S
System pro M compact S ystem
2
Miniature circuit breakers 00 Se pro
M
S200, S200P, S200U, S200UP ries
14
Description
Features
The S2 Series of miniature circuit breakers
offer a compact solution to protection
requirements. The S2 devices are current
limiting, DIN rail mounted and can offer a
good equivalent to fused systems.
The S2 is available with application-specific
trip characteristics to provide maximum
circuit protection. The breakers offer
thermal-magnetic trip protection according
to B, C, D, K and Z characteristics.
For the worldwide market, the breakers
carry UL, CSA, IEC, CE and many other
agency approvals and certifications.
• Current limiting
• Fast breaking time (2.5 – 3.5 msec)
• Unique bus connection system
• Wide range of accessories
• Available with variable depth handle
mechanism
• Optional Z curve for SCR protection
• CE certified and marked
• DIN rail or front panel mounting
• Finger safe terminals
• Multi-function terminals
• Suitable for reverse feed
• 480Y/277VAC and 500VDC versions
• UL489 Listed - branch circuit protective
device. UL file # E212323
• UL1077 Recognized - supplemental
protective device. UL file # E76126
ed
old
M
re nd
u
t
a
nia ers rs
i
d M reak ecto
e
t
rov uit B Pro
p
Ap Circ ntal
L
U se me
Ca pple
Su
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
14
M
o
pr ies
em Ser
st
Sy 200
S
14
General information
General information
Applications
Miniature circuit breakers (MCBs) are used throughout the world in all
types of electrical installations. ABB MCBs are approved for use by
Underwriters Laboratories in systems rated up to 600VAC/VDC. Devices
are also certified per CSA.
MCBs are approved per IEC-898 and VDE 0641, and certified under
IEC-947 and VDE 0660 standards for use in systems rated up to
690VAC.
MCBs can be applied to 16 2/3Hz – 400Hz and DC power systems.
Special direct current version MCBs include a permanent magnet for DC
fault current interruption. These "UC" versions are rated 250/500VDC
under UL1077/CSA 22.2 No. 235.
Continuous current ratings are as low as 0.2 amperes and up to 125
amperes maximum.
MCBs are of compact size and can be quickly mounted on standard
35mm DIN rail or can be front mounted by use of a front mounting kit.
MCBs include line and load side terminals for conductors from 18
through 4AWG (0.75 – 25mm2) for 63 amperes.
MCBs can also be connected via busbar conductors which can be
either upper or lower mounted for top feed or bottom feed. Dual
function terminals allow busbars to be connected with main incoming
line conductors without separate lugs.
MCBs can be used for equipment protection, in commercial appliances,
protection of control circuits against overcurrent faults, computer
equipment and other computer peripheral devices.
Accessories
Auxiliary devices can be added to the, S200 series MCBs:
• Shunt trips
• Auxiliary contacts
• Bell alarm contacts
• Aux/bell alarm contacts
• Undervoltage release
Accessory device modules can be field mounted to all above listed ABB
MCBs. Auxiliary contacts are also available for the S500 series MCB.
14
14.2
UL 489
S200U and S200UP MCBs are listed as molded case circuit breakers
for use as branch circuit protective devices. Miniature MCCBs and
accessories are listed under UL file E212323.
UL 1077
S200 and S200P MCBs are recognized as supplementary protectors
and are intended for use as overcurrent protection within an appliance
or other electrical equipment where branch circuit overcurrent
protection is already provided or not required. MCBs and accessories
are recognized under UL File E76126.
CSA C22.2
MCBs and accessories are certified under CSA C22.2 No. 235 per File
LR98793.
Tripping characteristics
Time-current curves
ABB miniature circuit breakers are available with different trip
characteristics, allowing for maximum system protection.
B Characteristic
Available with the S200 and S500 series has rated currents of 6 through
63 amperes in 10 steps. The "B" time-current curve is designed
primarily for use in cable protection applications. Instantaneous tripping
occurs between approximately 3 to 5 times rated current in 50/60Hz
systems. This quick trip curve maximizes protection of control circuits
under low short circuit fault levels that could damage control wiring.
C Characteristic
Available in the S200 and S500 series with rated currents up through 63
amperes and the S290 series with rated currents of 80, 100 and 125
amperes. The "C" time-current curve is designed for medium magnetic
start-up currents. Instantaneous tripping occurs between 5 and 10
times rated current in 50/60 Hz systems.
D Characteristic
The new magnetic trip action has an instantaneous trip between 10 and
20 times the breaker rating. Thus, the S200 and S500-D can be a good
protective solution for applications involving high in-rush transformers,
motors and other high inductive systems. It is also suitable for any
application where a high instantaneous trip point is desired.
K Characteristic
The "K" time-current characteristic considers high magnetic start-up
currents from motors, transformers and other equipment. Instantaneous
tripping occurs between 8 and 12 times rated current in 50/60Hz
systems. The "K" characteristic is available up through 63 amperes.
The "K" curve offers the best protection for the broadest range of
electrical systems. The higher magnetic trip settings maximizes
protection while allowing for higher in-rush currents during system startup. Available in S200P, S200U, S200UP and S500.
Z Characteristic
Also available up through 63 amperes, the "Z" characteristic offers
instantaneous tripping between 2 and 3 times rated current in 50/60Hz
systems. This trip characteristic is available in the S200P, S200U and
S200UP series with both the 480Y/277VAC and 250/500VDC ratings.
Many applications require a very low short circuit trip setting in order
to protect semiconductor or other sensitive devices and the "Z" trip
characteristic may provide maximum protection and service in these
applications.
Low Voltage Products & Systems
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
General information
Interruption ratings
Trip characteristics overview
Trip characteristics overview
Interruption ratings
Voltage
120 VAC
Rated interrupting
capacity
Rated
current
0.5
0.5
0.2
0.2
0.2
18kA
32 - 63A
26 - 45A
S500-B,C,D
S500-K
30kA
6 - 25A
0.15 - 25A
S500-B,C,D
S500-K
6kA
0.5 - 63A
0.5 - 63A
S200-B,C,D
S200-K
Single pole
Single pole
10kA
0.5
0.5
0.2
0.2
0.2
0.2
0.2
0.2
63A
63A
63A
63A
63A
63A
25A
25A
S200-B,C,D
S200-K
S200P-K,Z
S200P-K,Z
S200U-K,Z
S200U-K,Z
S200UP-K,Z
S200UP-K,Z
Multi pole
Multi pole
Single pole
Multi pole
Single pole
Multi pole
Single pole
Multi pole
18kA
32 - 63A
26 - 45A
S500-B,C,D
S500-K
30kA
6 - 25A
0.15 - 25A
S500-B,C,D
S500-K
6kA
0.5 - 63A
0.5 - 63A
S200-B,C,D
S200-K
10KA
0.2 - 63A
0.2 - 25A
S200P-K,Z
S200UP-K,Z
6kA
0.5 - 63A
0.5 - 63A
S200-B,C,D
S200-K
10KA
0.2 - 63A
0.2 - 25A
S200P-K,Z
S200UP-K,Z
60 VDC
10kA
0.5 - 63A
0.5 - 63A
S200-B,C,D
S200-K
Single pole
Single pole
125 VDC
10kA
0.5 - 63A
0.5 - 63A
0.2 - 63A
S200-B,C,D
S200-K
S280UC-K,Z
Multi pole
Multi pole
Single pole
250 VDC
4.5kA
0.2 - 63A
S280UC-K,Z
Single pole
500 VDC
4.5kA
0.2 - 63A
S280UC-K,Z
Multi pole
277 VAC
480Y/277 VAC
-
63A
63A
63A
63A
25A
Comment
10kA
240 VAC
-
MCB
type
S200-B,C,D
S200-K
S200P-K, Z
S200U-K, Z
S200UP-K, Z
Curve
Magnetic
characteristic 1
B
C
D
K
Z
3 - 5X
5 - 10X
10 - 20X
8 - 12X
2 - 3X
Thermal
characteristic
1.13
1.13
1.13
1.05
1.05
1.45X
1.45X
1.45X
1.20X
1.20X
Series
S200, S500
S200, S290, S500
S200, S500
S200, S500
S200
1 All values are relative to MCB's ampere rating.
Low Voltage Products & Systems
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
14
14.3
M
o
pr ies
em Ser
st
Sy 200
S
General information
Tripping curves
14
B
C
D
5000
5000
5000
1000
500
1000
500
1000
500
100
50
100
50
100
50
10
5
10
5
10
5
1
0.5
1
0.5
1
0.5
AC
0.1
0.05
AC
0.1
0.05
0.01
2
3
5
7 10
20 30
0.01
1
multiple of rated current
2
3
K
5000
1000
500
1000
500
100
50
100
50
10
5
10
5
1
0.5
1
0.5
seconds
5000
seconds
10
18 20 30
1
2
3
5
10
20 30
multiple of rated current
UC-K
10,000
AC
0.1
0.1
0.05
0.05
DC
DC
0.01
0.01
1
2
3
5
8 10 12
20 30
1
multiple of rated current
2
3
5
10
20 30
multiple of rated current
UC-Z
Z
10,000
5000
5000
1000
500
1000
500
100
50
100
50
10
5
10
5
1
0.5
1
0.5
seconds
10,000
seconds
5
multiple of rated current
10,000
AC
0.1
0.1
0.05
0.05
DC
DC
0.01
0.01
1
2
3
5
10
multiple of rated current
14.4
DC
DC
0.01
1
AC
0.1
0.05
DC
14
seconds
10,000
seconds
10,000
seconds
10,000
20 30
1
2
3
5
10
20 30
multiple of rated current
Low Voltage Products & Systems
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
General information
Construction details
Electro-magnetic protection
Tripping lever
Operating
mechanism
Upper terminal
Thermal protection-bimetal
Operator
14
Arc chamber
Space for
identification marker
Fixed contact
Moving contact
DIN rail holder
Lower terminal
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
M
o
pr ies
em Ser
st
Sy 200
S
S200
480Y/277 VAC
Supplemental protectors
14
B
UL 1077
CSA C22.2 No. 235
VDE 0641
IEC-898
Cable protection
Rated
current
Catalog
number
List
price
S201-B6
S201-B10
S201-B13
S201-B16
S201-B20
S201-B25
S201-B32
S201-B40
S201-B50
S201-B63
$ 36
36
36
36
38
38
40
42
48
56
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
6
10
13
16
20
25
32
40
50
63
S201-B, 1 pole
S202-B, 2 pole
S201-BNA, 1 P+N
A
10
4.5
14
List
price
Delivery
class
Sugg.
order
qty
S203-B6
S203-B10
S203-B13
S203-B16
S203-B20
S203-B25
S203-B32
S203-B40
S203-B50
S203-B63
$ 118
118
118
118
130
132
142
148
170
194
A
1
13.5
S203-B6NA
S203-B10NA
S203-B13NA
S203-B16NA
S203-B20NA
S203-B25NA
S203-B32NA
S203-B40NA
S203-B50NA
S203-B63NA
142
142
142
142
162
168
176
184
212
240
B
1
18.0
S204-B6
S204-B10
S204-B13
S204-B16
S204-B20
S204-B25
S204-B32
S204-B40
S204-B50
S204-B63
156
156
156
156
172
176
188
196
224
256
B
1
18.0
Wgt. oz.
(1 pc.)
6
10
13
16
20
25
32
40
50
63
3 pole + neutral
S201-B6NA
S201-B10NA
S201-B13NA
S201-B16NA
S201-B20NA
S201-B25NA
S201-B32NA
S201-B40NA
S201-B50NA
S201-B63NA
62
62
62
62
68
72
74
76
90
102
S202-B6
S202-B10
S202-B13
S202-B16
S202-B20
S202-B25
S202-B32
S202-B40
S202-B50
S202-B63
78
78
78
78
86
88
94
98
112
128
B
5
9.0
2 pole
6
10
13
16
20
25
32
40
50
63
Catalog
number
3 pole
1 pole + neutral
6
10
13
16
20
25
32
40
50
63
Rated
current
6
10
13
16
20
25
32
40
50
63
4 pole
A
5
9.0
6
10
13
16
20
25
32
40
50
63
S203-B, 3 pole
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
S204-B, 4 pole
S203-BNA, 3P+N
B
10,000
5000
1000
500
100
50
seconds
10
5
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
7 10
20 30
multiple of rated current
Discount schedule CB5
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
S200
480Y/277 VAC
Supplemental protectors
C
UL 1077
CSA C22.2 - NO. 235
VDE 0641
IEC-898
Cable & equipment protection
Rated
current
Catalog
number
List
price
S201-C0.5
S201-C1
S201-C1.6
S201-C2
S201-C3
S201-C4
S201-C6
S201-C8
S201-C10
S201-C13
S201-C16
S201-C20
S201-C25
S201-C32
S201-C40
S201-C50
S201-C63
$ 42
42
42
42
42
42
42
42
42
42
42
42
46
48
52
60
68
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S201-C, 1 pole
S202-C, 2 pole
S201-CNA, 1P+N
S203-C, 3 pole
A
10
4.5
S204-C, 4 pole
S203-CNA, 3P+N
C
10,000
5000
1000
500
84
84
84
84
84
84
84
84
84
84
84
84
88
90
96
112
130
S202-C0.5
S202-C1
S202-C1.6
S202-C2
S202-C3
S202-C4
S202-C6
S202-C8
S202-C10
S202-C13
S202-C16
S202-C20
S202-C25
S202-C32
S202-C40
S202-C50
S202-C63
96
96
96
96
96
96
96
96
96
96
96
96
106
106
116
136
152
B
5
9.0
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S203-C0.5
S203-C1
S203-C1.6
S203-C2
S203-C3
S203-C4
S203-C6
S203-C8
S203-C10
S203-C13
S203-C16
S203-C20
S203-C25
S203-C32
S203-C40
S203-C50
S203-C63
$ 138
138
138
138
138
138
138
138
138
138
138
138
156
158
174
200
228
A
1
13.5
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S203-C0.5NA
S203-C1NA
S203-C1.6NA
S203-C2NA
S203-C3NA
S203-C4NA
S203-C6NA
S203-C8NA
S203-C10NA
S203-C13NA
S203-C16NA
S203-C20NA
S203-C25NA
S203-C32NA
S203-C40NA
S203-C50NA
S203-C63NA
200
200
200
200
200
200
200
200
200
200
200
200
206
212
224
204
304
B
1
18.0
S204-C0.5
S204-C1
S204-C1.6
S204-C2
S204-C3
S204-C4
S204-C6
S204-C8
S204-C10
S204-C13
S204-C16
S204-C20
S204-C25
S204-C32
S204-C40
S204-C50
S204-C63
218
218
218
218
218
218
218
218
218
218
218
218
234
238
260
300
338
14
4 pole
A
5
9.0
100
50
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
B
1
18.0
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
10
5
seconds
List
price
3 pole + neutral
S201-C0.5NA
S201-C1NA
S201-C1.6NA
S201-C2NA
S201-C3NA
S201-C4NA
S201-C6NA
S201-C8NA
S201-C10NA
S201-C13NA
S201-C16NA
S201-C20NA
S201-C25NA
S201-C32NA
S201-C40NA
S201-C50NA
S201-C63NA
2 pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
Catalog
number
3 pole
1 pole + neutral
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
Rated
current
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
10
18 20 30
multiple of rated current
Discount schedule CB5
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
M
o
pr ies
em Ser
st
Sy 200
S
S200
480Y/277 VAC
Supplemental protectors
14
UL 1077
CSA C22.2
VDE 0641
IEC-898
Cable & equipment protection
D
Rated
current
Catalog
number
List
price
S201-D0.5
S201-D1
S201-D1.6
S201-D2
S201-D3
S201-D4
S201-D6
S201-D8
S201-D10
S201-D13
S201-D16
S201-D20
S201-D25
S201-D32
S201-D40
S201-D50
S201-D63
$ 42
42
42
42
42
42
42
42
42
42
42
42
46
48
52
60
68
S202-D0.5
S202-D1
S202-D1.6
S202-D2
S202-D3
S202-D4
S202-D6
S202-D8
S202-D10
S202-D13
S202-D16
S202-D20
S202-D25
S202-D32
S202-D40
S202-D50
S202-D63
96
96
96
96
96
96
96
96
96
96
96
96
106
106
116
136
152
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
S201-D, 1 pole
Catalog
number
List
price
S203-D0.5
S203-D1
S203-D1.6
S203-D2
S203-D3
S203-D4
S203-D6
S203-D8
S203-D10
S203-D13
S203-D16
S203-D20
S203-D25
S203-D32
S203-D40
S203-D50
S203-D63
$ 138
138
138
138
138
138
138
138
138
138
138
138
156
158
174
200
228
Delivery
class
Sugg.
order
qty
A
1
Wgt. oz.
(1 pc.)
3 pole
1 pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
Rated
current
A
10
4.5
A
5
9.0
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
13.5
2 pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S202-D, 2 pole
14
S203-D, 3 pole
D
10,000
5000
1000
500
100
50
seconds
10
5
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
10
20 30
multiple of rated current
Discount schedule CB5
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
S200
480Y/277 VAC
Supplemental protectors
K
UL 1077
CSA C22.2 - NO. 235
VDE 0641
IEC-898
Cable & equipment protection
Rated
current
Catalog
number
List
price
S201-K0.5
S201-K1
S201-K1.6
S201-K2
S201-K3
S201-K4
S201-K5
S201-K6
S201-K8
S201-K10
S201-K13
S201-K15
S201-K16
S201-K20
S201-K25
S201-K30
S201-K32
S201-K40
S201-K50
S201-K60
S201-K63
$ 42
42
42
42
42
42
42
42
42
42
42
42
42
42
46
48
48
52
60
68
68
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
S201-K, 1 pole
S202-K, 2 pole
S201-KNA, 1P+N
A
10
4.5
S203-K, 3 pole
S201-K0.5NA
S201-K1NA
S201-K1.6NA
S201-K2NA
S201-K3NA
S201-K4NA
S201-K6NA
S201-K8NA
S201-K10NA
S201-K13NA
S201-K16NA
S201-K20NA
S201-K25NA
S201-K32NA
S201-K40NA
S201-K50NA
S201-K63NA
84
84
84
84
84
84
84
84
84
84
84
84
88
90
96
112
130
S202-K0.5
S202-K1
S202-K1.6
S202-K2
S202-K3
S202-K4
S202-K5
S202-K6
S202-K8
S202-K10
S202-K13
S202-K15
S202-K16
S202-K20
S202-K25
S202-K30
S202-K32
S202-K40
S202-K50
S202-K60
S202-K63
96
96
96
96
96
96
96
96
96
96
96
96
96
96
106
106
106
116
136
152
152
B
5
9.0
S204-K, 4 pole
S203-KNA, 3P+N
K
10,000
5000
1000
500
100
50
seconds
10
5
1
0.5
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
0.5
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
30
32
40
50
60
63
S203-K0.5
S203-K1
S203-K1.6
S203-K2
S203-K3
S203-K4
S203-K5
S203-K6
S203-K8
S203-K10
S203-K13
S203-K15
S203-K16
S203-K20
S203-K25
S203-K30
S203-K32
S203-K40
S203-K50
S203-K60
S203-K63
$ 138
138
138
138
138
138
138
138
138
138
138
138
138
138
156
158
158
174
200
228
228
A
1
13.5
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S203-K0.5NA
S203-K1NA
S203-K1.6NA
S203-K2NA
S203-K3NA
S203-K4NA
S203-K6NA
S203-K8NA
S203-K10NA
S203-K13NA
S203-K16NA
S203-K20NA
S203-K25NA
S203-K32NA
S203-K40NA
S203-K50NA
S203-K63NA
200
200
200
200
200
200
200
200
200
200
200
200
206
212
224
264
304
B
1
18.0
S204-K0.5
S204-K1
S204-K1.6
S204-K2
S204-K3
S204-K4
S204-K6
S204-K8
S204-K10
S204-K13
S204-K16
S204-K20
S204-K25
S204-K32
S204-K40
S204-K50
S204-K63
218
218
218
218
218
218
218
218
218
218
218
218
234
238
260
300
338
14
4 pole
2 pole
0.5
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
30
32
40
50
60
63
List
price
3 pole + neutral
1 pole + neutral
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
Catalog
number
3 pole
1 pole
0.5
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
30
32
40
50
60
63
Rated
current
A
5
9.0
AC
0.1
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
B
1
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
0.05
DC
0.01
1
2
3
5
8 10 12
18.0
20 30
multiple of rated current
Discount schedule CB5
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
M
o
pr ies
em Ser
st
Sy 200
S
S200P
480Y/277 VAC
Supplemental protectors
14
K
UL 1077
CSA C22.2 - NO. 235
VDE 0660
Cable & equipment protection
Rated
current
Catalog
number
List
price
S201P-K0.2
S201P-K0.3
S201P-K0.5
S201P-K0.75
S201P-K1
S201P-K1.6
S201P-K2
S201P-K3
S201P-K4
S201P-K6
S201P-K8
S201P-K10
S201P-K13
S201P-K16
S201P-K20
S201P-K25
S201P-K32
S201P-K40
S201P-K50
S201P-K63
$ 54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
56
58
64
70
80
S202P-K0.2
S202P-K0.3
S202P-K0.5
S202P-K0.75
S202P-K1
S202P-K1.6
S202P-K2
S202P-K3
S202P-K4
S202P-K6
S202P-K8
S202P-K10
S202P-K13
S202P-K16
S202P-K20
S202P-K25
S202P-K32
S202P-K40
S202P-K50
S202P-K63
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
130
134
134
162
182
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S201P-K, 1 pole
Rated
current
Catalog
number
List
price
S203P-K0.2
S203P-K0.3
S203P-K0.5
S203P-K0.75
S203P-K1
S203P-K1.6
S203P-K2
S203P-K3
S203P-K4
S203P-K6
S203P-K8
S203P-K10
S203P-K13
S203P-K16
S203P-K20
S203P-K25
S203P-K32
S203P-K40
S203P-K50
S203P-K63
$ 194
194
194
194
194
194
194
194
194
194
194
194
194
194
194
196
200
214
246
280
Delivery
class
Sugg.
order
qty
A
1
Wgt. oz.
(1 pc.)
3 pole
A
10
4.6
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
13.9
2 pole
S202P-K, 2 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
14
S203P-K, 3 pole
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
A
5
9.2
K
10,000
5000
1000
500
100
50
seconds
10
5
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
8 10 12
20 30
multiple of rated current
Discount schedule CB7
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
S280 (W)
480Y/277 VAC
Supplemental protectors
K
UL 1077
CSA C22.2 - NO. 235
VDE 0660
Cable & equipment protection
Rated
current
Catalog
number
List
price
S281-K0.2W
S281-K0.3W
S281-K0.5W
S281-K0.75W
S281-K1W
S281-K1.6W
S281-K2W
S281-K3W
S281-K4W
S281-K6W
S281-K8W
S281-K10W
S281-K13W
S281-K16W
S281-K20W
S281-K25W
S281-K32W
S281-K40W
S281-K50W
S281-K63W
$ 54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
56
58
64
70
80
S282-K0.2W
S282-K0.3W
S282-K0.5W
S282-K0.75W
S282-K1W
S282-K1.6W
S282-K2W
S282-K3W
S282-K4W
S282-K6W
S282-K8W
S282-K10W
S282-K13W
S282-K16W
S282-K20W
S282-K25W
S282-K32W
S282-K40W
S282-K50W
S282-K63W
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
130
134
134
162
182
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S281-KW, 1 pole
Catalog
number
List
price
S283-K0.2W
S283-K0.3W
S283-K0.5W
S283-K0.75W
S283-K1W
S283-K1.6W
S283-K2W
S283-K3W
S283-K4W
S283-K6W
S283-K8W
S283-K10W
S283-K13W
S283-K16W
S283-K20W
S283-K25W
S283-K32W
S283-K40W
S283-K50W
S283-K63W
$ 194
194
194
194
194
194
194
194
194
194
194
194
194
194
194
196
200
214
246
280
Delivery
class
Sugg.
order
qty
B
3
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S283-KW, 3 pole
3 pole
B
10
4.6
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
Delivery Class
B
5
9.2
14
g
on
t
g
rin tors
h
c
t
wi nne
e
us al co
r
Fo min
ter
10,000
5000
1000
500
100
50
10
5
1
0.5
AC
0.1
0.05
DC
0.01
2
3
5
13.9
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
ue
K
1
Wgt. oz.
(1 pc.)
2 pole
S282-KW, 2 pole
seconds
Rated
current
8 10 12
20 30
multiple of rated current
Discount schedule CB7
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
M
o
pr ies
em Ser
st
Sy 200
S
S280UC
500 VDC
Supplemental protectors
14
K
UL 1077
VDE 0660
CSA 22.2
No. 235
Cable and Equipment Protection
Rated
current
Catalog
number
List
price
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
S281UC-K, 1 pole
Rated
current
Catalog
number
List
price
S283UC-K0.2
S283UC-K0.3
S283UC-K0.5
S283UC-K0.75
S283UC-K1
S283UC-K1.6
S283UC-K2
S283UC-K3
S283UC-K4
S283UC-K6
S283UC-K8
S283UC-K10
S283UC-K16
S283UC-K20
S283UC-K25
S283UC-K32
S283UC-K40
S283UC-K50
S283UC-K63
$ 370
370
370
370
370
370
370
370
370
370
370
370
370
370
382
408
448
472
534
Delivery
class
Sugg.
order
qty
B
3
Wgt. oz.
(1 pc.)
3 pole
S281UC-K0.2
S281UC-K0.3
S281UC-K0.5
S281UC-K0.75
S281UC-K1
S281UC-K1.6
S281UC-K2
S281UC-K3
S281UC-K4
S281UC-K6
S281UC-K8
S281UC-K10
S281UC-K16
S281UC-K20
S281UC-K25
S281UC-K32
S281UC-K40
S281UC-K50
S281UC-K63
$ 104
104
104
104
104
104
104
104
104
104
104
104
104
104
108
110
116
136
152
S282UC-K0.2
S282UC-K0.3
S282UC-K0.5
S282UC-K0.75
S282UC-K1
S282UC-K1.6
S282UC-K2
S282UC-K3
S282UC-K4
S282UC-K6
S282UC-K8
S282UC-K10
S282UC-K16
S282UC-K20
S282UC-K25
S282UC-K32
S282UC-K40
S282UC-K50
S282UC-K63
242
242
242
242
242
242
242
242
242
242
242
242
242
242
248
256
266
312
348
B
10
4.6
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
13.9
2 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
S282UC-K, 2 pole
14
S283UC-K, 3 pole
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
B
5
9.2
Direct current applications
The S280UC differs from standard miniature circuit breakers in that the UC versions include a permanent
magnet which aids in the extinguishing of the arc during medium and high level faults. It is necessary to
observe the correct polarity and current direction when connecting the UC breakers. Two examples of correct
connection are shown below.
Maximum voltage between leads
250VDC
UC-K
10,000
500VDC
1000
500
L-
L+
100
50
10
5
seconds
Two Pole
LS282UC
Single Pole
S281UC
5000
1
0.5
-1
-1 +2
+2
+2
0.1
LOAD
+
0.05
DC
0.01
1
2
3
5
10
multiple of rated current
20 30
L-1
L+
L+
3+
3+ 4-
4LOAD
+
LOAD
+
Termination points are marked on all UC type MCBs, points one (1) and four (4) are negative and points two
(2) and three (3) are positive. Four pole breakers are also available for voltage reversal applications.
Discount schedule CB7
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
S200P & S280UC
480Y/277 VAC & 500 VDC
Supplemental protectors
UL 1077
VDE 0660
CSA 22.2
No. 235
Fast trip characteristic
Z
480Y/277 VAC
Rated
current
500 VDC
Catalog
number
List
price
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
S201P-Z, 1 pole
S201P-Z0.5
S201P-Z1
S201P-Z1.6
S201P-Z2
S201P-Z3
S201P-Z4
S201P-Z6
S201P-Z8
S201P-Z10
S201P-Z16
S201P-Z20
S201P-Z25
S201P-Z32
S201P-Z40
S201P-Z50
S201P-Z63
$ 70
70
70
70
70
70
70
70
70
70
70
70
74
78
88
100
S202P-Z0.5
S202P-Z1
S202P-Z1.6
S202P-Z2
S202P-Z3
S202P-Z4
S202P-Z6
S202P-Z8
S202P-Z10
S202P-Z16
S202P-Z20
S202P-Z25
S202P-Z32
S202P-Z40
S202P-Z50
S202P-Z63
162
162
162
162
162
162
162
162
162
162
162
170
170
176
206
232
S203P-Z0.5
S203P-Z1
S203P-Z1.6
S203P-Z2
S203P-Z3
S203P-Z4
S203P-Z6
S203P-Z8
S203P-Z10
S203P-Z16
S203P-Z20
S203P-Z25
S203P-Z32
S203P-Z40
S203P-Z50
S203P-Z63
244
244
244
244
244
244
244
244
244
244
244
248
254
266
306
344
B
10
4.5
S202P-Z, 2 pole
B
5
9.2
S203P-Z, 3 pole
Z
Sugg.
order
qty
B
10
4.6
B
5
9.2
10,000
5000
5000
1000
500
1000
500
100
50
100
50
10
5
10
5
seconds
1
0.5
AC
0.1
0.05
0.5
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
S281UC-Z0.5
S281UC-Z1
S281UC-Z1.6
S281UC-Z2
S281UC-Z3
S281UC-Z4
S281UC-Z6
S281UC-Z8
S281UC-Z10
S281UC-Z16
S281UC-Z20
S281UC-Z25
S281UC-Z32
S281UC-Z40
S281UC-Z50
S281UC-Z63
$ 168
168
168
168
168
168
168
168
168
168
168
170
176
188
216
242
0.5
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
S282UC-Z0.5
S282UC-Z1
S282UC-Z1.6
S282UC-Z2
S282UC-Z3
S282UC-Z4
S282UC-Z6
S282UC-Z8
S282UC-Z10
S282UC-Z16
S282UC-Z20
S282UC-Z25
S282UC-Z32
S282UC-Z40
S282UC-Z50
S282UC-Z63
390
390
390
390
390
390
390
390
390
390
390
398
410
426
498
558
B
1
13.9
0.5
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
S283UC-Z0.5
S283UC-Z1
S283UC-Z1.6
S283UC-Z2
S283UC-Z3
S283UC-Z4
S283UC-Z6
S283UC-Z8
S283UC-Z10
S283UC-Z16
S283UC-Z20
S283UC-Z25
S283UC-Z32
S283UC-Z40
S283UC-Z50
S283UC-Z63
594
594
594
594
594
594
594
594
594
594
594
603
612
657
756
855
14
B
3
Delivery Class
1
0.5
0.1
DC
0.01
0.01
2
3
5
13.9
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
0.05
DC
1
Wgt. oz.
(1 pc.)
UC-Z
10,000
seconds
Delivery
class
3 pole
3 pole
0.5
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
List
price
2 pole
2 pole
0.5
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
Catalog
number
1 pole
1 pole
0.5
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
Rated
current
10
multiple of rated current
20 30
1
2
3
5
10
20 30
multiple of rated current
Discount schedule CB7
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
M
o
pr ies
em Ser
st
Sy 200
S
S200U
240 VAC
Miniature MCCBs
14
K
UL 489
CSA C22.2 - NO. 5
VDE 0660
Cable & equipment protection
Rated
current
Catalog
number
List
price
S201U-K0.2
S201U-K0.3
S201U-K0.5
S201U-K0.75
S201U-K1
S201U-K1.6
S201U-K2
S201U-K3
S201U-K4
S201U-K5
S201U-K6
S201U-K8
S201U-K10
S201U-K13
S201U-K15
S201U-K16
S201U-K20
S201U-K25
S201U-K30
S201U-K32
S201U-K40
S201U-K50
S201U-K60
S201U-K63
$ 54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
56
58
58
64
70
80
80
S202U-K0.2
S202U-K0.3
S202U-K0.5
S202U-K0.75
S202U-K1
S202U-K1.6
S202U-K2
S202U-K3
S202U-K4
S202U-K5
S202U-K6
S202U-K8
S202U-K10
S202U-K13
S202U-K15
S202U-K16
S202U-K20
S202U-K25
S202U-K30
S202U-K32
S202U-K40
S202U-K50
S202U-K60
S202U-K63
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
130
134
134
134
162
182
182
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
30
32
40
50
60
63
S201U-K, 1 pole
S202U-K, 2 pole
14
S203U-K, 3 pole
S204U-K, 4 pole
K
Catalog
number
List
price
S203U-K0.2
S203U-K0.3
S203U-K0.5
S203U-K0.75
S203U-K1
S203U-K1.6
S203U-K2
S203U-K3
S203U-K4
S203U-K5
S203U-K6
S203U-K8
S203U-K10
S203U-K13
S203U-K15
S203U-K16
S203U-K20
S203U-K25
S203U-K30
S203U-K32
S203U-K40
S203U-K50
S203U-K60
S203U-K63
$ 194
194
194
194
194
194
194
194
194
194
194
194
194
194
194
194
194
196
200
200
214
246
280
280
S204U-K0.2
S204U-K0.3
S204U-K0.5
S204U-K0.75
S204U-K1
S204U-K1.6
S204U-K2
S204U-K3
S204U-K4
S204U-K5
S204U-K6
S204U-K8
S204U-K10
S204U-K13
S204U-K15
S204U-K16
S204U-K20
S204U-K25
S204U-K30
S204U-K32
S204U-K40
S204U-K50
S204U-K60
S204U-K63
265
265
265
265
265
265
265
265
265
265
265
265
265
265
265
265
265
275
285
285
314
343
392
392
Delivery
class
Sugg.
order
qty
A
1
13.9
B
1
18.0
Wgt. oz.
(1 pc.)
3 pole
A
10
4.6
2 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
30
32
40
50
60
63
Rated
current
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
30
32
40
50
60
63
4 pole
A
5
9.2
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
30
32
40
50
60
63
10,000
5000
Delivery Class
1000
500
h
nc e
a
r
c
s b devi
a
e
ed
ist tectiv
l
9
48 t pro
L
U cui
cir
100
50
seconds
10
5
1
0.5
AC
0.1
0.05
DC
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
0.01
1
2
3
5
8 10 12
20 30
multiple of rated current
Discount schedule CB12
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
S200U
240 VAC
Miniature MCCBs
Z
UL 489
CSA C22.2 - NO. 5
VDE 0660
Cable & equipment protection
Rated
current
Catalog
number
List
price
S201U-Z0.5
S201U-Z0.75
S201U-Z1
S201U-Z1.6
S201U-Z2
S201U-Z3
S201U-Z4
S201U-Z5
S201U-Z6
S201U-Z8
S201U-Z10
S201U-Z15
S201U-Z16
S201U-Z20
S201U-Z25
S201U-Z30
S201U-Z32
S201U-Z40
S201U-Z50
S201U-Z60
S201U-Z63
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
74
74
78
88
100
100
S202U-Z0.5
S202U-Z0.75
S202U-Z1
S202U-Z1.6
S202U-Z2
S202U-Z3
S202U-Z4
S202U-Z5
S202U-Z6
S202U-Z8
S202U-Z10
S202U-Z15
S202U-Z16
S202U-Z20
S202U-Z25
S202U-Z30
S202U-Z32
S202U-Z40
S202U-Z50
S202U-Z60
S202U-Z63
162
162
162
162
162
162
162
162
162
162
162
162
162
162
170
170
170
176
206
232
232
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
30
32
40
50
60
63
S201U-Z, 1 pole
S202U-Z, 2 pole
S203U-Z, 3 pole
Catalog
number
List
price
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
3 pole
A
10
4.6
2 pole
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
30
32
40
50
60
63
Rated
current
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
30
32
40
50
60
63
S203U-Z0.5
S203U-Z0.75
S203U-Z1
S203U-Z1.6
S203U-Z2
S203U-Z3
S203U-Z4
S203U-Z5
S203U-Z6
S203U-Z8
S203U-Z10
S203U-Z15
S203U-Z16
S203U-Z20
S203U-Z25
S203U-Z30
S203U-Z32
S203U-Z40
S203U-Z50
S203U-Z60
S203U-Z63
244
244
244
244
244
244
244
244
244
244
244
244
244
244
248
254
254
266
306
344
344
A
1
13.9
S204U-Z0.5
S204U-Z0.75
S204U-Z1
S204U-Z1.6
S204U-Z2
S204U-Z3
S204U-Z4
S204U-Z5
S204U-Z6
S204U-Z8
S204U-Z10
S204U-Z15
S204U-Z16
S204U-Z20
S204U-Z25
S204U-Z30
S204U-Z32
S204U-Z40
S204U-Z50
S204U-Z60
S204U-Z63
343
343
343
343
343
343
343
343
343
343
343
343
343
343
343
363
363
382
431
490
490
B
1
18.0
4 pole
A
5
9.2
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
30
32
40
50
60
63
Delivery Class
S204U-Z, 4 pole
h
nc e
a
r
c
s b devi
a
e
ed
ist tectiv
l
9
48 t pro
L
U cui
cir
Z
10,000
5000
1000
500
100
50
seconds
10
5
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
10
20 30
multiple of rated current
Discount schedule CB12
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
14
M
o
pr ies
em Ser
st
Sy 200
S
S200UP
480Y/277 VAC
Miniature MCCBs
14
K
UL 489
CSA C22.2 - NO. 5
VDE 0660
Cable & equipment protection
Rated
current
Catalog
number
List
price
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
S201UP-K, 1 pole
S202UP-K, 2 pole
14
S203UP-K, 3 pole
Catalog
number
List
price
Delivery
class
Sugg.
order
qty
A
1
13.9
B
1
18.0
Wgt. oz.
(1 pc.)
3 pole
S201UP-K0.2
S201UP-K0.3
S201UP-K0.5
S201UP-K0.75
S201UP-K1
S201UP-K1.6
S201UP-K2
S201UP-K3
S201UP-K4
S201UP-K5
S201UP-K6
S201UP-K8
S201UP-K10
S201UP-K13
S201UP-K15
S201UP-K16
S201UP-K20
S201UP-K25
$ 90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
S202UP-K0.2
S202UP-K0.3
S202UP-K0.5
S202UP-K0.75
S202UP-K1
S202UP-K1.6
S202UP-K2
S202UP-K3
S202UP-K4
S202UP-K5
S202UP-K6
S202UP-K8
S202UP-K10
S202UP-K13
S202UP-K15
S202UP-K16
S202UP-K20
S202UP-K25
210
210
210
210
210
210
210
210
210
210
210
210
210
210
210
210
210
210
A
10
4.6
2 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
Rated
current
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
S203UP-K0.2
S203UP-K0.3
S203UP-K0.5
S203UP-K0.75
S203UP-K1
S203UP-K1.6
S203UP-K2
S203UP-K3
S203UP-K4
S203UP-K5
S203UP-K6
S203UP-K8
S203UP-K10
S203UP-K13
S203UP-K15
S203UP-K16
S203UP-K20
S203UP-K25
$ 320
320
320
320
320
320
320
320
320
320
320
320
320
320
320
320
320
320
S204UP-K0.2
S204UP-K0.3
S204UP-K0.5
S204UP-K0.75
S204UP-K1
S204UP-K1.6
S204UP-K2
S204UP-K3
S204UP-K4
S204UP-K5
S204UP-K6
S204UP-K8
S204UP-K10
S204UP-K13
S204UP-K15
S204UP-K16
S204UP-K20
S204UP-K25
440
440
440
440
440
440
440
440
440
440
440
440
440
440
440
440
440
440
4 pole
A
5
9.2
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
Delivery Class
h
nc e
a
r
c
s b devi
a
e
ed
ist tectiv
l
9
48 t pro
L
U cui
cir
S204UP-K, 4 pole
K
10,000
5000
1000
500
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
100
50
seconds
10
5
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
8 10 12
20 30
multiple of rated current
Discount schedule CB17
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
S200UP
480Y/277 VAC
Miniature MCCBs
Z
UL 489
CSA C22.2 - NO. 5
VDE 0660
Cable & equipment protection
Rated
current
Catalog
number
List
price
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
S201UP-Z, 1 pole
S202UP-Z, 2 pole
Catalog
number
List
price
Delivery
class
Sugg.
order
qty
A
1
13.9
B
1
18.0
Wgt. oz.
(1 pc.)
3 pole
S201UP-Z0.5
S201UP-Z0.75
S201UP-Z1
S201UP-Z1.6
S201UP-Z2
S201UP-Z3
S201UP-Z4
S201UP-Z5
S201UP-Z6
S201UP-Z8
S201UP-Z10
S201UP-Z15
S201UP-Z16
S201UP-Z20
S201UP-Z25
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
S202UP-Z0.5
S202UP-Z0.75
S202UP-Z1
S202UP-Z1.6
S202UP-Z2
S202UP-Z3
S202UP-Z4
S202UP-Z5
S202UP-Z6
S202UP-Z8
S202UP-Z10
S202UP-Z15
S202UP-Z16
S202UP-Z20
S202UP-Z25
270
270
270
270
270
270
270
270
270
270
270
270
270
270
270
A
10
4.6
2 pole
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
Rated
current
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
S203UP-Z0.5
S203UP-Z0.75
S203UP-Z1
S203UP-Z1.6
S203UP-Z2
S203UP-Z3
S203UP-Z4
S203UP-Z5
S203UP-Z6
S203UP-Z8
S203UP-Z10
S203UP-Z15
S203UP-Z16
S203UP-Z20
S203UP-Z25
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
S204UP-Z0.5
S204UP-Z0.75
S204UP-Z1
S204UP-Z1.6
S204UP-Z2
S204UP-Z3
S204UP-Z4
S204UP-Z5
S204UP-Z6
S204UP-Z8
S204UP-Z10
S204UP-Z15
S204UP-Z16
S204UP-Z20
S204UP-Z25
564
564
564
564
564
564
564
564
564
564
564
564
564
564
564
4 pole
A
5
9.2
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
Delivery Class
S203UP-Z, 3 pole
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
ch
n
a
br evice
s
d a ive d
e
t
t
is
9 l rotec
8
4
p
UL cuit
cir
S204UP-Z, 4 pole
Z
10,000
5000
1000
500
100
50
seconds
10
5
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
10
20 30
multiple of rated current
Discount schedule CB17
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
14
M
o
pr ies
em Ser
st
Sy 200
S
S290
480Y/277 VAC
14
VDE 0660
Cable and equipment protection
C
480 VAC
Rated
current
List
price
Delivery
class
Sugg.
order
qty
S291-C80
S291-C100
S291-C125
$ 138
144
192
B
6
9.2
S292-C80
S292-C100
S292-C125
340
364
568
B
3
18.4
S293-C80
S293-C100
S293-C125
536
548
732
B
2
27.6
S294-C80
S294-C100
S294-C125
740
756
948
B
1
36.8
72
B
1
1.75
112
B
1
1.75
144
B
1
6.2
B
1
6.2
Catalog
number
Wgt. oz.
(1 pc.)
1 pole
80
100
125
2 pole
80
100
125
S291-C80
3 pole
80
100
125
4 pole
80
100
125
Auxiliary contact
S290-H11
S290-H11
Bell alarm
S290-S
Shunt trip
S290-A1
For field mounting, left side, 110V – 415VAC
S290-A2
144
For field mounting, left side, 24 – 48VDC
14
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
C
10,000
5000
1000
500
100
50
seconds
10
5
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
10
18 20 30
multiple of rated current
Discount schedule CB12
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
Accessories
Busbars
0HASE
Amp
rating
Number
of
poles
Busbar
length
(mm)
End cap
catalog
number
S200 &
S200P 1
63
80
60
60
988
988
–
–
PS1/60
PS1/60/16
S200U &
S200UP
23
80
6
12
18
108
216
324
–
–
–
PS1/6/16BP
PS1/12/16BP
PS1/18/16BP
For
use on:
,
Catalog
number
List
price
Delivery
class
Suggested
Weight
order qty.
(ozs)
quantity
$ 36
46
A
1
9
14
30
60
90
B
1
1.4
2.9
4.3
,
0HASE
Amp
rating
For
use on:
,
,
Number Busbar
of
length
poles
(mm)
End cap
catalog
number
Catalog
number
List
price
Delivery
class
Suggested
order qty.
quantity
A
1
B
1
1.8
3.7
5.5
List
price
Delivery
class
Suggested
order qty.
quantity
Weight
(ozs)
$ 130
176
A
1
12
20
44
88
132
B
1
2
4
6
S200 &
S200P 1
63
80
58
58
1035
1035
PS-ENDSP
PS-ENDSP
PS2/58SP
PS2/58/16SP
$ 122
152
S200U &
S200UP
23
80
6
12
18
108
216
324
–
–
–
PS2/6/16BP
PS2/12/16BP
PS2/18/16BP
40
80
120
Weight
(ozs)
11
18
, , , ,
0HASE
,
,
,
For
use on:
Amp Number Busbar
of
length
rating
poles
(mm)
S200 &
S200P 1
63
80
60
60
1065
1065
S200U &
S200UP
23
80
6
12
18
108
216
324
End cap
catalog
number
Catalog
number
PS-ENDSP PS3/60SP
PS-ENDSP PS3/60/16SP
–
–
–
PS3/6/16BP
PS3/12/16BP
PS3/18/16BP
End cap
catalog
number
Catalog
number
, , , , , ,
0HASE
For
use on:
S200 &
S200P
,
,
,
Amp Number Busbar
of
length
rating
poles
(mm)
80
60
1056
PS-END1SP PS4/60/16SP
List
price
$ 236
Delivery
class
Suggested
order qty.
quantity
Weight
(ozs)
B
1
22
Delivery Class
,
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
, , , , , , , ,
NOTE
ALL BUS BARS MAY BE CENTER FED IN
ORDER TO DOUBLE THE AMPACITY RATING
NOTE
BUS BARS MAY BE USED ON LINE OR LOAD
SIDE OF MCBS
1 UL Approved for use on UL1077 miniature circuit breakers. UL File #E76126
2 UL approved for use on UL 489 miniature circuit breakers. UL File # E250145
3 UL 489 bus bars may not be cut.
Low Voltage Products & Systems
Discount schedule CB8
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
14.19
14
M
o
pr ies
em Ser
st
Sy 200
S
Accessories
Busbars
14
1 Phase with 1 auxiliary
For
use on:
Amp
rating
Number
of
poles
Busbar
length
(mm)
End cap
catalog
number
S200 &
S200P
63
80
38
38
1044
1044
—
—
PS1/38H
PS1/38/16H
Amp
rating
Number
of
poles
Busbar
length
(mm)
End cap
catalog
number
Catalog
number
48
1065
PS-ENDSP
Catalog
number
List
price
$ 50
56
Delivery
class
Suggested
order qty.
quantity
Weight
(ozs)
B
1
7.4
10.1
Delivery
class
Suggested
order qty.
quantity
Weight
(ozs)
L1
L1
L1
L1....
2 Phase with 1 auxillary
For
use on:
S200 &
S200P
L1
L1 L2
L1 L2
80
List
price
PS2/48/16SP $ 174
B
1
23.3
Delivery
class
Suggested
order qty.
quantity
Weight
(ozs)
B
1
22.6
Delivery
class
Suggested
order qty.
quantity
Weight
(ozs)
B
1
30.8
L2
L1 L2....
3 Phase with 1 auxillary
For
use on:
S200 &
S200P
L1
L2
14
L1 L2 L3
Amp
rating
Number
of
poles
Busbar
length
(mm)
80
39
980
Amp
rating
Number
of
poles
Busbar
length
(mm)
58
1048
End cap
catalog
number
Catalog
number
List
price
PS-ENDSP PS3/39/16SP $ 158
L3
L1 L2 L3....
0HASE.FORUSEWITHPOLE-#"gS
ONPHASE7SYSTEM
For
use on:
S200 &
S200P
80
End cap
catalog
number
Catalog
number
List
price
PS-END1SP PS4/58/16NSP $ 238
Insulated busbar assembly contains 4 separate circuits for use with 1+N or 2 pole MCBs.
.
,
,
,
Delivery Class
, .
, .
, .
, .
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
,
NOTE
ALL BUS BARS MAY BE CENTER FED IN
ORDER TO DOUBLE THE AMPACITY RATING
NOTE
BUS BARS MAY BE USED ON LINE OR LOAD
SIDE OF MCBS
Discount schedule CB8
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
Accessories
Electrical
accessories
For
use on:
Catalog
number
S200 &
S200P
S2C-H6R
S200U
S200UP
S2C-H6RU
List
price
Delivery
class
Suggested
order quantities
Wgt. oz.
(1 pc.)
Auxiliary contacts
For field mounting: right side
Form C 1 NO / 1 NC
$ 36
S2C-H6R
A
1
1.4
The auxiliary contacts will signal whether the breaker is in the ON or OFF position. The contacts are rated 2A/277 VAC and 1.5A/125 VDC.
Minimum operating voltage is 24 VAC/VDC.
Wire size: 18 AWG to 16 AWG.
Bell alarm
S200 &
S200P
S2C-S/H6R
For field mounting, right side
48
S200U
S200UP
A
1
1.4
S2C-S6RU
The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically the contacts would be connected to an alarm
or bell to signal the operator that an overcurrent trip has occured. The bell alarm also includes a test button for testing the alarm contacts without
opening the breaker. The contact is rated 2A/277 VAC and 1.5A/125 VDC. Minimum operating voltage is 24 VAC/VDC.
S2C-S/H6R
* Combination bell alarm/auxiliary contact
Shunt trip
For field mounting, right side
A1: 12-60 VAC (12-60VDC)
A2: 110-415 VAC (110-250 VDC)
S200 &
S200P
S2C-A1
S2C-A2
138
A
1
5.2
S200U & S2C-A1U
S200UP S2C-A2U
For remote tripping of breaker, a shunt trip device can be added to the MCB. The solenoid device opens the breaker after control voltage is
applied. Shunt trips are available for on control system voltage (12-415 VAC/VDC).
S2C-A_
Undervoltage release
For field mounting, right side
12 VDC
24 VAC/VDC
48 VAC/VDC
110 VAC/VDC
220 VAC/VDC
415 VAC
S200 &
S200P
S2C-UA12
S2C-UA24
S2C-UA48
S2C-UA110
S2C-UA230
S2C-UA400
216
A
1
5.2
When control voltage drops below approximately 50% of rated voltage, the UVR opens the breaker. The breaker can not be operated unless
proper control voltage is first applied to the UVR coil. Similar in size and mounting to the shunt trip accessory.
Factory mounting
S2C-UA_
All accessories may be easily mounted in the field. For factory mounting of any accessory devices, add $30
list to total price per breaker. To create complete catalog number, take suffix of accessory device following
“S2C-” and add suffix to end of breaker part number. Multiple suffixes must be added in alphabetical order.
Example: S202-K20A1
$ 264
S202-K20A2H6R
$ 300
(2 pole, 20A breaker with type A1 shunt trip) S202-K20 @ $96 + S2C-A1
@ $138 + factory mounting @ $30 = $264
(2 pole, 20A breaker with type A2 shunt trip and H6R aux. contacts) S202K20 @ $96 + S2C-A1 @ $138 + S2C-H6R @ $36 + factory mounting @ $30 = $300
Auxiliary contacts and shunt trips may be mounted in combination.
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
Discount schedule CB8
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
14
M
o
pr ies
em Ser
st
Sy 200
S
14
Accessories
S200
Electrical
accessories
Catalog
number
List
price
Delivery
class
Suggested
order quantities
Wgt. oz.
(1 pc.)
S500-ME1
S500-ME2
S500-ME3
S500-K1
$ 60
70
80
16
A
1
2.1
2.9
3.6
1.5
MB-CL
35
A
1
2
MB-3PD
35
A
1
2.5
SA1
SA2
9
19
A
10
0.7
0.1
BS
BS1/40
74
74
A
1
—
12402
12404
12406
12408
32
45
56
66
B
1
2.0
2.8
3.4
4.1
84
98
126
210
A
1
8.1
10.8
20.4
41.0
BP-1P
BP-12P
6
7
A
—
1
—
—
—
S2C-DH
76
A
1
9.2
21
A
1
8
Front mounting kit
For 2 poles
For 2 – 5 poles
For 2 – 10 poles
Optional rear terminals
S500-ME2
Includes flange, mounting rail and hardware.
Front mounting clip
For 1 – 4 poles
Simple mounting clip for up to four module mounting.
Front mounting bracket
For 1 – 3 poles
For flush mounting of three pole MCBs: includes hardware.
MB-CL
Locking device
Adaptor only
Padlock only w/ 2 keys
Allows breaker to be locked in ON or OFF position.
Labeling accessory
MB-3PD
1 sheet = 40 blank labels
1 sheet = 40 numbered labels
Adhesive labels mount on front face of components.
Enclosure, IP40
SA1
For 2 modules
For 4 modules
For 6 modules
For 8 modules
For additional protection against accidental contact. Includes integrated mounting rail.
14
Enclosure, IP55
SA2
For 4 modules
For 6 modules
For 10 modules
For 20 modules
12644
12646
12650
12652
Molded plastic complete with mounting rail and knock-outs for cable entries.
Blanking plates
Single pole (set of 10)
Twelve pole (snap-off, set of 1)
12404
Handle mechanism
For use with 2, 3 and 4 pole S2 MCBs and disconnect switch handles with 5mm shaft.
DIN rail
Universal mounting
SMR-39
35mm DIN rails are available in 39-inch strips (1 meter).
S2C-DH
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
SMR-39
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
Accessories
S200
Busbar accessories
Catalog
number
Description
Busbar end caps
SZ-BSK
2 & 3 phase
4 phase
PS-ENDSP
PS-END1SP
List
price
Delivery
class
Suggested
order qty.
Weight
ounce
qty. (2 pc.)
$2
A
10
—
Busbar tooth covers
(shrouds unused portion of busbar)
SZ-BSK
4
A
10
—
Busbar mounted terminal block,
1 pole, for use on all busbars.
Wire size: 14 AWG to 2 AWG
SZ-ESK2
10
A
1
1.0
Electrical accessories
Catalog
number
Item
List
price
Delivery
class
Suggested
order quantities
Wgt. oz.
(1 pc.)
$ 40
40
4
4
A
A
A
A
1
1
1
1
4
4
4
4
Catalog
number
List
price
Delivery
class
Suggested
order quantities
Wgt. oz.
(1 pc.)
SZ-AST55I
SZ-AST50I
$ 15
15
B
10
10
0.5
0.5
15
15
B
10
10
0.5
0.5
Posidrive tools
SZ-ESK2
Screwdriver, #1
Screwdriver, #2
Bit, #1
Bit, #2
SD-PZ1
SD-PZ2
BIT-PZ1
BIT-PZ2
Connection terminals
Cross section
AWG/mm2
For
use on:
1/0 (50mm2) Straight
1/0 (50mm2) 90°
SZ-AST55_
S200 & S200P
1/0 (50mm2) Straight
S200U & S200UP
1/0 (50mm2) 90°
SZ-AST55U
SZ-AST50U
Ring tongue accessories
Description
Ring tongue terminal
For use on
S200 & S200P
S200U & S200UP
Plug
SZ-AST50_
Catalog
number
SZ-AST55UPRT
S2C-P
List
price
Delivery
class
Suggested
order qty.
qty. (2 pc.)
Weight
ounce
$5
A
10
0.5
N/C
A
10
—
Factory mounting
Ring tongue connection terminals may be easily mounted in the field. For factory mounting, add $5 list per connector. To
create a complete catalog number, add the suffix as defined below:
Top & bottom: S201 - K20W $ 62
(Single pole, 20A breaker with 2 ring tongue terminals) S201-K20 @ $42 +
SZ-AST55UPRT times 2 @ $5 + factory mounting times 2 @ $5 = $62
Bottom only: S201 - K20BW $ 52
(Single pole, 20A breaker with 1 ring tongue terminal) S201-K20 @ $42 +
SZ-AST55UPRT @ $5 + factory mounting @ $5 = $52
Top only, S201 - K20TW
(Single pole, 20A breaker with 1 ring tongue terminal) S201-K20 @ $42 +
SZ-AST55UPRT @ $5 + factory mounting @ $5 = $52
$ 52
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
Discount schedule CB8
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
14
M
o
pr ies
em Ser
st
Sy 200
S
14
Technical data
Mounting and operating instructions
Mounting
Operation
Universal mounting position using snap-on
mounting to standard 35x7.5mm DIN rail.
MCBs are switched on by moving the handle to the
upper position. Stamped onto the handle switch, a
“I” is visible confirming that the breaker is closed.
Miniature circuit breakers (MCBs) can also be
mounted to front of door using a panel cut-out with
breaker handle protruding through panel opening
for external operation. Special front mounting kit
page 23.
Mounting MCB
Connection
Terminals are suitable for solid or flexible
conductors from 18 to 4 AWG (0.75 to 25mm2) with
no busbar connected. When maximum busbar size
of 36 mm2 is used, maximum cable is 6 AWG (16
mm2).
Maximum tightening torque of 17.5 in-lb (2 Nm)
for line/load terminals and 4.5 in-lb (0.5Nm) for
accessory device terminals.
The MCBs are “trip-free,” if the handle is being
forced to the “ON” position, the breaker will still trip
under fault conditions.
The “O” marking indicates that the breaker is in the
“OFF” position. The MCB is now open and the load
is disconnected from line power.
When a breaker has tripped, the MCB handle should
first be set to the full “OFF” position to make certain
the trip mechanism has been reset. Once the fault
has been determined and cleared the MCB can
again be switched “ON”.
Maintenance
ABB miniature circuit breakers require no special
maintenance; only normal electrical system
maintenance procedures are required.
Removing MCB
Possible mounting arrangements of MCB accessories
Legend
+S/H+S/H (H)+S/H (H)
S 200
Auxiliary contact
Bell alarm/Auxiliary contact
H
S/H
Bell alarm/Auxiliary contact
used as auxiliary contact S/H (H)
+H+H+H
14
Shunt trip
ST
Undervoltage release
UR
+ST+H+H+H
+ST+S/H+S/H (H)+S/H (H)
+UR+H+H+H
+UR+S/H+S/H (H)+S/H (H)
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Technical data
Busbars & connectors
Connection methods
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
Top and bottom dual function terminals
provided in open position for connection to
busbars or cable.
Terminals allow for connection of cable
18-4 AWG [top row] and 18-8 AWG [bottom
row].
Two slots per terminal offer the ability to
connect, independently, two conductors.
This may be cables or bus bar.
Top and bottom terminals may be bussed
together with single phase or multi-phase
busbars as shown. Both line and load side
terminals can be bus bar connected.
Easy removal of devices from an assembly
when using bus bar in the bottom, load side
terminals.
Conductors may only be inserted into open
terminals, preventing mis-wiring and potential
problems.
Low Voltage Products & Systems
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
14
14.25
M
o
pr ies
em Ser
st
Sy 200
S
Technical data
14
S200-B
S200-C, -D
S200-K
Approvals:
UL
CSA
VDE
IEC
Item
1077
C22.2 — No.235
0641, 0660
898, 947
1077
C22.2 — No. 235
0660
898, 947
1077
C22.2 — No. 235
0660
898, 947
1077
—
0660
898, 947
No. of poles:
1,2,3,4 1+N,3+N
1,2,3, 1+N,3+N
1,2,3,4, 1+N,3+N
1,2,3,4,1+N,3+N
Tripping characteristic:
Rated currents:
Minimum operating voltage:
120VAC
C,D
K
K
0.5 to 63A
0.5 to 63A
0.2 to 63A
12V
12V
12V
Single pole
Multi pole
Single pole
Multi pole
Single pole
Multi pole
Single pole
Multi pole
10kA
—
10kA
—
10kA
—
10kA
—
10kA
240VAC
6kA
10kA
6kA
10kA
6kA
10kA
10kA
277VAC
6kA
—
6kA
—
6kA
—
10kA
—
—
6kA
—
6kA
—
6kA
—
10kA
60VDC
10kA
10kA
10kA
10kA
10kA
10kA
—
—
125VDC
—
10kA
—
10kA
—
10kA
—
—
277/480 VAC
Frequency:
50/60Hz (See below)
50/60Hz (see below)
50/60Hz (see below)
50/60Hz (see below)
240/415VAC
60VDC
415VAC
110VDC
240/415VAC
60VDC
415VAC
110VDC
240/415VAC
60VDC
415VAC
110VDC
240/415VAC
60VDC
415VAC
110VDC
Rated voltage
IEC single pole
IEC multi-pole
Protection category:
IP20
IP20
IP20
IP20
Depth of unit per DIN 43880:
68mm
68mm
68mm
68mm
Mounting position:
optional
optional
optional
optional
Standard mounting:
35mm DIN rail
35mm DIN rail
35mm DIN rail
35mm DIN rail
18-4 AWG [top]
18-8 [bottom]
17.5 in-lbs.
#2 Posidrive
18-4 AWG [top]
18-8 [bottom]
17.5 in-lbs.
#2 Posidrive
18-4 AWG [top]
18-8 [bottom]
17.5 in-lbs.
#2 Posidrive
18-4 AWG [top]
18-8 [bottom]
17.5 in-lbs.
#2 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
-25°C to +70°C
-40°C to + 70°C
-25°C to +70°C
-40°C to + 70°C
-25°C to +70°C
-40°C to + 70°C
-25°C to +70°C
-40°C to + 70°C
Shock resistance:
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
Vibration resistance:
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
6kA switching
6kA switching
6kA switching
—
Main and shunt trip terminals:
Wire size
14
B
6 to 63A
12V
UL/CSA rated voltage &
interrupting capacity
S200P-K
Torque
Tool
Accessory terminals
Wire size
Torque
Tool
Service life at rated load:
Ambient temperatures:
Storage temperatures
Disconnecting neutral rating:
Influence of frequency on electro-magnetic trips
Magnetic trip values shown on trip curves are valid for 50/60Hz applications.
For frequencies other than 50/60Hz, the magnetic (instantaneous) trip values are
increased by the factor given below:
16 2/3 - 60Hz 100Hz
Approx. factor
1
1.1
200Hz
400Hz
DC
1.2
1.5
1.5
Thermal tripping is independent of frequency.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
Technical data
Item
Approvals:
UL
CSA
VDE
IEC
S280UC-K
S200P-Z
S280UC-Z
S290-C
1077
—
0660
898,947
1077
—
0660
898, 947
1077
—
0660
898, 947
—
—
0660
898
1,2,3
1,2,3,4
1,2,3
1,2,3,4
No. of poles:
Tripping characteristic:
Rated currents:
K
Z
Z
C
0.2 to 63A
0.5 to 63A
0.5 to 63A
80 to 125A
12V
12V
Minimum operating voltage:
12V
UL/CSA rated voltage &
interrupting capacity
12V
Single pole
Multi pole
Single pole
Multi pole
Single pole
Multi pole
120VAC
10kA
—
10kA
—
10kA
—
—
240VAC
10kA
10kA
10kA
10kA
10kA
10kA
—
277VAC
10kA
—
10kA
—
10kA
—
—
—
4.5kA for 0.2-40A
5kA for 50-63A
—
10kA
—
4.5kA for 0.2-40A
5kA for 50-63A
—
60VDC
10kA
10kA
—
—
10kA
10kA
—
125VDC
10kA
10kA
—
—
10kA
10kA
—
250VDC
4.5kA
4.5kA
—
—
4.5kA
4.5kA
—
—
4.5kA
—
—
—
4.5kA
277/480 VAC
500VDC
Frequency:
Rated voltage
IEC single pole
—
50/60Hz (see below)
50/60 Hz (see below)
50/60Hz (see below)
50/60Hz (see below)
240/415VAC
220VDC
415VAC
440VDC
240/415VAC
60VDC
415VAC
110VDC
240/415VAC
220VDC
415VAC
440VDC
230/440VAC
60VDC
440VAC
110VDC
IEC multi-pole
Protection category:
IP20
IP20
IP20
IP20
Depth of unit per DIN 43880:
68mm
68mm
68mm
70mm
Mounting position:
optional
optional
optional
optional
Standard mounting:
35mm DIN rail
35mm DIN rail
35mm DIN-rail
35mm DIN-rail
14
Main and shunt trip terminals:
Wire size
0.2-40A
18-4 AWG
50A & above
18-2 AWG
17.5 in-lbs.
#2 Posidrive
Torque
Tool
Accessory terminals
Wire size
Torque
Tool
18-4 AWG [top]
18-8 AWG [bottom]
17.5 in-lbs.
#2 Posidrive
0.5-40A
18-4 AWG
18-2 AWG
17.5 in-lbs.
#2 Posidrive
80-125A
14-1/0 AWG
17.5 in-lbs.
#2 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
10,000 operations
––
-25°C to +55°C
-40°C to + 70°C
-25°C to +70°C
-40°C to + 70°C
-25°C to +55°C
-40°C to + 70°C
-5°C to +45°C
-40°C to + 70°C
Shock resistance:
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
Vibration resistance:
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
60m/s2, at 10 – 150 Hz
Service life at rated load:
Ambient temperatures:
Storage temperatures
Influence of frequency on electro-magnetic trips
Magnetic trip values shown on trip curves are valid for 50/60Hz applications.
For frequencies other than 50/60Hz, the magnetic (instantaneous) trip values are
increased by the factor given below:
16 2/3 - 60Hz 100Hz
Approx. factor
1
1.1
200Hz
400Hz
DC
1.2
1.5
1.5
Thermal tripping is independent of frequency.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
M
o
pr ies
em Ser
st
Sy 200
S
Technical data
14
Item
Approvals:
UL
CSA
VDE
IEC
No. of poles:
Tripping characteristic:
S200U-K
S200U-Z
S200UP-K
S200UP-Z
489
C22.2 No.5
0660
898,947
489
C22.2 No.5
0660
898, 947
489
C22.2 No.5
0660
898, 947
489
C22.2 No.5
0660
898
1,2,3,4
1,2,3,4
1,2,3,4
1,2,3,4
K
Z
K
Z
0.2 to 63A
0.2 to 63A
0.2 to 25A
0.2 to 25A
12V
12V
12V
12V
120VAC
10kA
10kA
10kA
10kA
240VAC
10kA
10kA
10kA
10kA
277VAC
10kA
10kA
480/277 VAC
—
—
10kA
10kA
Frequency:
Rated voltage
IEC single pole
50/60Hz (see below)
50/60 Hz (see below)
50/60Hz (see below)
50/60Hz (see below)
240/415VAC
220VDC
415VAC
440VDC
240/415VAC
60VDC
415VAC
110VDC
240/415VAC
220VDC
415VAC
440VDC
240/415VAC
220VDC
415VAC
440VDC
Rated currents:
Minimum operating voltage:
UL/CSA rated voltage &
interrupting capacity
IEC multi-pole
Protection category:
IP20
IP20
IP20
IP20
Depth of unit per DIN 43880:
68mm
68mm
68mm
68mm
Mounting position:
optional
optional
optional
optional
Standard mounting:
35mm DIN rail
35mm DIN rail
35mm DIN-rail
35mm DIN-rail
18-4 AWG [top]
18-8 AWG [bottom]
17.5 in-lbs.
#2 Posidrive
18-4 AWG [top]
18-8 AWG [bottom]
17.5 in-lbs.
#2 Posidrive
18-4 AWG [top]
18-8 AWG [bottom]
17.5 in-lbs.
#2 Posidrive
18-4 AWG [top]
18-8 AWG [bottom]
17.5 in-lbs.
#2 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
-25°C to +70°C
-40°C to + 70°C
-25°C to +70°C
-40°C to + 70°C
-25°C to +70°C
-40°C to + 70°C
-25°C to +70°C
-40°C to + 70°C
Shock resistance:
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
Vibration resistance:
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
Main and shunt trip terminals:
Wire size
Torque
Tool
14
Accessory terminals
Wire size
Torque
Tool
Service life at rated load:
Ambient temperatures:
Storage temperatures
Influence of frequency on electro-magnetic trips
Magnetic trip values shown on trip curves are valid for 50/60Hz applications.
For frequencies other than 50/60Hz, the magnetic (instantaneous) trip values are
increased by the factor given below:
16 2/3 - 60Hz 100Hz
Approx. factor
1
1.1
200Hz
400Hz
DC
1.2
1.5
1.5
Thermal tripping is independent of frequency.
14.28
Low Voltage Products & Systems
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
Technical data
Wire size comparison
Comparison of IEC and AWG wire sizes
mm
AWG (mm )
Amps / UL
Amps / IEC
1.0
—
1.5
—
16 (1.3)
—
—
10
—
8
—
12
—
2.5
—
14 (2.1)
—
12 (3.3)
15
—
20
—
20
—
4
—
6
—
10 (5.3)
—
—
30
—
25
—
32
—
10
—
8 (8.4)
—
6 (13.3)
50
—
65
—
50
—
16
—
25
—
4 (21.2)
—
—
85
—
65
—
85
—
—
35
3 (26.7)
2 (33.6)
—
100
115
—
—
—
115
Ampacities for AWG wire are based on copper cable rated 75° C, except for 16AWG which is based on 60° C wire. Taken from UL508 Table 52.2.
Consult applicable standards for futher detail and information.
14
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
M
o
pr ies
em Ser
st
Sy 200
S
Approximate dimensions
S200, S200P, S200U, S200UP
14
00.00
Inches
00.00
[Millimeters]
S200 & S200P
S200U
S200UP
14
S290
Accessories mount to right side
of MCB only
1.77
45
1.97
1.03
50
26
1.06
27
2.13 54
0.69
17.5
0.35
0.35
9
9
-H
Auxiliary
switch
-S
Bell
alarm
3.19 81
-A1, -A2
Shunt
trip
14.30
Low Voltage Products & Systems
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
Approximate dimensions
Accessories
00.00
Inches
00.00
[Millimeters]
Accessories
mm
S 2C-H...
S 2C-S...
S 2C-S/H...
S 2C-A...
S 2C-UA...
45
69
85
8.8
45
69
85
17.5
6.8
6.8
44
MB-CL
Front mounting clip
44
mm
C.L.
1.77
45 D
2.26 1.77
57.5
C.L.
45
0.69
17.5
1.38
35
2.07
52.5
MB-3PD
Front mounting bracket
14
3.25
2.12 ( 3P )
in
1.43 ( 2P )
1.87
CL
C
L
BREAKER CUT OUT
0.74 ( 1P )
BKT. MT. HOLES
0.25 DIA. TYP 2
S2C-DH
Handle mechanism
CL
CL
0.63
16
2.07 52.5
0.83
21
1.38 35
3.54
90
4.36
110.4
1.77
45
3.26
82.5
0.27 6.9
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
M
o
pr ies
em Ser
st
Sy 200
S
14
Approximate dimensions
Accessories
00.00
Inches
00.00
[Millimeters]
12402-12408
12650
12644
4.92
4.92
125
125
4.92
4.13
125
230
4.13
105
9.06
105
7.09
7.09
180
180
14
12646
12652
6.09
155
4.92
9.84
250
5.32
125
6.30
4.13
135
160
105
7.09
180
12.60
320
14.32
Low Voltage Products & Systems
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
Cross-reference
Older
version
Suggested
replacement
series
Physical
comparison
Electrical
comparison
S260-B
S200-B
Same pole spacing
Same trip characteristic
S260-C
S200-C
Same pole spacing
Same trip characteristic
S260-D
S200-D
Same pole spacing
Same trip characteristic
S270-K
S200-K
Same pole spacing
Same trip characteristic
S280-K
S200P-K
Same pole spacing
Same trip characteristic
S280-Z
S200P-Z
Same pole spacing
Same trip characteristic
S280U-K
S200U-K
Same pole spacing
Same trip characteristic
S280UX-K
S200U-K
Smaller pole spacing
Same trip characteristic
Many older styles of ABB miniature circuit breakers have been replaced by new and improved versions. Many of these newer styles can be directly interchanged, both
electrically and physically, with the older version. There are also many international styles of ABB circuit breakers which are not normal stock items and may be interchanged with stocked ABB versions.
14
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com