Installation Manual Manual PA/PG3000IM Revision G December 2007 PA/PG3000 SERIES Gage and Absolute Hermetically Sealed Adjustable Electronic Pressure Transmitters ® AEROSPACE AND POWER INSTRUMENTS • GULTON-STATHAM™ PRODUCTS 1644 Whittier Avenue • Costa Mesa, CA 92627 This page intentionally left blank FILENAME: Q:\EngDocs\Manual Indust_Nuc\PAPG3000IM G.doc 2 CAGE CODE: 99564 PA/PG3000 Installation Manual MODEL PA/PG3000 GAGE AND ABSOLUTE ELECTRONIC PRESSURE TRANSMITTERS CAUTION TO AVOID POSSIBLE INVALIDATION OF WARRANTY, PLEASE READ BEFORE INSTALLATION AND MAINTENANCE Ametek Gulton-Statham conducts a policy of continuous product development. The specifications in this document may therefore be changed without formal notification. 3 PA/PG3000 Installation Manual TABLE OF CONTENTS SECTION PAGE I INTRODUCTION 5 II. SPECIFICATIONS 7 III. MECHANICAL INSTALLATION 10 IV. ELECTRICAL INSTALLATION 13 V. CALIBRATION 21 VI. MAINTENANCE, ETC. 24 VII. TROUBLESHOOTING 25 VIII. RETURN FOR REPAIR 26 IX. WARRANTY 29 X NACE COMPLIANCE & APPROVALS 30 XI INTRINSICALLY SAFE SYSTEMS 34 XII. INSTRUMENT NOTES 40 4 FIGURE NO PG3000 Cross Sectional Illustration Amplifier Block Diagram Non-Condensing Gas Installation Liquid Or Condensing Gas Installation Electrical Block Diagram Multiple Transmitter Installation Diagram Transient Protection Factory Molded Cable TP114 Transient Protector C100/101 Electrical Connector TP131 Electrical Schematic TP131 Mechanical Installation Wiring With TP131 Installed Wiring Without TP131 Installed Elevated Zero Application Elevated Zero Examples Suppressed Zero Application Suppressed Zero Applications Compound Pressure Calibration Gage vs. Absolute Pressure Zero Adjustment Zero Adjustment Product Approval - North America Class, Division, Group - North America Barrier Requirements - FM Barrier Requirements - CSA Barrier Requirements - ATEX 1.1 1.2 3.1 3.2 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 10.1 10.2 11.1 11.2 11.3 PA/PG3000 Installation Manual SECTION I INTRODUCTION Sensor The heart of the 3000 series is a strain gage sensor that converts a mechanical force (pressure) to an electrical signal. A Wheatstone resistance bridge circuit is molecularly deposited on a metal bending beam using a technique similar to the process used to manufacture high-density integrated circuit chips. The deposition process is carried out in a Class 100 clean room under direct computer control to ensure conformance to Ametek Gulton-Statham's specification. Each finished beam is tested for linearity, sensitivity, thermal stability, bridge resistance and balance before installation in the sensor assembly. The sensing mechanism is isolated from the process fluid by an isolation diaphragm and silicone fill fluid. 5 PA/PG3000 Installation Manual then performance tested in an environmental chamber at temperatures to 180°F (82°C) (or 180°F (104°C) for HT units) to verify characteristics within the operating thermal band. Amplifier The simple DC electronics provide excitation voltage to the Wheatstone bridge, converts the bridge output to a current (mA) signal and provides electrical offset of zero to simulate (0) psi (see Figure 1.2). The amplifier is packaged in a hermetically sealed 316 stainless steel housing to guard against moisture and corrosion, the leading cause of electronic component failure in competitive transmitters. Ametek Gulton-Statham utilizes high-energy product magnets to couple the internal potentiometers to the external adjustment screws. As the outside magnet is turned, the internal magnet also turns, thereby adjusting the zero and span potentiometers. After calibration is completed, the external magnets may be removed and keepers inserted to provide “tamper-proof” installation. Measurement Reference The PA/PG3000 transmitters feature a sealed gage sensor with a fixed reference of 14.7 psi. The sealed gage sensor allows the transmitter to be electrically offset to simulate 0 psia for vacuum applications. (For further installation details see Section V, Mechanical Installation.) Small Lightweight, Easily Mounted The hybrid DC electronics of the 3000 series is simple and reliable, requiring far less space than in competitive transmitters. The small size electronics enclosure, made of 316 stainless steel, provides a lighter and more rugged unit, for easy and inexpensive mounting. In Process Verification The transmitters are tested for accuracy, stability and reliability during each manufacturing phase. Sensing assemblies are checked in an environmental chamber to verify performance characteristics and eliminate mechanical stresses. Simultaneously, amplifiers are burned in at elevated temperatures to eliminate premature component failures. The electronic amplifier assembly and sensors are then matched, assembled and welded together to form the complete transmitter. The completed unit is 6 PA/PG3000 Installation Manual SECTION II SPECIFICATIONS 7 PA/PG3000 Installation Manual 8 PA/PG3000 Installation Manual 9 PA/PG3000 Installation Manual SECTION III MECHANICAL INSTALLATION Location Selection Ametek Gulton-Statham 3000 series transmitters have been specifically designed and constructed to operate in hazardous environments. It is, however, important to recognize that these are precision measuring instruments whose accuracy, reliability and stability may have a great influence on process efficiency and quality. For best results, the location should be selected with care. GENERAL Most problems associated with pressure transmitters are generally the result of improper installation. The importance of following the instructions and considering the recommendations provided in this section cannot be overemphasized. Unpacking The shipping container should be examined carefully before unpacking. If there are visible signs of significant damage, do not open the container, but notify the carrier and Ametek Gulton-Statham immediately. If no external damage is apparent, the container should be opened and the contents compared with the packing list. The carrier and Ametek GultonStatham should be immediately notified if there is equipment damage or shortage. Please do not return goods without contacting Ametek Gulton-Statham in advance. Vibration & Shock The influences of shock and vibration should always be minimized. Vibration often occurs in locations at certain times and under certain process conditions, and not at other times. Evaluate the conditions with care. See the specifications section for the likely errors associated with vibration on transmitter performance. It may be possible to reduce any harmful influences of vibration by correct selection of the type of mounting, as well as the location. The stiffness and flexibility of the mounting will have an effect as will the location of the bracket and support structure. Close attachment to a heavier component may well reduce the vibration effect. Remember that vibration forces can be transmitted through the process piping and fluids in the system, as well as through the structure itself. Testing All 3000 series transmitters are factory calibrated and performance verified prior to shipment. Customer testing before installation is usually unnecessary and not recommended in most circumstances. Storage & Shipment For extended storage or for shipment, the transmitter should be kept in its shipping container. Do not remove plugs or covers. If the transmitter has been installed, be sure all process fluid is completely drained from the unit. Clean the transmitter thoroughly if it has been exposed to corrosive conditions while in service. Always store the transmitter in a suitable environment (see Section II, Specifications, and Section VI, Maintenance, Storage, Shelf Life & Spares). Temperature In order to achieve optimum performance, the transmitter should not be exposed to the high or low temperature extremes. It is good practice to minimize, or avoid, sudden or large variations in temperature, which can affect performance. Consider all the possible sources of temperature. Heat or cold may come from the process connections, ambient air, or by radiation from or to nearby cold or hot objects. Extended lengths of piping will generally provide more surface area for cooling (or heating) of hot or cold lines connecting to the transmitter. Use shields to block radiant and convective heat transfer between the transmitter and hot or cold objects in close proximity. 10 PA/PG3000 Installation Manual Transmitter Location Proper location of the transmitter with respect to the process measurement is critical for accurate gage pressure measurements. For noncondensing gases, the transmitter should be located above the process taps (see Figure 3.1). For liquid or condensing gases, the transmitter should be located below the process taps (see Figure 3.2). Other, general considerations should include: Accessibility The location should be selected to allow direct access for adjustment or recalibration while in service. The zero and span magnets should always be accessible. Also, the transmitter should be removable in the event shop servicing is required. Consideration of optional equipment should also be made. For example, if a meter/junction box is incorporated, it must be accessible for convenient viewing and wiring. From the model number on the ID plate, determine the options that have been included in the unit to be installed. 11 • Impulse tubing should be kept as short as possible and of sufficient diameter to avoid friction loss. • Slope impulse piping at least 1 (one) inch per foot up toward the process connections for non-condensing gas. • Slope impulse piping at least 1 (one) inch per foot down toward the process connections for liquid or steam. • Ambient temperature extremes fluctuations should be avoided. • Sediment should be kept from depositing in the impulse tubing. • The transmitter should be isolated from hot or corrosive process fluids. • In dry leg applications, possible condensation in the impulse piping should be avoided. • For steam service, impulse tubing should be filled with water to prevent contact of live steam with the transmitter. or PA/PG3000 Installation Manual NON-CONDENSING GAS INSTALLATION • Mount the transmitter such that the impulse piping connection is made from below the transmitter. • Ensure there are no low spots in the impulse piping between the process taps and transmitter connection. • Slope the impulse piping at least one (1) inch per foot down toward the process taps. • Install valving between the process taps and transmitter to permit static equalization (zero adj.) and process shut off. FIGURE 3.1 LIQUID OR CONDENSING GAS INSTALLATION • Mount the transmitter such that the impulse piping connection is made from above the transmitter. • Ensure there are no vapor traps in the impulse piping between the process taps and transmitter connection. • Slope the impulse piping at least one (1) inch per foot upward to the process taps. • Install valving between the process taps and transmitter to permit static equalization (zero adjustment) and process shut off FIGURE 3.2 12 PA/PG3000 Installation Manual Process Connections Process tubing should be installed so it will not produce added mechanical stresses on the transmitter during seismic disturbances. This is often accomplished with the use of stress-relief loops in the process tubing or by separately supporting the process tubing close to the transmitter. SECTION IV ELECTRICAL INSTALLATION ELECTRICAL TERMINATIONS The 3000 series pressure transmitters are supplied with one of five possible electrical terminations: The PG/PA3000 series transmitters are supplied with one of three possible process connections: CODE 4. CODE 8. CODE 9. CODE 2. ½-14 NPT process connection per ANSI B2.1. Flange fitting for three-valve manifold. High pressure tube port (autoclave F250C). CODE 6. CODE 8. CODE 0. Mounting Bracket Installation The Models EW3 and EW7 2 in. pipe mounting bracket can be installed to provide a rigid support for the PG/PA3000 series transmitter. Two (2) mounting screws and U-bolt assembly are provided for mounting the transmitter to a 2inch pipe. CODE A. Three-wire 16 AWG. 36 in, long BLACK WIRE - Positive WHITE WIRE - Negative GREEN WIRE - Ground Molded Submersible Service Cable, 3-conductor, 16 AWG, Neoprene Insulated Electrical accessory connected to transmitter at the factory 3-Conductor cable, 18AWG, Teflon Insulated, 60 in. long, Molded Submersible Service Cable, 3-conductor, 16 AWG, Viton Insulated Wiring The Transmitter The power supply requirements range from +12 VDC at no load to +55 VDC at a maximum 2150 ohms load. All power to the transmitter is supplied over signal wiring, No additional wiring is required. Shielded twisted pairs or shielded cable provide the maximum noise immunity. When using shielded cable, make sure only one end is grounded (see Figures 4.1 and 4.2). Under no circumstance should the transmitter signal wiring be placed in the same conduit with AC power circuits. Materials Required: Description: 2-inch pipe mounting bracket with carbon steel hardware EW3 Bracket P/N: 064127-000-003 OR Description: 2-inch pipe mounting bracket with 316 CRES hardware EW7 Bracket P/N: 064127-316-003 13 PA/PG3000 Installation Manual A single transmitter or multiple transmitters may be connected to a +DC power supply providing that the type of wire, length from the transmitter, and line resistance are taken into consideration. Make sure the power supply used has a minimum voltage (AC) ripple and meets your requirements to overcome voltage drop (line loss) and current loss in your closed loop circuit. The negative side of the power supply should be grounded. Do not exceed the specified load limitations of the transmitter for a particular power supply voltage. A block diagram of a typical single transmitter installation is shown in Figure 4.1, and a multiple transmitter installation in Figure 4.2. Output Damping The 3000 series gage pressure transmitters are supplied damped with a response time of 300 milliseconds for a 63% step to input pressure. Optional fast response of less than 10 milliseconds is available (see Figure 4.3). 14 PA/PG3000 Installation Manual Operation The Ametek Gulton-Statham Model TP131 (see figures 4.7 and 4.8) and Model TP114 Transient Suppressors (see Figure 4.5) are designed to isolate any 3000 series two-wire pressure transmitter against damaging electrical transients such as lightning or lightning induced, inductive switching (EMI), and electrostatic discharge (ESD). Each lead wire is protected by a gas filled surge protector and ultra-fast clamping circuit to provide a low clamping voltage, which automatically shunts damaging electrical transients to ground. The circuitry is environmentally protected against man-made or atmospheric conditions to provide extended reliability. These transient suppressors are rated as follows: SURGE CAPACITY MAXIMUM VOLTAGE SURGE ADDED LOOP RESISTANCE Factory Molded Cables For high moisture related or submerged applications, the 3000 series transmitters can be supplied with factory molded Neoprene or Viton cabling (see Figure 4.4). The cabling consists of three 16 AWG tin/copper conductors, compression molded to the electrical connection of the transmitter electronics housing. The protective, corrosion resistant cover provides a reliable moisture proof seal. These cables can typically be submerged to depths of up to 500 feet (1000 psi external pressure) without degradation of the molded seal. Optional Electrical Connectors Ametek Gulton-Statham 3000 series transmitters can be supplied with optional electrical connectors for moisture related, submerged or quick connect/disconnect requirements. 5000 amps 700 VDC 44 ohms Installation The TP131 is designed to install directly beneath the terminal block of the Ametek Gulton-Statham MA130 series, NEMA rated electrical enclosure (see Figures 4.9 and 4.10). Its unique packaging requires only that the terminal block be removed from the junction box and the TP131 be inserted. Additional assembly screws are supplied with the TP131. These screws must be installed in place to maintain electrical continuity from the terminal block, through the TP131, and to the transmitter. C100/101 (Quick) Electrical Connector For applications which may require a quick disconnect for ease of removal of the transmitter, or require flexible electrical terminations, the 3000 series can be factory fitted with a Ametek Gulton-Statham C100/101 electrical connector (see Figure 4.6). The C100/101 assembly consists of the C100 adapter, which is fitted to the electrical connection of the transmitter electronic housing at the factory, and the C101 electrical connector that is fitted with the field terminations by the user. The C100 is a four-pin adapter in which only three pins are utilized: for the ground (Green Pin B), the positive (Black, Pin A), and the negative (White, Pin D) terminations to the transmitter. The C101 is a four-pin MS3106F14S-12S type quick disconnect receptacle with cable clamp. NOTE: PIN C IS LEFT OPEN The TP114 is factory installed into the electrical conduit connection of any 3000 series transmitter, or compatible electrical enclosure. Its electronic components are identical to the TP131 in performance characteristics, but are housed in a stainless steel tube, internally threaded at each end. This allows simple installation between the conduit connection of the TP114 and the electrical conduit. 15 PA/PG3000 Installation Manual 16 PA/PG3000 Installation Manual 17 PA/PG3000 Installation Manual 18 PA/PG3000 Installation Manual 19 PA/PG3000 Installation Manual the o-ring upon reinstallation of the cover onto the junction box housing. Junction Box Field Installation Procedure The PA/PG3000 series is offered with a 3/4-14 NPT thread for the installation of the optional junction box. Should it be necessary to reinstall a new junction box in the field, the following procedure will assist in doing so. 5. Reinstall new o-ring. 6. Apply a new coating of anti-seize thread compound on the external threads of the junction box cover. Note: Prior to applying compound, visually inspect threads and sealing surfaces to ensure no contaminants which may effect proper thread engagement or sealing are adhering to these areas. 1. After the existing junction box has been removed. Clean any contaminants from the conduit thread of the transmitter electronics housing. 2. Apply thread sealant listed below to conduit threads of the transmitter electrical housing. Then, starting at zero thread engagement, install the junction box a minimum 5-thread axial engagement. 7. With zero thread engagement, place the cover unto the junction box and rotate the cover a minimum of 8 ½ revolutions in the clockwise direction. This will properly secure the cover and ensure sealing of the o-ring. Note. No tooling to assist for additional mechanical leverage or torqueing is required. Junction Box O-ring Field Replacement Procedure Scope: During periodic maintenance procedures, it may be necessary to remove the cover from the factory installed hazardous location qualified junction box, to access field wiring terminations. When the cover has been removed, it is recommended standard practice to replace the o-ring seal to ensure proper sealing during reinstallation. Note: While o-ring will properly seal after 8 ½ revolutions, exceeding this until metal to metal contact between the cover and housing is made, will not degrade the seal. The method for installation requires hand tightening only! No tooling to assist for additional mechanical leverage should be utilized. Procedure 1. By hand, remove the junction box cover from the housing by rotating in the counter clockwise direction until the threads are completely disengaged. Conduit Installation The PA/PG3000 series has ¾-14 NPTF conduit threads for either the transmitter threaded housing connection, or the optional junction box threaded conduit connections. Apply thread sealant to conduit threads. Then, starting at zero thread engagement, install the conduit by rotating 4-7 turns in the clockwise direction. 2. Remove the o-ring seal from the base of the threads on the junction box cover and properly dispose of it to ensure it will not be re-used. 3. Wipe existing anti-seize thread compound and contaminants from the external threads of the junction box cover and the internal threads of the junction box housing. 4. Apply a thin uniform coating of silicone lubricant to the new o-ring surface. Note: Silicone lubricant is utilized to aid in sealing and prevention of damage to 20 PA/PG3000 Installation Manual Range Value, Upper -The highest value of a measured variable that a device is adjusted to measure. SECTION V CALIBRATION Proper Range Selection The 3000 series transmitters are factory calibrated, either to the specified range or to the maximum span of the transmitter. Since the unit is hermetically sealed, provision has been made for zero and span adjustments through external screwdriver adjustable magnets. The external adjustment screws are coupled to internal zero and span potentiometers by the use of permanent magnets, which are mounted back to back on the transmitter housing. Zero and span adjustments are non-interacting. Definition Of Ametek Gulton-Statham Terms (Based On SAMA Standard PMC20-1-1973 "Process Measurement And Control Terminology") Accuracy - Conformity of an indicated value to an accepted standard value or true value. Reference accuracy is the limit that errors will not exceed when the instrument is used under reference operating conditions. Calibration -Adjustment of the output of a device to bring it to a desired value, within a specified tolerance, for a particular value of input. For gage pressure applications, proper range selection is of the greatest importance in ensuring compatibility of the transmitter to the actual application. In most applications, the transmitter type selected is predetermined by the environmental and physical limitations. Linearity - The maximum deviation of an actual characteristic (average of upscale and downscale readings) from a straight line positioned so as to minimize the maximum deviation. Each transmitter manufacturer may specify a unique elevation and suppression limit based on the turndown ratio capability of the electronic amplifier. To determine if a transmitter is capable of the intended application, the following formula (where LCV = lower calibrated value) can be utilized. Span - The algebraic difference between the upper and lower range values. Range - The region between the limits within which a quantity is measured or transmitted. %Elevation or suppression = Elevation & Suppression of Electronic Pressure Transmitters (Definitions extracted from ISA STANDARD & PRACTICES FOR INSTRUMENTATION, 9th Edition, Volume 2, 1998.) LCV X 100 SPAN The following rules apply: The elevation of a transmitters output cannot exceed the maximum span. Range, Suppressed Zero - A range in which the zero value of the measured variable is less than the lower range value. The suppression of a transmitters output cannot be greater than the maximum span minus the minimum span. Range, Elevated Zero - A range in which the zero value of the measured variable, measured signal, etc., is greater than the lower range value. Example: 100 psi with 5:l turndown. Maximum Span = 100 psi Minimum Span = Range Value, Lower - The lowest value of the measured variable that a device is adjusted to measure. 100 = 20 psi 5 100-20 = 80 psi Max Suppression = 80 psi 21 PA/PG3000 Installation Manual Zero Suppression Applications Zero suppression occurs when the transmitter body is installed below the process connection. Suppression of zero output may be achieved for differential pressure, gage pressure, and remote seal applications. The actual amount of zero suppression is determined by multiplying the vertical distance between the transmitter body and process connection, times the specific gravity of the process media or filled capillary leg (see Figure 5.3 and 5.4). Zero Elevation Applications Zero elevation occurs when the transmitter is installed above the process connection. The actual amount of zero elevation is determined by multiplying the vertical distance between the transmitter body and the process connection, times the specific gravity of the process media or filled capillary leg (see Figure 5.1). Elevation is treated as a negative value because the static head created by the process or fill fluid, acts as a negative pressure on the transmitter. The term “suppressed span” is often used for elevated zero applications; however; the term “elevated zero range” is preferred to avoid confusion for the actual calibration required (see Figure 5.2). 22 PA/PG3000 Installation Manual Field Calibration For Field or Shop calibration, a dummy load resistor may be substituted for the receiving instrument. The dummy load (generally 250 ohms) is installed in series with the loop. A digital multimeter or VOM is connected to read the output across the dummy load. A pressure source of known accuracy should be connected to the process or pressure connection of the transmitter. Compound Calibrations Calibrations that require a reference (4mA) setting below atmospheric pressure and a span (20mA) above atmospheric pressure are generally referred to as compound calibrations. These types of calibrations are common in applications in which vacuum is involved. (See Figure 5.5) • Apply the desired zero reference pressure or vacuum. Adjust zero to indicate 4.00 mA (1 volt across 250 ohm res.). To decrease the output, turn the ZERO SCREW CCW; increase output, turn the screw CW. Adjustment of the zero output will have no interaction with the span output. ZERO ADJUSTMENT Calibration for Vacuum Service The PA/PG3000 series can be calibrated for absolute (vacuum) service. The sensor is sealed and is not subject to barometric pressure influence. It therefore can be electronically offset to simulate an absolute pressure. With an elevated capability to full vacuum (-14.7 psi) the zero output (4mA) can be adjusted to 0 psia (-14.7 psi). NOTE: For suppressed zero calibrations, a pressure equivalent to the anticipated Zero Suppression is applied to process connection. For elevated zero calibrations, vacuum equivalent to the anticipated Zero Elevation is drawn on the process connection. Elevation can be to full vacuum. True or Low Gage Application For gage pressure applications requiring very low measurements or a zero reference which is influenced by barometric pressure (true gage), the model PD/PDH3000 can be utilized by venting the reference (LP) side to atmosphere. Consult factory for options. 23 PA/PG3000 Installation Manual • SECTION VI Pressure equivalent to the maximum span and the span adjusted to indicate 20 mA (5 volts across 250 ohm resistor). Turn the SPAN SCREW CW to decrease output and CCW to increase output. Adjustment of the span output will have no interaction with the zero output. MAINTENANCE, STORAGE, SHELF LIFE & SPARES MAINTENANCE Unlike most electronic pressure transmitters, the 3000 series require very little maintenance. The hermetically sealed design prevents moisture intrusion into the electronics assembly, thus eliminating frequent electronics assembly replacement. The hermetic design also eliminates the requirement for o-ring seals in the electronics enclosure, which require periodic replacement due to environmental aging. In addition, only periodic verification of the zero reference calibration may be required to confirm that no process variables have changed or altered the initial reference calibration. It will also ensure that the transmitter is maintaining performance within its published specifications. SPAN ADJUSTMENT NOTE: In the event of any change in the output readings, repeat adjustments until the readings are correct. Should an inability to adjust the output persist, contact the factory for technical assistance. STORAGE, SHELF LIFE &, SPARE PARTS RECOMMENDATIONS The 3000 Series feature an environmentally protected electronics amplifier. The active electronic components are sealed in an allwelded stainless steel enclosure. This enclosure is rated for 100% relative humidity, therefore, eliminating special storage requirements and additional spare parts inventories. Storage & Shelf Life: Five (5) years at a maximum temperature of 100°F (38°C) in a warehouse type environment. It is not necessary to make special precautions for storage. It is, however, suggested that the unit be stored at, or near, room temperature and out of contact with direct sunlight. The transmitter is unaffected by relative humidity. Spares Recommendations: With the greatly reduced probability of electronics failure due to moisture and other contaminants, no spare parts are necessary. In the unlikely event of a failure, it is recommended that a minimum of one or two transmitters are maintained as spares. 24 PA/PG3000 Installation Manual SECTION VII TROUBLESHOOTING GENERAL In the event of a transmitter malfunction, the procedures listed below will assist in isolating the problem and its source. These procedures will also help in determining whether the fault can be corrected on site. The information is intended to assist in diagnosis of 3 primary malfunction symptoms. Under each symptom, checking procedures are listed for conditions most likely to result in the malfunction. To expedite the troubleshooting process, select the symptom most closely resembling the unit's apparent malfunction and use the information in this manual. Start with the most likely and easiest to check conditions. No Output Or Low Output Signal • Check for shorts and multiple grounds in loop wiring. Check polarity of connections. • Check loop impedance. • Check for entrapped gas in liquid lines. • Check transient suppressor (if used) for 1 megohm or greater resistance to ground from each lead. • Check for transmitter. adequate voltage to High Output Signal • Check output of power supply. • Check transmitter connections. • Check to see if block and bleed valves are fully open. Check for entrapped gas in liquid lines, and entrapped liquid in gas lines. • Check for sediment, or other blockage, in the impulse lines to the transmitter. Erratic Output • Check for intermittent shorts open circuits, and multiple grounds in loop wiring. Detective or damaged transmitters should be returned to Ametek Gulton-Statham per the instructions defined in Section IX. • • 25 • Check piping for entrapped gas in liquid lines or for liquid in dry lines. • Check for transmitter. adequate voltage to PA/PG3000 Installation Manual SECTION VIII RETURN FOR REPAIR Authorization Number When returning a transmitter for repair, please call and request a Return Material Authorization (RMA) Number from our CUSTOMER SERVICE DEPARTMENT, Telephone (949) 642-2400, FAX (949) 642-9490. The following information will be requested: Please pack the transmitter and paperwork in a box that will prevent shipping damage. Ship the package, transportation prepaid, to the following address: Ametek Gulton-Statham, 1644 Whittier Ave. Costa Mesa California 92627 ATTENTION: Repair Department. RMA#: _____________________ 1. Name, address, and telephone number of the individual to be contacted for further details. 2. Model number and serial number of transmitter. 3. A brief description of the problem, including any related circumstances. 4. A brief description of the service, including maximum pressure, temperature, and period of time in service. 5. Purchase Order for repair. 6. Complete shipping instructions for returning unit. 7. All transmitters returned for repair must be accompanied by a hazardous chemical disclosure form per OSHA Standard 28CFR1910.1200, "Right To Know Law". A form may be obtained from customer service or a copy may be made from the sample enclosed on page 22. NOTE: Please include the Return Material Authorization Number (RMA) on the Return Address. Chemical Disclosure Requirements "The Right To Know Law" All transmitters returned for repair evaluation must be accompanied by a hazardous chemical disclosure form per OSHA Standard 28CFR1 910.1200, "Right To Know Law". Copies may be obtained from the Customer Service Department. PLEASE NOTICE If the product has been in contact with potentially harmful chemicals or gases, it should be thoroughly decontaminated prior to return to Ametek Gulton-Statham. Upon evaluation, a quotation indicating the repairs required and applicable charges will be forwarded to the customer. Non-warranty repair work will not be initiated until the customer issues authorization to proceed. Charges for repairs, not covered under warranty, will be quoted from the factory. Warranty repairs will be performed at no charge and without customer authorization. 26 PA/PG3000 Installation Manual TRANSMITTER HAZARDOUS CHEMICAL DISCLOSURE “Right To Know Law” OSHA Standard (28CFR1910.1200) Company Name Date Address Phone RMA # Signature Serial Number: Model Number: □ □ Has not been exposed to hazardous chemicals □ □ Has not been exposed to hazardous chemicals □ □ Has not been exposed to hazardous chemicals. Has been exposed to hazardous chemicals and has been properly neutralized Chemical Name: Neutralized With: Serial Number: Model Number: Has been exposed to hazardous chemicals and has been properly neutralized. Chemical Name: Neutralized With: Serial Number: Model Number: Has been exposed to hazardous chemicals and has been properly neutralized Chemical Name: Neutralized With: 27 PA/PG3000 Installation Manual RETURN MATERIAL AUTHORIZATION Shipments of returned goods may be refused unless preauthorized by Ametek Gulton-Statham. An RMA number is obtained by calling our Product Services Department (949) 642-2400. Note: Enclose form with shipment. CALLER Issued by: RMA No Date: TECH. CONTACT SHIPPING INFORMATION COMPANY UPS AIRFREIGHT OTHER COMPANY (IF DIFFERENT FROM LEFT) ADDRESS ADDRESS CITY STATE PHONE FAX ZIP CITY PURCHASE ORDER STATE ZIP ATTENTION The following material is hereby authorized to be returned: MODEL/DESCRIPTION S/N (s) CUSTOMER OBSERVED MALFUNCTION 1 2 3 4 5 SERVICE CONDITIONS: Temperature °F to °F, Line pressure VDC Other: ACTION REQUESTED: 1 Evaluate and repair, bill applicable charges (upon our approval) against P.O. 2 Return of loan or demo equipment. Loan Order 3 Return of Distributor stock (unused condition) SHIP TO: Approval: Ametek Gulton-Statham, 1644 Whittier Ave. Costa Mesa California 92627 Phone: (949) 642-2400 Fax: (949) 642-9490 28 Date: PA/PG3000 Installation Manual SECTION IX WARRANTY Seller warrants that the products and services furnished hereunder will, at the time of shipment, be free from all defects in material and workmanship under normal use and service, and will conform to Seller's applicable standard published specifications for a period of five (5) years from the original date of shipment. Seller's sole obligation hereunder shall be limited to, at Seller's option, either replacing or repairing any products for which (I) written notice of nonconformance hereunder is received within the warranty period, and (II) after Seller's authorization, are returned to Seller's factory of origin, freight prepaid; and (III) after examination are disclosed, to Seller's satisfaction, to be nonconforming. Any such repair or replacement shall not extend the period within which such warranty can be asserted. This warranty shall not apply to products which Seller determines have, by Buyer or another, been subjected to operating and/or environmental conditions in excess of the maximum values therefore in applicable specifications or otherwise have been subjected to misuse, neglect, improper installation, repair alteration or damage. This warranty may be asserted by Buyer only and not by Buyer's customers or users of the Buyer's products and is expressed in lieu of all other warranties, expressed, implied, or statutory, including any implied warranty of fitness for a particular purpose or merchantability, and all other obligations or liabilities on the Seller's part. Seller neither assumes nor authorizes any other person to assume for Seller any other liabilities in connection with the sale of said products. In no event shall Seller be liable for any special, incidental, or consequential damages. 29 PA/PG3000 Installation Manual SECTION X C. 1. NACE COMPLIANCE AND APPROVALS 2. NACE MR-01-75 COMPLIANCE The NACE Standard is not a code document and is not intended for certification of the materials and procedures described. This Standard was prepared as a material requirement for oil field equipment. The NACE Committee, in its March 15, 1979 Atlanta meeting, recognized the inadequacy in its treatment of process instruments. The NACE Standard can serve as a useful guideline in selecting materials for hydrogen sulfide applications. I. NACE Standard MR-01-75 (1984 Revision) per Paragraph 1.2 applies to parts and materials exposed to sour gas environments. As defined in Paragraph 1.3, “Fluids containing water as a liquid and hydrogen sulfide… (which) ….may cause sulfide stress cracking (SSC) of susceptible materials.” The parts of the 3000 series transmitters that are normally exposed to the process environment are process flanges, flange adapters, isolation diaphragm assemblies, drain/vent valves, drain plugs, and “o” rings. II. Compliance of the exposed portions (wetted parts) in relationship to the Standard are: A. 1. Process Flanges and Flange Adapters Stainless steel flanges and adapters are a casting of 315 stainless steel and comply with the Standard per Paragraph 3.6 and Table 2. Hastelloy C flanges and adapters comply per Paragraph 4.1.5.1 and Table 3, 2. B. 1. D. “O”-rings “O”-rings are not covered by this Standard. Teflon “O”-rings have been provided for these types of applications in the past with satisfactory results. III. Compliance of Fabrication Procedures: A. The Hastelloy C. diaphragms use electric resistance welds. The heat affected zone is extremely small and metallurgical changes in the weld zone are minimal. The intent of the Standard is met. All exposed threads are cut and comply with the Standard per Paragraph 5.5.1.1. Bolting is non-exposed per Paragraph 1.3 and 6.3. B. C. Isolation Diaphragm Assembly Diaphragms of Hastelloy C comply per Paragraph 4.1.5.1 and Table 3. Isolation diaphragms of 316 SS comply per Paragraph 3.6 and Table 2. 30 Drain/Vent Valves and Drain Plugs Hastelloy C drain/vent valves comply per Paragraph 4.2.5.1 and Table 3. 316 stainless steel drain/vent valves comply per Paragraph 3.6 and Table 2. IV. Paragraph 1.3.1.2 defines specific areas in which “off-the-shelf” equipment” may be considered outside the scope of the Standard when used on “crude oil, or two or three phase crude, water and gas”. Ametek Gulton-Statham has had years of successful service in these areas. V. Other parts of the pressure transmitter, such as sealed 316 stainless steel electronics housing, circuit boards, bolts, nuts, module housing, etc., are not exposed components as defined in Paragraphs 1.3.1 and 1.2 and are outside the scope of the Standard. VI. Transmitters used in a closed environment (per Paragraph 6.2.1.2) are required to use B7M bolts, which will meet NACE specifications. PA/PG3000 Installation Manual For further information, see Flammable and Combustible Liquids Code, NFPA30-1977; Storage and Handling of Liquified Petroleum Gases, NFPA 58-1979; Storage and Handling of Liquified Petroleum Gases at Utility Gas Plants, NFPA 59-1979; and Classification of a Class I Hazardous Locations for Electrical Installations in Chemical Plants, NFPA 497-1975 (ANSI). Ametek Gulton-Statham Transmitters for Hazardous Locations Ametek Gulton-Statham transmitters have been approved for use in hazardous locations in USA by Factory Mutual Research (FM); in Canada by Canadian Standards Association (CSA) and in Europe to ATEX certification to IEC 60079. Hazardous locations are classified according to the properties of the flammable vapors, gases, dust and fibers that may be present, and the likelihood that a combustible concentration is present. For protection against static electricity hazards, see Recommended Practice on Static Electricity, NFPA 77-1977 (ANSI). In USA and Canada hazardous locations have been divided into class, division and group as described below. Class I, Division II, Groups A, B, C & D Class I, Division II, locations are those in which ignitable concentrations of flammable gases or vapors may exist only under abnormal operating conditions, failure of ventilating equipment or areas adjacent to Class I, Division I, locations where vapors might occasionally accumulate. Class I, Division 1, equipment may be used for this service. Class I, Division I, Groups A, B, C & D Class I, Division I, locations are those in which ignitable concentrations of flammable gases or vapors may exist under normal operating conditions. Electrical equipment for this class of service may be “explosion-proof”, “intrinsically safe”, “purged”, or otherwise protected to meet the intent of Article 500 and 501 of the National Electrical Code. Class II, Division I, Groups E, F & G Class II, Division I, locations are those areas where combustible dust is normally present in the atmosphere in such quantities that would support ignition or explosion. Equipment listed as suitable for Class II locations is “dustignition-proof” or otherwise designed and installed to meet the intent of Article 500 through 503 of the national Electrical Code (NEC). “Explosion-proof” refers to the ability of a device to withstand an internal explosion of a specified gas or vapor and prevent the ignition of external gages or vapors when sparking, flashing or explosions occur within the enclosure. In addition, the external temperature of the device will not ignite the surrounding atmosphere. “Intrinsically safe” equipment and wiring are incapable of releasing sufficient electrical or thermal energy to cause ignition of specified gases or vapors in their most ignitable concentrations. “Dust-ignition-proof” as used in the preceding paragraph means that the enclosure of the device will exclude ignitable quantities of the dust that may affect the performance or rating, or where installed per code, will not allow sparks, arcs or heat to ignite materials external to the enclosure. “Purged” systems are designed to provide a continuous source of clean air or inert gas under a positive pressure with effective safeguards against failure, thus providing a non-hazardous atmosphere. Equipment suitable for Class I locations is not necessarily suitable for Class II or III locations unless specifically identified as such. 31 PA/PG3000 Installation Manual Class II, Division II, Groups E, F & G Class II, Division II, locations are areas in which combustible dust will not normally be present in sufficient quantities to support combustion, or infrequently present in combustible quantities only by the failure of electrical equipment or apparatus. Class II, Division I, equipment may be used for this service. In addition to meeting the requirements for hazardous (classified) locations as defined by the National Electrical Code (NEC), the 3000 series transmitters meet the requirements of the National Electrical Manufacturers Association (NEMA) for Classes 3, 4, 6, 7 & 9 as defined below: NEMA 3 NEMA 3 enclosures are dust tight, rain tight and sleet (ice) resistant suitable for outdoor service. Class III, Divisions I & II Class III, Divisions I and II, locations are hazardous due to presence of combustible fibers or flyings which are not normally present in the atmosphere in quantities that would support combustion. NEMA 4 NEMA 4 enclosures are watertight, dust tight and designed to prevent seepage from a direct stream of water. The preceding classification definitions have been taken from the 1981 edition of the National Electrical Code (NEC). Please consult this reference for complete information regarding the selection and installation of devices for hazardous location service. NEMA 6 NEMA 6 enclosures are watertight, dust tight, submersible and ice resistant suitable for use in either indoor or outdoor applications. It is the user’s responsibility to select equipment suitable for the hazardous (classified) location and install such equipment in accordance with published standards and approved codes. NEMA 7 NEMA 7 enclosures are designed for Class hazardous (classified) locations. See NEC Article 502 for complete information. Various equipment approved for hazardous (classified) locations may be combined in a system and approved as a system by arranging for site inspection by the applicable agency. NEMA 9 NEMA 9 enclosures are designed for Class II hazardous (classified locations. See NEC Article 502 for complete information. 32 PA/PG3000 Installation Manual EXPLOSION PROOF X - Approved Class I, Division I INTRINSICALLY SAFE Class I, Div II Class I, Division I GROUPS A B C D E F G A B C D PA/PG3000 X X X X X X X X X X X MA134, 5, 6 X X X X X X X X X X X X X X X X X X X C100/101 TP114/131 X X X X X X X FIGURE 10.1 PRODUCT APPROVAL - NORTH AMERICAN 33 PA/PG3000 Installation Manual SECTION XII INTRISICALLY SAFE SYSTEMS Scope This document is intended as a guide to the user for the proper installation of Ametek Gulton-Statham transmitters in intrinsically safe loop configurations. The configurations contained in the document are to be utilized with approved barriers only. Certified barriers are listed in the list of Certified Electrical Equipment. Hazardous Area Requirements Wiring connected to the hazardous area terminals must be separated from nonintrinsically safe wiring. All wiring has distributed inductance and capacitance. The maximum permitted cable parameters for the particular barrier must not be exceeded. If the capacitance and inductance of the cable used are not known, values of to PF/FT, and 0.2 uH/FT, may be used as conservative criteria for cable. Factory Mutual Barrier Application Rules & Diagram Installation Different intrinsically safe systems shall not be run in the same multi-conductor cable. Different intrinsically safe circuits of the same intrinsically safe system shall not be run in the same cable, unless at least 0.25 mm thickness insulation is used on each conductor, or unless no hazard results from interconnection., If in doubt contact the local inspection authority. The barrier must be located in a non-hazardous area, and be mounted in an appropriate enclosure or other protected space. The barrier must be grounded, via two independent connections, to a ground electrode in the non-hazardous area. Grounding practices should conform to NEC Article 250. The resistance from the barrier to the ground electrode must not exceed one (1) ohm. Hazardous area equipment shall not have exposed any surfaces that operate at a temperature in excess of ignition temperate of the specific gas, vapor, or dust. Refer to NFPA 325 for ignition listings. Barrier installation must be in accordance with the Ametek Gulton-Statham Intrinsically Safe loop diagram shown on Drawing No. 64706 (See Figure 11.1). Safe Area Requirements Equipment connected to the non-hazardous area terminals must not be supplied from, nor contain, a source of potential with respect to ground under normal or fault conditions exceeding 250 V RMS. Mains powered equipment connected to the non-hazardous area terminals must be isolated from the mains supply by a double wound transformer, unless the applicable electrical code permits multiple grounding of the neutral lead. 34 PA/PG3000 Installation Manual 35 PA/PG3000 Installation Manual Canadian Standards Association Barrier Application Rules & Diagram Barrier Application Rules Hazardous Area Requirements Installation Wiring connected to the hazardous area terminals must be separated from nonintrinsically safe wiring The barrier must be located in a non-hazardous (safe) area, and be mounted in an appropriate enclosure or other protected space. All wiring has distributed inductance and capacitance. The maximum permitted cable parameters for the particular barrier must not be exceeded. If the capacitance and inductance of the cable used are not known, values of 60 PF/FT, and 0.1 UH/FT, may be used as a conservative criteria for cable. The barrier must be grounded, via two independent connections, to a ground electrode in the non-hazardous area. Grounding practices should conform to C22.1-1k975, Section 10. The resistance from the barrier to the ground electrode MUST NOT EXCEED ONE (1) OHM. Different intrinsically safe systems shall not be run in the same multi-conductor cable. Different intrinsically safe circuits of the same intrinsically safe system shall not be run in the same cable, unless at least 0,15 mm thickness insulation is used on each conductor, or unless no hazard results from interconnection. If in doubt, contact the local inspection authority. Barrier installation must be in accordance with Ametek Gulton-Statham intrinsically safe loop diagrams shown on Drawing No. 64915 (See Figure 11.2). Safe Area Requirements Equipment connected to the non-hazardous area terminals must not be supplied from, nor contain, a source of potential with respect to ground under normal or fault conditions exceeding 250 V RMS. Hazardous area equipment shall not have exposed any surface that operates at a temperature in excess of the ignition temperature of the specific gas, vapor, or dust. Refer to C22.2 No. 30-1970 for ignition listings. Mains powered equipment connected to the non-hazardous area terminals must be isolated from the mains power supply by a double wound transformer, unless the applicable electrical code permits multiple grounding of the neutral lead. 36 PA/PG3000 Installation Manual 37 PA/PG3000 Installation Manual ATEX Barrier Application Rules and Diagram Barrier Application Rules Installation Hazardous Area Requirements The barrier must be located in a non-hazardous (safe) area, and be mounted in an appropriate enclosure or other protected space. Wiring connected to the hazardous area terminals must be separated from nonintrinsically safe wiring The barrier must be grounded, via two independent connections, to a ground electrode in the non-hazardous area. Grounding practices should conform to ATEX. The resistance from the barrier to the ground electrode MUST NOT EXCEED ONE (1) OHM. All wiring has distributed inductance and capacitance. The maximum permitted cable parameters for the particular barrier must not be exceeded. If the capacitance and inductance of the cable used are not known, values of 60 PF/FT, and 0.1 UH/FT, may be used as a conservative criteria for cable. Barrier installation must be in accordance with Ametek Gulton-Statham intrinsically safe loop diagrams shown on Drawing No. 40716 (See Figure 11.3). Different intrinsically safe systems shall not be run in the same multi-conductor cable. Different intrinsically safe circuits of the same intrinsically safe system shall not be run in the same cable, unless at least 0,15 mm thickness insulation is used on each conductor, or unless no hazard results from interconnection. If in doubt, contact the local inspection authority. Safe Area Requirements Equipment connected to the non-hazardous area terminals must not be supplied from, nor contain, a source of potential with respect to ground under normal or fault conditions exceeding 250 V RMS. Hazardous area equipment shall not have exposed any surface that operates at a temperature in excess of the ignition temperature of the specific gas, vapor, or dust. Refer to ATEX for ignition listings. Mains powered equipment connected to the non-hazardous area terminals must be isolated from the mains power supply by a double wound transformer, unless the applicable electrical code permits multiple grounding of the neutral lead. 38 PA/PG3000 Installation Manual 39 PA/PG3000 Installation Manual INSTRUMENT NOTES 40