for the furnishlng and the installation of the fire protectj

advertisement
07
/29/L0
LLII
GENERAT
1.01
PRovIsIoNs
NO.
:
063545
sEcrroN 15301
fficTIoN
sYsTEMs woRK
SCOPE AI{D INTERPRETATION
These Specificat.ions and accompanying Drawinqs provide
B
for the furnishlng and the installation of the fire
protectj-on systems, including all accessories such as
hose stat.ions and cabinets, sprinkler heads, flow
switches, fire/sprinkler booster pumps, etc.
The specificat.ions and Drawings require the Master Fire
Suppression Piping Contractor, to provide all- 1abor,
materials, equipment and appurtenances to perform of
all Work pertaining or incidental- theret.o, which is
needed to complete the Work shown on the Drawj-ngs and
cal-l-ed for in the Specif ications.
C
n,raf am cltlLl
Thc
c(]mnl
f -i re nrol-er-f
i n^ DyDLEItt
-h,.i the
rrrs
vvrrrl/!sLs cl- c rJ!s
IJ!vLguuf\JII
D.
work
shal_l_
be so lnstalled as to give proper and continuous
service under all- conditions, and shall be j-n
accordance with the requirements of all public
authorities having jurisdiction and to the complete
satisfaction of the Authority. Any Work shown on the
Drawings and not particularly
descrj-bed in the
specifications, or vice versa or any Work which may be
deemed ncr-cqsarv to complete the Contract shall_ be
provided by t.he Contractor as part of its Contract.
For purposes of clearness and legibility,
fire
protection Drawings are essentially diagrammatic and
size and l-ocation of equipment are drawn to scale
wherever possible.
The Drawings indicate size,
connection points and routes of pipe.
It is not
j-ntended, however, that al-1 of f sets, rises and drops
are shown. Provide piping as required to fit
structure, avoid obstruction, and retain clearances,
headroom openings and passageways.
E.
Sprinklers shown and described on the Drawings shall be
connecLed to water supply piping in accordance with
the requirements of NFPA L3-02, Standard for the
Installation of Sprinkler Systems as amended Section
Ql-01 of Appendix O of the 2008 NYC Building Code,
cie.soi te ^n\z z1^qq i hl o OmiSSiOn Of indiCatiOn
Of SUCh
ni ni ncr n n tho
nl ane
Any question involving the
installation of such piping shal-l be referred to the
Authority for resolution.
The Fire Protection Systems Contractor shal-l- comply
wit.h the Commissioning Requirements of Section S01560
l/vuv4v!v
vlt
E'
or
f
!v!
MrcscA
rPrrmni
urlryrrrv
Lrrg
l/lqlro.
ncr nIJIJe!qLu-.
Anna ral-
rr
e
F.i
!!!g
-^
nraf
aa{- i a11 svsf
JJouurlrJems sha
Jlrq f f
I/!vLguLrvrr
GENERJAI PROVISIONS FOR TIRE
PROTECTION SYSTEMS WORK
15301
1
o7
/2e/LO
LLW
be tested in accordance with the
the NYC Fire Code.
NYC
NO.: 063545
Buildinq Code and
Instalfation of sprinkler and standpipe syst.ems are
sublect to the special inspection requirements of
Sections BC L]04.2I and BC I704.22 respectively of
Chapter I1 of the NYC Buil-ding Code.
The Contractor shal-l- cooperate and provide access to
Special Inspectors hired by the Authority for
conducting Special Inspections.
H
Qnnna
nf
rilnr];: .
f if a
The
rrr9
!!!9
.i on
nrnf
y!vusvLJvrror-1-
WOf
k
Of
this
contract shal-l- include but shafl- not be limited to the
following systems, equipment and services:
1. Provide a complete combined fire protection system
consistinq of:
Qr-
rnrln'i nav // uI/!
onrinkl_ef
-
riSef S and f iSef
C6ntf Ol
valves, distribution and branch piping, drain
l-ines, hose valves, hose racks and cabinets,
roof manifolds, Siamese fire department
nrlmn
nnn1- rnl I orq
connor-f
i nn
f i ro
?.rrrmna :nrl
and al-1 associated appurtenances and alarm
evllllsvLlvllt
!f!g
yUltlyD
qIlV
I/Ultty
VVtIL!V!IE!Ot
devices.
Spri-nklers connection to combined risers,
sprinkler f loor controf val-ve assembly,
distribution and branch piping, sprinkler
heads, all associated appurtenances and
connection to alarm devices.
Provide a compJ-ete sprinkler system consistj-ng of
risers and riser control- val-ves, sprinkler heads,
floor control valve assembly,'l drain 1ines,
Q'i amaca f
rnA
hrrmn
nnnf rn1
vrru! arc r,
a]_]_
and
^rrmnc
t'
associated appurtenances and connection to afarm
1-\
devices.
3.
mrcscA
Provide a complete fire
standpipe system
consisting of risers, and riser control valves,
distribution and branch piping, drain l-ines, hose
valves, hose racks and cabinets, roof mani-folds,
Slamese fj-re department connection, fire pumps and
pump controllers, and al-l- associated appurtenances
and connection to al-arm devices.
Piping:
Instal-l-ation
of
complete
sprinkler/standpipe systems piping from t.he point
of connection at a fJ-anged fitting at the water
source piping instalfed
by the plumbing
contractor. Piping includes among other things:
Siamese connection and fittings, O.S & Y valves,
GENERAI, PROVISIONS FOR FIRE
PROTECTION SYSTEMS WORK
15301
2
o7
LLII NO. : 063545
/29lLO
control val-ves,
flow swj-tches, floor control- valve
qnli
rqqomkrl
rz , jr:
nkl or
ha-Ac
..idus, 1.rnoa
nose
sL *rnage prpang , -y
station and cabinets etc.
ln7:f
ar
Qrrnnl i oc I'
oh-ri se
Hi
rrrYra
lrrli I d'i nrrs
in
Sited
Seismic Design Category C or D shal-l be provided
with a secondary on-site water supply equal to the
hydraulically cal-cul-ated sprinkler water demand.
Equipment and devices furnished under other
Sections of this Contract that are integrated with
inr''l rrdino
the firc y!nrnfer-1_
ion uf.qrzstemel-ectriCalv Lvv
u uvrr,r
ss+rrY
devices for system monitoring and alarms, shall- be
piped by this Contractor.
A11 vafves control-ling the water supply for
automatic sprinkler systems, pumps, tanks, water
l-evefs, and water-flow switches on a1l sprinkler
systems shall- be electrically supervised by the
fire al-arm system.
Val-ves controlling
wat.er supplles to standpi-pe
in
l-ha
ayran
naq'iiinn
position
so that a change in the normaf
of the
valve will- generat.e a supervisory signal which
shal-f be transmitted to the fire alarm svstem.
qrrqfam<
ch:ll
ha
qrrnorrriqad
Uut/u!Ir'vv+
Combination Sprinkler & Standpipe System: In light
hazard occupancies with only l-imited ordinary
hazard areasr drr automatic fire pump serving the
f irst 300 f eet of the st.andpipe system shal-1 be
used as the primary supply to the sprinkler
system, provided that an automatic secondary power
supply is available to drive the pump, where
secondary power is required by other provisions of
f hrt- t-ha nrrmrl .i s frrl I rr srrnglyiSed
he lnrio r_ :nrl
us-Y
aS
srrv
to pump runnj-ng and power loss.
Sprinkler Booster: Where the pressure from the
city water main is insufficient to comply with the
requirements of the referenced standard, but is
suf f icient to provide at l-east 5 PSI at the
highest levelof sprinklers asj determj-ned by Lest,
.i
-,,|^*-f
cl or-fLrrif uqf
r-a I ry
I rz dr
vcll
clll
cl.u
Lulttct L-LU^ t
L,L! a rran
sf,su
^r1m^ inStalled
IJLrrttP
for the purpose of boosting or increasing the city
water pressure in the sprinkler system may be used
.|-
10.
<rrhi
anf
f n
l-ha
f nl I nr.r-i na
!v+!vvYfrlY
radrr
i ramanl-
c .
shall- be of approved centrifugal type,
capable of delivering at least 200 9pm, and
shalf be capable of suppl-ying t.he cal-cul-ated
Pumps
flow and pressure demand of the sprinkler
q\7eram
NYCSCA
GENERJAI PROVISIONS FOR FIRE
PROTECTION SYSTEMS WORK
15301
3
o7
/29/LO
LLTI
NO.: 063545
Pumps shal-l- be maintained under approved
automatic control with closed circuit
supervisory attachment. The supervisory
attachments shall be di-rect.ly connected to an
office where maintenance personnel are in
attendance 24hours a day; or in lieu thereof,
the supervisory at.tachment may be directly
connected to the centraf station of an
approved operating fire alarm company.
Fire Pumps: Automatic fire pumps shall be
connected to an approved waLer source in
accordance with NFPA 20, Standard for the
Install-ation of Stationary Pumps for Fire
Protection and the f ol-lowinq:
Any required automatic f ire pump shal-l- draw
from two independent street water mains in
different streets, except that: (1) any
automatic fire pump may draw from a single
water main if auqmented by a suctj-on tank or
pump are provided with tamper switches that
are wired to an approved central station of
an operating fire alarm company. Where two
services are installed, one service from the
street water mai-n shal-l- be run directly to
the pump, and the other service may be used
for domestic water supply. The connectj-on
from water to the mains to the pumps shall be
at least 6" pipe size and shall- be flushed
before conneclion is made to the svstem.
When a water service supplies both the
domestic service and the fire pump, a remoLe
control valve shall- be placed on the domestic
service connection at the point where such
connection is taken from the city supply or
service main. Such remote control- val-ve sha1l
be control-led f rom a point near the pump
control panel. In lieu of a remote controlvalve, a manually operated val-ve may be used
to shut-off the entire domestic water supply
to the building, provided such val-ve is
located in the fire pump room and is taqged
h
11.
1-\
nrnnar]r,
€nr identifiCatiOn.
Fire pumps shall- be placed on concrete pads
at least 1,2 inches above the pump room floor
with a clearance of a t least 3 ft.
maintained on al-1 sides f rom wal-1s or f rom
Tn the
ol-her
arrrr
i nmonfu i n l-Lrre
hc T\11mn rnnm
eYuryrrrurr
event of the use of a vertica] shaft
centrifugal fire pump, the t2 in. high
NYCSCA
GENER;AI PROVISIONS FOR FIRE
PROTECTTON SYSTEI,IS WORK
15301
4
o7
/29lLO
LLW
NO.: 063545
concrete pad may be omitted, provided the
bott.om of the electric driving motor and allelectrical appurtenances are rai-sed at least
12 in. above the pump room.
L2
. Floor Control Val-ves: For a sprinkler system, an
approved, supervised, indicating conLrol- valves
: c caml.rl rz sha I I l-re nrnrz'i jerl
he nn'i nl- Of
aI
connection to the riser on each floor in hiqh-ri-se
buildings.
{-
13
L4
Taql-
i nrr
nf
l_
ha
cnri
nlrl
UIJllIrl\r9L9J-Yv-
ar
qrzcf om
cha'l
I
ha
rJar
-aa
the provisions of Section 15330, paragraph 3.05.B.
Testing of the combination wet standpipe and
sprinkler system shall- as per Section 15332,
nararrranh ? 03.B.
15.
Painting requirements for the dedicated piping of
a combined standpipe and sprinkler system shall be
Drinl-ina
as per Article 3.02 of 15332.
piping
requirements
for
of
sprinkler
dedicated
.sv.sf em sha I 'l l^rc a.q oer Artlcle
3.03 of Section
LrriY
1s330.
'L
76. Piping, Equipment Supports, and seismic bracing:
To comprise all- restraints, hangers, pipe guides,
rods, beam clamps, brackets, pipe anchors, other
attachments, ffoor flanges, masonry anchors,
bol-ts, nuts, washers, and other items as required
to fully support all- piping and equipments
instal-l-ed under this contract. Provide spring
hangers, seismic restraints, and vibration mount.s
where recommended by equipment manufacturers,
where required to meet noise abatement regulations
ni ni nn
:nrl
:nrl
a e na-ae
ea r\z
l-Lvn nrarzanf
orrtli
nmanloq!y
arlu
sYufyrttsrrL
IJrsvsflL
PfIJrrrY
vibrations being transmitted to struclure.
L] . Instrumentation: Provide thermometers, pressure
qauges and other items for all piping and
equipment installed under this conLractr ds
indicated on contract drawings and as necessary
for operation, maintenance and adjustments.
18
Miscellaneous Work: Incl-uded shal-l be all items of
mat.erials, piping, controls, wiring and other
*.i ^^^r'r ^rllreeurrqatevqo
items
not
shown on
specif icaIly
Contract Drawings or called for herein but which
are normally furnished and required for a complete
instal-l-ation of this tvpe.
I9
Sealing of Openings : Openings l-ef t in waIIs,
f l-oors, ceilings or partitions shall- be seal-ed.
lnrcscA
GENERAJ, PROVISIONS FOR FIRE
PROTECTTON SYSTEI{S WORK
15301
5
o7
/2e/L0
LLlil NO.
20
:
063545
Finish shall match existing adjoining finish in
all- respects.
The NYC Building Code classifies school-s as
Occupancy Category III in BC Tabl-e 1604.5. Seismic
requirements of the New York City Building code
apply to New Buildings, Additions, and retrofit
work on Existing Buildings constructed after
L! r t/ t yy3 Decame errectl_ve.
Refer to Section 15303, "Seismic Controls,
Fire Protection Svstems" for the bracing
ra^rli
ramanf
rsyufrErrrErrLD
h
-
nf
(J!
aarr i nmanf
ELlu_Ll.,il.rgrlL
and appurtenances.
j-ons (including the combining of
tensil-e and shear loadings ) to sei-smic
bracing designs shall be stamped by
Contractor' s Registered Professional Engineer
with at l-east f ive vears of seismic desi-qn
'l rl i na
l-rrli
experr_ence
in
non-structural
v u! rsrrrY
componenLs in New York State. The Contractor
shall retain a registered professiona.lengineer who shall- provide al-l required shop
drawings (signed and seal-ed) . Contractor's
engineer shall also field inspect all
install-ations of vibration isol-ators and
seismic bracing and shall- submit affidavit
that
all
isol-ators/bracing have been
Cal-culat
i n^nrna
n-a
installed
l_n
with
signed/seal-ed coordinated shop drawings.
27
the
Coordinati-on Drawings: The Fire Protection Systems
contractor shall cooperate with the HVAC, P&D, and
El-ectrical- contractors in the development of the
coordj-nation drawings. The drawings, indicating
ductwork, steam, hydronic & fuel- piping, etc.
shall- be generated by the HVAC contractor, who in
turn is to provide them to the Fire Protection
Systems contractor for the inclusion of sprinkler
and standpipe piping in this coordination set.
This is after the P&D subcontractor has entered
its information, and will- subsequently be given to
the Electrical contractor. The specified order in
which the various trade contractors impose their
work on the coordination drawings is not intended
to qrant priority to any one trade contractor in
the al-locatj-on of space. At the completion of this
phase, hold a coordination meeting to el-iminate
any interference among the trades that the
drawings indicate and to avoid any conflicts j-n
installinq the Vrlork.
N:rcscA
GENERAT PROVISIONS FOR FIRE
PROTECTION SYSTEMS WORK
15301
6
o7
Ltlil NO. :
/29lLA
22.
Project Record
rrnrlar
UIIUgI
L.O2 CODES A}ID
A.
R
th'i
LtIf
Documents:
q i nn
c ^-nrzi V f DJUIIt
-lJLl/
raf
Ig!gI
ar
F-nr
l-
ho
063545
racrrl jagplents
to Section
c0L720.
STA}IDARDS
It shal-f be unlawful for any person to perform the work
referred to under this Fire Protection Specifications
and/or shown on the Fire Protection Contract Drawinqs
unl-ess such person is a licensed master fire
suppression piping contractor, as permitted by the NYC
Building Code and unless such work is performed under
the direct and continuing supervision of a licensed
master fire suppression piping contracLor.
Where requirements for products, materials, systems,
equipment, methods and other portion of the work
specified herein exceed minimum requirements of
I ^+^-..
-irrri
orti nr.ign
^Crenr.-i es
harr.i
!EYUTOLUTy
O.ysrrulED
rlqvrI19 ^^
OVer
the
J L.rrf DL,rf,\-L
construction work, contractor shall comply with such
qna.i f i r-al'l rz
qr1a.'i f i arl
rearlri remon1_ q
horoi n
rrnl oq<
approved otherwi-se by the Authority.
vI/vvf
1.03
TORCH BT'RNING OPERATION
A
C.
1.04
The storing and use of oxygen and combustible gases in
conjunction with torch burning apparatus is subject to
the Rules and Regulations of the Division of Fire
Prevention of the Fire Department of t.he City of New
Ynrlr I :t- aqt- Fire Prevention (F. P. ) Directive. Fire
watches shall- be provided during al-I operations using
torches for burning, cutting or welding.
Contractor shall apply for and obtain permits for the
use and storage of such equipment on school premises.
The operator of such equipment shall have a
certificate of fitness issued-br the Fire Department.
The cost of permits, certificates,
fire watches,
apparatus and other items requi-red in t.he torch
burning operation shal-l- be borne by t.he Contractor at
no additional cost to the Authoritv.
PROTECTION OE. I{ATERIALS A}ID WORK
A
New
Building
of piping shall- be temporarily closed by
a proper fitting, until piping is approved and
ready for service.
Mot.ors and appurtenances shall be covered and
Open ends
nroter:ted
N:rcscA
nrnr-rress
drrrino l-ha
of the WOrk.
errv
F!vY!r
GEIIERJAI. PROVISIONS FOR FIRE
PROTECTION SYSTEMS WORK
15301
7
07
/2s/LO
1.05
1.05
:
063545
GUARANTEES AIID WARRANTIES
A
The Requirements of Section G01740 and this Articl-e
shall apply to Guarantees and Warranties.
R
Contractor's Guarantees:
The Contractor guarantees
that all- Work of this Contract is f ree f rom alldefects, and is as specified, and that shoul-d any
defects, which cannot be proven to have been caused by
improper use, develop within the space of one year
from the date of substant.ial completion of the Work,
such defects shal-l be made good by the Contractor,
free of cost to the School Construction Authority.
OPENINGS A![D CIIASES
A.
1.07
LLTI NO.
In addition to the requi-rements in t.he Articl-e entitled
Cutting, Patching and Removals of Section S01010, the
following shall- also apply:
Openi-ngs through exterior f oundation walls shal-l be
made watertight by the Contractor after pipes, conduits
and other items passing through the wall- have been
installed. This building is planned and detail-ed, and
is the intent of these specifications to provide a
structure that will- prevent the penetration by rodents
and vermi-n of any vacant space where they might find a
harborage. The Contractor will be held responsible for
securing this condition by the closing of all points of
access to such spaces, including the passage of piping
and conduits, through all wa11s, partitions, ceilings
and furred out spaces, the closing of access to voids
in hollow til-e or cinder bl-ocks. There shal-l be a
special inspection of the buitding with regard to this
matter before final- acceptance.
INSTRUCTION OT CUSTODIA}I
A.
![vcscA
After the fire protection system has been tested, and
all- other items adjusted and operating properly to the
satisfaction of the Authority, Contractor shall
furnish a competent person to j-nstruct the Custodial
staff i-n the operation and maintenance of the systems.
Contractor shal-l- video record all the training
sessions for various equipment and svstems as
ena-'i f i orl
l_n
individualsections
of
these
Specifications. Determination of the date and time of
such instruction shal-l be under the direction of the
Authorityf s Representative.
PROVISIONS FOR FIRE
PROTECTION SYSTEMS WORK
GENERJAL
15301
8
o7
/ze/Lo
1.08
LLII
NO.
:
063545
ST'BMITTATS
A.
Formal submission for approval of manufacturer is not
required if the Contractor provides equipment as per
manufacturer/model- number or series listed in the
qr.rarrifinr1-inn
Formal submissions are also not
requJ-red f or material-s and appurtenances (ex . pipes,
et.c.) if the Contractor provides items as defined in
the specificati-on. In this case, Contractor must
submit affidavit (for record purposes only) stating
that fisted equipment and/or items as defined in the
specification
wj-ll- be provided.
Submit.tals are
mandatory for certaj-n critical items and will be so
noted in the respective specifications. Submittal-s are
always required to verif y capacit.y.
Schedules,
installation instruct.ions, startup manuals, operation
and maintenance manuafs, and shop drawings are always
requi-red to be submitted.
1.09
CLEANING AIID REPAIR
A.
P
At the completion of the Work and before the final
inspection is made the Contractor shall thoroughly
flush the system and leave it free from al-l marks,
scratches, sta j-ns , and other damage .
Al-1 pumps,
fifters, and other equipment shal-l- be cl-eaned and l-eft
in condition to operate, and the work, as a whol-e, left
in perfect working order. Remove al-l- tools, debris and
excess materials from the premises.
Contractor shall not leave sharp exposed metal- edges
(bottom of threaded rods, equipment supports, etc.)
that could otherwise present safety hazards to the
building' s occupants/work staff .
E![D OF SECTION
NYCSCA
GENERAJ, PROVISIONS TOR FIRE
PROTECTION SYSTEMS WORK
1s301
9
07
LLII
/29lLO
LIST OF
SUBI,IITTAI,
NO.
:
063545
SUBIT{ITTATS
DATE
ST'BDIITTED
DATE APPRO\ZED
Coordination Drawings:
Contractor' s affidavits
For submission of specifi-ed
Material s / or appurtenances
Paint.inq Schedu]e:
***
NYCSCA
GENERJAI, PROVTSIONS FOR FIRE
PROTECTION SYSTEMS ?TORK
1s301
10
07
LLII NO. : 063545
/2elLo
sEcTroN 15303
SEISMTC CONTROLS, FIRE PROTECTION SYSTEMS
PART
1-
GENERAL
1.01 DESCRIPTION OF WORK
A
Provide a complet.e system of seismic controls for each
item of fire protection piping and equipment as
specified herein and as needed for a complete and
.i
^^f
Provide braclng for the equipment
r/!vrrE! r..o'o-lation.
as shown on the Drawinq Schedules.
l
B
New School Buildings, Additlons and Existing School
Buildings constructed after LL l7-1995 went into
effect subject to the seismic requirements of the New
York City Construction Code are considered as Seismic
Use Group If and a corresponding Occupancy Category
III "Structures that represent a substantial- hazard to
human life in the event
as ncr
r"' Tel'rle BC 1504.5.
r-
Al l
f i ra
nrnl-an1_
v LUv
y!
i an
seismically secured.
1.
of faifure" for seismic desiqn
ni ni nn
yrt/trrY
equipment must
rnr{
be
It is the intent of the seismic controls of this
specification to keep all- mechanical building
system components in place during a sei-smic evenL
and to prevent the release of hazardous or
f Iammabl-e material-s contained within buildinq
mechanical systems.
2.
A1t such systems must be instal-l-ed in strict
accordance with the seismic codes, component
'l.rrri
manufacturers'
and
vur
i Ai na
rsrrlY
construction
standards. Whenever a conflict occurs between
the manufacturers' and construction standards,
the most stringent shall- apply.
3.
This specification is considered to be the
minimum requirements for seismic consideration
and is not intended as a substitute for more
.i
sf
ri nocnJ- *^f
JL!arlYsIIL
IIO.LI\JIIO.f^^--r 7
^+^f
DLCTLET
VI
t ^^al
IvUC
construction
reguirements.
NYCSCA
sErsMrc coNTRoLS, FrRE
PROTECTTON SYSTE!{S
15303
-
1
07
/2e/L0
LL?I NO.
:
063545
The work in this section includes, but is not
limited to t.he foll-owinq:
Seismic bracing for piping.
Listed flexible piping connections
Seismic bracing for equipment.
Certif i-cation of seismic bracinq desiqns
install-ation supervision.
ri
Certification
housekeeping
of
and
seismic attachment
of
^-,.i[/auD.
A11 fire
protection systems are included.
Eguj-pment buried underqround is excluded but
."tty of services throug-h the foundation wal-l- is
included. Equipment listed below is typical and
is not to be construed as compl-ete:
Tanks
91hr
Pumps
nd
In qeneral, where the fail-ure of the equipment
supports would cause a l-ife safety hazard (to
personnel or to other systems) such equipment
shal-l- be desiqned to resist the seismic forces.
A11 seismic bracing described in this section
shall be the product of a single manufacturer.
L.O2 DEFINITIONS
A
ICC-ES: International Code Council- Eval-uation Service.
ICC-ES performs technical- evaluations of building
products, components, methods, and materiai-s and
ronnrl-
P
T,i fo
q a'\n nnria
S:fol-
cnmnl
i rnna
vvrrrl/r
rqlrvu
.
rz (rrq1vjuLvr(ru. amq.
Al-l- systems involved with fire protection including
f i ra
l.rOOSt.ef
standpipes, sprinkler ni ^i -^ t !r!v
v\
yurrryet
^rrmno
jockey
pumps,
pumps,
fire pump control panels and
sprinkler booster pump control panels are defined as
I i fo
C.
N:rcscA
qrfo.l-
rz qrzc{. omq
Positive Attachment:
SEIS}4IC CONTROLS, FIRE PROTECTION SYSTEMS
15303
2
oz
/29/L0
LLIrI NO.
:
063545
A positive attachment is defined as a cast-in anchor,
a seismic drilled-in wedge anchor or anchor bolt ICC
certified for cracked concrete, adhesive anchor, oy a
welded or bolted connection to structure. Beam clamps
(2 sided or 1 sided beam clamps with restraining
strans)
/
arc
onl rr
qlv
a
l l owed far
permitted for seismic braces.
D.
hancrcrg and are
nOt
Transverse Bracrnq:
Bracing which limits motion perpendicul-ar to the
centerline of the pice or duct.
TI
T
anni
!\Jtr9
i nr "l
a fL tA
LIL,LJLrcl_L
Q,r:ni
IJr
AUarrynn. .
Bracing which l-imits motion parallel to the centerl-ine
of the pipe or duct.
1.03
REI.ATED SECTIONS
Related Sections include the foll-owinq but are not limited
to:
A
Division 3 Sections.
B.
Division 15 Sections.
1. 04 SUPPLEMENTAL
ST'BD{ITTAI,,S
The manufacturer of seismic bracing shall provide
submittals for products as detail-ed below. These are to be
submitted for record purposes only.
Contractor's
Registered Professional Engineer shal-l sign and sealsubmittal-s. Architect/Engineer of Record shall verify that
the structural support system can support al-l seismic l-oads
where the bracinq is attached to the structure.
A
N.
P,
NYCSCA
f)aqari
UgQU!IVLJVE
nl- i rza
Tl:t
UA.l'cl.
=.
1.
Catalog cuts or data sheets on specific braci-ng
detail-inq compliance with the specification.
2.
Detail-ed schedul-es of rigidly
showing seismic bracing.
mounted equipment
Shop Drawings
SEISMIC CONTROLS, FrRE PROTECTION SYSTEMS 15303 3
o7
/29lLO
LLDI NO.
1.
bases
member SizeS and
s.lr u! rrrCtural
u\
support. point locations.
Provi-de all details of suspension and support for
r.o'i I i nrr rrurrY
hrrnrr
InJhoro
urrre!u
?
063545
Submit fabrication details for equipment
i nr-l rrd'i ncr di
mensi nns
v4rrrvrru!vf
r9 t-
2.
:
aarr i nmanl-L .
sYuflrrltEtr
r^rrl'lq
wqrrJ,
f-l nnrq
!fvv!J,
elrl-rq
Jrqvp
nr
LrL
crrnnlamanfarrr
DL]IJIJf,E:rttEllLClIy
c.|-aa-l
DLEEf
work are used for seismic bracing locations,
detaifs of acceptabl-e attachment methods for
ducts and pipe must be included and approved
condition
+-l^^
L^€^-^
for
accepted
r_s
install-ation. Braclng manufacturers' submittals
must include spacing, static loads and seismic
loads at all att.achment and support points.
Provide specific details of seismic bracing and
anchors; include number, size and locations for
oa r-h
rt i ano
Shnn
urrvy
r!^^!.^^^r
uvlrLIouLUI
aar
rlrai^ri
u!awJllYJ nr-^
roc'i
^-r J^ Isyro
r
i nmon
1-
r 'r
^1^^
DlrclJ_L
q1-LgIEU
ororl
ha
IJE
nrafaqqi
IJ!u!EoJrvllq!
ci ana^
DJVrlgu/
nne I
/qa:'l
DEqJEUorl
anci naar
str\jrrreE!
l-rrz
py
.
6
Housekeeping pad details (for coordination wi-th
Structural Engineer of Record) .
1.
Finc
rlaf ri 'l e
ininfs-
building
hrli lrlinn
r-
nf
fnr
hrar,j;1s
aqi nn
-rn
-- ----..J
or
v!
Ser_smr_c
attachmentS
qLLq
systems or dissimilar
rnrl servl.ce entry.
*..*
or
tO
expansaon
diSSimilar
parts of the
(
Seismic Certification and Anal-vsis:
1.
Seismic bracing cal-culations must be provided for
al1 connectj-ons of equipment to the structure.
Calculations must be stamped by the Contractor' s
registered professional engineer with at l-east
f ive years of seismi-c desi-gn experience in nonst.ructural building components, licensed in New
York State.
2.
NYCSCA
At1 bracing devices shall be tested and certified
in accordance with ICC-ES AC 156 or other
recognized government agency showing maximum
ratings. Local NYC acceferations are to be used
when computing seismic inertia forces. Where
preapproved devices are not availabl-e, submittals
sErsMrc coNTRoLs, FrRE
PROTECTTON SYSTEMS
15303
4
o7
LLII
/29/LO
NO.
:
053545
based on independent testing shall be provided.
Calcul-ations (including the combination of
tensile and shear loadings relative to seismic
bracing designs) must be stamped by a registered
nrofessional
^--i^^^-
gfrYarrgg.|uE
y!v!EDDrvrlqf
ri^^nsed
with at least
in New York State
of seismic design
calcul-ations must
five years
Testing and
include shear and tensi-l-e loads as well as one
test or analysis at 45 degrees to the weakest
mode. Professional Engineer shall- be retained by
the Contract.or at its expense.
experrence.
Analysis must indicate calcul-ated dead loads,
static seismic loads and capacity of materials
utilized
for connections to equipment and
structure.
Analysis must detail anchoring
methods, bolt dj-ameter, embedmenL and/or weld
length. All sej-smic bracing devices shall be
designed to accept, without failure,
the
accel-erations detailed herein acting through the
equipment center of gravity. Overturning moments
mav exceed forces at qround l-evel-.
Wedge Anchor/expansion
cracked
^^^1
ayy-L
concrete,
D.
ICC-ES Reports for
including
seismic
.: ^^1- .i 1 .i !.r LclrJr
r -L Ly .
Adhesive anchor
6.
bolt
ICC-ES Reports.
Riser
diagrams and calculations
anticipated expansion and contraction.
showi-ng
Submit welding certificates.
Oualify weldi-ng
procedures and personnel- according to AWS Dl.1,
"Structural_ Weldinq Code-Steef".
Contractor's
Installation
1
05
Registered
Af
fidavit
Professional-
Engineer's
.
SUPPLEMENTAL QUALTTY ASSLRAI{CE
n
Manufacturer' s Qualifications
Isoi-ator /Bracing manufacturer shall be regularly
engaged in the manufacturing of vibration isolating
and seismic bracing materials, whose products have
N]rcscA
SEISMIC CONTROLS, FIRE PROTECTION SYSTEMS
15303
5
07
tL![
/29/L0
NO.
:
063545
been in satisfactory use in similar servj-ce for not
l-ess t.han f ive vears.
R,
Seismic Engineer's Qualifications and Duties
Contractor's Registered Professional Englneer shal-lhave a minimum of five years seismic design experience
in non-structural- building components and shatl be
l-icensed in New York State. Contractor's resistered
^-^ lcr-L
I/r\JreDDrur
^-^€^^^.i
1
engl-neer
Shall-
determine
vibratiOn
isol-ation and seismic bracing sizes and locations and
provide field supervision and inspection to ensure
proper instafl-ation and performance. The Contractor's
ronicl-arar{
gprrinoor
grrYrrrsE!
vrrqr
^-OfeSSj_Ona]_
eh:ll
srrhm.i
Quvllrf,u
orrq!J
t
sicrned
orYrt{
and sealed affidavit stating that the installation is
in full
compliance with the signed/sealed shop
drawinqs.
1.06
SUPPLEMENTAI COpE At{p STAI{pARpS REQUIREMENTS
A.
Chapter 16 of the New York Cit.y Building
B
ASCE
L
NFPA
Code.
1 - 2002 Minimum Design Loads for Buildings and
Other Structures.
No.13 Standard for the Instal-lation of Sprinkler
Systems-2002 as modified by Appendix a of the New York
City Building
D.
E
F-
c
Practical Guide to Seismic Restrainl, 1,999
ANSI/SMACNA Seismic Restraint Manual: Guidel-ines f or
Mechanical- Systems, 3'o Edition, 2008.
NFPA No. 14 Standard for the Installation of Standpipe
and Hose Systems as modified by Appendi-x O of the New
York Citv Buildinq Code.
ASHRAE:
NFPA No. 20-1999 Standard for
Stationary
1.07
REI,ATED
A
Code.
Pumps
the
for Fire Protection.
Instal-lati-on of
WORK
Housekeeping pads
Housekeeping pad size,
reinforcement and
monolithic pad attachment to the structure shal-1
NYCSCA
SEISMIC CONTROLS, FIRE PROTECTION SySTEtdS
15303
6
o7
/29/LO
LLW
NO.: 063545
be detailed and deslgned by the Contractor's
Registered Professional Engineer.
2.
Housekeeping pads shall- be coordinated with
Contractor's Registered Professlonal- Engineer and
sized to provide a minimum edge distance of ten
(10 ) bol-t diamet.ers all
around the outermosL
anchor bolt to al-low development of ful-l drill-in
wedge anchor ratings. If cast-in anchors are to
be used, the housekeeping pads shall be sized to
accommodate the ACI requlrements for bolt
coverage and embedment.
R
Qrrnnl
amarl{_ 2 p17 u
ul/yv!
u Steel
J Qrrnnnrl-
Contractor shal-I supply supplementary support
steel- for al-l- equipment, piping, etc. as required
or specif i-ed.
C.
Attachments
1.
Contractor shalf supply bracing attachment plates
'i nqar1- c
annnrof
a
cast into housekeeping n:rlc
etc. in accordance with tt calcul-ations of the
"
contractor' s engineer.
'vvrl9!vuv+IlUv!uU'
1.08
SEISMIC ACCETERATION LE\ZELS
A
The horizontal accelerations (in g's) are defined as
the ratio of the horizontal- seismlc force to the
l-rrr nrrrnneae
nf
weight of the element being hrrnorl
orces in non-buil-ding
also include al-1 normaf
operating contents for items such as tanks, vessels,
n: I nrr'l al- i na
el- rrrnt- rrrao ,
:nrl
B.
fles
SC.i
v9JrYrr i Crn
oEJJrrL SmiC
he wei oh{- shaf f
f
{urlv
nin'ina
Seismic bracing shal-l be designed for seismic
fects/accel-erati-ons as per the l-atest NYC Building
Code and ASCE-7-2002. For Seismic Design Category C
and D, al-l- MEP components shal-l- be designed and
constructed to seismic requirements.
ef
1.
MrcscA
Sei smi r- Dcs i crn Caf ecrorv
vg9vYv!J911
and Seismic Accelerations
are indicated on the Structural
Drawi-nqs.
SEISMIC CONTROLS, FIRE PROTECTION SYSTEIdS
15303
7
07
tLW NO.: 063545
/29/L0
2.
(.
Component Importance Factors are indicated in the
"Component Seismic Importance Factors Ip,, schedule
on the Fire Protection Drawinqs.
The horizontal acceleration levels for sprinkler and
fire standpipe piping, sprinkler and fire standpipe
f i ro
nrlmr1<
hnnq.| or
nrrmne f
dni
vL rrar<
:nrl
f i ra
r.rrl
r-mP
controllers are as defined in NFPA No.13-2002 and NFPA
No.20-1999. NFPA L4-2003 Articles 4.4 and 6.L.2.5
ror-rtii
!uyur!v
ra
fLrrqe
haf
.l-
ho
urrs
ini
ni na t
J vrrrrrly
standpipe and fittings
h:nni
IIcrIl9fIr9 na
:nrl
o.IIll
?rr=a'i nn
L/!auftlv
be in accordance with
nf
\J!
€-i -^
!ars
NFPA 13-
2002.
PART
2-
2.OL
MA}TUFACTI'RERS
A.
2.02
PRODUCTS
Failure is defi-ned as the discontinuance of any
attachment point between equipment and structure,
verticaf permanent deformation gfreater than \/8"
and/or horizontal 'oermanent deformation sreater than
r/4,,.
PRODUCT DESCRIPTIONS
A.
Thrust Limiters
The horizontal thrust restraint shal-l- consist of a
spring element in series with a neoprene molded cup
with the same defl-ection as specified for the
Thc snri ncr el-ement shal-l- be
mountings or hangers.
designed so it can be preset for thrust at the factory
and adjusted in the fiel-d to allow for a maximum of
1-/4" movement at start and stop. The assembly shall
be furnished with 1 rod and anql-e brackets f or
attachment to both the equipment
and the structure.
Hori- zontal- restraints
shal-l- be attached at the
centerl-ine of thrust and symmetrical on either side of
the unit. Horizontal- thrust restraints shal-l- be type
WBI/WBD as manufactured by Mason Industries, Inc. or
approved equal.
P,
Pipe Riser Resilient Support
Al-l-directlonal acoustic pipe anchor shal1 consist of
two steel tubes separated by a minj-mum of 74" thick, 50
durometer neoprene.
Include steel and neoprene
NYCSCA
SEISMTC CONTROLS, FrRE PROTECTTON SYSTEMS
15303
8
07
/2e/L0
LLW
NO.: 063545
verti-ca1 limit stops arranged to prevent vertical
travel in both directions. Design support for a
maximum l-oad on the material of 500 psig and for equal
resistance in al-i- directions.
C.
Resil-ient Pipe Guides
Tel
esr:oni r:
rs!sovvyrv
Arr.hAAnanf
q!!(f.IrYErttEllL
n€
\JI
tWO Steel_
tUbeS
separated by a mi-nimum of \tt thick
neonrenc .
F'ar-tnrrzJ
sof
"v
rrili do ho'i
lrv+Yrl crh1-
r^ri
be
Shall
60 durometer
th
a shea r nin
Iexpansion and
to al-1ow vertical- motion due to pipe
contraction.
Shear pin sha1l be removable and reinsertable to allow for selection of pipe movement.
Guides shal-l- be capabl-e of motion to meet .l-ocation
requr-rements.
Seismic Bracing/Restraint Devices
Manufacturers:
Mason
t-\
Tndustries, Inc.
Vibration El-iminator
Co.
, Inc.
Vibration Mountinss & Controls/Korfund
d.
International Seismic Application Technology
(rsAT)
.
Restrained Elastomeric Mount: Bridge bearing
neoprene mount j-ngs shal-1 have a minimum static
deflection of 0.2' and all directional seismic
capability. The mount shall consist of a ductil-e
iron casting containing two separated and opposed
molded neoprene elements. The el-ements shal-lprevent the central- threaded sleeve and
attachment bol-t from contacting the castinq
during normal operation.
The shock absorbing
neoprene materials shall be compounded to bridge
bearing specifications. Mountings shal-l be tested
and certified in accordance with ICC-ES AC 156
for the maximum certified horizontal and vertical
load ratings. Mountings shal1 be Mason Industries
Trrno
.Jr-*.Yr--P,R r'\r arrr,'rrarrorl
aarra I
Sheet metal panels shall be bol-ted to the walls
or supporting structure by assemblies consisti-ng
N:rcscA
SEISMIC CONTROLS, FIRE PROTECTTON SYSTSMS
15303
9
o7
tLI[
/2elLO
of
a nA.)nrono
^ 1^^--^^
1^rrrsh
NO.
:
063545
ino r-rrshioned between 2 steel_
The outer
sl-eeve shal-f prevent
the
sheet metal from cutting into the neoprene.
Panel hol-es shall be enlarged as required.
Neoprene el-ements shal-I pass over the bushing to
n
cushion the back panel horizontal-lv.
A
J^r^^-l
LUE-L
disc shall cover the inside neoprene element and
the inner steel- sl-eeve shall be elongated to act
as a stop so tightening the anchor bolts does not
interfere with panel isolation in 3 planes.
Bushing assembfies shall- be applied to the ends
of steel- cross members where applicable.
Atl
neoprene shal-f be bridge bearing quality.
Bushing assemblies shall be type PB as
manufactured by Mason Industries, Inc. or
approved equal.
4.
Washer/Bushing: A one-piece molded bridge bearing
neoprene washer/bushing shall be used.
The
bushing shall surround the anchor bol-t and have a
flat washer face to avoid metal to metal contact.
Nconreno
l'rrr
sh i
vuurrrrrYr
nos
manufactured by
approved equal.
5.
sha
rrrur- I I
ha
t-u
rzna
_vv
_Y
Mason Industries,
HG
Inc.
aS
or
Seismic cable bracing shall- consist of galvanized
steel aircraft cables sized to resi-st seismic
loads with a mj-ni-mum safety f actor of two and
arranged to provide all-directional- bracing.
Cabl-es shall be pre-stretched to achieve a
certified minimum modulus of elasticity.
Cable
end connections shall be steel- assembli-es that
swivel to f inal i-nstall-ation angle and utilize
two clamping bolts to provide proper cable
engaqement. Cables shal-l not be al-l-owed to bend
across sharp edges. Cabl-e assemblies shal-I be
tested and certifi-ed in accordance with ICC-ES AC
156
verifying the maximum certified Ioad
ratings. Cable assemblies shall- be secured with
Mason fndustries Type SCB (or approved equal) at
the ceiling and at the cl-evis bol-t. Mason
Industries Inc. type SCBH (or approved equal)
shal-l be used between the hanger rod nut. and the
clevj-s. Mason Industries type SCBV (or approved
equal ) shal-1 be used if cable is clamped to a
beam.
NYCSCA
sErsMrc coNTRoLs, FIRE PROTECTTON SYSTEMS
15303
10
o7
/2e/L0
LLW
NO.: 063545
Seismic sol-id braces shall- consist of steelangles or channels to resist seismic loads with a
minimum safety factor of 2 and arranged to
nrorricic aI-l directional restraj_nt. Seismic so.l-id
brace end connectors shall- be steel assembl-ies
that swivel- to the f inal- installation angle and
util-ize two through bolts to provide proper
attachment. Seismic solid brace assembly shall
be tested and certified in accordance with ICC-ES
AC 156
verif ying the maximum certif ied l-oad
ratings. Solid seismic brace assembl-ies shall- be
1-
rzna
"Jy"pJu!+vu'
Tnn
rrrv.
v!
^r
qqP. r c
rnnrnrzarl
qI/I1!vvsu
manUf aCtUf ed
aarr =
EYuof
l
trrz
Ma
son
Tndrrs1- ri cs
_
.
Steel- angles, sized to prevent buckling, shall- be
clamped to pipe or equipment rods utiliz:-nq a
minimum of three ductil-e iron clamps at each
bracing location when required.
Pnrl
n I rmn
support rods is not acceptable.
tA,6tdlhdnt
B.
assemblies shall be tested and certified in
accordance with ICC-ES AC 156. Rod clamp
assembl-ies shall be Type SRC as manufacLured by
Mason Industries, Inc. or approved equal.
Pipe clevis cross bolt braces are required in all
bracing locati-ons. They shall- be special- purpose
preformed channels deep enough to be hel-d in
place by bol-ts passing over the cross bol-t.
C]evis cross braces shall be tested and certified
in accordance with ICC-ES AC 156.
Clevis cross
brace shall be type CCB as manufactured by Mason
Tnrlrr cl- ri ac , Tnn
annrnrrarl
affrri I
Qao E-i arrra
?approv-*
-nc. or
^r
9 of ASHRAE Practical Guide to Seismic Restraint,
7999.
All--directional seismic snubbers shall- consi-st of
i-nterl-ocking steel members restrained by a onepiece molded neoprene bushing of bridge bearing
Bushing shal1 be replaceable and a
minimum of I/4" thick.
Rated loadings shall not
exceed 1000 psi. A minimum air gap of I/8" shallbe i-ncorporated in t.he snubber design in all
directi-ons before contact is made between the
rigid and resil-ient surfaces. Snubber end caps
shall- be removabl-e to allow inspecti-on of
internal clearances. Neoprene bushings shall be
rotated to insure no short circuits exist before
svstems are activated. Snubbers shall- be tested
NYCSCA
sErsMrc coNTRors, FrRE pRoTEcTroN sysTEMs
15303
11
07
/29lLO
LLTI NO.
:
063545
and certified i-n accordance with ICC-ES AC 156
verifying the maximum certified horizontal- and
vertical- load ratings.
Snubber shal-l- be Type
Z-L225 as manufactured by Mason Industries, Inc.
or approved equal.
'1
n
All directional seismic snubbers shall consist of
interlocking steel- members restrained by shock
absorbent rubber material-s compounded to bridge
bearinq specifications.
Elastomeric materials
shal-l- be replaceable and a minimum of 3/4" thick.
Rated loadings shall not exceed 1000 psi.
Snubbers shal-l be manufactured with an air gap
between hard and resilient material- of not l-ess
than 1/8" nor more that 1-/4". Snubbers shal1 be
installed with factory set clearances.
The
capacity of the seismic snubber at 3/8" deflection
shall be equal or greater than the load assigned
to the mounting grouping controlled by the
snubber mult.iplied by the applicable rrGrr f orce.
Submittal-s shall include the load deflection
curves up to I/2" deflection in the xt y and z
planes. Snubbers shall be tested and certified
in accordance with ICC-ES ac 156 verifying the
maximum certif ied horizontal- and verti-cal load
*^+
-^^
LOLf -; rrvD.
Snubbers shall be seri-es Z-I}IT as
manufactured by Mason Industries, Inc. or
approved equa1.
l1
Stud wedge anchors shall be epoxy adhesive based
and manufactured from full diameLer wire, noL
from undersized wire that is "rol-Ied up" to
create the thread. The stud anchor shall also
have a safety shoulder which fully supports the
wedge ring under load. The stud anchors shal,l be
tested and certified in accordance with ICC-ES AC
156 verifying its al-lowable loads. Drill-in stud
wedge anchors shal-l- be type SAS as manuf actured
by Mason Industries, Inc. or approved equal.
T2
Femal-e wedge anchors are preferred in floor
locations so isol-ators or equipment can be slid
into place after the anchors are install-ed.
Anchors shall be epoxy adhesive based and
manufactured from full diameter wire, and shallhave a safety shoulder to fully support the wedge
rinq under l-oad
Female wedge anchors shal-1 be
NYCSCA
SEISMIC CONTROLS, FIRT PROTECTION SYSTEMS
15303
L2
07
LL!{ NO. : 063545
/29/L0
tested and certified in accordance with
ICC*ES
AC
56 rzeri
vs!r!Jrrrvf rz.i nr*
loads .
Dril-l--in
female wedge anchors shall be type SAB aS
manufactured by Mason fndustries,
Inc
or
- r r ^,vable
afJvv
+1^^.i
LIIUft
'1
rJv
approved equal.
t_3
Listed
l-exibl-e spherical expansion j oints shal-lEPDM in the covers, liners
Any
and Kevlar@ tire
cord frictioning.
substitutj-ons must have equal or superior
physical and chemical- characteristi-cs.
Sol-id
steel rings shal-l be used within t.he raised face
f
employ peroxide cured
rrrt'rl^:er f l:nocd
encls to rlrerrenf nrrl I nrrt
Flexibl-e
cable
bead'r wire
is not acceptable. Sizes 2u and
'r rrq
'r
^ -^^ - DIIc:lf,f
^1" ^
harrc
wo snhereS
f orYg!
reinf orced with a
vs
Lwv
oyrl
ductil-e iron externaf ring between spheres.
Flanges shall- be split ductile iron or steel with
hooked or similar interlocks.
Sizes 15" to 24"
may be single sphere .
Sizes 3 / 4" to l-r4u may
have threaded two piece bol-ted flange assemblies,
one sphere and cable retenLion. Connectors shall
be rated at 250 psi up to 170o F with a uniform
drop in allowabl-e pressure to 2I5 psi at 250" F in
sizes through 14". 16" through 24" single sphere
minimum ratings are 180 psi at 170o F and 150 psi
at 250" F. Hiqher rated connectors may be used to
A11 expansion
accommodate service conditions.
joints must be factory tested to 150% of rated
pressure for 72 minutes before shipment. Safety
factors to burst and flange pulJ-out shall be a
minimum of 3/L. Concentric reducers to the above
1-
-i
-^^ r
!-^+q Lf,rrv
rrro.y be
expans j-on j oints .
substituted
f or
equal
ended
Expansion joints shall- be installed in piping
gaps equal to the length of the expansion joints
under pressure. Control rods need only be used
in unanchored piping locations where the
manufacturer determines the install-ation exceeds
the pressure requirement without control rods.
If control rods are used, they must have ttu thick
Neoprene washer bushings large enough in dj-amet.er
to take the thrust at 1000 psi maximum on the
washer area.
All expansion joints shall be install-ed on the
equi-pment side of the shut of f valves.
N:rcscA
SEISMIC CONTROLS, FIRE PROTECTION SYSTEMS
15303
13
07
/2elLO
LLIV NO.
:
063545
L4. Listed f l-exible stain]-ess steel hose shall have
stainl-ess steel braid and carbon steel fitt.ings.
Sizes 3" and larger shal-l- be flanged. Smaller
sizes shall have mal-e nipples. Minimum lengths
shal-l- be as tabulated:
h lan^6a{
3"xL4", 4"xL5", 5"x79", 6"x20", 8"x22",
I0"x26", t2"x28", 14"x30", 76"x32"
Mr I o IrIi nn'l ac
t4"x9" , 3,a"xl0" , L"xII"
,
L-I / 4" x1-2" , 1,-I / 2" xL3"
2"xL4", 2-I/2t'xI9"
Hoses shal-l be inst.al-led on the equipment side of
the shut-off valves horizontally and paral-l-el to
the equipment shafts wherever possible.
15
Hoirsekecni
rrvuDEAEsIJrrry
ncr -.-r
_t:/ou
^*^1-^..^a)
crtl(/lr\Jr
shall
COnSiSt Of
a
ductile iron casting that is tapered and
hexagonal, smaller at its base than at its top.
Tha ,r^nar ^^':tion
shal-l have holes for rebar to
_vvr
pass through. The anchor shall be continuously
threaded from top to bottom for the atLachment of
soleplates.
Housekeeping pad anchors shall be
attached to the structural slab uslng a stud
wedge anchor. Housekeeping pad anchors shall be
type HPA and stud wedge anchor sha1l be type SAS
both as manufactured by Mason Industries, Inc. or
approved equa1.
PART
3-
3.01
PREPAR;ATION
A.
EXECUTION
For seismic braced equipment installed indoors, allmetal parts, including rails and bases, shall be
painted at the factory with one coat of primer paint
and one coat of aluminum paint. Other means or rust
resisting painting may be accepted, subject to prior
approval.
mrcscA
SEISMTC CONTROLS, FrRE PROTECTTON SYSTEIIS
15303
L4
ot
LLII
lzelLo
B
NO.
:
053545
Seismic braced equipment installed outdoors shal-1 have
steel parts hot dipped galvanized, all bol-ts
and all- springs cadmium plated and
all
cadmium plated,
neoprene coated.
C
3
.02
Seismic braced equipment installed outdoors shall be
designed and instal-led to resist wind loads in
accordance with the NYC Bui-ldinq Code.
SUPPTEMENTAL INSTAJ"LATION
A
Af
nU
arnh
sqUII
'l
aa'.j6166nt
gYLlIyrttErrU
Or-af
IvUqLMl
inn_ t
f1^^
LIfg
nrorz-i
vvIUE fle
PL
!gYUrrl
i-ed
deflection under the imposed load to produce uniform
loading and defl-ection even when equipment weight is
not evenlv distributed.
Jack inerti-a blocks and
bases into position and wedge in place as required;
Ieveling bolts shal-1 not be used as jacking screws.
Afl-or
n!LE!
anrr-inman1gYUfytrrEtlL
adirrstcrl-
ic
fD
romn\za
in
Ill
nl:na
Pro.\-g
r^radnac
anA
ctIlu
anfl
Iarralinrr
fgvglJrrv
-iar:ks-
hn'll-q
vvrLo
VeftiCal
ar^
qrs
l-imit
stops shall be out of contacL during normal operation.
B.
Where the fl-oor is
waterproofed or finished with
waterproof cement, install seismic bracing in such
manner that the waterproofing is not damaged.
3.03 FrELp
A
d.
QUALTTY CONTROL
.Fl-ra
hrimn
rrrE
manUfaCtgfef
lttaftulcl(JLLIIE:I
yurrry
shal
Drrq!r
'l
i nsner:*
rrroyguL
!l^^
Lrfg
1^+-rl
uvrrryrgLgu
hrrmh
yurrrl/
install-ation and report in writ j-ng any install-ation
error or faults that could affect performance. Per
NFPA 20-I999 Article 4-6.L.2, the pumps shall be
started and al-l-owed to run. The operation shall be
observed for vibration while running. The operating
vibration Iimi-ts shall be in accordance with the
Hydraulics Institute Standards for Centrifugal, Rotary
and Reciprocating Pumps. The drj-ver shall be observed
for proper operation. Submit report indicating any
sf cns
f a ken
al-uea
f n 6166611 rz nnmnl
vvlryrv
the
iSO.l_atiOn
WOf
k
including but not limited to correctinq any bent pump
or column shaft, resetting of the impeller shaft and
eJ-iminat j-ng any strain
transmitted through the
rli cnharaa
n'in
r'.Prn9.
All- reports
the Authority for final approval
NYCSCA
shall- be reviewed bv
SEISMIC CONTROLS, FTRE PROTECTION SYSTEMS
15303
15
07
/29/LO
3.04
LLW
NO.: 063545
GENERAI
A
All seismic bracing systems shall- be installed in
strict
accordance with the manufacturers written
instructions and all certified submittal data.
R
Instal-lati-on of seismic bracing shalf not cause any
change of position of equipment or piping resulting in
stresses or mi-sali-qnment.
(-
Bring to the architects/engineers attention any
discrepancies between the Contract Documents and the
field conditions or changes required due to specific
qo'l anf i nn
equipment
pr j-or
to
install-ation.
Corrective work necessitated by discrepancies after
installation shall be at the Contractor's expense.
efvrrt
D.
Correct, dL no additional cost, all inst.allations
which are deemed defective in workmanship and
mrf
a--.i
ILTOLEL-LClID. ^'1
E.
^
Overstressing of the building structure must not occur
because of overhead support of equipment. Contractor
must submit loads to the sLructural engineer of record
for approval. Generally bracing may occur from:
Flanges of structural beams.
2.
TJnnar f rrrco ^orris
i n l-rar iOiSt
COnStfUCtiOn.
Cast in place inserts, expansion bol-ts/ wedge
type
dril-l-ed-in
concrete anchors/adhesive
anchors.
F
Cable assembl-ies are installed taut on non-isol-ated
systems. Seismic solid braces may be used in place of
cabl-es on rigidly attached systems only.
G.
At l-ocations where cable or seismic solid brace
restraints are located, the gravity support rods must
be braced when necessary to accept compressive loads
by clamping with stee1 angles that are sized t.o
prevent the buckling of the rods. A minimum of three
ductile iron clamps shall be used. Welding of support
rods is not acceptable.
NYCSCA
SEISMIC CONTROLS, frRE PROTECTION SYSTEMS
15303
15
o7
LtW NO.: 063545
/2e/LO
H.
I.
J.
K.
At all- f ocations where cable or seismi-c solid brace
restraints are attached to pipe clevises, the clevis
cross bol-t must be reinforced with braces.
Drill-in
concrele anchors for ceiling and wallinstal-l-ation shall be provided and femal-e wedqe type
anchors shal-l- be used for f loor mounted equipment.
Hand buil-t elastomeric expansion joints
may be used
when pipe sj-zes exceed 24" or specified movements
exceed support capabilities.
Equipment shalf be protected against excessive
displacement that results from high thrust in relation
to the equipment weight. Horizontal- thrust restraint
shall be used.
3.05 SEISMIC BRACING/RESTRAINT OF FIRE PROTECTION PIPING/
EQUIPMENT
A.
H
New f ire
protect
i-on
enri
nlz-l ar
.nd
c+LCrrruIJrPs
rnAn'i nn
D
^'i ^i nn
PrPrrry
shal-I be braced in accordance with NFPA 1,3-2442
the NYC Constructi-on Codes
.l
.i
f i re vruLEt-Lt(Jrl
nr^+^^f .; ^^ Er-,lLlJ-vrttetlL
^onsidered
^-..: -*^*+
fD^
\ea€at-rz
anrrinmglll
qllv
oq!EuJ
sYurlrrrrgrrL
and DrrqIJ
Shall_ vE
be DErDrrlrvqrry
SeiSmiCal'l rz hrar:ed
v!qusv
A'l
nrf
l_ife
!f!g
the seismic acceferatj-on fevels
anr'i
nman{eYuf
yrrrvrr L .
'Fhe horizontal
for
life
acceleration
rrsi-^
u9rrrY
safety
levels
sprinkler and fire standpipe piping; sprinkler
fire standpipe fire pumps, booster pumps, drivers,
flre pump controllers are as defined in NFPA No.
2002 and NFPA No. 20-L999.
(-
and
for
and
and
1-3-
The seismic bracing of fire standpipe piping and
sprinkler pi-ping is gioverned by Article 9.3 of NFPA
No.13, Standard for the Installation of Sprinkler
Systems-2002 as modified by Appendix O of the New York
City Building Code. NFPA 14-2003 Articles 4.4 and
6.1.2.5 require that the joining, hanging and bracing
of fire standpipe and fittinqs be in accordance with
NFPA L3_2002.
Listed fl-exible pipe couplings joining grooved
end pipe shall be provided as flexure joints for
n'i ni nn
NrcscA
L)-1 ll
/)'tAi vlq a
-
-l
vI
^r
rrnar
rq!Yv!.
SEISMTC CONTROLS, FrRE PROTECSTON SYSTEMS
15303
L7
07
/29/L0
LLW
NO.: 063545
Couplings shall be instal-l-ed within 24" of the
top and bottom of al-l risers. Exceptions to this
are listed in Article 9.3.2.3 of NFPA 1,3*2002.
Swing j oints assembled with l-isted flexible
fittings shal-l- be install-ed where fire nrn.|an1- i nn
piping, regardl-ess of size, crosses v'l.rrrilAina
ur luJrrY
joints.
seismic
4.
Clearance: Cfearance shall be provided around al-l
prpr_ng
extending
Wct-LID I
floors,
through
platforms, including drains, fire department
connections, and other auxil-iary piping.
size of the hole is nomlnally 2 :-n. larger than
the pipe for 1 in. nominal to 3-1/2 in. nominal &
4 in. larger than the code for pipe 4 in. &
larqer. Clearance for structural members sha1l be
at l-east 2 in. as per 9.3.4.2 of NFPA 13-2002.
l llg
Sway Bracing: Both transverse and longitudinal-
sway bracing shall- be sized and fastened per
9.3.5 of NFPA 13-2002.
Longitudinal- sway bracing shal-I be spaced at a
maximum of 80ft. on center for feed and cross
mains. The distance between the last base and the
enci of ninc
sha1l not exceed 40 ft.
.y-_vv
1.
Ton
."rur]lY of
risars
exr:eecl'i ncr 3,
.i
rrr
.i
f,rr-
^
^-^f 1^ ishal-l_ be
1
rsrrYLrr
.i
,-J.i -ra+
^^
secured against drifting
aLLy
LrJ!suLf\Jrrt
q
utilizing a four way sway lrrar-c ncr
3.5.5
of
F--
NFPA L3_2002.
Rrar:i no sh: I I
cross mai-ns.
be attaChed
A 'lann{-l.r aF t'r-yv
ninc
sha'l 'l rrvt
nn|-- be bfaCed
move
tO SeCtiOnS
differently.
Restraint of sprinkler branch lines is governed by
Article 9.3. 6 of NFPA No.13, Standard for the
Installation of Sprinkler Systems-2002 as modified by
Appendix O of the New York City Building Code.
Restraint shall be provided by use of one of the
following:
1.
NYCSCA
i ror-f 'l rz f n f eed and
rrrurr
of the buildinq that. will
D.
d
A listed sway brace assembfy
SEISMIC CONTROLS, FIRE PROTECTION SYSTEI{S
15303
18
oz
LLII NO. : 063545
/29lLo
A wraparound U-hook satisfying the requirements
of Articfe 9.3.5.3. B of NFPA L3-2002.
No. L2, 440-1b wire installed at least 45 degrees
from the vertical- plane and anchored on both
eirloe
nf
fho
-..-
pfpe.
r
Other approved means.
3.05 BUILDING SEISMIC OR EXPAI{SION JOINTS
A
R
prorzirle
r !vvrus
n.i
l/fysno
^Ec^^L^
\JrrJcL>r
r^^-.^
_LUTJP>,
^*r
crllLl
-,,jdos:
9urusDr
n.i
ne
yJ}Js
ha]_]_
L)a
joints;
pipe swlng joints and expansion joints
utili zing qrooved pipe (per Victaul-ic or approved
equal); l-isted flexible braided stainless steel pipe
loops and listed flexible braj-ded bronze pipe loops or
other l-isted flexible joints capable of accommodating
seismic displacements where pipes pass through
building seismic or expansion joints, the width of
which are shown on the Structural Drawings. Refer to
the ANSI/SMACNA Seismic Restraint Manual-, 3'o Edition,
i *'j '.^ DyD
^"^tem shall not be braced or
2008 - ^A !!Yr\-r
ri oi I --IJIIJrrr9
avvu.
attached to dissimil-ar parts of the building or to t.wo
dissimilar
buildinq
systems that may respond
differently during an earthquake without providing the
above mechanisms to absorb the movement
loops, anchors and guides shall
and
torsion,
compression
extension. The Contractor's registered professional
engineer shall- detail al-l- piping j oints that pass
hrnrrrrh
hrri I rl'i nrr qai cm-i n or expansl-on -iai nl- q
The
Contractor's registered professional engineer shal-1
also detail all- piping joints required as a result of
bracing or attachment to dissimilar building systems
or dissimilar parts of the building.
Joints,
offsets,
accommodate bending,
]_
PART
4.
4
SCHEDUTES
01 EQUTPMENT SETSMTC
BRACTNG/RESTRATNT SCHEpLLE
Equipment seismic bracing schedule shall- be submitted by
the Contractor's
registered professional
engineer.
j-pment
Schedule shall- list aII equ
with associated se j-smic
bracing.
N:rcscA
Contractor's
registered
professional- enqineer
SEISMIC CONTROLS, E'IRE PROTECTTON SYSTEIT{S
15303
19
o7
LLII
/29lLO
NO.
:
063545
shall- indicate the details of the seismic bracing of
equipment and nature of the mounting (steel dunnagie,
directly mounted to pad or mounted on concreLe filled
inertia base) .
EI{D OF SECTION
mrcscA
SEISMIC CONTROLS, FIRE PROTECTION SYSTEMS
15303
20
07
/29lLO
LL?il NO.
:
063545
LIST OF ST'BIIITTALS
ST'BMITTAT
DATE
ST'BMTTTED
DATE APPRO\ZED
Catalog Cuts of
Rrrai
na
Schedul-e of Equipment
Showing Bracing
Signed/Sealed
Shop Drawings
1. Fabrication Details for Equipment Bases
2. Details of Suspension and Support for Ceiling Equipment
3. Details of Attachments for Alf Pipes
4. Details of Seismic Bracing and Anchors
5. Housekeeping Pad Detail-s (for coordination with Structuraf
Engineer of Record)
6
- Pi oe
Deta i f s
for
Cross'i nr^r Soi
uvrJrLLfvsm'i r-
Dissimilar Building and Service Entry
rrr
v!
Exnensi on
!^ysrrurvrr
,-Ioi nl- s
vvrrruJt
-
Seismic Certification
and Analysis
1 qianarl/earIgd
s/
uvsf
vv
St
ructure
Cal-cs..
vqrvJ
(Tnclir-:l-incl
uq
LarrY
\ rrluf
Loads
Transmitted
to
)
2. Restraining Devices: ICC-ES AC 156 Certification
3. Wedge/Expansj-on/Adhesive Anchor ICC-ES AC 156 Certification
4. Riser Diagrams and Calcul_ations
Welding Certificates
Contractor' s Registered
Professj-onal Engineer' s
Installation Affidavit
***
NYCSCA
SEISMIC CONTROLS, FIRE PROTECTION SYSTEMS
15303
2L
07
/29/L0
LLVil NO.
THTS PAGE
NYCSCA
IS
:
063545
INTENTIONATLY LEFT BI,AIiIK
SEISMIC CONTROLS, FIRE PROTECTION SYSTEIlIS 15303
22
o7
/29lLO
LLVI NO.
:
063545
SECTION L5332
CoMBINATION IIET STAr{DPrPE/SPRINKLER SYSTEM
PART
1.01
1-
GENERAL
DESCRIPTION OF
A.
WORK
Provide a combination wet sprinkler/wet standpipe
system as specified herein, ds shown on the Drawings
and as needed for a complete and proper install-ation.
Product speci f ic requirements are cont.ained herein,'
Section 15301, General Provisions for Fire Protection
Systems Work, shaff be referred to for general
requirements.
R
Work Included:
A'l I
n!I
n'i nincr
yryrlrY,
onrrinmonlsYuaIJlLLgIlLt
h
IlOlrVg!Dt
ara
gLU.
2a
qo
ana-ifia.{
Dl/sU.J-
herein, ds shown on drawings and as required by
authorities.
1.
su
l-ocal-
Prpe ano r f tt'l_ngs .
Check valves.
Control val-ves.
Siamese connections.
Roof Manifold.
Hose Val-ve and Cap.
Hose Val-ve Cabinet.
Fire Hose and Nozzles.
Lobby Hose Cabinet.
10. Lobby Storage Cabinet with locking
Key.
11. Paintinq and Identification of Pipe.
L.02
RELATED WORK SPECIFTED ELSEI{HERE
A
NYCSCA
P.ain1- ina
COMBINATION
Section
I{ET STA}IDPIPE/SPRINKLER SYSTEM
09900
15332
1
o7
Ltl[
/2elLO
P,
Seismi-c Controls, Fire
Protection
C
D
1.03
NO.
:
063545
Section
Svstem
1-5303
Di-vision 15 Sections.
Division 16 Sections.
ST'BMITTA],S
A
Product Data: Certifi-cate for Hose Threads: Verify
that the hose threads on Fire Department connections
match the threads on equipment used by the New York
City Fire Department.
B
Submit copies of alf permits and approved drawings
issued by the Const.ruction Inspection Division (CID) .
C.
Shop Drawings
Complete combination wet standpipe/wet sprinkler
system layout indicating t.he locat ions of
qrrri rrr^r9!
nkl or
JIJ!
trc-l^
rlco.LlD
t
L^^^
IIUDej
rzrl
v qr rrac
v so t
rlarz.i
aac /
v a\-ED
vE
:nrl
CtItLr
accessorles. Include separate details of special
or not easily visualized piping arrangem"r-ri= and
inspector's test valves and connecti-ons.
Hydraulic calculations shall- be complete and
cross referenced to the appropriate drawing
sheets.
Wiring Diagrams: Power, signal,
and control
t'ri ri nn
n'i €ferentiate
between manufacturerinstal-Ied and fiefd-inst.al-l-ed wiring.
Pina
- *r-
anr{ fift-i
*--*ngs.
Check val-ves.
Control valves.
Siamese connation.
NYCSCA
8.
Roof manifold.
v
Hose val-ve and cap.
1n
Hose val-ve cabinet.
COMBINATION ![ET STAI{DPIPE/SPRINKLER
SYSTEM 15332
2
07
/29lto
LLII
NO.
:
063545
11. Lobby Hose cablnet.
L2. Fire Hose and nozzl-es.
L)
E
Test Reports as specified in the Fiel-d Quality ControlArt.icle.
Cert.ification of Installation:
nnmnl al_ i nn
of
Submit certificate
snri rrrr!ru!
nk l er/stancln'i
/ r uqrrvl/ryu
uy!
ne
r"rnrlz
vvv!
r\t
upon
whi g[
indicates that work has been tested in accordance with
The New York City Building Code NFPA 13 (2002
Edition), NFPA L4 (2003 Edition) and afso that system
is operational, complete and has no defects.
Mai-ntenance data: Include an instruction manual
describing the operation and maintenance of the system
in the maintenance manual.
g
Maj-ntenance materials: Sprinkler heads, steel cabinet,
wrench, caps and chains.
1
D'ina
rnrl
2.
Valves.
I'it-t-'
- , _,rngs
.
Siamese Connections.
A
Roof Manifold.
Hose Val-ve and Cap.
Hose Valve Cabinet.
L.
04
SUPPLEMENTAI QUAIITY ASSURAT\ICE
A. Codes and Standards
NFPA CompJ-iance: Install combinati-on wet f ire
standpipe / weL sprinkler systems in accordance
with NFPA 13-2002 and NFPA L4-2003.
UL Compliance: Provide sprinkler/standpipe
products in accordance with their listings and UL
standards; provide UL label on each product.
3.
NYCSCA
City Construction Code: Comply with the
requirements of The New York Citv Construction
New York
CoMBTNATTON T|ET STAIIDPrPE/SPRTNKLER
SYSTEM 15332
3
07
LtW NO.: 053545
/29/L0
Codes and with the Rules and Regulations of the
Rrri I di nr^r l)on:r1- mcn1- - tho
NYC Of fiCe
Of TeChniCal_
Certification & Research (OTCR), The Division of
Fire Prevention of the Fire Department and al-1
other public authorities having jurisdiction.
4.
Fire
Department/Marshal
Compliance: Instal-l
sprinkler/fire
standpipe systems in accordance
with local- requlati-ons
of the NYC Fire
Department.
5.
Screw Thread Connections: Comp1y with local Fire
Department regulations for sizes, threading and
arrangement of connections for
aarrinmanr- to Siamese connections.
1.05
fire
department
EXTRA }{ATERIAJ,S
A. Heads: For each style and temperature ranqe required,
furnish additional sprinkler heads, amounting to six
heads when fewer than 300 heads are installed and
twelve heads when between 300 and L200 heads are
install-ed. All the spare heads will- be enclosed in a
steel cabinet with a special sprinkler wrench to be
del-ivered to the Authority. Obtain a receipt.
R
Del-iver also two spare caps and cha j-ns f or each
Siamese connection
Obtain a recei-pt.
PART
2
PRODUCTS
2 . OL MA}IUFACTI'RERS
A
Qrrl-rjaal-
a
nnmnl
vvrrlyrrqtrug i enna
1uv
w.i
wI
h
1LIMY
rongjlgglents
Of
the
Specifications and Drawings, manufacturers offering
products which may be incorporated in the work
incl-ude, buL are not limit.ed to, the following:
Potter-Roemer Inc.
Croker Corp., Division of Fire-End and Croker Corp
Elkhart Brass Manufacturing Co., Inc.
2
.02
PIPING IIATERIAJ"S
A.
N':rcscA
r/-^^^
ggtlg!
-- af
I
COMBINATION
IIET STA}IDPIPE/SPRINKLSR SYSTEI{ 15332
4
07
/29lLO
LLVI NO.
1.
Prorzi do n in'i ncr maf
a I s and
f ar:torv
qrru
fLrq uv!erirur9
063545
f abricated
piping products of sizes, types, pressure and
temperature ratings, and capacities as indicated
on the Drawingis. Provide f ittings of material-s
.-_+^_.:^.r^
rll
in
Jqa D uSed
uDgu
the
LlIg
DIJ! lrtn
Snr.inkler
rE!
standpipe systems.
tha1ni*^
urrq L mafr_h
rrlq LUrr
_yr_yg
fire
2.
:
/
rrra LEI
/
Provide signed and sealed hydraulic calcul-ations
prepared by a NYS licensed professional engineer
for the Authority's review that incorporat.e the
final pipe sizes and sprinkler head l-ocations.
The calcufations are to show that a 5 psi safety
factor,
which is part of the Contract design
shown on the documents, is maint.ained over the
code requi-red calculated pressures.
In order to accommodate additional- sprinkler
heads and fittings or revisj-ons done to the pipe
routing due to interferences, branch piping may
-,vised in size and l-ocation. Sizes of
risers, mains, cross-over maj-ns and sub*mains are
not to be changed from those on the Contract
h^^
,.]
f n
l,-^
-^--.:
^^J
-.:
.-
^..i
-^
^-l
1 ^^^+..i
^*
Drawings.
B
Aboveground
Pipe, Within the Building
1.
Pipe sha1l be schedule 10 standard black steel as
per ASTM 195 for pipe si zes up to 6-inch (wal-l
thickness, .134 inch), when j oined by ro.l-l;F
arnnrrar{
fi{-+in^-hA
v!vvvEu
rl
IL
LLIItgD
cttlL,t
instal-led i-n buildings
not exceeding 300 feet in height and having a
system operating at up to 300 psi.
)
Pipe joined by threaded fittings or cut-groove
fittings shall comply with minimum wal-l thickness
of schedul-e 40 for pipe sizes ranging f rom 6-in
and up to 8-in in diameter when the buil-dinq's
heiqht is above 300 feet.
Fittings shall be b1ack, threaded malleable cast
iron or f langed casL stee.l- and shall have a
pressure rating of 350 psi water working
pressure. Pressure ratings shall be cast in or on
the fittinqs.
N:rcscA
CoMBTNATTON
r{ET STANDPTPE/SPRTNKLER SYSTEM 15332
-
5
07
LtW NO.: 063545
/29lLO
Mechanical Coupling Type Fittings:
The use of mechanical coupling type fittings
on fire standpipe / sprinkl-er combination
system in l-ieu of threaded fittings
or
flanged fittings
or grooved fittings
is
acceptable j-n sizes 2" to 8" incl-usive. The
mechanical couplings shall- be sel-f -centering
and shal-l- engage and lock the grooved pipe
and / or fittings in a positive couple while
a I I nvli nrr
f!v!
nr
enma
nf
or
daaraa
:na,. l a angufar
pape
deflection, contractj-on and expansion. Each
coupling shaf f consist of a mall-eable iron
or ductil-e iron housing in two or more
conmanl-e
qincr'l a
-
mnlflafl
rlrvfvuv
r'nmnngjlign
vvlLLI/v!
sealing gasket, and two or more steel ovalneck track bofts with hex nuts.
l^t
Flexrble couplings shall be of St.yle-77 as
manufactured by Victaul-ic Company of Amerlca
nnrrnl
i nn
or
approved
s\4uqf
Entire
installation i-ncluding pipe grooving shall
be performed in accordance with the
manufacLurer's i-nstructions. Only couplings,
together with their respective grooved end
pipe fittings
having fire
department
approval will be accepted.
.
C.
Underground Pipe -Inside and Outside the Building
I *'i
-.^^ Jllcr
^'^.11- be ductil-e iron class 52 for 4"
PrPtr:J
pipe size and cl-ass 56 f or 6" pipe size
n'1
nrf
mor-h:ni
rtLvvrlqrlrvql
r':'l
in'i
nfU
J vllr
nina
Irryg.
Tn
rll
:rlrl'i
qUUI
i nn
1Uf,Vllt
J-l.ra
Ltlg
fn-m^
lAlttC
n€
U!
the manufacturer and the pressure to which the
prpe was tested shall- be permanently and legibly
indicated on all- pipes.
Fittings shall be ductile iron mechanical joints
with pressure rating of 350 psi. Pressure ratings
shall be permanently indicated on the fittings.
Duct.ile iron pipe shal-l be lined in accordance
with AVWA C104, Cement-Mortar lining for DuctileIron Pipe and Fittings for Water.
NYCSCA
COMBINATION
IIET STA}IDPTPE/SPRINKTER SYSTEM 15332
6
01/29/LO
2.03
LLW
ITAI{GERS
A.
AI{D
NO.: 063545
SUPPORTS
Adjustable steel clevis hangers, adjustabl-e steel band
hancrers
rlr
adirrs1- alrl o
l'rand
h:nrrorc
piping hangers and supports.
Two-bol-t riser
supporrs.
cl-amps f or
fOr
hOriZOntal-
vert ical
piping
Steel turnbuckles and malleable iron sockets for
hanger-rod attachments .
3.
Concrete inserts, top-beam C-clamps, side beam or
channel clamps or center beam clamps for building
attachments. C-type clamps used to attach hangers
to the building structure in areas subject to
earthquakes shall- be equipped with a retaining
strap or safety hook to prevent movement. See
Fiqure 1-1 of ASHRAE Practical Guide to Sei-smic
nestraint, Iggg. C-type clamps, with or without
qf r-^^
ref ai ni no DU!ClP-7
!ELqIITIIIY
^r^^'r'r IrOt
DIJCIJJ
be USed tO attaCh
braces to the buildinq structure.
4.
2.04
The seismic bracing of sprinkler/ standpipe
piping is governed by Articl-e 9.3 of NFPA No.1302 & Article 4.4 of NFPA No. 14-03, respectively
standards for the Installation of Sprinkler &
Standpipe Systems as modified by of the NYC
Building Code.
VAL\ZES
A
A11 sprinkler and standpipe valves shall be ULlFM
approved. Provide valves shown on the Drawings, needed
for a proper installation, and complying with the
following:
1.
Gate Valves: 300 psi WWP: 3/4" to 2", bronze
body, OS&Y indicating type; double or wedge disc
with threaded ends. 2 I/2" and up: IBBM, OS&Y
indicating type; doubl-e or wedge disc with end
connections as required to sui-t the piping
svstem.
Val-ve Locki-ng Devices: chain z 3/16" galvanized
steel-, welded link; padlock; key tags: l-- tt" dia.
NYCSCA
COMBINATION I{ET STAIVDPIPE/SPRINKI,ER
SYSTEI{ 15332
1
o7
/2elto
LLII NO. : 063545
Brass, stamped with val-ve number and service; "S"
hooks: brass , for securing keys to key tags.
Check Val-ves: IBBM, single clapper swing check
with metal to metal or rubber faced checks,
suitable
for
horizontaland
verticalinstallation; end connections as required to suit
r1^^
prpr_ng
psi.
Accepted
system;
300
manufacturers: Stockham, NIBCO or other approved
LIIE
equa1.
B
Control Valves
Ri-ser control- valves shall be O. S & Y. gate
valves with flanged cast iron body, bronze
mounted and 300 P.S.I. WWP, Stockham G-634 or
NrBCO F-607-0.
They shall- be electrically
supervised by tamper switches t.hat send a signal
to the fire alarm system. Control val-ve location
shall be clearly indicated with necessary signs
and arrows.
2.
Floor control valves shall be install-ed at the
point of connection to the riser on each floor.
Valves shal-l be fitted with a supervising
electrical tamper switch. Provide a fl-oor control
valve assembly as per Figure A. 8 . L6 .4 .2 (b) of NFPA
L3-2002 in the sprinkler supply piping on each
floor.
Sectional and riser control vafves 6 inch and
larger shall have a minimum 3.a" inch val-ve by-pass.
4.
Metal tag wlth number identifying control valve
shall- be conspicuously marked with the number
assigned to it on the riser diagram for the
standpipe system. The marking shall be in white
fi arrraa
!+.,s!vv,
l1
/^
r ,2"
hiqhr
ofi a 2" square engraved
anodized aluminum tag with a red background. Tags
shal-1 be as manufactured by Seton Nameplate
Corp.,
New Haven,
Connecticut or by
EMED Co.
Special Valves
Provide val-ves, UL l-isted, in accordance with
their listing.
Provide sizes and t.ypes that
match piping and equj-pment connections.
N:rcscA
COMBINATION ITET STAI{DPIPE/SPRINKLER
SYSTEM L5332
8
o7
/29lLO
LLTI NO.
274"
(far
:
063545
Angle Hose Valve and lta" Hose connection
q.l-arvoq rrraafar
1 nnO qrrrrrra
faa.l- \. .
!euL/
Angle hose valve, with threads conforming to
FDNY standards, shall be 2tt' similar to
Potter Roemer model- # 4015, 2%" X Lh" red
enamel- steel hose rack simil-ar to Potter
Roemer model # 2194; )74" hose rack brass
nipple simil-ar to model # 2156 (Potter
Roemer) ; 2r/tu x It1" brass reducer (Potter
Roemer model- # 2810 ) ; L2t" pin lug brass
(Potter Roemer, model 2934); Il/t''
coupling
'linorj
rrllEu
rrnlrz
yUJy
fIav
!reA
hnco
rrvre
/I^n^l-L
\-LgiI9 Lrl
CtD
hi\r
lLlcry
J-ro
Us
required) see Potter Roemer, model 2915; !%"
brass nozzLe see Potter Roemer, model 2941;
)t'4r escutcheon see Potter Roemer model 275L.
Provide Ttt" diameter hose of sufficient
lengths to suppress a fire in the stage
area. Hose connections sha1l- be equipped
with a fog nozzLe and be mounted in a
cabinet.
i^\
21,2" AnqLe
Hose Val-ve:
Angle hose val-ve, with threads conforming to
FDNY standards, shall be 2t4" similar to
Potter Roemer model- 4015; )1,2't cast brass cap
with female hose thread as per Potter Roemer
model 4625; )L-7" pin ]ugs and chaj-n as per
model 215L (Potter Roemer). If hose is not
instal-1ed in a cabinet, escutcheon shal1 be
Potter
2.
Roemer model- 47L2.
Al-arm Check Valve: Provi-de cast-iron water f low
alarm check valve, 300 psi working pressure.
Alarm check valve shall be equipped with a
pneumatic retard device to prevent false alarms
due to water surqes.
Water Flow Detector: Provide a paddle type water
fl-ow detector in the sprinkler supply piping in
the location indicated on the Drawi-ngs. Detector
shal-1 be so constructed and instal-led that any
fl-ow of water from the system equal to or greater
than that from a singJ-e automatic sprinkler of
the smal-l-est ori-fice size installed on the svstem
NYCSCA
COMBINATION I{ET STAI{DPIPE/SPRINKLER
SYSTEM L5332
9
07
tLT[ NO. : 053545
/29lLO
will result i-n an audible alarm on the premises
within 5 minutes after such fl-ow begins and until
such flow stops. Listed paddle type water fl-ow
detector does not require approval number from
NYC Office of Technical Certificat.ion and
Research
(OTCR).
Backflow Preventi-on Val-ve
The
backflow
el or-l- ri r.a'l I rz
preventor
qrrnarrz'i cad
1-"
py
valves
shall
be
r^**^r
^
cl
Lo.rrrPE
switch
installed in accordance with NFPA 12 and
senarate'lrz annunciated.
Tamncri ncr with
t.he
backfl-ow preventor valves shall send a si-gnal to
the fire alarm svstem.
5.
Electrical Subcontractor shall- provide the fire
protection electric afarm equipment including the
control panel, siqns, wiring, etc. A11 equipment
for the Combination Wet Standpipe /Sprinkler
system which is not specifically cal-l-ed for to be
provided by any other contractors and/or
subcontractors shal1 be provided by the Master
Fire Suppression Piping Subcontractor.
Approved Manufacturers
:
Grinnel-l- Fj-re Protecti-on Systems Co. , Inc.
Firematic Sprinkler Devices
Reliable Automatic Sprinkler
Victaulic Co. of America.
2.05
Co.
GAUGES
A
Provide gauges shown
with the foll-owinq:
on
the Drawings and complying
Provide pressure gauges of materials, capaci-ti-es
and ranges, desiqned and constructed for use in
service as required:
Type: General- use, I% accuracy, ANSI 840.1.
NYCSCA
b
Case: drawn steel or brass, cast aluminum,
shatterproof glass fens, 4t/r" diameter.
c.
Connector: brass with I/4" mal-e
COMBINATION I{ET STA}IDPIPE/SPRINKLER
NPT.
SYSTEM 15332 -
10
07
/29lLO
LLTil NO.
d
Scal-e:
white
coated
permanently et.ched markings.
:
063545
with
aluminum,
Range: conform to the following:
1) Vacuum: 30" Hg 15 psi.
200 psi.
2) Water: 0
2.
Approved Manufacturers
Ametek /US Gauge
:
Ernst Flow Industries
Marsh Beffofram
Mi I innn
f-nrnnral--irri
q uJ
Trerice
(H.
urvrr
nn
O) Co.
Werss fnstruments, Inc.
Wesler Instruments
R,
Pressure Gauge Cocks:
Provide pressure gauqe cocks between pressure
gauges and gauge tees on piping systems. Construct
gauge cock of brass with I/4" female NPT on each
end, and \\T'l handle brass plug.
a.
Syphonz L/4" straight coil- constructed of
brass tubing or loop-shaped section of
brass, stainfess-steel or steel pipe with
7/4" mal-e NPT on each end.
b.
Snubber:
I/ 4" brass bushing with corrosion
resistant porous metal disc, through which
nraQQrr16
f iltered.
Select di-sc
f l-uid is
material for fluid
served or pressure
rati-ng.
2. Manufacturers:
r-
same
as for pressure
gauges.
Pressure and/ or Temperature Gauge Connector P1ugs:
l.
Provide gauge connector plugs rated for 500psi at
200"F. Construct of brass and finish in nickel
plate equipped with I/4" or L/2" NPS fitting,
with
sel-f-sealing valve
core type
neoprene
gasketed orifice suit.able inserting I/8" OD probe
assembly from dial- type j-nsertion pressure and/or
NYCSCA
COMBINATION I{ET STAI{DPIPE/SPRINKLER
SYSTEDI 15332 . 11
o7
/29lLO
LLVI NO.
l-amnarrf
rrra
drlrAA
l-arr-i n
lYury
.
063545
wit.h qasketed
Of if
iCe
i ndi
r-a1-us
9q
screw cap and chain.
Approved manufacturers
:
:
MiI ior-n CnrnnaSljgn
Mc Di nj na D'^CUCIS
r !v\
CO.
Peterscln Ecrrr i ppgnl Co.
j-sco, A Spedco, Inc.
Trerice (H.O) Co.
Watts Regulator Co.
S
2.06
SPRINKLER
A
Co.
HE,AD
Drnrri da cnr-i nkl_ef!
trznc
head Of
v!
LJ yE
rtvqs
rtrvf
and in accordance with their listinq.
ed
Provide ordinary temperature-rated
requirements for temperature rating
haarl<
ae nrnrTidg6l
in
B
.3 .2.2,
I .3.
nn
qnri
nf
T-'lr:r^z'i nac
nlrl orq
i f
qnri nlu I ar
2.3,8.3.2.4,
8.3.2.5 of NFPA-13-2002 are complied with.
Qulck response sprinkl-ers shal-l- be instal-l-ed
according to their listing and in Iight-hazard
occupancies as defined in NFPA-1,3-02.
Wet or dry sprinklers that utilize O-rings as
seafs are not to be used on projects. O-ring
snri nkl ors r-en uvyrqvv
ciecrradc vvv!
n\ror time.
LrrLLv.
heads can corrode r or minerals,
snri
TheSe
arrgou
oyr!rrJ\rv! nkl er
sa1ts, and other
contaminants in water can affect the polymeric
rubber O-ring seal-s. These factors coul-d cause
the sprinkler heads to not activate in a fire.
Heads that use Tefl-on coated Bel]evilfe metal-lic
seal-s rather than a rubber O-rinq are to be used.
Upright
Pendent
Recess Pendent
Concealed Includinq Cover Plate
5r_oe walr
Finishes for Upright, Pendent and Recess
Pendent: chrome plate for occupied areas,
cast or plain brass for unoccupi-ed areas.
NYCSCA
CoIIBINATTON WET STA]IDPrPE/SPRTNKLER
SYSTEM 15332
L2
o7
/2e/!o
LLW
NO.: 063545
Sprinkler Cabinet and Wrench: Provide steel,
baked red enameled, snri nk'l cr box with
capacity to store snri nkl cr heads and
h
wrench.
c.
Approved Manufacturers:
Firematic Sprinkler Devices, Inc
Grinnell Corp.
Viking Corp.
Reliable Automatic Sprinkler Co.
Vict.aulic Co. of America.
2.07
SIAMESE CONNECTIONS
Fl-ush type shall- be of the size indicated on drawings.
Siamese connect.ions shalI be polished brass with two
individual drop clapper valves and cast iron plugs
na.i nrari
rzal
T 619 with
qllu
no'l
wrLrf
bfaSS vlIqIIl
v!eQQ
vvJLIIth
Chain
and wi
Jvrrvvv
IJvIfDI i .qhed
lettered *COMBINATION STANDPIPE/ SPRINKLER". The
plate
lett.er inscription shatl be either an integral part of
the plate or on a separate nameplate securely fastened
to or above the siamese connection. Flush type shall
be Potter Roemer Fig. 5020G Series r ot Croker Corp.
Fig. 6030 Series. Threads shall be to NYC Fire
Ilon: r1-mant oneCif iCatiOnS
.
Exposed type shall be of the size indicated on the
drawings. Siamese connections shall- be polished brass
with two individual drop clapper valves, pin lug
swivels, plugs and chains and with polished brass wallplate lettered * COMBINATfON STANDPIPE / SpnfnKLER".
The Ietter inscription shall- be either an integral
part of the plate or on a separate nameplate securely
fastened to or above the siamese connection. Expose
type shal-l be Potter- Roemer, Fi9. 5750 Series or
Croker Corp. Fig 6430 Series. Threads shal-l be to NYC
Fi re
C.
l)enarf
ena- i f i n.f ionS.
monl-u uyuvr!rvqu
Sidewal-k type shall be of the size indicated on
drawi-ngs. It shall be polished brass, complete with
78" sleeve, cast brass plugs and chains, and fl-oor
plate lettered *COBINATION SPRTNKLER / STANDPIPE". The
letter inscrlption shal-l- be ei-ther an integral part of
the plate or on a separate nameplate securely fastened
to or above the siamese connection Sidewalk type shall
be Potter Roemer 5760 Series or Croker Corp. Fio. 6510
NYCSCA
COMBTNATION
I{ET STAI{DPIPE/SPRINKLER SYSTEM
15332
13
07
/29/LO
LLW
Series. Sidewalk
made of red brass.
L.
siamese
NO.: 063545
connection risers shall-
'1.^
Where a fence encloses a portion of the buildinq
containing
a
Fire
T-)orr:
uu}/sr
ri-monl.
r.nnnonlrrvv
i nn
ulvrr
t
Contractor
shal-l provide and secure to the fence
.l
rl'i raaf
rz nnnng
v_v_vv jlg
SiameSe COnneCtiOn
the
a Steel
sign containing the following wording: "F. D.
Siamese Connection located...Feet behind Sigin. "
Sign shal-l- be f inished in porcelaJ-n enamef with
one inch red letters on white backqround.
Approved Manuf acturers
:
Elkhart Brass Mfg. Co., Inc
Croker
Potter
2.08
Roemer
I,ADDERS
A. Provide permanent heavy stee.l- ladders to provide
access to valves in accordance with the code
requirements. Ladders shall be of width and height
required, shall- be made of heavy steel- bars and heavy
'l
rirn^c
rnrl
sh: I r
ho
normanenf
vu
urJI rz fasLened
yu!rrrqrrvrr
at
IOCatiOn.
Where the shut-off valve adjacent to the spri-nkler
alarm valve is located higher than 6 | above the floor,
ladder shal-1 be provided where directed.
2.09
AUTOIfATIC BAI,L DRIP
A
2.LO
Automatic Ball Drip shal-1 be 3 / 4" Potter-Roemer Fig.
5982 or Croker Corp. Fig . 6181, .
ROOF !{A}IIFOID
A
Roof manifold shall- be cast brass, three-way
horizontal- type of size indicated on the Drawings,
Potter-Roemer Fig No. 5881 or Croker Corp. Fig. 6850.
Roof manifold shall- be fitted with three cast brass
val-ves equaf to Potter-Roemer Fiq. No. 4065 or Croker
.
.-Y
Cap with chain shal-1 be PotterRoemer 4625 or Croker Corp. Fig. 5713. Threads shallbe to Fire Department Specifications.
t nrh
mrcscA
H l d
ht t t h
CoMBTNATION If,ET STAr{DPIPE/SPRINKLER
SYSTEM 15332
L4
o7
/29/LO
LLTil NO.
2.LL FIRE
:
063545
DEPARTI4ENT HOSE VAL\ZE AND CABINET
A. Cabinet shal-I be recessed type , 20 gauge steel- body
and white enamel inside. Exposed trim and door shal-l
be 1B gauge, type 304 stainless steel with a No. 4
finish. Cabinet doors shall- have duo-panel wire
inserted cl-ear glass. Door sha11 be hinged right or
left as required. Cabinet shall- be Potter Roemer SS1810-AW or Croker corp. Fiq. SS-2700-AW.
Fire Department Lobby Hose Cabinet: Cabinet shallbe recessed type, 20 gauge steel body and baked
white polyester finish j-nside. Exposed trim and
door sha1l be 18-gauge, with continuous steelhinge (brass pin). Cabinet door shall have duopanel wj-re inserted cl-ear glass. Door shal-l- be
hinged right or left as required with l-ock and
key in a key cabinet. Cabinet shall be Potter
Roemer 1302or Croker Corp. Fig. 21-90 or approved
equal.
2.
Lobby Key Storage Cabinet: cabinet shall be 18gauge white coated steel with FDNY l-ocks. Hol-ds
key for the lobby hose cabinet. Cabi-net
inst.al-lation requires 5"x5 "x3't wall opening.
Cabinet shall be Pot.ter Roemer model- # 1950 NYFD
Yale lock # SYA1 , or Croker Fig. 2928 .
3.
Fire Hose Cabinet: Series 1100, 18-gauge steelbox, wall- mounting and size i e radrli rarl
.
Angle Hose Val-ve Cabinet: Serj-es 1800, 18-gauge
steel box, wal1 mounti-ng and si zo eq ror.niired.
4
B. Hose val-ve shal-1 have nominal 214" inch threads
conforming to FDNY standards. It shall be an angle
val-ve, cast braSs body, complete with wheel- handle,
with red enamel-ed finish caps and chain. Valves shall
be Potter Roemer Fig. 4065 or Croker Corp. Fig. 5015.
Cap with chain shall- be Potter Roemer 4625 or Croker
Corp. Fig. 5713. Threads shall- be to NYC Fire
department specifications. Provide escutcheon plate
Potter Roemer No. 2151 or Croker Corp. Fig. 5735 for
val-ve.
lnrcscA
COMBINATION I{ET STA}IDPIPE/SPRINKLER
SYSTEI'I 15332
15
o7
LLII NO.: 063545
/2elLO
1.
Fire hose shall be Polyflex fire hose (375 feet
provided in the lobby), model # 2915 by Potter
Roemer.
C. The equipment specified for the Fire Department Hose
Val-ve and Cabinet shall be of one manufacturer for
each compl_ete unit.
D. Provi-de signs as required by Fire Department. Potter
f nrn
tsfd
/9\I
Roemer Fig. 5300 Series or I rizar
rfY.
LJJt.
vv!I/.
2.L2
PATNTING
A.
Paints used on dedicated piping
sprinkler and standpipe shall_ not:
to
combination
Exceed the VOC content l-imits established in the
Green Seal Standard GS-11 pa'inf e - f i r<l edition,
20,
May
1993.
Exceed the VOC content limit
of 250 g/L
established in the Green Seal Standard GC-03,
Anti-Corrosive paints, second edition, January '7,
L991
R
PART
3.01
3-
.
Provide col-ors indicated in Paraqraph 3.03.C
1.
First (1"t) coat
Alkyd vinyl Acrylic
Primer L.2 Mil_l_s DFT.
2.
Second (2"d) coat
- Enamel- 1.3 Mills
Latex
Semi-Gloss Vinyl Acrylic Latex
DFT.
EXECUTION
INSTALLATION
A. Approval of coMBINATION STANDPIpE/ SPRINKLER System:
All necessary permits for work in connection with the
installat j-on of the sprinkler/standpipe system shal_1
be obtaj-ned by t.he Contractor before commencing any of
the combination sprinkler/ fire standpipe work. The
Authority wifl- prepare and submit plans for the
combination standpipe/ sprinkler system to the
Building Code Compliance Division and obtain approval
for same.
NYCSCA
COMBINATION IVET STA}IDPIPE/SPNTUXT,ER
SYSTEM 15332
16
o7
/29/to
R,
LLW
NO.: 063545
Instal-l-ation of Identification
1.
Instafl- signs on sprinkler/f:-re standpipe systems
in accordance with NYC Fire Code, NFPA 13 and
NFPA
2.
14 requl-rements.
Each val-ve in
the sprinkle r / f :-re standpipe
l-ra 1-:naarl in aCCOrdanCe With the
requJ-rements of The New York City Fire Code.
svsf ems sha I I
('
Pipi-ng Install-ation
Tnsta'l I
ni ncs
and
2 .02 .
ni
na f i tt i ncrs
I.t}."!rUU4rlY
'i
n
aCCOfdanCe
wi-th Article
At the top of the highest
riser there shal-1 be provided, above the main
roof 1eve1, a three way manifol-d equipped with
three ) ttrr inch hose valves with hose val-ve caps.
The lowest vafve shall be located with the hose
end at least 18 inch above the roof and the
highest valve with the hose end not more than 60
i-nch above the roof . The manif old may be set in a
horizontal or vertical position, provided the
hose outlets are set back between 18 inch and 60
inch above the roof level-. Where the manifol-d is
l-ocated other than within a heated stair
enclosure, the control valve shal-l- be located in
a horizontal- run of piping below the roof, with a
long stem extending through the roof and equipped
with a wheel handle at its upper end at least t2
inch above the roof. Between the control valve
and the manifold there shall be provided within
the heated space a L,t" inch open drip or a 3,'4" inch
automatic bal-l drip, with the drip pipe extended
to spill over a plumbing fixture or a drain.
2.
Comply with requirements of NFPA 13-02 and
NFPA
14-03 for
instal-lation
of
sprinkler/ f:-re
standpipe piping material-s. Instal-l- piping
products where indicated, in accordance with
manufacturer's written instructions and in
accordance with recognized industrv practices to
qrzqf amq
nnmrr'l rz
uri l-h
ensure that
piping
requirements and serve int.ended purposes.
rJrLvlLLU
vvlrryrJ
vvf
Lrr
Coordinate with other work includi-ng plumbing
pipingr dS necessary to interface components of
cnri rrrr\rs!
nlz'l
rt/!
NYCSCA
ar
ni
ni
yr}JrtrY
IJ!vlJgr
-rry " 'Vith
!
COMBINATION WET STAI{DPIPE/SPRINKLER
Othef
WOf k.
SYSTEM 15332
L7
07
tLW NO.: 063545
/29/L0
4
f
nsta1l drain piping at l-ow point.s of piping
qrzq1-
om<
Drnrr j 6jp flra i n ni
n'i ncr a]y+y+rrY
|-
ho
val-ve that wilf be carried down to
^f afm CheCk
the f loor to
discharge into the nearest floor drain, unless
otherwise shown on the Drawings. Low points of
snri nk'l cr/firo
!f !s
oy!rrrArs!/
*': *'i*st:nrin'i no P-LP-L-tI\j
+1^^+
LIlcl.L
Cannot be
oLqrrulrrl/s
drained through the alarm val-ve drain shall also
be provided with drains as may be shown on the
T-trr','.i
n*a
uLcrwfrluar
\Jr
.i
o.D Ic\4u_LIc(r.
-^^
Install
valve
indicated, or
i nrli r.af od -
lllvlgqgvg,UugrlgyfF
hose connections of sizes
not otherwise
3/ 4" size
if
rrn qnr"i nkl er /
f ) rc
s1-
:ndni ng
at
endS
of branch l-ines and cross mains at l-ocations
where indicated on the Drawinss.
Install Inspector's test connection at t.he f l-oor
control val-ve assemblv on each f loor.
D.
Instal-lation
of Valves
Install
valves and water
indicated on the Drawinqs.
flow detectors
where
Val-ves shal-l- be f itted with tamper swi-tches for
srrnerrzision
ouIJs!
vrDrvrl
..r
v!
fr-^
Lrrs
v}Jgrt
position
I
of
the
val-ve.
The tamper switch is operated by a cam connected
to the valve stem. The Contractor should make
certain that the valve disc when fully open does
not interfere with the operation of other system
components immediately adjacent to the valve.
E
F
G
Installation of Fire protection Pressure
Instal-l qauges in accordance with Article 2.05.
Gauges:
Install-ation of El-ectrical Devices: Provide wirj-ng
requirements for control- panel, be1ls, valves, Lamper
swj-tch, alarm val-ves, and water flow detectors.
Installation of Sprinkler Head
t.
Instal-l- sprinkler head at the proper posit ion
shown on the Drawingis r ot as required. Instal-lconceal-ed type sprinkler heads with factory
painted white cover plate in areas with suspended
r-o.il.incrs
usf f flrYD.
lncr-1
f fr,)Lo.rr r
^^^r
reL.e-5eLr
+---^
LYvg
^*-.fkl_ef
DIJrfrl
with manufacturer supply escutcheon.
NYCSCA
CoIIBINATTON r{ET STA}IDPrPE/SPRINKTER
SYSTEM 15332
head
18
o7
LLII NO. : 063545
/29/L0
2.
InStal_l
qnri nlrl ar
ni ni nn
ho:dq
trvqvu,
and
al_l_ Other
items and accessories to cl-ear electric l-iqhtinq
fixtures.
Body f or f l-ush type S j-amese connection shal1 be
roughed in during construction. Escutcheon and nipple
assemblies shall be installed after constructi-on.
One Siamese connection shall be provided for each 300
feet of exterior buildinq wal-1 or f racti-on thereof
facing upon each street or public space.
OR
For buildings facing two paralleI streets or publrc
spaces without an intersecting street or public space,
one Siamese connection shall be provided for each 300
feet of exterior buildinq wall- or fraction thereof
f ront
'i
ncr rrn^n
eaCh
ra I I e I
SUCh na
I/q!qr!v4
JUVrr
qf
raaf u
J u!v9
n
v! r
nrrl^'l
lg
yuvr.
a?14 /ra
OR
For buildings fronting two intersecting st.reets or
public space and the total length of exterior building
walls facing each street or public spaces is not over
300 feet, only one Siamese connection shall- be
instal-l-ed provided the Siamese connection is l-ocated
within l-5 feet of the corner and on the street with
the longest building frontage.
Unless otherwise indicated on Drawings, Siamese
connections shall be placed not less than 18" not more
than 36" above t.he f evel- of the adi oininq qround or
si-dewalk.
Each Siamese connection shal1 be instal-led with a
check val-ve located inside the buifdinq in a
horizontal section of the pipe l-ines where shown on
the Drawinqs.
Install bal-1 drip valve to bottom of check valve or
low point of piping between check valve and Siamese
connection as to properly drain system to prevent
!!gg-frru.
Freestanding sidewalk type Siamese connections shallbe provided at l-ocations shown on the Drawings. The
riser pipe to a free standing siamese connection shal-l-
MrcscA
COMBINATION I{ET STAIIDPIPE/SPRINKLER
SYSTEM 15332
19
o7
/29lLO
LLVI NO.
:
063545
be red brass. When instal-led behind a fence, provide
radrli
rorl
i nn
-I--'.rrtg
-* nnan
i n
rJt
orr
i
reirce €nr
ror n:easy
access.
fLr.Le
ha
€an^^
Hose Va]ves shall- be l-ocated not less than 5 ' -0 " nor
more than 6'-0" above the fl-oor or stair landinq.
J.
Exposed and concealed piping shall- be primed with one
(1) coat of zinc chromate and one (1) coat of red
Anam6'1
n=jnf
F'
cl-rnrlnina
:nrl
dr6\^n
par_nt far
pal_nt ror
erlaflrer n:'inf
Y- ien
sprinkler piping.
K
For additional materials and method, refer to Section
09900 - Paintinq.
L. After the finished coat of paint has been applied to
the piping, this contractor shall- do aIl- pipeline
identification labeling as per NFPA 13-02, NFPA 14-03
and the NYC Fire Code.
3.02 FIELD PAINTING
n
Paints and coatings used in the interior
of building
fLvo mark
ni
n'i ncr ru!
for fuElrLf!t(/oLtulr
i donf i €r ^^+ 'i ^^ .yurI.
^"*'1oSeS shal_1 not
rrlq!^
}JryrrlY
exceed the VOC content. limits established in Section
c01600.
B
Paint exposed sprinkler/f:-re standpipe piping with a
priming coat and two finish coats as specified in
Section 09900 : Painting. Protect sprinkler heads
drrrincr
nainl- i-uu!!rry
yof,rrLJrl9
snni nk'l cr / f i -o
'.'i+1'^-^r l n:nAr
l-rarrsPaintincr
!Qf,rru!rry
wrLrr
uaYDr
Dlrro.ra
IJClPEr
c1-usrrvl/ryu
:ndni na ni n'i nrl-I h:ncrcrs
end
ttsltYeL
e fu
other items and accessories shall conform to t.he
rg\lLf
('
.i
rl-gItlgll
-^*^-r
Of
a]_]_
code
^ .
LD
Painting of Dedicated Piping:
Dedicated piping to combinatj-on standpipe &
sprinkler system such as risers, cross-over mains
and cross-over connections shall be painted red
and the handl-es of val-ves f itted into the
dedicated piping shal-I be painted yellow prior to
the hydrostatic pressure test of the system.
Painting shall be applied whether the pipe is
ulti-mately conceal-ed or remained exposed.
N:rcscA
COMBINATION WET STAI{DPIPE/SPRINKLER
SYSTEM 15332 20
o7
/2elto
LLTI NO.
:
053545
Cross-over mains, cross-over connections and
risers of combinat j-on standpi-pe & sprinkl-er
systems that are exposed duri-ng al-terations shal_l_
be painted red and the handl-es of val-ves serving
the dedicated piping shal-l- be painted ye1low. If
under filing done for the al-teration work a
hydrostatic pressure test is requj-red, painting
of pipe shall be done bef ore t.he test.
3.03 FIELD QUATITY
CONTROL/INTERDISCIPLINARY
TESTS
A}ID
FTUNCTIONAI PERFOR!,IAIICE TESTS
A.
Fire Protection Piping Flushing: Prior to connecting
Combination Fire Standpipe/Sprinkler risers
for
flushing, flush water feed mains, l-ead-in connections
and control portions of Fire Protection piping. After
fire protection piping installation has been completed
and before piping is placed in service, flush entlre
fire protection system, as required to remove foreign
substances, under pressure as specified in NFPA l-3 and
NFPA 1-4. Continue flushing until water is cl-ear, and
check to ensure that debris has not clogged sprinkler
heads or f ire hose val-ves.
B
ACJ
L
Hrzrlrr-rq.|-a.lrrJvrvDLquIU
ir,
Taqlinn.
I9JLf,lIY.
Affor
n!LE!
qlTafnm
JlDLelttT
f'lrr<hina
!JUOTIIITY
r-aa.lLYDL
fire
protection piping hydrostatically,
for
period of 2 hour, dt not fess than 200 psi or
50 psi in excess of the system working pressure,
whichever is greater. Check system for leakage of
ioi nts - The
1-
csf
nrFsqrrra
Shal-l- be read frOm
a
gage i-ocated at the fow point of each syst.em or
zone being tested.
2.
Ron:ir
r\syqr!
a)r
v!
eliminate
'l
ano
76n1 ouE
!syf
eakaqe.
nini-^
IJtIJlrrg
qrzql-am
DJ
D usttr
2e
qD
radrii
rarl
l-uva
Test the entire f ire protection instal-l-ation,
including fire al-arm system, in accordance with
the requiremenLs of the NYC Fire Code and give at
l-east 2 days advance notice in writing of tests
and inspections t.o the Construction Inspection
Divlsi-on and the Authoricv.
Tests shal-l be
conducted in the presence of the Commissioner or
Commissioner's authorized representative and the
lnrcscA
CoMBTNATTON
!{ET STAI{DPrPE/SPRTNKLER SYSTEM 15332
-
2L
o7
/29/L0
LLW
Arrfhori i-rzI s RenresentatirzesLqs+veut
F
i rc
NO.: 053545
l)cnertment
and
any other public authority having jurisdiction.
In lieu of t.he presence of the Commissioner or
Commissioner's authorized representativer the
Commissioner may accept a signed statement of an
Architect or Engineer, whose name is submitted
with the advanced notification specified above,
declaring that Architect or Engineer has
witnessed the tests and that the combi-nation
meol- e
snri nkl or
srzq1- om
standpipe /
the
requirements of the NYC Fire Code and the NYC
Building Code. If a representative of the
Commissioner or the Commissioner does not appear
within 2 days after receipt of such signed
statement by the Commissioner, the report shal-lbe deemed to be accepted by the Commissioner.
Al1 tests shal-l- be perf ormed as part of this
contract.
L
(-
9T
Interdisciplinary Pre-Start-Up and Start-Up
Tests / Inspections
:
The Contractor shall conduct interdisciplinary prestart up and start up tests/inspections (ex. verifying
correct seismic restraint installations,
verifying
correcL install-ation of sprinkler flow detectors and
alarm gong) as per the manufacturer's start up
procedures. Contractor shal-1 submit signed start up
affidavit signed by the fact.ory authorized service
representative/Contractor's seismic P.E. certification
indj-cating that all- of the manufacturer's pre-st.art up
and start up procedures have been successfully
completed.
D.
Functionaf Performance Tests:
Contractor shal-1 also
submit signed functional
signed by the factory
authorized service representative indicating that aII
of the manufacturer's functional performance tests
(flushing, hydrostatic t.ests and testing of the fire
al-arm system activation) have been successfully
performance testing affidavit
completed.
NYCSCA
CoMBTNATTON
r[ET STAr{DPIPE/SPRTNKLER SYSTEM 15332
-
22
07
/2e/L0
3.04
LLW
NO.: 063545
SPECIAL INSPECTION
A. Installation of sprinkler systems is subject to the
special inspection requirements of chapter I1 of the
NYC Building Code. The Authority will engage a
Qnan'ial
.|-o
Tnsner.J-or
norform
+rrut/uvuv!
Lv
y9!!vlttr
1-hc
rA.^r1.lirefl
LrrE
!gyur!gu
.i
nsncr-f iOnS.
Irto}JEUL-
B. Cooperate with t.he Aut.hority and provide al_l_ required
access to facilitate
all testinq and inspection
rel-ated to the Special Inspection.
EIID OF SECTION
NYCSCA
CoMBINATTON r{ET STANDPTPE/SPRTNKTER
SYSTEM 15332 - 23
07
/2elLO
LLW
NO.: 053545
LIST OF ST'BMTTTAIS
DATE
ST'BD{ITTAI
St'B}4ITTED DATE APPROVED
Product Data:
1. Manufacturer's Product Data
2. Instal-l-ation Instructions
3. Certificat.e: Hose Threads
NYC
DOB
1. Permlts:
zt
n^h-^*'^rl
urawl_ngs
T1.
^PPLOVeU
Shop Drawings:
1. Sprinkler Layout
2.
J.
Hrzclrarrl
4
ts I rT
ir- CalCulationS
WJ_rr_ng IJr_agrams
I nde
5. Check val-ves
6. Control valves
7. Siamese connections
B. Roof Manifold
9. Hose Valve and Cap
10. Hose Valve Cabinet
11. Pipe
Toqf
Ronnrl.<.
Certi-f icates:
1. Certification of
Installation:
Maintenance Data:
- Snare Pari-S LiSts
2. Instruction Manual
3. Maintenance Manual
1
Maintenance Material:
1. Head
2. Steel- Cabinet
3. Wrench
MTCSCA
COMBINATION I{ET STA}IDPIPE/SPRINKLER
SYSTEM 15332 24
o7
/29/t0
LLII
NO.
:
053545
4. Caps and Chains
Contractor's Start-Up
And Demonstration Affidavit
NYCSCA
COMBINATION ITET STAI{DPIPE/SPRTNKLER
SYSTEM 15332 - 25
07
LLII
/29/LO
TTIIS PAGE
NYCSCA
IS
NO.
:
053545
INTENTIONAILY LEFT BLANK
COMBINATION TIET STAIIDPIPE/SPRINKLER
SYSTEM 15332 26
07
tLW NO.: 063545
/2e/L0
sEcrroN 15333
FIRE PI'MPS
PART
1-
1.01
GENER.AI
DESCRIPTION
Or WORK
A. Provide the electrical motor-drj-ven fire pump systems
as indicated on the Drawings, ds specified herein, and
as needed for a complete and proper installation.
Product specific requirements are contained herein;
Section 15301, General Provisions for Fire protection
Systems Work, shall be referred to for general
requarements.
L.O2
RELATED SECTIONS
A. Division 3 Sections.
Division 15 Sectrons.
C
Division l6 Sections.
R,
1.03
SYSTEM DESCRIPTION
A
1.04
E-'i
ra
Drrmn vl(rrcf
om. rl1ha
i res
u LUirr.
f rre
!f !!
nt.lmn
srzstem COnSiStS
pJ,
yurrry
Of a
horizontal or vertical split case fire pump or endsuction fire pump, fire pump motor, automatlc transfer
switch, fire pump controller, jockey pump, jockey pump
motor, jockey pump controller, associated valves,
gauges, and test apparatus to supply water to the
combined standpi-pe & sprinkler system.
1. The jockey pump maintains a minimum pressure in
the combined standpipe & sprinkler system.
2. The fire pump starts in the event of a drop in
pressure below the minimum pressure mai-ntained bv
the jockey pump
SttBtl[ITTALS
A.
Product Data: Submit the installation and start-up
instructi-ons for each type of product indicated.
Incl-ude pump characteristic and performance curve for
eacn pump.
a
Shop Drawings: Submit the shop drawings for the pumps
and drivers, pump controll-ers and automatic transfer
switches, pump accessori-es and specialties, jockey
pumps, jockey pump controll-ers,
jockey pump
accessories and specialties.
Incl-ude plans,
ol
v!E
orralinnq
v q uf,vrrQ
t
ot.her work.
tiwcscA
<anf Lf
r9v
i nnq
vlro
FIRE
t
rla{-=i'l
ug
LcIIID,
PUMPS
a
rnA
o.lILr
at.tachments to
15333
1
07
/29lLO
LLW
NO.: 063545
A11 Shop DrawJ-ngs shall also be submitted to El-ectrical
.tr^! u!
(.
-^^-^---\J v ct I1 .
cr_v_yr
Wiring Diagrams: Submit. the wiring diagrams for the
electrical power and control- wiring. Differentiate
between manufacturer-i-nstalled and field-installed
r"ri ri nn
D.
E
.
IQrrl-rm]
UVrrLr +.
L VrrE
^^^"
UV}Jy
rJ
L\
E]_eCtfiCa]_.
Maintenance Data: Submit maintenance data and parts
l-ist for each pump; pump controller and automatic
Lransfer switch and accessories, including "troubl-e
shooting" and emergency guide in maintenance manuals
in accordance with the requirements of Division 1.
Incl-ude operati-on manual-s.
Test Reports
1.
F:n{-nrrz narr^rmance test: certified test curve for
each pump.
Field acce'otance test.
3. Comply with Modified NYC Fire Code Chapter
Section BC 901 (901.5) (Acceptance Test).
F. Digital
recordings produced during the
traininq.
G. Contractor's start-up and demonstration affidavit.
1.05
SUPPLEI{ENTAT QUAl,rTy ASSURiAI{CE
A. Codes and Standards: Materials and equipment for pump
systems should be of the type and size approved by the
New York City Fire Department.
B. UL, NEMA, NFPA and FM Compliance: Provide pump systems
that are UL listed and labeled and complv with NEMA
standards.
Conform
to
the
requarements
and
recommendations of NFPA 20
Standard for the
Instal-Iation of Stationary Pumps for Fire Protection
and NFPA 70
National Electrical Code. The pump
system shall be approved by Factory Mutual (FM).
C. Factorv Performance Test
1. Each unit shall be given a complete performance
test i-n accordance with NFPA 20 and the Modified
New York City Fire Code; Appendix O Section BC
QL02 and Chapter 9 Sectj-ons BC 903 & BC 905. A
certified
test curve shall be prepared and
submi-tted f or each pump.
NYCSCA
FIRE
PT'MPS
15333
-
2
07
/2e/L0
LL9[
2.
NO.: 063545
Controlfer: Each pump controller
shall be
completely tested before shipment from the
factory.
2 . PRODUCTS
2 . OL IIATERIATS . GENERAT
A. Each pump shal-l be of the type, size and capacity
listed in the pump schedules on the Drawings.
2.02 CENTRIFIUGAL PT'MPS
A. UL 448, factory-assembled and tested, electric-drive,
centrifugal pumps capable of furnishing not less than
150% of rated capacity at not less than 652 of totalrated head and with shutoff head l-imited to I40% of
total rated head.
1. Finish: Manufacturer's standard red paint applied
to factory-assembl-ed and tested unit before
PART
shipping.
2.
Nameplate:
with
Complete
capacities,
characteristics, and other pertinent data.
B. In-Line Fire/ Sprinkler Booster Pumps: Vertically
mounted type with el-ectric-motor driver directly
mounted to pump casinq.
1. Manufacturers:
Patterson Fire Pump Division - A subsidiary of the
Gorman-Rupp Company
Sterling Peerless Pump; Sterling Fl-uid
Systems
Group
Reddy-Buffaloes
Pump Co.
Aurora Pump; Pentair
Pump Group.
A-C Pump; ITT Industries
2.
NYCSCA
Vertical in-l-ine design with the following:
a. Casing: Radially spJ-it cast-iron, with the
suction and discharge flanges located on a
common centerline, 1B0o apart, for mounting
in the pipeline.
FIRE
PT'MPS
1s333
3
07
/29/LO
LL9il NO.
b.
c.
d.
:
063545
Impeller: Cast bronze of construction to
match pump, statically
and dynamically
balanced, and keyed to shaft.
Wear Rings: Replaceable, bronze.
Shaft and Sleeve: Steel- shaft with bronze
sleeve.
1)
Shaft Bearings: Grease-lubricated ball
bearings in cast-iron housinq.
2)
Seals: Stuf f ing box with a minj-mum of
four rings of graphite-impregnated
braided yarn packing, lantern ring and
bronze packing gland.
("
I-'ira
Drrmzl ..
q.innla
horiznnfaf
LLVL!LVL!WC
Of
Sterling Peerless Pump; Sterling Fl-uid
Systems
UJrrYf
g
^r
V!
mrrlt.i
rtlur
LI -Sfaclc_
J LqYE,
vertical split case, electrical motor drive, double or
single suction, bronze fitted centrifugal fire pump
mounted on a common base plate with the electricalpump driver complete with coupling and coupling guard.
End-suction fire pumps are also acceptable.
1. Manufacturers:
Patterson Fire Pump Division - A subsidiary of the
Gorman-Rupp Company
Group
PaAArz-FlffalOeS
uu!
!qrvvJ
Prrmn
urrly
Qg.
\
!
Aurora Pump; Pentair
Pump Group.
A-C Pump; fTT Industries
2.
MTCSCA
The construction features for the fire pump
component parts shall_ be as foll_ows:
a. Casing: Cast iron, horizontal- or vertical,
axial- or radial sclit case.
b. Shaft: A1loy steel-, machined and ground to
close tolerances.
c. Shaft Sleeve: Bronze.
d. Bearinqs: girease lubricated bal-1 bearings.
e. Impeller: Cast bronze, statically
and
dynamically balanced, keyed to the shaft.
f.
Casing Wear Rings: Bronze wear rings.
FIRE PT'MPS
15333 4
07
LtI[
/29lLO
Crrtrnl
v
Qa'l f -rl
i ani
nn
f I avi
l-r'1
a
anrrn]
:
053545
of
'i
--*y-rng
the manufacturer's recommendations.
Tl,r conl r.l- a.
Drrr
, -.np and dri-ver are mounted on a
fabricated steel 1-r^^^^l
JJcT.DCPJO.^+^Le .
Stuffinq Boxes: Extra deep for proper
h
i.
2. 03 ELECTRICAL
i nrr.
NO.
seal-ing.
MOTOR DRIVER
A. The electrical motor for the pump shal-l_ be Ul-listed,
NEMA MG-1, open drip-proof, squirrel cage induction
motor with grease f ubricated ball_ beari_ngs complying
with NFPA 20 and NFPA 10. The l-ocked motor current
shall not exceed the values specified in NFPA 20.
Include wiring compatible with controll_er used.
2 . 04
PtnIP
A
CONTROLLERS
Pump Controllers, General-: UL 278 and NFPA 20; UL
listed and FM approved for ftre/sprinkler booster pump
service, suitable for use with the electric motor to
be used,' combined automati-c and manual operation;
f actory assembl-ed and wj-red; and factory tested for
capacities and electrical characteristics required.
Mark control-1er "Fire Pump or Sprinkler Booster Pump
Controller".
1.
Manufacturers:
hrr6trn
| t
|n^
rrrv.
Master Control Systems, fnc.
Malrnn
rreL!vrr,
Tnn
rf
tv.
Hubbell Industrial Controls, Inc.
2.
Rate controll-ers for scheduled pump horsepower and
short-circuit
short-circuit
location.
withstand rating at least. equal to
current available at controll-er
Enclosure: UL 50, NEMA 2, drip proof, indoor
unless special-purpose encl-osure is reconrmended by
the manufacturer. Provide manufacturer's standard
red paint applied to factory-assembled and tested
unit before shipping.
The automatic transfer switch shall be capable of
automatic power transfer from normal to alternate
qenerator emergency power source in case of normal
NYCSCA
FIRE
PI'MPS
1s333
-
5
o7
LLII NO. : 053545
/29/LO
supply fallure and automatically re-transfer after
restoration of normal power conditions. Automatic
emergiency power transfer switch factory mounted
and interwired with the pump controller. AIIwiring between the pump control-ler and the
transfer switch shall be done at the factory and
the enti-re unit assembly f act.ory tested. The
automatic transfer switch sha1l be reviewed and
:rrrrrrrrzorl
l.rrr
*.y.Y-vvvvvJulfugJllrYfllvv!.
5.
6
l-
ho trl'l or.f ri cz I
Provide controfs, devices, afarms, functions, and
operations l-ist.ed in NFPA 20 as required f or
drivers and controller types used, and specific
items listed bel-ow.Tho yrlrmcr
controll-er shall_ contain but not be
v ui{}
limited to the followinq:
o
.
Isol-atinq switch.
Voftage surge protector.
.
Circuit breaker, of the appropriate size
ratinq.
.
Motor starter,
for
o
Power on pilot
pushbuttons.
light,
.
Contact, for remote indication of "Pump Run",
"Loss of Power" and "Phase Reversaf".
o
Q-30Opsi Pressure Switch, with adjustable
settlnqs.
.
Control-
o
Running period timer, set for pump runni-ng
time.
o
o
Remote start relay.
Emergency start handl-e.
.
System pressure recorder, elecLric ac dri-ven
wit.h spring backup.
engagemenr.
1
N:rcscA
Ilncri naar
.
relays
transformer.
automati-c and manual
start and stop
and
controf
Nameplate:
with
Complete
characteristics, approvals and listings,
perti-nent data.
FIRE
PT'MPS
and
manuaf
circuit
capacity,
and other
1s333
6
o7
/29lLO
R
LLIV NO.
063545
Ful-1-Service Fire-Pump Controller and Automatic
Transfer Switch: The automatic transfer swi-tch and the
pump controll-er shall each be mounted in separate
enclosure, mechanically attached to form one unit and
provide for protected interl-ock wiring.
Type Starting: Wye-de1ta, closed transition,
reduced voltage or Across the Line, full voltage.
2.
Mounting: Ff oor-stand type f or f ield el-ectricalconnections mounted on the pump base.
Automat.ic Transfer Switches: UL 2I8 and UL 1008
and rc.nri rom4nlg fOf and attaChed tO fi re-nrrmn
control-l-ers. Include UL 50 Type 2 enclosure
complying with the fire pump controfler above,
with automatic transfer switch with rating af
least equal to fire-pump driver-motor horsepower.
sLLqurrvs
A
C.
:
The
f i re
l)rrmr-\ nnnl- rnl I o1
With
Lv
the
!r!9
I/urtry
aUtOmatiC
transfer switch shafl- be Firetrol- Inc. Model- FTA1350-TS or Mode] FTA-1000-TS; Master Control
Systems, Inc. Model MCYT-18 or Model- MCAT-l-8;
Metron Inc. Model- Series M-435 or Model Series
MP300 with MTS Automatic Transfer Switch; Hubbell
Industrial Controfs, Inc. Model Integrated LXi2800 or Model LXi-2200 both wlth LX450 Automatic
Transfer Switch.
Limited-Service Transfer Switch Fire-Pump/Sprinkler
Booster Pump Controllers: This unit shall combine the
features of a Limited Service Cont.roller with a
dedicated transfer switch. The combination Limited
Servi-ce Control-ler/Transfer Switch shall- be in a
single compact encl-osure and shal-l be approved by the
City of New York for firelsprinkler
booster pump
service, factory assembled, wired and tested as a
single unit.
1.
Type Starting: Across the line.
2.
Thermal magnetic circuit breaker.
In addition to the above, the Limited-Service
Transfer Switch Pump Control-i-ers shal-1 include the
following:
Visual- indication of Phase Reversal-, Trans f er
Switch Normal-, Transfer Switch Emergency and
IsoJ-ating Switch
Open.
Audible indication of Transfer Switch i-n Emerqencv
and Emergency Isolating Swi-tch Open.
NYCSCA
FIRE
PT'MPS
1s333
7
07
LLII NO. : 063545
/2elLO
for Transfer Switch Emergency, and
Remote contacts
Tsn'l ef i nrr
Sr^ri
lgl
Open.
Mounting: Skid
connectl_ons.
mounted for
f
ietd
el-ectrical
The combination l-imited service pump control_l-er
with the automatic transfer switch shal-l- be
Firetrol- Inc . Model FTA-7 50-TS, Master Control_
Systems, Inc. Model MCLT-18, Metron Inc. Model_
Series M-30 with MTS Automatic Transfer Switch and
Hubbell Industrial- Controls, Inc. Model- Integrated
LX-2500 with LX 450 Automat.ic Transfer Switch.
2
.05
JOCKEY PI'MP
A.
Where indicated on the l)rawi nos ,- nr:ovide
a
l'.
nonl- ri frrn:'i
coupled electric moLor riri rzan
pump. The jockey pump shal I be manufactured bv:
!!uYqa
v!4vvrrt
Cl_ose
iJvvr\e_)'
nnlrorz
Grundfos Pumps Corp
Sterling Peerl-ess Pump; Sterling Fl_uid Systems Group
A-C Pump; ITT Industries
Paco Pumps, Inc.
Taco, Inc.
B
The constructi-on shall- be as fol_l_ows:
l'-:
Cast iron or stainless steel-.
q i nn.
Stainless steel machi-ned and qround
to close tolerances.
Bronze or stainl-ess steel i-mpe11er
keyed to shaft, and secured to
shaft by impeller nut.
Shaft:
Tmrral
-l
ar.
Mechanical seal-:
2.06
JOCKEY PT'MP CONTROLLER
A.
NYCSCe,
Tunssten carbide.
The
-i
or-kcrr
nrrml)
I,ur!!y r-r'rni- rnl I or
qha'l I
i nnnrnnr:l,rate a :a maana'lmagnetl-c'
starter,
manual
operation
"Hand-off-Automatic"
selector switeh, fusibl-e disconnect switch and
pressure regulator.
The control-l-er is pressure
activated and shall comply with UL50B. The control-ler
shal-1 be factory-assembled, wired, and tested. The
control-l-er shall be across-the-l-ine type and shall, be
manufactured by Metron Inc., Firetrol_ Inc., Master
FTRE
PT'MPS
1s333
-
8
oz
/29/Lo
tLTil NO.
:
063545
Control Systems, Inc. and Hubbel-l- Industrial Controls,
fnc.
B. Accessory features shal_I be provided as fol_lows:
r
-i
2 . 07
nA
i nrr
nori
ry
lrs!rvu
r^rr-korz Y.lrrmn
Rttnn
r\urlrrrf
l-Lfllrg!,
i mar
{-n
Lv
nrarran1I/rgvgrrL
'i na
nrrnl
uyuf
ltly
nf
uI
.
I20V control transformer with fused secondarv.
o
Q-300
o
Encl_osure, NEMA type 1.
o
pil_ot liqht.
PRESST'RE
l-ha
LIIE
psi pressure switch.
RELIEF VALVE
A. Provi-de an iron body pressure relief valve with brass
internal- parts. The pressure relief valve shal_l_ be
supplied by the pump manufacturer.
2.08
CONTROLLER SENSING PIPES
A. Provide nonferrous metal sensing piping, L/2" stze,
with I/2" globe valves for. testing mechanism of
controller
from system to pump controller as
indicated. Provide bronze check val-ve with 3 / 32"
orifice in clapper or ground face union with noncorrosive diaphragm having 3/32" orifice.
Fabri-cate
pipe and fittings in accordance with NFPA 20.
2.09
PI'MP ACCESSORIES A}ID SPECIAJ,TIES
A. Jockey Pump: Pressure refief valve.
B. Sprinkler Booster/Eire pump:
1.
Automatlc ai_r release valve.
2. Casinq rel-ief valve.
3. Compound suction gage, 3-I/2" diameter dial.
4. Discharge gage, 3-L/2" diameter dial.
5. Eccentric tapered suction reducer.
6. Concentri-c tapered discharged reducer.
7.
Ball drip val_ve.
z.LO
NYCScjA
HOSE VATVE HEApER/TEST CONNECTTON
FIRE
PT'MPS
15333
9
o7
/29/L0
LL9il
NO.: 063545
A. Three-way wall- mounted type with f langed inl_et and
N.P.T. outlets with nipples and rising stem pump test
valves with femal-e N.P.T. inlets and male hose thread
outlets with caps and chains; wall escutcheon with
all brass with
"PUMP TEST CONN. " cast into it;
polished f inish. Pipe shal-l_ be sized as required or
as shown on the Drawings. Hose thread shall_ comply
with the New York City Fire Department. requirements.
1. Fl-ush type connections may be used where space
wil-1 not accommodate a proiectinq unit.
2.LL
FLOW METER
A
Provide metering devices for testing of the pump. The
metering devices shal-l- be listed and FM approved. They
shall be capabl_e of water flow of not l-ess than Ij5
percent of t-atea pump capacity.
Tlra
mat-
ar chrll
tlLo!ufrouqlg
have +/
- 22 full
SCaf
e accuracv.
Venturi Fire Pump Test Meter: Venturi: carbon
steel machined casting painted red, Meter:
al-uminum body, 4" dial, 304SS case with rubber
ring, glass window; brass ball val_ves and
fittings, rubber hoses with brass fittings rated
at 750 psi working pressure The test meter shal_l_
l'ra rl'ra ad,iar of the Venturi- Fire Pump Test Meter
provided by Globaf Vision Inc.
uYuqr
PART
3-
3.01
v!
Lltg
vElluul
E:GCUTION
INSTAII,ATION
A. Install pump systems as shown on the Drawingsr or as
.qnor-i f i od
horai n
or as recommended bv the
manufacturer written instructions to be completel_v
operable and in accordance with NFPA 20.
rt9!gJtl,
P
C.
NYCSCe,
Prnrri
rle
l- ha
na
r'ini
pl-pl_r]g
trnq
vatve-,
, rz='l
rri crrr'l
c.i al..f
f a
g.L-ass,
test
^] -an
valve with header, automatic air -*Jnt
release valve,
pressure gauges, supports and accessories as indicated
on the Drawings and as specified i_n other sections for
the complete piping connections of the pump systems.
The pump system install-ation and power supply for the
pump systems shall- comply with applicable portions of
the NYC Fi-re Code.
FIRE
PI'MPS
1s333
10
07
/29lLO
LLVI NO.
:
053545
D. Install- a pressure relief valve in the pump and jockey
Ii ^^harcro
ra'l 'i a€
-'a-l
-'a
Tha
rl'i qnh:r^a
mi\7
l.ra
\.r_LDU..s-:,e.
Ie_L_LeI
Vd_LVe
...eJ
us
IJuluy
piped back into the suction side of each pump on the
pump side of the suction valve with a visual- siqht
glass in the rel-ief val-ve discharge.
E
nltmn rliqnharrra
be connected to the cross
connecti-on main f or "hal-lthe combined standpipe and
sprinkler system at or below the street entrance fl-oor
l-eve1 and shall- be of the size indicated on the
The fire
Drawings.
F. The f ire pumps suction l_ine shall be connected to the
fire services provided as shown on the Drawings.
3.02
FIELD ACCEPTA}ICE TEST
A
A field acceptance performance test shal1 be conducted
upon the pump system installation completion.
test shoul-d be conducted as recommended in NFPA 20 in
the presence of the Authority and al-l other authority
with jurisdiction.
A fiel-d performance standard curve
shall be produced and compared for verification with
l ltg
f he far:f orrz nglformance
R
The fiold
curve.
na':f6rmance
vvr
test f or the pump system shal-1
also comply with the requirements of The Modified New
York City Fire Code Appendix O Chapter 9 Sectj-on BC
901 (901.5).
(\
V.
perf orm
shallnecessary
Tests and Functional Performance
Tests accordinq to manufacturer' s procedures.
The adequacy and dependability of the water source are
of primary importance and shall be fu1ly determined,
j-n the future.
wi-th due al-lowance for its reliability
E'i ra ^r enri 1]<lg1 Booster pump instal-Iation shall be
arranged Co alfow the test- of the pump at its rated
conditions as well as the suction supply at the
maximum fl-ow available from the pump. The fire
y!vLevLrvrr oyst€tn must have outl-ets avail_able to test
the pump and suct j-on supply piping.
Testing the Sprinkler Booster Pumps with Fl_ow Meter &
Test Val-ve Header at Perimeter Wal_l (Option 1)
The test procedure is as follows:
1.
Make a visual- check of the unit. The val-ve on the
discharge side of the meter should be closed and
discharge from the flowmeter shall- be recirculated
to the sprinkler booster pump suction line. (Note
that this test is to be done after verj-fying the
adequacy of the street supply per Par. D above;
FIRE PT'MPS
15333 11
Contractor
rftL
IIIE ^
T*1-^-.J.i
^^-: ^1.i. rnary
rnrerqrscl_pt_
D.
vl-!
nral-aa{_
E.
NYCSCA
.i
^-
rrtrtrv!
^r.^r^-
uvvo
-.-^+
uE!
L^-.
o7
/2e/L0
LLTI NO.
rrori
frri
nrr
:rlaarrrnrr
nf
l- ]ra
cf raaf u
:
063545
crrnnl
u
sIrI/ 4 rz
marnq
discarding water from the piping system and
f l ow rate throrroh a i-hose manifol-d
instal-l-ed f or purposes of conducting the initial-
me^sl'rri no
nrrmn
2.
1-aq t- \
Sfarf
.S'l
tho nrrmp.
i crhf I rz rrncn the
throttle
A
meter
valve).
discharge val-ve (meter
Check the qeneral operation of t.he unit. Watch for
vibration, leaks (oiI or water), unusuaf noises,
--r
arlu
(.,Ps!qL!vrr.
^-.:craf i
^^^^-^'r
vErrEIo.f
nn
Arlirrsf
nuJ
UDL
nar:k'i
yqvArrry
no ol
yr ands.
Discharge of water. The steps are as follows:
Racrrlal-a
t\EYUTALg
b.
Ua-UIIO!Vg
a
fLEDL,'
aof
\ .
---rrrF
VAIve
(meter
\rrleLv!
thrOttfe
urr!
valve) to achieve various fl-ow readings.
Important test points are at 150 percent
rated capacity, rated capacity, and shutoff.
Intermediate points can be taken if desired
to help develop the performance curve. (If
available suction suppl-ies do not permit the
flowing of 150% of rated pump capacity, the
pump shal-l be operated at maximum a1]owable
discharge to determine its acceptance. This
reduced capacity shal-1 not constitute an
rrn:nnont:l-.-l
urrquuEvuclLJlE
6.
r':^^r-
fho
LIlg
Record the following data at each test point
Drrmn
1-\
rnm
Srrr:t i on rlrFssure.
fti sr.h: r.ro
nroSSU1.e
YvIJ!v.
d.
From
.
test meter, record
gpm.
Amnaroq
Volts
g
Cal-culation of test resul-ts is as fol-l-ows:
1)
2)
N:rcscA
Rated Speed. Determine that pump
operating at rated rpm.
Capacity: From test meter, the totali-s read directlv.
FIRE
PT'MPS
15333
r_s
gpm
L2
o7
LLII NO. : 063545
/29/LO
3)
Total Head. For horizontal- pumps total
head is the sum of the fol-l-owins:
a)
Pressure measured by the discharge
gauge at pump discharge flange.
b)
Velocity
head difference,
d'i sr-harrra-
Gauge
c)
pump
nrrmn Ucrrntinn.
UV LJVT
elevation corrections to
nanlarl
eErlus!rJlls
/"1
anrl
/n l"a
(yfuD
i na
nr
\Jr
pump
mi n"c\
rrL_LJIL,tD,f
.
Pressure measured by suction gauge
\
:f
aL
yurtlP
crrn{- i66
-LluL-Lurr
fl:nna
!1e]rvs.
i s nccraf i rro rnzhen nre.qsltrF
vu
t/!
rl1hirr^
f r1-L5 rr--l
vct_Lue
iS
abOve
2 ati
4\
El-ectrical fnput. Voltage and amperes
are read directly from the volt/ammeter.
This readi-ng is compared to the motor
naman'l :l-a
frrl I -l oa j am6e1.eS. The On]V
qeneral cal-culation i-s to determine t.he
maximum amperes al-l-owed due to the motor
service factor. In the case of 1.15
service factor, the maximum amperes are
approximately 1 . 15 t.imes motor amperes,
because changes j-n power f actor and
efficiency are not considered. If the
maximum amperes recorded on the test do
not exceed this figure, the motor and
pump wil-l- be judged sat.isfactory. It i_s
most important to measure voltage and
amperes accurately on each phase should
the maximum amperes logged on the test
exceed the calculated maximum amperes.
This measurement is important since a
poor power supply with low voltage will_
cause a high ampere reading. This
condition can be corrected onfv bv
'i n
i mnrnrzamanll-ra
v v urlrurr u rrr
urrv
yvwcl
SUpply.
Thef e
^ni.ris nothing that can be done to the motor
rvsv
LL+ J
{-
nr
ur
q\
l-ho
Lrle nrrmr
yurrrl).
Concl-usion. The f inal step in the test
cal-cul-ation is to plot the test points.
A fiel-d head-capacity curve is plotted,
and a f iel-d ampere-capacity curve is
plotted. A study of these curves will
show the performance of the pump as it
was tested as compared to the factorv
rl:t:
F'
Testing the Fire
2)
riwcscA
Pump Through
FIRE
PT'MPS
A Roof Manifold (Option
15333
13
wlr
o7
/29lLO
LLII
NO.
:
063545
The test procedure is as fol-l-ows:
a vj-suaI check of the unit. Verify that hose
and nozzles are securely tied down. See that the
hose val-ves are cl-osed. At least fifty feet of
approved two and one-half inch rubber lined hose
equipped with pfay pipe nozzLe shall be connected
to the header manifold located downstream of the
adjustabl-e meter throttle valve. One 50' long hose
assembly shal-l be connected in parallel for each
two hundred fifty gpm of rated pump capacity.
Make
5
t[Ycsc3,
Start the pump.
Partial-l-y open one or two hose valves.
Check the general operation of the unit. Watch for
vi-bration, l-eaks (oil or water) , unusual- noises,
and general operation. Adjust packing glands.
Discharge of water. The steps are as foll-ows.
Using the test vaf ve header, regiulate the
discharge by means of the hose valves,
adj ustable meter throttle
val-ve and a
selection of the nozzle tips. The pfay pipe
has a removable tip. The tip has a L-L/B-inch
nozzle, and when the tip is removed, the play
pipe has a l-3/4 inch nozzLe. Hose valves
should be shut off before removins or puttinq
on the I-L/ B inch tip.
b
Important test points are at 150 percent
rated capacity, rated capacity, and shutoff.
Intermediate points can be taken if desired
to help develop the performance curve. If
availabl-e suction suppl-ies do not permit the
flowing of 150% of rated pump capacity, the
pump shall be operated at maximum al-lowabl-e
discharge to determine its acceptance. This
reduced capacity shal-l not const j-tute an
unacceptabl€ test.
An acceptable pump
capacity shal-l- be demonstrated when at l-east
50 feet of 2-I/2" rubber lined hose is
utilized with a L-I/ B i-nch nozzLe, after the
meter throttl-e val-ve has been adjusted to
si-mulate the static pressure due to the
height of the riser. The fire pump or
sprinkl-er booster pump capacity wil-l only be
acceptable if the rise of pressure across the
pump matches that stated in the Schedul-e of
Equipment on the construct.ion documents while
FIRE
PT'MPS
15333
L4
o7
LLII NO. : 063545
/2elLO
simul-taneously delivering the capacity
stat.ed in the Schedule of Equipment.
as
Verification of the adequacy of the street
r^r.a+-ar qrrnrrl rz i c r^.rrli rod
\/ori frri nrr .arlc
**..jquacy
of the street supply means discarding water
from the piping system and measuring the flow
rate.
Record the following data at each test point:
c.
Prrmn rnm
h
Srrr:f i on nrFssure.
f)i enl'r arda
Yv
nraqqrrro
,v!
rl
Number and size of hose nozzles, Pitot
pressure for each nozzle, and total gpm.
g.
Amnara<
Vo1ts.
Cal-cuf
a.
h
ati-on of test resuf ts is as foll-ows.
Rated Speed. Determine that pump is operating
at rated rpm.
Capacity: For hose valve header setup using a
fire stream table, determine the gpm (L/min)
for each nozzLe at each Pitot reading. For
example, 16 psi Pitot pressure with L-3/4
inch nozzle indicates 364 gpm. Add the gpm
for each hose line to determine total- volume.
Total Head: For horizontal pumps total head
is the sum of the followinq:
r)
Pressure measured by the discharge qauge
at pump discharge flange.
rl'i f f aranna
pump's
2)
Velocity
head
discharqe, and pump suctj-on.
3)
Gauge elevation corrections tro pump
^o.iarl
![YCSCA
/nl
rrc
\i/+qu
nr
mi nrrc\
lrr+rree/
'
Pressure measured by suction gauge at
F'1 ^-^^
^^
^..^r.i
This value is
rro.rr\js.
JLr\-Lr(Jlr
[JullrP
negative when pressure is above zero.
Electrical Input: Voltage and amperes are
read directly from the vol-t/ammeter. This
FIRE PT'MPS
15333 15
4)
d.
i na
07
/29/L0
LLT{ NO.
:
053545
reading is compared to the motor nameplate
full--Ioad amperes. Determine the maximum
amperes al-Iowed due to the motor service
factor. In the case of 1.15 servi-ce factor,
the maximum amperes are approximately 1.15
times motor amperes , rf t.he changes in power
factor and efficiency are not considered. If
the maximum amperes recorded on the test do
not exceed this figure, the moLor and pump
wil-1 be j udged sat.isf actory. It is most
important to measure voltage and amperes
accurately on each phase should the maximum
amperes logged on the test exceed the
calculated maximum amperes. This measurement
is important since a poor power supply with
low voltage will- cause a high ampere reading.
This condition can be corrected only by
improvement in the power supply. There is
nothing that can be done to the motor or the
pump.
e.
G.
Conclusion: The final step in the test
cal-culation is to plot the test points. A
field head-capacity curve is plotted, and a
field ampere-capacity curve is plotted. A
study of these curves will
show the
performance of the pump as it was tested as
compared to the factory data.
Pump Phase Reversal Test: For el-ectric motors, a test
shall- be performed to ensure that there is not a phase
reversal- conditi-on in either the normal- power supply
configuration or from alternate power supply.
Controfler Acceptance Test: Pump controllers shall be
tested in accordance with the manufacturer's
recommended test procedure.
As a minimum, no l-ess
than six automat.ic and six manual operations shall be
performed during the acceptance test. A pump driver
shal-l be operated for a period of at least 5 mi-nutes
r''-j
nf l-ha
...'erations.
frrI'l
snccri uurfrrv -^ c'clL-tr
^-^h \./!
!u!r
DIJEsu
Llrs
v_t1(
qo.rrrange Of the COntfOllef
aritomaf i c crn6ra1- i nn uu\auvrr
qL
at
qf
erf
DLq!L
tha
Urls
nltmh
yurrry
€rnm
!rurrl
:-l'l
o.LL
nrnrri
lJtvvlugu
rlarl
q.l- rrf
i na
JLa!LatIV
The
ShaII
€a=f
rrraa
IECILU!ED.
This sequence shall incl-ude pressure switches and
remote starting signals. The selection, size, and
sett.ing of al-l- overcurrent. protective devices,
including pump control-l-er circuit breaker shall be
confirmed to be in accordance with NFPA 20
NYCSCA
FIRE
PT'MPS
1s333
16
o7
/29lLO
LLW
NO.: 063545
requirements. The pump shall be started once from each
power source and run for a mini-mum of 5 minutes.
Manual emergency operation shal-l- be accomplished by a
manual actuation of the emergency handl-e to the fulJ-y
latched position in a continuous motion. The handle
shal-I be latched for the duration of this test run.
Emorrronnrz
Pnr^zor
Qrrnn-l rr.
On instal-lations with an
emergency source of power and an automatj-c transfer
switch, loss of primary source shall be simulated and
Lransfer shal-1 occur while the pump is operating at
peak load. Transfer from normal to alternate source
and retransfer from alternate to normal source shallnot cause opening of overcurrent protection devices in
either 11ne.
At least hal-f of the manual and
automatic operations of the controller acceptance
tests shall be performed with the pump connected to
v4I'I'LJ.
f l-^
- l r^--^ra
Lrre dJLerrrd Le SOUf Ce
.
J. Test Duration: The pump shall be in operation for not
less than t hour total time durinq all of the
fnrccrni ncr lgglg.
K. The Contractor must communicate in writing to the
Architect or Engineer of Record and the Aut.hority the
testing method to be used.
3.03
INTERDISCIPLINARY TESTS A}ID ET'NCTIONAT PERFORI{ANCE TESTS
A
B
Tnl_ ard'i
qr-i nl i n:rrz
Pro-Q1and
qrru
vtu Lq!arf u -TJn
Sf erl- -Tln Toqj- q'
v
The Contractor shal-l- conduct interdisciplinary prestar.t up and start up tests as per the manufacturer's
start up procedures. Contractor shall submit signed
start up affidavit signed by t.he factory authorized
service representative indicating that all- of the
manufacturer's pre-start up and start up procedures
have been successfully completed.
Functional Performance Tests:
Contractor shal-l- also-i submit signed functionalnar€n-m=-^^
o<l--*r^),
i nrr rf f rlrrzi I
ei r.rnorl hrz |- ho far-.|n
perrormance fL--*- --ry
authorized service representative indicating that aIlof the manufacturer's functional performance tests have
been successful-l-y completed.
3.04
TRJAINING
A
The Custodian (or buil-ding manaqer) and DOE Maintenance
Representative shall be trained on the operation and
mai-ntenance of the syst.em. All
NYCSCA
training shall be
digitally recorded and shal-I be a minimum of I hours.
A11 digital recordingis shall be turned over to the
15333 L7
FTRI PI'MPS
o7
/29lLO
LLW
NO.: 063545
DOE Maintenance Representative within 48
hours of the completion of training.
Obtain receipt
that the videos were submi-tted and furnish receipt. to
the Authoritv.
Custodian and
3.05
COMMISSIONING OF FIRE PUMPS
A.
Master Fire Suppression Piping Contractor shal-l_ comply
with the Commissioning Requirements of Contract
Specification Section S01660 for fire pumps/sprinkler
oooster pumps.
R
A11 testing of sprinkler piping shal-f be completed
prior to commencement of the Commissioning process.
E![D OF SECTION
NYCSCJI
FIRE
PT'MPS
15333
18
o7
/2elLO
LLl$ NO.
LIST OF
:
063545
ST'BI{ITTATS
DATE SI,BII{ITTED DATE APPROVED
SUBMITTAL
Product Data:
1. Manufacturers Product Data
2. Instal-l-ation
Instruction
qf
?
: r'F- -rrn
s_v TnStf UCtiOnS
4 - Pttmn CharaCteriStic
5. Performance
Curves
Shop Drawi-ngs:
1
Aqqamhl
rz-T'*
ype
. Morrnti ncr netails
3. Connecti-on Details
2
tfl.i
-^-^,
vvJ_r-i rrrg
urdgrams
^^ n.i
:
1. Power Wiring
2. Control- Wiring
Maintenance Data:
1
- Snarc
PerfS
LiSt
2. Maintenance Manua]
3 . Operat ion Manual-s
Taqf
1
2
-
Rannrl-c.
Far:f
orrr PcrformanCe Test
- Field
J
'v.
Ar-r-opl3ngg TeSt
Digital recordings
v!
rro._LtlJIlv
Contractor' s Start-Up and
Demonstration Af f idavit
.***
NYCSCA
FIRE
PT'MPS
1s333
19
07
LLll
/2e/Lo
NO.
:
063545
THIS PAGE IS INTENTIONALLY LETT BI,A}IK
N:rcscA
FIRE
PUMPS
1s333
-
20
O7/29/LO
LLW
No.:
063545
sEcTroN 15401
GENER;AL
1.01
PROVISIONSEF-EMEffG A}ID
DRAINAGE WORK
SCOPE AND INTERPRETATION
A
These Specifications and accompanying Drawings provide
for the furni-shing, setting and connection of sanitary
f ixtures, the instal-lation of drai-nage, water supply,
and gas supply systems.
B
The specifications and Drawings require the Contractor
C
to provide al-l labor, materials, equipment and
appliances to perform of afl Work pert.aining or
incidental thereto, which is needed to complete the
Work shown on the Drawings and cal-Ied for in the
Specifications.
The eomnl ete srzstems :nd 1-he Work Shal_l_ be SO inStalled
as to gl-ve proper and continuous service under allconditions, anO shall be in accordance with the
requi-rements of all
public authoriti-es having
jurisdiction and to the complete satisfaction of the
Arrf hnri
rz
Antr
l,r]nrLol-rnr
Any
Work shown
on the Drawings and not
-uJ.
particularly
described in the specifications, or vice
versa or any Work which may be deemed necessary to
complete the Contract shal-l be provided by the
Contractor as part of its Contract.
For purposes of clearness and legibility,
plumbing
Drawinqs are essentially diagrammatic and size and
l-ocation of equipment are drawn to scale wherever
nneeil-rla
The Drawings indicate size, connection
nni
n{- o
:nA
nf
ni no
yvf rrLo.1]Ll
I\JLrLgD
-nir].oq
LrL
It is not intended,
Pr-yE.
however, t.hat al-l- of f sets, rises and drops are shown.
Provide piping as required to fit structure, avoid
obstruction, and retain clearances, headroom openings
.f-
T-\
U
I/vv9fv+9.
and passageways.
Fj-xtures shown and described on the Drawings shal-l be
connected with waste, vent and water supply piping in
accordance with the resuirements of New-York Citv
Drri'l Ai n^
r\^i^
l^^^.i
fLs
*,-.l.i ^^!.: ion
uurrvlaty
^*.: -^..: ^^c
^*
^ *i^
vvss,
usDpr
urr€ omission
indicat
of
of
such piping on the plans. Any question involving the
install-ation of such piping shall be referred to the
Authori-ty f or resolution.
Fi-xtures, piping and other plumbing items which are
shown and described on the Drawings and are not
specif ically l-abeled "Future" or "N. I . C. " shall- be
provided by the Contractor. Related Work necessary
for the proper install-ation shal-l be performed by the
Contractor.
..:
F.
NTCSCA
GENERAI PROVISIONS FOR P&D
WORI(
15401
-
1
Download