FLOW FEEDBACK (DUAL VOLTAGE) ASSEMBLY The new dual voltage Flow Feedback card receives the valve potentiometer (V-Pot) signal representing the actual valve flow, and provides a scaled output or flow feedback signal ranging between 0 10 Vdc that represents the signal received. The flow feedback card has been a key component of the analog product line for many years. The new feedback card can be powered by either the original DC voltage used on the analog product, or it can be powered by 24 Vac for use with the Celeris platform. Originally developed for use with BEV/BSV valves, the flow feedback signal is used to provide flow values for those valves that are non-electronic. The flow value is then used in calculations for room or zone balance. The base-line functionality of the new flow feedback card is the same as in the previous version. However, with a dual voltage option the new card is ideal for use with both Celeris and analog systems. Dual Voltage Flow Feedback Card and Assembly SPECIFICATIONS Outputs (1) Material Compatible with PPC flame retardant black box part number 520000-011LF Signal Type Range Tolerance Voltage 0.0V - 10.0V 5% F.S. Enclosure Regulatory Compliance • Dimensions: 6" x 3.2" x 1.9" * • Weight with PCB: >6 oz. • Color: black Mounting The Flow Feedback Card is factory installed in the PPC flame retardant black box part number 520-000-011LF. Performance • Volume control accurate to +/- 5% of airflow command signal. • Available in flows from 35-6000 cfm (60-10,000 m3/hr). • Response time to change in command signal <1 second. Power Requirements • Power Supply: 24 VAC; +/-15%; 50/60 Hz; 1.5 VA Or +/-15 VDC; +/-15 %; 35 mA ISO Operating Range The Flow Feedback Card operates in the same environment as an AH/V board. The following spec items are based on benchmark testing of AH/V. • Ambient Temperature - 0-50 C (32-122 F) • Storage Temperature - 0-60 C (32-140 F) • Humidity - 10% to 90% non-condensing VAV Controller • 0-10 Vdc command signal • 0-10 Vdc flow feedback signal 75 Discovery Way • Acton, MA 01720 USA • RoHS • FCC This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: 1. This device may not cause harmful interference. 2. This device must accept any interference received, including interference that may cause undesired operation. • EU Contact Address: Honeywell GmbH Boeblinger Str. 17 71101 Schoenaich Germany Phoenix Controls Designs, Develops, Manufactures, and sells products , systems, and service to control the environment and airflow of critical spaces. Phoenix Controls is registered to ISO 9001:2008. Warranty Phoenix Controls Warrants all venturi valves against defects in material and workmanship for a period of 5 years. In addition, all other equipment manufactured by Phoenix Controls, such as sash sensors, fume hood monitors, and equipment supplied but not manufacturered by Phoenix Controls is covered by a 3 year warranty. • Tel (978) 795-1285 ©2010 Phoenix Controls Corporation. Specifications subject to change without notice. Rev. 07/16 • Fax (978) 795-1111 MKT-0238 MPC-2255 • www.phoenixcontrols.com FLOW FEEDBACK ASSEMBLY—1 OF 2 FEATURES Phoenix Controls dual-voltage flow feedback boards can be used in parallel, or the board can be used as a replacement as follows: Phoenix Part Number Notes PRT-800-000-013LF Replaces PRT-800-000-006 DC only and the combination of PRT-109-900-153LF AC to DC power converter and PRT-800-000-006. APPLICATIONS Phoenix Controls flow feedback cards are used for airflow control requiring two-position valves. The flow feedback cards provide the functionality necessary for velocity control to maintain a constant velocity as the volume of air flow varies. A change in the air flow causes the card to drive its valve to one of two pre-set positions. INSTALLATION The flow feedback assembly is factory installed in the PPC flame retardant black box part number 520-000-011LF. One PCB required per flow feedback assembly. POINTS AND WIRING TB1 1 2 3 4 5 6 TB2 1 2 3 TB1 (GROUND) (FEEDBACK OUT) FEEDBACK IN (L1-24VAC HOT) (L2-24VAC COM) FEEDBACK CARD #1 1 2 3 4 5 6 TB2 1 2 3 (GROUND) (FEEDBACK OUT) TB1 1 2 3 4 5 6 (GROUND) (FEEDBACK OUT) TB1 FEEDBACK IN TB2 (L1-24VAC HOT) (L2-24VAC COM) FEEDBACK CARD #2 TO BMS 24VAC POWER 1 2 3 1 2 3 4 5 6 (GROUND) (FEEDBACK OUT) TB2 (+15VDC) (-15VDC) FEEDBACK CARD #1 1 2 3 (+15VDC) (-15VDC) FEEDBACK CARD #2 TO BMS +/- 15VDC POWER MAINTENANCE Phoenix Controls flow feedback cards require no ongoing preventive maintenance. Once the field setup has been completed, the cards will provide years of continuous operation. 2 OF 2—FLOW FEEDBACK ASSEMBLY MKT-0238 MPC-2255 ©2010 Phoenix Controls Corporation. Specifications subject to change without notice. Rev. 07/16