GUIDE SPECIFICATIONS TW Series Two Stage Water-to-Water Reverse Cycle Chillers & Low Temp Boilers TW025-071 Reverse Cycle Chillers / Low Temperature Boilers GENERAL Units shall be Underwriter Laboratories (UL) listed for safety on all models. Each unit shall be run tested at the factory, pallet mounted and stretch wrapped. The units shall be manufactured in an ISO 9001:2000 certified facility, designed to operate with entering fluid temperatures between 20˚F (-7˚C) and 120˚F (49˚C) as manufactured by Bosch in Fort Lauderdale, Florida. Refrigerant shall be R-410A. CASING & CABINET The cabinet shall be fabricated from heavy gauge steel finished with a vinyl coated black cabinet and decorative gold anodized aluminum front panel for corrosion protection. The interior shall be insulated with ½" (12.7mm) thick foil faced glass fiber. All units shall allow sufficient service access to replace the compressor without unit removal. The compressor shall be covered with a multi-density sound absorbing blanket and have a floating base pan to minimize noise transmission. REFRIGERATION CIRCUITS All units shall contain a hermetically sealed refrigerant circuit including a two stage scroll compressor, bidirectional thermal expansion valve metering device, coaxial style fluid-torefrigerant heat exchangers, refrigerant reversing valve and service ports. Compressor shall be high efficiency, two stage scroll type, designed for heat pump duty, quiet operation and mounted on rubber vibration isolators. Compressor motors shall be equipped with overload protection. Refrigerant reversing valves shall be pilot operated sliding piston type with replaceable encapsulated magnetic coils energized only during the chiller cycle. The coaxial water-to-refrigerant heat exchanger shall be constructed of a convoluted copper (optional cupronickel) inner tube and steel outer tube with a designed refrigerant working pressure of 600 PSIG (4100kPa) and a designed water side working pressure of no less than 400 PSIG (2750kPa). Due to their susceptibility to fouling, brazed plate heat exchangers are not acceptable. The fluidto-refrigerant heat exchangers shall be insulated to prevent condensation at low fluid temperatures. Catalog (TW Technical Data Sheet) ELECTRICAL Controls and safety devices will be factory wired and mounted within the unit. Controls shall include comfort alert module, compressor contactor, 24V transformer, reversing valve coil and solid state lockout controller (UPM) The UPM controller shall include the following features: Anti-short cycle time delay, random start, brown out/surge/power interruption protection, 120 second low pressure switch bypass timer, shutdown on high or low refrigerant pressure safety switch inputs, shutdown for the optional freezestat, 24 VAC alarm output for remote fault indication, unit reset at thermostat or disconnect, ability to defeat time delays for servicing and automatic intelligent reset. The UPM shall automatically reset after a safety shut down and restart the unit, if the cause of the shut down no longer exists, after the anti-short cycle and random start timers expire. Should a fault re-occur within 60 minutes after reset, then a permanent lockout will occur. A light emitting diode (LED) shall annunciate the following alarms: high refrigerant pressure, low refrigerant pressure and low water temperature (when equipped with the optional low water temperature sensor). The LED will display each fault condition as soon as the fault occurs. If a permanent lockout occurs, then the fault LED will display the type of fault until the unit is reset. Safety devices include a low pressure cutout set a 40 PSIG (280 kPa) for loss of charge protection (freezestat and/or high discharge gas temperature sensor are not acceptable) and a high pressure cutout control set at 600 PSIG (4100 kPa). An optional energy management relay that allows unit control by an external source shall be factory installed. A terminal block with screw terminals shall be provided for control wiring. PIPING Water piping connections shall be female pipe thread with a single set of source and load connections flush mounted to the unit cabinet. hEAT RECOvERy PACkAGE 208/230 volt units shall be equipped with an optional factory installed internal heat recovery kit for domestic hot water production. This kit shall include a vented, double walled coaxial water to refrigerant heat exchanger, circuit breaker protected circulating pump, high water temperature safety cutoff and a low refrigerant temperature cutout. TWSPECS.INDD REV: 03-11 A B C 24.12 24.12 24.12 24.12 24.12 32.50 32.50 32.50 32.50 32.50 24.00 24.00 24.00 24.00 24.00 Height Width Depth 2.70 2.30 2.30 2.30 3.00 D 2.50 2.30 2.60 2.60 2.25 E F 13.70 14.30 14.30 14.30 17.25 NOTES: All dimensions within +/- 0.125". Specifications subject to change without notice. TW025 TW035 TW049 TW061 TW071 MODEL FhP Manufacturing Co. 601 N.W. 65th Court Fort Lauderdale, FL 33309 Phone: (954) 776-5471 Fax: (800) 776-5529 http://www.bosch-climate.us 2.50 2.35 2.65 2.65 2.25 G 3.25 3.70 3.70 3.20 3.25 H 1.95 2.55 2.65 2.65 2.25 J 14.25 15.70 15.70 15.20 17.00 K 1.95 2.55 2.65 2.65 2.25 L 7.15 7.15 7.15 7.15 7.15 M 4.25 4.25 4.25 4.25 4.25 P 6.55 6.55 6.55 6.55 6.55 Q 8.05 8.05 8.05 8.05 8.05 9.55 9.55 9.55 9.55 9.55 1.25 1.25 1.25 1.25 1.25 T Water HRP Conn. Conn. 3/4 FTP 5/8 FPT 3/4 FTP 5/8 FPT 1-1/8 FPT 5/8 FPT 1-1/8 FPT 5/8 FPT 1-1/8 FPT 5/8 FPT Cabinet Type: CS-Remote Control US-Unit Mounted Controller TWSDGIP.P65 REV: 03-11 Condenser Material: C-Copper N-Cupro-Nickel Water Connections: F-Front Return Air Location: X-None Nominal Capacity: Voltage: 1-208/230-1-60 Supply Air Location: X-None Series: TW-Water-to-Water TW___-_ __ _-_ _ _ TW Series Reverse Cycle Chiller Nomenclature 11.00 11.00 11.00 11.00 11.00 N Dimensions R S Two Stage Reverse Cycle Chillers TW025-071 Series WATER COOLED ChILLERS AND LOW TEMP BOILERS SPECIFICATION DATA SHEET TW SERIES FLUID FLOW & PRESSURE DROP ELECTRICAL SPECIFICATIONS Compressor TW025 Electrical Characteristics Elect. Symbol RLA LRA Min. Circuit Ampacity 208/230-1-60 -1 10.3 52 12.9 Max. Fuse Size 20 Chilled Fluid Side (@ 55OF) Flow (GPM) ∆P (FOH) 3.0 1.29 4.0 2.18 5.0 3.27 6.0 4.55 8.0 7.67 Cond. Fluid Side (@ 85OF) Flow (GPM) ∆P (FOH) 3.0 1.17 4.0 1.97 5.0 2.96 6.0 4.12 8.0 6.94 ChILLER PERFORMANCE - PART LOAD hEATING PERFORMANCE Based on 5 GPM chilled fluid & 10OF condenser fluid temp. rise. Based on 10OF load temp. rise & 5 GPM source fluid flow. Leaving Entering Total Load Source Capacity Fluid (˚F) Fluid (˚F) (Tons) 1.27 75o 1.24 80o 1.22 40o 85o 1.18 90o 1.15 95o 1.32 75o 1.29 80o 1.26 42o 85o 1.23 90o 1.19 95o 1.37 75o 1.34 80o 1.31 44o 85o 1.28 90o 1.24 95o 1.39 75o 1.37 80o 1.33 45o 85o 1.30 90o 1.26 95o 1.98 75o 1.98 80o 1.98 46o 85o 1.98 90o 1.98 95o 1.47 75o 1.44 80o 1.41 48o 85o 1.37 90o 1.33 95o 1.53 75o 1.50 80o 1.46 50o 85o 1.42 90o 1.38 95o Total Capacity (MBtuH) 15.24 14.93 14.58 14.21 13.81 15.82 15.50 15.14 14.75 14.33 16.43 16.09 15.71 15.30 14.87 16.74 16.39 16.00 15.59 15.14 23.78 23.78 23.78 23.78 23.78 17.70 17.32 16.91 16.47 16.00 18.37 17.97 17.54 17.07 16.59 Power Input (kW) 0.89 0.97 1.05 1.13 1.22 0.89 0.97 1.05 1.13 1.22 0.89 0.97 1.04 1.13 1.22 0.89 0.96 1.04 1.13 1.22 1.62 1.62 1.62 1.62 1.62 0.89 0.96 1.04 1.13 1.21 0.89 0.96 1.04 1.12 1.21 EER 17.06 15.41 13.92 12.56 11.32 17.75 16.03 14.47 13.05 11.77 18.46 16.66 15.03 13.56 12.23 18.82 16.98 15.32 13.82 12.46 4.29 4.29 4.29 4.29 4.29 19.94 17.99 16.22 14.63 13.19 20.72 18.68 16.85 15.19 13.70 Heat Rejection (MBtuH) 18.28 18.23 18.16 18.07 17.97 18.86 18.80 18.71 18.60 18.49 19.47 19.38 19.28 19.15 19.02 19.77 19.68 19.57 19.43 19.29 18.24 18.24 18.24 18.24 18.24 20.73 20.61 20.46 20.31 20.14 21.39 21.25 21.09 20.91 20.72 Leaving Entering Load Source Fluid (˚F) Fluid (˚F) 35O 40O O 100 50O 60O 70O 35O 40O O 110 50O 60O 70O 35O 40O O 120 50O 60O 70O 35O 40O O 125 50O 60O 70O Total Capacity (MBtuH) 15.80 16.86 19.21 21.92 25.03 15.78 16.77 19.00 21.57 24.53 15.76 16.70 18.80 21.23 24.02 15.77 16.68 18.71 21.07 23.78 Power Input (kW) 1.22 1.20 1.18 1.16 1.13 1.41 1.40 1.37 1.34 1.32 1.62 1.61 1.58 1.55 1.52 1.74 1.72 1.69 1.66 1.62 COP 3.81 4.10 4.77 5.55 6.47 3.28 3.52 4.07 4.71 5.46 2.85 3.05 3.50 4.02 4.64 2.66 2.84 3.25 3.73 4.29 Heat of Abs. (MBtuH) 11.65 12.75 15.18 17.97 21.16 10.97 12.01 14.33 16.99 20.04 10.23 11.22 13.42 15.95 18.85 9.84 10.81 12.95 15.42 18.24 Units are complete packages featuring 2 stage operation and containing refrigeration compressor, reversing valve, expansion valve metering device and water to refrigerant heat exchangers. Also included are safety controls: Overload protection for compressor, high and low refrigerant pressure switches and a lock-out control circuit. FhP Manufacturing Company 601 N.W. 65th Court Fort Lauderdale, FL 33309 Phone: (954) 776-5471 Fax: (800) 776-5529 http://www.bosch-climate.us As a result of continuing research and development, specifications are subject to change without notice. TW025.1INDD Rev:03-11 WATER COOLED ChILLERS AND LOW TEMP BOILERS SPECIFICATION DATA SHEET TW SERIES FLUID FLOW & PRESSURE DROP ELECTRICAL SPECIFICATIONS Compressor TW025 Electrical Characteristics Elect. Symbol RLA LRA Min. Circuit Ampacity 208/230-1-60 -1 10.3 52 12.9 Max. Fuse Size 20 Chilled Fluid Side (@ 55OF) Flow (GPM) ∆P (FOH) 3.0 1.28 4.0 2.17 5.0 3.26 6.0 4.54 8.0 7.64 Cond. Fluid Side (@ 85OF) Flow (GPM) ∆P (FOH) 3.0 1.16 4.0 1.96 5.0 2.95 6.0 4.10 8.0 6.92 ChILLER PERFORMANCE - FULL LOAD hEATING PERFORMANCE Based on 5 GPM chilled fluid & 10OF condenser fluid temp. rise. Based on 10OF load temp. rise & 5 GPM source fluid flow. Leaving Entering Total Load Source Capacity Fluid (˚F) Fluid (˚F) (Tons) 1.77 75o 1.73 80o 1.68 40o 85o 1.63 90o 1.59 95o 1.83 75o 1.78 80o 1.74 42o 85o 1.69 90o 1.64 95o 1.89 75o 1.84 80o 1.80 44o 85o 1.75 90o 1.69 95o 1.92 75o 1.88 80o 1.83 45o 85o 1.78 90o 1.72 95o 1.96 75o 1.91 80o 1.86 46o 85o 1.81 90o 1.76 95o 2.02 75o 1.97 80o 1.92 48o 85o 1.86 90o 1.81 95o 2.08 75o 2.03 80o 1.98 50o 85o 1.93 90o 1.87 95o Total Capacity (MBtuH) 21.23 20.72 20.18 19.61 19.02 21.95 21.42 20.86 20.28 19.67 22.68 22.14 21.56 20.96 20.33 23.06 22.50 21.92 21.31 20.67 23.50 22.94 22.33 21.73 21.07 24.21 23.63 23.02 22.38 21.71 25.01 24.41 23.77 23.11 22.42 Power Input (kW) 1.36 1.44 1.53 1.63 1.74 1.36 1.45 1.54 1.64 1.74 1.36 1.45 1.54 1.64 1.75 1.37 1.45 1.54 1.64 1.75 1.36 1.45 1.54 1.64 1.74 1.37 1.46 1.55 1.65 1.76 1.38 1.46 1.56 1.66 1.76 EER 15.65 14.37 13.15 12.00 10.93 16.14 14.81 13.56 12.38 11.28 16.63 15.26 13.98 12.76 11.63 16.87 15.49 14.19 12.96 11.81 17.30 15.90 14.50 13.30 12.10 17.63 16.19 14.83 13.55 12.35 18.15 16.67 15.26 13.95 12.71 Heat Rejection (MBtuH) 25.86 25.64 25.42 25.19 24.96 26.59 26.35 26.11 25.86 25.62 27.34 27.08 26.82 26.56 26.29 27.72 27.46 27.19 26.92 26.64 28.14 27.87 27.57 27.31 27.01 28.90 28.61 28.31 28.01 27.71 29.71 29.40 29.09 28.77 28.44 Leaving Entering Load Source Fluid (˚F) Fluid (˚F) 35O 40O O 100 50O 60O 70O 35O 40O O 110 50O 60O 70O 35O 40O O 120 50O 60O 70O 35O 40O O 125 50O 60O 70O Total Capacity (MBtuH) 21.77 23.11 26.05 29.36 33.08 21.60 22.87 25.67 28.84 32.41 21.45 22.65 25.30 28.31 31.72 21.38 22.55 25.12 28.05 31.37 Power Input (kW) 1.67 1.66 1.65 1.65 1.65 1.90 1.89 1.88 1.87 1.88 2.16 2.15 2.13 2.13 2.14 2.30 2.29 2.27 2.27 2.27 COP 3.83 4.08 4.62 5.22 5.87 3.33 3.55 4.01 4.51 5.05 2.91 3.09 3.48 3.90 4.35 2.72 2.89 3.24 3.63 4.04 Heat of Abs. (MBtuH) 16.09 17.45 20.42 23.73 27.44 15.12 16.43 19.27 22.45 26.00 14.08 15.32 18.03 21.05 24.43 13.53 14.74 17.37 20.32 23.61 Units are complete packages featuring 2 stage operation and containing refrigeration compressor, reversing valve, expansion valve metering device and water to refrigerant heat exchangers. Also included are safety controls: Overload protection for compressor, high and low refrigerant pressure switches and a lock-out control circuit. FhP Manufacturing Company 601 N.W. 65th Court Fort Lauderdale, FL 33309 Phone: (954) 776-5471 Fax: (800) 776-5529 http://www.bosch-climate.us As a result of continuing research and development, specifications are subject to change without notice. TW025.2INDD Rev:03-11 WATER COOLED ChILLERS AND LOW TEMP BOILERS SPECIFICATION DATA SHEET TW SERIES FLUID FLOW & PRESSURE DROP ELECTRICAL SPECIFICATIONS Compressor TW035 Electrical Characteristics Elect. Symbol RLA LRA Min. Circuit Ampacity 208/230-1-60 -1 16.7 82 20.9 Max. Fuse Size 35 Chilled Fluid Side (@ 55OF) Flow (GPM) ∆P (FOH) 4.5 3.00 6.0 5.05 7.5 7.56 9.0 10.53 12.0 17.75 Cond. Fluid Side (@ 85OF) Flow (GPM) ∆P (FOH) 4.5 2.71 6.0 4.56 7.5 6.84 9.0 9.52 12.0 16.06 ChILLER PERFORMANCE - PART LOAD hEATING PERFORMANCE Based on 5.3 GPM chilled fluid & 10OF condenser fluid temp. rise. Based on 10OF load temp. rise & 5.3 GPM source fluid flow. Leaving Entering Total Load Source Capacity Fluid (˚F) Fluid (˚F) (Tons) 1.73 75o 1.69 80o 1.65 40o 85o 1.61 90o 1.57 95o 1.79 75o 1.75 80o 1.71 42o 85o 1.67 90o 1.62 95o 1.85 75o 1.82 80o 1.77 44o 85o 1.73 90o 1.68 95o 1.89 75o 1.85 80o 1.80 45o 85o 1.76 90o 1.71 95o 1.92 75o 1.88 80o 1.84 46o 85o 1.79 90o 1.74 95o 1.99 75o 1.94 80o 1.90 48o 85o 1.85 90o 1.80 95o 2.05 75o 2.01 80o 1.96 50o 85o 1.91 90o 1.86 95o Total Capacity (MBtuH) 20.76 20.33 19.85 19.34 18.78 21.50 21.05 20.56 20.03 19.46 22.25 21.79 21.28 20.74 20.15 22.64 22.16 21.65 21.10 20.51 23.05 22.57 22.02 21.46 20.87 23.82 23.32 22.78 22.21 21.59 24.64 24.12 23.56 22.97 22.34 Power Input (kW) 1.31 1.40 1.50 1.61 1.72 1.31 1.40 1.50 1.60 1.72 1.30 1.39 1.49 1.60 1.71 1.30 1.39 1.49 1.59 1.71 1.13 1.38 1.48 1.59 1.70 1.28 1.38 1.48 1.58 1.70 1.28 1.37 1.47 1.57 1.69 EER 15.82 14.47 13.20 12.01 10.89 16.46 15.05 13.73 12.49 11.33 17.13 15.66 14.28 12.99 11.78 17.47 15.97 14.56 13.24 12.01 17.90 16.40 14.83 13.50 17.03 18.56 16.95 15.44 14.04 12.74 19.32 17.64 16.07 14.61 13.25 Heat Rejection (MBtuH) 25.24 25.12 24.98 24.83 24.66 25.95 25.82 25.67 25.50 25.32 26.68 26.53 26.37 26.18 25.99 27.06 26.90 26.72 26.53 26.33 27.45 27.27 27.08 26.89 26.68 28.20 28.02 27.82 27.60 27.38 28.99 28.78 28.57 28.34 28.09 Leaving Entering Load Source Fluid (˚F) Fluid (˚F) 35o 40o o 100 50o 60o 70o 35o 40o o 110 50o 60o 70o 35o 40o o 120 50o 60o 70o 35o 40o o 125 50o 60o 70o Total Capacity (MBtuH) 21.57 22.93 25.87 29.11 32.67 21.42 22.74 25.58 28.71 32.13 21.23 22.51 25.26 28.27 31.56 21.12 22.38 25.08 28.03 31.26 Power Input (kW) 1.70 1.68 1.63 1.57 1.49 1.95 1.92 1.87 1.81 1.73 2.23 2.21 2.15 2.08 2.00 2.39 2.37 2.31 2.24 2.15 COP 3.73 4.01 4.65 5.44 6.41 3.23 3.46 4.00 4.65 5.45 2.79 2.99 3.44 3.97 4.63 2.59 2.77 3.18 3.67 4.26 Heat of Abs. (MBtuH) 15.78 17.21 20.31 23.75 27.57 14.79 16.18 19.19 22.54 26.24 13.61 14.97 17.91 21.15 24.74 12.95 14.30 17.20 20.39 23.92 Units are complete packages featuring 2 stage operation and containing refrigeration compressor, reversing valve, expansion valve metering device and water to refrigerant heat exchangers. Also included are safety controls: Overload protection for compressor, high and low refrigerant pressure switches and a lock-out control circuit. FhP Manufacturing Company 601 N.W. 65th Court Fort Lauderdale, FL 33309 Phone: (954) 776-5471 Fax: (800) 776-5529 http://www.bosch-climate.us As a result of continuing research and development, specifications are subject to change without notice. TW035.1INDD Rev:03-11 WATER COOLED ChILLERS AND LOW TEMP BOILERS SPECIFICATION DATA SHEET TW SERIES FLUID FLOW & PRESSURE DROP ELECTRICAL SPECIFICATIONS Compressor TW035 Electrical Characteristics Elect. Symbol RLA LRA Min. Circuit Ampacity 208/230-1-60 -1 16.7 82 20.9 Max. Fuse Size 35 Chilled Fluid Side (@ 55OF) Flow (GPM) ∆P (FOH) 4.5 2.98 6.0 5.04 7.5 7.55 9.0 10.52 12.0 17.71 Cond. Fluid Side (@ 85OF) Flow (GPM) ∆P (FOH) 4.5 2.69 6.0 4.55 7.5 6.83 9.0 9.51 12.0 16.02 ChILLER PERFORMANCE - FULL LOAD hEATING PERFORMANCE Based on 5.3 GPM chilled fluid & 10OF condenser fluid temp. rise. Based on 10OF load temp. rise & 5.3 GPM source fluid flow. Leaving Entering Total Load Source Capacity Fluid (˚F) Fluid (˚F) (Tons) 2.37 75o 2.31 80o 2.25 40o 85o 2.19 90o 2.12 95o 2.45 75o 2.39 80o 2.33 42o 85o 2.26 90o 2.19 95o 2.53 75o 2.47 80o 2.40 44o 85o 2.33 90o 2.27 95o 2.57 75o 2.51 80o 2.44 45o 85o 2.37 90o 2.30 95o 2.61 75o 2.55 80o 2.48 46o 85o 2.41 90o 2.34 95o 2.69 75o 2.63 80o 2.56 48o 85o 2.49 90o 2.42 95o 2.78 75o 2.71 80o 2.64 50o 85o 2.57 90o 2.49 95o Total Capacity (MBtuH) 28.43 27.73 27.01 26.26 25.48 29.37 28.65 27.90 27.13 26.32 30.33 29.58 28.81 28.01 27.19 30.82 30.06 29.28 28.47 27.63 31.32 30.54 29.74 28.92 28.07 32.33 31.53 30.71 29.86 28.98 33.36 32.55 31.70 30.82 29.91 Power Input (kW) 1.98 2.09 2.22 2.36 2.50 1.99 2.10 2.23 2.37 2.52 2.00 2.11 2.24 2.38 2.53 2.00 2.12 2.25 2.38 2.53 2.01 2.13 2.25 2.39 2.54 2.02 2.14 2.26 2.40 2.55 2.03 2.15 2.27 2.41 2.56 EER 14.39 13.25 12.17 11.14 10.17 14.78 13.61 12.51 11.46 10.47 15.19 13.99 12.86 11.78 10.76 15.39 14.18 13.03 11.94 10.91 15.60 14.40 13.20 12.10 11.10 16.03 14.77 13.57 12.45 11.38 16.46 15.17 13.95 12.79 11.69 Heat Rejection (MBtuH) 35.17 34.88 34.58 34.30 34.02 36.14 35.83 35.51 35.20 34.90 37.14 36.80 36.46 36.13 35.80 37.65 37.30 36.94 36.60 36.26 38.17 37.79 37.43 37.07 36.72 39.21 38.82 38.43 38.05 37.67 40.28 39.87 39.45 39.04 38.64 Leaving Entering Load Source Fluid (˚F) Fluid (˚F) 35o 40o o 100 50o 60o 70o 35o 40o o 110 50o 60o 70o 35o 40o o 120 50o 60o 70o 35o 40o o 125 50o 60o 70o Total Capacity (MBtuH) 29.26 31.03 34.85 39.09 43.77 29.13 30.82 34.48 38.54 43.02 29.09 30.69 34.17 38.02 42.30 29.10 30.66 34.04 37.79 41.95 Power Input (kW) 2.30 2.31 2.32 2.32 2.33 2.61 2.62 2.62 2.63 2.62 2.98 2.98 2.98 2.98 2.97 3.19 3.19 3.19 3.18 3.17 COP 3.73 3.94 4.41 4.93 5.52 3.27 3.45 3.85 4.30 4.80 2.86 3.02 3.36 3.74 4.17 2.67 2.82 3.13 3.48 3.88 Heat of Abs. (MBtuH) 21.41 23.15 26.95 31.16 35.84 20.21 21.89 25.53 29.58 34.07 18.91 20.51 23.99 27.85 32.15 18.22 19.78 23.17 26.94 31.13 Units are complete packages featuring 2 stage operation and containing refrigeration compressor, reversing valve, expansion valve metering device and water to refrigerant heat exchangers. Also included are safety controls: Overload protection for compressor, high and low refrigerant pressure switches and a lock-out control circuit. FhP Manufacturing Company 601 N.W. 65th Court Fort Lauderdale, FL 33309 Phone: (954) 776-5471 Fax: (800) 776-5529 http://www.bosch-climate.us As a result of continuing research and development, specifications are subject to change without notice. TW035.2INDD Rev:03-11 WATER COOLED ChILLERS AND LOW TEMP BOILERS SPECIFICATION DATA SHEET TW SERIES FLUID FLOW & PRESSURE DROP ELECTRICAL SPECIFICATIONS Compressor TW049 Electrical Characteristics Elect. Symbol RLA LRA Min. Circuit Ampacity 208/230-1-60 -1 21.2 96 26.5 Max. Fuse Size 45 Chilled Fluid Side (@ 55OF) Flow (GPM) ∆P (FOH) 6.0 2.72 8.0 4.59 10.0 6.87 12.0 9.56 16.0 16.09 Cond. Fluid Side (@ 85OF) Flow (GPM) ∆P (FOH) 6.0 2.46 8.0 4.15 10.0 6.22 12.0 8.65 16.0 14.56 ChILLER PERFORMANCE - PART LOAD hEATING PERFORMANCE Based on 8.1 GPM chilled fluid & 10OF condenser fluid temp. rise. Based on 10OF load temp. rise & 8.1 GPM source fluid flow. Leaving Entering Total Load Source Capacity Fluid (˚F) Fluid (˚F) (Tons) 2.36 75o 2.30 80o 2.24 40o 85o 2.18 90o 2.12 95o 2.44 75o 2.38 80o 2.32 42o 85o 2.26 90o 2.19 95o 2.52 75o 2.46 80o 2.40 44o 85o 2.34 90o 2.27 95o 2.56 75o 2.50 80o 2.44 45o 85o 2.38 90o 2.31 95o 2.60 75o 2.54 80o 2.49 46o 85o 2.42 90o 2.35 95o 2.69 75o 2.63 80o 2.57 48o 85o 2.50 90o 2.42 95o 2.78 75o 2.72 80o 2.65 50o 85o 2.58 90o 2.51 95o Total Capacity (MBtuH) 28.26 27.63 26.93 26.19 25.38 29.24 28.58 27.87 27.10 26.28 30.23 29.55 28.82 28.04 27.20 30.74 30.05 29.31 28.52 27.66 31.25 30.54 29.82 29.02 28.16 32.31 31.59 30.81 29.98 29.10 33.39 32.64 31.84 30.99 30.09 Power Input (kW) 1.75 1.88 2.01 2.15 2.30 1.75 1.87 2.00 2.14 2.30 1.74 1.86 1.99 2.14 2.29 1.73 1.86 1.99 2.13 2.28 1.73 1.85 1.99 2.22 2.28 1.72 1.84 1.98 2.12 2.27 1.71 1.83 1.97 2.11 2.26 EER 16.12 14.72 13.41 12.17 11.02 16.75 15.29 13.92 12.64 11.44 17.40 15.88 14.46 13.13 11.88 17.74 16.18 14.73 13.38 12.11 18.10 16.50 15.00 13.60 12.30 18.79 17.14 15.59 14.16 12.81 19.53 17.81 16.20 14.70 13.31 Heat Rejection (MBtuH) 34.25 34.03 33.79 33.53 33.25 35.19 34.96 34.70 34.42 34.12 36.16 35.91 35.63 35.33 35.01 36.66 36.39 36.10 35.79 35.46 37.15 36.86 36.60 36.27 35.94 38.18 37.87 37.55 37.21 36.85 39.22 38.90 38.55 38.18 37.80 Leaving Entering Load Source Fluid (˚F) Fluid (˚F) 35o 40o o 100 50o 60o 70o 35o 40o o 110 50o 60o 70o 35o 40o o 120 50o 60o 70o 35o 40o o 125 50o 60o 70o Total Capacity (MBtuH) 29.32 31.16 35.12 39.50 44.33 28.99 30.77 34.60 38.82 43.46 28.58 30.31 34.02 38.07 42.52 28.35 30.06 33.70 37.68 42.03 Power Input (kW) 2.28 2.26 2.20 2.13 2.03 2.62 2.59 2.53 2.45 2.35 3.01 2.98 2.92 2.83 2.72 3.23 3.20 3.13 3.04 2.93 COP 3.76 4.04 4.67 5.44 6.39 3.24 3.48 4.00 4.64 5.41 2.78 2.98 3.42 3.94 4.57 2.57 2.75 3.16 3.63 4.20 Heat of Abs. (MBtuH) 21.53 23.45 27.61 32.24 37.39 20.05 21.92 25.96 30.45 35.42 18.30 20.13 24.07 28.42 33.23 17.33 19.14 23.02 27.31 32.03 Units are complete packages featuring 2 stage operation and containing refrigeration compressor, reversing valve, expansion valve metering device and water to refrigerant heat exchangers. Also included are safety controls: Overload protection for compressor, high and low refrigerant pressure switches and a lock-out control circuit. FhP Manufacturing Company 601 N.W. 65th Court Fort Lauderdale, FL 33309 Phone: (954) 776-5471 Fax: (800) 776-5529 http://www.bosch-climate.us As a result of continuing research and development, specifications are subject to change without notice. TW049.1INDD Rev:03-11 WATER COOLED ChILLERS AND LOW TEMP BOILERS SPECIFICATION DATA SHEET TW SERIES FLUID FLOW & PRESSURE DROP ELECTRICAL SPECIFICATIONS Compressor TW049 Electrical Characteristics Elect. Symbol RLA LRA Min. Circuit Ampacity 208/230-1-60 -1 21.2 96 26.5 Max. Fuse Size 45 Chilled Fluid Side (@ 55OF) Flow (GPM) ∆P (FOH) 6.0 2.70 8.0 4.56 10.0 6.84 12.0 9.53 16.0 16.05 Cond. Fluid Side (@ 85OF) Flow (GPM) ∆P (FOH) 6.0 2.44 8.0 4.12 10.0 6.19 12.0 8.62 16.0 14.52 ChILLER PERFORMANCE - FULL LOAD hEATING PERFORMANCE Based on 8.1 GPM chilled fluid & 10OF condenser fluid temp. rise. Based on 10OF load temp. rise & 8.1 GPM source fluid flow. Leaving Entering Total Load Source Capacity Fluid (˚F) Fluid (˚F) (Tons) 3.28 75o 3.20 80o 3.11 40o 85o 3.03 90o 2.93 95o 3.40 75o 3.31 80o 3.22 42o 85o 3.13 90o 3.04 95o 3.52 75o 3.43 80o 3.33 44o 85o 3.24 90o 3.14 95o 3.58 75o 3.48 80o 3.39 45o 85o 3.29 90o 3.20 95o 3.64 75o 3.54 80o 3.45 46o 85o 3.35 90o 3.25 95o 3.76 75o 3.66 80o 3.57 48o 85o 3.46 90o 3.36 95o 3.89 75o 3.79 80o 3.69 50o 85o 3.58 90o 3.47 95o Total Capacity (MBtuH) 39.42 38.41 37.38 36.31 35.21 40.79 39.75 38.68 37.58 36.44 42.20 41.12 40.02 38.88 37.70 42.91 41.82 40.70 39.54 38.34 43.66 42.53 41.38 40.19 38.98 45.12 43.97 42.79 41.58 40.32 46.65 45.46 44.24 42.98 41.68 Power Input (kW) 2.59 2.73 2.88 3.04 3.22 2.60 2.75 2.90 3.06 3.23 2.62 2.76 2.91 3.07 3.25 2.62 2.76 2.91 3.08 3.25 2.63 2.77 2.92 3.08 3.26 2.64 2.78 2.93 3.10 3.27 2.65 2.79 2.95 3.11 3.28 EER 15.21 14.05 12.96 11.93 10.94 15.66 14.48 13.36 12.29 11.27 16.13 14.91 13.76 12.66 11.62 16.36 15.13 13.96 12.85 11.79 16.60 15.40 14.20 13.00 12.00 17.09 15.80 14.59 13.43 12.33 17.58 16.27 15.02 13.83 12.69 Heat Rejection (MBtuH) 48.26 47.74 47.22 46.70 46.20 49.68 49.12 48.56 48.01 47.47 51.12 50.53 49.94 49.35 48.77 51.86 51.25 50.64 50.04 49.44 52.63 51.98 51.34 50.71 50.09 54.13 53.47 52.80 52.14 51.48 55.70 54.99 54.29 53.58 52.88 Leaving Entering Load Source Fluid (˚F) Fluid (˚F) 35o 40o o 100 50o 60o 70o 35o 40o o 110 50o 60o 70o 35o 40o o 120 50o 60o 70o 35o 40o o 125 50o 60o 70o Total Capacity (MBtuH) 39.70 42.27 47.85 54.08 60.97 39.28 41.73 47.05 53.00 59.60 38.93 41.24 46.29 51.94 58.22 38.78 41.03 45.93 51.42 57.53 Power Input (kW) 3.01 3.02 3.03 3.04 3.04 3.38 3.39 3.40 3.41 3.40 3.82 3.83 3.84 3.85 3.84 4.08 4.08 4.10 4.10 4.09 COP 3.87 4.10 4.62 5.21 5.88 3.41 3.61 4.05 4.56 5.13 2.98 3.15 3.53 3.96 4.45 2.79 2.94 3.29 3.68 4.13 Heat of Abs. (MBtuH) 29.43 31.97 37.50 43.70 50.60 27.74 30.16 35.44 41.37 47.98 25.88 28.17 33.18 38.81 45.12 24.87 27.09 31.96 37.44 43.59 Units are complete packages featuring 2 stage operation and containing refrigeration compressor, reversing valve, expansion valve metering device and water to refrigerant heat exchangers. Also included are safety controls: Overload protection for compressor, high and low refrigerant pressure switches and a lock-out control circuit. FhP Manufacturing Company 601 N.W. 65th Court Fort Lauderdale, FL 33309 Phone: (954) 776-5471 Fax: (800) 776-5529 http://www.bosch-climate.us As a result of continuing research and development, specifications are subject to change without notice. TW049.2INDD Rev:03-11 WATER COOLED ChILLERS AND LOW TEMP BOILERS SPECIFICATION DATA SHEET TW SERIES FLUID FLOW & PRESSURE DROP ELECTRICAL SPECIFICATIONS Compressor TW061 Electrical Characteristics Elect. Symbol RLA LRA Min. Circuit Ampacity 208/230-1-60 -1 25.6 118 32.2 Max. Fuse Size 50 Chilled Fluid Side (@ 55OF) Flow (GPM) ∆P (FOH) 7.5 4.44 10.0 7.50 12.5 11.24 15.0 15.64 20.0 26.32 Cond. Fluid Side (@ 85OF) Flow (GPM) ∆P (FOH) 7.5 4.02 10.0 6.79 12.5 10.17 15.0 14.16 20.0 23.83 ChILLER PERFORMANCE - PART LOAD hEATING PERFORMANCE Based on 10.5 GPM chilled fluid & 10OF condenser fluid temp. rise. Based on 10OF load temp. rise & 10.5 GPM source fluid flow. Leaving Entering Total Load Source Capacity Fluid (˚F) Fluid (˚F) (Tons) 2.99 75o 2.90 80o 2.80 40o 85o 2.70 90o 2.60 95o 3.11 75o 3.02 80o 2.92 42o 85o 2.82 90o 2.71 95o 3.24 75o 3.14 80o 3.04 44o 85o 2.94 90o 2.83 95o 3.30 75o 3.20 80o 3.10 45o 85o 3.00 90o 2.89 95o 3.37 75o 3.27 80o 3.16 46o 85o 3.06 90o 2.94 95o 3.50 75o 3.40 80o 3.29 48o 85o 3.18 90o 3.07 95o 3.64 75o 3.53 80o 3.42 50o 85o 3.31 90o 3.19 95o Total Capacity (MBtuH) 35.88 34.78 33.64 32.44 31.18 37.35 36.22 35.05 33.83 32.54 38.85 37.70 36.50 35.25 33.93 39.63 38.45 37.23 35.97 34.64 40.41 39.23 37.96 36.70 35.33 42.00 40.77 39.50 38.19 36.81 43.64 42.37 41.06 39.71 38.30 Power Input (kW) 2.10 2.24 2.40 2.56 2.74 2.09 2.23 2.39 2.55 2.73 2.08 2.23 2.38 2.55 2.72 2.08 2.22 2.38 2.54 2.72 2.07 2.22 2.37 2.54 2.72 2.06 2.21 2.37 2.53 2.71 2.05 2.20 2.36 2.52 2.70 EER 17.11 15.51 14.03 12.66 11.39 17.88 16.21 14.67 13.24 11.92 18.68 16.93 15.32 13.84 12.46 19.09 17.30 15.66 14.14 12.74 19.50 17.70 16.00 14.50 13.00 20.37 18.45 16.70 15.09 13.60 21.26 19.25 17.42 15.74 14.19 Heat Rejection (MBtuH) 43.03 42.43 41.82 41.19 40.52 44.47 43.84 43.20 42.54 41.85 45.95 45.29 44.62 43.93 43.22 46.71 46.03 45.35 44.64 43.91 47.47 46.80 46.06 45.37 44.60 49.03 48.31 47.57 46.82 46.05 50.64 49.88 49.10 48.32 47.51 Leaving Entering Load Source Fluid (˚F) Fluid (˚F) 35o 40o o 100 50o 60o 70o 35o 40o o 110 50o 60o 70o 35o 40o o 120 50o 60o 70o 35o 40o o 125 50o 60o 70o Total Capacity (MBtuH) 34.79 37.59 43.63 50.31 57.70 33.74 36.49 42.38 48.85 55.96 32.47 35.19 40.96 47.24 54.08 31.74 34.45 40.17 46.36 53.08 Power Input (kW) 2.74 2.70 2.63 2.56 2.48 3.13 3.10 3.02 2.94 2.85 3.60 3.56 3.47 3.37 3.28 3.87 3.82 3.72 3.62 3.52 COP 3.73 4.07 4.85 5.76 6.82 3.15 3.45 4.11 4.87 5.75 2.64 2.90 3.46 4.10 4.83 2.41 2.64 3.17 3.75 4.42 Heat of Abs. (MBtuH) 25.46 28.37 34.64 41.58 49.24 23.04 25.92 32.08 38.83 46.22 20.18 23.05 29.13 35.72 42.88 18.55 21.42 27.48 34.01 41.07 Units are complete packages featuring 2 stage operation and containing refrigeration compressor, reversing valve, expansion valve metering device and water to refrigerant heat exchangers. Also included are safety controls: Overload protection for compressor, high and low refrigerant pressure switches and a lock-out control circuit. FhP Manufacturing Company 601 N.W. 65th Court Fort Lauderdale, FL 33309 Phone: (954) 776-5471 Fax: (800) 776-5529 http://www.bosch-climate.us As a result of continuing research and development, specifications are subject to change without notice. TW061.1INDD Rev:03-11 WATER COOLED ChILLERS AND LOW TEMP BOILERS SPECIFICATION DATA SHEET TW SERIES FLUID FLOW & PRESSURE DROP ELECTRICAL SPECIFICATIONS Compressor TW061 Electrical Characteristics Elect. Symbol RLA LRA Min. Circuit Ampacity 208/230-1-60 -1 25.6 118 32.2 Max. Fuse Size 50 Chilled Fluid Side (@ 55OF) Flow (GPM) ∆P (FOH) 7.5 4.42 10.0 7.46 12.5 11.20 15.0 15.59 20.0 26.26 Cond. Fluid Side (@ 85OF) Flow (GPM) ∆P (FOH) 7.5 3.99 10.0 6.74 12.5 10.13 15.0 14.10 20.0 23.76 ChILLER PERFORMANCE - FULL LOAD hEATING PERFORMANCE Based on 10.5 GPM chilled fluid & 10OF condenser fluid temp. rise. Based on 10OF load temp. rise & 10.5 GPM source fluid flow. Leaving Entering Total Load Source Capacity Fluid (˚F) Fluid (˚F) (Tons) 4.06 75o 3.95 80o 3.85 40o 85o 3.74 90o 3.62 95o 4.20 75o 4.10 80o 3.99 42o 85o 3.87 90o 3.75 95o 4.35 75o 4.24 80o 4.13 44o 85o 4.01 90o 3.89 95o 4.43 75o 4.32 80o 4.20 45o 85o 4.08 90o 3.96 95o 4.51 75o 4.41 80o 4.28 46o 85o 4.15 90o 4.02 95o 4.66 75o 4.55 80o 4.42 48o 85o 4.30 90o 4.17 95o 4.82 75o 4.70 80o 4.58 50o 85o 4.44 90o 4.31 95o Total Capacity (MBtuH) 48.67 47.43 46.15 44.82 43.44 50.43 49.16 47.83 46.45 45.02 52.24 50.92 49.54 48.12 46.64 53.16 51.81 50.41 48.97 47.46 54.08 52.91 51.32 49.83 48.30 55.97 54.55 53.08 51.56 49.99 57.89 56.42 54.90 53.34 51.71 Power Input (kW) 3.34 3.54 3.75 3.98 4.22 3.35 3.55 3.76 3.99 4.23 3.37 3.56 3.77 4.00 4.24 3.37 3.57 3.78 4.00 4.25 3.38 3.58 3.78 4.01 4.25 3.39 3.59 3.80 4.02 4.27 3.41 3.60 3.81 4.03 4.28 EER 14.56 13.40 12.31 11.27 10.29 15.04 13.85 12.72 11.65 10.64 15.52 14.30 13.13 12.03 10.99 15.76 14.52 13.35 12.23 11.17 16.00 14.80 13.60 12.40 11.40 16.50 15.21 13.98 12.82 11.72 17.00 15.68 14.42 13.22 12.09 Heat Rejection (MBtuH) 60.07 59.51 58.95 58.39 57.84 61.88 61.27 60.66 60.06 59.46 63.73 63.07 62.41 61.76 61.12 64.66 63.98 63.30 62.63 61.96 65.61 65.11 64.23 63.51 62.81 67.54 66.78 66.03 65.28 64.54 69.50 68.70 67.90 67.10 66.31 Leaving Entering Load Source Fluid (˚F) Fluid (˚F) 35o 40o o 100 50o 60o 70o 35o 40o o 110 50o 60o 70o 35o 40o o 120 50o 60o 70o 35o 40o o 125 50o 60o 70o Total Capacity (MBtuH) 49.67 52.97 60.12 68.00 76.59 49.31 52.46 59.27 66.79 75.00 49.00 51.98 58.46 65.60 73.42 48.86 51.76 58.06 65.02 72.64 Power Input (kW) 3.99 3.99 3.97 3.96 3.96 4.51 4.51 4.49 4.47 4.46 5.11 5.11 5.09 5.06 5.04 5.44 5.44 5.42 5.40 5.37 COP 3.65 3.90 4.43 5.03 5.67 3.20 3.41 3.87 4.38 4.93 2.81 2.98 3.37 3.80 4.27 2.63 2.79 3.14 3.53 3.97 Heat of Abs. (MBtuH) 36.06 39.37 46.56 54.47 63.08 33.93 37.08 43.95 51.53 59.79 31.56 34.56 41.10 48.32 56.22 30.29 33.21 39.57 46.61 54.32 Units are complete packages featuring 2 stage operation and containing refrigeration compressor, reversing valve, expansion valve metering device and water to refrigerant heat exchangers. Also included are safety controls: Overload protection for compressor, high and low refrigerant pressure switches and a lock-out control circuit. FhP Manufacturing Company 601 N.W. 65th Court Fort Lauderdale, FL 33309 Phone: (954) 776-5471 Fax: (800) 776-5529 http://www.bosch-climate.us As a result of continuing research and development, specifications are subject to change without notice. TW061.2INDD Rev:03-11 WATER COOLED ChILLERS AND LOW TEMP BOILERS SPECIFICATION DATA SHEET TW SERIES FLUID FLOW & PRESSURE DROP ELECTRICAL SPECIFICATIONS Compressor TW071 Electrical Characteristics Elect. Symbol RLA LRA Min. Circuit Ampacity 208/230-1-60 -1 27.2 150 34.0 Max. Fuse Size 60 Chilled Fluid Side (@ 55OF) Flow (GPM) ∆P (FOH) 9.0 4.05 12.0 6.83 15.0 10.24 18.0 14.25 24.0 23.97 Cond. Fluid Side (@ 85OF) Flow (GPM) ∆P (FOH) 9.0 3.66 12.0 6.18 15.0 9.27 18.0 12.89 24.0 21.70 ChILLER PERFORMANCE - PART LOAD hEATING PERFORMANCE Based on 11.0 GPM chilled fluid & 10OF condenser fluid temp. rise. Based on 10OF load temp. rise & 11.0 GPM source fluid flow. Leaving Entering Total Load Source Capacity Fluid (˚F) Fluid (˚F) (Tons) 3.60 75o 3.52 80o 3.42 40o 85o 3.33 90o 3.23 95o 3.74 75o 3.65 80o 3.56 42o 85o 3.46 90o 3.36 95o 3.89 75o 3.79 80o 3.69 44o 85o 3.59 90o 3.49 95o 3.96 75o 3.86 80o 3.76 45o 85o 3.66 90o 3.56 95o 4.03 75o 3.94 80o 3.84 46o 85o 3.73 90o 3.63 95o 4.19 75o 4.09 80o 3.98 48o 85o 3.87 90o 3.76 95o 4.35 75o 4.24 80o 4.13 50o 85o 4.02 90o 3.90 95o Total Capacity (MBtuH) 43.25 42.19 41.09 39.96 38.79 44.92 43.82 42.69 41.51 40.31 46.65 45.51 44.33 43.12 41.87 47.53 46.37 45.17 43.94 42.67 48.41 47.23 46.02 44.78 43.51 50.26 49.04 47.77 46.48 45.14 52.15 50.88 49.57 48.23 46.85 Power Input (kW) 2.70 2.89 3.10 3.32 3.55 2.68 2.87 3.08 3.29 3.52 2.66 2.85 3.06 3.27 3.50 2.65 2.84 3.05 3.26 3.49 2.64 2.84 3.04 3.25 3.48 2.63 2.82 3.02 3.23 3.45 2.61 2.80 3.00 3.21 3.43 EER 16.04 14.59 13.26 12.05 10.93 16.77 15.25 13.87 12.60 11.44 17.53 15.95 14.50 13.18 11.96 17.92 16.30 14.83 13.48 12.23 18.30 16.70 15.20 13.80 12.50 19.13 17.41 15.84 14.40 13.07 19.97 18.17 16.54 15.04 13.66 Heat Rejection (MBtuH) 52.45 52.05 51.66 51.27 50.90 54.06 53.62 53.18 52.75 52.33 55.73 55.25 54.76 54.28 53.81 56.58 56.08 55.57 55.06 54.57 57.43 56.91 56.38 55.87 55.37 59.23 58.65 58.07 57.49 56.92 61.06 60.43 59.80 59.17 58.55 Leaving Entering Load Source Fluid (˚F) Fluid (˚F) 35o 40o o 100 50o 60o 70o 35o 40o o 110 50o 60o 70o 35o 40o o 120 50o 60o 70o 35o 40o o 125 50o 60o 70o Total Capacity (MBtuH) 44.44 47.30 53.68 61.01 69.37 44.34 47.03 53.05 59.99 67.93 44.37 46.88 52.52 59.05 66.54 44.44 46.87 52.31 58.62 65.89 Power Input (kW) 3.58 3.50 3.35 3.20 3.06 4.10 4.01 3.84 3.67 3.50 4.70 4.60 4.40 4.20 4.01 5.04 4.93 4.72 4.51 4.30 COP 3.64 3.96 4.69 5.58 6.64 3.17 3.44 4.05 4.79 5.68 2.77 2.99 3.50 4.12 4.86 2.59 2.79 3.25 3.81 4.49 Heat of Abs. (MBtuH) 32.24 35.35 42.24 50.08 58.92 30.36 33.35 39.95 47.48 55.98 28.33 31.18 37.50 44.70 52.86 27.26 30.04 36.21 43.25 51.22 Units are complete packages featuring 2 stage operation and containing refrigeration compressor, reversing valve, expansion valve metering device and water to refrigerant heat exchangers. Also included are safety controls: Overload protection for compressor, high and low refrigerant pressure switches and a lock-out control circuit. FhP Manufacturing Company 601 N.W. 65th Court Fort Lauderdale, FL 33309 Phone: (954) 776-5471 Fax: (800) 776-5529 http://www.bosch-climate.us As a result of continuing research and development, specifications are subject to change without notice. TW071.1INDD Rev:03-11 WATER COOLED ChILLERS AND LOW TEMP BOILERS SPECIFICATION DATA SHEET TW SERIES FLUID FLOW & PRESSURE DROP ELECTRICAL SPECIFICATIONS Compressor TW071 Electrical Characteristics Elect. Symbol RLA LRA Min. Circuit Ampacity 208/230-1-60 -1 27.2 150 34.0 Max. Fuse Size 60 Chilled Fluid Side (@ 55OF) Flow (GPM) ∆P (FOH) 9.0 4.03 12.0 6.80 15.0 10.21 18.0 14.21 24.0 23.93 Cond. Fluid Side (@ 85OF) Flow (GPM) ∆P (FOH) 9.0 3.64 12.0 6.15 15.0 9.23 18.0 12.85 24.0 21.65 ChILLER PERFORMANCE - FULL LOAD hEATING PERFORMANCE Based on 11.0 GPM chilled fluid & 10OF condenser fluid temp. rise. Based on 10OF load temp. rise & 11.0 GPM source fluid flow. Leaving Entering Total Load Source Capacity Fluid (˚F) Fluid (˚F) (Tons) 4.71 75o 4.60 80o 4.47 40o 85o 4.34 90o 4.21 95o 4.88 75o 4.75 80o 4.63 42o 85o 4.49 90o 4.36 95o 5.04 75o 4.91 80o 4.78 44o 85o 4.65 90o 4.50 95o 5.13 75o 5.00 80o 4.86 45o 85o 4.72 90o 4.58 95o 5.21 75o 5.08 80o 4.94 46o 85o 4.80 90o 4.65 95o 5.39 75o 5.25 80o 5.11 48o 85o 4.96 90o 4.81 95o 5.57 75o 5.42 80o 5.28 50o 85o 5.13 90o 4.97 95o Total Capacity (MBtuH) 56.58 55.15 53.67 52.13 50.54 58.51 57.03 55.50 53.91 52.27 60.50 58.97 57.39 55.74 54.04 61.51 59.96 58.35 56.68 54.95 62.56 60.96 59.31 57.61 55.86 64.63 63.00 61.30 59.55 57.74 66.78 65.09 63.34 61.53 59.67 Power Input (kW) 3.99 4.21 4.43 4.66 4.90 4.01 4.23 4.45 4.68 4.93 4.03 4.25 4.47 4.70 4.95 4.04 4.26 4.48 4.71 4.96 4.05 4.27 4.49 4.72 4.97 4.07 4.29 4.51 4.75 4.99 4.09 4.31 4.53 4.77 5.02 EER 14.17 13.11 12.12 11.19 10.31 14.58 13.50 12.48 11.52 10.61 15.01 13.89 12.84 11.85 10.92 15.22 14.09 13.03 12.02 11.08 15.40 14.30 13.20 12.20 11.20 15.88 14.70 13.59 12.55 11.56 16.32 15.11 13.97 12.90 11.89 Heat Rejection (MBtuH) 70.20 69.50 68.78 68.03 67.27 72.20 71.45 70.68 69.88 69.07 74.25 73.45 72.63 71.79 70.93 75.30 74.48 73.63 72.76 71.87 76.38 75.51 74.62 73.72 72.82 78.52 77.62 76.69 75.75 74.78 80.74 79.79 78.81 77.81 76.79 Leaving Entering Load Source Fluid (˚F) Fluid (˚F) 35o 40o o 100 50o 60o 70o 35o 40o o 110 50o 60o 70o 35o 40o o 120 50o 60o 70o 35o 40o o 125 50o 60o 70o Total Capacity (MBtuH) 58.07 61.72 69.65 78.51 88.36 57.29 60.80 68.42 76.93 86.40 56.46 59.82 67.13 75.28 84.36 56.03 59.32 66.46 74.44 83.31 Power Input (kW) 4.58 4.60 4.64 4.66 4.69 5.08 5.11 5.15 5.18 5.21 5.64 5.67 5.72 5.76 5.80 5.95 5.98 6.04 6.08 6.12 COP 3.72 3.93 4.40 4.93 5.52 3.30 3.49 3.89 4.35 4.86 2.93 3.09 3.44 3.83 4.26 2.76 2.91 3.23 3.59 3.99 Heat of Abs. (MBtuH) 42.44 46.02 53.83 62.60 72.36 39.95 43.37 50.85 59.25 68.61 37.21 40.47 47.60 55.61 64.57 35.74 38.91 45.87 53.68 62.43 Units are complete packages featuring 2 stage operation and containing refrigeration compressor, reversing valve, expansion valve metering device and water to refrigerant heat exchangers. Also included are safety controls: Overload protection for compressor, high and low refrigerant pressure switches and a lock-out control circuit. FhP Manufacturing Company 601 N.W. 65th Court Fort Lauderdale, FL 33309 Phone: (954) 776-5471 Fax: (800) 776-5529 http://www.bosch-climate.us As a result of continuing research and development, specifications are subject to change without notice. TW071.2INDD Rev:03-11