ALSECURE
Fire, safety and
environmental cables
Trust Alsecure
you safe and
Alsecure is the cable you can stake your
reputation on when safety and security
are critical – to maintain circuit integrity
for mains power, lighting, alarms, pumps,
and other essential services when under fire.
Contents
Introduction2
Alsecure® Envirolex®4
Building Flat 6
Flexible Single Core
8
Data10
Alsecure® Premium® INFIT™
12
Single Core 90ºC
14
Multicore 90ºC
16
Instrumentation (COMING SOON)
20
Technical
Nomenclature and Fire Resistance Cable Rating System
22
Installation Guide
24
The Cable Range
25
e to keep
secure.
Nexans Olex Alsecure range is highly flexible and can be
handled and installed safely and easily with standard tools
just like normal building cables.
For more information on these products or for information
on Nexans Olex power, industrial and mining products, visit
www.olex.com.au
1
Building a sustainable
future with Nexans Olex.
Sustainable development has become a major concern in
As a result, Nexans Olex have developed a three tier offering
our society in recent years. For the construction industry,
for its range of environmental, fire and safety cables for the
particularly in buildings, sustainable development implies
building and construction industry based on the following
a built environment which is habitable, safe and healthy.
considerations:
Nexans Olex recognizes the importance of sustainable
Adopting GBCA guidelines on Best Practice PVC, to ensure
development in the building and construction industry and
this material is used (manufactured and processed) in a
opportunities for advancement of cable design and technology.
responsible manner throughout our manufacturing plants,
suppliers’ value chain and end of life management.
Halogen free fire retardant products for a safe and healthy
building environment.
Long life cables made from materials with low
environmental impact both during and after service life.
2 |
Environmental, fire
and safety cables
PVC Best Practice Manufactured Cables
Nexans Olex complies with GBCA PVC Best Practice Guidelines.
All PVC used in Nexans Olex manufactured cables follows the
guidelines for Best Practice PVC.
Using Nexans Olex manufactured PVC cables can contribute
to your project earning points towards your new building’s
GBCA Green Star rating (PVC Best Practice Audit document
is available upon request).
Alsecure® Envirolex®
Extensive range of enhanced performance cables for the
construction industry engineered from low smoke halogen
free materials with improved fire retardant properties
(over standard PVC cables) reduced smoke, acid gas and
hazardous fume generation particularly under fire conditions,
while retaining the excellent mechanical and electrical
properties designed into Nexans Olex cables.
Alsecure® Premium INFIT® (Ceramifiable®)
Complete range of high performance fire safety/ fire resistant
cables engineered from materials developed in conjunction
with CSIRO. This unique cable polymeric insulation material
hardens into a protective ceramic shield when exposed to fire,
maintaining circuit integrity and life-saving essential services.
In addition to its unique property, the material has low calorific
value and fire retardant properties with minimal generation of
hazardous smoke and corrosive fume emissions.
Electric cables and their use can
contribute towards sustainable
construction because they can
be an important contributor
to energy efficiency, providing
a safe and healthy built
environment and protect people
and equipment in case of
emergency or fire.
Fire Resistant
Flame Retardant
Low Smoke Zero Halogen
No Acid Gas & Hazardous
Fume Emissions
Mica Free
Medium Fire Performance
Flame Retardant
Low Smoke Zero Halogen
Reduced Acid Gas
& Hazardous Fume
Emissions
Lead and other
Heavy Metal Free
Alsecure ®
Premium INFIT ™
(Ceramifiable)
Alsecure ® Envirolex ®
PVC Best Practice Manufactured Cables
As defined by GBCA
3
For a safer environment,
you can breathe easy.
Alsecure® Envirolex® cables are an extensive range
of enhanced performance cables for the construction
industry engineered to dramatically reduce
Cl
Br
Fl
environmental impact, particularly under fire conditions,
while retaining the excellent mechanical and electrical
properties designed into Nexans Olex cables.
4
Halogen
free
Low
smoke
ALSECURE
ENVIROLEX
®
Alsecure Envirolex
®
®
®
Alsecure® Envirolex® cables are an extensive range of enhanced performance cables
for the construction industry engineered to dramatically reduce environmental impact,
Alsecure® Envirolex® Building Flat
6
properties designed into Nexans Olex cables. Olex uses a variety of inorganically filled
Alsecure® Envirolex® Flexible
8
polyolefin based materials to engineer the cables in the Alsecure Envirolex range to
Alsecure® Envirolex® Data
particularly under fire conditions, while retaining the excellent mechanical and electrical
®
®
10
meet a wide variety of end users and performance requirements.
Cable types from building wires, flexible, low voltage power, multicore control and data.
Applications
Advantages of Alsecure® Envirolex® Cables
Conductor range up to 630mm2 for single core cables
Improved performance in case if fire:
– Flame retardant/self-extinguishing
– Reduced acid, gas and smoke generation
– Non-corrosive
– Reduced toxicity
Halogen free (i.e. no chlorine, bromine etc.)
Lead free
Easy termination and installation requirements
Made in accordance with Australian Standards
Alsecure® Envirolex® cables have been tested according to and comply with the
requirements as specified in AS1660.5.6.
Alsecure® Envirolex® products include readily strippable cables for general construction
purposes as well as the tougher products commonly found in cables with high
performance capability.
Alsecure® Envirolex® materials can also be used as alternatives for all other low voltage
power and control cables (Refer Nexans Olex Handbook for Low Voltage power and
Control cable from pages 8 to 25). Cables are available on request, subject to minimum
production run.
Setting the highest standards
Properties Australian Standards
International Standards
Flame Retardant
AS/NZS1660.5.6
IEC60332-1
Bunched Retardance
AS/NZS1660.5.1
IEC60332-3-2A
Low Smoke AS/NZS1660.5.2
IEC61034-2
Halogen Free AS/NZS1660.5.3
IEC60754-1
Non Corrosive AS/NZS1660.5.4
IEC60754-2
Get product and
technical information
wherever you are with
the Olex Handbook app.
See page 25 for details.
Cl
Br
Fl
Fire
resistant
Low
smoke
Corrosion
resistant
Electro magnetic
interference
Low
smoke
Operating
temp 90°C
Flame
retardant
Halogen
free
Operating
temp 90°C
High
flexibility
Flame
retardant
Chemical
resistance
Cl
Br
Fl
Halogen
free
Cl
Br
Fl
5
Alsecure Envirolex
Building Flat
®
®
Alsecure ® Envirolex ® cables have been tested according to and comply with the
requirements of the single flame tests specified in AS/NZ1660-5.6. Alsecure ® Envirolex ®
products include readily strippable cables for general construction purposes as well as
the tougher products commonly found in cables with higher fire performance capability.
Specifications
NominalNominalEarth
insulation
sheath
conductor
thicknessthicknessarea
mmmmmm 2 Nominal Approx. Product
overall
mass
code
diameter
mmkg/100m
Solid Cu
Strand Cu
Solid Cu
Strand Cu
Strand Cu
Strand Cu
Strand Cu
Strand Cu
0.6
0.6
0.6
0.6
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.0
1.1
1.1
1.2
1.3
1.0
1.5
2.5
2.5
2.5
2.5
4.0
6.0
9.0x4.25.7
10.0x4.67.2
11.2x5.011.0
11.7x5.311.1
13.4x6.215.2
14.5x6.819.2
17.0x7.829.8
19.7x8.943.7
CTCP02JA002
CTCP05JA002
CTCP06JA002
CTCP07JA002
CTCP09JA002
CTCP11JA002
CTCP13JA002
CTCP15JA002
Strand Cu
Strand Cu
0.6
0.6
0.9
1.0
1.5
2.5
12.7x4.69.4
14.9x5.314.6
ETCP05JA003
ETCP07JA003
Nominal Main
conductor
conductor
area
type
mm 2
2C+E
1.0
1.5
2.5
2.5
4.0
6.0
10.0
16.0
3C+E
1.5
2.5
Construction 2 & 3 core + earth flat, 450/750V X-90 (XLPE) insulated,
HFS-90-TP sheathed to AS/NZS 5000.2, copper conductor, 90°C.
6 |
ALSECURE
ENVIROLEX
®
®
Enhanced performance cables
 L ow Smoke
 F lame Retardant
 S elf – Extinguishing
 H alogen Free
 L ead Free
 L ow Acidity
 N on Corrosive in Fire Situations
Single Phase Current Ratings
Two core XLPE/PVC 90° 0.6/1kV cables.
Table of ratings are also applicable to armoured cables.
 N o Special Termination or
Installation Requirements
.
Unenclosed
Enclosed
Buried
Underground
Cond. Spaced
Touching
Conduit in
Unenclosed
Unenclosed
direct
ducts
size
air round & partially
& completely or flat
surrounded
surrounded
cable
by thermal
by thermal
mm 2
insulation insulation
Single
phase
voltage
drop
mV/A.m
1
1.5
2.5
4
6
10
16
Cu
54.1
34.7
18.9
11.8
7.85
4.68
2.95
Cu
18 24 34 45 57 78 104 Cu
17 22 31 42 53 73 97 Cu
16 20 28 37 46 63 82 Cu
14 18
25
33
42
58 78 Cu
9
11 16 21 27 36 49 Cu
19 24 34 45 56 75 132 Cu
19
24
34
45
56
75
98
Applications
 Power and Lighting
Three Phase Current Ratings
Three and four core XLPE/PVC 90° 0.6/1kV cables.
Table of ratings are also applicable to armoured cables.
Unenclosed
Enclosed
Buried
Underground
Cond. Spaced
Touching
Conduit in
Unenclosed
Unenclosed
direct
ducts
size
air round & partially
& completely or flat
surrounded
surrounded
cable
by thermal
by thermal
mm 2
insulation insulation
Cl
Br
Fl
Three
phase
voltage
drop
mV/A.m
Fire Cu
1.5
resistant 20 2.5
28 CuChemical
30resistance
16.4
Low
smoke
Cu CorrosionCuElectro magnetic
Cu Halogen
19 resistant16 interference15
free
26 24 21
Cu
Operating
9temp
90°C
13 CuHigh
20
flexibility
29 Cu Flame
20retardant
29
Cl
Br
Fl
Halogen
free
Low
smoke
Operating
temp 90°C
Operating
temp 90°C
Flame
retardant
Flame
retardant
Cl
Br
Fl
Halogen
free
Cl
Br
Fl
Halogen
free
FIRE, SAFETY AND ENVIRONMENTAL CABLES
Low
smoke
Operating
temp 110°C
High
flexibility
Physical
toughness
Flame
retardant
Chemical
resistance
| 7
Alsecure Envirolex
Flexible
®
®
Applications Flexible cable is intended for installations with moving equipment,
electric appliances and for building sites. This cable can be installed in open air
or buried (with extra mechanical protection).
Specifications
NominalMaximum
NominalApprox.Product
conductor
diameter
overall mass
code
area
of wires
diameter
mm 2mm mm kg/100m
100.218.514
BZHX01AA001
160.219.820
BZHX02AA001
25
0.21
11.3
30
BZHX03AA001
35
0.21
12.6
40
BZHX04AA001
50
0.31
14.2
54
BZHX05AA001
70
0.31
16.2
74
BZHX06AA001
95
0.31
18.3
99
BZHX07AA001
120 0.5120.7125BZHE87AA001
150 0.5122.6150BZHE88AA001
185 0.5124.6179BZHE89AA001
240 0.5127.7240BZHE90AA001
300 0.5131.0290BZHE91AA001
400 0.5135.4389BZHE92AA001
500 0.5140.0498BZHE93AA001
630 0.5144.0629BZHE94AA001
Construction 110°C: 0.6/1kV cables, flexible, X-110 (XLPE) insulated and HFS-110-TP
sheathed to AS/NZS 5000.1 (Power) and AS/NZS 1995 (Welding, copper conductors,
110°C continuous, LSOH.
Note: Also available in green/yellow earth 10-120mm 2
8 |
ALSECURE
ENVIROLEX
®
®
Enhanced performance cables
Features and Benefits
 1 10°C
 F lame Retardant
 N o Heavy Metals
 N o Corrosive Emissions
 L ow Smoke
 F lexible
 H alogen Free
Single Phase Current Ratings
Two single core R-HF-110, R-E-110, X-HF-110° cables
UnenclosedEnclosed Buried
UndergroundSingle
C ond. Spaced
Spaced
Touching Conduit
Partially Completely direct
ducts
phase
s ize
from
in air
surrounded surrounded voltage
surface
by thermal by thermal drop
m m2insulation
insulationmV/A.m
Applications
 Welding Flex
CuCuCuCuCu Cu CuCuCuCu
10
103 99 8178 62 40 11988 97
4.97
16
137 131 107104 83 53
154115 1273.12
25
183 175 143137 109 72
198148 1631.99
35
225 214 176165 132 88
238177 1951.43
50
276 261 215205 164 –
282214 2361.07
70
349 328 272255 204 –
346262 2880.751
95
434 406 339321 257 –
416321 3520.556
120
505 471 394369 296 –
473366 4000.453
150
581 540 454430 344 –
531420 4480.382
185
673 624 527493 394 –
601477 5170.323
240
806 743 630594 476 –
698561 6000.271
300
934
857
730––– 789
648694
0.240
400
1094
998
853––– 898
738790
0.216
500
1278
1155
990–––1018
837921
0.199
630
1498
1334
1146–––1148
973
1045
0.185
 S witchboard
 M ains Power
 F lexible Robotic Cable
Three Phase Current Ratings
Three single core R-HF-110, R-E-110, X-HF-110° cables
UnenclosedEnclosed Buried
Underground
Single
C ond. Spaced
Spaced
Touching Conduit
Partially Completely direct
ducts
phase
s ize
from
in air
surrounded surrounded voltage
surface
by thermal by thermal drop
m m2insulation
insulation
mV/A.m
Cl
Br
Fl
Halogen
Fire Cu
Corrosion Electro magnetic
Low
CuCuCuCu
free
resistant
resistant
interference
smoke
10
99 86 81 71 57 16 132 114 107 93 74 25 177 153 143 125 100 Cl
35 Br218 188 176 151 121 Fl 267 50
230 215 182 146 70 339 291 272 234 187 Halogen
Low
Operating
Flame
95
363 33990°C
285
228 free 422 smoke
temp
retardant
120 492 422 394 337 269 150 565 486 453 382 306 185 656 564 526 449 359 Cl
240 Br786 674 629 548 439 Fl 912 300
780 727 626 501 400
1069 Operating
910 847 718 575 Halogen
Flame
500
981 865 692 free 1248 temp1053
90°C retardant
630 1462 1217 1132 983 787 OperatingCuCu
High
Flame Cu
Chemical
Cu
Cu
Cu
temp 90°C
flexibility
retardant
resistance
40 77 77 88 4.3
4.3
53 130 99 115 2.7
2.71
72 168 130 148 1.72
1.72
88 201 155 176 1.24
1.25
–
237 184 212 0.924 0.929
–
291 230 259 0.65
0.657
–
348 277 315 0.481 0.491
–
396 322 357 0.392 0.403
–
445 362 400 0.331 0.344
–
503 415 461 0.28
0.296
–
583 492 533 0.235 0.252
–
657 556 617 0.208 0.227
–
746 631 700 0.187 0.208
–
843 736 815 0.172 0.195
–
947 827 920 0.160 0.184
Cl
Br
Fl
Halogen
free
Low
smoke
Operating
temp 110°C
High
flexibility
Physical
toughness
Flame
retardant
Chemical
resistance
FIRE, SAFETY AND ENVIRONMENTAL CABLES
Cl
Br
Fl
| 9
Alsecure Envirolex
Data/Comms
®
®
Applications Offering you an alternative to standard PVC sheath cables, a range
of LSZH cables for security, data and fire is now available from Nexans Olex.
LAN
Number of
cores/pairs
Nominal
Nominal
Stranding Approximate
conductor
overall
mass for
area
diameter
cable
mm 2mm 2 No./mmkg/100m
Maximum
Sheath colour
Pack sizes
conductor
resistance @20°C
ohm/km
Product
code
4 pairs
4 pairs
0.22
0.22
93.8
93.8
JCAT5ELSZHA3
JCAT6LSOH
5.3
5.3
1/0.50
1/0.50
3.2
3.2
Blue
Grey
300m reel
300m reel
Unscreened Security
Number of
cores/pairs
Nominal
Nominal
Stranding Approximate
conductor
overall
mass for
area
diameter
cable
mm 2mm 2 No./mmkg/100m
Maximum
Sheath colour
Pack sizes
conductor
resistance @20°C
ohm/km
Product
code
4 cores
N/A
0.5
0.75
45.2
26.4
JSC5WT4LSOHB30
JSF75WTBKLSOH
4.7
3.0x6.0
14/0.20
24/0.20
3.4
3.1
White
White/blk stripe
300m box
500m reel
Unscreened Alarm
Number of
cores/pairs
Nominal
Nominal
Stranding Approximate
conductor
overall
mass for
area
diameter
cable
mm 2mm 2 No./mmkg/100m
Maximum
Sheath colour
Pack sizes
conductor
resistance @20°C
ohm/km
Product
code
2 cores
1.5
13.6
JRSI502A3LSOH
5.3
7/0.50
5
Red
300m reel
Screened Data
Number of
cores/pairs
Nominal
Nominal
Stranding Approximate
conductor
overall
mass for
area
diameter
cable
mm 2mm 2 No./mmkg/100m
Maximum
Sheath colour
Pack sizes
conductor
resistance @20°C
ohm/km
Product
code
6 cores
2 pairs
0.22
0.35
95.3
55
JD6CSLSOH
JD2PISLSOHB30
5.5
4.3
7/0.20
7/0.25
4.7
3
Grey
Grey
300m box
300m box
Coaxial
Number of
cores/pairs
Nominal
Nominal
Stranding Approximate
conductor
overall
mass for
area
diameter
cable
mm 2mm 2 No./mmkg/100m
Maximum
Sheath colour
Pack sizes
conductor
resistance @20°C
ohm/km
Product
code
N/A
6.2
62
JBCRG59CCTVLSOH
10 |
–
1/0.60
5.5
Black
500m reel
ALSECURE
ENVIROLEX
®
®
Enhanced performance cables
Features and Benefits
 L ow Smoke
 H alogen Free
 F lame Retardant
 L ead Free
 L ow Acidity
 N o Special Termination
Over the past few years there has been an increase in the awareness
or Installation Requirements
and demand for safety within public places, such as, hospitals,
Applications
government buildings, airports, tunnels and railway stations etc.
 S ecurity System
 A ccess Control
Contractors are now being asked to install cables which, in the
 R ailway Stations
event of fire are non hazardous to the public and the environment.
 H ospitals
 C inemas
 Shopping and Commercial Centres
Nexans Olex has produced a range of LSZH cables which in the
event of a fire, have three main characteristics with safety in mind,
low smoke, low hazardous fumes and low flame propagation.
 Government Buildings/Schools
 Airports
 Tunnels
Cl
Br
Fl
Fire
resistant
Low
smoke
Corrosion
resistant
Electro magnetic
interference
Low
smoke
Operating
temp 90°C
Flame
retardant
Operating
temp 90°C
Flame
retardant
Low
smoke
Operating
temp 110°C
Halogen
free
Operating
temp 90°C
High
flexibility
Physical
toughness
Flame
retardant
Chemical
resistance
Operating
temp 110°C
High
flexibility
Flame
retardant
Flame
retardant
Chemical
resistance
Cl
Br
Fl
Halogen
free
Cl
Br
Fl
Halogen
free
Cl
Br
Fl
Halogen
free
High
flexibility
Cl
Br
Fl
Halogen
free
Low
smoke
Cl
Br
Fl
Fire
resistant
Low
smoke
Corrosion
resistant
Halogen
free
Chemical
resistance
FIRE, SAFETY AND ENVIRONMENTAL CABLES
| 11
Alsecure Projects
Brisbane Airport Link
Value: $10 million AUD
Contract: To supply 1,100kms Alsecure
Premium Fire Resistant Cables
Cable types supplied: 10mm2-630mm2
Single Core, 4mm2- 95mm2 Multicore,
Instrumentation
Project completed: April 2012
Application: Tunnel Cabling – (alarms,
pumps, fans, essential services)
Bligh Street Project
Value: $2 million AUD
Contract: To supply Alsecure Premium
Fire Resistant Cables
Cable types supplied: 10mm2 to 630mm2
Single Core, 2.5mm2 to 95mm2 Multicore
Project completed: 2010
Application: Mains power for essential
services
Next Distribution Centre
Value: $600k
Contract: To supply Alsecure Premium
Fire Resistant Cables
Cable types supplied: 10mm2 to 630mm2
Single Core, 2.5mm2 to 95mm2 Multicore
Project completed: 2012
Application: Mains power for essential
services
Rolleston Coal Project
Value: $330k
Contract: To supply Alsecure Premium
Fire Resistant Cables
Cable types supplied: 300mm2 Single Core
Project completed: 2012
Application: Mains power for essential
services
Ultimate fire
protection.
Fire may destroy everything else in its path, but Alsecure®
Ceramifiable® literally gets tougher. Ceramifiable’s insulation layer
hardens into a protective ceramic shield when exposed to fire,
maintaining circuit integrity and life-saving essential services.
Alsecure® Ceramifiable® stands up to fire without mica tape, making
it more flexible and easier to strip then traditional fire rated cables.
12
ALSECURE
PREMIUM INFIT™
®
INFIT™ –
Alsecure Premium
in Fire Safety Cables
Breakthrough
Originally developed in conjunction with the CSIRO & Cooperative Research Centre for
Alsecure® Premium INFIT™
Polymers, Alsecure® Premium INFIT™ utilises the latest in polymer composite technology.
Single Core Flex 90°C
14
Multicore 90ºC
16
Unlike conventional polymers that breakdown in a fire emergency, the INFIT (previously
known as Ceramifiable®) polymer technology transforms from a flexible, plastic covering
into a tough insulating ceramic barrier that preserves circuit integrity (no breaks or short
Instrumentation and Data
circuits) of essential/critical services and equipment such as fire alarms, emergency
(COMING SOON) 20
lighting, pumps, fans and important process safety continue to operate for period
Applications
of time.
How does Alsecure® Premium® INFIT™ work?
INFIT™ technology operates by including the components to form a ceramic material
into a polymeric matrix that is the insulation of the cable. These components are able to
form a ceramic when activated by the high temperature of a fire. The aspect that defines
the product is that the transition is seamless, in that the ceramic is forming at the same
time as the polymer is degrading. This means that the insulation shape and size remains
approximately the same before and after a fire.
Features and Benefits
Superior fire performance
Zero hazardous fume emissions
Fire
Low
Halogen
free
resistant
smoke
Corrosion
resistant
Electro magnetic
interference
Cl
Br
Fl
Halogen
free
Operating
temp 90°C
High
flexibility
Flame
retardant
Chemical
resistance
Fire resistant
Cl
Br
Fl
Superior
thermal performance

Environmentally
friendly
Halogen
Low
Operating– no mica,
Flame lead or toxic materials
free
smoke
temp 90°C
retardant
High flexibility

ClSafe, easy to use, terminable and handle
Fl
Br
Resistant to mechanical and water impacts
Halogen
free
Operating
temp 90°C
Flame
retardant
Setting the highest standards
Properties Cl
Br
Fl Retardant
Flame
Halogen
Low
Fire
Retardant
free
smoke
Operating
temp 110°C
Australian Standards
International Standards
AS/NZS1660.5.6
IEC60332-1
High
Physical
Flame
AS/NZS
3013toughness
WS52W retardant
flexibility
Chemical
resistance
Circuit Integrity
AS/NZS 1660.5.5
IEC60331.11
Flame
Retardant Cl
AS/NZS 1660.5.1
IEC60332-3
Fl
Low
Smoke
AS/NZS 1660.5.2
IEC61034-2
Halogen
Halogen
free
AS/NZS 1660.5.3
IEC60754-1
AS/NZS 1660.5.4
IEC60754-2
Br
Low
Free
smoke
Non Corrosive For more details on the features
Fire
Corrosion
Low
olex.marketing@nexans.com
resistant
smoke
resistant
Cl
Br
and
Fl benefits,
Halogen
free
Get product and
technical information
wherever you are with
the Olex Handbook app.
See page 25 for details.
please email us at
Operating
temp 110°C
High
flexibility
Flame
retardant
Chemical
resistance
Operating
temp 90°C
High
flexibility
Flame
retardant
Chemical
resistance
Cl
Br
Fl
Fire
resistant
Low
smoke
Corrosion
resistant
Halogen
free
| 13
Cl
Br
Fl
Alsecure Premium INFIT
®
™
(Ceramifiable) Single Core Flex 90ºC
Applications Suitable for use in power circuits, consumer mains, sub mains including
lift sub mains, pumps and essential circuits – 0.6/1KV.
Specifications
Nominal
Nominal
Nominal
conductor
insulation
sheath
cross section
thickness
thickness
area
2
mm
mm mm
Nominal
Approx
Minimum bending
overall mass
radius during
cable
installation
diameter
mm kg/100mmm
kN
10 16
25
35
50
70
95
120
150
185
240
300
400
500
630
9.5 10.5
12.2
13.4
15.4
17.1
19.4
21.6
23.6
26.1
29.3
32.4
36.3
41.7
45.9
0.2
0.3
0.5
0.8
1.1
1.5
2.1
2.6
3.3
4.0
5.2
6.5
8.7
10.9
13.7
1.0 1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
2.8
2.8
1.4 1.4
1.4
1.4
1.4
1.4
1.5
1.5
1.6
1.7
1.8
1.9
2.0
2.1
2.2
16 22
33
42
59
78
105
128
156
189
249
303
390
508
647
45 50
60
80
90
105
115
130
140
155
175
195
220
250
275
Colours – insulation white (natural), outer sheath – red.
Construction 0.6/1 kV, Single Conductor, Stranded Flexible (Class 6 to AS/NZS 1125)
Plain Annealed Copper, INFIT™ Ceramifiable ® (HFI-90-TP to AS/NZS 3808) Insulated,
Halogen Free Flame Retardant (HFS-90-TP to AS/NZS 3808) Sheathed Cable to AS/NZS 5000.1,
90°C Maximum Operating Temperature, WS52W Fire Rated to AS/NZS 3013.
14 |
Maximum
pulling
tension
Product
code
PXKX01AA001
PXKX02AA001
PXKX03AA001
PXKX04AA001
PXKX05AA001
PXKX06AA001
PXKX07AA001
PXKE87AA001
PXKE88AA001
PXKE89AA001
PXKE90AA001
PXKE91AA001
PXKE92AA001
PXKE93AA001
PXKE94AA001
ALSECURE
PREMIUM INFIT
®
®
Fire Rated – Ceramifiable®
Features and Benefits
 Easy to Install
 No Mica Tape
 No Protective Equipment Needed
 Fire Resistant
 Non Hazardous
 No Heavy Metals
 No Corrosive Emissions
Single Phase Current Ratings
Two single core HFI-90-TP, 90° 0.6/1kV cables
 Low Smoke
UnenclosedEnclosed Buried
UndergroundSingle
C ond. Spaced
Spaced
Touching Conduit
Partially Completely direct
ducts
phase
s ize
from
in air
surrounded surrounded voltage
surface
by thermal by thermal drop
insulation
mV/A.m
m m2insulation
 Low Calorific Value
 Flexible
Applications
CuCuCuCuCu Cu CuCuCuCu
10
8381 6464 51 32
7777 86
4.87
16
110
106858266 43 13698 110
3.10
Cl
25
147141 114109 87
57
173127 1422.00
Br
Fl
35
183174 141132 105
71
210154 1711.43
50
231218 178167 134 –
256190 2121.00
Halogen –
Fire 292274
Corrosion
Electro magnetic
Operating312232
High
Flame
Chemical
Low
70
225204
163
2570.718
free
resistant
resistant
interference
temp 90°C
flexibility
retardant
resistance
smoke
95
351328
271248
198 –
364276
2990.558
120
418389 322286 229 –
419319 3500.448
150
483448 373336 269 –
473368 3950.375
Cl
185
528412 4500.323
Br 555512 428377 301 –
Fl 668613 515452 361 –
240
616486 5230.269
300
772
705
594
–
–
–
693
548
604
0.239
Halogen
Low
Operating
Flame
400
933
843
715
–
–
–
804
650
700
0.211
free
smoke
temp 90°C
retardant
500 1090
975
830
–
–
–
906
733
812
0.195
630 1288
1135
969
–
–
–
1031
860
931
0.181
 Power Circuit
 Consumer Mains and Subs Mains
 Lift Sub Mains
 Pumps
 Essential Circuits
Cl
Three
Br Phase Current Ratings
Fl
Three single core HFI-90-TP, 90° 0.6/1kV cables
Halogen
Operating
Flame
free UnenclosedEnclosed
temp 90°C
retardant
Buried
Underground
Single
C ond. Spaced
Spaced
Touching Conduit
Partially Completely direct
ducts
phase
s ize
from
in air
surrounded surrounded voltage
surface
by thermal by thermal drop
m m2insulation
insulation
mV/A.m
Cl
Br
Fl
Chemical
Halogen
Low
Operating
High
Physical
Flame
Cu
CuCuCuCu
Cu
CuCu
Cu
Cu
Cu
resistance
free
smoke
temp 110°C
flexibility
toughness
retardant
10
81 69 64 55 44 32 66 66 78 4.22
4.22
16
106 91 85 73 59 43 115 85 99 2.68
2.68
25
142 121 114 94 75 57 146 109 128 1.73
1.74
35
177 151 141 118 94 71 176 134 154 1.24
1.24
Cl
Br
50Fl 223 191 178 144 115 –
215 163 191 0.869 0.875
70
283 241 225 183 146 –
261 203 231 0.622 0.630
Low
Halogen
95
341 290 271 214 171 –
304 237 268 0.483 0.492
free 406 smoke
120
346 322 256 205 –
349 279 313 0.388 0.399
150
470 400 372 291 233 –
394 316 352 0.325 0.338
185
540 459 427 334 267 –
440 357 401 0.280 0.295
240
651 553 514 391Cl
313 –
511 416 465 0.233 0.251
Br
300
752 637 591 458 Fl
366 –
575 479 537 0.207 0.227
400
909 764 709 533 426 –
664 554 620 0.183 0.204
Corrosion
High 746 Flame
Chemical
Low
Halogen
500Fire 1062 884 821 630
504 Operating
–
642 717
0.169 0.192
resistant
resistant
temp
110°C
flexibility
retardant
resistance
smoke
free
630 1256 1030 956 719 575 –
846 729 818
0.157 0.181
Cl
Br
Fl
Fire
resistant
Low
smoke
Corrosion
resistant
Halogen
free
Operating
temp 90°C
High
flexibility
Flame
retardant
Chemical
resistance
FIRE, SAFETY AND ENVIRONMENTAL CABLES
Cl
Br
| 15
Alsecure Premium INFIT
®
™
(Ceramifiable) 90ºC Multicore
Applications Suitable for use in power circuits, consumer mains and sub mains
including lift sub mains, pumps and essential circuits – 0.6/1KV.
Specifications
Number NominalNominalNominal
of
conductor
insulation
sheath
cores
cross section
thickness
thickness
area
2
mm mm mm
Nominal Approx.
Product
overall
mass
code
diameter
mmkg/100m
2
0.75
1.0
1.8
10.6
14.1
PEKE99AA002*
3
0.75
1.0
1.8
11.1
16.0
PEKE99AA003*
4
0.75
1.0
1.8
12.0
18.6
PEKE99AA004*
3+E
1.51.01.8 11.9
19.8
PDKP05AA003
4
1.51.01.8 12.2
20.3
PEKP05AA004
4+E
1.51.01.8 12.9
23.4
PDKP05AA004
2
2.51.01.8 11.8
22.8
PEKP07AA002
2+E
2.51.01.8 12.2
22.4
PDKP07AA002
3
2.51.01.8 12.4
23.1
PEKP07AA003
3+E
2.51.01.8 13.2
26.6
PDKP07AA003
4+E
2.51.01.8 14.3
31.2
PDKP07AA004
2
4.01.01.8 12.9
27.9
PEKP09AA002
2+E
4.01.01.8 13.1
27.1
PDKP09AA002
3
4.01.01.8 13.6
29.5
PEKP09AA003
3+E 4.01.01.8 14.2
32.7
PDKP09AA003
4+E
4.01.01.8 15.4
39.8
PDKP09AA004
Colours: 2 Core – red, black
3 Core – red, white, blue
4 Core – red, white, blue, black
*Coming soon.
Construction 0.6/1 kV, Multiple Conductor, Stranded (Class 2 to AS/NZS 1125) Plain Annealed
Copper, INFIT™ Ceramifiable ® (HFI-90-TP to AS/NZS 3808) Insulated, Halogen Free Flame Retardant
(HFS-90-TP to AS/NZS 3808) Sheathed Cable to AS/NZS 5000.1, 90°C Maximum Operating
Temperature, WS52W Fire Rated to AS/NZS 3013.
16 |
ALSECURE
PREMIUM INFIT
®
®
Fire Rated – Ceramifiable®
Features and Benefits
 Easy to Install
 No Mica Tape
 No Protective Equipment Needed
 Fire Resistant
 Non Hazardous
 No Heavy Metals
 No Corrosive Emissions
Single Phase Current Ratings
Two Core or Two Core and Earth HFI-90-TP, 90° Cables 0.6/1kV
Unenclosed
Enclosed
Partially
Buried
Underground
Cond.
Spaced
Touching
Conduit
surrounded
Completely direct
ducts
size
in air
by thermal
surrounded insulation
by thermal mm2insulation
 Low Smoke
Single
phase
voltage
drop
mV/A.m
 Low Calorific Value
Applications
CuCu
Cu
CuCuCu
Cu
118 171614 9
1919
1.5
24 222018 11
2424
2.5
34 312825 16
3434
445 423733 21
4545
Cu
54.1
34.7
18.9
11.8
 Power Circuit
 Consumer Mains and Subs Mains
 Lift Sub Mains
 Pumps
Three Phase Current Ratings
Three Core or Three/Four Core and Earth HFI-90-TP, 90° Cables 0.6/1kV
 Essential Circuits
Unenclosed
Enclosed
Partially
Buried
Underground
Cond.
Spaced
Touching
Conduit
surrounded
Completely direct
ducts
size
in air
by thermal
surrounded insulation
by thermal mm2insulation
Single
phase
voltage
drop
mV/A.m
CuCu
Cu
CuCuCu
Cu
116 141312 7
1616
1.5
20 191615 9
2020
2.5
28 262421 13
2929
438 353028 18
3737
Cu
46.8
30
16.4
10.2
Cl
Br
Fl
Fire
resistant
Low
smoke
Corrosion
resistant
Halogen
free
Operating
temp 90°C
Flame
retardant
Chemical
resistance
FIRE, SAFETY AND ENVIRONMENTAL CABLES
| 17
Alsecure Premium INFIT
®
™
(Ceramifiable) 90ºC Multicore
Applications Suitable for use in power circuits, consumer mains and sub mains
including lift sub mains, pumps and essential circuits – 0.6/1KV.
Specifications
Number NominalNominalNominal
of
conductor
insulation
sheath
cores
cross section
thickness
thickness
area
mm 2 mm mm
Nominal Approx.
Product
overall
mass
code
diameter
2+E
3+E
4+E
2+E
3+E
4+E
3+E
4+E
3+E
4+E
3+E
4+E
4+E
14.3
15.4
16.9
16.0
17.3
18.9
19.4
21.3
23.6
26.3
24.7
27.4
33.2
6
6
6
10
10
10
16
16
25
25
35
35
50
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.2
1.2
1.2
1.2
1.4
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
mmkg/100m
Colours: 2 Core – red, black
3 Core – red, white, blue
4 Core – red, white, blue, black
Construction 0.6/1 kV, Multiple Conductor, Stranded (Class 2 to AS/NZS 1125) Plain Annealed
Copper, INFIT™ Ceramifiable ® (HFI-90-TP to AS/NZS 3808) Insulated, Halogen Free Flame Retardant
(HFS-90-TP to AS/NZS 3808) Sheathed Cable to AS/NZS 5000.1, 90°C Maximum Operating
Temperature, WS52W Fire Rated to AS/NZS 3013.
18 |
29
37
45
40
52
65
73
94
108
137
139
176
242
PDTP11AA002
PDTP11AA003
PDTP11AA004
PDTP13AA002
PDTP13AA003
PDTP13AA004
PDTP15AA003
PDTP15AA004
PDTC17AA003
PDTC17AA004
PDTC18AA003
PDTC18AA004
PDTC19AA004
ALSECURE
PREMIUM INFIT
®
®
Fire Rated – Ceramifiable®
Features and Benefits
 Easy to Install
 No Mica Tape
 No Protective Equipment Needed
 Fire Resistant
 Non Hazardous
 No Heavy Metals
Single Phase Current Ratings
Two Core or Two Core and Earth HFI-90-TP, 90° Cables 0.6/1kV
Unenclosed
EnclosedBuried
Underground
Single
Cond.
Spaced
Touching
Conduit
Partially
Completely direct
ducts
phase
size
in air
surrounded
surrounded voltage
by thermal
by thermal drop
mm2
insulationinsulation
mV/A.m
 No Corrosive Emissions
 Low Smoke
 Low Calorific Value
Applications
CuCu
Cu
CuCuCu
Cu Cu
657 534642 27
5656
7.85
1078 736358 36
7575
4.68
16
104 978278 49 13298
2.95
25140 131110105 66
170128
1.86
35173 162132129 81
205154
1.35
50211 197162158
-
244185
1.00
 Power Circuit
 Mains and Subs Mains
 Lift Sub Mains
 Power to Fire Pumps
 Essential Circuits
Three Phase Current Ratings
Three Core or Three/Four Core and Earth HFI-90-TP, 90° Cables 0.6/1kV
Unenclosed
EnclosedBuried
Underground
Single
Cond.
Spaced
Touching
Conduit
Partially
Completely direct
ducts
phase
size
in air
surrounded
surrounded voltage
by thermal
by thermal drop
mm2
insulationinsulation
mV/A.m
CuCu
Cu
CuCuCu
Cu Cu
648 453836 22
4646
6.8
1066 625349 31
6363
4.05
1688 836866 41 11081
2.55
25
119 1119189 56 143
107
1.61
35147 137114110 69
172130
1.17
50180 168136134
-
204155
0.868
Cl
Br
Fl
Fire
resistant
Low
smoke
Corrosion
resistant
Halogen
free
Operating
temp 90°C
Flame
retardant
Chemical
resistance
FIRE, SAFETY AND ENVIRONMENTAL CABLES
| 19
Alsecure Premium INFIT
®
™
(Ceramifiable) Instrumentation & Data
Applications Suitable for use in alarms, pumps, fans and instrumentation.
Designed for use as instrumentation cables 110V AC/150V DC.
Specifications
Number Nominal
Approx. Minimum
of
diameter
mass
bending radius
pairs
during installation
kg/100mmm
mm 2
Conductor 0.75mm 2
1
2
4
6
8
10
12
16
20
24
Conductor 1.5mm 2
1
2
4
6
8
10
12
16
20
24
Maximum
pulling
tension
kN
Product
code
PBKP03AA001
PBKP03AA002
PBKP03AA004
PBKP03AA006
PBKP03AA008
PBKP03AA010
PBKP03AA012
PBKP03AA016
PBKP03AA020
PBKP03AA024
7.8
12.2
13.5
16.3
18.6
20.4
22.3
25.5
28.3
30.9
6.6
13.0
20.5
29.3
38.2
46.2
55.0
71.7
88.5
105.2
115
185
200
240
280
310
340
380
430
460
0.06
0.12
0.24
0.36
0.48
0.60
0.72
0.96
1.20
1.40
8.4
13.2
14.7
17.6
20.2
22.4
24.5
28.0
31.1
33.9
8.0
15.8
25.6
36.9
48.2
59.6
71.0
92.7
114.5
136.2
125
200
220
270
300
340
370
420
470
500
0.12
0.24
0.48
0.72
0.96
1.20
1.40
1.90
2.40
2.90
Colours – insulation natural/black, outer sheath red only.
Individual/Overall Screened and Triple are available upon request. MOQ applies.
M
O
C
Construction 110 V AC / 150 V DC , Multiple Paired Conductor, Stranded Plain Annealed Copper , INFIT™
Ceramifiable ® (HFI-90-TP to AS/NZS 3808) Insulated, Overall Screened with a Polyester/Aluminium laminate tape
and Stranded Tinned Annealed Copper Drain Wire, Halogen Free Flame Retardant (HFS-90-TP to AS/NZS 3808)
Sheathed Cable, 90°C Maximum Operating Temperature, WS51W Fire Rated to AS/NZS 3013.
Note: WS51W Fire rating.
20 |
G
N
I
PBK184AA001
PBK184AA002
PBK184AA004
PBK184AA006
PBK184AA008
PBK184AA010
PBK184AA012
PBK184AA016
PBK184AA020
PBK184AA024
G
ALSECURE
PREMIUM INFIT
®
®
Fire Rated – Ceramifiable®
Features and Benefits
 Easy to Install
 No Mica Tape
 No Protective Equipment Needed
 Fire Resistant
N
O
 Halogen Free
 Non Hazardous
 No Heavy Metals
Alsecure Premium Ceramifiable Instrumentation & Data
O
S
 No Corrosive Emissions
Nominal
conductor
area
mm 2
Maximum
Conductor
Inductive
Insulation
conductor DC
resistance at
reactance at
resistance at
resistance at 50Hz
50Hz
20°C
20°C
Ohm/kmOhm/kmOhm/km MegOhm/km
0.75
1.5
21.2
13.6
27
17.3
0.119
0.111
15
13
 Low Smoke
 Low Calorific Value
Applications
 Pumps and Sprinkler Systems
 Fire Alarms
 Process Control Safety Systems
 Smoke and Gas Detection Systems
Cl
Br
Fl
Fire
resistant
Low
smoke
Corrosion
resistant
Halogen
free
Flame
retardant
Chemical
resistance
FIRE, SAFETY AND ENVIRONMENTAL CABLES
| 21
Technical Information
Nomenclature and Fire Resistance Cable Rating System
AS/NZS 3013:2005 specifies a rating system for wiring code.
Fire Rating
Characteristic letters – WS (‘Wiring System’)
XN/A
Fire protection period – 1 to 5
1
15 minutes
Rating against mechanical damage – 1 to 5
2
30 minutes
3
60 minutes
4
90 minutes
5
120 minutes
Circuit integrity subjected to water after a fire – W
Note
Where a value is not yet determined or applicable an
‘x’ is inserted
WS means wiring system
W means water test after fire
Fire Tests – Fire Retardancy – Bunched Cable Test – AS/NZS1660.5.1
Sample characteristics
Samples vertically tied on a ladder
Number
depending on the non metallic volume per
metre of ladder and the targeted category
Minimum length
3500mm
Test characteristics
Air input
20.5kW burner
Duration 5000 l/min
40min (cat A-B)
20min (cat C-D)
Requirement
Flame spread ≤ 2.5metres
Acid Corrosivity Test – AS/NZS1660.5.4
Sample characteristics
Compound
0.5 to 1g/test
Test characteristics
Furnace temperature
Duration
NFC20453 800°C
others 900°C
NFC20453 20min
EN & IEC 30min
Test outputs
Corrosivity (pH) and conductivity
Requirement
To water pH ≥ 3.5
To water conductivity ≤ 100µ5cm
22 |
Fire Retardant – Single Cable Test – AS/NZS1660.5.6
Sample characteristics
Length600mm
Sample positioned vertically in a standardised cabin
Test characteristics
Calibrated flame
1kW
Flame angle 45°/sample
Flame blue tip touching the cable
Flame application time 1 to 4min depending on the cable diameter
Requirement
To H1 > 50mm
To H2 < 540mm
Low Smoke – AS/NZS1660.5.2
Sample characteristics
Cable length
Number
1.0m
External diameter
(mm)
D > 40
20 < D ≤ 40
10 < D ≤ 20
5 < D ≤ 10
1 < D ≤ 5
Number of test sample
CablesBundles
1
2
3
N1
-
N2
N 1 = 45/D & N 2 = 45/3D
Test characteristics
Standardised alcohol fire source below the samples
Requirement
Cable specification (≥ 80; 70; 60%)
Circuit Integrity Test – AS/NZS1660.5.5
Sample characteristics
Cable diameter
Minimum length
mm
1200mm
Test characteristics
Flame temperature
Ring number
Voltage
Duration 750ºC
cable dia ≤ 10 to 5
cable dia ≤ 10 to 5
cable nominal voltage
105min
(90min with fire + 15min under voltage)
Requirement
Function continuity ≥ 105min
23
Alsecure® Fire Rated Installation Guide
The following installation guide details procedures required to maintain the fire performance features of the Alsecure® – FR range.
This guide is intended to cover typical installation situations, however common sense should always be adopted. In all cases it is the contractor’s
responsibility to ensure that the various standards and regulations applicable to the installation are observed.
AS/NZS 3013: 2005 RATED
Fire Zone
8 No joins or terminations in fire zone.
4 Bends must be supported.
10 x OD
(6 x OD)
Maximum bending radius of 10 x OD based
4 on rigid conductors (Class 2) and 6 x OD based
on flexible conductors (Class 6)
Fixing Devices
45°
Less
than 45°
Max 1000mm
4 Steel percussion bolts*
4 Steel screw & bolt*
4 Steel expansion bolts*
90°
Max 500mm
Fire Rated
Barrier
Fasteners
Greater
than 90°
4 Galvanised steel clips*
8 NO rope/wire/nylon ties
Fire Rated Barrier
Fixing Distances
Double point (WS x 2)
4 Single point (WS x 1)
galvanised saddles*
4 Stainless steel ties*
For emergency lighting,
use fire rated junction boxes
within the fire zone.
Max 250mm
8 NO plastic/nylon/aluminium
Building Structures Equally Fire Rated Walls and Structures (2 hours to AS1530.4)
Where Cable Mechanical Rating
Protection Adequate
Where Additional Mechanical
Protection Required
WS x 1
Fixed direct onto wall/structure
WS x 2
WS x 1
WS x 2
Laid into trays
Steel
Mesh
or
Steel
Sheet
Cover
Tied onto ladders/struts
Suspended onto catenary
Steel Catenary must support cable
over total span.
Anchor points fire rated.
Under Steel
Beam
Steel
Cover
Steel
Pipe
In Corner
Position
*Installation load shall not exceed 50% of manufacturer’s recommended load bearing capacity.
Note: It is the contractor’s responsibility to ensure that Alsecure® Fire Rated cables are installed in accordance with the relevant standards
and regulations for fire rated areas. Contact your local Nexans Olex sales office for further guidelines on suitable fixing methods and materials.
24 |
The Nexans Olex Cable Range
Low voltage power
and control cables
Flexible power
and control cables
Specialised industrial cables
Building wires
Versolex® – XLPE/TPE
Airport lighting cables:
– Primary and secondary cables
Flats
– Power
Automation cables
PVC/PVC SDIs
– Welding
Offshore Oil and gas cables
XLPE/PVC single cores
– EMC/VSD
Defence cables – AO 14,000
PVC/PVC circulars
– Submersible
– VG cables
– Milspec cables
XLPE/PVC multicores
Flexolex EPR/CPE power
Armoured PVC/PVC circulars
Titanex®
Rolling stock cables
Armoured XLPE/PVC multicores
PVC/PVC power
Materials handling cables
Multicore control
PVC/PVC control
Marine cables
Armoured multicore control
Data & communications
cables
Wind turbine cables
Datolex – Security
Extra High Voltage U/G XLPE to 330kV
Neutral screened
Aerial
®
®
Varolex® screened VSD/EMC
HV transmission cables
– Figure 8
(joints, terminations, engineering
Fire performance cables
– Category 5e
services, condition monitoring)
Pyrolex™ Ceramifiable® Fire Rated (FR)
– Coaxial
– single core ES110
Gardolex™ Garden Lighting
Bare overhead conductors
– multicore ES90
Audiolex™ – Speaker
– Coaxial
Fire Safe (FS) power
Rolling stock
Fibre – Multi Mode
– Single Mode
Locomotive
Envirolex®
Telephone – Internal
Instrolex®
instrumentation cables
Data
– External
Overall screened armoured
Mining cables (flexible)
to 33kV
Individual & overall screened
Reeling and trailing cables
Individual & overall screened armoured
to AS/NZS 1802 and 2802
Thermocouple extension wire
Feeder cables
Overall screened
Machine cables
– All Aluminium
– All Aluminium alloy 1120
– ACSR
– Steel earth wire and stay wire
(galvanised or aluminium clad)
HV distribution cables
U/G XLPE to 33kV
Paper insulated lead covered to 33kV
Aerial bundled cable XLPE to 33kV
(metallic and non-metallic screened)
Covered Conductor
Single Point Suspension
HV submarine cables
11kV to 33kV (EHV also)
XLPE, EPR or PILC insulation
The right cable at your fingertips.
Radial water barrier:
– Al/HDPE, LAS, stainless steel sheath
Mechanical protection:
– Single, double wire armour, HDPE,
hessian served
The new Olex Handbook app now
available. Search your app store for
‘Olex Handbook’ or scan a QR code.
25
Australia Head Office 207 Sunshine Road Tottenham
Victoria 3012 Australia Phone 613 9281 4444
Cable Sales Phone 1300 CABLES
New Zealand Paraite Road Bell Block
New Plymouth New Zealand Phone 646 755 9800
www.olex.co.nz
For more information see
www.olex.com.au
OLC14515
LOW VOLTAGE
INDUSTRIAL
HIGH VOLTAGE
FIRE RATED
DATA/COMMS
MINING
Download