U905 Catalog Section
A note from IDEC:
Due to continuous product improvements, specifications are subject to change without notice.
For up-to-date information, or to request a full copy of this catalog,
please visit us at www.idec.com
Relays
Selection Guide
Selection Guides, continued
General Purpose Relays
RR Series
RH Series
RM Series
RY Series
D-8
D-11
D-14
D-17
Appearance
Page
Features
• Highly reliable
• Large capacity
• 8-pin, 11-pin, or 11-blade
plug-in base
• 1 to 3 pole switching
• AC or DC coils
•
•
•
•
•
Options
Indicator light
Check button
Side flange
Indicator light
Check button
Top mount
Indicator light
Check button
Top mount
Indicator light
Check button
Top mount
Contact Configuration
1, 2, 3 Form C
1, 2, 3, 4 Form C
2 Form C
2, 4 Form C
Contact Rating (resistive)
10A, 30V DC
10A, 120V, 240V AC
1/3HP, 240V AC
1/4HP, 120V AC
10A, 30V DC
10A, 120V, 240V AC
1/3HP, 240V AC
1/6HP, 120V AC
5A, 30V DC
5A, 120V AC, 240V AC
DPDT: 3A, 30V DC;
3A, 120V AC, 240V AC
4PDT: 5A, 30V DC;
5A, 120V AC, 240V AC
Contact Material
Silver
Silver-cadmium oxide
Silver
Silver, gold-plated
Minimum Electrical Life
500,000 operations
(10A, 120V AC)
500,000 operations
(10A, 120V AC)
500,000 operations
(5A, 240V AC)
200,000 operations
(DPDT: 3A, 120V AC)
(4PDT: 5A, 120V AC)
Minimum Mechanical Life
10,000,000 operations
50,000,000 operations
50,000,000 operations
50,000,000 operations
Dielectric Strength
(between contact and coil)
2,000V AC, 1 minute
2,000V AC, 1 minute
2,000V AC, 1 minute
2,000V AC, 1 minute
(4-pole version)
6, 12, 24, 48, 110V DC
6, 12, 24, 48, 110V DC
6, 12, 24, 48, 110V DC
6, 12, 24, 48, 110V DC
6, 12, 24, 120, 240V AC
6, 12, 24, 120, 240V AC
6, 12, 24, 120, 240V AC
6, 12, 24, 120, 240V AC
Power Consumption
(approximately)
2.5VA/1.5W
SPDT: 1VA/0.8W
2PDT: 1.2VA/0.9W
3PDT: 1.7VA/1.5W
4PDT: 2VA/1.5W
1.4VA/0.9W
DPDT: 1.0VA/0.8W
4PDT: 1.2VA/0.9W
Termination
Pin/Blade
Blade/PCB
Blade/PCB
Blade/PCB
Sockets
SR2P
SR3P
SR3B
SH1B
SH2B
SH3B
SH4B
SY4S
SY2S
SY4S
Coil Voltage
Compact midget size
Highly reliable
Large capacity
AC or DC coils
1 to 4 pole switching
• Compact miniature size
• Highly reliable
• AC or DC coils
UL Recognized
Files No. E59804
E64245
UL Recognized
Files No. E67770
E59804
E64245
Approvals
*
• Compact ice-cube size
• 2- or 4-pole switching
• Bifurcated contacts for dry
circuit switching
CSA Certified
File No.LR35144
*
CSA Certified
File No.LR35144
*
*
File No. BL951113332319
File No. BL951113332319
* CE marking and TUV ratings do not apply to RR blade style relays.
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332
D-3
D
Relays
Selection Guide
Selection Guides, continued
General Purpose Latching Relays
RR2KP Series
RH2L Series
RY2KS Series
RY2L Series
D-22
D-24
D-26
Appearance
Page
D
D-20
• Magnetic dual coil
• Self-maintaining without
power
• Separate set and reset coils
• AC or DC coils
•
•
•
•
•
Midget size latch relay
10A capacity
Dual coil
Power saving pulse input
Indicator shows set-reset
condition
• AC or DC coils
• Magnetic dual coil
• Self-maintaining without
power
• Separate set and reset coil
• AC or DC coils
•
•
•
•
•
Options
Check button
—
Check button
—
Contact Configuration
2 Form C
2 Form C
2 Form C
2 Form C
Contact Rating
(resistive)
10A, 30V DC
10A, 120V AC
10A, 30V DC
7.5A, 240V AC
10A, 120V AC
3A, 30V DC
3A, 120V AC
3A, 30V DC
3A, 120V AC
3A, 240V AC
Contact Material
Silver
Silver-cadmium oxide
Silver, gold-plated
Silver, gold-flashed
Minimum
Electrical Life
500,000 operations
200,000 operations
200,000 operations
200,000 operations
Minimum
Mechanical Life
5,000,000 operations
10,000,000 operations
5,000,000 operations
10,000,000 operations
Dielectric Strength
(between contact and coil)
1,500V AC, 1 minute
2,000V AC, 1 minute
1,500V AC, 1 minute
1,500V AC, 1 minute
Features
Miniature size latch relay
3A capacity
Dual coil
Power saving pulse input
Mechanical indicator to
show set/reset condition
• AC or DC coils
6, 12, 24, 110V DC
6, 12, 24V DC
6, 12, 24, 110V DC
6, 12, 24V DC
6, 12, 24, 120, 240V AC
6, 12, 24, 120V AC
6, 12, 24, 120, 240V AC
6, 12, 24, 120V AC
Power Consumption
AC: 2.2VA
DC: 1.5W
1.2VA/2W (set)
0.5VA/0.9W (reset)
AC: 1.5VA
DC: 1.2W
0.7VA/1.2W (set)
0.35VA/0.6W (reset)
Termination
Pin
Blade/PCB
Blade
Blade/PCB
Sockets
SR3P
SH3B
SY4S
SY4S
Coil Voltage
UL Recognized
Files No. E67770
E55996
Approvals
CSA Certified
File No.LR35144
Sockets (for reference only)
Panel Mount
SH1B-51
SH3B-51
SY2S-61
SY4S-51
For more socket information, see Section F.
D-4
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332
Relays
Selection Guide
Selection Guides, continued
Solid State Relays
RSS Series
RA Series
RB Series
D-35
D-39
D-42
Appearance
Page
Isolation Method
Phototransistor coupler
Phototransistor coupler
Phototransistor coupler
Zero-Voltage Switching
Yes
Yes
Yes
Voltage
Range
DC: 4 – 32V
AC: 90 – 280V
3 – 28V DC
3 – 28V DC
Impedance
1500Ω (DC)
40K, +10% (AC)
1.2kΩ (approximately)
1.5kΩ (approximately)
Maximum
Load Current
10, 25, 50, 75, and 90A
1.2A
1.5A, 2A
Voltage
Range
48 – 660V AC
70 – 250V AC
5 – 60V DC
Drop-Out
Voltage
1.5V, maximum
0.8V DC, minimum
0.8V DC, minimum
Mounting Style
Panel mount
Blade/Plug-in, Pin/Plug-in, PC mount
Sockets
—
SR2P-...
SH1B-...
Input
Rating
Output
Rating
Approvals
D
SR2P-...
SH1B-...
SH2B-...
—
UL Recognized
Files No. E59804
CSA Certified
File No.LR38595-94M
Sockets (for reference only)
DIN Rail Mount
SR2P-05
DIN Rail
SR3P-05C (finger-safe)
SY2S-05
SY4S-05
SH2B-05
BNDN-1000
SH-05C (finger-safe)
PC Mount
SH1B-62
SH4B-62
Hold-Down Springs/Clips
For more details on sockets,
see Section F.
SR2B-02F1
SH4B-02F1
SFA-202
SFA-301
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332
D-5
Relays
RB Series
RSS Series — Panel Mount Solid State Relays
Key features of the RSS series include:
• Photo isolation
• 1,200 volt blocking voltage
• 4,000 volt optical isolation
• Zero voltage turn-on
• 100% tested at rated current
• High surge capability
• Optional finger-safe terminal cover (RSS-CVR)
• Dual SCR output
• Built-in snubber
UL Recognized
File No. E59804
D
Output
Specifications
Input
CSA Certified
File No. LR38595-94M
Series
RSSDN
RSSAN
Voltage Range
4 – 32V DC
90 – 280V AC
Impedance
1,000Ω
40K ±10%
Pick-up Voltage
4V DC
90V AC
Drop Out Voltage
1V DC
10V AC
Dielectric Strength
(input-output-base)
4,000 RMS (minute)
Part Numbers
Part Numbers: RSS Series
Part No.
Continuous Output Current
4,000 RMS
(minute)
Capacitance
(input to output)
8pF
8pF
Reverse Voltage Protection
Yes (–32VDC)
N/A
Current (continuous)
10A
25A
50A
75A
90A
1-Cycle Surge Current
100A
250A
750A
750A
1,000A
1-Second Surge Current
30A
75A
145A
200A
280A
Voltage Drop
at Rated Current
1.6V (maximum)
Voltage Range
48 – 660V AC
Contact
1 Form A (SPST-NO)
Over Voltage Rating
1200 PIV
Frequency Range
47 – 80Hz
Off-State Leakage
at Rated Voltage
20mA (maximum)
Turn-on Time
1/2 cycle at 60Hz
Turn-off Time
1/2 cycle at 60Hz
Minimum Holding Current
50mA
Zero Voltage Switching
Yes
Static DV/DT
200V/µsec
Commutating DV/T
Snubbed for 0.5 power factor
at rated load
DC
AC
10A
RSSDN-10A
RSSAN-10A
25A
RSSDN-25A
RSSAN-25A
50A
RSSDN-50A
RSSAN-50A
75A
RSSDN-75A
RSSAN-75A
90A
RSSDN-90A
RSSAN-90A
2. The fingersafe cover is part no. RSS-CVR.
1. See page D-45 for dimensions.
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332
D-35
Relays
RB Series
Recommended Loads
Transformer Loads
Transformer loads sometimes result in severe inrush current when the transformer saturates during the first cycle. Use a relay rated for this surge, which
has a 1/2 cycle surge current greater than the maximum applied line voltage ÷
the transformer’s primary resistance (approximately 10x rated current).
Recommended Loads
SSR Rating
Recommended Loads
SSR Rating
at 120V AC
at 240V AC
at 120V AC
at 240V AC
2A
2A
2A
2A
150VA
300VA
4A
3A
3A
4A
200VA
400VA
10A
1KW
2KW
10A
500VA
1KVA
25A
2KW
4KW
25A
1KVA
2KVA
50A
3KW
6KW
50A
2KVA
4KVA
Recommended Loads
SSR Rating
at 120V AC
at 240V AC
2A
250W
500W
4A
400W
800W
10A
1KW
2KW
25A
2KW
4KW
50A
3KW
6KW
Calculating Input Current
RSS relays (DC in/AC out) have a circuit with 1,000Ω in series
with opto-couplers LEDs. At 4V input, the relay will turn on with
3mA: [4V – (1V drop across LED) = 3V]; [3V ÷ 1,000Ω = 3mA].
[(Input Voltage – 1) ÷ Impedance] = Input Current (A)
At higher voltages, the current will be
correspondingly higher.
1
4
TRIGGER
CIRCUIT
3
2
RSSAN AC INPUT
EQUIVALENT CIRCUIT
Solenoid Valves and Contactors
RSS relays use high-noise immunity circuitry with a snubber to handle the
electrical noise generated by inductive loads.
Recommended Loads
SSR Rating
SNUBBER
Heater Loads
When using solid state relays for driving heaters where the load is switched
on and off rapidly and continuously, severe thermal stress will result. In such
cases, use an SSR relay at no more than 75% of the rating.
1
4
at 120V AC
at 240V AC
2A
250W
500W
4A
400W
800W
10A
900W
1,800W
25A
2,100W
4,200W
50A
3,800W
7,500W
TRIGGER
CIRCUIT
SNUBBER
D
Lamp Loads
Zero voltage switching is ideal for driving incandescent lamps,
since the cold filiment will not be subjected to a large inrush
current. Using a zero-switched SSR will reduce inrush current
and prolong lamp life.
+
3
2
RSSDN DC INPUT
EQUIVALENT CIRCUIT
RSS series relays provide a highly reliable means of switching AC loads when
applied properly. Read the following technical notes prior to installing IDEC’s
quality solid state relays.
D-36
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332
Relays
RB Series
Technical Notes
Environment
Do not install SSRs near sources of excessive heat. Make sure applications are
dry and well ventilated.
If SSRs must be installed in an environment subject to high temperatures or poor
ventilation, or if SSRs are mounted collectively, reduce the load current so that it
does not approach the ambient temperature-load current recommendation. (See
the Temperature Derating Curves on the following page.)
When SSRs are used with inductive loads, suppress the inrush current to half of
the peak surge current.
Heat Sinks
Heat sinks are recommended for 10, 25, 50, 75, and 90 amp rated solid state
relays depending on ambient temperature and mounting position. The recommended heat sink dimensions and material are shown in the table:
Output Rating
Dimensions
Material
10A
12" x 12" x 1/8"
Aluminum (black anodized)
25A
12" x 12" x 1/8" (DC/AC)
Aluminum (black anodized)
25A
15" x 15" x 1/8" (AC/AC)
Aluminum (black anodized)
50A
15" x 15" x 1/8"
Aluminum (black anodized)
75A
17" x 17" x 1/8"
Aluminum (black anodized)
90A
17" x 17" x 1/8"
Aluminum (black anodized)
D
Using a thermal compound between the base of the SSR and the heat sink for
heat dissipation is recommended.
Wiring
Locate SSRs as far from motor leads as possible to prevent malfunction from
induced current.
Use shielded wires for input leads when they are exposed to a source of induced
current.
Mounting
Provide sufficient ventilation.
Use #6 – 32 screws, flat washers, and lock washers to secure mounting on heat
sinks.
Vertical mounting is recommended to allow air to flow unimpeded. Horizontal or
inverted mounting is possible, but the SSR must be derated according to the derating curves on the following page.
Additional Information
Do not exceed the load voltage and current specifications.
A small-capacity load may not turn off due to the leackage current present after
the SSR has turned off. If this is the case, use a resistor in parallel with the load
to shunt the leakage current.
Observe the polarity of input terminals. Failure to do so may cause damage to
the SSR.
When the SSR output is subjected to a higher than rated voltage, a varistor or
other element should be connected to the output terminals to absorb the overvoltage.
When the input signal contains a ripple voltage, the lowest ripple amplitude
should exceed the minimum pick-up voltage of 4V.
Over 4V
0V
Lowest Voltage
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332
D-37
Relays
RB Series
Temperature Derating Curves: RSS Series
it-Free Air
20
30 40
50 60
70 80 90 100
Relay Base Temp (°C)
in
50 Amp Heatsink
50
k
k
in
ts
ir
ts
60
ea
H
Free A
10 Amp Un
ea
on
ink
75 Amp Mounted on H
ed
ats
k
p Unit-
5
He
sin
at
25 Am
80
nt
He
10 Amp
10
90 Amp
ou
on
15
100
M
ed
nt
20
RMS On-State Current (Amps)
25
ou
D
Derating Curve
50-Amp, 75-Amp, and 90-Amp
M
RMS On-State Current (Amps)
Derating Curve
10-Amp and 25-Amp
90 Amp Unit-Fre
20
e Air
50 Amp-Free Air
20
30 40
50 60
70 80 90 100
Relay Base Temp (°C)
For information on heat sink size, refer to the Technical Notes on
the previous page.
D-38
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332
Relays
RB Series
RA Series — DC-AC Solid State Relays
Photo-Coupled, Zero Voltage Switching
Key features of the RA series include:
• 1A, 2A, 10A, and 20A current ratings,
30V AC to 264V AC output ratings
• Zero-voltage switching reduces inrush current
• Solid-state design: no arc, no chatter, no bounce
• High-speed, high-frequency switching, long life
• Photo-coupler completely isolates the input and output
• Wide input signal voltage range and small signal
requirements enable direct drive from IC level signals
• Diode protection against reverse polarity
• Output circuit contains an RC snubber circuit
(except RAHB)
• Sealed with epoxy resin for high resistance to moisture
and vibration
• Panel mount, plug-in, and PCB mount models
Output
Specifications
Input
Series
RAFL, RAPP
RAHB
RALB
Voltage Range
3 – 28V DC
4 – 30V DC
Impedance
Approximately 1.2KΩ
Approximately 1.5KΩ
Pick-up Voltage
3V DC maximum
4V DC maximum
Drop-out Voltage
0.8V DC minimum
1V DC minimum
Load Voltage Range
70 – 250V AC
30 – 264V AC
Maximum Load Current 2A
1A
2A
Off-State Leakage
Current (maximum)
5mA (at 120V AC)
9mA (at 240V AC)
3mA (at 120V AC)
6mA (at 240V AC)
4mA (at 100V AC)
8mA (at 200V AC)
Voltage Drop with
Output On (maximum)
1.7V rms
3V rms
1.6V rms
1-Cycle Surge Current
60A peak (non-repetitive)
16A peak (non-repetitive)
60A peak (non-repetitive)
Minimum Operating
Current
50mA
Operating Time
Reset Time
Characteristics
D
1/2 cycle of line voltage maximum +1ms or less
Insulation Resistance
100MΩ or more (500V DC megger)
Dielectric Strength
Between live parts: 1,500V AC, 1 minute
Between live and dead metal parts: 2,000V AC, 1 minute
Between input and output:
2,500V AC, 1 minute
Between I/O and housing:
2,500V AC, 1 minute
Operating Temperature
–20 to +80°C
–30 to +80°C
Storage Temperature
–25 to +100°C
–30 to +100°C
Contact Configuration
SPNO (Form A)
RAPP: 1 SPNO and 2 SPNO
See page D-45 for dimensions.
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332
D-39
Relays
RB Series
Part Numbers
Part Numbers: RA Series
Plug-in
PCB Mount
Type
RAPP
Termination
Pin
Blade
Blade
PCB
Output Current/Voltage Range
2A (70 – 250V AC)
1A (70 – 250V AC)
2A (30 – 264V AC)
2A (70 – 250V AC)
Zero-Voltage Switching
Yes
Yes
Yes
Yes
Output: RC Absorbing
Yes
No
No
Yes
Complete Part No.
RAPP-202Z (1 SPNO)
RAPP-202Z2 (2 SPNO)
RAHB-201Z
RALB-202ZL
RAFL-202Z
RAHB
RALB
RAFL
1. UL recognized and CSA certified models are available from IDEC. RALB series includes an operation indicator standard.
D
Part Numbers: Sockets
Relays
Standard DIN Rail Mount
Finger-Safe DIN Rail Mount
Panel Mount
PC Mount
Spring (optional)
RAPP
SR2P-05
SR2P-06
SR2P-05C
SR2P-51
—
SR2B-02F1
SR3P-01F1
RAHB
SH1B-05
SH1B-05C
SH1B-51
SH1B-62
SY2S-02F1
SY4S-51F1
RALB
SH2B-05
SH2B-05C
SH2B-51
SH2B-62
SY4S-51F1
SY4S-02F1
2. See Section F for details on sockets. All DIN rail mount sockets shown above can be mounted using DIN rail BNDN-1000.
Internal Circuit
Zero-Voltage Switching
The zero-voltage circuit initiates switching near zero volts AC and is reset
when the load current crosses zero. Switching is delayed until the next zerocrossing, even if an input signal enters during the AC cycle. Inrush current is
reduced to a minimum.
(+)
Input
(-)
Photo-Coupler
Source
Receiver
Zero
Cross
Switching
Output
Element
R
Output
C
3. The surge absorber circuit is not contained in RAHB types.
D-40
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332
Relays
RB Series
Temperature Derating Curves
RALB
Load Current (Amps)
2.5
2.0
1.5
1.0
0.8A
0.5
–20
0 20 40 60 80 100
Ambient Temperature °C
D
Connection Diagram
RAPP-202Z (2 SPNO)
Z1
5
Input 2
6
(+)
7
1
(-)
Z2
Load1
8
Input
~
Z1
4
5
8
9
12 Output
14 (+)
(+)
6
(+)
7
1
8
Z4
Load2
Z3
~
Input 1
Bottom View
Connect overvoltage absorbing elements in place
of Z1, Z2, Z3, and Z4 when switching inductive loads.
Z2
(–) 13
5
3
(-)
2
Connect overvoltage absorbing elements in place
of Z1 and Z2 when switching inductive loads.
RALB
1
4
Output 2
~
Output
4
3
(-)
2
Output 1
Z2
Load
RAPP-202Z2 (1 SPNO)
Load
RAHB
~
Z1
1
Z2
5
Load
Output 9
Input
~
Z1
(-) 13
RAFL
14 (+)
Z2
(2)
(+) (~)
Input Output Z1
(+) (~)
(4)
(1)
(3)
Input
Load
Bottom View
Connect overvoltage absorbing elements in place
of Z1 and Z2 when switching inductive loads.
~
Connect an external RC absorber to the output terminals and
overvoltage absorbing elements in place of Z1 and Z2
when switching inductive loads.
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332
D-41
Relays
RB Series
RB Series — DC-DC Type Solid State Relays
Input
Output
Specifications
Characteristics
D
Key features of the RB series include:
• 3V to 8V DC input signal voltage,
5V to 60V DC output load range
• A photo-coupler ensures complete isolation between input and
output terminals, resulting in high dielectric strength
• An all solid-state design generates no arc, no chatter, no
bounce, and no mechanical noise
• Capable of high-speed and high-frequency switching with long
life and excellent reliability
• Input diode protection against reverse polarity
• Sealed with epoxy resin for high resistance to moisture, shock,
and vibration
• Available in PC mount or plug-in models
Series
RBPP, RBHB, RBMB, RBFL
Voltage Range
3 to 28V DC
RBLB
Impedance
Approximately 1.5kΩ
Pick-up Voltage
3V DC maximum
4V DC maximum
Drop-out Voltage
0.8V DC minimum
1V DC minimum
Load Voltage Range
5 to 60V DC
Maximum Load Current
2A
Off-State Leak Current
2mA maximum
Voltage Drop Output On
1.5V rms
Surge Current, 1 Cycle
5A (1 second maximum)
Minimum Operational Current
50mA
Operating Time
0.5ms maximum
Reset Time
2ms maximum
Insulation Resistance
100MΩ minimum (measured with 500V DC megger)
Dielectric Strength
Between live parts: 2,000V AC, 1 minute
Between live and dead metal parts: 2,000V AC, 1 minute
Operating Temperature
–25 to +80°C
Storage Temperature
–30 to 100°C
Contact Configuration
SPNO (Form A)
RBPP: 1 SPNO or 2 SPNO
4 to 30V DC
–30 to +80°C
See page D-46 for dimensions.
D-42
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332
Relays
RB Series
Part Numbers
Part Numbers: RB Series
Plug-in
PCB Mount
Type
RBPP
RBHB
RBMB
RBLB
RBFL
Termination
Pin
Blade
Blade
Blade
PC board
2A (5 – 60V DC)
2A (5 – 60V DC)
2A (5 – 60V DC)
2A (5 – 60V DC)
2A (5 – 60V DC)
RBHB-0502
RBMB-0502
RBLB-0502L
RBFL-0502
Applicable Load
Complete Part No.
RBPP-0502 (1 SPNO)
RBPP-0502-2 (2 SPNO)
1. RBLB series includes an operation indicator standard.
Part Numbers: Sockets
Relays
Standard DIN Rail Mount
RBPP
SR2P-05
SR2P-06
Finger-Safe DIN Rail Mount
Panel Mount
PC Mount
SR2P-05C
SR2P-51
RBHB
SH1B-05
SH1B-05C
SH1B-51
SH1B-62
SY2S-02F1
SY4S-51F1
RBMB
SH2B-05
SH2B-05C
SH2B-51
SH2B-62
SY4S-02F1
SY4S-51F1
RBLB
SH2B-05
SH2B-05C
SH2B-51
SH2B-62
SY4S-02F1
SY4S-51F1
—
Spring (optional)
D
SR2B-02F1
SR3P-01F1
2. See Section F for details on sockets. All DIN rail mount sockets shown above can be mounted
using DIN rail BNDN-1000.
Internal Circuit
An input signal actuates the drive circuit through the photo-coupler, causing the output transistor to turn on the output. Turning off the input returns the output to the off
state. Unlike AC solid-state relays, IDEC’s DC-DC solid-state relays do not require
zero-voltage switching.
Photocoupler
Input
Source
Receiver
(+)
Drive
Circuit
(+)
Output
(-)
(-)
Temperature Derating Curves
RBLB
Load Current (Amps)
2.5
2.0
1.5
1.0
0.8A
0.5
–20
0 20 40 60 80 100
Ambient Temperature °C
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332
D-43
Relays
RB Series
Connection Diagrams
RBPP-0502 (one switching circuit)
4
(+)
Output
Load
Z
3
2
(-)
(-) 1
RBHB
1
5
6
7
8 (+)
(+) 5
Output
(-) 9
Load
Z
(-) 13
Input
14 (+)
Input
RBFL
RBPP-0502-2 (two switching circuit)
(2)
(+) (+)
Output Z
Input
(-) (-)
(4)
(1)
(3)
Input 2
Output 1
Load
Z
(+)
(-)
4
5
3
2
(-)
1
8
(+)
(+)
6
(+)
7
Output 2
(-)
D
Load
Load
Bottom View
Z
(-)
Connect an overvoltage absorbing element in place of Z.
Be sure to connect a diode in parallel with the inductive load.
Input 1
Bottom View
RBMB
Load
Z
4
(+) 5
Output
(-) 9
8
5
12
9
(-)13
14 (+)
Input
D-44
RBLB
1
4
1
(-) 13
8 (+)
Output
12 (-)
14 (+)
Load
Z
Input
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332
Relays
Dimensions
RSS, RA, and RB Dimensions
1.9" (48.26mm)
RSS-CVR
RSS Series
1.05" (26.67mm)
8-32 Pan Head Screw
Large Saddle Clamp
1.75" (44.5mm)
-4
3+
1.88" (47.74mm)
0.2"
(4.8mm)
1.0" (25.4mm)
6-32 Pan Head Screw
2.4" (6.96mm)
2
1.88" (47.6mm)
1.7" (43.2mm)
2.25" (57.2mm)
1
2.65" (67.31mm)
ø0.187"
(4.5mm)
1.1" (27.9mm)
Small Saddle Clamp
.155" (3.94mm) Dia.
D
Test Probe Access Holes
0.95" (24.1mm)
R 0.265" (6.7mm)
0.09" (2.3mm)
0.79"
(20.07mm)
1.075"
(27.31mm)
0.5" (12.70mm)
0.37" (9.40mm)
Material: Polycarbonate-Clear
RA Series
RAHB
RAFL
1.08"
(27.6mm)
0.211"
(5.4mm)
1.33"
(34.1mm)
0.25"
(6.4mm)
0.53"
(13.6mm)
0.585"
(15mm)
Ø 0.031"
(0.8mm)
1.09"
(27.94mm)
0.59"
(15.24mm)
1.4"
(36mm)
0.69"
(17.78mm)
0.936"
(24mm)
RALB
RAPP and RBPP
Ø 0.101"
(2.6mm) Hole
0.019"
(0.5mm)
1.07"
(27.5mm)
1.42"
(36mm)
1.39"
(35.6mm)
1.83"
(47mm)
0.039"
(1mm)
1.13"
(29mm)
0.195"
(5mm)
0.819"
(21mm)
0.25"
(6.4mm)
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332
D-45
Relays
Dimensions
Dimensions, continued
RB Series
RBMB, RBLB
RBPP
0.101"
(2.6mm) Hole
1.42"
(36.4mm)
0.019"
(0.5mm)
0.195"
(5mm)
1.39"
(35.6mm)
Operation
Indicator
(RBLB only)
D
1.07"
(27.5mm)
0.819"
(21mm)
0.25"
(6.4mm)
1.83"
(47mm)
0.585"
(15mm)
0.019"
(0.5mm)
Ø 0.031"
(0.8mm)
1.09"
(27.94mm)
1.4"
(36mm)
D-46
1.13"
(29mm)
0.183"
(4.7mm)
RBHB
RBFL
0.039"
(1mm)
Ø 0.10"
(2.6mm) Hole0.183"
(4.7mm)
1.08"
(27.6mm)
0.59"
(15.24mm)
0.69"
(17.78mm)
0.936"
(24mm)
1.33"
(34.1mm)
0.25"
(6.4mm)
0.53"
(13.6mm)
USA: (800) 262-4332 or (408) 747-0550, Western Canada: (888) 578-9988 or Eastern Canada (888) 317-4332