Fire Control Panels - Tyco SimplexGrinnell

Fire Control Panels
UL, CSFM Listed; FM Approved;
MEA (NYC) Acceptance*
XA Loop Interface to the 4100ES or 4100U Fire
Alarm Control Panel, Module 4100-3115
Features
XA device loop,
Class B or Class A
Simplex IDNet™
addressable devices
®
Allows the Simplex 4100ES or 4100U to operate
as either an XA Loop Master Panel or an XA Loop
Data Gathering Panel
When operating as an XA loop Master Panel:
 Connects to up to 255 input devices and up to 255 output
devices on a single XA loop to monitor, supervise, and
control
 Monitoring status includes Normal, Trouble, or Alarm
 XA loop devices can be 4-wire if command output
functions are used, or 3-wire if used for monitoring only
 XA loop devices appear to the 4100ES/4100U similar to
IDNet™ addressable devices including custom labels
with up to 40 characters
When operating as an XA loop Data Gathering Panel:
 Communicates status and receives control from the XA
loop’s Autocall compatible Master Panel
 Control includes Acknowledge, Silence, Reset, and
device level commands
 4100ES/4100U operates as a stand-alone fire alarm
control panel for its connected devices and appliances
4100ES or 4100U panels equipped with Simplex
Network communications can send XA loop
device information to other Network nodes
XA
device
1
3
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:251
(non-high rise) and 7170-0026:250 (high rise) for allowable values and/or conditions
concerning material presented in this document. It is subject to re-examination, revision, and
possible cancellation. Accepted for use – City of New York Department of Buildings –
MEA35-93E. This product was not ULC listed as of document revision date. Additional
listings may be applicable; contact your local Simplex product supplier for the latest status.
Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety
Products Westminster.
6
SI M PL EX T I M E RECO RDER CO .
40 9 0 - 9 0 0 2
REL AY I AM
I NSTAL . I NSTR.
DATE CO DE:
4
7
5 74 - 1 84
8
1
XA
device
F IRE
PULL
ALARM
DOWN
4100-3115
XA Loop
Module
4100ES/4100U Fire Alarm
Control Panel (4100ES shown)
Description
System Flexibility. When a fire alarm system using
existing XA loop devices requires expansion, use of the
4100-3115 XA Loop Interface Module allows the
expansion to include the capabilities of the 4100ES or
4100U fire alarm control panel. This module allows the
host control panel to be selected to function as either the
XA loop master controller (head end) or as a Data
Gathering Panel as an intelligent device on the XA loop
reporting to a remote master controller.
Multiple XA Loop Interface Modules can be
installed in the 4100ES/4100U allowing a variety of
system expansion situations to be satisfied. The
4100ES/4100U accepts up to a total of 30 modules of this
type which also includes IDNet modules, MAPNET II®
modules, and VESDA® modules
On-Board LEDs are provided for service diagnostics to
indicate XA loop status, internal 4100ES/4100U
communications status, and supervision status when
functioning as a master controller for the XA loop.
For additional information, refer to Installation and
Programming Guide 579-513.
5
2
XA
device
4100ES/4100U XA Loop Interface Block Diagram
4100-3115 Specifications
Power Requirements
Voltage
Current
24 VDC from expansion bay
power supply if present; or wired
to AUX (+) and AUX ( -) from
Auxiliary 24 VDC in panel
570 mA @ 24 VDC
XA Loop Specification Reference
Maximum Resistance
Maximum Capacitance
Current
Voltage/Frequency
Maximum Addresses per Loop
100  per wire
1.5 µF wire-to-wire
1.5 µF wire-to-shield
500 mA
24 VAC, 250 Hz
255
General Specifications
Operating Temperature Range
Humidity Range
Mounting
Output Wiring Connections
32 F to 120 F (0 C to 49 C)
Up to 93% RH, non-condensing
@ 90° F (32° C)
4” x 10” (102 mm x 254 mm)
module requires two vertical
expansion bay blocks
On-board terminal blocks for field
wiring 18 to 12 AWG (0.82 mm2
to 3.31 mm2 )
S4100-0041-3
XA Loop Interface System Diagram, Master Panel Operation
XA
device
Optional connection to
Simplex Network loop
XA
device
Local notification appliances
XA device loop,
Class B or Class A;
3-wire or 4-wire
XA
device
FIRE
1
3
ALARM
5
2
6
SI M P LEX TI M E RE CO RDE R CO .
40 90- 900 2
RELAY I AM
I NSTAL. I NSTR. 57 4- 1 84
DATE CO DE:
4
PULL
7
DOWN
8
1
Local addressable devices
4100-3115 XA Loop
Interface Module
4100ES/4100U Fire Alarm
Control Panel (4100ES shown)
XA Loop Interface System Diagram, Data Gathering Panel Operation
XA
device
Optional connection to
Simplex Network loop
XA
device
AUTOCALL®
compatible
XA Panel
Local notification appliances
XA
device
FIRE
1
3
ALARM
5
2
6
S I M PL EX T I M E RE CO RDER CO .
4 090- 9 00 2
RELAY I AM
I NSTAL . I NSTR. 57 4- 184
DATE CO DE:
4
7
PULL
DOWN
8
1
Local addressable devices
4100-3115 XA Loop
Interface Module
4100ES/4100U Fire Alarm
Control Panel (4100ES shown)
Tyco is a registered trademark of Tyco International Services GmbH and is used under license. Simplex, the Simplex logo, IDNet, AUTOCALL, and MAPNET II are trademarks of
Tyco International Ltd. and its affiliates and are used under license. VESDA is a trademarks of Xtralis Pty Ltd.
Tyco Safety Products Westminster • Westminster, MA • 01441-0001 • USA
www.tycosafetyproducts-usa-wm.com
S4100-0041-3
© 2011 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.