series - Gentex

advertisement
Low Profile Ceiling Mount Speaker/Strobe and
S S P K C L P
Ceiling or Wall Mount Speaker
Applications
S E R I E S
The Gentex SSPK24CLP is a ceiling mount, selectable candela speaker/strobe
and the SSPKCLP is a ceiling or wall mount speaker designed to meet code
requirements for audio, visual and voice communications. The SSPKCLP
Series are quality speaker products that offer both dependable evacuation
signaling and visual alarms, or a combination of both. The SSPK24CLP has
high output tamperproof candela selections are 15, 30, 75, 95 and 115.
The SSPKCLP Series can be mounted in a 4” square x 2-1/8” deep back
box, an extension ring is not needed.
The SSPKCLP Series provides a 25 or 70.7 VRMS speaker with field
selectable power taps of 1/8W, 1/4W, 1/2W, 1W, 2W or 4W. The SSPK24CLP
strobes can be synchronized by using the Gentex Synchronization Control
Module, FACP’s or power supplies that include the Gentex Synchronization
Protocol.
The SSPKCLP Series grills are constructed of high impact textured plastic.
The SSPKCLP is warranted for 3 years from the date of purchase. The
SSPKCLP devices are UL 1971 listed for use with fire protective signaling
systems.
SSPK24CLPW
SSPKCLPR
Product Listings
Standard Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
24VDC Tamperproof Selectable Candela Selections of 15, 30, 75, 95 and 115.
Unit Dimension: 6.1” Square X 1.88” Deep
SSPK24CLP Ceiling Mounting to a standard 4” X 2-1/8" Deep Back Box
• UL1480, UL 1971 and UL 2043 Listed
SSPKCLP Ceiling or Wall Mounting to a standard 4” X 2-1/8" Deep Back Box
• CSFM # 7320-0569:137
High Quality dBA Output (Intelligible)
• BS&A/MEA # 580-06-E Vol. 3
Frequency Range 400-4000Hz
Product Compliance
Screw Terminals, Separate In/Out Wiring (12-18 Gauge)
Field Selectable Power Taps: 1/8W, 1/4W, 1/2W, 1W, 2W, 4W
• Americans with Disabilities Act (ADA)
• NFPA 72
Speaker Voltage 25 or 70.7 VRMS Standard, Field Selectable
To Synchronize Use the Gentex Synchronization Control Module
Tamperproof Grill
Faceplate Available in Red or Off-White
UL 1480/UL 1971/UL 2043 Listed for Fire Protective Service/Signal for Hearing Impaired
Xenon Strobe Maintains Constant Flash Rate (1Hz) Regardless of Input Voltage1
Low Profile Evacuation Speakers and Speaker/Strobes
Model Number
Description
Part Number
SSPKCLPR
Speaker
904-1445-002
SSPKCLPW
Speaker
904-1446-002
SSPK24CLPR
Speakers/Strobe
904-1441-002
SSPK24CLPW
Speaker/Strobe
904-1443-002
Notes:
The SSPKCLP Series is not listed for outdoor use.
Operating temperature: 32°to 120°F (0° to 49° C).
Gentex does not recommend using a coded or pulsing
signaling circuit with any of our strobe products (see
technical bulletin number 014).
"R" = Red Faceplate
"W" = Off-White Faceplate
"P" = Plain (no lettering) Available with all models.
Input Watts
1/8
1/4
1/2
1
2
4
Speaker dBA @ 10 ft.
25 Volts
70.7 Volts
74.6 dBA
73.7 dBA
77.7 dBA
76.7 dBA
80.5 dBA
79.6 dBA
83.1 dBA
82.5 dBA
85.6 dBA
85.4 dBA
87.9 dBA
87.9 dBA
SSPK24CLP CEILING MOUNT
Candela
15cd
30cd
24 VDC
72mA
88mA
120mA
130mA
UL Max1
STROBE CURRENT RATINGS
75cd
95cd
115cd
176mA
200mA
214mA
272mA
318mA
360mA
1 RMS current ratings are per UL average RMS method. UL maximum current rating is the maximum
RMS current within the listed voltage range (16-33VDC for 24VDC units) (8-17VDC for 12VDC units).
For strobes the UL max current is usually at the minimum listed voltage (16VDC for 24VDC units)
(8VDC for 12VDC units). For audibles the maximum current is usually at the maximum listed voltage.
For unfiltered FWR ratings, see installation manual.
S S P K C L P
S E R I E S
SSPK24CLP Candela Selection
Power Tap Selection
SSPKCLP Mounting Diagram
Mounts to a standard 4" square x 2-1/8"back box or to
Gentex GBLP surface back box
Adjust brightness by turning dial with screwdriver.
Candela selection is displayed on front of unit.
Wiring Diagram
NOTE: DO NOT USE
LOOPED WIRE UNDER
TERMINALS. BREAK
WIRE RUN TO PROVIDE
SUPERVISION OF
CONNECTION.
*MAX. WIRE DISTANCE (IN FEET)= PANEL VOLTAGE — DEVICE MINIMUM VOLTAGE X WIRE CONDUCTIVITY
TOTAL CURRENT DRAW
*CAUTION: APPLIES ONLY TO REGULATED SUPPLIES
.
NOTICE: POWER IS SUPPLIED TO DEVICES WHEN CONTROL PANEL IS LATCHED.
Architect & Engineering Specifications
The fire alarm speaker shall be Gentex SSPKCLP, SSPK24CLP or equivalent. The speaker shall be capable of producing alarm
tones or voice on all 25 or 70.7 VRMS audio systems. The speaker shall provide incremental tap settings of 1/8, 1/4, 1/2, 1, 2 or 4
watts. Minimum dBA ratings at 1/4 watt shall be 76.7dBA and at 4 watts 87.9dBA. Tap settings shall be adjustable with field selectable
jumper pins. The speaker shall also have an optional visual signal capability.
The visual signal shall have a 1Hz flash rate regardless of input voltage. All field wiring connections shall be made via separate
in-out terminal connections and the speaker or speaker strobe shall be UL, CSFM and BS&A/MEA listed and comply with all local,
state and federal fire alarm codes/standards.
12 units per carton
17 pounds per carton
Important Notice:
These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes
only, are necessarily summary, and are not purported to serve as legal advice and should not be used
as such. Gentex makes no representations and warranties, express or implied, that these materials
are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws,
regulations and rules. The materials do not address all legal considerations as there is inevitable
uncertainty regarding interpretation of laws, regulations and rules and the application of such laws,
regulations and rules to particular fact patterns. Each person's activities can differently affect the
obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be
used only for informational purposes and should not be used as a substitute for seeking professional
legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the
information contained in this material.
551-0065-02
Download