Visual Dr audible May be used in all weather conditions Can be bridged across phases, and js unaffected Indication unaffected by temperature Camplies with VDE 0681 by nejghbauring valtage fjelds A Live Line Tester is essentially an operating rod with an indication device which detects and shows whether voltage is present on the item to be tested. Single phase contact, i. e. physical contact with the conductor to be tested is a necessary part of the test procedure. The Voltage Detector will then indicate whether parts of an installation are under operating voltage or not All ARCUS Voltage testers comply with VDE 0681 part 4/10.86 and consequently all requirements of that specification are fully met as a minimum. As there are approximately 30 requirements in the specification, we list below some of the more important safety constructional features of the ARCUSTON and ARCUSLIGHT. Extension Piece In contrast to VDE 0427/1.63, ARCUS Live Line Testers have an extension piece. This overcomes the problem of interference frorn neighbouring voltage fields as weIl as the influence of stray voltages and induced voltages. Conducting Parts The current limiting resistors in the extension piece will not reduce its insulation safety. The Live Line Tester is safe to use when bridging across phases, both in the dry conditions and in the case of Testers which "may be used in damp or wet conditions" under heavily precipitous conditions. The Tester may rest across parts under voltage for up to 1 minute. Insulation Level Each Live Line Tester is subjected to standard routine tests to ensure its complete safety: Tests are made on leakage current and voltage bridging safety levels. Each tester is calibrated to the maximum operating voltage Um. In the routine test the voltage Um is raised by 20% so as to provide a suitable safety factor. Mechanical Safety Routine tests are made on the ability of each tester to withstand vibration and impact shock of the type that will be met under normaloperating conditions. Voltage Threshold Level The Tester will only indicate nominal operating voltages. Since the Tester can only show voltages from phase to earth, the indication "Line Alive" is given within the range 0.15 x Un and 0.4 x Un. For wide range testers the threshold level will be between 0.15xUn of the higher voltage and 0.4 x Un of the lower voltage. In order to comply with VDE 0681, a wide range detector is limited to a maximum ratio of 2 : 1 between the upper and lower voltage levels. For example if a detector is supplied for operation at 60 -110 KV, the threshold point will be between > 16,5 KVand 24 KV dependent on the test assembly when measured to earth. It should be noted that the Live Line Testers which are offered for u. K. operating voltages of 11 -33 KV therefore have a wider ratio of 2 : 1 and would not comply with VDE 0681 in this respect only. D. C. Valtages The Live Line Testers described in this pamphlet are not to be used tor D. C. voltages. Stray Voltages The term stray voltages covers voltages which are induced by capacitive or inductive coupling. Stray voltages are generally less than 10% of the nominal voltage and will consequently not be indicated by the detector. Occasionally, there will be situations where the interference is from a much higher voltage source, e. g. a 30 KV line can be subjected to interference from a 380 KV line. The voltage tester is not able to differentiate between stray voltages and operating voltages in such cases. Stray Fields Since the detector is a single phase device, it follows that voltage measurement is always made with reference to earth potential. Earlier Live Line Testers were influenced by the effect of a distorted earth field, e. g. around large corona screening rings or neighbouring conductors of the same potential. The danger of false indication through this cause does not exist with the ARCUS detectors, since the signal detection equipment and indicator housing are located weIl away from the test probe and are outside the effect of stray fields which can cause these incorrect indications. Signal Clarity The test electrode of the ARCUSTON is visually located onto the item to be tested. An audible indication is then given as to whether the line is alive or not. All personne' in a large area will be able to hear the noise signal which will overcome a substantial background noise. The optical indication of the ARCUSLIGHT is clearly shown from two different light sources. Operators who are colour blind can therefore still use this equipment while observing a change in the position of the light. ta aperate Built-in selfchecking device Wide range of GonstruGtion Indication The two conditions "Line Dead" and "Line Alive" are indicated on the ARCUSTON by means of an intermittent tone which changes to a continuous note when the line is alive. For the U. K. the normal sound indication system which is chosen is "Line Alive" Noise Stops and "Line Dead" -continuous note. With the ARCUSliGHT the lamp will change from green to red if the line is alive. These methods of signalling provide a failsafe indication. Self-Checking Device The self-checking device ensures that the batteries are fully charged and that all components within the electronic circuit are functioning correctly. In the event of a fault on the soldered connections orcomponents, this will be detected by the self-checking device and the normal "Circuit Healthy" signal will not be given. The capacity of the usual batteries is checked as weIl. The functional capability of impedances which are not in the electronic circuit must be checked by independent measurements and tests. These impedances are selected, so as to be completely stable at the appropriate voltages of the instrument. The switching of the ARCUSTON detector by means of a rotating ring, ensures that the safety check must be completed before and after the live line test is made. In the case of the ARCUSLIGHT the safety check is carried out by pressing the push button. If the light changes from green to red when this button is pressed and back to green again when the button is released, then the ARCUSLIGHT is ready for use. Switching on the ARCUSTON by rotating the annular ring switch. Ease cf Handling The use of light components and multisectional closed operating rods enables the tester to be easily handled on masts. Routine Maintenance Safety Tests Each instrument will be subjected to a different amount of wear and tear, storage and transportation. There is consequently no set schedule in VDE 0681 as to the frequency of routine maintenance and safety testing. It is the responsibility of the appropriate engineer in the organisation concerned to decide on the type and frequency of the tests to be undertaken. We would suggest that these tests should include the checking of the threshold voltage level, the measurement of leakage current and a thorough inspection for mechanical damage. The high voltage tester is an important device both for the safety of personnel and for the installation. It must be treated with care and respect. The Association of German Electrical Power Companies (DKE) will prepare a guideline for routine safety checks and recommendations on the care of these instruments. Full range of accessories Application in Type-tested switchgear Voltage testers which comply with VDE 0681 are suitable for type-tested switchgear under certain conditions. (See VDE 0101 /4. 71, section 23 and DIN 57670 part 6/VDE 0670 part 6, May 1976 issue). Creepage distances for the insulation of voltage testers follow the basic recommendations of distances for flash-over levels in VDE 0101. Before using the voltage tester in a type-tested switchboard it is necessary to ascertain whether the use of the tester is acceptable on that particular piece of equipment. All leading German manufacturers of switchboards have approved the ARCUS Voltage Detector for use with their equipment. The ARCUSTON Uve Une Tester in use on a 20 kV mast. References I. DIN 57681/VDE 0681 Part 11/3.77 and Part 4/8.78. 2. DIN 57105 sheet 1/VDE 0105 Part 1/5.75. 3. Stuffel, etc. -b Bd 30 (1978) Vol. 15. 2 "Also to be used with precipitation" "Also to be usedwith precipitation" Safeoperationalsoin Gaseof precipitationsecuredby separate closedglasfibre-reinforced insulated tubeswith plasticinsulatorswhich interruptflow of water. Whilstcontactwith the part to be checkenis madevisually,the ear will detectthe soundsignal independently. Single Valtage Range Testers Type No. Nominal Voltage / Viltual Va/ue 50-60 Hz 610102 Weight each 12 20 24 30 36 LG1 7,2 kV kV kV kV mm mm mm mm kg 1950 1405 480 425 1,65 5-6 610100 Dimensions 10 G!. LG21) 2395 p 1600 LV 675 / In caseof types 610096-610102 the construction"not to be used with precipitation"can be achieved by omittingthe mid-sectionoperating red.Thusconvenientoperation is possiblein narrowrooms. LH 425 2,00 The followingmanufactures have checkedthe applicationof the ARCUSTON on their switchgear: CalorEmag,Sachsenwerk, AEG, BBC.We will providefurther informationwith regardto other manufacturers on request. Carryingcasefor types 610099/100 900 mm Ig. 610096/101/102 1100 mm Ig. 610061/062/097/0981290mm Ig. Plasticcarryingbagsfor types 610067/068/069 are included. The ARCUSTON has a three positionring switch.The middle positionprovidesa compulsory checkof batterychargeand correctoperationof the electronic circuit. The indication"Iine alive" is not affectedby strayvoltageswhenthe conductor-earth voltageof the item to be testedis at least40 % of the nominalvoltageratingof the tester. The integralself-checkingdevice verifiesthe correctoperationof the completeelectroniccircuit, withoutthe necessityof applying an extemalvoltage. Dimensions and weights are on Iy approximate values. 1) shonened execu!ion wi!hou! using middle pan of !he rod. In !his version uni! "cannot be used in damp and wet conditions". Screwconnectionwith cylindrical guidingsecuresnaturalstability and facilitatesassernbly.The internalthreadcannotbe darnaged. ~@ s ..5l ~ /1RCUS ~~ Electranic High Valtage Live D Une ~ Tester "Not to be used with precipitation" Whilstcontactwith the part to be checkedis madevisually,the ear will detectthe soundsignal independently. Suitabletor bothoverheadline and sub-stationtesting.The long slendertest tip tacilitatesuse in continedspacesand compactsubstations. The followingmanufacturers have checkedthe applicationof the ARCUSTON on their switchgear: CalorEmag,Sachsenwerk, AEG, BBC.We will be pleasedta provideinformationwith regardta othermanufacturers on request. Single Valtage Range Testers Nominal Voltage / Vil1ual Value 50-60 Hz Type No. Dimensions Weight each 30 36 LV LI LH 12 20 24 LG 7,2 kV kV kV kV mm mm mm mm 10 5-6 / Carryingcasefor types 610080/081 900 mm Ig. 610058/082/083 1100 mm Ig. 610059/060 1290 mm Ig. Forfurtherdetailssee page12. kg 610081 p 1175 480 510 185 1,40 610083 p 1560 675 640 245 1,50 The ARCUSTON has a three positionring switch.The middle positionprovidesa compulsory checkof batterychargeand correct operationof the electroniccircuit. The indication "line alive" is not affected by stray voltages when the conductor-earth voltage of the item to be tested is at least 40 % of the nominal voltage rating of the tester. Wide Valtage Range Testers Type No. Nominal Voltage / Virtual Value 50-60 Hz 610059 Weight/ each 5 10 30 36 LV LI LH 12 20 24 LG 6 kV kV kV kV mm mm mm mm 1495 p Dimensions Dimensions and weights are approximate 800 510 185 The integral self-GheGkingdeviGe verifies the GorreGtoperation of the Gomplete eleGtroniGGirGuit,without the neGessityof applying an external voltage. kg 1,45 The test electrode has a threaded tip ta enable accessary tips ta be applied -see page 12. values. Screwconnectionwith cylindrical guidingsecuresnaturalstability and facilitatesassembly.The intemalthreadcannotbe damaged. 4 51 ~@ J'J "Also to be used with precipitation" "Also to be usedwith precipitation" Safeoperationalsoin Gaseof precipitationsecuredby separate closedglasfibre-reinforced insulated tubeswith plasticinsulatorswhich interruptflow of water. Whilstcontactwith the part to be checkedis madevisually,the ear will detectthe soundsignal independently. The compactconstructionenables the testerto be usedin narrow rooms.Dueto contructivefeatures the test is passedalso under precipitationand the operating voltageis far belowthe admissive values. Single Valtage Range Testers Type Nominal Voltage / Virtual Value 50-60 Hz No. Dimensions Weight 10 20 LV 12 24 30 36 LG 7,2 kV kV kV kV mm mm 5-6 / each LI mm LH mm kg 610125 1265 480 540 245 1,65 610127 1460 675 540 245 1,75 Thefollowingmanufacturers have checkedthe applicationof the ARCUSTON on their switchgear: CalorEmag,Sachsenwerk, AEG, BBC.We will be pleasedto provide inforrnation with regardto other manufacturers on request. Canyingcasefor types 610124/125 900 mm Ig. 610121/126/127 1100mm Ig. 610122/123 1290mm Ig. Forfurtherdetailssee page12. The ARCUSTON has a three positionring switch.The middle positionprovidesa compulsory checkof batterychargeand GorreGt operationof the electroniccircuit. Wide Valtage Range Testers Type No. Nominal Voltage / Virtual Value 50-60 Hz 5 10 12 20 24 30 6 kV kV kV kV LG LV LI LH mm mm mm mm 1585 and weights Weight each 36 610122 Dimensions Dimensions are approximate 800 540 245 / The indication"line alive" is not affectedby stray voltageswhenthe conductor-earth voltageof the item to be testedis at least40 % of the nominalvoltageratingof the tester. kg 1,75 The integralself-GheGking deviGe verifiesthe GorreGt operationof the Gomplete electroniG GirGuit, without the neGessity of applyingan extemalvoltage. values. Screwconnectionwith cylindrical guidingserucesnaturalstability andfacilitatesassembly.The intemalthreadcannotbe damaged. 5 ,-, "Also to be used with precipitation" "Alsoto be usedwith precipitation" Safeoperationalsoin Gaseof precipitationsecuredby separate closedglasfibre-reinforced insulated tubeswith plasticinsulatorswhich interruptflow of water. Voltageindicationis givenby two well-separated colouredlamps. Theseensureclearindicationunder unfavourable conditions,e.g. againstbrightsunlight. In caseof types 610109-610112 and 610117-610119 the construction "not to be usedwith precipitation"can be obtainedby omittingthe mid-sectionoperating rod.Thusconvenientoperationis possiblein narrowspaces. Single Valtage Range Testers 10 12 20 24 30 7,2 kV kV kV kV 5-6 610110 610112 Dimensions Nominal Voltage / Virtual Value 50-60 Hz Type No. LG1 LH mm mm mm mm kg 1950 1405 480 425 1,65 2395 1600 p Type No. LV 36 p Wide Valtage LG21) Weight/ each 675 425 Nominal 2,00 Voltage / Virtual Dimensions Value Weight each Hz LH mm p 2270 . 1730 610153 3590 All dimensions and weights . 6260 are approximate values. 1) shortened execution without using middle part of the rod. In this version unit "cannot be used in demp end wet conditions". 6 Carryingcasefor types 610109-610111 900 mm Ig. 610112-610119 1100mm Ig. 610153/154 1290mm Ig. Forfurtherdetailssee page12. Range Testers kV 50-60 610118 The followingmanufactures have checkedthe applicationof the ARCUSTON on their switchgear: CalorEmag,Sachsenwerk, AEG, BBC.We will be pleasedto provide informationwith regardto other manufacturers on request. kg 800 425 1,90 715 420 2,40 690 1160 800 4,10 1000 5,80 / To switchon and carryout the safetycheck,the push buttonis depressed. If the light changes from greento red whenthe button is pressedand then backto green again,the ARCUSLIGHT is operating correctlyand is readyfor use. The indication"line alive" is not affectedby strayvoltageswhenthe conductor-earth voltageof the item to be testedis at least40 % of the nominalvoltageratingof the tester. The integral self-checking device verifies the correct operation of the complete electronic circuit, without the necessity of applying an external voltage. Screwconnectionwith cylindrical guidingsecuresnaturalstability and facilitatesassembly.The internalthreadcannotbe damaged. 5b- ~~ ~ u "Not to be used with precipitation" Valtageindicatianis givenby twa well-separated calauredlamps. Theseensureclearindicatian underunfavaurable canditians,e.g. againstbrightsunlight. Suitabletor bothoverheadline and sub-stationtesting.The long slendertest tip tacilitatesuse in continedspacesand compact sub-station; Thefollowingmanufacturers have checkedthe applicationof the ARCUSTON on their switchgear: CalorEmag,Sachsenwerk, AEG, BBC.We will be pleasedto provide infonnationwith regardto other manufacturers on request. Single Valtage Range Testers Type Nominal Voltage / Viltual Value 50-60 Hz Noc 12 20 24 30 7,2 kV kV kV kV 5-6 10 Dimensions Weightl each LG LV LI LH mm mm mm mm 36 Availablefor storageand transport: CarryingGasefor types 610088-610090 900 mm Ig. 610072-610091 1100 mm Ig. Forfurtherdetailssee page12. kg 610089 @ 1175 480 510 185 1,30 610091 p 1560 675 640 245 1,60 To switchon and carryout the safetycheck,tf}epush buttonis depressed. If the light changes from greento red when the button is pressedand then backto green again,the ARCUSLIGHT is operating correctlyand is readyfor use. The indication"Iine alive" is not affectedby stray voltageswhenthe conductor-earth voltageof the item to be testedis at least40 % of the nominalvoltageratingof the tester. Wide Valtage Range Testers Type No. Nominal Voltage / Viltual Va/ue 50- 60 Hz 610073 Weight each 5 10 30 36 LV LI LH 12 20 24 LG 6 kV kV kV kV mm mm mm mm p Dimensions Dimensions 1495 and weights are approximate 800 510 185 / The integralself-GheGking deviGe velifiesthe GOrreGt operationof the GompleteeleGtroniG GirGuit without the neGessity of applyingan extemalvoltage. kg 1,55 Thetest electrodehas a threaded tip ta enableaccessarytips ta be applied-see page12. values. Screwconnectionwith cylindrical guidingsecuresnaturalstability and facilitatesassembly.The internalthreadcannotbe damaged. 7 "Also to be used with precipitation" "Also to be used with precipitation" Safe operation also in case of precipitation secured by separate closed glasfibre-reinforced insulated tubes with plastic insulators which interrupt flow of water. Valtage indicatian is given by twa well-separated calaured lamps. These ensure clear indicatian under unflavaurable canditians, e. g. against bright sunlight. The compactconstruction enables the testerto be usedin narrow rooms.Dueto constructivefeatures the test is passedalso under precipitationand the operating voltageis far belowthe admissive values. Single Voltage Range Testers Type No. Nominal Voltage / Vil1ual Value 50-60 Hz Dimensions Weight 30 36 LV LI LH 12 20 24 LG 7;2 kV kV kV kV mm mm mm mm 5-6 10 / each kg 610132 1265 480 540 245 1,45 610134 1460 675 540 245 1,75 Availablefor storageand transport: Carryingcasefor types 610131-610133 900 mm Ig. 610128-610134 1100 mm Ig. Forfurtherdetailssee page12. To switch on and carry out the safety check, the push button is depressed. If the light changes from green to red when the button is pressed and then back to green again, the ARCUSLIGHT is operating correctly and is ready for use. Wide Valtage Range Testers Type No. Nominal Voltage / Virtual Value 50-60 Hz 5 10 12 20 24 30 6 kV kV kV kV Dimensions each LG LV mm mm 1585 and weights Weight LI LH 36 610129 Dimensions Thefollowingmanufacturers have checkedthe applicationof the ARCUSTON on their switchgear: CalorEmag,Sachsenwerk, AEG, BBC.We will be pleasedto provide infonnationwith regardto other manufacturers on request. are approximate 800 mm 540 mm 245 / The indication "line alive" is not affected by stray voltages when the conductor-earth voltage of the item to be tested is at least 40 % of the nominal voltage rating of the tester. kg 1,75 The integral self~heGking deviGe verifies the GorreGtoperation of the GompleteeleGtroniGGirGuit,without the neGessityof applying an external voltage. values. Screwconnectionwith cylindrical guidingsecuresnaturalstability and facilitatesassembly.The internalthreadcannotbe damaged. 8 "1 "Also to be used with precipitation" Safe handling also with precipitation secured by foamed glasfibrereinforced insulated tubes with plastic insulatorn which interrupt flow of water. After "siliconing" the extension probe is safe against bridging in case of precipitation. Voltage indication is given by two well-separated coloured lamps. These ensure clear indication under unfavourable conditions, e. g. against bright sunlight. This live line tester is a special execution tor small stations such as Isopont, Mipak and Krone KES 10. Use in these stations is possible because ot the slender, long tip. It can be inserted into openings with a diameter of 14 mm. Type-No. 610136 tor nominal voltage: UN = 10 kV/50 -60 Hz Virtual value: Um = 12 kV/50-60 Hz Available for storage and transport: Canying Gase900 mm long. For further details see page 12. Dimensions: lH Lj LV LG Weight / each 1250 480 540 240 1,5 kg mm mm mm mm To switch on and carry out the safety check, U1epush button is depressed. If the light changes from green to red when the button is pressed and then back to green again, the ARCUSLIGHT is operating correctly and is ready for use. The integral self-checking device verifies the correct operation of the complete electronic circuit, without the necessity of applying an extemal voltage. The indication"Iine alive" is not affectedby strayvoltageswhenthe conductor-earth voltageof the item to be testedis at least40 % of the nominalvoltageratingof the tester. Screw connection with cylindrical guiding secures natural stability and facilitates assembly. The internal thread cannot be damaged. 9 D --' ~ .~~ "Also to be used with precipitation" Medium Voltage ARCUSTON Order No.698 576/5Weight: Total length: Transport length: 30 kV 2,0 kg 1645 mm 1235 mm This valtage tester is equipped with 3 valtage levels tar the camplete medium valtage. The labeion the switching ring shows the possible adjustment to 5-10kV 10-20 kV 20-30 kV before the live line test. As with all long standing acoustical voltage testers the electronic circuit and the batteries are automatically tested during switching on and off when turning the switching ring. In the position "function control" a permanent sound is heard to show that the tester is operating orderly. After switching rupted sound changes into when touching on the tester an intercan be heard which a permanent sound a live line with the test tip. The voltage tester with precipitation. The VDE-GS-symbol ted by the VDE-test is suitable tor use has been granorganisation. The tester is separable into 2 parts tor transport by means ot a coupling. "Also to be used with precipitation" Safe operation also in case of precipitation secured by separate closed glasfibre-reinforced insulated tubes with plastic insulators which interrupt flow of water. WhilstGontaGt with the partsto be GheGked is madevisually,the ear will deteGtthe soundsignal independently. The compactconstructionenables the testerto be usedin narrow rooms.Dueto constructivefeatures the test is passedalso under precipitationand the operating voltageis far belowthe admissive values. The followingmanufacturers have checkedthe applicationof the ARCUSTON on their switchgear: CalorEmag,Sachsenwerk, AEG, BBC.Wewill be pleasedto provide infonnationwith regardto other manufacturers on request. Rigidcarryingcase1290mm length type 615019or carryingbag type 69863305. This ARCUSTON is switchedon with a 5-stageswitchingring. By compulsionthe functionof the electronicsectionand the load conditionof the batteriesis tested in the secondswitchingposition. The indication "Iine alive" is not affected by stray voltages when the conductor-earth voltage of the item to be tested is at least 40 % of the nominal voltage rating of the tester. The integral self-checking device verifies the correct operation of the complete electronic circuit, without the necessity of applying an external voltage. Screwconnectionwith cylindrical guidingsecuresnaturalstability and facilitatesassembly.The internalthreadcannotbe damaged. 10 ß ~~ ~i ARCUSDISTANT III Order no.61 0 250 UN = 110- Weight: Length: 380 kV 1,2 kg 950 mm The acoustical distance tester ARCUSDISTANT III can be used to determine whether an h. v. overhead line is alive from the position of the traverse of the mast without galvanic contact. The 2-part tester consists insulating rod (2). of an electronic indicating section (1) and the In assembled condition the indicating section is traversable on the operating rod (3). This enables the user to place the tester parallel to the axis of the insulator independent Iy from his position. The green mark (4) on the indiGating seGtion has to be GontaGted to the insulator armature whiGh is earthed at the mast. The deteGtion whether the respeGtive overhead line is alive or dead is Garried out with the extension part (5) whiGh dives into the eleGtriG field with its length 4. Since almost 20 years our enterprise otters distance testers from 110 kV on. On high voltage masts the detection of the absence of tension is considerably facilitated by the use of distance testers. On the other hand different influences from the outside have an effect on the response behaviour of the ARCUSDISTANT III as the voltage state of the conductor to be tested has to be proven at the electrical field of the protection armature which is earthed at the mast. For voltage testing speciallyon masts with several systems of different nominal voltage, angular masts, etc., weil experienced personnel is required. The safest method is to carry out the test during disconnecting where the change from a permanent tone to an intermittent signal is considered as reliable indication of a disconnected overhead line. In the meantime the cammittee 214.4.6 "Distance Valtage Testers" has elabarated a VDE-guideline ta which the ARCUSDISTANT III is adapted. Carrying bag tor storage and transport Order No.616 065 Carrying bag with strap and zipper made of waterproof nylon material and a stuffing of cellular caouchouc, dimensions 810x200x120 mm. 11 - Fork contact Probe Extension for use in encapsulated switchgear. Can be bridged across phases up to UN 10 kV. Suitable for ARCUSTON and ARCUSLIGHT. Order ref. 611009 Order ref. 698766 Contact tor use on overhead lines. Suitable tor ARCUSTON and ARCUSLIGHT tor system voltages 5 -60 kV. Order ret. 611 011 Storage for tube \ZS21 mm1) for tube \ZS24 mm 1) Type no. Type No.611 Siemens 8 CK ~ 615029 15030 615019 Up to UN 30 kV safe against bridging, also to be used with precipitation, suitable for ARCUSTON and ARCUSLIGHT. no. Type no. tor tube tor tube 21 mm ~ 1) 24mm~1) length mm I 1698760 I 830 885 611018 I 698650 I 1190 1245 611019 I 698761 I 360 415 "Also to be used with precipitation" I) i 830 885 In case of order pIease state the tube diameter extension tip of the high voltage live line tester. 12 260 110 1100 260 110 1290 260 110 Rod support Switching "Not to be used with precipitation" I 698762 Height 900 Upon request Garrying Gases with shaped foam inlays or Gases with additional inlays for aGGessories are available. length mm 611013 611025 Width mm Total Operating 1 cases Outside dimensions Length 017 Extension Type and carrying Carrying case tor ARCUSTON and ARCUSLIGHT up to UN 60 kV made ot rigid plastic material with toamed inlay. Tip tor Station Type piece of the Rod Head shartened. tor storage ot tester, operatingand earthing rods -with a flexible grip roller. Can be tixed onto the wall by means ot two screws. Order Type No.611 020 can be screwed ARCUSLIGHT-rads ref. 611015 anta which ARCUSTONcannat be