Installation and Maintenance Manual IMM 1157-1 Group: Chiller Part Number: 331373601 Effective: September 2014 Supercedes: March 2012 Water-Cooled Screw Compressor Chillers WGS 130AW to WGS 190AW, Packaged Water-Cooled Chiller WGS 130AA to WGS 190AA, Chiller with Remote Condenser 120 to 200 Tons, 420 to 700 kW R-134A, 60 Hz Table of Contents Introduction ....................................... 3 Electrical Data ................................. 30 General Description ..................................... 3 Nomenclature ............................................... 3 Inspection..................................................... 3 Wiring Diagrams ........................................ 38 Control Panel Layout ................................. 46 Installation ......................................... 4 Vibration Isolators ....................................... 6 Sequence of Operation .................... 49 Start-Up and Shutdown .................. 50 Flow Switch ............................................... 12 Glycol Solutions ........................................ 13 Condenser Water Piping ............................ 14 Water Pressure Drop .................................. 15 Pre Start-up ................................................ 50 Start-up....................................................... 50 Weekend or Temporary Shutdown ............. 51 Start-up after Temporary Shutdown ........... 51 Extended Shutdown ................................... 51 Start-up after Extended Shutdown ............. 51 Refrigerant Piping ........................... 18 System Maintenance ....................... 52 Unit with Remote Condenser ..................... 18 Factory-Mounted Condenser ..................... 21 General ....................................................... 52 Electrical Terminals ................................... 53 POE Lubrication ........................................ 53 Sight Glass and Moisture Indicator ............ 54 Sump Heaters ............................................. 54 Water Piping .................................... 10 Dimensional Data ............................ 22 Physical Data.................................... 25 WGS-AW, Water-Cooled ........................... 25 WGS-AA Remote Condenser .................... 26 Unit Configuration .......................... 27 Components ............................................... 27 Maintenance Schedule .................... 55 System Service ................................. 56 Troubleshooting Chart ............................... 58 Wiring ............................................... 28 BAS Interface ............................................ 29 Remote Operator Interface Panel ............... 29 Unit controllers are LONMARK certified with an optional LONWORKS communications module. Manufactured in an ISO Certified Facility ©2014 Daikin Applied. Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to make changes in design and construction at any time without notice. 2 WGS 130A to WGS 190A IMM 1157 Introduction General Description Daikin Model WGS water chillers are designed for indoor installations and are available with factorymounted water-cooled condensers (Model WGS AW), or arranged for use with remote air-cooled or evaporative condensers (Model WGS AA). Each water-cooled unit is completely assembled and factory wired before evacuation, charging and testing. They consist of two semi-hermetic rotary screw compressors, a two-circuit shell-and-tube evaporator, two shell-and-tube water-cooled condensers (WGS-AW), and complete refrigerant piping. Units manufactured for use with remote condensers (Models WGS-AA) have all refrigerant specialties factory-mounted and connection points for refrigerant discharge and liquid lines. Liquid line components are manual liquid line shutoff valves, charging valves, filter-driers, liquid line solenoid valves, sight glass/moisture indicators, and electronic expansion valves. The electrical control center includes a MicroTech II microprocessor control system and equipment protection and operating controls necessary for dependable, automatic operation. The compressor circuits are equipped with individual compressor isolation circuit breakers on single point power connection options. A unit disconnect switch is available as an option over the standard power block. Nomenclature W G S 130 A W Water-Cooled Condensing W = Water-Cooled Condenser A = Unit Less Condenser Global Design Vintage Rotary Screw Compressor Nominal Capacity (Tons) Inspection When the equipment is received, carefully check all items against the bill of lading to be sure of a complete shipment. Carefully inspect all units for damage upon arrival. All shipping damage must be reported to the carrier and a claim must be filed with the carrier. Check the unit serial plate before unloading the unit to be sure that it agrees with the power supply available. Physical damage to unit after acceptance is not the responsibility of Daikin Applied. Note: Unit shipping and operating weights are given in the physical data tables beginning on page 25. IMM1157-1 WGS 130A to 190A 3 Installation WARNING Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and experienced with this type of equipment. Avoid contact with sharp edges. Personal injury can result. Start-up by Daikin Applied is included on all units sold for installation within the USA and Canada and must be performed by them to initiate the standard limited product warranty. Two-week prior notification of start-up is required. The contractor should obtain a copy of the Start-up Scheduled Request Form from the sales representative or from the nearest Daikin Applied service office. Handling Every model WGS-AW water chiller with water-cooled condensers is shipped with a full refrigerant charge. For shipment, the charge is contained in the condensers and is isolated by the condenser liquid shutoff valves and the compressor discharge valves. A nitrogen/helium holding charge is applied to remote condenser models to maintain a slight positive system pressure. After installation, the unit must be leak-tested, vacuumed, and charged with the operating charge of refrigerant. The operating charge is field-supplied and charged on remote condenser models. WARNING Escaping refrigerant can displace air and cause suffocation. Immediately evacuate and ventilate the equipment area. If the unit is damaged, follow Environmental Protection Agency (EPA) requirements. Do not expose sparks, arcing equipment, open flame or other ignition source to the refrigerant. Moving the Unit If optional factory-installed skids are not used, some means such as dollies or skids must be used to protect the unit from damage and to permit easy handling and moving. Figure 1, Lifting the Unit Remote Condenser Chiller Water-Cooled Chiller 48.0 (1219.2) 48.0 (1219.2) 108.0 (2743.2) 84.0 (2133.6) 62.0 (1574.8) 62.0 (1574.8) WGS 130-190 PACKAGE WGS LESS CONDENSER LIFT ONLY WITH HOLES PROVIDED IN BASE R3306437 01 B0200 Notes: 1. You must use lifting halo or "I" spreader equal to the dimensions shown. 2. Each lifting cable alone must be strong enough to lift chiller. 3. Perform all moving and handling with skids or dollies under the unit when possible, and do not remove them until the unit is in the final location. (continued next page) 4 WGS 130A to 190A IMM1157-1 4. 5. In moving, always apply pressure to the base on the skids only and not to the piping or other components. A long bar will help move the unit. Do not drop the unit at the end of the roll. Do not attach slings to piping or equipment. Do not attempt to lift the unit by lifting points mounted on the compressors. They are for lifting only the compressor should one need to be removed from the unit. Move unit in the upright horizontal position at all times. Set unit down gently when lowering from the truck or rollers. Table 1, Lifting Loads WGS Model 130A 140A 160A 170A 190A AW, Package Units, lbs. (kg) AA, Less Condenser Units, lbs (kg) Shipping Weight RF RB LF LB 2276 (1032) 2276 (1032) 2368 (1074) 2471 (1096) 2471 (1096) 1699 (770) 1699 (770) 1794 (813) 1813 (822) 1813 (822) 2213 (1003) 2213 (1003) 2300 (1042) 2350 (1065) 2350 (1065) 1651 (749) 1651 (749) 1742 (790) 1763 (799) 1763 (799) 7840 (3556) 7840 (3556) 8206 (3722) 8345 (3785) 8345 (3785) RF RB LF LB 1428 (647) 1428 (647) 1515 (687) 1515 (687) 1515 (687) 1444 (655) 1444 (655) 1543 (700) 1543 (700) 1543 (700) 1386 (629) 1386 (629) 1470 (667) 1470 (667) 1470 (667) 1402 (636) 1402 (636) 1496 (679) 1496 (679) 1496 (679) Shipping Weight 5659 (2567) 5659 (2567) 6024 (2732) 6024 (2732) 6024 (2732) NOTES: 1. RF=right front, RB=right back, LB=left back, LF=left front, when view from the control panel. See Figure 2 on page 6. 2. The optional sound enclosure adds 650 lbs (295 kg) to the lifting weight, evenly distributed. Location WGS chillers are designed for indoor application and must be located in an area where the surrounding ambient temperature is 40°F to 122°F (4.4°C to 50°C). Because of the NEMA 1 electrical control enclosures, do not expose the units to the weather. A plastic cover over the control box is supplied as temporary protection during shipment. A reasonably level and sufficiently strong floor is required for the water chiller. If necessary, provide additional structural members to transfer the weight of the unit to the nearest beams. Note: Unit shipping and corner weights are given in Table 1. Operating weights are in the physical data tables beginning on page 25. Space Requirements for Connections and Servicing The chilled water piping enters and leaves the unit from the right side when looking at the front of the unit (control panel end). Left-hand connections are available as an option. Condenser water connections are located at the rear of the unit, opposite the control panel. Provide clearance of at least 4 feet (1625 mm), or more if codes require in front of the panel. Three feet (1219 mm) clearance should be provided on all other sides and ends of the unit for general servicing. The National Electric Code (NEC) may require additional clearance in front of the control panel and should be consulted. On units equipped with a water-cooled condenser (Type WGS-AW), also provide clearance for cleaning or removal of condenser tubes on one end of the unit. The clearance for cleaning depends on the type of apparatus used, but can be as much as the length of the condenser (10 feet, 3050 mm). Tube replacement requires the tube length of condenser plus one to two feet of workspace. This space can often be provided through a doorway or other aperture. Placing the Unit The small amount of vibration normally encountered with the water chiller makes this unit particularly desirable for basement or ground floor installations where the unit can be mounted directly to the floor. The floor construction should be such that the unit will not affect the building structure, or transmit noise and vibration into the structure. IMM1157-1 WGS 130A to 190A 5 Vibration Isolators It is recommended that isolators be used on all upper level installations or in areas where vibration transmission is a consideration. Figure 2, Isolator Locations 3 LF LB Control Panel End 1 Transfer the unit as indicated under “Moving the Unit.” on page 4. In all cases, set the unit in place and level with a spirit level. When springtype isolators are required, install springs running under the main unit supports. 4 Condenser Connections RF FRB 2 The unit should be set initially on shims or blocks at the listed spring free height. When all piping, wiring, flushing, charging, etc., is completed, the springs are adjusted upward to loosen the blocks or shims, which are then removed. Use a rubber anti-skid pad under isolators if hold-down bolts are not used. Installation of spring isolators requires flexible piping connections and at least three feet of flexible electrical conduit to avoid straining the piping and transmitting vibration and noise. NOTE: All spring isolators have four, same color springs per housing. Table 2, Weights & Vibration Isolators, Packaged Unit, w/o Sound Enclosure ARRANGEMENT WGS-AW, WITH WATER-COOLED CONDENSERS, WITHOUT SOUND ENCLOSURE UNIT SIZE CORNER WEIGHT LBS OPR. (KG) WT. Lbs. (kg) 1 2 3 4 SPRING-FLEX MOUNTINGS 1 2 3 RUBBER-IN-SHEAR MOUNTINGS 4 1 2 3 4 8557 130AW (3881) 1778 2556 1732 2491 1D-2040 1D-3600 1D-2040 (806) (1159) (786) (1130) Black Green Black RP-4 RP-4 RP-4 1D-3600 Green Brick Red Lime Brick Red RP-4 8557 140AW (3881) 1778 2556 1732 2491 1D-2040 1D-3600 1D-2040 (806) (1159) (786) (1130) Black Green Black RP-4 RP-4 RP-4 1D-3600 Green Brick Red Lime Brick Red RP-4 Lime 9314 (4225) 1910 2805 1863 2736 1D-2700 1D-3600 1D-2700 (866) (1272) (845) (1241) Purple Green Purple RP-4 9505 170AW (4311) 1959 2852 1911 2783 1D-2700 1D-3600 1D-2700 (889) (1294) (867) (1262) Purple Green Purple 9505 (4309) 1959 2852 1911 2783 1D-2700 1D-3600 1D-2700 (889) (1294) (867) (1262) Purple Green Purple RP-4 RP-4 RP-4 1D-3600 Green Brick Red Lime Brick Red RP-4 RP-4 RP-4 1D-3600 Green Brick Red Lime Brick Red RP-4 RP-4 RP-4 1D-3600 Green Brick Red Lime Brick Red 160AW 190AW Lime Lime RP-4 Lime RP-4 Lime NOTE: ID 2040, ID 2700 and ID 3600 have four same color springs per housing. 6 WGS 130A to 190A IMM1157-1 Table 3, Weights & Vibration Isolators, Packaged Unit, w/ Sound Enclosure ARRANGEMENT WGS-AW, WITH WATER-COOLED CONDENSERS, WITH SOUND ENCLOSURE UNIT OPR. WT. SIZE Lbs. (kg) 130AW 140AW 160AW 170AW 190AW CORNER WEIGHT LBS (KG) 1 2 3 4 SPRING-FLEX MOUNTINGS 1 2 3 RUBBER-IN-SHEAR MOUNTINGS 4 1 2 3 4 9205 4179 1928 875 2730 1239 RP-4 1882 2665 1D-2700 1D-3600 1D-2700 1D-3600 854 1210 Purple Green Purple Green Brick Red RP-4 RP-4 RP-4 Lime Brick Red Lime 9205 4179 1928 875 2730 1239 1882 2665 1D-2700 854 1210 Purple RP-4 1D-3600 1D-2700 1D-3600 Green Purple Green Brick Red RP-4 RP-4 RP-4 Lime Brick Red Lime 9962 4523 2060 935 2979 1352 2013 2910 1D-2700 914 1321 Purple 1D-3600 1D-2700 1D-3600 Green Purple Green RP-4 RP-4 RP-4 RP-4 Lime Charcoal Lime Charcoal 10153 4609 2109 957 3026 1374 2061 2957 1D-2700 936 1342 Purple 1D-3600 1D-2700 1D-3600 Green Purple Green RP-4 RP-4 RP-4 RP-4 Lime Charcoal Lime Charcoal 10153 4609 2109 957 3026 1374 2061 2957 1D-2700 936 1342 Purple 1D-2700 1D-2700 1D-2700 Green Purple Green RP-4 RP-4 RP-4 RP-4 Lime Charcoal Lime Charcoal NOTE: ID 2700 and ID 3600 have four same-color springs per housing. Table 4, Weights & Vibration Isolators, Remote Condenser, Without Sound Enclosure ARRANGEMENT WGS-AA, FOR REMOTE CONDENSER, WITHOUT SOUND ENCLOSURE (SEE NOTE) SPRING-FLEX MOUNTINGS RUBBER-IN-SHEAR MOUNTINGS UNIT OPR. WT. CORNER WEIGHT LBS (KG) SIZE LBS. (KG) 1 2 3 4 1 2 3 4 1 2 3 4 RP-4 RP-4 RP-4 RP-4 6265 1572 1603 1530 1560 1D-2040 1D-2040 1D-2040 1D-2040 130AA Brick Brick Brick Brick (2842) (713) (727) (694) (708) Black Black Black Black Red Red Red Red RP-4 RP-4 RP-4 RP-4 6265 1572 1603 1530 1560 1D-2040 1D-2040 1D-2040 1D-2040 140AA Brick Brick Brick (2842) (713) (727) (694) (708) Black Black Black Black Brick Red Red Red Red RP-4 RP-4 RP-4 RP-4 7022 1752 1800 1708 1758 1D-2040 1D-2040 1D-2040 1D-2040 160AA Brick Brick Brick (3185) (794) (818) (775) (797) Black Black Black Black Brick Red Red Red Red RP-4 RP-4 RP-4 RP-4 7022 1752 1800 1708 1758 1D-2040 1D-2040 1D-2040 1D-2040 170AA Brick Brick Brick (3185) (794) (818) (775) (797) Black Black Black Black Brick Red Red Red Red RP-4 RP-4 RP-4 RP-4 7022 1752 1800 1708 1758 1D-2040 1D-2040 1D-2040 1D-2040 190AA Brick Brick Brick (3185) (794) (818) (775) (797) Black Black Black Black Brick Red Red Red Red NOTE: ID 2040 has four same-color springs per housing. Table 5, Weights & Vibration Isolators, Remote Condenser, With Sound Enclosure UNIT SIZE 130AA 140AA 160AA 170AA 190AA ARRANGEMENT WGS-AA, FOR REMOTE CONDENSER, WITH SOUND ENCLOSURE (SEE NOTE) CORNER WGT RUBBER-IN-SHEAR OPR. WT. SPRING-FLEX MOUNTINGS LBS (KG) MOUNTINGS LBS. (KG) 1 2 3 4 1 2 3 4 1 2 3 4 RP-4 RP-4 RP-4 RP-4 6913 1722 1777 1680 1734 1D-2040 1D-2040 1D-2040 1D-2040 Brick Brick Brick Brick 3139 782 807 763 787 Black Black Black Black Red Red Red Red RP-4 RP-4 RP-4 RP-4 6913 1722 1777 1680 1734 1D-2040 1D-2040 1D-2040 1D-2040 Brick Brick Brick Brick 3139 782 807 763 787 Black Black Black Black Red Red Red Red RP-4 RP-4 RP-4 RP-4 7666 1902 1974 1858 1932 1D-2040 1D-2040 1D-2040 1D-2040 Brick Brick Brick Brick 3480 864 896 844 877 Black Black Black Black Red Red Red Red RP-4 RP-4 RP-4 RP-4 7666 1902 1974 1858 1932 1D-2040 1D-2040 1D-2040 1D-2040 Brick Brick Brick Brick 3480 864 896 844 877 Black Black Black Black Red Red Red Red RP-4 RP-4 RP-4 RP-4 7666 1902 1974 1858 1932 1D-2040 1D-2040 1D-2040 1D-2040 Brick Brick Brick Brick 3480 864 896 844 877 Black Black Black Black Red Red Red Red NOTE: ID 2040 has four same color springs per housing. IMM1157-1 WGS 130A to 190A 7 Table 6, Isolator Kit Part Numbers Model AW, w/o Sound Enclosure WGS 130AW WGS 140AW WGS 160AW WGS 170AW WGS 190AW Spring Part Number 332320601 332320601 332320602 332320602 332320602 R-I-S Part Number 332325601 332325601 332325601 332325601 332325601 Model AW, w Sound Enclosure WGS 130AW WGS 140AW WGS 160AW WGS 170AW WGS 190AW Spring Part Number 332320602 332320602 332320602 332320602 332320602 R-I-S Part Number 332325601 332325601 332325602 33232562 332325602 Model AA, w/o Sound Enclosure WGS 130AA WGS 140AA WGS 160AA WGS 170AA WGS 190AA Spring Part Number 332320603 332320603 332320603 332320603 332320603 R-I-S Part Number 332325603 332325603 332325603 332325603 332325603 Model AA, w/ Sound Enclosure WGS 130AA WGS 140AA WGS 160AA WGS 170AA WGS 190AA Spring Part Number 332320603 332320603 332320603 332320603 332320603 R-I-S Part Number 332325603 332325603 332325603 332325603 332325603 NOTE: Model AW = packaged, water-cooled, Model AA = remote condenser, air-cooled Figure 3, CP-4, Spring Flex Mounting Figure 4, RP-4, R-I-S Mounting 6.25 5.00 3.75 3.00 ø .500-13NC-2B R4 VM&C .56 TYP. VM&C 4.63 3.87 R.28 TYP. R4 R.250 TYP. RECESSED GRIP RIBS DURULENE MATERIAL R.750 TYP. 1.13 ± .25 APPROX. 1.63 .38 NOTES: 1. MOUNT MATERIAL TO BE DURULENE RUBBER. 2. MOLDED STEEL AND ELASTOMER MOUNT FOR OUTDOOR SERVICE CONDITIONS. 3. 8 WGS 130A to 190A RAISED GRIP RIBS DRAWING NUMBER 3314814 ALL DIMENSIONS ARE IN DECIMAL INCHES RP-4 MOUNT VERSION WITH STUD IN PLACE. IMM1157-1 Figure 5, WGS-AA, Remote Condenser Configuration Discharge Connections Liquid Return Connections IMM1157-1 WGS 130A to 190A 9 Water Piping Vessel Drains at Start-up Evaporators are drained of water in the factory and shipped with an open ball valve in the drain hole. The drain is located on the bottom of the vessel. Be sure to close the valve prior to filling the vessel with fluid. Condensers: Units are drained of water in the factory and are shipped with condenser drain plugs in the heads removed and stored in a bag in the control panel. Be sure to replace plugs prior to filling the vessel with fluid. General Due to the variety of piping practices, follow the recommendations of local authorities for code compliance. They can supply the installer with the proper building and safety codes required for a proper installation. The piping should be designed with a minimum number of bends and changes in elevation to keep system cost down and performance up. Other piping design considerations include: 1. All piping should be installed and supported to prevent the chiller connections from bearing any strain or weight of the system piping. 2. Vibration eliminators to reduce vibration and noise transmission to the building. 3. Shutoff valves to isolate the unit from the piping system during unit servicing. 4. Manual or automatic air vent valves at the high points of the system. Drains should be placed at the lowest points in the system. 5. Some means of maintaining adequate system water pressure (e.g., expansion tank or regulating valve). 6. Temperature and pressure indicators located within 3 feet (0.9 meters) of the inlet and outlet of the vessels to aid in unit servicing. 7. A strainer or some means of removing foreign matter from the water before it enters the pump. It should be placed far enough upstream to prevent cavitation at the pump inlet (consult pump manufacturer for recommendations). A strainer can prolong pump life and help maintain system performance. Important Note A cleanable 20-mesh strainer must also be placed in the water line just prior to the inlet of the evaporator. This will aid in preventing foreign material from entering the unit and decreasing the performance of the evaporator. 8. If the unit is used as a replacement chiller on a previously existing piping system, flush the system thoroughly prior to unit installation. Regular water analysis and chemical water treatment on the evaporator and condenser are recommended immediately upon equipment start-up. 9. In the event glycol is added to the water system as an afterthought for freeze protection, recognize that the refrigerant suction pressure will be lower, cooling performance will be less, and water side pressure drop will be higher. If the percentage of glycol is large, or if propylene glycol is used instead of ethylene glycol, the added pressure drop and loss of performance could be substantial. Reset the freezestat and low leaving water alarm temperatures. The freezestat is factory set to default at 32°F (0°C). Reset the freezestat setting to approximately 8° to 10°F (4.4° to 5.5°C) below the leaving chilled water setpoint temperature. See the section titled “Glycol Solutions” on page 13 for additional information concerning the use of glycol. 10 WGS 130A to 190A IMM1157-1 10. Make a preliminary leak check of the water piping before filling the system. ! WARNING This unit contains POE lubricants that must not come into contact with any surface or material that might be harmed by POE, including certain polymers (e.g. PVC/CPVC and polycarbonate piping). Note: A water flow switch or pressure differential switch must be mounted in the evaporator outlet water line to signal that there is water flow before the unit will start. Figure 6, Typical Field Evaporator Water Piping Water Strainer Vent In Valved Pressure Gauge Vibration Eliminator Out Drain Flow Gate Valve Flow Protect All Field Piping Against Freezing Vibration Flow Balancing Gate Eliminator Switch Valve Valve NOTE: Water piping must be supported independently from the unit. System Water Volume All chilled water systems need adequate time to recognize a load change, respond to that load change and stabilize, without undesirable short cycling of the compressors or loss of control. In air conditioning systems, the potential for short cycling usually exists when the building load falls below the minimum chiller plant capacity or on close-coupled systems with very small water volumes. Some of the things the designer should consider when looking at water volume are the minimum cooling load, the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors. Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown, a rule of thumb of “gallons of water volume equal to two to three times the chilled water gpm flow rate” is often used. A properly designed storage tank should be added if the system components do not provide sufficient water volume. Variable Chilled Water Flow Reducing chilled water flow in proportion to load can reduce total system power consumption. Certain restrictions apply to the amount and rate of flow change. The rate of flow change should be a maximum of 10 percent of the change, per minute. Do not reduce flow lower than the minimum flows listed in the pressure drop data on page 16. Chilled Water Piping The system water piping must be flushed thoroughly prior to making connections to the unit evaporator. A perforated metal basket strainer with 0.125-inch perforation, 40% open area. IMM1157-1 WGS 130A to 190A 11 must be installed in the return water line before the inlet to the chiller. Lay out the water piping so the chilled water circulating pump discharges into the evaporator inlet. The return water line must be piped to the evaporator inlet connection and the supply water line must be piped to the evaporator outlet connection. If the evaporator water is piped in the reverse direction, a substantial decrease in capacity and efficiency of the unit will be experienced. A flow switch must be installed in the horizontal piping of the supply (evaporator outlet) water line to prove water flow before starting the unit. Provide drain connections at all low points in the system to permit complete drainage. Air vents should be located at the high points in the system to purge air out of the system. The evaporator is equipped with vent and drain connections. Install pressure gauges in the inlet and outlet water lines to the evaporator. Pressure drop through the evaporator can be measured to determine water flow from the flow/pressure drop curves on page 16. Vibration eliminators are recommended in both the supply and return water lines. Insulate chilled water piping to reduce heat loss and prevent condensation. Perform complete unit and system leak tests prior to insulating the water piping. Insulation with a vapor barrier is recommended. If the vessel is insulated, the vent and drain connections must extend beyond the proposed insulation thickness for accessibility. Flow Switch Field Installed A water flow switch must be mounted in the leaving evaporator and condenser water line to prove adequate water flow before the unit can start. This will protect against slugging the compressors on start-up. It also serves to shut down the unit in the event that water flow is interrupted to guard against evaporator freeze-up. A flow switch is available from Daikin Applied under part number 01750330. It is a “paddle” type switch and adaptable to any pipe size from 1 in. (25 mm) to 6 in. (152 mm) nominal. Certain flow rates are required to open the switch and are listed in Table 7. Switch terminals Y and R should be made to panel terminals 60 and 67 (chilled water) and 60 and 76 (condenser water). There is also a set of normally closed contacts on the switch that could be used for an indicator light or an alarm to indicate when a “no flow” condition exists. 1. Apply pipe sealing compound to only the threads of the switch and screw unit into the 1-in. (25-mm) reducing tee. The flow arrow must be pointed in the correct direction. 2. Piping should provide a straight length before and after the flow switch of at least five times the pipe diameter without any valves, elbows, or other flow restricting elements. 3. Trim the flow switch paddle if needed, to fit the pipe diameter. Make sure the paddle does not hang up in the pipe. ! CAUTION Make sure the arrow on the side of the switch is pointed in the direction of flow. Connect the flow switch according to the wiring diagram (see wiring diagram inside control box door). Incorrect installation will cause improper operation and possible evaporator damage. 12 WGS 130A to 190A IMM1157-1 Table 7, Flow Switch Flow Rates Pipe Size (NOTE !) Min. Adjst. Max. Adjst. Flow No Flow Flow No Flow inch mm gpm Lpm gpm Lpm gpm Lpm gpm Lpm 1 1/4 32 (2) 5.8 1.3 3.7 0.8 13.3 3.0 12.5 2.8 1 1/2 38 (2) 7.5 1.7 5.0 1.1 19.2 4.4 18.0 4.1 2 51 13.7 3.1 9.5 2.2 29.0 6.6 27.0 6.1 2 1/2 63 (3) 18.0 4.1 12.5 2.8 34.5 7.8 32.0 7.3 3 76 27.5 6.2 19.0 4.3 53.0 12.0 50.0 11.4 4 102 (4) 65.0 14.8 50.0 11.4 128.0 29.1 122.0 27.7 5 127 (4) 125.0 28.4 101.0 22.9 245.0 55.6 235.0 53.4 6 153 (4) 190.0 43.2 158.0 35.9 375.0 85.2 360.0 81.8 8 204 (5) 205.0 46.6 170.0 38.6 415.0 94.3 400.0 90.8 NOTES: 1. A segmented 3-inch paddle (1, 2, and 3 inches) is furnished mounted, plus a 6-inch paddle loose. 2. Flow rates for a 2-inch paddle trimmed to fit the pipe. 3. Flow rates for a 3-inch paddle trimmed to fit the pipe. 4. Flow rates for a 3-inch paddle. 5. Flow rates for a 6-inch paddle Optional Factory-Mounted The chiller may be equipped with the optional factory-mounted flow switch. The 24 Vac powered flow sensors are a solid state alternative to mechanical switches for sensing the acceptable flow rate of water. The flow sensors are extremely reliable with no moving parts that can become stuck or break in the flow process. These compact units are constructed of corrosion-resistant materials and 316 stainless steel parts and are factory-installed directly through a ¼ inch NPT into the flow. No field adjustments are required. The flow sensors operate on the calorimetric principle. The sensors use the cooling effect of a flowing fluid to provide reliable flow rate detection of liquids over a very wide flow range. The amount of thermal energy that is removed from the tip determines the local flow rate and when it exceeds a setpoint it changes the output-state. Glycol Solutions When using a glycol solution, the chiller capacity, flow rate, evaporator pressure drop, and chiller power input can be calculated using the following formulas. Refer to Table 8 for ethylene glycol and Table 9 for propylene glycol. Capacity, Capacity is reduced compared to that of plain water. To find the reduced value, multiply the chiller’s capacity when using water by the capacity correction factor C to find the chiller’s capacity when using glycol. Flow, Multiply the water flow by the G correction factor to determine the glycol flow required to give the same Delta-T as water. To determine evaporator gpm (or T) knowing T (or gpm) and capacity: Glycol GPM 24 x Glycol Capacity x Flow Correction G From Tables T For Metric Applications -- Determine evaporator lps (or T) knowing T (or lps) and kW: Glycol Lps kW x Flow Correction G from Tables 4.18 x T Pressure Drop, To determine glycol pressure drop through the cooler, enter the water pressure drop graph on page 16 at the actual glycol flow. Multiply the water pressure drop found there by correction factor P to obtain corrected glycol pressure drop. Power, To determine glycol system kW, multiply the water system kW by factor K. IMM1157-1 WGS 130A to 190A 13 Test coolant with a clean, accurate, glycol solution hydrometer (similar to that found in service stations) to determine the freezing point. Obtain percent glycol from the freezing point found in Table 8. On glycol applications the supplier normally recommends that a minimum of 25% solution by weight be used for protection against corrosion or the use of additional inhibitors. Note: The effect of glycol in the condenser is negligible. As glycol increases in temperature, its characteristics have a tendency to mirror those of water. Therefore, for selection purposes, there is no derate in capacity for glycol in the condenser. Table 8, Ethylene Glycol % Ethylene Glycol 10 20 30 40 50 Freeze Point °F °C 26 -3.3 18 -7.8 7 -13.9 -7 -21.7 -28 -33.3 C Capacity K Power G Flow P Pressure Drop 0.996 0.986 0.978 0.966 0.955 0.999 0.998 0.996 0.993 0.991 1.035 1.060 1.092 1.131 1.182 1.096 1.219 1.352 1.530 1.751 C Capacity K Power G Flow P Pressure Drop 0.987 0.975 0.962 0.946 0.929 0.992 0.985 0.978 0.971 0.965 1.010 1.028 1.050 1.078 1.116 1.068 1.147 1.248 1.366 1.481 Table 9, Propylene Glycol % Percent Glycol 10 20 30 40 50 Freeze Point °F °C 26 -3 19 -7 9 -13 -5 -21 -27 -33 ! CAUTION Do not use automotive grade antifreeze. Industrial grade glycols must be used. Automotive antifreeze contains inhibitors, which cause plating on copper tubes. The type and handling of glycol used must be consistent with local codes. Condenser Water Piping Arrange the condenser water so the water enters the condensers’ bottom connections or the single bottom manifold connection if the optional manifold has been ordered. The condenser water will discharge from the top condenser connections or the single top connection of the optional manifold. Failing to arrange the condenser water as stated above will negatively affect the capacity and efficiency. Install pressure gauges in the inlet and outlet water lines to the condenser. Pressure drop through the condenser should be measured to determine flow on the pressure drop/flow curves on page 17. Vibration eliminators are recommended in both the supply and return water lines. Water-cooled condensers can be piped for use with cooling towers or well water. Cooling tower applications should be made with consideration of freeze protection and scaling problems. Contact the cooling tower manufacturer for equipment characteristics and limitations for the specific application. 14 WGS 130A to 190A IMM1157-1 Evaporator Leaving Water Temperature(F) Head pressure control must be provided if the entering condenser water can fall below the curve 65 values displayed in the graph to 60 the right. The MicroTech II unit controller can provide this 55 function, using entering condenser 50 water as the control point. The 45 control will work with or without the optional condenser manifolds. 40 The water sensors are factory35 installed. 30 The controller setpoints have to be 50 60 70 80 90 adjusted for water control and Condenser Entering Water Temperature(F) certain output connections made to the tower components. See the operating manual OM WGS and the field wiring diagram in this manual for further details. Condenser Water Sensors Packaged WGS chillers are supplied with one ECWT sensor and one LCWT sensor. The option the unit is ordered with will determine the sensor location requirements. Listed below are the two possibilities. WGS Ordered Without the Condenser Manifold: If the unit is ordered without the condenser manifold option, the entering and leaving water sensors will have to be field-installed in their respective condenser water piping, at a common location. Since each WGS is supplied with an independent condenser vessel per refrigerant circuit, the water temperature sensors must be installed in a location prior to the water piping split on the entering water side and after the piping is rejoined on the leaving water side. The sensors ship with the chiller, temporarily attached to the condenser vessel. The sensors will be landed on the control panel end and provided with additional lead length for field installation. WGS Ordered With the Condenser Manifold: If the unit is ordered with the condenser manifold option, both sensors will be factoryinstalled in the manifolds. Water Pressure Drop The vessel flow rates must fall between the minimum and maximum values shown on the appropriate evaporator and condenser curves. Flow rates below the minimum values shown will result in laminar flow that will reduce efficiency, cause erratic operation of the electronic expansion valve and could cause low temperature cutoffs. On the other hand, flow rates exceeding the maximum values shown can cause erosion in the evaporator and condenser. Measure the chilled water pressure drop through the evaporator at field-installed pressure taps. It is important not to include valves or strainers in these readings. IMM1157-1 WGS 130A to 190A 15 Figure 7, Evaporator Pressure Drop WGS 130 – WGS 190 WGS 130, 140 WGS 160, 170, 190 Minimum Flow WGS Model Flow Rate Nominal Flow Pressure Drop Flow Rate Maximum Flow Pressure Drop Flow Rate Pressure Drop gpm L/s Ft. kPa gpm L/s Ft. kPa gpm L/s Ft. kPa 130AW/AA 195 12.3 5.8 17.4 312 19.7 13.5 40.4 520 32.9 33.9 101.1 140AW/AA 211 13.4 6.7 20.0 338 21.4 15.6 46.6 563 35.6 39.0 116.5 160AW/AA 235 14.9 4.6 13.8 376 23.8 10.8 32.3 627 39.7 27.3 81.6 170AW/AA 254 16.1 5.3 15.9 407 25.8 12.5 37.3 678 42.9 31.6 94.2 190AW/AA 273 17.3 6.1 18.1 437 27.7 14.2 42.5 728 46.1 35.9 107.2 Note: Minimum, nominal, and maximum flows are at a 16F, 10F, and 6F chilled water temperature range respectively and at ARI tons. 16 WGS 130A to 190A IMM1157-1 Figure 8, Condenser Pressure Drop WGS 130 – WGS 190 WGS 170, 190 with Manifold WGS 130, 140, 160 with Manifold WGS 170, 190 without Manifold WGS 130, 140, 160 without Manifold Pressure Drop Without Optional Condenser Manifold WGS Model Minimum Flow Flow Rate Pressure Drop gpm L/s Ft. kPa Nominal Flow Flow Rate Pressure Drop gpm L/s Ft. kPa Maximum Flow Flow Rate Pressure Drop gpm L/s Ft. kPa 130AW 140AW 160AW 170AW 190AW 304 304 304 372 372 390 422 470 509 546 650 704 784 848 911 WGS Model Minimum Flow Flow Rate Pressure Drop gpm L/s Ft. kPa Nominal Flow Flow Rate Pressure Drop gpm L/s Ft. kPa Maximum Flow Flow Rate Pressure Drop gpm L/s Ft. kPa 130AW 140AW 160AW 170AW 190AW 304 304 304 372 372 390 422 470 509 546 650 704 784 848 911 19.2 19.2 19.2 23.5 23.5 4.1 4.1 4.1 4.3 4.3 12.2 12.2 12.2 12.8 12.8 24.7 26.7 29.8 32.2 34.6 6.5 7.4 9.0 7.9 9.0 19.3 22.2 26.9 23.7 26.9 41.1 44.5 49.6 53.7 57.6 16.0 18.5 22.4 19.8 22.5 47.9 55.1 66.8 59.1 67.1 Pressure Drop With Optional Condenser Manifold IMM1157-1 19.2 19.2 19.2 23.5 23.5 4.7 4.7 4.7 5.3 5.3 14.0 14.0 14.0 15.8 15.8 24.7 26.7 29.8 32.2 34.6 7.4 8.5 10.3 9.4 10.7 WGS 130A to 190A 22.0 25.3 30.7 28.1 32.0 41.1 44.5 49.6 53.7 57.6 18.5 21.3 25.8 23.8 27.1 55.1 63.5 77.1 71.1 80.9 17 Refrigerant Piping Unit with Remote Condenser General For remote condenser application (WGS-AA), the chillers are shipped with a nitrogen/helium holding charge of 20 psi is used to pressurize the system with a slight positive pressure to prevent contaminants from entering the unit. This holding charge should not be mistaken as a refrigerant charge, and can not be used as part of the final total refrigerant charge. After installation, the unit should be pressurized and tested for leaks, vacuumed and charged with the correct refrigerant operating charge, taking into consideration the length of refrigerant piping. The operating charge is field-supplied and charged for remote condenser models. It is important that the unit be kept tightly closed until the remote condenser is installed and piped to the unit. It is the contractor’s responsibility to install the interconnection piping, leak-test the entire system, evacuate the system, and supply the system refrigerant charge. The system should be held under vacuum until it is charged under supervision of the Daikin Applied authorized service technician who will supervise unit commissioning. The unit operating charge (less piping and condenser) can be found on page 26. ! IMPORTANT NOTE ! Service Form SF99006 and an isometric sketch of the Remote Piping Layout showing pipe size, location of fittings, measured lengths and elevations MUST BE SUBMITTED TO Daikin Technical Response Center and reviewed before order entry. A Daikin Applied service representative will not perform startup without reviewed Service Form SF99006 and drawing. Installation must match reviewed drawing. All field piping, wiring and procedures must comply with design guidelines set forth in the product literature, and be performed in accordance with ASHRAE, EPA, local codes and industry standards and per included sizing tables. Any product failure caused, or contributed to, by failure to comply with appropriate design guidelines will not be covered by manufacturer’s warranty. Daikin Technical Response: Fax: 763-509-7666; Phone : 540-248-9201; e-mail: techresponse@daikinapplied.com The following notes apply to all size units: Maximum linear line length shall not exceed 75 feet. Maximum Total Equivalent Length (TEL) shall not exceed 180 feet. The condenser shall not be located more than 15 feet above the indoor unit. The condenser shall not be located more than 20 feet below the indoor unit. No underground piping. It is important that the unit piping be properly supported with sound and vibration isolation between tubing and hanger, and that the discharge lines be looped at the condenser and trapped at the compressor to prevent refrigerant and oil from draining into the compressors. Looping the discharge line also provides greater line flexibility. The discharge gas valves, liquid line solenoids, filter-driers, moisture indicators, and thermostatic expansion valves are all factory-mounted as standard equipment with the water chiller. After the equipment is properly installed, leak tested, and evacuated, it can be charged with R-134a and started under Daikin Applied service supervision. Total operating charge will depend on the air-cooled condenser used and volume of the refrigerant piping. Note: On the arrangement WGS-AA units (units with remote condensers), the installer must record the refrigerant charge by stamping the total charge and the charge per circuit on the serial plate in the appropriate blocks provided for this purpose. 18 WGS 130A to 190A IMM1157-1 The following discussion is intended for use as a general guide to the piping of air-cooled and evaporative condensers. Use the tables shown in this manual for sizing the discharge and liquid lines. Discharge lines must be designed to handle oil properly and to protect the compressor from damage that can result from condensing liquid refrigerant in the line during shutdown. Careful consideration must be given for sizing each section of piping so that gas velocities are sufficient at all operating conditions to carry oil. If the velocity in a vertical discharge riser is too low, considerable oil can collect in the riser and the horizontal header, causing the compressor to lose its oil and result in damage due to lack of lubrication. When the compressor load is increased, the oil that had collected during reduced loads can be carried as a slug through the system and back to the compressor, where a sudden increase of oil concentration can cause liquid slugging and damage to the compressor. Any horizontal run of discharge piping should be pitched away from the compressor approximately 1/8-inch per foot (10.4 mm per m) or more. This is necessary to move, by gravity, any oil lying in the header. Any discharge line coming into a horizontal discharge header should rise above the centerline of the discharge header. This is necessary to prevent liquid refrigerant from draining from the condenser when the compressor is not operating. If the compressors are lower than the condenser, or refrigerant migration is possible, a check valve should be installed at the condenser. A check/relief valve may be necessary in the liquid line at the condenser for applications where the liquid line is higher than the condensing unit or where refrigerant migration is an issue. The liquid line should be insulated when it is routed where the ambient exposure is higher than the condenser’s ambient temperature. A relief device may also be required in the discharge line piping. Figure 9 illustrates a typical piping arrangement involving a remote air-cooled condenser located at a higher elevation than the compressor. This arrangement is commonly encountered when the air-cooled condenser is on a roof and the compressor is on grade level or in a basement equipment room. Notice in Figure 9 that the discharge line is looped at the bottom and top of the vertical run. This is done to prevent oil and condensed refrigerant from flowing back into the compressor and causing damage. The highest point in the discharge line should always be above the highest point in the condenser coil. Include a purging vent at this point to extract non-condensables from the system. This method should also be employed if the air-cooled condenser is located on the same level as the compressor. Head Pressure Control The MicroTech II circuit controllers are capable of controlling the fans of remote air-cooled condensers connected to each of the unit’s two refrigerant circuits. Control is based on condensing temperature and uses a combination of fan variable frequency drive (VFD) and fan cycling. Recommended Refrigerant Pipe Sizes NOTES: 1. 2. Pressure drop is in equivalent degrees F. On WGS 140 and 170, the # 1 circuit is always the smallest and is closest to the control panel. Horizontal or Downflow Discharge Line Sizes Recommended Discharge Line Size, inch, O.D. Nominal Circuit Tons Conn. Size At Unit WGS 130, Both WGS 140, Cir #1 65 2 5/8 Line Size Press Drop, F 2 5/8 0.55 2 5/8 0.82 2 5/8 1.10 2 5/8 1.37 2 5/8 1.64 WGS 140, Cir #2 WGS 160, Both WGS 170, Cir #1 80 2 5/8 Line Size Press Drop, F 2 5/8 0.80 2 5/8 1.21 2 5/8 1.61 2 5/8 2.01 3 1/8 1.04 WGS 170, Cir #2 WGS 190, Both 95 2 5/8 Line Size Press Drop, F 2 5/8 1.08 2 5/8 1.62 2 5/8 2.16 3 1/8 1.17 3 1/8 1.40 Unit, Circuit IMM1157-1 Up to Up to Up to Up to Up to 50 Equiv.Ft 75 Equiv.Ft 100 Equiv.Ft. 125 Equiv.Ft. 150 Equiv.Ft. WGS 130A to 190A 19 Recommended Vertical Upflow Discharge Line Sizes Unit, Circuit Recommended Discharge Line Size, inch, O.D. Nominal Connection Circuit Size, O.D. Tons at WGS Unit Up to 50 Equiv. Ft Up to 75 Equiv. Ft Up to 100 Equiv. Ft. WGS 130, Both WGS 140, Cir #1 65 2 5/8 Line Size Press Drop, F 2 1/8 1.52 2 1/8 2.28 2 1/8 3.03 WGS 140, Cir #2 WGS 160, Both WGS 170, Cir #1 80 2 5/8 Line Size Press Drop, F 2 5/8 0.80 2 5/8 0.99 2 5/8 1.32 WGS 170, Cir #2 WGS 190, Both 95 2 5/8 Line Size Press Drop, F 2 5/8 0.94 2 5/8 1.41 2 5/8 1.88 Recommended Liquid Line Size Unit, Circuit Recommended Liquid Line Size, inch O.D. Nominal Conn. Circuit Size, Tons at Unit Up to Up to Up to Up to Up to 50 Equiv.Ft 75 Equiv.Ft 100 Equiv.Ft. 125 Equiv.Ft. 150 Equiv.Ft. WGS 130, Both WGS 140, Cir #1 65 1 3/8 Line Size Press Drop, F 1 3/8 0.76 1 3/8 1.14 1 3/8 1.52 1 3/8 1.89 1 3/8 2.27 WGS 140, Cir #2 WGS 160, Both WGS 170, Cir #1 80 1 3/8 Line Size Press Drop, F 1 3/8 1.11 1 3/8 1.67 1 3/8 2.23 1 3/8 2.78 1 3/8 3.34 WGS 170, Cir #2 WGS190, Both 95 1 3/8 Line Size Press Drop, F 1 3/8 1.50 1 3/8 2.25 1 5/8 1.33 1 5/8 1.66 1 5/8 1.99 Figure 9, Condenser Above Compressor (One of Two Circuits Shown) Check Valve (Preferred) Relief Valve Pressure Tap Condenser Pitch Discharge Line Maximum linear line length shall not exceed 75 ft. Maximum Total Equivalent Length (TEL) shall not exceed 180 ft. The condenser shall not be located more than 15 ft above the indoor unit. The condenser shall not be located more than 20 ft below the indoor unit. Loop To Evaporator 20 WGS 130A to 190A IMM1157-1 Factory-Mounted Condenser Units with the standard factory-mounted, water-cooled condensers are provided with complete refrigerant piping and full operating refrigerant charge at the factory. There is a possibility on water-cooled units utilizing low temperature pond or river water as a condensing medium that if the water valves leak, the condenser and liquid line refrigerant temperature could drop below the equipment room temperature on the “off” cycle. This problem arises only during periods when cold water continues to circulate through the condenser and the unit remains off due to satisfied cooling load. If this condition occurs: 1. Cycle the condenser pump off with the unit. 2. Check the liquid line solenoid valve for proper operation. Relief Valve Piping The ANSI/ASHRAE Standard 15, Safety Standard for Refrigeration Systems, specifies that pressure relief valves on vessels containing Group 1 refrigerant (R-134a) “shall discharge to the atmosphere at a location not less than 15 feet (4.6 meters) above the adjoining ground level and not less than 20 feet (6.1 meters) from any window, ventilation opening or exit in any building.” The piping must be provided with a rain cap at the outside terminating point and with a drain at the low point on the vent piping to prevent water buildup on the atmospheric side of the relief valve. In addition, a flexible pipe section should be installed in the line to eliminate any piping stress on the relief valve(s). The size of the discharge pipe from the pressure relief valve should not be less than the size of the pressure relief outlet. When two or more valves are piped together, the common header and piping to the atmosphere should not be less than the sum of the area of each of the lines connected to the header. The locations of the unit relief valves are shown on the piping schematic drawing on page 27. There are six valves on the water-cooled units, one for each circuit on the compressor oil separator (54 lb. air/min., 350 psi), suction line (17.3 lb. air/min., 200 psi), and condenser (54 lb. air/min., 350 psi). Remote condenser models have four valves. NOTE: Provide fittings to permit vent piping to be easily disconnected for inspection or replacement of the relief valve. Figure 10, Relief Valve Piping IMM1157-1 WGS 130A to 190A 21 Dimensional Data WGS-AW Water-Cooled Figure 11, WGS 130AW through WGS 190AW Packaged Chiller Without Optional Condenser Water Manifolds REMOVABLE LIFTING BRACKETS 13.8 (350.5) 8.3 (210.8) 20.5 (520.7) 169.9 (4315.5) 29.0 (736.6) “X” RELIEF VALVE RELIEF VALVE CONTROL PANEL CIRC. #1 RELIEF VALVES (ONE HIDDEN) CIRC. #2 FIELD POWER KNOCKOUTS VENT “A” EVAPORATOR “C” WATER OUT DRAIN “Y” “Z” FIELD CONTROL KNOCKOUTS 120.0" (3048.0) RECOMMENDED CLEARANCE FOR CONDENSER TUBE SERVICING 31.8 (807.7) 16.2 (411.5) “B” 34.0 (863.6) WATER IN “D” WATER OUT RELIEF VALVES 1 PER CIRCUIT CONDENSER WATER IN 4.0 IN. (101.6) SCH 40 PIPE VICTAULIC GROOVED. INLET AND OUTLET 0 .88 (22.4) MOUNTING HOLES TYP. 4 114.8 (2915.9) 11.75 (298.4) 14.75 (374.6) REMOVABLE LIFTING BRACKETS 330643201D010B WGS 130-190 Packaged Notes: 1. Unit water connection handing is oriented facing the control panel. 2. Unit shown with standard right-hand evaporator connections. Left-hand available as option. 3. Condenser connections available only as shown. 22 Evaporator Victualic Inches (mm) Dimensions Inches (mm) WGS Models Center of Gravity Inches (mm) Additions for Sound Enclosure Inches (mm) “A” “B” “C” “D” “X” “Y” “Z” Length Width Height WGS 130AW140AW 74.6 (1894.8) 29.3 (744.2) 95.0 (2413.0) 6.0 (152.4) 83.9 (2131.1) 35.8 (909.3) 16.8 (426.7) 4.0 (101.6) 2.5 (63.5) 3.0 (76.2) WGS 160AW190AW 76.6 (1945.6) 30.4 (772.2) 92.9 (2359.6) 8.0 (203.2) 84.0 (2133.6) 36.0 (914.4) 16.8 (426.7) 4.0 (101.6) 2.5 (63.5) 5.0 (127.0) WGS 130A to 190A IMM1157-1 WGS-AW, Water-Cooled with Optional Condenser Manifolds Figure 12 WGS 130AW through 190AW with Optional Condenser Manifolds REMOVABLE LIFTING BRACKETS 13.8 (350.5) 8.3 (210.8) 20.5 (520.7) 169.9 (4315.5) “X” 29.0 (736.6)0 RELIEF VALVE RELIEF VALVE RELIEF VALVES (ONE HIDDEN) CONTROL PANEL CIRC. #1 CIRC. #2 FIELD POWER KNOCKOUTS VENT “A” EVAPORATOR WATER OUT DRAIN “C” WATER IN “D” “Y” 31.8 (807.7) “Z” “B” 0 .88 (22.4) MOUNTING HOLES TYP. 4 16.2 (411.5) 34.0 FIELD CONTROL (863.6) KNOCKOUTS WATER OUT RELIEF VALVES 1 PER CIRCUIT CONDENSER 114.8 (2915.9) WATER IN 4.0 IN. (101.6) SCH 40 PIPE VICTAULIC GROOVED. INLET AND OUTLET 32.0 (812.8) 35.0 (889.0) 330643601D010B WGS 130-190 w/Manifold REMOVABLE LIFTING BRACKETS Notes: 1. Unit water connection handing is oriented facing the control panel. 2. Unit shown with standard right-hand evaporator connections. Left-hand available as option. 3. Condenser connections available only as shown. IMM1157-1 Evaporator Victualic Inches (mm) Dimensions Inches (mm) WGS Models Center of Gravity Inches (mm) Additions for Sound Enclosure Inches (mm) “A” “B” “C” “D” “X” “Y” “Z” Length Width Height WGS 130AW140AW 74.6 (1894.8) 29.3 (744.2) 95.0 (2413.0) 6.0 (152.4) 83.9 (2131.1) 35.8 (909.3) 16.8 (426.7) 4.0 (101.6) 2.5 (63.5) 3.0 (76.2) WGS 160AW190AW 76.6 (1945.6) 30.4 (772.2) 92.9 (2359.6) 8.0 (203.2) 84.0 (2133.6) 36.0 (914.4) 16.8 (426.7) 4.0 (101.6) 2.5 (63.5) 5.0 (127.0) WGS 130A to 190A 23 WGS-AA Remote Condenser Figure 13, Dimensions, WGS 130AA through WGS 190AA Remote Condenser 85.6 (2174.2) 77.8 (1976.1) REAR VIEW “E” 19.3 (490.2) 0 2.625" DISCHARGE #1 FIELD CONNECTION 0 1.375" LIQUID #2 FIELD CONNECTION “D” 0 2.625" DISCHARGE #2 FIELD CONNECTION 0 1.375" LIQUID #1 FIELD CONNECTION “F” 32.0 (812.8) 179.3 (4554.2) “X” FRONT VIEW RELIEF VALVE RELIEF VALVE CONTROL PANEL FIELD POWER KNOCKOUTS CIRC. #1 RELIEF VALVES (ONE HIDDEN) CIRC. #2 “A” VENT “Y” “C” EVAPORATOR WATER OUT WATER IN DRAIN “Z” 18.0 (457.2) 0 .88 MOUNTING HOLES 4 PLACES 34.0 (863.6) LIFTING HOLES 4 PLACES VICTAULIC GROOVED INLET AND OUTLET 6.00 SCH 40 PIPE for WGS 130-140 “B” FIELD CONTROL KNOCKOUTS 12.0 (304.8) 155.3 (3944.6) 8.00 SCH 40 PIPE FOR WGS 160-190 330643401D010B WGS 130-190 Less Condenser Notes: 1. 2. Unit water connection handing is oriented facing the control panel. Unit shown has right hand evaporator water connections. Dimensions Inches (mm) WGS Models WGS 130140AW WGS 160190AW 24 “A” “B” “C” “D” 60.8 (1544.3) 38.1 (967.7) 95.0 (2413.0) 33.1 (840.7) 62.8 (1595.1) 39.6 (1005.8) 92.9 (2359.7) 32.7 (830.6) Center of Gravity Inches (mm) “E” “F” Additions for Sound Enclosure Inches (mm) “X” “Y” “Z” Length Width Height 26.1 19.7 (662.9) (500.4) 92.3 (2344.4) 32.3 (820.4) 16.8 (426.7) 4.0 (101.6) 2.5 (63.5) 3.0 (76.2) 25.7 21.7 (652.8) (551.2) 92.5 (2349.5) 32.5 (825.5) 16.7 (424.2) 4.0 (101.6) 2.5 (63.5) 5.0 (127.0) WGS 130A to 190A IMM1157-1 Physical Data WGS-AW, Water-Cooled Table 10, WGS-130AW - WGS-190AW WGS UNIT SIZE Unit capacity @ ARI conditions tons, (kW) (1) No. Circuits COMPRESSORS, Frame 3 Nominal Horsepower Number (2) % Minimum Capacity (Modulated) Oil Charge per Compressor oz., (l) CONDENSER Number No. Refrigerant Circuits Diameter, in., (mm) Tube Length, in., (mm) 130AW 140AW 160AW 170AW 190AW 130.0 (457.1) 140.7 (494.7) 156.7 (551.0) 169.6 (596.3) 182.1 (640.3) 2 2 2 2 2 65 1 65 1 65 1 80 1 80 1 80 1 80 1 95 1 95 1 95 1 15 256 (7.6) 13/17 256 (7.6) 15 256 (7.6) 14/16 256 (7.6) 15 256 (7.6) 2 1 12 (305) 120 (3048) 2 1 12 (305) 120 (3048) 2 1 12 (305) 120 (3048) 2 1 12 (305) 120 (3048) 2 1 12 (305) 120 (3048) Design W.P. psig, (kPa): Refrigerant Side 350 (2413) 350 (2413) 350 (2413) 350 (2413) 350 (2413) Water Side 150 (1034) 150 (1034) 150 (1034) 150 (1034) 150 (1034) No. of Passes 2 2 2 2 2 Pump-Out Capacity per Circuit, 330 (150) 330 (150) 330 (150) 296 (134) 296 (134) lb., (kg) (3) Connections: Water In & Out, in, (mm) victaulic 4.0 (101) 4.0 (101) 4.0 (101) 4.0 (101) 4.0 (101) Relief Valve, In., (mm) 0.5 (12.7) 0.5 (12.7) 0.5 (12.7) 0.5 (12.7) 0.5 (12.7) Purge Valve, Flare In., (mm) .625 (15.9) .625 (15.9) .625 (15.9) .625 (15.9) .625 (15.9) Vent & Drain, in. (mm) FPT 0.5 (12.7) 0.5 (12.7) 0.5 (12.7) 0.5 (12.7) 0.5 (12.7) Liquid Subcooling Integral Integral Integral Integral Integral EVAPORATOR Number 1 1 1 1 1 No. Refrigerant Circuits 2 2 2 2 2 Water Volume, gallons, (l) 68 (257) 68 (257) 115 (435) 115 (435) 115 (435) Refrig. Side D.W.P., psig, (kPa) 354 (2441) 354 (2441) 354 (2441) 354 (2441) 354 (2441) Water Side D.W.P., psig, (kPa) 152 (1048) 152 (1048) 152 (1048) 152 (1048) 152 (1048) Water Connections: Inlet & Outlet, in., (mm) victaulic 6.0 (152) 6.0 (152) 8.0 (203) 8.0 (203) 8.0 (203) Drain & Vent (NPT INT.) 0.5 0.5 0.5 0.5 0.5 UNIT DIMENSIONS (4) Length In., (mm) 169.9 (4315.5) 169.9 (4315.5) 169.9 (4315.5) 169.9 (4315.5) 169.9 (4315.5) Width In., (mm) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864) Height In., (mm) 74 (1880) 74 (1880) 75.5 (1918) 75.5 (1918) 75.5 (1918) UNIT WEIGHTS (5) Operating Weight, lb., (kg) 8557 (3881) 8557 (3881) 9314 (4225) 9505 (4311) 9505 (4311) Shipping Weight, lb., (kg) 7840 (3556) 7840 (3556) 8206 (3722) 8345 (3785) 8345 (3785) Operating Charge per Circuit, 127 (58) 127 (58) 128 (58) 124 (56) 124 (56) R-134a, lb., (kg) Notes: 1. Certified in accordance with ARI Standard 550/590-98. 2. All units have one compressor per circuit. 3. 80% full R-134a at 90°F (32°C) per refrigerant circuit. 4. Dimensions are without the optional sound enclosure. See dimension drawings for enclosure dimensions. 5. The optional sound enclosure adds 650 lbs (295 kg) to the shipping and operating weights. IMM1157-1 WGS 130A to 190A 25 WGS-AA Remote Condenser Table 11, WGS-130AA - WGS-190AA WGS UNIT SIZE 130AA 140AA 160AA 170AA 190AA Unit capacity @ 44F LWT, 116.0 (407.9) 125.9 (442.7) 136.1 (478.5) 148.0 (520.4) 160.1 (562.9) 125F SDT, tons, (kW) No. Circuits 2 2 2 2 2 COMPRESSORS, FRAME 3 Nominal Horsepower 65 65 65 80 80 80 80 95 95 95 Number (2) 1 1 1 1 1 1 1 1 1 1 % Minimum Capacity (Modulated) 15 13/17 15 14/16 15 Oil Charge per Compressor oz., (l) 256 (7.6) 256 (7.6) 256 (7.6) 256 (7.6) 256 (7.6) CONDENSER (Remote) EVAPORATOR Number 1 1 1 1 1 No. Refrigerant Circuits 2 2 2 2 2 Water Volume, gallons, (l) 68 (257) 68 (257) 115 (435) 115 (435) 115 (435) Refrig. Side D.W.P., psig, (kPa) 354 (2441) 354 (2441) 354 (2441) 354 (2441) 354 (2441) Water Side D.W.P., psig, (kPa) 152 (1048) 152 (1048) 152 (1048) 152 (1048) 152 (1048) Water Connections: Inlet & Outlet, in., (mm) victaulic 6.0 (152) 6.0 (152) 8.0 (203) 8.0 (203) 8.0 (203) Drain & Vent (NPT INT.) 0.5 0.5 0.5 0.5 0.5 UNIT DIMENSIONS (3) Length In., (mm) 179.3 (4554.2) 179.3 (4554.2) 179.3 (4554.2) 179.3 (4554.2) 179.3 (4554.2) Width In., (mm) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864) Height In., (mm) 60 (1524) 60 (1524) 61.8 (1570) 61.8 (1570) 61.8 (1570) UNIT WEIGHTS (4) Operating Weight, lb., (kg) 6265 (2841) 6265 (2841) 7022 (3185) 7022 (3185) 7022 (3185) Shipping Weight, lb., (kg) 5659 (2567) 5659 (2567) 6024 (2732) 6024 (2732) 6024 (2732) Operating Charge per Circuit, 35 (15.9) 35 (15.9) 36 (16.5) 36 (16.5) 36 (16.5) lb., (kg) R-134a Notes: 1. Certified in accordance with ARI Standard 550/590-98. 2. Dimensions are without the optional sound enclosure. See dimension drawings for enclosure dimensions. 3. The optional sound enclosure adds 650 lbs (295 kg) to the shipping and operating weights. 26 WGS 130A to 190A IMM1157-1 Unit Configuration The chiller unit has two refrigerant circuits, each with a single semi-hermetic rotary screw compressor, a shared two-circuited shell-and-tube evaporator, a water-cooled condenser, interconnecting refrigerant piping and refrigerant specialties. A single two-section control panel contains the control and starting equipment. Figure 14, Schematic Piping Diagram (One of Two Circuits) DISCHARGE TUBING DISCHARGE SHUT-OFF AND CHECK VALVE SCHRADER VALVE SUCTION SHUT-OFF VALVE (OPTIONAL) SCREW COMPRESSOR PRESSURE RELIEF VALVE CHARGING VALVE SCHRADER VALVE SUCTION TUBING WATER OUT PRESSURE RELIEF VALVE WATER IN ELECTRONIC EXPANSION VALVE DX EVAPORATOR PRESSURE RELIEF VALVE CHARGING VALVE SCHRADER VALVE WATER OUT WATER COOLED CONDENSER LIQUID TUBING WATER IN PACKAGE UNIT ONLY LIQUID SIGHT GLASS LESS CONDENSER UNIT ONLY FIELD DISCHARGE CONNECTION. FIELD LIQUID CONNECTION. SCHRADER VALVE (LESS CONDENSER ONLY) LIQUID FILTER DRYER LIQUID SHUT-OFF VALVE 330643901 -C010A WGS REFRIGERANT PIPING Components Table 12, Major Components Unit Size IMM1157-1 Compressor Size Frame 3200 Condenser Size Evaporator Size System #1 System #2 System #1 System #2 130A Small Small EV40271212 C1210-101 C1210-101 140A Small Medium EV40271212 C1210-101 C1210-101 160A Medium Medium EV50271313 C1210-101 C1210-101 170A Medium Large EV50271313 C1210-121 C1210-121 190A Large Large EV50271313 C1210-121 C1210-121 WGS 130A to 190A 27 Wiring Field Wiring, Power The WGS “A” vintage chillers are built standard with: Multi-point (2) power supply to a terminal block per circuit with no compressor isolation circuit breakers. Optional power connections include: Multi-point power connection to a non-fused disconnect switches with through-thedoor handle mounted in the control box in lieu of the power block Multi-point power connection to high interrupt rated disconnect switches with throughthe-door handle Multi-point power connection to high interrupt disconnect switches with through-thedoor handle in a high short circuit current rated panel Single point power connection to a terminal block with individual compressor isolation circuit breakers per circuit Single point power connection to high interrupt circuit breakers with through-the-door handles and with individual compressor isolation circuit breakers per circuit Single point power connection to a high interrupt rated disconnect switch in a high short circuit current rated panel and with individual compressor isolation circuit breakers per circuit. A factory installed control circuit transformer is standard. Optionally, a field-installed control power source can be wired to the unit. Circuit breakers for backup compressor short circuit protection are standard on all units. Wiring and conduit selections must comply with the National Electrical Code and/or local requirements. An open fuse indicates a short, ground, or overload. Before replacing a fuse or restarting a compressor, the trouble must be found and corrected. Tables in the Electrical Data section (page 30) give specific information on recommended wire sizes. NOTE: Use only copper conductors in main terminal block. Terminations are sized for copper only. Field Wiring, Control A factory-mounted control transformer is provided to supply the correct control circuit voltage. The transformer power leads are connected to the power block PB1 or disconnect switch DS1. Interlock Wiring, Condenser Pump Starter or Air-Cooled Condenser Fan Starter The MicroTech II controller can interlock a condenser pump starter, and tower fans, and control a tower bypass valve on water-cooled units. Up to six air-cooled condenser fan contactors per circuit can be controlled by the MicroTech II unit controller on remote condenser applications. Pressure switches supplied with the condenser can also control condenser fan operation. Coil voltage must be 115 volts with a maximum of 20 VA. An evaporator and condenser (water-cooled units only) flow switch is necessary on all units. It is also advisable to wire a chilled water pump interlock in series with the flow switch for additional evaporator freeze protection. 28 WGS 130A to 190A IMM1157-1 Ambient Air Sensor Units with a remote air-cooled condenser will have an outdoor air sensor furnished with the unit inside the control panel and wired to the correct terminals. It must be installed outdoors in a location that will give the true outdoor temperature that the condenser coils will see. Splicing of the sensor lead may be required. The sensor must be installed for the unit to operate. BAS Interface Connection to the chiller for all building automation systems (BAS) protocols is at the unit controller. An optional interface module, depending on the protocol being used, may have been factory-installed in the unit controller (or it can be field installed). Protocols Supported Table 13, Standard Protocol Data Protocol Physical Layer Data Rate Controller Other BACnet/IP or BACnet/Ethernet Ethernet 10 Base-T 10 Megabits/sec MicroTech II Reference ED 15062 BACnet MSTP RS-485 MicroTech II Reference ED 15062 MicroTech II Reference ED 15062 MicroTech II Reference ED 15063 LONWORKS Modbus RTU FTT-10A RS-485 or RS-232 9600, 19200 or 38400 bits/sec 78kbits/sec 9600 or 19200 bits/sec The interface kits on the MicroTech II controller are as follows: BACnet Kit P/N 350147404: BACnet/IP, BACnet MS/TP, or BACnet Ethernet LONWORKS Units equipped with a pCo2 (with DIP switches) for CP1 require Kit P/N 350147401. Units equipped with a pCo3 (no DIP switches) for CP1 require Kit P/N 350147409. Modbus: Modbus RTU Optional Open Choices™ BAS interfaces. The locations and interconnection requirements for the various standard protocols are found in their respective installation manuals. Modbus IM 743-2 LONWORKS IM 735-2 BACnet IM 736-2 Referenced documents may be obtained from the local Daikin Applied sales office, from the local Daikin Applied service office, or from the Daikin Technical Response Center, located in Staunton, Virginia (540-248-0711). These documents can also be found on www.DaikinApplied.com under Product Information > (chiller type) > Control Integration. The following are trademarks or registered trademarks of their respective companies: BACnet from the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., LonTalk, LONMARK and LONWORKS from Echelon Corporation, and Modbus and Modbus RTU from Schneider Electric. Remote Operator Interface Panel The box containing the optional remote interface panel will have installation instructions, IOM MT II Remote, shipped with it. The manual is also available for downloading from www.DaikinApplied.com. IMM1157-1 WGS 130A to 190A 29 Electrical Data Table 14, Electrical Data, Water-cooled, Single-Point Connection WGS UNIT SIZE 130AW 140AW 160AW 170AW 190AW VOLTS 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 POWER SUPPLY FIELD WIRE MINIMUM CIRCUIT AMPACITY (MCA) QTY n/a n/a 243 201 162 n/a n/a 253 209 169 n/a n/a 261 216 174 n/a n/a 276 228 182 n/a n/a 288 237 189 n/a n/a 3 3 3 n/a n/a 3 3 3 n/a n/a 3 3 3 n/a n/a 3 3 3 n/a n/a 3 3 3 MIN. WIRE GAUGE n/a n/a 250 4/0 2/0 n/a n/a 250 4/0 2/0 n/a n/a 300 4/0 2/0 n/a n/a 300 4/0 3/0 n/a n/a 350 250 3/0 FIELD FUSE SIZE or BREAKER SIZE RECOMMENDED n/a n/a 300 225 200 n/a n/a 300 250 200 n/a n/a 300 250 200 n/a n/a 350 300 225 n/a n/a 350 300 225 MAXIMUM n/a n/a 350 250 225 n/a n/a 350 300 225 n/a n/a 350 300 250 n/a n/a 400 300 250 n/a n/a 400 300 250 Notes 1. Table based on 75°C field wire. 2. Complete notes are on page 40. 30 WGS 130A to 190A IMM1157-1 Table 15, Electrical Data, Water-cooled, Multiple-Point Connection WGS UNIT SIZE 130AW 140AW 160AW 170AW 190AW ELECTRICAL CIRCUIT 1 (COMP 1) ELECTRICAL CIRCUIT 2 (COMP 2) POWER FIELD FUSING FIELD FUSING MINIMUM MINIMUM POWER SUPPLY SUPPLY VOLTS CIRCUIT FIELD WIRE CIRCUIT REC MAX REC MAX FIELD WIRE AMPS AMPS FUSE FUSE FUSE FUSE MIN. WIRE MIN.WIRE (MCA) QTY (MCA) QTY SIZE SIZE SIZE SIZE GAUGE GAUGE 208 247 3 250 300 400 247 3 250 300 400 230 223 3 4/0 300 400 223 3 4/0 300 400 380 135 3 1/0 175 225 135 3 1/0 175 225 460 112 3 2 150 200 112 3 2 150 200 575 90 3 3 110 150 90 3 3 110 150 208 247 3 250 300 400 267 3 300 350 450 230 223 3 4/0 300 400 240 3 250 300 400 380 135 3 1/0 175 225 145 3 1/0 175 250 460 112 3 2 150 200 120 3 1 150 200 575 90 3 3 110 150 97 3 3 125 150 208 267 3 300 350 450 267 3 300 350 450 230 240 3 250 300 400 240 3 250 300 400 380 145 3 1/0 175 250 145 3 1/0 175 250 460 120 3 1 150 200 120 3 1 150 200 575 97 3 3 125 150 97 3 3 125 150 208 267 3 300 350 450 292 3 350 350 500 230 240 3 250 300 400 263 3 300 350 450 380 145 3 1/0 175 250 160 3 2/0 200 250 460 120 3 1 150 200 132 3 1/0 175 225 575 97 3 3 125 150 105 3 2 150 175 208 292 3 350 350 500 292 3 350 350 500 230 263 3 300 350 450 263 3 300 350 450 380 160 3 2/0 200 250 160 3 2/0 200 250 460 132 3 1/0 175 225 132 3 1/0 175 225 575 105 3 2 150 175 105 3 2 150 175 NOTES: 1. Table based on 75°C field wire. 2. Complete notes are on page 40. 3. 3/0 wire is required for the disconnect switch option, 2/0 may be used for power block connection. IMM1157-1 WGS 130A to 190A 31 Table 16, Electrical Data, Remote Condenser, Single-Point Connection WGS UNIT SIZE 130AA 140AA 160AA 170AA 190AA VOLTS MINIMUM CIRCUIT AMPACITY (MCA) 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 n/a n/a n/a 252 192 n/a n/a n/a 265 203 n/a n/a n/a 275 212 n/a n/a n/a 299 236 n/a n/a n/a 318 255 POWER SUPPLY FIELD WIRE MIN. WIRE QTY GAUGE n/a n/a n/a n/a n/a n/a 3 250 MCM 3 3/0 AWG n/a n/a n/a n/a n/a n/a 3 300 MCM 3 4/0 AWG n/a n/a n/a n/a n/a n/a 3 300 MCM 3 4/0 AWG n/a n/a n/a n/a n/a n/a 3 350 MCM 3 250 MCM n/a n/a n/a n/a n/a n/a 3 (2) 250 MCM 3 250 MCM FIELD FUSE SIZE or BREAKER SIZE RECOMMAXIMUM MENDED n/a n/a n/a n/a n/a n/a 300 350 225 250 n/a n/a n/a n/a n/a n/a 300 350 250 250 n/a n/a n/a n/a n/a n/a 350 350 250 300 n/a n/a n/a n/a n/a n/a 350 400 300 300 n/a n/a n/a n/a n/a n/a 400 450 300 350 Notes 1. Table based on 75°C field wire. 2. Complete notes are on page 40. 32 WGS 130A to 190A IMM1157-1 Table 17, Electrical Data, Remote Condenser, Multiple-Point Connection WGS UNIT SIZE 130AA 140AA 160AA 170AA 190AA ELECTRICAL CIRCUIT 1 (COMP 1) ELECTRICAL CIRCUIT 2 (COMP 2) POWER POWER FIELD FUSING MINIMUM FIELD FUSING MINIMUM SUPPLY SUPPLY VOLTS CIRCUIT CIRCUIT FIELD WIRE FIELD WIRE REC. MAX REC. MAX AMPS AMPS FUSE FUSE FUSE FUSE MIN.WIRE MIN. WIRE (MCA) QTY (MCA) QTY SIZE SIZE SIZE SIZE GAUGE GAUGE 208 290 3 350 350 500 290 3 350 350 500 230 263 3 300 350 450 263 3 300 350 450 380 160 3 2/0 200 250 160 3 2/0 200 250 460 140 3 1/0 175 250 140 3 1/0 175 250 575 107 3 2 150 175 107 3 2 150 175 208 290 3 350 350 500 334 3 400 450 600 230 263 3 300 350 450 300 3 350 400 500 380 160 3 2/0 200 250 182 3 3/0 225 300 460 140 3 1/0 175 250 153 3 2/0 200 250 575 107 3 2 150 175 118 3 1 150 200 208 334 3 2-250 450 600 334 3 2-250 450 600 230 300 3 350 400 500 300 3 350 400 500 380 182 3 3/0 225 300 182 3 3/0 225 300 460 153 3 2/0 200 250 153 3 2/0 200 250 575 118 3 1 150 200 118 3 1 150 200 208 334 3 2-250 450 600 390 6 2-250 500 700 230 300 3 350 400 500 353 3 2-250 450 600 380 182 3 3/0 225 300 223 3 4/0 300 400 460 153 3 2/0 200 250 177 3 3/0 225 300 575 118 3 1 150 200 142 3 1/0 175 250 208 390 6 2-250 500 700 390 6 2-250 500 700 230 353 3 2-250 450 600 353 3 2-250 450 600 380 223 3 4/0 300 400 223 3 4/0 300 400 460 177 3 3/0 225 300 177 3 3/0 225 300 575 142 3 1/0 175 250 142 3 1/0 175 250 NOTES: 1. Table based on 75°C field wire. 2. Complete notes are on page 40. 3. 3/0 wire is required for the disconnect switch option, 2/0 may be used for power block connection. IMM1157-1 WGS 130A to 190A 33 Table 18, Water-cooled, Compressor Amp Draw WGS UNIT SIZE 130AW 140AW 160AW 170AW 190AW 34 RATED LOAD AMPS VOLTS 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 CIRCUIT #1 CIRCUIT #2 197 178 108 89 72 197 178 108 89 72 213 192 116 96 77 213 192 116 96 77 233 210 128 105 84 197 178 108 89 72 213 192 116 96 77 213 192 116 96 77 233 210 128 105 84 233 210 128 105 84 WGS 130A to 190A Table 19, Remote Condenser, Compressor Amp Draw WGS UNIT SIZE 130AA 140AA 160AA 170AA 190AA RATED LOAD AMPS VOLTS 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 CIRCUIT #1 CIRCUIT #2 232 210 128 112 85 232 210 128 112 85 267 240 145 122 94 267 240 145 122 94 312 282 178 141 113 232 210 128 112 85 267 240 145 122 94 267 240 145 122 94 312 282 178 141 113 312 282 178 141 113 IMM1157-1 Table 20, Water-cooled, Field Wiring Information with Single-Point Power WGS UNIT SIZE 130AW 140AW 160AW 170AW 190AW WIRING TO STANDARD UNIT POWER BLOCK VOLTS 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 TERMINAL SIZE AMPS n/a n/a 400 400 400 n/a n/a 400 400 400 n/a n/a 400 400 400 n/a n/a 400 400 400 n/a n/a 400 400 400 CONNECTOR LUG RANGE PER PHASE (COPPER WIRE ONLY) n/a n/a #6-350 #6-350 #6-350 n/a n/a #6-350 #6-350 #6-350 n/a n/a #6-350 #6-350 #6-350 n/a n/a #6-350 #6-350 #6-350 n/a n/a #6-350 #6-350 #6-350 WIRING TO OPTIONAL NONFUSED DISCONNECT SWITCH IN UNIT CONNECTOR LUG RANGE SIZE PER PHASE AMPS (COPPER WIRE ONLY) n/a n/a n/a n/a 400 3/0-500 250 #6-350 250 #6-350 n/a n/a n/a n/a 400 3/0-500 250 #6-350 250 #6-350 n/a n/a n/a n/a 400 3/0-500 250 #6-350 250 #6-350 n/a n/a n/a n/a 400 3/0-500 250 #6-350 250 #6-350 n/a n/a n/a n/a 400 3/0-500 250 #6-350 250 #6-350 Table 21, Remote Condenser, Field Wiring Information with Single-Point Power WGS UNIT SIZE 130AA 140AA 160AA 170AA 190AA IMM1157-1 WIRING TO STANDARD UNIT POWER BLOCK VOLTS 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 TERMINAL SIZE AMPS n/a n/a n/a 400 400 n/a n/a n/a 400 400 n/a n/a n/a 400 400 n/a n/a n/a 400 400 n/a n/a n/a 400 400 CONNECTOR LUG RANGE PER PHASE (COPPER WIRE ONLY) n/a n/a n/a #6-350 #6-350 n/a n/a n/a #6-350 #6-350 n/a n/a n/a #6-350 #6-350 n/a n/a n/a #6-350 #6-350 n/a n/a n/a #6-350 #6-350 WIRING TO OPTIONAL NONFUSED DISCONNECT SWITCH IN UNIT CONNECTOR LUG RANGE SIZE PER PHASE AMPS (COPPER WIRE ONLY) n/a n/a n/a n/a n/a n/a 400 3/0-500 250 #6-350 n/a n/a n/a n/a n/a n/a 400 3/0-500 250 #6-350 n/a n/a n/a n/a n/a n/a 400 3/0-500 250 #6-350 n/a n/a n/a n/a n/a n/a 400 3/0-500 250 #6-350 n/a n/a n/a n/a n/a n/a 400 3/0-500 400 3/0-500 WGS 130A to 190A 35 Table 22, Water-cooled, Field Wiring to Multiple-Point Power Block WIRING TO UNIT POWER BLOCK CONNECTOR WIRE RANGE PER VOLTS TERMINAL SIZE (AMPS) PHASE (COPPER WIRE ONLY) CKT 1 CKT 2 CKT 1 CKT 2 #6-350 #6-350 208 400 400 #6-350 #6-350 230 400 400 #6-350 #6-350 130AW 380 400 400 #6-350 #6-350 460 400 400 #6-350 #6-350 575 400 400 #6-350 #6-350 208 400 400 #6-350 #6-350 230 400 400 #6-350 #6-350 140AW 380 400 400 #6-350 #6-350 460 400 400 #6-350 #6-350 575 400 400 #6-350 #6-350 208 400 400 #6-350 #6-350 230 400 400 #6-350 #6-350 160AW 380 400 400 #6-350 #6-350 460 400 400 #6-350 #6-350 575 400 400 #6-350 #6-350 208 400 400 #6-350 #6-350 230 400 400 #6-350 #6-350 170AW 380 400 400 #6-350 #6-350 460 400 400 #6-350 #6-350 575 400 400 #6-350 #6-350 208 400 400 #6-350 #6-350 230 400 400 190AW #6-350 #6-350 380 400 400 #6-350 #6-350 460 400 400 #6-350 #6-350 575 400 400 WGS UNIT SIZE Table 23, Remote Condenser, Field Wiring to Multiple-Point Power Block WIRING TO UNIT POWER BLOCK CONNECTOR WIRE RANGE PER VOLTS TERMINAL SIZE (AMPS) PHASE (COPPER WIRE ONLY) CKT 1 CKT 2 CKT 1 CKT 2 #6-350 #6-350 208 400 400 #6-350 #6-350 230 400 400 #6-350 #6-350 130AA 380 400 400 #6-350 #6-350 460 400 400 #6-350 #6-350 575 400 400 #6-350 #6-350 208 400 400 #6-350 #6-350 230 400 400 #6-350 #6-350 140AA 380 400 400 #6-350 #6-350 460 400 400 #6-350 #6-350 575 400 400 #6-350 #6-350 208 400 400 #6-350 #6-350 230 400 400 #6-350 #6-350 160AA 380 400 400 #6-350 #6-350 460 400 400 #6-350 #6-350 575 400 400 #6-350 #6-350 208 400 400 #6-350 #6-350 230 400 400 #6-350 #6-350 170AA 380 400 400 #6-350 #6-350 460 400 400 #6-350 #6-350 575 400 400 #6-350 #6-350 208 400 400 #6-350 #6-350 230 400 400 #6-350 #6-350 190AA 380 400 400 #6-350 #6-350 460 400 400 #6-350 #6-350 575 400 400 WGS UNIT SIZE 36 WGS 130A to 190A IMM1157-1 Table 24, Water-cooled , Field Wiring to Multiple-Point Disconnect Switc WGS UNIT SIZE 130AW 140AW 160AW 170AW 190AW VOLTS 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 WIRING TO UNIT DISCONNECT SWITCH TERMINAL SIZE CONNECTOR WIRE RANGE PER PHASE (AMPS) (COPPER WIRE ONLY) CKT 1 CKT 2 CKT 1 CKT 2 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 400 #6-350 3/0-500 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 250 #6-350 #6-350 400 400 3/0-500 3/0-500 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 250 #6-350 #6-350 400 400 3/0-500 3/0-500 250 400 #6-350 3/0-500 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 250 #6-350 #6-350 400 400 3/0-500 3/0-500 400 400 3/0-500 3/0-500 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 250 #6-350 #6-350 Table 25, Remote Condenser, Field Wiring to Multiple-Point Disconnect Switch WGS UNIT SIZE 130AA 140AA 160AA 170AA 190AA IMM1157-1 VOLTS 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 208 230 380 460 575 WIRING TO UNIT DISCONNECT SWITCH TERMINAL SIZE CONNECTOR WIRE RANGE PER PHASE (AMPS) (COPPER WIRE ONLY) CKT 1 CKT 2 CKT 1 CKT 2 400 400 3/0-500 3/0-500 400 400 3/0-500 3/0-500 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 250 #6-350 #6-350 400 400 3/0-500 3/0-500 400 400 3/0-500 3/0-500 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 250 #6-350 #6-350 400 400 3/0-500 3/0-500 400 400 3/0-500 3/0-500 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 250 #6-350 #6-350 400 400 3/0-500 3/0-500 400 400 3/0-500 3/0-500 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 250 #6-350 #6-350 400 400 3/0-500 3/0-500 400 400 3/0-500 3/0-500 250 250 #6-350 #6-350 250 250 #6-350 #6-350 250 250 #6-350 #6-350 WGS 130A to 190A 37 Wiring Diagrams Figure 15, WGS 130AW – 190AW Field Wiring Diagram UNIT MAIN DISCONNECT (BY OTHERS) TERMINAL BLOCK GND LUG 3 PHASE TO COMPRESSOR(S) POWER SUPPLY FUSED CONTROL CIRCUIT TRANSFORMER FU4 FU5 120 VAC NOTE: ALL FIELD WIRING TO BE INSTALLED AS NEC CLASS 1 WIRING SYSTEM WITH CONDUCTOR RATED 600 VOLTS FU7 TB1 (115 VAC) TB1-2 ALARM BELL RELAY 1 BELL 2 1 EVAP. PUMP RELAY #1 (BY OTHERS) 120 VAC 1.0 AMP MAX 2 N 120 VAC 85 CHWR EVAP. PUMP RELAY #2 (BY OTHERS) 120 VAC 1.0 AMP MAX 2 N 120 VAC 86 CWR COND. PUMP RELAY #1 (BY OTHERS) 120 VAC 1.0 AMP MAX 2 87 CWR COND. PUMP RELAY #2 (BY OTHERS) 120 VAC 1.0 AMP MAX M11 TOWER FAN #1 (BY OTHERS) 120 VAC 1.0 AMP MAX 2 88 2 N 120 VAC N 120 VAC N 120 VAC 89 M12 TOWER FAN #2 (BY OTHERS) 120 VAC 1.0 AMP MAX 2 78 77 COOLING TOWER BYPASS (BY OTHERS) 80 FACTORY SUPPLIED ALARM FIELD WIRED ALARM BELL OPTION (BY OTHERS) 79 ABR 81 ALARM BELL RELAY ICE MODE SWITCH (BY OTHERS) OFF AUTO MANUAL OFF AUTO ON N 0-10VDC N 24 VAC NOR. OPEN PUMP AUX. CONTACTS (OPTIONAL) NOR. OPEN PUMP AUX. CONTACTS (OPTIONAL) *MANDATORY IF FACTORY FLOW SWITCH OPTION IS NOT SELECTED 4-20MA FOR + EVAP. WATER RESET (BY OTHERS) 4-20MA FOR DEMAND LIMIT (BY OTHERS) 60 66 897 IF REMOTE STOP CONTROL IS USED, REMOVE LEAD 897 FROM TERM. 40 TO 53. 60 *MANDATORY IF FACTORY FLOW SWITCH OPTION IS NOT SELECTED COND. FLOW SWITCH (BY OTHERS) 0-10VDC TB1 (24 VAC OR 30 VDC) ON MANUAL EVAP. FLOW SWITCH (BY OTHERS) N 75 TIME CLOCK REMOTE STOP SWITCH (BY OTHERS) NO 120 VAC 82 CHWR COM 2 ALARM BELL OPTION + - 68 60 67 60 76 72 70 71 70 DWG. 330588201 REV. 0B GND 38 WGS 130A to 190A IMM1157-1 Figure 16, WGS 130AA – 190AA Field Wiring Diagram (Remote Condenser) UNIT MAIN DISCONNECT (BY OTHERS) TERMINAL BLOCK GND LUG 3 PHASE TO COMPRESSOR(S) POWER SUPPLY FUSED CONTROL CIRCUIT TRANSFORMER FU4 FU5 120 VAC NOTE: ALL FIELD WIRING TO BE INSTALLED AS NEC CLASS 1 WIRING SYSTEM WITH CONDUCTOR RATED 600 VOLTS FU7 TB1 (115 VAC) TB1-2 ALARM BELL RELAY 1 BELL 2 CHWR EVAP. PUMP RELAY #1 (BY OTHERS) 120 VAC 1.0 AMP MAX CHWR EVAP. PUMP RELAY #2 (BY OTHERS) 120 VAC 1.0 AMP MAX FACTORY SUPPLIED ALARM FIELD WIRED ALARM BELL OPTION ABR 120 VAC 82 N 2 120 VAC 85 N 2 24 VAC 81 ALARM BELL RELAY COM NO 2 ALARM BELL OPTION 1 75 CIRCUIT #1 CIRCUIT #2 TB6 M11 92 98 145 CONDENSER FAN CONTACTOR COIL #193 M12 98 146 145 CONDENSER FAN CONTACTOR COIL #294 M13 TB7 144 98 148 145 CONDENSER FAN CONTACTOR COIL #3 95 M14 98 CONDENSER FAN CONTACTOR COIL #4 96 M15 98 CONDENSER FAN CONTACTOR COIL #597 M16 98 120 VAC NO1 N 2 N 2 NO3 2 C J12 120 VAC N (LOCATED ON CIRCUIT CONTROLLER) 98 M22 98 145 152 145 154 145 CONDENSER FAN CONTACTOR COIL #6 NO4 245 2 N M24 120 VAC NO5 N 2 NO6 2 95 120 VAC J13 (LOCATED ON CIRCUIT CONTROLLER) 98 98 M26 ON 254 120 VAC NO1 2 N 120 VAC NO2 2 N 120 VAC NO3 2 C N C NO4 2 120 VAC N 120 VAC NO5 2 N J13 (LOCATED ON CIRCUIT CONTROLLER) 120 VAC NO6 2 J12 (LOCATED ON CIRCUIT CONTROLLER) N TB1 (24 VAC) 60 MANUAL 97 245 CONDENSER FAN CONTACTOR COIL #6 OFF AUTO 252 245 CONDENSER FAN CONTACTOR COIL #5 120 VAC REMOTE STOP SWITCH (BY OTHERS) 96 98 M25 250 245 CONDENSER FAN CONTACTOR COIL #4 N TIME CLOCK 897 66 IF REMOTE STOP CONTROL IS USED, REMOVE LEAD 897 FROM TERM. 40 TO 53. OFF AUTO ICE MODE SWITCH (BY OTHERS) EVAP. FLOW SWITCH (BY OTHERS) 248 CONDENSER FAN CONTACTOR COIL #3 C 150 246 245 CONDENSER FAN CONTACTOR COIL #294 M23 244 245 CONDENSER FAN CONTACTOR COIL #193 120 VAC NO2 92 98 M21 ON 60 MANUAL NOR. OPEN PUMP AUX. CONTACTS (OPTIONAL) *MANDATORY IF FACTORY FLOW SWITCH OPTION IS NOT SELECTED. 4-20MA FOR EVAP. WATER RESET (BY OTHERS) 4-20MA FOR DEMAND LIMIT (BY OTHERS) + - + - 68 60 67 72 70 71 70 GND DWG. 330588101 REV. 0C See notes on page 40. IMM1157-1 WGS 130A to 190A 39 Notes for “Electrical Data Single/Multiple Point” Power: 1. Wire sizing amps is 10 amps if a separate 115V power supply is used. 2. Unit wire size ampacity is equal to 125% of the largest compressor motor, plus 100% of the RLA of all other loads in the circuit, including the control transformer. 3. Recommended power lead wire sizes for 3 conductors per conduit are based on 100% conductor ampacity in accordance with NEC. Voltage drop has not been included. Therefore, power leads should be kept short. All terminal block connections must be made with copper (type THW) wire. 4. The recommended power lead wire sizes are based on an ambient temperature of 86°F (30°C). Ampacity correction factors must be applied for other ambient temperatures. Refer to the National Electrical Code Handbook. 5. The recommended fuse size or HACR circuit breaker size is equal to 150% of the largest compressor motor RLA plus 100% of the remaining compressor RLA. 6. The maximum fuse size or HACR circuit breaker size is equal to 225% of the largest compressor motor RLA plus 100% of the remaining compressor RLA. 7. Must be electrically grounded according to national and local electrical codes. Power Limitations: 1. Voltage within 10 percent of nameplate rating. 2. Voltage unbalance not to exceed 2% with a resultant current unbalance of 6 to 10 times the voltage unbalance per NEMA MG-1, 1998 Standard. This is an important requirement and must be adhered to. Notes for “Electrical Data” 1. Requires a disconnect switch per circuit to supply electrical power to the unit. If field supplied, this power supply must either be fused or use an HACR type circuit breaker. 2. Use copper wiring to unit power block or optional non-fused disconnect switch. 3. All field wire size values given in table apply to 75°C rated wire per NEC. Notes for Wiring Diagram Remote Condenser Units On remote condenser units, head pressure control by cycling fans can be accomplished several ways. The MicroTech II controller in the unit can be used. It senses discharge pressure and will stage up to 6 condenser fans when wired in accordance with Figure 16 on page 39. If the condenser has more than 6 fans, 2 can be operated on a step. For example, a condenser with 10 fans would have 2 fans on steps #1 through #4 and one fan each on steps #5 and #6. Condensers with less than 6 fans would use the appropriate MicroTech II steps beginning with #1. Wire so that the first-on, last-off fan stage has one fan on it. The Daikin ACD condensers have unit-mounted and wired single fan motor VFD combined with fan cycling by pressure switches for the balance of the fans available as an option. They can be used for staging fans instead of the WGS MicroTech II controller. See Ambient Air Sensor note on page 29. Circuit Breakers The circuit breaker used in the High Short Circuit panel option may have a higher trip rating than the unit Maximum Overload Protection (MOP) value shown on the unit nameplate. The circuit breaker is installed as a service disconnect switch and does not function as branch circuit protection, mainly that the protection device must be installed at the point of origin of the power wiring. The breaker (disconnect switch) is oversized to avoid nuisance trips at high ambient temperature conditions. 40 WGS 130A to 190A IMM1157-1 Figure 17, Schematic Diagram Legend Designation IMM1157-1 Description Standard Location Designation Description Standard Location ABR Alarm Bell Relay Field Mounted M12 Tower Fan 1 Field Mounted BB Bias Block Outer Panel PB1 / 2 Power Block Inner Panel CB1 / 2 Circuit Breaker Inner Panel REC 115V Outlet (Optional) Outer Panel CB11 / 211 Circuit Controller Output Breaker Output Panel RS1 Remote Stop Switch Field Mounted CB12 / 22 Circuit Controller Compr. Heater Output Panel S1 System Shut-Off Switch Outer Panel CHW1 Chilled Water Flow Switch Field Mounted S01 Suction Pressure Compressor CHWR Chilled Water Relay Field Mounted S02 Discharge Pressure Compressor CWR Cond. Water Relay Field Mounted S03 Liquid Pressure Liquid Line CWI Cond. Water Flow Switch Field Mounted S04 Suction Temperature Compressor Cir. Contr. 1 / 2 Circuit Controller Outer Panel S05 Discharge Temperature Compressor Compr 1 / 2 Compressors Behind Control Box S06 Liquid Temperature Liquid Line DS ½ Disconnect Switch Inner Panel S07 Outside Ambient Temperature Behind Control Box FU4 T1 Primary Fuse Inner Panel S08 Leaving Water Sensor Leaving Water Nozzle FU5 T1 Primary Fuse Inner Panel S09 Entering Water Temperature Entering Water Nozzle FU6 T1 Secondary Fuse Inner Panel S10 Demand Limit Reset Field Mounted FU7 T1 Secondary Fuse Inner Panel S11 Leaving Water Reset Field Mounted F3 115v Outlet Fuse (Optional) Cir. #2 Outer Panel CS Circuit System Switch Outer Panel GRD Ground Inner Panel Load/Unload Load/Unload Solenoid Compressor Htr-Compr Compressor Heater Compressor T1 Control Transformer Inner Panel Outer Panel MHP High Pressure Switch Compressor T2 Unit Contr. 24V Transformer MHPR Mechanical High Pressure Relay Outer Panel T13 / T23 Circuit Contr. 24V Transformer Outer Panel MS1 Mode Switch Field Mounted T14 / T24 Comp. Load/Unload 24V Transformer Outer Panel SSS ½ Comp. Solid State Starter Inner Panel T15 / T25 EXV Driver 24V Transformer Outer Panel MJ Mechanical Jumper Control Box TB1 – TB2 Terminal Blocks Outer Panel M11 Tower Fan 2 Field Mounted WJ Wire Jumper Control Box WGS 130A to 190A 41 Figure 18, WGS 130 - 190, Circuit Controller Schematic Wiring Diagram (SEE LINE 693) TO T15 116 114 1 T13 120V 2 5 24V 6 113 20 40 120 121 139 (SEE LINE 687) MJ MJ 40 123 122 GO J1 G EVAP PRESS TRANSDUCER (S01) 0-5 VDC RED WHT BLK 0-5 VDC RED WHT BLK J1 CONDENSER PRESS TRANSDUCER (S02) J2 J2 J3 BIAS 5 BIAS 6 SLIDE LOAD INDICATOR 21 VDC DC GROUND 1 2 25 26 882 883 3 137 138 3 J4 1 J5 1 J11 SUCTION TEMP. (S04) DISCHARGE TEMP. (S05) BLK RED B120 OHMS B4 BC4 B5 J3 BC5 BLK RED A+ GND PE SHIELD 124 VG 125 VGD C1 Y1 J4 Y2 0-10VDC EXV DRIVER 126 NO1 Y3 (SEE DETAIL 1) J12 Y4 D3 SA- BLACK SB+ WHITE A+ GREEN B- SCOM SHLD GND NO2 NO3 C1 CIRCUIT SWITCH 127 128 WJ ID1 CS ID2 C4 ID3 NO4 FLT STARTER FAULT 164 165 TB1-6 TB1-7 PE GRN DIFFERENTIAL PRESSURE SWITCH J5 DPS BLK WHT C 21 129 ID5 131 ID6 1 MHPR MECHANICAL HIGH PRESSURE FAULT 130 2 4 ID7 ID8 132 IDC1 D I GIT A L O UT P U T S ID4 J13 NO5 NO6 C4 C7 J14 NO7 B6 C7 B7 NO8 MJ SLIDE LOAD INDICATOR MJ 24 4-20MA 3 133 J6 CONDENSER LEAVING WATER TEMP. (S12) BLK RED J15 B8 134 GND NC8 22 3 20 2 PE 135 C8 ID9 C9 ID10 NO9 OLS 1 GREEN J16 COMPRESSOR SSS CONTACT NO10 ID11 J7 NO11 DETAIL 2 - THERMISTOR CARD 136 IDC9 NO12 J3-2 1 ID13H 2 J17 ID13 LP* REMOTE EVAP. ONLY. IN SERIES WITH 170 IDC13 ID14 42 188 171 170 NOTES: OIL SEP. HEATER C9 40 MOTOR GUARDISTOR J3-1 ID12 1) * - REPRESENTS CIRCUIT 2) ONE HUNDRED SERIES FOR CIRCUIT #1 3) TWO HUNDRED SERIES FOR CIRCUIT #2 WGS 130A to 190A C12 NC12 J8 NO13 J18 ID14H C13 NC13 (LOWER LEVEL) CONTROLLER IMM1157-1 Schematic Wiring Diagram (Continued) LINE NO. -601 -602 -603 TB1 1 105, 114, 116, 160 -604 -605 1 2 180 -606 -607 2 2 101, 113, 117,183 161, 187 177 -608 -609 3 4 181, MHP-1 182, 184, MHP-2 -610 -611 20 20 122, 124 127, BLK, 130, 2-OIL -612 -613 21 22 WHT, 129 3-OIL, 135 -614 -615 24 25 3-SLIDE, 133 -616 -617 26 27 -618 -619 28 30 172, 1-LOAD 173, 1-UNLOAD 176, 177 -620 -621 49 40 188, 189 123, 125 -622 -623 40 40 RED, 1-OIL, 136, 139 -624 -625 50 90 (RESISTOR USED ONLY AT END OF DAISY CHAIN) -626 -627 91 92 93 144 146 WHITE -628 -629 94 95 148 150 96 97 152 1 T1 115V 102 2 NB 103 FU7 105 1 101 (SEE LINE 694) 2 117 MJ (p LAN) TO OTHER CIRCUIT CONTROLLERS AND UNIT CONTROLLER BLACK GROUND -630 -631 (TERMINATE AT EACH CONTROLLER) CB11 1 TERMINAL BLOCK AND LEAD NUMBERS MHP 3 180 -632 -633 MHPR 4 181 182 1 -634 -635 183 2 0 1 -636 -637 184 92 PE PE 132, 134, RED 163, 2-LOAD, 2-UNLOAD, 190 170 171 154 GRN - OIL GRN - DPS GRN - LOAD GRN - UNLOAD -638 -639 98 144 PE PE 1-SLIDE, 137 2-SLIDE, 138 M*1 -640 -641 93 M*2 146 -642 -643 94 148 -644 -645 M*3 -646 -647 -648 -649 -650 -651 95 150 -652 -653 -654 -655 M*4 96 152 M*5 -656 -657 97 154 M*6 REMOTE COND. -658 -659 T14 1 120V 160 5 162 24V 161 -660 -661 163 -662 -663 2 6 -664 -665 -666 -667 PE (SEE LINE 690) 185 27 172 1 -668 -669 GRN 1 2 SV LOAD SOLENOID -670 -671 2 -672 -673 PE GRN 1 28 173 -674 -675 2 UNLOAD SOLENOID 1 SV 2 -676 -677 50 -678 -679 SSS RUN 186 K1 -680 -681 187 -682 -683 CB12 HTR-OIL SEP. 30 175 176 177 189 49 -684 -685 197 HEATER 1 2 INT ANALOG OUTPUT J4-Y3 126 TB1-40 139 SV BLACK 190 50 EXV MOTOR 185 TO: TB1-1 1 5 120V TO: TB1-2 117 - PID WHITE GREEN RED 116 191 + 195 + 24V AC 196 - 24V AC DETAIL 1 EXV DRIVER T15 2 6 PUMPDOWN 192 PUMPDOWN -686 -687 -688 -689 -690 -691 -692 -693 -694 -695 -696 -697 -698 -699 -700 SCHEM. 330588401 REV. 0B IMM1157-1 WGS 130A to 190A 43 Figure 19, WGS 130 - 190, Unit Controller Schematic Wiring Diagram 812 75 813 60 MJ 801 PE 802 GO G PE J1 SHIELD OUTSIDE AIR TEMP or COND. ENTERING WATER TEMP. (S07) BLK RED B1 MJ 73 71 DEMAND LIMIT (S10) 4-20MA 70 72 EVAP. WATER TEMP. RESET (S11) 4-20MA 804 B2 806 B3 GND 805 J11 B- 70 814 J2 +VDC A+ PE SHIELD GND EVAP. LEAVING WATER TEMP (S08) EVAP. ENTERING WATER TEMP (S09) BLK B4 RED BC4 BLK B5 RED BC5 884 VG 885 VG0 887 Y1 889 Y2 J3 C1 NO1 COOLING TOWER BYPASS 886 COOLING TOWER VFD 888 77 (0-10VDC) 79 78 (0-10VDC) 80 J4 Y3 Y4 UNIT SWITCH S1 807 808 ID1 809 ID2 810 ID3 811 ID4 D IG IT AL OU T P UT S J12 NO3 C1 C4 NO4 J13 CHWI RS1 NO5 NO6 897 REMOTE SWITCH 60 NO2 C4 66 EVAP. FLOW SWITCH 67 MS1 MODE SWITCH C7 68 J14 CWI COND. FLOW SWITCH 815 ID5 76 60 FACTORY INSTALLED FLOW SWITCHES BRN WHT 67 C7 ID6 75 BLU ID7 60 NO8 76 BRN 75 WHT ID8 BLU J15 WGS 130A to 190A C8 NC8 IDC1 800 NOTE: J2-B1 OUTSIDE AIR TEMP. IS FOR TGS UNITS ONLY AND CONDENSER ENTERING WATER TEMP. IS FOR WGS UNITS ONLY. 44 NO7 J5 CONTROLLER IMM1157-1 WGS 130 - 190, Unit Controller Schematic Wiring Diagram (Continued) 1 2 LINE NO. CONTACT LOCATION TERMINAL BLOCK AND LEAD NUMBERS -301 -302 FU12 890 115V OUTLET B 1 REC W 891 PE G 2 1 820, 822, 890 -304 2 60 821, 891 801, 807, 884 60 60 897, 830 812 75 75 800, 885 802, 886 75 75 813, 888 -305 -306 -307 MJ -308 -309 -310 -311 -312 820 1 LINE 1 T2 120V 2 24V 6 -313 LINE 2 -314 821 -315 5 LOAD 1 LOAD 2 -316 MJ BIAS BLOCK -317 -318 -319 - (p LAN) TO CIRCUIT CONTROL BOXES BLACK WHITE GROUND 880 -320 TO UNIT CONTROLLER B- -321 + 881 TO UNIT CONTROLLER A+ 5 882 TO CIRCUIT CONTROLLER J4 G 883 TO CIRCUIT CONTROLLER J4 -322 -323 -324 (TERMINATE AT EACH CONTROLLER) -325 -326 -327 1 822 SEE LINE 301 -328 -329 EVAPORATOR PUMP 1 82 2 120V CHWR 823 -330 -331 EVAPORATOR PUMP 2 85 120V -332 CHWR 824 -333 COND. PUMP 1 86 120V 825 TB1 -303 60 60 2 2 2 66 897, 809 67 68 70 810 811 70 71 806 804 72 73 805 814 76 77 815 886 78 79 887 888 80 889 81 82 83 829 823 84 85 86 824 825 87 88 89 826 827 828 -334 CWR -335 -336 -337 WJ -338 -339 -340 COND. PUMP 2 87 120V 826 -341 CWR -342 TOWER FAN 1 120V 88 TOWER FAN 2 TB1-89 ARE FIELD WIRING TERMINALS. -343 M11 827 NOTE: TB1-75 THRU -344 120V 89 -345 M12 828 -346 -347 -348 -349 -350 -351 -352 -353 -354 -355 -356 UNIT ALARM 81 75 829 ABR -358 LINE 306 -359 60 830 -357 SEE SEE LINE 307 -360 -361 -362 -363 -364 -365 SCHEM. 330588301 REV. 0B IMM1157-1 WGS 130A to 190A 45 Control Panel Layout Figure 20, Outer (Microprocessor) Panel T2, Unit Controller T13, Circ#1 Controller T14, Circ#1 Load Solenoid T15, Circ#1 EXV Power T23, Circ#2 Controller T24, Circ#2 Load Solenoid T25, Circ#2 EXV Power Unit Controller MHPR11 &12, Mechanical High Pressure Relay Circ#1 Controller Circuit Breaker & Switch Panel External Disconnect Handle Circ#1 & 2 EXV Drivers Circ#2 Controller TB3, Circ#2 Controller Terminal Board TB2Circ#1 Controller Terminal Board TB1 Unit Controller Terminal Board NOTES: 1. 2. 3. 46 Transformers T2 through T25 are class 100, 120V to 12V. Switches for MHPR 11 and 12 (Mechanical High Pressure Switches) are located on the compressors. Mechanical High Pressure Switches Open at 310 psi, Close at 250 psi WGS 130A to 190A IMM1157-1 Figure 21, Inner (Power) Panel Circ#1 Solid State Starter Circ#2 Solid State Starter SSS1 Bypass Contactor SSS2 Bypass Contactor Secondary Fuses External Disconnect Handle Circ#1 Circuit Breaker Circ#2 Circuit Breaker Unit Disconnect Switch W/ External Handle T1, Supply Voltage to 120V Transformer Primary Fuses Outside (Microprocessor) Panel IMM1157-1 WGS 130A to 190A 47 Figure 22, Circuit Breaker/Fuse Panel Open Location S1 Main Unit On-Off Switch CS2, Circuit#2 On-Off Switch CS1, Circuit#1 On-Off Switch CB11 Circ#1 Circuit Breaker CB12, Circ#1 Sump Heater Open Location CB21, Circ#2 Circuit Breaker CB22, Circ#2 Sump Heater Open Locations Location for Optional 115V Receptacle Figure 23, Inner and Outer Panel Diagrams OUTER PANEL T2 T13 T14 T15 INNER PANEL T23 T24 T25 MHPR 1 MHPR 2 SINGLE POINT OR CIR. #1 DS HANDLE (MULTIPOINT) SSS #1 D3 CONTR. BRD. UNIT CONTROLLER EXV. DRIVER #1 S 1 D3 CONTR. BRD. THERMISTOR CARD BYPASS CONTACTOR CS2 CS1 SSS #2 S P CT3 THERMISTOR CARD BYPASS CONTACTOR CT1 CT3 CT2 CT1 CT2 CB11 CB12 CIRCUIT CONTROLLER #1 SP CB21 CB22 MODBUS CARD SP CONVERTER BOARD CIR. #2 DS HANDLE (MULTIPOINT) F U 6 FU7 F3 EXV. DRIVER #2 T1 C B 1 C B 2 DS1 CIRCUIT CONTROLLER #2 TB1 TB11 REC OPTION F U 4 F U 5 (DS1 DS2 MULTIPOINT POWER) G N D TB21 330589001 REV. 00 - Legend 48 WGS 130A to 190A IMM1157-1 Sequence of Operation Compressor Heaters With the control power on, 120V power is applied through the control circuit Fuse FU7 to the compressor oil separator heater(HTR-OIL SEP). Startup/Compressor Staging During cool mode the following must be true to start a circuit operating. The evaporator and condenser pump outputs must be energized and flow must be established for a period of time defined by the evaporator recirculate setpoint. Established flow will be detected by evaporator and condenser water flow switches. The water temperature leaving the evaporator must be greater than the Active Leaving Water Temperature setpoint, plus the Startup Delta-T, before a circuit will start. The first circuit to start is determined by sequence number. The lowest sequence numbered circuit will start first. If all sequence numbers are the same (default), then the circuit with the fewest number of starts will start first. During operation the slides for load and unload will be pulsed such that the active leaving water temperature setpoint is maintained. The second circuit start will occur once the first circuit has loaded to 75% slide capacity or is in Capacity Limit and the water temperature leaving the evaporator is greater than the active leaving water temperature Setpoint plus Stage Delta-T. The circuits will load or unload simultaneously through a continuous capacity control to maintain the evaporator leaving water temperature. If all sequence numbers are the same, the circuit with the most run hours will be shutdown first. The circuit with the most run hours will stop when the water temperature leaving the evaporator is less than the Active Leaving Water Temperature Setpoint minus Stage Delta-T. The last remaining circuit will shutdown when the water temperature leaving the evaporator is greater than the Active Leaving Water Temperature Setpoint minus the Stop Delta-T. Automatic Pumpdown The WGS has separate refrigerant circuits so the refrigerant charge is stored in the condenser when the circuit is off. Pumpdown to the condenser helps keep refrigerant from migrating to the compressor. It also helps establish a pressure differential on start for oil flow. In a normal shutdown, each circuit will close its expansion valve, causing the evaporator pressure to reach a low-pressure setpoint. Once this setpoint is reached, or a specified amount of time has elapsed, the running circuit will be shut down. Chilled Water and Condenser Water Pumps The chiller’s MicroTech II controller has a total of four pump outputs, two for the evaporator and two for the condenser. There is a manual setting in the software for the user to select either pump output 1 or 2. It is recommended that the chiller’s outputs control the water pumps, as this will offer the most protection for the unit. Cooling Tower Control The MicroTech II controller can control the cooling tower fans and/or a tower bypass valve. This provides a simple and direct method to control the unit’s discharge pressure. Programming directions and the sequence of operation can be found in the MicroTech II manual. Some means of discharge pressure control must be installed if the condenser water temperature can fall below the values shown on page Error! Bookmark not defined.. Condenser Fan Control The MicroTech II controller can be programmed to cycle on and off condenser fans based on the discharge pressure. Details are in the MicroTech II manual. IMM1157-1 WGS 130A to 190A 49 Start-Up and Shutdown Pre Start-up 1. Flush and clean the chilled-water system. Proper water treatment is required to prevent corrosion and organic growth. 2. With the main disconnect open, check all electrical connections in control panel and starter to be sure they are tight and provide good electrical contact. Although connections are tightened at the factory, they can loosen enough in shipment to cause a malfunction. 3. Check and inspect all water piping. Make sure flow direction is correct and piping is made to correct connection on evaporator and condenser. 4. Open all water flow valves to the condenser and evaporator. 5. Flush the cooling tower and system piping to be sure the system is clean. Start evaporator pump and manually start condenser pump and cooling tower. Check all piping for leaks. Vent the air from the evaporator and condenser water circuit, as well as from the entire water system. The cooler circuit should contain clean, treated, noncorrosive water. 6. Check to see that the evaporator water temperature sensor is securely installed. 7. Make sure the unit control switch S1 is open (off) and the circuit switches CS1 and CS2 are open. Place the main power disconnect switch to “on.” This will energize the compressor sump heaters. Wait a minimum of 12 hours before starting the unit. 8. Measure the water pressure drop across the evaporator and condenser, and check that water flow is correct (on pages 16 and 17) per the design flow rates. 9. Check the actual line voltage to the unit to make sure it is the same as called for on the compressor nameplate, within + 10%, and that phase voltage unbalance does not exceed 2%. Verify that adequate power supply and capacity is available to handle load. 10. Make sure all wiring and fuses are of the proper size. Also make sure that all interlock wiring is completed per Daikin Applied diagrams. 11. Verify that all mechanical and electrical inspections by code authorities have been completed. 12. Make sure all auxiliary load and control equipment is operative and that an adequate cooling load is available for initial start-up. Start-up 1. Open the compressor discharge shutoff valves until backseated. Always replace valve seal caps. 2. Open the two manual liquid line shutoff valves (king valves). 3. Verify that the compressor sump heaters have operated for at least 12 hours prior to start-up. Crankcase should be warm to the touch. 4. Check that the MicroTech II controller is set to the desired chilled water temperature. 5. Start the system auxiliary equipment for the installation by turning on the time clock, ambient thermostat and/or remote on/off switch and water pumps. 6. Switch on the unit circuit breakers. 7. Set circuit switches CS1 and CS2 to ON for normal operation. 8. Start the system by setting the unit system switch S1 to ON. 9. After running the unit for a short time, check the oil level in each compressor, rotation of condenser fans (if any), and check for flashing in the refrigerant sight glass. 50 WGS 130A to 190A IMM1157-1 Weekend or Temporary Shutdown Move circuit switches CS1 and CS2 to the off pumpdown position. After the compressors have shut off, turn off the chilled water pump if not on automatic control from the chiller controller or building automation system (BAS). With the unit in this condition, it will not restart until these switches are turned back on. Power to the unit (disconnect closed) so that the sump heaters will remain energized. Start-up after Temporary Shutdown 1. Start the water pumps. 2. Check compressor sump heaters. Compressors should be warm to the touch. 3. With the unit switch S1 in the “ON” position, move the circuit switches CS1 and CS2 to the ON position. 4. Observe the unit operation for a short time, noting unusual sounds or possible cycling of compressors. Extended Shutdown 1. 2. 3. 4. 5. 6. Close the manual liquid line shutoff valves. After the compressors have shut down, turn off the water pumps. Turn off all power to the unit. Move the unit control switch S1 to the “OFF” position. Close the discharge shutoff valves. Tag all opened disconnect switches to warn against start-up before opening the compressor suction and discharge valves. 7. Drain all water from the unit evaporator, condenser and chilled water piping if the unit is to be shut down during the winter and exposed to below-freezing temperatures. Do not leave the vessels or piping open to the atmosphere over the shutdown period to help prevent excessive corrosion. Start-up after Extended Shutdown 1. Inspect all equipment to see that it is in satisfactory operating condition. 2. Remove all debris that has collected on the surface of the condenser coils (remote condenser models) or check the cooling tower, if present. 3. Open the compressor discharge valves until backseated. Always replace valve seal caps. 4. Open the manual liquid line shutoff valves. 5. Check circuit breakers. They must be in the “OFF” position. 6. Check to see that the circuit switches CS1 and CS2 and the unit control switch S1 are in the “OFF” position. 7. Close the main power disconnect switch. The circuit disconnects switches should be off. 8. Allow the sump heaters to operate for at least 12 hours prior to start-up. 9. Start the chilled water pump and purge the water piping as well as the evaporator in the unit. 10. Start the system auxiliary equipment for the installation by turning on the time clock, ambient thermostat and/or remote on/off switch. 11. Check that the MicroTech II controller is set to the desired chilled water temperature. 12. Switch the unit circuit breakers to “ON.” 13. Start the system by setting the system switch S1 and the circuit switches to “ON”. IMM1157-1 WGS 130A to 190A 51 ! CAUTION Most relays and terminals in the control center are powered when S1 is closed and the control circuit disconnect is on. Therefore, do not close S1 until ready for start-up or serious equipment damage can occur. 14. After running the unit for a short time, check the oil level in the compressor oil sight glass and check the liquid line sight glass for bubbles. System Maintenance General To provide smooth operation at peak capacity and to avoid damage to package components, set and follow a program of periodic inspections. The following items are intended as a guide to be used during inspection and must be combined with sound refrigeration and electrical practices to help provide trouble-free performance. The liquid line sight glass/moisture indicator on all circuits must be checked to be sure that the glass is full and clear and that the moisture indicator indicates a dry condition. If the indicator shows that a wet condition exists or if bubbles show in the glass, even with a full refrigerant charge, the filter-drier element must be changed. Water supplies in some areas can foul the water-cooled condenser to the point where cleaning is necessary. The fouled condenser will be indicated by an abnormally high condenser approach temperature (saturated discharge temperature minus leaving condenser water temperature) and can result in nuisance trip-outs. To clean the condenser, mechanical cleaning or a chemical descaling solution should be used according to the manufacturer’s directions. Systems with remote air-cooled condensers require periodic cleaning of the finned surface of the condenser coil. Cleaning can be accomplished by using a cold water spray, brushing, vacuuming, or high-pressure air. Do not use tools that could damage the coil tubes or fins. The compressor oil level must be checked periodically to be sure that the level is near the center of the oil sight glass located on the compressor (see Figure 24). Low oil level can cause inadequate lubrication and if oil must be added, use oils referred to in the following “Compressor Lubrication” section. A pressure tap has been provided on the liquid line downstream of the filter-drier and solenoid valve but before the expansion valve. An accurate subcooled liquid pressure and temperature can be taken here. The pressure read here could also provide an indication of excessive pressure drop through the filter-drier and solenoid valve due to a clogging filterdrier. Note: A normal pressure drop through the solenoid valve is approximately 3 psig (20.7 kPa) at full load conditions. ! CAUTION A blown fuse or tripped protector indicates a short ground or overload. Correct the problem before replacing fuses or restarting compressor. The control panel must be serviced by a trained and qualified technician. Improper service can damage equipment. 52 WGS 130A to 190A IMM1157-1 ! CAUTION The panel is always energized, even when the system switch is off. Pull the main unit disconnect to de-energize the panel and crankcase heaters. Failure to do so can result in severe personal injury or death. If motor or compressor damage is suspected, do not restart until qualified service personnel have checked the unit. Electrical Terminals ! DANGER To avoid severe injury or death from electric shock, turn off all power and lockout and tagout electric source before continuing with the following service. Note unit might be powered from multiple sources. POE Lubrication POE type oil is used for compressor lubrication. This type of oil is extremely hygroscopic, which means it will quickly absorb moisture if exposed to air and may form acids that can be harmful to the chiller. Avoid prolonged exposure of POE oil to the atmosphere to prevent this problem. For more details on acceptable oil types, contact your Daikin Applied service representative. ! CAUTION POE oil must be handled carefully using proper protective equipment (gloves, eye protection, etc). The oil must not come in contact with certain polymers (e.g. PVC), as it may absorb moisture from this material. Also, do not use oil or refrigerant additives in the system. It is important that only the manufacturer’s recommended oils be used. Acceptable POE oil types are: CPI/Lubrizol Emkarate RL68H Exxon/Mobil EAL Arctic 68 Hatcol 3693 Everest 68 No routine lubrication is required on WGS units. Figure 24, Compressor Oil Filter The Lub Control measures the pressure drop across the lubricant filter and shuts off the compressor if the differential pressure becomes too high. It is reset through the circuit controller. Change oil when pressure drop exceeds 15 psig. Compressor Oil Filter Lub Control Oil Level Sight Glass IMM1157-1 WGS 130A to 190A 53 Sight Glass and Moisture Indicator The refrigerant sight glasses should be observed periodically. A monthly observation should be adequate. A clear glass of liquid indicates that there is adequate refrigerant charge in the system to provide proper feed through the expansion valve. The sight glass should be clear when the ambient temperature is above 75F (23C) and all fans on a circuit are running, when air cooled. Bubbling refrigerant in the sight glass may occur at other conditions and may indicate that the system is short of refrigerant charge. Refrigerant gas flashing in the sight glass could also indicate an excessive pressure drop in the line, possibly due to a clogged filter-drier or a restriction elsewhere in the system. An element inside the sight glass indicates what moisture condition corresponds to a given element color. If the sight glass does not indicate a dry condition after about 12 hours of operation, the unit should be pumped down and the filter-driers changed. If the system is suspected of being short of refrigerant, a qualified service technician with EPA certification should be contacted to thoroughly check out the unit and add refrigerant if necessary. Sump Heaters The compressors are equipped with sump lubricant heaters. The function of the heater is to keep the temperature in the crankcase high enough to prevent refrigerant from migrating to the crankcase and condensing in the lubricant during the off-cycle. When a system is to be started up initially, the power to the heaters should be turned on for at least 12 hours before the compressors are started. The sump should be up to about 80°F (26.7°C) before the system is started up (warm to the touch), to minimize lubrication problems or liquid slugging of compressor on start-up. If the crankcase is cool (below 80°F) (26.7°C) and the oil level in the sight glass is full to top, allow more time for oil to warm before starting the compressor. The crankcase heaters are on whenever power is supplied to the unit and the compressor is not running. 54 WGS 130A to 190A IMM1157-1 Maintenance Schedule I. Compressor A. Performance Evaluation (Log & Analysis) * B. Motor Meg. Windings Ampere Balance (within 10%) Terminal Check (tight connections, porcelain clean) Motor Cooling (check temperature) C. Lubrication System Oil Level Oil Appearance (clear color, quantity) Oil change if indicated by oil analysis II. Controls A. Operating Controls Check Settings and Operation B. Protective Controls Test Operation of: Alarm Relay Pump Interlocks High and Low Pressure Cutouts III. Condenser B. Test Water Quality C. Clean Condenser Tubes (or as required) D. Eddy current Test - Tube Wall Thickness E. Seasonal Protection IV. Evaporator B. Test Water Quality C. Clean Evaporator Tubes (or as required) D. Eddy current Test - Tube Wall thickness (or as required) E. Seasonal Protection V. Expansion Valves A. Performance Evaluation (Superheat Control) VI. Compressor - Chiller Unit A. Performance Evaluation B. Leak Test: Compressor Fittings and Terminal Piping Fittings Vessel Relief Valves C. Vibration Isolation Test D. General Appearance: Paint Insulation VII. Starter(s) A. Examine Contactors (hardware and operation) B. Verify Overload Setting and Trip C. Test Electrical Connections Key: O = Performed by in-house personnel IMM1157-1 O X X X X O O X X X X X X X X X X X X X X X O X X X X X X X X X X = Performed by service personnel WGS 130A to 190A 55 System Service DANGER ! Service on this equipment must be performed by trained, experienced technicians. Causes for repeated tripping of equipment protection controls must be investigated and corrected. Disconnect all power (there may be multiple sources) before doing any service inside the unit or severe personal injury or death can occur. NOTE: Anyone servicing this equipment must comply with the requirements set forth by the EPA concerning refrigerant reclamation and venting. Filter-Driers Figure 25, Filter-Drier Assembly There is a filter-drier assembly for each circuit located in the liquid line. The cartridges should be changed when the pressure drop across them exceeds the values shown in Table 26 below, when measured at the Schrader fittings before and after the housing. To change the filter: Expansion Valve Evaporator Sensor Schrader Fitting Filter-Drier Sight Glass Schrader Fitting Condenser Liquid Line Valve Expansion Valve 1. Shut off the circuit. This will close the expansion valve. 2. Shut off the condenser liquid shutoff valve, isolating the filterdrier. 3. Remove any remaining refrigerant from one of the Schrader valves using approved EPA procedures. 4. Remove the housing cover, after checking that there is no positive pressure in the filterEvaporator drier. 5. ReplaceSensor the filters, reinstall the cover, evacuate, and open the liquid line valve. Table 26,Schrader Liquid Line Filter-Drier Pressure Drop Fitting PERCENT CIRCUIT LOADING (%) 100% 75% Sight 50% Glass 25% MAXIMUM RECOMMENDED PRESSURE Schrader DROP ACROSS FILTER DRIER PSIG (KPA) Fitting 7 (48.3) Filter-Drier 5 (34.5) 3 (20.7) Condenser 3 (20.7) Liquid Line Valve 56 WGS 130A to 190A IMM1157-1 Electronic Expansion Valve The electronic expansion valve is located in the liquid line entering the evaporator. The expansion valve meters the amount of refrigerant entering the evaporator to match the cooling load. It does this by maintaining constant condenser subcooling. (Subcooling is the difference between the actual refrigerant temperature of the liquid as it leaves the condenser and the saturation temperature corresponding to the condenser pressure.) All WGS chillers are factory set at 20F subcooling at 100% slide position and 10F (12.2C) subcooling at minimum slide position. These settings can be offset by discharge superheat. When the control panel is first powered, the microprocessor will automatically step the valve to the fully closed (shut) position and the indicator light on the EXV will show closed position. The valve can also be heard closing as it goes through the steps. The valve will take approximately 30 seconds to go from a full open position to a full closed position. The position of the valve can be viewed at any time by using the MicroTech II controller keypad through the View Refrigerant menus. There are 6386 steps between closed and full open. There is also a sight glass on the EXV to observe valve movement. If the problem can be traced to the power element only, it can be unscrewed from the valve body without removing the valve, but only after pumping the unit down. Evaporator The evaporator is a shell-and-tube unit. Normally no service work is required on the evaporator. Water-cooled Condenser The condensers are of the shell-and-tube type with water flowing through the tubes and refrigerant in the shell. External finned copper tubes are rolled into steel tube sheets. Integral subcoolers are incorporated on all units. All condensers are equipped with 350 psig (2413 kPa) relief valves. Normal tube cleaning procedures can be followed. IMM1157-1 WGS 130A to 190A 57 Troubleshooting Chart PROBLEM 1. 2. 3. Compressor Will Not Run Compressor Noisy or Vibrating 3. 6. 7. 8. No cooling required. Liquid line solenoid will not open. Motor electrical trouble. 6. 7. 8. 9. Loose wiring. 9. 1. Flooding of refrigerant into compressor. 1. 2. Improper piping support on suction or liquid line. Worn compressor. Condenser water insufficient or temperature too high. 2. 2. 3. 4. 5. 6. Fouled condenser tubes (water-cooled condenser). Clogged spray nozzles (evaporative condenser). Dirty tube and fin surface (air cooled condenser). Noncondensables in system. System overcharge with refrigerant. Discharge shutoff valve partially closed. Condenser undersized (air-cooled). 7. High ambient conditions (air-cooled). 7. 1. 2. 3. Faulty condenser temp. regulation. Insufficient refrigerant in system. Low suction pressure. 1. 2. 3. 4. Condenser too large. 4. 5. Low ambient conditions (air-cooled) 5. 1. Excessive load. 1. 2. 1. 2. 3. 4. Expansion valve overfeeding. Lack of refrigerant. Evaporator dirty. Clogged liquid line filter-drier. Expansion valve malfunctioning. 2. 1. 2. 3. 4. 5. Condensing temperature too low. 5. 6. Compressor will not unload. 6. 7. 1. 2. Insufficient water flow. Clogged suction oil strainer. Excessive liquid in crankcase. 7. 1. 2. 3. 4. Low oil level. Flooding of refrigerant into crankcase. 3. 4. 4. 5. 2. Low Discharge Pressure High Suction Pressure Low Suction Pressure 1. 2. Thermal overloads tripped or fuses blown. Defective contactor or coil. System shut down by equipment protection devices. 3. 1. High Discharge Pressure POSSIBLE CAUSES Main switch, circuit breakers open. Fuse blown. 4. 5. 3. 1. 3. 4. 5. 6. Little or No Oil Pressure 58 WGS 130A to 190A POSSIBLE CORRECTIVE STEPS Close switch Check electrical circuits and motor winding for shorts or grounds. Investigate for possible overloading. Replace fuse or reset breakers after fault is corrected. Overloads are auto reset. Check unit closely when unit comes back on line. Repair or replace. Determine type and cause of shutdown and correct it before resetting protection switch. None. Wait until unit calls for cooling. Repair or replace coil. Check motor for opens, short circuit, or burnout. Check all wire junctions. Tighten all terminal screws. Check superheat setting of expansion valve. Relocate, add or remove hangers. Replace. Readjust temperature control or water regulating valve. Investigate ways to increase water supply. Clean. EPA purge the noncondensables. Remove excess refrigerant. Open valve. Check condenser rating tables against the operation. Check condenser rating tables against the operation. Check condenser control operation. Check for leaks. Repair and add charge. See corrective steps for low suction pressure below. Check condenser rating table against the operation. Check condenser rating tables against the operation. Reduce load or add additional equipment. Check remote bulb. Regulate superheat. Check for leaks. Repair and add charge. Clean chemically. Replace cartridge(s). Check and reset for proper superheat. Replace if necessary. Check means for regulating condensing temperature. See corrective steps for failure of compressor to unload. Adjust flow. Clean. Check sump heater. Reset expansion valve for higher superheat. Check liquid line solenoid valve operation. Add oil. Adjust expansion valve. IMM1157-1 PROBLEM Compressor Loses Oil Motor Overload Relays or Circuit Breakers Open Compressor Thermal Switch Open Freeze Protection Opens IMM1157-1 1. POSSIBLE CAUSES Lack of refrigerant. 1. 2. 3. Velocity in risers too low (A-C only). Oil trapped in line. 2. 3. 1. Low voltage during high load conditions. 1. 2. Defective or grounded wiring in motor or power circuits. Loose power wiring. High condensing temperature. 2. 5. Power line fault causing unbalanced voltage. 5. 6. 6. 1. High ambient temperature around the overload relay Operating beyond design conditions. 2. 1. 2. 3. Discharge valve partially shut. Thermostat set too low. Low water flow. Low suction pressure. 2. 1. 2. 3. 3. 4. WGS 130A to 190A 3. 4. 1. POSSIBLE CORRECTIVE STEPS Check for leaks and repair. Add refrigerant. Check riser sizes. Check pitch of lines and refrigerant velocities. Check supply voltage for excessive line drop. Replace compressor-motor. Check all connections and tighten. See corrective steps for high discharge pressure. Check Supply voltage. Notify power company. Do not start until fault is corrected. Provide ventilation to reduce heat. Add facilities so that conditions are within allowable limits. Open valve. Reset to 42°F (6°C) or above. Adjust flow. See “Low Suction Pressure.” 59 Daikin Training and Development Now that you have made an investment in modern, efficient Daikin Applied equipment, its care should be a high priority. For training information on all Daikin Applied HVAC products, please visit us at www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department. Warranty All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. To find your local Daikin Applied representative, go to www.DaikinApplied.com. Aftermarket Services To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787). To find your local service office, visit www.DaikinApplied.com or call 800-432-1342. This document contains the most current product information as of this printing. For the most upto-date product information, please go to www.DaikinApplied.com. Products manufactured in an ISO Certified Facility. IMM 1157-1 (09/14) ©2014 Daikin Applied | (800) 432-1342 | www.DaikinApplied.com