(A Govt. of West Bengal Undertaking) HIDCO BHABAN, Premises N

advertisement
West Bengal Housing Infrastructure Development Corporation Limited
(A Govt. of West Bengal Undertaking)
HIDCO BHABAN, Premises No.35-1111, Major Arterial Road, 3rd Rotary, New Town, Kolkata-700156
Telephone No. (033) 2324-6037 / 38, Fax: (033) 2324-3016
e-mail: info@wbhidco.in website: www.wbhidcoltd.com
No-HIDCO/GM (E)-IV/93(P-II)/129/Dtd-13/06/2013.
Corrigendum No.3 OF 2013-2014 OF GM (ENGG. )-IV, W.B HIDCO
Sub - “Interior works including acoustic, stage crafting, audio electrical & HVAC system of
auditorium (nearly 1000 capacity) in Vocational Training Institute in AA-IIB, New Town,
Kolkata”
Ref – e-NIT No.12 of 2013-2014 of G.M (E)-IV, WB HIDCO.
In reference to above tender, one BOQ of items with specification is hereby uploaded for the intending
bidders of the above work. The bidders are requested to place their offers according to these B.O.Q items,
in their financial bid in e-tender. Moreover, the bidders have to place rate and amount in B.O.Q sheet
which is being uploaded with this corrigendum and they have to submit it in a separate sealed envelop, to
justify their rates in the financial offer, along with submission of Demand Draft for Tender fees and EMD.
This sealed envelop containing BOQ items rate and amount will be opened along with financial offer of etender on 21.06.2013 at 3.00 P.M. If any discrepancy is noted in between financial offer and supporting
BOQ rate and amount, then the total financial offer will be liable to cancellation.
All other terms and conditions remain unchanged.
General Manager (Engg)-IV
WB HIDCO
TECHNICAL SECTION
SECTION -
TECHNICAL SPECIFICATION
T1
Standard Specification
T2
Design Parameters, ODU & IDU specification
T3
Basis of Design
T4
Standard Specification of Thermal/Acoustic
Insulation
T5
Standard Specification of G.I. Duct Work
T6
Equipment wise Technical Data to be
furnished by the Tenderer
LIST OF APPROVED MAKES
Section T-1
STANDARD SPECIFICATION
The followings terms have been used in the tender specifications.
ISI
Bureau of Indian Standards.
ASHRAE
American Society of Heating Refrigerating & Air-conditioning
Engineers, USA.
ISHRAE
Indian Society of Heating Refrigerating & Air-conditioning
Engineers.
ASME
American Society of Mechanical Engineers.
ASA
American Standard Association.
B.S.
British Standards.
CMH
Cubic Meter per Hour.
BTU/Hr.
British Thermal Unit per Hour.
Kcal/Hr.
Kilo Calories per Hour.
HZ
Hertz.
H.P.
Horse Power
Kg/Cm2
Kilo Gram per Square Centimeter.
SAG
Supply Air Grills.
SAD
Supply Air Diffuser.
SAF
Supply Air Filters.
FD
Fire Damper.
VCD
Volume Control Damper.
RAD
Return Air Damper.
FAD
Fresh Air Damper.
RH
Relative Humidity.
DB
Dry Bulb Temperature.
WB
Wet Bulb Temperature.
DP
Drain Point.
The codes, regulation as detailed below shall be followed in this contract :1.
Safety code for air-conditioning
(revised) amendment 1
1991)
IS 659 : 1964 (reaffirmed
2.
Safety code for mechanical
Refrigeration
1991)
IS 660 : 1963 (reaffirmed
3.
Testing of refrigeration
compressors
IS 5111 : 1993
4.
Air-Cooled heat exchangers
(amendment 1)
IS 10470 : 1983
(reaffirmed 1991)
5.
Metal Duct Work
IS 655/SMACNA/DW – 142
6.
Refrigeration
As per ASHRAE / ISI /
Air-conditioning &
Refrigeration
Air-conditioning institute
Standards / ISHRAE
SAFTEY CODES
The following IS codes shall be followed:
Safety code for mechanical refrigeration
IS 660
Safety code for air conditioning
IS 659
Safety code for scaffolds & ladders
IS 3696 Part – I & II, 1966)
Code of practice for fire precaution in
Welding & cutting operations
IS 3016
Code for safety procedures and practices
In electrical works
IS 5216
Safety code for constructions involving
Use of hot bituminous material
IS 5916 (1970)
Safety requirements for wall openings, railings etc.
Code of practice for safety and health
Requirements in electrical & gas welding
And cutting operations.
IS 4912 (1978)
IS 3696 (1966)
Section– T-2
DESIGN PARAMETERS, ODU & IDU specifications
T2.00 Given below are some design parameters which should be followed in
addition to those given in various sections of technical specifications enclosed.
T2.01
DC INVERTER SCROLL UNIT
a) Temperature of air to inlet of condenser ºC
:
b) Refrigerant
:
48ºC max.
R-410a
SPECIFICATION OF VARIABLE REFRIGERANT FLOW
SYSTEM
1.0
The specifications under this section covers the supply, installation, testing
and commissioning of the VARIABLE REFRIGERANT FLOW SYSTEM
conforming to these specifications and in accordance with the requirements of
the Schedule of Equipment and detailed Bill of Quantities.
1.1
General:
Each VRF Unit shall consist of air cooled outdoor unit, multi-split system air
conditioner indoor unit, each having capability to cool for the requirements of
the individual area to be air-conditioned. The VRF unit should be capable of
connecting different type indoors and Air Handling Units to one refrigerant
circuit and control individually.
Each VRF unit shall have minimum two number scroll compressors and in
each module there shall be at least one DC inverter scroll Compressor (With
controller) and capable of changing the rotating speed to follow variations in
cooling loads. Each indoor units shall have the capability to cool for the
requirement of the rooms.
Compressor installed in each module unit shall be equipped with at least one
DC Inverter Scroll Compressor. The system shall be capable of changing the
rotating speed of Inverter compressor by Inverter controller to follow
variations in cooling and heating load. The vendor should supply imported
factory assembled, wired and tested outdoor unit instead of being shipped in
modular section and later being sub-assembled at site. The Outdoor units
shall be suitable for mix-match connection of all type of Indoor units.
The Unit shall be capable of extending refrigerant piping up to maximum
200m in length with 110 mtrs. height difference between outdoor and indoor
units.
The compressors shall be OEM make.
The minimum COP at full load shall be 3.73 .
The unit shall be suitable for non CFC GREEN refrigerant R-410A.
1.2
OUTDOOR UNIT:
The outdoor unit shall be imported factory assembled, weather proof casing,
constructed from heavy gauge mild steel panels and coated with baked
enamel finish. The unit should be completely factory wired, tested with all
necessary controls tested prior to dispatch conforming to the following
specifications.
a) All outdoor units module shall consist of minimum two scroll compressors
for each Machine with one Inverter drive compressor capable to operate
even when one compressor is unserviceable.
b) The outdoor unit shall be such in design that it facilitates installation one
after another close to each other. Preference would be given to compact
units having smaller foot print.
c) Outdoor units should be rugged of anti-corrosion design and should have
strong base plate for easy mounting of unit.
d) The outdoor unit shall comprise of sub cooling feature to effectively use the
entire coil surface through proper circuit/bridge in order to prevent flushing
of refrigerant owing to large length of piping.
f) The condensing unit shall be provided with microprocessor based control
panel.
g) The outdoor unit shall be provided with Aero spiral design fan exhibiting low
noise level characteristics complete with aero fitting grille to facilitate spiral
discharge of airflow to effect reduction in pressure losses. The fan should be
capable to respond to external static pressure of 5mm.
h) The outdoor unit shall be factory gas charged with
refrigerant R-410A .
high efficiency
i) Motor shall be speed controlled to ensure a stable operation for varying
ambient; by a factory fitted direct acting head pressure activated variable
speed drive to give precise discharge pressure and minimum power
consumption of condenser fan motor.
j) The condenser shall be complete with provisions for refrigerant piping
connections, shut off valves and any other standard accessories necessary
with the equipment supplied.
The condensing unit shall be designed to facilitate fail safe operation when
connected to multiple indoor units.
1.3
Scroll Compressor:
The scroll compressor shall be an industrial quality rugged, cast iron, direct
hermetic compressor with scroll plates, suction & discharge service valves. The
compressor shall be completely enclosed in a chamber with no leakage path
and providing the capability for scroll plates to separate. The compressor shall
be provided with industrial solid motor mounts internal motor protection and
vibration isolation pads. Each compressor shall be independently wired and
piped to its own circuit for efficient operation & ease of maintenance. The
compressor speed shall not exceed 3000 RPM.
The compressor shall be highly efficient DC inverter scroll type. One of the
compressors should be of Inverter control. The inverter compressor shall
change the speed in accordance to the variation in cooling or heating load
requirement through signals analyzed through the micro processor of the Unit.:
a) All outdoor units shall have to operate through inverter drive to give
accurate cooling with minimum required power meet load
fluctuation and indoor unit individual control. All parts of compressor shall
be sufficiently lubricated stock. Forced lubrication may also be employed.
b) Oil heater shall be provided in the compressor casing.
c) The Inverter compressor shall be efficient & reliable & shall be OEM make.
1.4
HEAT EXCHANGER:
The heat exchanger shall be constructed with copper tubes mechanically
bonded to aluminum fins to form a cross fin coil.
a) The aluminum fins shall be covered by anti-corrosion resin film.
b) The unit should have optimized path of heat exchanger for better
efficiency of condenser.
c) The unit shall be provided with necessary number of direct driven low
noise level propeller type fans arranged for vertical discharge. Each fan
shall have a safety guard.
1.5
REFRIGERANT CIRCUIT:
The refrigerant circuit shall include liquid & gas shut-off valves and a solenoid
valves at condenser end. The equipment must have inbuilt refrigerant
stabilization control for proper refrigerant distribution.
1.6
SAFETY DEVICES:
All necessary safety devices shall be provided to ensure safe operation of the
system.
Following safety devices shall be integral part of the out door unit :
a)
High pressure switch
b)
Fan drive overload protection switch
c)
Fusible plug
d)
Overload relay including overload protection for inverter driven
compressor.
Oil Recovery System
Unit shall be equipped an oil recovery system to ensure stable operation with
long refrigeration piping lengths.
The system must be provided with oil balancing circuit to avoid poor
lubrication in any unit.
T2.02 INDOOR UNITS
Air Handling UNITS:
The units shall be floor mounted double skin type suitable for VRF DX system
having multiple circuit with electronic expansion valve. GI outer casing should
be with 0.6mm thickness with 25mm CFC free PUF insulation of density
40KG/cum complete with blower section suitable for static pressure as
mentioned in bill of quantity.
Unit shall have an attractive external casing for supply and return air.
a)
Maximum Face velocity across cooling coil MPM
:
152.0
b)
Maximum face velocity across pre-filters MPM
:
152.0
Section T-3
BASIS OF DESIGN
T3.00 Outside design conditions
Summer / Monsoon / Winter
T3.01 Inside design conditions
Auditorium area
Cleanliness




T3.02
DBT °C
37.8/32.2/13.3
WBT °C
28.3/30.0/8.9
DBT °C
24 ± 1.5 Deg. C
-
RH
60±5%
Filtration level 90% down to 10 micron.
Occupancy
666 for 7206 sqft
Fresh Air
As per ASHRAE 62.1 2007
Illumination
1.1 Watt/sq. ft.
Exposed roof considered as thermally insulated by means of TF quality
thermocole or equivalent thermal insulating material from inside for the airconditioned area.
POWER SUPPLY: Stabilised three phase four wire AC supply i.e. 415
Volts ± 10 % & 50 Hz ± 5 % with double earthing shall be made available in
the outdoors & in each AHU panel by the client through their own agencies.
T3.03 EXPOSED ROOF / CEILING: All exposed roof / Ceiling shall be insulated
with 50mm thick TF quality thermocole.
T3.04 ASSOCIATED CIVIL / ELECTRICAL AND OTHER WORKS TO BE
PROVIDED TO THE AC CONTRACTOR BY THE CLIENT (THROUGH
THEIR OWN AGENCIES)
a)
Structural platform, if any, for installation of outdoor units .
b)
Stabilised three phase four wire AC supply i.e. 415 Volts ± 10% & 50
Hz ± 5% with double earthing and termination shall be made available
near the outdoor units .
Any kind of false ceiling work, return air boxing, wooden /aluminium
frames for fixing grills / diffuser/duct work etc. for the respective
premises.
c)
d)
Power for erection, testing and commissioning of the plant.
e)
Any kind of masonry shafts for laying pipes / cables / ducts etc.
T3.05 SYSTEM DESCRIPTION & FEATURE
Inverter Type VRF System
The system shall be intelligent and energy efficient too. The system will
typically consist of an outdoor unit using an inverter controlled variable speed
compressor connected to serially arranged refrigerant pipe or with number of
indoor units. The scope of present tender shall be:
-
Provision
Provision
Provision
Provision
of
of
of
of
Floor Standing Air Handling unit
ductwork inside the conditioned area.
duct insulation
grills, diffusers, duct dampers, fire dampers etc.
For inverter controlled machine the outdoor unit shall be controlled through
inverter which controls the frequency of controller motor to match the
auditorium A.C. load. The unit shall be provided with highly sophisticated
electronic control for efficient zone control. This ensures optimal airconditioning of individual space and thereby minimizes the power
consumption. The simplicity of variable of VRV system results in easier
installation and system functions under high ambient condition.
The suction line shall be insulated with polyethelene /nitrile rubber based
insulation. Depending on load, IDU and ODU shall operate. Suitable drain
shall be connected to the IDU to remove condensate.
The compressor controlled through inverter or engagement/dis-engagement
of fixed and rotating scroll will modulate the refrigerant flow to meet the
varying cooling loads.
The unit shall be capable of operating in stepless control mode. The unit shall
be provided with all necessary controls as well as accessories.
Tenderer shall quote any of the above alternatives. However, technical details
including power consumption shall be furnished by the tenderer clearly.
Section T-4
STANDARD SPECIFICATION OF THERMAL /
ACOUSTIC INSULATION
T4.01
INSULATION OF PIPES
T4.02
a)
The pipe to be insulated should be cleaned thoroughly with steel
brush for removing dirt, rust and grease.
b)
Fix insulation of specified thickness tightly and seal all joints
with adhesive compound.
THERMAL INSULATION OF DUCT
MaterialCross linked closed cell preformed
polyethelene/closed cell nitrile based preformed section .
Thickness-
section
of
Min. 9 mm for closed cell polyethelene having K valve
0.027-0.029 and minimum density 32 kg/m3/12 mm thk.
for nitrile rubber base insulating material.
The material shall be fire retardant type with Class-I fire rating. The
material shall have self-extinguishing and non-dripping quality and CFC
free.
T04.03
UNDER DECK INSULATION
Material-
50mm thick TF quality Thermocole.
The material shall be fire retardant type with self-extinguishing and
non-dripping characteristics.
Section-T5
STANDARD SPECIFICATION OF G.I. DUCT WORK
T5.00
SCOPE
The scope of work covers supply and installation of
i)
ii)
iii)
iv)
Sheet metal ducting.
Air intake and exhaust louvers.
Grills and Diffusers.
Volume control dampers.
T5.01
For Grills & diffusers, tenderer shall submit catalogues since the units
are standard.
T5.02
MATERIAL
T5.02.01
The material for various applications of air ducting shall be as follows :
Application
Material
Ducting for Air-conditioning
G I sheets continuous galvanized
with minimum zinc coating 180 g/sq.
m both side inclusive as per IS:277 –
1977.
T5.02.02
All galvanized plain sheets shall be free from wrinkle. The zinc shall be
clean, even and free from galvanized spots. Material shall be of
approved make.
T5.03
All ducts for air-conditioning shall be rectangular in cross section and
shall be fabricated as per ISI/SMACNA.
T5.04
Standard elbows with a R/D ratio not less than 1.25 shall be used as
far as possible. Where space restrictions do not permit use of standard
radius, elbow with lesser R/D ratio and square elbow with equally
spaced double thickness vanes may be used.
T5.05
GRILLS/DIFFUSERS
Supply air grills shall be double deflection type with the horizontal face
bars and vertical rear bars placed in a rigid marginal frame. All grills
shall be provided with integral opposed blade, grill face key operated
dampers.
Return air grilles shall have fixed face bars. Bars shall be set at 40
deflection of vision-proof installation the grilles shall be complete with
rigid marginal frames and shall be matching with supply grilles.
Diffusers shall be round/rectangular face with horizontal air diffusion
pattern. All diffusers shall be provided with face operated volume
control dampers.
Section T-6
EQUIPMENTWISE TECHNICAL DATA TO BE FURNISHED BY THE TENDERER
T6.00
SCOPE
Tenderer shall furnish the equipmentwise technical data as per the
following :
A)
OUTDOOR UNITS
a)
Make –
b)
Model –
c)
Compressor type –
d)
No. of compressors –
e)
Refrigerant –
f)
Capacity at the specified condition –
g)
Air discharge
h)
Electrical power supply
i)
Input power at full load
j)
Input power at part load
k)
EER
l)
Net weight
m)
Condenser air quantity
n)
No. of fans per condenser
o)
Overall dimension
p)
Controls provided
B) Floor Standing Air handling Units
a)
b)
c)
d)
e)
f)
g)
h)
Make
Model
Capacity
Air flow
Power supply
Dimension
Net weight
Power consumption
LIST OF APPROVED MAKES
S.N Description
Makes
1
2
VRF system
Air Handling Units
DAIKIN/TOSHIBA/MITSUBISHI/VOLTAS
Edgetech/Zeco/Airflow
3
GI Sheet
Sail/Nippon/Tata/Jyoti
4
Grilles/Diffusers
Caryaire/Air master/ Premier/MR Sheet
5
Thermal Insulation
Armacell/K Flex/ UP Twiga/Beardsell
6
Copper Pipe
Mandev/Nippon/Rajco/Mehta
TECHNICAL SECTION
Section T-1
STANDARD SPECIFICATION
The followings terms have been used in the tender specifications, drawings
etc.
HZ
Hertz.
H.P.
Horse Power
Codes to be followed:
1.
PVC insulated ( HD) Electric
Cables for working voltage up
Including 1100 Volts.
IS : 1554 ( Part I)
2.
HRC Cartridge fuse links
upto 650 Volts.
IS 2208 : 1976
3.
Starter
IS 8554 ( Part I) 1979
4.
Three phase induction motors
IS : 325
5.
PVC insulated ( heavy duty )
cables for working voltage
up to 1.1. KV and up to 11 KV
Grade respectively.
IS 1554 : 1981 Part I &
6.
Code of practice for electrical
wiring installations.
IS 732 : 1989
7.
Code of practice for earthing
IS 3043 : 1966
8.
Circuit breaker A.C
IS 2516 : 1980 Part I & II
9.
Contactors for A.C for voltage
upto 1100 V.
IS 2959 : 1975
10.
Low voltage switch gear and control
IS 8623 : 1993 Part I
11.
Specification for cables glands
IS 4821
12.
Code for selection, installation &
maintenance of switch gear and
control gear.
IS 10118 : 1982 Part I to IV
SAFTEY CODES
Code for safety procedures and practices
In electrical works
IS 5216
Section-T2
T2.01 ASSOCIATED CIVIL / ELECTRICAL AND OTHER WORKS TO BE
PROVIDED TO THE AC CONTRACTOR BY THE CLIENT (THROUGH
THEIR OWN AGENCIES)
a)
Stabilised three phase four wire AC supply i.e. 415 Volts ± 10% & 50
Hz ± 5% with double earthing and termination shall be made available
near the outdoor unit of each floor in a D/B. Outlet feeder from the
D/B to the micro-processor panel/unit of the outdoor unit shall be
carried out by the successful contractor.
b)
Power for erection, testing and commissioning of the plant.
SectionT-3
STANDARD SPECIFICATIONS OF ELECTRICAL
DISTRIBUTION BOX AND CABLES
T3-01
MOTOR CONTROL CENTRE
CONSTRUCTIONAL FEATURE
Single front non-draw out design, free standing/wall mounted,
compartmentalized type.
Panel with sheet steel (CRCA), i.e. 1.6 mm thick. except front door.
The same may be 2 mm thk. sheet steel.
Dust and vermin proof design. The degree of Protection Class for
enclosure shall be minimum IP-55 with 35 KA fault level.
Safety insulating barriers shall be provided in each module to prevent
accidental contact with live parts.
Cutouts in the modular door shall have neoprene gaskets ensuring to
prevent dust ingress.
Neoprene gaskets shall be used for cable alley door fixing.
All terminations shall be shrouded in an approved manner. The entire
enclosure shall meet with IS:2147/1962. Feeder connections shall be
made out of solid insulated copper/aluminium wires or strips with
bimetallic clamps wherever required. Internal wiring, bus bar markings
etc. shall conform to IS:375/1963. Internal wiring shall have terminal
ferrules. Main switch should be at an easily accessible height and the
highest switch operating handle should not be over 1.75m from floor
level. Cable glands need not form part of the switch board as the cost
of glands will form part of the cable termination.
Incomers shall be three phase and neutral and of copper or aluminium
or aluminium alloy and rated for a temperature rise of 30C over the
ambient temperature specified, based on insulated conductor rating
(IS:8084-1976).
Isolators shall be fixed on wall on self-supported angle iron frame work
as required and mounted as near to the motor as possible. Where
several motors are installed, isolators if required shall be provided at a
central location on a common frame work.
All panels shall be meggar-tested and shall not be commissioned till
the values are more than 2.5 megohms phase to phase and 1.5
megohms phase to neutral. All meters on the panel shall be calibrated
before commissioning.
The general arrangement and fabrications drawings shall be got
approved before taking up for fabrication.
T3-02
CABLES
All cabling work from MCC/Distribution Board to various drives as well
as to various local control centers shall be carried out by the successful
tenderer.
LT power cables within the enclosed premises shall be PVC insulated,
unarmoured PVC sheathed Copper conforming to IS:1554-1988.
Cables, running indoors shall be laid on walls, ceiling, inside shafts or
trenches. Single cables laid shall be fixed directly to walls or ceiling and
supported at not more than 500 mm. Where number of cables are run,
necessary perforated cable trays shall be provided. Perforated cable
trays shall be mild steel or Aluminium as specified in the schedule of
work.
SR. NO.
A
PROPOSED SCOPE OF WORKS & BUDGETARY ESTIMATE FOR
VTI AUDITORIUM AT NEW TOWN, KOLKATA
ITEM NAME
TECHNICAL SPECIFICATION
UNIT
QTY.
Sqm.
8600
INTERIORS & ACOUSTIC TREATMENT
1
PEST CONTROL & ANTI-TERMITE TREATMENT (at all areas)
Providing Pest control and Anti-termite treatment by appointing a
specialised agency as per the specifications mentioned by the
Bureau of Indian Standards and Agencies specifications (whichever
is higher) for general civil, timber / carpentry works, gypsum related
work, including a 5-year guarantee under suitable undertaking on
stamp paper etc., complete as directed. (Mode of measurement to
be on carpet-area of floor and not the area of surface treated)
2
DISMANTLING (as provisional item)
Dismantling of brick masonary & plaster works and carting away of
debris from site as required & directed by EIC.
Sqm.
10
FULL BRICKWORK (for stage structure)
Brick work 250mm thick, with F.P.S. bricks of class designation 75 in
superstructure above plinth in all shapes and sized in cement
mortar 1:6 (1 cement : 6 medium course sand) all complete
including the cost of scaffolding and curing as directed by EIC.
Cum.
2
4
HALF BRICKWORK (as provisional item)
Brick work 125mm thick, with F.P.S. bricks of class designation 75 in
superstructure above plinth in all shapes and sized in cement
mortar 1:4 (1 cement : 4 medium course sand). Cost to include
lintels above doors etc. all complete including the cost of
scaffolding and curing as directed by EIC.
Sqm.
20
5
CEMENT PLASTER (as provisional item)
Applying cement plaster upto 15mm thick in 1:6 cement sand
mortar as directed by EIC.
Sqm.
50
PLASTER OF PARIS (as provisional item)
Providing & applying punning upto 6mm thick (avg.) layer of super
fine Plaster of Paris applied over selected existing and new
plastered surface on walls and columns finished smooth, inclusive
of surface preparation as directed and instructed by EIC. The
finished surface shall be smooth and in perfect level so as to avoid
unevenness and ready to take on paint.
Sqm.
50
CARPET FLOORING AT HALL AREA
Providing & laying of broadloom roll carpet of 22 oz., 100% eco
solution premium branded nylon, solution dyed, pattern loop of
approved shade, all complete.
Sqm.
785
WOODEN FLOORING AT STAGE
Providing & laying HDF plank (1200 x 200mm) flooring, Class 33 Heavy Commercials AC-5 grade as per manufacturer's specification
of approved shade including 2mm foam beneath for stage &
adjacent steps and all accessories complete.
Sqm.
145
PLYWOOD PANELING WITH GLASSWOOL IN-FILL
Providing & fixing plywood paneling with 12mm thick commercial
plywood fixed on plywood framework of section 19 x 50mm
including all hardwares. The inside of the structure will be filled with
50mm thick glasswool of 48Kg / cum all as per direction of EIC.
Sqm.
800
Sqm.
260
Sqm.
300
Sqm.
100
3
6
7
8
9
10
11
12
Providing & fixing of acoustic fabric paneling as per manufacturer's
specification. The panel comprise of 12mm thick recron acoustical
ACOUSTIC FABRIC PANELING WITH RECRON IN-FILL over plywood board. The top will be covered with fire rated fabric of approved
paneling
shade with PVC edge gripper, all complete as per design, drawing &
direction of EIC. Rate does not include the cost of base plywood
paneling.
Providing & fixing of jute mat paneling as per manufacturer's
specification. The panel comprise of 12mm thick recron acoustical
board. The top will be covered with jute mat of approved shade
JUTE MAT PANELING WITH RECRON IN-FILL over plywood paneling
with PVC edge gripper, all complete as per design, drawing &
direction of EIC. Rate does not include the cost of base plywood
paneling.
Providing & pasting of 6mm thick approved HDF decorative
embossed panel finished with lustre paint / melamine polish as per
DECORATIVE PANELING over plywood paneling
design, drawing & direction of EIC. Rate does not include the cost of
base plywood paneling.
RATE
AMOUNT
13
14
15
16
17
18
19
20
21
VENEER PANELING over plywood paneling
Providing & pasting of 4mm thick approved veneer finished with PU
matt polish as per design, drawing & direction of EIC. Rate does not
include the cost of base plywood paneling.
Sqm.
140
SKIRTING
Providing & fixing 150mm high 12mm thick commercial plywood
with 4mm thick approved veneer pasting finished with melamine
polish as directed by EIC.
Base rate of veneer - Rs. 1000/- Per Sqm.
Rmt.
200
ACOUSTIC GYPSUM FALSE CEILING
Providing & fixing acoustic gypsum ceiling with designed profile on
ceiling board as per manufacturer's specifications. Rate to include
all fastening accessories with approved finishes. Ceiling boards shall
be made of IGL make of size 1200mm x 2400mm of approved
design. Board shall render a NRC level of 0.75 - 0.85. Suspension
system shall be done with hanger bar, intermediate channel and
ceiling section as per manufacturer's specification. Installation to
comprise of main intermediate channels spaced at 1200mm centres
securely fixed to the structural soffit by approved hangers at
1200mm maximum centres & not more than 150mm from spliced
joints. The last hanger at the end of each main runner should not be
greater than 600mm from the adjacent wall. Rate to include all cutouts / filling for lights, AC grills & diffusers and other services as
required at site.
Sqm.
510
PLAIN GYPSUM FALSE CEILING
Providing & fixing of false ceiling with 12.5mm thick plain gypsum
board as per India Gypsum / manufacturer's specification, all
complete and ready to apply paint as per design, drawing &
direction of EIC. Rate to include all cut-outs / filling for lights, AC
grills & diffusers and other services as required at site.
Sqm.
400
LAMINATED FALSE CEILING
Providing & fixing of false ceiling with 12mm thick BWR plywood of
approved make fixed on GI frameworks finished with 1mm thick
approved laminate of approved make, all complete as per design,
drawing & direction of EIC. Rate to include all cut-outs / filling for
lights, AC grills & diffusers and other services as required at site.
Sqm.
150
MS CATWALK OVER HALL & STAGE
Supply, installation, erection and fabrication of catwalk with MS of
desired sections over hall and stage area. The structure shall be as
per approved design & direction of EIC. Rate includes painting of
the structure with enamel paint of approved make and shade.
Lot
1
MS LIGHT & SOUND PORCH
Supply, installation, erection and fabrication of porch with MS of
desired sections and necessary supports as per approved design &
direction of EIC. 19mm thick commercial plywood to be fixed on the
structure as platform. The verticals to be finished with 4mm thick
approved veneer, all as per direction of EIC.
Base rate of veneer - Rs. 1000/- Per Sqm.
Lot
1
MS LADDER
Supply, installation, erection and fabrication of ladder with MS of
desired sections to make access to light & sound porch. The
structure shall be as per approved design & direction of EIC. Rate
includes painting of the structure with enamel paint of approved
make and shade.
Nos.
1
GENERAL PAINTING
Acrylic emulsion paint with approved shade and colour of ICI Dulux
/ Asian Paints or equivalent with two coats of putty, two coats of
primer and three coats of approved acrylic emulsion paint, including
preparation of surface, scrapping, sand papering, scaffolding, all
materials, labour etc. complete.
Sqm.
1000
FLUSH DOOR
Providing & fixing of double leaf door made with 38mm thick solid
core flush door to avoid flanking noise, finished with 4mm thick
approved veneer with melamine polish on both sides, including in
position necessary fittings and hardwares like handles, hinges, door
closers, locks etc. of approved make.
Base rate of veneer - Rs. 1000/- Per Sqm.
Nos.
9
23
GREEN ROOM LEDGE & MIRROR
Providing & fixing plywood ledge (450mm depth) with 19mm thick
commercial plywood fixed on plywood framework of section 19 x
50mm, including all hardwares and finished with 1mm thick
approved laminate as directed by EIC including 4mm thick mirror
with edge-polished on 9mm thick commercial plywood backing
fixed with SS studs as per design & direction of EIC.
Base rate of laminate - Rs. 350/- Per Sqm.
Rmt.
20
24
SAFETY SIGNAGES
Nos.
40
25
STAGE PODIUM
Nos.
1
26
SALE COUNTER
Providing & fixing of sale counter at lobby using stone top as per
drawing & direction of EIC. Base rate of stone : Rs. 4000/- per sqm.
Rmt.
22
FULL GLAZED PARTITION & DOOR (for VIP seating enclosure)
Supply & installation of full height glass partition with 12 mm thick
toughened clear glass resting on SS patch fittings of approved make
all complete as per direction of the Architect & EIC.
Sqm.
45
STAGE WOODEN UNDERSTRUCTURE
Providing & fixing hardwood beam of section 100 x 150mm in both
directions over brick pillars with top fixed with 40mm thick wooden
plank as per design & direction of EIC.
Sqm.
145
22
27
28
Total Amount
Providing & fixing acrylic autoglow box signage as per approved
design.
Providing & fixing of podium as per design made of 19mm thick
commercial plywood and 4mm thick veener of approved shade. The
veneer to be melamine polised, all complete as per design &
direction of Architect / EIC.
B
Sr. No.
1
2
3
4
5
6
7
8
9
10
STAGE CRAFTING
Item Description
GRID FABRICATION: 75mm x 75mm x 6mm MS Angle main
runner (Lower Level) 75 OD MS pipe (Bottom Level) and cross
section 32 OD Black Pipe with cover 19mm commercial ply
and red oxide and black paint complete set (Catway).
PROCINIUME GRID: 100 X 100 Square Box Medium Guage
main runner cross section 50x50 square box with red Oxide
and black paint complete.
Providing, fitting and fixing of motorized Horizental operated
main curtain mechanism with curtain controller unit complete
with 1.5 HP 230 volt single/three phase Compton greaves or
equivalent make A.C. motor, worn reduction gear, rigid
coupling 25 mm dia
Main Cartain cloath. Providing, fixing, testing and
commissioning of double gathered main curtain in two part to
be made with cotton velvet cloth of approved make, shade
and colour, including backing cloth of approved make,
decorative bridle with ball fringes, tassels etc.
Back curtain (Manual) complete with black cotton cloth.
Fril Bar : P & F manually operation Fril Bar up & Down
system 100 mm dia bearing fitted pulley and MS Bracket 8mm
Poly puppling rope 32 OD MS Black Pipe and black Cloth
Complete set.
Light Bar Wing System : P & F Light Bar mechanism consisting
of 100 mm dia bearing fitted with pully with MS bracket 6 mm
thick steel flexible wire adjustable stainer / rope clamp, 48
mm OD Black Pipe and 1000 Kg capacity manual winch with
paint complete set.
Wings Mechanism (Horizontal & Moveable)
With 1inch OD pipe along with jute & Black Cloth.
Cyclorama frame & cloth (Bombay Dying) With 48mm OD pipe
–cross member 32 OD Pipe.
Light Ladder
Total Amount
Unit
Qty.
Set
1
Set
1
Set
1
Set
1
Set
1
Set
5
Lot
4
Set
6
Set
1
Set
4
Rate
Amount
C
Sr. No.
1
ELECTRICAL WORK
Item Description
Unit
Qty.
MAIN LV POWER DISTRIBUTION BOARD
nos.
1
nos.
4
nos.
1
nos.
1
Supply, delivery, installation, testing & commissioning of Main
LT Distribution Board with 400A Rated, Al. busbar (as per the
relevant SLD Dwg. and as per our specification)
The Main incomer and feeder details are furnished below :
Incomer
1 - 400A TP+N, MCCB (35KA) with front door drive handle,
door interlocking system
1 - lot indicating lamp & control fuses
1 - Voltmeter with Sel. Sw. 0 - 500V, 96 X 96, MI type
1 - Ammeter with Sel. Sw. 0 - 400A, 96 X 96, MI type
3 - C.T 400/5A, 10VA, Cl - 1.0
1 - C.T 400/5A, 10VA, Cl - 1.0
1 - Micro-processor based load manager suitable for 3ph, 4
wire, system, 5A C.T secondary
Feeders
MCCB TP+N with front door drive handle with door
interlocking of following rating
3NOS - 160A
3NOS - 125A
MCB Feeder 10 KA Curve - C
4 - 63A TPN MCB
2
2.1
MCB DB
LIGHTING / POWER DB
Supply, delivery, testing & commissioning of ready made MCB
DB double door with TOP & BOTTOM ENTRY - with separate
Neutral per phase, double door, suitable for IP - 41 protection
with DB and feeder name plate engraved
2.2
Incomer
1 - 4P MCB ISOLATOR - 63A
Feeder
9 - SP MCB - 10A, 10 KA
9 - SP MCB - 25A, 10 KA
STAGE LIGHTING DB
Supply, delivery, testing & commissioning of ready made
VERTICAL MCB DB with TOP & BOTTOM ENTRY - with
separate Neutral per phase, double door, suitable for IP - 41
protection with DB and feeder name plate engraved
2.3
Incomer
1 -TPN+N MCCB MCCB -125A
Feeder
3 Nos - 32A TP MCB
3 Nos - 10A SP MCB
SOUND SYSTEM DB
Supply, delivery, testing & commissioning of ready made TPN
4WAY DOUBLE DOOR MCB DB with TOP & BOTTOM ENTRY with separate Neutral per phase double door, suitable for IP 41 protection with DB and feeder name plate engraved
Incomer
1 - TPN MCB 63A, 10KA
Ph. Feeder
3 - DP RCCB (30mA) - 40 A
Sub-Feeder
12 - SP MCB 16A, 10 KA
Rate
Amount
3
3.1
EARTHING
Supply & installation of Earth Pit as per IS : 3043 with GI plate
(600 x 600 x 6 mm) electrode (placed at a depth of 3.0 Mtr), 2
nos. GI earth Flat of size 25 x 6mm shall be bolted with the
plate & will be drawn upto ground level, one 3 Mtr long GI
pipe.
nos.
2
nos.
2
mtrs.
150
mtrs.
150
nos.
2
4.2
Supply, laying & interconnection by bolting / welding of the
following size of GI Flat tape 50 X 6mm sq. horizontal run,
along the parapet / wall by suitable insulated saddling.
Welding / brazing part should be covered by bituminous paint
after installation.
mtrs.
250
4.3
Maintenance free Earth Pit made of ground enhancing
material (GEM) of required qty 6 Bags of II.3Kg/bag and
copper bonded earth rods (3 nos) of size 5/8" dia x 4' length
and 3 no. of earthrod clamp & 15 Mtr 50 X 0.5mm soft Copper
strip.
nos.
2
mtrs.
250
nos.
2
nos.
2
mtrs.
mtrs.
4000
500
mtrs.
500
mtrs.
500
mtrs.
1500
mtrs.
1500
mtrs.
mtrs.
mtrs.
6000
150
150
mtrs.
200
3.2
3.3
3.4
4
4.1
4.4
4.5
4.6
5
Maintenance free Earth Pit made of ground enhancing
material (GEM) of required qty 3 Bags of II.3Kg/bag and
copper bonded earth rods (3 nos) of size 5/8" dia x 10' length
and 1 no. of earthrod clamp.
25 x 6mm GI Flat for riser / along cable tray for earth station
at each
25 x 3mm Copper Flat for UPS earthing
LIGHTNING PROTECTION
Supply, delivery and installation of GI pipe electrode Earth Pit
as per IS : 3043, class B, 50mm dia, 3 Mtr long GI pipe with
10mm dia hole around the surface of the pipe shall be used.
Necessary accessories like watering, flunnel with wire mesh,
etc.
Supply, laying & interconnection by welding / bolting of the
25 X 3mm size of Al. Flat horizontal & vertical run along the
building wall from top to the ground level Earth Pit by suitable
insulated saddle.
Supply & installation of 5 PRONG Lighting Conductor to be
fixed on the strategic points at roof top wall as per the
instruction by EIC.
Supply & installation of Earth Test link with 300mm length Al.
Flat of 40 x 6mm size to be fixed on porcelain insulator
support on wall.
INTERNAL WIRING FOR POWER / LIGHT POINTS
NOTE :
Wiring for lighting, exhaust fan, power points etc. shall have
to be done by rigid PVC conduit on exposed part or with rigid
PVC conduit wherever recessed in wall / plastered surface
whenever concealed along the wall. Necessary PVC JB /
Circular box / Inspection JB have to be provided.
CIRCUIT MAINS / SUB-MAINS WIRING AND DIRECT LIGHTING
Circuit Mains shall be drawn through PVC conduit from LDB to
the switch board or between switch board by loop in - loop
out method.
Supply & laying of following sizes of rigid PVC conduit on
surface / recessed manner with chase cutting, mending good
of the surface / wall / tray including fixing of Circular / Square
JB, Inspection JB, clamp, socket, fish wires, etc.
5.1
5.2
5.3
5.4
5.5
i)
ii)
iii)
iv)
v)
5.6
i) 25mm dia PVC conduit
ii) 32mm dia PVC conduit
Supply & laying of PVC flexible conduit (For final length of
connection, if any)
20mm dia PVC flexible conduit
Supply & drawing of following sizes of PVC insulated FRLS
stranded copper conductor wires, 1100V grade in existing PVC
conduit / or laying / wiring upto power plug point (6A, 6/16A,
or AC point)
2 x 4.0 sq.mm Cu + 1 x 1.5 sq.mm Cu wire (for AC)
2 x 2.5 sq.mm Cu + 1 x 1.5 sq.mm Cu wire (for sub-main
wiring)
3 x 1.5 sq.mm Cu wire
4C x 25 sq.mm Cu flexible cable (For AC)
4C X 16 sq.mm Cu flexible cable (for AC)
300mm GI Cable Tray with hanging support and all required
accessories
6
POINT WIRING (CONTROLLED FROM SWITCH BOARD)
Point Wiring shall be started from the respective modular
switch of the switch board upto the first point of light / fan /
power point. 20/25mm dia through pre-laid MS/PVC conduit
shall be used in recessed manner along the wall. Cost of
modular switch, switch board, tressaplate etc. are not
included in the price.
Light points by suitable conduit and 3 x 1.5 sq.mm Cu wire
6.1
(upto 5 Mtr)
Exhaust Fan / Raw power points (6/10 Amps) by suitable
conduit and 3 x 1.5 sq.mm Cu wire along with supply of switch
6.2
modular type. Control & ON / OFF function shall be done by
switch.
6.3 Modular Switch & Socket
6/10 Amps switch
16 Amps switch
6 Amps socket
16 Amps socket
6.4 Modular Tressaplate with M.S Box
1 Mod
2 Mod
3 Mod
4 Mod
6 Mod
8 Mod
12 Mod
Wiring for power socket point 6A or 6/16A socket etc. shall
NOTE :
be paid as per the Meter run of conduit & wiring.
7
7.1
a)
b)
7.2
7.3
25mm PVC conduit heavy gauge
32mm PVC conduit heavy gauge
Supply and laying of CAT-6 Data Cable
Supply and laying of 2 pair Telephone Cable
8.1
8.2
8.3
a)
b)
90
points
40
nos.
nos.
nos.
nos.
50
15
20
15
nos.
nos.
nos.
nos.
nos.
nos.
nos.
10
15
25
4
6
10
6
mtrs.
mtrs.
mtrs.
mtrs.
250
150
305
200
mtrs.
mtrs.
150
250
nos.
nos.
8
12
TELEPHONE / NETWORKING
Supply and laying Raceways / Conduits on existing flooring /
wall. The Raceways / Conduits shall be fixed to the flooring
with clamps for finished levels as per site conditions or
through partitions with all accessories, bends, pull wire etc.
8
points
CABLE & CABLE TERMINATION
Supply, laying, dressing, testing & commisssioning of the
following sizes of 1.1 KV grade XLPE, armoured cable of Al /
Copper conductor, with GI strip / wire armour to be laid along
prepared trench / pre-laid cable tray with proper clamping /
saddle.
3.5C x 70 sq.mm Al wire
4C x 25 sq.mm Al wire
End termination for 1.1 KV grade cables with single
compression type cable gland and heavy duty Al / tinned
copper cable sockets. Rate shall be inclusive of all sundry
materials like adhesive, tapes etc. including plugging unused
holes, saddle etc.
3.5C x 70 sq.mm Al wire
4C x 25 sq.mm Al wire
Total Amount
Sr. No.
GENERAL ILLUMINATION
Item Description
Unit
Qty.
Supply & installation of Light Fittings
1
2 x 26W Recessed Down Lighter with Atco Dimmable Ballast
with 2 nos. 26W DE lamp 4 pin … For seating area
Nos.
160
2
LED Strip in 7.2 per mtr. with 30 LEDs with driver
Rmt.
200
3
12V/50W White Halogen Fitting with Osram Electronic
Transformer and 12V/50W Halogen lamp … For special focus
Nos.
15
4
Wall-mounted luminaire as mirror light … For green room
Nos.
15
Nos.
90
Nos.
1
5
6
2 x 18W Surface-mounted Down Lighter with Electronic
Ballast with 2 nos. 18W lamp … For ancilliary areas
Dimmer with Rack
Total Amount
Rate
Amount
D
Sr. No.
STAGE LIGHTING
Item Description
Unit
Qty.
1
Supply & installation of Light Fittings
1KW Fresnel Spots with bi-post halogen lamp
Nos.
8
2
1KW acting area Flood Light with 4-leaf burn door, with lamp
Nos.
8
3
1KW Par 64 with 1KW lamp CP-60
500W Cyclorama Flood Light with halogen lamp & color
holder
18 Channel Mixture
Power pack consisting of 6 Channel Electronic Dimmer with 3phase incoming supply & 4KW per channel DMX with
interconnections
Color Gel
2 x 36W Surface type CFL fitting with 2 nos. 36W CFL lamp
(General Light for Stage)
32 x 2 Channel Patch Panel with 32 MCB, plug tops, sockets
indicators, complete with interconnections
Smoke Diffuser
Accessories
G-Clamp for fixing the Luminaries
Dimmer Rack for mounting 2 Electronic Dimmers
1.5 sq.mm 2 core PVC insulated copper cable
1 X 10 sq.mm cable
1 X 6 sq.mm cable
Total Amount
Nos.
20
Nos.
8
Nos.
1
Nos.
2
Nos.
40
Nos.
16
Nos.
1
Nos.
1
Nos.
Nos.
Coil
Coil
Coil
50
1
18
1
1
4
5
6
7
8
9
10
1
2
3
4
5
Rate
Amount
E
Sr. No.
1
2
3
4
5
6
7
8
9
10
11
FIRE DETECTION & ALARM SYSTEM
Item Description
Supply & installation of 1 loop Addressable Main Fire Alarm
Panel
Supply & installation of Addressable Smoke Detector with
Base for BFC
Supply & installation of Addressable Smoke Detector with
Base for AFC
Supply & installation of Addressable Multi Sensor (Photo &
Heat) Detector with Base for BFC
Supply & installation of Beam Detector with Base
Supply & installation of Addressable Manual Call Point with
Base
Supply & installation of Addressable Wall-mount Sounder
with Strobe with Base
Supply & installation of Response Indicator
Supply & installation of Control Module
Supply & installation of Fault Isolation module
Supply & laying of Fire resistant Armoured Cable 2C 1.5
sq.mm.
Total Amount
Page 10
Unit
Qty.
Nos.
1
Nos.
15
Nos.
15
Nos.
5
Nos.
7
Nos.
10
Nos.
10
Nos.
Nos.
Nos.
15
8
3
Rmt.
2000
Rate
Amount
F
Sr. No.
1
2
3
SPRINKLER BRANCHING SYSTEM
Item Description
Supply & installation of
Main & Sub Branching of Pipe
Dropping pipe and all necessary fitting items, length of drop
considered as 1200mm.
Pendant / Wall type Sprinkler including rosset plate, as
required.
Total Amount
Unit
Qty.
Lot
1
Nos.
80
Nos.
40
Rate
Amount
G
Sr. No.
1
2
3
4
FIRE EXTINGUISHER
Item Description
MAP 90
Net Weight 2 Kg
MAP 90
Net Weight 6 Kg
CO2 4.5 Kg
HCFC 123 Clean Agent 4 Kg
Total Amount
Unit
Qty.
Nos.
5
Nos.
13
Nos.
Nos.
1
1
Rate
Amount
H
Sr. No.
SOUND & AUDIO-VISUAL SYSTEM
Item Description
A3
DISPLAY SYSTEM
Projector Screen - 278'' diagonal High Gain motorized screen
with 16:10 aspect ratio
6000 Lumens WXGA (16:10 aspect ratio) DLP Projector with
long throw Lens
Ceiling-mount Manual Kit for Projector
A4
50" diagonal or higher Proffessional LED Display
A5
A6
A7
A8
A9
Ceiling Mount Kit for LED Display
1:6 VGA Distrbution Amp
1:5 Video Distribution Amplifier
VGA Transmeter & Receiver
Floor Box on stage
A1
A2
Make
Qty.
DRAPER / DALITE
1
PANASONIC / SONY
1
1
SAMSUNG / PANASONIC
4
Custom
EXTRON / KRAMER
EXTRON / KRAMER
EXTRON / KRAMER
Custom
4
1
1
7
2
VIDEO SYSTEM
B1
DVD Player with USB Input
B2
B3
18X Optical Zoom, CCD PTZ Camera
Visualiser (Document Camera)
PIONEER / SAMSUNG /
SONY
VADDIO / SONY
SAMSUNG / ELMO
1
1
1
AUDIO SYSTEM
MIPRO / BOSCH / AKG/
SHURE
MIPRO / BOSCH / AKG/
SHURE
MIPRO / BOSCH / AKG/
SHURE
MIPRO / BOSCH / AKG/
SHURE
C1
Directional Wireless Handheld Microphone
C2
Directional Wireless Collar / Lapel Microphone// SHURE
C3
Gooseneck Microphone for Podium
C4
Handheld (VOCAL & INSTRUMENTAL) Wired Microphone
C5
LINE ARRAY / FOH Speaker – Active, modular beam steering
system, 130 - 20 KHz, beam control limit 400 Hz.
C6
1000 Watt power Amplifier for driving 800 Watt Speakers
C7
280 Watt 15" portable powered Speaker System, bi
‐amplified,
220 Watt low frequency, 60 Watt high frequency, 15"
low‐frequency transducer, 1" (exit) neodymium compression
driver
C8
Speaker Management System
C9
24 Channel Mixer WITH EFFECTS
C10
18" Self Powered Suwoofer with inbuilt 600W amplifier
C11
12" Self Powered Stage Monitor Speakers with dual 500Watt
inbuilt amplifier
C12
200 Watt Green Room Speakers
C13
Power Amplifier for Green room
D1
D2
INSTALLATION EQUIPMENT, ACCESSORIES & CABLES
27U Closed Rack
VALRACK / RITTAL
Cable & Connector
EXTRON / KRAMER
LS
LS
D3
ACCESSORIES & CABLES
LS
E1
INSTALLATION & CERTIFICATION
Installation, Designing & Programming
E2
Training, Project Documentation & Project Management
Total Amount
2
2
1
8
JBL / BOSCH/QSC/
TANOY
2
CROWN / QSC /
LABGRUPPEN/BOSE
1
JBL / BOSCH /
QSC/TANOY
4
DBX / BSS
SOUND CRAFT /
YAMAHA/ BEHRINGER
JBL / BOSCH/QSC/
TANOY
JBL / BOSCH/QSC/
TANOY
JBL / BOSCH/QSC/
TANOY
CROWN / LABGRUPPEN/
QSC/BOSE
As per approved make
1
1
2
2
1
1
Rate
Amount
I
Sr. No.
1
2
3
4
AUDITORIUM CHAIRS
Item Description
Supply & installation of
JUPITER Chair with Desklet of Godrej make for
auditorium general seating OR Equivalent from
HAWORTH / HERMAN MILLER / FIGUERAS
GLAMOUR Chair with Cup-holder of Godrej make for
auditorium VIP seating OR Equivalent from HAWORTH
/ HERMAN MILLER / FIGUERAS
DIAS Chair of Godrej make, model 7001D OR
Equivalent from HAWORTH / HERMAN MILLER /
FIGUERAS
SS Chairs on beam for lobby seating
Total Amount
Page 14
Unit
Qty.
Nos.
966
Nos.
16
Nos.
8
Nos.
3
Rate
Amount
J
SR.
NO.
1
3
4
5
6
1
2
3
4
5
5.1
(a)
(b)
6.1
6.2
6.3
6.4
6.5
7
7.1
7.2
8
9
10
J
HVAC SYSTEM
DESCRIPTION
Supplying of factory built floor mounted double skin type air handling units suitable for VRF
system, having multiple circuit with electronic expansion valve consisting of GI casing of
thickness 0.6mm outside layer with CFC free polyurethane foam(PUF),thickness 23 ± 2 mm,
density 40 ± 2 kg/cu.m. insulation, factory injected between them by injection molding
machine, complete with blower section with blower suitable for static pressure as detailed
below, minimum 2 bend GSS / PVC eliminators, cooling coil section with aluminum finned (Fin
spacing 12 FPI, condensing tray made up of Aluminium, Test pressure - 38kg/ Sq.cm.,
Insulation material-13mm thick close cell Nitrile rubber, Make of insulation- Armacell) copper
tubes (tube thickness not less than 0.41 mm, outside dia 12.7 mm, header material Copper,
Coil casing GI) cooling coil, filter sections with 50mm thick metal viscous/ washable synthetic
type pre-filters (EU-4) (Thermodyne/ AAF/ Spectrum make), belt driven fan (Nicotra / Kruger
make, Type – DIDW Forward curved) with TEFC drive motor (ABB/ Crompton/ Siemens/
Havells make, η factor EFF-2) suitable for 415 ± 10% volts, 50 Hz, 3 phase, AC supply, drain
connections, stainless steel drain pan thermometers and pressure gauges at the inlet and
outlet of coil, necessary vibration isolation arrangement, mixing box with GI dampers etc.
20000 CFM having 25 mm of Wg as min ESP & 6 row deep Coil
18000 CFM having 25 mm of Wg as min ESP & 6 row deep Coil
8400 CFM having 25 mm of Wg as min ESP & 6 row deep Coil
6850 CFM having 25 mm of Wg as min ESP & 6 row deep Coil
Supply of the DC Inverter Technology based Multi V Plus III Outdoor units (R-410A)
20 HP
24 HP
56 HP
60 HP
Expansion Kit Type 3
Communication Kit for AHU
Wired Remote for AHU
Sub-Total A
PART _ B
ITC of the following Multi-V Plus III static Ceiling Concealed Ductable indoor units with R-410A
refrigerant and wired remote
20000 CFM
18000 CFM
8400 CFM
6850 CFM
ITC of the of the DC Inverter Technology based Multi V Plus III Outdoor units with R 410 A Gas
Charge
20 HP
24 HP
56 HP
60 HP
SITC of the following sizes Cu. refrigerant pipes duly insulated with 19mm/13mm close cell
elastometric nitrite rubber insulation between each set of outdoor and indoor units including
refnet joints for VRF units.
SITC of Drain Water pipe with insulation as per specification
32 mm NB
Duct Work as per specification.
G.I. Ducting including dampers, turning vanes, splitter dampers etc. as per required.
22 G
24 G
Supply air grilles with VCD, Powder coated extruded aluminum
Return air grilles without VCD, Powder coated extruded aluminum
Supply Air Diffusers with VCD, Powder coated extruded aluminum
Return Air Diffusers with VCD, Powder coated extruded aluminum
Fusible link type fire damper at IDU supply duct
Ducting Insulation as per specification.
Supply & fixing of additional Thermal insulation for supply air duct using 9mm thick class " O "
Closed cell nitrile rubber based elastomeric insulation. Adhesive shall be used additionally
with VOC level not exceeding 50 grms / Litre.
Additional Duct Acoustic Insulation 12mm thick rigid board RB fiberglass.
Electrical Control Cable Work including double earthing as per specn.
Flexible Canvas Connection
Underdeck Thermal Insulation with 50mm thick TF quality thermocole
Sub-Total B
Total Basic
Taxes
Grand Total Amount
TECHNICAL SPECIFICATION AND APPROVED MAKE LIST
QTY.
UNIT
1.00
1.00
1.00
1.00
Nos
Nos
Nos
Nos
1.00
1.00
1.00
1.00
4.00
4.00
4.00
Nos
Nos
Nos
Nos
Nos
Nos
Nos
1.00
1.00
1.00
1.00
Nos
Nos
Nos
Nos
1.00
1.00
1.00
1.00
Nos
Nos
Nos
Nos
100.00
RMT
40.00
RMT
150.00
800.00
RO
15.00
10.00
RO
2.00
Sqm
Sqm
Sqm
Sqm
Sqm
Sqm
Sqm
800.00
Sqm
150.00
120.00
4.00
750.00
Sqm
RMT
Nos
Sqm
RATE
AMOUNT
1
3
4
5
6
1
2
3
4
5
5.1
(a)
(b)
6.1
6.2
6.3
6.4
6.5
7
7.1
7.2
8
9
10
Supplying of factory built floor mounted double skin type air handling units suitable for VRF
system, having multiple circuit with electronic expansion valve consisting of GI casing of
thickness 0.6mm outside layer with CFC free polyurethane foam(PUF),thickness 23 ± 2 mm,
density 40 ± 2 kg/cu.m. insulation, factory injected between them by injection molding
machine, complete with blower section with blower suitable for static pressure as detailed
below, minimum 2 bend GSS / PVC eliminators, cooling coil section with aluminum finned (Fin
spacing 12 FPI, condensing tray made up of Aluminium, Test pressure - 38kg/ Sq.cm.,
Insulation material-13mm thick close cell Nitrile rubber, Make of insulation- Armacell) copper
tubes (tube thickness not less than 0.41 mm, outside dia 12.7 mm, header material Copper,
Coil casing GI) cooling coil, filter sections with 50mm thick metal viscous/ washable synthetic
type pre-filters (EU-4) (Thermodyne/ AAF/ Spectrum make), belt driven fan (Nicotra / Kruger
make, Type – DIDW Forward curved) with TEFC drive motor (ABB/ Crompton/ Siemens/
Havells make, η factor EFF-2) suitable for 415 ± 10% volts, 50 Hz, 3 phase, AC supply, drain
connections, stainless steel drain pan thermometers and pressure gauges at the inlet and
outlet of coil, necessary vibration isolation arrangement, mixing box with GI dampers etc.
20000 CFM having 25 mm of Wg as min ESP & 6 row deep Coil
18000 CFM having 25 mm of Wg as min ESP & 6 row deep Coil
8400 CFM having 25 mm of Wg as min ESP & 6 row deep Coil
6850 CFM having 25 mm of Wg as min ESP & 6 row deep Coil
Supply of the DC Inverter Technology based Multi V Plus III Outdoor units (R-410A)
20 HP
24 HP
56 HP
60 HP
Expansion Kit Type 3
Communication Kit for AHU
Wired Remote for AHU
Sub-Total A
PART _ B
ITC of the following Multi-V Plus III static Ceiling Concealed Ductable indoor units with R-410A
refrigerant and wired remote
20000 CFM
18000 CFM
8400 CFM
6850 CFM
ITC of the of the DC Inverter Technology based Multi V Plus III Outdoor units with R 410 A Gas
Charge
20 HP
24 HP
56 HP
60 HP
SITC of the following sizes Cu. refrigerant pipes duly insulated with 19mm/13mm close cell
elastometric nitrite rubber insulation between each set of outdoor and indoor units including
refnet joints for VRF units.
SITC of Drain Water pipe with insulation as per specification
32 mm NB
Duct Work as per specification.
G.I. Ducting including dampers, turning vanes, splitter dampers etc. as per required.
22 G
24 G
Supply air grilles with VCD, Powder coated extruded aluminum
Return air grilles without VCD, Powder coated extruded aluminum
Supply Air Diffusers with VCD, Powder coated extruded aluminum
Return Air Diffusers with VCD, Powder coated extruded aluminum
Fusible link type fire damper at IDU supply duct
Ducting Insulation as per specification.
Supply & fixing of additional Thermal insulation for supply air duct using 9mm thick class " O "
Closed cell nitrile rubber based elastomeric insulation. Adhesive shall be used additionally
with VOC level not exceeding 50 grms / Litre.
Additional Duct Acoustic Insulation 12mm thick rigid board RB fiberglass.
Electrical Control Cable Work including double earthing as per specn.
Flexible Canvas Connection
Underdeck Thermal Insulation with 50mm thick TF quality thermocole
Total Amount
1.00
1.00
1.00
1.00
Nos
Nos
Nos
Nos
1.00
1.00
1.00
1.00
4.00
4.00
4.00
Nos
Nos
Nos
Nos
Nos
Nos
Nos
1.00
1.00
1.00
1.00
Nos
Nos
Nos
Nos
1.00
1.00
1.00
1.00
Nos
Nos
Nos
Nos
100.00
RMT
40.00
RMT
150.00
800.00
RO
15.00
10.00
RO
2.00
Sqm
Sqm
Sqm
Sqm
Sqm
Sqm
Sqm
800.00
Sqm
150.00
120.00
4.00
750.00
Sqm
RMT
Nos
Sqm
K
ELECTRICAL WORK of HVAC
Sr. No.
Item Description
1.0
Power Distribution Board
The type of DB shall be vertical or horizontal based on design and site
conditions.
MCB DB - Vertical /horizontal type
Incomer - 700 A, DP MCB
Outgoing - 200A, SP, MCB - 3 nos. ( 2W+1SB)
Outgoing - 100A, SP, MCB- 3 nos. ( 2 W+1SB)
Outgoing - 63 A, SP, MCB - 5 nos. (4 W+1SB)
PVC insulated, steel armoured, copper conductor 4 core cables.
1.1 kV grade armored PVC / XLPE insulated, steel armoured, copper
conductor power cables. The cables shall be laid in tray / wall
including termination with single compresson gland.
4 C x 50 sq.mm (XLPE)
4 C x 16 sq.mm (XLPE)
4 Cx 10 sqmm ( XLPE)
Earth Strips
Supply and laying GI earth strips on cable tray or below ground as per
site condition. Earth strip joints should have welded joints only.
25 x 3 mm GI. strip
8SWG GI Wire
Miscellaneous Items
MS Painted Perforated Cable Tray
Prefabricated - cable trays - made out of 2 mm thick galvised sheet.
Rate shall include necessary angle iron support and M10 full threaded
down rods, M10 anchor fasteners etc., complete. Maximum height of
suspension shall not exceed 500mm. The support shall be provided at
every 1 Mtr.
Size of Cable Tray :150 mm x 50 mm
Size of Cable Tray :100 mm x 50 mm
Total Amount
1.1
2.0
2.1
2.2
2.3
3
3.1
3.2
4
4.1
4.2
Qty.
Unit
1
Nos.
150
90
100
Rmt
Rmt
Rmt
360
100
Rmt
Rmt
160
250
Rmt.
Rmt.
Rate
Amount