U.S. AIR FORCE TELECOMMUNICATIONS SYSTEMS CABLING STANDARDS 802d Communications Squadron Lackland Air Force Base, Texas 12 July 2011 Chg 1, 1 Dec 11 This document provides guidance on the installations standards required for all Outside Plant (OSP) cabling and Inside Plant (ISP) cabling projects installed at Lackland Air Force Base, Texas. Page 2 of 40 2/8/12 TABLE OF CONTENTS PART ONE - GENERAL 1.1 REFERENCES 1.2 SYSTEM DESCRIPTION 1.2.1 General 1.2.2 Environmental Requirements 1.2.3 Input Line Surge Protection 1.2.4 Power Line Surge Protection 1.3 QUALIFICATIONS 1.3.1 Minimum Contractor Qualifications 1.3.2 Minimum Manufacturer Qualifications 1.4 SUBMITTALS 1.4.1 Pre-construction Drawings - Communications Distribution System 1.4.2 Post-construction Drawings (As-Built Drawings) - Communications Distribution System 1.4.3 Instructions - Manufacturer‟s Recommendations 1.4.4 Qualifications 1.4.5 Reports - Copper Wire and Fiber Optic Cable Test Reports 1.4.6 Certificates - Communications Distribution System 1.4.7 Materials and Equipment 1.4.8 Installers 1.5 STORAGE AND DELIVERY 1.5.1 General 1.5.2 Delivery and Storage of Outside Plant Cable 1.6 OPERATIONS AND MAINTENANCE MANUALS 1.7 RECORD KEEPING AND DOCUMENTATION 1.7.1 Cables 1.7.2 Termination Hardware Page 3 of 40 2/8/12 PART TWO - PRODUCTS 2.1 MATERIALS AND EQUIPMENT 2.1.1 Quality 2.1.2 Nameplates 2.1.3 Connectors, Patch Panels, Faceplates 2.2 UNSHIELDED TWISTED-PAIR (UTP) CABLE SYSTEM 2.2.1 Cable Insulation 2.2.2 Underground Cable 2.2.3 Building Entrance Cable 2.2.4 Inside Wiring (I/W) Telephone & LAN/Data Cables 2.2.5 Horizontal Cable 2.2.6 Connecting Hardware 2.3 PROTECTOR MODULES 2.4 EQUIPMENT MOUNTING BACKBOARD/s 2.5 FIBER OPTIC CABLE SYSTEM 2.5.1 Outside Plant Fiber Optic Cable System 2.5.2 Backbone Fiber Optic Cable 2.5.3 Horizontal Distribution Fiber Optic Cable 2.5.4 Connecting Hardware 2.5.5 Outside Plant Cable Splices, Connectors, Cable Assemblies, and Organizers 2.6 MISCELLANEOUS ITEMS 2.6.1 Shield Connectors 2.6.2 Grounding 2.6.3 Grounding Braid 2.6.4 Cable Warning Tape 2.6.5 Nylon Pull Rope 2.7 CATEGORY 6 LAN PATCH PANELS 2.8 DATA CABINETS Page 4 of 40 2/8/12 2.9 MANHOLES 2.10 CABLE RACKS AND CABLE RACK SUPPORTS 2.11 CONDUIT 2.12 COMMUNICATIONS CLOSETS PART THREE - EXECUTION 3.1 WORKMANSHIP 3.2 VERIFICATION OF DIMENSIONS 3.3 INSTALLATION 3.3.1 General 3.3.2 Horizontal Distribution System 3.3.3 Telecommunications (Telephone & LAN/Data) Outlets 3.3.4 Terminal Blocks 3.3.5 Communications Raceways/Cable Trays 3.3.6 Conduit Below Slab-on-grade or in the Ground 3.3.7 Duct Lines 3.3.8 Building Entry Conduit 3.3.9 Cable 3.3.10 Manholes 3.4 UNDERGROUND CABLE SYSTEMS 3.4.1 Bending Radius 3.4.2 Electrical Protection 3.4.3 Underground Splice Closures 3.4.4 Encapsulant 3.4.5 Duct Sealing 3.4.6 Testing 3.4.7 Multi-pair Cable 3.4.8 Shield Continuity 3.4.9 Cable Faults and Splicer Errors Page 5 of 40 2/8/12 3.4.10 Pressure Testing 3.5 BURIED CABLE SYSTEMS 3.5.1 Base Civil Engineering Work Clearance Request 3.5.2 Multi-pair Telephone Cable 3.5.3 Splicing 3.5.3.1 Splice Connectors 3.5.3.2 Shield Bonding Connectors 3.5.3.3 Outside Plant Multi-pair Cables 3.5.3.4 Splicing Sequence 3.5.4 Marking 3.5.4.1 Cable Tags 3.5.5 Buried Splice Closures 3.5.6 Encapsulant 3.5.7 Cut Cable Restorations 3.6 OUTSIDE PLANT CABLE SPLICING 3.6.1 Copper Conductor Splices 3.6.2 Fiber Optic Splices 3.7 TERMINATION 3.7.1 General 3.7.2 Procedure 3.7.3 Cable Protector Modules 3.7.4 Terminal Blocks 3.7.5 Common User Telephone & LAN/Data Outlets 3.7.6 Telephone Terminal Backboard (TTB) 3.7.7 Equipment Racks (Data Cabinets) 3.7.8 Rack Mounted Equipment 3.7.9 Concrete Pull-boxes and Manholes 3.8 GROUNDING Page 6 of 40 2/8/12 3.8.1 General 3.8.2 Telecommunications Main Ground Bus Bar 3.8.3 Manholes 3.8.4 Bonding Ribbon Clamps 3.9 ADMINISTRATION AND LABELING 3.9.1 Labeling 3.9.2 Marking Cable Tags 3.10 CABLE TELEVISION INSTALLATION 3.11 INSTALLATION INSPECTIONS 3.11.1 Pre-installation Inspection 3.11.2 In-progress Inspections 3.11.3 Final Inspection 3.11.4 Corrective Action and Verification Inspection 3.12 COMMUNICATIONS DISTRIBUTION SYSTEM TESTING 3.12.1 General 3.12.2 Procedure 3.12.3 Unshielded Twisted-Pair Tests 3.12.14 Copper Cable Tests 3.12.5 Category 6 Circuit Tests 3.12.6 Fiber Optic Cable Tests - Outside Plant 3.12.7 Fiber Optic Cable Tests - Facility Interior 3.12.8 Test Results 3.13 REPAIR OF EXISTING WORK Page 7 of 40 2/8/12 PART ONE - GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. These publications are referred to in the text by basic designation only. Engineering Technical Letter (ETL) 02-12 (Jun 2002): Communications and Information System Criteria for Air Force Facilities 38 EIG Handbook 33-01 (2005) Communications and Information AETC First 400 Feet Standard Guidance at all AETC Bases (10 Mar 2006) U.S. Air Force Technical Orders 31W3-10-12-WA-1 Copper cable Placement 31W3-10-13-WA-1 Cable Splicing 31W3-10-14-WA-1 Termination 31W3-15-15-WA-1 Outside Plant Testing 31W3-10-19-WA-1 Standard Install Practice, Telephone, Outside Plant Install, Pole line 31W3-10-21-WA-1 Outside Plant Cable Maintenance and Repair 31W3-10-22-WA-1 Telecommunications Engineering, Outside Plant, Telephone 31Z-10-37, 1-1-689-1-WA-1, 1-1-689-3-WA-1, 1-1-689-5-WA-1, 1-1-691-WA-1, 1-1-700-WA-1 Corrosion Prevention and Protection 31-1-141-1-WA-1 General Testing Information and Safety Precautions 31-10-3-WA-1 Standard Installation Practices 31-10-10-WA-1 Anchoring Devices for CE Ground Equipment 31-10-11-WA-1 Standard Installation Practices Cross Connections 31-10-13-WA-1 Cabling for Fixed Ground Equipment 31-10-24-WA-1 Comm Systems Grounding, Bonding and shielding American Society for Testing and Materials (ASTM) ASTM A228 Standard Specification for Steel Wire, Music Spring Quality ASTM C338-93 (2008) Standard Test Method for Softening Point of Glass ASTM E814-11a Standard Test Method for Fire Tests of Penetration Fire Stop Systems Building Industry Consulting Service International (BICSI) Standards Page 8 of 40 2/8/12 Telecommunications Distribution Methods Manual 8610 Hidden River Parkway Tampa, FL 33637 1-800-242-7405 bicsi@bicsi.org Electronic Industries Alliance / Telecommunications Industries Association (EIA/TIA) TIA/EIA-455-25-B Repeated Impact Testing of Fiber Optic Cables and Cable Assemblies TIA/EIA-455-41-A Compressive Loading Resistance of Fiber Optic Cables TIA/EIA-455-46-A Spectral Attenuation Measurement for Log Length, GradedIndex Optical Fibers TIA/EIA-455-51-A Pulse distortion Measurement of Multimode Glass Optical Fiber Information Transmission Capacity TIA/EIA-455-53-A (1990) Attenuation by substation Measurement for Multimode Graded Index Optical Fiber TIA/EIA-455-60-A Length Measurement of Optical Waveguide Fibers by Line-ofFlight TIA/EIA-568-B.1 (2001; Addendum 2001) Commercial Building Telecommunications Cabling Standard- Part 1: General Requirements (ANSI/TIA/EIA-568-B.1) TIA/EIA-606-A (2002) Administration Standard for the Telecommunications Infrastructure of Commercial Buildings TIA-569-B Commercial Building Standards for Telecommunications Pathways and Spaces (ANSI/TIA/EIA-569-A-98) EIA/TIA-455-30-B Frequency Domain Measurement of Multimode Optical Fiber EIA-455-33-A Fiber Optic Cable Tensile Loading and Bending Test EIA/TIA-455-81-B Compound Flow (Drip) Test for Filled Fiber Optic Cable EIA/TIA-455-82B Fluid Penetration Test for Fluid-Blocked Cable American Standards Institute (ANSI) ANSI-J-STD-607-A Commercial Building Grounding (Earth) and Bonding Requirements for Telecommunications ANSI/TIA/EIA-492AAAA-A (1998) Detail Specification for 50-um Core Diameter/ 125-um Cladding Diameter Class IA Graded Index Multimode Optical Fibers ANSI/EIA/TIA-47B Output Far Field Radiation Pattern Measurement Institute of Electrical and Electronics Engineers (IEEE) Page 9 of 40 2/8/12 IEEE C62.41 (1991) Recommended Practice for Surge Voltages in LowVoltage AC Power Circuits Insulated Cable Engineers Association (ICEA) ICEA S-56-434-1983 (1991) Polyolefin Insulated Communications Cables for Outdoor Use ICEA S-83-596-2001 (2001) Fiber Optic Premises Distribution Cable National Fire Protection Association (NFPA) NFPA 70 (2011) National Electrical Code National Electrical Manufacturers Association (NEMA) NEMA WC 63.1 (2005) Twisted Pair Premise Voice and Data Communications Cables NEMA WC 66 (2001) Category 6 and Category 7 100 Ohm Shielded and Unshielded Twisted Pairs Rural Utilities Service (RUS) REA PC 2 Splicing Plastic-Insulated Cables REA PE-33 (1985) Shield Bonding Connectors – Bulletin 345-65 REA PE-80 (1982) Gas Tube Surge Arresters - Bulletin 345-83 REA TE&CM 823 (1980) Electrical Protection by Use of Gas Tube Arrestors RUS Bulletin 345-63 (PC-4) (1976) Standard for Acceptance Tests and Measurements of Telephone Plant RUS Bulletin 1751F-644 (1998) Design and Construction of Underground cable (Physical Plant) RUS Bulletin 1753F-201 (1997) Standard for Acceptance Tests and Measurements of Telephone Plant RUS Bulletin 1753F-401 (PC-2) (1995) Standard for Splicing Copper & Fiber Optic Cables RUS Bulletin 1753F-401 (1995) Standard for Splicing Copper and Fiber Optic Cables RUS Bulletin 1755I-100 (2009) List of Materials Acceptable for Use on Systems of REA Telephone Borrowers Underwriters Laboratories, Inc. (UL) UL 497 (1995) Protectors for Paired Conductor Communication Circuits UL 1479 Fire Tests of Through-Penetration Firestops Page 10 of 40 2/8/12 1.2 SYSTEM DESCRIPTION 1.2.1 General The communications distribution system shall consist of inside-plant horizontal and outside-plant cables and connecting hardware to transport telephone and data (including LAN) signals between equipment in dispersed buildings as well as equipment within a building. 1.2.2 Environmental Requirements Equipment and cable to be utilized indoors shall be rated for continuous operation under ambient environmental conditions of 0 to 50 degrees C dry bulb and 10 to 85 percent relative humidity, noncondensing. Equipment shall be rated for continuous operation under the ambient environmental temperature, pressure, humidity, and vibration conditions specified or normally encountered for the installed location. 1.2.4 Input Line Surge Protection Inputs and outputs shall be protected against surges induced on wiring. Communications equipment shall be protected against surges induced on any communications circuit. Cables and conductors (except fiber optics which serve as communications circuits from consoles to field equipment and between field equipment) shall have surge protection circuits installed at each end. Protection shall be furnished at equipment, and additional triple electrode gas surge protectors rated for the application on each wire line circuit shall be installed within 1 meter of the building cable entrance. Fuses shall not be used for surge protection. The inputs and outputs shall be tested in both normal mode and common mode using the following two waveforms: a. A 10-microsecond rise time by 1000 microsecond pulse width waveform with a peak voltage of 1500 volts and a peak current of 60 amperes. b. An 8-microsecond rise time by 20 microsecond pulse width waveform with a peak voltage of 1000 volts and a peak current of 500 amperes. 1.2.5 Power Line Surge Protection Equipment connected to ac circuits shall be protected from power line surges. Equipment shall meet the requirements of IEEE C62.41. Fuses shall not be used for surge protection. 1.3 QUALIFICATIONS 1.3.1 Minimum Contractor Qualifications All work under this section shall be performed by and all equipment shall be furnished and installed by a BICSI Certified Telecommunications Contractor, hereafter referred to as the Contractor. With the exception of furnishing and installing conduit, electrical boxes, and pull-wires, the Electrical Contractor shall not do this work. The Contractor shall have the following qualifications in telecommunications systems installation: a. Supervisors and installers assigned to the installation of this system or any of its components shall be Building Industry Consulting Services International (BICSI) Registered Cabling Installers, Technician Level. Submit documentation of current BICSI certification for each of the key personnel. b. All supervisors and installers assigned to the installation of this system or any of its components shall have factory certification from each equipment manufacturer that they are qualified to install and test Page 11 of 40 2/8/12 the provided products. General electrical trade staff (electricians) shall not be employed for the installation of the communications distribution system cables, equipment, and associated hardware. c. All installers assigned to the installation of this system or any of its components shall have a minimum of 3 years experience in the installation of the specified copper wire, fiber optic cable and components. NOTE: Each installer may be required to make an approved dummy splice of each type to be employed in the execution of this contract in the presence of the Contracting Officer or representative. Splices shall be in accordance with the cable manufacturer‟s instructions. The Contractor shall furnish all materials needed for dummy splices, at no cost to the government. 1.3.2 Minimum Manufacturer Qualifications The equipment and hardware provided under this contract will be new and the standard products of a manufacturer with a minimum of 3 years experience in producing the types of systems and equipment specified. Items of equipment shall essentially duplicate equipment that has been in satisfactory use at least 2 years prior to bid opening. 1.4 SUBMITTALS Government approval is required for submittals with a “GA” designation; submittals having a “FIO” designation are for information only. The following shall be submitted in accordance with Section entitled, SUBMITTAL PROCEDURES: 1.4.1 Pre-construction Drawings - Communications Distribution System (FIO) Detail drawings including a complete list of equipment and material. Detail drawings shall contain complete wiring and schematic diagrams and other details required demonstrating that the system has been coordinated and will function properly as a system. Drawings shall include vertical riser diagrams, equipment rack details, and elevation drawings of telecommunications closet walls, outlet faceplate details for all outlet configurations, sizes and types of all cables, conduits, and cable trays. Drawings shall show proposed layout and anchorage of equipment and associated items, and equipment relationship to other parts of the work including clearance for maintenance and operation. 1.4.2 Post-construction Drawings (As-Built Drawings) - Communications Distribution System (FIO) As-built drawings for the installed outside plant wiring system infrastructure shall be submitted per TIA/EIA-606-A. Drawings will be submitted to 802 CS in either AutoCAD or Bentley MicroStation formats. The drawings shall show the location of all cable terminations and location and routing of all cable terminations and location and routing of all backbone and horizontal cables. The identifier for each termination and cable shall appear on the drawings. As-built drawings for the installed inside plant wiring system infrastructure shall be submitted in Visio format. Copy of as-built drawings will be provided to 802 CS within 14 days after completion of installation. 1.4.3 Instructions - Manufacturer’s Recommendations (FIO) Where installation procedures or any part thereof are required to be in accordance with the recommendations of the manufacturer of the material being installed, printed or electronic copies of these recommendations shall be provided prior to installation. Installation of the item will not be allowed to proceed until the recommendations are received and approved. 1.4.4 Qualifications (GA) Page 12 of 40 2/8/12 The qualifications of the Manufacturer, Contractor, and the Installer to support and perform the work specified herein. This shall include proof of the minimum qualifications specified herein. 1.4.5 Reports - Copper Wire and Fiber Optic Cable Test Reports (GA) Test Reports in booklet form with witness signatures verifying execution of tests. Reports shall show the field tests performed to verify compliance with the specified performance criteria. Test reports shall include record of the physical parameters verified during testing. Test reports shall be submitted to the Base Communications Squadron within 14 days after completion of testing. The Contractor shall provide all necessary personnel, equipment, instrumentation, and supplies required to properly test and document the transmission media parameters of the voice and data transmission systems. 1.4.6 Certificates - Communications Distribution System (FIO) Written certification that the premises distribution system complies with the TIA/EIA-568-B, TIA/EIA-569-B and TIA/EIA-606-A standards. 1.4.7 Materials and Equipment (FIO) Where materials or equipment are specified to conform, are constructed or tested to meet specific requirements, certification that the items provided conforming to such requirements. Certification by a nationally recognized testing laboratory that a representative sample has been tested to meet the requirements, or a published catalog specification statement to the effect that the item meets the referenced standard, will be acceptable as evidence that the item conforms. Compliance with these requirements does not relieve the Contractor from compliance with other requirements of the specifications. All existing telephone & LAN/Data outlets, data patch panels or other communications equipment scheduled for demolition, shall be disposed of by the contractor. All demolished telephone LAN/Data outlet locations shall be replaced with equipment specified by paragraph 2.2.6.1 of this specification. Under no circumstances will telephone & LAN/Data outlets be demolished without replacement. 1.4.8 Installers (GA) The Contractor shall submit certification that all the installers are factory certified to install and test the provided products. Supervisors and installers assigned to the installation of this system or any of its components shall be Building Industry Consulting Services International (BICSI) Registered Cabling Installers, Technician Level. Submit documentation of current BICSI certification for each of the key personnel. 1.5 STORAGE AND DELIVERY 1.5.1 General Material shall be delivered in unopened original containers plainly labeled with the manufacturer‟s name and brand. Equipment placed in storage shall be stored with protection from the weather, humidity and temperature variation, dirt and dust or other contaminants. Metallic materials exposed to the weather shall be protected against corrosion. 1.5.2 Delivery and Storage of Outside Plant Cable All cable shall be shipped on reels. The diameter of the drum shall be at least 13 times the diameter of the cable. The reels shall be substantial and so constructed as to prevent damage during shipment and handling. The outer end of the cable shall be securely fastened to the reel head to prevent the cable from becoming loose in transit. The inner end of the cable shall project into a slot in the side of the reel, or into housing on the inner slot of the drum, in such a manner and with sufficient length to make it available for testing. The inner end shall be fastened to prevent the cable from becoming loose during installation. Page 13 of 40 2/8/12 End seals shall be applied to each of the cables to prevent moisture from entering the cable. The reels with cable shall be suitable for outside storage conditions when the temperature ranges from minus 40 degrees C to plus 65 degrees C, with relative humidity from zero to 100 percent. All project material shall be delivered to the following address: 410 North Franklin Luke Drive Bldg 1530, Gate 5, Bay 9 & 10, Door 11 San Antonio, TX 78226 1.6 OPERATIONS AND MAINTENANCE MANUALS Commercial off-the-shelf manuals shall be furnished for operation, installation, configuration, and maintenance for all products provided as a part of the communications distribution system. Specification sheets for all cable, connectors, and other equipment shall be provided. 1.7 RECORD KEEPING AND DOCUMENTATION 1.7.1 Cables A record of all installed cable shall be provided in hard copy format media using Windows based computer cable management software per TIA/EIA-606-A. The cable records shall include the required data fields for each cable and complete end-to-end circuit report for each complete circuit from the assigned outlet to the entry facility per TIA/EIA-606-A. 1.7.2 Termination Hardware A record of all installed patch panels and outlets shall be provided in hard copy format using Windows based computer cable management software per TIA/EIA-606-A. The hardware records shall include only the required data fields per TIA/EIA-606-A. Page 14 of 40 2/8/12 PART TWO - PRODUCTS 2.1 MATERIALS AND EQUIPMENT 2.1.1 Quality Materials and equipment shall be the standard products of a manufacturer regularly engaged in the manufacture of the products. They shall also be the manufacturer‟s latest standard design that has been in satisfactory use for at least 2 years prior to installation. Materials and equipment shall conform to the respective publications and other requirements specified below and to the applicable requirements of NFPA 70. 2.1.2 Nameplates Each major component of equipment shall have the manufacturer‟s name, address, type or style, model and/or serial number, and catalog number on a plate firmly secured to the equipment. 2.1.3 Connectors, Patch Panels, Faceplates All horizontal cabling will be terminated to Leviton brand or compatible connectors, patch panels, and faceplates. 802 CS/SCOW will verify compatibility. 2.2 UNSHIELDED TWISTED-PAIR (UTP) CABLE SYSTEM 2.2.1 Cable Insulation For each individual Category 6 cable, the insulation material used on each pair shall be the same in all physical, electrical, and chemical respects. The use of Teflon insulated plenum-rated Category 6 cable is acceptable for both plenum and non-plenum applications. If Teflon insulated plenum-rated cable is used by the Contractor; it shall be type 4x0, where all four-pairs are Teflon insulated. Type 3x1 and 2x2 are not acceptable. 2.2.2 Underground/Buried Cable Underground/buried telephone cable smaller than 1800-pair, shall be type REA PE-89, #24 AWG solid copper conductor, gel-filled cable. Larger pair count cable (i.e.: 1800-pair, 2400-pair, and 3600-pair) shall be type REA PE-89, #26 AWG solid copper conductor, gel-filled cable. Gopher (armor) protection is required. 2.2.3 Building Entrance Cable Building entrance cable shall be #24 AWG, solid copper conductor, type REA PE-89 gel-filled telephone cable. 2.2.4 Inside Wiring (I/W) Telephone & LAN/Data Cables Inside wiring cables shall be 4-pair (#24 AWG) solid tinned copper, PVC insulated, station-type gray color, CMP rated, unshielded twisted-pairs, PVC jacket, Category 6 horizontal cable. I/W cable shall be continuous from each outlet to the Category 6 patch panel indicated on the drawings. Splicing of individual cables shall not be permitted. At each telephone & LAN/Data outlet, four-pair I/W cable shall be terminated on the modular outlet assembly wired per T568-B wiring configuration. At the communications room terminate the cable on CAT-6 common user patch panels and mark with the appropriate outlet number. 2.2.5 Horizontal Cable Page 15 of 40 2/8/12 Horizontal cable shall meet the requirements of TIA/EIA-568B for Category 6 horizontal cable. Cable shall be label-verified. Cable jacket shall be factory marked at regular intervals indicating verifying organization and performance level. Conductors shall be solid untinned copper #24 AWG. Cable shall be rated CMP per NFPA 70. 2.2.6 Connecting Hardware Connecting and cross-connecting hardware shall be the same category as the cable it serves. Hardware shall be in accordance with TIA/EIA-568B. 2.2.6.1 Telecommunications (Telephone & LAN/Data) Outlets Quad outlets will be installed at each telephone & LAN/data location unless specified otherwise. Each quad shall contain 2ea telephone outlets and 2ea LAN/data outlets. Telecommunications outlets shall be Category 6, RJ45 8-pin voice and data modular outlet assemblies housed in a quad-hole, flush wallmount faceplate. All terminations shall be done according to T568-B wiring scheme as required by TIA/EIA-568-B. Wall-mount telephone outlets (for wall-mounted telephone sets) shall be 8-pin modular outlet assemblies (type RJ-45 modular wall-telephone jack) mounted in a simplex housing as indicated on the drawings. Each modular outlet shall accept a 4-pair Category 6 cable (8-conductors) and each modular outlet assembly shall be numbered for easy identification and location. All outlets will be wired directly to the Common User Patch Panel located in the Telecommunications Room serving the floor that the outlets are located on. 2.2.6.3 Terminal Blocks Terminal blocks shall be wall-mounted wire termination units consisting of insulation displacement connectors mounted in plastic blocks, frames or housings. Blocks shall be type 110, which meet the requirements of TIA/EIA-568-B for Category 6. Blocks shall be mounted on standoffs and shall include cable management hardware. Insulation displacement connectors shall terminate 22 or 24 gauge solid copper wire as a minimum and shall be connected in pairs so that the horizontal cable and cross-connect blocks shall terminate all subscriber lines. The blocks shall be attached to the left side of the plywood telephone terminal backboard in vertical rows. 2.3 PROTECTOR MODULES The protector modules shall be of the three-electrode gas tube type. Protection modules shall be classified as light, medium, heavy, or maximum duty depending on their performance in categories of impulse life, maximum surge impulse and 60 Hz current carrying capacity as specified in REA TE & CM 823. The gas modules shall be fail-short and shall shunt high voltage to ground in less than 100 microseconds, shall have an external spark gap, and shall comply with UL 497. 2.4 EQUIPMENT MOUNTING BACKBOARD Plywood backboards, ¾” thick (sized as specified) shall be provided and installed with the finished side facing outward and painted with two-coats of fire retardant paint. 2.5 FIBER OPTIC CABLE SYSTEM 2.5.1 Outside Plant Fiber Optic Cable System 2.5.1.1 Fiber Optic Cable Reeled fiber optic cable shall be of continuous manufacture with no factory splices in the fiber. 2.5.1.2 Compatible Components Page 16 of 40 2/8/12 Materials used within a given cable shall be compatible with all other materials used in the same cable when such materials come into intimate contact. All cable components used shall have no adverse affect on optical transmission or on the mechanical integrity characteristics of the fiber placed in the cable. All materials used shall be nontoxic, non-corrosive, and shall present no thermal hazard. The minimum required material components applied to fiber optic cable construction are central core or sheath strength member, color-coded optical fibers, inner jacket, pulling strength members, and outer jacket. 2.5.1.3 Cable Cores A central core member or sheath strength member shall be included to serve as a cable core foundation to reduce strain on the fibers but not to serve as a pulling strength member. The materiel of the central core member shall be nonmetallic. The sheath strength member may be either metallic or nonmetallic. The metallic strength element shall be spring quality music type wire per ASTM A228. The nonmetallic strength element shall be glass filament. 2.5.1.4 Single-mode Optical Fiber Single-mode optical fibers (strand count to be specified) shall be contained in the cable. The single-mode fiber shall be step index optical glass. The core diameter, if an addressable parameter, shall be 8.5 plus or minus 2 microns. If the core diameter is not addressed, then the mode field diameter shall be 10 microns plus or minus 1 micron. The cladding diameter shall be 125 microns plus or minus 5 microns. The core-cladding offset shall be less than 1 micron. The minimum tensile strength of the fiber after primary protective coating shall be greater than 344Mpa (50,000 psi). The softening point of the clad material of the optical fiber shall be 1630 degrees C plus or minus 50 degrees C in compliance with ASTM C338-93. 2.5.1.5 Optical Fiber Coatings The optical fiber shall be coated with a suitable material to preserve the intrinsic high tensile strength of the glass fiber. The outside diameter of the coated optical fiber shall be 250 microns plus or minus 15 microns. The coating material shall be readily removable, mechanically or chemically, without damaging the optical fibers when the removal is desired. 2.5.1.6 Color-Coding The primary protective coated fiber shall be color-coded for individual fiber identification. The maximum outside diameter of color-code coated fiber shall be less than 300 microns. 2.5.1.7 Fiber Protection The color-coded fibers shall be surrounded with loose buffer tubes, channels or other innovative design, or in a tight buffer construction, for protection from external mechanical and environmental influences. The interior of the tube shall be filled with a suitable gel-filling compound to prevent water migration. The loose tube buffering, channel or other innovative design, or tight buffer construction, shall be color-coded for tube identification. The material of the buffering tube shall be PVC, Mylar, nylon, or a functionally equivalent material. 2.5.1.8 Tint Requirements The color concentrates or tints used to color the optical fibers and the buffer tubes shall not be susceptible to migration and chemical reaction with gel-filling compound. 2.5.1.9 Buffer Tubes The buffer tubes shall be located concentrically around the cable central core member and covered with a black, low or medium density polyethylene inner jacket in accordance with ICEA S-56-434-1983. Page 17 of 40 2/8/12 2.5.1.10 Filling Compound Requirements The inner jacket interior and buffer cavity shall contain a gel-type-filling compound. The filling compound shall be of suitable viscosity so that it shall protect the ingress of water and/or soluble chemicals and shall not flow at the temperature of up to 65 degrees C. The gel-filling compound shall be colorless, electrically non-conducting, inert gel-type, waterproof, nontoxic, with no thermal hazards, and compatible chemically and mechanically with all cable components and associated splice hardware materials to which it may make contact. The gel filling shall be removable, as required; using commercially available products under field conditions. 2.5.1.11 Tensile Strength The cable shall contain a nonconductive central strength member as well as a layer of aramid type yarn encircling the cable core. The strength member shall provide a maximum pulling load of 1335 Newtons. 2.5.1.12 Outer Jacket Black, low or medium density, high-molecular weight, polyethylene materials shall be applied longitudinally over the entire inner jacket and sheathing strength member to form the cable outer jacket, in accordance with ICEA S-56-434-1983. The outer jacket shall be smooth, concentric, non-nutrient to fungus, and free from holes, splits, blisters, or other imperfections. The overall outside cable diameter shall not exceed 3/4”. 2.5.1.13 Fiber Differentiation The individual optical fiber shall be easily and positively identified from the buffer tube color code and the optical fiber primary coating color code. 2.5.1.14 Cable Labeling The outer jacket shall bear the manufacturer‟s name, year of manufacture, and length marker. The length marking shall employ continuous four- or five-digit numbers in meters, such as: Manufacturer‟s Name - Year XXXX meter The markings shall be repeated clearly and distinguishably on every meter on the cable outer jacket. The marking ink shall be fully compatible with the jacket material, non-smearing, non-water soluble, abrasion resistant, and durable enough to withstand field handling during placement and subsequent operations. 2.5.1.15 Attenuation The optical attenuation of each optical fiber in the reeled cable shall be no greater than 1.0 decibels/km within a peak emissive region of 850 nm to 1300 nm for multimode fiber optic cable and 1310 nm to 1550 nm for singlemode fiber optic cable. The attenuation shall be measured on completed cable reel length, and normalized linearly to 1 km. The measurement method shall be in accordance with TIA/EIA-455-46A (FOTP-46) or TIA/EIA-455-53A (FOTP-53). 2.5.1.16 Bandwidth Each optic fiber within the cable (reeled) shall have its bandwidth measured between 3 decibels optical power points, as compared to a reference signal, for a light source with a peak optical emissive region of 850 nm to 1300 nm for multimode fiber optic cable and 1310 nm to 1550 nm for singlemode fiber optic cable. The effective system bandwidth of at least one GHz-km is required. The effective system bandwidth multiplied by the cable length raised to the negative length-dependence factor (or gamma Page 18 of 40 2/8/12 factor). Gamma shall be in the range of 0.85 to 0.9. The bandwidth measurement shall be in accordance with EIA/TIA-455-30-B (FOTP-30) frequency domain or TIA/EIA-455-51A (FOTP 51) time domain. 2.5.1.17 Numerical Aperture The numerical aperture of each optical fiber shall be 0.2 plus or minus 0.02 within an optical emissive region of 850 nm to 1300 nm for multimode fiber optic cable and 1310 nm to 1550 nm for singlemode fiber optic cable. The method of numerical aperture measurement shall be in accordance with EIA/TIA 455-47B (FOTP-47). 2.5.1.18 Bending Tolerance The cable shall be able to withstand bending to a minimum radius of ten times the cable outer diameter with no tensile load applied and twenty times the cable outer diameter with maximum tensile load applied during installation, without damage to cable components or degradation of the optical fiber performance at room temperature. 2.5.1.19 Tensile Load Tolerance The fiber optic cable shall withstand a pull force of at least 1780 Newtons, to be applied to the pulling strength member during operation without incurring any damage or detriment to fiber optic cable and optical performance. The tensile strength test shall be per EIA 455-33-A (FOTP-33). 2.5.1.20 Cyclic Flexing Tolerance The fiber optic cable shall withstand at least twenty bending cycles at minimum bend radius without damage to the fiber optic cable components or degrading optical performance. The cyclic flexing test shall be in accordance with EIA 455-65 (FOTP-65). 2.5.1.21 Crush Resistance The minimum crush resistance of the fiber optical cable shall be greater than 650 Newton/cm without damage to cable components or degrading optical performance. The crush resistance test shall be in accordance with TIA/EIA 455-41A (FOTP-41). 2.5.1.22 Impact Resistance The fiber optic cable shall be capable of withstanding twenty impacts, at a force of five Newtons-meters, without damage to cable components, or degradation of optical performance. The impact resistance test shall be in accordance with TIA/EIA 455-25B (FOTP-25). 2.5.1.23 Gel Compound Temperature Tolerance The optic cable shall be tested for the ability of the gel-filling compound in the interior of the inner jacket and buffer to resist flow at the temperature range of minus 40 degrees C to 60 degrees C in accordance with EIA/TIA-455-81B (FOTP-81). 2.5.1.24 Fluid Penetration Test The optic cable shall be capable of preventing the entry of axial migration of 62 kPa (9 psi) pressurized water when subjected to fluid penetration testing in accordance with EIA/TIA-455-82-B (FOTP-82). 2.5.1.25 Performance Requirements The fiber optic cable shall comply with the mechanical performance requirements herein while used in duct applications where the temperature varies minus 20 degrees C to plus 60 degrees C. Optical Page 19 of 40 2/8/12 performance degradation shall be less than 5 percent of the optical performance requirements in the temperature range of minus 20 degrees C to plus 60 degrees C. The fiber optic cable shall not be damaged in storage where the temperature may vary from minus 40 degrees C to plus 65 degrees C. 2.5.1.26 Defects and Imperfections Fiber optic cables shall be free of material and manufacturing defects, and of dimensional non-uniformity which would seriously impair the functionality of the cables. The fiber optic cables shall also be free from surface imperfections and internal defects, which would prevent them from meeting the mechanical and transmission requirements of this specification. 2.5.2 Backbone Fiber Optic Cable 2.5.2.1 Multimode Multimode fiber optic backbone cable (strand count to be specified) shall meet the requirements of TIA/EIA-568-B, TIA/EIA-492AAAA-A and ICEA S-83-596-2001 for 50/125-micrometer multimode graded index optical fiber cable. Numerical aperture for each fiber shall be a minimum of 0.275. Cable construction shall be tight buffered type. Individual fibers shall be color-coded for identification. Cable shall be imprinted with fiber count and aggregate length at regular intervals. Cable shall be rated OFNR per NFPA 70. 2.5.3 Horizontal Distribution Fiber Optic Cable 2.5.3.1 Multimode Multimode fiber optic horizontal cable shall meet the requirements of TIA/EIA-568-B, TIA/EIA-492AAAAA, and ICEA S-83-596-2001 for 50/125-micrometer multimode graded index optical fiber cable. Numerical aperture for each fiber shall be a minimum of 0.275. Cable construction shall be tight buffered type, two strands. Individual fibers shall be color-coded for identification. Cable shall be imprinted with fiber count, fiber type, and aggregate length at regular intervals of 40”. Cable shall be rated and marked OFPN per NFPA 70. 2.5.4 Connecting Hardware 2.5.4.1 Connectors Connectors shall be SC-type with ceramic ferrule material with a maximum insertion loss of .5 decibels. Connectors shall meet performance requirements of TIA/EIA-568-B. Connectors shall be field installable. Connectors shall utilize adhesive for fiber attachment to ferrule. Connectors shall terminate fiber sizes as required for the service. Station cable faceplates shall be provided and shall be ivory in color, impact resistant plastic double gang, with double-sided female SC coupler. 2.5.4.2 Fiber Optic Patch Panels Patch panels shall be a complete system of components by a single manufacturer, and shall provide termination, splice storage, routing, radius limiting, cable fastening, storage, and cross-connection. Patch panels shall be 19” wall/rack-mounted panels. Patch panels shall provide strain relief for cables. Panels shall be provided with labeling space. Patch panel connectors and couplers shall be the same type and configuration as used elsewhere in the system. 2.5.4.3 Patch Cords Patch cords shall be cable assemblies consisting of flexible optical fiber cable with connectors of the same type as used elsewhere in the system. Optical fiber shall be the same type as used elsewhere in the system. Patch cords shall be complete assemblies from manufacturer‟s standard product lines. Page 20 of 40 2/8/12 Patch cords will be rated at the same or higher performance category as the cabling to which it connects and must meet the requirements described in TIA/EIA-568-B.1. 2.5.5 Outside Plant Cable Splices, Connectors, Cable Assemblies, and Organizers 2.5.5.1 Copper Cable Splices Copper cable splices shall consist of a moisture resistant, two- or three-wire connector held rigidly in place to assure maximum continuity. The correct connector size shall be used to accommodate the cable gauge of the cable to be supplied. Connectors used shall be listed in RUS Bulletin 1755I-100. 2.5.5.2 Splice Connectors Splicing connectors will be PICABOND filled and suitable for the gauge of conductor being spliced. Splices will be in fold-back configuration. 2.5.5.3 Fiber Optic Cable Splices Fiber optic cable splices shall consist of a fusion splice where two fibers are thermally fused together forming a continuous fiber length. 2.5.5.4 Pre-connectorized Single-Fiber Cable Assembly Fiber cable connectors shall be the biconical type, field installable, self-aligning, and self-centering. The connectors shall be terminated on a 10-foot length of single-fiber cable. The single-fiber cable shall contain a buffered optical fiber of the same type and specification as that used in the multi-fiber cable. 2.5.5.5 Fiber Optic Splice Organizer The splice organizer shall be suitable for housing fiber optic fusion splices in a neat and orderly fashion. The closure shall allow for a minimum of one meter of cable to be neatly stored without kinks or twists. The splice organizer in the closure shall provide individual strain relief for each splice. The case shall be suitable for reentry for future maintenance or modification, without damage to the cable or splices. All required splice organizer hardware, such as splice trays, protective glass shelves, and shield bond connectors shall be provided in the organizer kit. 2.6 MISCELLANEOUS ITEMS 2.6.1 Shield Connectors Shield bonding connectors, bond bars, braids, ribbons, clamps, etc. shall be IAW RUS Bulletin 1753F-803 (PE-33). Shield connectors shall make a stable, low-impedance electrical connection between the shield of the communications cable and a conductor such as a strap, bar, or wire. The connector shall be made of tin-plated tempered brass. Cable shields shall be bonded and continuous throughout the cable length. 2.6.2 Grounding Grounding hardware such as corrosion resistant wire, clamps, etc. necessary to properly bond/ground the cable in maintenance holes shall be provided. 2.6 2 Grounding Braid Grounding braid shall provide low electrical impedance connections for dependable shield bonding. The braid shall be made from flat tin-plated copper. 2.6.3 Cable Warning Tape Page 21 of 40 2/8/12 Cable warning tape shall be a minimum of 3” wide, orange in color, and suitable for buried applications. The warning tape shall be continuously imprinted with the words “WARNING - COMMUNICATIONS CABLE BELOW”, at not more than 48” intervals and shall be placed approximately 12” below finished grade levels of such lines to permit easy location of the duct line. 2.6.4 Nylon Pull Rope A ¼” nylon pull rope shall be installed in all empty duct runs & innerduct runs. 2.7 CATEGORY 6 COMMON LAN/VOICE (CLV) PATCH PANELS CLV patch panels shall consist of RJ-45 8-pin modular jacks (front of patch panel); with rear-installation type 110 insulation displacement terminations. 4-pair Category 6 wire from CLV jack at workstation shall terminate at the rear of patch panel. Size of patch panel shall reflect number of CLV drops on blueprint (i.e. one port on patch panel to each individual telephone/data outlet on the faceplate, plus 15 percent for future use). Mount CLV patch panels inside wall mounted lockable data cabinets 40”H X 24”W X 24”D deep (unless specified differently). All wiring and components shall be TIA/EIA-568-B compliant, wired to T568-B wiring configuration. Label patch panels IAW TIA/EIA-606-A 2.7.1 Voice Frequency (VF) Patch Panels VF patch panels shall consist of RJ-45 8-pin modular jacks (front of patch panel); with rear-installation type 110 insulation displacement terminations. Install 24AWG Tie Cable from the back of VF patch panels to type 110 punch down blocks mounted on the telecommunications room plywood backboard. All 8 wires of each RJ-45 jack shall be wired to the 110 type punch down block. The 110 type punch down block shall be labeled to identify corresponding RJ-45 jacks in the patch panel. Provide patch panel density to terminate number of telephone and other analog services identified in drawings plus 15 percent for expansion. All wiring and components shall be TIA/EIA-568-B compliant, wired to T568-BA wiring configuration. Label patch panels IAW TIA/EIA-606-A 2.8 DATA CABINETS Data cabinets shall be floor mounted enclosures with side panels, metal mesh lockable front & rear doors with identical keys, and depth-adjustable front and rear mounting rails. Horizontal cable management devices shall be integral to the cabinets. One 19” rack mounted power strip with 12 outlets with surge protection, a ground bus bar with a #6 AWG ground cable connected to the master ground bus bar, and a quad 120V, 20A outlet on 2ea dedicated circuit breakers terminated to NEMA 5-20 receptacles mounted within the cabinet. Depending on network equipment to be installed, 802 CS may also require a 208V, 30A outlet on a dedicated circuit breaker terminated to NEMA receptacle and mounted within the cabinet (specific NEMA receptacle type TBD dependent on equipment to be installed). Equipment racks shall provide capability to mount equipment 19” wide. The equipment rack shall be 72”H x 24”W x 42”D. Lockable data cabinets shall be Rittal, Blackbox or 802 CS approved equivalent. 2.9 MANHOLES Manholes will be type J-4, designed for telephone communications. Minimum dimensions of manholes will be 10‟L x 6‟W x 7‟H (or as specified). Each manhole wall that is opposite a duct entrance will have one pulling-in iron installed 6”-12” below the duct entrance level. LockDown-LockDry manhole locks will be installed on all communications manhole covers. 2.10 Cable Racks and Cable Rack Supports Communications industry standard cable racks, hooks and extensions shall be used to support cables in maintenance holes. The cable hooks shall be secured using cable rack locking clips. All cables and splice closures shall be supported using racking clips, cable racks, and cable hooks. If cable racks and supports Page 22 of 40 2/8/12 do not exist on sections that require support, the contractor shall be required to provide and install necessary hardware to support the cable. 2.11 CONDUIT Conduit will be bell-end type. Number and size will be specified. All ducts shall be placed a minimum of 30” below finished grade and encased in concrete. Conduits that are bore installed are not required to be encased in concrete. 2.12 COMMUNICATIONS CLOSETS Communications closets will be minimum 8‟ X 10‟, climate controlled with dedicated electrical circuits installed as specified. A minimum four each 4” conduits will be installed from the servicing communications manhole/handhole to the room. Conduits will run into the room and terminate at the wall centered under one of the TTBs. Page 23 of 40 2/8/12 PART THREE - EXECUTION 3.1 WORKMANSHIP All materials and equipment shall be installed in accordance with recommendations of the manufacturer to conform to the contract documents. 3.2 VERIFICATION OF DIMENSIONS The Contractor shall become familiar with the details of the work, verify dimensions in the field, and advise the Contracting Officer of any discrepancy before performing the work. 3.3 INSTALLATION 3.3.1 General System components and associated items shall be installed in accordance with NFPA 70, manufacturer‟s instructions, and as shown. Necessary interconnections, services, and adjustments required for a complete and operable signal distribution system shall be provided. Components shall be labeled in accordance with TIA/EIA-606-A. Penetrations in fire-rated construction shall be firestopped in accordance with Section entitled, FIRESTOPPING. Wiring shall be installed in accordance with TIA/EIA568-B. Wiring, terminal blocks, and outlets shall be marked in accordance with TIA/EIA-606-A. Cables shall not be installed in the same cable tray, utility pole compartment, or floor trench compartment with ac power cables. Cables not installed in conduit or wireways shall be properly secured and neat in appearance. 3.3.2 Horizontal Distribution System 3.3.2.1 Cable Laying 3.3.2.2 Interior wiring shall be installed in raceways, cable trays, and boxes as specified and terminated at station locations indicated. 3.3.2.3 All cables between the same points shall be run over the same path. 3.3.2.4 All cables and wiring shall be installed and terminated at all station locations as indicated on project drawings. Wiring shall take the form of a “Universal Wiring Plan” where horizontal cables are wired directly, home run fashion, from a distribution point to the appropriate modular jack plate, jack assembly, or floor jack to support the use of single-line type sets and electronic sets. Each individual cable run shall be continuous and uninterrupted and shall have no bridge taps, branches, splices or connections at any point. 3.3.2.5 Cables shall be installed in accordance with applicable fire codes, the manufacturer‟s recommendations and the requirements listed below. 3.3.2.6 There shall be no kinks, sharp bends or deformation in the installed cable. Any bends in the cable shall meet the recommendations of the cable manufacturer. 3.3.2.7 There shall be attachments, fastenings, and supports in conformance with the cable manufacturer‟s recommendations for the type and size cable, as installed, and consistent with the installed environment. 3.3.2.8 All vertical cable runs in duct or on ladder shall be tied with plastic straps or lacing twine at the top of the run and at least every 36” to prevent cable strain. Horizontal wiring shall not be bundled in groups larger than 16 cables. Page 24 of 40 2/8/12 3.3.2.9 A proper cable lubricant, approved by the Contracting Officer or representative, shall be applied at the manufacturer‟s recommended rate during the installation of the cable assemblies into conduits. No cable lubricant is to be utilized on cable assemblies installed in cable trays. 3.3.2.10 The cable shall be installed in a manner to prevent crushing, stretching, abrasion, puncture, and other mechanical damage. 3.3.2.11 All cables and cross-connects shall be neatly strapped, dressed and adequately supported. Provide cable clamps, strain relief devices, and ties as required to maintain the professional appearance of the installation and as recommended by the manufacturer. Where required, strain relief devices and ties shall be classified low smoke and low fume for use in air pleonasm in accordance with NFPA 70. 3.3.2.12 In no case shall any cable be attached to any conduit, pipe, associated supporting clamp or bracket, or false (suspended) ceiling system. 3.3.2.13 No less than 12” of slack material shall be left in each horizontal cable at each outlet and no less than 10” at the telecommunications closet, to facilitate maintenance. 3.3.2.14 Cables shall be installed in the conduits and cable trays provided and as indicated on the drawings. Cable shall not be installed outside of these wireways, including, but not limited to, freely suspended without support, on decks or walking surfaces, on suspended ceiling grid work, or on the work of other trades which are not specifically designated as wireways. 3.3.2.15 Horizontal cables shall not be installed in the same cable tray, utility pole compartment, or floor trench compartment with ac power cables. 3.3.2.16 Within the telecommunications closets, the cable shall be supported at all times by cable trays and cable ladders, down to the telecommunications/equipment racks or backboard as indicated on the drawings. Within the telecommunications rack or on the backboard, cable shall be supported by cable management rings and panels. 3.3.2.17 Cables shall be installed loosely within horizontal cable trays and conduits. Cables shall not be taped, laced or strapped to each other or bundled in groups larger than 16 cables. 3.3.2.18 Cable shall enter and leave the cable trays in a manner that conforms to the manufacturer‟s recommendations and the drawings. 3.3.2.19 Backbone and horizontal cable shall be properly terminated and tagged at both ends to provide permanent station identification. 3.3.3 Telecommunications (Telephone & LAN/Data) Outlets 3.3.3.1 Faceplates As a minimum, quad outlet faceplates shall be installed and labeled with permanent type labeling IAW paragraph 3.7.1. 3.3.3.2 Outlet Placement Telecommunications (Telephone & LAN/Data) outlets shall be installed in the approximate positions indicated on the drawings. All outlets shall be mounted 18” plus or minus 2” above the finished floor (AFF) or 6” plus or minus 2” for counter tops. All wall telephone outlets shall be mounted 54” plus or minus 2” AFF for standard telephones, and 34” AFF for handicap access telephones. 3.3.3.3 Wall Outlets Page 25 of 40 2/8/12 3.3.3.3.1 Unless specified otherwise, quad outlets shall be installed and flush-mounted on the wall. Each outlet shall be steel duplex ac power type box fastened in the wall, without assistance from the cover. Steel conduit (a minimum of 1”) shall extend from the distribution system directly to the outlet. 3.3.3.3.2 The quad outlets shall be installed as follows: Two blue connectors in the top left and top right positions and two white connectors in the bottom left and right positions. The connectors will be terminated to the T568-B standard. 3.3.3.4 Floor-mounted Telecommunications Outlets The outlet box shall be cast in place in the concrete slab, and shall connect to the under floor duct system. All outlets shall be connected individually to the under floor duct. 3.3.3.5 Floor-mounted Access Boxes The access box shall be cast in place in the concrete slab and shall connect to the distribution system with knockouts that accept standard 2” conduit box connectors. All access boxes shall be connected to individual conduits, home run to the telecommunications/LAN room. Floor-mounted access boxes used with systems furniture shall connect to the systems furniture communications track using ¾” (minimum) flex conduit(s) from the access box. The flex conduit shall be covered with non-metallic, non-conductive insulation and shall not be allowed to contact (electrically) any other distribution systems. Where required, flex conduit insulation shall be classified low smoke and low flame in accordance with NFPA 70. All box connector threads shall be covered by plastic bushings with the enclosure. Flex conduit runs shall be limited to one meter (approx. 40”). Flex conduit shall have electrical continuity to the access box. 3.3.3.6 Unshielded Twisted-pair Cable (UTP) Unshielded twisted-pairs shall have a minimum of 6” of slack cable loosely coiled into the telecommunications outlet boxes. Minimum manufacturers bend radius for each type of cable shall not be exceeded. Each pair shall be terminated on appropriate outlets, terminal blocks or patch panels. No cable shall be unterminated or contain unterminated elements. Pairs shall remain twisted together to within the proper distance from the termination as specified in EIA TSB 40-A. Conductors shall not be damaged when removing insulation. Wire insulation shall not be damaged when removing outer jacket. 3.3.3.7 Fiber Optic Cable Each fiber strand shall have connectors installed. The pull strength between the connector and the attached fiber shall be not less than 11.3 kg. The mated pair loss, without rotational optimization, shall not exceed 1.0 decibels. Fiber optic connectors shall be installed per TIA/EIA-568-B. 3.3.3.8 Pull-Cords Pull-cords shall be installed in all conduits serving telecommunications outlets, which do not initially have copper or fiber optic cables installed. 3.3.4 Terminal Blocks Terminal blocks shall be mounted in orderly rows and columns. Adequate vertical and horizontal wire routing areas shall be provided between groups of blocks. Industry standard wire routing guides shall be utilized. 3.3.5 Communications Raceways/Cable Trays 3.3.5.1 Communications Raceways Page 26 of 40 2/8/12 Communications raceways shall be installed as specified. Raceways shall allow sufficient space for cables to be installed without compromising the cable manufacturer's recommended minimum bending radii. Raceway fill shall not exceed 40 percent. Raceways indicated shall be installed in accordance with the previous requirements for conduit and tubing and with the additional requirements that no length of run shall exceed 50‟ for ¾” sizes, and 100‟ for 1” or larger sizes, and shall not contain more than two 90degree bends or the equivalent. Additional pull or junction boxes shall be installed to comply with these limitations whether or not indicated. Inside radii of bends in conduits of ¾” size shall not be less than 41/2” and 2” size or larger shall not be less than ten times the nominal diameter. 3.3.5.2 Cable Trays Cable trays shall form a wireway system, and shall be of nominal 6” depth and 12” or 18” wide, unless larger dimensions are required to maintain a maximum 50 percent cross sectional area cable fill. All cable trays outside of the communications rooms shall be ladder type and installed above the acoustical ceiling, and inside the communications rooms shall be ladder type and installed at 6” above equipment racks, and wall plywood backboards. Cable trays shall be constructed of aluminum, copper-free aluminum or zinc-coated steel. Trays shall include dimension and direction-transition fittings, splice and end plates, cable dropout chute fittings, conduit-end tray fasteners and miscellaneous hardware all provided by the cable tray manufacturer. Edges, fittings and hardware shall be finished free from burrs and sharp edges. Conduits terminated at cable trays shall be provided with insulated throat bushings. Cable tray transition fittings shall have not less than the load-carrying ability of straight tray sections and shall have the manufacturer‟s minimum standard radius. Radius of bends shall be 12”. Routing of cable trays shall be parallel or perpendicular to walls and ceilings and shall not be run diagonally across rooms. Cable trays shall penetrate fire rated walls and partitions in accordance with Article 300 of NFPA 70. Fire stop any cable tray penetrations through fire walls to meet fire resistance ratings required in ASTM E81411a or UL 1479. Ground cable tray with a #6 AWG ground cable & connect to the ground bus bar in each Comm room. 3.3.5.3.1 Support The cable tray shall be supported using the manufacturers' recommended support brackets, threaded rods and associated hardware. The cross strap shall not be used to support the overhead cable tray. Vertical structures such as cabinets, relay racks, frames and bays, attached to the floor for panelmounted equipment, may be used for supporting associated cable ladder runs. The installation of all cable trays, ducts, and ladders shall conform to industry standards. 3.3.5.4 Grounding The cable pathway system shall be grounded to the facility ground at intervals not to exceed 75‟. This grounding may be accomplished through the mounting hardware or by separate wire (minimum #6 AWG). 3.3.5.5 Wall Transitions The Contractor shall seal holes in walls around signal ducts and conduits equivalent to that of the wall. Duct covers shall be spliced on each side of the wall (with joint shields) to allow a non-removable section of cover within the wall. Any reductions required at firewalls shall provide multiple runs through the wall totaling at least as many square inches of area as the duct or conduit running to the wall. 3.3.5.6 Firestopping It shall be the responsibility of the Contractor to perform all sealing, filling, or firestopping through bulkhead fittings with materials and practices in compliance with applicable codes, regulations and directives. 3.3.6 Conduit Duct Below Slab-on-grade or in the Ground Page 27 of 40 2/8/12 All cables below slab-on-grade shall be protected by a conduit system. No conduit system shall be installed horizontally within concrete slab-on-grade. For slab-on-grade construction, horizontal runs of rigid plastic, rigid steel or electrical metal tubing (EMT) shall be installed below the floor slab. Conduit passing vertically through slabs-on-grade shall be rigid steel or EMT. Rigid steel or EMT conduits installed below slab-on-grade or in the earth shall be field-wrapped with 0.010 inch thick pipe-wrapping plastic tape applied with a 50 percent overlay, or shall have a factory-applied polyvinyl chloride, plastic resin, or epoxy coating system. 3.3.6.1 Duct and Fittings, Non-metallic Type for Installation Underground Wall thickness and fittings shall be suitable for the application. Ducts shall be single, round-bore types. Ducts shall be of the same material when used for applications requiring the same type of wall thickness. 3.3.6.2 Plastic Duct NEMA TC 6 thick-wall type DB. Conduit fittings shall conform to the applicable NEMA standards, except that where NEMA standards for conduit fittings do not exist for the type of plastic installed, fittings shall be as recommended by the conduit manufacturer. 3.3.7 Duct Lines Duct lines shall be non-encased direct-burial, thick-wall type (Schedule 40) for duct lines between manholes, handholes, pullboxes and building entry or as shown on the drawings. Where ducts are installed under roadways, parking lots or asphalt areas they will be encased in concrete. Never allow more than one bend between manholes. Ducts should enter manhole perpendicular to manhole wall. Ducts shall enter manholes as near as possible equidistant floor and roof. 3.3.7.1 Duct Installation Numbers and sizes (4” duct typical) of ducts shall be installed as indicated. Duct lines shall be laid with a minimum slope of 4” per 100‟. Depending on the contour of the finished grade, the high-point may be at a terminal, a manhole, a handhole, pullbox, or between manholes, pullboxes or handholes. Ducts shall be provided with end-bells whenever duct lines terminate in manholes, pull boxes or handholes. When power and comm ducts cross each other, every effort will be made to cross at right angles while maintaining a minimum separation of 3” of concrete or 12” of earth between the power and comm ducts. Duct line markers shall be provided as indicated at the ends of long duct line stub-outs or for other ducts whose locations are indeterminate because of duct curvature or terminations at completely below-grade structures. In lieu of markers, a cable warning tape shall be used. The cable warning tape shall be a minimum of 3” wide, orange in color, and suitable for buried applications. The warning tape shall be continuously imprinted with the words “WARNING - COMMUNICATIONS CABLE BELOW” at no more than 48” intervals and shall be placed approximately 12” below finished grade levels of such lines to permit easy location of the duct line. A ¼” nylon pull rope shall be installed in all empty duct runs. All ducts will be sealed with duct sealant in accordance with specification paragraph 3.3.7.6. 3.3.7.2 Duct Treatment Ducts shall be kept clean of concrete, dirt, or foreign substances during construction. Field cuts requiring tapers shall be made with proper tools and match factory tapers. After a duct line is completed, a standard flexible mandrel shall be used for cleaning followed by a brush with stiff bristles. Mandrels shall be at least 12” long and have diameters ¼” less than the inside diameter of the duct being cleaned. 3.3.7.3 Duct Storage Ducts shall be stored to avoid warping and deterioration with ends sufficiently capped to prevent entry of water or solid substances. Ducts shall be thoroughly cleaned before being installed. Plastic ducts shall be stored on a flat surface and protected from the direct rays of the sun. Page 28 of 40 2/8/12 3.3.7.4 Installation of Couplings Joints in each type of duct shall be made in accordance with the manufacturer‟s recommendations for the particular type of duct and coupling selected. In the absence of specific recommendations, all various types of duct couplings shall be made watertight as specified. 3.3.7.5 Plastic Duct Joints Duct joints shall be made by brushing plastic solvent cement on insides of plastic coupling fittings and on outsides of duct ends. Each duct and fitting shall be slipped together with a quick one-quarter-turn twist to set the joint tightly. 3.3.7.6 Duct Sealant After cable as been placed, each lateral duct at the building, each entrance and exit duct in each manhole, and each riser and pedestal location shall be sealed. Compounds for sealing ducts and conduit shall have putty-like consistency, workable with the hands at temperatures as low as 35 degrees F., and shall not harden materially when exposed to the air. Compounds shall readily caulk or adhere to clean surfaces of plastic or metallic raceways, cable shields, jackets, covers, or insulation. Compounds shall form a seal without dissolving, noticeably changing characteristics, or removing any of the ingredients. Compounds shall have no injuries effect upon the skin of workers. 3.3.8 Building Entry Conduit Conduits for underground telephone cable shall be installed as indicated and as shown on the drawings. 3.3.9 Telephone Cable All telephone cable shall have the number of insulated twisted-pairs as indicated or as shown on the drawings. All telephone cables shall be installed in raceways unless otherwise indicated on the drawings. 3.3.9.1 Guaranteed Pairs All pairs in each cable shall be usable. All conductors for incoming and tie-cables shall be usable, except those identified as defective by the manufacturer. 3.3.9.2 Splicing Splicing shall be in accordance with REA PC-2. All pairs shall be spliced. All outside cable splices shall be watertight. Cable shields shall be bonded together at all cable splices with bonding harnesses to maintain sheath continuity. Splices shall be grounded to the manhole grounding system in accordance with paragraph 3.6.1. 3.3.9.3 Underground Cable Underground cable installation shall be accomplished in accordance with the requirements set forth in RUS Bulletin 1751F-644. When installing cable in existing conduit, the following applies: the Contractor may use existing conduit or innerduct only when at least one additional vacant conduit is available. Any conduit or innerduct used will be identified to the base Communications Squadron prior to use. If installation will utilize the last vacant conduit additional conduit will be installed per para 3.3.7.1. For cable installed in ducts and conduit, a cable feeder guide shall be used between the cable reel and the face of the duct and conduit, to protect the cable and guide it into the duct and conduit as it is payed off the reel. As the cable is payed off the reel, it shall be inspected for jacket defects. Precautions shall be taken during installation to prevent the cable from being kinked or crushed. A pulling eye shall be attached to the cable and used to pull the cable through the duct and conduit system. Cable shall be Page 29 of 40 2/8/12 hand-fed and guided through each manhole. As the cable is payed off the reel into the cable-feeder guide, it shall be sufficiently lubricated with a type of lubricant recommended by the cable manufacturer. Where the cable is pulled through a manhole, additional lubricant shall be applied at all intermediate manholes. Dynamometers or load-tension instruments shall be used to ensure that the pulling line tension does not exceed the installation tension value specified by the cable manufacturer. The mechanical stress placed upon a cable during installation shall not be such that the cable is twisted or stretched. Cables shall be handled and placed in such a manner as to avoid kinks and other shield deformities. Cable kinked or flattened shall not be installed. Lead sleeves or duct splices shall not be permitted. Cable racks and hooks shall be installed in manholes to support installed cables. 3.3.9.4.1 Outdoor Cable Installation All outdoor connections shall be weatherproof through the use of weather boots or other approved methods. All filled cable splice points in underground facilities shall be encapsulated using re-enterable type splice cases and encapsulant compound. All air core cable splice points shall be sealed in an airtight pressure type splice case and shall be tested with 15 PSI back pressure to insure there are no leaks. 3.3.9.4.2 Innerduct Install Maxcell or equivalent Inner Duct. Install three (3) each three (3) cell, 1.25” O.D. inner duct (one w/ tracer wire), in one of the new ducts. Tracer wire will be connected throughout the entire length of the mesh installation. Only one cable shall be installed in a given innerduct. Existing and new unoccupied innerducts shall be trimmed leaving 50 mm exposed. 3.3.9.4.3 Surge Protection All cable and conductors that serve as communication lines through off-premise lines shall have surge protection installed at each end which meets the requirements of REA PE-80. 3.3.10 Manholes Minimum dimensions of manholes will be 10‟ long x 6‟ wide x 7‟ high (or as specified). Manholes will be installed with long wall parallel to duct back coming from C.O. If a bonding ribbon does not exist, contractor shall provide and install one (1) each 10‟ x 3/4” diameter ground rod, bonding ribbon and all associated hardware. 3.3.10.1 Contractor Use of Government Manholes The Contractor shall pump maintenance holes when required. Following installation the Contractor shall ensure the maintenance holes are clean and free of materials and debris, if caused by the installation. 3.3.10.3 Restoration of Manholes The Contractor shall be responsible for site restoration. Restoration at each location shall be to the original condition. Note: 802CS Cable Maintenance will identify to the Contractor those maintenance holes, if any, that are permit required and coordinate with Base Safety Office for procedures to be followed by Contractor personnel when working in the maintenance holes. 3.4 UNDERGROUND CABLE SYSTEMS 3.4.1 Bending Radius Bending radius shall conform to EIA/TIA & BICSI standards under load and no-load conditions. Page 30 of 40 2/8/12 3.4.2 Electrical Protection The contractor shall provide electrical protection IAW T.O. 31W3-10-13 paragraphs 10-3 through 10-11, as applicable, and ANSI-J-STD-607-A. 3.4.3 Underground Splice Closures Splice cases used at Lackland will be Preformed Line Products (PLP) stainless steel splice case with filling flange. Splices shall be sealed with stainless steel closures of a size adequate for the size and type (foldback) of splice to be enclosed. (12.5 x 28”, 9.5”x 28”, 6.5”x 28 or 4”x 28”) 3.4.4 Encapsulant Lackland does not use encapsulant within the splice cases. Splices cases will require to be flash tested and have a minimum of 7 to 9 psi of back pressure. Splice Cases must hold pressure for 24 hours. 3.4.5 Duct Sealing After installing cable in a duct entering a maintenance hole or a building, seal around cable with a universal duct plug or removable putty sealant (duxseal). Duxseal is authorized for base use and has MSDS on file with 802CES. 3.4.6 Testing The Contractor shall furnish all test equipment and personnel required to conduct testing. During any testing phase, the Government reserves the right to perform any of the Contractor performed inspections and tests to assure results conform to prescribed requirements. The Contractor shall record all inspections and tests as they are accomplished and make all test sheets/results available for 802CS/SCX representative review as tests are completed. The Contractor shall notify the 802CS/SCX representatives at least three working days prior to any testing and shall make available to them all testing standards and criteria used to accomplish testing. All copper cable testing will be IAW RUS Bulletin 1753F-201. 3.4.7 Multi-pair Cable Prior to splicing activities at any particular splice location, test pairs to be affected by splicing activities for cable faults (grounds, shorts, crosses, and opens) and splicer errors (splits, reverses, and transpositions). Document these readings and furnish copies to 802CS/SCX representatives. 3.4.8 Shield Continuity After splicing activities at any particular splice location, test shall be made to ensure that shield is electrically continuous across the splice. 3.4.9 Cable Faults and Splicer Errors Test cable in accordance with T.O. 31w3-10 series. Any cable faults or splicing errors detected, if caused by the installation, shall be corrected in the splice in which they were made. 3.4.10 Pressure Testing Stainless Steel splice cases shall be flash tested in accordance with manufacturer‟s instructions. After flash testing, the splices cases will require having a minimum of 7 to 9 psi of back pressure and must hold this pressure for 24 hours. Page 31 of 40 2/8/12 3.5 BURIED CABLE SYSTEMS 3.5.1 Base Civil Engineering Work Clearance Requests The contractor shall obtain a Base Civil Engineering Work Clearance Request, AF Form 103, prior to any trenching or digging. The contractor shall obtain an approved Base Civil Engineering Work Request, AF Form 332, prior to any facility, maintenance hole or hand-hole modification. The contractor shall trench, excavate, confined space entry, confined space atmospheric testing/forced air ventilation, and mark and barricade open trenches IAW OSHA standards, and local procedures 3.5.2 Multi-pair Telephone Cable Cable to be installed shall be RUS Specification PE-89. Gopher (armor) protection is required. 3.5.3 Splicing 3.5.3.1 Splice Connectors Splicing connectors will be filled PICABOND suitable for the gauge of conductor being spliced. Splices will be fold-back configuration. 3.5.3.2 Shield Bonding Connectors Shield bonding connectors, bond bars, braids, ribbons, clamps, etc. shall be IAW RUS Bulletin 1753F-803 (PE-33). Cable shields shall be bonded and continuous throughout the cable length. 3.5.3.3 Outside Plant Multi-pair Cables Multi-pair cables shall be spliced IAW 31W3-10-13 and RUS Bulletin 1753F-401, using PICABOND connectors in the butt configuration (where 2 conductors enter the same side of the PICABOND) and the fold-back method. Use connectors appropriate for the gauge of conductor being spliced. All cable pairs within a cable shall be properly spliced. Binder group integrity shall be adhered to at all times. Applicable color codes shall be followed IAW RUS Bulletin 1753F-401. All Multi-pair splices shall be enclosed in a sealed closure. The contractor shall ensure no splice is left unattended unless it has been sealed to prevent the entrance of moisture. The Contractor and the designated government Quality Assurance representative shall inspect all splices prior to sealing the closure. If, for any reason, moisture contaminates a splice, all affected connectors shall be replaced and the entire splice retested. 3.5.3.4 Splicing Sequence Sequence is at the discretion of the Contractor with 802CS Cable Maintenance approval. However, a pre-test will be accomplished on the existing cable prior to splicing. A post-test shall be conducted and documented on all affected pairs once splicing is completed. 3.5.4 Marking 3.5.4.1 Cable Tags All tags shall be permanently labeled and corrosion resistant. Install cable tags in all maintenance holes, terminals and BD pedestal at all affected locations. If there is a splice in the maintenance hole, install a tag on each side of the splice. Information on the tag shall identify cable by size, type, cable number and count. New cables and all affected existing cables shall be tagged / retagged at each terminal location and in each maintenance hole. Example: P9-24PF M01, 1-900 3.5.5 Buried Splice Closures Page 32 of 40 2/8/12 Splice cases used at Lackland will be Preformed Line Products (PLP) stainless steel splice case with filling flange. Splices shall be sealed with stainless steel closures of a size adequate for the size and type (fold back) of splice to be enclosed (i.e.: 12.5 x 28”, 9.5”x 28”, 6.5”x 28 or 4”x 28”). All buried splices will be encapsulated with appropriate re-enterable compound. 3.5.6 Encapsulant Lackland does use encapsulant within the splice cases. Splices cases will be encapsulated with reenterable compound. Re-enterable compound will be compatible with communications type cable. 3.5.7 Cut Cable Restorations If determined cable was cut do to contractor error, critical circuits must be restored within 8 hours. All other circuits must be restored with 24 hours (at least temporary restoration). 3.6 OUTSIDE PLANT CABLE SPLICING 3.6.1 Copper Conductor Splices Copper conductor cable splicing shall be accomplished in accordance with RUS Bulletin 1753F-401 (PC2). 3.6.2 Fiber Optic Splices All fiber optic splicing will be fusion spliced. Fiber optic splicing shall be in accordance with the manufacturer‟s recommendation and shall exhibit an insertion loss not greater than 0.2 decibels for fusion splices. 3.7 TERMINATION 3.7.1 General Cables and conductors shall sweep into termination areas; cables and conductors shall not bend at right angles. Manufacturer‟s minimum bending radius shall not be exceeded. When there is multiple system type drops to individual workstations, relative position for each system shall be maintained on each system termination block or patch panel. 3.7.2 Procedure All inside wiring telephone cables shall be numbered; terminated at the telephone/data jack assemblies end, terminal block end, and tagged at both ends to provide permanent identification. Termination of inside-wire at the telephone terminal backboard shall be made on type 110 terminal blocks. Inside wiring cables not installed in raceways/conduits shall be properly secured using cable tie wraps. Terminations shall be done in accordance with TIA/EIA-568-B. All equipment shall be Category 6 rated. 3.7.3 Cable Protector Modules Cable protector modules shall be mounted directly (5‟ at center AFF) & positioned on the left half of the backboard. The assemblies mounted on each vertical frame shall be connected with a #6 AWG copper conductor to provide a low resistance path to the building ground. Note: Protector modules will be furnished as part of the project. Consult drawings or contract for further direction. 3.7.4 Terminal Blocks Page 33 of 40 2/8/12 Type 110 terminal blocks shall be provided at the telephone terminal backboard to terminate and crossconnect all analog copper lines. Separate 110 terminal blocks shall be used to terminate the Voice Frequency (VF) patch panel located in the equipment cabinet/rack. Terminal blocks shall be stenciled to indicate telephone/outlet assembly numbers using black marking on designation strips (provided in 110 type hardware backboard kits). Use sequential numbering that doesn‟t exist on new or existing blocks. The telephone/patch panel outlets/assemblies will be stenciled on the faceplate with the same number as its location number on the terminal blocks. All equipment shall be Category 6 rated. Note: Crossconnections at telephone terminal backboard from cable protector modules (if installed) to 110 blocks sized to terminate the entire cable will be accomplished by the contractor. Cross connects from the cable entrance 110 blocks to the VF patch panel 110 blocks will be accomplished by the contractor. Consult drawings or contract for further direction. 3.7.5 Common User Telephone & LAN/Data Outlets Termination at each respective telephone & LAN/Data outlet assembly shall be made on 8-pin modular jack assemblies mounted on a quad 4-hole outlet faceplate (unless otherwise indicated on the drawings). Common User outlets will be labeled on the faceplate IAW 38 EIG Handbook 33-01/TIA/EIA-606-A. The completed installation shall meet TIA/EIA-568-B industry standard for “Flush-mounted terminals and connectors.” All equipment shall be Category 6 rated. 3.7.6 Telephone Terminal Backboard (TTB) 3.7.6.1 Backboard Placement The Contractor shall provide and install at least 2 TTB‟s per BICSI standards. The backboards shall be mounted to the wall at all corners with minimum 3/8” hardware, and shall be constructed of ¾” ACX plywood with finished side facing outward, with two coatings on both sides of fire retardant paint. The left half of the TTB shall be used for mounting the telephone feeder cable protection units. The right half of the TTB will be used for mounting and terminating of I/W telephone cables, terminal blocks, & patch panels. 3.7.6.2 Backboard Configuration A 4-plex dedicated 120 VAC; 20-amp circuit will be installed directly under each backboard, running the circuit in conduit (under the false floor where such exists). Both vertical and horizontal cable management rings and panels shall be installed on the backboard as indicated on the drawings. 3.7.6.3 Terminal Blocks Terminal blocks shall be mounted in orderly rows and columns. Adequate vertical and horizontal wire routing areas shall be provided between groups of blocks. Industry standard wire routing guides shall be utilized. 3.7.7 Equipment Racks (Data Cabinets) 3.7.7.1 Rack Placement Exact rack placement will be specified by the Communications Squadron. Racks shall be leveled and bolted to the true floor at all corners with minimum 3/8” hardware and to any adjacent racks. Racks must be positioned to allow a minimum 36” of clearance in front and behind the racks. Racks must be placed to allow complete opening of other fixed area enclosure doors or covers. 3.7.7.2 Rack Configuration Page 34 of 40 2/8/12 A dual outlet dedicated 120 VAC; 20-amp circuit will be mounted in each rack, running the circuit in conduit (under the false floor where such exists). Both vertical and horizontal cable management rings and panels shall be installed in the racks as indicated on the drawings. 3.7.7.3 Copper Patch Panels Category 6 copper patch panels shall be mounted in equipment racks with sufficient modular jacks to accommodate the installed cable plant plus fifteen percent (15%) spares. Cable guides shall be provided above, below and between each panel. 3.7.7.4 Fiber Optic Patch Panels Fiber optic patch panels shall be mounted in equipment racks with sufficient ports to accommodate the installed cable plant plus fifteen percent (15%) spares. A slack loop of 36” of fiber shall be provided within each panel. The outer jacket of each cable entering a patch panel shall be secured to the panel to prevent movement of the fibers within the panel, using clamps or brackets specifically manufactured for that purpose. 3.7.8 Rack Mounted Equipment Equipment to be rack mounted shall be securely fastened to racks by means of the manufacturer‟s recommended fasteners. 3.7.9 Concrete Pull-boxes and Manholes Concrete pull-boxes and manholes shall consist of pre-cast reinforced concrete boxes, extensions, bases, and covers. A minimum of 3” to 6” of sand or rock suitable as a base material shall be placed in the bottom of the excavation prior to the setting of the vault. The base material shall be compacted and graded level at the proper elevation to receive the manhole in relative position to the conduit grade. Concrete reinforcing shall be that which is regularly used in the standard product of the manufacturer. Each manhole shall be equipped with a standard ladder of hot-dipped galvanized steel construction nonslip rungs. One end of the ladder shall be formed into hooks to engage the handhole step. Pull-box and manhole tops shall be flush with sidewalks or curbs and placed ½” above surrounding grades when remote from curbed roadways or sidewalks. Install two cable support brackets on each sidewall of handhole and three support brackets on each sidewall of manhole. Each cable support bracket shall have a minimum of two 7” cable steps installed. Finish conduit flush with interior walls and grout around conduits. Bell-ends shall be required on the end of each conduit and finish grout applied. Install bellends flush with wall of pull-box/manhole. Covers for pull-boxes and manholes shall be able to withstand traffic load bearing applications. Covers shall be marked “TELEPHONE.” Each pull-box/manhole shall be equipped with one copper ground-rod pounded into sump area of pull-box/manhole. Leave groundrod exposed 6” above base of sump. Sump shall be broken and all loose concrete removed from pullbox/manhole. Size of pull-boxes/manholes shall be as shown on the drawings. Minimum size of pull-box: 4‟W X 4‟L X 4‟D. Minimum size of manhole: 5‟W X 10‟L X 7‟D. 3.8 GROUNDING 3.8.1 General Signal distribution system ground shall be installed in the telecommunications entrance facility and in each telecommunications closet in accordance with ANSI-J-STD-607-A. NOTE: Except where specifically indicated otherwise, all exposed non-current carrying metallic parts of telephone & LAN/Data equipment, cable shields, and terminals shall be grounded. Equipment racks (i.e. LAN/Data cabinets) shall also be connected to the respective Comm room ground bus bar. 3.8.2 Telecommunications Main Ground Bus Bar (TMGB) Page 35 of 40 2/8/12 Install a 10”L X 4”W X 1/4”T ground bus bar with 1/4” DIA. attachment holes at the base of TTB, left side, 6” below top of each TTB in each Comm room.. Use wall mounting brackets with insulators. Install a #4 AWG ground cable from master Bldg ground & terminate to the ground bus bar. Apply No-Ox grease to the ground terminal lugs installed. 3.8.3 Terminals Install a #6 AWG solid copper conducting ground-cable from the telephone cable protector/s and data cabinets to and terminate these cables (using terminal lugs), onto the ground bus bar in the respective Comm room. Install a ground tag at point of connection to the cable protectors. Provide No-OX grease to terminal lugs used. 3.8.3 Manholes A ¾” DIA, 10‟ copper clad steel ground rod will be driven to a depth so that 6” of the ground rod remains above the finished manhole floor. Resistance to ground of 10-ohm or less is desired. A soft-tinned copper, 3/8”W X 1/16” thick bonding ribbon shall be used to ground all splices to the manhole ground system. Bonding ribbon shall be attached to the manhole walls on 18” centers with bonding ribbon clamps. 3.8.4 Bonding Ribbon Clamps Bonding ribbon clamps shall be attached to walls of the manhole using ¼” X 1” hammer-drive anchors. 3.9 ADMINISTRATION AND LABELING 3.9.1 Labeling 3.9.1.1 Cable Labeling All cables shall be labeled in accordance with TIA/EIA-606-A within 6” of the connection with wrap-around adhesive write-on strips that seal the writing behind clear tape. The Contractor shall label all cables at each end with a unique identifier. All cables shall be labeled at each connection with their functions, local connection point, and remote connection point. Labels shall be permanent and readable from 12”. Labels shall not be removable by normal cable movement, nor shall they be easily removed by hand. 3.9.1.2 Wall Plate Labeling All wall plates shall be labeled such that the numbering scheme is left-to-right starting at drawing North on the floor plan and continuing in a clockwise direction. The top position of the quad outlet wall plate shall be marked with the following information: STR or PTR: Rack#: Patch Panel: Port#: STR or PTR where distant end of cable terminates Rack # where distant end of cable terminates Patch panel # where distant end of cable terminates Port # at the patch panel where distant end of cable terminates The bottom position of the quad outlet wall plate shall be marked with the following information: Wall plate # in the room Room # where installed 3.9.1.3 Patch Panel Labeling Page 36 of 40 2/8/12 All patch panels shall be labeled with corresponding jacks and wall plate numbers where distant end of cable terminates. 3.9.1.4 Terminal labeling All outside plant cable terminals shall be labeled with terminal #, cable #, and cable count. 3.9.2. Marking Cable Tags All tags shall be permanently labeled and corrosion resistant. Install cable tags in all maintenance holes, terminals and BD pedestals at all affected locations. For splices in the maintenance hole, install a tag on each side of the splice. Information on the tag shall identify cable by size, type, cable number and count. New cables and all affected existing cables shall be tagged/retagged at each terminal location and in each maintenance hole. Example: Fiber tags 12L8.3F Bxxx (ITN bldg)-171S (end bldg), 1-12 Copper Tags P1-19PF x01, 1-100 x = L (LAFB), M (LTA), K (Kelly) 3.10 CABLE TELEVISION INSTALLATION All cable television wiring installations for Lackland AFB facilities must meet the service provider‟s specifications. The installation must be accomplished by a contractor who is authorized and certified by the service provider. The service provider is: Time Warner Cable Business Services 1900 Blue Crest Lane San Antonio, TX 78247 Contact the 802d Communications Squadron for current Time Warner Cable POC information. 3.11 INSTALLATION INSPECTIONS Quality Assurance shall be provided through the performance of pre-installation, in-progress, and final inspections. 3.11.1 Pre-installation Inspection The Contractor shall inspect all equipment and materials to be utilized in this project. All items shall be verified for compliance with the requirements of this document, the installation, and other referenced standards. This inspection shall also include determination of site preparation, availability of installation materials, status of Government-furnished equipment (GFE), Contractor-furnished equipment (CFE), local purchase request (LPR) items, as well as leased equipment and transmission facilities (as applicable). The Contracting Officer or representative will participate in and witness the pre-installation inspection. 3.11.2 In-progress Inspections The Contractor shall perform in-progress inspections, which shall include visual inspections of equipment condition, wiring, splicing, fiber-optic cabling, mounting and placement of equipment, miscellaneous hardware and adherence to safety procedures. The Contracting Officer or representative will also perform in-progress inspections as required and verify that the Contractor in-progress inspections are performed in order to assure compliance with the specified installation criteria. 3.11.3 Final Inspection Page 37 of 40 2/8/12 The Contractor shall conduct a final inspection that encompasses all phases of the installed project. This inspection shall be conducted to verify that all phases of the contract have been completed according to the contract requirements and proper installation practices have been followed. This inspection shall include a review of the „red-lined‟ drawings, if applicable. The Contracting Officer or representative will participate in and witness the final inspection. 3.11.4 Corrective Action and Verification Inspection The Contractor shall correct any areas of noncompliance with requirements that are revealed by inspections. Following correction, a re-examination of previous noncompliance areas will be conducted at the discretion of the Contracting Officer or representative. 3.12 COMMUNICATIONS DISTRIBUTION SYSTEM TESTING 3.12.1 General Materials and documentation to be furnished under this specification are subject to inspections and tests. All components shall be terminated prior to testing. Equipment and systems will not be accepted until the required inspections and tests have been made, demonstrating that the signal distribution system conforms to the specified requirements, and that the required equipment, systems, and documentation have been provided in writing. 3.12.2 Procedure The Contractor shall provide all necessary personnel, equipment, instrumentation, and supplies required to properly test and document the transmission media parameters of the voice and data transmission systems. The Contractor shall also notify the Base Communications Squadron 21 days before the acceptance tests are to be conducted. NOTE: The Government shall retest to verify Contractor‟s final test results. Specific tests shall include: 3.12.3 Unshielded Twisted-Pair Tests All metallic cable pairs shall be tested for proper identification and continuity. All opens, shorts, crosses, grounds, and reversals shall be corrected. Correct color-coding and termination of each pair shall be verified in the communications closet and at the outlet. Horizontal wiring shall be tested from and including the termination device in the communications closet to and including the modular jack in each room. Backbone wiring shall be tested end-to-end, including termination devices, from terminal block to terminal block, in the respective communications closets. These tests shall be completed and all errors corrected before any other tests are performed. 3.12.4 Copper Cable Tests Cable tests shall be performed with all cables in place. Testing shall be performed in accordance with RUS Bulletin 345-63, (PC-4) for Shield Continuity, Conductor Insulation Resistance, and DC Loop Resistance Measurements and TIA/EIA-568-B for attenuation, capacitance, and near-end crosstalk. All defective pairs, except those identified as defective by the manufacturer, in accordance with the applicable cable specifications, shall be made good by the Contractor. Cable test results shall be documented and provided to the Communications Squadron. 3.12.5 Category 6 Circuit Tests All Category 6 circuits shall be tested to confirm that each circuit transmits data at the industry standard rated capacity (250 MHz for Category 6 data transmission). 3.12.6 Fiber Optic Cable Tests - Outside Plant Page 38 of 40 2/8/12 Connectors shall be visually inspected for scratches, pits or chips and shall be reterminated if any of these conditions exist. The following optical tests shall be performed: Optical Time Domain Reflectometer (OTDR) Test, and Attenuation Test. These tests shall be performed on the completed end-to-end spans which include the near-end pre-connectorized single-fiber cable assembly, outside plant as specified, and the far-end pre-connectorized single-fiber cable assembly. The following acceptance tests shall be performed for each fiber in the completed cable length. Single-mode fibers do not require Bandwidth Test. 3.12.6.1 Optical Time Domain Reflectometer (OTDR) Test The OTDR test shall be used to determine the adequacy of the cable installations. The OTDR tests will show any irregularities, such as discontinuities, micro-bending, improper splices, for the cable span under test. Hardcopy fiber signature records shall be obtained from the OTDR for each fiber in each span and shall be included in the test results. The OTDR test shall be measured in both directions. A reference length of fiber, 1-km minimum, used as the delay line, shall be placed before the new end-connector and after the far-end patch panel connectors for inspection of connector signature. 3.12.6.2 Attenuation Test End-to-end attenuation measurements shall be made on all fibers, in both directions, using an 850 nanometer light source at one end and the optical power meter on the other end. These tests will be used to verify that the cable system attenuation requirements are met. The measurement method shall be in accordance with EIA/TIA-455-53A (FOTP-53). 3.12.7 Fiber Optic Cable Tests - Facility Interior 3.12.7.1 Contractor’s Field Test The Contractor shall verify the complete operation of the data transmission system in conjunction with field testing associated with systems supported by the fiber optic data transmission system as specified prior to formal acceptance testing. Field tests shall include a flux density test. These tests shall be performed on each link and repeated from the opposite end of each link. 3.12.7.2 Optical Time Domain Reflectometer (OTDR) Tests OTDR tests shall be performed using the fiber optic test procedures of TIA/EIA-455-59-A (FOTP-59) and TIA/EIA-455-60-A (FOTP-60). An OTDR test shall be performed on all fibers of the fiber optic cable on the reel prior to installation. The OTDR shall be calibrated to show anomalies of 0.2 decibels as a minimum. Photographs of the traces shall be furnished to the Government. An OTDR test shall be performed on all fibers of the fiber optic cable after it is installed. The OTDR shall be calibrated to show anomalies of 0.2 decibels as a minimum. If the OTDR test results show anomalies greater than one decibel, the fiber optic cable segment is unacceptable to the Government. The unsatisfactory segments of cable shall be replaced with a new segment of cable. The new segment of cable shall then be tested to demonstrate acceptability. Photographs of the traces shall be furnished to the Government for each link. 3.12.7.3 Power Attenuation Test Power attenuation test shall be performed at the light wavelength of the transmitter to be used on the circuit being tested. The flux shall be measured at the fiber optic receiver end and shall be compared to the flux injected at the transmitter end. There shall be a jumper added at each end of the circuit under test so that end connector loss shall be validated. Rotational optimization of the connectors will not be permitted. If the circuit loss exceeds the calculated circuit loss by more than 2 decibels, the circuit is unsatisfactory and shall be examined to determine the problem. The Government shall be notified of the problem and what procedures the Contractor proposes to eliminate the problem. The Contractor shall prepare and submit a report documenting the results of the test. Page 39 of 40 2/8/12 3.12.7.4 Gain Margin Test The Contractor shall test and verify that each circuit has a gain margin that exceeds the circuit loss by at least 6 decibels. 3.12.8 Test Results Written test results and as-built drawings shall be provided to the Base Communications Squadron within 14 days after completion of tests. This applies to all fiber optic cable and copper wire installations. 3.13 REPAIR OF EXISTING WORK All work shall be carefully laid out in advance where cutting, chasing, or drilling of floors, walls, partitions, ceilings or other surfaces as necessary for the proper installation, support, or anchorage of the conduit or raceway. This work shall be carefully done, and any damage to building, piping, or equipment shall be repaired by skilled craftsmen of the trades involved at no additional cost to the Government. Page 40 of 40 2/8/12