature:....................-10…+ 50 °C, Δ temperature between object and ambience ≥ 5 K
Electrical connection:......................0.14 - 1.5 mm², via terminal screw on plate
Enclosure: ............................................plastic, material polyamide,
30 % glass-globe-reinforced,
with quick-locking screws,
colour pure white (similar RAL 9010)
Detection range
ABWF
Connecting scheme
ABWF
Connecting diagram
ABWF
Dimensions: ........................................72 x 64 x 39.4 mm
Installation: ..........................................on-wall
Cable union:.........................................M16, including strain relief
Protection class: ...............................III (according to EN 60 730)
Protection type: .................................IP 65 (according to IEC 529)
Standards: ...........................................CE conformity, electromagnetic compatibility
according to EN 61 326 + A1 + A2,
EMC directive 89 ⁄ 336 ⁄ EWG
Low-voltage directive 73 ⁄ 23 ⁄ EWG
Dimensional drawing
ABWF
Outdoor motion detector ABWF:
Type ⁄ WG1
Detection
Presence⁄motion
Output
ABWF - S
Yes⁄No
Normally-open contact
ABWF - Ö
Yes⁄No
Breaker contact
OPERATING INSTRUCTIONS, MOUNTING & INSTALLATION
Room motion sensor⁄presence detector with switching output
RBWF
APPLICATION:
A motion sensor⁄presence detector detects the presence of persons and motions. It is used in
monitoring or recognizing conditions and for motion-depending control of room functions, e.g. for
lowering temperatures in unused rooms. It is applied in corridors, in outdoor areas, in industrial
halls, in offices, in residential and business facilities.
RBWF
TECHNICAL DATA:
Power supply: .....................................24 V AC⁄DC
Sensor:..................................................infrared motion sensor
Detection range: ...............................360°, angle of beam 90°⁄110°, reach ca. 10 m
Output: ..................................................without ⁄ with motion,
potential-free normally-open⁄breaker contact 230 V⁄2 A
Follow-up time: ...................................adjustable from 1s to 16 min
Ambient temperature:....................0…+ 50 °C, Δ temperature between object and ambience ≥ 5 K
Electrical connection:......................0.14 - 1.5 mm², via terminal screw on plate
Enclosure: ............................................plastic, material ABS,
colour pure white (similar RAL 9010),
optional stainless steel
Detection range
RBWF
Connecting scheme
RBWF
Connecting diagram
RBWF
Dimensions: ........................................79 x 81 x 26 mm
Installation: ..........................................wall-mounted or on in-wall flush box Ø 55 mm,
socket with 4 holes for mounting on vertically or
horizontally installed flush boxes,
with predetermined breaking point for on-wall cable entry
Protection class: ...............................III (according to EN 60 730)
Protection type: .................................IP 30 (according to IEC 529)
Standards: ...........................................CE conformity, electromagnetic compatibility
according to EN 61 326 + A1 + A2,
EMC directive 89 ⁄ 336 ⁄ EWG
Low-voltage directive 73 ⁄ 23 ⁄ EWG
Dimensional drawing
RBWF
Room motion detector RBWF:
Type ⁄ WG1
Detection
Presence⁄motion
Output
RBWF - S
Yes⁄No
Normally-open contact
RBWF - Ö
Yes⁄No
Breaker contact
OPERATING INSTRUCTIONS, MOUNTING & INSTALLATION
Room motion sensor⁄presence detector, in-wall, with switching output
RBWF - UP
APPLICATION:
A motion sensor⁄presence detector detects the presence of persons and motions. It is used in
monitoring or recognizing conditions and for motion-depending control of room functions, e.g. for
lowering temperatures in unused rooms. It is applied in corridors, in offices, in residential and
business facilities.
RBWF - UP
TECHNIC AL DATA:
Power supply: .....................................24 V AC⁄DC
Sensor:..................................................infrared motion sensor
Detection range: ...............................360°, angle of beam 90°⁄110°, reach ca. 10 m
Output: ..................................................without ⁄ with motion,
potential-free normally-open⁄breaker contact 230 V⁄2 A
Follow-up time: ...................................adjustable from 1s bis 16 min
Ambient temperature:....................-10…+50 °C, Δ temperature between object and ambience ≥ 5 K
Enclosure: ............................................plastic
Installation: ..........................................in in-wall flush box Ø 55 mm
Detection range
RBWF - UP
Electrical connection:......................0.14 - 2.5 mm², via plug terminals on plate
Protection class: ...............................III (according to EN 60 730)
Protection type: .................................IP 20 (according to IEC 529)
Standards: ...........................................CE conformity, electromagnetic compatibility
according to EN 61 326 + A1 + A2,
EMC directive 89 ⁄ 336 ⁄ EWG
Low-voltage directive 73 ⁄ 23 ⁄ EWG
Panel switch programme: .............standard: Busch-Jaeger Reflex Si,
colour alpine white (similar RAL 9010)
(other switch programmes, switch manufacturers,
colours and prices upon request)
Dimensional drawing
Connecting diagram
RBWF - UP - S
Installation scheme
RBWF - UP
RBWF - UP
Room motion detector (in-wall) RBWF - UP:
Type ⁄ WG1
Detection
Presence⁄motion
Output
RBWF - UP - S
Yes⁄No
Normally-open contact
OPERATING INSTRUCTIONS, MOUNTING & INSTALLATION
Ceiling built-in motion sensor⁄presence detector with switching output
DBWF
APPLICATION:
A motion sensor⁄presence detector detects the presence of persons and motions. It is used in
monitoring or recognizing conditions and for motion-depending control of room functions, e.g. for
lowering temperatures in unused rooms. It is installed in suspended ceilings in corridors, offices,
residential and business facilities. The measuring transducer is accommodated apart from the
sensor in a separate enclosure.
DBWF
TECHNICAL DATA:
Power supply: .....................................24 V AC⁄DC
Sensor:..................................................infrared motion sensor
Detection range: ...............................360°, angle of beam 90°⁄110°, reach ca. 10 m,
circular, when installed at a height of 3 m,
the sensor covers a radius of ca. 3.4 m
Output: ..................................................potential-free normally open contact 230 V⁄ 2A
Follow-up time: ...................................adjustable from 1s to 16 min
Ambient temperature:....................-10…+50 °C, Δ temperature between object and ambience ≥ 5 K
Cable length: .......................................2 m, other lengths optional
(connecting cables between sensor and electronics)
Detection range
DBWF
Process connection: .......................in suspended ceiling, ceiling cut-out d = 26 mm,
cover D = 30 mm
Connecting head: ..............................aluminium, colour signal white (similar RAL 9003)
Protection type (sensor):...............IP 30 (according to IEC 529)
Measuring transducer:
Enclosure: ............................................plastic, material polyamide, 30 % glass-globe-reinforced,
with quick-locking screws, colour pure white (similar RAL 9010)
Dimensions: ........................................72 x 64 x 39.4 mm
Cable union:.........................................M16, including strain relief
Electrical connection:......................0.14 - 1.5 mm², via terminal screw
Protection class: ...............................III (according to EN 60 730)
Protection type: .................................IP 65 (according to IEC 529)
Connecting scheme
DBWF - S
Connecting diagram
DBWF
Standards: ...........................................CE conformity, electromagnetic compatibility according to
EN 61 326 + A1 + A2, EMC directive 89 ⁄ 336 ⁄ EWG
Low-voltage directive 73 ⁄ 23 ⁄ EWG
Dimensional drawing
DBWF
Ceiling built-in motion detector DBWF:
Type ⁄ WG1
Detection
Presence⁄motion
Output
DBWF - S
Yes⁄No
Normally-open contact
OPERATING INSTRUCTIONS, MOUNTING & INSTALLATION
OPERATING INSTRUCTIONS, MOUNTING & INSTALLATION
Mounting and installation:
General notes
Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of
the Electrical and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the
exclusive terms and conditions.
In addition, the following points are to be observed:
- These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!
- Devices must only be connected to safety extra-low voltage and under dead-voltage condition.
To avoid damages and errors at the device (e.g. by voltage induction) shielded cables are to be used, laying parallel with currentcarrying lines is to be avoided, and EMC directives are to be observed.
- This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control
authorities, the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and
safety regulations and has to prevent perils of any kind.
- No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
- Consequential damages caused by a fault in this device are excluded from warranty or liability.
- These devices must be installed by authorised specialists only.
- The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are
exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.
- In case of any modifications made by the user, all warranty claims are forfeited.
- This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or
heat irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.
- Operating this device close to other devices that do not comply with EMC directives may influence functionality.
- This device must not be used for monitoring applications, which solely serve the purpose of protecting persons against hazards
or injury, or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.
- Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
- Modifications of these records are not permitted.
- In case of a complaint, only complete devices returned in original packing will be accepted.
Notes regarding products ABWF, DBWF, RBWF, RBWF-UP
- The sensor is mounted inside the enclosure cover. Make sure not to damage the cable ⁄ sensor when opening enclosure.
- If necessary for mounting and/or electric wiring, unplug connector carefully and plug it back on again in the same position after
mounting and electric wiring.
- Protect sensor surface against any kind of dirt and/or damage.
- Scratches, dirt, and also partial shading falsify the measuring result.
- Applying overvoltage will destroy the device.
- If this device is operated beyond the specified range, all warranty claims are forfeited.
OPERATING INSTRUCTIONS, MOUNTING & INSTALLATION
General description:
This device is used for the detection of persons in up to 10 meters distance. The temperature difference between persons to be
detected and ambience must be greater than 5 K. When motion is detected, the potential-free relay output closes (-S) respectively
opens (-Ö). The hold time for the output (closed relay contact in case of -S, open relay contact in case of -Ö), measured from the
time when last motion was detected, can be pre-set at a potentiometer between 4 seconds and ca. 16 minutes.
The sensor is characterized by its broad reach while being small in size.
The potential-free normally-open / breaker contact is used for switching extra-low voltage only.
SUPPLY VOLTAGE:
Connecting scheme
Individual operation
Connecting scheme
Parallel operation
For operating voltage reverse polarity protection, a one-way rectifier or reverse polarity protection diode is integrated in this device
variant. This internal one-way rectifier also allows operating
0 – 10 V devices on AC supply voltage.
The output signal is to be tapped by a measuring instrument. Output voltage is measured her against zero potential (O V) of the input
voltage!
When this device is operated on DC supply voltage, the operating
voltage input UB+ is to be used for 15...36 V DC supply and UB – or
GND for ground wire!
When several devices are supplied by one 24 V AC voltage supply,
it is to be ensured that all ”positive“ operating voltage input terminals (+) of the field devices are connected with each other and all
”negative“ operating voltage input terminals (–) (= reference
potential) are connected together (in-phase connection of field
devices). All outputs of field devices must be referenced to the
same potential!
In case of reversed polarity at one field device, a supply voltage
short-circuit would be caused by that device. The consequential
short-circuit current flowing through this field device may cause
damage to it.
Therefore, pay attention to correct wiring!
© Copyright by S+S Regeltechnik GmbH · Reprints, in part or in total, are only permitted with the approval of S+S Regeltechnik GmbH.
1252 V/06 
These instructions must be read before installation and putting
in operation and all notes provided therein are to be regarded!