(1/ EC-Certificate of Conformity
(2)
Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Directive 94/9/EC
(3)
EC-Certiflcate of Conformity Number:
EPS 09 ATEX 1 236 X
(4) Equipment:
12P7633X012, 12P7632X012, 12P7634X012, 12P7635X012
(5) Manufacturer:
(6) Address:
Revision: 1
Emerson Process Management- Fisher-Rosemount Systems
1100 West Louis Henna Blvd, Round Rock, Texas, 78681-7430, USA
(7) This equipment and any acceptable variation thereto are specified in the schedule to this certificate
and the documents therein referred to.
(8)
Bureau Veritas Consumer Products Services Germany GmbH, Notified Body No. 2004 in
accordance with Article 9 of the Council Directive 94/9/EC of March 23rd 1994, certifies, based on
a voluntary testing, that this equipment has been found to comply with the Essential Health and
Safety Requirements relating to the design and construction of equipment and protective systems
intended for use in potentially explosive atmospheres, given in Annex II of the Directive.
The examination and test results are recorded in the confidential report 09TH0448.
(9)
Compliance with the Essential Health and Safety Requirements has been assured by compliance
with:
EN 60079-0:2009
EN 60079-15:2010
(10) If the sign "X" is placed after the certificate number, it indicates that the equipment is subject to
special conditions for safe use specified in the schedule to this certificate.
(11) This EC-Certificate of Conformity relates only to the design and the construction of the specified
equipment in accordance with Directive 94/9/EC. Further requirements of this Directive apply to the
manufacture and supply of this equipment.
(12) The marking of the equipment shall include the following:
@11 3G Ex nA nC IIC T3 Gc
Certifi(
3artment
ÿion protection
)'11 3G Ex nA nC IIC T4 Gc
Türkheim, February 21,2014
k'««Ffÿs ¢ÿ9
Paqe 1 / 2
Certificates without signature are void. This certificate is allowed to be distributed only if not modified.
Extracts or modifications taust be authorized by Bureau Veritas Consumer Products Services Germany GmbH.
EPS 09 ATEX 1 236 X Rev. 1 - This certificate is internally administrated under the following number: 10-017z
I ÿIIII ;ÿII;IIÿIII
|Vll ÿII :• ab f=ÿ't
Annexe
(13)
(14)
EC-Certificate of Conformity EPS 09 ATEX 1 236 X
(15)
Descri tion of e ui ment:
Power supply for built in use, supplied by mains and providing galvanically isolated d.c. output.
Revision 1: Re-evaluation according to EN 60079:2009 and EN 60079-15:2010
Electrical data:
12P7633X012
12P7632X012
Input: 100-240Vac; 50-60Hz; 1,4-0,65A
Output: 24-28Vdc; 5-4,5A
Input: 100-240Vac; 50-60Hz; 2,1-0,9A
Output: 12-15Vdc; 15-12A
12P7634X012
Input: 100-240Vac; 50-60Hz; 2,8-1,2A
Output: 24-28Vdc; 10-9A
12P7635X012
Input: 100-240Vac; 50-60Hz; 5,4-2,4A
Output: 24-28Vdc; 20-17, lA
(16) Test re port: 09TH0448
(17) Special conditions for safe use:
The power supply must be installed in an IP54 enclosure or cabinet in the final installation. The
enclosure / cabinet must comply with the requirements of EN 60079-15:2010.
The rated ambient temperature is -25°C < Ta >--60°C.
(18) Essential health and safety requirements:
standards.
tion
.ÿnt of explosion protection
Türkheim, February 21, 2014
Page 2 / 2
Certificates without signature are void. This cedificate is allowed to be distributed only if not modified.
Extracts or modifications taust be authorized by Bureau Verilas Consumer Products Services Germany GmbH.
EPS 09 ATEX 1 236 X Rev. 1 - This certificate is internally administrated under the following number: 10-017z
|vJI :Il :|ÿ-]
11) EC-Certificate of Conformity
(2)
Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Directive 94/91EC
(3)
EC-Certificate of Conformity Number:
EPS 11 ATEX 1 312 X
(4) Equipment:
12P7637X012, 12P7638X012, 12P7639X012
(5) Manufacturer:
(6) Address:
Revision: 2
Fisher-Rosemount Systems- Emerson Process Management
1100 West Louis Henna BIvd, Round Rock, Texas, 78681-7430, USA
(7) This equipment and any acceptable variation thereto are specified in the schedule to this certificate
and the documents therein referred to.
(8)
Bureau Veritas Consumer Products Services Germany GmbH, Notified Body No. 2004 in
accordance with Article 9 of the Council Directive 94/9/EC of March 23rd 1994, certifies, based on
a voluntary testing, that this equipment has been found to comply with the Essential Health and
Safety Requirements relating to the design and construction of equipment and protective systems
intended for use in potentially explosive atmospheres, given in Annex II of the Directive.
The examination and test results are recorded in the confidential report 10TH0536.
(9)
Compliance with the Essential Health and Safety Requirements has been assured by compliance
with:
EN 60079-0:2012
EN 60079-15:2010
(10) If the sign "X" is placed after the certificate number, it indicates that the equipment is subject to
special conditions for safe use specified in the schedule to this certificate.
(11) This EC-Cer[ificate of Conformity relates only to the design and the construction of the specified
equipment in accordance with Directive 94/9/EC. Further requirements of this Directive apply to the
manufacture and supply of this equipment.
(12) The marking of the equipment shall include the following:
@11 3G Ex nA IIC T4 Gc
Cerlifi(
osion protection
Türkheim, February 21, 2014
.]
Paqe 1 / 2
Cerlificates without signature are void. This certificate is allowed to be dislributed only if not modified.
Extracts or modifications taust be authorized by Bureau Veritas Consumer Products Services Germany GmbH.
EPS 11 ATEX 1 312 X Rer. 2 - This cerlificate is internally administrated under the following number: 11-031z
Annexe 1
(13)
(14)
EC-Certificate ofConformity EPS 11 ATEX 1 312 X
(15)
Descri tion of e ui ment:
Redundancy modules are used to isolate the output voltages of the individual power supply of a
redundant power supply system. To achieve redundancy, one extra power supply must be installed
in order to deliver the required current in case one power supply in the system fails. The
redundancy modules have two input channels and one output and utilize diodes or MOSFET's to
isolate the two inputs. They can be used to build 1+1 and N+I redundant systems.
Revision 1: Evaluation according to new edition of standards (EN 60079-0:2009, EN 60079-
15:2010
Revision 2: Evaluation according to new edition of standards (EN 60079-0:2012, EN 6007915:2010). Additional models added.
Electrical data:
12P7637X012:
Input: 2 x 12-48Vdc (+/-25%); 2 x 0-10A
Output: Input voltage - 0,9V; 0-20A
12P7638X012:
Input: 2 x 12-28Vdc (+/-30%); 2 x 0-20A
Output: Input voltage - 0,1V; 0-40A
12P7639X012:
Input: 2 x 12-28Vdc (+/-30%); 0-40A
Output: Input voltage - 0,1V; 0-80A
(16) Test ÿort: 10TH0536
(17) Special conditions for safe use:
The equipment must be installed in an IP54 enclosure or cabinet in the final installation. The
enclosure / cabinet must comply with the requirements of EN 60079-15:2010.
-25°C < Ta _< +60°C: 12P7637X012
-40°C < Ta -< +60°C: 12P7638X012, 12P7639X012
(18) Essential health and safety requirements:
Met by standards.
ion protection
Türkheim, February 21, 2014
)
, o'/
s
o
Page 2 / 2
Certificates without signature are void. This certificate is allowed to be distributed only if not modified.
Extracts or modifications taust be authorized by Bureau Veritas Consumer Products Services Germany GmbH.
EPS 11 ATEX 1 312 X Rev. 2 -This certificate is internally administrated under the following number: 11-031z
I :/Ul ÿœ :ff:llll
Lv1:11 ÿlllHfÿßÿ
1) EC-Certificate of Conformity
(2)
Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Directive 94/9/EC
(3)
EC-Certificate of Conformity Number:
EPS 14 ATEX 1 638 X
(4) Equipment:
(5) Manufacturer:
(6) Address:
Revision: 0
12P7636X012
Fisher-Rosemount Systems, Inc.
1100 West Louis Henna Blvd, Round Rock, TX 78681-7430, USA
(7) This equipment and any acceptable variation thereto are specified in the schedule to this certificate
and the documents therein referred to.
(8) Bureau Veritas Consumer Products Services Germany GmbH, Notified Body No. 2004 in
accordance with Article 9 of the Council Directive 94/9/EC of March 23rd 1994, certifies, based on
a voluntary testing, that this equipment has been found to comply with the Essential Health and
Safety Requirements relating to the design and construction of equipment and protective systems
intended for use in potentially explosive atmospheres, given in Annex II of the Directive.
The examination and test results are recorded in the confidential report 14TH0029.
(9) Compliance with the Essential Health and Safety Requirements has been assured by compliance
with:
EN 60079-0:2012
EN 60079-15:2010
(10) If the sign "X" is placed after the certificate number, it indicates that the equipment is subject to
special conditions for safe use specified in the schedule to this certificate.
(11) This EC-Certificate of Conformity relates only to the design and the construction of the specified
equipment in accordance with Directive 94/9/EC. Further requirements of this Directive apply to the
manufacture and supply of this equipment.
(12) The marking of the equipment shall include the following:
'11 3G Ex nA nC IIC T4 Gc
tiÿUNg$-...
Ge
)artment
Iosion protection
Türkheim, May 05, 2014
Page 1 / 2
Certificates without signature aie void. This certificate is allowed to be dJstributed only if not modified.
Extracts or modificat[ons must be authorized by Bureau Veritas Consumer Producls Services Germany GmbH.
EPS 14 ATEX 1 638 Rev. X
ImlTIIÿP=IWl
Annexe
(13)
(14) EC-Certificate of Conformity EPS 14 ATEX 1 638 X
(15)
Descri tion of e ui ment:
Power supply with mains input and galvanically separated d.c. output voitage.
Electrical data:
Input
Output
100-240Vac; 50-60Hz; 11.2-4.6A
24-28Vdc; 40.0-34.3A
(16) Test re_port: 14TH0029
(17) Special conditions for safe use:
The equipment shall be installed in an enclosure that provides a degree of protection not less than
IP 54 in accordance with EN 60079-15. The equipment shall only be used in an area of not more
than pollution degree 2, as defined in EN 60664-1.
(18) Essential health and safety requirements:
Mer by standards.
of explosion protection
Türkheim, May 05, 2014
ù ,-,,.
\
,
\
Page 2 / 2
Certificates without signature aie void. This certificate is allowed to be distdbuted only if not modified.
Extracts or modilications taust be authorized by Bureau Veritas Consumer Products Services Germany GmbH.
EPS 14 ATEX 1 638 Rev. X
Related documents