Quick Reference Card | for Chiller with 2 Reciprocating Compressors GSC TP 1 ASSIGNMENT OF THE PUSH BUTTONS Hint! Activating a push button by finger touch causes a colour change from blue into light green. Grey marked push buttons can't be activated, a finger touch will not initiate any action. 1.1 Key Push buttons of the upper menu bar Function Call up the menu overview Call up display of actual values Call up Submenus: Settings ® Control (operation mode) ® Compr. speed ® Timer settings ® Sensor values ® Options Call up Submenus: Events ® Alarm messages ® Trend Call up Extras Submenus: (Set up) ® Configuration ® Password ® Date/ Time ® Language ® Service ® Start up manager Move to next screen Back to previous screen | E_894511_4 | 23.10.2013 1 Quick Reference Card | for Chiller with 2 Reciprocating Compressors GSC TP 1.2 Key Push buttons of the lower menu bar Function Switch on the compressor unit, start enabled Switch off the compressor unit, start disabled Start 1st compressor (Press key for 5 sec. in operation mode ”Manual”) Increase capacity of 1st compressor (in case of manual capacity control only) Stop 1st compressor (Press key for 5 sec. in operation mode ”Manual”) Decrease capacity of 1st compressor (in case of manual capacity control only) Start 2nd compressor (Press key for 5 sec. in operation mode ”Manual”) Increase capacity of 2nd compressor (in case of manual capacity control only) Stop 2nd compressor (Press key for 5 sec. in operation mode ”Manual”) Decrease capacity of 2nd compressor (in case of manual capacity control only) Show/ blank help text Show/ blank pulldown menue 2 | E_894511_4 | 23.10.2013 Quick Reference Card | for Chiller with 2 Reciprocating Compressors GSC TP 2 OVERVIEW OF THE OPERATING MODES Operating modes Signal for… Name Remark Start/Stop Capacity +/- 0 Service Compressor motor blocked 1 Manual Manual control via display Manual Manual + Manual 2 Manual + Auto Manual start/stop via display and full automatic local capacity control Manual Auto 3 Auto + Auto Full automatic start/stop and local capacity control Auto Auto 4 Remote Start/stop and capacity demand via digital contacts (hardware) from a remote master controller. The GSC derives from the continuous +/- signals the pulses for capacity (indirect). External External Start/stop and capacity demand via digital contacts (hardware) from a remote master controller. The master also generates the +/- signals as pulses for controlling the slide position directly. External + HW (cont) 5 Remote + HW (pulse) 6 7 8 External pulses Remote Start/stop via digital contacts (hardware) from a remote External + HW (loc. SP) master controller. The GSC controls the output depend- + setpoint ing on a local setpoint (display) and from this setpoint deviation also automatically switches the package On/Off . Local Remote Start/stop via digital contacts (hardware) from a remote External + HW (ext. SP) master controller. The GSC controls the output depend- + setpoint ing on an external setpoint (analog input) and from this deviation setpoint also automatically switches the package On/ Off. Remote Remote Network + Net (cont) 9 continuous Remote + Net (pulse) | E_894511_4 | 23.10.2013 Start/stop and capacity demand via network from a remote master controller. The GSC derives from the continuous +/- signals the pulses for controlling the capacity (indirect). Network Start/stop and capacity demand via network from a remote master controller. The master also generates the +/- signals as pulses for controlling the capacity directly. Network setpoint setpoint continuous Network pulses 3 Quick Reference Card | for Chiller with 2 Reciprocating Compressors GSC TP Operating modes Signal for… 10 Network Local + setpoint deviation setpoint Start/stop via network from a remote master controller. Network The GSC controls the output depending on an external + setpoint setpoint sent via the network and from this setpoint also deviation automatically switches the package On/Off. Network 11 Remote Start/stop via network from a remote master controller. + Net (loc. SP) The GSC controls the output depending on a local setpoint (display) and from this setpoint also automatically switches the package On/Off. Remote + Net-Net SP 4 setpoint | E_894511_4 | 23.10.2013