LAVC Standards CAMPUS STANDARDS- MATRIX (Note: Campus Preferences are indicated first, followed by additional manufacturers in italics which are being considered by LACCD.) PLEASE READ & FOLLOW THE DIRECTIONS PROVIDED BELOW The Campus Standards Summary provided is to be used as a guide; but, LAVC has a comprehensive design standards which governs the design of any of our projects. The document referenced is “Campus Design Standards, Los Angeles Valley College, Los Angeles Community College District, June 26, 2010. The following language is included in this document, “In case there is a valid need to deviate from the standards, a written request needs to be submitted to and a formal written approval needs to be received from the Campus Maintenance & Operations (M&O) or IT Departments. Furthermore, these design standards are not to be deviated from for the purpose of value engineering unless formally approved by M&O or IT.” STANDARD CAMPUS PREFERRED AIR CONDITIONING TRANE, MCQUAY, BARD, YORK BOILER PARKER, LOCHINVAR BATHROOM ACCESSORIES TOILET BOWL URINAL American Standard KOHLER (KINGSTON BOWL K-4330) KOHLER K-4960-ET (AMERICAN STAND.) BIKE RACK BLEACHERS CEILING SYSTEMS WALL & CEILING ACCESS DOORS CLASSROOM TECHNOLOGIES MARKER BOARDS TACK BOARD SQUARE OR RECTANGULAR FRAMES WITH HINGED LOCKED DOOR TRI BEST VISUAL DISPLAY (800-281-3411), A SERIES NELSON ADAMS/GSI DURACITE 1064M CLARIDGE PRODUCTS VINYL COVERED CORK OVER HARD BOARD 1 of 14 LAVC Standards CAMPUS STANDARDS- MATRIX (Note: Campus Preferences are indicated first, followed by additional manufacturers in italics which are being considered by LACCD.) PLEASE READ & FOLLOW THE DIRECTIONS PROVIDED BELOW The Campus Standards Summary provided is to be used as a guide; but, LAVC has a comprehensive design standards which governs the design of any of our projects. The document referenced is “Campus Design Standards, Los Angeles Valley College, Los Angeles Community College District, June 26, 2010. The following language is included in this document, “In case there is a valid need to deviate from the standards, a written request needs to be submitted to and a formal written approval needs to be received from the Campus Maintenance & Operations (M&O) or IT Departments. Furthermore, these design standards are not to be deviated from for the purpose of value engineering unless formally approved by M&O or IT.” STANDARD ELECTRICAL EQUIPMENT PANELS BREAKERS SWITCHES RECEPTACLES PLATES PARKING CONTROL EQUIPMENT OUTLET BOXES & FITTINGS SCREW COVER ENCLOSURES & PULL BOXES UNDERGROUND CONCRETE PULL BOXES FLOOR OUTLETS TELEPHONES ABOVE FLOOR OUTLETS PLUGS ABOVE FLOOR OUTLETS EXTENSION FLOOR OUTLETS ABOVE FLOOR SERVICE FITTING ABOVE FLOOR SERVICE FITTINGS FOR DATA OUTLETS CAMPUS PREFERRED BOLT ON, SQUARE D, GENERAL ELECTRIC, CUTLER HAMMER SQUARE D GE, CUTLER HAMMER PASS & SEYMOUR, LEVITON, HUBBELL, BRYANT PASS & SEYMOUR, LEVITON, HUBBELL, BRYANT LIGHT PANEL/TEHCNOLOGIES LLC MODEL #P301 120, SERIAL #K0201011, ENGINEERED O-Z GEDNEY, STEEL CITY, THOMAS & BETTS HOFFMAN, COOPER B-LINE QUICKSET HARVEY HUBBELL INC. B-2503 HARVEY HUBBELL INC. SC-3098, PEDESTALS WITH SS309B PLATES HARVEY HUBBELL INC. SC-3092 HARVEY HUBBELL F3186 HUBBELL SC3098 WITH COVER PLATES SS309DS, O-Z DUPLEX RECEPTACLES WALKERBOX STEEL OMNIBOX 880 WALKERBOX, RESOURCE RFB, WITH APPLICABLE SOURCE III ACTIVATION COVER C.W. COLE TLS-353-6 FOR WOOD FLOORS, C.W. COLE TLS353-6-C FOR CONCRETE SLABS CORBIN NO. 60 KEYS FOR ACCESS TO OPERATE EQUIPMENT & CORBIN 70 KEYS FOR SERVICE ACCESS ARROW-HART 5242-I, HUBBELL 5242-I OR LEVITON 5242-I SINGLE RECEPTACLES, 15AMPS, 125 VOLTS NEMA 5-15R, ARROW-HART 5351-I FLOOR OUTLETS MULTI SERVICE FLOOR OUTLETS FLOOR POCKETS KEYS & LOCKS 2 of 14 LAVC Standards CAMPUS STANDARDS- MATRIX (Note: Campus Preferences are indicated first, followed by additional manufacturers in italics which are being considered by LACCD.) PLEASE READ & FOLLOW THE DIRECTIONS PROVIDED BELOW The Campus Standards Summary provided is to be used as a guide; but, LAVC has a comprehensive design standards which governs the design of any of our projects. The document referenced is “Campus Design Standards, Los Angeles Valley College, Los Angeles Community College District, June 26, 2010. The following language is included in this document, “In case there is a valid need to deviate from the standards, a written request needs to be submitted to and a formal written approval needs to be received from the Campus Maintenance & Operations (M&O) or IT Departments. Furthermore, these design standards are not to be deviated from for the purpose of value engineering unless formally approved by M&O or IT.” STANDARD CAMPUS PREFERRED GROUND FAULT INTERRUPTER TYPE RECEPTACLES SURGE-SUPPRESSION RECEPTACLES FOR COMPUTERS & DATA EQUIPMENT RECEPTACLES FOR CASH REGISTERS & OTHER ELECTRONIC EQUIPMENT WEATHERPROOF RECEPTACLES TAMPER-RESISTANT RECEPTACLES LOCK TYPE SWITCHES NEMA 5-15R, HUBBELL GF52621 & HUBBELL S26 PLATE ROTARY LOCK SWITCHES PILOT LIGHT SWITCHES REMOTE CONTROL SWITCHES 7 DAY SOLID STATE ELECRONIC TYPE TIME SWITCHES ARROW-HART 1191 SINGLE POLE HUBBELL HBL 1221-PL, HUBBELL HBL 1221-PL7 HUBBELL HBL 1556-I EZ CONTROLS MODEL EZ-701-1, EZ-701-2 LOCAL SWITCHES, SINGLE POLE, DOUBLE POLE, 3-WAY & 4-WAY TIMERS & PHOTOCONTROL HUBBELL HBL 1221-I SINGLE POLE, HBL 1222-I, DOUBLE POLE, HBL 1223-I 3-WAY, & HBL 1224-I 4-WAY EZ CONTROL MODEL EZ-701-1 & 2/ TORK LOCK TYPE SWITCHES HUBBELL HBL 1221-L SINGLE POLE, HBL 1222-L DOUBLE POLE, HBL 1223-L 3-WAY, & HBL 1224-L 4-WAY. KEYS FOR LOCK TYPE SWITCHES; HUBBELL NO. HBL 1209 ARROW-HART 1191 SINGLE POLE,CAT. ARROW-HART 1192 DOUBLE POLE, ARROW-HART 1193 3-WAY. LOCK SHALL BE TUMBLER TYPE120 BY VOLT CORBIN, KEYED TO A HH41 HBL KEY.1221SINGLE POLE, SWITCHES; HUBBELL PL. SINGLE POLE 277 VOLT SWITCHES SHALL BE HUBBELL HBL 1221-PL7 HUBBELL HBL 1556-I ROTARY LOCK SWITCHES PILOT LIGHT SWITCHES REMOTE CONTROL SWITCHES HUBBELL #5262S HUBBELL #IG5262GY ARROW-HART 5252-WP HUBBELL HBLSG62HI, NEMA 5-15R HUBBELL HBL1221-L SINGLE POLE, HBL 1222-L DOUBLE POLE 3 of 14 LAVC Standards CAMPUS STANDARDS- MATRIX (Note: Campus Preferences are indicated first, followed by additional manufacturers in italics which are being considered by LACCD.) PLEASE READ & FOLLOW THE DIRECTIONS PROVIDED BELOW The Campus Standards Summary provided is to be used as a guide; but, LAVC has a comprehensive design standards which governs the design of any of our projects. The document referenced is “Campus Design Standards, Los Angeles Valley College, Los Angeles Community College District, June 26, 2010. The following language is included in this document, “In case there is a valid need to deviate from the standards, a written request needs to be submitted to and a formal written approval needs to be received from the Campus Maintenance & Operations (M&O) or IT Departments. Furthermore, these design standards are not to be deviated from for the purpose of value engineering unless formally approved by M&O or IT.” STANDARD CAMPUS PREFERRED TELEPHONE DIALERS FOR ELEVATORS VIKING ELECTRONICS INC. MODEL K-1500 YARD BOXES GROUNDING ELECTRODES GROUND CONNECTOR CHEMICAL GROUND SYSTEM GROUND BOX/INSPECTION WELL LOW-VOLTAGE WIRE HEAT SHRINK WIRE WRAP-AROUND TAPE MARKERS MEDIUM-VOLTAGE CABLES BROOKS 36 BLACKBURN COPPER BONDED STEEL GROUND ROD 7510 BURNDY TYPE GRC34 OR TYPE GAR SUPERIOR GROUNDING SYSTEM INC., IRWINDALE & CA (TEL: 800-747-7925 MODEL NO. GS-10K2V150CS, OR L SHAPED FOR HORIZONTAL INSTALLATION MODEL NO. GS-10K2L360CS MODEL GS-CBX-12 SOUTHWIRE, GENERAL CABLE ESSEX RAYCHEM SHRINKMARK, BRADY PERMA SLEEVE RAYCHEM CABLE MARKERS, BRADY PERMA-CODE GE POWER CABLE, VULKENE, OR OKONITE MEDIUM-VOLTAGE SPLICES & TERMINATION 3M CABLE ACCESSORY PRODUCTS GROUND ROD 4 of 14 LAVC Standards CAMPUS STANDARDS- MATRIX (Note: Campus Preferences are indicated first, followed by additional manufacturers in italics which are being considered by LACCD.) PLEASE READ & FOLLOW THE DIRECTIONS PROVIDED BELOW The Campus Standards Summary provided is to be used as a guide; but, LAVC has a comprehensive design standards which governs the design of any of our projects. The document referenced is “Campus Design Standards, Los Angeles Valley College, Los Angeles Community College District, June 26, 2010. The following language is included in this document, “In case there is a valid need to deviate from the standards, a written request needs to be submitted to and a formal written approval needs to be received from the Campus Maintenance & Operations (M&O) or IT Departments. Furthermore, these design standards are not to be deviated from for the purpose of value engineering unless formally approved by M&O or IT.” STANDARD ELECTRICAL FIXTURES LAMPS FIXTURES CAMPUS PREFERRED PHILIPS, F32T8/ADV850/ALTO TO MATCH EXISTING FIXTURES INSTALLED BY VIRON DURING CAMPUS WIDE LIGHTING UP GRADE OUTLET BOXES & FITTING O-Z GEDNEY, STEEL CITY, THOMAS & BETTS SCREW COVER ENCLOSURES & PULL BOXES HOFFMAN, COOPER B-LINE UNDERGROUND CONCRETE PULL BOXES QUICKSET FLOOR OUTLETS HARVEY HUBBELL INC. B-2503 TELEPHONES ABOVE FLOOR OUTLETS HARVEY HUBBELL INC. SC-3098 PLUGS ABOVE FLOOR OUTLETS HARVEY HUBBELL INC. SC-3092 5 of 14 LAVC Standards CAMPUS STANDARDS- MATRIX (Note: Campus Preferences are indicated first, followed by additional manufacturers in italics which are being considered by LACCD.) PLEASE READ & FOLLOW THE DIRECTIONS PROVIDED BELOW The Campus Standards Summary provided is to be used as a guide; but, LAVC has a comprehensive design standards which governs the design of any of our projects. The document referenced is “Campus Design Standards, Los Angeles Valley College, Los Angeles Community College District, June 26, 2010. The following language is included in this document, “In case there is a valid need to deviate from the standards, a written request needs to be submitted to and a formal written approval needs to be received from the Campus Maintenance & Operations (M&O) or IT Departments. Furthermore, these design standards are not to be deviated from for the purpose of value engineering unless formally approved by M&O or IT.” STANDARD CAMPUS PREFERRED ELECTRICAL VEHICLES AND CHARGERS ELEVATORS HYDRAULIC ELEVATORS THYSEEN KRUPP EMERGENCY EYEWASH & SHOWER EMERGENCY MANAGEMENT SYSTEM 6 of 14 LAVC Standards CAMPUS STANDARDS- MATRIX (Note: Campus Preferences are indicated first, followed by additional manufacturers in italics which are being considered by LACCD.) PLEASE READ & FOLLOW THE DIRECTIONS PROVIDED BELOW The Campus Standards Summary provided is to be used as a guide; but, LAVC has a comprehensive design standards which governs the design of any of our projects. The document referenced is “Campus Design Standards, Los Angeles Valley College, Los Angeles Community College District, June 26, 2010. The following language is included in this document, “In case there is a valid need to deviate from the standards, a written request needs to be submitted to and a formal written approval needs to be received from the Campus Maintenance & Operations (M&O) or IT Departments. Furthermore, these design standards are not to be deviated from for the purpose of value engineering unless formally approved by M&O or IT.” STANDARD CAMPUS PREFERRED EMERGENCY POWER SYSTEM FINISHES EXTERIOR PLASTER EXTERIOR PLASTER FIELD TILE DALTILE DIAMANTE 12"X12" COLOR: TBD GROUT MAPEI GRID ACOUSTIC TILE RESILIENT WALL CARPET PAINT PRODUCTS LA HABRA (818-504-9180) HIGHLAND (818-785-3131) FIELD TILE AND BASE DALTILE SEMI-GLOSS 4" X 4" , ACCENT TILE, DALTILE SEMI-GLOSS 4"X4" GROUT MAPEI, PAINT DUN EDWARDS ARMSTRONG PRELUDE ARMSTRONG 1729 FIND FISSURED (RH90, 24" X 48" X5/8" BURKE FLOORING PRODUCTS, ROPPE JOHNSON RUBER CO. TANDUS DUNN EDWARDS SPECIAL CONSTRUCTION PHOTOVOLTAICS SHELL SOLAR, UNISOLAR, ATLANTIS ENERGY, SHARP SOLAR FURNISHING BLINDS M&B FIRE PROTECTION ACCESS PANEL ANGLE VALVE VSR-F J.R. SMITH #4760, ELMDOR #DW-AKL JOSAM NIBCO #T-301, KENNEDY #98 SD, FAIRBANK #0210, POTTERROEMER #4070 7 of 14 LAVC Standards CAMPUS STANDARDS- MATRIX (Note: Campus Preferences are indicated first, followed by additional manufacturers in italics which are being considered by LACCD.) PLEASE READ & FOLLOW THE DIRECTIONS PROVIDED BELOW The Campus Standards Summary provided is to be used as a guide; but, LAVC has a comprehensive design standards which governs the design of any of our projects. The document referenced is “Campus Design Standards, Los Angeles Valley College, Los Angeles Community College District, June 26, 2010. The following language is included in this document, “In case there is a valid need to deviate from the standards, a written request needs to be submitted to and a formal written approval needs to be received from the Campus Maintenance & Operations (M&O) or IT Departments. Furthermore, these design standards are not to be deviated from for the purpose of value engineering unless formally approved by M&O or IT.” STANDARD CAMPUS PREFERRED BUTTERFLY VALVE CHECK VALVE KENNEDY VALVE OR EQUAL STOCKHAM B-319, CRANE 37, AMERICAN 31F GATE VALVES OUTSIDE SCREW AND YOKE FIRE SPRINKLER PIPES SPRINKLER STOCKHAM B-133, CRANE 459, GRINNNELL FIG. 66 STOCKHAM B-133, CRANE 459, GRINNNELL FIG. 66 SHALL MEET ASTM A795 OR A135 MODEL G AUTOMATIC SPRINKLERS SPRAY UPRIGHT, SPRAY PENDENT AND CONVENTIONAL, THE RELIABLE AUTOMATIC SPRINKLER CO. INC. 8 of 14 LAVC Standards CAMPUS STANDARDS- MATRIX (Note: Campus Preferences are indicated first, followed by additional manufacturers in italics which are being considered by LACCD.) PLEASE READ & FOLLOW THE DIRECTIONS PROVIDED BELOW The Campus Standards Summary provided is to be used as a guide; but, LAVC has a comprehensive design standards which governs the design of any of our projects. The document referenced is “Campus Design Standards, Los Angeles Valley College, Los Angeles Community College District, June 26, 2010. The following language is included in this document, “In case there is a valid need to deviate from the standards, a written request needs to be submitted to and a formal written approval needs to be received from the Campus Maintenance & Operations (M&O) or IT Departments. Furthermore, these design standards are not to be deviated from for the purpose of value engineering unless formally approved by M&O or IT.” STANDARD CAMPUS PREFERRED FIRE ALARM SYSTEM SIMPLEX/GRINNELL MODEL 4100 FLOORING ACCESS FLOORING SYSTEM RAISED FLOORING ASM MODULAR SYSTEM, 215 E. BAY ST. #205A, TecCrete Access Flooring FOOD SERVICE EQUIPMENT HARDWARE ACCESS DOORS EXTERIOR CEILING DOOR FIRE RATED AUTOMATIC INSULATED ELECTRIC OPERATION OVERHEAD COILING GRILLES FOLDING DOORS ALUMINUM-FRAMED ENTRANCES & STORE FRONT GLASS ENTRANCES & STOREFRONT ALUMINUM WINDOWS FLAGPOLES DIRECTORIES & BULLETIN BOARDS BAUCO, KARP ASSOCIATES INC. JL INDUSTRIES COOKSON COMPANY COOKSON COMPANY OVERHEAD DOOR CORPORATION COOKSON COMPANY, PACIFIC ROLLING DOORS MODERNFOLD, 1171 "1" AVENUE, NEW CASTLE, IN 47362, (TEL: 800-869-1450) UNITED STATES ALUMINIUM CORP., KAWNEER COMPANY BRITE VUE/OLD CASTLE, BLUMCRAFT, VISTAWALL, CR LAURENCE OR EQUAL WAUSAU, MODU-LINE 2250 SIGNATURE SERIES 12E, THERMAL BREAK WINDOW MORGAN-FRANCIS CO. INC. GREENSTEEL INC. IRRIGATION SYSTEMS 9 of 14 LAVC Standards CAMPUS STANDARDS- MATRIX (Note: Campus Preferences are indicated first, followed by additional manufacturers in italics which are being considered by LACCD.) PLEASE READ & FOLLOW THE DIRECTIONS PROVIDED BELOW The Campus Standards Summary provided is to be used as a guide; but, LAVC has a comprehensive design standards which governs the design of any of our projects. The document referenced is “Campus Design Standards, Los Angeles Valley College, Los Angeles Community College District, June 26, 2010. The following language is included in this document, “In case there is a valid need to deviate from the standards, a written request needs to be submitted to and a formal written approval needs to be received from the Campus Maintenance & Operations (M&O) or IT Departments. Furthermore, these design standards are not to be deviated from for the purpose of value engineering unless formally approved by M&O or IT.” STANDARD CAMPUS PREFERRED KITCHEN, APPLIANCES LIGHTING/INDOOR-OUTDOOR PHOTOTELECTRIC CONTROL OUTDOOR LIGHTING CONTROL TORK SERIES 2100 TORK SERIES DZS-200 LIGHTING SUPPLIES ELECTRONIC TYPE TIME SWITCHES EZ CONTROLS MODEL EZ-701-1, EZ-701-2 LOCKERS METAL LOCKERS MECHANICAL SYSTEMS BALANCING VALVES BALL VALVES PENCO PRODUCTS INC. QUIET QUALITY SERIES STORAGE SYSTEMS OH, MEDART INC. GREENWOOD, MS, LIST INDUSTRIES INC., BOCA RATON, FL SARCO TYPE IBW WHANDLE, HOMESTEAD FIG 1112, ILLINOIS SERIES 4000 HAMMOND 8301/8311, STOCKHAM S-216-BR-R-T/S-216-BR-RS, AMERICAN FIG. 2/2S, MILWAUKEE BA 100/BA 150, NIBCO T-585-70/S-585-70 10 of 14 LAVC Standards CAMPUS STANDARDS- MATRIX (Note: Campus Preferences are indicated first, followed by additional manufacturers in italics which are being considered by LACCD.) PLEASE READ & FOLLOW THE DIRECTIONS PROVIDED BELOW The Campus Standards Summary provided is to be used as a guide; but, LAVC has a comprehensive design standards which governs the design of any of our projects. The document referenced is “Campus Design Standards, Los Angeles Valley College, Los Angeles Community College District, June 26, 2010. The following language is included in this document, “In case there is a valid need to deviate from the standards, a written request needs to be submitted to and a formal written approval needs to be received from the Campus Maintenance & Operations (M&O) or IT Departments. Furthermore, these design standards are not to be deviated from for the purpose of value engineering unless formally approved by M&O or IT.” STANDARD CAMPUS PREFERRED BUTTERFLY VALVES MILWAUKEE, CENTERLINE, STOCKHAM, CRANE, OR DEZURIK CHECK VALVE HAMMOND IB940/IB912T, STOCKHAM B-320B/B-310B, AMERICAN 31F/31FS, CRANE 1707/1707S, NIBCO T-413/S413 KOSO, PACIFIC SEISMIC PRODUCTS HAMMOND IB645/IB647, CRANE 1701/1701S, WALWORTH FIG. 7/4SJ, MILWAUKEE 105/115, AMERICAN 3F/3FS, STOCKHAMIB440T/IB418, B-103/B-104, NIBCO T-113/S-113 HAMMOND STOCKHAM B-13-T/B-14, NIBCO T- EARTHQUAKE VALVE GATE VALVES GOLBE VALVES 211-Y/S-211-Y MOBILE MODULAR UNITS PAINT PIPE PLUMBING FIXTURES-TOILET ROOMS ACCESS PLATES BACKFLOW PREVENTION ASSEMBLIES BACKWATER SEWER VALVE ASSEMBLY CLEANOUT ASSEMBLIES J.R. SMITH #4760 AK, ELMDOR #DW-AKL, MILKORMOR DW AK1, ZURN Z-1462-VP WILKINS 720A, WATTS 800 MUQT, CHAMPION 262, WATTS 288A, WILKINS 35, WILLKINS 975 OR 375, WATTS 909 NE S009 NRS, FEBCO 860, 870, 880 WILKINS 920 OR 720A, WATTS 800M3QT, SMITH 7022-S, ZURN Z-1090 SMITH 4532-U, ZURN Z-1446-BP 11 of 14 LAVC Standards CAMPUS STANDARDS- MATRIX (Note: Campus Preferences are indicated first, followed by additional manufacturers in italics which are being considered by LACCD.) PLEASE READ & FOLLOW THE DIRECTIONS PROVIDED BELOW The Campus Standards Summary provided is to be used as a guide; but, LAVC has a comprehensive design standards which governs the design of any of our projects. The document referenced is “Campus Design Standards, Los Angeles Valley College, Los Angeles Community College District, June 26, 2010. The following language is included in this document, “In case there is a valid need to deviate from the standards, a written request needs to be submitted to and a formal written approval needs to be received from the Campus Maintenance & Operations (M&O) or IT Departments. Furthermore, these design standards are not to be deviated from for the purpose of value engineering unless formally approved by M&O or IT.” STANDARD CAMPUS PREFERRED CIRCULATING PUMPS, HOT WATER & HEATING ELECTRIC WATER COOLER DIELECTRIC UNIONS FAUCET FLOOR DRAIN BELL & GOSSETT OR WEIMAN OR TACO HAWS HWBFA8LSS WATTS 3100-IPXS, 3110-SXS, 3200-IPXIP CHICAGO NO. 897-CP, KOHLER NO. K-8907 SMITH NO. 2005Y-A-U-PO50, ZURN, ZN-415-B, SQUARE TOP, SMITH NO. 2005Y-B-U-PO50, ZURN ZN-415-S FLOOR SINK ROOF RECEPTOR HOSE BIBS TOILET PARTITIONS SMITH NO. 3140Y/31540Y, ZURN Z-1901/ZN 1900 SMITH NO. 3980Y-C, ZURN Z-108-RC ACORN NO. 8141/8102, ZURN 1350-5-LD BOBRICK PLUMBING VALVES AND ACCESSORIES WALL MOUNTED DRINKING FOUNTAINS BLACKWATER SEWER VALVE ASSEMBLY CLEANOUT ASSEMBLIES CIRCULATING PUMPS, HOT WATER & HEATING DRINKING FOUNTAIN FLOOR DRAIN FLOOR SINK ROOF RECEPTOR HOSE BIBS LAVATORIES PIPE HANGERS PRESSURE REGULATING VALVE ASSEMBLIES ROOF DRAIN ROOF OVERFLOW DRAIN SERVICE SINK HAWS CORP. SMITH 7022-S SMITH 7022-S, ZURN Z-1446-BP BELL & GOSSETT OR WEIMAN OR TACO HAWS MODEL 1119.14, WITH BRACKET6700.4 ROUND TOP- SMITH NO. 2005Y-A-U-PO50, ZURN ZN-415-B SQUARE TOP, SMITH NO. 2005Y-B-U-PO50, ZURN ZN-415-S SMITH NO. 3140Y/31540Y, ZURN Z-1901 /ZN 1900 SMITH NO. 3980 Y-C ACORN NO. 8141/8102, ZURN 1350-5-LD AMERICAN STAND. 0356.015, KOHLER K2006 WITH CHICAGO 404-A317CP DECK MOUNTED FAUCET WITH WRIST BLADE HANDLE SUPERSTRUT OR UNISTRUT OR B-LINE MASON-NEILLAN 71, SCHRADER 3464 OR 3466 SMITH 1010Y-ERC/1010Y-RC, ZURN Z-100-ERC/Z-100-RC SMITH 1080Y-ERC/1080Y-RC, ZURN Z-100-89-ERC/Z-100-89KOHLER K-6718 WITH K-6673 TRAP STAND & STRAINER & K- 12 of 14 LAVC Standards CAMPUS STANDARDS- MATRIX (Note: Campus Preferences are indicated first, followed by additional manufacturers in italics which are being considered by LACCD.) PLEASE READ & FOLLOW THE DIRECTIONS PROVIDED BELOW The Campus Standards Summary provided is to be used as a guide; but, LAVC has a comprehensive design standards which governs the design of any of our projects. The document referenced is “Campus Design Standards, Los Angeles Valley College, Los Angeles Community College District, June 26, 2010. The following language is included in this document, “In case there is a valid need to deviate from the standards, a written request needs to be submitted to and a formal written approval needs to be received from the Campus Maintenance & Operations (M&O) or IT Departments. Furthermore, these design standards are not to be deviated from for the purpose of value engineering unless formally approved by M&O or IT.” STANDARD CAMPUS PREFERRED SINK KOHLER K-6718 WITH K-6673 TRAP STAND & STRAINER & K8907 FAUCET STOP VALVES THERMOSTATIC MIXING VALVE ASSEMBLIES ANGLE CHICAGO 442-LK, CRANE 8:5113 LEONARD TYPE TM, LAWLER 4000 SERIES 802, 805 & 66, POWER TYPE 430 SERIES TRAP PRIMER URINAL WATER CLOSET WATER HEATER WATER HAMMER ARRESTORS PPP P2-500, SMITH KOHLER K-4960-ET AMERICAN, LOCHINVAR, A.O.SMITH, RAYPACK, LARRS PPP, DOLE 13 of 14 LAVC Standards CAMPUS STANDARDS- MATRIX (Note: Campus Preferences are indicated first, followed by additional manufacturers in italics which are being considered by LACCD.) PLEASE READ & FOLLOW THE DIRECTIONS PROVIDED BELOW The Campus Standards Summary provided is to be used as a guide; but, LAVC has a comprehensive design standards which governs the design of any of our projects. The document referenced is “Campus Design Standards, Los Angeles Valley College, Los Angeles Community College District, June 26, 2010. The following language is included in this document, “In case there is a valid need to deviate from the standards, a written request needs to be submitted to and a formal written approval needs to be received from the Campus Maintenance & Operations (M&O) or IT Departments. Furthermore, these design standards are not to be deviated from for the purpose of value engineering unless formally approved by M&O or IT.” STANDARD CAMPUS PREFERRED PORCELAIN TILE-CERAMIC ROOFING SECURITY ALARM SYSTEM SYSTEM CCTV STORAGE/TRANSFER TELEPHONE SYSTEM WATER FOUNTAINS DRINKING FOUNTAIN FAUCET HAWS MODEL 1119.14, WITH BRACKET6700.4 CHICAGO NO. 897-CP, KOHLER NO. K-8907 WINDOW COVERING 14 of 14