Digital
Time Switch
TB62
Features
• Standard housing 35 x 90 x 61mm in line with
DIN 43880 - 2 TE
• Two models: 1-circuit and 2-circuit types
• Weekly programming
• Switching function: ON - AUTO - OFF
• Automatic changeover standard time/daylight saving
time for Europe, UK and the USA
• Vacation mode
• Running reserve for 6 years (in case of power
failure)
• 50 programs
• Minimum switching interval: 1 minute
• Manual override key ON/OFF on the front
• Manual operation can be locked out
• Reset key
• LED operation display
• Cover can be swung open
• Cover can be secured
• Output: Relay 1c, 250V AC, 16A
• Rated operating voltage: 230V AC, 50/60Hz
• Mounting method: Wall mounting, DIN rail
TB6210187
1 circuit
TB6220187
2 circuits
TB6210187
with cover open
Product types
Model numbers
Operating voltage
Running reserve
TB6210187
Digital time switch, weekly programming, 1 circuit
Description
220-240VAC
6 years
TB6220187
Digital time switch, weekly programming, 2 circuits
220-240VAC
6 years
TB62203777
Terminal cover and mounting plate for wall mounting
Technical Data
Model number
TB6210187
TB6220187
Type
1 BRTU according to EN60730-2-7
Program cycle
Weekly
Operating voltage
220-240VAC (-15% to +10% of the operating voltage)
Frequency
50-60Hz
Power consumption
2W
Switching capacity
Resistive load (cosF=1)
16A / 250VAC
Inductive load (cosF=0,7)
8A / 250VAC
Number of circuits
1
2
Number of circuits
1 relay contact output
2 relay contact outputs
Contact type
1 changeover contact
Driving method
Memory capacity
2 changeover contacts
Quartz oscillation
50 programs
Minimum switching interval
50 programs/circuit
1 minute
Manual switching
Override function
Changeover, standard time/daylight saving time
Yes
Time accuracy
±15 seconds/month (at 25°C)
Running reserve
6 years for clock memory and program (lithium battery)
Ambient temperature
-20°C to +55°C
Humidity
Max. 85%
Applicable wire
Max. 2.5mm²
Weight
100g
120g
Protection degree II when mounted properly
Protection degree
IP20 according to EN60529
Pollution degree
3
Overvoltage category
III
03/2009
TB 62
Dimensions, Part names
61
55
44
(Unit: mm)
40
35
33
5.5
1.8
Front cover
6 L
Manual operation
button
POWER
ON/OFF
ON/OFF
1
2
65
45
130
90
1 2
65.2
45
4 5
Mounting plate
(optional)
1 2
3 N
Terminal cover
(optional)
1
8
34.5
Indicators and buttons:
1 Power
2
3
4
10
9
,
5
6
7
Mounting
2
3
7
4
6
5
s DIN rail mounting
8 Output
: ON
: OFF
9
: Summer time
: Winter time
10 Manual button locked
s Removal
1 Hook
DIN rail
(DIN EN 50022,
35mm)
2
1
Pull down DIN rail attachment lever to
release. Lift.
2 Push on
s Secure front cover
Thread wire, etc. through hole
and secure.
4
5
6
s Direct mounting
*TB6220377 (* (optional parts) *)
1 terminal cover, 1 mounting plate
4
*
L
5
6
*
L
CAUTION: Minimize the wire hole to ensure
class II construction.
Connection diagram
1-circuit type
2-circuit type
Load 2
Power
source
1 2
Power
source
Load
3
L
4 5
6
L
N
1 2
3
N
Power
source
Power
source
03/2009
Load 1
Power
source
TB 62
MODE Press “MODE” to set the clock, select the program, make holiday settings and set summer or winter time.
front cover open
[Normal]
[Clock]
[Program] 1
[Holiday]
[Program] 2
[Summer / Winter]
[Normal]
2-circuit types only
front cover close
Clock setting
year
month
day
hour
minute
second reset
year
Program setting
Number of programs
remaining
hour ON
minute ON
day ON
(m)
hour OFF
day OFF
Next program
setting
(m)
: Press to confirm the flashing day and pass to the next.
: Press to ignore the flashing day and pass to the next.
(m)
Review, add, clear or change program.
Holiday setting
minute OFF
This function allows you to cancel ON programs for the holidays specified.
start year
start month
start day
end year
end month
end day
start year
Setting is completed
Summer / Winter time setting
EURO
UK
Preset time in
following table.
Preset time in
following table.
USA
configuration
Preset time in
following table.
Preset time
EURO
UK
USA
Summer time start date
Last Sunday in March at 2AM
Last Sunday in March at 1AM
Second Sunday in March at 2AM
manual
Program start date of
summer and winter time.
See below.
: Press in normal mode to switch between
summer and winter time.
Winter time start date
Last Sunday in October at 3AM
Last Sunday in October at 2AM
First Sunday in November at 2AM
(mm) week indication
Programming the start date of summer time and winter time
configuration
start month
start month
start minute
start week
(mm)
start hour
start day
start hour
start week
start day
first week
fourth week
second week
last week
start minute
(mm)
start month
third week
Setting is completed.
Manual operation
The manual operation button can be operated when the
front cover is closed.
Press the manual operation button for 1 second to switch
between manual and programmed operation.
4 5
1 2
6 L
ON/OFF
ON/OFF
1
2
1 2
: Function to lock out manual operation
+ : Press these buttons simultaneously to activate or
deactivate the lock.
POWER
unlocked
+
+
3 N
03/2009
locked
Download