K Series COMMERCIAL & TECHNICAL DATASHEET K Series Selection table of RCCB's Nominal current (A) Sensitivity Series (mA) Poles Type 2P A 4P A 16 25 40 63 80 100 Isolator Add-on appl. devices Rated voltage KB 30 240 x Selection table of RCBO's Series Sensitivity (mA) Poles Type 30 1P+N A x 240/415 Nominal current (A) Tripping Isolator Add-on 6 10 16 20 25 32 charact. appl. devices Rated voltage KDMA100 C 240 2 Series KG60 Standards Tripping characteristics Nominal current Calibration temperature Number of poles (# mod) Neutral pole protection Nominal voltage Un AC DC A ºC 1P 2P 3P 4P 1P (1) 2P (in series) (1) Frecuency Maximum service voltage Ubmax between two wires Minimum service voltage Ubmin Selectivity class (EN/IEC 60898-1) Isolator application EN/IEC 60947-2 Rated insulation voltage Pollution degree 2 Pollution degree 3 Impulse withstand test voltage Insulation resistance Dielectric rigidity Vibrations resistance (in x, y ,z direction) (EN/IEC 77/16,3) Endurance electrical at Un, In mechanical Utilisation category (EN/IEC 60947-2) Mounting position (for all devices): any except upside down Incoming top or bottom Protection degree (according to UL94) Self extinguish degree (according to UL94) Tropicalisation (according to EN/IEC 60068-2 / DIN 40046) Operating temperature Storage temperature Terminal capacity Rigid cabke min/max (top) Flexible cable min*/max (top Rigid cabke min/max (bottom) Flexible cable min*/max (bottom) V V V V DC V DC Hz V V V V kV MΩ kV ºC/RH ºC ºC mm² mm² mm² mm² EN 60898 B, C 6 - 63 30 1 / 2 / 3 / 4 yes 230/400 230 400 50/60 250 12 500 440 6 1000 2,5 3 10000 20000 KG Series Technical data of MCB's any yes IP20 / IP40 V2 +55ºC/95% H.R. -25/+55 -25/+55 1 / 25 or 2x10 0,75 / 25 or 2x10 1 / 25 or 2x10 0,75 / 25 or 2x10 (*Flexible cable 0,75/1/1,5 mm² with cable lug) Add-on devices (side add-on) Busbar systems Accesories Dimensions Approvals CE-marking Torque Auxiliary contacts Tele U Tele L Tele MP PBS Pin (top/bottom) Fork (top/bottom) Nm (HxDxW) 86x68xW Weight/mod. Package mm/mod. g mod. 4,5 yes / yes - / yes 18 120 12 yes 3 KG Series Characteristics according to EN/IEC 60898-1 Miniature Circuit Breakers (MCB) are intended for the protection or wiring installations against both overloads and short-circuit in domestics or commercial wiring installations where operation is possible by uninstructed people. Magnetic release An electromagnet with plunger ensures instantaneous tripping in the event of shortcircuit. The standard distinguishes three different types, following the current for instantaneous release: type B, C. Icn (A) Test current B 3 x In 5 x In C 5 x In 10 x In Tripping time Applications 0,1 < t < 45s (In≤32A) Only for resistive loads such as: 0,1 < t < 90s (In>32A) - electrical heating t < 0,1s - water heater - stoves 0,1 < t < 15s (In≤32A) Usual loads such as: 0,1 < t < 30s (In>32A) - lighting t < 0,1s - socket-outlets - small motors Thermal release The release is insulated by a bimetal strip in case of overload. The standard defines the range of releases for specific overload values. Reference ambient temperatures is 30 ºC. Test current 1,13 x In 1,45 x In 2,55 x In Tripping time t ≥ 1h t ≥ 2h t ≥ 1h t ≥ 1h 1s > t 1s > t (In ≤ 63A) (In > 63A) (In ≤ 63A) (In > 63A) > 60s (In ≤ 32A) > 120s (In > 32A) 4 KG Series 5 Series Standards Magnetic tripping characteristics Residual tripping characteristics Tripping time at IΔn Instantaneous ms Selective ms Rated current A Rated residual current IΔn mA Calibration temperature ºC Number of poles versus modules Rated voltage Un 2P AC V 3P AC V 4P AC V Frecuency Hz Maximum service voltage Ubmax V Minimum service voltage Ubmin V Minimum voltage for leakage protection V Power supply Selectivity class (EN/IEC 60898-1) Rated marking and breaking capacity (Im) A Residual marking and breaking capacity (I∆ m) A Conditional short-circuit capacity (Icn) A Conditional residual short-circuit capacity (IΔ c) A Rated Short-circuit capacity (Icn) A Grid distance (safety distance between two devices) mm Isolator application Insulation degree Insulation voltage V (DC) Shock voltage kV Insulation resistance MΩ Dielectric rigidity V Shock resistance (in x, y, z direction) (EN/IEC 60077/16,3) Vibrations resistance (in x, y ,z direction) (EN/IEC 77/16,3) Endurance electrical at Un, In mechanical at Un, In Protection degree (outside/inside electrical enclosure with door) Self extinguish degree (according to UL94) Tropicalisation (according to EN/IEC 60068-2 / DIN 40046) ºC/RH Pollution degree (acc. EN/IEC 60947-1) Operating temperature ºC Storage temperature ºC Terminal capacity Rigid cabke min/max (top) mm² Flexible cable min*/max (top mm² Rigid cabke min/max (bottom) mm² Flexible cable min*/max (bottom) mm² KBD 2P KBP 4P EN/IEC 61008-1 A < 40 40 30 30 1 240 - EN/IEC 61008-1 A < 40 40 30 30 1 50/60 2P=265 2P=117 415 50/60 4P=455 4P=205 Voltage independent Voltage independent Top/Bottom 500 (or 10xIn) 500 (or 10xIn) Top/Bottom 500 (or 10xIn) 500 (or 10xIn) 10000 fuse 100A gLgG 10000 fuse 100A gLgG 10000 fuse 100A gLgG 10000 fuse 100A gLgG 35 yes 440 6 1000 2500 35 yes 440 6 1000 2500 KB Series Technical data of RCD's 40g, 18 shocks 5 ms 40g, 18 shocks 5 ms 1,5g. 30 min, 0…80Hz 1,5g. 30 min, 0…80Hz 10000 20000 IP20 / IP40 V2 +55ºC/95% H.R. 3 -25...+60 -25...+70 1,5 / 25 1,5 / 25 1,5 / 25 1,5 / 25 10000 20000 IP20 / IP40 V2 +55ºC/95% H.R. 3 -25...+60 -25...+70 1,5 / 50 1,5 / 35 1,5 / 50 1,5 / 35 4/4 5/5 no no no no yes / yes - / yes 2 36 2P=250 2P=1/6 yes yes yes yes yes yes / yes yes / yes 4 72 4P=368 4P=1/3 yes (*Flexible cable 0,75/1/1,5 mm² with cable lug) Torque Add-on devices (side add-on) Busbar systems Dimensions Approvals CE-marking Top/Bottom Auxiliary contacts Tele U Tele L Tele MP PBS Pin (top/bottom) Fork (top/bottom) # Poles (HxDxW) 86x68xW Weight/mod. Package Nm mm/mod. g mod. 6 KB Series Technical data on the RCCB's. Laser print. KBDA240/30 KBPA440/30 KBPLA440/30 Series KDMA100 Standards EN/IEC 61009-1 Magnetic tripping characteristics C Residual tripping characteristics A < 40 Tripping time at IΔn Instantaneous ms Selective ms Rated current 10,16 A Rated residual current IΔn 30 mA Calibration temperature 30 ºC Number of poles versus modules 1 Rated voltage Un 2P AC 230 (1P+N) V 3P AC V 4P AC V Frecuency 50/60 Hz Maximum service voltage Ubmax 255 V Minimum service voltage Ubmin 117 V Minimum voltage for leakage protection Voltage independent V Power supply Top/Bottom Selectivity class (EN/IEC 60898-1) 3 Rated marking and breaking capacity (Im) A Residual marking and breaking capacity (I∆ m) 6000 A Conditional short-circuit capacity (Icn) A Conditional residual short-circuit capacity (IΔ c) A Rated Short-circuit capacity (Icn) 10000 A Grid distance (safety distance between two devices) 35 mm Isolator application yes Insulation degree Insulation voltage 440 V (DC) Shock voltage 6 kV Insulation resistance 1000 MΩ Dielectric rigidity 2500 V Shock resistance (in x, y, z direction) (EN/IEC 60077/16,3) 40g, 18 shocks 5 ms Vibrations resistance (in x, y ,z direction) (EN/IEC 77/16,3) 1,5g. 30 min, 0…80Hz Endurance electrical at Un, In 10000 mechanical at Un, In 20000 Protection degree (outside/inside electrical enclosure with door) IP20 / IP40 Self extinguish degree (according to UL94) V2 Tropicalisation (according to EN/IEC 60068-2 / DIN 40046) +55ºC/95% H.R. ºC/RH Pollution degree (acc. EN/IEC 60947-1) 3 Operating temperature -25...+60 ºC Storage temperature -25...+70 ºC Terminal capacity Rigid cabke min/max (top) 1 / 25 mm² Flexible cable min*/max (top 1,5 / 16 mm² Rigid cabke min/max (bottom) 1 / 35 mm² Flexible cable min*/max (bottom) 1 / 25 mm² Torque Top/Bottom 3/4 Nm Add-on devices Auxiliary contacts yes (side add-on) Tele U yes Tele L yes Tele MP yes Busbar systems Pin (top/bottom) yes / yes Fork (top/bottom) - / yes # Poles 1P+N Dimensions (HxDxW) 86x68xW 36 mm/mod. Weight/mod. 250 g Package 1/6 mod. Approvals CE-marking yes KDM Series Technical data of RCBO's KDM Series Technical data on the RCBO's. Laser print. KDMA100C10/030 KDMA100C16/030