Medium Voltage Switchgear and Switches Medium Voltage Switches up to 24 kV Vacuum Circuit Breaker Type: NVL CA_508_GB_0710.book Seite 2 Freitag, 1. Februar 2008 11:31 11 CA⋅508⋅GB⋅0710 Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVL Index Index Page 2 Main features 3 Requirements Application examples Economic efficiency Reliability of supply High operator safety 4 4 4 4 4 Switchgear unit arrangement 5 Key to type references 6 Technical data/standards 7 Overview of modules 8 Delivery programme of vacuum circuit breakers 10 Vacuum circuit breaker equipment 11 Circuit diagram 12 Control and indicator elements 14 Notes 15 CA_508_GB_0710.book Seite 3 Freitag, 1. Februar 2008 11:31 11 CA⋅508⋅GB⋅0710 Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVL Main features Main features Type NVL vacuum circuit breakers are type-tested switchgear devices for use throughout the world in medium voltage panels up to 24 kV. • Compact design • Simple and robust drive • Long durability • Low-maintenance • High reliability • High operator safety • 10.000 mechanical switching operations • Simple installation • Ideally designed insulation for panel installation • Options for customer-specific equipment 3 CA_508_GB_0710.book Seite 4 Freitag, 1. Februar 2008 11:31 11 CA⋅508⋅GB⋅0710 Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVL Requirements Application examples NVL vacuum circuit breaker is suitable for use in switching stations for power generation and power distribution for: • • • • • • • • • • • • • Utility companies Combined heat and power stations Power distribution at buildings Steel industry Heavy industry Airport power distribution systems Automotive industry Chemical industry Petro-chemical industry Food industry Main distribution substations Shipbuilding Stand-by generating supplies Economic efficiency High operator safety The flexibility of the standardised NVL vacuum circuit breaker with its options for configuration to customer requirements allows it to be functionally matched to its application. The circuit-breaker can be extended or modified at a later date after installation. The simple and clear arrangement of the operating and indicator elements and optional locking elements, e.g. key locks for actuating keys or electromechanical actuation locks, guide the user to actuate safely. Reliability of supply The high quality of vacuum circuit breaker with separate compartments for busbars, switchgear and cable connections ensures a high degree of reliability in operation and supply for the application. Thus the devices can be equipped, for instance, with an auto-reclosure in order to restore availability as quickly as possible after a fault in the mains power supply. 4 CA_508_GB_0710.book Seite 5 Freitag, 1. Februar 2008 11:31 11 CA⋅508⋅GB⋅0710 Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVL Switch arrangement Switch arrangement The NVL vacuum circuit breaker consists of the basic switch frame, the three switch poles and the switch mechanism. The baseframe must be earthed via a defined fixed earthing point. The switch poles include the vacuum switching chamber with contact system, the contact pressure springs, the tripping springs, as well as cast-resin parts. The cast-resin parts are for insulation, support and protection. In addition to their insulating function, they also absorb external forces from the switching process, contacting and short-circuit forces. They also provide mechanical protection for the vacuum chamber. A stored energy spring mechanism is used as an operating mechanism. The closing spring is charged using a crank handle or a motor drive. During the making process, the closing spring charges the contact pressure spring and closes the contacts. At the same time, the tripping springs are charged. To achieve operational capability short-time interruption, after the closing spring has been discharged it is recharged either manually or automatically if a motorised drive is mounted. By this means the necessary energy is stored for a short-time interruption, such as the switching sequence "OFF"-"ON"-"OFF". 5 CA_508_GB_0710.book Seite 6 Freitag, 1. Februar 2008 11:31 11 CA⋅508⋅GB⋅0710 Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVL Key to type references Key to type references NVL vacuum circuit breaker The NVL circuit breaker can be equipped with a wide variety of standardised customer options. The types of device are differentiated in their widths, ratings and principal functions. N. . . . .A-. . . ./. . . . /. . . . -. . . .-A Example : NVL2A-12/25/1250-150A Type of equipment:: VL = Vacuum circuit breaker Type of insulating enclosure: 2, 3 6 Rated voltage: 12 17 24 = 12 kV = 17.5 kV = 24 kV Rated short-circuit breaking current 16 20 25 31 = 16 kA = 20 kA = 25 kA = 31.5 kA Rated current: 630 A 1250 A 1600 A 2000 A 2500 A Distance between pole centres: 150 mm 210 mm 230 mm 275 mm CA_508_GB_0710.book Seite 7 Freitag, 1. Februar 2008 11:31 11 CA⋅508⋅GB⋅0710 Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVL Technical data/standards Technical data for NVL vacuum circuit breaker Rated voltage Ur [kV] 12 17,5 24 Hz 50 50 50 Rated lightning impulse withstand voltage Up kV 75 95 125 Rated power-frequency withstand voltage Ud kV 28 38 50 A 630 630 630 A 1250 1250 1250 A 1600 1600 A 2000 2000 A 2500 2500 Rated frequency fr Rated normal current Ir Optional Rated short-circuit breaking current Isc Optional Rated peak withstand current Ip Optional Rated short-time withstand current Ik at tk = 3 s Optional kA 16 kA 20 20 20 kA 25 25 25 kA 31.5 31.5 kA 40 kA 50 50 50 kA 62.5 62.5 62.5 kA 80 80 kA 16 kA 20 20 20 kA 25 25 25 kA 31.5 31.5 °C -5 to +40 °C +35 Average measured over 24 h maximum % 95 Average measured over 1 month maximum % 90 Altitude maximum m 1000 Opening time ms <55 Closing time ms <45 Arcing time ms approx. 15 Rated operating sequence (for automatic reclosing) O-0.3s-CO-15s-CO Classification M2, C2, E1 Ambient temperature T Average measured over 24 h maximum Relative humidity Standards NVL vacuum circuit breaker satisfy the listed VDE standards and IEC publications: VDE 0671 part 100 VDE 0670 part 1000 (VDE 0671 part 1*) * in future ** so far IEC 62271-100 IEC 62271-1 (IEC 60694**) 7 CA_508_GB_0710.book Seite 8 Freitag, 1. Februar 2008 8:27 08 CA⋅508⋅GB⋅0710 Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVL Overview of modules Y1 Trip element ON S1/S2 Signalling/control switch (stored energy spring mechanism) X1 Terminal strip X0: Plug-in connector, 64-pole Y2/Y5 1. Trip element OFF Transport mount S4 wipe contact, signal OFF K1 Anti-pumping relay Y7 Electric closing lock-out Y3/Y4/Y5 2. Trip element OFF Stored energy spring mechanism manual winding S19 Signalling switch 1S, mech. push-button ON activated Y6 3. Trip element OFF Earthing terminal Closing spring 8/9 M1 Stored energy spring mechanism motor Q1 Auxiliary contacts/signalling switch, 10 or 20-pole CA_508_GB_0710.book Seite 8 Freitag, 1. Februar 2008 8:27 08 CA⋅508⋅GB⋅0710 Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVL Overview of modules Y1 Trip element ON S1/S2 Signalling/control switch (stored energy spring mechanism) X1 Terminal strip X0: Plug-in connector, 64-pole Y2/Y5 1. Trip element OFF Transport mount S4 wipe contact, signal OFF K1 Anti-pumping relay Y7 Electric closing lock-out Y3/Y4/Y5 2. Trip element OFF Stored energy spring mechanism manual winding S19 Signalling switch 1S, mech. push-button ON activated Y6 3. Trip element OFF Earthing terminal Closing spring 8/9 M1 Stored energy spring mechanism motor Q1 Auxiliary contacts/signalling switch, 10 or 20-pole CA_508_GB_0710.book Seite 10 Freitag, 1. Februar 2008 11:31 11 CA⋅508⋅GB⋅0710 Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVL Delivery programme Delivery programme Rated voltage Ur: 12 kV Switch types:1) Rated voltage Ur: 17.5 kV Switch types:1) NVL2A-12/20/630-150A NVL2A-12/25/630-150A NVL2A-12/31/630-150A NVL2A-12/20/1250-150A NVL2A-12/25/1250-150A NVL2A-12/31/1250-150A NVL2A-12/20/630-210A NVL2A-12/25/630-210A NVL2A-12/31/630-210A NVL2A-12/20/1250-210A NVL2A-12/25/1250-210A NVL2A-12/31/1250-210A NVL3A-12/20/1600-210A NVL3A-12/25/1600-210A NVL3A-12/31/1600-210A NVL3A-12/20/2000-210A NVL3A-12/25/2000-210A NVL3A-12/31/2000-210A NVL3A-12/20/2500-210A NVL3A-12/25/2500-210A NVL3A-12/31/2500-210A NVL2A-17/20/630-150A NVL2A-17/25/630-150A NVL2A-17/31/630-150A NVL2A-17/20/1250-150A NVL2A-17/25/1250-150A NVL2A-17/31/1250-150A NVL2A-17/20/630-210A NVL2A-17/25/630-210A NVL2A-17/31/630-210A NVL2A-17/20/1250-210A NVL2A-17/25/1250-210A NVL2A-17/31/1250-210A NVL3A-17/20/1600-210A NVL3A-17/25/1600-210A NVL3A-17/31/1600-210A NVL3A-17/20/2000-210A NVL3A-17/25/2000-210A NVL3A-17/31/2000-210A NVL3A-17/20/2500-210A NVL3A-17/25/2500-210A NVL3A-17/31/2500-210A 1) Key to type references → page 6. a Rated voltage Ur: 24 kV Switch types:1) 3) NVL2A-24/16/630-210A NVL2A-24/20/630-210A NVL2A-24/25/630-210A NVL2A-24/16/630-230A NVL2A-24/20/630-230A NVL2A-24/25/630-230A NVL2A-24/16/1250-230A NVL2A-24/20/1250-230A NVL2A-24/25/1250-230A NVL2A-24/16/630-275A NVL2A-24/20/630-275A NVL2A-24/25/630-275A NVL2A-24/16/1250-275A NVL2A-24/20/1250-275A NVL2A-24/25/1250-275A 3) 3) 3) 3) 3) 3) 3) 3) 3) 3) 3) 3) 3) 3) c a f h d e 106 164 g 16 b Technical data and dimensions2): Rated voltage Ur [kV] 12 17.5 24 Distance between pole centres a mm 150 210 210 1503) 210 2103) 2103) 2303) 275 Rated normal current Ir 630 630 1600 630 630 1600 630 630 630 1250 1250 2000 1250 1250 2000 1250 1250 A 2500 Type of insulating enclosure 2 2 3 2 2 3 2 2 2 b 435 555 555 435 555 555 555 595 685 c 370 370 390 370 370 390 431 431 431 d 594 594 594 594 594 594 594 594 594 e 255 255 300 255 255 300 255 255 255 f 198 198 153 198 198 153 198 198 198 g 66 66 66 66 66 66 66 66 66 h 402 402 402 402 402 402 402 402 402 2) 3) 4) Additional technical data → page 7. possible additional insulation plates (phase insulation) required in the panel; not included in the scope of delivery In development. Date of delivery on request. Dimensions 10 2500 mm 3) 3) 3) 3) 3) 4) 3) 4) 3) 3) 4) 3) 4) CA_508_GB_0710.book Seite 11 Freitag, 1. Februar 2008 11:31 11 CA⋅508⋅GB⋅0710 Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVL Equipment for vacuum circuit breaker Equipment for vacuum circuit breaker Type: NVL....A-....../......./......... - ........A Standard equipment: charged spring drive with manual actuation Example: NVL2A-12/25/1250-150A 1. trip element "OFF" auxiliary contacts 5 NO + 5 NC (up to 4 NO + 5 NC free available) mechanical switching operation counter mechanical push-buttons "ON" and "OFF" mechanical position indicator mechanical spring charge indicator Additional equipment: 64-pin plug connector with mechanical interlocking motorised accumulator drive incl. trip element "ON", annunciator switch for spring charging, anti-pumping relay 2. trip element "OFF" 3. trip element "OFF" with auxiliary contacts, extension 5 NO + 5 NC transformer operated trip, alternative to 1. or 2. trip element undervoltage release, 100 V AC (non-delayed) alternative to 2. trip element auxiliary contact extension 5 NO + 5 NC signalling switch spring accumulator tensioned electric closing lock-out fleeting contact switch message "OFF" key interlocking for mechanical OFF-push-button key interlocking for mechanical ON-push-button signalling switch "mech. ON-push-button activated" Auxiliary voltages for circuit-breaker 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 110 V AC 230 V AC Motorised drive, stored energy spring mechanism 1. trip element "Off" 2. trip element "Off" 3. trip element "Off" trip element "On" electric closing lock-out 11 CA_508_GB_0710.book Seite 12 Freitag, 1. Februar 2008 11:31 11 CA⋅508⋅GB⋅0710 Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVL Circuit diagram Circuit diagram Motor X0 X1 S1 X0 A1 X0 X1 Q1 Y2 Y3 Y4 V4 Y5 V5 Y6 Y1 K1 M1 S1 S2 S4 S6 S19 S5 S7 A3 X1 3 1 1 Description: ON with anti pumping relay 4 S1 2 3 M1 11/13 21 M ~ K1 22 14 2 S2 1 12 24 Q1 11 23 X1 5 Y1 X1 2 X1 X0 A2 X0 OFF (1) OFF (2) X0 X0 X1 A5 7 X1 A1 K1 A2 Y7 V7 6 Plug-in connector 64-pole Terminal strip Auxiliary switch 1. trip element OFF 2. trip element OFF Undervoltage release OFF (alternative to Y3) Rectifier for Y4 Transformer operated trip OFF (alternative to Y2 or Y3) Rectifier for Y5 3. trip element OFF Trip element ON Anti-pumping relay Stored energy spring mechanism motor Control switch (ON release and motor) Signalling/control switch (spring accumulator tensioned) Fleeting contact switch, message OFF Fleeting contact break (in case of local actuation) Signalling switch, mech. ON-push-button activated Control switch, interlocking of el. switching on (with drawer unit only) Control switch, release interlocking of el. switching on (in conjunction with Y7 only) Electric closing lock-out Rectifier for Y7 A4 OFF (3) alternative trip element OFF (2) alternative trip element OFF (2) if necessary (1) electric closing lock-out A7 X0 D1 X0 C5 X0 A9 X0 C7 16 X1 31 X1 19 X1 21 X1 29 <U 14 Q1 13 64 54 Q1 Q1 53 Y4 V4 63 Y7 V7 I> Y5 X1 8 Y2 X1 X0 9 A6 1. trip element 12 17 V5 32 Y3 Y6 X1 18 X1 33 X1 20 X1 22 A8 X0 D2 X0 C6 X0 A10 X0 2. trip element 3. trip element Undervoltage release (non-delayed) Transformer operated trip X1 30 X0 C8 with control switch S7 (integrated in „ON"-release path) CA_508_GB_0710.book Seite 13 Freitag, 1. Februar 2008 11:31 11 CA⋅508⋅GB⋅0710 Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVL Circuit diagram Fleeting contact switch message "OFF" ON-push-button actuated Spring accumulator tensioned Messages X0 C3 C1 Auxiliary contacts Availability optional Consider the assembled trip elements X0 B1 26 B9 1 Signal Plug-in connector X1 15 B7 B4 C11 4 S2 X0 C11 A13 B11 B15 3 C15 D15 A11 A15 B13 C13 Q1 S19 1 1 4 S6 3 22 64 32 54 42 52 62 72 74 82 84 92 94 102 104 21 63 31 53 41 51 61 71 73 81 83 91 93 101 103 A12 4 S4 X1 16 27 D16 1 2 C10 X0 C4 A16 B14 C14 X0 C12 A14 B12 B16 C16 X0 B2 B5 B8 B3 C2 B10 B6 13 CA_508_GB_0710.book Seite 14 Freitag, 1. Februar 2008 11:31 11 CA⋅508⋅GB⋅0710 Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVL Operating and display elements Operating and display elements The operating and display area is located on the front side of the vacuum circuit breaker. All functional elements, e.g. the mechanical push-buttons for switching on and off, the indicator for the switch position and the stored energy spring mechanism are clearly arranged in order to ensure simple operation. The operating push-buttons can be equipped with optional key interlocking devices. Operation opening for manual winding up of spring accumulator Push-button ON Spring charge indicator Push-button OFF mechanical switching operation counter Switch position indicator Optional key interlocking devices for ON/OFF push-buttons 14 CA_508_GB_0710_04.fm Seite 15 Freitag, 22. Februar 2008 2:33 14 CA⋅508⋅GB⋅0710 Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVL Notes Notes 15 Technical-Commercial Department Tel.: +34 94 431 87 31 Fax: +34 94 431 87 32 E-Mail: oib@ormazabal.com SF6-insulated switchgear Type Type Type Type GA GAE CPG.0 CPG.1 Air-insulated switchgear Type EA Type AMC Air-insulated switches Type NVL Type KL(F), T, DES Subject to alteration CA 508 GB 0710