S System pro M compact S ystem 2 Miniature circuit breakers 00 Se pro M S200, S200P, S200U, S200UP ries 14 Description Features The S2 Series of miniature circuit breakers offer a compact solution to protection requirements. The S2 devices are current limiting, DIN rail mounted and can offer a good equivalent to fused systems. The S2 is available with application-specific trip characteristics to provide maximum circuit protection. The breakers offer thermal-magnetic trip protection according to B, C, D, K and Z characteristics. For the worldwide market, the breakers carry UL, CSA, IEC, CE and many other agency approvals and certifications. • Current limiting • Fast breaking time (2.5 – 3.5 msec) • Unique bus connection system • Wide range of accessories • Available with variable depth handle mechanism • Optional Z curve for SCR protection • CE certified and marked 14 • DIN rail or front panel mounting • Finger safe terminals • Multi-function terminals • Suitable for reverse feed • 480Y/277VAC and 500VDC versions • UL489 Listed - branch circuit protective device. UL file # E212323 • UL1077 Recognized - supplemental protective device. UL file # E76126 ed old M re nd u t a nia ers rs i d M reak ecto e t rov uit B Pro p Ap Circ ntal L U se me Ca pple Su Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.1 1SXU 000 023 C0201 M o pr ies em Ser st Sy 200 S 14 General information General information Applications Miniature circuit breakers (MCBs) are used throughout the world in all types of electrical installations. ABB MCBs are approved for use by Underwriters Laboratories in systems rated up to 600VAC/VDC. Devices are also certified per CSA. MCBs are approved per IEC-898 and VDE 0641, and certified under IEC-947 and VDE 0660 standards for use in systems rated up to 690VAC. MCBs can be applied to 16 2/3Hz – 400Hz and DC power systems. Special direct current version MCBs include a permanent magnet for DC fault current interruption. These "UC" versions are rated 250/500VDC under UL1077/CSA 22.2 No. 235. Continuous current ratings are as low as 0.2 amperes and up to 125 amperes maximum. MCBs are of compact size and can be quickly mounted on standard 35mm DIN rail or can be front mounted by use of a front mounting kit. MCBs include line and load side terminals for conductors from 18 through 4AWG (0.75 – 25mm2) for 63 amperes. MCBs can also be connected via busbar conductors which can be either upper or lower mounted for top feed or bottom feed. Dual function terminals allow busbars to be connected with main incoming line conductors without separate lugs. MCBs can be used for equipment protection, in commercial appliances, protection of control circuits against overcurrent faults, computer equipment and other computer peripheral devices. Accessories Auxiliary devices can be added to the, S200 series MCBs: • Shunt trips • Auxiliary contacts • Bell alarm contacts • Aux/bell alarm contacts • Undervoltage release Accessory device modules can be field mounted to all above listed ABB MCBs. Auxiliary contacts are also available for the S500 series MCB. 14 14.2 1SXU 000 023 C0201 UL 489 S200U and S200UP MCBs are listed as molded case circuit breakers for use as branch circuit protective devices. Miniature MCCBs and accessories are listed under UL file E212323. UL 1077 S200 and S200P MCBs are recognized as supplementary protectors and are intended for use as overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided or not required. MCBs and accessories are recognized under UL File E76126. CSA C22.2 MCBs and accessories are certified under CSA C22.2 No. 235 per File LR98793. Tripping characteristics Time-current curves ABB miniature circuit breakers are available with different trip characteristics, allowing for maximum system protection. B Characteristic Available with the S200 and S500 series has rated currents of 6 through 63 amperes in 10 steps. The "B" time-current curve is designed primarily for use in cable protection applications. Instantaneous tripping occurs between approximately 3 to 5 times rated current in 50/60Hz systems. This quick trip curve maximizes protection of control circuits under low short circuit fault levels that could damage control wiring. C Characteristic Available in the S200 and S500 series with rated currents up through 63 amperes and the S290 series with rated currents of 80, 100 and 125 amperes. The "C" time-current curve is designed for medium magnetic start-up currents. Instantaneous tripping occurs between 5 and 10 times rated current in 50/60 Hz systems. D Characteristic The new magnetic trip action has an instantaneous trip between 10 and 20 times the breaker rating. Thus, the S200 and S500-D can be a good protective solution for applications involving high in-rush transformers, motors and other high inductive systems. It is also suitable for any application where a high instantaneous trip point is desired. K Characteristic The "K" time-current characteristic considers high magnetic start-up currents from motors, transformers and other equipment. Instantaneous tripping occurs between 8 and 12 times rated current in 50/60Hz systems. The "K" characteristic is available up through 63 amperes. The "K" curve offers the best protection for the broadest range of electrical systems. The higher magnetic trip settings maximizes protection while allowing for higher in-rush currents during system startup. Available in S200P, S200U, S200UP and S500. Z Characteristic Also available up through 63 amperes, the "Z" characteristic offers instantaneous tripping between 2 and 3 times rated current in 50/60Hz systems. This trip characteristic is available in the S200P, S200U and S200UP series with both the 480Y/277VAC and 250/500VDC ratings. Many applications require a very low short circuit trip setting in order to protect semiconductor or other sensitive devices and the "Z" trip characteristic may provide maximum protection and service in these applications. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S2 tem 00 p Se ro M rie s 14 General information Interruption ratings Trip characteristics overview Trip characteristics overview Interruption ratings Voltage 120 VAC Rated interrupting capacity Rated current 0.5 0.5 0.2 0.2 0.2 18kA 32 - 63A 26 - 45A S500-B,C,D S500-K 30kA 6 - 25A 0.15 - 25A S500-B,C,D S500-K 6kA 0.5 - 63A 0.5 - 63A S200-B,C,D S200-K Single pole Single pole 10kA 0.5 0.5 0.2 0.2 0.2 0.2 0.2 0.2 63A 63A 63A 63A 63A 63A 25A 25A S200-B,C,D S200-K S200P-K,Z S200P-K,Z S200U-K,Z S200U-K,Z S200UP-K,Z S200UP-K,Z Multi pole Multi pole Single pole Multi pole Single pole Multi pole Single pole Multi pole 18kA 32 - 63A 26 - 45A S500-B,C,D S500-K 30kA 6 - 25A 0.15 - 25A S500-B,C,D S500-K 6kA 0.5 - 63A 0.5 - 63A S200-B,C,D S200-K 10KA 0.2 - 63A 0.2 - 25A S200P-K,Z S200UP-K,Z 6kA 0.5 - 63A 0.5 - 63A S200-B,C,D S200-K 10KA 0.2 - 63A 0.2 - 25A S200P-K,Z S200UP-K,Z 60 VDC 10kA 0.5 - 63A 0.5 - 63A S200-B,C,D S200-K Single pole Single pole 125 VDC 10kA 0.5 - 63A 0.5 - 63A 0.2 - 63A S200-B,C,D S200-K S280UC-K,Z Multi pole Multi pole Single pole 250 VDC 4.5kA 0.2 - 63A S280UC-K,Z Single pole 500 VDC 4.5kA 0.2 - 63A S280UC-K,Z Multi pole 277 VAC 480Y/277 VAC Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com - 63A 63A 63A 63A 25A Comment 10kA 240 VAC - MCB type S200-B,C,D S200-K S200P-K, Z S200U-K, Z S200UP-K, Z Curve Magnetic characteristic 1 B C D K Z 3 - 5X 5 - 10X 10 - 20X 8 - 12X 2 - 3X Thermal characteristic 1.13 1.13 1.13 1.05 1.05 1.45X 1.45X 1.45X 1.20X 1.20X Series S200, S500 S200, S290, S500 S200, S500 S200, S500 S200 1 All values are relative to MCB's ampere rating. 14 14.3 1SXU 000 023 C0201 M o pr ies em Ser st Sy 200 S General information Tripping curves 14 B C D 5000 5000 5000 1000 500 1000 500 1000 500 100 50 100 50 100 50 10 5 10 5 10 5 1 0.5 1 0.5 1 0.5 AC 0.1 0.05 AC 0.1 0.05 0.01 2 3 5 7 10 20 30 0.01 1 multiple of rated current 2 3 K 10 18 20 30 1 2 3 5 10 20 30 multiple of rated current UC-K 5000 5000 1000 500 1000 500 100 50 100 50 10 5 10 5 1 0.5 1 0.5 seconds 10,000 seconds 5 multiple of rated current 10,000 AC 0.1 0.1 0.05 0.05 DC DC 0.01 0.01 1 2 3 5 8 10 12 20 30 1 multiple of rated current 2 3 5 10 20 30 multiple of rated current UC-Z Z 10,000 5000 5000 1000 500 1000 500 100 50 100 50 10 5 10 5 1 0.5 1 0.5 seconds 10,000 seconds DC DC 0.01 1 AC 0.1 0.05 DC 14 seconds 10,000 seconds 10,000 seconds 10,000 AC 0.1 0.1 0.05 0.05 DC DC 0.01 0.01 1 2 3 5 10 multiple of rated current 14.4 1SXU 000 023 C0201 20 30 1 2 3 5 10 20 30 multiple of rated current Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S2 tem 00 p Se ro M rie s 14 General information Construction details Electro-magnetic protection Tripping lever Operating mechanism Upper terminal Thermal protection-bimetal Operator 14 Arc chamber Space for identification marker Fixed contact Moving contact DIN rail holder Lower terminal Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.5 1SXU 000 023 C0201 M o pr ies em Ser st Sy 200 S S200 480Y/277 VAC Supplemental protectors 14 B UL 1077 CSA C22.2 No. 235 VDE 0641 IEC-898 Cable protection Rated current Catalog number List price S201-B6 S201-B10 S201-B13 S201-B16 S201-B20 S201-B25 S201-B32 S201-B40 S201-B50 S201-B63 $ 36 36 36 36 38 38 40 42 48 56 Delivery class Sugg. order qty Wgt. oz. (1 pc.) 1 pole 6 10 13 16 20 25 32 40 50 63 S201-B, 1 pole S202-B, 2 pole S201-BNA, 1 P+N A 10 4.5 14 List price Delivery class Sugg. order qty S203-B6 S203-B10 S203-B13 S203-B16 S203-B20 S203-B25 S203-B32 S203-B40 S203-B50 S203-B63 $ 118 118 118 118 130 132 142 148 170 194 A 1 13.5 S203-B6NA S203-B10NA S203-B13NA S203-B16NA S203-B20NA S203-B25NA S203-B32NA S203-B40NA S203-B50NA S203-B63NA 142 142 142 142 162 168 176 184 212 240 B 1 18.0 S204-B6 S204-B10 S204-B13 S204-B16 S204-B20 S204-B25 S204-B32 S204-B40 S204-B50 S204-B63 156 156 156 156 172 176 188 196 224 256 B 1 18.0 Wgt. oz. (1 pc.) 6 10 13 16 20 25 32 40 50 63 3 pole + neutral S201-B6NA S201-B10NA S201-B13NA S201-B16NA S201-B20NA S201-B25NA S201-B32NA S201-B40NA S201-B50NA S201-B63NA 62 62 62 62 68 72 74 76 90 102 S202-B6 S202-B10 S202-B13 S202-B16 S202-B20 S202-B25 S202-B32 S202-B40 S202-B50 S202-B63 78 78 78 78 86 88 94 98 112 128 B 5 9.0 2 pole 6 10 13 16 20 25 32 40 50 63 Catalog number 3 pole 1 pole + neutral 6 10 13 16 20 25 32 40 50 63 Rated current 6 10 13 16 20 25 32 40 50 63 4 pole A 5 9.0 6 10 13 16 20 25 32 40 50 63 S203-B, 3 pole Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time S204-B, 4 pole S203-BNA, 3P+N B 10,000 5000 1000 500 100 50 seconds 10 5 1 0.5 AC 0.1 0.05 DC 0.01 1 2 3 5 7 10 20 30 multiple of rated current 14.6 1SXU 000 023 C0201 Discount schedule CB5 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S2 tem 00 p Se ro M rie s 14 S200 480Y/277 VAC Supplemental protectors C UL 1077 CSA C22.2 - NO. 235 VDE 0641 IEC-898 Cable & equipment protection Rated current Catalog number List price S201-C0.5 S201-C1 S201-C1.6 S201-C2 S201-C3 S201-C4 S201-C6 S201-C8 S201-C10 S201-C13 S201-C16 S201-C20 S201-C25 S201-C32 S201-C40 S201-C50 S201-C63 $ 42 42 42 42 42 42 42 42 42 42 42 42 46 48 52 60 68 Delivery class Sugg. order qty Wgt. oz. (1 pc.) 1 pole 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 S201-C, 1 pole S202-C, 2 pole S201-CNA, 1P+N S203-C, 3 pole A 10 4.5 S204-C, 4 pole S203-CNA, 3P+N C 10,000 5000 1000 500 84 84 84 84 84 84 84 84 84 84 84 84 88 90 96 112 130 S202-C0.5 S202-C1 S202-C1.6 S202-C2 S202-C3 S202-C4 S202-C6 S202-C8 S202-C10 S202-C13 S202-C16 S202-C20 S202-C25 S202-C32 S202-C40 S202-C50 S202-C63 96 96 96 96 96 96 96 96 96 96 96 96 106 106 116 136 152 B 5 9.0 Delivery class Sugg. order qty Wgt. oz. (1 pc.) 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 S203-C0.5 S203-C1 S203-C1.6 S203-C2 S203-C3 S203-C4 S203-C6 S203-C8 S203-C10 S203-C13 S203-C16 S203-C20 S203-C25 S203-C32 S203-C40 S203-C50 S203-C63 $ 138 138 138 138 138 138 138 138 138 138 138 138 156 158 174 200 228 A 1 13.5 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 S203-C0.5NA S203-C1NA S203-C1.6NA S203-C2NA S203-C3NA S203-C4NA S203-C6NA S203-C8NA S203-C10NA S203-C13NA S203-C16NA S203-C20NA S203-C25NA S203-C32NA S203-C40NA S203-C50NA S203-C63NA 200 200 200 200 200 200 200 200 200 200 200 200 206 212 224 204 304 B 1 18.0 S204-C0.5 S204-C1 S204-C1.6 S204-C2 S204-C3 S204-C4 S204-C6 S204-C8 S204-C10 S204-C13 S204-C16 S204-C20 S204-C25 S204-C32 S204-C40 S204-C50 S204-C63 218 218 218 218 218 218 218 218 218 218 218 218 234 238 260 300 338 14 4 pole A 5 9.0 100 50 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 B 1 18.0 Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time 10 5 seconds List price 3 pole + neutral S201-C0.5NA S201-C1NA S201-C1.6NA S201-C2NA S201-C3NA S201-C4NA S201-C6NA S201-C8NA S201-C10NA S201-C13NA S201-C16NA S201-C20NA S201-C25NA S201-C32NA S201-C40NA S201-C50NA S201-C63NA 2 pole 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 Catalog number 3 pole 1 pole + neutral 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 Rated current 1 0.5 AC 0.1 0.05 DC 0.01 1 2 3 5 10 18 20 30 multiple of rated current Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Discount schedule CB5 14.7 1SXU 000 023 C0201 M o pr ies em Ser st Sy 200 S S200 480Y/277 VAC Supplemental protectors 14 UL 1077 CSA C22.2 VDE 0641 IEC-898 Cable & equipment protection D Rated current Catalog number List price S201-D0.5 S201-D1 S201-D1.6 S201-D2 S201-D3 S201-D4 S201-D6 S201-D8 S201-D10 S201-D13 S201-D16 S201-D20 S201-D25 S201-D32 S201-D40 S201-D50 S201-D63 $ 42 42 42 42 42 42 42 42 42 42 42 42 46 48 52 60 68 S202-D0.5 S202-D1 S202-D1.6 S202-D2 S202-D3 S202-D4 S202-D6 S202-D8 S202-D10 S202-D13 S202-D16 S202-D20 S202-D25 S202-D32 S202-D40 S202-D50 S202-D63 96 96 96 96 96 96 96 96 96 96 96 96 106 106 116 136 152 Delivery class Sugg. order qty Wgt. oz. (1 pc.) S201-D, 1 pole Catalog number List price S203-D0.5 S203-D1 S203-D1.6 S203-D2 S203-D3 S203-D4 S203-D6 S203-D8 S203-D10 S203-D13 S203-D16 S203-D20 S203-D25 S203-D32 S203-D40 S203-D50 S203-D63 $ 138 138 138 138 138 138 138 138 138 138 138 138 156 158 174 200 228 Delivery class Sugg. order qty A 1 Wgt. oz. (1 pc.) 3 pole 1 pole 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 Rated current A 10 4.5 A 5 9.0 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 13.5 2 pole 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 S202-D, 2 pole 14 S203-D, 3 pole D 10,000 5000 1000 500 100 50 10 5 seconds 1 0.5 AC 0.1 0.05 DC 0.01 1 2 3 5 10 20 30 multiple of rated current 14.8 1SXU 000 023 C0201 Discount schedule CB5 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S2 tem 00 p Se ro M rie s 14 S200 480Y/277 VAC Supplemental protectors K UL 1077 CSA C22.2 - NO. 235 VDE 0641 IEC-898 Cable & equipment protection Rated current Catalog number List price S201-K0.5 S201-K1 S201-K1.6 S201-K2 S201-K3 S201-K4 S201-K5 S201-K6 S201-K8 S201-K10 S201-K13 S201-K15 S201-K16 S201-K20 S201-K25 S201-K30 S201-K32 S201-K40 S201-K50 S201-K60 S201-K63 $ 42 42 42 42 42 42 42 42 42 42 42 42 42 42 46 48 48 52 60 68 68 Delivery class Sugg. order qty Wgt. oz. (1 pc.) S201-K, 1 pole S202-K, 2 pole S201-KNA, 1P+N A 10 4.5 S203-K, 3 pole S201-K0.5NA S201-K1NA S201-K1.6NA S201-K2NA S201-K3NA S201-K4NA S201-K6NA S201-K8NA S201-K10NA S201-K13NA S201-K16NA S201-K20NA S201-K25NA S201-K32NA S201-K40NA S201-K50NA S201-K63NA 84 84 84 84 84 84 84 84 84 84 84 84 88 90 96 112 130 S202-K0.5 S202-K1 S202-K1.6 S202-K2 S202-K3 S202-K4 S202-K5 S202-K6 S202-K8 S202-K10 S202-K13 S202-K15 S202-K16 S202-K20 S202-K25 S202-K30 S202-K32 S202-K40 S202-K50 S202-K60 S202-K63 96 96 96 96 96 96 96 96 96 96 96 96 96 96 106 106 106 116 136 152 152 B 5 9.0 S204-K, 4 pole S203-KNA, 3P+N K 10,000 5000 1000 500 100 50 seconds 10 5 1 0.5 Delivery class Sugg. order qty Wgt. oz. (1 pc.) 0.5 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 S203-K0.5 S203-K1 S203-K1.6 S203-K2 S203-K3 S203-K4 S203-K5 S203-K6 S203-K8 S203-K10 S203-K13 S203-K15 S203-K16 S203-K20 S203-K25 S203-K30 S203-K32 S203-K40 S203-K50 S203-K60 S203-K63 $ 138 138 138 138 138 138 138 138 138 138 138 138 138 138 156 158 158 174 200 228 228 A 1 13.5 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 S203-K0.5NA S203-K1NA S203-K1.6NA S203-K2NA S203-K3NA S203-K4NA S203-K6NA S203-K8NA S203-K10NA S203-K13NA S203-K16NA S203-K20NA S203-K25NA S203-K32NA S203-K40NA S203-K50NA S203-K63NA 200 200 200 200 200 200 200 200 200 200 200 200 206 212 224 264 304 B 1 18.0 S204-K0.5 S204-K1 S204-K1.6 S204-K2 S204-K3 S204-K4 S204-K6 S204-K8 S204-K10 S204-K13 S204-K16 S204-K20 S204-K25 S204-K32 S204-K40 S204-K50 S204-K63 218 218 218 218 218 218 218 218 218 218 218 218 234 238 260 300 338 14 4 pole 2 pole 0.5 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 List price 3 pole + neutral 1 pole + neutral 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 Catalog number 3 pole 1 pole 0.5 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 Rated current A 5 9.0 AC 0.1 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 B 1 18.0 Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time 0.05 DC 0.01 1 2 3 5 8 10 12 20 30 multiple of rated current Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Discount schedule CB5 14.9 1SXU 000 023 C0201 M o pr ies em Ser st Sy 200 S S200P 480Y/277 VAC Supplemental protectors 14 K UL 1077 CSA C22.2 - NO. 235 VDE 0660 Cable & equipment protection Rated current Catalog number List price S201P-K0.2 S201P-K0.3 S201P-K0.5 S201P-K0.75 S201P-K1 S201P-K1.6 S201P-K2 S201P-K3 S201P-K4 S201P-K6 S201P-K8 S201P-K10 S201P-K13 S201P-K16 S201P-K20 S201P-K25 S201P-K32 S201P-K40 S201P-K50 S201P-K63 $ 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 56 58 64 70 80 S202P-K0.2 S202P-K0.3 S202P-K0.5 S202P-K0.75 S202P-K1 S202P-K1.6 S202P-K2 S202P-K3 S202P-K4 S202P-K6 S202P-K8 S202P-K10 S202P-K13 S202P-K16 S202P-K20 S202P-K25 S202P-K32 S202P-K40 S202P-K50 S202P-K63 128 128 128 128 128 128 128 128 128 128 128 128 128 128 128 130 134 134 162 182 Delivery class Sugg. order qty Wgt. oz. (1 pc.) 1 pole 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 S201P-K, 1 pole Rated current Catalog number List price S203P-K0.2 S203P-K0.3 S203P-K0.5 S203P-K0.75 S203P-K1 S203P-K1.6 S203P-K2 S203P-K3 S203P-K4 S203P-K6 S203P-K8 S203P-K10 S203P-K13 S203P-K16 S203P-K20 S203P-K25 S203P-K32 S203P-K40 S203P-K50 S203P-K63 $ 194 194 194 194 194 194 194 194 194 194 194 194 194 194 194 196 200 214 246 280 Delivery class Sugg. order qty A 1 Wgt. oz. (1 pc.) 3 pole A 10 4.6 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 13.9 2 pole S202P-K, 2 pole 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 14 S203P-K, 3 pole Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time A 5 9.2 K 10,000 5000 1000 500 100 50 seconds 10 5 1 0.5 AC 0.1 0.05 DC 0.01 1 2 3 5 8 10 12 20 30 multiple of rated current 14.10 1SXU 000 023 C0201 Discount schedule CB7 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S2 tem 00 p Se ro M rie s 14 S280 (W) 480Y/277 VAC Supplemental protectors K UL 1077 CSA C22.2 - NO. 235 VDE 0660 Cable & equipment protection Rated current Catalog number List price S281-K0.2W S281-K0.3W S281-K0.5W S281-K0.75W S281-K1W S281-K1.6W S281-K2W S281-K3W S281-K4W S281-K6W S281-K8W S281-K10W S281-K13W S281-K16W S281-K20W S281-K25W S281-K32W S281-K40W S281-K50W S281-K63W $ 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 56 58 64 70 80 S282-K0.2W S282-K0.3W S282-K0.5W S282-K0.75W S282-K1W S282-K1.6W S282-K2W S282-K3W S282-K4W S282-K6W S282-K8W S282-K10W S282-K13W S282-K16W S282-K20W S282-K25W S282-K32W S282-K40W S282-K50W S282-K63W 128 128 128 128 128 128 128 128 128 128 128 128 128 128 128 130 134 134 162 182 Delivery class Sugg. order qty Wgt. oz. (1 pc.) 1 pole 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 S281-KW, 1 pole Catalog number List price S283-K0.2W S283-K0.3W S283-K0.5W S283-K0.75W S283-K1W S283-K1.6W S283-K2W S283-K3W S283-K4W S283-K6W S283-K8W S283-K10W S283-K13W S283-K16W S283-K20W S283-K25W S283-K32W S283-K40W S283-K50W S283-K63W $ 194 194 194 194 194 194 194 194 194 194 194 194 194 194 194 196 200 214 246 280 Delivery class Sugg. order qty B 3 Wgt. oz. (1 pc.) 3 pole B 10 4.6 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 13.9 2 pole S282-KW, 2 pole 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 S283-KW, 3 pole Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time B 5 9.2 14 e gu n o g t rs n i r o th nect i w se l con u r a Fo min r te K 10,000 5000 1000 500 100 50 10 5 seconds Rated current 1 0.5 AC 0.1 0.05 DC 0.01 1 2 3 5 8 10 12 20 30 multiple of rated current Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Discount schedule CB7 14.11 1SXU 000 023 C0201 M o pr ies em Ser st Sy 200 S S280UC 500 VDC Supplemental protectors 14 K UL 1077 VDE 0660 CSA 22.2 No. 235 Cable and Equipment Protection Rated current Catalog number List price Delivery class Sugg. order qty Wgt. oz. (1 pc.) 1 pole 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 63 S281UC-K, 1 pole Rated current Catalog number List price S283UC-K0.2 S283UC-K0.3 S283UC-K0.5 S283UC-K0.75 S283UC-K1 S283UC-K1.6 S283UC-K2 S283UC-K3 S283UC-K4 S283UC-K6 S283UC-K8 S283UC-K10 S283UC-K16 S283UC-K20 S283UC-K25 S283UC-K32 S283UC-K40 S283UC-K50 S283UC-K63 $ 370 370 370 370 370 370 370 370 370 370 370 370 370 370 382 408 448 472 534 Delivery class Sugg. order qty B 3 Wgt. oz. (1 pc.) 3 pole S281UC-K0.2 S281UC-K0.3 S281UC-K0.5 S281UC-K0.75 S281UC-K1 S281UC-K1.6 S281UC-K2 S281UC-K3 S281UC-K4 S281UC-K6 S281UC-K8 S281UC-K10 S281UC-K16 S281UC-K20 S281UC-K25 S281UC-K32 S281UC-K40 S281UC-K50 S281UC-K63 $ 104 104 104 104 104 104 104 104 104 104 104 104 104 104 108 110 116 136 152 S282UC-K0.2 S282UC-K0.3 S282UC-K0.5 S282UC-K0.75 S282UC-K1 S282UC-K1.6 S282UC-K2 S282UC-K3 S282UC-K4 S282UC-K6 S282UC-K8 S282UC-K10 S282UC-K16 S282UC-K20 S282UC-K25 S282UC-K32 S282UC-K40 S282UC-K50 S282UC-K63 242 242 242 242 242 242 242 242 242 242 242 242 242 242 248 256 266 312 348 B 10 4.6 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 63 13.9 2 pole 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 63 S282UC-K, 2 pole 14 S283UC-K, 3 pole Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time B 5 9.2 Direct current applications The S280UC differs from standard miniature circuit breakers in that the UC versions include a permanent magnet which aids in the extinguishing of the arc during medium and high level faults. It is necessary to observe the correct polarity and current direction when connecting the UC breakers. Two examples of correct connection are shown below. Maximum voltage between leads 250VDC UC-K 10,000 500VDC 1000 500 L- L+ 100 50 10 5 seconds Two Pole LS282UC Single Pole S281UC 5000 1 0.5 -1 -1 +2 +2 +2 0.1 LOAD + 0.05 DC 0.01 1 2 3 5 10 multiple of rated current 14.12 1SXU 000 023 C0201 20 30 L-1 L+ L+ 3+ 3+ 4- 4LOAD + LOAD + Termination points are marked on all UC type MCBs, points one (1) and four (4) are negative and points two (2) and three (3) are positive. Four pole breakers are also available for voltage reversal applications. Discount schedule CB7 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S2 tem 00 p Se ro M rie s 14 S200P & S280UC 480Y/277 VAC & 500 VDC Supplemental protectors UL 1077 VDE 0660 CSA 22.2 No. 235 Fast trip characteristic Z 480Y/277 VAC Rated current 500 VDC Catalog number List price Delivery class Sugg. order qty Wgt. oz. (1 pc.) S201P-Z, 1 pole S201P-Z0.5 S201P-Z1 S201P-Z1.6 S201P-Z2 S201P-Z3 S201P-Z4 S201P-Z6 S201P-Z8 S201P-Z10 S201P-Z16 S201P-Z20 S201P-Z25 S201P-Z32 S201P-Z40 S201P-Z50 S201P-Z63 $ 70 70 70 70 70 70 70 70 70 70 70 70 74 78 88 100 S202P-Z0.5 S202P-Z1 S202P-Z1.6 S202P-Z2 S202P-Z3 S202P-Z4 S202P-Z6 S202P-Z8 S202P-Z10 S202P-Z16 S202P-Z20 S202P-Z25 S202P-Z32 S202P-Z40 S202P-Z50 S202P-Z63 162 162 162 162 162 162 162 162 162 162 162 170 170 176 206 232 S203P-Z0.5 S203P-Z1 S203P-Z1.6 S203P-Z2 S203P-Z3 S203P-Z4 S203P-Z6 S203P-Z8 S203P-Z10 S203P-Z16 S203P-Z20 S203P-Z25 S203P-Z32 S203P-Z40 S203P-Z50 S203P-Z63 244 244 244 244 244 244 244 244 244 244 244 248 254 266 306 344 B 10 4.5 S202P-Z, 2 pole B 5 9.2 S203P-Z, 3 pole Z Sugg. order qty B 10 4.6 B 5 9.2 Wgt. oz. (1 pc.) 0.5 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 63 S281UC-Z0.5 S281UC-Z1 S281UC-Z1.6 S281UC-Z2 S281UC-Z3 S281UC-Z4 S281UC-Z6 S281UC-Z8 S281UC-Z10 S281UC-Z16 S281UC-Z20 S281UC-Z25 S281UC-Z32 S281UC-Z40 S281UC-Z50 S281UC-Z63 $ 168 168 168 168 168 168 168 168 168 168 168 170 176 188 216 242 0.5 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 63 S282UC-Z0.5 S282UC-Z1 S282UC-Z1.6 S282UC-Z2 S282UC-Z3 S282UC-Z4 S282UC-Z6 S282UC-Z8 S282UC-Z10 S282UC-Z16 S282UC-Z20 S282UC-Z25 S282UC-Z32 S282UC-Z40 S282UC-Z50 S282UC-Z63 390 390 390 390 390 390 390 390 390 390 390 398 410 426 498 558 B 1 13.9 0.5 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 63 S283UC-Z0.5 S283UC-Z1 S283UC-Z1.6 S283UC-Z2 S283UC-Z3 S283UC-Z4 S283UC-Z6 S283UC-Z8 S283UC-Z10 S283UC-Z16 S283UC-Z20 S283UC-Z25 S283UC-Z32 S283UC-Z40 S283UC-Z50 S283UC-Z63 594 594 594 594 594 594 594 594 594 594 594 603 612 657 756 855 14 B 3 13.9 UC-Z 10,000 10,000 5000 5000 1000 500 1000 500 100 50 100 50 10 5 10 5 1 0.5 seconds seconds Delivery class 3 pole 3 pole 0.5 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 63 List price 2 pole 2 pole 0.5 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 63 Catalog number 1 pole 1 pole 0.5 1 1.6 2 3 4 6 8 10 16 20 25 32 40 50 63 Rated current AC 0.1 0.05 Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time 1 0.5 0.1 0.05 DC DC 0.01 0.01 1 2 3 5 10 20 30 multiple of rated current Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 1 2 3 5 10 20 30 multiple of rated current Discount schedule CB7 14.13 1SXU 000 023 C0201 M o pr ies em Ser st Sy 200 S S200U 240 VAC Miniature MCCBs 14 K UL 489 CSA C22.2 - NO. 5 VDE 0660 Cable & equipment protection Rated current Catalog number List price S201U-K0.2 S201U-K0.3 S201U-K0.5 S201U-K0.75 S201U-K1 S201U-K1.6 S201U-K2 S201U-K3 S201U-K4 S201U-K5 S201U-K6 S201U-K8 S201U-K10 S201U-K13 S201U-K15 S201U-K16 S201U-K20 S201U-K25 S201U-K30 S201U-K32 S201U-K40 S201U-K50 S201U-K60 S201U-K63 $ 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 56 58 58 64 70 80 80 S202U-K0.2 S202U-K0.3 S202U-K0.5 S202U-K0.75 S202U-K1 S202U-K1.6 S202U-K2 S202U-K3 S202U-K4 S202U-K5 S202U-K6 S202U-K8 S202U-K10 S202U-K13 S202U-K15 S202U-K16 S202U-K20 S202U-K25 S202U-K30 S202U-K32 S202U-K40 S202U-K50 S202U-K60 S202U-K63 128 128 128 128 128 128 128 128 128 128 128 128 128 128 128 128 128 130 134 134 134 162 182 182 Delivery class Sugg. order qty Wgt. oz. (1 pc.) 1 pole 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 S201U-K, 1 pole S202U-K, 2 pole 14 S203U-K, 3 pole S204U-K, 4 pole K Catalog number List price S203U-K0.2 S203U-K0.3 S203U-K0.5 S203U-K0.75 S203U-K1 S203U-K1.6 S203U-K2 S203U-K3 S203U-K4 S203U-K5 S203U-K6 S203U-K8 S203U-K10 S203U-K13 S203U-K15 S203U-K16 S203U-K20 S203U-K25 S203U-K30 S203U-K32 S203U-K40 S203U-K50 S203U-K60 S203U-K63 $ 194 194 194 194 194 194 194 194 194 194 194 194 194 194 194 194 194 196 200 200 214 246 280 280 S204U-K0.2 S204U-K0.3 S204U-K0.5 S204U-K0.75 S204U-K1 S204U-K1.6 S204U-K2 S204U-K3 S204U-K4 S204U-K5 S204U-K6 S204U-K8 S204U-K10 S204U-K13 S204U-K15 S204U-K16 S204U-K20 S204U-K25 S204U-K30 S204U-K32 S204U-K40 S204U-K50 S204U-K60 S204U-K63 265 265 265 265 265 265 265 265 265 265 265 265 265 265 265 265 265 275 285 285 314 343 392 392 Delivery class Sugg. order qty A 1 13.9 B 1 18.0 Wgt. oz. (1 pc.) 3 pole A 10 4.6 2 pole 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 Rated current 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 4 pole A 5 9.2 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 10,000 5000 Delivery Class 1000 500 h nc e a r c s b devi a e ed ist tectiv l 9 48 t pro L U cui cir 100 50 seconds 10 5 1 0.5 AC 0.1 0.05 DC A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time 0.01 1 2 3 5 8 10 12 20 30 multiple of rated current 14.14 1SXU 000 023 C0201 Discount schedule CB12 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S2 tem 00 p Se ro M rie s 14 S200U 240 VAC Miniature MCCBs Z UL 489 CSA C22.2 - NO. 5 VDE 0660 Cable & equipment protection Rated current Catalog number List price S201U-Z0.5 S201U-Z0.75 S201U-Z1 S201U-Z1.6 S201U-Z2 S201U-Z3 S201U-Z4 S201U-Z5 S201U-Z6 S201U-Z8 S201U-Z10 S201U-Z15 S201U-Z16 S201U-Z20 S201U-Z25 S201U-Z30 S201U-Z32 S201U-Z40 S201U-Z50 S201U-Z60 S201U-Z63 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 74 74 78 88 100 100 S202U-Z0.5 S202U-Z0.75 S202U-Z1 S202U-Z1.6 S202U-Z2 S202U-Z3 S202U-Z4 S202U-Z5 S202U-Z6 S202U-Z8 S202U-Z10 S202U-Z15 S202U-Z16 S202U-Z20 S202U-Z25 S202U-Z30 S202U-Z32 S202U-Z40 S202U-Z50 S202U-Z60 S202U-Z63 162 162 162 162 162 162 162 162 162 162 162 162 162 162 170 170 170 176 206 232 232 Delivery class Sugg. order qty Wgt. oz. (1 pc.) 1 pole 0.5 0.75 1 1.6 2 3 4 5 6 8 10 15 16 20 25 30 32 40 50 60 63 S201U-Z, 1 pole S202U-Z, 2 pole S203U-Z, 3 pole Catalog number List price Delivery class Sugg. order qty Wgt. oz. (1 pc.) 3 pole A 10 4.6 2 pole 0.5 0.75 1 1.6 2 3 4 5 6 8 10 15 16 20 25 30 32 40 50 60 63 Rated current 0.5 0.75 1 1.6 2 3 4 5 6 8 10 15 16 20 25 30 32 40 50 60 63 S203U-Z0.5 S203U-Z0.75 S203U-Z1 S203U-Z1.6 S203U-Z2 S203U-Z3 S203U-Z4 S203U-Z5 S203U-Z6 S203U-Z8 S203U-Z10 S203U-Z15 S203U-Z16 S203U-Z20 S203U-Z25 S203U-Z30 S203U-Z32 S203U-Z40 S203U-Z50 S203U-Z60 S203U-Z63 244 244 244 244 244 244 244 244 244 244 244 244 244 244 248 254 254 266 306 344 344 A 1 13.9 S204U-Z0.5 S204U-Z0.75 S204U-Z1 S204U-Z1.6 S204U-Z2 S204U-Z3 S204U-Z4 S204U-Z5 S204U-Z6 S204U-Z8 S204U-Z10 S204U-Z15 S204U-Z16 S204U-Z20 S204U-Z25 S204U-Z30 S204U-Z32 S204U-Z40 S204U-Z50 S204U-Z60 S204U-Z63 343 343 343 343 343 343 343 343 343 343 343 343 343 343 343 363 363 382 431 490 490 B 1 18.0 4 pole A 5 9.2 0.5 0.75 1 1.6 2 3 4 5 6 8 10 15 16 20 25 30 32 40 50 60 63 Delivery Class S204U-Z, 4 pole h nc e a r c s b devi a e ed ist tectiv l 9 48 t pro L U cui cir Z 10,000 5000 1000 500 100 50 seconds 10 5 A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time 1 0.5 AC 0.1 0.05 DC 0.01 1 2 3 5 10 20 30 multiple of rated current Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Discount schedule CB12 14.15 1SXU 000 023 C0201 14 M o pr ies em Ser st Sy 200 S S200UP 480Y/277 VAC Miniature MCCBs 14 K UL 489 CSA C22.2 - NO. 5 VDE 0660 Cable & equipment protection Rated current Catalog number List price Delivery class Sugg. order qty Wgt. oz. (1 pc.) 1 pole 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 S201UP-K, 1 pole S202UP-K, 2 pole 14 S203UP-K, 3 pole Catalog number List price Delivery class Sugg. order qty A 1 13.9 B 1 18.0 Wgt. oz. (1 pc.) 3 pole S201UP-K0.2 S201UP-K0.3 S201UP-K0.5 S201UP-K0.75 S201UP-K1 S201UP-K1.6 S201UP-K2 S201UP-K3 S201UP-K4 S201UP-K5 S201UP-K6 S201UP-K8 S201UP-K10 S201UP-K13 S201UP-K15 S201UP-K16 S201UP-K20 S201UP-K25 $ 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 S202UP-K0.2 S202UP-K0.3 S202UP-K0.5 S202UP-K0.75 S202UP-K1 S202UP-K1.6 S202UP-K2 S202UP-K3 S202UP-K4 S202UP-K5 S202UP-K6 S202UP-K8 S202UP-K10 S202UP-K13 S202UP-K15 S202UP-K16 S202UP-K20 S202UP-K25 210 210 210 210 210 210 210 210 210 210 210 210 210 210 210 210 210 210 A 10 4.6 2 pole 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 Rated current 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 S203UP-K0.2 S203UP-K0.3 S203UP-K0.5 S203UP-K0.75 S203UP-K1 S203UP-K1.6 S203UP-K2 S203UP-K3 S203UP-K4 S203UP-K5 S203UP-K6 S203UP-K8 S203UP-K10 S203UP-K13 S203UP-K15 S203UP-K16 S203UP-K20 S203UP-K25 $ 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 S204UP-K0.2 S204UP-K0.3 S204UP-K0.5 S204UP-K0.75 S204UP-K1 S204UP-K1.6 S204UP-K2 S204UP-K3 S204UP-K4 S204UP-K5 S204UP-K6 S204UP-K8 S204UP-K10 S204UP-K13 S204UP-K15 S204UP-K16 S204UP-K20 S204UP-K25 440 440 440 440 440 440 440 440 440 440 440 440 440 440 440 440 440 440 4 pole A 5 9.2 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 Delivery Class h nc e a r c s b devi a e ed ist tectiv l 9 48 t pro L U cui cir S204UP-K, 4 pole K 10,000 5000 1000 500 A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time 100 50 seconds 10 5 1 0.5 AC 0.1 0.05 DC 0.01 1 2 3 5 8 10 12 20 30 multiple of rated current 14.16 1SXU 000 023 C0201 Discount schedule CB17 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S2 tem 00 p Se ro M rie s 14 S200UP 480Y/277 VAC Miniature MCCBs Z UL 489 CSA C22.2 - NO. 5 VDE 0660 Cable & equipment protection Rated current Catalog number List price Delivery class Sugg. order qty Wgt. oz. (1 pc.) 1 pole 0.5 0.75 1 1.6 2 3 4 5 6 8 10 15 16 20 25 S201UP-Z, 1 pole S202UP-Z, 2 pole Catalog number List price Delivery class Sugg. order qty A 1 13.9 B 1 18.0 Wgt. oz. (1 pc.) 3 pole S201UP-Z0.5 S201UP-Z0.75 S201UP-Z1 S201UP-Z1.6 S201UP-Z2 S201UP-Z3 S201UP-Z4 S201UP-Z5 S201UP-Z6 S201UP-Z8 S201UP-Z10 S201UP-Z15 S201UP-Z16 S201UP-Z20 S201UP-Z25 115 115 115 115 115 115 115 115 115 115 115 115 115 115 115 S202UP-Z0.5 S202UP-Z0.75 S202UP-Z1 S202UP-Z1.6 S202UP-Z2 S202UP-Z3 S202UP-Z4 S202UP-Z5 S202UP-Z6 S202UP-Z8 S202UP-Z10 S202UP-Z15 S202UP-Z16 S202UP-Z20 S202UP-Z25 270 270 270 270 270 270 270 270 270 270 270 270 270 270 270 A 10 4.6 2 pole 0.5 0.75 1 1.6 2 3 4 5 6 8 10 15 16 20 25 Rated current 0.5 0.75 1 1.6 2 3 4 5 6 8 10 15 16 20 25 S203UP-Z0.5 S203UP-Z0.75 S203UP-Z1 S203UP-Z1.6 S203UP-Z2 S203UP-Z3 S203UP-Z4 S203UP-Z5 S203UP-Z6 S203UP-Z8 S203UP-Z10 S203UP-Z15 S203UP-Z16 S203UP-Z20 S203UP-Z25 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 S204UP-Z0.5 S204UP-Z0.75 S204UP-Z1 S204UP-Z1.6 S204UP-Z2 S204UP-Z3 S204UP-Z4 S204UP-Z5 S204UP-Z6 S204UP-Z8 S204UP-Z10 S204UP-Z15 S204UP-Z16 S204UP-Z20 S204UP-Z25 564 564 564 564 564 564 564 564 564 564 564 564 564 564 564 4 pole A 5 9.2 0.5 0.75 1 1.6 2 3 4 5 6 8 10 15 16 20 25 14 Delivery Class S203UP-Z, 3 pole A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time ch n a br evice s d a ive d e t t is 9 l rotec 8 4 p UL cuit cir S204UP-Z, 4 pole Z 10,000 5000 1000 500 100 50 seconds 10 5 1 0.5 AC 0.1 0.05 DC 0.01 1 2 3 5 10 20 30 multiple of rated current Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Discount schedule CB17 14.17 1SXU 000 023 C0201 M o pr ies em Ser st Sy 200 S S290 480Y/277 VAC 14 VDE 0660 Cable and equipment protection C 480 VAC Rated current List price Delivery class Sugg. order qty S291-C80 S291-C100 S291-C125 $ 138 144 192 B 6 9.2 S292-C80 S292-C100 S292-C125 340 364 568 B 3 18.4 S293-C80 S293-C100 S293-C125 536 548 732 B 2 27.6 S294-C80 S294-C100 S294-C125 740 756 948 B 1 36.8 72 B 1 1.75 112 B 1 1.75 144 B 1 6.2 B 1 6.2 Catalog number Wgt. oz. (1 pc.) 1 pole 80 100 125 2 pole 80 100 125 S291-C80 3 pole 80 100 125 4 pole 80 100 125 Auxiliary contact S290-H11 S290-H11 Bell alarm S290-S Shunt trip S290-A1 For field mounting, left side, 110V – 415VAC S290-A2 144 For field mounting, left side, 24 – 48VDC 14 Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time C 10,000 5000 1000 500 100 50 seconds 10 5 1 0.5 AC 0.1 0.05 DC 0.01 1 2 3 5 10 18 20 30 multiple of rated current 14.18 1SXU 000 023 C0201 Discount schedule CB12 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14 Sy s S2 tem 00 p Se ro M rie s Accessories Busbars 0HASE AmpNumber For of rating use on: poles S200 & S200P 1 , , BusbarEnd cap Catalog ListDelivery length catalog number price class (mm) number 63 80 60 60 988 988 S200U & S200UP 80 23 6 12 18 108 216 324 PS-END0 PS1/60 PS-END0 PS1/60/16 – – – PS1/6/16BP PS1/12/16BP PS1/18/16BP Suggested Weight order qty. (ozs) quantity $ 36 1 A 46 9 14 30 60 B 1 90 1.4 2.9 4.3 0HASE AmpNumber BusbarEnd cap Catalog ListDelivery For of length catalog rating number price class use on: poles (mm) number 63 80 58 58 1035 1035 PS-ENDSP PS-ENDSP PS2/58SP PS2/58/16SP $ 122 152 A 1 11 18 S200U & S200UP 80 23 6 12 18 108 216 324 – – – PS2/6/16BP PS2/12/16BP PS2/18/16BP 40 80 B 1 120 1.8 3.7 5.5 S200 & S200P 1 , , Suggested Weight order qty. (ozs) quantity , , , , 0HASE AmpNumber BusbarEnd cap Catalog ListDelivery For of length catalog rating number price class use on: poles (mm) number , , , S200 & S200P 1 63 80 60 60 1065 1065 S200U & S200UP 80 23 6 12 18 108 216 324 PS-ENDSP PS3/60SP PS-ENDSP PS3/60/16SP – – – PS3/6/16BP PS3/12/16BP PS3/18/16BP Suggested order qty. quantity Weight (ozs) $ 130 A 1 176 12 20 44 88 B 1 132 2 4 6 , , , , , , 0HASE AmpNumber BusbarEnd cap Catalog ListDelivery For of length catalog rating number price class use on: poles (mm) number , , , Suggested order qty. quantity Weight (ozs) S200 & $ 236 80 60 1056 PS-END1SP PS4/60/16SP B 1 S200P 22 Delivery Class , A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time , , , , , , , , NOTE All bus bars may be center fed in order to double the ampacity rating NOTE BUS BARS MAY BE USED ON LINE OR LOAD SIDE OF MCBS 1 UL Approved for use on UL1077 miniature circuit breakers. UL File #E76126 2 UL approved for use on UL 489 miniature circuit breakers. UL File # E250145 3 UL 489 bus bars may not be cut. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Discount schedule CB8 14.19 1SXU 000 023 C0201 14 14 M o pr ies em er st 0 S y S 20 S Accessories Busbars 1 Phase with 1 auxiliary AmpNumber For of rating use on: poles S200 & S200P 63 80 38 38 BusbarEnd cap Catalog ListDelivery length catalog number price class (mm) number 1044 1044 PS-END0 PS-END0 Suggested Weight order qty. (ozs) quantity PS1/38H $ 50 1 B PS1/38/16H 56 7.4 10.1 L1 L1 L1 L1.... 2 Phase with 1 auxillary 0HASE AmpNumber For of rating use on: poles , , , , , , , L1 L1 L2 L1 L2 , , 80 48 1065 PS-ENDSP PS2/48/16SP $ 174 Suggested Weight order qty. (ozs) quantity B 1 23.3 L2 L1 L2.... 3 Phase with 1 auxillary 0HASE AmpNumber For of rating use on: poles , 200 & S S200P , L1 L2 14 L1 L2 L3 200 & S S200P BusbarEnd cap Catalog ListDelivery length catalog number price class (mm) number 80 39 BusbarEnd cap Catalog ListDelivery length catalog number price class (mm) number 980 PS-ENDSP PS3/39/16SP $ 158 B Suggested Weight order qty. (ozs) quantity 1 22.6 L3 L1 L2 L3.... 0HASE.FORUSEWITHPOLE-#"gS ONPHASE7SYSTEM AmpNumber For of rating use on: poles 200 & S S200P 80 58 BusbarEnd cap Catalog ListDelivery length catalog number price class (mm) number 1048 PS-END1SPPS4/58/16NSP $ 238 B Suggested Weight order qty. (ozs) quantity 1 30.8 Insulated busbar assembly contains 4 separate circuits for use with 1+N or 2 pole MCBs. . , , , Delivery Class , . , . , . , . A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time , -#""USBARACCESSORIES "USBARMOUNTED NOTE TERMINALBLOCK "USTOOTHCOVERS PN3:%3+POLE All bus bars may bePN3:"3+POLES center fed in order to double the ampacity rating NOTE BUS BARS MAY BE USED ON LINE OR LOAD SIDE OF MCBS"USBAR%ND#APS 14.20 1SXU 000 023 C0201 Discount schedule CB8 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14 Sy s S2 tem 00 p Se ro M rie s Accessories Electrical accessories For use on: Catalog number List price Delivery class Suggested order quantities Wgt. oz. (1 pc.) Auxiliary contacts For field mounting: right side S200 & S2C-H6R Form C 1 NO / 1 NC S200P $ 36 A 1 S200U S2C-H6RU S200UP S2C-H6R 1.4 The auxiliary contacts will signal whether the breaker is in the ON or OFF position. The contacts are rated 2A/277 VAC and 1.5A/125 VDC. Minimum operating voltage is 24 VAC/VDC. Wire size: 18 AWG to 16 AWG. Bell alarm S200 & S2C-S/H6R S200P A 1 For field mounting, right side 48 S200U S2C-S6RU S200UP S2C-S/H6R 1.4 The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically the contacts would be connected to an alarm or bell to signal the operator that an overcurrent trip has occured. The bell alarm also includes a test button for testing the alarm contacts without opening the breaker. The contact is rated 2A/277 VAC and 1.5A/125 VDC. Minimum operating voltage is 24 VAC/VDC. * Combination bell alarm/auxiliary contact Shunt trip S200 & S2C-A1 For field mounting, right side S200P S2C-A2 A1: 12-60 VAC (12-60VDC) A2: 110-415 VAC (110-250 VDC) S200U & S2C-A1U S200UP S2C-A2U 138 A 1 5.2 For remote tripping of breaker, a shunt trip device can be added to the MCB. The solenoid device opens the breaker after control voltage is applied. Shunt trips are available for on control system voltage (12-415 VAC/VDC). S2C-A_ Undervoltage release For field mounting, right side 12 VDC 24 VAC 48 VAC S200 & 110 VAC S200P 220 VAC 415 VAC S2C-UA12 S2C-UA24 S2C-UA48 216 S2C-UA110 S2C-UA230 S2C-UA400 A 1 5.2 When control voltage drops below approximately 50% of rated voltage, the UVR opens the breaker. The breaker can not be operated unless proper control voltage is first applied to the UVR coil. Similar in size and mounting to the shunt trip accessory. Delivery Class S2C-UA_ A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Discount schedule CB8 9/6/07 Rev. 14.21 1SXU 000 023 C0201 14 M o pr ies em Ser st Sy 200 S 14 Accessories S200 Electrical accessories Catalog number List price Delivery class Suggested order quantities Wgt. oz. (1 pc.) S500-ME1 S500-ME2 S500-ME3 S500-K1 $ 60 70 80 16 A 1 2.1 2.9 3.6 1.5 MB-CL 35 A 1 2 MB-3PD 35 A 1 2.5 SA1 SA2 9 19 A 10 0.7 0.1 BS BS1/40 74 74 A 1 — 12402 12404 12406 12408 32 45 56 66 B 1 2.0 2.8 3.4 4.1 84 98 126 210 A 1 8.1 10.8 20.4 41.0 BP-1P BP-12P 6 7 A — 1 — — — S2C-DH 76 A 1 9.2 21 A 1 8 Front mounting kit For 2 poles For 2 – 5 poles For 2 – 10 poles Optional rear terminals S500-ME2 Includes flange, mounting rail and hardware. Front mounting clip For 1 – 4 poles Simple mounting clip for up to four module mounting. Front mounting bracket For 1 – 3 poles For flush mounting of three pole MCBs: includes hardware. MB-CL Locking device Adaptor only Padlock only w/ 2 keys Allows breaker to be locked in ON or OFF position. Labeling accessory MB-3PD 1 sheet = 40 blank labels 1 sheet = 40 numbered labels Adhesive labels mount on front face of components. Enclosure, IP40 SA1 For 2 modules For 4 modules For 6 modules For 8 modules For additional protection against accidental contact. Includes integrated mounting rail. Enclosure, IP55 14 SA2 For 4 modules For 6 modules For 10 modules For 20 modules 12644 12646 12650 12652 Molded plastic complete with mounting rail and knock-outs for cable entries. Blanking plates Single pole (set of 10) Twelve pole (snap-off, set of 1) 12404 Handle mechanism For use with 2, 3 and 4 pole S2 MCBs and disconnect switch handles with 5mm shaft. DIN rail Universal mounting SMR-39 35mm DIN rails are available in 39-inch strips (1 meter). S2C-DH Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time SMR-39 14.22 1SXU 000 023 C0201 Discount schedule CB8 Discount schedule H6 – Handles & shafts Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14 Sy s S2 tem 00 p Se ro M rie s Accessories S200 Busbar accessories Catalog List Delivery Suggested Description number price class order qty. Busbar end caps SZ-BSK 2 & 3 phase 4 phase PS-ENDSP PS-END1SP Weight ounce qty. (2 pc.) $ 2 A 10 — Busbar tooth covers (shrouds unused portion of busbar) SZ-BSK 4 A 10 — Busbar mounted terminal block, 1 pole, for use on all busbars. Wire size: 14 AWG to 2 AWG SZ-ESK2 10 A 1 1.0 Delivery class Suggested order quantities Wgt. oz. (1 pc.) Electrical accessories Item Catalog number List price Posidrive tools SZ-ESK2 Screwdriver, #1 Screwdriver, #2 Bit, #1 Bit, #2 SD-PZ1 SD-PZ2 BIT-PZ1 BIT-PZ2 $ 40 40 4 4 A A A A 1 1 1 1 4 4 4 4 List price Delivery class Suggested order quantities Wgt. oz. (1 pc.) $ 15 B 15 10 10 0.5 0.5 15 B 15 10 10 0.5 0.5 Connection terminals SZ-AST55_ Cross section AWG/mm2 For use on: Catalog number 1/0 (50mm2) Straight S200 & S200P 2 1/0 (50mm ) 90° SZ-AST55I SZ-AST50I 1/0 (50mm2) Straight S200U & S200UP 1/0 (50mm2) 90° SZ-AST55U SZ-AST50U Ring tongue accessories Catalog List Delivery Description For use on number price class Ring tongue terminal S200 & S200P S200U & S200UP Plug SZ-AST55UPRT S2C-P Suggested order qty. qty. (2 pc.) Weight ounce $ 5 A 10 0.5 N/C A 10 — SZ-AST50_ Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Discount schedule CB8 9/6/07 Rev. 14.23 1SXU 000 023 C0201 14 M o pr ies em Ser st Sy 200 S 14 Technical data Mounting and operating instructions Mounting Operation Universal mounting position using snap-on mounting to standard 35x7.5mm DIN rail. MCBs are switched on by moving the handle to the upper position. Stamped onto the handle switch, a “I” is visible confirming that the breaker is closed. Miniature circuit breakers (MCBs) can also be mounted to front of door using a panel cut-out with breaker handle protruding through panel opening for external operation. Special front mounting kit page 23. Mounting MCB Connection Terminals are suitable for solid or flexible conductors from 18 to 4 AWG (0.75 to 25mm2) with no busbar connected. When maximum busbar size of 36 mm2 is used, maximum cable is 6 AWG (16 mm2). Maximum tightening torque of 17.5 in-lb (2 Nm) for line/load terminals and 4.5 in-lb (0.5Nm) for accessory device terminals. The MCBs are “trip-free,” if the handle is being forced to the “ON” position, the breaker will still trip under fault conditions. The “O” marking indicates that the breaker is in the “OFF” position. The MCB is now open and the load is disconnected from line power. When a breaker has tripped, the MCB handle should first be set to the full “OFF” position to make certain the trip mechanism has been reset. Once the fault has been determined and cleared the MCB can again be switched “ON”. Maintenance ABB miniature circuit breakers require no special maintenance; only normal electrical system maintenance procedures are required. Removing MCB Possible mounting arrangements of MCB accessories Legend +S/H+S/H (H)+S/H (H) S 200 Auxiliary contact Bell alarm/Auxiliary contact H S/H Bell alarm/Auxiliary contact used as auxiliary contact S/H (H) +H+H+H 14 Shunt trip ST Undervoltage release UR +ST+H+H+H +ST+S/H+S/H (H)+S/H (H) +UR+H+H+H +UR+S/H+S/H (H)+S/H (H) 14.24 1SXU 000 023 C0201 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Technical data Busbars & connectors Connection methods Sy s S2 tem 00 p Se ro M rie s 14 Top and bottom dual function terminals provided in open position for connection to busbars or cable. Terminals allow for connection of cable 18-4 AWG [top row] and 18-8 AWG [bottom row]. Two slots per terminal offer the ability to connect, independently, two conductors. This may be cables or bus bar. Top and bottom terminals may be bussed together with single phase or multi-phase busbars as shown. Both line and load side terminals can be bus bar connected. Easy removal of devices from an assembly when using bus bar in the bottom, load side terminals. Conductors may only be inserted into open terminals, preventing mis-wiring and potential problems. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14 14.25 1SXU 000 023 C0201 M o pr ies em Ser st Sy 200 S Technical data 14 S200-B S200-C, -D S200-K Approvals: UL CSA VDE IEC Item 1077 C22.2 — No.235 0641, 0660 898, 947 1077 C22.2 — No. 235 0660 898, 947 1077 C22.2 — No. 235 0660 898, 947 1077 — 0660 898, 947 No. of poles: 1,2,3,4 1+N,3+N 1,2,3, 1+N,3+N 1,2,3,4, 1+N,3+N 1,2,3,4,1+N,3+N Tripping characteristic: Rated currents: Minimum operating voltage: 120VAC C,D K K 0.5 to 63A 0.5 to 63A 0.2 to 63A 12V 12V 12V Single pole Multi pole Single pole Multi pole Single pole Multi pole Single pole Multi pole 10kA — 10kA — 10kA — 10kA — 10kA 240VAC 6kA 10kA 6kA 10kA 6kA 10kA 10kA 277VAC 6kA — 6kA — 6kA — 10kA — — 6kA — 6kA — 6kA — 10kA 277/480 VAC 60VDC 10kA 10kA 10kA 10kA 10kA 10kA — — 125VDC — 10kA — 10kA — 10kA — — Frequency: 50/60Hz (See below) 50/60Hz (see below) 50/60Hz (see below) 50/60Hz (see below) 240/415VAC 60VDC 415VAC 110VDC 240/415VAC 60VDC 415VAC 110VDC 240/415VAC 60VDC 415VAC 110VDC 240/415VAC 60VDC 415VAC 110VDC Rated voltage IEC single pole IEC multi-pole Protection category: IP20 IP20 IP20 IP20 Depth of unit per DIN 43880: 68mm 68mm 68mm 68mm Mounting position: optional optional optional optional Standard mounting: 35mm DIN rail 35mm DIN rail 35mm DIN rail 35mm DIN rail 18-4 AWG [top] 18-8 [bottom] 17.5 in-lbs. #2 Posidrive 18-4 AWG [top] 18-8 [bottom] 17.5 in-lbs. #2 Posidrive 18-4 AWG [top] 18-8 [bottom] 17.5 in-lbs. #2 Posidrive 18-4 AWG [top] 18-8 [bottom] 17.5 in-lbs. #2 Posidrive 18-16 AWG 4.5 in-lbs. #1 Posidrive 18-16 AWG 4.5 in-lbs. #1 Posidrive 18-16 AWG 4.5 in-lbs. #1 Posidrive 18-16 AWG 4.5 in-lbs. #1 Posidrive In < 32 A, 20,000 operations In > 32 A, 10,000 operations In < 32 A, 20,000 operations In > 32 A, 10,000 operations In < 32 A, 20,000 operations In > 32 A, 10,000 operations In < 32 A, 20,000 operations In > 32 A, 10,000 operations -25°C to +70°C -40°C to + 70°C -25°C to +70°C -40°C to + 70°C -25°C to +70°C -40°C to + 70°C -25°C to +70°C -40°C to + 70°C Shock resistance: 30g minimum of 2 impacts, shock duration of 13ms 30g minimum of 2 impacts, shock duration of 13ms 30g minimum of 2 impacts, shock duration of 13ms 30g minimum of 2 impacts, shock duration of 13ms Vibration resistance: 5g, 20 cycles, 5 Hz, 150 Hz @ 0.8 ~ In 5g, 20 cycles, 5 Hz, 150 Hz @ 0.8 ~ In 5g, 20 cycles, 5 Hz, 150 Hz @ 0.8 ~ In 5g, 20 cycles, 5 Hz, 150 Hz @ 0.8 ~ In 6kA switching 6kA switching 6kA switching — Main and shunt trip terminals: Wire size 14 B 6 to 63A 12V UL/CSA rated voltage & interrupting capacity S200P-K Torque Tool Accessory terminals Wire size Torque Tool Service life at rated load: Ambient temperatures: Storage temperatures Disconnecting neutral rating: Influence of frequency on electro-magnetic trips Magnetic trip values shown on trip curves are valid for 50/60Hz applications. For frequencies other than 50/60Hz, the magnetic (instantaneous) trip values are increased by the factor given below: 16 2/3 - 60Hz 100Hz Approx. factor 1 1.1 200Hz 400Hz DC 1.2 1.5 1.5 Thermal tripping is independent of frequency. 14.26 1SXU 000 023 C0201 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S2 tem 00 p Se ro M rie s 14 Technical data Item Approvals: UL CSA VDE IEC S280UC-K S200P-Z S280UC-Z S290-C 1077 — 0660 898,947 1077 — 0660 898, 947 1077 — 0660 898, 947 — — 0660 898 1,2,3 1,2,3,4 1,2,3 1,2,3,4 No. of poles: Tripping characteristic: Rated currents: K Z Z C 0.2 to 63A 0.5 to 63A 0.5 to 63A 80 to 125A 12V 12V Minimum operating voltage: 12V UL/CSA rated voltage & interrupting capacity 12V Single pole Multi pole Single pole Multi pole Single pole Multi pole 120VAC 10kA — 10kA — 10kA — — 240VAC 10kA 10kA 10kA 10kA 10kA 10kA — 277VAC 10kA — 10kA — 10kA — — — 4.5kA for 0.2-40A 5kA for 50-63A — 10kA — 4.5kA for 0.2-40A 5kA for 50-63A — 60VDC 10kA 10kA — — 10kA 10kA — 125VDC 10kA 10kA — — 10kA 10kA — 250VDC 4.5kA 4.5kA — — 4.5kA 4.5kA — — 4.5kA — — — 4.5kA 277/480 VAC 500VDC Frequency: Rated voltage IEC single pole — 50/60Hz (see below) 50/60 Hz (see below) 50/60Hz (see below) 50/60Hz (see below) 240/415VAC 220VDC 415VAC 440VDC 240/415VAC 60VDC 415VAC 110VDC 240/415VAC 220VDC 415VAC 440VDC 230/440VAC 60VDC 440VAC 110VDC IEC multi-pole Protection category: IP20 IP20 IP20 IP20 Depth of unit per DIN 43880: 68mm 68mm 68mm 70mm Mounting position: optional optional optional optional Standard mounting: 35mm DIN rail 35mm DIN rail 35mm DIN-rail 35mm DIN-rail 14 Main and shunt trip terminals: Wire size 0.2-40A 18-4 AWG 50A & above 18-2 AWG 17.5 in-lbs. #2 Posidrive Torque Tool Accessory terminals Wire size Torque Tool 18-4 AWG [top] 18-8 AWG [bottom] 17.5 in-lbs. #2 Posidrive 0.5-40A 18-4 AWG 18-2 AWG 17.5 in-lbs. #2 Posidrive 80-125A 14-1/0 AWG 17.5 in-lbs. #2 Posidrive 18-16 AWG 4.5 in-lbs. #1 Posidrive 18-16 AWG 4.5 in-lbs. #1 Posidrive 18-16 AWG 4.5 in-lbs. #1 Posidrive 18-16 AWG 4.5 in-lbs. #1 Posidrive In < 32 A, 20,000 operations In > 32 A, 10,000 operations In < 32 A, 20,000 operations In > 32 A, 10,000 operations In < 32 A, 20,000 operations In > 32 A, 10,000 operations 10,000 operations –– -25°C to +55°C -40°C to + 70°C -25°C to +70°C -40°C to + 70°C -25°C to +55°C -40°C to + 70°C -5°C to +45°C -40°C to + 70°C Shock resistance: 30g minimum of 2 impacts, shock duration of 13ms 30g minimum of 2 impacts, shock duration of 13ms 30g minimum of 2 impacts, shock duration of 13ms 30g minimum of 2 impacts, shock duration of 13ms Vibration resistance: 5g, 20 cycles, 5 Hz, 150 Hz @ 0.8 ~ In 5g, 20 cycles, 5 Hz, 150 Hz @ 0.8 ~ In 5g, 20 cycles, 5 Hz, 150 Hz @ 0.8 ~ In 60m/s2, at 10 – 150 Hz Service life at rated load: Ambient temperatures: Storage temperatures Influence of frequency on electro-magnetic trips Magnetic trip values shown on trip curves are valid for 50/60Hz applications. For frequencies other than 50/60Hz, the magnetic (instantaneous) trip values are increased by the factor given below: 16 2/3 - 60Hz 100Hz Approx. factor 1 1.1 200Hz 400Hz DC 1.2 1.5 1.5 Thermal tripping is independent of frequency. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.27 1SXU 000 023 C0201 M o pr ies em Ser st Sy 200 S Technical data 14 Item Approvals: UL CSA VDE IEC No. of poles: Tripping characteristic: S200U-K S200U-Z S200UP-K S200UP-Z 489 C22.2 No.5 0660 898,947 489 C22.2 No.5 0660 898, 947 489 C22.2 No.5 0660 898, 947 489 C22.2 No.5 0660 898 1,2,3,4 1,2,3,4 1,2,3,4 1,2,3,4 K Z K Z 0.2 to 63A 0.2 to 63A 0.2 to 25A 0.2 to 25A 12V 12V 12V 12V 120VAC 10kA 10kA 10kA 10kA 240VAC 10kA 10kA 10kA 10kA 277VAC 10kA 10kA 480/277 VAC — — 10kA 10kA Frequency: Rated voltage IEC single pole 50/60Hz (see below) 50/60 Hz (see below) 50/60Hz (see below) 50/60Hz (see below) 240/415VAC 220VDC 415VAC 440VDC 240/415VAC 60VDC 415VAC 110VDC 240/415VAC 220VDC 415VAC 440VDC 240/415VAC 220VDC 415VAC 440VDC Rated currents: Minimum operating voltage: UL/CSA rated voltage & interrupting capacity IEC multi-pole Protection category: IP20 IP20 IP20 IP20 Depth of unit per DIN 43880: 68mm 68mm 68mm 68mm Mounting position: optional optional optional optional Standard mounting: 35mm DIN rail 35mm DIN rail 35mm DIN-rail 35mm DIN-rail 18-4 AWG [top] 18-8 AWG [bottom] 17.5 in-lbs. #2 Posidrive 18-4 AWG [top] 18-8 AWG [bottom] 17.5 in-lbs. #2 Posidrive 18-4 AWG [top] 18-8 AWG [bottom] 17.5 in-lbs. #2 Posidrive 18-4 AWG [top] 18-8 AWG [bottom] 17.5 in-lbs. #2 Posidrive 18-16 AWG 4.5 in-lbs. #1 Posidrive 18-16 AWG 4.5 in-lbs. #1 Posidrive 18-16 AWG 4.5 in-lbs. #1 Posidrive 18-16 AWG 4.5 in-lbs. #1 Posidrive In < 32 A, 20,000 operations In > 32 A, 10,000 operations In < 32 A, 20,000 operations In > 32 A, 10,000 operations In < 32 A, 20,000 operations In > 32 A, 10,000 operations In < 32 A, 20,000 operations In > 32 A, 10,000 operations -25°C to +70°C -40°C to + 70°C -25°C to +70°C -40°C to + 70°C -25°C to +70°C -40°C to + 70°C -25°C to +70°C -40°C to + 70°C Shock resistance: 30g minimum of 2 impacts, shock duration of 13ms 30g minimum of 2 impacts, shock duration of 13ms 30g minimum of 2 impacts, shock duration of 13ms 30g minimum of 2 impacts, shock duration of 13ms Vibration resistance: 5g, 20 cycles, 5 Hz, 150 Hz @ 0.8 ~ In 5g, 20 cycles, 5 Hz, 150 Hz @ 0.8 ~ In 5g, 20 cycles, 5 Hz, 150 Hz @ 0.8 ~ In 5g, 20 cycles, 5 Hz, 150 Hz @ 0.8 ~ In Main and shunt trip terminals: Wire size Torque Tool 14 Accessory terminals Wire size Torque Tool Service life at rated load: Ambient temperatures: Storage temperatures Influence of frequency on electro-magnetic trips Magnetic trip values shown on trip curves are valid for 50/60Hz applications. For frequencies other than 50/60Hz, the magnetic (instantaneous) trip values are increased by the factor given below: 16 2/3 - 60Hz 100Hz Approx. factor 1 1.1 200Hz 400Hz DC 1.2 1.5 1.5 Thermal tripping is independent of frequency. 14.28 1SXU 000 023 C0201 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S2 tem 00 p Se ro M rie s 14 Technical data Wire size comparison Comparison of IEC and AWG wire sizes mm AWG (mm ) Amps / UL Amps / IEC 1.0 — 1.5 — 16 (1.3) — — 10 — 8 — 12 — 2.5 — 14 (2.1) — 12 (3.3) 15 — 20 — 20 — 4 — 6 — 10 (5.3) — — 30 — 25 — 32 — 10 — 8 (8.4) — 6 (13.3) 50 — 65 — 50 — 16 — 25 — 4 (21.2) — — 85 — 65 — 85 — — 35 3 (26.7) 2 (33.6) — 100 115 — — — 115 Ampacities for AWG wire are based on copper cable rated 75° C, except for 16AWG which is based on 60° C wire. Taken from UL508 Table 52.2. Consult applicable standards for futher detail and information. 14 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.29 1SXU 000 023 C0201 M o pr ies em Ser st Sy 200 S Approximate dimensions S200, S200P, S200U, S200UP 14 00.00 Inches 00.00 [Millimeters] S200 & S200P S200U S200UP 14 S290 Accessories mount to right side of MCB only 1.77 45 1.97 1.03 50 26 1.06 27 2.13 54 0.69 17.5 0.35 0.35 9 9 -H -S Auxiliary switch Bell alarm 3.19 81 -A1, -A2 Shunt trip 14.30 1SXU 000 023 C0201 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S2 tem 00 p Se ro M rie s 14 Approximate dimensions Accessories 00.00 Inches 00.00 [Millimeters] Accessories mm S 2C-H... S 2C-S... S 2C-S/H... S 2C-A... S 2C-UA... 45 69 85 8.8 45 69 85 17.5 6.8 6.8 44 MB-CL Front mounting clip 44 mm C.L. 1.77 45 D 2.26 1.77 57.5 C.L. 45 0.69 17.5 1.38 35 2.07 52.5 MB-3PD Front mounting bracket 14 3.25 2.12 ( 3P ) in 1.43 ( 2P ) 1.87 CL C L BREAKER CUT OUT 0.74 ( 1P ) BKT. MT. HOLES 0.25 DIA. TYP 2 S2C-DH Handle mechanism CL CL 0.63 16 2.07 52.5 0.83 21 1.38 35 3.54 90 4.36 110.4 1.77 45 3.26 82.5 0.27 6.9 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.31 1SXU 000 023 C0201 M o pr ies em Ser st Sy 200 S 14 Approximate dimensions Accessories 00.00 Inches 00.00 [Millimeters] 12402-12408 12644 12650 4.92 4.92 125 125 4.92 4.13 125 230 4.13 105 9.06 105 7.09 7.09 180 180 14 12646 12652 6.09 155 4.92 9.84 250 5.32 125 6.30 4.13 135 160 105 7.09 180 12.60 320 14.32 1SXU 000 023 C0201 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S2 tem 00 p Se ro M rie s 14 Cross-reference Older version Suggested replacement series Physical comparison Electrical comparison S260-B S200-B Same pole spacing S260-C S200-C Same pole spacing Same trip characteristic S260-D S200-D Same pole spacing Same trip characteristic S270-K S200-K Same pole spacing Same trip characteristic S280-K S200P-K Same pole spacing Same trip characteristic S280-Z S200P-Z Same pole spacing Same trip characteristic S280U-K S200U-K Same pole spacing Same trip characteristic S280UX-K S200U-K Smaller pole spacing Same trip characteristic Same trip characteristic Many older styles of ABB miniature circuit breakers have been replaced by new and improved versions. Many of these newer styles can be directly interchanged, both electrically and physically, with the older version. There are also many international styles of ABB circuit breakers which are not normal stock items and may be interchanged with stocked ABB versions. 14 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.33 1SXU 000 023 C0201 M o pr ies em Ser st Sy 200 S 14 Notes 14 14.34 1SXU 000 023 C0201 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com S ys System pro M compact S5 tem Miniature Circuit Breakers 00 Se pro M rie s S500 Series 14 Description Features Increasing energy requirements result in larger short-circuit currents which place heavy demands on protective switchgear regarding safety, reliability and switching capacities. The S500 heavy-duty circuit breaker fulfills these requirements by virtue of its technical features. It is equipped with a thermal and/or electromagnetic release to protect circuits, motors, switchgear and systems from the effects of overload and short-circuit currents. For the worldwide market, the S500 breakers carry UL, CSA, IEC, CE and many other agency approvals. • • • • • • • • • • • High breaking capacity Energy-limiting Current-limiting Extremely fast breaking time Optimal selectivity Various versions for special applications Compact dimensions, DIN cap size Easy and quick to install Easy to connect; finger safe terminals Wide range of accessories UL 1077 recognized 600VAC and 500VDC versions UL File # E167556 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.35 1SXU 000 023 C0201 14 S500 600Y/277 VAC M o pr ies em Ser st Sy 500 S 14 B UL 1077 VDE 0641 Rated current C CSA C22.2 IEC 947-2 Catalog number List price Delivery class Weight (oz.) 1 pc 6 10 13 16 20 25 32 40 50 63 S501-B6 S501-B10 S501-B13 S501-B16 S501-B20 S501-B25 S501-B32 S501-B40 S501-B50 S501-B63 $ 168 168 168 168 168 168 168 168 186 202 S502-B6 S502-B10 S502-B13 S502-B16 S502-B20 S502-B25 S502-B32 S502-B40 S502-B50 S502-B63 328 328 328 328 328 328 328 328 362 392 S503-B6 S503-B10 S503-B13 S503-B16 S503-B20 S503-B25 S503-B32 S503-B40 S503-B50 S503-B63 478 478 478 478 478 478 478 478 526 574 B 8.90 6 10 13 16 20 25 32 40 50 63 B 17.85 6 10 13 16 20 25 32 40 50 63 B 10,000 5000 1000 500 D 100 50 seconds List price AC 0.1 0.05 DC 0.01 1 2 3 5 7 10 20 30 multiple of rated current C 6 10 13 16 20 25 32 40 50 63 B 25.36 6 10 13 16 20 25 32 40 50 63 $ 168 168 168 168 168 168 168 168 184 202 B 8.90 S502-C6 S502-C10 S502-C13 S502-C16 S502-C20 S502-C25 S502-C32 S502-C40 S502-C50 S502-C63 328 328 328 328 328 328 328 328 362 392 B 17.85 S503-C6 S503-C10 S503-C13 S503-C16 S503-C20 S503-C25 S503-C32 S503-C40 S503-C50 S503-C63 478 478 478 478 478 478 478 478 526 574 B 25.36 CSA C22.2 IEC 947-1 Catalog number Delivery Class List price Delivery class Wgt. oz. (1 Pc.) A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time 13 16 20 25 32 40 50 63 S501-D13 S501-D16 S501-D20 S501-D25 S501-D32 S501-D40 S501-D50 S501-D63 $ 190 190 190 190 190 190 210 226 S502-D13 S502-D16 S502-D20 S502-D25 S502-D32 S502-D40 S502-D50 S502-D63 372 372 372 372 372 372 408 442 S503-D13 S503-D16 S503-D20 S503-D25 S503-D32 S503-D40 S503-D50 S503-D63 544 544 544 544 544 544 600 646 D 10,000 5000 B 13 16 20 25 32 40 50 63 5000 1000 500 100 50 10 5 100 50 10 5 B 17.85 1 0.5 AC 0.1 0.05 DC 0.01 2 3 5 10 18 20 30 13 16 20 25 32 40 50 63 1 0.5 AC 0.1 0.05 DC 0.01 1 3 pole 1 1000 500 8.90 2 pole 10,000 Delivery Weight class (oz.) 1 pc S501-C6 S501-C10 S501-C13 S501-C16 S501-C20 S501-C25 S501-C32 S501-C40 S501-C50 S501-C63 1 pole 1 0.5 seconds UL 1077 VDE 0641 Rated current 10 5 6 10 13 16 20 25 32 40 50 63 seconds 14 Catalog number 3 pole 3 pole S503-C10 Rated current 2 pole 2 pole S502-C6 CSA C22.2 IEC 947-2 1 pole 1 pole S501-C16 UL 1077 VDE 0641 2 3 5 10 20 30 multiple of rated current B 25.36 multiple of rated current 14.36 1SXU 000 023 C0201 Discount schedule CB10 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S5 tem 00 p Se ro M rie s S500 600Y/277 VAC K UL 1077 VDE 0641 Rated current 14 CSA C22.2 IEC-898 Catalog number Delivery Class List price Delivery class Wgt. oz. (1 Pc.) A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time 1 pole 0.1 0.14 0.2 0.28 0.38 0.53 0.73 1 1.4 2 2.8 3.8 5.3 7.3 10 14 18 23 29 34 38 S501-D20 S502-D13 – – – – – – – – – – – – – – – – – – – – – 0.15 0.21 0.3 0.42 0.58 0.8 1.1 1.5 2.1 3 4.2 5.8 8 11 15 20 26 32 37 41 45 S501-K0.15 S501-K0.21 S501-K0.3 S501-K0.42 S501-K0.58 S501-K0.8 S501-K1.1 S501-K1.5 S501-K2.1 S501-K3 S501-K4.2 S501-K5.8 S501-K8 S501-K11 S501-K15 S501-K20 S501-K26 S501-K32 S501-K37 S501-K41 S501-K45 $ 182 182 182 182 182 182 182 182 182 182 182 182 182 182 182 182 182 202 202 226 226 0.15 0.21 0.3 0.42 0.58 0.8 1.1 1.5 2.1 3 4.2 5.8 8 11 15 20 26 32 37 41 45 S502-K0.15 S502-K0.21 S502-K0.3 S502-K0.42 S502-K0.58 S502-K0.8 S502-K1.1 S502-K1.5 S502-K2.1 S502-K3 S502-K4.2 S502-K5.8 S502-K8 S502-K11 S502-K15 S502-K20 S502-K26 S502-K32 S502-K37 S502-K41 S502-K45 356 356 356 356 356 356 356 356 356 356 356 356 356 356 356 356 356 392 392 442 442 0.15 0.21 0.3 0.42 0.58 0.8 1.1 1.5 2.1 3 4.2 5.8 8 11 15 20 26 32 37 41 45 S503-K0.15 S503-K0.21 S503-K0.3 S503-K0.42 S503-K0.58 S503-K0.8 S503-K1.1 S503-K1.5 S503-K2.1 S503-K3 S503-K4.2 S503-K5.8 S503-K8 S503-K11 S503-K15 S503-K20 S503-K26 S503-K32 S503-K37 S503-K41 S503-K45 518 518 518 518 518 518 518 518 518 518 518 518 518 518 518 518 518 574 574 644 828 B 8.90 B 17.85 2 pole 0.1 0.14 0.2 0.28 0.38 0.53 0.73 1 1.4 2 2.8 3.8 5.3 7.3 10 14 18 23 29 34 38 S503-K6 K 10,000 5000 14 3 pole 1000 500 100 50 10 5 seconds – – – – – – – – – – – – – – – – – – – – – 1 0.5 AC 0.1 0.05 DC 0.01 1 2 3 5 8 10 12 20 30 multiple of rated current Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 0.1 0.14 0.2 0.28 0.38 0.53 0.73 1 1.4 2 2.8 3.8 5.3 7.3 10 14 18 23 29 34 38 – – – – – – – – – – – – – – – – – – – – – B 25.36 Discount schedule CB10 14.37 1SXU 000 023 C0201 S500UC 600Y/277 VAC 600 VDC M o pr ies em Ser st Sy 500 S 14 B UL 1077 VDE 0660 Rated current CSA C22.2 Catalog number List price Delivery Weight class (oz.) 1 pc S501UC-B40 S501UC-B6 S501UC-B10 S501UC-B13 S501UC-B16 S501UC-B20 S501UC-B25 S501UC-B32 S501UC-B40 S501UC-B50 S501UC-B63 $ 226 226 226 226 226 226 226 226 258 292 S502UC-B6 S502UC-B10 S502UC-B13 S502UC-B16 S502UC-B20 S502UC-B25 S502UC-B32 S502UC-B40 S502UC-B50 S502UC-B63 442 442 442 442 442 442 442 442 502 568 C 8.90 S502UC-B16 List price Delivery class Weight (oz.) 1 pc 6 10 13 16 20 25 32 40 50 63 S503UC-B6 S503UC-B10 S503UC-B13 S503UC-B16 S503UC-B20 S503UC-B25 S503UC-B32 S503UC-B40 S503UC-B50 S503UC-B63 $ 646 646 646 646 646 646 646 646 734 832 C 25.36 S504UC-B6 S504UC-B10 S504UC-B13 S504UC-B16 S504UC-B20 S504UC-B25 S504UC-B32 S504UC-B40 S504UC-B50 S504UC-B63 908 908 908 908 908 908 908 908 1030 1164 C 35.75 4 pole 2 pole 6 10 13 16 20 25 32 40 50 63 Catalog number 3 pole 1 pole 6 10 13 16 20 25 32 40 50 63 Rated current C 17.85 6 10 13 16 20 25 32 40 50 63 Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time S503UC-B50 14 B 10,000 5000 1000 500 100 50 10 5 seconds 1 0.5 AC 0.1 0.05 DC 0.01 1 2 3 5 7 10 20 30 multiple of rated current 14.38 1SXU 000 023 C0201 Discount schedule CB10 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S5 tem 00 p Se ro M rie s S500 UC 600Y/277 VAC 600 VDC K UL 1077 VDE 0660 Rated current 14 CSA C22.2 Catalog number List price Delivery class Weight (oz.) 1 pc 1 pole 0.1 0.14 0.2 0.28 0.38 0.53 0.73 1 1.4 2 2.8 3.8 5.3 7.3 10 14 18 23 29 34 38 S501UC-K0.15 S502UC-K0.15 – – – – – – – – – – – – – – – – – – – – – S503UC-K0.15 – – – – – – – – – – – – – – – – – – – – – Catalog number List price Delivery class Weight (oz.) 1 pc C 25.36 C 35.75 3 pole 0.15 0.21 0.3 0.42 0.58 0.8 1.1 1.5 2.1 3 4.2 5.8 8 11 15 20 26 32 37 41 45 S501UC-K0.15 S501UC-K0.21 S501UC-K0.3 S501UC-K0.42 S501UC-K0.58 S501UC-K0.8 S501UC-K1.1 S501UC-K1.5 S501UC-K2.1 S501UC-K3 S501UC-K4.2 S501UC-K5.8 S501UC-K8 S501UC-K11 S501UC-K15 S501UC-K20 S501UC-K26 S501UC-K32 S501UC-K37 S501UC-K41 S501UC-K45 $ 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 286 286 320 320 0.15 0.21 0.3 0.42 0.58 0.8 1.1 1.5 2.1 3 4.2 5.8 8 11 15 20 26 32 37 41 45 S502UC-K0.15 S502UC-K0.21 S502UC-K0.3 S502UC-K0.42 S502UC-K0.58 S502UC-K0.8 S502UC-K1.1 S502UC-K1.5 S502UC-K2.1 S502UC-K3 S502UC-K4.2 S502UC-K5.8 S502UC-K8 S502UC-K11 S502UC-K15 S502UC-K20 S502UC-K26 S502UC-K32 S502UC-K37 S502UC-K41 S502UC-K45 488 488 488 488 488 488 488 488 488 488 488 488 488 488 488 488 488 558 558 622 622 C 8.90 2 pole 0.1 0.14 0.2 0.28 0.38 0.53 0.73 1 1.4 2 2.8 3.8 5.3 7.3 10 14 18 23 29 34 38 Rated current 0.1 0.14 0.2 0.28 0.38 0.53 0.73 1 1.4 2 2.8 3.8 5.3 7.3 10 14 18 23 29 34 38 – – – – – – – – – – – – – – – – – – – – – 0.15 0.21 0.3 0.42 0.58 0.8 1.1 1.5 2.1 3 4.2 5.8 8 11 15 20 26 32 37 41 45 S503UC-K0.15 S503UC-K0.21 S503UC-K0.3 S503UC-K0.42 S503UC-K0.58 S503UC-K0.8 S503UC-K1.1 S503UC-K1.5 S503UC-K2.1 S503UC-K3 S503UC-K4.2 S503UC-K5.8 S503UC-K8 S503UC-K11 S503UC-K15 S503UC-K20 S503UC-K26 S503UC-K32 S503UC-K37 S503UC-K41 S503UC-K45 $ 712 712 712 712 712 712 712 712 712 712 712 712 712 712 712 712 712 814 814 910 910 – – – – – – – – – – – – – – – – – – – – – 0.15 0.21 0.3 0.42 0.58 0.8 1.1 1.5 2.1 3 4.2 5.8 8 11 15 20 26 32 37 41 45 S504UC-K0.15 S504UC-K0.21 S504UC-K0.3 S504UC-K0.42 S504UC-K0.58 S504UC-K0.8 S504UC-K1.1 S504UC-K1.5 S504UC-K2.1 S504UC-K3 S504UC-K4.2 S504UC-K5.8 S504UC-K8 S504UC-K11 S504UC-K15 S504UC-K20 S504UC-K26 S504UC-K32 S504UC-K37 S504UC-K41 S504UC-K45 996 996 996 996 996 996 996 996 996 996 996 996 996 996 996 996 996 1142 1142 1276 1276 4 pole C 17.85 0.1 0.14 0.2 0.28 0.38 0.53 0.73 1 1.4 2 2.8 3.8 5.3 7.3 10 14 18 23 29 34 38 14 Delivery Class S504UC-K0.15 A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time UC-K 10,000 5000 1000 500 100 50 seconds 10 5 1 0.5 0.1 0.05 DC 0.01 1 2 3 5 10 20 30 multiple of rated current Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Discount schedule CB10 14.39 1SXU 000 023 C0201 M o pr ies em Ser st Sy 500 S 14 Accessories Electrical accessories Catalog number List price Delivery class Wgt. oz. (1pc.) Electrical accessories Auxiliary contacts 1 N.O./1 N.C. 2 N.O. 2 N.C. $ 84 B 12 V 24 V 48 V 110 V 230 V 500 V 2.14 Bell alarm with auxiliary contacts 1 N.O./1 N.C. 2 N.O. 2 N.C. List price Delivery class Wgt. oz. (1pc.) Undervoltage release S500-H11 S500-H20 S500-H02 For field mounting left side S500-H11 Auxiliary contacts Catalog number suffix S500-S11 S500-S20 S500-S02 92 B 2.14 B 5.71 AL12 AL24 AL48 AL110 AL230 AL500 224 B 5.71 Shunt trip 12 V 24 V 48 V 110 V 230 V 500 V Handle mechanism 100 $ 266 Factory mount only. For field mounting left side S500-RD3 UA12 UA24 UA48 UA110 UA230 UA500 B 6.5 For use with 1-4 pole S500 MCBs and disconnect switch selector handles with 5mm shafts Factory mount only. Front mounting kit S500-RD3 For 1 pole 1 to 3 poles 1 to 7 poles S500-ME1 S500-ME2 S500-ME3 60 70 80 2.1 2.9 3.6 A Power feed terminal – Accepts into 2/0 AWG S500-K2 25 A 2 Suggested order quantity is 5. Busbars – 3 phase L1, L2, L3 S500-K2 14 Amp rating Number of poles 150 3x8 4x4 3 x 13 Busbar length (mm) End cap catalog number Catalog number List price Delivery class Suggested order qty. quantity Weight (ozs) 650 435 1055 — — — S500-BB38 S500-BB44 S500-BB313 $ 182 142 274 A 1 1 List price Delivery class Wgt. oz. (1pc.) A 10 S500-BB38 Busbar end caps Electrical accessories Catalog number S500-EK $ 25 Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time 14.40 1SXU 000 023 C0201 Discount schedule CB8 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Sy s S5 tem 00 p Se ro M rie s Technical data Item 14 S500-B, C, D S500-K Approvals: UL CSA VDE IEC 1077 C22.2 - No.235 0641/6.78 947-2 1077 C22.2 - No. 235 0641/6.78 — No. of poles: 1,2,3, +N, +NA 1,2,3, +N, +NA Tripping characteristic: B.C.D. K Rated currents: 6 to 63A 0.1 to 45A Rated voltage: UL/CSA single pole UL/CSA multi pole 277VAC 600YVAC 277VAC 600YVAC 690VAC 690VAC 6-25A – 30KA/240VAC 14KA/277VAC 0.15-25A – 30KA/240VAC 14KA/277VAC 32-63A – 18KA/240VAC 14KA/277VAC 26-45A – 18KA/240VAC 14KA/277VAC 6-63A – 14KA/480VAC 6KA/600VAC 0.15-45A – 14KA/480VAC 6KA/600VAC 50/60 Hz 50/60Hz IEC single pole Rated interrupting capacity: Single pole Multi-pole Frequency: Mounting position: optional optional Standard mounting: 35mm DIN rail 35mm DIN rail Conductors from 16-4AWG (1-25sq mm) Conductors from 16-4AWG (1-25sq mm) Service life at rated load: 20,000 operations 20,000 operations Calibration temperature: 40°C 40°C Terminals: Item S500UC-B, K Approvals: UL CSA VDE 1077 C22.2 0660 1,2,3, 4 No. of poles: B: 6 to 63A K: 0.15 to 45A Rated currents: Rated voltage: UL single pole UL multi pole 277VAC/250VDC 600VAC/600VDC IEC multi pole 690VAC/750VDC Rated interrupting capacity: 14 B, K Tripping characteristic: B single pole: 6 – 25A 32 – 63A 18KA/240VAC 30KA/240VAC 14KA/277VAC 14KA/277VAC 30KA/250VDC 30KA/250VDC 6 – 63A 14KA/480VAC 6KA/600VAC 30KA/500VDC 6 – 63A 14KA/480VAC 6KA/600VAC 30KA/600VDC 30KA/240VAC 18KA/240VAC 14KA/277VAC 14KA/277VAC 30KA/250VDC 30KA/250VDC 0.15 – 45A 14KA/480VAC 6KA/600VAC 30KA/500VDC 0.5 – 45A 14KA/480VAC 6KA/600VAC 30KA/600VDC B two-pole: B three-pole: K single pole: 0.15 – 25A 32 – 45A K two-pole: K three-pole: Frequency: 50/60Hz Mounting position: optional Standard mounting: Terminals: Service life at rated load: Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 35mm DIN-rail Conductors from 16 to 4AWG (1-25sq mm) 20,000 operations 14.41 1SXU 000 023 C0201 M o pr ies em Ser st Sy 500 S Approximate dimensions 14 00.00 Inches 00.00 [Millimeters] S500 2.95 75 1.97 50 0.98 25 3.64 92.5 1.73 44 3.15 3.62 1.77 45 80 2.22 56.5 92 CL 2.95 75 1.14 29 0.24 6 S500-RD3 Handle mechanism 14 3.15 80 1.60 40.7 S500 Front mounting kit CL 4.41 2.91 112 74 2.00 51 0.24 D CUT-OUT 6D CL 1.81 46 "L" L + 0.51 13 L L + 1.02 26 3.31 84 14.42 1SXU 000 023 C0201 0.31 8 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Galaxie circuit breakers GD, GH, GN & GV Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com cir G cu ala it br xie ea ke 14 rs Description Features Galaxie circuit breakers are door mounted for AC and DC applications. The breakers offer thermal-magnetic and magnetic-only trip protection. For the worldwide market, the Galaxie breakers carry UL, CSA, IEC, CE and many other agency approvals and certifications. • Convenient actuators: Switch type, rocker switch & pushbutton • Various termination mountings • Tropicalization protection • 480Y/277 VAC • UL 1077 Recognized – supplemental protective device. UL File # E75741. 14.43 1SXU 000 023 C0201 14 s xie ker a l a Ga bre it cu r i c 14 GD, GH, GN & GV Series circuit breakers Fitted, unpluggable or projecting type Catalog number explanation Circuit Breakers OPTIONS SERIES RATING ENGRAVED GD Standard Galaxie AC 240/415 V 50/60 Hz can be used at 48 V DC max. J GH High rupturing capacity Galaxie AC 240/415 V 50/60 Hz METAL THREADED BUSHING W GN Special Galaxie 100 V DC max. GV Special Galaxie 150 V DC max. GA Severe environment Galaxie (i.e. military use) consult us For fastening and operations 6-7-8. Tightening torque : 3 Nm max. (compulsory with option K) CIRCUIT BREAKER SERIES GD MODEL D 2 R VERSIONS 14 On resetting button With adjustable thermal protection (Not possible with option K) U One-pole B Two-pole (1 protected pole) (2 protected poles) MECHANICAL IMPACT T Three-pole (3 protected poles) V 50 g Q Four-pole (4 protected poles) E 100 G 1+N Two-pole (1 protected pole + neutral) 3+N Four-pole (3 protected poles + neutral) TROPICALIZATION T (Compulsory with option E 100) RATING (In : Amps) 0.1 - 0.2 - 0.3 - 0.5 - 1 - 1.5 - 2 - 2.5 - 3 - 4 - 5 6 - 8 - 10 - 12 - 13 - 16 - 20 - 25 - 30 - 32 Heavy duty types : ratings according to NF EN60 898 Other ratings, consult us. THERMAL PROTECTION C Temperature compensated from + 20°C to + 60°C K Temperature compensated from - 40°C to + 85°C series GD, GH and GA (Compulsory with Option W) MODELS L Thermal-magnetic - Curve B according to NF EN60 898 U Thermal-magnetic - Curve C according to NF EN60 898 D Thermal-magnetic - Curve D according to NF EN60 898 Ratings 6 to 32 A S Thermal-magnetic (series GN and GV only) according to NF F 62001 T Thermal (except series GH) AUXILIARY CONTACT FOR POSITION SIGNALLING O/F P1 on 1 pole P2 on 2 poles P3 on 3 poles P4 on 4 poles 1 See next page 2 Series GD, Model D only FASTENINGS AND OPERATIONS 1 00 - 01 - 02 - 03 - 04 - 05 - 06 - 07 - 08 - 09 TERMINATIONS 1 00 - 01 - 02 - 03 - 07 - 08 - 09 - 33 - 43 EXAMPLE : 1 Circuit breaker Series : Galaxie standard AC - Version : 2 protected poles - Rating : 10 A - Model : magnetic-thermal, curve C - Fastenings and operations : Threaded bushing flush type 2 buttons - Terminations : Screws and back connectors - With Options Auxiliary for position signalling O/F : on 2 poles - Tropicalization has reference GDB10U0703 P2T GD B 10 U 07 03 14.44 1SXU 000 023 C0201 P2 - T - - - Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com cir G cu ala it br xie ea ke 14 Technical data rs UL, CSA : For list of certified products : consult us Characteristics SERIES GD SERIES GH 240 V AC (50/60 Hz) 240/415 V AC (50/60 Hz) 415 V AC (50/60 Hz) 48 V DC max. 240/415 V AC (50/60 Hz) 415 V AC (50/60 Hz) Circuit breakers NF F62 001 : consult us SERIES GN SERIES GV Rated voltage 1 + neutral version One pole version Multipole version One pole and two pole version 100 V DC max. 150 V DC max. Interrupting capacity 3 000 A According to standard IEC 898 4 500 A (models U and D: rating ≥ 5 A) 4 500 A (model L: rating ≥ 10 A) 1 000 A (48 V DC max.) 10 In cal. < 5 A ; 20 In cal > 5 A According to standard NF F62 001 500 A 1 000 A (48 V DC max.) 10 In cal. < 5 A ; 20 In cal > 5 A 10 In cal. < 5 A ; 20 In cal > 5 A Other characteristics 4 000 2 000 V rms Life, number of cycles (On+Off) Dielectric withstanding voltage Tripping curves (1) (2) S 4 000 2 000 V rms Curve B : 3 In < S < 5 In - Curve C : 5 In < S < 10 In - Curve D : 10 In < S < 20 In < 14 In 4 000 2 000 V rms 4 000 2 000 V rms Nominal current 0.1 to 2 A : 5 In < S < 10 In - 3 to 32 A : 7 In < S Mechanical shock 30 g. 30 g. 30 g. 30 g. -5° C to 40° C -5° C to 40° C -25° C to + 70° C -25° C to + 70° C Ambient temperature 14 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.45 1SXU 000 023 C0201 s xie ker a l a Ga bre it cu r i c 14 Approximate dimensions -ILLIMETERS Fastenings and operations No 00 - 01 - 02 - 03 - 04 - 06 - 07 - 08 Fastenings / Operations 1 Width Pole N° 2 8 07 08 15 21 28 32 32 32 43 07 08 09 4 4 4 11 37 00 01 02 03 33 15 4 8 06 32 32 32 32 32 4 8 05 Size C Size B 8 17,5 15 8 Terminations Pole N° 1 00 01 02 03 04 Size A 12 4 32 09 Pole Pole Pole N° 1 N° 2 N° 3 2 Widths 3 Widths Fastenings and operations No 05 - 09 Four-pole circuit breaker : o Fastening and operation N 05 only Pole N° 2 1 Width Pole N° 1 2 Widths Pole Pole Pole N° 3 N° 2 N° 1 Pole Pole Pole Pole N° 4 N° 3 N° 2 N° 1 3 Widths = 1 handle 4 Widths = 2 handles NOTE : Neutral on pole N° 1 any Fastenings and operations Fastenings and operations (3 poles max. except 02 : 2 poles and 05 : 4 poles) PROJECTION MOUNTING SCREW FLUSH MOUNTING Maximum thickness of mounting panel : 3 mm. 3 mm. 6 mm. 6 mm. 6 mm. 3 mm. 00 01 02 03 04 05 06 1,8 Nm max. 07 08 6 mm. 09 Tightening torque : 1,8 Nm max. 1,8 Nm max. 3 Nm max. Terminations 14 00 16 A max. Except Fastening 08 14.46 1SXU 000 023 C0201 01 02 03 33 43 240 A max. 2 poles max. 2 poles max. 07 08 16 A max. 2 poles max. 16 A max. 09 16 A max. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com System pro M compact Residual current devices F200, F670 series 2 Pole S Re yste sid m p u de al c ro M u vic rr es en t 14 4 Pole Description RCDs provide ground fault equipment protection by monitoring the leakage of current to ground. The F200 and F670 series will trip when ground faults are detected in excess of the GF trip rating of the device. These devices provide GF protection only and are used in series with standard MCBs which provide overload and short circuit protection. The F200 and F670 series can be used as a main device providing GF protection for several MCB branch devices. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com The F200 and F670 series are UL1053 recognized for use in 480Y/277VAC applications. The F202 and F672 is for use in single phase/two wire or two wire systems. The F204 and F674 is for use in three phase/four wire systems. The F200 and F670 series RCDs replace the F360, F370 and F660 series with no change in 14 fit, form or function. The F200 and F670 have a profile similar to the S2 MCBs and can be used with the MCB busbars. 14.47 1SXU 000 023 C0201 M t o pr rren em cu st ual es y S sid vic Re de 14 F200 & F670 Residual current devices Breaker F202 F672 GF trip level Two pole 480Y/277VAC Four pole 480Y/277VAC List price 16 25 40 63 80 100 F202AC-16/0.01 F202AC-25/0.03 F202AC-40/0.03 F202AC-63/0.03 F672-80/0.03 F672-100/0.03 $ 500 300 400 550 1600 2200 100mA 25 40 63 80 100 F202AC-25/0.1 F202AC-40/0.1 F202AC-63/0.1 F672-80/0.1 F672-100/0.1 300 400 550 1600 2200 300mA 25 40 63 80 100 F202AC-25/0.3 F202AC-40/0.3 F202AC-63/0.3 F672-80/0.3 F672-100/0.3 300 400 550 1300 1800 30mA 25 40 63 80 100 125 F204AC-25/0.03 F204AC-40/0.03 F204AC-63/0.03 F674-80/0.03 F674-100/0.03 F674-125/0.03 350 450 600 1300 1800 1800 100mA 25 40 63 80 100 125 F204AC-25/0.1 F204AC-40/0.1 F204AC-63/0.1 F674-80/0.1 F674-100/0.1 F674-125/0.1 350 450 600 1300 1800 1800 300mA 25 40 63 80 100 125 F204AC-25/0.3 F204AC-40/0.3 F204AC-63/0.3 F674-80/0.3 F674-100/0.3 F674-125/0.3 350 450 600 1200 1600 1600 500mA 25 40 63 F204AC-25/0.5 F204AC-40/0.5 F204AC-63/0.5 450 600 650 F204, F674 14 Catalog number 10mA 30mA F202, F672 F204 F674 Rated current Delivery class Suggested order qty Wgt. oz (1 Pc.) B 1 13.8 B 1 19.0 Above devices are UL 1053 recognized and IEC 1008 approved. Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time 14.48 1SXU 000 023 C0201 Discount schedule CB14 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14 S Re yste sid m p u de al c ro M u vic rr es en t Accessories F200 1 Electrical accessories For use on: Catalog number List price Delivery class Suggested order quantities Wgt. oz. (1 pc.) Auxiliary contacts For field mounting: right side F200 S2C-H6R $ 36 Form C 1 NO/ 1 NC A 1 1.4 The auxiliary contacts will signal whether the breaker is in the ON or OFF position. The contacts are rated 2A/277 VAC and 1.5A/125 VDC. Minimum operating voltage is 24 VAC/VDC. Wire size: 18 AWG to 16 AWG. S2C-H6R Bell alarm For field mounting, right side F200 S2C-S/H6R 48 A 1 1.4 The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically the contacts would be connected to an alarm or bell to signal the operator that an overcurrent trip has occured. The bell alarm also includes a test button for testing the alarm contacts without opening the breaker. The contact is rated 2A/277 VAC and 1.5A/125 VDC. Minimum operating voltage is 24 VAC/VDC. * Combination bell alarm/auxiliary contact Shunt trip For field mounting, right side S2C-S/H6R F200 A1: 12-60 VAC (12-60VDC) A2: 110-415 VAC (110-250 VDC) S2C-A1 S2C-A2 138 A 1 5.2 For remote tripping of breaker, a shunt trip device can be added to the MCB. The solenoid device opens the breaker after control voltage is applied. Shunt trips are available for on control system voltage (12-415 VAC/VDC). Undervoltage release For field mounting, right side 12 VDC 24 VAC 48 VAC F200 110 VAC 220 VAC 380 VAC S2C-A_ S2C-UA12 S2C-UA24 S2C-UA48 216 S2C-UA110 S2C-UA230 S2C-UA400 A 1 5.2 When control voltage drops below approximately 50% of rated voltage, the UVR opens the breaker. The breaker can not be operated unless proper control voltage is first applied to the UVR coil. Similar in size and mounting to the shunt trip accessory. Factory mounting All accessories can be easily mounted in the field. For factory mounting of any accessory devices, add $30 list to total price per breaker. To create complete catalog number, take suffix of accessory device following “S2C-” and add suffix to end of breaker part number. Multiple suffixes must be added in alphabetical order. Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time S2C-UA_ 1 Please consult factory for F670 accessories. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Discount schedule CB8 14.49 1SXU 000 023 C0201 14 M t o pr rren em cu st ual es y S sid vic Re de 14 Technical data F200, F670 F200AC F670 UL 1053 & IEC 61008 2P, 4P 16,25,40,63 AMPS 480Y/277 VAC 254 (440 for F200 left neutral) 110 ( 195 for F200 left neutral) 50…60 Hz 50…60 Hz 10 KA 1 KA 6 KV 2.5 KV 250 AMPS UL1053 & IEC 61008 2P, 4P 2P- 80,100 4P- 80,100,125 480Y/277 VAC 254 (440 for left neutral) 110 ( 195 for left neutral) 50…60 Hz 50…60 Hz 10 KA 2 KA 6 KV 2.5 KV 250 AMPS Blue sealable in ON-OFF position yes 10000 20000 -25°C… +55°C -40°C… +70°C Blue sealable in ON-OFF position yes 10000 20000 -25°C… +55°C -40°C… +70°C Terminal size top/bottom per cable Tightening torque mounting Connection Withdraw from busbar failsafe bidirectional cylinder-lift terminal at top and bottom (shock protected) 6 AWG Max. 17.5 in-lb max. 35mm din rail by means of fast clip From top & bottom Possible without the use of tools 6 AWG Max. 17.5 in-lb max. 35mm din rail by means of fast clip From top & bottom Possible without the use of tools Approximate dimensions 2 Pole mm 4 Pole mm 85x69x35 MM 85x69x70 MM 85x69x35 MM 85x69x70 MM Weight 2 Pole g 4 Pole g 200g 350g 200g 350g Combination with auxiliary elements Auxiliary contact signal contact/ auxiliary switch shunt trip undervoltage release yes yes yes yes yes yes yes yes Electrical features Standards Poles Rated current In Rated Voltage Ui Max operating voltage of curcuit test Min operating voltage of circuit test Rated Frequency Rated conditional Short-circuit current Rated residual breaking capacity Rated impulse withstand voltage (1.2/50) Uimp Power- frequency voltage dielectric strength Surge current resistance acc. To VDE 0432 Part 2 (wave 8/20) Mechanical features Toggle Contact position indicator Electrical Life Mechanical life Ambient temperature Storage temp. Installation Terminal Type 14 14.50 1SXU 000 023 C0201 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 00.00 Inches 00.00 [Millimeters] S Re yste sid m p u de al c ro M u vic rr es en t 14 Approximate dimensions Circuit diagrams F200, F670 Approximate dimensions Circuit diagrams POLE POLE 42)0 5.)4 4%34 #4 . 42)0 5.)4 4%34 #4 . 14 1 To use on 3p/3w systems, add jumper between 4 and 8N for operation of test button. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.51 1SXU 000 023 C0201 M t o pr rren em cu st ual es y S sid vic Re de 14 Notes 14 14.52 1SXU 000 023 C0201 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com System pro M compact Modular DIN rail components E220 - E270 Series S Mo yste d m co ular pro mp D on IN r M en ail ts 14 Description • Safe connection by box terminals • Captive screws with Pozidrive slotted head, Pozidrive system, Gr. 1 • Snap-on labels available • Quick mounting with snap-on clip, easily accessible and detachable at the bottom • Protection against unintentional direct touch • System approach for control and circuit protection • Compact size that dimensionally matches the S2 MCB series • Control and pilot functions can be along side protective devices Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com • DIN rail mounted with 45mm front opening • For use in auxiliary and logic devices • Provide additional user functions for system control and operation • Include pushbuttons, indicating lights and selector switches • ABB System Pro M compatibility • Most devices are both UL 508 recognized 14 and are IEC compliant • Labeled with the CE Mark 14.53 1SXU 000 023 C0201 M l o i pr ra N m I s e st r D nt Sy dula one p Mo om c 14 E221 & E222 Switches, 240VAC 16 & 25A Type Rated current Catalog number List price Delivery schedule Suggested order qtys Weight (Oz.) 1 piece Switches E221-10 1 N.O. + 1 N.C. 2 N.O. + 2 N.C. 3 N.O. + 1 N.C. 16 16 16 E221-11 E221-22 E221-31 $ 90 177 177 B 10 2.46 1 N.O. 2 N.O. 3 N.O. 4 N.O. 16 16 16 16 E221-10 E221-20 E221-30 E221-40 59 110 120 159 B 10 1.94 2.12 2.29 2.47 1 N.O. + 1 N.C. 1 N.O. 2 N.O. 3 N.O. 4 N.O. 25 25 25 25 25 E222-11 E222-10 E222-20 E222-30 E222-40 140 107 141 159 239 B 10 2.47 1.94 2.12 2.29 2.47 1 Change-over contact 2 Change-over contacts 16 16 E221-6 E221-6/2 69 125 B 10 2.12 2.47 1 Change-over contact 25 E222-6 128 B 10 2.12 Form “C” switches Form “C” switches (I-O-II, Hand-OFF-Automatic) 1 Pole 2 Pole 16 16 E221-4 E221-4/2 99 147 B 10 2.12 2.47 1 Pole 25 E222-4 150 B 10 2.12 Note: Above devices are UL 508 recognized and IEC certified. A300 pilot duty UL file # E171252 Delivery Class A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time 14 14.54 1SXU 000 023 C0201 Discount schedule CB20 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com E241 - E274 Disconnect switches 45, 63, 80 & 100A 14 S Mo yste d m co ular pro mp D on IN r M en ail ts Page Deleted 4/24/06 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14 14.55 1SXU 000 023 C0201 M l o i pr ra N m I s e st r D nt Sy dula one p Mo om c 14 E225 - E229, E10 Pilot devices Type Catalog number List price Delivery schedule Pack units pcs. Weight (Oz.) 1 piece Pushbutton, 1 N.O. + 1 N.C. contact Grey Red Green Yellow Black Blue E225-11B E225-11C E225-11D E225-11E E225-11F E225-11G $ 75 A 10 1.94 100 A 10 1.94 E229-B/110 E229-C/110 E229-D/110 E229-E/110 E229-G/110 93 A 10 1.59 E10/24 E10/110 E10/220 24 A 1 0.14 Illuminated pushbutton, 1 N.O. contact with lamp, 120 VAC E225-11F Clear Red Green Yellow Blue E227-10B/110 E227-10C/110 E227-10D/110 E227-10E/110 E227-10G/110 Pilot light with lamp, 120 VAC Clear Red Green Yellow Blue E227-10E Lamps 24 VAC/DC 120 VAC/DC 220 VAC/DC Note: Above devices are UL 508 recognized and IEC certified. UL file # E171252 Special features • • • • • 14 Safe connection via box terminals Captive screws with Phillips/Slotted head, Posidriv system, Gr. 1 Snap-on labels available Protection against unintentional touch acc. to DIN VDE 0106 Part 100 Lenses and pushbuttons in six colors Elapsed time meter E233-120/60 Type Catalog number 24 VAC, 60 Hz 120 VAC, 60 Hz 240 VAC, 60 Hz E233-24/60 E233-120/60 E233-240/60 List price $ 130 Delivery schedule Pack units pcs. Weight (KG) 1 piece B A B 1 Delivery schedule Pack units pcs. Weight (KG) 1 piece 0.045 • Non-resettable • 100,000 hours (99999.99) UL file #171252 Sockets Type E1175 Catalog number List price Socket, 250 VAC, 50/60 Hz Italian standard E1173 $ 57 B 1 0.2 Socket, 250 VAC, 50/60 Hz French standard E1174 $ 57 B 1 0.2 Socket, 250 VAC, 50/60 Hz Schuko standard E1175 $ 57 B 1 0.2 Socket w/cover, 250 VAC, 50/60 Hz Schuko standard E1175-C $ 57 B 1 0.2 Delivery Class E1175-C 14.56 1SXU 000 023 C0201 A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time Discount schedule CB20 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com S Mo yste d m co ular pro mp D on IN r M en ail ts 14 Digital meters Measuring instruments Type Catalog number List price Delivery schedule Pack units pcs. Weight (KG) 1 piece Digital timer, 230 VAC, 50/60 Hz DTS7/1 $ 422 B 1 0.3 Voltmeter 600 VAC, 50-400 Hz VLMD-1-2 510 B 1 0.3 Ammeter 15-20-25-40-60A, 250-400-600A, 50-400 Hz AMTD-1 510 B 1 0.3 Transformer, 230 VAC, 50/60 Hz 4-8-12 VAC sec TM15/12 135 B 1 0.3 DTS7/1 VLMD-1-2 14 TM15/12 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.57 1SXU 000 023 C0201 M l o i pr ra N m I s e st r D nt Sy dula one p Mo om c 14 Technical data Components for quick mounting onto DIN rails (35mm) Mounting depth: Mounting width: 68mm 1, 2, 3 and 4 pole switches = 17.5mm (= 1 module) E220 Switches, 16 & 25A Switching capacity: Short-circuit withstanding capacity: Toggle sealable: Connection cross-sections: Rated AC voltage: 1.25 In, 1.1Un, cos j = 0.6 3 kA, 380V, cos j = 0.9 In ON and OFF positions Up to 1 x 6mm2 or 2 x 2.5mm2 240 VAC UL/CSA (E171252) 250/440 VAC IEC E240/270 Disconnect switches, 45, 63, 80, & 100A Switching capacity: Short-circuit withstanding capacity: Connection cross-sections: 1.25 In, 1.1Un, cos j = 0.3 E240 = 10kA, E270 = 25kA RMS E240 up to 25mm2 E270 up to 50mm2 240/400/415 VAC Rated AC voltage: E Series components for quick mounting onto DIN rails (35mm) Mounting depth Mounting width: Color: Connection cross sections: Rated current: Rated voltage: Rated voltage: 68mm 17.5mm (=1 module) RAL 7035, grey Up to 1 X 6mm2 or 2 X 2.5mm2 16A 250 VAC IEC 240 VAC UL/CSA (E171252) Terminal markings 5 1 1 3 5 7 1 3 5 7 1 3 1 1 3 1 3 5 1 3 5 7 2 4 6 8 2 4 6 8 2 4 2 2 4 2 4 6 2 4 6 8 7 3 2 NO & 2 NC 2 6 4 8 3 NO & 1 NC 2 NO 1 NO 2 NO Switches 3 NO 4 NO Disconnect switches 14 1 3 1 3 7 1 3 5 7 1 3 1 3 7 5 1 3 I 2 2 1 NO 8 2 6 8 2 NO 2 3 NO 1 Pole Illuminated pushbutton 2 0 8 1 3 7 5 II I 2 2 Pole II 2 1 Pole Form "C" switches 0 8 2 Pole Form "C" switches (Hand - OFF- Auto) Terminal assignments for pushbuttons and indicator lights 5 1 7 3 1 1 7 5 1 1 MAX 2W 2 6 4 8 2 8 6 1 NO & 1 NC Pushbutton 14.58 1SXU 000 023 C0201 MAX 2W 2 2 2 1 NO Illuminated 1 NO Pilot light Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com S Mo yste d m co ular pro mp D on IN r M en ail ts 14 Approximate dimensions 00.00 Inches 00.00 [Millimeters] E220 1.77 3.35 3.35 45.0 85.0 85.0 1.99 50.5 0.69 2.52 64.0 0.69 17.5 17.5 Pilot light Pushbutton E220, 16 & 25A 1.77 3.35 45.0 85.0 1.99 50.5 0.69 2.52 64.0 E233 17.5 1.97 50.0 14 3.35 1.77 85.0 45.0 1 2 3 4 5 9 9 2.52 64.0 0.69 17.5 E240/270 1.77 3.52 45.0 89.5 1.38 35.0 1.99 50.5 0.69 2.52 64.0 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 17.5 1.38 52.5 2.76 70.0 14.59 1SXU 000 023 C0201 M l o i pr ra N m I s e st r D nt Sy dula one p Mo om c 14 Approximate dimensions E1173 - E1175 DTS VLMD, AMTD TMS 14 14.60 1SXU 000 023 C0201 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Tr su ans Transient voltage surge supressors rg ien es t up vol TVSS, OVR range t p 14 re age ss or s Description • • • • • • • • • • Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Compact DIN rail mounting Broad range 1, 2, 3, & 4 pole versions Replaceable plug cartridges Finger safe 15, 40, 65 & 100 kA versions Three position visual status indication Auxiliary contact for remote signalling UL 1449, File # E238957 & E22406 14 14.61 1SXU 000 023 C0201 ge lta ors o t v ess ien ppr s n u Tra ge s r su 14 General points on lightning and its risks Causes of transient overvoltages The most serious consequences of lightning are the death of people and farm animals, and the destruction of equipment: telephone lines, transformers connected to the electrical distribution network, electrical meters, household appliances, etc. At the same time, the growing amount of equipment incorporating very sensitive electronic devices increases the number of incidences linked to lightning. Within companies, if office automation equipment or machines (in factories) are put out of action, it nearly always leads to operating losses, the cost of which is much more than that of the damaged equipment. For example, if a bank’s computers are no longer operational, it suffers large operating losses. For the general public, the damage is mainly material: computer, household appliances, home cinema, etc. ROBUSTNESS OF EQUIPMENT 1950 1970 2000 PROPAGATION OF DISTURBANCES Causes of transient overvoltages 14 A transient overvoltage is a voltage peak with a maximum duration of less than one millisecond. There are two possible causes of overvoltages on electrical networks: • natural causes (lightning), • other causes due to equipment or switching devices. 1950 1970 2000 Natural overvoltages on low voltage networks are caused by direct lightning strikes. The high level of energy contained in a direct lightning strike on a lightning conductor or an overhead low voltage line leads to considerable damage of the installation. The overvoltage can be over 20 times the nominal voltage. Operating or switching overvoltages linked to a network’s equipment create overvoltages of a lower level (3 to 5 times the nominal voltage) but occur much more frequently, thus causing premature ageing of the equipment. Three categories of overvoltage propagate on low voltage networks: • direct lightning strikes, • indirect effects of lightning strikes, • operating or switching overvoltages. Propagation of overvoltages by electrical networks (power and low current) 14.62 1SXU 000 023 C0201 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com General points on lightning and its risks Causes of transient overvoltages Tr su ans rg ien es t up vol pr tag es so e rs 14 Overvoltages due to direct lightning strikes These can take two forms: • When lightning strikes a lightning conductor or the roof of a building which is earthed, the lightning current is dissipated into the ground. The impedance of the ground and the current flowing through it create large difference of potential: this is the overvoltage. This overvoltage then propagates throughout the building via the cables, damaging equipment along the way. • When lightning strikes an overhead low voltage line, the latter conducts high currents which penetrate into the building creating large overvoltages. The damage caused by this type of overvoltage is usually spectacular (e.g. fire in the electrical switchboard causing the destruction of buildings and industrial equipment) and results in explosions. Direct lightning strike on a lightning conductor or the roof of a building Direct lightning strike on an overhead line Overvoltages due to the indirect effects of lightning strikes The overvoltages previously mentioned are also found when lightning strikes in the vicinity of a building, due to the increase in potential of the ground at the point of impact. The electromagnetic fields created by the lightning current generate inductive and capacitive coupling, leading to other overvoltages. Within a radius up to several kilometres, the electromagnetic field caused by lightning in clouds can also create sudden increases in voltage. Although less spectacular than in the previous case, irreparable damage is also caused to so called sensitive equipment such as fax machines, computer power supplies and safety and communication systems. 14 Increase in ground potential Magnetic field Electrostatic field Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.63 1SXU 000 023 C0201 ge lta ors o t v ess ien ppr s n u Tra ge s r su 14 Different types of surges Equipment containing electronic switching components is also likely to generate electrical disturbances comparable to overvoltages. The consequences of which on sensitive equipment, albeit not visible, are no less detrimental: premature ageing and unpredictable or fleeting breakdowns. Operating overvoltages are produced when reactive or capacitive equipment is switched on and off. Furthermore, interrupting factory production, lighting or transformers can generate overvoltages which will themselves cause greater damage to nearby electrical equipment. Direct lightning strikes Indirect lightning strikes Operating overvoltages 14 Micro breaks Temporary phenomenon Duration > 200ms Too long for TVSS ➪ ➪ Harmonics Transient phenomenon Duration < 1ms TVSS needed ➪ Representation of the various disturbances on electrical networks Different type of power supply disturbances Main effects • Atmospheric discharges • Industrial interferences • Switching operations on the power distribution system • Destruction of the equipment • Premature aging • Incorrect operations 14.64 1SXU 000 023 C0201 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Tr su ans rg ien es t up vol pr tag es so e rs 14 OVR Range Main features TVSSs protect installations by limiting transient overvoltages and run-off lightning currents for electric and electronic equipment. They are divided into three families: • Type 2 TVSSs provide protection for equipment against transient overvoltage and they are installed in the Main Switch Board (MSB), or in the Sub-Distribution Board (SDB). In addition to the standard TVSSs, two options are available: the Safety reserve system and the remote indication (TS), in order to ensure a preventive maintenance of the installation. ABB TVSS (OVR range) offer the same “plus” advantages of the other System pro M compact devices, in order to get a perfect compatibility with all the modular range of products. ABB safety reserve system Contact for alarm connection All these TVSS products comply with the international standard IEC 61643-1 and the European standard EN 61643-11. They also comply with UL 1449 and CSA C22.2. 14 Pluggable unit / replacement modules DIN rail unit, easy installation and wiring Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.65 1SXU 000 023 C0201 ge lta ors o t v ess ien ppr s n u Tra ge s r su 14 Technical data OVR range Technical Features Electrical features 14 Mechanical features Installation Dimensions and weight Standards Type / test class Poles Types of networks Type of current Nominal voltage Un Max. cont. operating voltage Uc Voltage protection level Up at In Nominal discharge current In (8/20) Maximal discharge current Imax (8/20) Impulse current Iimp (10/350) Follow current Ifi Operating current Ic Short circuit withstand Icc Disconnector gG - gL fuse curve C circuit breaker curve K circuit breaker Stocking temperature Operating temperature Degree of protection Fire resistance according to UL 94 Material of Housing Maximal altitude Integrated thermal disconnector State indicator Compatibility with OVR Sign Safety reserve TS remote indicator Wire range L/N solid wire stranded wire Stripping length L/N Tightening torque L/N Wire range PE solid wire stranded wire Stripping length PE Tightening torque PE Pole dimensions (H x D x W) Pole weight Type 2 (L-N / L-PE / N-PE) (L-N / L-PE / N-PE) V V kV kA kA kA kA mA kA IEC 61643-1 / EN 61643-11 / UL1499 / CSA T2 / II 1P / 1P+N / 3P / 3P+N / 4P TNS - TT - TNC - IT / Wye / Delta A.C. All US network voltages 150 / 275 / 320 / 440 / 550 / 660 0.6 / 1.2 / 1.4 / 1.8 / 2.5 / 2.9 5 / 15 / 20 / 30 15 / 40 / 65 / 100 / None <1 50 A A 16 - 25 10 - 40 °C °C m -40 to +80 -40 to +80 IP 20 V2 PC grey RAL 7035 2000 Yes Yes Yes Option Option mm2 mm2 mm Nm 2.5 ... 25 2.5 ... 16 12.5 2 mm2 mm2 mm Nm 2.5 ... 25 2.5 ... 16 12.5 2 mm g 85 x 58 x 17.5 120 Technical Features of the integrated auxiliary contact Electrical features Contact complement 1NO (1 make contact), 1NC (1 normally closed contact) 12V D.C. - 10 mA 250V A.C. - 1A Min. load Max. load Installation 14.66 1SXU 000 023 C0201 Connection cross-section mm2 1.5 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Tr su ans rg ien es t up vol pr tag es so e rs 14 OVR Range Single pole Transient voltage surge suppressor Function: TVSS provides protection for equipment against transient overvoltage (indirect lightning strike) that occur on the electrical network (mains); the maximum discharge current (Imax) ranges from 15 to 100 kA per pole, based on MOV technology. Application: residential, commercial, industrial Standard: CEI 61643-1 / EN 61643-11 / UL 1449 / CSA 8/20 current wave Type 2 - Surge Protection Devices – Single pole Max Discharge Current (KA) 15 40 65 100 Nominal Voltage (V) MOV Voltage (V) Voltage Protection Level Up (KV) Catalog number List price 120 150 .06 OVR 15 150 OVR 15 150 s P 230 275 1.2 OVR 15 275 OVR 15 275 P TS 277 320 1.4 OVR 15 320 220 220 350 $ 230 350 220 340 400 440 1.8 OVR 15 440 OVR 15 440 P 480 550 2.5 OVR 15 550 275 600 660 2.9 120 150 0.6 OVR 15 660 OVR 40 150 s P OVR 40 150 s P TS 290 440 510 230 275 1.2 OVR 40 275 P OVR 40 275 s P OVR 40 275 s P TS 320 345 400 277 320 1.4 400 440 1.8 OVR 40 320 P OVR 40 320 s P OVR 40 320 s P TS OVR 40 440 OVR 40 440 s P OVR 40 440 s P TS 320 350 405 285 350 400 480 550 2.5 600 120 660 150 2.9 0.6 230 275 1.2 OVR 40 550 OVR 40 550 s OVR 40 660 s OVR 65 150 s P OVR 65 275 s P OVR 65 275 s P TS 435 475 490 395 490 565 495 520 277 320 1.4 OVR 65 320 s P OVR 65 320 s P TS 400 440 1.8 OVR 65 440 s P OVR 65 440 s P TS 465 530 480 600 550 660 2.5 2.9 OVR 65 550 s 600 230 275 1.2 OVR 65 660 s OVR 100 275 s P OVR 100 275 s P TS 675 830 955 277 320 1.4 OVR 100 320 s P OVR 100 320 s P TS 890 1025 400 440 1.8 OVR 100 440 s OVR 100 440 s P OVR 100 440 s P TS 800 870 1005 OVR 1N 65 275 s P TS Network 1N Single phase (left), neutral (right) 3N Three phase (left), neutral (right) N1 Neutral (left), single phase (right) N3 Neutral (left), three phases (right) 3L Three poles 4L Four poles Nothing Single pole Max. discharge current 8/20 Imax (kA) 15 40 65 100 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Discount schedule CB15 TS Integrated remote indication P Pluggable unit Nothing: Single block s with safety reserve Max. continuous operating voltage Uc (V) 660 550 440 385 320 275 150 75 14.67 1SXU 000 023 C0201 14 ge lta ors o t v ess ien ppr s n u Tra ge s r su 14 OVR TVSS Multi-pole Transient voltage surge suppressor Function: TVSS provides protection for equipment against transient overvoltage (indirect lightning strike) that occur on the electrical network (mains); the maximum discharge current (Imax) ranges from 15 to 100 kA per pole, based on MOV technology. Application: residential, commercial, industrial Standard: CEI 61643-1 / EN 61643-11 / UL 1449 / CSA 8/20 current wave Max Discharge Current (KA) Nominal Voltage (V) MOV Voltage (V) Voltage Protection Level Up (KV) Catalog number 120 150 0.6 OVR 1N 15 150 OVR 1N 15 150 s P TS OVR 3N 15 150 230 275 1.2 277 320 1.4 120 150 0.6 230 275 1.2 277 320 1.4 400 440 1.8 120 150 0.6 230 275 1.2 277 320 1.4 400 440 1.8 277 320 1.4 15 40 65 100 List price $ 365 665 625 OVR 3L 15 275 P OVR 3N 15 275 OVR 3N 15 320 625 690 980 OVR 1N 40 150 s P OVR 1N 40 150 s P TS OVR 3N 40 150 s P TS OVR 3N 40 275 s P OVR 3L 40 275 s P 665 935 1160 1120 950 OVR 3N 40 320 P OVR 3N 40 320 s P OVR 3N 40 320 s P TS OVR 3N 40 440 s P 1175 1250 1450 1290 OVR 1N 65 150 s P OVR 3N 65 150 s P OVR 3N 65 150 s P TS OVR 3L 65 275 s P OVR 3N 65 275 s P OVR 3N 65 320 s P OVR 3N 65 320 s P TS OVR 3N 65 440 s P OVR 4L 65 440 s 1000 1535 1640 1045 1280 1650 1900 1245 1320 OVR 3N 100 320 s P 3200 OVR 3N 100 320 s P TS 3600 14 OVR 1N 65 275 s P TS Network 1N Single phase (left), neutral (right) 3N Three phase (left), neutral (right) N1 Neutral (left), single phase (right) N3 Neutral (left), three phases (right) 3L Three poles 4L Four poles Nothing Single pole Max. discharge current 8/20 Imax (kA) 15 40 65 100 14.68 1SXU 000 023 C0201 Discount schedule CB15 TS Integrated remote indication P Pluggable unit Nothing: Single block s with safety reserve Max. continuous operating voltage Uc (V) 660 550 440 385 320 275 150 75 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com OVR Range Very low voltage transmission lines protection Tr su ans rg ien es t up vol pr tag es so e rs 14 Transmission line surge arresters (OVR TC) provide protection against transient overvoltages for equipment connected to telephone lines (digital or analog) & current loops. Standards Info: Modular low current surge arresters comply with IEC 61643-21 / UL 1449. Schematic diagrams L1 L1 l1 L2 l2 L2 OVR TC 06 V OVR TC 200 V in parallel OVR TC / xx V / 200 FR in series Dimensions Dimensions (mm) OVR TC (all models) W H D 17.5 85 63 Connection L1 L1 L2 L2 OVR TC 200 FR OVR TC 48 V OVR TC 24 V OVR TC 12 V OVR TC 06 V OVR TC 200 V OVR TC 200 FR 14 l1 OVR TC 200 V in parallel l2 OVR TC / xx V / 200 FR in series Fixing Simply clips onto DIN rail. Pratical info: Telecom and dataline protection surge arresters are installed in electrical switchboards or enclosures using DIN rail. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.69 1SXU 000 023 C0201 ge lta ors o t v ess ien ppr s n u Tra ge s r su 14 Electrical characteristics Types of network Number of pairs Type of protection Type of current Nominal voltage: Un Max cont operating voltage: Uc Voltage protection level: Up at In Nominal discharge current: In (8/20) Maximum discharge current: Imax (8/20) Bandwidth Operating current: Ic Degree of protection 50 Hz withstand (15 mn) Mechanical characteristics L/N connection terminals: – solid wire – stranded wire PE connection terminal: – solid wire – stranded wire Integrated thermal disconnector End of life indicator Compatibility with OVR Sign Miscellaneous characteristics Storage temperature Operating temperature Maximum altitude Case material Insulating material Reference standard Weight Technical data 6V OVR TC 06 V 12 V OVR TC 12 V 24 V OVR TC 24 V 48 V OVR TC 48 V 200 V OVR TC 200 V 200 V OVR TC 200 FR Communication 1 Series Low currents 6V 7V 15 V 5 kA 10 kA 10 MHz 20 mA IP 203 10 A Communication 1 Series Low currents 12 V 14 V 20 V 5 kA 10 kA 2 MHz 20 mA IP 203 10 A Communication 1 Series Low currents 24 V 27 V 35 V 5 kA 10 kA 4 MHz 20 mA IP 203 10 A Communication 1 Series Low currents 48 V 53 V 70 V 5 kA 10 kA 6 MHz 20 mA IP 203 10 A Communication 1 Parallel Low currents 200 V 220 V 700 V 5 kA 10 kA 100 MHz IP 203 - Communication 1 Series Low currents 200 V 220 V 300 V 5 kA 10 kA 3 MHz 20 mA IP 203 10 A No No No Yes Yes Yes 0.5 ... 2.5 mm2 0.5 ... 2.5 mm2 0.5 ... 2.5 mm2 0.5 ... 2.5 mm2 Yes Yes Yes -40 °C to +80 °C -40 °C to +80 °C 2000 m PC grey RAL 7032 UL94 V0 classification IEC 61643-21 / UL 1449 150 g 14 14.70 1SXU 000 023 C0201 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Tr su ans rg ien es t up vol pr tag es so e rs 14 Installation rules Principles of coordination for TVSS The first surge arrester does not provide effective protection for the whole installation by itself. Certain electrical phenomena can double the protection’s residual voltage if cable lengths exceed 10m. Surge arresters must be coordinated when they are installed refer to the tables below. Coordination required if: The first surge arrester does not reach the protection voltage (Up ) by itself. The first surge arrester is more than 10m away from the equipment to be protected. The first surge arrester diverts most of the current to the ground and the remaining surge current is diverted to the ground by the second surge arrester. The value of this remaining surge current gets lower as the distance between both surge arresters gets longer. The lower is the current going through the last surge arrester, the lower is the voltage protection level applied to the downstream equipment. Coordination between Type 2 TVSS units 65 kA 8/20 ➤ TVSS L>1m (1 m minimum between the two devices) ➤ TVSS 15 kA 8/20 14 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.71 1SXU 000 023 C0201 ge lta ors o t v ess ien ppr s n u Tra ge s r su 14 Approximate dimensions OVR range Transient voltage surge suppressor TVSS without TS TVSS with TS 45 87.3 95.6 87.3 45 97 63 63 40 40 1 pole 17,6 OVR 15 275 P OVR 15 440 P OVR 40 275 P OVR 40 275 s P TS OVR 40 440 P OVR 40 440 s P TS OVR 65 275 s P TS OVR 65 440 s P TS 14 4 poles OVR 4L 15 275 P OVR 4L 40 275 P OVR 4L 40 275 s P TS OVR 4L 65 275 s P TS 1SXU 000 023 C0201 52,8 OVR 3L 15 275 P OVR 3L 40 275 P OVR 3L 40 275 s P TS OVR 3L 65 275 s P TS 3 poles + Neutral 14.72 3 poles 70,4 OVR 3N 15 275 P OVR 3N 40 275 P OVR 3N 40 275 s P TS OVR 3N 65 275 s P TS Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Tr su ans rg ien es t up vol pr tag es so e rs 14 Technical details Installation rules for TVSS choice of associated breaking devices (fuse/circuit breaker) Choice of disconnector Surge arresters must be associated with upstream short-circuit protection and residual current protection against indirect contact (usually already present in the installation) Function Application Protection against fault currents Thermal protection The breaking device associated with the surge arrester can be either a circuit breaker or a fuse. Its rating should take into consideration the surge arrester’s characteristics and the short-circuit current of the installation. Thermal protection is integrated into the surge arrester. Maximum circuit-breaker or fuse protection rating depending on Imax and Iimp of the surge arrester. TVSS surge arresters Circuit-breaker (curve K) Fuse (gG) • Icc = 300 A to 1 kA 40 A 25 A • Icc = 1 kA to 7 kA 40 A 25 A • Icc = 7 kA and above 40 A 25 A TVSS surge arresters Circuit-breaker (curve C) Fuse (gG) 100 kA (8/20) 14 65 kA (8/20) • Icc = 300 A to 1 kA 30 A 20 A • Icc = 1 kA to 7 kA 32 A to 40 A 40 A • Icc = 7 kA and above 32 A to 63 A 63 A • Icc = 300 A to 1 kA 25 A 16 A • Icc = 1 kA to 7 kA 25 A 25 A 25 A to 50 A 50 A • Icc = 300 A to 1 kA 10 A to 25 A 16 A • Icc = 1 kA to 7 kA 10 A to 32 A 16 A • Icc = 7 kA and above 10 A to 40 A 25 A to 40 A 40 kA (8/20) • Icc = 7 kA and above 15 kA (8/20) Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.73 1SXU 000 023 C0201 ge lta ors o t v ess ien ppr s n u Tra ge s r su 14 Technical details Cabling and installation of Surge Protection Devices in an electrical panel ➤ Remember that a 10 kA lightning current passing through a 1 m length of cable generates 1000 Volts. Equipment protected by a surge arrester is subjected to a voltage equal to the sum of the Up voltage of the surge arrester, Ud of its disconnector and the sum of the inductive voltages of connecting cables (U1+U2+U3). It is therefore essential that the total length (L = L1+L2+L3) of the connecting cables is as short as possible (0.50 m). U1 ➤ 50 cm rule L1 ➤ If this length (L = L1 + L2+L3) exceeds 0.50m, it is necessary to carry out one of the following: • Reduce this length by moving the connection terminals. • Choose a surge arrester with a lower Up value. • Install a second, coordinated surge arrester near the device to be protected so as to adapt the combined Up value to the impulse withstand of the equipment to be protected. ➤ UD L L2 ➤ U2 ➤ UP Wiring ring surfaces The wires must be arranged in such a way that they are as close to each other as possible (see adjacent diagram) to avoid overvoltages induced by a ring surface between phases, the neutral and the PE conductor. ➤ ➤ L3 U3 Routing of clean cables and polluted cables During installation, lay clean cables (protected) and polluted cables as shown in the adjacent diagrams. To avoid magnetic coupling between the different cable types (clean and polluted), it is strongly advised that they are kept apart (> 30 cm) and if a crossing cannot be avoided, it should be at right angles (90°). ➤ Polluted cables D > 30 cm ➤ Crossing at 90° Clean cables Polluted cable Main circuitbreaker Clean cable Ring surface Surge arrester circuitbreaker Terminal / MCB 14 Feeder 1 Clean cable ➤ MCB / TVSS Polluted cable D > 30 cm ➤ D < 30 cm ➤ ➤ Feeder 2 TVSS / Earth terminal Equipotential grounding: It is critical to check the earth equipotentiality of the various items of equipment. Note: The cross-section of the connecting cables is calculated according to the local short-circuit current level (where the surge arrester is installed). It must be equal to the cross-section of the installation’s upstream cables. The minimum cross-section for the earth conductor is 4 mm2 if there is not a lightning conductor and 10 mm2 if there is a lightning conductor. 14.74 1SXU 000 023 C0201 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Application sheets OVR Surge Protection Devices Operating principle Tr su ans rg ien es t up vol pr tag es so e rs 14 Example of installation The Surge Protection Devices (TVSS), suitable for residential, commercial and industrial applications, are designed to limit transient overvoltage and run-off lightning currents. Application environments As shown in the diagrams, one of the possible applications is to protect the equipment (TV, computer, ...) against overvoltage thanks to a Surge Protection Device (TVSS) which ensures the protection in common mode (Ph-PE / N-PE) and differential mode (Ph-N). The Surge Protection Devices (TVSS) are necessary in any environment where the lightning risk exists (direct lightning strike / overvoltage). , , , . %QUIPMENT PROTECTED 14 Type 2 TVSS Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.75 1SXU 000 023 C0201 ge lta ors o t v ess ien ppr s n u Tra ge s r su 14 General points on lightning and its risks Diagram of an installation protected against lightning and its indirect effects The 100KA or 65KA surge arrester (depending on the lightning risk) fitted in the installation’s main incoming electrical switchboard, is capable of deviating the energy of a direct lightning strike. This is the first stage of the electrical network’s protection. The behaviour of the cables, subjected to a transient signal, limits the effectiveness of a surge arrester to 10 m of cable. It is therefore necessary to use one or more surge arresters in the installation in order to obtain the required level of protection for the equipment. Here, a 40KA or 15KA surge arrester (depending on the lightning risk) should be used in coordination with the incoming surge arrester. This is the second stage of the protection. Finally, if there is a risk of overvoltage on the electrical network, this risk also exists for the auxiliary wiring network. The appropriate protection is a surge arrester designed to protect telephone or data transmission lines (OVR TC). This is fitted in series on the network. Protects the building Protects the telephone network Telephone Line Surge Arrester OVR TC 200 FR 14 Sub-distribution switchboard PABX Incoming power cable Incoming telephone line Main electrical switchboard Protects the machines OVR 3N 65 275s PTS 14.76 1SXU 000 023 C0201 Protects computer feeders OVR 3N 15 275 s P TS Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Selection Example of a protected industrial installation GE (Generator set) Transformer T1 OVR 3N 65 440s PTS 14 Transformer T2 OVR 3N 65 440s PTS (1) Tr su ans rg ien es t up vol pr tag es so e rs OVR 3N 65 440s PTS (1) MSB 10 (1) MSB 11 Type 2 Surge Arrester OVR 3N 40 440 s P TS SDB 20 (Sub-distribution board) MSB 12 Type 2 Surge Arrester OVR 3N 40 440 s P TS SDB 21 (Sub-distribution board) Type 2 Surge Arrester OVR 3N 15 440 s P TS (1) SDB 23 (Sub-distribution board) Surge Arrester Type 2 OVR 3N 40 440 s P TS SDB 22 (Sub-distribution board) Type 2 Surge Arrester OVR 3N 15 440 s P TS (1) SDB 24 (Sub-distribution board) 14 Surge Arrester Type 2 OVR 3N 15 440 s P TS (1) SDB 25 (Sub-distribution board) The above diagram is an example of an industrial application located in an area where the lightning strike density (Ng) is 1.2 lightning strikes per km2 and per year: • the building is protected by a lightning conductor. • the lightning conductor's earthing strip is connected to the installation's earth network. • the earthing system is IT (with distributed neutral) and then TNS for the sub-distribution boards. • main switch boards (MSB) 10, 11 and 12 are fitted with Type 2 surge arresters OVR 3N 65 440 s PTS. • sub-distribution boards (SDB) 20, 21 and 22 are fitted with Type 2 surge arresters OVR 3N 40 440 s P TS. • sub-distribution boards (SDB) 23, 24 and 25 are fitted with Type 2 surge arresters OVR 3N 15 440 s P TS. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 14.77 1SXU 000 023 C0201 ge lta ors o t v ess ien ppr s n u Tra ge s r su 14 Terminology of electrical characteristics Surge arrester: Device designed to limit transient overvoltages and run-off lightning currents. It consists of at least one non-linear component. It must comply with European standard EN 61643-11. 1.2/50 wave: Standardized overvoltage waveform created on networks and which adds to the network’s voltage. 8/20 wave: Current waveform which passes through equipment when subjected to an overvoltage. Type 2 surge arrester: Surge arrester designed to run-off energy caused by an overvoltage comparable to that of an indirect lightning strike or an operating overvoltage. It has successfully passed testing to the standard with the 8/20 wave (class II test). Up: Voltage protection level / Let through voltage Parameter characterising surge arrester operation by the level of voltage limitation between its terminals and which is selected from the list of preferred values in the standard. This value is greater than the highest value obtained during voltage limitation measurements (at In). 8/20 In: Nominal discharge current. Peak current value of an 8/20 waveform (15 times) flowing in the surge arrester. It is used to determine the Up value of the surge arrester. Imax: Maximum discharge current for class II testing. Peak current value of an 8/20 waveform flowing in the surge arrester with an amplitude complying with the class II operating test sequence. 14 Imax is greater than In. µs Type 2 Surge Arresters Imax: current wave Un: Nominal AC voltage of the network : nominal voltage between phase and neutral (AC rms value). 14.78 1SXU 000 023 C0201 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com