Crompton Protector Trip Relays

advertisement
Crompton Protector Trip Relays
• Phase Loss, Reversal or Sequence
• Under and Over Current or Voltage Protection
• Load Detection
• Monitoring of Systems
The Crompton Protectors provide continuous surveillance of the monitored circuit. When the
current moves outside the set point limit, the relay operates. An illuminated LED indicates when
the relay is energized. For 3 phase systems, the sequence of connection is not important.
Standard overcurrent relays will energize on trip when the nominal input current plus the user
adjustable “over nominal value” is exceeded, after the preset additional delay period if set.
The relay will automatically reset to de-energize when the input current is lowered past the setpoint
minus the hysteresis (differential) value.
L 252-PHU
Standard undercurrent relays will de-energize on trip when the input current is below the nominal
value minus the user adjustable “under nominal value” after the preset additional delay period
if set. The relay will automatically reset to energize when the input current is raised past the
setpoint plus the hysteresis value.
On request, any product can be manufactured with the energize/de-energize functions reversed.
MISC.
ORDERING INFORMATION
System
Input Aux. Power
Protection
AC Current
(Adjustable time delay 0-10 sec., fixed hysteresis 1%)
Single Phase
5A
120V
Under current 40-120%
Single Phase
5A
120V
Over current 40-120%
Single Phase
5A
120V
Under & over current
3 Phase 3 or 4 Wire 5A
120V
Under current
3 Phase 3 or 4 Wire 5A
120V
Over current
System
Protection
AC Voltage
(Adjustable hysteresis 1-15%)
Single Phase L-N
Under Voltage 75-100%
Over Voltage 100-125%
Over and Under Voltage
3 Phase, 3 Wire L-L
Under Voltage 75-100%
Over Voltage 100-12%
Over and Under Voltage
3 Phase, 4 Wire L-N
Under Voltage 75-100%
Over Voltage 100-12%
Over and Under Voltage
AC Voltage (Adjustable time delay 0-10 sec., fixed hysteresis 1%)
Single Phase L-N
Under Voltage 75-100%
Single Phase L-N
Over Voltage 100-12%
3 Phase, 3 Wire L-L
Under Voltage 75-100%
3 Phase, 3 Wire L-L
Over Voltage 100-12%
3 Phase, 4 Wire L-N
Under Voltage 75-100%
3 Phase, 4 Wire L-N
Over Voltage 100-12%
System
Input
Protection
Frequency
(Adjustable hysteresis 0.1-3.0Hz)
Single Phase
120 VAC
Under Frequency 55-65 Hz
Single Phase
120 VAC
Over Frequency 55-65 Hz
Single Phase
120 VAC
Under & Over (2 output relays)
Combined Under/Over Voltage and Under/Over Frequency
Single Phase 120V / 60 Hz
Over & Under Voltage
Over & Under Frequency (50-70 Hz)
(4 Independent Double Pole
change over relays)
131
Catalog Number
252-PAUU-LSBX-C6-DG-D1-EB
252-PAOU-LSBX-C6-DG-D1-EA
253-PADU-LSBX-C6-DG-D1-EC
253-PAVU-LSBX-C6-DG-D1-EB
253-PAPU-LSBX-C6-DG-D1-EA
Catalog Number
252-PVUU-PQBX-C6-EB
252-PVOU-PQBX-C6-EA
253-PVBU-PQBX-C6-EC
252-PVKU-PQBX-C6-EB
252-PVAU-PQBX-C6-EA
253-PVMU-PQBX-C6-EC
252-PVVU-PQBX-C6-EB
252-PVPU-PQBX-C6-EA
253-PVEU-PQBX-C6-EC
252-PVZU-PQBX-C6-EB-T1
252-PVHU-PQBX-C6-EA-T1
252-PVJU-PQBX-C6-EB-T1
252-PVCU-PQBX-C6-EA-T1
252-PVXU-PQBX-C6-EB-T1
252-PVSU-PQBX-C6-EA-T1
Catalog Number
252-PHUU-PQBX-C6-EB
252-PHOU-PQBX-C6-EA
253-PHDU-PQBX-C6-EC
256-PHUV-PQBX-C6
L 252-PVR
Crompton Protector Trip Relays
ORDERING INFORMATION
Input
Protection
120V L-L 60 Hz
Phase Sequence, Under Voltage
120V L-L 60 Hz
480V L-L 60 Hz
120V L-L 60 Hz
480V L-L 60 Hz
Phase Loss & Unbalance
Phase Loss & Unbalance
Phase Loss, Unbalance, Under Voltage
Phase Loss, Unbalance, Under Voltage
5A, 120V, 60 Hz
5A, 120V, 60 Hz
5A, 120V, 60 Hz
5A, 120V, 60 Hz
Input
120V/60 Hz
120V/60 Hz
Input
18-20V*
18-20V*
24V
Input
Catalog Number
Reverse Power 2-20%
Reverse Power 2-20%
Reverse Power 2-20%
Reverse Power 2-20%
Protection
BUS
Phase Angle & Voltage
Phase Angle & Voltage
Protection
Live BUS
Dead BUS
Under Voltage External Time Delay
Under Voltage Differential 1-15%
Over & Under Voltage (2 relays)
Protection
Aux Power
252-PVRU-PQBX-C6
252-PSFU-PQBX-C6
252-PSFU-SEBX-C6
252-PSGU-PQBX-C6-T1-1A
252-PSGU-SEBX-C6-T1-1A
256-PASU-LSBX-PQ-C6-EA
256-PATU-LSBX-PQ-C6-EA
256-PAQU-LSBX-PQ-C6-EA
256-PARU-LSBX-PQ-C6-EA
Catalog Number
256-PLLU-PQBX-C6
256-PLDU-PQBX-C6
Catalog Number
252-PDUU-NABX-T1-EB
252-PDEU-NABX-EB
253-PDCU-BDBX-T1-EC-BD
Catalog Number
50 mV
50 mV
100 mV
100 mV
J,K,T,S,T
J,K,T,S,T
High Trip
Low Trip
High Trip
Low Trip
High Trip
Low Trip
120V
120V
120V
120V
120V
120V
252-PBTU-ECBX-DG-T1-EA
252-PBSU-ECBX-DG-T1-EA
252-PBTU-GBBX-DG-T1-EA
252-PBSU-GBBX-DG-T1-EA
252-PTOU-T*BX-DB-T1-EA
252-PTUU-T*BX-DB-T1-EB
1 mADC
1 mADC
1 mADC
4-20 mADC
4-20 mADC
4-20 mADC
10 VDC
10 VDC
10 VDC
Protection
Low Trip 0-80%
Hip Trip 40-120%
Low/High, 2 relays
Low Trip 0-80%
Hip Trip 40-120%
Low/High, 2 relays
Low Trip 0-80%
Hip Trip 40-120%
Low/High, 2 relays
DC Aux. Power
120V
120V
120V
120V
120V
120V
120V
120V
120V
252-PBAU-FABX-DG-T1-EB
252-PBBU-FABX-DG-T1-EA
252-PBVU-FABX-DG-T1-EC
252-PBAU-HGBX-DG-T1-EB
252-PBBU-HGBX-DG-T1-EA
252-PBVU-HGBX-DG-T1-EC
252-PBAU-MTBX-DG-T1-EB
252-PBBU-MTBX-DG-T1-EA
252-PBVU-MTBX-DG-T1-EC
Catalog Number
3 Trip Points
3 Trip Points
12 VDC
24 VDC
MISC.
System
Phase Sequence & Phase Failure
3 Phase 3 or 4 Wire
Phase Balance
3 Phase 3 or 4 Wire
3 Phase 3 or 4 Wire
3 Phase 3 or 4 Wire
3 Phase 3 or 4 Wire
Reverse Power
1 ph or 3 ph, 4w
3 Phase, 3 Wire
1 ph or 3 ph, 4w, Push
3 ph 3w Push
System
Synchro-Check (Paralleling)
1ph or 3ph, 3w or 4w
1ph or 3ph, 3w or 4w
System
DC Voltage Relay
DC Relay
DC Relay
DC Relay
System
DC Millivolts/Thermocouple
DC Millivolt
DC Millivolt
DC Millivolt
DC Millivolt
Thermocouple**
Thermocouple**
DC Transducer Trip
Transducer
Transducer
Transducer
Transducer
Transducer
Transducer
Transducer
Transducer
Transducer
System
Speed Sensing
5V to 75V peak to peak
253-PH3U-BGBX-FS-V2
253-PH3U-BGBX-FS-V4
* 20-30V also available
** Specify TC Type and Temperature Range
SPECIFICATIONS
Relay Contacts:
Temperature:
Enclosure:
Dimensions:
DPDT, 5A@240VAC/24VDC (resistive)
0-60°C operating (0-40°C for UL)
Flame retardant polycarbonate/ABS, IP50
252: 2.2" x 2.8" x 4.4" (55 x 70 x 112 mm)
253: 2.9" x 2.8" x 4.4" (75 x 70 x 112 mm)
132
Crompton System Protection Relay
•
•
•
•
Monitor 3Ø Voltage & Current
12 Protective Relay Functions
8 or 12 User Programmable Relays
True RMS Measurements
Power Metering
•
•
•
•
Voltage L1-N (L1-L2)
Voltage L2-N (L2-L3)
Voltage L3-N (L3-L1)
Current L1
Current L2
Current L3
Neutral Current
Ground Current
System Watts
System VA
System VAr
Power Factor
Phase Angle
Gen Frequency
Bus Frequency
Gen-Bus Angle
Sync-Check Dead Bus
Under Voltage
Reverse Power
Phase Voltage Sequence
Applications
Voltage Unbalance
Time Overcurrent
Neutral Ground Fault
AND
OR
NAND
NOR
XOR
Over Frequency
Under Frequency
ORDERING INFORMATION
4W – PQ
LS – C6 – BD – 08 – MB
▲
▼
▼
▼
▼
Nominal Voltage
4W = 4 Wire
Nominal Voltage
3W = 3 Wire
Current
Auxiliary Power
Communications
LS = 5 Amp
BD = 24 Vdc
MB = Modbus RTU
▼
▼
NU = 57.7 Volts L/N
NX = 63.5 Volts L/N
P7 = 127 Volts L/N
PA = 69 Volts L/N
PK = 100 Volts L/N
PM = 110 Volts L/N
PQ = 120 Volts L/N
R4 = 220 Volts L/N
RQ = 230 Volts L/N
RR = 240 Volts L/N
RS = 250 Volts L/N
R6 = 277 Volts L/N
PK = 100 Volts L/L
PM = 110 Volts L/L
PO = 115 Volts L/L
PQ = 120 Volts L/L
RM = 208 Volts L/L
RU = 380 Volts L/L
RW = 400 Volts L/L
SB = 415 Volts L/L
SD = 440 Volts L/L
SE = 480 Volts L/L
▼
▼
132a
▼
•
•
•
•
•
•
•
General Purpose Protection
Generator Protection
Motor Protection
Cable Protection
Feeder Protection
Distribution Protection
Automatic Transfer Switches
SPECIFICATIONS
Over Voltage
Logic Functions
CR/SPR – 01
High Contrast LCD Display
Simple Menu Driven User Interface
RS485 Modbus Communications
Watchdog Relay
Sync-Check
Voltage Restrained Time Overcurrent
•
•
•
•
•
•
•
•
•
ANSI Trip Functions
Up to 34 true RMS power
measurements can be made
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Non Volatile Real Time Memory
Trip Event History Log
Time and Date Stamping
Front of Panel Mounting
▼
Current
Maximum Primary CT Value
Continuous Current Rating
Short Duration Current
Maximum CT Burden
Voltage
Maximum Primary PT Value
Continuous Voltage Rating
Short Duration Voltage
Maximum PT Burden
Relays
Contact Rating
Max Breaking Capacity
Auxiliary Supply
Working Range
Power
Communications
▼
Frequency
Relays
C5 = 50 Hz
C6 = 60 Hz
08 = Eight Relays
12 = Twelve Relays
Operating Temp.
Relative Humidity
Dimensions
Panel Cutout
Standards
Isolated 5A CT inputs
10 kA AC
2 x Nominal
20 x Nominal (1 sec)
< 0.6 VA
Direct or PT inputs
400kV AC
1.2 x Nominal
2 x Nominal (1 sec)
< 0.2 VA
Form C (NO + NC)
250 V AC, 5 A
2000 VA
24 VDC
9 to 36 VDC
< 20 VA
2 wire RS485, Modbus
RTU protocol. Includes all
features and functions
available through the
front panel.
0° to +50°C
95% non condensing
7.87”W x 4.17” H x 6.93” D
(200 x 106 x 176 mm)
7.36” x 3.66” (187 x 93 mm)
ANSI/IEEE C37.90,
UL508
138
Instrument Transformer
AC Current Transducers
NK Technologies
Ground Fault Sensor
• Large Window Area
• 0.5% FS accuracy
• 4-20mA DC Output
• 120VAC or 24VDC Power
The PCL is a 4 terminal
device with separate
connections for power
and load. The PCM is a
two terminal device.
24V is applied between
the + terminal and ground.
The output load may be
inserted in either the
– line for negative ground
systems or the + line for
positive ground systems.
TRANSDUCERS /
SENSORS
Output Load:
Size (LxWxH, inches)
PCL-5 thru 75
PCL-100 & up
PCM-5 thru 20
PCM-30 & up
SPECIFICATIONS
Setpoint:
Average responding, RMS calibrated
0-120% of rated current (typical)
50/60Hz
-30 to 60°C
600V, 10kV BIL full wave
30mA DC
1% max peak
PCL 120VAC ±10%
PCM 24VDC ±10%
PCL <1000 ohms
PCM <600 ohms
Window dia
0.94"
2.13"
0.93"
1.25"
2.7 x 2.4 x 4.5
4.5 x 4.7 x 4.9
2.7 x 2.4 x 2.75
4.5 x 4.7 x 4.9
ORDERING INFORMATION
Model
PCL-5
PCL-20
PCL-75
PCL-100
PCL-150
PCL-200
PCL-300
PCL-400
PCL-600
PCM-5
PCM-10
PCM-20
PCM-30
PCM-50
PCM-75
PCM-100
PCM-150
PCM-200
PCM-300
*Switch selectable
Rated Current
5A
10A, 15A, 20A*
25A, 50A, 75A*
100A
150A
200A
300A
400A
600A
5A
10A
20A
30A
50A
75A
100A
150A
200A
300A
• Fixed or selectable setpoint
• Solid-state or relay output
• Green LED Power-On indication
Detects ground fault (earth leakage) conditions by monitoring all currentcarrying conductors in a grounded single or three phase system.
SPECIFICATIONS
Output Signal:
Linear Range:
Frequency:
Operating Temperature:
Insulation Level:
Maximum Output:
Output Ripple:
Supply Voltage:
Connections
#8 screws
#8 studs
#10 screws
#8 studs
AG1, AG2: factory calibrated
AG3: field jumper selected
Solid-state Output: Isolated dry contact
AC Switch: 1A @ 240VAC
DC Switch: 0.15A @ 30VAC
Leakage <10 micro Amps (N.O.), <2.5mA (N.C.)
Mechanical Output: Single pole relay
Auto Reset: SPDT, 1A @ 125VAC, 2A @ 30VDC
Latching: SPST, 1A @ 125VAC, 2A @ 30VDC
Response Time:
200ms @ 5% above trip point
60ms @ 50% above trip point
15ms @ 500% above trip point
Isolation:
5kVAC (tested)
Frequency:
50–400 Hz (monitored circuit)
Power Supply:
66-132VAC
19.2-28.8VAC/DC
Loading:
2VA max.
Case:
UL94 V0 Flammability Rated
Environment:
-4 to 122°F (-20 to 50°C), < 95% RH, non-condensing
Size:
3.9"W x 3.0"H x 1.5"D (99x76x38mm)
Listings:
UL 1053, Class 1 Recognized, CE
ORDERING INFORMATION
To Order Insert Code for Each Letter to Select Catalog Number
Example: AG1-NOAC-120-FS-005
AG A – B – C – D – E
A Se tpoint
1
5–100mA factory set
2*
80–950mA factory set
3
5/10/30mA jumper set (TR3 only)
B Output Type
NOAC
Normally Open solid state, 1A @ 240VAC
NCAC
Normally Closed solid state, 1A @ 240VAC
NODC
Normally Open solid state, 0.15A @ 30VDC
NCDC
Normally Closed solid state, 0.15A @ 30VDC
NCR1
Normally Closed SPST Relay (requires LA option)
NOR1
Normally Open SPST Relay (requires LA option)
SDT1
SPDT Relay (Form C) with autoreset (requires DEN or ENE option)
C Power Suppl y
120
120VAC
24U*
24VAC/VDC
D Op tions
FS
Normally Energized (solid state output only)
NF
Normally De-energized (solid state output only)
ENE
Normally Energized, auto-reset (SDT1 output only)
DEN
Normally De-energized, autoreset (SDT1 output only)
LA
Latching (NOR1 and NCR1)
E Se tpoint
TR3
Tri-set (5/10/30mA)
nnn
Factory set trip point in mA
*Not UL recognized.
95
NEW
NK Technologies AC Current Switches
AS and ASX current switches combine a current
sensor, signal conditioner, and limit alarm in a
single package. AS1 series are well suited to
automation systems of all kinds with their
universal solid-state outputs and a wide
frequency response. AS3 series have a high
current output that works well with relay logic
control schemes. ASX series combine the AS3
design with a built in adjustable time delay. All
models feature high visibility LED indication and
rugged construction. AC monitoring models are
available in solid and split core cases.
FF Case Style
L
If you control or monitor electric powered loads, you need current
switches. Monitor fans, pumps, lights, and heaters for proper operation.
Current switches give positive feedback that the load is operating and
are much easier to install than alternatives like pressure switches,
optical sensors, or zero speed switches.
L FT Case Style
SP Case Style
L
SPECIFICATIONS
Power Required:
Setpoint Range:
Frequency Range:
Outputs
Solid State N.O.:
Solid State N.C.:
Solid State -15 Option:
Off State Leakage:
Response Time:
Hysteresis:
Sensing Aperture:
Case:
Environmental:
Listings:
AS3 Series
None — Self Powered
1–6, 6–40, 40–175A (fixed core)
1–6, 6–40, 40–200A (split core)
UL Listed to 1270 VAC
6–100 Hz
6–100 Hz
UL Listed (pending)
to 1270 VAC
50-100 Hz
0.2A @ 240 VAC/VDC
0.2A @ 135 VAC/VDC
N/A
None
0.120 Second
5% of Setpoint
0.55", 14 mm Dia. (FF Case)
0.75", 19 mm Dia. (FT Case)
0.85", 21.5 mm Sq. (SP Case)
UL 94V-O Flammability Rated
-58 to 149° F (-50 to 65° C)
0–95% RH, Non-condensing
UL and ULC 508 Listed, CE
1A @ 240 VAC
1A @ 240 VAC
15A @ 120 VAC, 10A @240 VAC
NC only: 2.5 mA
0.120 Second
5% of Setpoint
0.55", 14 mm Dia. (FF Case)
0.85", 21.5 mm Sq. (SP Case)
1.0A @ 240 VAC
1.0A @ 240 VAC
N/A
NC only: 2.5 mA
0.1 Second
5% of Setpoint
0.75”, 19 mm Dia. (FT Case)
0.85”, 21.5 mm Sq. (SP Case)
UL 94V-O Flammability Rated
-58 to 149° F (-50 to 65° C)
0–95% RH, Non-condensing
UL and ULC 508 Listed, CE
UL 94V-0 Flammability Rated
5 to 158 ° F (-15 to 70 ° C)
TRANSDUCERS /
SENSORS
Isolation Voltage:
NEW
ASX Series
None — Self Powered
1.5-12, 12-55, 50-200 A
AS1 Series
None — Self Powered
1–150A (fixed core)
1.5–150A (split core)
UL Listed to 1270 VAC
UL and ULC 508, CE (pending)
ORDERING INFORMATION
To Order—Insert Number Code for Each Letter to Select Catalog Number.
Example: AS1 - NCU-FT
A – B – C – D
A
B
Basic Model
AS1
AS3, ASX
Output
NOU
NCU
NOAC
NCAC
C
AC Sensing, Single Range
AC Sensing, 3 Ranges
AS1 Normally Open
AS1 Normally Closed
AS3, ASX, Normally Open
AS3, ASX, Normally Closed
D
Case and Connection
FF
Fixed Core, Front Connection
FT
Fixed Core, Top Connection (AS1, ASX only)
SP
Split Core
Options
GO
Fixed GO/No-GO Setpoint (AS1 only)
(blank)
Adjustable Setpoint
NL
No LED (AS1, AS3 only)
15
15A @ 120 VAC Output (AS3 only)
104
Veris Split Core KW Transducers
ORDERING INFORMATION
®
• Meter electronics and current transformers
in a single package
• Split-core system eliminates the need to
remove conductors
• Automatic compensation for CT orientation
• Continuous TRMS Readings
TRANSDUCERS /
SENSORS
SPECIFICATIONS
Input Primary Voltage
Number of Phases Monitored
Internal Isolation
Insulation Class
Temperature Range
Humidity Range
Accuracy
Output
Supply Power (current loop)
CT Opening
208-480VAC rms, 50/60Hz
One or Three
2000VAC rms
600VAC rms
0 to 60°C, 50°C for 2400A
0 to 95% non-condensing
±1%
4-20mA
9-30VDC; 30mA max.
Small 1.5" x 1.25" (38x32mm)
Medium 2.9" x 2.45" (73x62mm)
Large 5.5" x 2.45" (140 x 62mm)
Models with Modbus and Pulse Outputs also available.
Single CT Models for Use w/ Balanced 3Ø Loads or 1Ø 2 Wire Installations
Max.
Model
Voltage
Amps
CT Size
VE/H8041-0100-2
208/240
100
small
VE/H8041-0300-2
208/240
300
small
VE/H8041-0400-3
208/240
400
medium
VE/H8041-0800-3
208/240
800
medium
VE/H8041-0800-4
208/240
800
large
VE/H8041-1600-4
208/240
1600
large
VE/H8041-2400-4
208/240
2400
large
VE/H8042-0100-2
480
100
small
VE/H8042-0300-2
480
300
small
VE/H8042-0400-3
480
400
medium
VE/H8042-0800-3
480
800
medium
VE/H8042-0800-4
480
800
large
VE/H8042-1600-4
480
1600
large
VE/H8042-2400-4
480
2400
large
Three CT Models for Use with Any 3Ø Load or 1Ø 3 Wire Installations
Max.
Model
Voltage
Amps
CT Size
VE/H8043-0100-2
208
100
small
VE/H8043-0300-2
208
300
small
VE/H8043-0400-3
208
400
medium
VE/H8043-0800-3
208
800
medium
VE/H8043-0800-4
208
800
large
VE/H8043-4600-4
208
1600
large
VE/H8043-2400-4
208
2400
large
VE/H8044-0100-2
480
100
small
VE/H8044-0300-2
480
300
small
VE/H8044-0400-3
480
400
medium
VE/H8044-0800-3
480
800
medium
VE/H8044-0800-4
480
800
large
VE/H8044-1600-4
480
1600
large
VE/H8044-2400-4
480
2400
large
Veris Current Switch & Relay
• Independent switch & relay operation
• Command & status in one device
• Adjustable setpoint
• Relay & switch status LEDs simplify setup
®
SPECIFICATIONS
Current Range:
Sensor Power:
Insulation Class:
Frequency Range:
Temperature Range:
Humidity Range:
Setpoint Adjustable:
Hysteresis:
Dimensions:
Sensor Opening:
1-135A
Induced
600VAC rms
50/60Hz.
-15° to 60°C
0-95% non-condensing
1-135A
10% Typical
2.95" x 2.68" x 1.04"
0.75" (19mm) Dia.
ORDERING INFORMATION
H735
L
Model
Relay
Contacts*
VE/H735 Form A (SPST) 5(3)A@250VAC, 30VDC, 1/6HP
VE/H738 Form A (SPST) 10(5)A@250VAC, 30VDC, 1/3HP
VE/H739 Form A (SPST) 10(5)A@250VAC, 30VDC, 1/3HP
VE/H748
Form C (SPDT) 8(3.5)A@250VAC, 30VDC, 1/4HP
VE/H749
Form C (SPDT) 8(3.5)A@250VAC, 30VDC, 1/4HP
VE/H758 Form A (SPST) 10(5)A@250VAC, 30VDC, 1/3HP
VE/H759 Form A (SPST) 10(5)A@250VAC, 30VDC, 1/3HP
* Resistive load (inductive load).
Also available in split core style (H930 series)
103
Coil
24VAC/DC 10mA
24VAC/DC 10mA
24VAC/DC 10mA
24VAC/DC 10mA
24VAC/DC 10mA
9-12VDC 10mA
9-12VDC 10mA
Solid State Output
0.1A@30VAC/DC N.O.
1.0A@30VAC/DC N.O.
0.2A@120VAC/DC N.O.
1.0A@30VAC/DC N.O.
0.2A@120VAC/DC N.O.
1.0A@30VAC/DC N.O.
0.2A@120VAC/DC N.O.
Download