System pro M compact Miniature circuit breakers S200, S200P

advertisement
S
System pro M compact S ystem
2
Miniature circuit breakers 00 Se pro
M
S200, S200P, S200U, S200UP ries
14
Description
Features
The S2 Series of miniature circuit breakers
offer a compact solution to protection
requirements. The S2 devices are current
limiting, DIN rail mounted and can offer a
good equivalent to fused systems.
The S2 is available with application-specific
trip characteristics to provide maximum
circuit protection. The breakers offer
thermal-magnetic trip protection according
to B, C, D, K and Z characteristics.
For the worldwide market, the breakers
carry UL, CSA, IEC, CE and many other
agency approvals and certifications.
• Current limiting
• Fast breaking time (2.5 – 3.5 msec)
• Unique bus connection system
• Wide range of accessories
• Available with variable depth handle
mechanism
• Optional Z curve for SCR protection
• CE certified and marked
14
• DIN rail or front panel mounting
• Finger safe terminals
• Multi-function terminals
• Suitable for reverse feed
• 480Y/277VAC and 500VDC versions
• UL489 Listed - branch circuit protective
device. UL file # E212323
• UL1077 Recognized - supplemental
protective device. UL file # E76126
ed
old
M
re nd
u
t
a
nia ers rs
i
d M reak ecto
e
t
rov uit B Pro
p
Ap Circ ntal
L
U se me
Ca pple
Su
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.1
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 200
S
14
General information
General information
Applications
Miniature circuit breakers (MCBs) are used throughout the world in all
types of electrical installations. ABB MCBs are approved for use by
Underwriters Laboratories in systems rated up to 600VAC/VDC. Devices
are also certified per CSA.
MCBs are approved per IEC-898 and VDE 0641, and certified under
IEC-947 and VDE 0660 standards for use in systems rated up to
690VAC.
MCBs can be applied to 16 2/3Hz – 400Hz and DC power systems.
Special direct current version MCBs include a permanent magnet for DC
fault current interruption. These "UC" versions are rated 250/500VDC
under UL1077/CSA 22.2 No. 235.
Continuous current ratings are as low as 0.2 amperes and up to 125
amperes maximum.
MCBs are of compact size and can be quickly mounted on standard
35mm DIN rail or can be front mounted by use of a front mounting kit.
MCBs include line and load side terminals for conductors from 18
through 4AWG (0.75 – 25mm2) for 63 amperes.
MCBs can also be connected via busbar conductors which can be
either upper or lower mounted for top feed or bottom feed. Dual
function terminals allow busbars to be connected with main incoming
line conductors without separate lugs.
MCBs can be used for equipment protection, in commercial appliances,
protection of control circuits against overcurrent faults, computer
equipment and other computer peripheral devices.
Accessories
Auxiliary devices can be added to the, S200 series MCBs:
• Shunt trips
• Auxiliary contacts
• Bell alarm contacts
• Aux/bell alarm contacts
• Undervoltage release
Accessory device modules can be field mounted to all above listed ABB
MCBs. Auxiliary contacts are also available for the S500 series MCB.
14
14.2
1SXU 000 023 C0201
UL 489
S200U and S200UP MCBs are listed as molded case circuit breakers
for use as branch circuit protective devices. Miniature MCCBs and
accessories are listed under UL file E212323.
UL 1077
S200 and S200P MCBs are recognized as supplementary protectors
and are intended for use as overcurrent protection within an appliance
or other electrical equipment where branch circuit overcurrent
protection is already provided or not required. MCBs and accessories
are recognized under UL File E76126.
CSA C22.2
MCBs and accessories are certified under CSA C22.2 No. 235 per File
LR98793.
Tripping characteristics
Time-current curves
ABB miniature circuit breakers are available with different trip
characteristics, allowing for maximum system protection.
B Characteristic
Available with the S200 and S500 series has rated currents of 6 through
63 amperes in 10 steps. The "B" time-current curve is designed
primarily for use in cable protection applications. Instantaneous tripping
occurs between approximately 3 to 5 times rated current in 50/60Hz
systems. This quick trip curve maximizes protection of control circuits
under low short circuit fault levels that could damage control wiring.
C Characteristic
Available in the S200 and S500 series with rated currents up through 63
amperes and the S290 series with rated currents of 80, 100 and 125
amperes. The "C" time-current curve is designed for medium magnetic
start-up currents. Instantaneous tripping occurs between 5 and 10
times rated current in 50/60 Hz systems.
D Characteristic
The new magnetic trip action has an instantaneous trip between 10 and
20 times the breaker rating. Thus, the S200 and S500-D can be a good
protective solution for applications involving high in-rush transformers,
motors and other high inductive systems. It is also suitable for any
application where a high instantaneous trip point is desired.
K Characteristic
The "K" time-current characteristic considers high magnetic start-up
currents from motors, transformers and other equipment. Instantaneous
tripping occurs between 8 and 12 times rated current in 50/60Hz
systems. The "K" characteristic is available up through 63 amperes.
The "K" curve offers the best protection for the broadest range of
electrical systems. The higher magnetic trip settings maximizes
protection while allowing for higher in-rush currents during system startup. Available in S200P, S200U, S200UP and S500.
Z Characteristic
Also available up through 63 amperes, the "Z" characteristic offers
instantaneous tripping between 2 and 3 times rated current in 50/60Hz
systems. This trip characteristic is available in the S200P, S200U and
S200UP series with both the 480Y/277VAC and 250/500VDC ratings.
Many applications require a very low short circuit trip setting in order
to protect semiconductor or other sensitive devices and the "Z" trip
characteristic may provide maximum protection and service in these
applications.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
General information
Interruption ratings
Trip characteristics overview
Trip characteristics overview
Interruption ratings
Voltage
120 VAC
Rated interrupting
capacity
Rated
current
0.5
0.5
0.2
0.2
0.2
18kA
32 - 63A
26 - 45A
S500-B,C,D
S500-K
30kA
6 - 25A
0.15 - 25A
S500-B,C,D
S500-K
6kA
0.5 - 63A
0.5 - 63A
S200-B,C,D
S200-K
Single pole
Single pole
10kA
0.5
0.5
0.2
0.2
0.2
0.2
0.2
0.2
63A
63A
63A
63A
63A
63A
25A
25A
S200-B,C,D
S200-K
S200P-K,Z
S200P-K,Z
S200U-K,Z
S200U-K,Z
S200UP-K,Z
S200UP-K,Z
Multi pole
Multi pole
Single pole
Multi pole
Single pole
Multi pole
Single pole
Multi pole
18kA
32 - 63A
26 - 45A
S500-B,C,D
S500-K
30kA
6 - 25A
0.15 - 25A
S500-B,C,D
S500-K
6kA
0.5 - 63A
0.5 - 63A
S200-B,C,D
S200-K
10KA
0.2 - 63A
0.2 - 25A
S200P-K,Z
S200UP-K,Z
6kA
0.5 - 63A
0.5 - 63A
S200-B,C,D
S200-K
10KA
0.2 - 63A
0.2 - 25A
S200P-K,Z
S200UP-K,Z
60 VDC
10kA
0.5 - 63A
0.5 - 63A
S200-B,C,D
S200-K
Single pole
Single pole
125 VDC
10kA
0.5 - 63A
0.5 - 63A
0.2 - 63A
S200-B,C,D
S200-K
S280UC-K,Z
Multi pole
Multi pole
Single pole
250 VDC
4.5kA
0.2 - 63A
S280UC-K,Z
Single pole
500 VDC
4.5kA
0.2 - 63A
S280UC-K,Z
Multi pole
277 VAC
480Y/277 VAC
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
-
63A
63A
63A
63A
25A
Comment
10kA
240 VAC
-
MCB
type
S200-B,C,D
S200-K
S200P-K, Z
S200U-K, Z
S200UP-K, Z
Curve
Magnetic
characteristic 1
B
C
D
K
Z
3 - 5X
5 - 10X
10 - 20X
8 - 12X
2 - 3X
Thermal
characteristic
1.13
1.13
1.13
1.05
1.05
1.45X
1.45X
1.45X
1.20X
1.20X
Series
S200, S500
S200, S290, S500
S200, S500
S200, S500
S200
1 All values are relative to MCB's ampere rating.
14
14.3
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 200
S
General information
Tripping curves
14
B
C
D
5000
5000
5000
1000
500
1000
500
1000
500
100
50
100
50
100
50
10
5
10
5
10
5
1
0.5
1
0.5
1
0.5
AC
0.1
0.05
AC
0.1
0.05
0.01
2
3
5
7 10
20 30
0.01
1
multiple of rated current
2
3
K
10
18 20 30
1
2
3
5
10
20 30
multiple of rated current
UC-K
5000
5000
1000
500
1000
500
100
50
100
50
10
5
10
5
1
0.5
1
0.5
seconds
10,000
seconds
5
multiple of rated current
10,000
AC
0.1
0.1
0.05
0.05
DC
DC
0.01
0.01
1
2
3
5
8 10 12
20 30
1
multiple of rated current
2
3
5
10
20 30
multiple of rated current
UC-Z
Z
10,000
5000
5000
1000
500
1000
500
100
50
100
50
10
5
10
5
1
0.5
1
0.5
seconds
10,000
seconds
DC
DC
0.01
1
AC
0.1
0.05
DC
14
seconds
10,000
seconds
10,000
seconds
10,000
AC
0.1
0.1
0.05
0.05
DC
DC
0.01
0.01
1
2
3
5
10
multiple of rated current
14.4
1SXU 000 023 C0201
20 30
1
2
3
5
10
20 30
multiple of rated current
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
General information
Construction details
Electro-magnetic protection
Tripping lever
Operating
mechanism
Upper terminal
Thermal protection-bimetal
Operator
14
Arc chamber
Space for
identification marker
Fixed contact
Moving contact
DIN rail holder
Lower terminal
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.5
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 200
S
S200
480Y/277 VAC
Supplemental protectors
14
B
UL 1077
CSA C22.2 No. 235
VDE 0641
IEC-898
Cable protection
Rated
current
Catalog
number
List
price
S201-B6
S201-B10
S201-B13
S201-B16
S201-B20
S201-B25
S201-B32
S201-B40
S201-B50
S201-B63
$ 36
36
36
36
38
38
40
42
48
56
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
6
10
13
16
20
25
32
40
50
63
S201-B, 1 pole
S202-B, 2 pole
S201-BNA, 1 P+N
A
10
4.5
14
List
price
Delivery
class
Sugg.
order
qty
S203-B6
S203-B10
S203-B13
S203-B16
S203-B20
S203-B25
S203-B32
S203-B40
S203-B50
S203-B63
$ 118
118
118
118
130
132
142
148
170
194
A
1
13.5
S203-B6NA
S203-B10NA
S203-B13NA
S203-B16NA
S203-B20NA
S203-B25NA
S203-B32NA
S203-B40NA
S203-B50NA
S203-B63NA
142
142
142
142
162
168
176
184
212
240
B
1
18.0
S204-B6
S204-B10
S204-B13
S204-B16
S204-B20
S204-B25
S204-B32
S204-B40
S204-B50
S204-B63
156
156
156
156
172
176
188
196
224
256
B
1
18.0
Wgt. oz.
(1 pc.)
6
10
13
16
20
25
32
40
50
63
3 pole + neutral
S201-B6NA
S201-B10NA
S201-B13NA
S201-B16NA
S201-B20NA
S201-B25NA
S201-B32NA
S201-B40NA
S201-B50NA
S201-B63NA
62
62
62
62
68
72
74
76
90
102
S202-B6
S202-B10
S202-B13
S202-B16
S202-B20
S202-B25
S202-B32
S202-B40
S202-B50
S202-B63
78
78
78
78
86
88
94
98
112
128
B
5
9.0
2 pole
6
10
13
16
20
25
32
40
50
63
Catalog
number
3 pole
1 pole + neutral
6
10
13
16
20
25
32
40
50
63
Rated
current
6
10
13
16
20
25
32
40
50
63
4 pole
A
5
9.0
6
10
13
16
20
25
32
40
50
63
S203-B, 3 pole
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
S204-B, 4 pole
S203-BNA, 3P+N
B
10,000
5000
1000
500
100
50
seconds
10
5
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
7 10
20 30
multiple of rated current
14.6
1SXU 000 023 C0201
Discount schedule CB5
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
S200
480Y/277 VAC
Supplemental protectors
C
UL 1077
CSA C22.2 - NO. 235
VDE 0641
IEC-898
Cable & equipment protection
Rated
current
Catalog
number
List
price
S201-C0.5
S201-C1
S201-C1.6
S201-C2
S201-C3
S201-C4
S201-C6
S201-C8
S201-C10
S201-C13
S201-C16
S201-C20
S201-C25
S201-C32
S201-C40
S201-C50
S201-C63
$ 42
42
42
42
42
42
42
42
42
42
42
42
46
48
52
60
68
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S201-C, 1 pole
S202-C, 2 pole
S201-CNA, 1P+N
S203-C, 3 pole
A
10
4.5
S204-C, 4 pole
S203-CNA, 3P+N
C
10,000
5000
1000
500
84
84
84
84
84
84
84
84
84
84
84
84
88
90
96
112
130
S202-C0.5
S202-C1
S202-C1.6
S202-C2
S202-C3
S202-C4
S202-C6
S202-C8
S202-C10
S202-C13
S202-C16
S202-C20
S202-C25
S202-C32
S202-C40
S202-C50
S202-C63
96
96
96
96
96
96
96
96
96
96
96
96
106
106
116
136
152
B
5
9.0
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S203-C0.5
S203-C1
S203-C1.6
S203-C2
S203-C3
S203-C4
S203-C6
S203-C8
S203-C10
S203-C13
S203-C16
S203-C20
S203-C25
S203-C32
S203-C40
S203-C50
S203-C63
$ 138
138
138
138
138
138
138
138
138
138
138
138
156
158
174
200
228
A
1
13.5
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S203-C0.5NA
S203-C1NA
S203-C1.6NA
S203-C2NA
S203-C3NA
S203-C4NA
S203-C6NA
S203-C8NA
S203-C10NA
S203-C13NA
S203-C16NA
S203-C20NA
S203-C25NA
S203-C32NA
S203-C40NA
S203-C50NA
S203-C63NA
200
200
200
200
200
200
200
200
200
200
200
200
206
212
224
204
304
B
1
18.0
S204-C0.5
S204-C1
S204-C1.6
S204-C2
S204-C3
S204-C4
S204-C6
S204-C8
S204-C10
S204-C13
S204-C16
S204-C20
S204-C25
S204-C32
S204-C40
S204-C50
S204-C63
218
218
218
218
218
218
218
218
218
218
218
218
234
238
260
300
338
14
4 pole
A
5
9.0
100
50
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
B
1
18.0
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
10
5
seconds
List
price
3 pole + neutral
S201-C0.5NA
S201-C1NA
S201-C1.6NA
S201-C2NA
S201-C3NA
S201-C4NA
S201-C6NA
S201-C8NA
S201-C10NA
S201-C13NA
S201-C16NA
S201-C20NA
S201-C25NA
S201-C32NA
S201-C40NA
S201-C50NA
S201-C63NA
2 pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
Catalog
number
3 pole
1 pole + neutral
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
Rated
current
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
10
18 20 30
multiple of rated current
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule CB5
14.7
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 200
S
S200
480Y/277 VAC
Supplemental protectors
14
UL 1077
CSA C22.2
VDE 0641
IEC-898
Cable & equipment protection
D
Rated
current
Catalog
number
List
price
S201-D0.5
S201-D1
S201-D1.6
S201-D2
S201-D3
S201-D4
S201-D6
S201-D8
S201-D10
S201-D13
S201-D16
S201-D20
S201-D25
S201-D32
S201-D40
S201-D50
S201-D63
$ 42
42
42
42
42
42
42
42
42
42
42
42
46
48
52
60
68
S202-D0.5
S202-D1
S202-D1.6
S202-D2
S202-D3
S202-D4
S202-D6
S202-D8
S202-D10
S202-D13
S202-D16
S202-D20
S202-D25
S202-D32
S202-D40
S202-D50
S202-D63
96
96
96
96
96
96
96
96
96
96
96
96
106
106
116
136
152
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
S201-D, 1 pole
Catalog
number
List
price
S203-D0.5
S203-D1
S203-D1.6
S203-D2
S203-D3
S203-D4
S203-D6
S203-D8
S203-D10
S203-D13
S203-D16
S203-D20
S203-D25
S203-D32
S203-D40
S203-D50
S203-D63
$ 138
138
138
138
138
138
138
138
138
138
138
138
156
158
174
200
228
Delivery
class
Sugg.
order
qty
A
1
Wgt. oz.
(1 pc.)
3 pole
1 pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
Rated
current
A
10
4.5
A
5
9.0
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
13.5
2 pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S202-D, 2 pole
14
S203-D, 3 pole
D
10,000
5000
1000
500
100
50
10
5
seconds
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
10
20 30
multiple of rated current
14.8
1SXU 000 023 C0201
Discount schedule CB5
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
S200
480Y/277 VAC
Supplemental protectors
K
UL 1077
CSA C22.2 - NO. 235
VDE 0641
IEC-898
Cable & equipment protection
Rated
current
Catalog
number
List
price
S201-K0.5
S201-K1
S201-K1.6
S201-K2
S201-K3
S201-K4
S201-K5
S201-K6
S201-K8
S201-K10
S201-K13
S201-K15
S201-K16
S201-K20
S201-K25
S201-K30
S201-K32
S201-K40
S201-K50
S201-K60
S201-K63
$ 42
42
42
42
42
42
42
42
42
42
42
42
42
42
46
48
48
52
60
68
68
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
S201-K, 1 pole
S202-K, 2 pole
S201-KNA, 1P+N
A
10
4.5
S203-K, 3 pole
S201-K0.5NA
S201-K1NA
S201-K1.6NA
S201-K2NA
S201-K3NA
S201-K4NA
S201-K6NA
S201-K8NA
S201-K10NA
S201-K13NA
S201-K16NA
S201-K20NA
S201-K25NA
S201-K32NA
S201-K40NA
S201-K50NA
S201-K63NA
84
84
84
84
84
84
84
84
84
84
84
84
88
90
96
112
130
S202-K0.5
S202-K1
S202-K1.6
S202-K2
S202-K3
S202-K4
S202-K5
S202-K6
S202-K8
S202-K10
S202-K13
S202-K15
S202-K16
S202-K20
S202-K25
S202-K30
S202-K32
S202-K40
S202-K50
S202-K60
S202-K63
96
96
96
96
96
96
96
96
96
96
96
96
96
96
106
106
106
116
136
152
152
B
5
9.0
S204-K, 4 pole
S203-KNA, 3P+N
K
10,000
5000
1000
500
100
50
seconds
10
5
1
0.5
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
0.5
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
30
32
40
50
60
63
S203-K0.5
S203-K1
S203-K1.6
S203-K2
S203-K3
S203-K4
S203-K5
S203-K6
S203-K8
S203-K10
S203-K13
S203-K15
S203-K16
S203-K20
S203-K25
S203-K30
S203-K32
S203-K40
S203-K50
S203-K60
S203-K63
$ 138
138
138
138
138
138
138
138
138
138
138
138
138
138
156
158
158
174
200
228
228
A
1
13.5
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S203-K0.5NA
S203-K1NA
S203-K1.6NA
S203-K2NA
S203-K3NA
S203-K4NA
S203-K6NA
S203-K8NA
S203-K10NA
S203-K13NA
S203-K16NA
S203-K20NA
S203-K25NA
S203-K32NA
S203-K40NA
S203-K50NA
S203-K63NA
200
200
200
200
200
200
200
200
200
200
200
200
206
212
224
264
304
B
1
18.0
S204-K0.5
S204-K1
S204-K1.6
S204-K2
S204-K3
S204-K4
S204-K6
S204-K8
S204-K10
S204-K13
S204-K16
S204-K20
S204-K25
S204-K32
S204-K40
S204-K50
S204-K63
218
218
218
218
218
218
218
218
218
218
218
218
234
238
260
300
338
14
4 pole
2 pole
0.5
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
30
32
40
50
60
63
List
price
3 pole + neutral
1 pole + neutral
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
Catalog
number
3 pole
1 pole
0.5
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
30
32
40
50
60
63
Rated
current
A
5
9.0
AC
0.1
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
B
1
18.0
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
0.05
DC
0.01
1
2
3
5
8 10 12
20 30
multiple of rated current
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule CB5
14.9
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 200
S
S200P
480Y/277 VAC
Supplemental protectors
14
K
UL 1077
CSA C22.2 - NO. 235
VDE 0660
Cable & equipment protection
Rated
current
Catalog
number
List
price
S201P-K0.2
S201P-K0.3
S201P-K0.5
S201P-K0.75
S201P-K1
S201P-K1.6
S201P-K2
S201P-K3
S201P-K4
S201P-K6
S201P-K8
S201P-K10
S201P-K13
S201P-K16
S201P-K20
S201P-K25
S201P-K32
S201P-K40
S201P-K50
S201P-K63
$ 54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
56
58
64
70
80
S202P-K0.2
S202P-K0.3
S202P-K0.5
S202P-K0.75
S202P-K1
S202P-K1.6
S202P-K2
S202P-K3
S202P-K4
S202P-K6
S202P-K8
S202P-K10
S202P-K13
S202P-K16
S202P-K20
S202P-K25
S202P-K32
S202P-K40
S202P-K50
S202P-K63
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
130
134
134
162
182
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S201P-K, 1 pole
Rated
current
Catalog
number
List
price
S203P-K0.2
S203P-K0.3
S203P-K0.5
S203P-K0.75
S203P-K1
S203P-K1.6
S203P-K2
S203P-K3
S203P-K4
S203P-K6
S203P-K8
S203P-K10
S203P-K13
S203P-K16
S203P-K20
S203P-K25
S203P-K32
S203P-K40
S203P-K50
S203P-K63
$ 194
194
194
194
194
194
194
194
194
194
194
194
194
194
194
196
200
214
246
280
Delivery
class
Sugg.
order
qty
A
1
Wgt. oz.
(1 pc.)
3 pole
A
10
4.6
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
13.9
2 pole
S202P-K, 2 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
14
S203P-K, 3 pole
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
A
5
9.2
K
10,000
5000
1000
500
100
50
seconds
10
5
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
8 10 12
20 30
multiple of rated current
14.10
1SXU 000 023 C0201
Discount schedule CB7
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
S280 (W)
480Y/277 VAC
Supplemental protectors
K
UL 1077
CSA C22.2 - NO. 235
VDE 0660
Cable & equipment protection
Rated
current
Catalog
number
List
price
S281-K0.2W
S281-K0.3W
S281-K0.5W
S281-K0.75W
S281-K1W
S281-K1.6W
S281-K2W
S281-K3W
S281-K4W
S281-K6W
S281-K8W
S281-K10W
S281-K13W
S281-K16W
S281-K20W
S281-K25W
S281-K32W
S281-K40W
S281-K50W
S281-K63W
$ 54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
56
58
64
70
80
S282-K0.2W
S282-K0.3W
S282-K0.5W
S282-K0.75W
S282-K1W
S282-K1.6W
S282-K2W
S282-K3W
S282-K4W
S282-K6W
S282-K8W
S282-K10W
S282-K13W
S282-K16W
S282-K20W
S282-K25W
S282-K32W
S282-K40W
S282-K50W
S282-K63W
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
130
134
134
162
182
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S281-KW, 1 pole
Catalog
number
List
price
S283-K0.2W
S283-K0.3W
S283-K0.5W
S283-K0.75W
S283-K1W
S283-K1.6W
S283-K2W
S283-K3W
S283-K4W
S283-K6W
S283-K8W
S283-K10W
S283-K13W
S283-K16W
S283-K20W
S283-K25W
S283-K32W
S283-K40W
S283-K50W
S283-K63W
$ 194
194
194
194
194
194
194
194
194
194
194
194
194
194
194
196
200
214
246
280
Delivery
class
Sugg.
order
qty
B
3
Wgt. oz.
(1 pc.)
3 pole
B
10
4.6
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
13.9
2 pole
S282-KW, 2 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
S283-KW, 3 pole
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
B
5
9.2
14
e
gu
n
o
g t rs
n
i
r
o
th nect
i
w
se l con
u
r
a
Fo min
r
te
K
10,000
5000
1000
500
100
50
10
5
seconds
Rated
current
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
8 10 12
20 30
multiple of rated current
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule CB7
14.11
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 200
S
S280UC
500 VDC
Supplemental protectors
14
K
UL 1077
VDE 0660
CSA 22.2
No. 235
Cable and Equipment Protection
Rated
current
Catalog
number
List
price
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
S281UC-K, 1 pole
Rated
current
Catalog
number
List
price
S283UC-K0.2
S283UC-K0.3
S283UC-K0.5
S283UC-K0.75
S283UC-K1
S283UC-K1.6
S283UC-K2
S283UC-K3
S283UC-K4
S283UC-K6
S283UC-K8
S283UC-K10
S283UC-K16
S283UC-K20
S283UC-K25
S283UC-K32
S283UC-K40
S283UC-K50
S283UC-K63
$ 370
370
370
370
370
370
370
370
370
370
370
370
370
370
382
408
448
472
534
Delivery
class
Sugg.
order
qty
B
3
Wgt. oz.
(1 pc.)
3 pole
S281UC-K0.2
S281UC-K0.3
S281UC-K0.5
S281UC-K0.75
S281UC-K1
S281UC-K1.6
S281UC-K2
S281UC-K3
S281UC-K4
S281UC-K6
S281UC-K8
S281UC-K10
S281UC-K16
S281UC-K20
S281UC-K25
S281UC-K32
S281UC-K40
S281UC-K50
S281UC-K63
$ 104
104
104
104
104
104
104
104
104
104
104
104
104
104
108
110
116
136
152
S282UC-K0.2
S282UC-K0.3
S282UC-K0.5
S282UC-K0.75
S282UC-K1
S282UC-K1.6
S282UC-K2
S282UC-K3
S282UC-K4
S282UC-K6
S282UC-K8
S282UC-K10
S282UC-K16
S282UC-K20
S282UC-K25
S282UC-K32
S282UC-K40
S282UC-K50
S282UC-K63
242
242
242
242
242
242
242
242
242
242
242
242
242
242
248
256
266
312
348
B
10
4.6
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
13.9
2 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
S282UC-K, 2 pole
14
S283UC-K, 3 pole
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
B
5
9.2
Direct current applications
The S280UC differs from standard miniature circuit breakers in that the UC versions include a permanent
magnet which aids in the extinguishing of the arc during medium and high level faults. It is necessary to
observe the correct polarity and current direction when connecting the UC breakers. Two examples of correct
connection are shown below.
Maximum voltage between leads
250VDC
UC-K
10,000
500VDC
1000
500
L-
L+
100
50
10
5
seconds
Two Pole
LS282UC
Single Pole
S281UC
5000
1
0.5
-1
-1 +2
+2
+2
0.1
LOAD
+
0.05
DC
0.01
1
2
3
5
10
multiple of rated current
14.12
1SXU 000 023 C0201
20 30
L-1
L+
L+
3+
3+ 4-
4LOAD
+
LOAD
+
Termination points are marked on all UC type MCBs, points one (1) and four (4) are negative and points two
(2) and three (3) are positive. Four pole breakers are also available for voltage reversal applications.
Discount schedule CB7
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
S200P & S280UC
480Y/277 VAC & 500 VDC
Supplemental protectors
UL 1077
VDE 0660
CSA 22.2
No. 235
Fast trip characteristic
Z
480Y/277 VAC
Rated
current
500 VDC
Catalog
number
List
price
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
S201P-Z, 1 pole
S201P-Z0.5
S201P-Z1
S201P-Z1.6
S201P-Z2
S201P-Z3
S201P-Z4
S201P-Z6
S201P-Z8
S201P-Z10
S201P-Z16
S201P-Z20
S201P-Z25
S201P-Z32
S201P-Z40
S201P-Z50
S201P-Z63
$ 70
70
70
70
70
70
70
70
70
70
70
70
74
78
88
100
S202P-Z0.5
S202P-Z1
S202P-Z1.6
S202P-Z2
S202P-Z3
S202P-Z4
S202P-Z6
S202P-Z8
S202P-Z10
S202P-Z16
S202P-Z20
S202P-Z25
S202P-Z32
S202P-Z40
S202P-Z50
S202P-Z63
162
162
162
162
162
162
162
162
162
162
162
170
170
176
206
232
S203P-Z0.5
S203P-Z1
S203P-Z1.6
S203P-Z2
S203P-Z3
S203P-Z4
S203P-Z6
S203P-Z8
S203P-Z10
S203P-Z16
S203P-Z20
S203P-Z25
S203P-Z32
S203P-Z40
S203P-Z50
S203P-Z63
244
244
244
244
244
244
244
244
244
244
244
248
254
266
306
344
B
10
4.5
S202P-Z, 2 pole
B
5
9.2
S203P-Z, 3 pole
Z
Sugg.
order
qty
B
10
4.6
B
5
9.2
Wgt. oz.
(1 pc.)
0.5
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
S281UC-Z0.5
S281UC-Z1
S281UC-Z1.6
S281UC-Z2
S281UC-Z3
S281UC-Z4
S281UC-Z6
S281UC-Z8
S281UC-Z10
S281UC-Z16
S281UC-Z20
S281UC-Z25
S281UC-Z32
S281UC-Z40
S281UC-Z50
S281UC-Z63
$ 168
168
168
168
168
168
168
168
168
168
168
170
176
188
216
242
0.5
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
S282UC-Z0.5
S282UC-Z1
S282UC-Z1.6
S282UC-Z2
S282UC-Z3
S282UC-Z4
S282UC-Z6
S282UC-Z8
S282UC-Z10
S282UC-Z16
S282UC-Z20
S282UC-Z25
S282UC-Z32
S282UC-Z40
S282UC-Z50
S282UC-Z63
390
390
390
390
390
390
390
390
390
390
390
398
410
426
498
558
B
1
13.9
0.5
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
S283UC-Z0.5
S283UC-Z1
S283UC-Z1.6
S283UC-Z2
S283UC-Z3
S283UC-Z4
S283UC-Z6
S283UC-Z8
S283UC-Z10
S283UC-Z16
S283UC-Z20
S283UC-Z25
S283UC-Z32
S283UC-Z40
S283UC-Z50
S283UC-Z63
594
594
594
594
594
594
594
594
594
594
594
603
612
657
756
855
14
B
3
13.9
UC-Z
10,000
10,000
5000
5000
1000
500
1000
500
100
50
100
50
10
5
10
5
1
0.5
seconds
seconds
Delivery
class
3 pole
3 pole
0.5
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
List
price
2 pole
2 pole
0.5
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
Catalog
number
1 pole
1 pole
0.5
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
Rated
current
AC
0.1
0.05
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
1
0.5
0.1
0.05
DC
DC
0.01
0.01
1
2
3
5
10
20 30
multiple of rated current
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
1
2
3
5
10
20 30
multiple of rated current
Discount schedule CB7
14.13
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 200
S
S200U
240 VAC
Miniature MCCBs
14
K
UL 489
CSA C22.2 - NO. 5
VDE 0660
Cable & equipment protection
Rated
current
Catalog
number
List
price
S201U-K0.2
S201U-K0.3
S201U-K0.5
S201U-K0.75
S201U-K1
S201U-K1.6
S201U-K2
S201U-K3
S201U-K4
S201U-K5
S201U-K6
S201U-K8
S201U-K10
S201U-K13
S201U-K15
S201U-K16
S201U-K20
S201U-K25
S201U-K30
S201U-K32
S201U-K40
S201U-K50
S201U-K60
S201U-K63
$ 54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
56
58
58
64
70
80
80
S202U-K0.2
S202U-K0.3
S202U-K0.5
S202U-K0.75
S202U-K1
S202U-K1.6
S202U-K2
S202U-K3
S202U-K4
S202U-K5
S202U-K6
S202U-K8
S202U-K10
S202U-K13
S202U-K15
S202U-K16
S202U-K20
S202U-K25
S202U-K30
S202U-K32
S202U-K40
S202U-K50
S202U-K60
S202U-K63
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
130
134
134
134
162
182
182
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
30
32
40
50
60
63
S201U-K, 1 pole
S202U-K, 2 pole
14
S203U-K, 3 pole
S204U-K, 4 pole
K
Catalog
number
List
price
S203U-K0.2
S203U-K0.3
S203U-K0.5
S203U-K0.75
S203U-K1
S203U-K1.6
S203U-K2
S203U-K3
S203U-K4
S203U-K5
S203U-K6
S203U-K8
S203U-K10
S203U-K13
S203U-K15
S203U-K16
S203U-K20
S203U-K25
S203U-K30
S203U-K32
S203U-K40
S203U-K50
S203U-K60
S203U-K63
$ 194
194
194
194
194
194
194
194
194
194
194
194
194
194
194
194
194
196
200
200
214
246
280
280
S204U-K0.2
S204U-K0.3
S204U-K0.5
S204U-K0.75
S204U-K1
S204U-K1.6
S204U-K2
S204U-K3
S204U-K4
S204U-K5
S204U-K6
S204U-K8
S204U-K10
S204U-K13
S204U-K15
S204U-K16
S204U-K20
S204U-K25
S204U-K30
S204U-K32
S204U-K40
S204U-K50
S204U-K60
S204U-K63
265
265
265
265
265
265
265
265
265
265
265
265
265
265
265
265
265
275
285
285
314
343
392
392
Delivery
class
Sugg.
order
qty
A
1
13.9
B
1
18.0
Wgt. oz.
(1 pc.)
3 pole
A
10
4.6
2 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
30
32
40
50
60
63
Rated
current
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
30
32
40
50
60
63
4 pole
A
5
9.2
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
30
32
40
50
60
63
10,000
5000
Delivery Class
1000
500
h
nc e
a
r
c
s b devi
a
e
ed
ist tectiv
l
9
48 t pro
L
U cui
cir
100
50
seconds
10
5
1
0.5
AC
0.1
0.05
DC
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
0.01
1
2
3
5
8 10 12
20 30
multiple of rated current
14.14
1SXU 000 023 C0201
Discount schedule CB12
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
S200U
240 VAC
Miniature MCCBs
Z
UL 489
CSA C22.2 - NO. 5
VDE 0660
Cable & equipment protection
Rated
current
Catalog
number
List
price
S201U-Z0.5
S201U-Z0.75
S201U-Z1
S201U-Z1.6
S201U-Z2
S201U-Z3
S201U-Z4
S201U-Z5
S201U-Z6
S201U-Z8
S201U-Z10
S201U-Z15
S201U-Z16
S201U-Z20
S201U-Z25
S201U-Z30
S201U-Z32
S201U-Z40
S201U-Z50
S201U-Z60
S201U-Z63
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
74
74
78
88
100
100
S202U-Z0.5
S202U-Z0.75
S202U-Z1
S202U-Z1.6
S202U-Z2
S202U-Z3
S202U-Z4
S202U-Z5
S202U-Z6
S202U-Z8
S202U-Z10
S202U-Z15
S202U-Z16
S202U-Z20
S202U-Z25
S202U-Z30
S202U-Z32
S202U-Z40
S202U-Z50
S202U-Z60
S202U-Z63
162
162
162
162
162
162
162
162
162
162
162
162
162
162
170
170
170
176
206
232
232
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
30
32
40
50
60
63
S201U-Z, 1 pole
S202U-Z, 2 pole
S203U-Z, 3 pole
Catalog
number
List
price
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
3 pole
A
10
4.6
2 pole
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
30
32
40
50
60
63
Rated
current
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
30
32
40
50
60
63
S203U-Z0.5
S203U-Z0.75
S203U-Z1
S203U-Z1.6
S203U-Z2
S203U-Z3
S203U-Z4
S203U-Z5
S203U-Z6
S203U-Z8
S203U-Z10
S203U-Z15
S203U-Z16
S203U-Z20
S203U-Z25
S203U-Z30
S203U-Z32
S203U-Z40
S203U-Z50
S203U-Z60
S203U-Z63
244
244
244
244
244
244
244
244
244
244
244
244
244
244
248
254
254
266
306
344
344
A
1
13.9
S204U-Z0.5
S204U-Z0.75
S204U-Z1
S204U-Z1.6
S204U-Z2
S204U-Z3
S204U-Z4
S204U-Z5
S204U-Z6
S204U-Z8
S204U-Z10
S204U-Z15
S204U-Z16
S204U-Z20
S204U-Z25
S204U-Z30
S204U-Z32
S204U-Z40
S204U-Z50
S204U-Z60
S204U-Z63
343
343
343
343
343
343
343
343
343
343
343
343
343
343
343
363
363
382
431
490
490
B
1
18.0
4 pole
A
5
9.2
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
30
32
40
50
60
63
Delivery Class
S204U-Z, 4 pole
h
nc e
a
r
c
s b devi
a
e
ed
ist tectiv
l
9
48 t pro
L
U cui
cir
Z
10,000
5000
1000
500
100
50
seconds
10
5
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
10
20 30
multiple of rated current
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule CB12
14.15
1SXU 000 023 C0201
14
M
o
pr ies
em Ser
st
Sy 200
S
S200UP
480Y/277 VAC
Miniature MCCBs
14
K
UL 489
CSA C22.2 - NO. 5
VDE 0660
Cable & equipment protection
Rated
current
Catalog
number
List
price
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
S201UP-K, 1 pole
S202UP-K, 2 pole
14
S203UP-K, 3 pole
Catalog
number
List
price
Delivery
class
Sugg.
order
qty
A
1
13.9
B
1
18.0
Wgt. oz.
(1 pc.)
3 pole
S201UP-K0.2
S201UP-K0.3
S201UP-K0.5
S201UP-K0.75
S201UP-K1
S201UP-K1.6
S201UP-K2
S201UP-K3
S201UP-K4
S201UP-K5
S201UP-K6
S201UP-K8
S201UP-K10
S201UP-K13
S201UP-K15
S201UP-K16
S201UP-K20
S201UP-K25
$ 90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
S202UP-K0.2
S202UP-K0.3
S202UP-K0.5
S202UP-K0.75
S202UP-K1
S202UP-K1.6
S202UP-K2
S202UP-K3
S202UP-K4
S202UP-K5
S202UP-K6
S202UP-K8
S202UP-K10
S202UP-K13
S202UP-K15
S202UP-K16
S202UP-K20
S202UP-K25
210
210
210
210
210
210
210
210
210
210
210
210
210
210
210
210
210
210
A
10
4.6
2 pole
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
Rated
current
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
S203UP-K0.2
S203UP-K0.3
S203UP-K0.5
S203UP-K0.75
S203UP-K1
S203UP-K1.6
S203UP-K2
S203UP-K3
S203UP-K4
S203UP-K5
S203UP-K6
S203UP-K8
S203UP-K10
S203UP-K13
S203UP-K15
S203UP-K16
S203UP-K20
S203UP-K25
$ 320
320
320
320
320
320
320
320
320
320
320
320
320
320
320
320
320
320
S204UP-K0.2
S204UP-K0.3
S204UP-K0.5
S204UP-K0.75
S204UP-K1
S204UP-K1.6
S204UP-K2
S204UP-K3
S204UP-K4
S204UP-K5
S204UP-K6
S204UP-K8
S204UP-K10
S204UP-K13
S204UP-K15
S204UP-K16
S204UP-K20
S204UP-K25
440
440
440
440
440
440
440
440
440
440
440
440
440
440
440
440
440
440
4 pole
A
5
9.2
0.2
0.3
0.5
0.75
1
1.6
2
3
4
5
6
8
10
13
15
16
20
25
Delivery Class
h
nc e
a
r
c
s b devi
a
e
ed
ist tectiv
l
9
48 t pro
L
U cui
cir
S204UP-K, 4 pole
K
10,000
5000
1000
500
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
100
50
seconds
10
5
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
8 10 12
20 30
multiple of rated current
14.16
1SXU 000 023 C0201
Discount schedule CB17
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
S200UP
480Y/277 VAC
Miniature MCCBs
Z
UL 489
CSA C22.2 - NO. 5
VDE 0660
Cable & equipment protection
Rated
current
Catalog
number
List
price
Delivery
class
Sugg.
order
qty
Wgt. oz.
(1 pc.)
1 pole
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
S201UP-Z, 1 pole
S202UP-Z, 2 pole
Catalog
number
List
price
Delivery
class
Sugg.
order
qty
A
1
13.9
B
1
18.0
Wgt. oz.
(1 pc.)
3 pole
S201UP-Z0.5
S201UP-Z0.75
S201UP-Z1
S201UP-Z1.6
S201UP-Z2
S201UP-Z3
S201UP-Z4
S201UP-Z5
S201UP-Z6
S201UP-Z8
S201UP-Z10
S201UP-Z15
S201UP-Z16
S201UP-Z20
S201UP-Z25
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
S202UP-Z0.5
S202UP-Z0.75
S202UP-Z1
S202UP-Z1.6
S202UP-Z2
S202UP-Z3
S202UP-Z4
S202UP-Z5
S202UP-Z6
S202UP-Z8
S202UP-Z10
S202UP-Z15
S202UP-Z16
S202UP-Z20
S202UP-Z25
270
270
270
270
270
270
270
270
270
270
270
270
270
270
270
A
10
4.6
2 pole
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
Rated
current
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
S203UP-Z0.5
S203UP-Z0.75
S203UP-Z1
S203UP-Z1.6
S203UP-Z2
S203UP-Z3
S203UP-Z4
S203UP-Z5
S203UP-Z6
S203UP-Z8
S203UP-Z10
S203UP-Z15
S203UP-Z16
S203UP-Z20
S203UP-Z25
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
S204UP-Z0.5
S204UP-Z0.75
S204UP-Z1
S204UP-Z1.6
S204UP-Z2
S204UP-Z3
S204UP-Z4
S204UP-Z5
S204UP-Z6
S204UP-Z8
S204UP-Z10
S204UP-Z15
S204UP-Z16
S204UP-Z20
S204UP-Z25
564
564
564
564
564
564
564
564
564
564
564
564
564
564
564
4 pole
A
5
9.2
0.5
0.75
1
1.6
2
3
4
5
6
8
10
15
16
20
25
14
Delivery Class
S203UP-Z, 3 pole
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
ch
n
a
br evice
s
d a ive d
e
t
t
is
9 l rotec
8
4
p
UL cuit
cir
S204UP-Z, 4 pole
Z
10,000
5000
1000
500
100
50
seconds
10
5
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
10
20 30
multiple of rated current
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule CB17
14.17
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 200
S
S290
480Y/277 VAC
14
VDE 0660
Cable and equipment protection
C
480 VAC
Rated
current
List
price
Delivery
class
Sugg.
order
qty
S291-C80
S291-C100
S291-C125
$ 138
144
192
B
6
9.2
S292-C80
S292-C100
S292-C125
340
364
568
B
3
18.4
S293-C80
S293-C100
S293-C125
536
548
732
B
2
27.6
S294-C80
S294-C100
S294-C125
740
756
948
B
1
36.8
72
B
1
1.75
112
B
1
1.75
144
B
1
6.2
B
1
6.2
Catalog
number
Wgt. oz.
(1 pc.)
1 pole
80
100
125
2 pole
80
100
125
S291-C80
3 pole
80
100
125
4 pole
80
100
125
Auxiliary contact
S290-H11
S290-H11
Bell alarm
S290-S
Shunt trip
S290-A1
For field mounting, left side, 110V – 415VAC
S290-A2
144
For field mounting, left side, 24 – 48VDC
14
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
C
10,000
5000
1000
500
100
50
seconds
10
5
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
10
18 20 30
multiple of rated current
14.18
1SXU 000 023 C0201
Discount schedule CB12
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14
Sy
s
S2 tem
00 p
Se ro M
rie
s
Accessories
Busbars
0HASE
AmpNumber
For of
rating
use on:
poles
S200 &
S200P 1
,
,
BusbarEnd cap
Catalog
ListDelivery
length
catalog
number
price
class
(mm)
number
63
80
60
60
988
988
S200U &
S200UP
80
23
6
12
18
108
216
324
PS-END0 PS1/60
PS-END0 PS1/60/16
–
–
–
PS1/6/16BP
PS1/12/16BP
PS1/18/16BP
Suggested Weight
order qty. (ozs)
quantity
$ 36
1
A
46
9
14
30 60
B
1
90
1.4
2.9
4.3
0HASE
AmpNumber BusbarEnd cap
Catalog
ListDelivery
For of
length
catalog
rating
number
price
class
use on:
poles
(mm)
number
63
80
58
58
1035
1035
PS-ENDSP
PS-ENDSP
PS2/58SP
PS2/58/16SP
$ 122
152
A
1
11
18
S200U &
S200UP
80
23
6
12
18
108
216
324
–
–
–
PS2/6/16BP
PS2/12/16BP
PS2/18/16BP
40 80
B
1
120
1.8
3.7
5.5
S200 &
S200P 1
,
,
Suggested Weight
order qty.
(ozs)
quantity
, , , ,
0HASE
AmpNumber BusbarEnd cap
Catalog
ListDelivery
For
of
length
catalog
rating
number
price
class
use on:
poles
(mm)
number
,
,
,
S200 &
S200P 1
63
80
60
60
1065
1065
S200U &
S200UP
80
23
6
12
18
108
216
324
PS-ENDSP PS3/60SP
PS-ENDSP PS3/60/16SP
–
–
–
PS3/6/16BP
PS3/12/16BP
PS3/18/16BP
Suggested
order qty.
quantity
Weight
(ozs)
$ 130
A
1
176
12
20
44
88
B
1
132
2
4
6
, , , , , ,
0HASE
AmpNumber BusbarEnd cap
Catalog
ListDelivery
For
of
length
catalog
rating
number
price
class
use
on:
poles
(mm)
number
,
,
,
Suggested
order qty.
quantity
Weight
(ozs)
S200 &
$ 236
80
60
1056 PS-END1SP PS4/60/16SP
B
1
S200P
22
Delivery Class
,
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
, , , , , , , ,
NOTE
All bus bars may be center fed in
order to double the ampacity rating
NOTE
BUS BARS MAY BE USED ON LINE OR LOAD
SIDE OF MCBS
1 UL Approved for use on UL1077 miniature circuit breakers. UL File #E76126
2 UL approved for use on UL 489 miniature circuit breakers. UL File # E250145
3 UL 489 bus bars may not be cut.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule CB8
14.19
1SXU 000 023 C0201
14
14
M
o
pr ies
em er
st 0 S
y
S 20
S
Accessories
Busbars
1 Phase with 1 auxiliary
AmpNumber
For
of
rating
use
on:
poles
S200 &
S200P
63
80
38
38
BusbarEnd cap
Catalog
ListDelivery
length
catalog
number
price
class
(mm)
number
1044
1044
PS-END0
PS-END0
Suggested Weight
order qty.
(ozs)
quantity
PS1/38H
$ 50
1
B
PS1/38/16H
56
7.4
10.1
L1
L1
L1
L1....
2 Phase with 1 auxillary
0HASE
AmpNumber
For
of
rating
use
on:
poles
, , , , , ,
,
L1
L1 L2
L1 L2
,
,
80
48
1065
PS-ENDSP PS2/48/16SP $ 174
Suggested Weight
order qty.
(ozs)
quantity
B
1
23.3
L2
L1 L2....
3 Phase with 1 auxillary
0HASE
AmpNumber
For
of
rating
use
on:
poles
,
200 &
S
S200P
,
L1
L2
14
L1 L2 L3
200 &
S
S200P
BusbarEnd cap
Catalog
ListDelivery
length
catalog
number
price
class
(mm)
number
80
39
BusbarEnd cap
Catalog
ListDelivery
length
catalog
number
price
class
(mm)
number
980
PS-ENDSP PS3/39/16SP $ 158
B
Suggested Weight
order qty.
(ozs)
quantity
1
22.6
L3
L1 L2 L3....
0HASE.FORUSEWITHPOLE-#"gS
ONPHASE7SYSTEM
AmpNumber
For
of
rating
use on:
poles
200 &
S
S200P
80
58
BusbarEnd cap
Catalog
ListDelivery
length
catalog
number
price
class
(mm)
number
1048
PS-END1SPPS4/58/16NSP $ 238
B
Suggested Weight
order qty.
(ozs)
quantity
1
30.8
Insulated busbar assembly contains 4 separate circuits for use with 1+N or 2 pole MCBs.
.
,
,
,
Delivery Class
, .
, .
, .
, .
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
,
-#""USBARACCESSORIES
"USBARMOUNTED
NOTE
TERMINALBLOCK
"USTOOTHCOVERS
PN3:%3+POLE
All
bus bars may bePN3:"3+POLES
center fed in
order to double the ampacity rating
NOTE
BUS BARS MAY BE USED ON LINE OR LOAD
SIDE OF MCBS"USBAR%ND#APS
14.20
1SXU 000 023 C0201
Discount schedule CB8
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14
Sy
s
S2 tem
00 p
Se ro M
rie
s
Accessories
Electrical
accessories
For
use on:
Catalog number
List price
Delivery class
Suggested
order quantities
Wgt. oz.
(1 pc.)
Auxiliary contacts
For field mounting: right side
S200 &
S2C-H6R
Form C 1 NO / 1 NC
S200P
$ 36
A
1
S200U
S2C-H6RU
S200UP
S2C-H6R
1.4
The auxiliary contacts will signal whether the breaker is in the ON or OFF position. The contacts are rated 2A/277 VAC and 1.5A/125 VDC.
Minimum operating voltage is 24 VAC/VDC.
Wire size: 18 AWG to 16 AWG.
Bell alarm
S200 &
S2C-S/H6R
S200P
A
1
For field mounting, right side
48
S200U
S2C-S6RU
S200UP
S2C-S/H6R
1.4
The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically the contacts would be connected to an alarm
or bell to signal the operator that an overcurrent trip has occured. The bell alarm also includes a test button for testing the alarm contacts without
opening the breaker. The contact is rated 2A/277 VAC and 1.5A/125 VDC. Minimum operating voltage is 24 VAC/VDC.
* Combination bell alarm/auxiliary contact
Shunt trip
S200 & S2C-A1
For field mounting, right side
S200P
S2C-A2
A1: 12-60 VAC (12-60VDC)
A2: 110-415 VAC (110-250 VDC)
S200U & S2C-A1U
S200UP S2C-A2U
138
A
1
5.2
For remote tripping of breaker, a shunt trip device can be added to the MCB. The solenoid device opens the breaker after control voltage is
applied. Shunt trips are available for on control system voltage (12-415 VAC/VDC).
S2C-A_
Undervoltage release
For field mounting, right side
12 VDC
24 VAC
48 VAC
S200 &
110 VAC
S200P
220 VAC
415 VAC
S2C-UA12
S2C-UA24
S2C-UA48
216
S2C-UA110
S2C-UA230
S2C-UA400
A
1
5.2
When control voltage drops below approximately 50% of rated voltage, the UVR opens the breaker. The breaker can not be operated unless
proper control voltage is first applied to the UVR coil. Similar in size and mounting to the shunt trip accessory.
Delivery Class
S2C-UA_
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule CB8
9/6/07 Rev.
14.21
1SXU 000 023 C0201
14
M
o
pr ies
em Ser
st
Sy 200
S
14
Accessories
S200
Electrical
accessories
Catalog
number
List
price
Delivery
class
Suggested
order quantities
Wgt. oz.
(1 pc.)
S500-ME1
S500-ME2
S500-ME3
S500-K1
$ 60
70
80
16
A
1
2.1
2.9
3.6
1.5
MB-CL
35
A
1
2
MB-3PD
35
A
1
2.5
SA1
SA2
9
19
A
10
0.7
0.1
BS
BS1/40
74
74
A
1
—
12402
12404
12406
12408
32
45
56
66
B
1
2.0
2.8
3.4
4.1
84
98
126
210
A
1
8.1
10.8
20.4
41.0
BP-1P
BP-12P
6
7
A
—
1
—
—
—
S2C-DH
76
A
1
9.2
21
A
1
8
Front mounting kit
For 2 poles
For 2 – 5 poles
For 2 – 10 poles
Optional rear terminals
S500-ME2
Includes flange, mounting rail and hardware.
Front mounting clip
For 1 – 4 poles
Simple mounting clip for up to four module mounting.
Front mounting bracket
For 1 – 3 poles
For flush mounting of three pole MCBs: includes hardware.
MB-CL
Locking device
Adaptor only
Padlock only w/ 2 keys
Allows breaker to be locked in ON or OFF position.
Labeling accessory
MB-3PD
1 sheet = 40 blank labels
1 sheet = 40 numbered labels
Adhesive labels mount on front face of components.
Enclosure, IP40
SA1
For 2 modules
For 4 modules
For 6 modules
For 8 modules
For additional protection against accidental contact. Includes integrated mounting rail.
Enclosure, IP55
14
SA2
For 4 modules
For 6 modules
For 10 modules
For 20 modules
12644
12646
12650
12652
Molded plastic complete with mounting rail and knock-outs for cable entries.
Blanking plates
Single pole (set of 10)
Twelve pole (snap-off, set of 1)
12404
Handle mechanism
For use with 2, 3 and 4 pole S2 MCBs and disconnect switch handles with 5mm shaft.
DIN rail
Universal mounting
SMR-39
35mm DIN rails are available in 39-inch strips (1 meter).
S2C-DH
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
SMR-39
14.22
1SXU 000 023 C0201
Discount schedule CB8
Discount schedule H6 – Handles & shafts
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14
Sy
s
S2 tem
00 p
Se ro M
rie
s
Accessories
S200
Busbar accessories
Catalog
List
Delivery
Suggested
Description
number
price
class
order qty.
Busbar end caps
SZ-BSK
2 & 3 phase
4 phase
PS-ENDSP
PS-END1SP
Weight
ounce
qty. (2 pc.)
$ 2
A
10
—
Busbar tooth covers
(shrouds unused portion of busbar)
SZ-BSK
4
A
10
—
Busbar mounted terminal block,
1 pole, for use on all busbars.
Wire size: 14 AWG to 2 AWG
SZ-ESK2
10
A
1
1.0
Delivery class
Suggested
order quantities
Wgt. oz.
(1 pc.)
Electrical accessories
Item
Catalog number
List price
Posidrive tools
SZ-ESK2
Screwdriver, #1
Screwdriver, #2
Bit, #1
Bit, #2
SD-PZ1
SD-PZ2
BIT-PZ1
BIT-PZ2
$ 40
40
4
4
A
A
A
A
1
1
1
1
4
4
4
4
List price
Delivery class
Suggested
order quantities
Wgt. oz.
(1 pc.)
$ 15
B
15
10
10
0.5
0.5
15
B
15
10
10
0.5
0.5
Connection terminals
SZ-AST55_
Cross section
AWG/mm2
For
use on:
Catalog
number
1/0 (50mm2) Straight
S200 & S200P
2
1/0 (50mm ) 90°
SZ-AST55I
SZ-AST50I
1/0 (50mm2) Straight
S200U & S200UP
1/0 (50mm2) 90°
SZ-AST55U
SZ-AST50U
Ring tongue accessories
Catalog
List
Delivery
Description
For use on
number
price
class
Ring tongue terminal
S200 & S200P
S200U & S200UP
Plug
SZ-AST55UPRT
S2C-P
Suggested
order qty.
qty. (2 pc.)
Weight
ounce
$ 5
A
10
0.5
N/C
A
10
—
SZ-AST50_
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule CB8
9/6/07 Rev.
14.23
1SXU 000 023 C0201
14
M
o
pr ies
em Ser
st
Sy 200
S
14
Technical data
Mounting and operating instructions
Mounting
Operation
Universal mounting position using snap-on
mounting to standard 35x7.5mm DIN rail.
MCBs are switched on by moving the handle to the
upper position. Stamped onto the handle switch, a
“I” is visible confirming that the breaker is closed.
Miniature circuit breakers (MCBs) can also be
mounted to front of door using a panel cut-out with
breaker handle protruding through panel opening
for external operation. Special front mounting kit
page 23.
Mounting MCB
Connection
Terminals are suitable for solid or flexible
conductors from 18 to 4 AWG (0.75 to 25mm2) with
no busbar connected. When maximum busbar size
of 36 mm2 is used, maximum cable is 6 AWG (16
mm2).
Maximum tightening torque of 17.5 in-lb (2 Nm)
for line/load terminals and 4.5 in-lb (0.5Nm) for
accessory device terminals.
The MCBs are “trip-free,” if the handle is being
forced to the “ON” position, the breaker will still trip
under fault conditions.
The “O” marking indicates that the breaker is in the
“OFF” position. The MCB is now open and the load
is disconnected from line power.
When a breaker has tripped, the MCB handle should
first be set to the full “OFF” position to make certain
the trip mechanism has been reset. Once the fault
has been determined and cleared the MCB can
again be switched “ON”.
Maintenance
ABB miniature circuit breakers require no special
maintenance; only normal electrical system
maintenance procedures are required.
Removing MCB
Possible mounting arrangements of MCB accessories
Legend
+S/H+S/H (H)+S/H (H)
S 200
Auxiliary contact
Bell alarm/Auxiliary contact
H
S/H
Bell alarm/Auxiliary contact
used as auxiliary contact S/H (H)
+H+H+H
14
Shunt trip
ST
Undervoltage release
UR
+ST+H+H+H
+ST+S/H+S/H (H)+S/H (H)
+UR+H+H+H
+UR+S/H+S/H (H)+S/H (H)
14.24
1SXU 000 023 C0201
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Technical data
Busbars & connectors
Connection methods
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
Top and bottom dual function terminals
provided in open position for connection to
busbars or cable.
Terminals allow for connection of cable
18-4 AWG [top row] and 18-8 AWG [bottom
row].
Two slots per terminal offer the ability to
connect, independently, two conductors.
This may be cables or bus bar.
Top and bottom terminals may be bussed
together with single phase or multi-phase
busbars as shown. Both line and load side
terminals can be bus bar connected.
Easy removal of devices from an assembly
when using bus bar in the bottom, load side
terminals.
Conductors may only be inserted into open
terminals, preventing mis-wiring and potential
problems.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14
14.25
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 200
S
Technical data
14
S200-B
S200-C, -D
S200-K
Approvals:
UL
CSA
VDE
IEC
Item
1077
C22.2 — No.235
0641, 0660
898, 947
1077
C22.2 — No. 235
0660
898, 947
1077
C22.2 — No. 235
0660
898, 947
1077
—
0660
898, 947
No. of poles:
1,2,3,4 1+N,3+N
1,2,3, 1+N,3+N
1,2,3,4, 1+N,3+N
1,2,3,4,1+N,3+N
Tripping characteristic:
Rated currents:
Minimum operating voltage:
120VAC
C,D
K
K
0.5 to 63A
0.5 to 63A
0.2 to 63A
12V
12V
12V
Single pole
Multi pole
Single pole
Multi pole
Single pole
Multi pole
Single pole
Multi pole
10kA
—
10kA
—
10kA
—
10kA
—
10kA
240VAC
6kA
10kA
6kA
10kA
6kA
10kA
10kA
277VAC
6kA
—
6kA
—
6kA
—
10kA
—
—
6kA
—
6kA
—
6kA
—
10kA
277/480 VAC
60VDC
10kA
10kA
10kA
10kA
10kA
10kA
—
—
125VDC
—
10kA
—
10kA
—
10kA
—
—
Frequency:
50/60Hz (See below)
50/60Hz (see below)
50/60Hz (see below)
50/60Hz (see below)
240/415VAC
60VDC
415VAC
110VDC
240/415VAC
60VDC
415VAC
110VDC
240/415VAC
60VDC
415VAC
110VDC
240/415VAC
60VDC
415VAC
110VDC
Rated voltage
IEC single pole
IEC multi-pole
Protection category:
IP20
IP20
IP20
IP20
Depth of unit per DIN 43880:
68mm
68mm
68mm
68mm
Mounting position:
optional
optional
optional
optional
Standard mounting:
35mm DIN rail
35mm DIN rail
35mm DIN rail
35mm DIN rail
18-4 AWG [top]
18-8 [bottom]
17.5 in-lbs.
#2 Posidrive
18-4 AWG [top]
18-8 [bottom]
17.5 in-lbs.
#2 Posidrive
18-4 AWG [top]
18-8 [bottom]
17.5 in-lbs.
#2 Posidrive
18-4 AWG [top]
18-8 [bottom]
17.5 in-lbs.
#2 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
-25°C to +70°C
-40°C to + 70°C
-25°C to +70°C
-40°C to + 70°C
-25°C to +70°C
-40°C to + 70°C
-25°C to +70°C
-40°C to + 70°C
Shock resistance:
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
Vibration resistance:
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
6kA switching
6kA switching
6kA switching
—
Main and shunt trip terminals:
Wire size
14
B
6 to 63A
12V
UL/CSA rated voltage &
interrupting capacity
S200P-K
Torque
Tool
Accessory terminals
Wire size
Torque
Tool
Service life at rated load:
Ambient temperatures:
Storage temperatures
Disconnecting neutral rating:
Influence of frequency on electro-magnetic trips
Magnetic trip values shown on trip curves are valid for 50/60Hz applications.
For frequencies other than 50/60Hz, the magnetic (instantaneous) trip values are
increased by the factor given below:
16 2/3 - 60Hz 100Hz
Approx. factor
1
1.1
200Hz
400Hz
DC
1.2
1.5
1.5
Thermal tripping is independent of frequency.
14.26
1SXU 000 023 C0201
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
Technical data
Item
Approvals:
UL
CSA
VDE
IEC
S280UC-K
S200P-Z
S280UC-Z
S290-C
1077
—
0660
898,947
1077
—
0660
898, 947
1077
—
0660
898, 947
—
—
0660
898
1,2,3
1,2,3,4
1,2,3
1,2,3,4
No. of poles:
Tripping characteristic:
Rated currents:
K
Z
Z
C
0.2 to 63A
0.5 to 63A
0.5 to 63A
80 to 125A
12V
12V
Minimum operating voltage:
12V
UL/CSA rated voltage &
interrupting capacity
12V
Single pole
Multi pole
Single pole
Multi pole
Single pole
Multi pole
120VAC
10kA
—
10kA
—
10kA
—
—
240VAC
10kA
10kA
10kA
10kA
10kA
10kA
—
277VAC
10kA
—
10kA
—
10kA
—
—
—
4.5kA for 0.2-40A
5kA for 50-63A
—
10kA
—
4.5kA for 0.2-40A
5kA for 50-63A
—
60VDC
10kA
10kA
—
—
10kA
10kA
—
125VDC
10kA
10kA
—
—
10kA
10kA
—
250VDC
4.5kA
4.5kA
—
—
4.5kA
4.5kA
—
—
4.5kA
—
—
—
4.5kA
277/480 VAC
500VDC
Frequency:
Rated voltage
IEC single pole
—
50/60Hz (see below)
50/60 Hz (see below)
50/60Hz (see below)
50/60Hz (see below)
240/415VAC
220VDC
415VAC
440VDC
240/415VAC
60VDC
415VAC
110VDC
240/415VAC
220VDC
415VAC
440VDC
230/440VAC
60VDC
440VAC
110VDC
IEC multi-pole
Protection category:
IP20
IP20
IP20
IP20
Depth of unit per DIN 43880:
68mm
68mm
68mm
70mm
Mounting position:
optional
optional
optional
optional
Standard mounting:
35mm DIN rail
35mm DIN rail
35mm DIN-rail
35mm DIN-rail
14
Main and shunt trip terminals:
Wire size
0.2-40A
18-4 AWG
50A & above
18-2 AWG
17.5 in-lbs.
#2 Posidrive
Torque
Tool
Accessory terminals
Wire size
Torque
Tool
18-4 AWG [top]
18-8 AWG [bottom]
17.5 in-lbs.
#2 Posidrive
0.5-40A
18-4 AWG
18-2 AWG
17.5 in-lbs.
#2 Posidrive
80-125A
14-1/0 AWG
17.5 in-lbs.
#2 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
10,000 operations
––
-25°C to +55°C
-40°C to + 70°C
-25°C to +70°C
-40°C to + 70°C
-25°C to +55°C
-40°C to + 70°C
-5°C to +45°C
-40°C to + 70°C
Shock resistance:
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
Vibration resistance:
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
60m/s2, at 10 – 150 Hz
Service life at rated load:
Ambient temperatures:
Storage temperatures
Influence of frequency on electro-magnetic trips
Magnetic trip values shown on trip curves are valid for 50/60Hz applications.
For frequencies other than 50/60Hz, the magnetic (instantaneous) trip values are
increased by the factor given below:
16 2/3 - 60Hz 100Hz
Approx. factor
1
1.1
200Hz
400Hz
DC
1.2
1.5
1.5
Thermal tripping is independent of frequency.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.27
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 200
S
Technical data
14
Item
Approvals:
UL
CSA
VDE
IEC
No. of poles:
Tripping characteristic:
S200U-K
S200U-Z
S200UP-K
S200UP-Z
489
C22.2 No.5
0660
898,947
489
C22.2 No.5
0660
898, 947
489
C22.2 No.5
0660
898, 947
489
C22.2 No.5
0660
898
1,2,3,4
1,2,3,4
1,2,3,4
1,2,3,4
K
Z
K
Z
0.2 to 63A
0.2 to 63A
0.2 to 25A
0.2 to 25A
12V
12V
12V
12V
120VAC
10kA
10kA
10kA
10kA
240VAC
10kA
10kA
10kA
10kA
277VAC
10kA
10kA
480/277 VAC
—
—
10kA
10kA
Frequency:
Rated voltage
IEC single pole
50/60Hz (see below)
50/60 Hz (see below)
50/60Hz (see below)
50/60Hz (see below)
240/415VAC
220VDC
415VAC
440VDC
240/415VAC
60VDC
415VAC
110VDC
240/415VAC
220VDC
415VAC
440VDC
240/415VAC
220VDC
415VAC
440VDC
Rated currents:
Minimum operating voltage:
UL/CSA rated voltage &
interrupting capacity
IEC multi-pole
Protection category:
IP20
IP20
IP20
IP20
Depth of unit per DIN 43880:
68mm
68mm
68mm
68mm
Mounting position:
optional
optional
optional
optional
Standard mounting:
35mm DIN rail
35mm DIN rail
35mm DIN-rail
35mm DIN-rail
18-4 AWG [top]
18-8 AWG [bottom]
17.5 in-lbs.
#2 Posidrive
18-4 AWG [top]
18-8 AWG [bottom]
17.5 in-lbs.
#2 Posidrive
18-4 AWG [top]
18-8 AWG [bottom]
17.5 in-lbs.
#2 Posidrive
18-4 AWG [top]
18-8 AWG [bottom]
17.5 in-lbs.
#2 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
18-16 AWG
4.5 in-lbs.
#1 Posidrive
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
In < 32 A, 20,000 operations
In > 32 A, 10,000 operations
-25°C to +70°C
-40°C to + 70°C
-25°C to +70°C
-40°C to + 70°C
-25°C to +70°C
-40°C to + 70°C
-25°C to +70°C
-40°C to + 70°C
Shock resistance:
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
30g minimum of 2 impacts,
shock duration of 13ms
Vibration resistance:
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In
Main and shunt trip terminals:
Wire size
Torque
Tool
14
Accessory terminals
Wire size
Torque
Tool
Service life at rated load:
Ambient temperatures:
Storage temperatures
Influence of frequency on electro-magnetic trips
Magnetic trip values shown on trip curves are valid for 50/60Hz applications.
For frequencies other than 50/60Hz, the magnetic (instantaneous) trip values are
increased by the factor given below:
16 2/3 - 60Hz 100Hz
Approx. factor
1
1.1
200Hz
400Hz
DC
1.2
1.5
1.5
Thermal tripping is independent of frequency.
14.28
1SXU 000 023 C0201
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
Technical data
Wire size comparison
Comparison of IEC and AWG wire sizes
mm
AWG (mm )
Amps / UL
Amps / IEC
1.0
—
1.5
—
16 (1.3)
—
—
10
—
8
—
12
—
2.5
—
14 (2.1)
—
12 (3.3)
15
—
20
—
20
—
4
—
6
—
10 (5.3)
—
—
30
—
25
—
32
—
10
—
8 (8.4)
—
6 (13.3)
50
—
65
—
50
—
16
—
25
—
4 (21.2)
—
—
85
—
65
—
85
—
—
35
3 (26.7)
2 (33.6)
—
100
115
—
—
—
115
Ampacities for AWG wire are based on copper cable rated 75° C, except for 16AWG which is based on 60° C wire. Taken from UL508 Table 52.2.
Consult applicable standards for futher detail and information.
14
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.29
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 200
S
Approximate dimensions
S200, S200P, S200U, S200UP
14
00.00
Inches
00.00
[Millimeters]
S200 & S200P
S200U
S200UP
14
S290
Accessories mount to right side
of MCB only
1.77
45
1.97
1.03
50
26
1.06
27
2.13 54
0.69
17.5
0.35
0.35
9
9
-H
-S
Auxiliary
switch
Bell
alarm
3.19 81
-A1, -A2
Shunt
trip
14.30
1SXU 000 023 C0201
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
Approximate dimensions
Accessories
00.00
Inches
00.00
[Millimeters]
Accessories
mm
S 2C-H...
S 2C-S...
S 2C-S/H...
S 2C-A...
S 2C-UA...
45
69
85
8.8
45
69
85
17.5
6.8
6.8
44
MB-CL
Front mounting clip
44
mm
C.L.
1.77
45 D
2.26 1.77
57.5
C.L.
45
0.69
17.5
1.38
35
2.07
52.5
MB-3PD
Front mounting bracket
14
3.25
2.12 ( 3P )
in
1.43 ( 2P )
1.87
CL
C
L
BREAKER CUT OUT
0.74 ( 1P )
BKT. MT. HOLES
0.25 DIA. TYP 2
S2C-DH
Handle mechanism
CL
CL
0.63
16
2.07 52.5
0.83
21
1.38 35
3.54
90
4.36
110.4
1.77
45
3.26
82.5
0.27 6.9
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.31
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 200
S
14
Approximate dimensions
Accessories
00.00
Inches
00.00
[Millimeters]
12402-12408
12644
12650
4.92
4.92
125
125
4.92
4.13
125
230
4.13
105
9.06
105
7.09
7.09
180
180
14
12646
12652
6.09
155
4.92
9.84
250
5.32
125
6.30
4.13
135
160
105
7.09
180
12.60
320
14.32
1SXU 000 023 C0201
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S2 tem
00 p
Se ro M
rie
s
14
Cross-reference
Older
version
Suggested
replacement
series
Physical
comparison
Electrical
comparison
S260-B
S200-B
Same pole spacing
S260-C
S200-C
Same pole spacing
Same trip characteristic
S260-D
S200-D
Same pole spacing
Same trip characteristic
S270-K
S200-K
Same pole spacing
Same trip characteristic
S280-K
S200P-K
Same pole spacing
Same trip characteristic
S280-Z
S200P-Z
Same pole spacing
Same trip characteristic
S280U-K
S200U-K
Same pole spacing
Same trip characteristic
S280UX-K
S200U-K
Smaller pole spacing
Same trip characteristic
Same trip characteristic
Many older styles of ABB miniature circuit breakers have been replaced by new and improved versions. Many of these newer styles can be directly interchanged, both
electrically and physically, with the older version. There are also many international styles of ABB circuit breakers which are not normal stock items and may be interchanged with stocked ABB versions.
14
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.33
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 200
S
14
Notes
14
14.34
1SXU 000 023 C0201
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
S
ys
System pro M compact
S5 tem
Miniature Circuit Breakers 00 Se pro M
rie
s
S500 Series
14
Description
Features
Increasing energy requirements result in
larger short-circuit currents which place
heavy demands on protective switchgear
regarding safety, reliability and switching
capacities.
The S500 heavy-duty circuit breaker fulfills
these requirements by virtue of its technical
features. It is equipped with a thermal and/or
electromagnetic release to protect circuits,
motors, switchgear and systems from the
effects of overload and short-circuit currents.
For the worldwide market, the S500 breakers
carry UL, CSA, IEC, CE and many other
agency approvals.
•
•
•
•
•
•
•
•
•
•
•
High breaking capacity
Energy-limiting
Current-limiting
Extremely fast breaking time
Optimal selectivity
Various versions for special applications
Compact dimensions, DIN cap size
Easy and quick to install
Easy to connect; finger safe terminals
Wide range of accessories
UL 1077 recognized 600VAC and
500VDC versions
UL File # E167556
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.35
1SXU 000 023 C0201
14
S500
600Y/277 VAC
M
o
pr ies
em Ser
st
Sy 500
S
14
B
UL 1077
VDE 0641
Rated
current
C
CSA C22.2
IEC 947-2
Catalog
number
List
price
Delivery
class
Weight
(oz.) 1 pc
6
10
13
16
20
25
32
40
50
63
S501-B6
S501-B10
S501-B13
S501-B16
S501-B20
S501-B25
S501-B32
S501-B40
S501-B50
S501-B63
$ 168
168
168
168
168
168
168
168
186
202
S502-B6
S502-B10
S502-B13
S502-B16
S502-B20
S502-B25
S502-B32
S502-B40
S502-B50
S502-B63
328
328
328
328
328
328
328
328
362
392
S503-B6
S503-B10
S503-B13
S503-B16
S503-B20
S503-B25
S503-B32
S503-B40
S503-B50
S503-B63
478
478
478
478
478
478
478
478
526
574
B
8.90
6
10
13
16
20
25
32
40
50
63
B
17.85
6
10
13
16
20
25
32
40
50
63
B
10,000
5000
1000
500
D
100
50
seconds
List
price
AC
0.1
0.05
DC
0.01
1
2
3
5
7 10
20 30
multiple of rated current
C
6
10
13
16
20
25
32
40
50
63
B
25.36
6
10
13
16
20
25
32
40
50
63
$ 168
168
168
168
168
168
168
168
184
202
B
8.90
S502-C6
S502-C10
S502-C13
S502-C16
S502-C20
S502-C25
S502-C32
S502-C40
S502-C50
S502-C63
328
328
328
328
328
328
328
328
362
392
B
17.85
S503-C6
S503-C10
S503-C13
S503-C16
S503-C20
S503-C25
S503-C32
S503-C40
S503-C50
S503-C63
478
478
478
478
478
478
478
478
526
574
B
25.36
CSA C22.2
IEC 947-1
Catalog
number
Delivery Class
List
price
Delivery
class
Wgt. oz.
(1 Pc.)
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
13
16
20
25
32
40
50
63
S501-D13
S501-D16
S501-D20
S501-D25
S501-D32
S501-D40
S501-D50
S501-D63
$ 190
190
190
190
190
190
210
226
S502-D13
S502-D16
S502-D20
S502-D25
S502-D32
S502-D40
S502-D50
S502-D63
372
372
372
372
372
372
408
442
S503-D13
S503-D16
S503-D20
S503-D25
S503-D32
S503-D40
S503-D50
S503-D63
544
544
544
544
544
544
600
646
D
10,000
5000
B
13
16
20
25
32
40
50
63
5000
1000
500
100
50
10
5
100
50
10
5
B
17.85
1
0.5
AC
0.1
0.05
DC
0.01
2
3
5
10
18 20 30
13
16
20
25
32
40
50
63
1
0.5
AC
0.1
0.05
DC
0.01
1
3 pole
1
1000
500
8.90
2 pole
10,000
Delivery Weight
class (oz.) 1 pc
S501-C6
S501-C10
S501-C13
S501-C16
S501-C20
S501-C25
S501-C32
S501-C40
S501-C50
S501-C63
1 pole
1
0.5
seconds
UL 1077
VDE 0641
Rated
current
10
5
6
10
13
16
20
25
32
40
50
63
seconds
14
Catalog
number
3 pole
3 pole
S503-C10
Rated
current
2 pole
2 pole
S502-C6
CSA C22.2
IEC 947-2
1 pole
1 pole
S501-C16
UL 1077
VDE 0641
2
3
5
10
20 30
multiple of rated current
B
25.36
multiple of rated current
14.36
1SXU 000 023 C0201
Discount schedule CB10
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S5 tem
00 p
Se ro M
rie
s
S500
600Y/277 VAC
K
UL 1077
VDE 0641
Rated
current
14
CSA C22.2
IEC-898
Catalog
number
Delivery Class
List
price
Delivery
class
Wgt. oz.
(1 Pc.)
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
1 pole
0.1
0.14
0.2
0.28
0.38
0.53
0.73
1
1.4
2
2.8
3.8
5.3
7.3
10
14
18
23
29
34
38
S501-D20
S502-D13
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
0.15
0.21
0.3
0.42
0.58
0.8
1.1
1.5
2.1
3
4.2
5.8
8
11
15
20
26
32
37
41
45
S501-K0.15
S501-K0.21
S501-K0.3
S501-K0.42
S501-K0.58
S501-K0.8
S501-K1.1
S501-K1.5
S501-K2.1
S501-K3
S501-K4.2
S501-K5.8
S501-K8
S501-K11
S501-K15
S501-K20
S501-K26
S501-K32
S501-K37
S501-K41
S501-K45
$ 182
182
182
182
182
182
182
182
182
182
182
182
182
182
182
182
182
202
202
226
226
0.15
0.21
0.3
0.42
0.58
0.8
1.1
1.5
2.1
3
4.2
5.8
8
11
15
20
26
32
37
41
45
S502-K0.15
S502-K0.21
S502-K0.3
S502-K0.42
S502-K0.58
S502-K0.8
S502-K1.1
S502-K1.5
S502-K2.1
S502-K3
S502-K4.2
S502-K5.8
S502-K8
S502-K11
S502-K15
S502-K20
S502-K26
S502-K32
S502-K37
S502-K41
S502-K45
356
356
356
356
356
356
356
356
356
356
356
356
356
356
356
356
356
392
392
442
442
0.15
0.21
0.3
0.42
0.58
0.8
1.1
1.5
2.1
3
4.2
5.8
8
11
15
20
26
32
37
41
45
S503-K0.15
S503-K0.21
S503-K0.3
S503-K0.42
S503-K0.58
S503-K0.8
S503-K1.1
S503-K1.5
S503-K2.1
S503-K3
S503-K4.2
S503-K5.8
S503-K8
S503-K11
S503-K15
S503-K20
S503-K26
S503-K32
S503-K37
S503-K41
S503-K45
518
518
518
518
518
518
518
518
518
518
518
518
518
518
518
518
518
574
574
644
828
B
8.90
B
17.85
2 pole
0.1
0.14
0.2
0.28
0.38
0.53
0.73
1
1.4
2
2.8
3.8
5.3
7.3
10
14
18
23
29
34
38
S503-K6
K
10,000
5000
14
3 pole
1000
500
100
50
10
5
seconds
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
8 10 12
20 30
multiple of rated current
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
0.1
0.14
0.2
0.28
0.38
0.53
0.73
1
1.4
2
2.8
3.8
5.3
7.3
10
14
18
23
29
34
38
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
B
25.36
Discount schedule CB10
14.37
1SXU 000 023 C0201
S500UC
600Y/277 VAC
600 VDC
M
o
pr ies
em Ser
st
Sy 500
S
14
B
UL 1077
VDE 0660
Rated
current
CSA C22.2
Catalog
number
List
price
Delivery Weight
class
(oz.) 1 pc
S501UC-B40
S501UC-B6
S501UC-B10
S501UC-B13
S501UC-B16
S501UC-B20
S501UC-B25
S501UC-B32
S501UC-B40
S501UC-B50
S501UC-B63
$ 226
226
226
226
226
226
226
226
258
292
S502UC-B6
S502UC-B10
S502UC-B13
S502UC-B16
S502UC-B20
S502UC-B25
S502UC-B32
S502UC-B40
S502UC-B50
S502UC-B63
442
442
442
442
442
442
442
442
502
568
C
8.90
S502UC-B16
List
price
Delivery
class
Weight
(oz.) 1 pc
6
10
13
16
20
25
32
40
50
63
S503UC-B6
S503UC-B10
S503UC-B13
S503UC-B16
S503UC-B20
S503UC-B25
S503UC-B32
S503UC-B40
S503UC-B50
S503UC-B63
$ 646
646
646
646
646
646
646
646
734
832
C
25.36
S504UC-B6
S504UC-B10
S504UC-B13
S504UC-B16
S504UC-B20
S504UC-B25
S504UC-B32
S504UC-B40
S504UC-B50
S504UC-B63
908
908
908
908
908
908
908
908
1030
1164
C
35.75
4 pole
2 pole
6
10
13
16
20
25
32
40
50
63
Catalog
number
3 pole
1 pole
6
10
13
16
20
25
32
40
50
63
Rated
current
C
17.85
6
10
13
16
20
25
32
40
50
63
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
S503UC-B50
14
B
10,000
5000
1000
500
100
50
10
5
seconds
1
0.5
AC
0.1
0.05
DC
0.01
1
2
3
5
7 10
20 30
multiple of rated current
14.38
1SXU 000 023 C0201
Discount schedule CB10
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S5 tem
00 p
Se ro M
rie
s
S500 UC
600Y/277 VAC
600 VDC
K
UL 1077
VDE 0660
Rated
current
14
CSA C22.2
Catalog
number
List
price
Delivery
class
Weight
(oz.) 1 pc
1 pole
0.1
0.14
0.2
0.28
0.38
0.53
0.73
1
1.4
2
2.8
3.8
5.3
7.3
10
14
18
23
29
34
38
S501UC-K0.15
S502UC-K0.15
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
S503UC-K0.15
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Catalog
number
List
price
Delivery
class
Weight
(oz.) 1 pc
C
25.36
C
35.75
3 pole
0.15
0.21
0.3
0.42
0.58
0.8
1.1
1.5
2.1
3
4.2
5.8
8
11
15
20
26
32
37
41
45
S501UC-K0.15
S501UC-K0.21
S501UC-K0.3
S501UC-K0.42
S501UC-K0.58
S501UC-K0.8
S501UC-K1.1
S501UC-K1.5
S501UC-K2.1
S501UC-K3
S501UC-K4.2
S501UC-K5.8
S501UC-K8
S501UC-K11
S501UC-K15
S501UC-K20
S501UC-K26
S501UC-K32
S501UC-K37
S501UC-K41
S501UC-K45
$ 250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
286
286
320
320
0.15
0.21
0.3
0.42
0.58
0.8
1.1
1.5
2.1
3
4.2
5.8
8
11
15
20
26
32
37
41
45
S502UC-K0.15
S502UC-K0.21
S502UC-K0.3
S502UC-K0.42
S502UC-K0.58
S502UC-K0.8
S502UC-K1.1
S502UC-K1.5
S502UC-K2.1
S502UC-K3
S502UC-K4.2
S502UC-K5.8
S502UC-K8
S502UC-K11
S502UC-K15
S502UC-K20
S502UC-K26
S502UC-K32
S502UC-K37
S502UC-K41
S502UC-K45
488
488
488
488
488
488
488
488
488
488
488
488
488
488
488
488
488
558
558
622
622
C
8.90
2 pole
0.1
0.14
0.2
0.28
0.38
0.53
0.73
1
1.4
2
2.8
3.8
5.3
7.3
10
14
18
23
29
34
38
Rated
current
0.1
0.14
0.2
0.28
0.38
0.53
0.73
1
1.4
2
2.8
3.8
5.3
7.3
10
14
18
23
29
34
38
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
0.15
0.21
0.3
0.42
0.58
0.8
1.1
1.5
2.1
3
4.2
5.8
8
11
15
20
26
32
37
41
45
S503UC-K0.15
S503UC-K0.21
S503UC-K0.3
S503UC-K0.42
S503UC-K0.58
S503UC-K0.8
S503UC-K1.1
S503UC-K1.5
S503UC-K2.1
S503UC-K3
S503UC-K4.2
S503UC-K5.8
S503UC-K8
S503UC-K11
S503UC-K15
S503UC-K20
S503UC-K26
S503UC-K32
S503UC-K37
S503UC-K41
S503UC-K45
$ 712
712
712
712
712
712
712
712
712
712
712
712
712
712
712
712
712
814
814
910
910
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
0.15
0.21
0.3
0.42
0.58
0.8
1.1
1.5
2.1
3
4.2
5.8
8
11
15
20
26
32
37
41
45
S504UC-K0.15
S504UC-K0.21
S504UC-K0.3
S504UC-K0.42
S504UC-K0.58
S504UC-K0.8
S504UC-K1.1
S504UC-K1.5
S504UC-K2.1
S504UC-K3
S504UC-K4.2
S504UC-K5.8
S504UC-K8
S504UC-K11
S504UC-K15
S504UC-K20
S504UC-K26
S504UC-K32
S504UC-K37
S504UC-K41
S504UC-K45
996
996
996
996
996
996
996
996
996
996
996
996
996
996
996
996
996
1142
1142
1276
1276
4 pole
C
17.85
0.1
0.14
0.2
0.28
0.38
0.53
0.73
1
1.4
2
2.8
3.8
5.3
7.3
10
14
18
23
29
34
38
14
Delivery Class
S504UC-K0.15
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
UC-K
10,000
5000
1000
500
100
50
seconds
10
5
1
0.5
0.1
0.05
DC
0.01
1
2
3
5
10
20 30
multiple of rated current
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule CB10
14.39
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 500
S
14
Accessories
Electrical
accessories
Catalog
number
List
price
Delivery
class
Wgt. oz.
(1pc.)
Electrical
accessories
Auxiliary contacts
1 N.O./1 N.C.
2 N.O.
2 N.C.
$ 84
B
12 V
24 V
48 V
110 V
230 V
500 V
2.14
Bell alarm with auxiliary contacts
1 N.O./1 N.C.
2 N.O.
2 N.C.
List
price
Delivery
class
Wgt. oz.
(1pc.)
Undervoltage release
S500-H11
S500-H20
S500-H02
For field mounting left side
S500-H11
Auxiliary contacts
Catalog
number suffix
S500-S11
S500-S20
S500-S02
92
B
2.14
B
5.71
AL12
AL24
AL48
AL110
AL230
AL500
224
B
5.71
Shunt trip
12 V
24 V
48 V
110 V
230 V
500 V
Handle mechanism
100
$ 266
Factory mount only.
For field mounting left side
S500-RD3
UA12
UA24
UA48
UA110
UA230
UA500
B
6.5
For use with 1-4 pole S500 MCBs and disconnect switch selector
handles with 5mm shafts
Factory mount only.
Front mounting kit
S500-RD3
For 1 pole
1 to 3 poles
1 to 7 poles
S500-ME1
S500-ME2
S500-ME3
60
70
80
2.1
2.9
3.6
A
Power feed terminal – Accepts into 2/0 AWG
S500-K2
25
A
2
Suggested order quantity is 5.
Busbars – 3 phase L1, L2, L3
S500-K2
14
Amp
rating
Number
of
poles
150
3x8
4x4
3 x 13
Busbar
length
(mm)
End cap
catalog
number
Catalog
number
List
price
Delivery
class
Suggested
order qty.
quantity
Weight
(ozs)
650
435
1055
—
—
—
S500-BB38
S500-BB44
S500-BB313
$ 182
142
274
A
1
1
List
price
Delivery
class
Wgt. oz.
(1pc.)
A
10
S500-BB38
Busbar end caps
Electrical
accessories
Catalog
number
S500-EK
$ 25
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
14.40
1SXU 000 023 C0201
Discount schedule CB8
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S5 tem
00 p
Se ro M
rie
s
Technical data
Item
14
S500-B, C, D
S500-K
Approvals:
UL
CSA
VDE
IEC
1077
C22.2 - No.235
0641/6.78
947-2
1077
C22.2 - No. 235
0641/6.78
—
No. of poles:
1,2,3, +N, +NA
1,2,3, +N, +NA
Tripping characteristic:
B.C.D.
K
Rated currents:
6 to 63A
0.1 to 45A
Rated voltage:
UL/CSA single pole
UL/CSA multi pole
277VAC
600YVAC
277VAC
600YVAC
690VAC
690VAC
6-25A – 30KA/240VAC
14KA/277VAC
0.15-25A – 30KA/240VAC
14KA/277VAC
32-63A – 18KA/240VAC
14KA/277VAC
26-45A – 18KA/240VAC
14KA/277VAC
6-63A – 14KA/480VAC
6KA/600VAC
0.15-45A – 14KA/480VAC
6KA/600VAC
50/60 Hz
50/60Hz
IEC single pole
Rated interrupting capacity:
Single pole
Multi-pole
Frequency:
Mounting position:
optional
optional
Standard mounting:
35mm DIN rail
35mm DIN rail
Conductors from 16-4AWG
(1-25sq mm)
Conductors from 16-4AWG
(1-25sq mm)
Service life at rated load:
20,000 operations
20,000 operations
Calibration temperature:
40°C
40°C
Terminals:
Item
S500UC-B, K
Approvals:
UL
CSA
VDE
1077
C22.2
0660
1,2,3, 4
No. of poles:
B: 6 to 63A
K: 0.15 to 45A
Rated currents:
Rated voltage:
UL single pole
UL multi pole
277VAC/250VDC
600VAC/600VDC
IEC multi pole
690VAC/750VDC
Rated interrupting capacity:
14
B, K
Tripping characteristic:
B single pole:
6 – 25A
32 – 63A
18KA/240VAC
30KA/240VAC
14KA/277VAC
14KA/277VAC
30KA/250VDC
30KA/250VDC
6 – 63A
14KA/480VAC
6KA/600VAC
30KA/500VDC
6 – 63A
14KA/480VAC
6KA/600VAC
30KA/600VDC
30KA/240VAC
18KA/240VAC
14KA/277VAC
14KA/277VAC
30KA/250VDC
30KA/250VDC
0.15 – 45A
14KA/480VAC
6KA/600VAC
30KA/500VDC
0.5 – 45A
14KA/480VAC
6KA/600VAC
30KA/600VDC
B two-pole:
B three-pole:
K single pole:
0.15 – 25A
32 – 45A
K two-pole:
K three-pole:
Frequency:
50/60Hz
Mounting position:
optional
Standard mounting:
Terminals:
Service life at rated load:
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
35mm DIN-rail
Conductors from 16 to 4AWG
(1-25sq mm)
20,000 operations
14.41
1SXU 000 023 C0201
M
o
pr ies
em Ser
st
Sy 500
S
Approximate dimensions
14
00.00
Inches
00.00
[Millimeters]
S500
2.95
75
1.97
50
0.98
25
3.64 92.5
1.73 44
3.15
3.62
1.77 45
80
2.22
56.5
92
CL
2.95 75
1.14
29
0.24 6
S500-RD3 Handle mechanism
14
3.15 80
1.60 40.7
S500 Front mounting kit
CL
4.41
2.91
112
74
2.00
51
0.24 D
CUT-OUT
6D
CL
1.81
46
"L"
L + 0.51 13
L
L + 1.02 26
3.31 84
14.42
1SXU 000 023 C0201
0.31 8
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Galaxie circuit breakers
GD, GH, GN & GV
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
cir G
cu ala
it
br xie
ea
ke
14
rs
Description
Features
Galaxie circuit breakers are door mounted
for AC and DC applications. The breakers
offer thermal-magnetic and magnetic-only
trip protection.
For the worldwide market, the Galaxie
breakers carry UL, CSA, IEC, CE and many
other agency approvals and certifications.
• Convenient actuators: Switch type,
rocker switch & pushbutton
• Various termination mountings
• Tropicalization protection
• 480Y/277 VAC
• UL 1077 Recognized – supplemental
protective device. UL File # E75741.
14.43
1SXU 000 023 C0201
14
s
xie ker
a
l
a
Ga bre
it
cu
r
i
c
14
GD, GH, GN & GV Series circuit breakers
Fitted, unpluggable or projecting type
Catalog number explanation
Circuit Breakers
OPTIONS
SERIES
RATING ENGRAVED
GD Standard Galaxie AC 240/415 V 50/60 Hz
can be used at 48 V DC max.
J
GH High rupturing capacity Galaxie
AC 240/415 V 50/60 Hz
METAL THREADED BUSHING
W
GN Special Galaxie 100 V DC max.
GV
Special Galaxie 150 V DC max.
GA Severe environment Galaxie
(i.e. military use) consult us
For fastening and operations 6-7-8.
Tightening torque : 3 Nm max.
(compulsory with option K)
CIRCUIT BREAKER SERIES GD MODEL D 2
R
VERSIONS
14
On resetting button
With adjustable thermal protection
(Not possible with option K)
U
One-pole
B
Two-pole
(1 protected pole)
(2 protected poles)
MECHANICAL IMPACT
T
Three-pole
(3 protected poles)
V
50 g
Q
Four-pole
(4 protected poles)
E
100 G
1+N Two-pole
(1 protected pole + neutral)
3+N Four-pole
(3 protected poles + neutral)
TROPICALIZATION
T
(Compulsory with option E 100)
RATING (In : Amps)
0.1 - 0.2 - 0.3 - 0.5 - 1 - 1.5 - 2 - 2.5 - 3 - 4 - 5
6 - 8 - 10 - 12 - 13 - 16 - 20 - 25 - 30 - 32
Heavy duty types : ratings according to
NF EN60 898 Other ratings, consult us.
THERMAL PROTECTION
C
Temperature compensated from + 20°C to + 60°C
K
Temperature compensated from - 40°C to + 85°C
series GD, GH and GA (Compulsory with Option W)
MODELS
L
Thermal-magnetic - Curve B
according to NF EN60 898
U
Thermal-magnetic - Curve C
according to NF EN60 898
D
Thermal-magnetic - Curve D
according to NF EN60 898
Ratings 6 to 32 A
S
Thermal-magnetic (series GN and GV only)
according to NF F 62001
T
Thermal (except series GH)
AUXILIARY CONTACT FOR POSITION SIGNALLING O/F
P1
on 1 pole
P2
on 2 poles
P3
on 3 poles
P4
on 4 poles
1 See next page
2 Series GD, Model D only
FASTENINGS AND OPERATIONS 1
00 - 01 - 02 - 03 - 04 - 05 - 06 - 07 - 08 - 09
TERMINATIONS 1
00 - 01 - 02 - 03 - 07 - 08 - 09 - 33 - 43
EXAMPLE :
1 Circuit breaker Series : Galaxie standard AC - Version : 2 protected poles - Rating : 10 A - Model : magnetic-thermal, curve C - Fastenings and operations :
Threaded bushing flush type 2 buttons - Terminations : Screws and back connectors - With Options Auxiliary for position signalling O/F : on 2 poles - Tropicalization
has reference GDB10U0703 P2T
GD B 10 U 07 03
14.44
1SXU 000 023 C0201
P2 -
T
-
-
-
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
cir G
cu ala
it
br xie
ea
ke
14
Technical data
rs
UL, CSA : For list of certified products : consult us
Characteristics
SERIES GD
SERIES GH
240 V AC (50/60 Hz)
240/415 V AC (50/60 Hz)
415 V AC (50/60 Hz)
48 V DC max.
240/415 V AC (50/60 Hz)
415 V AC (50/60 Hz)
Circuit breakers NF F62 001 : consult us
SERIES GN
SERIES GV
Rated voltage
1 + neutral version
One pole version
Multipole version
One pole and two pole version
100 V DC max.
150 V DC max.
Interrupting capacity
3 000 A
According to standard IEC 898
4 500 A (models U and D: rating ≥ 5 A)
4 500 A (model L: rating ≥ 10 A)
1 000 A (48 V DC max.)
10 In cal. < 5 A ; 20 In cal > 5 A
According to standard NF F62 001
500 A
1 000 A (48 V DC max.)
10 In cal. < 5 A ; 20 In cal > 5 A 10 In cal. < 5 A ; 20 In cal > 5 A
Other characteristics
4 000
2 000 V rms
Life, number of cycles (On+Off)
Dielectric withstanding voltage
Tripping curves (1) (2)
S
4 000
2 000 V rms
Curve B : 3 In < S < 5 In - Curve C : 5 In < S < 10 In - Curve D : 10 In < S < 20 In
< 14 In
4 000
2 000 V rms
4 000
2 000 V rms
Nominal current 0.1 to 2 A : 5 In < S < 10 In - 3 to 32 A : 7 In < S
Mechanical shock
30 g.
30 g.
30 g.
30 g.
-5° C to 40° C
-5° C to 40° C
-25° C to + 70° C
-25° C to + 70° C
Ambient temperature
14
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.45
1SXU 000 023 C0201
s
xie ker
a
l
a
Ga bre
it
cu
r
i
c
14
Approximate dimensions
-ILLIMETERS
Fastenings and operations No 00 - 01 - 02 - 03 - 04 - 06 - 07 - 08
Fastenings / Operations
1 Width
Pole
N° 2
8
07
08
15
21
28
32
32
32
43
07
08
09
4
4
4
11
37
00 01 02 03 33
15
4
8
06
32 32 32 32 32
4
8
05
Size C
Size B
8
17,5 15
8
Terminations
Pole
N° 1
00 01 02 03 04
Size A
12
4
32
09
Pole Pole Pole
N° 1 N° 2 N° 3
2 Widths
3 Widths
Fastenings and operations No 05 - 09
Four-pole circuit breaker :
o
Fastening and operation N 05 only
Pole
N° 2
1 Width
Pole
N° 1
2 Widths
Pole Pole Pole
N° 3 N° 2 N° 1
Pole Pole Pole Pole
N° 4 N° 3 N° 2 N° 1
3 Widths = 1 handle
4 Widths = 2 handles
NOTE :
Neutral on pole N° 1
any
Fastenings and operations
Fastenings and operations (3 poles max. except 02 : 2 poles and 05 : 4 poles)
PROJECTION MOUNTING
SCREW FLUSH MOUNTING
Maximum thickness of mounting panel :
3 mm.
3 mm.
6 mm.
6 mm.
6 mm.
3 mm.
00
01
02
03
04
05
06
1,8 Nm max.
07
08
6 mm.
09
Tightening torque :
1,8 Nm max.
1,8 Nm max.
3 Nm max.
Terminations
14
00
16 A max.
Except Fastening 08
14.46
1SXU 000 023 C0201
01
02
03
33
43
240 A max.
2 poles max.
2 poles max.
07
08
16 A max.
2 poles max.
16 A max.
09
16 A max.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
System pro M compact
Residual current devices
F200, F670 series
2 Pole
S
Re yste
sid m
p
u
de al c ro M
u
vic rr
es en
t
14
4 Pole
Description
RCDs provide ground fault equipment
protection by monitoring the leakage of
current to ground. The F200 and F670 series
will trip when ground faults are detected in
excess of the GF trip rating of the device.
These devices provide GF protection only and
are used in series with standard MCBs which
provide overload and short circuit protection.
The F200 and F670 series can be used as
a main device providing GF protection for
several MCB branch devices.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
The F200 and F670 series are UL1053
recognized for use in 480Y/277VAC
applications.
The F202 and F672 is for use in single
phase/two wire or two wire systems. The F204
and F674 is for use in three phase/four wire
systems.
The F200 and F670 series RCDs replace the
F360, F370 and F660 series with no change in 14
fit, form or function.
The F200 and F670 have a profile similar to
the S2 MCBs and can be used with the MCB
busbars.
14.47
1SXU 000 023 C0201
M t
o
pr rren
em cu
st ual es
y
S sid vic
Re de
14
F200 & F670
Residual current devices
Breaker
F202
F672
GF trip
level
Two pole
480Y/277VAC
Four pole
480Y/277VAC
List
price
16
25
40
63
80
100
F202AC-16/0.01
F202AC-25/0.03
F202AC-40/0.03
F202AC-63/0.03
F672-80/0.03
F672-100/0.03
$ 500
300
400
550
1600
2200
100mA
25
40
63
80
100
F202AC-25/0.1
F202AC-40/0.1
F202AC-63/0.1
F672-80/0.1
F672-100/0.1
300
400
550
1600
2200
300mA
25
40
63
80
100
F202AC-25/0.3
F202AC-40/0.3
F202AC-63/0.3
F672-80/0.3
F672-100/0.3
300
400
550
1300
1800
30mA
25
40
63
80
100
125
F204AC-25/0.03
F204AC-40/0.03
F204AC-63/0.03
F674-80/0.03
F674-100/0.03
F674-125/0.03
350
450
600
1300
1800
1800
100mA
25
40
63
80
100
125
F204AC-25/0.1
F204AC-40/0.1
F204AC-63/0.1
F674-80/0.1
F674-100/0.1
F674-125/0.1
350
450
600
1300
1800
1800
300mA
25
40
63
80
100
125
F204AC-25/0.3
F204AC-40/0.3
F204AC-63/0.3
F674-80/0.3
F674-100/0.3
F674-125/0.3
350
450
600
1200
1600
1600
500mA
25
40
63
F204AC-25/0.5
F204AC-40/0.5
F204AC-63/0.5
450
600
650
F204, F674
14
Catalog
number
10mA
30mA
F202, F672
F204
F674
Rated
current
Delivery
class
Suggested
order qty
Wgt. oz
(1 Pc.)
B
1
13.8
B
1
19.0
Above devices are UL 1053 recognized and IEC 1008 approved.
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
14.48
1SXU 000 023 C0201
Discount schedule CB14
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14
S
Re yste
sid m
p
u
de al c ro M
u
vic rr
es en
t
Accessories
F200 1
Electrical
accessories
For
use on:
Catalog number
List price
Delivery class
Suggested
order quantities
Wgt. oz.
(1 pc.)
Auxiliary contacts
For field mounting: right side
F200
S2C-H6R
$ 36
Form C 1 NO/ 1 NC
A
1
1.4
The auxiliary contacts will signal whether the breaker is in the ON or OFF position. The contacts are rated 2A/277 VAC and 1.5A/125 VDC.
Minimum operating voltage is 24 VAC/VDC.
Wire size: 18 AWG to 16 AWG.
S2C-H6R
Bell alarm
For field mounting, right side
F200
S2C-S/H6R
48
A
1
1.4
The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically the contacts would be connected to an alarm
or bell to signal the operator that an overcurrent trip has occured. The bell alarm also includes a test button for testing the alarm contacts without
opening the breaker. The contact is rated 2A/277 VAC and 1.5A/125 VDC. Minimum operating voltage is 24 VAC/VDC.
* Combination bell alarm/auxiliary contact
Shunt trip
For field mounting, right side
S2C-S/H6R
F200
A1: 12-60 VAC (12-60VDC)
A2: 110-415 VAC (110-250 VDC)
S2C-A1 S2C-A2
138
A
1
5.2
For remote tripping of breaker, a shunt trip device can be added to the MCB. The solenoid device opens the breaker after control voltage is
applied. Shunt trips are available for on control system voltage (12-415 VAC/VDC).
Undervoltage release
For field mounting, right side
12 VDC
24 VAC
48 VAC
F200
110 VAC
220 VAC
380 VAC
S2C-A_
S2C-UA12
S2C-UA24
S2C-UA48
216
S2C-UA110
S2C-UA230
S2C-UA400
A
1
5.2
When control voltage drops below approximately 50% of rated voltage, the UVR opens the breaker. The breaker can not be operated unless
proper control voltage is first applied to the UVR coil. Similar in size and mounting to the shunt trip accessory.
Factory mounting
All accessories can be easily mounted in the field. For factory mounting of any accessory devices, add $30 list to total price
per breaker. To create complete catalog number, take suffix of accessory device following “S2C-” and add suffix to end of
breaker part number. Multiple suffixes must be added in alphabetical order.
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
S2C-UA_
1 Please consult factory for F670 accessories.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule CB8
14.49
1SXU 000 023 C0201
14
M t
o
pr rren
em cu
st ual es
y
S sid vic
Re de
14
Technical data
F200, F670
F200AC
F670
UL 1053 & IEC 61008
2P, 4P
16,25,40,63 AMPS
480Y/277 VAC
254 (440 for F200 left neutral)
110 ( 195 for F200 left neutral)
50…60 Hz
50…60 Hz
10 KA
1 KA
6 KV
2.5 KV
250 AMPS
UL1053 & IEC 61008
2P, 4P
2P- 80,100 4P- 80,100,125
480Y/277 VAC
254 (440 for left neutral)
110 ( 195 for left neutral)
50…60 Hz
50…60 Hz
10 KA
2 KA
6 KV
2.5 KV
250 AMPS
Blue sealable in ON-OFF position
yes
10000
20000
-25°C… +55°C
-40°C… +70°C
Blue sealable in ON-OFF position
yes
10000
20000
-25°C… +55°C
-40°C… +70°C
Terminal size top/bottom per cable
Tightening torque
mounting
Connection
Withdraw from busbar
failsafe bidirectional cylinder-lift terminal at top and
bottom (shock protected)
6 AWG Max.
17.5 in-lb max.
35mm din rail by means of fast clip
From top & bottom
Possible without the use of tools
6 AWG Max.
17.5 in-lb max.
35mm din rail by means of fast clip
From top & bottom
Possible without the use of tools
Approximate dimensions
2 Pole mm
4 Pole mm
85x69x35 MM
85x69x70 MM
85x69x35 MM
85x69x70 MM
Weight
2 Pole g
4 Pole g
200g
350g
200g
350g
Combination with auxiliary elements
Auxiliary contact
signal contact/ auxiliary switch
shunt trip
undervoltage release
yes
yes
yes
yes
yes
yes
yes
yes
Electrical features
Standards
Poles
Rated current In
Rated Voltage Ui
Max operating voltage of curcuit test
Min operating voltage of circuit test
Rated Frequency
Rated conditional
Short-circuit current
Rated residual breaking capacity
Rated impulse withstand voltage (1.2/50) Uimp
Power- frequency voltage dielectric strength
Surge current resistance acc. To VDE 0432 Part 2
(wave 8/20)
Mechanical features
Toggle
Contact position indicator
Electrical Life
Mechanical life
Ambient temperature
Storage temp.
Installation
Terminal Type
14
14.50
1SXU 000 023 C0201
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
S
Re yste
sid m
p
u
de al c ro M
u
vic rr
es en
t
14
Approximate dimensions
Circuit diagrams
F200, F670
Approximate dimensions
Circuit diagrams
POLE
POLE
42)0
5.)4
4%34
#4
.
42)0
5.)4
4%34
#4
.
14
1 To use on 3p/3w systems, add jumper between 4 and 8N for operation of test button.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.51
1SXU 000 023 C0201
M t
o
pr rren
em cu
st ual es
y
S sid vic
Re de
14
Notes
14
14.52
1SXU 000 023 C0201
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
System pro M compact
Modular DIN rail components
E220 - E270 Series
S
Mo yste
d m
co ular pro
mp D
on IN r M
en ail
ts
14
Description
• Safe connection by box terminals
• Captive screws with Pozidrive slotted head,
Pozidrive system, Gr. 1
• Snap-on labels available
• Quick mounting with snap-on clip, easily
accessible and detachable at the bottom
• Protection against unintentional direct touch
• System approach for control and circuit
protection
• Compact size that dimensionally matches
the S2 MCB series
• Control and pilot functions can be along
side protective devices
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
• DIN rail mounted with 45mm front opening
• For use in auxiliary and logic devices
• Provide additional user functions for system
control and operation
• Include pushbuttons, indicating lights and
selector switches
• ABB System Pro M compatibility
• Most devices are both UL 508 recognized 14
and are IEC compliant
• Labeled with the CE Mark
14.53
1SXU 000 023 C0201
M l
o
i
pr ra
N
m
I
s
e
st r D nt
Sy dula one
p
Mo om
c
14
E221 & E222 Switches, 240VAC
16 & 25A
Type
Rated
current
Catalog
number
List
price
Delivery
schedule
Suggested
order qtys
Weight (Oz.)
1 piece
Switches
E221-10
1 N.O. + 1 N.C.
2 N.O. + 2 N.C.
3 N.O. + 1 N.C.
16
16
16
E221-11
E221-22
E221-31
$ 90
177
177
B
10
2.46
1 N.O.
2 N.O.
3 N.O.
4 N.O.
16
16
16
16
E221-10
E221-20
E221-30
E221-40
59
110
120
159
B
10
1.94
2.12
2.29
2.47
1 N.O. + 1 N.C.
1 N.O.
2 N.O.
3 N.O.
4 N.O.
25
25
25
25
25
E222-11
E222-10
E222-20
E222-30
E222-40
140
107
141
159
239
B
10
2.47
1.94
2.12
2.29
2.47
1 Change-over contact
2 Change-over contacts
16
16
E221-6
E221-6/2
69
125
B
10
2.12
2.47
1 Change-over contact
25
E222-6
128
B
10
2.12
Form “C” switches
Form “C” switches (I-O-II, Hand-OFF-Automatic)
1 Pole
2 Pole
16
16
E221-4
E221-4/2
99
147
B
10
2.12
2.47
1 Pole
25
E222-4
150
B
10
2.12
Note: Above devices are UL 508 recognized and IEC certified.
A300 pilot duty UL file # E171252
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
14
14.54
1SXU 000 023 C0201
Discount schedule CB20
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
E241 - E274 Disconnect switches
45, 63, 80 & 100A
14
S
Mo yste
d m
co ular pro
mp D
on IN r M
en ail
ts
Page
Deleted
4/24/06
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14
14.55
1SXU 000 023 C0201
M l
o
i
pr ra
N
m
I
s
e
st r D nt
Sy dula one
p
Mo om
c
14
E225 - E229, E10 Pilot devices
Type
Catalog
number
List
price
Delivery
schedule
Pack
units pcs.
Weight (Oz.)
1 piece
Pushbutton, 1 N.O. + 1 N.C. contact
Grey
Red
Green
Yellow
Black
Blue
E225-11B
E225-11C
E225-11D
E225-11E
E225-11F
E225-11G
$ 75
A
10
1.94
100
A
10
1.94
E229-B/110
E229-C/110
E229-D/110
E229-E/110
E229-G/110
93
A
10
1.59
E10/24
E10/110
E10/220
24
A
1
0.14
Illuminated pushbutton, 1 N.O. contact with lamp, 120 VAC
E225-11F
Clear
Red
Green
Yellow
Blue
E227-10B/110
E227-10C/110
E227-10D/110
E227-10E/110
E227-10G/110
Pilot light with lamp, 120 VAC
Clear
Red
Green
Yellow
Blue
E227-10E
Lamps
24 VAC/DC
120 VAC/DC
220 VAC/DC
Note: Above devices are UL 508 recognized and IEC certified. UL file # E171252
Special features
•
•
•
•
•
14
Safe connection via box terminals
Captive screws with Phillips/Slotted head, Posidriv system, Gr. 1
Snap-on labels available
Protection against unintentional touch acc. to DIN VDE 0106 Part 100
Lenses and pushbuttons in six colors
Elapsed time meter
E233-120/60
Type
Catalog
number
24 VAC, 60 Hz
120 VAC, 60 Hz
240 VAC, 60 Hz
E233-24/60
E233-120/60
E233-240/60
List
price
$ 130
Delivery
schedule
Pack
units pcs.
Weight (KG)
1 piece
B
A
B
1
Delivery
schedule
Pack
units pcs.
Weight (KG)
1 piece
0.045
• Non-resettable
• 100,000 hours (99999.99)
UL file #171252
Sockets
Type
E1175
Catalog
number
List
price
Socket, 250 VAC, 50/60 Hz
Italian standard
E1173
$ 57
B
1
0.2
Socket, 250 VAC, 50/60 Hz
French standard
E1174
$ 57
B
1
0.2
Socket, 250 VAC, 50/60 Hz
Schuko standard
E1175
$ 57
B
1
0.2
Socket w/cover, 250 VAC, 50/60 Hz
Schuko standard
E1175-C
$ 57
B
1
0.2
Delivery Class
E1175-C
14.56
1SXU 000 023 C0201
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
Discount schedule CB20
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
S
Mo yste
d m
co ular pro
mp D
on IN r M
en ail
ts
14
Digital meters
Measuring instruments
Type
Catalog
number
List
price
Delivery
schedule
Pack
units pcs.
Weight (KG)
1 piece
Digital timer, 230 VAC, 50/60 Hz
DTS7/1
$ 422
B
1
0.3
Voltmeter 600 VAC, 50-400 Hz
VLMD-1-2
510
B
1
0.3
Ammeter 15-20-25-40-60A,
250-400-600A, 50-400 Hz
AMTD-1
510
B
1
0.3
Transformer, 230 VAC, 50/60 Hz
4-8-12 VAC sec
TM15/12
135
B
1
0.3
DTS7/1
VLMD-1-2
14
TM15/12
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.57
1SXU 000 023 C0201
M l
o
i
pr ra
N
m
I
s
e
st r D nt
Sy dula one
p
Mo om
c
14
Technical data
Components for quick mounting onto DIN rails (35mm)
Mounting depth:
Mounting width:
68mm
1, 2, 3 and 4 pole switches = 17.5mm (= 1 module)
E220 Switches, 16 & 25A
Switching capacity:
Short-circuit withstanding capacity:
Toggle sealable:
Connection cross-sections:
Rated AC voltage:
1.25 In, 1.1Un, cos j = 0.6
3 kA, 380V, cos j = 0.9
In ON and OFF positions
Up to 1 x 6mm2 or 2 x 2.5mm2
240 VAC UL/CSA (E171252)
250/440 VAC IEC
E240/270 Disconnect switches, 45, 63, 80, & 100A
Switching capacity:
Short-circuit withstanding capacity:
Connection cross-sections:
1.25 In, 1.1Un, cos j = 0.3
E240 = 10kA, E270 = 25kA RMS
E240 up to 25mm2
E270 up to 50mm2
240/400/415 VAC
Rated AC voltage:
E Series components for quick mounting onto DIN rails (35mm)
Mounting depth
Mounting width:
Color:
Connection cross sections:
Rated current:
Rated voltage:
Rated voltage:
68mm
17.5mm (=1 module)
RAL 7035, grey
Up to 1 X 6mm2 or 2 X 2.5mm2
16A
250 VAC IEC
240 VAC UL/CSA (E171252)
Terminal markings
5
1
1
3
5
7
1
3
5
7
1
3
1
1
3
1
3
5
1
3
5
7
2
4
6
8
2
4
6
8
2
4
2
2
4
2
4
6
2
4
6
8
7
3
2 NO & 2 NC
2
6
4
8
3 NO & 1 NC
2 NO
1 NO
2 NO
Switches
3 NO
4 NO
Disconnect switches
14
1
3
1
3
7
1
3
5 7
1
3
1
3 7
5
1 3
I
2
2
1 NO
8
2
6 8
2 NO
2
3 NO
1 Pole
Illuminated pushbutton
2
0
8
1 3 7 5
II
I
2
2 Pole
II
2
1 Pole
Form "C" switches
0
8
2 Pole
Form "C" switches
(Hand - OFF- Auto)
Terminal assignments for pushbuttons and indicator lights
5
1
7
3
1
1
7
5 1
1
MAX
2W
2
6
4
8
2
8
6
1 NO & 1 NC
Pushbutton
14.58
1SXU 000 023 C0201
MAX
2W
2
2
2
1 NO
Illuminated
1 NO
Pilot light
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
S
Mo yste
d m
co ular pro
mp D
on IN r M
en ail
ts
14
Approximate dimensions
00.00
Inches
00.00
[Millimeters]
E220
1.77
3.35
3.35
45.0
85.0
85.0
1.99 50.5
0.69
2.52 64.0
0.69
17.5
17.5
Pilot light
Pushbutton
E220, 16 & 25A
1.77
3.35
45.0
85.0
1.99 50.5
0.69
2.52 64.0
E233
17.5
1.97
50.0
14
3.35
1.77
85.0
45.0
1
2
3
4
5
9
9
2.52
64.0
0.69
17.5
E240/270
1.77
3.52
45.0
89.5
1.38 35.0
1.99 50.5
0.69
2.52 64.0
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
17.5
1.38 52.5
2.76 70.0
14.59
1SXU 000 023 C0201
M l
o
i
pr ra
N
m
I
s
e
st r D nt
Sy dula one
p
Mo om
c
14
Approximate dimensions
E1173 - E1175
DTS
VLMD, AMTD
TMS
14
14.60
1SXU 000 023 C0201
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Tr
su ans
Transient voltage surge supressors
rg ien
es t
up vol
TVSS, OVR range
t
p
14
re age
ss
or
s
Description
•
•
•
•
•
•
•
•
•
•
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Compact
DIN rail mounting
Broad range
1, 2, 3, & 4 pole versions
Replaceable plug cartridges
Finger safe
15, 40, 65 & 100 kA versions
Three position visual status indication
Auxiliary contact for remote signalling
UL 1449, File # E238957 & E22406
14
14.61
1SXU 000 023 C0201
ge
lta ors
o
t v ess
ien ppr
s
n
u
Tra ge s
r
su
14
General points on lightning and its risks
Causes of transient overvoltages
The most serious consequences of lightning are the death of people and farm animals, and the destruction of equipment: telephone lines, transformers connected
to the electrical distribution network, electrical meters, household appliances, etc.
At the same time, the growing amount of equipment incorporating very sensitive electronic devices increases the number of incidences linked to lightning.
Within companies, if office automation equipment or machines (in factories) are put out of action, it nearly always leads to operating losses, the cost of
which is much more than that of the damaged equipment.
For example, if a bank’s computers are no longer operational, it suffers large operating losses. For the general public, the damage is mainly material: computer,
household appliances, home cinema, etc.
ROBUSTNESS OF EQUIPMENT
1950
1970
2000
PROPAGATION OF DISTURBANCES
Causes of transient overvoltages
14
A transient overvoltage is a voltage peak with a
maximum duration of less than one millisecond. There
are two possible causes of overvoltages on electrical
networks:
• natural causes (lightning),
• other causes due to equipment or switching devices.
1950
1970
2000
Natural overvoltages on low voltage networks are
caused by direct lightning strikes. The high level
of energy contained in a direct lightning strike on a
lightning conductor or an overhead low voltage line
leads to considerable damage of the installation. The
overvoltage can be over 20 times the nominal voltage.
Operating or switching overvoltages linked to a
network’s equipment create overvoltages of a lower
level (3 to 5 times the nominal voltage) but occur much
more frequently, thus causing premature ageing of the
equipment.
Three categories of overvoltage propagate
on low voltage networks:
• direct lightning strikes,
• indirect effects of lightning strikes,
• operating or switching overvoltages.
Propagation of overvoltages by electrical networks
(power and low current)
14.62
1SXU 000 023 C0201
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
General points on lightning and its risks
Causes of transient overvoltages
Tr
su ans
rg ien
es t
up vol
pr tag
es
so e
rs
14
Overvoltages due to direct lightning strikes
These can take two forms:
• When lightning strikes a lightning conductor or the roof of a building which is earthed, the lightning current is dissipated into the ground. The impedance of the
ground and the current flowing through it create large difference of potential: this is the overvoltage. This overvoltage then propagates throughout the building via
the cables, damaging equipment along the way.
• When lightning strikes an overhead low voltage line, the latter conducts high currents which penetrate into the building creating large overvoltages. The damage
caused by this type of overvoltage is usually spectacular (e.g. fire in the electrical switchboard causing the destruction of buildings and industrial equipment) and
results in explosions.
Direct lightning strike on a lightning conductor or the roof of a
building
Direct lightning strike on an overhead line
Overvoltages due to the indirect effects of lightning strikes
The overvoltages previously mentioned are also found when lightning strikes in the vicinity of a building, due to the increase in potential of the ground at the point of
impact. The electromagnetic fields created by the lightning current generate inductive and capacitive coupling, leading to other overvoltages.
Within a radius up to several kilometres, the electromagnetic field caused by lightning in clouds can also create sudden increases in voltage.
Although less spectacular than in the previous case, irreparable damage is also caused to so called sensitive equipment such as fax machines, computer power
supplies and safety and communication systems.
14
Increase in ground potential
Magnetic field
Electrostatic field
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.63
1SXU 000 023 C0201
ge
lta ors
o
t v ess
ien ppr
s
n
u
Tra ge s
r
su
14
Different types of surges
Equipment containing electronic switching components is also likely to generate electrical disturbances comparable to overvoltages.
The consequences of which on sensitive equipment, albeit not visible, are no less detrimental: premature ageing and unpredictable or fleeting breakdowns.
Operating overvoltages are produced when reactive or capacitive equipment is switched on and off.
Furthermore, interrupting factory production, lighting or transformers can generate overvoltages which will themselves cause greater damage to nearby electrical
equipment.
Direct lightning strikes
Indirect lightning strikes
Operating
overvoltages
14
Micro breaks
Temporary phenomenon Duration > 200ms
Too long for TVSS
➪
➪
Harmonics
Transient phenomenon Duration < 1ms
TVSS needed
➪
Representation of the various disturbances on electrical networks
Different type of power supply disturbances
Main effects
• Atmospheric discharges
• Industrial interferences
• Switching operations on the power distribution system
• Destruction of the equipment
• Premature aging
• Incorrect operations
14.64
1SXU 000 023 C0201
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Tr
su ans
rg ien
es t
up vol
pr tag
es
so e
rs
14
OVR Range
Main features
TVSSs protect installations by limiting
transient overvoltages and run-off
lightning currents for electric and
electronic equipment.
They are divided into three families:
• Type 2 TVSSs provide protection
for equipment against transient overvoltage and they are installed in the
Main Switch Board (MSB), or in the
Sub-Distribution Board (SDB).
In addition to the standard TVSSs,
two options are available: the Safety
reserve system and the remote
indication (TS), in order to ensure
a preventive maintenance of the
installation.
ABB TVSS (OVR range) offer the
same “plus” advantages of the other
System pro M compact devices,
in order to get a perfect compatibility with all the modular range of
products.
ABB safety reserve system
Contact for alarm connection
All these TVSS products comply
with the international standard IEC
61643-1 and the European standard
EN 61643-11.
They also comply with UL 1449 and
CSA C22.2.
14
Pluggable unit / replacement modules
DIN rail unit, easy installation and wiring
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.65
1SXU 000 023 C0201
ge
lta ors
o
t v ess
ien ppr
s
n
u
Tra ge s
r
su
14
Technical data
OVR range
Technical Features
Electrical features
14
Mechanical features
Installation
Dimensions and weight
Standards
Type / test class
Poles
Types of networks
Type of current
Nominal voltage Un
Max. cont. operating voltage Uc
Voltage protection level Up at In
Nominal discharge current In (8/20)
Maximal discharge current Imax (8/20)
Impulse current Iimp (10/350)
Follow current Ifi
Operating current Ic
Short circuit withstand Icc
Disconnector
gG - gL fuse
curve C circuit breaker
curve K circuit breaker
Stocking temperature
Operating temperature
Degree of protection
Fire resistance according to UL 94
Material of Housing
Maximal altitude
Integrated thermal disconnector
State indicator
Compatibility with OVR Sign
Safety reserve
TS remote indicator
Wire range L/N
solid wire
stranded wire
Stripping length L/N
Tightening torque L/N
Wire range PE
solid wire
stranded wire
Stripping length PE
Tightening torque PE
Pole dimensions (H x D x W)
Pole weight
Type 2
(L-N / L-PE / N-PE)
(L-N / L-PE / N-PE)
V
V
kV
kA
kA
kA
kA
mA
kA
IEC 61643-1 / EN 61643-11 / UL1499 / CSA
T2 / II
1P / 1P+N / 3P / 3P+N / 4P
TNS - TT - TNC - IT / Wye / Delta
A.C.
All US network voltages
150 / 275 / 320 / 440 / 550 / 660
0.6 / 1.2 / 1.4 / 1.8 / 2.5 / 2.9
5 / 15 / 20 / 30
15 / 40 / 65 / 100
/
None
<1
50
A
A
16 - 25
10 - 40
°C
°C
m
-40 to +80
-40 to +80
IP 20
V2
PC grey RAL 7035
2000
Yes
Yes
Yes
Option
Option
mm2
mm2
mm
Nm
2.5 ... 25
2.5 ... 16
12.5
2
mm2
mm2
mm
Nm
2.5 ... 25
2.5 ... 16
12.5
2
mm
g
85 x 58 x 17.5
120
Technical Features of the integrated auxiliary contact
Electrical features
Contact complement
1NO (1 make contact),
1NC (1 normally closed contact)
12V D.C. - 10 mA
250V A.C. - 1A
Min. load
Max. load
Installation
14.66
1SXU 000 023 C0201
Connection cross-section
mm2
1.5
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Tr
su ans
rg ien
es t
up vol
pr tag
es
so e
rs
14
OVR Range
Single pole
Transient voltage surge suppressor
Function: TVSS provides protection for equipment against transient overvoltage (indirect lightning strike) that occur on the electrical
network (mains); the maximum discharge current (Imax) ranges from 15 to 100 kA per pole, based on MOV technology.
Application: residential, commercial, industrial
Standard: CEI 61643-1 / EN 61643-11 / UL 1449 / CSA
8/20 current wave
Type 2 - Surge Protection Devices – Single pole
Max Discharge
Current (KA)
15
40
65
100
Nominal Voltage (V)
MOV Voltage (V)
Voltage Protection
Level Up (KV)
Catalog
number
List
price
120
150
.06
OVR 15 150
OVR 15 150 s P
230
275
1.2
OVR 15 275
OVR 15 275 P TS
277
320
1.4
OVR 15 320
220
220
350
$ 230
350
220
340
400
440
1.8
OVR 15 440
OVR 15 440 P
480
550
2.5
OVR 15 550
275
600
660
2.9
120
150
0.6
OVR 15 660
OVR 40 150 s P
OVR 40 150 s P TS
290
440
510
230
275
1.2
OVR 40 275 P
OVR 40 275 s P
OVR 40 275 s P TS
320
345
400
277
320
1.4
400
440
1.8
OVR 40 320 P
OVR 40 320 s P
OVR 40 320 s P TS
OVR 40 440
OVR 40 440 s P
OVR 40 440 s P TS
320
350
405
285
350
400
480
550
2.5
600
120
660
150
2.9
0.6
230
275
1.2
OVR 40 550
OVR 40 550 s
OVR 40 660 s
OVR 65 150 s P
OVR 65 275 s P
OVR 65 275 s P TS
435
475
490
395
490
565
495
520
277
320
1.4
OVR 65 320 s P
OVR 65 320 s P TS
400
440
1.8
OVR 65 440 s P
OVR 65 440 s P TS
465
530
480
600
550
660
2.5
2.9
OVR 65 550 s
600
230
275
1.2
OVR 65 660 s
OVR 100 275 s P
OVR 100 275 s P TS
675
830
955
277
320
1.4
OVR 100 320 s P
OVR 100 320 s P TS
890
1025
400
440
1.8
OVR 100 440 s
OVR 100 440 s P
OVR 100 440 s P TS
800
870
1005
OVR 1N 65 275 s P TS
Network
1N Single phase (left), neutral (right)
3N Three phase (left), neutral (right)
N1 Neutral (left), single phase (right)
N3 Neutral (left), three phases (right)
3L Three poles
4L Four poles
Nothing Single pole
Max. discharge current 8/20
Imax (kA)
15
40
65
100
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule CB15
TS Integrated remote indication
P
Pluggable unit
Nothing: Single block
s with safety reserve
Max. continuous operating
voltage
Uc (V)
660
550
440
385
320
275
150
75
14.67
1SXU 000 023 C0201
14
ge
lta ors
o
t v ess
ien ppr
s
n
u
Tra ge s
r
su
14
OVR TVSS
Multi-pole
Transient voltage surge suppressor
Function: TVSS provides protection for equipment against transient overvoltage (indirect lightning strike) that occur on the electrical
network (mains); the maximum discharge current (Imax) ranges from 15 to 100 kA per pole, based on MOV technology.
Application: residential, commercial, industrial
Standard: CEI 61643-1 / EN 61643-11 / UL 1449 / CSA
8/20 current wave
Max Discharge
Current (KA)
Nominal Voltage (V)
MOV Voltage (V)
Voltage Protection
Level Up (KV)
Catalog
number
120
150
0.6
OVR 1N 15 150
OVR 1N 15 150 s P TS
OVR 3N 15 150
230
275
1.2
277
320
1.4
120
150
0.6
230
275
1.2
277
320
1.4
400
440
1.8
120
150
0.6
230
275
1.2
277
320
1.4
400
440
1.8
277
320
1.4
15
40
65
100
List
price
$ 365
665
625
OVR 3L 15 275 P
OVR 3N 15 275
OVR 3N 15 320
625
690
980
OVR 1N 40 150 s P
OVR 1N 40 150 s P TS
OVR 3N 40 150 s P TS
OVR 3N 40 275 s P
OVR 3L 40 275 s P
665
935
1160
1120
950
OVR 3N 40 320 P
OVR 3N 40 320 s P
OVR 3N 40 320 s P TS
OVR 3N 40 440 s P
1175
1250
1450
1290
OVR 1N 65 150 s P
OVR 3N 65 150 s P
OVR 3N 65 150 s P TS
OVR 3L 65 275 s P
OVR 3N 65 275 s P
OVR 3N 65 320 s P
OVR 3N 65 320 s P TS
OVR 3N 65 440 s P
OVR 4L 65 440 s
1000
1535
1640
1045
1280
1650
1900
1245
1320
OVR 3N 100 320 s P
3200
OVR 3N 100 320 s P TS
3600
14
OVR 1N 65 275 s P TS
Network
1N Single phase (left), neutral (right)
3N Three phase (left), neutral (right)
N1 Neutral (left), single phase (right)
N3 Neutral (left), three phases (right)
3L Three poles
4L Four poles
Nothing Single pole
Max. discharge current 8/20
Imax (kA)
15
40
65
100
14.68
1SXU 000 023 C0201
Discount schedule CB15
TS Integrated remote indication
P
Pluggable unit
Nothing: Single block
s with safety reserve
Max. continuous operating
voltage
Uc (V)
660
550
440
385
320
275
150
75
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
OVR Range
Very low voltage transmission lines protection
Tr
su ans
rg ien
es t
up vol
pr tag
es
so e
rs
14
Transmission line surge arresters (OVR TC) provide protection against transient overvoltages for equipment connected to
telephone lines (digital or analog) & current loops.
Standards Info:
Modular low current surge arresters comply with IEC 61643-21 / UL 1449.
Schematic diagrams
L1
L1
l1
L2
l2
L2
OVR TC 06 V
OVR TC 200 V in parallel
OVR TC / xx V / 200 FR in series
Dimensions
Dimensions (mm)
OVR TC (all models)
W
H
D
17.5
85
63
Connection
L1
L1
L2
L2
OVR TC 200 FR
OVR TC 48 V
OVR TC 24 V
OVR TC 12 V
OVR TC 06 V
OVR TC 200 V
OVR TC 200 FR
14
l1
OVR TC 200 V in parallel
l2
OVR TC / xx V / 200 FR in series
Fixing
Simply clips onto DIN rail.
Pratical info:
Telecom and dataline protection surge arresters are installed in electrical
switchboards or enclosures using DIN rail.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.69
1SXU 000 023 C0201
ge
lta ors
o
t v ess
ien ppr
s
n
u
Tra ge s
r
su
14
Electrical characteristics
Types of network
Number of pairs
Type of protection
Type of current
Nominal voltage: Un
Max cont operating voltage: Uc
Voltage protection level: Up at In
Nominal discharge current: In (8/20)
Maximum discharge current: Imax (8/20)
Bandwidth
Operating current: Ic
Degree of protection
50 Hz withstand (15 mn)
Mechanical characteristics
L/N connection terminals:
– solid wire
– stranded wire
PE connection terminal:
– solid wire
– stranded wire
Integrated thermal disconnector
End of life indicator
Compatibility with OVR Sign
Miscellaneous characteristics
Storage temperature
Operating temperature
Maximum altitude
Case material
Insulating material
Reference standard
Weight
Technical data
6V
OVR TC 06 V
12 V
OVR TC 12 V
24 V
OVR TC 24 V
48 V
OVR TC 48 V
200 V
OVR TC 200 V
200 V
OVR TC 200 FR
Communication
1
Series
Low currents
6V
7V
15 V
5 kA
10 kA
10 MHz
20 mA
IP 203
10 A
Communication
1
Series
Low currents
12 V
14 V
20 V
5 kA
10 kA
2 MHz
20 mA
IP 203
10 A
Communication
1
Series
Low currents
24 V
27 V
35 V
5 kA
10 kA
4 MHz
20 mA
IP 203
10 A
Communication
1
Series
Low currents
48 V
53 V
70 V
5 kA
10 kA
6 MHz
20 mA
IP 203
10 A
Communication
1
Parallel
Low currents
200 V
220 V
700 V
5 kA
10 kA
100 MHz
IP 203
-
Communication
1
Series
Low currents
200 V
220 V
300 V
5 kA
10 kA
3 MHz
20 mA
IP 203
10 A
No
No
No
Yes
Yes
Yes
0.5 ... 2.5 mm2
0.5 ... 2.5 mm2
0.5 ... 2.5 mm2
0.5 ... 2.5 mm2
Yes
Yes
Yes
-40 °C to +80 °C
-40 °C to +80 °C
2000 m
PC grey RAL 7032
UL94 V0 classification
IEC 61643-21 / UL 1449
150 g
14
14.70
1SXU 000 023 C0201
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Tr
su ans
rg ien
es t
up vol
pr tag
es
so e
rs
14
Installation rules
Principles of coordination for TVSS
The first surge arrester does not provide effective protection for the whole installation by itself.
Certain electrical phenomena can double the protection’s residual voltage if cable lengths exceed 10m.
Surge arresters must be coordinated when they are installed refer to the tables below.
Coordination required if:
The first surge arrester does not reach the protection voltage (Up ) by itself.
The first surge arrester is more than 10m away from the equipment to be protected.
The first surge arrester diverts most of the current to the ground and the remaining surge current is diverted to
the ground by the second surge arrester.
The value of this remaining surge current gets lower as the distance between both surge arresters gets longer.
The lower is the current going through the last surge arrester, the lower is the voltage protection level applied
to the downstream equipment.
Coordination between Type 2 TVSS units
65 kA
8/20
➤
TVSS
L>1m
(1 m minimum between the two devices)
➤
TVSS
15 kA
8/20
14
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.71
1SXU 000 023 C0201
ge
lta ors
o
t v ess
ien ppr
s
n
u
Tra ge s
r
su
14
Approximate dimensions
OVR range
Transient voltage surge suppressor
TVSS without TS
TVSS with TS
45
87.3
95.6
87.3
45
97
63
63
40
40
1 pole
17,6
OVR 15 275 P
OVR 15 440 P
OVR 40 275 P
OVR 40 275 s P TS
OVR 40 440 P
OVR 40 440 s P TS
OVR 65 275 s P TS
OVR 65 440 s P TS
14
4 poles
OVR 4L 15 275 P
OVR 4L 40 275 P
OVR 4L 40 275 s P TS
OVR 4L 65 275 s P TS
1SXU 000 023 C0201
52,8
OVR 3L 15 275 P
OVR 3L 40 275 P
OVR 3L 40 275 s P TS
OVR 3L 65 275 s P TS
3 poles + Neutral
14.72
3 poles
70,4
OVR 3N 15 275 P
OVR 3N 40 275 P
OVR 3N 40 275 s P TS
OVR 3N 65 275 s P TS
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Tr
su ans
rg ien
es t
up vol
pr tag
es
so e
rs
14
Technical details
Installation rules for TVSS choice of associated
breaking devices (fuse/circuit breaker)
Choice of disconnector
Surge arresters must be associated with upstream short-circuit protection and residual current protection against indirect contact (usually already present in the installation)
Function
Application
Protection against
fault currents
Thermal protection
The breaking device associated with the surge arrester can
be either a circuit breaker or a fuse.
Its rating should take into consideration the surge arrester’s
characteristics and the short-circuit current of the installation.
Thermal protection is integrated into the surge arrester.
Maximum circuit-breaker or fuse protection rating depending
on Imax and Iimp of the surge arrester.
TVSS surge arresters
Circuit-breaker (curve K)
Fuse (gG)
• Icc = 300 A to 1 kA
40 A
25 A
• Icc = 1 kA to 7 kA
40 A
25 A
• Icc = 7 kA and above
40 A
25 A
TVSS surge arresters
Circuit-breaker (curve C)
Fuse (gG)
100 kA (8/20)
14
65 kA (8/20)
• Icc = 300 A to 1 kA
30 A
20 A
• Icc = 1 kA to 7 kA
32 A to 40 A
40 A
• Icc = 7 kA and above
32 A to 63 A
63 A
• Icc = 300 A to 1 kA
25 A
16 A
• Icc = 1 kA to 7 kA
25 A
25 A
25 A to 50 A
50 A
• Icc = 300 A to 1 kA
10 A to 25 A
16 A
• Icc = 1 kA to 7 kA
10 A to 32 A
16 A
• Icc = 7 kA and above
10 A to 40 A
25 A to 40 A
40 kA (8/20)
• Icc = 7 kA and above
15 kA (8/20)
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.73
1SXU 000 023 C0201
ge
lta ors
o
t v ess
ien ppr
s
n
u
Tra ge s
r
su
14
Technical details
Cabling and installation of Surge Protection Devices
in an electrical panel
➤
Remember that a 10 kA lightning current passing through a 1 m length of cable generates 1000 Volts. Equipment
protected by a surge arrester is subjected to a voltage equal to the sum of the Up voltage of the surge arrester,
Ud of its disconnector and the sum of the inductive voltages of connecting cables (U1+U2+U3).
It is therefore essential that the total length (L = L1+L2+L3) of the connecting cables is as short as possible
(0.50 m).
U1
➤
50 cm rule
L1
➤
If this length (L = L1 + L2+L3) exceeds 0.50m, it is necessary to carry out one of the following:
• Reduce this length by moving the connection terminals.
• Choose a surge arrester with a lower Up value.
• Install a second, coordinated surge arrester near the device to be protected so as to adapt the combined
Up value to the impulse withstand of the equipment to be protected.
➤
UD
L
L2
➤
U2
➤
UP
Wiring ring surfaces
The wires must be arranged in such a way that they are as close to each other as possible (see adjacent diagram)
to avoid overvoltages induced by a ring surface between phases, the neutral and the PE conductor.
➤
➤
L3
U3
Routing of clean cables and polluted cables
During installation, lay clean cables (protected) and polluted cables as shown in the adjacent diagrams.
To avoid magnetic coupling between the different cable types (clean and polluted), it is strongly advised that
they are kept apart (> 30 cm) and if a crossing cannot be avoided, it should be at right angles (90°).
➤
Polluted cables
D > 30 cm
➤
Crossing
at 90°
Clean cables
Polluted
cable
Main
circuitbreaker
Clean
cable
Ring
surface
Surge
arrester
circuitbreaker
Terminal / MCB
14
Feeder 1
Clean
cable
➤
MCB / TVSS
Polluted
cable
D > 30 cm
➤
D < 30 cm
➤
➤
Feeder 2
TVSS / Earth terminal
Equipotential grounding:
It is critical to check the earth equipotentiality of the various items of equipment.
Note:
The cross-section of the connecting cables is calculated according to
the local short-circuit current level (where the surge arrester is installed).
It must be equal to the cross-section of the installation’s upstream
cables.
The minimum cross-section for the earth conductor is 4 mm2 if there is
not a lightning conductor and 10 mm2 if there is a lightning conductor.
14.74
1SXU 000 023 C0201
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Application sheets
OVR Surge Protection Devices
Operating principle
Tr
su ans
rg ien
es t
up vol
pr tag
es
so e
rs
14
Example of installation
The Surge Protection Devices (TVSS), suitable for
residential, commercial and industrial applications,
are designed to limit transient overvoltage and
run-off lightning currents.
Application environments
As shown in the diagrams, one of the possible
applications is to protect the equipment (TV,
computer, ...) against overvoltage thanks to a
Surge Protection Device (TVSS) which ensures
the protection in common mode (Ph-PE / N-PE) and
differential mode (Ph-N).
The Surge Protection Devices (TVSS) are
necessary in any environment where the lightning
risk exists (direct lightning strike / overvoltage).
,
,
,
.
%QUIPMENT
PROTECTED
14
Type 2 TVSS
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.75
1SXU 000 023 C0201
ge
lta ors
o
t v ess
ien ppr
s
n
u
Tra ge s
r
su
14
General points on lightning and its risks
Diagram of an installation protected against lightning and its
indirect effects
The 100KA or 65KA surge arrester (depending on the lightning risk) fitted in the installation’s main incoming electrical switchboard, is capable of deviating the energy
of a direct lightning strike. This is the first stage of the electrical network’s protection.
The behaviour of the cables, subjected to a transient signal, limits the effectiveness of a surge arrester to 10 m of cable. It is therefore necessary to use one or more
surge arresters in the installation in order to obtain the required level of protection for the equipment.
Here, a 40KA or 15KA surge arrester (depending on the lightning risk) should be used in coordination with the incoming surge arrester. This is the second stage of
the protection.
Finally, if there is a risk of overvoltage on the electrical network, this risk also exists for the auxiliary wiring network. The appropriate protection is a surge arrester
designed to protect telephone or data transmission lines (OVR TC). This is fitted in series on the network.
Protects the building
Protects the telephone
network
Telephone Line
Surge Arrester
OVR TC 200 FR
14
Sub-distribution
switchboard
PABX
Incoming power
cable
Incoming
telephone line
Main
electrical
switchboard
Protects the machines
OVR 3N 65 275s PTS
14.76
1SXU 000 023 C0201
Protects computer feeders
OVR 3N 15 275 s P TS
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Selection
Example of a protected industrial installation
GE
(Generator set)
Transformer
T1
OVR 3N 65 440s PTS
14
Transformer
T2
OVR 3N 65 440s PTS
(1)
Tr
su ans
rg ien
es t
up vol
pr tag
es
so e
rs
OVR 3N 65 440s PTS
(1)
MSB 10
(1)
MSB 11
Type 2 Surge Arrester
OVR 3N 40 440 s P TS
SDB 20 (Sub-distribution board)
MSB 12
Type 2 Surge Arrester
OVR 3N 40 440 s P TS
SDB 21 (Sub-distribution board)
Type 2 Surge Arrester
OVR 3N 15 440 s P TS
(1)
SDB 23 (Sub-distribution board)
Surge Arrester Type 2
OVR 3N 40 440 s P TS
SDB 22 (Sub-distribution board)
Type 2 Surge Arrester
OVR 3N 15 440 s P TS
(1)
SDB 24 (Sub-distribution board)
14
Surge Arrester Type 2
OVR 3N 15 440 s P TS
(1)
SDB 25 (Sub-distribution board)
The above diagram is an example of an industrial application located in an area where the lightning strike density (Ng) is 1.2 lightning strikes per km2 and per year:
• the building is protected by a lightning conductor.
• the lightning conductor's earthing strip is connected to the installation's earth network.
• the earthing system is IT (with distributed neutral) and then TNS for the sub-distribution boards.
• main switch boards (MSB) 10, 11 and 12 are fitted with Type 2 surge arresters OVR 3N 65 440 s PTS.
• sub-distribution boards (SDB) 20, 21 and 22 are fitted with Type 2 surge arresters OVR 3N 40 440 s P TS.
• sub-distribution boards (SDB) 23, 24 and 25 are fitted with Type 2 surge arresters OVR 3N 15 440 s P TS.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
14.77
1SXU 000 023 C0201
ge
lta ors
o
t v ess
ien ppr
s
n
u
Tra ge s
r
su
14
Terminology of electrical characteristics
Surge arrester:
Device designed to limit transient overvoltages and run-off lightning
currents. It consists of at least one non-linear component. It must comply
with European standard EN 61643-11.
1.2/50 wave:
Standardized overvoltage waveform created on networks and which
adds to the network’s voltage.
8/20 wave:
Current waveform which passes through equipment when subjected
to an overvoltage.
Type 2 surge arrester:
Surge arrester designed to run-off energy caused by an overvoltage
comparable to that of an indirect lightning strike or an operating
overvoltage. It has successfully passed testing to the standard with the
8/20 wave (class II test).
Up:
Voltage protection level / Let through voltage
Parameter characterising surge arrester operation by the level of voltage
limitation between its terminals and which is selected from the list of
preferred values in the standard. This value is greater than the highest
value obtained during voltage limitation measurements (at In).
8/20
In:
Nominal discharge current.
Peak current value of an 8/20 waveform (15 times) flowing in the surge
arrester. It is used to determine the Up value of the surge arrester.
Imax:
Maximum discharge current for class II testing.
Peak current value of an 8/20 waveform flowing in the surge arrester
with an amplitude complying with the class II operating test sequence.
14 Imax is greater than In.
µs
Type 2 Surge Arresters
Imax: current wave
Un:
Nominal AC voltage of the network : nominal voltage between phase
and neutral (AC rms value).
14.78
1SXU 000 023 C0201
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com